NOSHOK 800 User Manual

Page 1
USER MANUAL
Electronic Indicating Pressure
USER MANUAL
Switch/Transmitter
S E R I E S 8 0 0
Page 2
The accepted technical regulations and all national guidelines must always be observed and
Copyright
All rights to these operating instructions are reserved. These operating instructions, including
extracts thereof, must not be copied or translated into other languages without our written
permission.
Safety Instructions and Warnings
Please read these instructions before installing and starting up the pressure switch. Failure to
follow the instructions will make all guarantee, warranty and compensation claims null and
void.
connection, and the correct tools must always be used.
complied with.
• Damaged devices must not be started up. If damage occurs during operation, suitable
measures must be taken to prevent persons or property from being put at risk by the damaged
pressure switch.
• The switch must only be repaired by NOSHOK.
complied with.
1
Page 3
Exclusion of Liability
NOSHOK guarantees that the pressure switch is in perfect working condition when it is delivered.
The basis consists of the technical data in the data sheet and these operating instructions.
Liability cannot be accepted for the suitability of the pressure switch.
The pressure switch has one analog output and one switch output or two switch outputs.
The analog output is calibrated in the factory, and the switch output(s) is (are) adjusted using
the two buttons: set point, reset point(hysteresis / window), switching function
The password protection that can be activated is a special feature, and prevents unauthorized
Electrical and Mechanical Connection
system. All connections to external electrical equipment must be made in accordance with
to N potential).
persons from modifying the adjusting parameters.
The optional dual rotating capability makes it possible for the electrical output and the display to be aligned i
ndependently.
2
Page 4
M12x1 socket with 2m cable
• straight version, order no.: FS-2-4P
• angled version, order no.: FA-2-4P
Round Connector M 12 x 1 (4-pin)
Signal Connector Colors of
Optional Wires
Supply: + 1 brown
Supply: - 3 blue
Switch output S 1 4 black
Switch output S 2 or
2 white
analog output
( 4 and 6 meter cables also available)
+ Supply
4
S1
R
L
R
L
- Supply
+ Supply
1
- Supply
4
S1
1
Sig
3
2
Sig
3
2
+ Supply
4
S1
R
1
N
R
1
- Supply
+ Supply
- Supply
1
4
S1
1
S2
R
3
2
3
2
2
R
2
S2
3
Page 5
outputs are operational. Brie y pressing button S1 causes the switching point 1 setting to be
current pressure to be taken over as the switching point. The hysteresis remains unchanged. If
occur, the switch automatically exits programming mode and switches to normal mode.
4
Page 6
BD_BE_BF_BSP 776
Password
Password protection can be activated in the main programming mode. The pressure switch is
If you forget the password, assistance can be obtained from NOSHOK.
Status-LED Switching Output
1 2
5
Page 7
Only for the version with two switching points!
Only for the version with two switching points!
Q ui c k P r o gr a m m in g - U s er Me n u
Q ui c k P r o g ra m m in g - U s er M en u
Function of the buttons:
S1 to run through the menu points,
to change the value S2 to select menu point, to return to the menu point
= These steps are available on switches configured with the Enchanced Software Option Only.
*The parameters which are marked with a *
can only be changed if the user is authorized in the set-up menu (CO.En). Otherwise, there will be only the display of the selected values in this menu.
Enter the quick programming user menu by pressing the buttons S1 + S2 for less than 3s.
Select the unit. Valid for all further settings.
Select the first switching point*
Select the first reset point*
Select the second switching point*
Select the second reset point*
The minimum pressure value stored is deleted if the button S1 is pressed for longer than 3s. The display flashes and the actual pressure value is stored.*
The maximum pressure value stored is deleted if the button S1 is pressed for longer than 3s. The display flashes and the actual pressure value is stored.*
Save the previous changes
YES: Save NO: Not Save
Returns to the actual pressure indication afterwards.
Return to the beginning of the user menu by pressing the button S1.
6
Page 8
M ai n Pr o g ra m m i ng - S e t U p M e nu
M ai n Pr o g r am m i ng - S e t U p Me n u
Function of the buttons:
S1 to run through the menu points,
to change the value S2 to select menu point, to return to the menu point
Enter the user menu by pressing the buttons S1 + S2 for at least 3s.
Only required for activated password. [PA.En]
= These steps are available on switches configured with the Enchanced Software Option Only.
Activate password.
YES: Password is required NO: Password is not required
Change password. Only possible with activated password.
[PA.En]
Preset-authorization for the user
The user has the permission
YES: To delete the max-min-memory NO: Do not delete the max-min-memory
Choice of measuring unit.
Applies to all further settings.
Display of the measuring unit. The measuring unit is shown in the display.
YES: 1s after every 10s NO: Not shown
Select the first switching point.
Select delay time of the first switching output. Range: 0.00 ... 99.99s Resolution: 0.01s
Select contact function of the first switching point. ncLS: Normally closed contact
noPn: Normally open contact
7
Page 9
M ai n Pr o g ra m m i ng - Co n t in u e d
M ai n Pr o g ra m m in g - C o n ti n u ed
Select the switching type of the first switching output. nPn: n-switching
PnP: p-switching
Select the switching function of the first switching output. hYSt: Hysteresis
GAtE: Gate Function
Select the first reset point.
Select delay time of the first switching output. Range: 0.00 ... 99.99s
Resolution: 0.01s
Only for the version with two switching points!
Select the second switching point.
Only for the version with two switching points!
Select delay time of the second switching output. Range: 0.00 ... 99.99s Resolution: 0.01s
Only for the version with two switching points!
Select the contact function of the second switching output. ncLs: Normally closed contact noPn: Normally open contact
Only for the version with two switching points!
Select the switching type of the second switching output. nPn: n-switching PnP: p-switching
Only for the version with two switching points!
Select the switching function of the second switching output. hYSt: Hysteresis GAtE: Gate function
Only for the version with two switching points!
Select the second reset point.
Only for the version with two switching points!
Select the delay time of the second reset point. Range: 0.00 ... 99.99s Resolution: 0.01s
8
Page 10
M ai n Pr o g ra m m i ng - Co n t in u e d
M ai n Pr o g ra m m in g - C o n ti n u ed
Return to the beginning of the set up menu by pressing the button S1.
To exit the menus
1. After the selection, the menu will automatically be closed whether the modified value is stored or not.
2. It is possible to exit the menu anytime by pressing the buttons S1 and S2 simultaneously.
3. If no button is pressed for 30 seconds, the menu will be closed automatically.
Error message
1. Flashing display of the actual pressure: measured pressure outside of range.
2. Flashing of the display during the programming: An invalid value was entered. Examples: Switching point above/below the adjustment range, reset point above/below the adjustment range, reset point above the switching point, analog output span is samller than 20% of the adjustment range filter more than 2s. When this happens, the buttons are locked for 3s and the switch takes over the next possible value.
Only for the version with analog output!
Select the pressure value of the analog output at 4mA/0V.
Only for the version with analog output!
Select the pressure value of the analog output at 20mA/10V.
Select output filters Range: 0.00...2.00s Resolution: 0.01s Grading: Step Size Range 10ms 0.00...0.2s 50ms 0.2 ...1.0s 100ms >1.0s
Authorization for the user.
The user has the permission
YES: To program
NO: To not program
the switching output in the user menu Save the previous changes.
YES: Save NO: Not Save
returns to the actual pressure indication afterwards.
9
Page 11
Con guration
Pressure, positive or negative
Pressure connection
Menu-guided programming using control buttons
Programmable pressure units: bar, psi
Materials
Measuring component
• Pressure connection
• Housing
Load change
Power consumption
Outputs
Switch outputs
• Function
Normally open contact (NO) or normally closed contact (NC),
programmable
• Switching current
0.5 A
• Setting
- Switching point
10 0% o f fu ll sc ale
10
Page 12
- Hysteresis
• Status indication
• Signal
Load resistance
Current output: < 500
• Hysteresis
0.3% o
0.2% of full scale
for thin
lm cell
Display
• Type
• Digits
• Accuracy
Rep
0.5% of full scale ( BFSL
Storage
• Media
• Ambient
0.017 % of Full Scale/°F
Electrical connection
Round connector M 12x1; 4-pin
Protection class
IP 65
CE - symbol
Interference emission and interference immunity in
Electrical protection classes
Pole reversal and overvoltage protection
Weight
f full scale
f full scale for ceramic cell,
eatability
11
Page 13
3.59”
(91.3 mm)
DIMENSIONS
1.38”
(35 mm)
Inches (mm)
Upper Part Rotates 330°
(40.6 mm)
1/4 NPT Standard
27 mm Hex
1.06”
30°
1.60”
M12x1
1.22”
(31.1 mm)
12
Page 14
is not required.
Remove the device as soon as device malfunctions start to occur. The internals cannot be
maintained by the customer. Replace the device or return it to the manufacturer to have it
Cleaning
Heavy soiling can be removed using a mild cleaning agent.
the country in which the device is installed.
13
Page 15
Notes:
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
_________________________________________________________
____
_____________________________________________________
_________________________________________________________
_________________________________________________________
14