NOSHOK 628-15000-1-1H-14-3, 628-10000-1-1H-14-3 User manual

Page 1
628 Series Intrinsically Safe
Hammer Union Transmitters
Technical Manual
www.GlobalTestSupply.com
Page 2
NOSHOK 628 Series
Intrinsically Safe Hammer Union Transmitters
Before installation, please read the entire manual.
Do not use the transmitter in any other way than described in these operating instructions, or protection provided by the equipment may be impaired.
Repairs done by the customer will void the warranty and approvals, and may create an explosion hazard.
DO NOT use these products as stop devices or in any other application where failure of the product could result in personal injury.
Ensure that the transmitter is only operated in accordance with the provisions as described in the following instructions.
www.GlobalTestSupply.com
Page 3
Table Of Contents
Chapter 1
Product Specications ................................................................. 4
Installation General......................................................................5
Removal, Maintenance and Repair ............................................. 6
Hazardous Location Information..................................................7
Understanding Approval Ratings .............................................. 8-9
Chapter 2
Intrinsically-Safe Installation ...................................................... 10
Control Drawings for I.S. Applications ..................................11-12
Chapter 3
Non-Incendive Installation ......................................................... 13
Installation Drawings for Non-Incendive Applications ..........14-15
Warranty ...................................................................................16
www.GlobalTestSupply.com
Page 4
Chapter 1
Product Specications
Excitation Voltage: 10-28 VDC Output: 4mA -20mA* Span: 16 mA *
Connections: +PWR/SIG: +EXCITATION VOLTAGE
-PWR/SIG: - EXCITATION VOLTAGE
(This terminal must also be grounded**. This is
normally accomplished in a non-hazardous area by grounding the supply return terminal per
control drawings 21076, 21077, 21078, & 21079)
Safe overload: ≥150% rated capacity Max. overload: ≥300% rated capacity
Shunt Calibration Circuit (optional):
Units with “-cal” connection but no “+cal”:
CONNECT TO NEGATIVE SIDE OF POWER SUPPLY TO ENGAGE the shunt calibration circuit. Do not engage the calibration circuit longer than one minute in a hazardous location.
Units with “+cal” & “-cal” connection:
To engage shunt, connect negative side of power supply to “-cal” and positive side of power supply to “+cal”. For units with a “+cal” connection, the shunt calibration circuit cannot be used or hooked up in hazardous locations.
IP rating:
Units are hermetically sealed and have an IP rating of at least IP54.
* Review calibration sheet for any customer specied variations.
** For ordinary, non-hazardous locations, the requirement for grounding the “-PWR/SIG” connection can be waived if powered by a class 2 circuit.
4
www.GlobalTestSupply.com
Page 5
Installation, General
See Chapter 2 for additional requirements when installing in hazardous locations.
Ensure that the transmitter is only used within the safe overload limit at all times.
Do not use the transmitter in any other way than described in these operating instructions, or protection provided by the equipment may be impaired.
Unpacking:
Inspect the transmitter for possible damage during transportation; should there be any damage, inform the transport company and NOSHOK right away.
Protection caps removed for inspection should be reinstalled until just before installation.
Never insert objects into the pressure port or press against
the sensor to deect in an attempt to simulate a load; this can
cause permanent damage to the diaphragm.
Installation:
The Safety of any system incorporating this transmitter is the responsibility of the installer.
Do not install the pressure transmitter if it has any damage. (Mark damaged units to prevent them from accidently being installed).
Some installations require special and/or expert knowledge for safe installation. For example, applications such high pressures, dangerous media, and mounting of heavy loads are beyond the scope of this manual. Trained and knowledgeable persons should be consulted during installation.
A shielded cable is preferred for signal quality. It should be grounded at one end. Grounded at both ends may introduce ground loop problems.
www.GlobalTestSupply.com
5
Page 6
Installation, continued
Verify that process connections are compatible.
Verify that wetted parts are compatible with the media.
Do not use with abrasive media.
When using o-rings, thread tape or sealants, verify that they are compatible with the media, temperature range, and pressure range of the transmitter.
Only tighten on the wrench ats closest to the pressure port.
Do not allow media to freeze in pressure port.
Removal, Maintenance and Repair
Transmitters require no maintenance during use.
All adjustments and repairs should be performed by NOSHOK. No disassembly or adjustments are permitted in hazardous locations.
Recommended recalibration cycle is one year, under normal conditions.
Never attempt to remove the transmitter when it is under load or pressure.
Take precaution with regard to remaining media in transmitter.
It may be hazardous, toxic, or ammable.
Repairs done by the customer will void warranty, approvals, and may create an explosion hazard.
Never insert objects into the pressure port or press against
the sensor to deect in an attempt to simulate a load; this can
cause permanent damage to the diaphragm.
6
www.GlobalTestSupply.com
Page 7
Hazardous Location Installations
Observe the relevant national regulations (e.g.: IEC 60079-14, NEC, CEC) and observe the applicable standards and directives for special applications (e.g. with dangerous media
such as acetylene, ammable gases or liquids and toxic gases
or liquids and with refrigeration plants or compressors).
Observe the ambient ratings on unit label.
All adjustments and repairs should be performed by NOSHOK. No disassembly or adjustments are permitted in hazardous locations.
Repairs done by the customer will void warranty, approvals, and may create an explosion hazard.
Protect the diaphragm against any contact with abrasive substances, pressure spikes, and do not touch with tools. If you damage the diaphragm, no intrinsic safety can be guaranteed.
Units meet dielectric strength requirements of 60079-11 paragraph 6.3.12.
Negative terminal, marked “-PWR/SIG”, must be grounded.
Barriers must comply with the entity parameters noted on the control drawings.
Installation not per the appropriate control drawing will invalidate the safety rating. See product label for applicable control drawing. For example, “install per 21076”.
Installation per the control drawing is required but it is not necessarily sufcient to ensure safety. The system in which it is installed must still conform to all applicable national and industrial standards.
www.GlobalTestSupply.com
7
Page 8
Understanding Approval Ratings
The relevant codes and standards should be consulted for
precise interpretation of the classications and marking. The denitions below are only for reference.
Units are not rated for mines.
8
www.GlobalTestSupply.com
Page 9
www.GlobalTestSupply.com
9
Page 10
Chapter 2
Intrinsically Safe Installation
Introduction
“Intrinsic safety” insures that a circuit operated under normal and
specied fault conditions is not capable of causing ignition of the
prescribed explosive atmosphere.
Installation The certication of each testing laboratory is valid when the transmitter has been installed according the installation drawings
or certicates of conformity included in this section.
10
www.GlobalTestSupply.com
Page 11
CSA Installation Drawings for Intrinsically Safe Applications
www.GlobalTestSupply.com
11
Page 12
CSA Installation Drawings for Intrinsically Safe Applications
CiLiPi
12
www.GlobalTestSupply.com
Page 13
Chapter 3
Non-Incendive Installation
Introduction
“Non-incendive” circuits are designed and constructed so that they are not capable under normal operating conditions or due to
opening, shorting, or grounding of eld wiring, of causing an ignition of the prescribed ammable gas or vapor.
Installation
The certication of each testing laboratory is valid when the transmitter has been installed according the installation drawings
or certicates of conformity included in this section.
www.GlobalTestSupply.com
13
Page 14
CSA Installation Drawings for Non-Incendive Applications
14
www.GlobalTestSupply.com
Page 15
www.GlobalTestSupply.com
15
Page 16
WARRANTY INFORMATION
NOSHOK’s Three Year Warranty applies to 628 Series Intrinsically Safe Hammer Union Transmitters.
NOSHOK guarantees all products
to be free from defects in
material and workmanship, to remain within catalogued accuracy
specications, and to operate within the catalogued performance specications.
These products must be operated within the catalogued environmen­tal and application parameters. Determination of failure will be made
by NOSHOK, Inc.’s equipment and personnel or a certied test facility
specializing in this type of evaluation. Instrument failures determined to be caused by over-range, incompatibility with environment or product media and abuse will not be considered under this warranty. NOSHOK, Inc. will, at its discretion, repair or replace the working parts of the damaged gauge without cost to the customer.