NOSHOK 622 User Manual

User Manual
FM
TRANSMITTERS
Series 621 and 622
Explosion-proof
(Factory Mutual and Canadian
Standards Association Approved)
®
APPROVED
US
©
NOSHOK
General
NOSHOK series 621 and 622 pressure transmitters are approved for use in hazardous location applications as follows:
Explosion-proof for Class I, Division 1, Groups A, B, C and D; Dust Ignition-proof for Class II and III, Division 1, Groups F and G. FM standards according to FMRC 3600, 3615 and 3810 and 3810. ANSI/ISA-12.27.01-2003 Approved single seal.
These transmitters must be installed and operated according to NEC and local codes. Improper installation or modifications to the electrical connection will void the hazardous approval rating.
Installation and commissioning
NOSHOK series 621 and 622 transmitters are supplied with a 1/2NPT Male conduit connection with either a 6jacketed cable or 6free leads. Series 621 and 622 transmitters meet the requirements of a single seal device as defined by ANSI/ISA 12.27.01-2003. Series 621 has threaded process connections and model 622 has G1/2B or G1B flush diaphragm connections. Refer to the catalog for complete specifications. Do not torque the process connector with a force greater than 37 foot pounds. Dust tight conduit seals must be used when installed in Class II and Class III installations.
For the 4 mA to 20 mA output version, install the power supply,transmitter and receiving instrument in a series circuit to form a 2 wire loop. The transmitter regulates the current in the loop.
The transmitter is classified for over-voltage category II and the pollution degree 1. For the voltage output version, the 3 wire system uses separate leads for the power supply and output signal.The 3rd lead is a common minus. Use a NEC Class 02 power supply, low voltage and low current maximum 100 VA even under fault conditions.