Page1of2
NORTROLLAS
MOUNTINGINSTRUCTIONS
General
LINETROLL111Kmountsonthepole3-5meters
belowtheconductorsasshowninfigure3.
Theindicatorcanbeinstalledonaliveline.
Beforemounting
LINETROLL111Kisaprogrammablefaultcurrent
indicator,before
installation.
andmustbeprogrammed
Mounting&programming
1.Unscrewthetopcapfromthelens,andsettherequired
switchcombinationsaccordingtoFig.4andtable1
onpage2.
4.Thepolebracketismountedonthepoleusing
thescrewssupplied.Thebracketshouldbemounted
verticallybeneaththeconductors.Fig.2&3.
5.Fixtheindicatortothebracketusingthescrews
supplied.Fig.2.
Fig.3.MountingofLT111Konapole
Fig.2.Fixingoftheindicator.
Pleaserefertotable1onpage2.
File:lt111mi2.cdrRev.date:1.07.95
3-5m.
SLOTSFOR
FASTENING
STRAP
WOODSCREW
WASHER
2.Whentheindicatorhasbeenprogrammed,thebattery
shouldthenbeconnected.SeeFig.1.
3.Replacethetopcapbyenteringthetopcaparrow
alignedwiththearrowonthelenslabel.
Fig.1.Connectionofthebattery
Toensurethatthebatteryhasreachedthenormal
operatingvoltage,theindicatorshouldbeleftto
flashforabout30minutes,
Thebrackethasalsoslotsforfasteningonboth
concreteandmetalpoleswithsteelstraps.
6.Iftheindicatorisprogrammedforvoltagereset,
andthelineisenergised,theindicatorwillreset
duringtheinstallation,orwithin15or30sec
aftertheinstallation.
LINETROLL111K
Programmable
Faultcurrent
indicator
Iftheindicatorshavebeeninstoreforsometime,the
batteryvoltagemaybelow.
bywhichtimethevoltage
willberestoredtotherequiredvalue.
ConsulttheUserGuideforthecorrectdistance
fromtheconductors.
TOPCAP
LINETROLL111KMOUNTINGINSTRUCTIONS