North Star M165938N User Manual

M165938N
ITEM NUMBER: 165938
TM
Owner’s Manual
Instructions for Installation/Set-up, Operation, Servicing, & Storage
Portable, Outdoor Use-Only, Triple Fuel Generator
6,600 Watt Continuous (8,000 Watt Surge) Capacity
SERIAL NUMBER: _____________
WARNING
READ and UNDERSTAND this manual completely before using the generator! Failure to properly set up,
operate, and maintain this generator could result in serious injury or death from carbon monoxide poisoning, electric shock, fire/explosion, or burns. In particular, be aware of the following hazards:
Generators give off carbon monoxide, a poisonous gas that can kill you. You CANNOT smell it, see it, or taste it.
ONLY run generator OUTDOORS and AWAY from building air intakes. NEVER run generator inside any enclosed or semi-enclosed spaces, including homes, basements, garages, sheds , boxes , RVs, boats or pick-up truck beds. These spaces can trap poisonous gases, EVEN if you run a fan or open windows.
Carbon monoxide is given off whether you are using gasoline, nat u ral gas, or propane to power the generator.
Install carbon monoxide alarms inside nearby structures/buildin gs (bat t er y -o perat ed , or plug-in with battery backup).
Electric shock / Electrocution
High voltage electricity from generator can kill. DO NOT operate in wet locations. Be sure generator is properly grounded. Use only UL-listed, outdoor-rated grounded extension cords of proper size.
NEVER plug the generator directly into a wall outlet. ANY connection to a building’s electrical system MUST ISOLATE THE GENERATOR FROM UTILITY POWER via a UL-approved transfer switch installed by a licensed electrician. Otherwise, back feed from the generator into the power grid could kill utility workers.
DO NOT overload generator (per rated capacity), and OPERATE ONLY in an area with adequate cooling ventilation so engine does not overheat. Exhaust can be extremely hot. Keep muffler at least 7’ from all combustible objects.
All fuels are flammable. Never fuel a running or hot engine. Never pump fuel directly into generator at gas station – use approved container to transfer fuel. Ensure there are no fuel leaks, and keep sources of sparks and flames away.
LPG/NG hook-ups must be completed by a certified gas technician and comply with all federal and local requirements.
ALWAYS keep a fire extinguisher rated “ABC” nearby.
CO Poisoning
Fire / Explosion
STOP!
CHOOSE THE RIGHT GENERATOR FOR YOUR NEEDS. See the “Power load Planning & Management” section
of this manual to determine your power load requirements and then compare to the generator’s rated capacity.
INSPECT COMPONENTS: Closely inspect to make sure no components are missing or damaged. See the “Unpacking
& Delivery Inspection” section for instructions on whom to contact to report missing or damaged parts.
ARRANGE FOR PROFESSIONAL INSTALLATION of transfer switch and/or NG/LPG hook-ups, if they will be used.
See the “Installation/Initial Set-Up” section for more information about these requirements.
Any Questions, Comments, Problems, or Parts Orders
Call NorthStar Product Support 1-800-270-0810
Hazard Signal Word Definitions
2
Table of Contents
Hazard Signal Word Definitions ................................................................................................. 2
About Your Generator ................................................................................................................. 4
Specifications ................................................................................................................................. 6
Safety Label Locations.................................................................................................................. 7
Machine Component Identification............................................................................................. 8
Power Load Planning & Management........................................................................................11
Installation / Initial Set-Up:
1. Unpacking & Delivery Inspection..........................................................................................13
2. Planning the Power Load........................................................................................................13
3. Gas Hook-up Installation for Natural Gas or Propane (LPG) – if using................................14
4. Set-up as a PORTABLE or BUILDING BACK-UP Power Source ......................................16
5. Selecting a Suitable Site.........................................................................................................19
6. Grounding the Generator........................................................................................................21
7. Battery Installation .................................................................................................................22
Operation:
1. General Safety Rules for Operation .......................................................................................23
2. Preparing for Operation..........................................................................................................26
3. Starting the Engine.................................................................................................................30
4. Checking Generator Output....................................................................................................32
5. Connecting Loads...................................................................................................................33
6. Switching Fuels (during operation)........................................................................................34
7. Stopping the Engine ...............................................................................................................34
8. Storage & Exercise.................................................................................................................35
Maintenance & Repair..................................................................................................................37
Troubleshooting.............................................................................................................................39
Summary of Important Safety Information for Operation.......................................................40
Generator Exploded View............................................................................................................45
Wiring Diagram.............................................................................................................................47
Generator Head Exploded View..................................................................................................48
3
About Your Generator
Thank you for purchasing your NorthStar portable generator!
About Your Generator
This engine-driven, portable generator is designed to provide up to 8,000 Watts of electrical power (6,600 watts continuous, 8,000 watts surge).
It can supply power:
1. As a portable power source electrical outlets.
2. As a back-up, standby power source for a building. A licensed electrician can connect
the generator to your building’s electrical system via the installation of an UL-approved transfer switch. (See the “Installation & Initial Set-up” section of this manual to learn more about specific requirements and precautions relating to wiring the generator to your building’s electrical system.)
You must select a generator adequately sized for your power needs. You need to determine the power needs of all the appliances/tools you wish to power at the same time and choose a generator rated to provide at least that power level. See the “Power Load Planning & Management” section of this manual to determine your specific power load requirements and then compare them to this generator’s rated capacity. You must not overload the generator. Overloading will cause damage to the generator and attached electrical devices, and may also result in fire.
You can power this generator with gasoline, natural gas (NG), or propane (LP) gas. The generator is designed so that it is easy to switch between fuel sources. However, there are special initial hook-up requirements for natural gas and propane. See the “Specifications” section of this manual with regard to specific gas flow and pressure requirements. In addition, note the following:
Natural gas. The standard delivery pressure provided to your building by your utility
company may not match the requirements of your generator.
a) If your standard delivery pressure is higher than allowable for this generator, you
may need to have a pressure-reducing regulator installed. (Note: The regulator supplied with this generator is NOT a pressure-reducing regulator).
b) If your standard delivery pressure is lower than allowable for this generator, you
will need changes to your natural gas service to elevate the delivery pressure.
ALL natural gas hook-ups must be completed by trained personnel from your natural gas utility company and inspected as required by your local building code.
Propane (LP). You will need a minimum 100 lb. LPG gas tank to run this generator – the
vaporization rate is insufficient with smaller tank sizes. A qualified propane gas technician must set up the valve and hose connection between the propane tank and generator in accordance with all local regulations and electric code.
See the “Installation / Initial Set-Up: Step 3” section of this manual for more detailed information.
Be sure to read about site selection and grounding requirements for running this generator. More detailed information can be found in the “Installation & Initial Set-up, Steps
5 & 6” of this manual.
. You can plug appliances directly into the generator’s
4
About Your Generator (cont’d)
This generator is too heavy for one person to lift without mechanical assistance. An optional wheel kit is available from NorthStar and is recommended if you will be moving the generator unassisted. Other optional accessories available from NorthStar include a vi nyl cover for storage, UL-approved transfer switches, and extension cords.
Contact NorthStar Product Support at 1-800-270-0810
with questions about optional accessories or to order.
Read this Manual
Improper use or maintenance of this generator can result in serious injury or death from
carbon monoxide poisoning, electric shock/electrocution, fire/explosion, or burns.
Read this manual completely before using the generator and follow all instructions and
safety rules.
You must follow all instructions and safety precautions presented throughout this manual. A summary of important safety information can be found at the end of the manual. Keep this manual for reference and review.
Proper preparation, operation, and maintenance will result in operator safety, as well as best performance and long life of the generator. For detailed engine operation and maintenance information, always refer to the engine Owner’s Manual furnished with the generator.
NorthStar is constantly improving its products. The specifications outlined herein are subject to change without prior notice or obligation. The purchaser and/or user shall assume liability for any modification and/or alterations of this equipment from original design and manufacture.
Before using, the user shall determine the suitability of this product for its intended use and assumes liability therein.
Contact NorthStar Product Support at 1-800-270-0810
for any questions about the appropriate use of this generator.
WARNING
Warranty Registration
Please fill out and submit the warranty registration card so that we have your contact information for any future product literature or replacement parts you may need.
ATTENTION:
All Rental Companies and Private Owners who loan this
equipment to others!
All persons to whom you rent/loan this generator must have access to and read this manual. Keep this owner’s manual with the generator at all times and advise all persons who will operate the machine to read it. You must also provide personal instruction on how to safely operate the generator and remain available to answer any questions a renter/borrower might have.
5
Specifications – Item #165938N
SPECIFICATIONS
Item Number #165938 Maximum Output 8000 Watts (W) Continuous Output: Gasoline Liquid Petroleum Gas (LPG) Natural Gas (NG) Voltage 120 / 240 Volt (V) Phase Single phase (4-wire) Frequency Regulation 56.5 - 63.3 Hertz (Hz) Voltage Regulation 110-129V Power Factor 1.0 p.f. Engine 13 HP Honda Engine Speed 3390 - 3798 RPM Fuel Type Unleaded gasoline/LPG/NG Pressure Range (LPG, NG) (7-11 in H2O, 4-6 oz.) Min. Flow Range (LPG, NG) (5.7 lb/hr-LPG, 2.0 CFM-NG) Fuel Capacity 6.5 gallons (24.6 L) Oil Capacity 1.16 US quarts (1.1 L) Starting Method Electric/Recoil 120V Receptacle 15 Amp (A) duplex (NEMA 5-15R)
20 Amp (A) duplex (NEMA 5-20R)
120/240V Receptacle 30 Amp (A) locking device Circuit Breaker (1) 15 Amp (A) thermal, push to reset
(2) 20 Amp (A) thermal, push to reset
(2) 30 Amp (A) thermal, push to reset Grounding Post Receives 10 Ga. wire or fork terminal Battery (not included)
Dimensions
Length 31.75” (80.6 cm) Width 23.63” (60.0 cm) Height 22.25” (56.5 cm) Dry Weight 225 lb. (102 kg) Gross Weight 250 lb. (114 kg)
12 Volt, 18 Amp-Hour minimum,
6600 Watts (W) 6200 Watts (W) 5200 Watts (W)
(NEMA L14-30R)
Group size U1
6
Safety Label Locations – Item #165938N
©2005 NT+E 1-800- 270-0810
WARNING
BURN HAZARD
Do not touch hot muffler.
PN 39260
Commercial-grade electric start engine
Extend run 6.5 gallon fuel ta nk
Maintenance-free brushless alternator design
Smooth running focus mount isolation system
BATTERIES:
1) contain caustic acid, 2) em it explosive gases, 3) ca n cause electric shock
ALWAYS use eye protection. Caustic acid and explosive gases can cause blindness or severe burns. NO smoking, sparks, or flames. NEVER touch both battery terminals at the same time with your hand or any non-insulated tools. FLUSH immediately with water if battery acid contacts eyes, skin, or clothing. CONNECT cables in co rrect sequence: FIRS T RED to POSITIVE terminal, then BLACK to NEGATIVE terminal. When disconne cting, DISCONNECT BLACK cable first, then RED. NEVER charge a visibly damaged or frozen battery. ALWAYS read and follow charger instructions.
charge battery with a trickle charger that is rated for 3 amps maximum.
©2007 NT+E 1-800-270-0810
Always make sure safety labels are in place and in good condition. If a safety label is missing or not legible, order new labels or unsafe operation could result.
To order replacement safety labels, call NorthStar Product Support at 1-800-270-0810.
WARNING - BATTERY HAZARDS
IF GENERATOR IS TO BE STORED LONGER THAN 2 MONTHS,
ATTENTION
A charged battery ensures reliable engine starting.
Starting Instr uctions - LP/NG
1. Connect regulator hose to LP/NG inlet
2. Set fuel selector switch to LP/NG
3. Start engine
Starting Instructions - Gasolin e
1. Set fuel selector switch to Gasoline
2. Start engine
Switching Fuels on the Fly
LP/NG to Gasoline:
1. Change fuel selector switch to Gas oli ne
Gasoline to LP/NG:
1. Change fuel selector switch to None
2. Wait for engine to start sputtering
3. Change fuel selector switch to LP/NG
See Owner's manual for more details
PN 779396
On-Product Warning Labels
Part numbers Description
39260 Burn Warning 779396 Battery Warning 779422 NorthStar 779424 Warning
7
Machine Component Identification - Item #165938N
Figure 1 (Ref. 1-12)
Ref. Description Ref. Description
1 Gas Cap with Gauge 11 Super Silent Muffler 2 6.5 Gallon Gas Tank 12 Air Cleaner 3 Battery Box 13 Engine Key Switch 4 Circuit Breakers 14 Fuel Valve 5 120V 15A Duplex Receptacle 15 Choke Lever 6 Fuel Selector Switch 16 Recoil 7 120V 20A Duplex Receptacle 17 LPG / NG - 3/4” NPT Inlet 8 120/240V 30A Locking Receptacle 18 Demand Regulator 9 Vibration Isolation Mounts 19 Generator Head
10 Oil Drain Plug
Figure 2 (Ref. 13-19)
8
Machine Component Identification - Item #165938N
REFERENCE GUIDE
Reference 1 – Gas Cap with Gauge
Reference 2 – 6.5 Gallon Gas Tank
Reference 3 – Battery Box
Reference 4 – Circuit Breakers
Reference 5 – 120V 15A Duplex Receptacle
Reference 6 – Fuel Selector Switch
Reference 7 – 120V 20A Duplex Receptacle
Reference 8 – 120/240V 30A Locking Receptacle
The gas cap is extra large, creating a large hole for refilling and a comfortable grip. You can always monitor the fuel level without removing the cap by using the fuel level indicator built into the gas cap. Large tank allows for extended run capabilities. Always allow room for gasoline expansion by not filling the gas tank completely full. The battery box provides protection for the battery and will accept a standard lawn tractor size battery (Group U1-7). The engine requires a 12 volts d.c. battery, with a minimum rating of 18Ah (Amp-Hour). See battery section for sizing. This portable single phase generator has 1-15 amp (A), 2-20 amp (A), and 2-30 amp (A) push to reset circuit breakers to protect against electrical overloads. The generator has a control panel with two duplex (two receptacles in a common housing) receptacles. This duplex is a 120 volt (V) 15 amp (A) straight blade receptacle, National Electrical Manufacturer’s Association (NEMA) number 5-15R. This receptacle accepts NEMA plug number 5-15P. The duplex is capable of drawing 15A out of either receptacle or a combination of both.
Switching from LP or NG to gasoline:
1. Disconnect all loads to generator.
2. Turn the gas line valve to ON position.
3. Flip the fuel selection switch to the GASOLINE position.
Switching from gasoline to LP or NG:
1. Disconnect all loads to generator.
2. Make sure LP or NG fuel is being supplied.
3. Flip the fuel selection switch to the NONE position.
4. Wait for the engine to begin sputtering, this indicates the engine is being starved of gasoline. Do not choke the engine when switching to LP/NG fuel.
5. Flip the fuel selection switch to the LP/NG
position.
6. Momentary sputtering is common. If engine
stops running, turn the ignition key to restart the engine.
7. Turn gasoline line valve to OFF position.
The second duplex is a 120V 20A straight blade receptacle, National Electrical Manufacturer’s Association (NEMA) number 5-20R. This receptacle accepts NEMA plug numbers 5-15P and 5-20P. Each receptacle on this duplex is capable of drawing 20A. The locking device is a 120/240V 30A NEMA L14-30R receptacle. This receptacle accepts a NEMA plug number L14-30P.
9
Machine Component Identification - Item #165938N
Reference 9 – Vibration Isolation Mounts
Reference 10 – Oil Drain Plug
Reference 11 – Super Silent Muffler Reference 12 – Air Cleaner
Reference 13 – Engine Key Switch
Reference 14 – Fuel Valve
Reference 15 – Choke Lever
Reference 16 – Recoil Reference 17 – LPG / NG – ¾” NPT Inlet
Reference 18 – Demand Regulator Reference 19 – Generator Head
The engine and generator are mounted on rubber cylinders that absorb most of the engine vibration. This feature eliminates the tendency of the machine to “walk” which is common in engine powered equipment. Refer to your Honda engine manual for oil change recommendations. Noise level is 8 dB less than Honda’s standard muffler.
Refer to your Honda engine manual for air cleaner care. The engine key is located on the engine. Always locate this switch and be familiar with its location before operating the generator. Consult the Honda engine owner’s manual for further instructions. The engine has an ON-OFF valve mounted on the front of the engine. Always keep this valve closed when the generator is not in use. Used during cold starts. The choke is only used with gasoline fuel. Refer to Honda engine manual for usage. Grasp firmly when starting engine. Before you start engine, smell next to floor for gas, if you do smell gas:
DO NOT start engine.
DO NOT light a match.
DO NOT flip on an electrical switch.
Exit area immediately and call gas supplier or
fire department. Minimum flow range required: NG - 2.0 CFM, LPG - 5.7 lb/hr. Pressure Range: 4-6 ounces, OR 7-11 inches of water column. NEVER over pressurize. Supplies the engine LP or NG fuel only if the engine is running. The electricity producing part of the generator.
10
Power Load Planning & Management
WARNING
NEVER exceed the rated wattage capacity of your generator. OVERLOADING may cause SERIOUS DAMAGE to the generator and
attached electrical devices, and may result in fire.
Your generator MUST BE SIZED PROPERLY to provide both the running and starting (surge) wattage of the devices you will be powering. Before using your generator, determine the running and starting wattage requirements of all the electrical devices you will be powering simultaneously. The sum of the running and starting wattages of the devices being powered must not exceed the continuous output rating of your generator. (The continuous output rating of your generator is listed in the “Specifications” section of this manual.) Note that:
Devices without electric motors such as light bulbs, radios, and televisions have the same running and starting wattage.
Devices with electric motors such as refrigerators, compressors, and hand tools typically require a starting wattage that is 3 to 5 times greater than the running wattage.
The running and starting wattage requirements are often listed on a device’s nameplate. If wattage is not given on the device’s nameplate, the wattage may be calculated by multiplying the nameplate voltage by nameplate amperage, Watts = Volts X Amps.
Example conversion to watts:
120 Volts X 5 Amps = 600 Watts
If only the running voltage is given on the nameplate for a device with an electric motor, the starting wattage can be approximated to be three to five times the running wattage.
Estimates for the running wattage requirements for common devices are listed in Table 1 below. Guidance for starting wattages is provided in the table’s footnotes.
Table 1
Device
Air conditioner (12.000 BTU) 1700 (a,b) Jet pump 800 (a) Battery charger (20 Amp) 500 Lawn mower 1200 Belt sander (3”) 1000 Light bulb (100 Watt) 100 Chain saw 1200 Microwave oven 700 Circular saw (6½”) 2000 (a,b) Milk cooler 1100 (a) Coffee maker 1800 (a,b) Oil burner on furnace 300 Compressor (1 HP) 1400 (a,b) Oil-fired space heater (140,000 Btu) 400 Compressor (3/4 HP) 1800 (a) Oil-fired space heater (85,000 Btu) 225 Compressor (1/2 HP) 1400 (a) Oil-fired space heater (30,000 Btu) 150 Curling iron 700 Oven 4500 Dishwasher 1200 Paint sprayer, Airless (1/3 HP) 600 (a) Edge trimmer 500 Paint sprayer, Airless (handheld) 150 Electric nail gun 1200 Radio 200 Electric range (1 element) 1500 Refrigerator 600 (b) Electric skillet 1250 Slow cooker 200 Furnace fan (1/3 HP) 1200 (a) Submersible pump (1-1/2 HP) 2800 (a)
Running
Watts Device
Running
Watts
11
Power Load Planning & Management (cont’d)
Device
Freezer 800 (b) Submersible pump (1 HP) 2000 (a) Hair dryer 1200 Submersible pump (1/2 HP) 1500 (a) Hand drill (1”) 1100 Sump pump 600 (a) Hand drill (1/2”) 875 Table saw 2000 (a) Hand drill (3/8”) 500 Television 500 Hand drill (1/4”) 250 Toaster 1000 Hedge trimmer 450 Vacuum cleaner 250 Home computer 150 VCR 70 Impact wrench 500 Water Heater 3000 Weed trimmer 500 (a) Hard-starting motors require 3-5 times the rated running watts (b) For extremely hard to start loads such as air conditioners and air compressors, consult the equipment
dealer to determine maximum wattage
Running
Watts Device
Running
Watts
To calculate the running and starting wattage requirements for the devices you will be powering, follow these steps:
1. Make a list of all electrical devices you will be powering at the same time with the generator.
2. List the greater of the running or starting wattage next to each device as obtained from the
devices’ nameplate or Table 1. If only the running wattage for a device with an electric motor is known, the starting wattage can be estimated to be at least 3 times the running wattage.
3. Add the wattages for all devices on your list. This total must be lower than the continuous output rating of your generator.
Example:
Device to be Powered
Light Bulb 75 W Refrigerator – 18 Cu. Ft. 1600 W Microwave 700 W Window AC 1800 W Sump pump (1/3 hp) 2100 W
Total 6275W
In this example, the generator must have a continuous output of at least 6275 W in order to power all of the devices simultaneously.
STAGGERING LOADS
Greater of Starting/Running
Wattage
You can increase the number of devices your generator can power by staggering the load on the generator. For example, you could alternately power your refrigerator and air conditioner for limited periods of time -- powering only one of the devices at a time and never powering both at the same time.
12
Installation / Initial Set-Up
There are a number of important steps required to set up your generator for initial use. These steps are:
Steps for Installation / Initial Set-Up
1. Unpacking & delivery inspection.
2. Planning the power load to stay within the generator’s rated capacity.
3. Getting gas hook-ups installed if natural gas or LP gas will be used as a fuel source.
4. Setting up generator for the type of power generation you need:
a. portable power source, or b. connected to a building as a back-up power source.
5. Selecting a site for using the generator.
6. Grounding.
7. Battery installation (electric start models only).
Each of these steps is discussed in detail below:
1. Unpacking & Delivery Inspection
You should inspect the generator immediately after you receive delivery.
See the “Machine Component Identification” section of this manual for a
If you have missing components, contact Product Support at 1-800-270-0810.
If you have damaged components, contact the freight company that delivered the unit and file a
Plan your power load so that you do not exceed the generator’s rated capacity.
See the “Power Load Planning & Management” section of this manual to review how to plan and manage power loads for the generator.
diagram of the generator and its components.
claim.
2. Planning the Power Load
13
Installation / Initial Set-Up
3. Gas Hook-up Installation for Natural Gas or LPG (if needed)
You can power this generator with gasoline, natural gas (NG), or propane (LP) gas. The generator is designed so that it is easy to switch between fuel sources. However, there are special initial hook-up requirements for natural gas and propane:
WARNING:
If you choose to operate the generator on NG or LPG, you must have the fuel line system installed by a certified gas technician.
Specific requirements for each type of hook-up are given below:
Natural Gas (NG) Hook-up
Contact your gas utility company for installation of a natural gas hook­up for the generator.
WARNING:
Natural gas is a highly explosive gas. All natural gas hook-ups must be completed by trained personnel from your natural gas utility company and inspected as required by your local building code.
This product is designed to operate on NG at a gas pressure range of 4 to
6 ounces per square inch (7”-11” of water column) and requires a minimum NG flow rate of 3.25 CFM.
The standard gas pressure normally delivered to your building by your
utility company may be higher or lower than the required 4-6 ounces per square inch (7”-11” of water column):
o If your standard delivery pressure exceeds 4-6 ounces per square
inch (7”-11” water column), you will need a pressure-reducing regulator installed. Excessive gas pressure will permanently damage this product and void the warranty if the generator is not installed correctly with a pressure-reducing regulator as needed.
Note: The regulator supplied with this product is NOT a
o If your standard delivery pressure is lower than 4-6 ounces per
square inch (7”-11” water column), you will need changes to your natural gas service to provide elevated delivery pressure. In addition you will need to have a pressure-reducing devices installed for your other natural gas appliances.
Propane (LPG) Hook-up
Contact your local propane supplier to install a propane fuel system for the generator.
WARNING:
LPG is a highly explosive gas. A qualified propane technician must make the valve and hose connection between the propane tank and generator in accordance with all local regulations and electrical codes. All LPG hook-ups should be completed by trained personnel from propane supplier and inspected as required by your local building code.
pressure-reducing regulator, but one can be supplied and installed by your gas utility technician at the time of fuel system hook-up.
14
Installation / Initial Set-Up
This product is designed to operate at an LPG gas pressure range of 7” to
11” of water column and requires a minimum LPG gas flow rate of 9.33 lb/hr, 2.2 Gal/hr, or 201,718 BTU/hr.
Note: All gas cylinders produce gas pressure in excess of 11” water
column. Introduction of gas pressure into the generator in excess of 11” water column will permanently damage this product and void the warranty. You will need a pressure­reducing regulator installed as part of your LP gas fuel system.
You will need a minimum 100 lb. LPG gas tank to operate the
generator.
This generator will not work with 20-lb gas cylinders used in gas grills and recreational equipment, or 40-lb gas cylinders used in forklifts and tractors. These smaller gas tanks do not have a sufficient vaporization rate to run the generator.
Some installations may require tanks even larger than 100-lb as a result of low surrounding air temperature and other appliances drawing fuel from the same tank.
15
Installation / Initial Set-Up
4. Set-up either as a BUILDING BACK-UP or PORTABLE Power Source
This generator is designed to provide up to 8,000W of electrical power. It can supply electricity in two ways:
1. As a back-up, standby power source for a building. For this application, you must arrange
for a licensed electrician to connect the generator to your building’s electrical system via the installation of an UL-approved transfer switch accordance with building electrical code and guidelines supplied by your power company.
2. As a portable power source. You can plug appliances or tools directly into the generator’s
electrical outlets.
Specific requirements for each are given below.
Note: Regardless of whether you use your generator as a back-up power source connected to a
building or as a portable power source, you must not overload the generator. Overloading may cause serious damage to the generator and attached electrical devices.
Using as a Back-up Power Source for a Building
Contact a licensed electrician to install a UL-approved transfer switch if
you want to use your generator as a back-up power source for a building. What does a transfer switch do? It:
a) Safely connects the generator to your building’s electrical system by
isolating your generator from your utility company’s power lines, AND
b) Connects your generator to a critical subset of your building’s circuits
that are needed for emergency power needs.
If your generator will be connected to your building’s electrical system, it MUST ALWAYS be isolated from the utility power grid with a UL-approved transfer switch installed by a licensed electrician in compliance with all applicable building and electrical codes, and in accordance with guidelines supplied by your power company.
DANGER:
A transfer switch must be installed in order to isolate your generator from the utility power grid. If your generator is NOT properly isolated from the utility system, serious hazards will arise: When your generator is running, it’s output will back feed
into the utility power line and transformer that are normally used to provide you with power. The transformer will step up the current to the normal line voltage. An unsuspecting utility line worker working on what he thinks is a deactivated line could be electrocuted.
If your generator is connected (running or not) when
utility power is restored, your generator will be destroyed. It could also explode or cause fire.
. The transfer switch must be installed in
16
Using as a
N
R
R
Portable Power Source
Installation / Initial Set-Up
In addition to isolating your generator from the utility system, the transfer switch connects your generator to a limited set of circuits in your building that have been chosen as critical to operate during a power outage.
The generator cannot power your entire home -- you must work with the installing electrician to determine which devices/appliances you wish to power during an outage. The electrician can help you determine which circuits and devices can be powered simultaneously without overloading the generator.
(See the previous section of this manual entitled “Power Load Planning &
Management” for more information on load application and selection.) When using the generator as a portable power source, you can plug electric devices and appliances directly into the generator’s electrical outlets.
There are three different kinds of electrical outlets on the generator:
1. One 120/240 Volt, 30 Amp locking receptacle (NEMA L14-30R locking receptacle compatible with L14-30P mating plug).
2. One 120 Volt, 20 Amp duplex straight-blade receptacle (NEMA 5­20R duplex receptacle compatible with NEMA 5-20P or 5-15P mating plugs).
3. One 120 Volt, 15 Amp duplex straight-blade receptacle (NEMA 5­15R receptacle compatible with NEMA 5-15P mating plug)/
NEMA
5-20
NEMA
5-15
FIG02683
(See more technical detail about these receptacles and their associated circuit breakers in the “Machine Component Identification” section of this manual.)
Make sure you plug each electrical device/appliance into the correct
generator outlet based on the device’s plug configuration and voltage/amperage rating. Never exceed the amperage rating of an outlet.
EMA
L14-30R
17
Installation / Initial Set-Up
Extension cords may be used to power devices that are located at a
distance from the generator. However, use only UL-listed, outdoor-rated, grounded extension cords of the proper size. Use Table 2 below to choose an adequately sized extension cord according to the amperage of the device being used and the length of the cord.
Table 2
All extension and appliance cords must be in good condition and not worn,
Northern Tool is NOT responsible for damage or injury resulting from customer use of inadequate extension cords.
Current/Power Maximum Extension Cord Length
Amps at Load #10 Ga. #12 Ga. #14 Ga. #16 Ga.
240V (watts) Cord Cord Cord Cord
10 2400 250' 150' 100' 75' 20 4800 125' 75' 50' 25' 30 7200 60' 35' 25' 10' 40 9600 30' 15' 10' * 50 12000 15' * * *
WARNING:
Use of under sized extension cords can cause electric shock, fire, or damage to connected devices.
bare, frayed, or otherwise damaged.
WARNING:
Use of damaged electric cords can cause electric shock or fire.
Note: If an extension cord becomes hot to the touch, it is overloaded or damaged and must be replaced.
18
Installation / Initial Set-Up
5. Select a Suitable Site
Before using the generator, you must select a suitable OUTDOOR location for installation and operation. This location should meet all of the criteria listed below.
WARNING:
You must choose a suitable site for operating your generator to avoid equipment damage and/or injury and possible death from carbon monoxide poisoning, electric shock, or fire. Choose a site that meets all of the criteria specified.
Dry, level surface The generator should be positioned on a dry, firm, level surface.
Ensure that the generator sits level and will not slide or shift during operation. If applicable, block the generator’s wheels to prevent sliding and shifting.
Outdoors only – dangerous carbon monoxide exhaust
WARNING: Carbon monoxide poisoning hazard
The exhaust from your generator contains carbon monoxide (CO), a poisonous gas that can kill. You cannot smell it, see it, or taste it.
Carbon monoxide exhaust is given off whether you are using gasoline, natural gas, or propane as the fuel source to power the generator.
Follow the directions below for choosing a location to operate your generator in order to avoid carbon monoxide poisoning.
The location you choose to operate the generator must be OUTDOORS and away from all air intakes:
Never run the generator inside any closed or semi-enclosed spaces (even if outdoors), including homes, garages, basements, sheds, or boxes. These spaces can trap poisonous gases, even if you run a fan or open windows.
Place the generator so that the exhaust fumes will not be directed towards people or building air intakes.
Ensure that working, battery-operated or battery back-up carbon monoxide alarms are used in any dwelling/structure that is in close proximity to the running generator.
Note that this generator is NOT designed or approved for use in vehicles or marine applications. Never run the generator inside RVs or other vehicles, on boats, or on pick-up truck beds.
WARNING:
Never attempt to attach ductwork to the muffler system to allow for installation inside an enclosure. This could cause hot air deflection, heat build-up, and increased exhaust back-pressure, resulting in possible exhaust leakage or damage to the generator.
Adequate cooling ventilation
The generator needs adequate, unobstructed flow of air to allow for proper cooling of engine and generator head.
WARNING:
Heat build-up from inadequate ventilation can result in fire, posing a serious risk to nearby persons and structures.
Situate so there is adequate clearance around generator to allow for cooling airflow so that heat does not build up.
19
Installation / Initial Set-Up
Never place the generator immediately adjacent to a building or other structure – allow at least a 7’ clearance.
Do not run the generator in close proximity to other heat-generating equipment, such as another generator. The combined heat that is generated may raise air temperature in the immediate area and there will not be adequate cooling ventilation.
Do not allow debris to accumulate and block airflow.
Do not operate with a tarp, blanket, or cover surrounding the generator.
No wet conditions Choose a location where the generator will NOT be exposed to rain,
snow, or direct sunlight. Exposure to water can cause electric shock.
You may operate the generator under an outdoor, canopy-like structure of heat-resistant material that is open on all sides. Make sure that all parts of canopy are at least 7’ from exhaust, and allow for adequate clearance above generator so that heat does not build up.
Hot exhaust clearance
Away from dust/dirt
Hearing protection
The exhaust gas from your generator is extremely hot and can cause combustible materials to catch on fire.
Make sure your generator’s exhaust system is at least 7 feet from all combustible materials and buildings/structures.
Equip the engine with a spark arrestor if the generator will be used near any ignitable forest, brush, or grassy land. (See the “Specifications” section of this manual to determine if your generator is already equipped.) Make sure you comply with applicable local, state, and federal codes.
Keep a fire extinguisher rated “ABC” nearby. Keep it properly charged and be familiar with its use.
Do not use the generator in extremely dusty or dirty conditions. Excessive dust and dirt can cause premature failure of the machine.
Generators can produce noise levels of up to 95 dB in close proximity, which can be dangerous to human hearing with prolonged exposure.
Hearing protection may be required for persons working within 15-20 feet of the running generator for an extended period of time.
WARNING:
Never attempt to attach ductwork to the muffler system to lower noise levels. This could cause hot air deflection, heat build-up, and increased exhaust back-pressure, resulting in possible exhaust leakage or damage to the generator.
20
Installation / Initial Set-Up
r
d
6. Grounding the generator
Always ensure the generator is properly grounded to prevent electrical shock.
You must always ground the generator by the following method when using the generator as a portable electrical source:
1) Drive a ¾” or 1” copper pipe or rod into the ground close to the generator. The pipe/rod must penetrate moist earth – the depth required will be dictated by local soil conditions. Consult with an electrician.
2) Connect an approved ground clamp to the pipe.
3) Run a 10 gauge wire from the clamp to the generator grounding post located on the rear of the generator head.
4) Do not connect the generator grounding post to a water pipe or a ground used by a radio system.
10 Ga. wire
Coppe
Pipe/Ro
Ground
Grounding Post
If a licensed electrician installs the generator with a connection to your building’s electrical circuit for use as a back-up power system, grounding may alternatively be completed through the building’s grounding system. Ask your electrician. If the generator is not grounded through your building’s electrical system, follow the procedure above.
WARNING:
Operating the generator when it is not properly grounded can result in electrical shock.
21
Installation / Initial Set-Up
7. Battery Installation
Your generator’s engine is equipped with an electric starter which requires the installation of a 12­volt lawn tractor size battery (Group U1). See the “Specifications” section of this manual for more specific battery requirements for this generator model, such as minimum amperage or CCA rating.
The battery is to be supplied by the customer and should be installed in the protective battery box located near the engine. Follow the instructions detailed below for connecting and disconnecting the battery.
WARNING: Battery hazards
Batteries are hazardous because they contain caustic acid, can emit explosive gases, and can cause electric shock. Caution must be exercised when making connections to a battery to avoid shock and contact with the acid, and to prevent any sparking that could lead to an explosion.
ALWAYS follow the general battery safety rules and instructions listed below.
General Battery Safety Rules
Connecting the battery
Disconnecting the battery
ALWAYS use eye protection when handling batteries.
NEVER smoke or work near sparks or other sources of ignition.
NEVER touch both battery terminals at the same time with your hand or
any non-insulated tools.
If battery acid contacts skin or clothing, flush immediately with water and neutralize with baking soda.
Always connect the cables in the following sequence to avoid possible shock:
1. Find the battery cables located inside the battery box.
2. Connect the red cable to the positive(+) terminal of the battery.
3. Then connect the black cable to the negative(-) terminal of the battery.
Always disconnect cables in the following sequence to avoid possible shock.
1. First, disconnect the black cable from the negative(-) terminal of the
battery.
2. Next, disconnect the red cable from the positive(+) terminal of the
battery.
22
Operation
Once you have set up your generator for use, it is time to start your generator. The following are the procedures necessary for safe, successful operation of your generator.
Operation Procedures
1. General Safety Rules for Operation
2. Preparing for Operation
3. Starting the Engine: a) Using LP/NG b) Using Gasoline
4. Checking Generator Output
5. Connecting Electrical Loads (Portable Power Generation)
6. Switching Fuels: a) From LP/NG to Gasoline b) From Gasoline to LP/NG
7. Stopping
8. Storage & Exercise of Generator
Each of these procedures is discussed in detail below:
1. General safety rules for operation
Before starting the generator, review the following general safety rules for operation:
WARNING: Failure to follow safety rules may result in serious injury or death to the operator or
Know proper use/how to stop. Be thoroughly familiar with proper use of the equipment and all
Instruct ope rators. The generator owner must instruct all operators in safe generator set-up and
Intended use . Carefully read about and understand the intended use of this generator. Do not use for
Under the influence. Never operate, or let anyone else operate, the generator while under the influence
Safety equipment / controls. Do not operate the generator unless all safety covers, guards, and barriers
Damaged. Do not operate the generator with damaged, missing, or broken parts.
Modifications. Do not modify the generator in any way. Modifications can create serious safety hazards
Engine spee d . Never attempt to modify the engine speed setting. The engine speed is preset at 3600 RPM
External fuel sources. Never attempt to connect external gasoline/diesel sources in order to increase
bystanders.
generator controls, output receptacles, and connections. Know how to stop the generator quickly if needed (see “Operation, Step 7 - Stopping the Engine”).
operation. Only trained adults should set up and operate the generator – Do not let children operate.
other purposes, as unforeseen hazards or equipment damage may result.
of alcohol, drugs, or medication.
are in place and in good working order, and all controls are properly adjusted for safe operation.
and will also void the warranty.
for safe and optimal performance of the generator. If speed needs adjusting, it must be done by factory­authorized personnel.
engine run time. Larger tank at pressure or higher elevation will cause gasoline to leak from carburetor during operation. Fire or explosion could result.
23
Operation (cont’d)
Malfunction during operation. Immediately turn off the generator if any of the following conditions
arise during operation:
o Excessive change in engine speed, slow or fast o Overheating in load connecting devices o Sparking or arcs from generator o Loss of electrical output o Receptacle damage o Engine misfire o Excessive vibration o Flame or smoke o Abnormal noise
Adjusting / repairing. Always turn off generator and remove spark plug(s) or spark plug wire(s) before
working on the generator to prevent accidental starting. on the generator head to prevent electrical shock. (See Maintenance & Repair section of this manual for instructions on how to do this.)
Carbon monoxide poisoning. The running engine gives off carbon monoxide, a poisonous gas that can
kill you. You CANNOT smell it, see it, or taste it. Follow all instructions for site selection and positioning the generator, and avoid inhaling the exhaust. If you start to feel sick, dizzy, or weak while using the generator, shut off the engine and get to fresh air RIGHT AWAY. See a doctor. You may have carbon monoxide poisoning.
Other exhaust dangers. This product contains or emits chemicals known to the State of California to
cause cancer, birth defects or other reproductive harm. Avoid inhalation of exhaust.
Wet conditions. Do not operate the generator or handle any electrical equipment while standing in water,
while barefoot, while hands are wet or while in the rain or snow. Electric shock may result.
Ground fault circuit interrupter. Always use a ground fault circuit interrupter (GFCI) protected
extension cord (or outlet, if generator is equipped) in damp or highly electrical conductive areas and on construction jobsites to prevent electrical shock.
Avoid contact. Avoid contact with bare wires, terminals, connections, etc. while the unit is running.
Electric shock accident. If an electric shock accident occurs, immediately shut down the source of
electrical power. If this is not possible, attempt to free the victim from the live conductor. Avoid direct contact with victim. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. Apply first aid and get immediate medical help.
Smoking/sparks. Never smoke near the running generator, and never operate near sources of sparks or
flames.
Hot muffler. Never touch hot muffler, hot exhaust manifold, or engine cooling fins. Exhaust and engine
parts can be very hot and will burn you.
Moving parts. Keep hands, feet, and apparel away from drive belts, fans, and other moving parts. Never
remove any drive belt or fan guard while the unit is operating.
Always discharge the capacitor before working
24
Operation (cont’d)
Static electricity and filling the gasoline tank:
Static electricity can initiate from ungrounded gasoline tanks or containers, from flowing
Static electricity can explosively ignite gasoline vapors that are present during the fueling process, resulting in serious burns to nearby persons. To avoid static electricity while fueling, certain steps must be followed before and during the fueling process in order to minimize and safely dissipate static charge build-up:
Touch a grounded metal object before starting. Always dissipate static charge from your body
before beginning the fueling process by touching a grounded metal object at a safe distance away from fuel sources.
Use a portable container to fill tank. Never fill the generator’s gas tank directly from the fuel pump –
the generator’s tank is not grounded and the high velocity flow of gasoline from a fuel pump can cause static electric build-up. Use an approved portable container to transfer gasoline to the generator’s tank.
Fill container on the ground. Never fill the portable gas container while it is sitting inside a vehicle,
trailer, trunk, or pick-up truck bed. ALWAYS place container on the ground to be filled.
Keep nozzle in contact with container. Keep nozzle in contact with the portable container at all times
while filling. Manually control the flow of gasoline; do NOT use the nozzle’s lock-open device.
Use a portable container made of metal or conductive plastic. It will dissipate charge to ground more
readily.
About static electricity and fueling Many common objects can accumulate and retain a static electric charge. Objects made of non-conductive materials (e.g. plastics) easily accumulate and retain static electric charge, as can objects made of conductive material (e.g. metal, water) if they are not electrically grounded. The static electric charge on an object, such as a human body or plastic fuel tank/container, can reach as high as several thousand volts!
A static electric spark can be generated if the static electric charge stored on an object “jumps” to another, less charged object. Such a spark can ignite invisible gasoline vapors that are present during fueling situations.
Typical sources of static electric hazards during fueling The following objects can accumulate a static electric charge and cause an ignition spark in typical fueling situations:
1) Ungrounded tanks/containers. Any ungrounded fuel tank or container can accumulate a static electric charge as a result of contact with other objects or friction during transportation. This static electricity can discharge as a spark to the grounded gasoline dispenser nozzle, as the nozzle is first brought close to the tank/container at the beginning of the fueling process.
2) Flowing gasoline flowing through a hose or pipe. This charge then transfers to and accumulates in the gas tank or container that is being filled. The total amount of charge accumulation depends on the amount of gas pumped into the container, the speed with which it is pumped, and whether or not the tank/container is grounded. If sufficient static electric charge accumulates in the fuel tank or container during the fueling process, the tank/container may discharge a spark to the grounded gasoline dispenser nozzle.
3) Persons resulting from contact with their car seat or electronics. The static electricity can discharge as a spark between that person’s hand and either the grounded dispenser nozzle or the fuel tank opening.
. A person dispensing the gasoline can carry a static electric charge on their body, typically
gasoline, and from persons carrying a static electric charge
. Most people are not aware that gasoline accumulates static electric charge while
25
Operation (cont’d)
2. Preparing for Operation
Position generator Position generator in accordance with the instructions given in
“Installation & Initial Set-up, Step 5: Select a Suitable Site” of this manual.
Operate outside only, on dry, level ground with adequate clearance and ventilation.
WARNING: Carbon monoxide poisoning hazard
Generators give off carbon monoxide exhaust, a poisonous gas that can kill. You CANNOT smell it, see it, or taste it. ONLY run generator OUTDOORS and away from air intakes. NEVER run generator inside any enclosed or semi-enclosed spaces, including homes, garages, basements, sheds, boxes, pick-up truck beds, RVs, or boats. These spaces can trap poisonous gases, EVEN if you run a fan or open windows.
you are using gasoline, natural gas, or propane to power the generator.
Ground generator Make sure the generator is grounded in accordance with instruction
given in “Installation & Initial Set-up, Step 6: Grounding the Generator” of this manual.
WARNING: Electric shock hazard
Always ensure generator is properly grounded to prevent electrical shock.
Perform scheduled maintenance as needed
Make sure that any regular maintenance has been performed as prescribed in this manual in the “Maintenance & Repair” section.
1. Refer to the engine owner’s manual for engine maintenance instructions.
2. Make sure battery is charged. Charge as needed according to your battery manufacturer’s instructions.
Check/add oil Check the oil level using the dipstick and add oil as needed.
Using a funnel, add oil up to the FULL mark on the dip stick with the recommended oil type for your engine and expected ambient conditions. (See engine Owner’s Manual for oil type and capacity, and more detailed oil check/fill instructions.)
WARNING: Burn hazard
Never open oil port while engine is running. Hot oil can spray over face and body.
Notes: o Low oil shutdown feature prevents the generator from starting without
sufficient oil.
o Engine is shipped without
IMPORTANT: Under long, continuous-run operating conditions, be prepared to:
Check engine oil level every time you refuel the engine if using gasoline, or every 24 operating hours if using NG/LPG.
Change oil after the first 20 operating hours, and at least every 100 operating hours thereafter, or as directed in engine owner’s manual.
Carbon monoxide exhaust is given off whether
oil. You must add oil before first use.
26
Operation (cont’d)
Fill gasoline tank (if using gasoline)
Check the gasoline level in the generator’s tank if you will be operating the generator on gasoline. If needed, fill tank with fresh unleaded gasoline from a portable container, after first reading the warnings and instructions below.
WARNING: Gasoline fire/explosion hazard
Gasoline is highly flammable and explosive. Heat, sparks, and flames can ignite gasoline vapors, which can become widespread during fueling. A flash fire and/or explosion could result and cause serious injury or death. Use extreme care when handling gasoline. Carefully follow all the instructions in this section to avoid the following conditions which could result in gasoline ignition:
gas vapor collection inside enclosures
static electric sparks
sparks from electric wiring, batteries, or running engines
sources of heat (such as a hot engine or exhaust)
open flames, including pilot lights
1) Before starting, review the following general safety precautions for fueling: a) Never pump gasoline directly into the generator’s gas tank at a gas
station – high velocity flow from the pump could result in a static electric build-up in the generator’s tank. Always use a portable container to fill the tank. See warning box about static electric spark
hazards below.
b) Fill gasoline tank OUTDOORS – never indoors. c) Stay away from all sources of heat, sparks, and flames. Do not smoke.
2) Turn generator engine off and allow to cool for at least two minutes before removing gas cap.
Note: A running or still-hot engine is hot enough to ignite fuel.
3) Remove generator gasoline cap.
4) Add gasoline through the fill opening:
- Use only a UL-approved portable gasoline container
to transfer the gasoline to the generator’s tank. Follow the safety warning and instructions below for avoiding static electric sparking.
- Do NOT overfill the gasoline tank. Allow at least 1/2” of empty space below the fill neck to allow for fuel expansion.
WARNING: Static electric spark hazard
A static electric spark can explosively ignite gasoline vapor, resulting in a flash fire that could cause serious injury or death.
To avoid static electric sparking while filling the gasoline tank,
the following steps must be followed to minimize and safely dissipate static electric charge build-up before and during the fueling process:
27
Start LPG/NG supply (if using)
Operation (cont’d)
Always dissipate static charge from your body before beginning
the fueling process by touching a grounded metal object at a safe distance from fuel sources.
Never fill the generator’s gas tank directly from the fuel pump –
the generator’s tank is not grounded and high velocity flow from the pump can cause static electricity build-up. Use an approved portable container to transfer gas to the generator’s tank.
Never fill the portable gas container while it is sitting inside a
vehicle, trailer, trunk, or pick-up truck bed. ALWAYS place container on the ground to be filled.
Keep nozzle in contact with portable container while filling.
Manually control the flow of gasoline; do NOT use nozzle’s lock­open device.
A portable container made of metal or conductive plastic is
preferred because it dissipates charge to ground more readily.
5) Clean up gasoline spills /splashes immediately.
If possible, move the generator away from spilled gasoline on the
ground.
Wipe up spilled gasoline, and wait 5 minutes for excess gasoline to
evaporate before starting engine.
Gasoline soaked rags are flammable and should be disposed of
properly.
If gasoline is spilled on your skin or clothes, change clothes and
wash skin immediately.
6) Replace gasoline cap securely before starting engine.
7) Store extra gasoline in a cool, dry place in an UL-approved, tightly sealed container.
IMPORTANT:
For continuous operation, be prepared to check and refuel the engine on a regular basis. A tank of gasoline should last about 4 hours under 100% load, and about 8 hours under 50% load. Propane (LPG):
1) Make sure the fuel hose is securely connected to the propane tank
regulator on one end, and the ¾” NPT gas inlet on the generator base on the other end.
2) Open the propane tank main valve.
3) Check ¾” NPT gas inlet connection for leaks each time you connect. Use
the leak test method described below.
Natural Gas:
1) Make sure the gas line is securely connected to the ¾” inlet on the
generator base.
2) Open line valve, if gas line is so equipped.
3) Check ¾” NPT gas inlet connection for leaks each time you connect.
Use the leak test method described below.
28
Operation (cont’d)
Inspect Fuel System / Check for Leaks
Personal Protection
Inspect fuel system & check for leaks BEFORE starting generator. Do not start generator until all needed repairs have been completed.
WARNING: Fuel leak hazard
Gasoline, LP gas (propane) and NG (natural gas) are highly explosive and fuel leaks can result in fire or explosions. You can be burned and seriously injured if the fuel system is not properly hooked up or there is a fuel leak when you start the engine.
1) Inspect the entire fuel system. Look for: Signs of leaks or deterioration,
chafed or spongy fuel hose, loose connections, loose or missing fuel hose clamps, a damaged gasoline tank, or a defective gasoline shut-off valve.
2) If you are using LPG or NG, check for leaks after opening supply valve:
a) Leak test method. Test for leaks on a regular basis by applying a
soap and water solution over pipes, hoses, and connections. Soap bubbles will form if there is a leak. Use this method to test after each reconnection to NG/LPG supply (for example, after moving the generator), and on a regular basis thereafter. This method will help you detect small leaks.
b) Also beware of gas odor. Both LP and NG have an odorant added
(rotten egg/sulfur smell) that will aid in the detection of more dangerous quantities of leaking gas. Note:
Natural gas. Natural gas is lighter than air and tends to collect in high areas.
LP gas (propane). LP gas is heavier than air and tends to settle in low areas. Smell next to floor for gas.
If you smell gas, DO NOT start engine! DO NOT light a match. DO NOT flip on an electrical switch. If possible, shut off LPG or NG supply. Exit area immediately and call gas supplier or fire department.
1) Hearing can be damaged from prolonged, close-range exposure to the
type of noise produced by this generator. The use of ear plugs or other hearing protection device is recommended for persons working within 15-20 feet of the running generator for an extended period of time.
2) Loose or dangling apparel can become entangled in moving parts. Metal
jewelry can conduct electricity. Never wear jewelry or loose-fitting clothing when starting or operating the generator.
29
Operation (cont’d)
A
t
3. Starting the Engine
After you have completed the pre-start checklist procedures, you are ready to start the engine.
The following directions detail how to start the engine with either LP/NG or Gasoline as the fuel source:
Using LP/NG To start engine using LP or Natural Gas:
WARNING:
DO NOT start engine if you smell gas. Exit area immediately and call gas supplier or fire department. If possible, shut off gas supply.
1) Disconnect all loads to the generator.
2) Flip fuel selector switch to the LP/NG position.
3) Start the engine:
a) Using electric start -
Turn the engine key switch to the START position and hold it there until the engine starts. When the engine starts, release the key, allowing it to return to the ON position.
b) Using recoil start
– Turn the engine key switch to the ON position. Pull the starter grip lightly until you feel resistance, then pull the starter cord out briskly and rapidly. Allow starter cord to return slowly.
Note: You must have the battery hooked up for recoil starting when
using LP/NG. The LP/NG fuel system requires a battery to function.
4) It may be necessary to momentarily depress the primer button while starting the engine, especially for cold starts.
NOTE: If you have trouble starting the engine with LP/NG, you may
need to adjust the load block:
a. Loosen the lock nut, then turn the adjustment screw clockwise until
resistance is felt. At this point the load block is completely shut-off.
djustmen
Screw
Lock Nut
b. While LP or NG is being supplied to the generator, turn the ignition
key to the start position and slowly turn the adjustment screw counterclockwise until the engine starts. (Depress the primer button when cold starting the engine.)
c. Once the engine is running, turn the adjustment screw very slowly to
smooth out engine performance.
d. Once the proper setting is achieved turn the brass lock nut to secure
the adjustment screw.
30
Operation (cont’d)
5) Under long, continuous-run operating conditions, be prepared to:
a) Check engine oil level every 24 operating hours,
b) Change oil after the first 20 operating hours, and at least every 100
Using Gasoline To start engine using gasoline:
1) Disconnect all loads to the generator.
2) Flip the fuel selector switch to the GASOLINE position.
3) Turn the gasoline line valve to the ON position.
4) For cold engine, move choke lever to full choke position. To restart a
5) Start the engine:
6) When engine starts, move choke lever to RUN position.
7) Under long, continuous-run operating conditions, be prepared to:
operating hours thereafter, as directed in the engine owner’s manual.
WARNING:
Never open oil port while engine is running. Hot oil can spray over face and body.
warm engine, move choke lever to half choke or to RUN position.
a) Using electric start –
i) Turn the engine key switch to the START position and hold it there
until the engine starts.
: If the engine fails to start after 5 seconds, release key and
NOTE
wait 10 seconds before attempting to start again. Cranking the electric starter for more than 5 seconds continuously can overheat and damage the starter motor.
ii) Release the key when the engine starts.
b) Using recoil start
– i) Turn the engine key switch to the ON position. ii) Pull the starter grip lightly until you feel resistance, then pull the starter
cord out briskly and rapidly.
iii) Allow starter cord to return slowly.
a) Check and refuel the engine on a regular basis. A tank of gas should
last about 4 hours under 100% load, and about 8 hours under 50% load. See engine owner’s manual for more detail.
WARNING:
A running engine is hot enough to ignite fuel. Never add fuel or remove gas cap if engine is running or still hot. Let cool at least 2 minutes.
b) Check engine oil level each time you refuel. c) Change oil after the first 20 operating hours, and at least every 100
operating hours thereafter, as directed in the engine owner’s manual.
WARNING:
Never open oil port while engine is running. Hot oil can spray over face and body.
31
Operation (cont’d)
4. Checking Generator Output
Although the speed of the engine was carefully adjusted at the factory so that the generator produces the proper voltage and frequency, output voltage should be checked periodically to ensure the generator is working properly before connecting loads to the generator.
Output voltage should be checked with a portable voltage meter:
1. Start engine and allow to warm up for five minutes. Do not connect any loads.
2. Use voltage meter to check output voltage at the generator’s outlets/receptacles.
3. Measured voltage should be within the following ranges:
4. If measured voltage is not within the specified range, have generator adjusted by factory authorized personnel. Do not attempt to adjust the engine speed yourself.
WARNING:
The generator must be run at the correct speed in order to produce the proper electrical voltage and frequency. Failure to do so could result in damage to equipment powered by the generator and possible injury to the individual.
a. 120V +/- 10% at 120V receptacles. b. 240V +/- 10% at 240V receptacles.
NOTE: Slight variation in voltage/speed with changing electrical loads
All engines have a tendency to slow down when a load is applied. When electrical loads are connected to the generator, the engine is more heavily loaded and as a result the speed drops slightly.
This slight decrease in speed, together with the voltage drop within the generator itself, results in a slightly lower voltage when the generator is loaded to its full capacity than when it is running with no load. Additionally, there may be small brief surges and drops in voltage as motors connected to the generator cycle on or off.
The slight variation has no appreciable effect in the operation of motors, lights, and most appliances.
32
Operation (cont’d)
5. Connecting Loads
You will want to be careful when connecting loads so as not to overload the generator, especially if you are powering devices with motors that require a higher starting power load.
Instructions are provided below for connecting loads when you are using the generator:
o As a portable power source o Connected to a building as a back-up power source
WARNING:
Do not overload generator. Make sure that combined starting and running loads do not exceed rated capacity of generator. Overloading the generator can cause damage to the generator and attached electrical devices, and may result in fire.
Using as a Portable Power Source
Using as a Back-up Power Source for a Building
Connect electrical loads one at a time according to the following instructions:
1. Allow engine to reach operating speed by allowing it to warm up for approximately 5 minutes before connecting electrical devices.
2. After engine is warmed up, begin by connecting the items that require the highest wattage first. The recommended sequence is as follows:
a. Connect items with motors such as refrigerators, freezers, air
conditioners, or small hand tools, one at a time. Let each motor
stabilize before connecting the next device. b. Connect any lights you are planning on powering. c. Connect voltage sensitive equipment such as electronics via surge
protectors. Plug devices such as TV’s, computers, and microwaves
into a UL listed voltage surge protector, then plug the surge
protector into the generator.
Each transfer switch installation will be unique. Proper instructions for how to safely bring the generator online with the
building’s electrical system should be provided by the installing electrician, who should also provide personal instruction to the owner/operator.
Failure to follow the proper procedure as provided by the electrician could expose persons to the hazards noted above.
33
Operation (cont’d)
6. Switching Fuels (during operation)
You can switch fuel sources (from gasoline to LP/NG, or from LP/NG to gasoline) while the generator is running. Follow the instructions below:
Switching from LP/NG to Gasoline
1. Disconnect all loads to the generator. Leave the engine running.
2. Turn the gasoline line shut-off valve to ON position.
3. Flip the fuel selector switch to the GASOLINE position.
Switching from Gasoline to LP/NG
1. Disconnect all loads to the generator. Leave the engine running.
2. Make sure LP or NG fuel is properly connected to ¾” NPT supply inlet and is being supplied.
WARNING:
If you smell gas, turn off engine and shut off gas supply immediately. Exit area and call gas supplier or fire department.
3. Flip the fuel selector switch to the NONE position. The fuel conversion should take 1-2 seconds.
4. Wait for the engine to begin sputtering. This indicates the engine is being starved of gasoline.
5. Flip the fuel selector switch to the LP/NG position.
6. Turn the gasoline line shut shut-off valve to OFF position.
Stop the engine using the following steps:
1. Disconnect all loads to the generator.
2. Turn engine key switch to OFF position.
7. Stopping
3. Turn gasoline line shut-off valve to OFF position.
4. The fuel lock-off solenoid automatically stops the flow of LP or NG to the engine.
5. Remove key from starter to prevent accidental starting of engine.
34
Operation (cont’d)
8. Storage & Exercise
When you are finished using the generator, you must:
o Disconnect all loads o Shut off fuel supply o Store the generator properly o Plan on exercising the engine regularly unless the generator is prepared for long-term
storage.
Detailed instructions are provided below.
Disconnect loads & turn off fuel supply
Cool engine before storing
Choose a storage location
Prevent accidental starting
Exercise generator every 4 weeks
When you are finished using the generator, disconnect all loads and turn off all sources of fuel supply:
1. Make sure all devices that were connected to the generator’s outlets are disconnected.
2. Check to be sure gasoline line shut-off valve is in OFF position.
3. If using propane, shut off propane tank valve.
4. If applicable, shut off natural gas line valve.
Let engine cool for at least five minutes before storing. A hot engine can be a fire hazard.
Store the generator in a location that is:
o Clean and dry o Away from sources of heat, open flames, sparks, or pilot lights, even
if the generator’s fuel tank is empty. Residual fuel in the tank could ignite.
o Away from extreme high or low temperatures.
Note: Do not store with battery charger always connected. Batteries that are over-charged can boil themselves dry and produce excessive amounts of hydrogen, an explosive gas.
Remove key from starter (for electric start engines) and secure key in a safe location, or remove spark plug(s) in order to ensure the generator
cannot be started accidentally in a storage location or by untrained persons.
The generator should be exercised regularly.
At least every four weeks, start the engine and let it run for 10 to 15 minutes with a small load plugged in, such as a lamp or fan.
Monthly exercising of the generator will:
o Dry out any moisture that has accumulated in the windings. If left,
this moisture can cause corrosion in the winding.
o Ensure that the unit is operating properly should it be needed in an
emergency.
35
Operation (cont’d)
Perform regular maintenance
Prepare engine for long term storage if needed
Perform periodic maintenance as directed in this manual to keep the
generator in safe working condition.
If you will not be able to exercise the generator regularly, you must prepare the engine for long term storage to prevent gum deposits from
forming and causing malfunction of the engine. Prepare engine for long term storage by:
o Removing all gasoline from the tank and carburetor
OR
o Adding fuel stabilizer to the gasoline (following manufacturer’s
instructions)
Fuel stabilizer steps:
1. Ensure gasoline tank is full.
2. Add fuel stabilizer to fuel tank.
3. Run engine at least 10 minutes after adding stabilizer to allow it to enter the fuel system.
4. Shut off engine
5. Disconnect spark plug wire and remove spark plug
6. Add one teaspoon oil through spark plug hole
7. Place rag over spark plug hole and turn starter (or pull the recoil) a few times to lubricate the combustion chamber.
8. Replace spark plug, but do not reconnect the spark plug wire.
36
Maintenance & Repair
Inspect and maintain your generator as specified below in order to keep it in safe and optimal working order. Follow all safety rules and recommended maintenance steps.
ALWAYS shut off the engine, disconnect the spark plug(s) and discharge the capacitor before cleaning, adjusting, or servicing the generator. Make sure all guards and shields are replaced before using.
Note: The generator head is brushless and maintenance free. The bearing is a heavy-duty sealed ball bearing which requires no maintenance or lubrication.
Maintenance & Repair
Follow safety rules Read and follow these safety rules whenever you will be servicing the
generator:
Turn off generator. Always turn off generator and remove spark plug(s)
or spark plug wire(s) before working on the engine or generator to prevent accidental starting.
Discharge capacitor. When the generator is shut down, the capacitor may
maintain a charge. Always discharge the capacitor before working on the generator head to prevent electrical shock. Discharge using a screwdriver with an insulated handle. While wearing safety glasses, touch opposite terminals of the capacitor together with the tip of the screwdriver. If there is stored charge in the capacitor, a spark will be generated thereby discharging the capacitor.
Replace guards. Make sure all guards and shields are replaced after
servicing the generator.
Repair. Major service, including the installation or replacement of parts,
should be performed only by a qualified electrical service technician. Obtain factory approved parts from NorthStar Product Support at 1-800­270-0810.
Replacement parts. If a part needs replacement, only use factory
approved repair parts. Replacement parts that do not meet specifications may result in a safety hazard or poor operation of the generator and will void the warranty.
Perform engine maintenance
Check receptacles Check receptacles before each use to make sure they are not cracked or
Perform engine maintenance as specified in the engine owner’s manual.
Engine maintenance items include:
1. Changing oil and oil filter
2. Air filter check/replacement
3. Spark plug cleaning and replacement
4. Fuel filter check/replacement
5. Fuel tank cleaning.
broken.
If a receptacle is cracked or otherwise damaged, do not use until replaced with an authorized factory part. Using cracked or damaged receptacles can be both dangerous to the operator and destructive to the equipment.
WARNING
37
Maintenance & Repair (cont’d)
Inspect fuel system / check for leaks
Inspect the fuel system and check for leaks on a regular basis.
1) Inspect the entire fuel system. Look for: signs of leaks or deterioration, chafed or spongy fuel hose, loose connections, loose or missing fuel hose clamps, damaged gasoline tank, or defective gasoline shut-off valve.
2) If you are using LPG or NG, test for leaks. After opening LPG/NG supply valve, apply a soap and water solution over pipes, hoses, and connections. Soap bubbles will form if there is a leak. Use this method to test after each reconnection to NG/LPG supply (such as after transporting generator), and on a regular basis thereafter.
Check GFCI (if equipped)
Once a month, test the Ground Fault Circuit Interrupter (GFCI) to protect against electrical shock due to failure of the GFCI. (Only for
those models equipped with GFCI – See the “Specifications” section.) To test the GFCI:
1. Depress the TEST button. The RESET button should extend from the receptacle. If the RESET button does not extend, contact NorthStar for replacement parts.
2. Restore power to the GFCI by firmly pressing the RESET button back into the receptacle until an audible click is heard.
Clean & inspect spark arrestor (if equipped)
Clean and inspect the spark arrestor muffler. (Only for those models
equipped with a spark arrestor – See the “Specifications” section.)
If the engine is equipped with a spark arrester muffler, clean and inspect it regularly (follow manufacturer’s service instructions). Replace if damaged.
Keep generator clean
Keep generator clean.
If dust or debris accumulates on the generator, clean the generator with a damp cloth or soft bristle brush. Do not allow air intakes to become blocked.
Note: Do not spray generator with a garden hose or pressure washer. Water may enter the generator and cause damage to the rotor, stator, or internal windings.
Recharge and maintain battery (if electric start)
Inspect, recharge, and maintain your battery according to your battery manufacturer’s instructions. (Only for those models equipped with electric
start.) Do not store with battery charger always connected. Batteries that are over-
charged can boil themselves dry and produce excessive amounts of hydrogen, an explosive gas.
IMPORTANT
:
If a part needs replacement, only use parts that meet the manufacturer’s specifications. Replace­ment parts that do not meet specifications may result in a safety hazard or poor operation of the generator.
Contact NorthStar Product Support at 1-800-270-0810
for any questions, problems, or parts orders
38
Troubleshooting
TROUBLESHOOTING
Problem Possible Causes Possible Remedies
Engine will not start.
Voltage too low. a) Engine speed too slow.
Circuit breaker trips. a) Defective load connected to generator.
Voltage too high. a) Engine speed too high. a) Bring generator to a qualified technician for Generator overheating. a) Generator is overloaded.
No output voltage. a) Defective load connected to generator.
Engine lacks power or sputters.
Engine shuts down during operation. Engine will not start on gasoline.
Engine will not start on LP or Natural Gas.
Engine sputters when switching from gasoline to LP or Natural Gas.
a) Low oil level. b) Fouled spark plug. c) Out of fuel. d) Stop switch in OFF position. e) Battery disconnected or dead. f) Fuel selector switch is OFF position.
b) Generator is overloaded.
b) Defective receptacle. c) Generator overloaded.
b) Insufficient ventilation.
b) Broken or loose wire. c) Defective receptacle.
d) Defective stator. e) Defective rotor. f) Defective capacitor. a) Generator is overloaded. b) Dirty air filter.
c) LP/NG hose is connected to the wrong carburetor inlet.
d) Fouled spark plug. a) Out of fuel. b) Low oil level. a) Engine out of fuel. b) Engine cold. c) Vacuum hose is loose.
a)Load Block needs adjustment b) Battery is low on charge causing engine to crank at a lower rpm. c) Inlet fuel pressure is incorrect.
d) Engine choke lever is in the choke position. e) Fuel lockoff valve upstream of the
generator set is turned off. a) This is normal operation. a) Run the unit with the fuel switch in the NONE
a) Fill crankcase to proper oil level. b) Clean or replace spark plug. c) Fill fuel tank. d) Place switch in ON position. e) Charge or replace battery. f) Place switch in desired location (Gasoline or LP/NG). a) Bring generator to a qualified technician for adjustment. b) Reduce the load. (See Power Load Planning & Mgt. section of this manual.) a) Disconnect load. b) Replace receptacle. c) Reduce the load. (See Power Load Planning & Mgt. section of this manual.)
adjustment. a) Reduce the load. (See Power Load Planning & Mgt. section of this manual.) b) Make sure there is at least 3 feet of clearance on all sides of generator. a) Disconnect load. b) Bring generator to a qualified technician for repair. c) Replace receptacle. d) Bring generator to a qualified technician for repair. e) Bring generator to a qualified technician for repair. f) Bring generator to a qualified technician for repair. a) Reduce the load. (See Power Load Planning & Mgt. section of this manual.) b) Clean or replace air filter. c) For LP, the hose should be on the left inlet. For NG, the hose should be on the right inlet. d) Clean or replace spark plug.
a) Fill fuel tank. b) Fill crankcase to proper oil level. a) Refuel engine. b) Choke engine. c) Reattach vacuum hose. Item 29 on Exploded View. a) See page 8 of this manual. b) Recharge battery.
c) Inlet fuel pressure should be within 7”-11” water column, or 4-6 oz. d) Move the choke lever to the open position. Never choke the engine when operating on LP or NG fuel. e) Open valve.
position for several seconds until the engine begins to hunt. Then move the switch to the LP/NG position.
39
Summary of Important Safety Information for Operation
This section provides a summary of the various safety procedures and measures that have been
presented throughout the manual. Keep this summary handy and refer to it to refresh your
memory about how to safely use your generator.
Carefully read and make sure you understand the following safety information before using the generator. Improper use or maintenance of the generator can result in
death
from carbon monoxide poisoning, electric shock, fire/explosion, or burns.
Read manual. Read this Owner’s Manual and the engine Owner’s Manual completely before attempting to
set-up and use the generator. Serious injury or death can result if safety instructions are not followed.
Instruct operators. The generator owner must instruct all operators in safe generator set-up and operation.
Do not allow anyone to operate the generator who has not read the Owner’s Manual and been instructed on its safe use.
Adults only. Only trained adults should set up and operate the generator. Do not let children operate.
Under the influence. Never operate, or let anyone else operate, the generator while under the influence of
alcohol, drugs, or medication.
Intended use. Carefully read about and understand the intended use of this generator. Do not use for other
purposes, as unforeseen hazards or equipment damage may result.
Prohibition Against Modifications
Never modify or alter the generator in any way. Modifications can create serious safety hazards and will also void the warranty.
Engine speed. Never attempt to modify the engine speed setting. The engine speed is preset at 3600 RPM for
safe and optimal performance of the generator. If speed needs adjusting, it must be done by factory­authorized personnel.
Fuel/exhaust system. Never modify the exhaust system, fuel tanks, or fuel lines. Carbon monoxide
poisoning, fire, or explosion could result.
Guards. Do not operate generator unless all guards and cover shields, which prevent access to moving parts and pinch points, are in place. Failure to guard the power transmission mechanisms may result in serious injury or death.
WARNING
serious injury or
General
Safety – Installation & Set-up
Battery Safety
Batteries are hazardous because they contain caustic acid, can emit explosive gases, and can cause electric shock.
Caution must be exercised when making connections to a battery to avoid shock and contact with the acid, and to prevent any sparking that could lead to an explosion. Follow safety rules carefully when connecting battery to generator:
Eye/skin protection. Always wear eye protection an d protective clothing when connecting or disconnecting battery.
Sparks/Smoking. Never smoke or work near sparks or other sources of ignition.
Electric shock. Never touch both battery terminals at the same time with your hand or any non-insulated
tools.
Connection/disconnection sequence. ALWAYS connect and disconnect cables to the correct battery terminals in the proper sequence:
o When CONNECTING the battery, connect the RED cable to the POSITIVE terminal FIRST. o When DISCONNECTING the battery, disconnect the BLACK cable from the NEGATIVE terminal FIRST
Acid/skin contact. If battery acid contacts skin or clothing, flush immediately with water and neutralize with baking soda.
40
Summary of Important Safety Information for Operation (cont’d)
Installation / Initial Set-up Safety
Dry, level surface. Situate generator on a dry, firm, level surface. Ensure generator sits level and will not slide or shift during operation. Block wheels if applicable.
Operate OUTSIDE only – dangerous carbon monoxide exhaust! Generators give off carbon monoxide exhaust, a poisonous gas that can kill. You CANNOT smell it, see it, or taste it. ONLY run generator OUTDOORS and away from building air intakes. NEVER run generator inside homes, garages, sheds, or other semi-enclosed spaces. These spaces can trap poisonous gases, EVEN if you run a fan or open windows. Carbon monoxide is given off whether you are using gasoline, natural gas, or propane to powe r the ge nerator.
No vehicle/marine use. This generator is NOT designed or approved for use in vehicles or marine applications. Never run the generator inside RVs or other vehicles, on boats, or on pick-up truck beds.
Cooling ventilation. The generator needs adequate, unobstructed flow of air to allow for proper cooling of engine and generator head. Situate so there is adequate clearance around generator to allow for cooling airflow. Do not allow debris to accumulate and block airflow.
Grounding. Always ensure generator is properly grounded to prevent electrical shock. This generator is equipped with a grounding post. Always complete the grounding path from the generator to a copper pipe/rod driven into moist earth to a sufficient depth. Check with an electrician for local grounding requirements. If a licensed electrician installs the generator with a connection to your building’s electrical circuit for use as a standby power system, grounding will be complete through the building’s grounding system.
Isolate connection to building’s electrical circuit. Never plug the generator directly into a wall outlet. ANY connection to a building’s electrical system MUST ISOLATE THE GENERATOR FROM UTILITY POWER via an UL-approved transfer switch installed by a licensed electrician in compliance with all applicable local building and electrical codes. If the generator is not isolated from the utility power system by such means, generator output will back feed into the utility power grid. This may result in injury or death to utility power workers or others who contact the lines during a power outage. It may also cause the generator to explode or cause fires when utility power is restored.
Natural gas hook-up. Always consult with your gas utility company to determine installation requirements for a natural gas hook-up. In order to safely operate your generator, you may need either a higher or lower pressure than the standard delivery pressure provided to your building. You may need a pressure reducing regulator, or you may need elevated delivery pressure which would require ch anges to your natural gas service. All natural gas generator hook-ups should be completed by trained personnel from your natural gas utility company and inspected as required by you local building code.
LPG hook-up. A qualified propane gas technician must set up the valve and hose connection between the propane tank and generator in accordance with all local regulations and electric code. Check with your local propane gas supplier.
Wet conditions. Water conducts electricity. Do not operate generator where it is wet. Operate on a dry surface under an open, canopy-like structure.
CO alarms. Ensure that working, battery-operated or battery back-up carbon monoxide alarms are used in any dwelling/structure that is in close proximity to the running generator.
Hot exhaust - fires. Exhaust from engine can be extremely hot and cause fire. Position muffler at least 7’ from combustible objects during operation.
Spark arrestor. Equip engine with a spark arrestor if generator will be used near any ignitable forest, brush, or grassy land. See the “Specifications” section of this manual to determine if your generator is already equipped. Make sure you comply with applicable local, state and federal codes.
Fire extinguisher. Keep a fire extinguisher rated “ABC” by the National Fire Protection Associatio n nearby. Keep it properly charged and be familiar with its use.
Safety – Before Use
Know how to operate
Review safety rules. Before each use of this generator, review the “Rules for Safe Operation.” Failure to follow these rules may result in serious injury or death.
Know how to operate. Be thoroughly familiar with all controls and with the proper use of the equipment. Know how to stop the generator quickly if needed.
41
Summary of Important Safety Information for Operation (cont’d)
Personal protective equipment
Hearing protection. The use of ear plugs or other hearing protection device is recommended for those in close proximity to the generator while it is operating.
Loose / dangling. Loose or dangling apparel can become entangled in moving parts. Metal jewelry can conduct electricity. Never wear jewelry or loose-fitting clothing when operating the generator.
Gasoline Safety
Gasoline is highly flammable and explosive. You can be burned or seriously injured when handling fuel. Use extreme care when handling:
Fuel outdoors. Fill fuel tank outdoors – never indoors. Gasoline vapors can ignite if they collect inside an enclosure. Explosion can result.
Use approved container. Never pump fuel directly into engine at gas station. Static charge can build and ignite fuel. Use an UL approved fuel container to transfer gas to the engine.
Running / hot engine. A running engine is hot enough to ignite fuel. Never add fuel or remove gas cap if engine is running or still hot. Stop the engine and allow to cool at least two minutes before adding fuel.
Heat / flames / sparks. Stay away from sources of heat, flame, or sparks while adding fuel.
Don’t overfill. DO NOT overfill the gas tank. Allow at least 1/2” of empty space below the fill neck to
allow for fuel expansion.
Replace cap. Replace gas cap securely before starting engine.
Spills. Clean up fuel spills immediately. Move generator away from spilled fuel on the ground. Wipe fuel
off engine and wait 5 minutes for excess fuel to evaporate before starting engine. Gas soaked rags should be disposed of properly.
On skin / clothes. If gasoline is spilled on your skin or clothes, change clothes and wash skin immediately.
Inspect fuel system. Check fuel system on a regular basis. Look for signs of leaks, deterioration, chafed or
spongy fuel hose, loose or missing fuel hose clamps, damaged fuel tank, or a defective fuel shut-off valve. Do not start generator until needed repairs have been completed.
Gasoline storage. Store gasoline in a cool, dry place in an UL-approved, tightly sealed container.
Propane & Natural Gas Safety
LP gas (propane) and natural gas are highly flammable and explosive. Even the slightest spark can ignite these fuels. You can be burned and seriously injured if the fuel system is not properly hooked up or there is a fuel leak when you start the engine.
Initial hook-up by qualified personnel. Initial hook-up must be completed by qualified personnel from your natural gas company or propane supplier and inspected per local code.
Inspect regularly. Inspect fuel system regularly for leaks. Do not start generator until leaks are repaired.
Smell for gas before starting the generator:
Natural gas
. Natural gas is lighter than air and tends to collect in high areas. After opening NG line
supply, smell for gas BEFORE starting engine.
LP gas (propane)
. LP gas is heavier than air and tends to settle in low areas. After opening propane
tank valve, smell next to floor for gas BEFORE starting engine. If you do smell gas, DO NOT start engine. DO NOT light a match. DO NOT flip on an electrical switch. Exit area immediately and call gas supplier or fire department. If possible shut off gas supply.
Safety – During Use
Safety equipment / controls. Always operate the generator with all safety covers, guards, and barriers in
place and in good working order, and all controls properly adjusted for safe operation.
Know how to stop. Be thoroughly familiar with proper use of the equipment and all generator controls,
output receptacles, and connections. Know how to stop the generator quickly if needed.
Damaged. Do not operate the generator with damaged, missing, or broken parts.
Check for gas leak before starting. After opening gasoline valve or LP/NG line supply, sm ell for gas before
starting engine. If you do smell gas, DO NOT start engine. DO NOT light a match. DO NOT flip on an electrical switch. Exit area immediately and call gas supplier or fire department. If possible shut off the LP/NG supply.
42
Summary of Important Safety Information for Operation (cont’d)
Carbon monoxide exhaust. The running engin e gives off carbon monoxide, a poisonous gas that can kill
you. You CANNOT smell it, see it, or taste it. If you start to feel sick, dizzy, or weak while using the generator, shut off the engine and get to fresh air RIGHT AWAY. See a doctor. You may have carbon monoxide poisoning.
Other exhaust dangers. This product contains or emits chemicals known to the State of California to cause
cancer, birth defects or other reproductive harm. Avoid inhalation of exhaust.
Smoking/sparks. Never smoke near the running generator, and never operate near sources of sparks or
flames.
Check output voltage. Check output voltage to ensure the generator is working properly before connecting
loads to the generator. Failure to do so could result in damage to equipment powered by the generator and possible injury to the individual. Do not adjust output speed of engine to change voltage. If voltage is not within specified range, have generator repaired by fact ory aut h ori zed personnel.
Stabilize before connecting loads. Start generator and let engine stabilize before connecting electrical loads.
Do not overload. Do not overload the generator. Make sure that combined starting and running loads do not
exceed rated capacity of generator or damage will result.
Protect sensitive electronics. Some electronic equipment, such as computers and audio/video equipment,
can be damaged by small fluctuations in the flow of power. Use a surge suppressor for any voltage-sensitive electronic equipment you will be powering with the generator.
Wet conditions. Do not operate the generator or handle any electrical equipment while standing in water,
while barefoot, while hands are wet or while in the rain or snow. Electric shock may result.
Ground fault circuit interrupter. Always use a ground fault circuit interrupter (GFCI) protected extension
cord (or outlet, if generator is equipped) in damp or highly electrical conductive areas and on construction jobsites to prevent electrical shock.
Electrical cords. Use only UL-listed, outdoor-rated, three prong extension cords of the proper size. All
extension and appliance cords must be in good condit ion and not worn, bare, frayed, or otherwise dam aged . Use of inadequate or damaged electric cords can cause electric shock or fire.
Avoid contact. Avoid contact with bare wires, terminals, connections, etc. while the unit is running.
Electric shock accident. If an electric shock accident occurs, immediately shut down the source of electrical
power. If this is not possible, attempt to free the victim from the live conductor. Avoid direct contact with victim. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. Apply first aid and get immediate medical help.
Hot muffler. Never touch hot muffler, hot exhaust manifold, or engine cooling fins. Exhaust and engine parts
can be very hot and will burn you.
Moving parts. Keep hands, feet, and apparel away from drive belts, fans, and other moving parts. Never
remove any drive belt or fan guard while the unit is operating.
Refueling. DO NOT refuel the engine until it has cooled at least two minutes.
Malfunction during operation. Immediately turn off the generator if any of the following conditions arise
during operation:
o Excessive change in engine speed, slow or fast o Overheating in load connecting devices o Sparking or arcs from generator o Loss of electrical output o Receptacle damage o Engine misfire o Excessive vibration o Flame or smoke o Abnormal noise
Adjusting / repairing. Always turn off generator and remove spark plug(s) or spark plug wire(s) befo r e
working on the generator to prevent accidental starting.
43
Summary of Important Safety Information for Operation (cont’d)
Safety – After use
Cool engine before storing. Let engine cool for at least five minutes before storing. A hot engine can be a
fire hazard.
Shut off fuel supply. Make sure gasoline shut-off valve is in the OFF position. Turn off propane tank valve
or shut NG line valve, as applicable.
Prevent accidental starting. When generator is not in use, remove key from starter (key start engines) and
secure in a safe location, or remove spark plug(s) in order to ensure that generator cannot be started in a storage location or by untrained persons.
Storage location. Store the generator in a dry location away from sources of heat, open flames, sparks or
pilot lights – such as water heaters, space heaters, furnaces, clothes dryers, or other gas appliances – EVEN IF the generator’s gas tank is empty. Residual gasoline could ignite.
Exercise regularly. Exercise generator every four weeks to dry out moisture that accumulates in the
windings. If generator cannot be exercised on a regular basis, prepare generator for long term storage.
Periodic maintenance. Perform periodic maintenance as directed in this manual to keep the generator in safe
working condition.
Safety - Inspection/Maintenance
Inspect and maintain your generator on a regular basis and repair as needed to keep it in safe working condition:
Turn off generator. Always turn off generator and remove spark plug(s) or spark plug wire(s) before
working on the engine or generator to prevent accidental starting.
Discharge capacitor. When the generator is shut down, the capacitor may maintain a charge. Always
discharge the capacitor before working on the generator head to prevent electrical shock.
Replace guards / shields. Make sure all guards and shields are replaced after servicing the generator.
Replacement parts. If a part needs replacement, only use parts that meet the manufacturer’s specifications.
Replacement parts that do not meet specifications may result in a safety hazard or poor operation of the generator and will void the warranty.
44
Generator Exploded View Rev- N
45
Generator Exploded View Rev- N
Diag # Part # Description Qty
1 171410 Hose Clamp 5 2 777164 Positive Battery Cable 1 3 38759 Fuel Tank Assembly 1 4 30754 Leather Washer 4 5 779422 Decal 1 6 32833 Roll Cage 1 7 33482 6mm Stud and Coupler Nut 1 8 36298 Straight Hose Nipple 1
9 36297 Load Block 1 10 31770 Engine Adapter 1 11 32811 LP/NG Hose 22” 12 31335 Engine, GX390 Honda 1 13 778530 Generator 1 14 777304 Generator Cover 1 15 36300 Regulator Assembly 1 16 33319 LP/NG Fuel Lockoff 1 17 777338 3/8 X 1/4 Reducer 1 18 777119 1/2” Hose Clamp 2 19 32798 3/4” Pipe 1 20 35946 O-Ring 1 21 36825 Regulator 1 22 33435 Regulator Bracket 1 23 31708 3/8” Split Conduit 7” 24 31772 Vacuum Switch 1 25 32815 Wire Harness 1 26 32809 Elbow 1 27 32810 Vacuum Hose 22” 28 306459 Ground Wire 1 29 777621 Generator Base Bracket 1 30 33321 Fuel Cap 1 31 34172 Isolation Mount 4 32 32844 Lower Bracket 4 33 778483 Generator Base 1 34 82018 5/16-18 X 2 Hex Head Bolt 4 35 777305 Control Box 1 36 33277 Clip Nut, 10-32 4 37 32797 10-32 X .75 Screw 4 38 777108 Negative Battery Cable 1 39 38435 Control Panel Assembly 1 40 779396 Battery Decal 1 41 777352 Battery Box 1 42 31868 Battery (Not Included) 1 43 32848 Upper Bracket 4 44 31850 Wire Harness 1 45 779424 Warning Decal 1 46 33484 Nameplate 1 47 30755 Fuel Filter 1 48 777345 1/4” Fuel Line 15” 49 38184 Engine Cover 1 50 39260 Burn Warning 1 51 32813 1/4” NPT, 1/4” Hose Barb 2 52 777163 Gas Lockoff Bracket 1 53 777147 Gasoline Lockoff 1
46
Wiring Diagram Rev- N
Diag # Part # Description Qty
1 31086 Thermal Circuit Breaker, 30 Amp 2 2 30643 Thermal Circuit Breaker, 20 Amp 2 3 306433 Thermal Circuit Breaker, 15 Amp 1 4 30975 Control Panel Face 1 5 306429 Binding Post 1 6 306438 15 Amp, 120 Volt Receptacle (NEMA 5-15R) 1 7 31736 20 Amp, 120 Volt Receptacle (NEMA 5-20R) 1 8 31824 Switch 1 9 306422 30 Amp, 120/240 Volt Locking Device Receptacle
(NEMA L14-30R) 10 38191 Wire Harness 1 11 31107 Wire Assembly 1 12 306604 Wire Assembly 1 13 38334 Wire Harness 1
B23 31106 Black Terminated Wire 1 B24 31108 Black Terminated Wire 1 B26 31109 Black Terminated Wire 1 B28 306599 Black Terminated Wire 1 B29 30660 Black Terminated Wire 1 B31 306601 Black Terminated Wire 1 G22 31823 Green Terminated Wire 1
W25 30977 White Terminated Wire 1
1
47
Generator Head Exploded View Rev- N
Item # Part # Description Qty
1 779919 Mount Plate (J609B) 1 2 779556 Fan Bolts 2 3 779557 Fan 1 4 779920 Drive End Bracket 1 5 779786 Enclosing Band 1 6 777304 End Cover 1 7 38271 End Cover Plug 1 8 779787 Stator 1
9 779788 Rotor 1 10 307481 Varistor 2 11 779789 Diode 2 12 779790 Securing Stud + Nut 1 13 38276 Bearing 1 14 38278 Non Drive End Bracket 1 15 779791 Capacitor 1 16 779792 Bracket Securing Stud 4
48
Loading...