This publication is the property of Northern Lights, Inc.
OPX300K1 09/09
3
Introduction
This manual describes procedures for operation,
maintenance, inspection and adjustment. It will help the
operator realize peak performance through effective,
economical and safe operation.
• Read this manual carefully BEFORE operating the
generator.
• Study this manual until proper operation becomes
personal habit.
• Operation, inspection, and maintenance should be
carried out carefully. Safety must be given the fi rst
priority.
Safety Rules
• To insure years of trouble-free operation, the
specifi ed maintenance is important and should be
performed.
• Insulation Resistance and Dielectric: When
measuring insulation resistance and dielectric, be
sure to disconnect the AVR and rectifi er.
• Be sure that the regulator is shut of f by switching the
CPR (circuit breaker) on the AVR to the off position
when the unit is run ning at less than rated speed, or
when the unit is to be run but no power generation is
required.
• Before starting your generator, be sure oper ating
conditions are safe.
• Ventilation: When selecting the installation site, be
sure that the area is well ventilated and that ambient
temperature does not exceed 40°C. If the
temperaure exceeds 40°C, de-rate the generator
output as per “data sheet” for operation.
• Be sure to provide generator with cover and
protection when op erating outside.
• Electrical equipment should always be kept clean. Oil, dust, moisture and salt are all harmful
to genera tors.
• Be careful with electricity. Do not touch rotating
parts.
• Ambient Environmental Conditions
a) Gas: Do not use in an environment of corrosive
or fl ammable gas (gasoline, hydrogen sulfi de,
meth ane gas, etc.)
b) Sandy Dust: Do not use equipment in places
with excessive sand and dust.
c) Humidity: Do not use in very humid
environments for long periods of time.
d) Salt/Seawater: Protect your generator from
exposure to salt, water, and water vapor.
PX-300K Series AC generators are based on BS
4999 part 20 and IEC34-5, IP21.
OPX300K1 09/09
4
Model and Serial Numbers
GENERATOR END MODEL NUMBERS
Generator Set Model No.................PXK Generator Model
M and NL753K ............................................PX-308K1
M and NL773L ..............................................PX-309K1
M and NL843JK ...........................................PX-310K1
M and NL843NK ..........................................PX-312K1
• When referencing Northern Lights equip ment by serial
number, it is important to differentiate between the engine,
generator end and generator set serial numbers.
• The engine serial number is either on a metal tag or stamped
directly into the engine block.
• The generator END serial number is on a metal tag attached
to the generator end.
• The generator SET serial number is on a separate metal tag
attached to the generator end. It may be a fi ve by one inch tag
installed directly below the gen erator end tag. Or, it may look
like the illustrations below. Please use the generator SET number
in cor respondence or when ordering parts.
Figure 1: Generator Set Serial Number Plate
OPX300K1 09/09
5
Mechanical Construction
STATOR
The stator frame is fabricated from rolled steel. The
round construction provides rigidity and strength to
resist excessive mechanical shocks. The stator core is
made of high quality silicon steel plates coated with
insulating fi lm for prevention of eddy currents. The
core is positioned along the internal surface of the
frame. The exciter fi eld core is made of special steel
plates capable of retaining a high degree of residual
magnetism.
BEARINGS
The long-life ball bearings are sealed to prevent grease
from escaping and to keep dirt out.
ROTOR
The rotor shaft is made of high quality carbon steel,
and is designed and manufactured to be mechanically
durable. The rotor is a salient revolving fi eld type
with the main fi eld core made from special steel plates
having superior magnetic characteristics. The fi eld core
elements, exciter rotor, rotary rectifi er and cooling fan
are integral parts of the same shaft.
COUPLING BOLT SPECIFICATIONS
The Coupling Bolt Torque for all PX-300K series models
is 32 lbs.ft.
COUPLING WITH PRIME MOVER
PX-300K series single bearing generators make centering
and direct coupling easy. Shim the generator legs as needed
for proper leveling. Coupling bolt size and torque will
vary according to the engine manufacturer. The bolt torque
for attaching the coupling plates to the generator rotor are
shown in COUPLING BOLT SPECIFICATIONS, above.
GROUNDING
The generator frame should be electrically grounded to the
base of the generator set. The neutral is not grounded to
the frame unless specifi ed.
VENTILATION
Cooling is provided by the cooling fan of the rotor
through suction ports and exhausted through outlet
ports. Every machine conforms to the cooling code
ICO1 of BS.
Initial Inspection and Coupling
INITIAL INSPECTION
If the generator is stored for long periods of time, store
in a clean, dry, ventilated area. After extensive storage
time, check the resistance of the coil insulation in
accordance with this manual (see MAINTENANCE,
page 9) before operation. Be sure there are no abnormal
sounds or any overheating during operation. It is
recommended that standby generators utilize a space
heater (op tional) in order to keep the coil insulation in
optimum working condition.
OPX300K1 09/09
6
Performance and Function
EXCITATION SYSTEM
The excitation system of the PX-300K Series generator uses an Automatic Voltage Regulator (AVR) which
uses a portion of the output power to supply controlled
DC power to the exciter fi eld (EX) as show in Figure 2.
When DC power is supplied to the exciter fi eld, output
from the exciter armature is rectifi ed by a 3-phase bridge
rotary rectifi er (Si) and supplied to the main fi eld coils.
See Figure 2.
AVR: Automatic Voltage
Regulator
EX: Exciter
Si: Rotating Rectifi er
Figure 3: For 50 Hz
Figure 2: PX-300K Block Diagram
AUTOMATIC VOLTAGE REGULATOR (AVR)
The PX-300K Series generators use a DST-51 AVR.
This is a compact voltage regulator for generators with
an output up to 50kW. The DST-51 can be used in 120V
single phase applications and is installed inside the generator junction box.
The DST-51 obtains sensing input from the main stator
coils and compares the rectifi ed value of the sensing volt-
age with the reference voltage produced inside the AVR.
Input power is obtained from the main stator.
Rectifi ed output power to the exciter fi eld is controlled
by switching a transistor on and off. This AVR will
control terminal voltage even if the input sine wave is
distorted.
Figure 4: For 60 Hz
UNDER SPEED PROTECTION
A frequency sensing circuit is built into the AVR.
When the generator speed drops to 90% of rated
speed this circuit protects the AVR by reducing
the voltage in proportion to the decrease in engine
speed. In addition, when the generator is hit with a
rapid overload, this circuit will lower the voltage to
protect the engine. See Figures 3 & 4.
ROTARY RECTIFIER AND SURGE
SUPPRESSOR
The rotary rectifi er assembly, consisting of six
diodes, functions as a 3-phase full wave rectifi er for
the output of the exciter armature and supplies this
to the main fi eld. To protect the diodes from large,
instanta neous voltage surges, surge absorbers are
provided as part of the rotating rectifi er assembly.
OPX300K1 09/09
7
Characteristics
VOLTAGE REGULATION
Generator terminal voltage regulation is within ±1% of the
rated voltage in lagging power factor. 1.0 to 0.8, when the
load is varied gradually from no load to full load. This value
includes the temperature drift and rotating variation.
RESPONSE
After supplying a load instantaneously, the generator voltage
should be restored to the steady condition in accordance with
BS4999 Part 40, grade VR2.11 to VR2.23.
VOLTAGE STABILITY
In constant load and engine speed, voltage stability remains
0.25% of the rated voltage.
MOTOR STARTING
The generator is capable of enduring up to 300% of the rated
current for 10 seconds at power factor of 0.
SHORT CIRCUIT
PX-300K Series AC generators can provide over 300% of
the rated current for a short period of time, with an
excitation support system (optional).
PHASE ROTATION
Phase sequence is T1-T2-T3 (U-V-W, A-B-C) with a
counterclockwise rotation of generator viewed from the
anti-coupling side.
Standard Voltage Tables and Connection Diagrams
Standard voltage selection table and connection diagram for PX-300K Series 1-phase 4-wire and 3-phase 12-wire AC
generators. See Page 24.
Winding Connection Frequency Voltages
3 Phase Series Star
(High Wye)
3 Phase Parallel Star
(Low Wye)
1 Phase
60 Hz 120
1 Phase
50 Hz 110
50 Hz 415/240 400/231 380/219
50 Hz 208/120 200/115 190/110
60 Hz 120/240
50 Hz 100/200 110/220 115/230 120/240
Figure 5: Standard Voltage Table
60 Hz 480/277 460/266 440/254 416/240
60 Hz 240/139 230/133 220/127 208/120
OPX300K1 09/09
8
Operation – Generator Set
STARTING
Before starting generator, check the following:
1. Make sure that the wiring is correct.
2. Be sure that nothing is blocking the air inlet/ outlet.
3. Make sure that the inside of the generator is clean.
4. Be sure the main line circuit breaker is switched
OFF.
After checking each of the above, start the genertor in the
following procedure:
1. Start engine in accordance with instructions in the
Operator’s Manual. Be sure there is no abnormal
sound or vibration.
2. The voltage will rise due to the increase in generator
speed. After making sure that each interphase voltage
is balanced, set the voltage and frequency to the rated
level. Be sure the CPR switch is “ON”. The voltage
will not rise with CPR “OFF”.
3. After running the generator without load, switch the
circuit breaker ON to start the load operation.
STOPPING
After putting the running generator in a no-load condition
by removing the generator load, stop the engine in
accordance with the Engine Manual.
VOL TAGE ADJUSTMENT
The generator has been adjusted to obtain optimum
voltage at the factory. If the voltage is different, adjust
the voltage with the Voltage Adjust provided on the
AVR.
RUNNING
Check the following while operating the generator:
1. Abnormal vibration and/or sound
2. Load
3. Environment:
Keep the air inlet/outlet clean and clear for optimum
cooling. Insuffi cient cooling causes over heating of the
generator.
Note: When a 3-phase generator is used at single phase
load, each phase current should be balanced and should
not exceed 50% of the rated current. In addition,
allowable unbalanced load is listed on the Data Sheet.
OPX300K1 09/09
9
Operation – Automatic Voltage
Regulator
SAFETY RULES
• Do not leave AVR connected when testing generator
with high-pot or megger.
• Adjust the engine only when the CPR is in “OFF”
position.
OPERATION
1. Make sure the wiring is correct.
2. Make sure the frequency selection switch is set to
the rated frequency (60 or 50 Hz).
3. To adjust the voltage turn the Voltage Adjust
(VR1) counter-clock wise. Make sure the CPR is
“ON”.
a. Start the engine with no load and increase the
engine speed slowly to the rated level.
The voltage will automatically build up (residual
voltage: more than 10V).
b. Adjust to the rated voltage using the Voltage
Adjust (VR1).
c. Make sure of the proper Volt/Frequency
characteristic by reducing the generator speed.
d. Make sure of voltage stability by switching the
load “ON” or “OFF”. Use the Stability Adjust
(VR2).
e. If you fi nd no problem with the AVR, start the
normal operation.
2. Voltage Adjustment:
If the voltage output is low, increase the voltage by
turning the Voltage Adjust (VR1) slowly clockwise.
3. Stability:
If the voltage output is unstable, increase the voltage by
turning the Stability Adjust (VR2) clockwise.
4. Voltage and Frequency:
Voltage and Frequency (Hz) have been preset at the
factory.
ADJUSTMENT
Each component of the AVR is adjusted at the factory
to obtain optimum voltage. If readjustment is
necessary, make sure the voltage, frequency, load, etc.
are functioning properly after readjustment.
1. Initial Excitation: For initial excitation use a
DC12V or DC24V battery.
a. Stop the generator.
b. Remove the AVR connectors.
c. Connect the fi eld terminal F(+) with the
polarity (+) of battery and the terminal F (-)
with the polarity (-) and excite AVR fi eld for 2
or 3 seconds.
OPX300K1 09/09
10