Northern Lights 281PSL1500, 281PSL1501, 281PSL1502, 282PSL1503, 282PSL1504 User Manual

...
Page 1
MAGNAPLUS® GENERATOR
www.marathonelectric.com
280–430 Frame
Installation, Operation,
and Maintenance Manual
Marathon Electric Mfg. Corp.
A Subsidiary of Regal-Beloit Corp.
Wausau, WI 54402-8003
Phone: (715) 675 3359
Fax: (715) 675 8026
Page 2
CONTENTS
Safety 2 Receiving and Storage 2 Principles of Operation 3 - 4 Installation 4 - 6 Wiring Connections 6 - 9 Operation 9 - 10 Maintenance 10 - 11 Testing 11 - 12 Service 12 - 14 Troubleshooting 14 - 17 Specifications 18 Parts List & Recommended Spare Parts 19 - 20
SAFETY
When in doubt, ask. Questions are much easier to handle than mistakes caused by a misunderstanding of the information presented in this manual.
RECEIVING AND STORAGE
RECEIVING AND STORAGE
Upon receipt of the generator, it is recommended that it be carefully examined for possible shipping damage. The generator was given to the freight carrier in good condition; thus, the carrier is responsible for the product from the factory dock to the destination. Any damage should be noted on the freight bill before accepting the shipment. Any claims for damage must be promptly filed with the delivering carrier.
PLEASE REMEMBER SAFETY FIRST. If you are not sure of the instructions or procedures contained herein, seek qualified help before continuing.
This service manual emphasizes the safety precautions necessary during the installation, operation, and maintenance of your MagnaPLUS generator. Each section of this manual has caution and warning messages. These messages are for your safety, and the safety of the equipment involved. If any of these cautions or warnings are not readily understood, seek clarification from qualified personnel before proceeding.
Before any service work is done, disconnect all power sources and lock out all controls to prevent an unexpected start-up of the generator set driver. Proper grounding (earthing) of the generator frame and distribution system in compliance with local and national electrical codes and specific site requirements must be provided. These safety precautions are necessary to prevent potential serious personal injury, or even death.
The hazards associated with lifting or moving your MagnaPLUS generator are pointed out in the installation and maintenance sections. Incorrect lifting or moving can result in personal injury or damage to the unit.
Prior to start-up of the unit ensure that all generator leads are properly connected to the generator link board located inside the connection box. Always assume that there will be voltage present at the generator terminals whenever the generator's shaft is rotating, and proceed accordingly. Residual voltage is present at the generator terminals and at the automatic voltage regulator panel connections even with the regulator fuse removed. Caution must be exercised, or serious injury or death can result.
UNPACKING AND HANDLING
Carefully read all instruction tags shipped with the unit. When lifting, attach an overhead crane to the lifting lug(s) on the generator frame. Apply lifting forces in a vertical direction. When transporting single bearing generators, the generator’s rotor must be adequately supported to prevent damage.
WARNING
THE LIFTING LUG(S) ON THE GENERATOR ARE DESIGNED TO SUPPORT THE GENERATOR ONLY. DO NOT LIFT A COMPLETE GENERATOR AND DRIVER ASSEMBLY BY MEANS OF LIFTING LUG(S) ON THE GENERATOR. PERSONAL INJURY OR EQUIPMENT DAMAGE MAY RESULT.
STORAGE
In the event that the generator is not immediately installed on its prime mover, it is recommended that the unit be stored indoors in a clean, dry area which is not subject to rapid changes in temperature and humidity. If the generator is stored for a long period of time, the generator should be tested, cleaned and dried as required before being put into service. See the maintenance section of this manual for further information. If the unit has been stored in an area where it has been subject to vibration, it is recommended that the bearing(s) be inspected and replaced as necessary.
This manual is not intended to be a substitute for properly trained personnel. Installation and repairs should only be attempted by qualified, trained people. The cautions and warnings point out known conditions and situations that are potentially hazardous. Each installation may well create its own set of hazards
2
Page 3
PRINCIPLES OF OPERATION
PMG (optional)
PMG Field
(rotor)
N
S
PMG
Armature
(stator)
PMG Input Power (optional)
Exciter Field
(stator)
(+)
DC (in)
(-)
Exciter Field Power
(1 phase, 300/250 hertz)
Rotating Assembly
Exciter Armature
(rotor)
3 Phase AC (out)
Rotating Rectifier Assembly
3 Phase -- Full Bridge
(DC out)
Automatic
Voltage
Regulator
Main Field
(rotor)
(+)
DC
(in)
(-)
Input Power -- Single Phase
(shunt powered regulator)
Sensing Input -- Single Phase
FIGURE 1 -- MagnaPLUS Circuit Diagram
Main Armature
3 Phase AC (out)
3 phase (optional)
(stator)
L
1
L
2
L
3
FIGURE 2 -- Typical MagnaPLUS Layout Diagram
3
Page 4
PRINCIPLE OF OPERATION
horsepower per generator KW in motor starting capability. For specific data contact Marathon Electric.
MagnaPLUS generators are a brushless, self excited, externally voltage regulated, synchronous AC generator. The generator is made up of six major components: main stator (armature), main rotor (field), exciter stator (field), exciter rotor (armature), rectifier assembly, and voltage regulator. In understanding the above terminology, note the following: stators are stationary, rotors rotate, a field is an electrical input, and an armature is an electrical output. These system components are electrically interconnected as shown in figure 1 and physically located as shown in figure 2.
The generator’s exciter consists of a stationary field and a rotating armature. The stationary field (exciter stator) is designed to be the primary source of the generator’s residual magnetism. This residual magnetism allows the exciter rotor (armature) to produce AC voltage even when the exciter stator (field) is not powered. This AC voltage is rectified to DC by the rotating rectifier assembly and fed directly to the main rotor (field). As the generator shaft continues to rotate, the main rotor (field) induces a voltage into the generator's main stator (armature). At rated speed, the main stator’s voltage produced by the residual magnetism of the exciter allows the automatic voltage regulator to function. The regulator provides voltage to the exciter resulting in a build-up of generator terminal voltage. This system of using residual magnetism eliminates the need for a special field flashing circuit in the regulator. After the generator has established the initial residual voltage, the regulator provides a controlled DC field voltage to the exciter stator resulting in a controlled generator terminal voltage.
PARALLEL OPERATION
All MagnaPlus generators are built with 2/3 pitch main stator windings and full amortisseur (damper) windings. These features make the MagnaPlus generators suitable for parallel operation when equipped with the proper voltage regulators and voltage regulator accessories. Consult with the factory for further information relative to parallel operations.
NONLINEAR LOADING
Solid state electronic control devices (variable frequency drives, precision motor controls, battery chargers, etc.) utilize electronic switching circuits (thyristors, SCRs, Diodes, etc.). These switching circuits introduce high frequency harmonics which distort the normal wave form of the generator. This creates additional heat in the generator windings and may cause the generator to over-heat. Problems which can occur are not limited to the generator. Poor wave shape may adversely effect various loads connected to the generator. Consult Marathon Electric for further information relative to nonlinear loads.
INSTALLATION
PREPARATION FOR USE
Voltage Regulation
In the standard configuration (shunt excited), the automatic voltage regulator receives both its input power and voltage sensing from the generator's output terminals (See Figure 1). With the optional PMG configuration, the regulator receives input power from the PMG. The regulator automatically monitors the generator's output voltage against an internal reference set point and provides the necessary DC output voltage to the exciter field required to maintain constant generator terminal voltage. The generator's terminal voltage is changed by adjusting the regulator's reference set point. Consult the regulator manual for specific adjustment and operating instructions.
MOTOR STARTING
When a motor is started, a large surge of current is drawn by the motor. This starting current is equivalent to the motors locked rotor or stall current and is 5 to 10 times normal full load current. When the generator supplies this in-rush of starting current, the generator voltage dips temporarily. If the motor is too large for the generator, the generator’s voltage dips greater than 30 percent. This may result in the motor starter de-energizing or the motor stalling. MagnaPlus generators generally supply .3 to .4
Although the generator has been carefully inspected and tested in operation prior to shipment from the factory, it is recommended that the generator be thoroughly inspected. Check all bolts for tightness and examine the insulation on lead wires for chafing prior to proceeding with installation. Remove all shipping tapes, bags, skids and rotor support blocking. For two bearing units, rotate the shaft by hand to ensure that it rotates smoothly without binding.
4
Page 5
WARNING
DISABLE AND LOCKOUT ANY ENGINE CRANKING DEVICES BEFORE ATTEMPTING TO INSTALL OR SERVICE THE GENERATOR. FOR ELECTRIC START SETS, DISCONNECT THE CRANKING BATTERY. FOR AIR START, DISCONNECT THE AIR SUPPLY. FOR MOTOR GENERATOR SETS, OPEN THE POWER SUPPLY TO THE DRIVE MOTOR. FAILURE TO COMPLY WITH THESE SAFETY PROCEDURES COULD RESULT IN SEVERE PERSONAL INJURY OR EQUIPMENT DAMAGE.
NEVER "BAR OVER" THE ENGINE GENERATOR SET USING THE GENERATOR'S FAN. THE FAN IS NOT DESIGNED FOR THIS PURPOSE. BARRING OVER THE SET WITH THE FAN COULD DAMAGE THE FAN AND RESULT IN PERSONAL INJURY OR EQUIPMENT DAMAGE.
driver and the generator's shaft. Aligning the generator and its driver as accurately as possible will reduce vibration, increase bearing life, and ensure minimum coupling wear. It may be necessary to shim the generator feet for proper support and alignment. Secure the feet of the generator with grade 5 or greater bolts through the holes provided in the mounting feet. Consult the coupling manufacturer's instructions for alignment specifications and procedures.
GENERATOR MOUNTING
Two Bearing Units -- Belt Driven
Two bearing MagnaPLUS generators can be belt driven provided belts are sized and applied correctly. Please refer to your supplier of belts and sheaves for correct sizing and tensioning specifications. A bearing life calculation should be performed. Marathon Electric recommends a minimum B-10 life of 40,000 hours. If cog type belts are used, a vibration may be introduced which could lead to premature failure of the bearings.
GENERATOR MOUNTING
Single Bearing Units.
Single bearing units are provided with an SAE flywheel housing adapter flange and flexible drive discs. Coupling the generator's shaft to the engine flywheel is accomplished with special steel drive discs bolted to the shaft. In addition to the drive discs, there may be a hub spacer, spacer discs, or a combination of hub spacer and spacer discs inserted between the drive discs and the shaft to achieve the proper shaft extension ("G" dimension per SAE J620c). Holes are provided in the periphery of the coupling discs which correspond to tapped holes in the prime mover's flywheel. The outside diameter of the drive discs fit in a rabbet in the flywheel so that concentricity is assured.
Grade 8 place bolts and hardened washers are recommended to mount the drive discs to the flywheel. DO NOT USE SPLIT TYPE LOCK WASHERS. Split lock washers when biting into the drive disc cause stress risers which may result in the disc fracturing.
The SAE flywheel housing adapter ring and the engine flywheel housing are designed to match each other with no further alignment necessary. Use grade 5 or greater mounting bolts. MagnaPLUS generator frames are constructed with two or three bolt holes per foot. The feet should be shimmed where necessary to obtain solid contact with the sub-base. With the frame securely bolted to the engine flywheel housing, there is no side thrust or pull on the generator frame, thus no real need to secure the feet with more than one bolt per foot.
END PLAY TESTING
Refer to the engine manual for recommended end play specifications and measurement procedures. If end play is not to specification, it is an indication that the generator shaft is not moving freely in the assembly, and normal life of the thrust bearing could be impaired. Probable causes of this problem are:
1. Improper seating of drive discs in the flywheel resulting in misalignment.
2. Improper mating of generator frame to engine flywheel housing resulting in misalignment.
3. Improper "G" dimension per SAE J620c on either the engine or generator.
TORSIONAL VIBRATION
Torsional vibrations are generated in all rotating shaft systems. In some cases, the amplitude of these vibrations at critical speeds may cause damage to either the generator, its driver, or both. It is therefore necessary to examine the torsional vibration effect on the entire rotating system. IT IS THE RESPONSIBILITY OF THE GENERATOR SET ASSEMBLER TO ASSURE THE TORSIONAL COMPATIBILITY OF THE GENERATOR AND ITS DRIVER. Drawings showing pertinent dimensions and weights of the rotating assembly will be supplied by Marathon Electric upon request.
GENERATOR MOUNTING
Two Bearing Generators -- Direct Drive
Two bearing generators are provided with a keyed shaft extension. For direct drive generators, the assembler furnishes a flexible coupling which is installed between the
5
Page 6
ENVIRONMENTAL CONSIDERATIONS
380
219
The MagnaPLUS generator is designed for heavy duty industrial applications; however, dirt, moisture, heat and vibration are enemies of rotating electrical machinery. Excessive exposure to the elements may shorten generator life. The temperature of the cooling air entering the intake openings of the generator should not exceed the ambient temperature shown on the generator’s nameplate. Generators intended for outdoor application should be protected with housings having adequate ventilation. Although the standard insulation systems are moisture and humidity resistant, space heaters are recommended for extreme conditions. If the generator is to be installed in an area where blowing sand and dust are present, the enclosure should be fitted with filters. Filters reduce erosion on the generator's insulation by blocking high velocity abrasive particles generated by the flow of cooling air through the generator. Consult the factory for appropriate filters and generator deratings required.
WIRING CONNECTIONS
Wiring of the generator and accessories should be done in accordance with good electrical practices. Follow government, industry and association standards.
The generator conduit box construction allows cable entry from multiple sides. A hole saw or other appropriate tool may be used to provide for conduit entrance. Protect the
interior of the generator from shavings when drilling or sawing. An approved connector must be used in conjunction with the conduit. To minimize the transmission of vibration, it is essential that flexible conduit be used for all electrical entrance to the generator conduit box.
All MagnaPLUS generators are equipped with link boards (terminal strips) for both internal and external connections. All connections made to the studs of the link board should be made with high quality ring terminals. Ring terminal sizes are: 6 mm (280 Series Frames) and 10 mm (360 and 430 Series Frames). Torque link board connections to the following specifications: 280 frame -- 5.4 NM (4 Ft Lb); 360 & 430 frame -- 27 NM (20 Ft Lb).
Refer to the connection diagram supplied with the generator and / or the proper diagrams shown in this manual. Install all inter-component and external wiring in accordance with national and local electrical codes. The neutral in the following connection diagrams shown below may be either grounded (earthed) or left above ground potential (floating). See national and local codes and / or the system distribution wiring schematic diagram for the proper connection of the neutral.
The following connection diagrams are shown for twelve lead generators. Ten lead generators have the same terminal designations except for leads T10, T11, and T12. These three leads are internally connected inside the generator and brought out as a single lead (T0). Ten lead generators can only be connected in a wye configuration
HIGH (SERIES) WYE CONNECTION
L
1
T
1
VOLTAGE (HIGH WYE)
T
4
T
7
T
T
12
T
9
T
6
T
3
L
3
10
T
11
T
8
T
5
L - N
L - L
T
2
L
2
Hz L-L L-N
60 480 277
460 266 440 254 416 240 380 219
50 416 240
400 231
6
Page 7
LOW (PARALLEL) WYE CONNECTION
190
110
200
100
100
NA
L
1
T
7
T
1
VOLTAGE (LOW WYE)
Hz L-L L-N
T
10
T
12
T
9
L
3
T
3
T
4
T
5
T
T
11
6
T
8
L - L
T
2
L
2
60 240 139
230 133 220 127 208 120 190 110
50 208 120
200 115
L - N
HIGH (SERIES) DELTA CONNECTION
L
1
T
12
T
9
T
6
T
3
L
3
T
T
11
8
T
1
T
5
`
T
4
T
T
L - L
7
T
10
L
2
2
VOLTAGE (HIGH DELTA)
Hz L-L L-N
60 277 139
240 120
50 240 120
220 110
L - N
LOW (PARALLEL) DELTA CONNECTION
L
1
T
12
T
6
T
9
L
3
T
3
T
11
T
5
L - L
T
1
T
7
T
10
T
8
T
2
L - L
T
4
L
2
VOLTAGE (LOW DELTA)
Hz L-L L-N
60 120 NA
110 NA
50 110 NA
7
Page 8
DOUBLE DELTA -- SINGLE PHASE CONNECTION
VOLTAGE (DOUBLE DELTA)
50
220
110
VOLTAGE (LOW ZIGZAG)
Hz
L-L
L-N
VOLTAGE (HIGH ZIGZAG)
Hz
L-L
L-N
T
3
T
5
T
6
T
2
T
12
T
11
T
9
T
8
Hz L-L L-N
60 240 120
220 110
L
T
2
1
L - N
T
T
4
7
T
L - N
L - L
L
10
1
Note: Single phase KW/KVA ratings are approximately equal to 50% of the generator’s three phase ratings.
LOW ZIG ZAG -- SINGLE PHASE (PARALLEL) CONNECTION
T
6
T
T
3
L
2
12
T
9
L - N
T
2
T
8
T
L - L
5
T
4
T
10
L - N
T
1
T
L
7
1
Note: Single phase KW/KVA ratings are approximately equal to 50% of the generator’s three phase ratings.
T
11
60 240 120
220 110
50 220 110
200 100
HIGH ZIG ZAG -- SINGLE PHASE (SERIES) CONNECTION
T
12
T
1
T
T
9
T
6
T
3
L
2
L - N
4
T
7
60 480 240
T
T
10
11
T
T
8
T
5
2
L
1
50 415 208
L - N
L - L
Note: Single phase KW/KVA ratings are approximately equal to 50% of the generator’s three phase ratings.
460 220
380 190
8
Page 9
DEDICATED SINGLE PHASE CONNECTION
200
100
HIGH VOLTAGE - SERIES CONNECTED
VOLTAGE (DEDICATED) Hz L-L L-N
L
T
1
1
L - N
T
2
T
3
L - N
L
T
2
4
L - L
60 240 120
220 110
50 220 110
OPERATION
PRE-START INSPECTION
Before starting the generator for the first time, the following inspection checks are recommended:
1. A visual inspection should be made for any loose parts, bad connections, or foreign materials.
2. Bar the set over by hand for at least 2 revolutions to be sure that there is no interference and that the set turns freely. If the set does not turn freely, check for clearance in the generator and exciter air gap.
3. Check all wiring against the proper connection diagrams, and ensure that all connections and terminations are tight and properly insulated.
WARNING
MAGNAPLUS GENERATORS MAY HAVE VOLTAGE PRESENT AT THE LEAD TERMINALS WHEN THE SHAFT IS ROTATING. DO NOT PERMIT OPERATION OF THE GENERATOR UNTIL ALL LEADS HAVE BEEN CONNECTED AND INSULATED. FAILURE TO DO THIS MAY RESULT IN PERSONAL INJURY OR EQUIPMENT DAMAGE
8. Review all prime mover prestart-up instructions, and
ensure that all recommended steps and procedures have been followed.
9. Remove any masking materials affixed during painting. Inspect the generator, prime mover, and any accessory equipment to ensure that nameplates, and all safety warning / caution signs and decals provided with the equipment are in place and clearly visible.
Note: It is strongly recommended that the authority having jurisdiction over the installation site be consulted to determine if any additional warning or caution notices, or additional safety devices are required by local codes / standards. Any such required notices or devices should be installed prior to initial startup.
START-UP
The following procedure should be followed when starting the generator set for the first time.
1. The generator output must be disconnected from the load. Be sure that the main circuit breaker or fused disconnect is in the open position.
2. Open the input power to the automatic voltage regulator. Remove the fuse or disconnect and insulate one of the regulator input power leads. (See separate regulator manual)
4. Verify that all equipment is properly grounded (earthed).
5. Clear the surrounding area of any materials that could
be drawn into the generator.
6. Check all fasteners for tightness.
7. Check all access plates, covers, screens and guards. If
they have been removed for assembly or inspection, reinstall and check for security.
3. Verify that all prime mover start-up procedures have been followed.
4. If the unit is provided with space heaters, ensure that they are de-energized. In some installations, a set of auxiliary contacts on the main circuit breaker or transfer switch will automatically open the space heater circuit when the generator is connected to the load.
5. Start the prime mover, and adjust it for proper speed. See generator nameplate.
9
Page 10
6. The purpose of this initial test with the regulator out of the circuit is to detect any wiring mistakes without exposing the unit to undue risk. Check all line to line and line to neutral voltages for balanced voltage. If voltages are balanced, shut down the set and reconnect the regulator. If voltages are unbalanced, shut down the equipment and check for improper wiring. If the problem persists, consult the factory.
2. Isolate all conditions that could apply voltage to the generator terminals while the generator is at rest. Failure to comply could result in personnel injury or equipment damage.
3. If the unit is equipped with space heaters, verify that the heater circuit is energized.
With the regulator de-energized, the residual voltage should be 10 - 25% of rated value. It is recommended that this residual voltage and driver RPM be recorded for use as a future troubleshooting benchmark.
WARNING
THE FOLLOWING TEST MUST BE CONDUCTED BY QUALIFIED ELECTRICAL PERSONNEL. LETHAL VOLTAGE MAY BE PRESENT AT BOTH THE GENERATOR AND VOLTAGE REGULATOR TERMINALS DURING THIS PROCEDURE. CAUTION MUST BE EXERCISED NOT TO COME INTO PERSONAL CONTACT WITH LIVE TERMINALS, LINKS, OR STUDS. SERIOUS INJURY OR DEATH COULD RESULT.
7. Start the set and adjust the terminal voltage to the
desired value by means of the regulator voltage adjustment. If the regulator is equipped with a stability adjustment, follow the instructions in the regulator manual to adjust the stability. Again, check all line to line and line to neutral voltages for balance. It is recommended practice to record the no load excitation (DC voltage to the exciter stator), generator terminal voltage, and driver speed as a benchmark for future troubleshooting.
8. Close the main circuit breaker to the load.
MAINTENANCE
The following maintenance procedures should be followed to ensure long equipment life and satisfactory performance. Maintenance intervals will depend upon operating conditions.
1. Routinely check intake and exhaust air screens to ensure that they are clean and free of debris. Clogged intake air screens will reduce cooling air flow and result in higher operating temperatures. This will reduce generator life and may result in generator damage.
2. All MagnaPLUS generators are equipped with double shielded ball bearings lubricated for the life of the bearing. Every 1,000 hours check the bearing(s) for smooth, quiet operation. For continuous duty generators, recommended practice is to replace the bearing during major overhauls of the engine.
3. Periodically inspect the unit for any buildup of contamination (dirt, oil, etc.) on the windings. If the wound components have become coated with heavy concentrations of oil and grime, the unit should be disassembled and thoroughly cleaned. This operation is not one that can be accomplished effectively on site, but rather one that should be conducted by an authorized service center equipped with the appropriate apparatus and solvents necessary to properly clean and dry the generator.
9. Monitor the generator output current to verify that it is at or below nameplate value.
10. Check generator speed (frequency) under load. Adjust as necessary. (Refer to prime mover or governor manuals)
SHUTDOWN PROCEDURE
There are no specific instructions for shutting down the generator; however, several good practices should be observed to prolong equipment life.
1. It is advisable to disconnect all loads (open main circuit breaker or disconnect) prior to shutdown. This is especially important if loads can be damaged by low voltage or low frequency conditions during generator "coast down".
WARNING
THE FOLLOWING TEST MUST BE CONDUCTED BY QUALIFIED ELECTRICAL PERSONNEL. LETHAL VOLTAGE MAY BE PRESENT AT BOTH THE GENERATOR AND VOLTAGE REGULATOR TERMINALS DURING THIS PROCEDURE. CAUTION MUST BE EXERCISED NOT TO COME INTO PERSONAL CONTACT WITH LIVE TERMINALS, LINKS, OR STUDS. SERIOUS INJURY OR DEATH COULD RESULT.
4. Every 2,000 operating hours or in conjunction with
scheduled engine maintenance, check the DC no load excitation voltage per item #7 in the startup procedure. Compare this voltage with the value recorded during initial startup. If this value of no load excitation voltage is markedly higher than the bench mark reading, it is an indication of problems in either the exciter, main field,
10
Page 11
or the rotating rectifier assembly. Ensure that RPM is the same as initial test.
5. Monitor and record insulation resistance with a 500 volt mega-ohm meter. The minimum acceptable reading is 2 mega-ohms. If the reading drops below the minimum, the generator should be cleaned and dried at an authorized service shop. Consult Marathon Electric for more information.
DRYING WINDINGS
Generators in service may inadvertently have their windings exposed to splashing or sprayed water. Units that have been in transit or storage for long periods of time may be subjected to extreme temperature and moisture changes causing excessive condensation. Regardless of the source of moisture, wet windings should be thoroughly dried out before operating the unit. If this precaution is not taken, serious damage to the generator can result. The following procedures may be utilized in drying the generator’s windings. The method selected will be influenced by winding wetness and situation limitations.
WARNING
THE FOLLOWING TEST MUST BE CONDUCTED BY QUALIFIED ELECTRICAL PERSONNEL. LETHAL VOLTAGE MAY BE PRESENT AT BOTH THE GENERATOR AND VOLTAGE REGULATOR TERMINALS DURING THIS PROCEDURE. CAUTION MUST BE EXERCISED NOT TO COME INTO PERSONAL CONTACT WITH LIVE TERMINALS, LINKS, OR STUDS. SERIOUS INJURY OR DEATH COULD RESULT.
CONSTANT EXCITATION TEST (12V BATTERY TEST)
The generator “no load” voltage is dependent on exciter input voltage and generator speed. With the generator operating at rated speed and 12 volts dc applied to the exciter field, the generators terminal voltage will be near rated value.
Space Heaters An electric heater may have been supplied with the generator. When energized from a power source other than the generator, the heater will gradually dry the generator. This process can be accelerated by enclosing the unit with a covering and inserting additional heating units. A hole should be left at the top of the covering to permit the escape of moisture. Care should be taken not to overheat various accessory equipment mounted with the generator.
Forced Air Another method to dry the generator is to run the set with no excitation (see startup procedure item #2). The natural flow of ambient air through the generator will tend to dry the windings. This method can be accelerated by adding a source of heat at the air intake to the generator. Heat at point of entry should not exceed 80 C (180° F).
TESTING
Visual Inspection
Remove covers and look for any obvious problems: burnt windings, loose connections, broken wires, frayed insulation, cracked brackets, missing hardware, etc. Check for foreign objects which may have been drawn into the generator. Verify that the generator’s air gaps (main rotor and exciter) are free from obstructions. If possible, rotate the generator manually to ensure free rotation. Never “bar over” the engine generator set using the generator fan.
1. Shutdown the generator set and connect a voltmeter on the generator terminals.
2. Disconnect the regulator’s F+ (F1) and F- (F2) leads and connect them to a 12V battery. Caution should be taken to ensure that the battery is not exposed to any potential arcing.
3. With no load on the generator (main breaker open) run the generator at rated speed. Measure the generator’s terminal voltage and compare this value with values recorded during installation.
If voltage readings are normal, the main generator and excitation are operating properly. Troubleshooting should continue with the regulator. If readings are not normal the problem is in the generator. Continue testing diodes, surge suppressor, and windings.
Continuity / Resistance Test
The generator has four components which can be checked using an ohm meter: exciter stator, exciter rotor, main stator and main rotor. Each of these components are comprised of various windings which form a complete electrical path of relatively low resistance. Using an ohm meter measure the loop resistance of each component. Compare these measured values with the values listed in the specification section of this manual. Note that very small resistance values require precision equipment to make accurate measurements; however, a standard ohm meter will provide a good indication of winding continuity.
11
Page 12
Insulation Test
Insulation resistance is a measure of the integrity of the insulating materials that separate the electrical windings from the generator’s steel core. This resistance can degrade over time or be degraded by contaminants: dust, dirt, oil, grease, and especially moisture. Most winding failures are due to a breakdown in the insulation system. In many cases, low insulation resistance is caused by moisture collected when the generator is shutdown
Insulation resistance is measured with a megger (mega­ohm meter). A megger measures insulation resistance by placing 500 volts between the winding and the frame of the generator. Caution must be taken to remove all electronic devices (regulators, diodes, surge protectors, capacitors, protective relays, etc.) from the winding circuit before checking the insulation. Winding insulation can be checked on the main stator, main rotor, exciter stator, and exciter rotor. Minimum resistance is 2 mega-ohms. If the winding resistance is low it must be dried (see maintenance section) or repaired.
When the positive test probe is connected to the diode's anode and the negative test probe is connected to the diode's cathode (forward biased), the diode will switch on and conduct electricity (figure 3). This is observed by a low resistance reading when using an ohm meter or the lighting of the bulb when using a battery light continuity tester. Reversing the test leads (reverse biased) will result in the diode switching off and no electricity will be conducted. The results of these tests should indicate one of three conditions:
1. Good diode: Will have a much greater resistance in one direction than the other. Typical reverse biased resistance will be 30,000 ohms or greater, while forward biased resistance will be less than 10 ohms. The battery-light tester will have the light "on" in one direction and "off" in the other.
2. Shorted condition: Ohmmeter reading will be zero, or very low in both directions. The continuity tester will have the light "on" in both directions.
3. Open condition: Ohmmeter will have a maximum (infinity) reading in both directions. Continuity tester light will be off in both directions.
DIODE TESTING
If the generator is close coupled to an engine, it may be necessary to "bar over" the engine in order to gain access to a given area of the rectifier assembly. NEVER use the generator's fan as a fulcrum to accomplish this. Use the engine manufacturer's recommended practice to manually turn over the engine. To prevent possible injury to personnel, and damage to the equipment, ensure that the engine cannot start during this procedure.
Remove the two main rotor leads and the three exciter rotor leads from the rectifier assembly (figure 4). The rectifier assembly is now electrically isolated from the generator. The diodes remain mounted and the diode leads remain connected to the terminal posts. Using an ohmmeter or a battery light continuity tester, place one test probe on the diode lead terminal post. In succession, touch the other test probe to the lead screw hole in each heat sink. Reverse the probes and repeat the procedure. You have now tested the three diodes connected to this terminal post in both the forward and reverse direction. Repeat the procedure using the other diode terminal post.
Forward Reverse
Terminal End
Anode
(+)
Stud End
Cathode
(-)
Cathode
(-)
Anode
(+)
Diode failure after a 25 hour "run-in" period is generally traceable to external causes such as a lightning strike, reverse current, line voltage spikes, etc. All 6 diodes are essentially in the same circuit. When a diode is stressed to failure, there is no easy method to determine remaining life in the other diodes. To avoid possible continued failures, it is recommended that the entire rectifier assembly be replaced rather than replacing individual diodes.
SERVICE
GENERAL
The service procedures given in this section are those which can reasonably be conducted on-site with a minimum number of special tools and equipment. All service procedures should be conducted by qualified maintenance personnel. Replacement parts may be ordered through an authorized service center or directly from the factory.
FIELD FLASHING
Restoring Residual Magnetism (not applicable on PMG equipped generators)
To restore residual magnetism to the generator, connect a 12 volt battery to the exciter field while the generator using the following procedure:
1. Shutdown the generator set. Remove the exciter field
leads F+ and F- from the regulator.
FIGURE 3: DIODE POLARITY
12
Page 13
CAUTION: Failure to remove the exciter field leads from the automatic voltage regulator during flashing procedures may destroy the regulator.
2. Connect the F+ and F- leads to the battery’s
corresponding positive and negative terminals. This should be done using an appropriate length of lead wire to separate the battery from the point of connection (batteries may explode when exposed to an electric arc). After 3 to 5 seconds, remove the F- lead. An inductive arc should result. If no arc is drawn, repeat the procedure.
3. Reconnect the F+ and F- leads to the regulator. Restart the generator and verify that terminal voltage is developed. If terminal voltage does not develop, repeat the field flashing procedure and / or consult the trouble shooting section.
BEARING REMOVAL
Prior to performing this operation, it is suggested that the alternator's shaft be rotated until two of the main rotor poles are in a vertical position. Once the bearing bracket is backed out, the rotor will drop on the main stator core. Having the rotor in this position will limit the amount of rotor drop to that of the air gap. Visually inspect the bearing bore for damage or wear. If worn or damaged, replace prior to reassemble.
clear the locating register on the frame. Lower the shaft extension until the rotor is resting on the main stator core. Continue to pull the bracket free from the bearing. Visually inspect the bearing bore for damage or wear. If worn or damaged, sleeve or replace prior to reassembly.
Reassembly note: Before the bearing bracket is seated against the frame, a threaded rod may be used to help align the inner bearing cap with the bearing bracket.
BEARING REPLACEMENT
Using a bearing puller, remove the existing bearing. It is strongly recommended that the bearing be replaced any time the it is removed from the shaft. ALWAYS install the same type and size bearing that was supplied as original equipment. Order by part number from the parts list, and include the unit serial number and part number when ordering. Heat the bearing to a maximum of 100oC (212oF) in an oven. Apply a thin coat of clean lubricating oil to the press-fit area of the rotor shaft. Using suitable heat resistant gloves, install the bearing over the end of the shaft until it seats against the shaft shoulder. The bearing should slide on the shaft and be seated without excessive force. Should the bearing bind on the shaft prior to being seated against the shoulder, a piece of tubing slightly larger than the press fit area can be used to drive the bearing to its final position. Using light taps with a soft mallet, apply pressure to the inner race only.
Opposite Drive End Bearing Bracket Removal. Prior to proceeding with bracket removal, disconnect exciter field leads F+ and F- from the automatic voltage regulator and ensure that they are free to move when the bearing bracket is removed. Remove the bearing bracket retaining bolts. Using a pair of screw drivers, wedge the bracket off the frame. After approximately 1/8 inch, the bracket will clear the locating register on the frame and will drop until the rotor is resting on the main stator core. Continue to pull the bracket free from the bearing. Visually inspect the bearing bore and o-ring (if equipped) for damage or wear. If worn or damaged, repair or replace prior to reassembly.
Drive End Bearing Bracket Removal, Two Bearing Units.
Remove any drive arrangement from the generator shaft extension. Remove the bearing lock ring retaining screws. There is no o-ring in the drive end bearing bracket. The shaft extension must be supported before proceeding further. A hoist and sling, jack, or some other means of support with a capacity of 2 tons should be used.
Remove the bearing bracket retaining cap screws. Using a flat bladed screw driver or chisel, pry the bracket back from the frame. After approximately 1/8 inch, the bracket will
RECTIFIER ASSEMBLY REMOVAL
The rectifier assembly cannot be removed until the opposite drive end bearing bracket and bearing have been removed (see bearing removal procedure). Remove the three exciter rotor leads from the heat sinks and the two main rotor leads from the main rotor posts (see Figures 4). Remove the screws securing the rectifier assembly and pull the assembly free from the shaft.
DIODE REPLACEMENT
Prior to installing a replacement diode on the heat sink, apply a thin film of conductive heat sink compound around the base of the diode (do not coat the threads). When installing a diode on the heat sink, care should be taken not to over torque the retaining nut which could cause damage to the device. Torque to 28 pound-inches. If not damaged, the existing diode lead wire may be unsoldered from the failed diode, and resoldered on the replacement.
13
Page 14
430 FRAME 280 / 360 FRAME
A - Exciter Rotor Lead, B - Main Rotor Lead, C - Red (+) Suppressor Lead, D - Black (-) Suppressor Lead
FIGURE 4: ROTATING RECTIFIER ASSEMBLY
RETURNED GOODS
Contact Marathon Electric Manufacturing Corporation for authorization before returning any product. We can not be responsible for any items returned without authorization.
CAUTION
Single bearing generators must have their rotor assembly properly secured to prevent damage during transit to the factory, or to an authorized service center.
TROUBLESHOOTING
This section is intended to suggest a systematic approach to locating and correcting generator malfunctions. The section is arranged according to the symptoms of the problem. The steps have been arranged in an attempt to do the easy checks first and prevent further damage when troubleshooting a disabled machine.
The first step of troubleshooting is to gather as much information as is possible from operating personnel and individuals present during the failure. Typical information includes: how long the unit had been operating; what loads were on line; weather conditions; protective equipment that did or did not function. In addition, information as to the operating condition of the generator's prime mover is vital. Has the prime mover been maintaining constant speed? If not, have there been extended periods of under speed operation? Has the prime mover experienced an over-speed condition? If yes, what was the maximum speed, and how long did the unit operate at that elevated speed?
The generator speed should be maintained at rated nameplate value during all operating tests. The frequency of the generator depends upon rotational speed. Most regulators used with MagnaPLUS generators have built in under frequency protection such that if the speed is reduced more than 5%, the voltage will drop off rather rapidly with further reductions in speed.
14
Page 15
WARNING
HIGH VOLTAGES MAY BE PRESENT AT THE GENERATOR’S TERMINALS WHEN THE UNIT IS RUNNING. SOME ACCESSORY EQUIPMENT SUCH AS SPACE HEATERS MAY BE ENERGIZED FROM AN OUTSIDE POWER SOURCE WHEN THE UNIT IS AT REST. TOOLS, EQUIPMENT, CLOTHING AND YOUR BODY MUST BE KEPT CLEAR OF ROTATING PARTS AND ELECTRICAL CONNECTIONS. SPECIAL PRECAUTIONS MUST BE TAKEN DURING TROUBLESHOOTING SINCE PROTECTIVE COVERS AND SAFETY DEVICES MAY BE REMOVED OR DISABLED TO GAIN ACCESS AND PERFORM TESTS. BE CAREFUL. SERIOUS PERSONAL INJURY OR DEATH CAN RESULT FROM THESE HAZARDS. CONSULT QUALIFIED PERSONNEL WITH ANY QUESTIONS.
GENERATOR PRODUCES NO VOLTAGE
CAUSE CHECK AND REMEDY
Voltmeter off or defective Check voltage with a separate meter at the generator terminals. Incorrect or defective connections Verify generator connections. See drawings supplied with the generator or lead
connection diagrams in this manual. Inspect all wiring for loose connections, open circuits, grounds, and short circuits.
Loss of residual Flash the field. Refer to field flashing in the service section. If the generator is equipped
with a PMG, field flashing is not necessary -- check regulator fuse and input power from the PMG.
Defective diodes, suppressor, or windings
Regulator protection operating Adjust regulator. Consult regulator manual. Regulator inoperative Adjust or replace regulator. Consult regulator manual.
Test the generator using the 12 volt battery test as specified in the testing section. If the results indicate generator problems, perform insulation, continuity, and diode tests as specified in the testing section.
GENERATOR PRODUCES LOW VOLTAGE, NO LOAD
CAUSE CHECK AND REMEDY
Underspeed operation Check speed using a tachometer or frequency meter. Voltmeter off or defective Check voltage with a separate meter at the generator terminals. Incorrect or defective connections Verify generator connections. See drawings supplied with the generator or lead
connection diagrams in this manual. Inspect all wiring for grounds, open circuits and short circuits.
Loss of regulator power Check regulator fuse and input power. Input power is produced by the generator’s
residual voltage or from an optional PMG. Regulator adjustment Adjust regulator settings. Consult regulator manual. Regulator incorrectly connected Review the generator connection diagram or reference the regulator manual. Defective diodes, suppressor, or
windings
Regulator inoperative Adjust or replace regulator. Consult regulator manual.
Test the generator using the 12 volt battery test as specified in the testing section. If the
results indicate generator problems, perform insulation, continuity, and diode tests as
specified in the testing section.
15
Page 16
GENERATOR PRODUCES LOW VOLTAGE WHEN LOAD APPLIED
CAUSE CHECK AND REMEDY
Excessive load Reduce load. The load on each leg should be evenly balanced, and rated current should
not be exceeded on any leg. Large motor starting or low load
power factor Driver speed droop or belt slip Check driver. If belt driven, check belt tension. Check under frequency setting on
Reactive droop If the generator is equipped for parallel operation, some droop is normal as reactive load
Line drop If voltage is proper at generator terminals but low at load terminals, increase external wire
Defective diodes, suppressor, or windings
Motor starting currents are too large for the generator. When starting multiple motors,
sequence the motors and start the largest motors first. Reduce lagging power factor load.
regulator. Under frequency voltage roll-off may be activated.
increases. When operating as a single unit, the parallel CT can be shorted to eliminate
this effect. Refer to Regulator manual.
size.
Test the generator using the 12 volt battery test as specified in the testing section. If the
results indicate generator problems, perform insulation, continuity, and diode tests as
specified in the testing section.
GENERATOR PRODUCES FLUCTUATING VOLTAGE
CAUSE CHECK AND REMEDY
Fluctuating engine speed Check engine and governor systems for malfunctions. Check load for fluctuation. Regulator stability Adjust Regulator stability. Refer to Regulator manual. Regulator external rheostat Replace defective or worn rheostat. Use shielded cable to minimize electrical noise. Defective rectifier assembly Check assembly for loose connections. Test the diodes as specified in the test section. Loose terminal or load connections Improve connections both mechanically and electrically. Defective regulator Replace regulator.
GENERATOR PRODUCES HIGH VOLTAGE
CAUSE CHECK AND REMEDY
Faulty metering Check voltage with separate meter at generator terminals. Incorrect connections Verify generator connections. Refer to drawings supplied with the generator or connection
diagrams in this manual. Regulator adjustments Adjust regulator. Consult regulator manual. Leading power factor Check the power factor of the load. If power factor is leading, change load configuration.
Excessive leading power factor (capacitors) can cause voltage to climb out of control. Incorrect regulator connection Verify regulator voltage sensing is connected correctly. Consult regulator manual. Defective regulator Replace regulator.
16
Page 17
GENERATOR BUILDS VOLTAGE FROM STARTUP,
THEN GOES TO LOW (RESIDUAL) VOLTAGE
CAUSE CHECK AND REMEDY
Regulator protective circuit operating
Check indicators on regulator. Correct problems and adjust regulator as is required.
Refer to regulator manual.
GENERATOR IS OVERHEATING
CAUSE CHECK AND REMEDY
Generator is overloaded Reduce load. Check with ammeter and compare with nameplate rating. Clogged ventilating screens Clean air passages. High room temperature or altitude Improve ventilation or reduce load. Insufficient circulation of cooling air Generator location and enclosure design must provide adequate air flow and minimize
recirculation of hot air. Unbalanced load The load on each leg should be as evenly balanced as possible and should not exceed
rated current on any one leg.
GENERATOR PRODUCES MECHANICAL NOISE
CAUSE CHECK AND REMEDY
Defective bearing Replace bearing. Loose or misaligned coupling Tighten, realign, or replace coupling. Belt slap or loose guards Check belt tensioning. Check belt guard fasteners.
EQUIPMENT RUNS NORMALLY ON UTILITY POWER,
BUT WILL NOT RUN ON GENERATOR SET
CAUSE CHECK AND REMEDY
Distorted voltage waveform Analyze load. Excessive SCR (thyristor) loading will cause distortion. Some equipment
may be sensitive to distorted waveforms. Refer to Marathon Electric.. Improper generator voltage or
frequency
CAUTION: Compare required voltage, frequency, and KVA with generator nameplate to ensure adequate generator capacity. If in doubt, consult Marathon Electric for information regarding generator capacity.
Check name plates of devices comprising the load. Compare required voltage and
frequency with that of the generator. Adjust driver speed and/or generator voltage as
necessary to match generator output to load requirements.
17
Page 18
SPECIFICATIONS
MODEL / FRAME SIZE EXCITER RESISTANCE
STATOR ROTOR 281, 282, 283, 284 23.0 .120 361, 362, 363 -- three phase 23.5 .120 361, 362, 363 -- dedicated single phase 23.0 .135 431, 432, 433 -- three phase 20.33 .076 431, 432 -- dedicated single phase 18.0 .105
EXCITER FIELD NO LOAD TERMINAL VOLTAGE
MODEL GENERATOR RESISTANCE NO LOAD VOLTS WITH 12 VDC FIXED EXCITATION
STATOR* ROTOR 480 V / 60 HZ HIGH WYE / 60 HZ HIGH WYE / 50 HZ 281PSL1500 4.20 .400 11.0 485 400 281PSL1501 4.15 .400 11.0 490 404 281PSL1502 3.20 .439 9.0 528 435 282PSL1503 2.00 .470 10.4 500 415 282PSL1504 1.51 .512 11.3 490 400 282PSL1505 1.00 .575 10.1 515 415 283PSL1506 .681 .654 11.0 495 400 283PSL1507 .480 .758 12.0 480 390 284PSL1508 .346 .875 12.0 480 375 361PSL1600 .381 .750 11.8 485 400 361PSL1601 .264 .810 12.5 475 385 361PSL1602 .181 .990 14.1 460 370 362PSL1604 .138 1.05 12.2 480 380 362PSL1606 .0980 1.20 10.8 500 405 363PSL1607 .0692 1.37 12.2 475 380 431PSL6202 .0214 .8114 15.1 440 360 431PSL6204 .0477 .6373 13.6 455 385 431PSL6206 .0371 .6793 13.82 455 370 431PSL6208 .0133 .715 12.20 475 390 432PSL6210 .0214 .8114 15.1 440 360 432PSL6212 .0226 .8656 14.1 445 385 433PSL6216 .01215 1.0672 16.2 425 345 433PSL6220 .01214 .9743 15.6 430 350
* Stator resistance measured line to line in a high wye connection.
DEDICATED GENERATOR RESISTANCE EXCITER FIELD
SINGLE PHASE STATOR ROTOR NO LOAD VOLTS / 60 HZ
281PSL1511 1.420 .381 8.3 281PSL1512 1.106 .395 8.1 281PSL1513 .632 .430 8.7 282PSL1514 .436 .450 9.2 282PSL1515 .240 .520 9.7 283PSL1516 .160 .620 13.3 284PSL1517 .0918 .760 12.2 284PSL1518 .0610 .857 16.6 361PSL1611 .0695 .750 17.5 361PSL1612 .0434 .857 16.1 361PSL1613 .0369 .926 13.6 362PSL1615 .0191 1.20 17.0 363PSL1617 .0119 1.35 23.0 431PSL1811 .0248 .516 9.9 431PSL1813 .0129 .615 13.8 432PSL1814 .00931 .643 15.1 432PSL1815 .00723 .852 11.2
18
Page 19
PARTS LIST – SINGLE BEARING Typical Generator Cross Section
Reference
Number
1 End Bracket (under end cover 360 & 430 frames) 11 Main Stator 2 Bearing 12 Main Rotor 3 O-ring (280 frame only) 13 Rotor Integral Keyway 4 Rectifier Assembly 14 Fan 5 Air Intake Screen (280 frame only) 15 Mounting Adapter (SAE) 6 Exciter Rotor 16 Shaft 7 Exciter Stator 17 Drive Hub 8 Link Board (terminal block) 18 Drive Disk (SAE) 9 Conduit Box 19 Exhaust Screen (drip cover not shown)
10 Generator Frame 20 Mounting Base
Note: Illustration above is a 280 frame MagnaPlus. Other Frame sizes are typical. Optional PMG not shown.
The generator model and serial numbers are required when ordering parts.
Part Name Reference
Number
Part Name
19
Page 20
PARTS LIST – DUAL BEARING
Typical Generator Cross Section
Reference
Number
1 End Bracket (under end cover 360 & 430 frames) 11 Main Stator 2 Bearing (nondrive end) 12 Main Rotor 3 O-ring (280 frame only) 13 Rotor Integral Keyway 4 Rectifier Assembly 14 Fan 5 Air Intake Screen (280 frame only) 15 End Bracket (drive end) 6 Exciter Rotor 16 Bearing (drive end) 7 Exciter Stator 17 Shaft 8 Link Board (terminal block) 18 Key 9 Conduit Box 19 Exhaust Screen (drip cover not shown)
10 Generator Frame 20 Mounting Base
Note: Illustration above is a 280 frame MagnaPlus. Other Frame sizes are typical. Optional PMG not shown.
The generator model and serial numbers are required when ordering parts.
Part Name Reference
Number
Part Name
20 SB 504 9/03
Loading...