Northern Heatpump RT-SE-033, RT-SE-020, RT-SE-026, RT-SE-040, RT-SE-052 Installation & Operating Instructions Manual

...
Page 1
Two-Stage Split Geothermal Heat Pump
Installation & Operating Instructions
Application
Retrofit existing forced air installations. Dual Heat – combine this geothermal unit and A-coil with stand-by gas or oil furnace. LMC (Load management control) ready.
Information
The air coil furnished with this product has been tested and certified with this unit. To maintain the specification performance and product certification, the air coil shipped with
this unit must be used.
This unit is NOT tax credit eligible when a coil other than the furnished coil is used.
For proper performance, the CFM airflow required in the specification table must be provided by the installed furnace blower/air handler.
Since this product requires line sets and air coil installation, an experienced and licensed refrigeration technician is required.
Domestic Water Heater, Desuperheater
Energy Star promotes the desuperheater and it is standard with this series. However, it only efficiently produces hot water if the tank temperature is less than 115° F (46° C). Thus, for proper and efficient application a hot water buffer tank is suggested, see page 17.
Note
The EZGEO control board has a configuration mode dial switch. This must be correctly set during installation, see EZGEO Controller (HC112) and Field Setup sections.
Drawings:
EC001, HC112, NH501, NR501, NS501, XX029
DO NOT DESTROY THIS MANUAL. PLEASE READ CAREFULLY AND KEEP IN A SAFE
PLACE FOR FUTURE REFERENCE BY A SERVICE TECHNICIAN.
Model: (RT-SE*)
09/29/2010 NI501
Page 2
Table of Contents
Introduction 1
Product Configurator (NC029) 2
Mechanical Specifications 3
Electrical Data 4
Product Dimensions 5
Installation Requirements 6
Mechanical Installation Overview 7
Mechanical Installation Source Water 9
Flushing and Filling Procedure 11
Desuperheater, Domestic Hot Water 16
Duct System/A-Coil 18
Mechanical Installation Refrigeration 19
Charging Procedure 21
Superheat and Subcooling 22
Electrical Hookup 25
EZGEO Controller 26
Temperature Sensors, Field Install 29
Gas Furnace Hookup – Mode D 30
Additional Hookup or Special Equipment Concerns 31
Field Setup or Programming 32
Operation Indicators 34
Power On, Start Up 35
Operational Tips 36
Troubleshooting 37
Accessories/Options 42
Drawings EC001
HC112 NH501 NR501 NS501 XX029
09/29/2010 NI501
Page 3
Introduction
When used and controlled properly, geothermal heat pumps can save hundreds of dollars in heating and cooling costs per year. Northern Heat Pump NorthStar Series geothermal heat pumps are designed to provide maximum efficiency, comfort, and reliability. Solid and simple electric controls allow for low maintenance and built in safety protection.
This is a pre-wired package for converting a new or existing oil or gas furnace into a dual heat system. This is a complete package for both heating and air conditioning, utility load control, and compatible with DC drive
variable speed furnaces. There are no additional relays or option hardware needed for the outlined application. The utility load control receiver properly switches the heating mode and properly controls the air conditioning
mode during summer load interrupt. The blower circuit and control is also designed for heating interrupt
(blower handled by gas furnace only) and continuous operating blower during cooling peak load interrupt.
Typically these controls and design features are only found in this product.
Moving and Storage
Units should be stored in original packaging in a clean dry area. Store and move units in normal upright position. Do not stack units.
Initial Inspection
Be certain to inspect all cartons and crates as units are received before signing the freight bill. Verify that all items received have no physical damage. Report any damages or shortages on the freight bill. The purchaser is responsible for filing the necessary claims with the carrier. Concealed or hidden damages not discovered until removing packaging must be reported to the carrier within 15 days of receipt.
Unit Location and Mounting
Locate the unit in an indoor area where the ambient temperature will remain above 45°F [8°C]. Northern Heat Pump provides 4 removable panels for ease of servicing; front (2), right and left bottom. This unit is zero clearance rated; however, allow enough room to remove panels for service and maintenance. Suggest setting
unit on a sound vibration pad, see accessories price sheet, R-PAD-2735-1-**. Water supply should not be hard
plumbed directly with copper pipe as this could transfer any vibration to living space.
Please read and understand conditions associated with proper installation, unauthorized changes, and POWER ON procedures.
Warranty Statement
See the last page of this manual for detailed limited warranty coverage explanation.
Safety Considerations
WARNING
BEFORE PERFORMING SERVICE OR MAINTENANCE OPERATIONS ON A SYSTEM, TURN OFF MAIN POWER SWITCHES TO THE INDOOR UNIT. IF APPLICABLE, TURN OFF THE ACCESSORY HEATER POWER SWITCH. ELECTRICAL SHOCK COULD CAUSE PERSONAL INJURY.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply, such as the following safety measures:
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations. Have a fire extinguisher available for all brazing operations.
09/29/2010 1 NI501
Page 4
Northern Heat Pump Configurator
R T - S E - 0 5 2 - 1 - C X D X 1 - X X - U S
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Model Number Digits
RT-SE-052-1-CXDX1-XX-US
Geo Source (1)
Unit Type (2)
T = Two Stage
Unit Style (3)
S = Split
Refrigerant (4)
E = R-410A
Nominal BTU (5, 6, 7)
020 = 1.5-ton 026 = 2.0-ton 033 = 2.5-ton 040 = 3.0-ton 045 = 3.5-ton 052 = 4.0-ton 062 = 5.0-ton
Split System Coils
Country of Origin (16, 17)
US = United States
Auxiliary kW Option (14, 15)
XX = None
Vintage (13)
1
Miscellaneous Kits (12)
X = None
Desuperheater Option (11)
D = Desuperheater w/ Factory
Installed Pump
X = None
Configuration Option (10)
C = Split Air Coil X = No Split Air Coil
Heat Exchanger Option (9)
C = Copper
Voltage Option (8)
1 = 208/230V, 1 Ph 2 = 208/230V, 3 Ph
R-AE-030-21-US
R = Geo
Always A
Refrigerant
E = R-410A
Coil Size
21 = 21” 24 = 24”
Coil Capacity
024 = 24k BTU (2-ton) 036 = 36k BTU (3-ton) 048 = 48k BTU (4-ton) 060 = 60k BTU (5-ton)
09/17/2010 NC029
Page 5
Mechanical Specifications – R410A Two-Stage Compressor
MODEL
RT-SE-020
(1.5 ton) Coax & Piping Water Volume – gal .43 .43 .65 .65 1.1 1.1 Internal Pressure Drop (feet) 6.2 6.2 4.2 5.5 6.2 8.0 Internal Pressure Drop (psi) 2.7 2.7 1.8 2.4 2.7 3.5 Source Temperature °F (min/max) 20°/120° 20°/120° 20°/120° 20°/120° 20°/120° 20°/120° Nominal source differential* ° F (H/C) 3/10° 3/12° 8/11° 9/11° 6/11° 6/10° Factory Charge R410A -(oz) * 40 46 46 64 96 96 Static Pressure – Nominal 0.3 0.3 0.3 0.3 0.3 0.3 Static Pressure – Design 0.5 0.5 0.5 0.5 0.5 0.5
Air Filter
Weight– Packaged (lbs) 420 440 460 480 503 530
*Shown as reference information only, see unit nameplate for the supplied factory charge for each specific unit.
Model Stage
Source
GPM
RT-SE-026 FL 7 35.49 900 39 4.52 29.70 900 32 4.24 24.47 900 26 3.82 RT-SE-026 PL 7 24.39 700 33 4.60 21.68 700 29 4.30 18.74 700 26 3.84
RT-SE-033 FL 8 41.36 940 42 4.04 36.30 950 36 3.95 27.65 950 28 3.49 RT-SE-033 PL 8 28.45 720 38 4.66 23.40 700 32 4.02 20.80 714 28 3.73
RT-SE-040 FL 10 52.00 1210 41 4.51 42.72 1205 34 4.27 33.19 1200 27 3.72 RT-SE-040 PL 10 37.47 1020 35 5.47 30.80 1000 30 4.72 27.28 1000 26 4.26
RT-SE-052 FL 13 68.18 1500 43 4.00 53.31 1500 36 3.72 44.93 1500 29 3.31 RT-SE-052 PL 13 47.09 1200 37 4.40 37.75 1200 30 3.72 33.75 1180 27 3.43
RT-SE-062 FL 15 81.87 1840 35 4.02 66.71 1840 35 4.02 53.35 1820 28 3.57 RT-SE-062 PL 15 63.45 1520 40 4.88 50.00 1470 32 4.11 45.40 1475 29 3.82
Model Stage
Source
GPM
RT-SE-026 FL 7 32.46 950 20 13.4 36.87 950 22 20.3 30.17 950 20 16.06 RT-SE-026 PL 7 24.35 750 20 14.5 28.00 750 21 22.0 22.66 750 22 19.2
RT-SE-033 FL 8 33.71 1000 20 14.2 38.87 1000 22 20.5 36.06 1000 21 15.9 RT-SE-033 PL 8 25.28 730 22 13.3 29.16 740 25 21.3 27.05 750 24 18.0
RT-SE-040 FL 10 42.28 1260 22 13.9 47.48 1260 23 20.0 44.68 1260 22 16.1 RT-SE-040 PL 10 31.69 1055 21 17.0 35.55 1055 22 27.1 34.92 1060 21 23.1
RT-SE-052 FL 13 55.75 1600 22 12.9 64.95 1600 23 19.1 58.00 1600 22 15.1 RT-SE-052 PL 13 41.70 1300 20 14.8 48.28 1275 22 24.4 46.63 1275 22 21.4
RT-SE-062 FL 15 71.21 1970 21 14.2 76.65 1970 23 18.7 72.60 1970 23 15.6 RT-SE-062 PL 15 54.06 1600 22 16.2 57.50 1630 21 23.1 60.34 1670 22 22.1
1. Capacities are based on temperatures shown in heading, source is left group, return air is right group.
2. Stated Btu/h are the ISO 13256-1 formula adjusted, actual HP supply energy delivered is 2% greater.
3. Temp rise is based on sensible only.
4. All ratings based upon operation at lower voltage of dual voltage rated models.
5. Ground Loop Heat Pump ratings based on 15% antifreeze solution.
HEATING – ISO 13256-1 SPECIFICATION – ENERGY STAR
Capacity
Btu/h
COOLING – ISO 13256-1 SPECIFICATION – ENERGY STAR
Capacity
Btu/h
7/8 X 21 7/8
X 27 1/2
WLHP – Water Loop GWHP – Ground Water GLHP – Ground Loop
68° F 68° F 50° F 68° F 32° F/41° F 68° F
Blower
CFM
WLHP – Water Loop GWHP – Ground Water GLHP – Ground Loop
86° F 80.6° F 59° F 80.6° F 77° F/68° F 80.6° F
Blower
CFM
Temp
Rise
Temp
Drop
RT-SE-026
(2 ton)
7/8 X 21 7/8
X 27 1/2
COP
EER
Capacity
Btu/h
Capacity
Btu/h
RT-SE-033
(2.5 ton)
7/8 X 21 7/8
X 27 1/2
Blower
CFM
Blower
CFM
RT-SE-040
(3 ton)
7/8 X 28 7/8
X 27 1/2
Temp
Temp
Drop
Rise
COP
EER
RT-SE-052
7/8 X 27 1/2
Capacity
Btu/h
Capacity
Btu/h
(4 ton)
X 37 7/8
RT-SE-062
7/8 X 27 1/2
Blower
CFM
Blower
CFM
(5 ton)
X 37 7/8
Temp
Rise
Temp
Drop
COP
EER
09/29/2010 3 NI501
Page 6
Electrical Data – Single Phase
Desup.
Pump
Model
Voltage Compressor
(60 Hz) RLA LRA FLA FLA FLA Ampac.
020 208/230-1 10.3 52 .15 4.4 14.9 17.4 30 026 208/230-1 14.1 70 .15 4.4 18.7 22.2 40 033 208/230-1 16.7 82 .15 4.4 21.3 25.4 50 040 208/230-1 16.7 96 .15 4.4 21.3 25.4 50 052 208/230-1 25.6 118 .15 4.4 30.2 36.6 60 062 208/230-1 27.2 150 .15 4.4 31.8 38.6 60
Loop
Pump
(Ext)
Total Min.
Max.
Fuse/
HACR
Electrical Data – Three-Phase
Desup.
Pump
Model
Voltage Compressor
(60 Hz) RLA LRA FLA FLA FLA Ampac.
020 200/230-3 7.1 59 .15 4.4 11.7 13.4 30 033 200/230-3 11.2 58 .15 4.4 15.8 18.6 40 040 200/230-3 13.5 88 .15 4.4 18.1 21.4 40 052 200/230-3 17.6 123 .15 4.4 22.2 26.6 50
Loop
Pump
(Ext)
Total Min.
Max.
Fuse/
HACR
09/29/2010 4 NI501
Page 7
Product Dimensions
09/29/2010 5 NI501
Page 8
Installation Requirements
1. All installation work must be performed by trained, qualified contractors or technicians. Northern Heat
Pump, sponsors installation and service schools to assist the installer. Visit our Website at
www.electromn.com
WARNING
ALL ELECTRICAL WIRING MUST BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE AND LOCAL ELECTRIC CODES, ORDINANCES, AND REGULATIONS.
WARNING
OBSERVE ELECTRIC POLARITY AND WIRING COLORS. FAILURE TO OBSERVE COULD CAUSE ELECTRIC SHOCK AND/OR DAMAGE TO THE EQUIPMENT.
CAUTION
This unit can only be used for its intended design as described in this manual. Any internal wiring changes, modifications to the circuit board, modifications or bypass of any controls, or installation practices not according to the details of this manual will void the product warranty, the safety certification label, and manufacturer product liability. Northern Heat Pump, cannot be held responsible for field modifications, incorrect installations, and conditions which may bypass or compromise the built-in safety features and controls.
2. If this is a Dual Heat system, this product relates only to the addition to the furnace ducting system external
to the gas or oil force air furnace. The owner/ installer assumes all responsibility and/or liability associated with any needed installation of the gas/oil furnace, fuel system, flue, chimney, etc. Any instructions or comments made within this manual (or factory phone assistance) relating to the gas/oil furnace are provided as comments of assistance and “helps” only.
for upcoming service schools.
CAUTION
This unit shall not be operated (either heating section or blower) until the interior of the structure is completed and cleaned. This also means all duct work must be complete with filter, etc. Manufacturer’s warranty is void if this unit is operated during structure construction.
CAUTION
Hazards or unsafe practices could result in property damage, product damage, severe personal injury and/or death.
3. All removed or discharged refrigerant must be recovered. Local and federal statutes are to be observed.
Should a compressor need replacing, the compressor oil is to remain with the compressor. Refrigerant lines on the compressor must be sealed.
4. Remember, safety is the installer’s responsibility and the installer must know this product well enough to
instruct the end user on its safe use.
At Northern Heat Pump, the safety of the installer and the end user is of highest priority. Remember, safety is the installer’s responsibility and the installer must know this product well enough to instruct the end user on its safe use. Professional installers should be trained and experienced in the areas of handling electrical components, sheet metal products, and material handling processes.
09/29/2010 6 NI501
Page 9
Mechanical Installation Overview
This NHP Series unit cannot produce furnace system. The following items should be carefully considered and properly followed for all installations:
Examination of the existing forced air furnace – Prior to starting this installation or furnace modification,
examine the total furnace system and make necessary comments or recommendations to the homeowner. Remember, if a marginal condition exists within the existing forced air system, the installation of a geothermal heat pump will not cure PRE-EXISTING conditions. Consider such items as proper fossil fuel ignition, is the furnace cycling on hi-limit, filter, adequate cold air return, adequate supply duct and room register (1 register per 100 CFM) etc.
Heating capacity – Size the geothermal heat pump according to the normal heating requirements as the building
exists today oversize the geothermal heat pump.
Supply plenum – Carefully examine all sides of the plenum. The coil must be installed on the supply side of
the fossil fuel furnace. Verify all transitions have angles less than 30, the coil is centered within the plenum, and there are no odd shaped angles or odd shaped transitions within the plenum.
Other plenum equipment – Auxiliary equipment such as humidifiers, zone plenum dampers, etc., located
within the plenum which may cause a non-uniform airflow issues may have to be removed if they cause to great reduction to system airflow. Zone dampers within the trunk line at least 12" (30cm) from the coil typically are no problem. When horizontal zone dampers are involved, perform all check-out functions with smallest zone open first.
Insufficient cold air return capacity – Installation experience indicates this is a major concern. In fact, it
could represent a problem in as many as 60% of the installations, especially if there is a requirement to increase airflow with the existing blower and the existing cold air return capacity is already undersized or restricted. Check the static pressure within the return cabinet or the suction at the filter cabinet door. Do not assume because there is a register on the wall, the hole behind the register or the passageways are equal to this register. Sharp offsets and transitions in the cold air return system often cause severe restrictions. Expect to add additional registers or a relief register in the main cold air return duct.
Blower CFM capacity – The furnace forced air system must have an airflow capacity larger than the minimum requirement on the NHP Series specification sheet (see unit nameplate and/or Mechanical Specifications on page 3). It is near impossible to correctly measure CFM airflow in an existing residential installation.
Experience and rule of thumb indicators will have to be followed to determine the existing furnace CFM capacity. The following may be helpful:
. Do not necessarily match to the existing furnace nameplate because it may be oversized. Do not
Comment – zone dampers cause back pressure on the blower and overall reduced airflow. Reduced airflow can cause the geothermal unit to perform poorly or in some cases cause icing or freeze ups in the geo loop or air coil.
a. Existing furnace nameplate
the systems static pressure. What changes have been made to the heating system since installation?
b. Blower motor size
2 ton unit - 1/3 HP or larger 3 ton unit - 1/2 HP or larger 4 ton unit - 3/4 HP or larger 5 ton unit - 1 HP or larger
c. Observe/examine airflow ducting system and design
industry equivalent duct capacity airflow charts and determine if the system is capable of delivering the CFM required on the nameplate. Especially check the number of registers and
airflow and cannot correct airflow problems inherent within the existing
- Typically represents a high or optimistic rating and is a function of
- Used only as a minimal guide.
- Use duct sizing table (ECØØ1), or
09/29/2010 7 NI501
Page 10
p
the number of “6 inch rounds”. The same would apply to cold air return duct capacity.
d. Calculated CFM
- By measuring the temperature rise across the existing furnace, the CFM can be approximated. The accuracy of this formula will depend upon the estimated or determined Btu output (actual heat energy across the furnace, not nameplate input).
CFM =
Btuh (output)
Temperature Rise x 1.08
Closed Loop Applications – Closed loop system re-circulates the same water/antifreeze solution through a closed system of underground high-density polyethylene pipe. As the solution passes through the pipe it collects heat (in the heating mode) that is being
Horizontal Closed Loop
transferred from the relatively warm surrounding soil through the pipe and into the relatively cold solution. The solution is circulated back to the heat pump that extracts its heat and then returns to the ground to absorb more heat from the earth. Earth loops must be sized properly for each particular geographic area and individual capacity requirements.
The NHP Series heat pumps are designed to operate on either vertical or horizontal closed loop applications. (Figures 1 & 2) Vertical loops are typically installed with a well drilling rig up to 200 feet (61 meters) deep or more. Horizontal systems are typically installed with excavating
Figure 1
Vertical Closed Loo
or trenching equipment approximately six to eight feet deep, depending on geographic location and length of pipe used.
Lake or Pond Loops – Closed loop systems may also be used in lakes or rivers to supply a heat source to the heat pump. Typically a loop consisting of geothermal pipe can be designed and placed in an area not much deeper than 15ft (4.5 meters) with some water currents present. In any lake or pond, municipal and area codes must be observed in regards to a lake or pond loop. The use of an environmentally friendly loop fluid like ethanol should be considered should damage ever occur to the loop. Consult an IGSHPA
Figure 2
or CGC certified installer for proper lake or pond loop design.
09/29/2010 8 NI501
Page 11
Mechanical Installation Source Water
WARNING
LOOP DESIGN IS EXTREMELY IMPORTANT FOR PROPER HEAT PUMP OPERATION. INCORRECT LOOP DESIGN WILL REDUCE HEAT PUMP EFFICIENCY, CAUSE POOR PERFORMANCE OR MAY RENDER THE SYSTEM UNUSABLE. CONTACT AN IGSHPA OR CGC CERTIFIED GEOTHERMAL LOOP CONTRACTOR FOR PROPER INSTALLATIONS.
Water Connections General
The following pages outline typical piping arrangements for the most common source water connection options,
as well as flushing and filling procedures and antifreeze requirements for closed loop systems. Do not connect
copper piping directly to the source water connection points on this unit. A section of flexible piping is recommended to reduce and isolate vibrations transmitting from the compressor into other parts of the system.
Once closed loops are completed, they must be pressure tested to at least 60 PSI to insure integrity. Once pressure is tested, loop must be purged of all foreign debris and filled with fluid. All air must be removed at this time by flushing the system. (Table 2) shows approximate fluid volumes.
Pressure/Temperature (P/T) plugs – Should be installed in the adaptor elbow on the entering
and leaving water line of the heat pump on a closed system. (Figure 3) A thermometer can be inserted into the P/T ports to check entering and leaving water temperatures. A pressure gauge can also be inserted into these P/T ports to determine the pressure differential between the entering and leaving water. This pressure differential can then be compared to the engineering specifications data to determine the flow rate of the system.
Loop Pump Selection – Select a loop circulation pump based upon the GPM required and total system pressure
drop. See specification, page 3. Geo heat pump Btu/h capacity and efficiency are directly related to the GPM
flow though the unit.
Vibration pad – suggest setting the unit on a sound vibration pad, available from most distributors or
accessories price sheet – R-PAD-2735-1-**.
Water quality – models with standard copper heat exchanger coils require the installer to evaluate water quality
and meet minimum water properties.
pH/calcium hardness pH < 7.5 and Ca harness < 100 PPM Iron fouling < 0.2 PPM (Ferrous)
< 0.5 PPM of oxygen
Hydrogen sulfide (H
S) < 0.5 PPM
2
Chloride levels < 20 PPM Erosion/clogging < 10 PPM, particles Filter, if required < 800 micron size
P/T Adapter
Figure 3
09/29/2010 9 NI501
Page 12
Figure 4 – Pressurized Closed Loop with Flow Center – Typical piping arrangement.
Figure 5 – Non-Pressurized Closed Loop with Flow Center – Typical piping diagram.
09/29/2010 10 NI501
Page 13
p
eat Pump
p
p
Flushing and Filling the System Using 3-Way Valves
Step 1
Use water and a high volume head circulator pump to flush air and debris and to fill the loop system.
Refer to recommendations provided by IGSHPA or CGC when choosing a pump for the flushing
process.
It is recommended that pump suction be from the bottom of a large volume container. Use a suction
Step 2
Pump water into the system by connecting the pump discharge hose to one (not both) of the 1.00” NPT water connections located on the sides of the module. Connect a return hose to the opposite side of the module to discharge debris and air as water is added to the loop.
Step 3
Rotate the module valves as shown in step 3 diagram:
Step 4
Start the pump. Add anti-freeze and water to the container as needed so that no air enters the system. This will push any air out of the loop. If flushing assembly is equipped with valves to reverse flow direction, do so occasionally to help remove trapped air. When bubbles cease in the return hose container, the earth loop has been completely flushed.
Step 5
Flush the heat pump. To do so, simply rotate the valves as shown in step 5 diagram while the pump is running. Flush the heat pump using the same procedure as used to flush the earth loop.
Pressurizing the System (does not apply to Figure 5) Step 6
After flushing and filling the system, rotate the module valve discharging into the flush container as shown in step 6A diagram to pressurize the loop. Then turn the valves as in step 6B.
Step 7
Turn off the flush cart pump. The system should remain pressurized. Release excess pressure by rotating either module valve to allow a small amount of water to pass through and out of the system and into the container. Some initial loss of pressure can be expected and is due to the expansion of the earth loop pipe under pressure. The pressure will stabilize if the system has no leaks.
Step 8
Flushing, filling and pressurization should be complete. Start the loop pump module circulators.
Step 9
Troubleshoot. If for some reason the circulators are not operating, power off and diagnose the problem.
Step 10
09/29/2010 11 NI501
line strainer to prevent debris discharged into the container from being recycled to the system.
Step 3
From Flush Cart
Step 5
From Flush Cart
To Heat Pump
Step 6A
From Flush Cart
To Heat Pump
From Heat Pum
Pressurize Loo
From Heat Pum
To H
To Flush Cart
To Flush Cart
Page 14
Using a single water pressure gauge, measure the pressure drop at the pressure/temperature plugs across the heat pump heat exchanger. Compare the measurement with the flow versus the pressure drop table (Table#3) and determine the actual flow rate. If the flow rate is low, recheck the selection of the loop pump module model for sufficient capacity. If the model is correct, there is likely trapped air or a restriction in the flow circuit. System pressure should increase rapidly as the flush pump works to force more water into the system. Additional flushing of the loop is needed if the water level in the loop falls. This shows that there is air in the system. System operating pressures should be between 10 to 40 PSI.
Antifreeze
DO NOT mix more than 25% propylene glycol with water to achieve a lower than 15°F [-9°C] freeze
protection. (See Table 3) A more concentrated mixture cannot be pumped through the earth loop at low temperatures. Lack of antifreeze will cause unit shutdown problems during cold weather operation (longest unit run time) when the loop temperatures fall below the freeze protection of the antifreeze. Flow rate requirements for closed loop solutions are higher than open loop systems because water temperatures supplied to the heat
pump are generally lower. Typically 2.0 to 3.0 gallons per minute (GPM) per ton are required for proper
operation of the heat pump and the earth coupled heat exchanger.
Table 2 – Approximate Fluid Volume (gal)
per 100ft
Pipe Size Volume
¾” IPS SDR 11 2.8
1” IPS SDR 11 4.5
Polyethylene
Rubber Hose 1” 3.9
Copper
1-1/4” IPS SDR 11 8.0
1-1/2” IPS SDR 11 10.9
2” IPS SDR 11 18.0
1” 4.1
1.25” 6.4
1.5” 9.2
Table 3 – Antifreeze Percentages by Volume*
Minimum Temperature for Freeze Protection
10°F 16°F 17°F 21°F 25°F
Type -12°C -9°C -8°C -6°C -4°C
Methanol 25% 21% 18% 16% 10%
Propylene
38% 30% 25% 22% 15%
Glycol
Ethanol 22% 20% 18% 14% 10%
*Reference information only, see product manufacturer
specification for percentage.
WARNING
DO NOT USE CALCIUM AS ANTI-FREEZE. FOLLOW CGC/IGSHPA RECOMMENDATIONS
FOR THE APPROPRIATE TYPE AND AMOUNT OF ANTI-FREEZE.
WARNING
PREVENTING FREEZE-UP IS INSTALLER/USER RESPONSIBILITY. LEAKING HEAT EXCHANGER OR PIPING (EXTERNAL OR INTERNAL WITHIN THE REFRIGERANT/
COMPRESSOR) ARE NOT COVERED BY WARRANTY.
09/29/2010 12 NI501
Page 15
Open Loop Well to Well – An open system gets its name from the open discharge of water after it has been
used by the heat pump. A well must be available that can supply all of the water requirements of the heat pump along with any other water requirements drawing off that same well. The well must be capable of supplying the heat pumps required flow rated for up to 24 hours per day for the coldest winter day.
Figure 6 shows the necessary components for water piping of an open system. First a bladder type pressure tank with a “draw down” of at least 1-1/2 to 2 times the well pump capacity must be installed on the supply side of the heat pump to prevent short cycling the well pump. Shut off valves and boiler drains on the entering and leaving water lines are necessary for future maintenance. A screen strainer is placed on the supply line with a mesh size of 40 to 60 and enough surface area to allow for particle buildup between cleanings. Pressure temperature (P/T) plugs are placed in the supply and discharge lines so that thermometers or pressure gauges can be inserted into the water stream. On the well water discharge side of the heat pump a flow control/shut off valve must be mounted to regulate the maximum water flow through the unit. Remove handle to prevent accidental change of flow.
A solenoid valve is then installed and wired to TB C & Y terminal on the heat pump. (Refer to NS501) This valve will open when the unit is running and close when the unit stops. A visual flow meter is then installed to allow visual inspection of the flow requirements. The flow meter can also be useful in determining when maintenance is required. Schedule 40 PVC piping, copper tubing, polyethylene or rubber hose can be used for supply and discharge water lines. Limit rubber hose to 10 ft. (3 meters) to prevent excessive pressure drop. Make sure line sizes are large enough to supply the required flow with a reasonable pressure drop (generally
1.00” diameter). Water discharge is generally made to a drain field, stream, pond, surface discharge, tile line, or storm sewer.
CAUTION
Using a drain field requires soil conditions and adequate sizing to assure rapid percolation or the required flow rates will not be achieved. Consult local codes and ordinances to assure compliance. Do not discharge water to a septic system. The heat pump should never be operated with flow rates (GPM) less than specified. Operation of the unit with less than required flow rate or no flow may result in freezing water in the water to refrigerant heat exchanger. This will cause the unit to shut down on low-pressure lockout. If the unit locks out, verify that the unit has the required flow and reset the unit by shutting off power to the unit for one minute. Do not continually reset the unit; if the unit locks out more than once call your service professional. Continued reset of the unit can freeze water inside the water coil to the point of rupturing the water coil (no warranty for frozen coils).
09/29/2010 13 NI501
Page 16
Figure 6: Open Loop Well to Well – Typical piping diagram.
Open Loop Freeze Protection Switch – Heat pump installations on open loop systems, using a non-antifreeze
protected water source during the heating mode require the use of a water coil freeze protection switch. If the water supply to the heat pump is interrupted for any reason, continued operation of the compressor will cause the water remaining in the water-to-refrigerant heat exchanger to freeze and rupture. The freeze protection switch will shut the unit down before freezing can occur and protect the heat pump against flow loss and damage.
Option – 39° F (4° C) pipe clamp-on, part number 6047. Connect in series with low limit.
Water Coil Maintenance – Water quality is a major concern for open systems. Problems can occur from
scaling, particle buildup, suspended solids, corrosion, pH levels outside the 7-9 ranges, or biological growth. If
poor water quality is known to exist in your area a cupronickel water coil may be required when ordering the
system, or installing a closed loop system may be the best alternative. Water coil cleaning on an open loop
system may be necessary on a regular basis.
09/29/2010 14 NI501
Page 17
Depending on the specific water quality issue, the water coil can be cleaned by the following methods:
Chlorine Cleaning (Bacterial Growth)
1. Turn thermostat to “Off” position.
2. Connect a circulating pump to hose bibs on entering water and leaving waterside of heat exchanger.
3. Using a five-gallon pail of water add chlorine bleach mixture. The chlorine should be strong enough to
kill the bacteria. Suggested initial mixture is 1 part chlorine bleach to 4 parts water.
4. Close shut off valves upstream and downstream of heat exchanger.
5. Open hose bibs to allow circulation of bleach solution.
6. Start pump and circulate solution through heat exchanger for 15 minutes to one hour. Solution should
change color to indicate the chlorine is killing the bacteria and removing it from the heat exchanger.
7. Flush used solution down the drain by adding fresh water supply. Flush until leaving water is clear.
8. Repeat procedure until solution runs clear through the chlorine circulation process.
9. Flush entire heat pump system with water. This procedure can be repeated annually, semiannually, or
as often as it takes to keep bacteria out of the heat exchanger, or when bacteria appears in a visual flow meter to the point the flow cannot be read.
Muriatic Acid Cleaning
Difficult Scaling and Particle Buildup Problems Consult installer due to dangerous nature of acids. Iron out solutions and de-scaling products are also useful.
09/29/2010 15 NI501
Page 18
Desuperheater, Domestic Hot Water
General
All NHP Series units are equipped with a desuperheater and an integrated circulating pump (can be a price deduct) that can provide Supplemental Domestic hot Water (SDW). This is done by stripping heat from the superheated gas leaving the compressor.
Fuses – 3-amp fuses are installed in series with the desuperheater pump. The fuses are located in the line
voltage control box, upper right. Remove the fuses (turn 230 power source off) to disable the pump whenever the system is not in operation.
General Plumbing and Installation Suggestions
1. Insulated ½” copper piping should be used from the hot water tank to the desuperheater connections on
the left side of the unit. The copper tubing should be straight to maintain good water velocity and prevent pockets from forming at the pump inlet.
CAUTION
Due to high water temperatures generated by the desuperheater, pex or poly pipe may rupture if coupled directly to heat pump outlet.
2. Shut off valves should also be used to service the desuperheater pump without draining the entire hot
water tank. Note: Always be sure these valves are open when pump is running.
3. Pump problems develop by running the pump dry or with air in the system. All air must be purged from
the desuperheater plumbing before the pump is engaged.
4. To purge air from the lines, loosen the desuperheater pump from its housing by turning the brass collar.
Let water drip out of the housing until flow is established and re-tighten the brass collar.
5. Never operate the system without the high temperature switch (normally factory installed) otherwise
tank temperatures could become dangerously high.
6. Poor water quality may restrict the effectiveness of using the desuperheater pump and will not allow the
pump to circulate.
7. Desuperheater maintenance includes periodically opening the drain on the hot water tank to remove any
deposits. Hard water may cause scale buildup in the desuperheater coil reducing its effectiveness.
8. The temperature difference between the water entering and leaving the desuperheater should be 5°F to
15°F. The water flow should be approximately 0.4 GPM per ton of nominal cooling.
9. Northern Heat Pump strongly suggests a water heater buffer tank, Figure 7, for the maximum efficiency
from the provided desuperheater module. The Figure 7A single tank plumbing and application is shown for information only.
There are a number of ways the desuperheater/pump can be plumbed with and into the building/household water
heater tank. However, many common methods used are not very effective because they simply circulate
already heated water from the water heater tank through the desuperheater. The heat pump desuperheater cannot effectively produce hot water energy if the temperature of the water entering the desuperheater is close to or beyond the compressor gas capability to transfer energy into this circulated water – typically 110° F (46° C) to 130° F (54° C).
Example – if the water heater electric element thermostat is set at 140° F (60° C), it will maintain
the tank at 140° F (60° C). There is no point in circulating 140° F (60° C) water through the desuperheater because it is picking up very little or no energy from the compressor hot gas.
In fact, the energy flow may even be negative if the Geo HP loop temperature is too low, it is
possible for a single tank hot water heater to actually flow energy into the Geo HP system with a
negative effect of energy efficiency.
09/29/2010 16 NI501
Page 19
Figure 7 – Desuperheater Piping, Buffer Tank
This is the most effective and efficient arrangement and the recommended installation. The buffer tank need not be as big as the standard water heater; 40­gallon size can be very effective. With this two tank system the desuperheater will always act as a
city/well water pre-heater and the standard water
heater (electric elements or gas) only requires tempering energy which is a very small percentage of domestic water heater energy required.
Figure 7A – Desuperheater, Single Tank Concept
Draw water from the bottom drain and returning it to the cold water supply line. This method requires a check valve in the cold water supply to prevent water from flowing into the building or household cold water supply. A spring-type check valve with a pressure rating of 1/2 PSI or less is recommended.
Inspect the dip tube in the water heater cold inlet for a check valve. If a check valve is present it must be removed or damage to the desuperheater circulator will occur.
Before restoring electrical supply to the water heater, adjust the temperature setting on the tank.
On tanks with both upper and lower elements, the
lower element should be turned down to the lowest setting, approximately 100° F (38° C). The upper element should be adjusted to 120° F (49° C) to 130° F (54° C). Depending upon the specific needs of the customer, you may want to adjust the upper element differently.
On tanks with a single element, lower the
thermostat setting to 120° F (49° C).
CAUTION
Do not run desuperheater pump without supply from water heater. This will damage the pump.
09/29/2010 17 NI501
Page 20
Duct System
An air filter must always be installed upstream of the air coil on the return air side of the air handler or furnace. If there is limited access to the filter rack for normal maintenance, it is suggested that a return air filter grill be installed. Be sure that the return duct is properly installed and free of leaks to prevent dirt and debris from bypassing the filter and plugging the air coil.
In applications using galvanized metal ductwork, a flexible duct connector is recommended on both the supply and return air plenums to minimize vibration from the blower. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of 1-inch thick glass fiber or be constructed of ductboard. Insulation is usually not installed in the supply branch ducts. Ducts in unconditioned areas should be wrapped with a minimum of 1-inch (25mm) duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected. If the air handler is connected to existing ductwork, a previous check should have been made to assure that the duct system has the capacity to handle the air required for the unit application. If ducting is too small, as in replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repairs made accordingly. The duct system and diffusers should be sized to handle the design airflow quietly. If air noise or excessive airflow is a problem, the blower speed can be changed to a lower speed to reduce airflow. This will reduce the performance of the unit slightly in heating; however, it will increase the temperature rise across the air coil. Airflow must still meet minimum requirements.
Air Coil Installation
This unit is furnished with the air coil matched to the heat pump system and compressor. To maintain the
product ratings, certification, etc. the furnished coil must be used.
Gas or Oil Furnace – Normally as required by the furnace manufacturer’s warranty, the refrigerant coil must be
in the supply or discharge plenum. It is recognized the furnished coil may be large and may present some physical plenum issues, but it is matched to the size of the heat pump and thus this coil must be accommodated within the forced air ducting system.
ST Duct Sensor – See page 29 for details relating to installing ST sensor above coil.
Airflow (CFM) – As listed on the unit nameplate and the page 3 specification table the minimum CFM must
flow through this coil. This is a function of the installer discerning the overall ducting system sizing/quality, the
furnace blower size/motor, furnace restrictions, return air restrictions, air filter, etc. This is not simply a function of looking at the furnace nameplate. Proper CFM must be assured and guaranteed by the installer.
As the plenum is fabricated or rebuilt, all transitions must have angles of less than 30°, the coil must be centered within the plenum, and there should not be any odd shaped angles or odd shaped transitions within the plenum.
09/29/2010 18 NI501
Page 21
Mechanical Installation Refrigeration
Overview
The NHP Series split unit includes pre-charged R-410A, with the filter drier factory installed in the unit. The
charge will have to be fine tuned based upon line set length and system performance. Line set lengths of over
25ft (7.6 meters) are not recommended due to performance loss and potential oil return issues.
Forced Air Coil – The refrigerant coil supplied with this product model number must be used for this
installation. The nameplate and specification table ratings only apply when using the furnished air coil.
Do not use existing or older A-coils because they probably are not designed for R-410A, may be
contaminated from other refrigerants, may not be large enough, and may not have the correct TXV metering valve.
Realizing the furnished coil is large, provisions and plenum arrangements must be made to
accommodate this coil. This is necessary again for proper Geo HP performance and meeting specification requirements, Energy Star, ARI, etc.
Airflow (minimum CFM) is also a key requirement for proper performance and rating, see previous
section.
Line Set Information – Factory charge is set to include enough refrigerant for 10ft (3 meters) of line set and the
forced air coil. If a line set of more than 10ft is used, additional R-410A refrigerant is required to be added to the system. Added amount of refrigerant needed is based upon 0.5oz per ft for 3/8” and 1.0oz per ft for 1/2" liquid lines.
Tube diameters and lengths for the line set are determined using the table on the following page. The suction lines must be insulated. When handling the line set, ensure that no kinks occur when bending the tubes into position. If one of the tubes happens to kink and it cannot be fully removed. The tube must be replaced; a kink in a tube will adversely affect system performance.
When installing the line set, it is imperative that the lines do not come in direct contact with any other surfaces. Adhering to this practice will further reduce any changes of compressor vibration transmitting into other areas of the building. When hangers are necessary; use hangers that incorporate isolation sleeves. Depending upon the length of tubing used, it is possible
Refrigerant Installation Practices – The line sets, recharging, and charge verification must be done by a
professional/licensed refrigeration technician. Industry standard and proper cleaning, nitrogen flow, brazing techniques, and leak verification must be followed with this installation. Brazed connections points on both the compressor side and air coil side of the line set is required. It is critical that 2-3 psi of nitrogen be circulated through the system in order to prevent internal oxidation. Low silver phos-copper braze alloy shall also be used on all brazed connection points.
Before brazing, wrap the service valves with a heat sink to prevent damage caused by excessive heat. This unit
is shipped with a factory charge, DO NOT open the service valves until the line set has been leak tested, purged, and evacuated. Depending upon the length of the line set, copper adapters may be needed to
accommodate larger diameter tubing.
Proper evacuation (500 microns) must take place prior to opening the main unit ball valves.
Once the initial charge level has been set, the final charge will then need to be fine tuned based upon the
subcooling and superheat chart.
09/29/2010 19 NI501
Page 22
A
A
A
Line Set Size Information
Model
10 Feet 20 Feet 30 Feet
Suction Liquid Suction Liquid Suction Liquid
020 ¾” ” ¾” ” ¾” ⅜” 026 ¾” ” ¾” ” ¾” ⅜” 033 ¾” ” ¾” ” ¾” ⅜” 040 ¾” ” ¾” ” ¾” ⅜” 052 ” 062 ” ½” ” ½”
See specification chart, page 3, or unit nameplate for factory charge. As stated earlier, this represents the furnished air coil and 10-foot line set. For additional line set length and charge “tweaking” field add as required, see pages 18, 21 and 22.
Forced Air Coil – Reference Information
Cased and Uncased Air Coil Dimensions
Uncased
Model Number
RT-SE-020 21.00" 17.00" 12.50" 17.50" 21.50" 15.75" 19.75" 16.25" 20.25" 14.50" RT-SE-026 21.00" 17.00" 12.50" 17.50" 21.50" 15.75" 19.75" 16.25" 20.25" 14.50" RT-SE-033 21.00" 21.00" 16.50" 21.25" 21.50" 19.50" 19.75" 20.25" 20.25" 18.50" RT-SE-040 21.00" 21.00" 16.50" 21.25" 21.50" 19.50" 19.75" 20.25" 20.25" 18.50" RT-SE-052 21.00" 24.00" 20.50" 25.50" 21.50" 23.75" 19.75" 24.25" 20.25" 21.625" RT-SE-062 21.00" 24.00" 20.50" 24.50" 21.50" 22.75" 19.75" 23.50" 20.25" 21.625"
Coil
Depth
Uncased
Coil
Width
Uncased
Coil
Height
Cabinet
Width "F"
Cabinet
Width "S"
- Includes TXV
- ¾” MPT primary and secondary drain connections
- Liquid line connect =
- Suction line connections: 1.5 to 3.0 ton = ¾”
4.0 to 5.0 ton = ⅞”
09/29/2010 20 NI501
Leaving
ir Width
"L"
Leaving
ir Depth
"P"
Entering
ir Width
"W"
Entering
Air Depth
"D"
Cabinet
Height
"H"
Page 23
Condensate Drain
Typical condensate drain installation, shown below. The droop in the internal hose should be considered when planning the drain installation.
If there is no nearby floor drain, a condensate drain pump must be used. See accessory parts list in the back of this manual.
Leak Testing – The line set must be pressurized and checked for leaks before evacuating and charging the unit.
To pressure the line set, attach refrigerant gauges to the service ports and add nitrogen until the pressure reaches 60-90 psig. Never use oxygen or acetylene to pressure test. Use a halogen leak tester or a good quality bubble solution to detect leaks on all connections made in the field. Check the service valve ports and stem for leaks. If a leak is found, repair it and repeat the above steps. For safety reasons do not pressurize system above 150 psig. The system is now ready for evacuation and charging.
System Evacuation – Ensure that the line set and air coil are evacuated before opening service valves to the
split unit. The line set must be evacuated to at least 500 microns to remove the moisture and air that may still be in the line set and coil. Evacuate the system through both service ports to prevent false readings on the gauge because of pressure drop through service ports.
09/29/2010 21 NI501
Charging Procedure
Page 24
Charging the System – After purging and evacuating the line set, fully open the service valves
counterclockwise. Add the previously calculated R-410A (liquid) into the liquid line service port. Never add liquid refrigerant into the suction side of a compressor. Start the unit and measure superheat and subcooling. Keep adding refrigerant until the unit meets the superheat and subcooling values on Unit Operating Conditions chart.
Superheat and Subcooling
Comments
1. This is a two TXV system – heating, internal to the main cabinet at the water coil refrigerant entrance
and cooling, within the plenum air coil at the air coil liquid entrance.
2. First begin in heating and check superheat associated with the TXV at the water coil (evaporator) as
follows.
3. Depending upon findings and requirement for adjustment, next check subcool and superheat in cooling.
Determining Superheat
1. Measure the temperature of the suction line at the point where the expansion valve bulb is clamped.
2. Determine the suction pressure in the suction line by attaching refrigeration gauges to the schrader
connection on the suction side of the compressor.
3. Convert the pressure obtained in Step 2 to the saturation temperature by using the R-410A
Pressure/Temperature Conversion Chart on page 23.
4. Subtract the temperature obtained in Step 3 from Step 1. The difference is the amount of superheat for
the unit. Refer to Unit Operating Conditions for superheat ranges at specific entering water conditions.
Superheat Adjustment
1. Remove the seal cap from the bottom of the valve.
2. Turn the adjustment screw clockwise to increase superheat and counterclockwise to decrease superheat.
One complete 360° turn changes the superheat approximately 3-4° F. regardless of refrigerant type. You may need to allow as much as 30 minutes after the adjustment is made for the system to stabilize.
3. Once the proper superheat setting has been achieved, replace and tighten the seal cap. Warning: There
are 8 total (360°) turns on the superheat adjustment stem from wide open to fully closed. When adjusting the superheat stem clockwise (superheat increase) and the stop is reached, any further clockwise turning adjustment will damage the valve.
09/29/2010 22 NI501
Page 25
Determining Subcooling
1. Measure the temperature of the liquid line on the small refrigerant line (liquid line) feeding the air coil
cabinet.
2. Measure the liquid line pressure by attaching refrigerant gauges to the schrader connection on the liquid
line service valve.
3. Convert the pressure obtained in Step 2 to the saturation temperature by using the R-410A
Pressure/Temperature Conversion Chart.
4. Subtract the temperature in Step 1 from the temperature in Step 3. The difference will be the subcooling
value for that unit. Refer to Unit Operating Conditions chart for subcooling ranges at specific enter water conditions.
Unit Operating Conditions* – First Stage
Entering
Water
Temp °F
50 70 90
Water
Flow
GPM/Ton
Suction
Pressure
psig
Discharge
Pressure
psig
Cooling – No Desuperheater
Suction
Pressure
psig
Discharge
Pressure
psig
Superheat Subcooling
Water Temp
Rise °F
Air Temp
Drop °F
Entering
Water
Temp °F
50 70 90
Water
Flow
GPM/Ton
Suction
Pressure
psig
Discharge
Pressure
psig
Heating – No Desuperheater
Suction
Pressure
psig
Discharge
Pressure
psig
Superheat Subcooling
Water Temp
Drop °F
Air Temp
Rise °F
Unit Operating Conditions* – Second Stage
Entering
Water
Temp °F
50 70 90
Water
Flow
GPM/Ton
Suction
Pressure
psig
Discharge
Pressure
psig
Entering
Water
Temp °F
50 70 90
NOTE: Cooling performance based on entering air temperatures of 80° F DB, 67° F WB.
Heating performance based on entering air temperatures of 70° F DB. * These are nominal expected conditions, will vary from model to model. Refrigeration technician must use his own experience and
judgment to verify proper charge and proper setting of TXV. However, TXV for Geo systems must be set for a balance between heating and cooling.
Water
Flow
GPM/Ton
Suction
Pressure
psig
Discharge
Pressure
psig
Cooling – No Desuperheater
Suction
Pressure
psig
Heating – No Desuperheater
Suction
Pressure
psig
Discharge
Pressure
psig
Discharge
Pressure
psig
Superheat Subcooling
Superheat Subcooling
Water Temp
Rise °F
Water Temp
Drop °F
Air Temp
Drop °F
Air Temp
Rise °F
DB
DB
DB
DB
09/29/2010 23 NI501
Page 26
PRESSURE
(PSIG)
60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96
98 100 102 104 106 108 110 112 114 116 118 120 122 124 126 128 130 132 134 136 138 140 142 144 146 148 150 152 154 156 158 160 162 164 166 168 170 172 174 176 178
TEMP
°F
8.5
9.9
11.2
12.5
13.8
15.1
16.3
17.5
18.7
19.8
21.0
22.1
23.2
24.3
25.4
26.5
27.5
28.6
29.6
30.6
31.6
32.6
33.5
34.5
35.4
36.4
37.3
38.2
39.1
40.0
40.9
41.7
42.6
43.4
44.3
45.1
45.9
46.7
47.5
48.3
49.1
49.9
50.7
51.5
52.2
53.0
53.7
54.5
55.2
55.9
56.6
57.4
58.1
58.8
59.5
60.2
60.8
61.5
62.2
62.9
Pressure/Temperature Conversion Chart for R-410A
PRESSURE
(PSIG)
180
182 184 186 188 190 192 194 196 198 200 202 204 206 208 210 212 214 216 218 220 222 224 226 228 230 232 234 236 238 240 242 244 246 248
250
252 254 256 258 260 262 264 266 268 270 272 274 276 278 280 282 284 286 288 290 292 294 296 298
TEMP
°F
63.5
64.2
64.8
65.5
66.1
66.8
67.4
68.0
68.7
69.3
69.9
70.5
71.1
71.7
72.3
72.9
73.5
74.1
74.7
75.3
75.8
76.4
77.0
77.5
78.1
78.7
79.2
79.8
80.3
80.9
81.4
81.9
82.5
83.0
83.5
84.1
84.6
85.1
85.6
86.1
86.6
87.1
87.7
88.2
88.7
89.2
89.6
90.1
90.6
91.1
91.6
92.1
92.6
93.0
93.5
94.0
94.5
94.9
95.4
95.8
PRESSURE
(PSIG)
300
302 304 306 308 310 312 314 316 318 320 322 324 326 328 330 332 334 336 338 340 342 344 346 348 350 352 354 356 358 360 362 364 366 368
370
372 374 376 378 380 382 384 386 388 390 392 394 396 398 400 402 404 406 408 410 412 414 416 418
TEMP
°F
96.3
96.8
97.2
97.7
98.1
98.6
99.0
99.5
99.9
100.4
100.8
101.2
101.7
102.1
102.5
103.0
103.4
103.8
104.2
104.7
105.1
105.5
105.9
106.3
106.7
107.2
107.6
108.0
108.4
108.8
109.2
109.6
110.0
110.4
110.8
111.2
111.6
112.0
112.3
112.7
113.1
113.5
113.9
114.3
114.7
115.0
115.4
115.8
116.2
116.5
116.9
117.3
117.6
118.0
118.4
118.7
119.1
119.5
119.8
120.2
PRESSURE
(PSIG)
420
422 424 426 428 430 432 434 436 438 440 442 444 446 448 450 452 454 456 458 460 462 464 466 468 470 472 474 476 478 480 482 484 486 488
490
492 494 496 498 500 502 504 506 508 510 512 514 516 518 520 522 524 526 528 530 532 534 536 538
TEMP
°F
120.6
120.9
121.3
121.6
122.0
122.3
122.7
123.0
123.4
123.7
124.1
124.4
124.8
125.1
125.4
125.8
126.1
126.5
126.8
127.1
127.5
127.8
128.1
128.5
128.8
129.1
129.4
129.8
130.1
130.4
130.7
131.1
131.4
131.7
132.0
132.3
132.7
133.0
133.3
133.6
133.9
134.2
134.5
134.9
135.2
135.5
135.8
136.1
136.4
136.7
137.0
137.3
137.6
137.9
138.2
138.5
138.8
139.1
139.4
139.7
PRESSURE
(PSIG)
540
542 544 546 548 550 552 554 556 558 560 562 564 566 568 570 572 574 576 578 580 582 584 586 588 590 592 594 596 598 600 602 604 606 608
TEMP
°F
140.0
140.3
140.6
140.9
141.2
141.4
141.7
142.0
142.3
142.6
142.9
143.2
143.5
143.7
144.0
144.3
144.6
144.9
145.1
145.4
145.7
146.0
146.2
146.5
146.8
147.1
147.3
147.6
147.9
148.2
148.4
148.7
149.0
149.2
149.5
09/29/2010 24 NI501
Page 27
Electrical Hookup
WARNING
DISCONNECT ALL ELECTRICAL POWER BEFORE ELECTRICALLY CONNECTING OR SERVICING THE UNIT. FAILURE TO DISCONNECT THE ELECTRICAL POWER BEFORE WORKING ON THIS PRODUCT CAN CREATE A HAZARD LEADING TO PERSONAL INJURY OR DEATH.
Line Voltage
The nameplate and/or Installation and Operating Manual specification page provides RLA, LRA, and total amps requirement. Select the proper wire size to comply with your type of wire routing and NEC field wiring requirements.
If this unit includes AUX EL module, its own nameplate provides kW and current/voltage requirement.
The field power supply connection is at the compressor contactor, at the end of the line voltage control box.
Disconnect – field provided external safety disconnect is required, see nameplate max amps. Loop pumps – the loop pump station can be powered at the TB above the contactor. 5-amp fusing is included,
left of terminal block.
Grounding – route and install the proper size ground conductor between the ground lug above the compressor
contactor and the building service entrance panel ground bus. This must be a conductor wire size according to NEC code for the total amp rating of the installed model. The conduit is not sufficient ground conductor.
WARNING
USE ONLY COPPER WIRE FOR CONNECTION TO THE CIRCUIT BREAKER TERMINALS AND INSIDE THIS PRODUCT’S CABINET.
WARNING
TO AVOID THE RISK OF ELECTRIC SHOCK OR DEATH, WIRING TO THE UNIT MUST BE PROPERLY GROUNDED. FAILURE TO PROPERLY GROUND THE UNIT CAN RESULT IN A HAZARD LEADING TO PERSONAL INJURY OR DEATH.
09/29/2010 25 NI501
Page 28
EZGEO Controller
EZGEO Features
Review attached HC112 HELPS document which lists the various characteristics and capability of this controller product.
Application
The EZGEO controller is standard on all Northern Heat Pump models.
Even more specific, this model factory default is mode D and SW OVER = position 1 (-15° OT).
WARNING
IF THERE IS NO AUTOMATIC STANDBY (GAS) OPERATING FROM THE EZGEO FURNACE TB-W, THE SW OVER DIAL SWITCH MUST BE SET TO Ø POSITION. THIS STATEMENT RELATES TO MODES B, C, AND D. ONCE THERE IS A LOGIC TRANSFER TO SB, THE FURNACE MUST FINISH OUT ROOMSTAT-W. THUS THERE IS NO FURNACE OR NO HEAT THE SYSTEM WILL BASICALLY BE LOCKED UP WAITING FOR HEAT ENERGY TO SATISFY THE THERMOSTAT.
Room Thermostat
This is general hookup information, before proceeding review previous section – EZGEO Controller – and
determine operating mode for this particular application.
Use conventional (not heat pump with O and compressor Y) heat/cool. This controller is designed to operate
from a basic 1H/1C thermostat. 2H/2C can be used (not recommended), see next section for comments relating to W2 and Y2 from the roomstat.
It can be mechanical, digital, power robbing, battery operated, setback, etc. If required, set heat anticipator to
0.2. If electronic/digital stat, setup may ask for “cycles per hour”. Since this is a heat pump product, efficiency relates to long run time, recommend small number (2 cycles per hour).
Note 1: Do not (even with heat pump) use a heat pump thermostat. Note 2: If programmable roomstat has external sensors, make sure setup is for display monitor only and
any programming for these sensors that has to do with interrupting any output functions, ODT,
auxiliary, setback, etc. are not active or program disabled.
Connect the standard R, W, G, Y stat terminals to the EZGEO board upper left terminal block. If the specific roomstat requires common or C, this can be picked up from a tab on the board bottom right.
NOTE
The installer must be familiar with the manufacturer’s low voltage wiring terminology, screw terminal terminology/colors, etc. This manufacturer’s terminology must be related to Northern Heat Pump’s screw terminal identification within this controller. The intent of this instruction
manual is not to train each installer on the terminology related to the specific product you are
installing.
09/29/2010 26 NI501
Page 29
Utility Load Control
Bottom 2-screw terminal block marked blue and blu/wht. Remove the jumper and extend the two wires to the utility furnished control device. For electric energy operation (off-peak) the two blue wires represent contact
closure as shipped. Do not apply external voltage or external power to the blue wires, they are simply
looking for a closed contact during off-peak.
The maximum “AC noise” on the blue wire is 5 volts, peak to peak. The blue/white TB is actually
common and if grounding is proper as suggested in the next paragraph, this should dampen any effect. But it is always good practice to run these wires separate from any current carrying line voltage Romex or other conductors.
One load control wire pair handles both winter and summer interrupt. If load control reverse logic is required, a “closed to interrupt contact” can be connected to SB SW to
COM. Another way to resolve this issue is through the use of an interposing relay. Consult factory if an interposing relay is required.
If load management interrupt does not apply, simply leave the blue wires jumpered.
Grounding
Caution – 24 volts common grounding – the installer must determine whether the furnace fan center
COM screw terminal has a good ground bond (not simply furnace skin). If the fan center COM is not adequately grounded, use a green wire from the EZGEO lower right C tab to a ground bond.
Optional – Alarm Output Annunciator
As shown on hookup drawing NH501, there are provisions for an external buzzer and LED device. When the Geo HP declares a fault or dead compressor alarm, this device will sound an audible and turn on the LED light.
The 2-wire hookup can be extended as much as 100 feet (30 meters) using 18 or 20 gauge wire. The audible can be turned off with the pushbutton. But if the system is not repaired within 4 hours the
audible will again sound.
The LED light will continue until the system is repaired and power off reset. The system may recover on its own, but the LED will continue indicating there “was” a fault situation.
This LED is only turned off by a power off reset at the disconnect.
Order R-AL-RS-1
09/29/2010 27 NI501
Page 30
Visual example only – the exact connections will depend upon operating mode. The ST air supply temperature probe pictured above is not standard equipment on the split unit.. Review previous section – EZGEO Controller.
09/29/2010 28 NI501
Page 31
Temperature Sensors
Outdoor Sensor (OT) – extend sensor to an outdoor location properly
sampling the outdoor temperature. Select a location away from direct sunlight and where the sensor will not pick up false temperature from the heat pump outdoor unit, refrigerant line sets, dryer vent, reflection off of steel siding, etc. Do not install the sensor in any type of enclosure, as this will falsely trap and pick up radiant sun temperature. Mount the sensor horizontally on the structure using the screws provided.
Duct Sensor (ST) – install in the warm air plenum at least 12” (31 cm) above heat pump A-coil. Locate to one
side so the air coming through the A-coil passes over the sensor tip. The ST sensor does not have an end cap; the small black electronic part just within the tube end is the actual sensor. The only purpose of the metal tube is the protection of the sensor. Best results are obtained by positioning the sensor so the black tip is directly in the air leaving the A-coil. This air is most often towards the edges of the plenum.
Other Sensor Related Comments
If additional cable length is required, you must use the following rules for extending the cable.
Use unshielded (low capacitance, preferred twisted) 3 or 4-wire low voltage cable. 50 feet (15 meters) is maximum (total). Do not, under any circumstances, use leftover wires within the normal thermostat cable. Route the sensor cable making sure you do not crimp, cut, staple, or damage the cable in any way. Keep sensor cables at least 12” (31cm) away from any line voltage wiring, romex, etc.
For easy sensor cable disconnect and reconnect, the WarmFlo board has a plug-in 4-place terminal block. Before disconnecting, you will notice two red wires are under the red screw and two white wires is under the COM screw. The black wire represents the data information from each sensor and must be connected to the appropriate OT or ST screw.
The sensor is polarity specific and is sensitive to incorrect voltage. It must be protected from static voltage, etc. Do not cross connect or inadvertently short out sensor wires with power on. Permanent destruct damage may result.
09/29/2010 29 NI501
Page 32
Gas Furnace Hookup – Mode D
See hookup drawing NH501, the gas furnace wiring is at the EZGEO board bottom left terminal block.
Gas Furnace (or Oil with Fan Center Terminal Wiring Strip)
The control board lower left 6 terminal screw points are used for the furnace interface. However, all 6 are not necessarily used, based on type of furnace, blower, burner, etc.
24-volt power – for the Split unit (mode D) the power for the EZGEO Controller comes from the gas furnace
transformer.
Basic furnace, PSC blower motor – in addition to R and C above, add W and G.
Variable speed blower, ECM motor, single Y – in addition to the above add Y to Y.
Variable speed blower, ECM motor, available Y1 and Y2 speeds – in addition to the above, the control
board Y goes to furnace Y1 and control board Y2 goes to furnace Y2.
2-stage or variable stage burner – if mode B, C, D and 2-stage furnace burner, program the gas furnace for
high burner internal control (next section also has other options for stat W2).
ECM blower motor speed/setup – the gas furnace blower is setup identical to an air conditioning/gas furnace
arrangement. See model number specification page and determine Y1 and Y2 CFM requirements for this Geo HP unit. Relate this directly to an air conditioner CFM requirement or CFM per ton. Set the gas furnace bit switches (or setup technique) for the ECM blower speed/CFM to deliver the proper airflow when the Geo HP Y1 or Y2 stages are active. These are the direct hardware connections at the furnace terminal block – Y1 and Y2.
ST Sensor – Installed above A-coil, see page 29.
09/29/2010 30 NI501
Page 33
Additional Hookup or Special System Equipment Concerns
Additional Room Thermostat Connection Points
On the EZGEO board, upper left, are three optional control tabs – W2, E-GAS, and Y2. These can be used for troubleshooting or emergency full output energy or with a conventional 2H/2C room thermostat. However,
when considering energy efficiency these points connected to a 2H/2C thermostat is not recommended.
W2 – mode B, this conditions AUX EL all stages on, with compressor in Y2. E-GAS – this conditions the system to standby or transfers the room thermostat W to gas furnace. This
is active for all modes, it should never be used for mode A when there’s no gas furnace connected.
Y2 – in cooling, this forces compressor to full capacity. It can be an override to the cooling sequence
condition shown in Figures 1, 2, 3, 4.
Special Oil Furnace Comment
This controller is designed to interface directly with a furnace fan center containing 24-volt transformer (40VA
or larger), blower relay, and a “W” function to operate the furnace. If this installation is for an oil furnace with
only oil control “T and T” terminals, a special fan center will need to be added with an isolation relay at the “W” terminal so only isolated contacts are connected to the oil burner master control “T and T”. Another choice is to order EE-5053 relay with accompanying HD001 instruction sheet.
Remotely Located Standby Override Switch
On the bottom of the board is an “SB SW” tab. Using an external switch between this “SB SW” tab and a common tab provides the same function as the two-position system selector switch on the front of your EZGEO control panel. In this configuration, either of these switches allows the homeowner to manually force the HVAC system to utilize a fossil fuel system. A closure of the external switch is the equivalent to the system selector switch being in the “up” or “standby” position.
Important note on cooling mode: To operate in cooling mode, neither of the switches can be in the override
position. Thus, the selector switch on your EZGEO control panel MUST be in the “down” position AND the external switch must be in “heat pump” or “normal” position in order for the heat pump to operate in cooling mode. If one or both of these switches are not the proper positions, cooling will not occur.
Load Control, Other Products or Hardware
If there is a need to “pass on” the utility load control receiver function to other heating equipment, radiant floor boiler, peak interrupter, etc; there is an isolated contact on this control board. Locate tabs COM/EL/SB. In the electric mode there is an isolated contact between COM and EL. This contact is for low voltage only, 1-amp maximum.
Note: There may be a 1 or 2 minute delay between this relay contact action and the actual load control
Optional – Alarm Output Annunciator
As shown on hookup drawing NH501, there are provisions for an external buzzer and LED device. When the Geo HP declares a fault or dead compressor alarm, this device will sound an audible and turn on the LED light.
receiver. This delay coincides with various blower purge functions.
Note: This contact also follows front panel standby switch and all other standby functions such as SOT-
S, etc.
The 2-wire hookup can be extended as much as 100 feet (30 meters), use 18 or 20 gauge wire. The audible can be turned off with the pushbutton. But if the system is not repaired within 4 hours the
audible will again sound.
The LED light will continue until the system is repaired and power off reset. The system may recover on its own, but the LED will continue indicating there “was” a fault situation.
This LED is only turned off by a power off reset at the disconnect.
Order R-AL-RS-1
09/29/2010 31 NI501
Page 34
Field Setup or Programming
It is extremely important the installer properly goes through this section and sets up the various switches to match the installation. Again, refer back to EZGEO Controller section for further details on these setups.
Warning: Power-down reset required whenever changing any of the switch positions on the back side
of the board.
Select Configuration or Hardware MODE – since this manual is dedicated to Split model, must be set on D.
D – Split/Gas
09/29/2010 32 NI501
Page 35
Switchover Temperature (SW OVER)
This switch is shipped from the factory with a square “GAS” label. This label should be removed ONLY if a secondary furnace is present and active in the system. The installer should remove the label and adjust this switch only after reading this manual and understanding the operation of the switch. Select the OT temperature to interrupt the compressor and transfer to the sequence shown on applicable mode Figures 2, 3, 4. This only applies when a gas furnace is connected. For all non-SB configurations must be set to 0 position (disable).
0 = Disable 4 = 5° F 1 = -15° F 5 = 10° F 2 = -10° F 6 = 20° F 3 = 0° F 7 = 30° F
Stat Override Timer (SOT)
Again, see the appropriate mode Figures 1, 2, 3, 4 for the sequence action after the SOT timeout (end). The intent of the SOT is to take care of very unusual heat/cool conditions or building matching situations, the general sequence relating to OT temperature should take care of proper thermostat cycling without ever reaching SOT timeout (end). Thus, it is recommended the SOT be a high number.
0 = 30 minutes 2 = 180 minutes 1 = 90 minutes 3 = 270 minutes
Efficiency Setting (Front Panel)
This applies to AUX EL module or supplementary heating only, mode B. With this dial switch the homeowner
can boost the default 110° F (43° C)ST target temp.
Normal = setup value (105° F) (40.5° C) A = +5° F B = +10° F
Information
Front panel decal showing efficiency dial and LED’s.
Gas Furnace CFM
See previous page on gas furnace hookup for proper programming of ECM motor for the required CFM output.
Outdoor Temp (OT) Factory Default Settings
Default
ST target temp 96° F (37°C) Dead compressor ST 85° F (29°C) OT temp, heating – HI > 20° F (-7°C) OT temp, heating – LO < 5° F (-15°C) OT temp, cooling – HI > 80° F (27°C)
09/29/2010 33 NI501
Page 36
Operation Indicators
Front Panel LED’s
- Hi-limit – when the AUX EL hi-limit probe (automatic reset or manual reset) opens this top red
LED is on. The electric elements will be interrupted via a safety relay circuit whenever this HL LED is illuminated (mode B only).
- PWR ON – indicates good fuse and 24-volt power source from the furnace terminal block.
- See below for bad sensor indication.
- Status mode – in some ways this can be a utility load control indicator, but there are additional
programmable functions which cause this unit to go to standby (see HC112 EZGEO section and sequence charts).
- In addition this LED provides monitor for the two alarm conditions.
Dead compressor – fast pulsing, 1/10 second ICM fault – slow pulsing, 1 second
- HP-Y1 – the output “Y” screw terminal is active at 24 volts high. This provides the “Y” input to
the ICM compressor monitor board. Compressor will react as a function of this ICM safety board.
- HP-Y2 – the output “Y2” screw terminal is active at 24 volts high.
- T-stat call – the room thermostat W or Y is active or 24 volts high.
- Gas call – the furnace “W” or terminal block feeding furnace W, 24 volts high.
Override Switch – the front panel slide switch (very similar to standard Electro-Mate DFC) is a direct hardware
disabling of the HP-Y1 and electric elements functions. The room thermostat heat call wire or function is directly controlling the fossil fuel or gas furnace. This function can also be on a remote switch, see previous statement for “SBSW” tab.
WARNING
THIS FRONT PANEL MANUAL OVERRIDE SWITCH IS A HARDWARE DIRECT TO GAS FURNACE FUNCTION. THUS THERE ARE NO BLOWER PURGE CYCLES. IF THE ELECTRIC ELEMENTS ARE ON AND HOT WHEN SWITCHING TO OVERRIDE AND IMMEDIATELY ALLOWING THE GAS FURNACE, OVERHEAT ON THE ELECTRIC ELEMENTS AND POTENTIAL ELECTRO-MATE MANUAL RESET IS POSSIBLE. THIS FRONT PANEL OVERRIDE SWITCH SHOULD ONLY BE ACTIVATED WHEN THERE IS NOT A ROOMSTAT HEAT CALL.
Note: This switch must be in the “normal” position during cooling.
ICM board (inside) – fault LED pulses with last open limit condition, see next page.
Sensor Monitor Indicators – in addition to using PC software to readout the temperature sensors, there is a
built-in go/no-go type monitor visible on the green PWR ON second from the top LED.
If there is detection of miswired or totally inoperative sensor, this LED has a blinking or pulse
mode. By checking the pulsing pattern, the appropriate sensor can be identified.
OT sensor - 100 ms blink every second ST sensor - two, 100 ms blinks every second Both bad - ½ second on, ½ second off, alternating.
09/29/2010 34 NI501
Page 37
Power On, Startup
Before applying power to the heat pump, check the following items:
1. Water supply plumbing to the heat pump is complete and operational.
2. Low voltage wiring of the thermostat and any additional control wiring is complete.
3. Set thermostat to the OFF position.
4. All high voltage wiring is correct including fuses, breakers, and wire sizes.
5. The heat pump is located in a warm area above 50°F [10°C]. Starting the system with low ambient
temperature conditions is more difficult.
6. Manually open water valve on well system to check flow. Never operate the system without adequate
source water ground loop or open loop supply.
7. You may now apply power to the unit. A 1 to 5 minute delay on power up is programmed into the heat
pump before the compressor will operate. This delay prevents short cycling of the unit.
During this time the blower may be active. Verify water flow rate and temperature of the source side flow to be at recommended levels.
8. The source side water flow rate is at the required level, see specification page. Low water temperature
starting may require flow reduction until the system is up to operating temperature.
The following steps will assure that your system is heating and cooling properly. After the initial time-out period is completed the heat pump is now ready for operation. Note: EZGEO, HC112, sequence charts (mode A, B, C, D) determine compressor staging.
1. Place the thermostat to the “HEAT” position. Turn the thermostat up to activate a call for heat. The
compressor should start.
2. After the unit has run for about 3 minutes, check the source side supply and return water temperature. A
water temperature decrease is normal in the heating mode, but the specific operating water temperature
can effect the water flow rate (GPM) stated in the specification table.
3. Verify warm air temperature rise and loop source water decrease are approximately as stated in the
specification table, page 3.
4. Turn the thermostat to the off position. The compressor will shut down in a few seconds.
5. Place the thermostat in the “COOL” position. Next turn thermostat down to active a call for cooling.
The compressor will start after a 5 minute anti-short cycle period from its last shutdown.
6. After the unit has run about 3 minutes, check the source side supply and return water temperatures. A
water temperature rise is normal in the cooling mode.
7. Verify cool air temperature drop and loop source water increase are approximately as stated in the
specification table, page 3.
8. Instruct the owner on correct operation of the thermostat and heat pump system.
09/29/2010 35 NI501
Page 38
Operational Tips
ICM Board – The ICM board performs the functions controlling the compressor operation: system lockout,
compressor anti-short cycle, and a five minute delay after power is applied.
The control will begin the 5-minute time delay upon a Y call from the thermostat. After the time delay expires, the compressor contactor will be energized as long as the high and low pressure switches are closed. If either switch is open after the delay expires, the compressor will not energize. If either switch opens while the compressor is energized, it will de-energize immediately and begin the anti-short cycle delay. The compressor will not be allowed to turn on again until the anti-short cycle delay expires and both pressure switches are closed. The flow switch will have a 30-second bypass timer in which the control will ignore an open flow switch for the first 30 seconds. If the flow switch remains open after the 30-second bypass timer expires, the unit will de-energize the compressor and begin the anti-short cycle delay. If the control experiences three high pressure, low pressure, or flow switch faults in a 60-minute period, it will lock out the compressor and energize the fault output. A manual reset of power will be required to reset the lockout condition.
Problems that could cause a lockout situation include:
1. Water flow problems
2. Air flow problems
3. Internal heat pump operation problems
The control has a status LED to indicate which type of fault or lockout has occurred. If a high pressure fault or lockout occurs, the status LED will blink once. If a low pressure fault or lockout occurs, the status LED will blink twice. If a flow switch fault occurs, the status LED will blink three times.
The anti-short cycle function puts a time-out period of 5 fixed ±20% minutes on the compressor before re-
starting. This function protects the compressor from repeated on/off operation in the event of a loose wire or faulty controller.
4. Cold ambient air temperature conditions
ICM Fault Code LED
1 blink = high pressure cutout (550 PSI) 2 blink = low pressure cutout (40 PSI) 3 blink = Flow switch open
CAUTION
The front panel override switch should not be changed during a heat call. There are no purge
cycles when manually changing the override switch with an active heat call and could cause an undesired overheat situation
High and Low Pressure Switches – The heat pump is equipped with both high and low pressure switches that
shut the unit off if the refrigerant pressure exceeds 550 PSI or goes below 40 PSI. The freeze protection switch (on open loop systems) will also activate the lockout at 40 PSI in the heating mode to protect the water coil against freeze rupture. Do not reset a well water system in the heating mode without first verifying water flow.
DO NOT reset the system more than once. Repeated resetting of the lockout can cause serious damage. If same lockout occurs contact your service dealer immediately.
Low Pressure
Cut-out pressure 40 PSI 550 PSI 1 blink = high pressure cutout
Cut-in pressure 65 PSI 420 PSI 2 blink = low pressure cutout
09/29/2010 36 NI501
Pressure Switch Settings
High Pressure
Switch
Switch
Fault Code LED
Page 39
Troubleshooting – EZGEO Control
Comment – Split, mode D, does not required ST sensor. Certain items below only relate to modes B and C. Sensor Temperature Calibration – both remote sensors are digital electronic and factory calibrated. Normally
these do not require field calibration or verification. However, if sensor temperature error is determined, use special PC software disc and PC serial port cable. The PC screen has direct readout of both temperatures, allows a visual determination of WarmFlo internal temperature settings, and can be used to offset either temperature sensor for troubleshooting and demonstration purposes. This is especially valuable during summer installation.
Override, “E” Tab Input – during a normal roomstat heat call and W2 is jumpered to W, it brings on all four
stages and essentially bypasses any temperature sensing or stage modulation functions. In other words, with an W2 input (still need the normal W stat input) this is simply a turn-on/turn-off device.
During a normal roomstat heat call and E-GAS is jumpered to W, it forces a standby (SB) action.
During a normal roomstat cool call and Y2 is jumpered to Y, it forces a compressor to full capacity.
SOT bypass – factory checkout procedure can jumper out (shorten time) this timer. Bad sensor, safety – if the internal logic detects open sensor wire, incorrectly wired sensor, or some bad sensor
transmitted value conditions; the green LED reverts to a pulsing mode. Basically the appropriate sensor is set internally to a 0° value and the WarmFlo main board only allows stage 1 and stage 2 on.
- OT sensor – approximately 1/10 second blip every ½ second
- ST sensor – two, 1/10 second blips every ½ second
Bad sensor, operating default condition – the detection of bad sensor forces the controller to a fixed stage
operation.
Internal fuses – the internal desuperheater pump and the source loop pump station terminal block have internal
fuses. These are located above the compressor contactor.
Troubleshooting/Repair Helps
1. This EZGEO controller contains several interference suppression components, but as an electronic logic
2. The terminal blocks for control wire hook-up are designed for a wire insertion and screw clamp down.
3. Use general heating system logic information and basic understanding of the terminal block wiring
4. The outdoor sensor must be located outdoors for this controller to correctly operate. Do not leave the
- Both bad – ½ second on and ½ second off, alternating
- ST sensor
Stages 1 and 2 on, stages 3 and 4 off (5 kW maximum) The PC screen reads “254” or “BAD”
- OT sensor
Set to a default of 2° F (-17° C), see Figures 1, 2, 3, 4 The PC screen reads “254” or “BAD”
- The external decal provides the fuse size and details.
product, unpredictable and unusual transients or interferences may sometimes cause strange results. If the EZGEO controller is “acting strange”, one immediate step would be power down reset. Simply turn off the 24-volt source power (probably furnace or air handler circuit breaker), when the green LED goes out, count to 10, and re-energize power supply.
If there is no wire connected and the screw is loose, the screw may not necessarily make a good electrical contact to the inside components. Example – if you are jumpering the thermostat terminals without thermostat wire connection or if you are attempting to measure voltage on the screw head, you may get erroneous or unpredictable results if the screw is not tightened down.
functions when measuring voltage to determine proper operation of this module.
outdoor sensor “hanging in conditioned space” and attempt to run this system. Note: OT sensor tip must be up.
09/29/2010 37 NI501
Page 40
Alarm/Fault Active
The status LED and alarm output continue until power-off reset. The EZGEO system will attempt to maintain room temperature or prevent freeze-up.
- Mode A – by definition, no backup, at each roomstat W cycle, compressor will retry.
- Modes B, C, D – with gas furnace standby roomstat W is transferred to gas furnace operation.
- Mode B, SW OVER = 0 – AUX EL will be active and do the heating.
- Cooling – same as mode A, each thermostat cycle will attempt a compressor.
Note: Do not repeatedly cycle the compressor and cause consecutive faults. This will result in permanent
compressor damage and perhaps void warranty. If the Geo system goes into a fault mode, it has already made three attempts to clear the limit condition, repeated cycling of the roomstat will not do any good, it will simply cause damage. Call for service.
Backup/freeze-up – the intent of modes B, C, D with either AUX EL or gas furnace is to prevent freeze-up. If
this Geo system is installed without backup (mode A) there is no secondary means of creating heat.
Correct use of mode selection – by definition modes B, C, D installation include gas furnace and/or AUX EL
module. If the system is setup in either B, C, D and there is no gas furnace and/or AUX EL freeze-up may still occur because the roomstat is assuming a heat source which will bring up the temperature to satisfy the roomstat.
WARNING
WHEN CONFIGURED WITH A GAS FURNACE AND/OR AUX EL (MODES B, C, D) IT IS THE USER’S RESPONSIBILITY TO HAVE CIRCUIT BREAKERS TURNED ON, GAS IN THE TANK, GAS VALVES OPEN, AN OPERATIONAL GAS FURNACE, ETC. THE EZGEO CONTROLLER CANNOT DETECT “NO GAS IN THE TANK”.
Overheat Plenum, Control Override
When AUX EL stages are not active, the ST sensor also control compressor functions. This also prevents compressor and gas furnace on at the same time (mode D/refrigerant coil in plenum).
- ST > 105° F – compressor Y2 turned off
- ST > 110° F – compressor off
Operation continues to the end of heat call cycle or if ST < 100° F (38° C) compressor Y2 will re-energize.
EZGEO Bypass
Behind the front panel hinged door the various wires from the EZGEO board terminate on a Geo standard terminology terminal block. If necessary to prevent building freeze-up, etc. the wires from the EZGEO board can be disconnected from this terminal block and the room thermostat (or another heat pump type roomstat) can be transferred to this terminal block to run the compressor/heat pump in an emergency mode.
- R to Y1 and Y2 – compressor high capacity and blower at full airflow.
- RV – can be left unterminated for heating (NHP concept design is reversing valve high during cooling)
- G – not needed.
- Fault – monitored output only, not needed.
Gas furnace only option, operating mode B, C, D – with EZGEO board disconnected, roomstat can go
directly to gas furnace W and appropriate blower terminals. This is assuming gas furnace has its own blower.
Front panel override switch – if mode is B, C, or D and gas furnace is active via EZGEO board with a
potential compressor problem (probably fault LED on) the front panel switch in the up position will transfer the roomstat to the gas furnace. Depending upon the blower configuration, it should follow with the functioning gas furnace, but local HVAC contractor needs to verify.
09/29/2010 38 NI501
Page 41
Troubleshooting – General
Problem Possible Cause Possible Solution
Unit does not run
Tripped breaker/blown fuse
Blown controller fuse Replace controller fuse. Replace with correct fuse.
Low voltage supply
Low voltage in circuit
Thermostat
Interruptible power Check incoming supply voltage
Thermostat
Reset circuit or replace fuse. Always check and use correct size
Contact local power company if voltage is below that specified for your unit
Check the 24 volt transformer for voltage less than 18 volts or possible burnout.
Set thermostat on "Cool" and lowest temperature setting and unit should run. Set thermostat on "Heat" and highest setting and unit should run. If in both cases the unit fails to run, thermostat could be wired incorrect or thermostat is faulty. To prove, disconnect thermostat wires on the unit and jumper between "Red", "Yellow" and "Green" terminals and unit should run.
Check settings, calibration and wiring and if thermostat has an anticipator set at 0.2
Hydronic pump runs but compressor does not or compressor short cycles
Wiring Check for loose or broken wires at compressor, capacitor or contactor
Blow fuse Replace controller fuse. Replace with correct fuse.
High or low pressure controls
Defective capacitor Check, if defective, remove and replace. Wire correctly.
Voltage supply low
Low voltage circuit Check 24 volt transformer for voltage under 18 volts or burnout.
Compressor overload open
Compressor motor grounded
Compressor windings open
Unit could be off on the high or low pressure cutout control. Check water GPM, ambient temperature and loss of refrigerant. If still failing to run, check for faulty pressure controls. Replace if needed.
If voltage is below minimum required, call local power company. Check compressor voltage for possible open terminal.
An internal compressor overload is used in all cases. If compressor is too hot, the compressor will not reset until cooled off. It may be defective or an open overload. Replace compressor.
Internal winding grounded to case. Replace the compressor. If burnt out, replace the liquid line filter drier also.
Check continuity of the windings with an ohm-meter. If windings are open, replace compressor and liquid line drier.
09/29/2010 39 NI501
Page 42
Unit Short Cycles
Thermostat
Improper thermostat location (e.g. near kitchen). Anticipator should be 1.0 or 1.2
Defective compressor overload, check and replace if necessary. If
Compressor overload
the compressor is running hot, it may be due to insufficient refrigerant charge.
Blow fuse Replace controller fuse. Replace with correct fuse.
Aqua stat The differential is set too close. Increase differential setting.
Wiring and controls Loose connection or control contactor defective.
Loop fluid Lack of pressure, temperature and/or quantity of water.
Insufficient cooling or heating
Loss of conditioned air
Thermostat
Airflow across fan coil
Refrigerant charge
Compressor
Reversing valve
Desuperheater
Check ductwork design or introduction of ambient air through windows and doors.
Improper thermostat location (e.g. near kitchen). Anticipator should be 0.2
Lack of airflow or improper distribution of air. Check motor speed and duct size. Also check filter for reduced air flow.
Low refrigerant charge causes inefficient operation. Adjust only after checking CFM and GPM
If discharge pressure is low and suction pressure too high, compressor is not pumping properly. Compressor needs to be replaced.
Defective valve creating bypass of refrigerant from discharge to suction side of compressor. When replacing reversing valve, direct heat away from valve and protect by wrapping in wet cloth.
Circuit (in-line fuse) should be disconnected in winter to allow full heat load to house.
Thermostat setting Check setting. Is it below room temperature?
Defective thermostat Check operations of thermostat. Replace if defective. No Response in Heating Mode
Wired incorrectly Check for loose, broken or incorrect wiring.
High aqua stat setting
09/29/2010 40 NI501
Heat pump is trying to heat water that is too hot. Reduce the setting on the aqua stat.
Page 43
Reversing valve does not
shift
Defective solenoid valve not energizing. Replace coil on valve.
Does Not Cool
(only heats)
Noisy Operation
Reversing valve does not
shift, valve is stuck
Aqua stat is set too low
Insufficient antifreeze
Compressor
Contactor
Rattles and vibrations
The solenoid valve is de-energized due to incorrect wiring at the unit or thermostat. Replace if valve is tight or frozen and will not move. Switch to cooling from heating a few times to help loosen valve.
Heat pump is trying to cool water too low. Increase setting on aqua stat.
Water is freezing in hydronic coil. Check antifreeze level and add if necessary to maintain proper freeze protection.
Make sure compressor is not in direct contact with cabinet. Cold surroundings can cause liquid slugging. Increase ambient temperature.
The "clattering" and "humming" noise in the contactor could be due to control voltage less than 18 volts. Check for low supply voltage, low transformer output or extra long runs of thermostat wires. If the contactor contacts are pitted, or corroded, or coil is defective, repair or replace.
Check for loose screws, panels or internal components. Tighten and secure. Copper piping could be hitting the metal surfaces, isolate if necessary.
Undersized ductwork will cause high airflow velocities and noisy
Water and airborne noises
operation. Excessive water through the water cooled heat exchanger will cause a squealing sound. Check for correct water flow for good operation and to eliminate noise.
Pump cavitation Purge air from closed loop system.
09/29/2010 41 NI501
Page 44
Accessories/Options
Fault/alarm external annunciator R-AL-RS-1 Fuse – source loop pump, 10A UFUSE1799 Fuse – desuperheater pump, 3A UFUSE1796 Open loop, freeze limit, 39° F (4° C), pipe mounted 6047 Sound vibration pad R-PAD-2735-1
Part Number
09/29/2010 42 NI501
Page 45
Electro-HELPS XIII
Page 46
Page 47
HELPS – EZGEO Controller
All functions and definitions will apply to all NHP models, see appropriate model or type. Use Installation Manual to determine which part of this Helps document applies.
This Electro Industries’ exclusive controller provides several installer and user-friendly functions for Geo heat pump applications. It will be helpful to grasp the EZGEO concept prior to studying the mode configuration charts and sequence of events.
First, this is a list of features/functions which are an integral part of this EZGEO system.
Geo source, forced air – EZGEO is standard on all Electro Industries’ models. Geo source, split – EZGEO is standard on all Electro Industries’ models. Room thermostat – conventional or commonly called 4-wire stat required. Application mode selection – 4-position dial switch allows installer to select the mode that fits the
hardware/usage configuration.
Outdoor temperature sensing (OT) – determines compressor staging, auxiliary electric (when
applicable) and/or switchover to gas.
Two-stage compressor (Copeland) – sequenced by outdoor temperature (OT) and SOT timeout, see
function charts – Figures 1, 2, 3, 4.
Forced air supply temperature sensing (ST) – used for the “dead compressor” alarm and controls
compressors if ST is too high – zone dampers, accidental gas furnace, full load to high, etc. – where AUX electric is installed (mode B only) this regulates AUX EL module based upon heating needs and comfort.
Alarms or fault notification – front panel yellow EL LED pulses at two different rates.
o After compressor control board (ICM) has sequenced through three retries. o Dead compressor, plenum temperature is less than set point (factory default 85° F).
Interface and control associated with utility control receivers (LMC or blues). Standby (SB) – forced function by LMC, front panel switch, optional remote switch, E-GAS, alarm, or
stat override timer (SOT). Also, for modes B, C, D when OT is below SW OVER set point.
Dual fuel – gas furnace with split models (RT-SE Series), mode D.
o This is also possible with other Geo units (two blower) but special consideration needs to be
Mode dial switch – installer must determine application/configuration and set up as required.
Mode
Switch
A Geo only N/A
B
C Geo/gas Value No AUX EL, gas furnace, auto SB, utility load control D Split/gas Value No AUX EL, gas furnace, auto SB, utility load control
SW OVER dial switch – if the OT sensor temperature is below this set point (at R to W start) the action shown on the appropriate Figures 2, 3, 4 mode sequence chart takes place. Remains to end of stat cycle. Notice – mode B has two conditions, correct position of SW OVER is very important.
If configured with AUX EL only (no gas), must set to 0 position. If no gas is connected or operational and SW OVER is set in a non-0 position, cold air only could result
because the stat W cannot be satisfied without a heating source.
addressed for ducting, airflow arrangements, both blowers, etc. (modes B and C).
Mode SW OVER Configuration
No AUX EL, no gas, no auto SB, but load control can interrupt compressor for cooling (not heating)
Geo/AUX EL 0
AUX EL (with compressor supplement or emergency), utility load control, etc. AUX EL, gas, auto SB, utility load control, etc. AUX EL is
Geo/AUX EL/gas Value
compressor supplement above SW OVER value, below SW OVER point gas has priority.
09/17/2010 1 HC112
Page 48
Heat/cool sequence – reference the Figures 1, 2, 3, 4 function sequence charts. These are selected or used based upon the application or setup mode (mode dial switch, back of EZGEO board, see above). Added information for the column headings:
Stats – represents the 4-wire stat W (heat) or Y (cool) call. OT – the range or outside temperature window for the various staging functions. This is checked at W
heat call and a second time at 10 minutes.
SOT – the stat override timer, represents the run time following the stat call. Timing begins at W or Y
high and at the timing end a specific action results.
SB – standby, interrupts all electric source or energy heating (compressor and AUX EL), converts or
transfers the stat W function to gas/oil as shown on the sequence charts. The return action from the listed initiating standby functions is different.
- SOT, SW OVER, OT chart line – continue to the end of stat W heat call
- Alarm – continues until power off reset
- LMC, SW OVER, E-gas (heating) – when function ends, clears SB, back to appropriate
sequence chart line (as if there is a new W call), SOT is reset
- LMC, override switch (cooling) – clears with end of function, SOT is not reset, blower = G
Heat pump three staging functions:
- Off – compressor not running
- Y1 – compressor contactor for run and low capacity
- Y2 – compressor solenoid for high capacity
Blower, ECM type – the nominal speed or CFM related to each specific model/size is programmed into
the ECM motor. These nominal CFM’s are triggered or controlled by three functions.
- G – continuous air
- Y1 – relates to compressor part capacity
- Y2 – relates to compressor full capacity
AUX EL – when auxiliary is installed (ordered separate) and the provided cable (standard WF
control/interface) is plugged into EZGEO board J1 (with a mode B only) these stages become active. The ST temperature relating to the ST-target factory default plus the front panel efficiency dial is the final determination on which stages are actually heating.
- STG 1 – first 5 kW
- STG 2-4 – the remaining connected or installed stages
Gas W – the mode B, C, or D functions when the gas furnace should be running. There also is an
attempted safety ST < 100° F sensing point and logic which does an EZGEO reset after 30-minute gas W.
SW OVER – the OT sensor is reporting a temperature value less than the SW OVER dial switch
setting, switch to standby (SB) or gas.
Alarm
– shows the two alarm conditions and the action based upon the appropriate mode settings.
Status front panel yellow EL LED – The alarm condition can be reset or cleared but the LED
continues to pulse until there’s actual power off and power cycled back on.
LMC – load management control or utility load control function, blue wires.
Variables/factory defaults – can be changed with PC software, listed are the factory default values.
Default
ST-target temp 96° Dead compressor ST 85° OT temp, heating – OT > 20° OT temp, heating – OT < 5° OT temp, cooling – OT > 80°
Efficiency dial, front panel – this is a “boost” temperature function to the setup ST-target temp.
0 = normal = download value 1 = A = download value + 5 2 = B = download value + 10 3 through 7 are programmed the same as normal
Front panel LED – see installation manual Observation Indicators section for detail.
09/17/2010 2 HC112
Page 49
SOT time dial switch – this is a 4-position rotary switch which begins counting time with each stat W (heat) or each stat Y (cool) input. Depending upon the dial switch setting (chart in installation manual, Field Setup section) action results after the selected minutes have elapsed. Figures 1, 2, 3, 4 charts provide this sequencing information.
Heating – at the end of LMC or SB, the SOT start time is reset to 0. Cooling – at the end of LMC, the SOT start time is not reset, as the SOT times out the system will go to
compressor full capacity.
ECM blower motor – this controller provides three outputs which coincide with G and heat pump stage Y1 and Y2. Whenever the AUX EL (mode B) is activated the blower is Y2 speed. However, the furnace TB outputs only apply to mode D (split) because the blower is external. For the configurations where the blower is within the Geo cabinet, the blower speeds are directly tied (hardware) to compressor Y1 and Y2.
The actual blower size, programming, and CFM output relate to the specific Geo HP model.
AUX EL (KN-**) electric heat module – can only apply to mode B (concerning mode D, there is
consideration for electric furnace, Electro-Mate with gas furnace, etc. but this is not documented). Also must be strip heat module or WarmFlo compatible with this EZGEO J1 cable.
1. Applies to mode B only.
2. Setup determines an “ST-target temp” which is similar to DT related with EZ-Mate or EB-A type
temperature set point. The operating set point is ST-target plus front dial boost selection.
3. This ST-target temp can be increased with the front dial boost setting, see page 1.
4. When the attached mode B sequence chart has checkmarks in STG1, stage 1 only is active and operates
at ST-target temp and boost.
5. When the mode B sequence chart has checkmarks in STG2-4, all stages operate at ST-target temp and
boost.
Note: This supplement electric module can only operate with the heat pump/compressor Y1 or Y2 functions. Because the blower is hardware connected to the HP-Y1 and HP-Y2 terminal block, the compressor must be active. If there is a hardware configuration arrangement where heating is needed below compressor plus AUX EL, that configuration must include a gas (or fossil fuel) furnace which is activated by SW OVER. However, under special short term installation conditions, if there is a desire to run AUX only (without compressor) the yellow wire at the ICM board Y tab can be disconnected.
Special LMC comment – with mode B and hardware configuration of all three heat sources, LMC causes auto SB/gas and gas continues to the end of SB. SB can happen in addition to LMC (see page 1 center). However, SB to gas has priority over Geo/AUX EL. W2 activates full AUX EL.
Alarms – EZGEO board has two functions, the Figures 1, 2, 3, 4 sequence charts provide the action when either of these alarms are active.
Fault is the output of the Geo unit internal ICM board indicating there has been three consecutive limit
or flow switch failures. The ICM board holds off the compressor until there is a power off reset. Where standby gas or AUX EL exist (B, C, D) heating will continue with the roomstat W.
ST < 85° F is a setup value referred to as dead compressor ST. 10 minutes after each new roomstat W
ST is monitored. If ST ever falls below the setup value a 30-minute timer is started (because there may also be an ICM board fault coincident with this). At the end of the 30 minutes if ST is still less than the setup value the unit switches to standby. The system remains in standby to the completion of stat W. Note: This only applies when there is no AUX EL active.
09/17/2010 3 HC112
Page 50
09/17/2010 4 HC112
Mode A – NHP Geo, Function Sequence, Figure 1
SOT Heat Pump Blower AUX EL
STAT OT
Start End
SB
Off Y1 Y2 G Y1 Y2 STG 1 STG 2-4
Gas W SW
OVER
Alarm
EL
LED
1 W > 20
+ N/A
2 W
+ +
3 W 5-20
+ +
4 W
+ +
5 W < 5
+ +
6 W
+ +
7 8 W Fault
T + Fault P
9 W
T ST < P 10 11 12 13 14 15 Y < 80
+
16 Y
+ +
17 Y > 80
+ +
18 Y
+ +
19 Y LMC
T Off 20 Y Fault
+ + Fault P
21 Y2
+ +
= EZGEO internal action or on
+ = Hardware within Geo unit (BL Y1 and Y2, not G) T = T-stat can do “FAN ON” G LMC = Utility receiver, on-peak
Page 51
09/17/2010 5 HC112
Mode B – NHP Geo, Function Sequence, Figure 2
SOT Heat Pump Blower AUX EL
STAT OT
Start End
SB
Off Y1 Y2 G Y1 Y2 STG 1 STG 2-4
Gas W SW
OVER
Alarm
EL
LED
1 W > 20
+
2 W
+ +
3 W 5-20
+ +
4 W
+ +
5 W < 5
+ +
Ø
6 W
+ +
Ø
7 W
T
Off 8 9 W LMC
T
Off
10 W Fault
+ +
Ø Fault P
11
Fault
+
Fault P
12 W X X X
X X X X < 85 P
13 W2
+ +
14 15 Y < 80
+
16 Y
+ +
17 Y > 80
+ +
18 Y
+ +
19 Y LMC
T Off
20 Y
+ + Fault P
21 Y2
+ +
= EZGEO internal action or on
+ = Hardware within Geo unit (BL Y1 and Y2, not G) T = T-stat can do “FAN ON” G X = Not used, ST has AUX EL temp. LMC = Utility receiver, on-peak Line 6/7 and 10/11 are OR, depending upon SW OVER setting SW OVER means non-Ø setting, OT > setting no action, OT < setting the action shown in the appropriate line
Page 52
09/17/2010 6 HC112
Mode C – NHP Geo, Function Sequence, Figure 3
SOT Heat Pump Blower AUX EL
STAT OT
Start End
SB
Off Y1 Y2 G Y1 Y2 STG 1 STG 2-4
Gas W SW
OVER
Alarm
EL
LED
1 W > 20
+
2 W
+ +
3 W 5-20
+ +
4 W
+ +
5 W < 5
+ +
6 W
T
Off 7 8 W
T
Off
9 W LMC
T
Off
10 W
Fault
+
Fault P
11 W
< 85 P
12 13 14 15 Y < 80
+
16 Y
+ +
17 Y > 80
+ +
18 Y
+ +
19 Y LMC
T Off
20 Y Fault
+ + Fault P
21 Y2
+ +
= EZGEO internal action or on
+ = Hardware within Geo unit (BL Y1 and Y2, not G) T = T-stat can do “FAN ON” G LMC = Utility receiver, on-peak
Page 53
09/17/2010 7 HC112
Mode D – NHP Geo, Function Sequence, Figure 4
SOT Heat Pump Blower AUX EL
STAT OT
Start End
SB
Off Y1 Y2 G Y1 Y2 STG 1 STG 2-4
Gas W SW
OVER
Alarm
EL
LED
1 W > 20
2 W
3 W 5-20
4 W
5 W < 5
6 W
T
Off 7 8 W
T
Off
9 W LMC
T
Off
10 W
Fault
T +
Fault P
11 12 13 14 15 Y < 80
16 Y
17 Y > 80
18 Y
19 Y LMC
Off
20 Y Fault
Fault P
21 Y2
= EZGEO internal action or on
+ = Hardware within Geo unit (BL Y1 and Y2, not G) T = T-stat can do “FAN ON” LMC = Utility receiver, on-peak
Page 54
Page 55
Page 56
TXV-C
PP
PP
GEO
LOOP FIELD
7/8
1/2
7/8
1/2
TXV-H
1/2
LWT
EWT
AIR COIL
COMP
F/D
PT-1 LL
PT-2
HL
LOOP­COIL
SDW­COIL
DW-RT
DW-ST
RV
- - - - - - - - - - - LINE SET - - - - - - - - - -
- - - LINE SET - - -
BV
BV
FL
BL
PT-1A
REC
T-3
Name
COMP Compressor
HL
Pressure high limit
LL
Pressure low limit
PT
Pressure test port
SDW-COIL Supplementary heat exchanger
DW-ST Ref : DW supply
DW-RT Ref: DW return
RV Reversing valve
BV Ball valve
AIR
COIL Air heat exchanger
BL
Ref: Blower
TXV-C
Expansion
valve - cool
TXV-H
Expansion
valve - heat
F/D
Filter/dryer
LOOP COIL
Source heat exchanger
P
Ref: Loop pump
FL
Flow switch
EWT
Ref: Loop entering
LWT
Ref: Loop leaving
T
Temperature test point
REC
Receiver
NR501 P1
Rev. B 09-17-2010
NORTHERN HEAT PUMP
SPLIT SYSTEM
- HEAT MODE
1
4.0 TON TO 5.0 TON UNITS USE 7/8” PIPE, 1.5 TON TO 3.0 TON USE 3/4” PIPE.
NOTES:
2
4.0 TON TO 5.0 TON UNITS USE BALL VALVES SIZED FOR 7/8” PIPE, 1.5 TON TO
3.0 TON ARE SIZED TO USE 3/4” PIPE.
1
1
2
T-3
T-3A
PT-3
T-2A
Page 57
TXV-C
PP
PP
GEO
LOOP FIELD
7/8
1/2
7/8
1/2
TXV-H
1/2
LWT
EWT
AIR COIL
COMP
F/D
PT-1 LL
PT-2
HL
LOOP­COIL
SDW­COIL
DW-RT
DW-ST
RV
- - - - - - - - - - - LINE SET - - - - - - - - - -
- - - LINE SET - - -
BV
BV
FL
BL
PT-1A
REC
T-3
Name
COMP Compressor
HL
Pressure high limit
LL
Pressure low limit
PT
Pressure test port
SDW-COIL Supplementary heat exchanger
DW-ST Ref : DW supply
DW-RT Ref: DW return
RV Reversing valve
BV Ball valve
AIR
COIL Air heat exchanger
BL
Ref: Blower
TXV-C
Expansion
valve - cool
TXV-H
Expansion
valve - heat
F/D
Filter/dryer
LOOP COIL
Source heat exchanger
P
Ref: Loop pump
FL
Flow switch
EWT
Ref: Loop entering
LWT
Ref: Loop leaving
T
Temperature test point
REC
Receiver
NR501 P2
Rev. B 09-17-2010
NORTHERN HEAT PUMP
SPLIT SYSTEM
- COOLING MODE
1
4.0 TON TO 5.0 TON UNITS USE 7/8” PIPE, 1.5 TON TO 3.0 TON USE 3/4” PIPE.
NOTES:
2
4.0 TON TO 5.0 TON UNITS USE BALL VALVES SIZED FOR 7/8” PIPE, 1.5 TON TO
3.0 TON ARE SIZED TO USE 3/4” PIPE.
1
1
2
T-3
T-3A
PT-3
T-2A
Page 58
Page 59
Page 60
Northern Heat Pump Residential
Limited Product Warranty
Effective November 1, 2009
Northern Heat Pump, LTD. warrants to the original owner, at the original installation site, for a period of three (3) years from date of original purchase, that the product and product parts manufactured by Northern Heat Pump, LTD. are free from manufacturing defects in materials and workmanship, when used under normal conditions and when such product has not been modified or cha nged in any manner after leaving the plant of Northern Heat Pump, LTD. If any product or product parts manufactured by Northern Heat Pump, LTD. are found to have manufacturing defects in materials or workmanship, such will be repaired or replaced by Northern Heat Pump, LTD. Northern Heat Pump, LTD., shall have the opportunity to directly, or through its authorized representative, examine and inspect the alleged defective product or product parts. Northern Heat Pump, LTD. may request that the materials be returned to Northern Heat Pump, LTD. at owner’s expense for factory inspection. The determination as to whether product or product parts shall be repaired, or in the alternative, replaced, shall be made by Northern Heat Pump, LTD. or its authorized representative.
TEN YEAR (10) LIMITED WARRANTY ON REFRIGERATION COMPONENTS
Northern Heat Pump, LTD. warrants that the compressor, reversing valve, expansion valve and heat exchanger(s) of its products are free from defects in materials and workmanship through the tenth year following date of original purchase. If any compressor, reversing valve, expansion valve or heat exchanger(s) are found to have a manufacturing defect in materials or workmanship, Northern Heat Pump, LTD. will repair or replace them at their discretion.
FIVE YEAR (5) LIMITED WARRANTY ON OPEN WIRE ELEMENTS
Northern Heat Pump, LTD. warrants that the open wire elements of its products are free from defect s in materials and workmanship through the fifth year following date of original purchase. If any open wire elements are found to have a manufacturing defect in materials or workmanship, Northern Heat Pump, LTD. will replace them.
Northern Heat Pump, LTD. shall cover labor costs according to the Repair / Replacement Labor Allowance Schedule for a period of three (3) years from the date of original purchase, to the original owner, at the original installation site on all parts excluding the compressor, reversing valve, expansion valve, and heat exchanger(s). Northern Heat Pump, LTD shall cover labor costs according to the Repair / Replacement Labor Allowance Schedule for a period of five (5) years from the date of original purchase, to the original owner, at the original installation site, on parts including the compressor, reversing valve, expansion valve, and heat exchanger(s). The Repair / Replacement Labor Allowance is designed to reduce the cost of repairs. This Repair / Replacement Labor Allowance may not cover the entire labor fee charged by your dealer / contractor.
Page 1 of 2 XX029
NORTHERN HEAT PUMP, LTD.
A Subsidiary of Electro Industries, Inc. 2150 West River Street, PO Box 538, Monticello, MN 55362 763-295-4138 • 800-922-4138 • fax 763-295-4434 sales@electromn.com
Page 61
CONDITIONS AND LIMITATIONS:
1. This warranty is limited to residential, single family dwelling installations only. Any commercial or multi-unit dwelling installations fall under the Northern Heat Pump Commercial Limited Product Warranty.
2. Northern Heat Pump, LTD. shall not be liable for performance related issues resulting from improper installation, improper sizing, improper duct or distribution system, or any other installation deficiencies.
3. If at the time of a request for service the or iginal owner cannot provide an original sales receipt or a warranty card registration then the warranty period for the product will have deemed to begin the date the product is shipped from the factory and NOT the date of original purchase.
4. The product must have been sold and installed by a licensed electrician, plumbing, or heating contractor.
5. The application and installation of the product must be in compliance with Northern Heat Pump, LTD. specifications, as stated in the installation and instruction manual, and all state, provincial and federal codes and statutes. If not, the warranty will be null and void.
6. The purchaser shall have maintained the product in accordance with the manual that accompanies the unit. Annually, a qualified and licensed contractor must inspect the product to assure it is in proper working condition.
7. All related heating components must be maintained in good operating condition.
8. All lines must be checked to confirm that all condensation drains properly from the unit.
9. Replacement of a product or product part under this limited warranty does not extend the warranty term or period.
10. Replacement product parts are warranted to be free from defects in material and workmanship for ninety (90) days from the date of installation. All exclusions, conditions, and limitations expressed in this warranty apply.
11. Before warranty claims will be honored, Northern Heat Pump, LTD. shall have the opportunity to directly, or through its authorized representative, examine and inspect the alleged defective product or product parts. Remedies under this warranty are limited to repairing or replacing alleged defective product or product parts. The decision whether to repair or, in the alternative, replace products or product parts shall be made by Northern Heat Pump, LTD. or its authorized representative.
THIS WARRANTY DOES NOT COVER:
1. Costs for labor for diagnosis, removal or reinstallation of an alleged defective product or product part, transportation to Northern Heat Pump, LTD. or Electro Industries, Inc., and any other materials necessary to perform the exchange, except as stated in this warranty. Replacement material will be invoiced to the distributor in the usual manner and will be subject to adjustment upon verification of defect.
2. Any product or product part that has been damaged as a result of being improperly serviced or operated, including, but not limited to, the following: operated during construction phase, with insufficient water or air flow; allowed to freeze; subjected to flood conditions; subjected to improper voltages or power supplies; operated with air flow or water conditions and/or fuels or additives which cause unusual deposits or corrosion in or on the product; chemical or galvanic erosion; improper maintenance or subject to any other abuse or negligence.
3. Any product or product part that has been damaged as a result of natural disasters, including, but not limited to, lightning, fire, earthquake, hurricanes, tornadoes or floods.
4. Any product or product part that has been damaged as a result of shipment or handling by the freight carrier. It is the receiver’s responsibility to claim and process freight damage with the carrier.
5. Any product or product part that has been defaced, abused or suffered unusual wear and tear as determined by Northern Heat Pump, LTD. or its authorized representative.
6. Workmanshi p of any installer of the product or product part. This warranty does not assume any liability of any nature for unsatisfactory performance caused by improper installation.
7. Transportation charges for any replacement product, product part or component, service calls, normal maintenance; replacement of fuses, filters, refrigerant, etc.
THESE WARRANTIES DO NOT EXTEND TO ANYONE EXCEPT THE ORIGINAL PURCHASER AT RETAIL AND ONLY WHEN THE PRODUCT IS IN THE ORIGINAL INSTALLATION SITE. THE REMEDIES SET FORTH HEREIN ARE EXCLUSIVE.
ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY DISCLAIMED WITH RESPECT TO ALL PURCHASERS OR OWNERS. NORTHERN HEAT PUMP, LTD. IS NOT BOUND BY PROMISES MADE BY OTHERS BEYOND THE TERMS OF THESE WARRANTIES. FAILURE TO RETURN THE WARRANTY CARD SHALL HAVE NO EFFECT ON THE DISCLAIMER OF THESE IMPLIED WARRANTIES.
ALL EXPRESS WARRANTIES SHALL BE LIMITED TO THE DURATION OF THIS EXPRESS LIMITED WARRANTIES SET FORTH HEREIN AND EXCLUDE ANY LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES RESULTING FROM THE BREACH THEREOF. SOME STATES OR PROVINCES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATIONS OR EXCLUSIONS MAY NOT APPLY. PRODUCTS OR PARTS OF OTHER MANUFACTURERS ATTACHED ARE SPECIFICALLY EXCLUDED FROM THE WARRANTY.
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY HAVE OTHER RIGHTS WHICH VARY UNDER THE LAWS OF EACH STATE. IF ANY PROVISION OF THIS WARRANTY IS PROHIBITED OR INVALID UNDER APPLICABLE STATE OR PROVINCIAL LAW, THAT PROVISION SHALL BE INEFFECTIVE TO THE EXTENT OF THE PROHIBITION OR INVALIDITY WITHOUT INVALIDATING THE REMAINDER OF THE AFFECTED PROVISION OR THE OTHER PROVISIONS OF THIS WARRANTY.
Page 2 of 2 XX029
Loading...