Nortek Security and Control 2GIG SMKT2345 User Manual

2GIG-SMKT2-345
L
I
S
T
D
WIRELESS PHOTOELECTRIC SMOKE ALARM
Installation Instructions
R
I
CM
Temperature Sensor
Test/Silence button
LED
Sounder vent
Temperature sensor
388 West Center Street
Orem, UT 84057
Technical Support 866-670-1591
www.2gig.com
DESCRIPTION
The 2GIG-SMKT2-345 is a photoelectric smoke alarm with a built-in transmitter designed for use with the 2GIG-CNTRL-345 security system. When smoke is detected, the alarm sounds a loud local alarm. Twenty seconds after the local alarm sounds, the built-in transmitter sends a digitally coded wireless signal to the Control Panel. The wireless signal will be repeated every 20 seconds as long as smoke is still present.
In addition to the photoelectric detector, the unit contains an integrated fi xed 135° temperature and rate-of-rise heat sensor that will send an alarm signal based on temperature detected.
BUILT-IN WIRELESS TRANSMITTER
The smoke alarm can send three different wireless signals to the alarm Control Panel: alarm, low battery, and status.
Every hour, the smoke alarm sends a status transmission to the Control Panel. The hourly signal updates the Control Panel with the smoke alarm’s condition. By monitoring status transmissions, the Control Panel can determine that the smoke alarm is still operational in the installation and if it has a low battery.
The Control Panel must be programmed to the transmitter’s serial number before system testing and operation. Refer to the Control Panel’s
instructions for details on programming.
INSTALLATION
1. Slide the battery compartment cover away from the unit to unsnap it and lift it off. See Figure 2.
2. Observing proper polarity, insert the two 3V lithium batteries supplied into the alarm battery compartment and replace the battery cover.
3. Remove the red plastic dust cover from the unit.
4. Refer to Page 3 for selecting a proper location for the smoke alarm.
5. Using the two screws and anchors provided, mount the base.
6. Attach the unit to the base as follows:
• Line up the raised alignment tab on the lip of the unit with the alignment arrow on the base. See Figure 3.
• Insert the unit into the base and turn clockwise approximately 15 degrees. It should snap fi rmly into place.
• IMPORTANT: The unit cannot be attached to the base if no batteries are installed.
PROGRAM SMOKE ALARM INTO THE CONTROL PANEL
Before testing the smoke alarm, the internal wireless transmitter must be programmed into the Control Panel.
1. Refer to the Control Panel’s instructions to prepare the receiver to accept the smoke alarm’s serial number.
2. Press the smoke alarm’s TEST/SILENCE button for 4 seconds. The smoke alarm will perform a sounder test, a sensitivity test, and send a test signal to the Control Panel.
3. Verify that the signal was received by the Control Panel and that the sensor was entered into the system.
4. Exit Control Panel programming before testing the smoke alarm.
Figure 1. Smoke Alarm Features
Battery compartment
Figure 2. Battery Compartment
Alignment tab
Alignment arrow
Figure 3. Smoke Alarm-to-Base Alignment
SMOKE TEST
Units should be tested in place annually using one of the following methods:
A. Use Smoke! in a can® and follow directions on the can.
B. Hold a smoldering punk or cotton wick close to the unit and gently direct
the smoke into the smoke entry openings for 20 seconds or until an alarm is indicated.
The smoke alarm LED should stay on and the sounder should emit a temporal three pattern, and an alarm should be indicated at the Control Panel. Disarm the system to reset the Control Panel alarm. Be sure to extinguish the
smoke source after testing!
SILENCE THE ALARM
Press the TEST/SILENCE button to silence the sounder during an alarm. After a few minutes, the sounder and alarm resume if smoke is still present.
1
SENSITIVITY TEST
1. Press and hold the TEST/SILENCE button for 4 seconds. Once the test starts, the smoke alarm LED fl ashes 1 to 9 times.
2. Count the number of LED fl ashes and use the following table to determine if any action is necessary.
FLASHES INDICATION ACTION
0-1
2-3
4-7
Unserviceable hardware fault
Unit is becoming insensitive
Unit is within normal sensitivity range
Reset and rerun sensitivity test. If the error persists, replace the unit. Clean and reset the unit. Rerun sensitivity test. If the error persists, replace the unit.
No action required
Verify that the optical chamber is
8-9
Unit is becoming too sensitive
snapped down securely. Clean the unit and replace the optical
chamber. After the LED fl ashes, if the sensitivity is within limits and all other tests pass, the unit goes into alarm and resets after 7 seconds. If the sensitivity is not within limits, or an unserviceable hardware fault has been detected, the unit LED extinguishes until the unit is serviced.
LED FUNCTIONS
Flashing — Flashes every 9 seconds to indicate normal operation.
On — Detects smoke
Off — Trouble or maintenance is required.
WHEN TO REPLACE THE BATTERIES
When the batteries are low, the unit extinguishes its LED and chirps every 45 seconds until the batteries are replaced. The low battery trouble chirps can be silenced for 24 hours by pressing the TEST/SILENCE button. Battery life is a minimum of one year, and varies depending on how often the unit is tested.
REPLACING THE BATTERIES
Use only 3V lithium batteries listed on the battery compartment cover.
1. Remove the unit from the mounting base, grasp the unit and turn it
counterclockwise approximately 15 degrees.
2. Slide the battery compartment cover away from the smoke alarm to
unsnap it and lift it off. See Figure 2.
3. Remove the batteries and dispose of them properly.
4. Observing correct polarity, insert two new 3V lithium batteries into the
battery compartment and replace the cover.
5. Reattach the unit to the mounting base. See Installation, Step 6.
6. Test the system.
CLEANING
Clean the cover with a dry or damp (water) cloth as needed to keep it free from dust and dirt.
When necessary, clean the interior and replace the optical chamber (part number ??????) as follows:
1. To remove the unit from the mounting base, grasp the unit and turn it
counterclockwise approximately 15 degrees.
2. Remove the batteries.
3. Slide a fl at-blade screwdriver in the slot on the alarm cap and gently push
the handle down to pry the alarm cap up and off. See Figure 4.
4. Squeeze the optical chamber where indicated and pull it up and away
from the optical base and discard. See Figure 5.
5. Blow out or use a soft-bristled brush to remove all dust and dirt from the
optical base.
6. Line the new smoke chamber up with the optical base by lining up the
arrows on the optical chamber to the latches on the optical base. Ensure that the LED cavity in the optical chamber is above the LED and snap the optical chamber down into place.
7. To replace the alarm cap as follows:
• Line the alarm cap up with the unit.
• Insert the alarm cap into the unit and turn clockwise approximately 15 degrees. It should snap fi rmly into place.
2
8. Observing proper polarity, replace the batteries and the battery compartment cover.
9. Reattach the unit to its mounting base. See Installation, Step 6.
10. Test the unit sensitivity.
MAINTENANCE
The units are designed for easy fi eld service and maintenance. When installed and used properly, they require minimal maintenance.
The unit should be tested weekly.
When a unit requires maintenance, it extinguishes its LED and stops sending supervisory signals to the alarm Control Panel.
If the Control Panel indicates supervisory trouble for the smoke alarm, perform the sensitivity test and follow the recommended actions.
SPECIFICATIONS
Voltage 3VDC Typical average standby current 35µA Typical test current 2mA Typical alarm current 70mA Battery type 3V lithium, Duracell® 123, Panasonic CR123A, Sanyo® 123A Low battery threshold 2.70V causes low battery signal Sounder 85dBa at 10’ temporal pattern Low battery beep rate 1 every 45 sec. Sensitivity 2.2% ± 1.3% / ft. Operating temperature 40°-100°F (4.4°-37.8°C) Operating humidity range 0-95% non-condensing Color White Alarm dimensions 5.6” x 2.4” (14.2 cm x 6.1cm) Base dimensions 5.4” x 0.46” (13.7 cm x 1.17cm) Drift compensation adjustment 0.5% / ft. max. Heat detector specifications Rate-of-rise 15°F/min>105°F (8.3°C/min>40.6°C Fixed 135°F ± 5°F (57.2°C ± 2.8°C) Listings ETL, UL217, CSFM
Figure 4. Removing the Smoke Alarm Cap
Smoke chamber latch
Alignment arrows
Optical base
Optical chamber
Alarm Cap
Figure 5. Smoke Alarm Parts
®
Loading...
+ 2 hidden pages