Nortech ATR434P Users Guide

The base-station is a robust, weatherproof device capable of being mounted outdoors and
C, 0 - 98% RH). The casing is
constructed of an ABS plastic, which is impact- and UV-resistant. O-ring seals are
in
the base.) Access to the electronics is via screws hidden behind clip-in panels on the front
be either wall, pole or gantry mounted. It must be positioned so that it ‘looks into’
Boom
Nortech International (Pty) Ltd
P O Box 4099 32A Wiganthorpe Road Willowton Hub Pietermaritzburg Pietermaritzburg 3201 South Africa 3200 South Africa Reg No. 98/1095
Tel: (033) 345 3456 Int Tel: +27 33 345 3456 Fax: (033) 394 6449 Int Fax: +27 33 394 6449 Email: mkt@nortech.co.za URL: www.nortech.co.za
AUTOTAG-P BASE-STATION (ATR430P Series) INSTALLATION GUIDE
This guide covers the following units:
ATR431P 115V AC Base-Station Unit ATR432P 230V AC Base-Station Unit ATR434P 12-24V DC Base-Station Unit
1. EQUIPMENT REQUIRED
3mm Allen key M4 x 20mm machine screws Power cable 3mm flat screwdriver M4 nuts Screened Communications Cable Side-cutters M4 washers (wide)
withstanding wide temperature / humidity ranges (-40°C to +70° incorporated to ensure minimal ingress of water and dust. (Cable access is via knockouts cover. The unit may
the vehicle.
Loop
Vehicle
708LF0211-01 October 1999 Autotag-P Base-Station Installation Leaflet Page 8 of 8
8 m max.
Figure 1. Positioning
708LF0211-01 October 1999 Autotag-P Base-Station Installation Leaflet Page 1 of 8
3. MOUNTING Wall mounting:
Wall mounting is possible when the wall is within the specified range of the furthest side of the vehicles to be monitored. The presence of metal re-inforcing in the wall has negligible effect on the operation of the base-station.
1.
2.
3.
4.
5.
6.
7.
8.
9.
NB:
Pole or gantry mounting:
1.
2.
3.
4.
6. FCC REGULATIONS
Determine the area in which the unit must detect. The base-station unit should be placed
facing the middle of this area (Figure 1) Unclip the two screw covers. Remove screws and front cover. Knockouts are provided on the base. Remove the appropriate knockouts, including that of
the cable access hole. Route power and communications cables through the cable access hole. Bolt base to wall via knockouts. Connect cables according to wiring diagram (see Section 3). Before applying power: Set the DIP switches according to the type of installation required.
If the ‘triggered’ setting is to be used, ensure the arming input is connected and that the
trigger system (e.g. loop detector) is functioning. Apply power. The RED LED should be illuminated. Holding a tag in front of the unit should cause the GREEN LED to flash and a beep to be
heard. This indicates that the base-station is receiving code from the tag.
The PCB does NOT need to be unscrewed from the front cover at any point. Doing so will
result in the warranty being voided.
When mounting on a pole, ensure that the flange has a minimum diameter of 120 mm A hole in the centre of the flange with min. diameter of 30 mm will allow for hidden cable
access. Ensure that the unit faces the window area of the vehicles to be monitored. Mounting instructions are the same as for the above.
When this system is used in the United States of America, only the following models may be used:
AUTOTAG-P BASE STATION MODELS
FT Number Part Number Voltage Protocol
708FT0233 ATR434P-C2 12-24V DC Clock & Data / Wiegand and RS-232 708FT0234 ATR434P-C2 12-24V DC
AUTOTAG-P TRANSPONDER MODELS
FT Number Part Number
708FT0210 AT430P Programmable Tag 708FT0211 AT430P Programmable Tag (McGann)
Model
Clock & Data / Wiegand and RS-232 (McGann)
User in the United States of America.
Please note the following important caution:-
Changes or modifications to this product not expressly approved by
Nortech International (Pty) Ltd, in writing, could void the user’s authority
to operate the product.
708LF0211-01 October 1999 Autotag-P Base-Station Installation Leaflet Page 2 of 8 708LF0211-01 October 1999 Autotag-P Base-Station Installation Leaflet Page 7 of 8
If there is more than one Base-Station in proximity to another, it is not desirable for multiple Base-Stations to read the same tag. The ID’s of the base stations must be set to different values. The ID’s are set with SW1, allowance has been made for 16 different ID’s.
Dip Switch 1 Configuration SW1:
Further literature on Autotag:
Autotag-P User Manual Autotag-P Tag Installation Guide Autotag-P Data Sheet Autotag-P Programming Station User Manual
dip-switch
4. LAYOUT OF MAIN BOARD
Address/ID SW1-5 SW1-4 SW1-3 SW1-2 SW1-1
0 ON ON ON ON ON 1 ON ON ON ON OFF 2 ON ON ON OFF ON 3 ON ON ON OFF OFF 4 ON ON OFF ON ON 5 ON ON OFF ON OFF 6 ON ON OFF OFF ON 7 ON ON OFF OFF OFF 8 ON OFF ON ON ON
9 ON OFF ON ON OFF 10 ON OFF ON OFF ON 11 ON OFF ON OFF OFF 12 ON OFF OFF ON ON 13 ON OFF OFF ON OFF 14 ON OFF OFF OFF ON 15 ON OFF OFF OFF OFF 16 OFF ON ON ON ON 17 OFF ON ON ON OFF 18 OFF ON ON OFF ON 19 OFF ON ON OFF OFF 20 OFF ON OFF ON ON 21 OFF ON OFF ON OFF 22 OFF ON OFF OFF ON 23 OFF ON OFF OFF OFF 24 OFF OFF ON ON ON 25 OFF OFF ON ON OFF 26 OFF OFF ON OFF ON 27 OFF OFF ON OFF OFF 28 OFF OFF OFF ON ON 29 OFF OFF OFF ON OFF 30 OFF OFF OFF OFF ON 31 OFF OFF OFF OFF OFF
708UM0210 708LF0210 708DS0210 708UM0201
708LF0211-01 October 1999 Autotag-P Base-Station Installation Leaflet Page 6 of 8
708LF0211-01 October 1999 Autotag-P Base-Station Installation Leaflet Page 3 of 8
5
. WIRING DETAIL
Connect the following lines: CN7 Pin 4 (DATA0), CN7 Pin 3 (DATA1) and CN5 Pin 1 (GND) to the corresponding terminals on the controller. Ensure that switch SW2-
Connect the following lines: CN7 Pin 4 (Clock), CN7 Pin 3 (Data), CN7 Pin 2 (Card
corres-ponding terminals of the controller.
odel. Connect CN7 Pin 5 (RS232 TX) to the receive pin of the controller. Connect CN7 Pin 6 (RS232 RX) to the transmit pin of the controller. Connect CN5 Pin 1 (GND) to the signal GND Pin of the
S485 model. Connect the following lines: CN7 Pin 6 (RS485 A), CN7 Pin 5 (RS485 B) and CN5 Pin 1 (GND) to the corresponding terminals of the controller. Ensure that each base station has a
This is done when the Base-station is to operate in ‘Triggered’ mode. A vehicle detector
The vehicle detector can be a loop detector, capacitive detector or any other unit capable of
relay closure whilst a vehicle is present. In the case of a loop detector
Connect CN7 Pin 1to the N/O relay output of the triggering device, and CN5 Pin 6 to the RELAY
CN7 6 Way Pluggable Screw Terminal PIN Wiegand Function Clock & Data Function
1 Triggered Input Triggered Input (Arming) 2 Not Used Card Present 3 DATA 1 Data 4 DATA 0 Clock 5 As per table below As per table below 6 As per table below As per table below
CN7 6 Way Pluggable Screw Terminal PIN RS232 Function RS485 Function
1 As per table above As per table above 2 As per table above Not Used 3 As per table above RS485 TX Active 4 As per table above Not Used 5 RS232 TX RS485 B 6 RS232 TX RS485 A
CN5 6 Way Pluggable Screw Terminal PIN FUNCTION
1 Signal Ground 2 External Indicator Output – Green 3 External Indicator Output – Red 4 External Indicator Input – Green 5 External Indicator Input – Red 6 SYNC
CN2 5 Way Pluggable Screw Terminal PIN FUNCTION
1 Relay Normally Open 2 Relay Normally Closed 3 Relay Common 4 DC Power In Negative 5 DC Power In Positive
CN1 # Way Pluggable Screw Terminal PIN FUNCTION
1 Mains Power Live 2 Mains Power Safety Earth 3 Mains Power Neutral
Note:Any additional wires used for GROUND connections should be connected to CN5 Pin 1. Connecting the Base-station to a controller:
Wiegand:
3 is ON.
Clock & Data:
Present) and CN5 Pin 1 (GND) to the Ensure that SW2-3 is OFF.
RS232: This feature is only available on the RS232 m
controller.
RS485: This feature is only available on the R
unique address by setting switches SW1-1 through SW1-5.
Connecting the Base-station to a triggering device:
positioned directly in front of the Base-station unit is used to trigger operation.
providing a CONTINUOUS this requires that the unit is configured for PERMANENT PRESENCE.
COMMON connection.
Operating multiple Base-Stations in proximity to one another:
When two or more Base-Station units are operated in proximity to one another they may cause mutual interference if not synchronised. Synchronisation ensures that their transmissions do not interfere with one another. To synchronise the units, connect the SYNC lines (CN5 Pin 6) and GND (CN5 Pin 1) on the 6-pin power connectors to the corresponding pins on all units (i.e. Pin 6 to Pin 6, Pin 1 to Pin 1).
Autotag-P Base-Station Installation Leaflet Page 4 of 8