Important: Read and save these instructions. This guide to be left with equipment.
1506222-L| 07 JAN 2014
GS
Series
Installation and
Operation Manual
Includes installation, operation,
maintenance, and troubleshooting
information for your GSTC / GHP gas
steam humidifier.
− Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
− WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Leave the building immediately.
Immediately call your gas supplier from a phone
remote from the building. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the fire
department.
− Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in
serious injury, death or property damage.
Be sure to read and understand the installation,
operation and service instructions in this manual.
Improper installation, adjustment, alteration, service
or maintenance can cause serious injury, death or
property damage.
INSTALLATION DATE (MM/DD/YYYY)
MODEL #
SERIAL #
Thank you for choosing Nortec.
Proprietary Notice
This document and the information disclosed herein are proprietary data of Nortec Humidity Ltd. Neither this document
nor the information contained herein shall be reproduced used, or disclosed to others without the written authorization
of Nortec Humidity Ltd., except to the extent required for installation or maintenance of recipient’s equipment. All
references to the Nortec name should be taken as referring to Nortec Humidity Ltd.
Liability Notice
Nortec does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use
of parts/components/equipment that are not authorized or approved by Nortec.
Copyright Notice
Copyright 2014Nortec Humidity Ltd.All rights reserved.
55 Key Pad
73 Troubleshooting
80 Wiring Diagrams &
Spare Parts
CAUTION: Servicing
Nortec does not accept any liability for installations of humidity equipment installed by
unqualified personnel or the use of parts/components/equipment that are not authorized
or approved by Nortec.
Every person working with the Nortec GS Series must read and understand the
installation and operating instructions before carrying out any work.
Disconnect main power and shut off gas supply before any servicing.
During and following operation of the humidifier, the steam and components in contact
with the steam can become hot and burn if touched.
Poorly maintained humidifiers can endanger health of building occupants.
The GS must be serviced in the intervals described in the maintenance section of this
manual.
Be mindful of weather. Opening a GSTC Outdoor enclosure exposes internal components
that should not come into contact with water. It is not recommended to perform ay
service on an Outdoor GSTC during rain, snow, sleep or hail.
CAUTION: Electrical
All electrical work should be done according to local electrical code.
Electrical connection to be performed by a licensed electrician.
CAUTION: General
The Nortec GS series must be kept clear and free of combustible materials, gasoline, and
other flammable vapors and liquids.
The indoor GS humidifier located in an insulated space must be kept free and clear of
insulating material. Do not add combustible insulating material to the appliance.
The GS humidifier requires proper ducting for combustion air and exhaust ventilation for
safe operation. Avoid blocking or obstructing air openings on the appliance, air openings
communicating with the area in which the appliance is installed and the spacing around
the appliance.
Should overheating occur, or the gas supply fails to shutoff, shut off the manual gas valve
to the appliance before switching off the electrical supply.
Do not use this appliance if any part has been under water. Immediately call a qualified
service technician to inspect the appliance and to replace any part of the control system
and any gas control which has been under water.
Introduction
GS Series Installation | 2
CAUTION: Installation
Installation and service must be performed by a qualified installer, service agency or the
gas supplier
The GS produces steam at atmospheric pressure. No devices which could block steam
output should be connected to the steam outlet.
Steam lines must be installed so that no restriction can produce backpressure in the
humidifier. Failure to follow installation instructions will result in improper operation and
could void warranty.
Regardless of selecting On/Off or modulating control method, Nortec humidifiers must
have a closed circuit across its On/Off security loop control terminal to operate. Nortec
highly recommends the use of a high limit humidistat and an air proving switch in series
for this function.
CAUTION: Plumbing
Plumbing to be performed by a licensed plumber.
All plumbing work should be done according to local plumbing code.
Unit damage caused by water quality outside of the specified ranges is not covered under
warranty.
Figure 1: GSTC-100
3 | GS Series Installation
General
This installation guide has been designed to provide assistance when installing, mounting, and
commissioning a GS Series humidifier. Actual on site application may vary. Consult Technical Services or
your local Nortec representative.
Warning
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide
poisoning, an explosion, fire, electrical shock, or other conditions which may cause personal injury or
property damage. Consult a qualified installer, service agency, local gas supplier, distributor, or branch for
information or assistance. The qualified installer or agency must use only factory authorized and listed kits
or accessories when modifying this product. A failure to follow this warning can cause electrical shock, fire,
personal injury, or death.
Should overheating occur, or the gas fails to shut off, shut off the manual gas valve to the appliance before
shutting off the electrical supply.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician
to inspect the appliance and to replace any part of the control system and any gas control which has been
under water.
Delivery
The standard delivery includes:
Gas Steam humidifier equipped with desired options.
In a bag you will find:
o Manuals.
o Adapter fittings for water connection.
o Steam hose for steam outlet with clamps.
o Hose and clamps for drain connection.
The GS Indoor Series offers an optional telescopic stand mounted inside the unit legs. Stand cross bracing
are shipped with the unit.
The GS Outdoor Series comes with all required venting to be installed on site.
Desired accessories ordered.
Receiving And Unpacking Equipment
Check packing slip to ensure ALL material has been delivered.
All material shortages are to be reported to Nortec within 48 hours from receipt of goods. Nortec
assumes no responsibility for any material shortages beyond this period.
Inspect shipping boxes for damage and note on shipping waybill accordingly.
After unpacking, inspect equipment for damage and if damage is found, notify the shipper promptly.
All Nortec products are shipped on an F.O.B. factory basis. Any and all damage, breakage or loss claims
are to be made directly to the shipping company.
GS Series Installation | 4
Figure 2: Model Designation
High Altitude
A derate in input exists for installations at higher altitudes. For Canadian models, an
automatic 10% derate applies to installations from 2000-4500 feet. For U.S. Models, refer to
the chart below for high altitudes derate information.
Table 1: High Altitude
Altitude
Derate %
Feet
Meters
0-2000
0-610
0
2001-3000
610-915
8
3001-4000
915-1220
12
4001-4500
1220-1370
16
4501-higher
1370-higher
Contact Factory
General Specifications
The Nortec GS Series humidifier is a completely new patented design based on leading edge technology.
The GS is designed to provide clean steam humidification at an economical price.
The GS Series humidifiers are designed exclusively for humidification in ventilation systems or direct room
humidification. Any other type of application, without the written consent of Nortec or your Nortec agent, is
considered as not conforming to the intended purposes. The manufacturer/supplier cannot be made liable
for any damages resulting from improper use.
Model Designation
The unit specification label indicates the model of gas humidifier according to Figure 2.
5 | GS Series Installation
MODEL GS 100 SPECIFICATIONS
FUEL
BLOWER SPEED
INPUT (BTUH)
STEAM CAPACITY (LBS/HR)
MANIFOLD PRESS. IN W.C.
NATURAL GAS
MAX
140,000
105
-0.05
MIN
45,000
25
-0.05
PROPANE
MAX
140,000
105
-0.35
MIN
50,000
25
-0.35
MODEL GS 200 SPECIFICATIONS
FUEL
BLOWER SPEED
INPUT (BTUH)
STEAM CAPACITY (LBS/HR)
MANIFOLD PRESS. IN W.C.
NATURAL GAS
MAX
280,000
210
-0.05
MIN
45,000
25
-0.05
PROPANE
MAX
280,000
210
-0.35
MIN
50,000
25
-0.35
MODEL GS 300 SPECIFICATIONS
FUEL
BLOWER SPEED
INPUT (BTUH)
STEAM CAPACITY (LBS/HR)
MANIFOLD PRESS. IN W.C.
NATURAL GAS
MAX
420,000
315
-0.05
MIN
45,000
25
-0.05
PROPANE
MAX
420,000
315
-0.35
MIN
50,000
25
-0.35
MODEL GS 400 SPECIFICATIONS
FUEL
BLOWER SPEED
INPUT (BTUH)
STEAM CAPACITY (LBS/HR)
MANIFOLD PRESS. IN W.C.
NATURAL GAS
MAX
560,000
420
-0.05
MIN
45,000
25
-0.05
PROPANE
MAX
560,000
420
-0.35
MIN
50,000
25
-0.35
MODEL GS 500 SPECIFICATIONS
FUEL
BLOWER SPEED
INPUT (BTUH)
STEAM CAPACITY (LBS/HR)
MANIFOLD PRESS. IN W.C.
NATURAL GAS
MAX
700,000
525
-0.05
MIN
45,000
25
-0.05
PROPANE
MAX
700,000
525
-0.35
MIN
50,000
25
-0.35
MODEL GS 600 SPECIFICATIONS
FUEL
BLOWER SPEED
INPUT (BTUH)
STEAM CAPACITY (LBS/HR)
MANIFOLD PRESS. IN W.C.
NATURAL GAS
MAX
840,000
630
-0.05
MIN
45,000
25
-0.05
PROPANE
MAX
840,000
630
-0.35
MIN
50,000
25
-0.35
Table 2: Model Specification
GS Series Installation | 6
Figure 3: Typical Installation Indoor
Installation
Indoor Installation
The installation must conform with local building codes or, in the absence of local codes, with the ANSI
Z223.1, National Fuel Gas Code, and/or CSA B149.1installation codes. Refer to the Gas Piping section of
this manual.
Locating and Mounting
GS Series humidifiers are designed for floor mounting or on a GS stand (optional). The clearance
dimensions shown in this manual are for reference only and are the minimum required for maintenance of
the humidifier. Local and national codes should be consulted prior to final location and installation of the
humidifier. Nortec cannot accept responsibility for installation code violations.
Figure 3 shows a typical installation with all required connections to the GS humidifier. Careful consideration
should be given to all of these connections when choosing a location for the humidifier.
7 | GS Series Installation
Warning:
Steam distributor on the built-on and remote mounted blower packs have a hot surface that could result
in burns if touched. Nortec recommends mounting at least 8 feet above the floor.
Figure 4: Mounting Clearances
Ambient temperature location for humidifier: 41ºF - 104ºF (5ºC - 40ºC).
Relative humidity location for humidifiers: 5% rh - 80% rh.
All GS humidifiers are rated for the clearance to shown in Figure 4.
Location of the steam distributor should be minimum of 36” above the humidifier.
Do not locate humidifier any further than absolutely necessary from steam distributor location. Net output
will be reduced as a result of heat loss through steam line. Also, increased static pressure (over 12" W.C.)
will result in hot water going down the drain. Consult factory if this situation occurs.
Where possible, mount humidifier at a height convenient for servicing.
Make sure the humidifier is mounted level.
Do not mount humidifier on hot surfaces.
The humidifier must be installed so that all electrical components are protected from exposure to water.
Do not mount humidifiers in an area where freezing may occur.
If humidifiers are mounted outdoors, a properly ventilated, temperature controlled, (above freezing),
weatherproof enclosure must be used.
Do not mount humidifiers on vibrating surface.
The humidifier shall not be installed directly on carpeting, tile or other combustible material other than wood
flooring.
Some insulating materials may be combustible. Prior to installing this appliance examine the area for
insulating material. If this appliance is installed in an insulated space, it must be kept free and clear of
insulating materials. If insulation is added after the appliance is installed, it will be necessary to examine
the area again.
GS Series Installation | 8
Inches w.c.
Gas
Min
Max
Natural
4.5
9.0
Propane
9.0
13.0
Warning:
Never use an open flame to check for gas leaks. If a leak does exist, a fire or explosion could occur,
resulting in damage, injury or death.
Gas Piping
Installation of piping must be in accordance with local codes, and ANSI Z233.1, “National Fuel Gas Code,” in
the United States or CSA B149.1 installation codes in Canada.
The following table indicates the maximum and minimum allowable gas pressures for the gas humidifier.
Table 3: Max & Min Gas Pressure
The gas inlet pipe size to the appliance is:
½” NPT for GS 100
¾” NPT for GS 200
1” NPT for GS 300 / 400
1 ¼” NPT for GS 500 / 600
Provide an adequate size gas supply line.
In all installations, a certified manual shut off valve, located outside the cabinet, must be installed. When
black iron gas pipe is used, a sediment trap must be located ahead of the humidifier gas controls. See
Figure 5: Gas Connection.
Leak test all gas connections external to the humidifier, using a commercial soap solution made to detect
leaks. Bubbles indicate gas leakage. Seal all leaks before placing the humidifier in operation.
The appliance and its individual shut-off valve must be disconnected from the gas supply piping system
during any pressure testing of that system at test pressures equal to or greater than 14” w.c. (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply piping system at test pressures equal or less than 14”
w.c. (3.5 kPa).
Dissipate test pressure from the gas supply line before re-opening the manual shut off valve to the
appliance.
9 | GS Series Installation
Figure 5: Gas Connection
Failure to follow this procedure may damage the gas valve. Over pressured gas valves are not covered by
warranty.
Do not use Teflon tape on gas line pipe threads. A flexible sealant suitable for use with natural gas and
propane gas is recommended.
Plan gas supply piping so that it will not interfere with removal of gas valves, blower assemblies, and front or
side service doors.
All gas piping should be adequately supported to prevent any strain on inlet piping.
The gas valve is provided with pressure taps to measure gas pressure upstream and downstream, (manifold
pressure). The minimum gas pressure shown is for the purpose of input adjustment.
A 1/8" NPT plugged tapping, accessible for test gage connection, must be installed immediately upstream of
the gas supply connection to the appliance.
GS Series Installation | 10
Warning:
Air supply line should not obstruct any services going to the humidifier front and right side cabinet
panels.
Combustion Air Requirements
General
Provide for adequate combustion and ventilation air in accordance with sections 5.3, air for combustion and
ventilation, of the national fuel gas code, ANSI z223.1, or sections 7.2, 7.3, 7.4 of CSA B149.1 installation
codes, or applicable provisions of the local building codes.
The required free area of supply air opening is:
13 in. Sq. (8,387 mm2), for GS 100
23 in. Sq. (14,839 mm2), for GS 200
35 in. Sq. (22,581 mm2), for GS 300
47 in. Sq. (30,323 mm2), for GS 400
59 in. Sq. (38,064 mm2), for GS 500
71 in. Sq. (45,806 mm2), for GS 600
Cabinet top and bottom contain air openings to provide combustion air to the forced draft blower. Do not
block these openings.
Excessive exposure to contaminated combustion air will result in safety and performance related problems.
Known contaminates include halogens, ammonia, and chlorides, excessive dust, lime or dirt. Excessive
exposure of electronics to the contaminants will also result in performance related problems. Contact nortec
technical services if you have any questions. If contaminants exist, isolate the unit from the contaminated
space.
Sealed Combustion Guidelines
Installation of the combustion air supply line must be carried out by adequately qualified personnel. All local
regulations relating to the provision of air supply systems must be observed and adhered to.
The air supply line and the exhaust must individually not exceed a respective equivalent length of 70 ft. (21
m). The vent pipe diameter must be maintained over the overall length of the vent.
The air supply line should be approximately as long as the flue gas venting and must be supported at every 5
ft. (1.5 m) and additionally at every pipe bend. At low temperatures, water condensation can form on the
outside of the pipe. To prevent this, it is recommended that the supply air line is insulated and an in line
heat is added. Consult factory.
Attach the air supply line to the manifold using a hose clamp or hose coupling if required. See Figure 6.
The air intake terminal and the flue gas terminal must end at an outside location. See Figure 8: Location of
air intake and glue gas terminal must comply with all local and national regulations.
11 | GS Series Installation
Warning:
Horizontal BH type venting must be used in a direct vent application.
Direct Vent Guidelines
Follow “sealed combustion guidelines”
All air piping must be listed type for direct vent application with sealed joints and seams, such as z flex.
The air supply line must be installed with air supply terminals provided.
Air hookup may be in plastic provided that it has fully sealed joints per CSA requirements.
Figure 6: Sealed Combustion and Direct Vent Connection
Exhaust Venting
General
The GSTC and GSP are classed category I and III fan assisted gas appliances. This allows two methods of
venting. Listed below are instructions for both venting systems, followed by specific requirements for each
system.
Review the requirements for both category I and III installations and select the venting method best suited
for the installation.
The maximum flue temperature is 400ºF for category I and category III installations. Normal operating range
is 360 to 380ºF.
Category I and III class can be used with sealed combustion option
Category III class must be used with direct vent option.
GS Series Installation | 12
General Requirements
The vent systems shall be listed to UL or UL/CSA standard and meet the installation requirements of the
national fuel code in the USA (ANSI z223.1) and the Canadian standards CSA B149.1 installation codes. Any
local jurisdictions reflecting changes to the above codes should be observed.
In applying the codes, reference should be given to the venting manufactures instructions, the serving gas
supplier regulations, and the specific instructions provided in this manual.
This appliance must be installed to comply with national regulations and codes. A qualified technician,
competent with these codes and the local requirements of the jurisdiction must carry out the installation.
Proper removal of combustion gases must be assured, and building materials must be protected from
degradation by flue gases.
Never mix venting types (B to BH or vice versa.) Never use two different manufacturer’s equipment for the
same chimney.
All vent runs should be as direct as possible with no more than 6 elbows in the system. Maintain an upward
slope of ¼” per ft on all horizontal vent pipe runs.
This appliance shall not be connected to a chimney flue servicing a separate appliance designed to burn
solid fuel.
This appliance may not be used in conjunction with a power venter or draft inducer.
For any vent lengths over 20 feet long, insulate the vent pipe to reduce the amount of condensate that could
form in the flue gases.
When the venting passes through a cold area or location that has large amounts of air passing over the
venting, it should be insulated to prevent condensation from forming inside the venting.
Vent pipe passing through walls, floors, and ceilings, must be installed with the proper clearances from
combustible materials, and venting manufactures fire stop equipment.
The venting shall not pass through any circulation air duct or plenum.
A drip “t” should be used for condensate removal. When a condensate drain is used it will be necessary to
install a trap to prevent flue gases from escaping. Install a trap with a minimum 12” standing water column.
Prior to activating the appliance, ensure that the trap is filled with water and that the drain terminates in
accordance with local plumbing codes.
Never vent into an unlined masonry or concrete chimney unless the chimney is sized and installed according
to the provisions of the national fuel code in the USA (ANSI z223.1) or the Canadian standards CSA B149.
Chimney or vent should extend at least 3’ (1 m) above a roof and at least 2’ (.6 m) above any ridge within 10’ (3 m) of the chimney. Local codes apply.
Install venting so as to prevent accumulation of condensate and have a means for condensate removal.
Plastic, PVC, CPVC and HTPV special gas vents are not approved for use with this appliance.
Select vent material and clearance according to the max vent gas temperature.
All horizontal runs must be adequately supported with hangers or straps to prevent sagging.
The vent must terminate at a sufficient height above the roof to prevent blockage by expected snowfall.
13 | GS Series Installation
Figure 7: Vertical Venting Using B Type
Figure 8: Vertical Venting Using B Type with Sealed Combustion
GS Series Installation | 14
UL Listed Cap
(by others)
Flashing,
4 in. (10 cm) min.
air space between
piping and combustible
materials
BH Vent
Maintain diameter of
exhaust outlet,
any combination of
vertical up / horizontal run,
max 100 ft (30 m),
slope 1/4 in./ft (2 cm/m).
2 ft (60 cm) min.
above any ridge
within 10 ft (3 m)
3 ft (90 cm)
min. above roof
Drain
(Note: Condensate
may require treatment,
consult local codes)
Support venting so
that weight is not
on exhaust outlet.
Condensate tee
(by others)
within 2 ft (60 cm)
of unit.
2 ft (30 cm)
min.
BH Vent Exhaust
Exhaust outlet
Install male to male
adapter (by others).
Terminate
Vertically
Horizontally
or
Horizontal exhaust
terminal must be
certified and can be
ordered from Nortec. If
BH venting used, orient
vertically, 6 in from wall.
Chose only one terminal
location (2 shown for
illustration only)
Figure 9: Vertical and Horizontal Venting Using BH Type
15 | GS Series Installation
Figure 10: Vertical and Horizontal Venting Using BG Type With Sealed Combustion
Use BH Vent for exhaust
and direct vent air intake.
- Maintain diameter of
exhaust outlet and intake.
- seal joints to meet
CSA 2.19.7,
- any combination of
vertical up / horizontal run,
- max 70 ft (20 m),
- slope 1/4 in./ft (2 cm/m).
Drain
(Note: Condensate
may require treatment,
consult local codes)
Support exhaust and
air intake lines.
Condensate tee
(by others)
within 2 ft (60 cm)
of unit.
2 ft (30 cm)
min.
Direct Vent Installation
Exhaust outlet
Install male to male
adapter (by others).
Terminate exhaust and
intake horizontally only
in same face of building.
-
- orient vertically,
- 6 in from wall.
Install Nortec or by
other certified terminals
Direct Vent may only be
installed with horizontal
BH Venting and with
horizontal exhaust and air
intake termination as shown.
Air Intake
Connect to intake
with hose cuff and
hose clamps
(by others).
Min 4 ft (1.2 m),
max 6 ft (1.8 m)
Figure 11: Direct Vent Installation
Figure 12: Vertical Co-Venting Using B Type
GS Series Installation | 16
Installation As A Category I Appliance
General
The GS Series humidifiers have a fan-assisted combustion which operates with a non-positive vent static
pressure when installed with the appropriate vent diameter.
Category I appliances must be vented vertically or nearly vertical (see Figure 7, 8, 9, 10 & 11).
This category appliance is restricted to vertical venting installations with limits placed on horizontal lengths
and vent diameters. Refer to the tables in local and/or national codes. No sidewall termination is accepted.
Vent piping must be UL or UL/CSA listed Type B. Required clearance for Type B vent is piping is 1” (25 mm).
A minimum equivalent vent length of 7 feet must be connected to the humidifier. Vent lengths must not
exceed 70’ (21 m). Each 90° elbow is equivalent to 10’ and each 45° elbow equals 5'. The vent run should
be as direct as possible with no more than 6 elbows in the system. Contact Nortec Technical Services if you
have any questions.
The vent pipe exiting the humidifier is sized for category III installations. A field supplied adapter is required
to increase the pipe immediately at the exit of the humidifier. The vent pipe must be expanded to the
minimum sizes listed below for each model, increasing as code requires.
The termination at the humidifier is a male connection. Standard venting hook-ups require a female path. It
is highly recommended that a female to female adapter be assembled onto the humidifier to establish the
proper venting sequence. Consult with the venting manufacturer for proper hook up.
Vent connectors shall not be connected into any portion of a mechanical draft system operating under
positive pressure.
Use only double wall (aluminum inner wall) b vent. Single wall venting cannot be used due to the increased
wet time in the lining. If the vent connector attaches to a lined masonry chimney, the chimney must be sized
and installed according to the provisions of the national fuel gas code or Canadian CSA B149.1 standards.
An approved venting manufacturer’s termination cap for the stack outlet must be used.
When the category I installation is selected it may be commonly vented with other listed gas fire appliances.
Total input rates of all appliances will determine the vent size the chimney must be sized and installed
according to the provisions of the national fuel gas code or Canadian CSA B149.1 standards.
A maximum of 4 gas appliances may be common vented on the same floor. Multiple story common venting
is not recommended.
Refer to the vent manufacturer’s instructions for proper clearances to combustibles.
Recommended B-Venting Manufacturers
Simpson Dura-vent
Selkirk Canada corporation
American metal products
Metal-fab Inc.
17 | GS Series Installation
Warning:
Provide a screen or barrier to prevent personal injury in areas where inadvertent personnel contact with
vent pipe can occur.
Figure 13: Exhaust Connection
Installation As A Category III Appliance
General
This venting system can be installed horizontally or vertically and can terminate on a rooftop or sidewall
provided the NFGC (Nation Fuel Gas Code) and CAN/CGA- B149 codes are followed. The venting
manufacturer instructions must also be followed.
Venting must be UL or UL/CSA listed, tested to ULC-5636 standard. Venting may be BH, L vent or Special
Gas Vent. The vent shall be listed and installed in accordance with the terms of the vent listing and the
manufacturer’s instructions. The instructions listed below should be followed as well.
A minimum equivalent vent length of 7 feet must be connected to the humidifier. Vent lengths must not
exceed 70’ (21 m). Each 90° elbow is equivalent to 10’ and each 45° elbow equals 5'. The vent run should
be as direct as possible with no more than 6 elbows in the system. Contact nortec technical service if you
have any questions
This category installation may not be common vented with any other natural draft gas appliance or power
assist appliance. All joints must be sealed using high temperature rtv silicone.
The gas humidifier is supplied with the following exhaust outlets.
GS 100 3”
GS 200 4”
GS 300/400 5”
GS 500/600 6”
The venting must remain the same diameter throughout the installation. Horizontal BH type venting must be
used in a direct vent application.
GS Series Installation | 18
Warning:
Provide a screen or barrier to prevent personal injury in areas where inadvertent personnel contact with
vent pipe can occur.
BH Vent Manufacturers
Flex-l international
Fas-n seal
Heat-fab Inc.
Z flex
Additional requirements when venting through a sidewall.
For sidewall venting, locate the humidifier as close as possible to the wall being used.
Locate the vent terminal at least three feet above any forced air inlet located within ten feet; or at least four
feet below, four feet horizontally from, or one foot above any door, window, or gravity air inlet into any
building.
A minimum horizontal clearance of four feet from electric meters, gas meters, regulator and relief equipment
is required.
For sidewall vent terminations, the humidifier must be installed with a certified vent terminal that can be
purchased from Nortec.
Locate the vent terminal at least 7 feet or 2.1 m above grade from public walkways, adjacent buildings,
operable windows and building openings, consistent with the National Fuel Gas Code ANSI Z223.1 and/or
CSA B149.1 Installation codes.
Locate the bottom of the vent terminal at least twelve inches above grade or ground, or normally expected
snow accumulation level. The snow level may be higher on walls exposed to prevailing winds.
Locate terminal at least 4 feet or 1.22 m from electric meter, gas meters, regulators, and relief equipment.
Avoid areas where local experience indicates that condensate drip may cause problems such as above
planters, patios, or over public walkways, or over an area where condensate or vapor could create a
nuisance or hazard, or could be detrimental to the operation of regulators, relief valves, or other equipment.
Refer to the vent manufacturer's installation instructions.
The vent terminal must be installed in the same atmospheric pressure zone as the combustion air inlet of
the humidifier. If this is not possible (as in cases of positive or negative room pressures) the humidifier
should be installed with the sealed combustion or direct vent option.
19 | GS Series Installation
Warning:
The electrical parts inside the humidifier are very sensitive to electrostatic discharge. Appropriate
measures against electrostatic discharge (esd protection) must be taken when carrying out installation
work.
Electrical and Plumbing
Electrical
Primary Wiring
All work concerning the electrical installation must be performed by qualified personnel.
The humidifier should only be connected to primary power (main power) after all installation work has been
completed.
An external disconnect switch must be installed close to the unit to allow for power interruption during
servicing and/or maintenance.
Humidifiers require field wiring to primary voltage terminal blocks. Depending on the unit, power
requirement must be 120 Vac or 208-240 Vac, 15 A, 20 A or 30 A separately fused circuit, single phase.
See Table 4 for details. Use only copper wire with a minimum 70 °C (158 °F) temperature rating. Wiring
can be fed through a 7/8" hole on the bottom or the top of the control compartment.
When installed, the appliance must be electrically grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical Code, ANSI/NFPA 70, and/or the CSA C22.1 Electrical
Code, if an external electrical source is utilized.
External wiring sizes must be in accordance with NEC and/or CEC and existing local electrical codes and bylaws.
Low Voltage Control Wiring
All GS models require at least one type of input control signal for unit operation. Refer to the sections below
that detail the types of controls that can be used with each model.
Low voltage control terminal strips are provided in the electrical compartment. Internal sides are factory
wired. External sides are to be field wired. Refer to the specific control-wiring diagram supplied with each
unit.
Field wiring from humidistat to humidifier and between devices should be shielded 18 AWG or heavier and
kept as short as possible.
Controls are available from NORTEC as accessories and can be ordered with the humidifier. Controls by
others may also be used as long as they meet the criteria noted below. The following is a summary of the
common types of controls that may be used with NORTEC Gas Humidifiers.
Wall or Duct Mounted Control On/Off Humidistat: Wired to make on drop in humidity, break on rise to
setpoint. Set to desired RH. Can be a make/break set of contacts from a Building Automation System.
Duct Mounted Safety High Limit On/Off Humidistat: Wired to make on drop in humidity, break on rise to
safety setpoint. Set to approximately 85% RH as a safety to prevent saturation and wetting in the duct.
Highly recommended for ducted applications.
Duct Mounted Safety Air Proving On/Off Switch: Wired to make when sensing air flow, break when no air
flow. Used as a safety to prevent saturation when there is no air flow. Highly recommended for ducted
applications.
GS Series Installation | 20
Voltage (V)
Rated Amps (A)
Suggested Breaker (A)
GSTC/GSP 100 Indoor
120
2.1
15
208-240
1.1
15
GSTC/GSP 200 Indoor
120
3.7
15
208-240
1.9
15
GSTC/GSP 300 Indoor
120
5.3
15
208-240
2.7
15
GSTC/GSP 400 Indoor
120
6.8
15
208-240
3.5
15
GSTC/GSP 500 Indoor
120
8.4
15
208-240
4.3
15
GSTC/GSP 600 Indoor
120
10
15
208-240
5.2
15
GSTC Outdoor 100
120
6.3
15
208-240
3.2
15
GSTC Outdoor 200
120
7.4
15
208-240
4
15
GSTC Outdoor 300
120
13.7
20
208-240
6.9
15
GSTC Outdoor 400
120
15.2
20
208-240
7.7
15
GSTC Outdoor 500
120
21
30
208-240
10.6
15
GSTC Outdoor 600
120
22.6
30
208-240
11.5
15
Wall or Duct Mounted Modulating Humidistat: Provides a modulating signal to the unit that represents the
output (up to 100%) required from the humidifier. Signal type can be changed in the field.
All GS models may be configured for either single or dual channel modulation. Control signals can be 0-10
VDC or 0-20 mA (0-5 VDC, 1-5 VDC, 4-20 mA and 2-10 VDC are also available). The unit must be ordered
from the factory for the desired signal type and number of channels. When configured for 2-channel
modulation the humidifier will generate steam only if both channels indicate a demand. If both channels are
demanding steam the humidifier will satisfy the lower demand signal.
Table 4: Current and Breaker Requirements for GS Series Units
21 | GS Series Installation
Figure 14: Primary 208-240 V 1 Phase Line Voltage Wiring To Unit
GS Series Installation | 22
NORTEC SERIES
EXTERNAL CONTROLS WIRING CONNECTIONS
LOW VOLTAGE TERMINAL STRIPS
May 27 2008
NORTEC SERIES
EXTERNAL CONTROLS WIRING CONNECTIONS
LOW VOLTAGE TERMINAL STRIP
WARNING: Failure to wire the controller
in accordance with the wiring diagram
supplied with the unit could permanently
damage the electronics. Such errors will
void the unit warranty.
- www.humidity.com -
EXTERNAL
INTERNAL
3
4
6
5
7
EXTERNAL
INTERNAL
Security Loop
24Vac
Signal
Input
"2”
Signal
Input
"1”
1
2
On/Off Control
Humidistat
Air Proving
Switch
High Limit
Humidistat
Blower
Pack
Other On / Off
Device
NOTE: If no On/Off Control
is used then a field jumper
must be connected across
terminals 1 and 2 in order
for the humidifier to operate.
5 Vdc
+ +
_
_
+
+
Single
Dual
POWER TO CONTROLLER OR
TRANSDUCER BY OTHERS
Both inputs to the
humidifier must be
the same type of
signal
Transducers:
Controllers (Humidistat):
Output signal across
3 - 4 and 3 - 5 increase
on RH rise
To be complete with RH
set point adjustment,
sensor circuit,
sensing element,
power source and
2 wire varying output signal.
RH demand are viewed on
display
Output signal across
3 - 4 and 3 - 5 decrease
on RH rise
To be complete with
sensing element,
power source and
2 wire varying output signal.
RH set point adjustment
is made at unit keypad.
RH set point and % RH
sensed are viewed on display
For all controller and transducer signals by others
8
24 Vac
Terminal 8 is a 24Vac input.
Upon receiving 24Vac a full tank
blowdown will be initiated
Figure 15: GS Series External Controls and Wiring Connections Low Voltage Terminal Strip
23 | GS Series Installation
Control Installation
Mount any wall humidistat (control or high limit) over standard electrical box at height similar to typical
thermostat. Any wall humidistat should be in location representative of overall space being humidified and
not in path of blower pack or air supply grill. Do not mount on an outside wall where temperature
fluctuations can affect control response.
Mount duct humidistat in location representative of overall air humidity, usually in return duct. Do not mount
it directly in front of steam distributor or in turbulent or mixing zone. Mount humidistat where air's humidity
and temperature are uniform and representative of spaces being humidified.
Mount duct high limit humidistat downstream of steam distributors far enough that, under normal humidity
and air flow conditions, steam will have been fully absorbed (typically at least 10 feet). It must be located to
sense high humidity only when uniform and representative air is over-humidified or approaching saturation.
Mount duct air-proving switch so that it is able to sense air flow or lack of it. Wire it to make when air flow is
sensed and break when air flow fails.
Check operation of all on/off controls before starting humidifier.
Calibration of controls (on/off or modulation) in the field may be necessary due to shipping and handling.
Verify humidistat accuracy before commissioning system.
GS Series Installation | 24
Figure 16: Plumbing Connections
Plumbing
Note: All water supply and drain line connections should be installed in accordance with local plumbing
codes.
Fill Water Supply Line
Each unit is supplied with an adapter for the fill valve (½”NPT). Fill rate 10 l/min all unit sizes. Size of piping
is a minimum ½” copper; recommend ¾” up to within 4 feet of unit.
Standard fill valves are sized for water pressure ranging from 30 to 80 psig (ideally 55 to 60 psig). For other
pressures, consult factory. This pressure should be measured at the humidifier if the water pressure is
suspect.
It is recommended to have a faucet installed close to the humidifier to allow quick filling of the system on
initial start up. This can also be very useful for mandatory cleaning of the unit.
ALWAYS supply and install a shut off valve and union in the water supply line dedicated to the humidifier to
facilitate servicing.
If water hammer occurs, install a shock arrester on the fill water line just before the inlet to the fill valve.
Water hammer will damage the fill valve.
A 1” air gap is designed into the fill system of the GS humidifier. Some local plumbing codes may still
require the installation of a double check valve on the fill line to the humidifier to prevent contamination of
the supply water system. Verify with local codes and install if necessary.
25 | GS Series Installation
Drain Line
The humidifier is equipped with a ¾”O.D. unthreaded drain outlet connection on the side of the humidifier.
A vacuum break valve is installed internal to the unit on the drain line. The drain water line must be piped to
a drain funnel to provide an air gap before connection to the building drainage system.
The air gap must be within 3 ft (1 m) of the humidifier.
The drain line should not end in a sink used frequently by personnel, or where plumbing codes prohibit it.
Route to a floor drain or equivalent for safety reasons. Internal drain water tempering will ensure a maximum
of 140ºF (60ºC) exiting water temperature.
Never install PVC piping as a drain line material. Always use material suitable for with-standing 140ºF
(60ºC).
Keep drain lines as short as possible. Keep drain lines sloped down, not level and not up since low spots in
drain lines will accumulate sediment and cause backup. The drain line should be 1-1.5" O.D. or larger.
Consult local codes.
When the drain pump is activated, the tank drains at a rate of 4.5-5.3 gal/min (18-20 l/min).
Aux Drain Port
An auxiliary drain port is also provided on the side of the humidifier. It can be used to manually drain the
unit, if required. The unit is shipped with this connection plugged. It is recommended to install a shut off
valve on this line (see Figure 16).
The auxiliary drain port is used with the standard freeze protection on Outdoor units. Install a shut off valve
on this line and pipe to the drain funnel (see Figure 16). The manual shut off valve must always be in the
open position when the unit is operating but can be closed for servicing of the unit.
Steam Lines and Condensate Line
Steam hoses and clamps are provided with the GS humidifier for connection to the steam lines. Refer to
Figure 17 for connection details.
For steam line installation between the humidifier and distribution system, consult the distribution system
installation manual. Steam Distributor Installation Manual. See Table 5: Steam Line Sizing for details on the
sizing and lengths of steam lines.
The GS Series of Gas-Steam humidifiers can develop steam pressures up to 12”w.c. to overcome duct and
steam line pressures. An enclosed trap on the drain line prevents steam from going to drain. Duct
pressures above 12” will cause steam to exits through the drain line. Consult factory.
GS Series Installation | 26
Humidifier
Steam
output
[ lb ]
MED-L copper tube
nominal steam
line size
Stainless steel tube
diameter (wall
thickness 0.065”)
Steam loss per foot
in condensation
[ lb/ft ]
Steam line
maximum
equivalent length
GS 100
100
1-1/2”
1-3/4”
0.11
90 ft
GS 200
200
3”
3”
0.16
90 ft
GS 300
300
3”
3”
0.16
180 ft
GS 400
400
4”
4”
0.22
180 ft
GS 500
500
4”
4”
0.22
220 ft
GS 600
600
4”
4”
0.22
260 ft
Nominal tube
size
Standard
90°-elbow
Standard
45°-elbow
Side-outlet
tee
Gate valve*
Globe valve*
1-1/2”
3.5 ft
1.75 ft
7 ft
0.8 ft
34 ft
1- 3/4”
3.5 ft
1.75 ft
7 ft
0.8 ft
34 ft
3”
5 ft
2.5 ft
11 ft
1.1 ft
54 ft
4”
8 ft
4 ft
15 ft
1.6 ft
80 ft
Figure 17: Steam Line Connection
Table 5: Steam Line Sizing
• Based on 3” duct static pressure, Maximum duct static pressure for GS is 12” w.c.
*Valve in full open position.
27 | GS Series Installation
Table 6: Effective Lengths of Typical Steam-Line Fittings
Outdoor Installation
GS Outdoor units are CSA certified for outdoor installation and come complete with exhaust venting and
internal ventilation (cooling) for the electronics. Heaters for freeze protection are standard with outdoor
units. All installations must conform with local building codes or, in the absence of local codes, with the
National Fuel Gas Code ANSI Z223.1 in the United States or CSA B149.1Installation codes in Canada.
NORTEC cannot accept responsibility for installation code violations.
Mounting
NOTE: Whenever possible do not expose drain water within the outdoor cabinetry. This could result in water
damage to electronic components. If a drain pan needs to be inside the cabinetry be sure to seal around it
so the cabinet doesn’t become over humidified during the drain cycles.
Typical rooftop installations are shown in Figure 18 & 19.
The GS Outdoor unit comes standard with cutouts in the base to allow for lifting by a forklift. When lifting by
this method, ensure that the forks extend across the entire base to prevent tipping or damage to the unit.
The enclosure also comes complete with four (4) removable lifting lugs fastened to the base. All four lugs
must be utilized if moving the unit in this manner. Protect the cabinet from damage from the lifting
cables/chains during lifting. The lifting lugs should be removed from the base once the unit has been
correctly positioned on the curb mounting.
See Figure 20 for clearance details.
The integral base of the GS Outdoor model is designed to mount on a curb. The curb must be built to
structurally support the entire weight of the humidifier when in operation. Required curb dimensions are
given in Figure 21.
Ensure that the humidifier is mounted level.
The pan in the bottom of all outdoor models has a pipe chase for routing of services into the humidifier from
below.
It is not necessary to make the hole in the roof the same size as the curb. The curb drawing shows the
location and size of the pipe chase required. The pipe chase should be sealed when the installation is
complete to ensure positive or negative pressure from the building.
The panels of the outdoor model have louvers to provide ventilation for the electronics and air for the
combustion process. Locate the unit so that louvered panels are a minimum of 10 ft from any mechanical
exhaust outlet.
When mounted on the curb, the lowest air intake louvers must be a minimum of 12” above any surface
where snow or ice could accumulate. In areas where normal snow accumulation is higher, mount the unit
accordingly.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of the humidifier.
The humidifier may be installed directly on combustible flooring or, in the U.S., on wood flooring or Class A,
Class B or Class C roof covering materials.
GS Series Installation | 28
Figure 18: GSTC Outdoor Typical Installation Rooftop with AHU
29 | GS Series Installation
Figure 19: GSTC Outdoor Typical Installation Rooftop without AHU
Figure 21: Roof Curb Dimensions
Figure 20: GSTC Outdoor Clearance
GS Series Installation | 30
Figure 22: Gas Piping
Figure 23: Gas Piping with Over Pressure Device
Gas Piping
Installation of piping must be in accordance with local codes, and the National Fuel Gas Code ANSI Z223.1
in the United States or CSA B149.1 Installation Codes in Canada.
Refer to the indoor gas piping installation guidelines for gas line sizes, pressures, leak testing procedures,
and safety instructions.
Gas lines are to be routed to the outside connection on the right side near the back of the unit. The
installation of a sediment trap and a certified manual shut-off valve are required outside of the unit. The gas
piping must not block access to or prevent opening of the right side service door. Refer to Figure 22 for
details.
Nortec recommends that each Gas Fired Humidifier has its own regulator installed in line to the unit. The
operating Natural Gas pressure supplied for the GS units must be in the range of 5-9” of Water Column and
propane version 10-14” of Water Column.
Over pressure protection devices shall be provided to prevent the pressure in the piping system from
exceeding that value that would cause unsafe operation of any connected and properly adjusted Gas
utilization equipment. See Figure 23.
If the system has a pressure that is higher than the max working pressure of our humidifier, then an Over
pressure protection system is required. If there is an Over pressure protection device installed, it MUST
consist of 2 devices in Series. (A pressure regulator plus one other device) Both these devices must be able
to work on their own without damaging any downstream piping or appliance, and the only way the
downstream system can be damaged is by the failure of both devices.
31 | GS Series Installation
Figure 24: Exhaust - Outdoor Units
Figure 25: Electrical Box
Exhaust Venting – Outdoor Units
All required exhaust venting is provided with each GS Outdoor model, by Nortec, including rain cap and
storm collar. All venting components external to the unit are shipped with the unit and must be installed on
site. Refer to Figure 24 for venting components.
Each vent length and the rain cap have a built-in mechanical locking band and gasket. Simply push together
each component to the stop bead, which provides an air & water-tight seal. Then tighten the integrated
locking band on each component to complete the installation of the exhaust venting.
The rain cap must extend at least 2 feet above any ridge within 10 feet of the unit. The exhaust venting can
be extended using additional vent lengths purchased from Nortec.
Electrical Installation
Power and control wiring is to be routed into the humidifier through the pipe chase in the base pan of the
outdoor models located in the burner area.
Installation details for primary and low voltage control wiring are the same as for indoor units.
A field supplied NEMA rated weatherproof disconnect switch must be mounted external to the GS Outdoor
unit to allow for power interruption during servicing and/or maintenance. A mounting plate, located on the
front of each outdoor model above the electrical access door, is available for mounting of the disconnect
switch. Two electrical conduits are provided for routing the primary wiring to the disconnect switch and then
back inside the enclosure to the main power terminal strip. See Figure 25 for details.
GS Series Installation | 32
Figure 26: Fill Water Connection
Figure 27: Drain Connection
Fill Water Supply Line
Each unit is supplied with a ½” NPT male connection to the fill valve. Refer to Figure 26 for connection
details. A minimum fill rate of 10 l/min (2.6 gal/min) is required for all unit sizes. Allowable pressure range
is 30-80 psig.
Always install a manual shut off within the building to allow isolation of the water to the unit. A union must
be installed on the fill line prior to the fill valve to allow for servicing.
Heat trace fill line piping above rooftop from the pipe chase up to the fill valve.
Drain Line
GS Outdoor units have an integrated 12”w.c. trap and vacuum break valve on the drain line. A drain hose,
connected to the outlet of the internal trap, terminates at the pipe chase in the burner section.
Route the drain hose to a drain funnel in the building to provide an air gap before entering main building
drain/sewage system.
When the drain pump is activated, the tank drains at a rate of 18-20 l/min (7-8 gal/min).
Drain piping must be rated for 212ºF (100ºC).
NOTE: Whenever possible do not expose drain water within the outdoor cabinetry. This could result in water
damage to electronic components. If a drain pan needs to be inside the cabinetry be sure to seal around it
so the cabinet doesn’t become over humidified during the drain cycles.
33 | GS Series Installation
Auxiliary Drain
Standard GS Outdoor units come with a capped ¾”NPT auxiliary drain connection at the bottom of the tank.
It is recommended to install a manual shut-off valve on this connection and route to drain (field supplied air
gap required).
GS Outdoor units standard with a freeze protection package have a normally open drain valve mounted at
the auxiliary drain connection and piping that terminates at the pipe chase in the base pan. This valve
opens and will drain the contents of the tank in the event of a power failure. Install a manual shut off valve
on this line and pipe to the drain funnel. This valve must always be left in the open position when in
operation but can be closed for servicing of the unit.
Drain pipe should be capable of withstanding 212°F (100°C) temperatures.
Steam Lines
The steam outlet connection is located at the back of the GS Outdoor unit. Steam hose(s) and clamps are
supplied with the unit and are intended to provide a flexible coupling outside of the unit to the building
steam lines. See Figure 28.
Figure 28: Steam Connection
GS Outdoor models can develop steam pressures up to 12”w.c. to overcome duct and steam line pressures. Pressures above 12”w.c. will cause steam to exit through the drain line.
Steam lines can be routed to an air handler on the roof or pipe chased (external to the unit) through the
rooftop to enter the building.
All steam lines must be insulated to reduce losses.
For steam line installation guidelines, consult the distribution system installation manual (Steam Distributor
Installation Manual.
GS Series Installation | 34
Operation
Combustion
The combustion system is based on a fully modulating forced draft combustion air blower(s), a negative
pressure regulated gas valve, and a 100% premix burner. On a call for humidity, the combustion air
blower(s) starts and creates a negative pressure(s) across an orifice located at the air inlet. The blower is
energized to purge the system, and then the hot surface igniter is activated. During this time the electronic
ignition module does a diagnostic check of safety systems including the air proving switch which senses the
negative pressure at the air inlet orifice. After the function of the safety systems has been verified, the gas
valve(s) will open and the gas/air mixture is ignited by the hot surface igniter. If a flame is sensed by the
flame sensor, the gas valve(s) remains open and combustion continues. If a flame is not sensed, the above
sequence is repeated to a maximum of three times after which the ignition module will lock out. The gas
valve(s) maintains a constant ratio air to gas independent of blower speed or external conditions. This air
and fuel is thoroughly mixed in the blower(s) and then forced through the burner ports where ignition occurs.
Hot products of combustion are forced through a baffle inside the heat exchanger and then vented outside.
The heat exchanger has a large flat surface to minimize scale build-up and promote scale shedding to the
bottom of the tank. This self-cleaning action helps to maintain the efficiency of the heat exchanger while the
smooth surfaces allow for easy cleaning when necessary. The heat exchanger has been heat treated to
protect against possible stress-corrosion cracking.
The GS 100 has a single removable combustion chamber/heat exchanger. The combustion system is
duplicated on larger units with multiple chambers inside a common tank.
Water Management
The GS Series of humidifiers is equipped with a unique float chamber water level monitoring device. Two
magnetic floats (one is a backup) measure 5 different water levels in the humidifier for proper operation. The
float chamber and board are located away from the boiling action to increase reading accuracy and reduce
mineral build-up since it is not in the boiling water. The float chamber is connected to the tank under the
water level and above the water level to ensure equalization of pressure between the tank and float
chamber. In addition, cooling water is introduced in the float chamber to reduce scale build-up. The unit also
includes an internal 1” air gap and a vacuum breaker to prevent siphoning effect.
On initial start-up, the solenoid operated fill valve fills the tank. The water level reaches the backup float first
and then the main float. If the backup and main floats do not read the same water level during the
operation of the unit, the unit will shut down on a fault. The unit will continue to fill the unit to the top green
position. The drain pump will then be energized to drain the water level down to just below the bottom red
position and then the fill valve will energize again to fill the unit to the middle yellow position. During this
time the software is performing a test on the fill valve and drain pump.
If a demand signal is present, the unit will then begin the combustion sequence. As the unit operates, the fill
valve with be pulsed to maintain the water level between the yellow and green positions. During steam
production the unit will also check if the floats and drain pump are operational by activating a drain
sequence every 24 hours (adjustable to time of day).
35 | GS Series Installation
Start-Up Procedure
Start-Up Checklist
Before the GS humidifier is operated for the first time, a complete inspection must be performed to ensure
that the installation and all water, gas, steam, electrical and venting connections to the humidifier conform
to the guidelines in this manual. Complete the checklist before commissioning the unit.
Qualified personnel must correct any deficiencies with the installation before commissioning takes place.
Prior to starting the humidifier, it is necessary to ensure that no dirt or dust has accumulated in the
electronics compartment or the burner area. A build up of dust on the electronics can cause overheating
and early failure of the components. If necessary, clean the area around the humidifier to prevent
contaminants from being drawn into the combustion blowers.
Filling The System
Before the GS unit will initiate combustion it must be filled with water and the internal controller must have
completed a self-test to verify that the water fill system, level controller, and drain pump are functioning
correctly.
Close the shut-off valve in the gas supply line.
Figure 29: Plumbing Connections
Remove any demand signal to the unit.
Open the shut-off valve in the water supply line.
Switch the humidifier on.
The fill valve will energize and the tank will begin to fill (fill time is approximately 10 to 30 minutes depending
on unit size). Once the float chamber has registered low water level, the unit will perform an internal test of
the fill and drain system as described in the Water Management section.
At the completion of the test, the float chamber will indicate middle float position (green LED) and the unit
will go into standby mode until a demand signal is received.
Proceed to the safety shut-off test.
GS Series Installation | 36
Testing the Ignition Safety Shut-Off
Test the ignition system safety shut-off in the following method.
Close the shut-off valve in the gas supply line.
Set the demand signal to the humidifier to 100%.
Ensure all external controls connected to the security loop are closed.
Switch the humidifier on.
At the completion of the float test, the humidifier will begin the combustion sequence by energizing the
combustion blowers.
All blowers will run at full output for 30 seconds to pre-purge the combustion chamber. During this time the
controller will monitor that all air proving switches closed to prove air flow.
The igniter(s) will be energized for 15 seconds, allowing it time to heat to the appropriate ignition
temperature and the gas valve will be energized.
After 4 seconds both the gas valve(s) and the igniter will be de-energized.
After three trials for ignition (complete with pre-purge) the red LED on the ignition control module will begin
blinking to indicate a safety lockout and a fault message will be displayed on the humidifier display.
Note: On multiple burner models, each burner tries to ignite in sequence. It is necessary to wait for all
burners to cycle to complete the test.
Manually re-open the gas supply to the humidifier. No gas should flow to the burner(s).
To reset the humidifier, shut off the power switch, and then turn the power back on.
Starting the Humidifier
Once the tank has been filled and the ignition safety test has been performed as outlined above, the
humidifier is ready to be put into operation.
Verify that the inspection checklist has been completed and all deficiencies with the installation have been
corrected.
Open the shut-off valve in the gas supply line.
Open the shut-off valve in the water supply line.
Ensure all external controls connected to the security loop are closed.
Verify that the building demand signal is connected to the humidifier.
Install and secure all cabinet service doors.
Switch the humidifier on.
At the completion of the float test, the humidifier will begin the combustion sequence and each burner will
ignite in sequence.
Depending on the system demand the combustion blowers will modulate faster or slower to control the
burner input.
The water in the tank will heat up and begin to boil, delivering steam to the distribution system.
During the boiling sequence the water fill valve will periodically activate to replenish water that has
evaporated from the tank.
Once the humidity requirements have been satisfied (demand drops below minimum %) all gas valves will be
de-energized and the blowers will be shut off after performing a post purge of the combustion chamber.
37 | GS Series Installation
The humidifier will go into standby mode until the next call for humidity (demand rises above minimum %) at
which time the unit will again begin the combustion sequence.
Taking Out Of Operation
If it is required that the humidifier be taken out of operation (e.g. for service or end of season shut-down),
proceed as follows:
If the unit is firing, remove the demand signal or open the security loop, allowing the burners to shut off and
the blowers to perform a post purge of the heat exchangers before shutting off.
Switch the main power switch from On to Off and then to the Drain position. The drain pump will be
energized and the tank will begin to drain.
Once the tank has completely emptied shut off the drain switch.
Close the shut-off valve in the gas supply line.
Close the shut-off valve in the water supply line.
Isolate the humidifier from the electrical power supply at the main disconnect switch.
GS Series Installation | 38
Humidifier Mounting
Verify proper clearances around the unit.
Humidifier mounted level.
Humidifier properly secured to stand and stand bolted to floor.
All service doors accessible.
Roof curb sized correctly (Outdoor Model Only).
Gas Piping
Correct gas line size installed.
Certified manual shut off valve and union installed.
Sediment trap installed.
Gas piping leak tested.
Air purged from lines.
Proper gas supply pressure.
Regulator dedicated for each gas unit.
Exhaust Gas Venting
Comply with local regulations.
Proper venting materials used (B or BH) – refer to gas codes.
Maximum vent length of 100 feet (70 feet for direct vent models).
Proper pipe diameter used.
Condensate tee installed.
Steam Lines
Slope up 2” per 12”
Sloped back to drain
Slope down ½” per 12”
Trapped 2” more than static duct pressure
Traps size ____________
Insulated
Length/Size ____________
90 deg. Elbows qty: ____
45 deg. Elbows qty: ____
Can condensate be trapped anywhere in the steam line? yes ___ no ___
Condensate Lines
Sloped back to drain
Trap is greater than 2” duct static pressure
Size of trap____________
Supply Water Line
Nortec supplied adapter installed on fill valve (½”NPT)
Manual shut off valve and union installed
Verified pressure (30 – 80 psig)
Water source of 10 l/min (2.6 gpm)
Leak tested
½” dia. At max 4ft of the unit
Table 7: GS Inspection Check List
39 | GS Series Installation
Drain Lines
Air gap located within 3ft of the unit
Minimum drain line size of 1” in dia.
Downward slope
Tundish (funnel) installed to provide air gap
Temperature rating of piping
Hose connections tightened
Auxiliary drain piped with shut off valve to tundish
Water Quality
Well water
City water
Softened water
RO/DI water
Conductivity:_______mhmos
Hardness: _______GPG
Silica____ppm
Chlorides:_______ppm
pH:_______
NOTE: Failure due to chloride corrosion is not covered under Nortec’s standard warranty if chloride
concentration is allowed to reach elevated levels in the tank. Consult factory for more information.
Electrical Installation
Comply with local regulations
Proper supply voltage (must match rating plate) and breaker size
Electrical disconnect switch close to humidifier
Cables properly affixed
Low voltage wiring & control signal(s) wired to correct terminals
Humidifier configured for correct control signal(s)
Type Of Controls Installed / Location Wiring / Setting
High Limit ______________________________
Air Proving _____________________________
Modulation Control ________________________
On/Off Control ___________________________
Controls by Nortec ________________________
Controls by Others ________________________
GS Series Installation | 40
Scale Management
General
The gas humidifier will periodically “blowdown” water from the tank to reduce the concentration of total
dissolved solids that accumulate during long term operation. Gas Humidifiers are shipped factory set with a
blowdown of 25%. This setting ensures that scale build-up will be minimized for all water conditions.
Once the water conditions are known, the blowdown rate can be adjusted by software (GSTC models) or by
using dip switches on the logic control board (GSP models).
Another effective means of controlling the amount of scale in the tank is with the use of the Full Tank
Blowdown (FTBD) built into the software. When this feature is activated, the drain pump will be energized to
drain the entire contents of the tank and then the tank will be refilled with fresh water, thus keeping the
amount of total dissolved solids to a minimum. The feature can be programmed in the software to occur
after a specific amount of operating time and can also be triggered by a signal sent to the humidifier from a
building management system.
Water Quality
Due to the wide range of water conditions found throughout North America it is important that the blowdown
is set according to the local water conditions. By water conditions we are referring to the hardness of the
water supplied to the humidifier. The hardness is measured in grains per gallon. It is also important to test
for silica content. Silicates may cause foaming and contribute to scale buildup in the humidifier tank and
float chamber.
Figure 30: Site Water Test Kit P/N 1507214
If you are unaware of the hardness or silica content of your water supply, there are many “do it yourself” kits
which can be purchased, or there are several companies that will perform the tests for a reasonable price.
You can even contact your municipality for your water condition or order the NORTEC water test kit.
NOTE: Water quality conditions resulting in component failures are not covered under NORTEC’s standard
warranty.
Silica Test: Measured in ppm (parts per million) Follow the directions with the kit. A high reading will
decrease the performance of your system. The recommended operating range for silica is 0 ppm to 14 ppm.
Note: A high silica content along with a high hardness content may increase the service intervals of the
system. Consult the factory if this condition exists at the site.
41 | GS Series Installation
Technology
Water /
Type
Water Cond.
Range
Hardness
Range
Silica Range
Alkaline
Range
Chlor.
Range
Gas-fired
Micromhos
GPG
PPM
pH
PPM
Potable
0-1500
0-12
0-14
6.5-7.5
0-40
Treated
0-100
0-1
0-1
7-7.5
0-40
Hardness: Measured in gpg (grains per gallon). Follow the instructions on each individually wrapped test
strip and use the colour chart provided. The recommended operating range for hardness is 0 gpg to 12 gpg.
Note: High hardness along with high silica may increase the service intervals of the system. Consult the
factory if this condition exists at the site.
pH: Follow the directions on the test strip bottle. The recommended operating range for pH is 6.5 to 7.5 on
the colour scale. Consult the factory if outside these parameters.
Chlorides: Measured in ppm (parts per million). Follow the directions on the test strip bottle. The
recommended level for chlorides is not to exceed 40 ppm.
NOTE: Failure due to chloride corrosion is not covered under Nortec’s standard warranty if chloride
concentration is allowed to reach elevated levels in the tank. Consult factory for more information.
High levels of chlorides will attack stainless steel. Consult the factory for additional information if your water
contains high levels of chlorides.
Conductivity: Measured in micromhos. Follow the directions for the conductivity pen found inside the box.
Multiply the digital reading by 1.5. The recommended operating range for conductivity is 0 - 1500
micromhos. Consult the factory is you measure outside these parameters.
Table 8: Water Quality Ranges
Nortec recommends performing a semi-annual water analysis to ensure optimal performance.
The humidifier is intended to operate on cold potable tap water.
DO NOT use a hot water source to supply the humidifier. Minerals will adhere more easily to surfaces and
the fill valve's small flow regulating orifice could become plugged.
Consider using a water softener. Longer operating times between tank cleaning will be reached on softened
water.
Reverse osmosis (RO) water can provide very long times before cleaning is required since it is cleaner than
softened water. Deionized (DI) water may be used with all models. Consult your Nortec representative for
quote on a water treatment system.
Safety Instructions
Refer to pages 1 and 2 of this guide, as well as all other marked safety instructions.
GS Series Installation | 42
Fault Conditions
General
This appliance is equipped with a self diagnostic ignition module which identifies a fault code when it occurs.
Refer to the fault & warning list.
GSTC Models
Faults are indicated with a fault message on the display of GSTC models. Recovery from lockout requires
resetting of the humidifier. This can be achieved by momentarily shutting off the power switch then turning it
back on, or by pressing the reset button on the logic control board mounted inside the electrical cabinet.
A history of all faults is stored in memory of the software and can be viewed through the service level on the
display. Refer to the keypad display menu structure at the end of the manual.
GSP Models
Faults are indicated on GSP models with a fault code on the small display screen attached to the logic
control board. The display can be viewed by removing the front electrical door. Check the display for the
fault code before shutting off power to the unit. Resetting the humidifier clears the fault. This can be
achieved by shutting off the power switch, then turning it back on, or by pressing the reset button on the
logic control board. A list of all fault codes and the type of fault they represent is located near the back of
the manual.
43 | GS Series Installation
Maintenance
General
To ensure proper performance and long operating life of the GS humidifier, it is recommended that the
appliance and installation be inspected at least once a year by a qualified service person. A proper
maintenance schedule should be followed. Since the amount and type of maintenance required is generally
as a result of how much the humidifier operates, all GS humidifiers monitor the amount of steam produced
over time and will indicate when service is required. All units come factory set with a service interval of 500
hours. This service interval can be adjusted through software (GSTC models) or by dip switch settings (GSP
models) on the logic control board.
All maintenance work must be performed by experienced and trained personnel.
Periodic cleaning of the screens in the vent terminal (where applicable) is recommended.
NOTE: Use only NORTEC original parts to replace damaged or defective components. Failure to do so may
cause improper operation of the humidifier and will void warranty.
Draining the Tank
During extended periods of inactivity such as off season or periods of very low demand, it is advisable to
drain the water from the tank. On all models this is accomplished by switching the unit to “Drain”.
Do not remove the front clean out port on the tank until the unit has completely drained. On GS 300-600
units do not remove the top clean out ports on the tank unless the water has cooled or the unit has
completely drained.
Ensure that power is switched on again during periods of demand.
The GSTC model of the Gas Steam humidifier includes a pre-cleaning sequence feature. When activated
(through the keypad), the unit will flush the humidifier, refill with cold water, and flush again reducing the
scale accumulated at the bottom of the tank.
GS Series Installation | 44
Parts
30-days
after
initial
start-up
Mid
End of
Season
(2000
hours)
What needs to be done?
Regular Maintenance
Preventive Maintenance
Hot Surface
Ignitor
X
Check for continuity.
Replace hot surface igniter
and flame sensor with
replacement kit.
Flame Sensor
X
Check that Flame Sensor is
straight.
Clean sensor with fine steel
wool.
Gas Burner
X
Remove from the unit and
clean with compressed air
from outside matting.
NOTE: It is recommended to
replace the burner gasket
each time a burner is
removed.
Drain Lines
X
Switch to drain and make
sure water flows freely.
Tank X X
X
Adjust blow down time when
required. Check that scale
has not accumulated above
2".
Drill out tank nipples when
required to ensure nipples
are not blocked with scale.
Clean tank when required.
Clean tank.
Magnesium
Anode
x
Check for severe corrosion
or scale build up on anode.
Replace or scrape off scale
if necessary.
Float Chamber
X X X
Ensure floats move freely.
Clean scale from float
chamber and hose
connecting to it.
Fill Lines
X X X
Adjust blow down time when
required. Check that scale
has not accumulated above
2".
Drain Lines
X X X
Clean tank when required.
Gas Venting
X X X
Inspect for leaks. Ensure
terminal cap is clear and any
condensation produced flows
to condensate traps. Flue
temp should be between
350-400ºF.
Direct Vent
X X
Inspect for leaks. Ensure
intake terminal is clear.
H/L Stack
Sensor
X X X
Visual check that sensor is
intact, wired and attached to
the exhaust.
Table 9: Mandatory Maintenance Schedule
45 | GS Series Installation
Warning:
Water and scale may be hot enough to cause burns. Turn off humidifier and allow it to cool before cleaning.
Warning:
Do not clean the magnesium anode using any chemicals – the anode can react with acids to create flammable
hydrogen gas.
Cleaning the Steel Tank
General
It is recommended that the tank be cleaned at least once every season to maintain optimum operation. It
may be necessary to increase the frequency of cleaning or increase the blowdown setting in areas of hard
water or prolonged annual usage (see the Blowdown Setting section of this manual).
Cleaning of the humidifier is mandatory and must be performed on a regular basis.
To reduce cleaning time, use the pre-cleaning sequence on the GSTC model to help evacuate mineral debris
from the unit. Check the controller operation to activate this feature.
The combustion chamber walls are usually self cleaning. The mineral buildup flakes off, due to the
expansion and contraction and violent boiling action during on/off cycles, and settles to the bottom of the
tank. The combustion end block will have scale build up, as will the heat transfer tubes. These surfaces must
be cleaned at regular intervals.
Frontal port cleaning will be done through the front door of the unit. Remove cabinet door on the left of the
LCD display using a Philips screwdriver. Remove the side tank port opening, by removing the 3/16 nuts (½”
key or socket is needed). When removed, check the magnesium anode on the inside of the clean out port for
severe corrosion or scale build up. Replace or clean the anode as necessary. Do not use chemicals to clean
the anode, scrape off scale only.
Additional clean out ports are available on the top of the 300/400 and 500/600 lb/h tanks. To access
these ports, remove the top cabinet panel using a Phillips screwdriver. Remove the top clean out ports my
removing the nuts.
Removal of the heat exchanger(s) is not necessary to clean the inside of the tank.
Scoop out loose scale with a small shovel such as those used for gardening. Once loose scale is removed,
use a scraper such as a plastic windshield scraper to remove scale adhering to the tank or heat exchanger
walls. DO NOT use a metal scraper that will scratch the stainless steel surfaces of the tank. Once all large
pieces of scale have been removed, vacuum the tank out with a shop vacuum, fill part way with water, and
flush remaining sediment from the tank through the drain.
Due to the presence of polymer gaskets around the heat exchanger, do not use any harsh cleaning
chemicals. Please consult NORTEC prior to using any chemicals. Once the lid has been replaced, fill the unit
with water and examine for leaks.
Inspect the drain and fill lines assembly for scale build-up and if necessary remove them from the humidifier
for cleaning. If the blowdown assembly becomes blocked, scale build-up in the tank will be accelerated and
damage to the humidifier could result. The drain pump may be opened and cleaned. Consult NORTEC for
proper procedure.
GS Series Installation | 46
Warning:
Disconnect power before servicing this appliance.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
dangerous operation.
Reassemble the drain and blowdown if they were removed. Re-install tank top and side lids making sure
tank cover gasket is intact. Do not over tighten hold down nuts. If using a torque wrench do not exceed 50
in/lb (5 ft/lb). Re-seal all cabinet lids.
Cleaning the float chamber is accomplished by removing the hold down screws to access the floats and
using a small brush to gently clean the scale from the floats and chamber. Ensure that floats are back in
place and o-ring is properly seated before tightening screws on float chamber. Special attention must be
used when removing or re-installing the float chamber.
The switch board must be replaced into the same position as before cleaning and the tie -wrap must be used
to hold the float chamber in position.
Figure 31: Cleaning Tank Access
Servicing the Unit
General
The combustion chamber, heat exchanger and flue baffles are all fabricated from stainless steel and do not
require internal cleaning.
Should the main burner fail to light, or flame is not detected during the first trial for ignition period, the gas
valve is de-energized and the control goes through an interpurge delay before another ignition attempt. The
control will attempt two additional ignition trials before going into lockout. The valve relay will be deenergized immediately, and the combustion blower will be turned off.
47 | GS Series Installation
Service Checks
Combustion Blower
The combustion air blower motors are permanently lubricated and do not require lubrication. Clean out any
dust that has accumulated in the blower housing using an air gun.
Burner
The combustion air blower motors are permanently lubricated and do not require lubrication. Clean out any
dust that has accumulated in the blower housing using an air gun.
Flame Sensor
Flame current is the current which passes through the flame from the sensor to ground. The ignition module
must detect a minimum flame current of 0.7 microamps or a flame proving lockout will occur. To measure
flame current, connect a DC micrometer to the FC- FC+ terminals on the module. Meter should read 0.7 uA
or higher. If meter reads below “0” on scale, meter leads are reversed. Disconnect power and reconnect
meter leads for proper polarity.
NOTE: Proper polarity of supply voltage to the unit is necessary for flame sensing to occur. Oxidation on
flame sensing rod can reduce measured current. The oxidation can be cleaned from the sensing rod using
steel wool or an emery cloth.
Igniter Check
If the igniter is suspected of being defective then the following test may be carried out;
Ensure that the power and gas is switched off before servicing.
To test the igniter, disconnect the igniter leads from their terminal connections.
Using a multimeter set the Ohm’s scale and place one of the meter leads on one of the igniter wire ends and
the other meter lead on the end of the other igniter wire.
Gas Valve Setting
The gas valves used in the GS Series humidifier are negative-pressure-regulated valves. The valve setting
listed on the product rating plate is shown relative to atmosphere – this setting will always remain constant.
The valves come preset from the factory for the correct gas type. If an adjustment is required, use the
following steps:
Remove the screw from the pressure port marked “out” on the back side of the gas valve.
Connect a hose from a digital manometer (or an inclined manometer capable of reading below 0.1”w.c.) to the “out” pressure port.
Activate the humidifier and measure the gas valve pressure once the valve is energized and a flame is
established in the combustion chamber. Verify this pressure to the pressure listed on the unit specification
label.
If the pressure needs adjusting, remove the locking cap on the top of the gas valve.
Below the locking cap is an adjustment screw. Increase the pressure by turning the adjustment screw
clockwise, decrease by turning counter-clockwise.
NOTE: The pressure will fluctuate slightly as the unit operates, especially with very sensitive measuring
devices. Use the mean pressure value as the set pressure.
Once the pressure has been adjusted, replace the locking cap.
Replace the screw in the “out” pressure port and tighten firmly.
GS Series Installation | 48
Figure 32: Flame Sensor and Igniter Assembly
Figure 33: Burner Assembly
Component Replacement
Consult factory prior to the replacement of any component.
All service work must be performed by experienced and trained personnel.
Only use original NORTEC spare parts to replace defective components. Damage caused by non-approved
parts is not covered under NORTEC’s standard warranty.
Hot surface igniter and flame sensor replacement
Shut off electrical power and gas supply to the humidifier.
Remove the right side service access door.
Disconnect all wiring to the igniter and flame sensor.
Unscrew the fixing nuts for the igniter and flame sensor. Carefully remove the igniter and flame sensor.
Reverse the sequence above to install the new igniter and flame sensor. Always install a new gasket when
replacing the flame sensor and igniter.
CAUTION: The silicon carbide igniter is breakable. Handle with great care to avoid damage.
Burner Removal and Installation
Shut off electrical power and gas supply to the humidifier.
Remove the right side service access door.
Disconnect all wiring to the combustion blower, gas valve, air proving switch, igniter and flame sensor (note
the connector assignment).
Undo the union on the flexible gas hose and disconnect the gas hose from the gas valve.
Undo the 4 nuts on the blower outlet and remove blower, leaving the gas valve/air inlet assembly and the
fan-board mounting bracket (if present) mounted to the blower.
Undo the 4 large nuts that secure the burner mounting plate to the face of the heat exchanger and carefully
remove the burner assembly. Handle the burner only by the metal surfaces. Do not grip the ceramic
matting as grease, dust or dirt can affect the performance of the burner.
Reverse the sequence above to re-install the burner after cleaning or, if necessary, replace with a new
burner. Inspect and replace any gaskets that may be damaged. Tighten the 4 brass nuts of burner
mounting plate to a torque of 95 in-lb.
Leak test the gas train before re-commissioning the humidifier.
49 | GS Series Installation
Figure 34: Combustion Blower Replacement
Figure 35: Gas Valve Replacement
Removal and Installation Of The Combustion Blower
Shut off electrical power and gas supply to the humidifier.
Remove the right side service access door.
Disconnect all wiring to the combustion blower, gas valve and air proving switch (note the connector
assignment).
Undo the coupling on the flexible gas hose and disconnect the gas hose from the gas valve.
Undo the 2 screws that mount the gas valve/air inlet assembly to the blower and remove the assembly.
Undo the 2 screws of the fan-board mounting bracket (if present) and remove bracket, leaving electronic
board and igniter jump start module(s) attached.
Undo the 4 nuts on the blower outlet and remove blower.
Reverse the sequence above to install the new combustion blower. Inspect and replace any gaskets that
may be damaged. When mounting the gas valve/air inlet assembly to the combustion blower, ensure that
the cork gasket is properly oriented or gas flow through the valve will be impeded.
Leak test the gas train before re-commissioning the humidifier.
Gas Valve Replacement
Shut off electrical power and gas supply to the humidifier.
Remove the right side service access door.
Disconnect all wiring to the gas valve and air proving switch (note the connector assignment).
Undo the coupling on the flexible gas hose and disconnect the gas hose from the gas valve.
Remove the hoses from the air proving switch (note the connection layout).
Undo the 2 screws that mount the gas valve/air inlet assembly to the blower and remove the assembly.
Undo the 4 screws and remove the gas pipe connection from the inlet of the gas pressure regulating valve.
Undo the 3 screws that hold the air inlet venturi to the gas valve. Remove the rubber grommet and brass
orifice mounted in the outlet of the gas valve.
GS Series Installation | 50
Figure 36: Air Switch Replacement
Figure 37: Float Chamber Replacement
Undo the 3 screws of the pressure switch support bracket and remove the assembly from the gas valve.
Reverse the sequence above to install the new gas pressure regulating valve. Inspect and replace any
gaskets that may be damaged. When mounting the gas valve/air inlet assembly to the combustion blower,
ensure that the cork gasket is properly oriented or gas flow through the valve will be impeded.
Leak test the gas train before re-commissioning the humidifier.
Air Switch Replacement
Shut off electrical power to the appliance.
Remove right side service panel.
Remove wiring connections to switch.
Remove pressure hose(s) from switch noting proper location.
Remove screws (2) holding the switch.
Reverse above procedure to re-install.
Float Chamber Replacement
Drain the contents of the tank and then shut off electrical power and water supply to the humidifier.
Remove the left front service access door.
Remove the cable connection to the float board.
Remove the hose clamps on the float chamber and remove all hoses (note the correct hose assignment).
Squeeze both sides of the mounting bracket to release it from the slots in the support bracket behind the
float chamber.
Reverse the above sequence to install the new module.
Leak test all water connections before re-commissioning the humidifier.
51 | GS Series Installation
Figure 38: Ignition Module Assembly
Figure 39: Transformer Assembly
Ignition Module Replacement
Shut off electrical power to the humidifier.
Remove the front electrical access door.
Disconnect all wiring connections to the ignition module, labeling as required.
Remove the 2 screws securing the ignition module and remove.
Reverse the above sequence to install the new module.
Transformer Replacement
Shut off electrical power to the appliance.
Remove front access door.
Disconnect wiring connections from transformer leads labeling as required.
Remove screws (2) holding transformer.
Reverse above procedure to re-install.
Fill Valve Replacement
Shut off electrical power and water supply to the humidifier.
Remove the right side service access door.
Remove all wiring connections to the fill valve.
Remove the hose clamps on the fill valve outlets and remove hoses (note the correct hose assignment).
Remove the 2 screws securing the fill valve to the cabinet and remove the valve.
Reverse the above sequence to install the new module. Leak test all water connections before recommissioning the humidifier.
Anode Replacement
Follow the steps in Cleaning the Steel Tank on page 46 to remove the clean-out port.
Lift the corroded anode off the steel rod. Replace with a new anode.
Re-attach the clean-out port.
GS Series Installation | 52
Figure 40: Fill Valve Replacement
Figure 41: Drain Pump Assembly
Figure 42: Fill Box Replacement
Drain Pump Replacement
Drain the unit completely. If the pump is broken use the auxiliary drain out port.
Shut off electrical power to the appliance.
Remove front and right doors.
Remove wiring connections to the pump.
Remove hoses attached to the pump.
Reverse above procedure to re-install.
NOTE: To avoid water spillage (some water will be left on the tank bottom after manual draining) use shop
vac to remove left over water.
Fill Box Replacement
Take the humidifier out of operation.
Undo the screw (Phillips screwdriver) and remove the right
side panel.
Remove hose clamps on the fill box connections and pull off
the hoses.
Undo the two nuts securing the fill box to the face of the tank,
then remove the fill box.
Re-installation is carried out in the reverse sequence. Make
sure the hoses are correctly secured with the hose clamps.
53 | GS Series Installation
Removal of the Heat Exchanger
Take the humidifier out of operation.
Disconnect the gas supply pipe from the connection on the humidifier and close off the pipe.
Unlock and remove the right side panel(s).
On Direct Vent units only: Remove hoses from air intake manifold and air inlet elbows.
Dismount flue gas pipe at the flue gas outlet connection.
On Direct Vent units only: Dismount air supply pipe at the air supply connection.
Unlock and remove the left and the right top panels.
Free all cable connections to the components (combustion blower, ignition module, air pressure switch, etc.)
of the respective heat exchanger.
IMPORTANT: Note the connector assignment.
Undo the coupling of the respective flexible gas pipe and remove the flexible gas pipe.
Dismount the burner with the air blower and the gas pressure regulating valve of the respective heat
exchanger.
Unscrew the nuts and remove the flue gas manifold from the tank.
Unscrew the nuts on the heat exchanger and pull out the heat exchanger from the tank.
Re-installation is carried out in the reverse sequence. Replace all seals with new ones.
Figure 43: Heat Exchanger Assembly
GS Series Installation | 54
Request – 50%
Humidify
01/01/0912:00:00
Security loop: Closed
Menu
Main Screen
The Total Controller main screen displays general
information including the current demand, the status of the
humidifier, the status of the security loop, the current date
and current time.
Note: If a warning is displayed, press the “?” button to
display the troubleshooting information.
Control Information (Humidistat/BMS Control)
Displays the limited manual capacity, the current demand
from the controller to the humidifier and the current output.
Note: If the humidifier is set to dual channel, the demand
of the high limit humidistat will be displayed next to Limit.
Control Information (Humidity Sensor Control)
Displays the limited manual capacity, the current space
relative humidity and the relative humidity set point. The
current output of the unit is displayed at the bottom of the
screen.
Note: If the humidifier is set to dual channel, the limiting
humidity sensor’s measured RH and the desired set point is
also displayed.
Key Pad
GSTC Total Controller Flow Chart
Total Controller
Upon start up, the LCD display will illuminate, the humidifier will start filling and the software will perform a
float chamber level check. After the system test, the humidifier will enter normal operation mode and wait
for a demand signal. See troubleshooting section for corrective action if error is detected and displayed
during start up.
Note: The displayed parameters depend on the configuration of the GSTC and the operation conditions;
the display may vary from the following screenshots.
Information Level
Pressing the right and left arrow keys of the Total Controller displays the current humidifier setting screens.
NO changes can be made to the settings at this level. Access the User Level to change the parameters
displayed.
Humidifier Information
Displays humidifier information and settings, including the
model name and output, the control signal type and the
software version.
Note: The Multi Mode indicates if the humidifier is
operating alone (StandAlone) or if is linked to other units
(Master or Slave). The REG mode indicates the control type,
either humidistat (Demand) or Transducer (RH).
Burner Information
Displays burner information. The lead burner is the first
burner to ignite for the present cycle. If burners are
disabled, they will be denoted by an X.
Note: In this view, burner 6 is disabled (denoted by X).
TANK STATUS
Fill Valve: Off
Drain Pump: Off
Float Levl: 5
Run Time: 12 hr
Serv. Time: 500hr
Serv. Due: 425hr
Esc
Tank Status
Displays information about the tank, operating time and
service time. The run time is the total operating time. The
service time indicates the fixed service interval length. The
service due time is the time remaining until service is
required.
Note: The service interval can be set in the Service Level.
SENSOR INPUTS
Sec. Loop: Closed
OT Sensors: Closed
Tank Temp: Closed
Esc
Sensor Status
The SENSOR INPUTS screen displays the current status of
the Security Loop, the Over Temperature Sensors and the
Tank Temperature Sensor.
Note: The Security Loop and the Over Temperature
Sensors must be Closed for the humidifier to operate.
FEATURES LIST
Idle Mode: Idle Drain
FTBD: On
Time Prop.: On
BD rate: 25
Drain Cool: Smart
Float Ck: On
Esc
Features Information
Displays information of the User Settings including the idle
mode, the Full Tank Blow Down status, the Time
Proportioning status, the Blow Down rate percentage, the
Drain Cool mode and the Float Check status.
Note: See User Defined Settings to change these
parameters.
Blower RPM Information
The Blower RPM screen displays the current RPM of each
blower.
OPERATIONAL HOURS
Total: 12
Weighted: 4
Esc
Operational Hours Information
Displays the total operation hours and the weighted hours.
The weighted hours is calculated based on percentage of the
output of the unit.
Note: If the unit operates for 2 hours at 50% output, the
resulting weighted hour is 1 hour.
100%
0%
-4 hrs 0 hrs
Demand: 50%
Menu
Humidity Demand Trend
This screen displays the humidity output over the past 4
hours. The current demand is also displayed numerically at
the bottom of the screen.
57 | GS Series Installation
Password
0335
Enter Code
Confirm with Set
EscSet
Request – 50%
Humidify
01/01/0912:00:00
Security loop: Closed
Menu?
Main Menu
Service Level
User Defined Setting
Control Setting
Diagnostic Menu
EscSet
5
Control Setting
Source: Analog
REG Mode: Demand
MOD Mode: Dual CH
Multi Mode: StandAlone
CNT Type: 0-10V
LIM Type: 0-10V
EscSet
Source
Analog
Analog
Digital
EscSet
Control Setting
Source: Analog
Analog
Enter Password
Press the “Menu” button from any
status screen.
Enter the user level code 0335 using
the UP arrow key to change the
numbers. The RIGHT arrow key moves
to the next digit.
Control Setting
The Control Setting menu allows the
user to modify humidifier
communication settings and limit the
maximum capacity.
Source
Verify that the control signal matches
the control type.
Typically, analog signal are sent from a
humidistat and are 0-10VDC or 0-20mA.
Digital signals are sent through a
network connection.
Control Setting
Source: Analog
REG Mode: Demand
MOD Mode: Dual CH
Multi Mode:StandAlone
CNT Type: 0-10V
LIM Type: 0-10V
EscSet
REG Mode
Demand
Demand
On/Off
RH (P)
RH (PI)
EscSet
REG Mode: Demand
Demand
REG Mode
Corresponds to the type of control used.
Demand: Modulating control
(Humidistat or BMS) signal range
usually 0-10VDC or 0-20mA.
On/Off : On/Off space controllers.
RH(P) and RH(PI): Humidity sensors,
generally signals between 2-10VDC and
4-20mA.
Control Setting
Source: Analog
REG Mode: Demand
MOD Mode: Single CH
Multi Mode: StandAlone
CNT Type: 0-10V
LIM Type: 0-10V
SetSet
MOD Mode
Single CH
Single CH
Dual CH
SetSet
MOD Mode: Dual CH
Dual CH
MOD Mode
Configures the humidifier to operate
with a Single Channel (control only) or
Dual Channel (control and high limit).
Note: In Dual Channel MOD Mode, a
second Limiting control signal is
required.
User Level
Control Settings
GS Series Installation | 58
Control Setting
REG Mode: Demand
MOD Mode: Single CH
Multi Mode:StandAlone
CNT Type: 0-10V
LIM Type: 0-10V
Short CD: On
SetSet
Multi Mode
StandAlone
StandAlone
Master
Slave
SetSet
StandAlone
Multi Mode: StandAlone
Multi Mode
Sets the humidifier to either
independent operation (StandAlone) or
linked operation (Master or Slave).
Note: If Master or Slave is selected
see Multi Unit Op. Range Settings,
displayed after the Manual Capacity.
Control Setting
MOD Mode: Dual CH
Multi Mode: StandAlone
CNT Type: 0-10 V
LIM Type: 0-10 V
Short CD: On
Short CD T: 300
EscSet
CNT Type
0-10 V
0-5 V
1-5 V
0-10V
2-10 V
0-16 V
3.2-16 V
0-20 mA
4-20 mA
EscSet
0-10 V
CNT Type: 0-10V
CNT Type
Configures the voltage or amperage
range of the control signal. Verify that
the signal matches the controller
(humidistat, transducer or network
connection).
Control Setting
Multi Mode: StandAlone
CNT Type: 0-10V
LIM Type: 0-10 V
Short CD: On
Short CD T: 300
Time Prop.: On
EscSet
LIM Type
0-10 V
0-5 V
1-5 V
0-10V
2-10 V
0-16 V
3.2-16 V
0-20 mA
4-20 mA
EscSet
0-10 V
LIM Type: 0-10V
LIM Type
Configures the voltage or amperage
range of the high limit control signal.
Verify that the signal matches the high
limit controller.
Control Setting
CNT Type: 0-10V
Lim Type: 0-10V
Short CD: Off
Short CD T: 300
Time Prop: On
Manual Cap.: 100
EscSet
Short Cycle Delay
Off
Off
On
EscSet
On
Short CD: On
Short Cycle Delay
Prevents short cycling or frequent
turning on and off of humidifier. When
turned On, unit continues to operate for
set period of time after demand is met.
Note: When Short CD is turned On,
time must be specified. See Short CD T.
Control Setting
LIM Type: 0-10V
Short CD: Off
Short CD T: 300
Time Prop: On
Manual Cap.: 100
ModBus Settings
EscSet
Short Cycle Delay Tm
300 s
300s
EscSet
Short CD T: 300
Short Cycle Delay Time
Time humidifier stays on after demand
is satisfied.
Note: Short CD has to be turned On.
See above.
59 | GS Series Installation
Control Setting
LIM Type: 0-10 V
Short CD: On
Short CD T: 300
Time Prop.: On
Manual Cap.: 100
ModBus Settings
EscSet
Time Proportioning
On
Off
On
EscSet
On
Time Prop.: On
Time Proportioning
Allows the humidifier to modulate at low
demand.
Control Setting
Multi Mode: StandAlone
CNT Type: 0-10 V
Short CD: Off
Time Prop.: On
Manual Cap.: 100
ModBus Settings
EscSet
Manual Capacity
100%
100%
EscSet
Manual Cap.: 100
Manual Capacity
Allows the user to manually set the
maximum output of the humidifier.
The RH Settings submenu is used to adjust setpoint, the proportional band, and the integral time if REG
Mode is set to RH (P) or RH (PI) and the humidifier is connected to humidity sensors. Access the RH Settings
submenu by pressing the menu key while RH Settings is highlighted in the Control Settings menu.
CNT Set-P
Sets the humidity setpoint value. The
humidifier will attempt to maintain this
humidity level in the space where the
control transducer is installed.
GS Series Installation | 60
Control Band
15% RH
15%RH
MenuSet
CNT Band: 15% RH
15% RH
Limit Set Point
80% RH
80%RH
MenuSet
LIM Set-P: 80%
80% RH
Limit Band
15% RH
15%RH
MenuSet
LIM Band: 15% RH
15% RH
Limit Damping
5 s
5s
MenuSet
LIM Damp: 15% RH
5 s
Control Integral Time
5 min
5min
MenuSet
CNT Itime: 5 min
5 min
CNT Band
CNT Band should not normally be changed.
The CNT Band setting adjusts the band
within which the humidifier will modulate
between 0 and 100% output. (Default =
15%)
Int Time
Int Time should not normally be changed. Int
Time adjusts the frequency at which the
controller corrects for proportional control
error. It is only displayed if REG Mode is set
to RH (PI)
LIM Set-P
Sets the duct high limit setpoint value. As
RH in the duct approaches the high limit the
output of the humidifier will be throttled
back to prevent wetting the duct. (Default =
80%)
LIM Band
Should not normally be changed. The LIM
Band setting adjusts the band within which
the humidifier will throttle down the
humidifier output from 100 to 0%. (Default
= 15%)
Limit Damping
Sets the number of seconds the sensed RH
must exceed the limit band before output is
throttled down. (Default = 5 s)
61 | GS Series Installation
RH Alerts
On
On
Off
MenuSet
RH Alerts: On
On
RH High
75% RH
75%RH
MenuSet
RH High: 75%
75% RH
RH Low
33% RH
33%RH
MenuSet
RH Low: 33% RH
33% RH
RH Alerts
Sets whether the humidifier will display
warnings when humidity rises above or falls
below configured limits. (Default = Off)
RH High
Sets the RH level above which the humidity
must rise before a warning is generated.
Warning is only generated if RH Alerts is set
to on.
RH Low
Sets the RH level below which the humidity
must fall before a warning is generated .
Warning is only generated if RH Alerts is set
to on.
GS Series Installation | 62
Control Setting
Short CD: Off
Short CD T: 300
Time Prop.: On
Manual Cap.: 100
Multi Unit Op. Range
ModBus Settings
EscSet
Multi Unit Op. Range
Multi Unit Op. Range
Consult GSTC Networking 2-10 Units
Installation and Wiring Diagram Instructions
for configuration details.
Multi Unit Op. Range
Full Out.:100
Zero Out.: 0
EscSet
Full Out. : 100
Full Out.
100 %
100 %
EscSet
Multi Unit Op. Range
Full Out.:100
Zero Out.: 0
EscSet
Zero Out. : 0
Zero Out.
0 %
0 %
EscSet
Control Settings - Multi Unit Operation Range
63 | GS Series Installation
Control Setting
LIM Type: 0-10V
Short CD: Off
Short CD T: 300
Time Prop.: On
Manual Cap.: 100
ModBus Settings
EscSet
Modbus Settings
Parity: None1
Addr: 1
Timeout: 300
Rem Disabl: On
EscSet
Modbus Settings
Parity :None1
Parity
None1
None1
None2
Odd
Even
EscSet
None1
Modbus Settings
Parity: None1
Addr: 1
Timeout: 300
Rem Disabl: On
EscSet
Addr : 1
Addr
1
1
EscSet
ModBus
Settings for network
communication to BMS.
Parity
Error check for network
communication.
Address
Modbus Address
Timeout
Time to ModBus timeout in
the absence of a digital
demand signal.
Remote Disable
Allows unit to be disabled
remotely through the network.
Modbus Settings
Parity: None1
Addr: 1
Timeout: 300
Rem Disabl: On
EscSet
Timeout : 300
Timeout
300 s
300 s
EscSet
Modbus Settings
Parity: None1
Addr: 1
Timeout: 300
Rem Disabl: Off
EscSet
Rem Disabl : On
Rem Disable
Off
Off
On
EscSet
On
Control Settings - Modbus Settings
GS Series Installation | 64
Password
0335
Enter Code
Confirm with Set
EscSet
Request – 50%
Humidify
01/01/0912:00:00
Security loop: Closed
Menu?
Main Menu
Service Level
User Defined Settings
Control Setting
Diagnostic Menu
EscSet
5
User Defined Setting
Drain Cool: Smart
BD rate: 25
FTBD: On
FTBD Time: 23:30
FTBD Hours: 100
Idle Mode: Idle Drain
EscSet
Drain Cool
Smart
Off
On
Smart
EscSet
User Defined Setting
Drain Cool: Smart
Smart
Enter Password
Press the “Menu” button from any
status screen.
Enter the user level code 0335
using the UP arrow key to change
the numbers. The RIGHT arrow key
moves to the next digit.
User Defined Settings
Allows the user to configure
humidifier operation parameters.
Drain Cool
Configure drain tempering. Set to
Smart for efficient drain water
cooling.
User Defined Setting
Drain Cool: Smart
BD rate: 25
FTBD: On
FTBD Time: 23:30
FTBD Hours: 100
Idle Mode: Idle Drain
EscSet
Blowdown Rate
25 %
25%
EscSet
BD rate: 25
Blowdown Rate
The blowdown rate adjusts the
amount of water that is drained
each hour. The percentage relates
to the tank volume.
Note: Current setting: 25% of the
tank each hour.
User Defined Setting
Drain Cool: Smart
BD rate: 25
FTBD: Off
FTBD Time: 23:30
FTBD Hours: 100
Idle Mode: Idle Drain
EscSet
Full Tank Blowdown
On
Off
On
EscSet
FTBD: On
On
Full Tank Blow Down
The tank can be set to drain
completely at a set time of day after
a set interval of weighted hours.
Note: See FTBD Time to set time
of day and FTBD Hours to set
interval.
User Defined Settings
65 | GS Series Installation
User Defined Setting
BD rate: 25
FTBD: On
FTBD Time: 23:30
FTBD Hours: 100
Idle Mode: Idle Drain
Idle Drain: 72
EscSet
FTBD Time
Hour: 23
Minute: 30
EscSet
FTBD Time: 23:30
Hour : 23
Full Tank Blow Down Time
Set the desired time of day to
completely drain the tank and refill.
Note: Since the FTBD interrupts
humidifier operation, it is
recommended to set time outside
peak operation time.
User Defined Setting
FTBD: On
FTBD Time: 23:30
FTBD Hours: 100
Idle Mode: Idle Drain
Idle Drain: 72
Fill Corr: 100
EscSet
FTBD Hours
100 h
100 h
EscSet
FTBD Hours: 100
Full Tank Blow Down Interval
Set the desired weighted time
interval between FTBDs.
Idle Mode
Idle Drain
Idle Only
Idle Drain
Keep Warm
EscSet
Idle Drain
User Defined Setting
FTBD Time: 23:30
FTBD Hours: 100
Idle Mode: Idle Drain
Idle Drain: 72
Fill Corr: 100
Drain Corr: 100
EscSet
Idle Mode: Idle Drain
Idle Mode
Configures humidifier operation
when there is no call for humidity.
Idle Only: Humidifier is on standby.
Idle Drain: Humidifier drains after
specified idling time (see Idle Drain).
Keep Warm: Water in tank is kept
between 140-160ºF (60 -70ºC)
User Defined Setting
Idle Mode: Idle Drain
Idle Drain: 72
Fill Corr.: 100
Drain Corr.: 100
Float Ck: 23:30
Date: 01/01/09
EscSet
Fill Correction
100 %
100 %
EscSet
Fill Corr: 100
Fill Correction
Adjust the fill on and fill off times.
Values above 100% will increase
the fill on time and values below
100% decrease fill on time.
User Defined Setting
Idle Drain: 72
Fill Corr.: 100
Drain Corr.: 100
Float Ck: 23:30
Date: 01/01/09
Time: 12:00:00
EscSet
Drain Correction
100 %
100 %
EscSet
Drain Corr: 100
Drain Correction
Used to compensate for variation in
drain pump flow rates. The drain
correction adjusts the actual drain
duration by drain time. Increasing
drain correction increases drain
duration and decreasing correction
decreases drain time.
GS Series Installation | 66
User Defined Setting
Fill Corr.: 100
Drain Corr.: 100
Float Ck: 23:30
Date: 01/01/09
Time: 12:00:00
Unit Steam: lb/hr
EscSet
Float Check
Hour: 23
Minutes: 30
Status: On
EscSet
Float Ck: 23:30
Hour : 23
Float Check
Set the time of day the humidifier
performs a test of the float chamber
levels. The test can be turned On or
Off.
Note: The Float Check does not
interrupt humidifier operation and
can be set at any time of day.
User Defined Setting
Drain Corr.: 100
Float Ck: 23:30
Date: 01/01/09
Time: 12:00:00
Unit Steam: lb/hr
Language: English
EscSet
Date
Day: 1
Month: 1
Year: 9
EscSet
Date: 01/01/09
Day : 1
Date
Set the current date displayed on
the main screen. The date is factory
set.
User Defined Setting
Float Ck: 23:30
Date: 01/01/09
Time: 12:00:00
Unit Steam: lb/hr
Language: English
Contrast: 3
EscSet
Time
Hour: 12
Minute: 0
EscSet
Time: 12:00:00
Hour : 12
Time
Set the current time displayed on
the main screen. The time is set at
the factory.
67 | GS Series Installation
User Defined Setting
Float Ck: 23:30
Date: 01/01/09
Time: 12:00:00
Unit Steam: lb/hr
Language: English
Contrast : 3
EscSet
Unit Steam
lb/hr
kg/hr
lb/hr
EscSet
Unit Steam: lb/hr
lb/hr
Unit Steam
Set the units of the steam output.
Can be set to either pounds per
hour or kilograms per hour.
User Defined Setting
Float Ck: 23:30
Date: 01/01/09
Time: 12:00:00
Unit Steam: lb/hr
Language: English
Contrast : 3
EscSet
Language
English
English
French
German
Dutch
EscSet
Language: English
English
Language
Set the Total Controller’s displayed
language.
User Defined Setting
Float Ck: 23:30
Date: 01/01/09
Time: 12:00:00
Unit Steam: lb/hr
Language: English
Contrast : 3
EscSet
Contrast
3
3
EscSet
Contrast: 3
Contrast
Set the Total Controller’s LCD
display contrast.
GS Series Installation | 68
Password
0335
Enter Code
Confirm with Set
EscSet
Request – 50%
Humidify
01/01/0912:00:00
Security loop: Closed
Menu?
Main Menu
Service Level
User Defined Settings
Control Setting
Diagnostic Menu
EscSet
5
Service Level
Burner Disable
Service Tm: 500
Tank Drain
Tank PreClean
Reset Error History
Reset Serv. Reminder
Service Level
The service level allows access to software controlled service tools and access to service time
intervals and reminders.
Burner Disable
Allows the user to disable and enable burners. Disabled burners are displayed in the information
level. Burners can only be disabled when the security loop is open.
Service Level
Burner Disable
Service Tm: 500
Tank Drain
Tank PreClean
Reset Error History
Reset Serv. Reminder
EscSet
Service Reminder
500 h
500 h
EscSet
Service Tm:500
Service Tm
Set time interval of the service
reminder.
Note: Do not modify. Interval set
from factory.
Service Level
69 | GS Series Installation
Service Level
Burner Disable
Service Tm: 500
Tank Drain
Tank PreClean
Reset Error History
Reset Serv. Reminder
EscSet
Interrupt Operation
and Drain Tank
NoYes
Tank Drain
Manual Drain
19m 45s
Stop
Tank Drain
Initiate software controlled complete drain of the tank.
Service Level
Burner Disable
Service Tm: 500
Tank Drain
Tank PreClean
Reset Error History
Reset Serv. Reminder
EscSet
Interrupt Operation?
(This operation
can take > 1hr)
NoYes
Tank PreClean
PreClean
Drain 1
5m 0s
Stop
Tank Pre-clean
Initiate pre-clean of the tank before major servicing. During pre-clean, the tank is drained, refilled
and then drained a second time.
Service Level
Burner Disable
Service Tm: 500
Tank Drain
Tank PreClean
Reset Error History
Reset Serv. Reminder
EscSet
Reset Error History
Are you sure?
NoYes
Reset Error History
Reset Error History
Resets error history.
Service Level
Burner Disable
Service Tm: 500
Tank Drain
Tank PreClean
Reset Error History
Reset Serv. Reminder
EscSet
Reset Serv. Reminder
are you sure?
NoYes
Reset Serv. Reminder
Reset Serv. Reminder
Resets service reminder.
Note: Service reminder should
only be reset after servicing.
GS Series Installation | 70
Password
0335
Enter Code
Confirm with Set
EscSet
Request – 50%
Humidify
01/01/0912:00:00
Security loop: Closed
Menu?
Main Menu
Service Level
User Defined Settings
Control Setting
Diagnostic Menu
EscSet
5
Diagnostics Menu
Fault History
Service History
Remote Test
EscSet
Fault History
12.01.01 12:00 RMW
12.01.01 12:00 DCF
Esc?
Diagnostics Menu
Fault History
12.01.01 12:00 RMW
RMW: RH LIMIT WARNING
The RH input
is lower than 3%.
Esc
RMW: System Response
Operation is
interrupted until an
input higher than 3%
is received.
Esc?
RMW: System Response
Operation is
interrupted until an
input higher than 3%
is received.
Esc?
RMW: Troubleshooting
Check connection
between sensor and
unit.
Esc?
RMW: Troubleshooting
Check that sensor
is function.
Esc?
RMW: Troubleshooting
Ensure controls are
located such that
they provide
accurate readings.
Esc?
RMW: Troubleshooting
Consult Factory
Esc?
Faulty History
Fault history reads as the following: MM/DD/YY HOUR:MINUTE Error Code
Press the “?” for an explanation of the error code and access to the troubleshooting guide. Use the UP
and DOWN arrow keys to navigate through the explanations and corrective action required.
Diagnostic Menu
Allows the user to read through the fault history,
the service history and perform a test of the remote
fault indicator.
Diagnostic Menu
71 | GS Series Installation
Diagnostics Menu
Fault History
Service History
Remote Test
EscSet
Service History
Service History
12.01.01 0000 Serv
Esc?
Service History
Display service history according
to date and time.
Diagnostics Menu
Fault History
Service History
Remote Test
EscSet
Remote Test
Remote Test
Steam Relay
Off
EscSet
Remote Test
Steam Relay
On
EscSet
Remote Test
Service Relay
Off
EscSet
Remote Test
Service
On
EscSet
Remote Test
Error Relay
Off
EscSet
Remote Test
Service
On
EscSet
Remote Test
Allows the user to test manually the remote fault indication. Three relays are available:
• Steam Production
• Service Needed
• Humidifier Error
GS Series Installation | 72
GSTC Warning
Displayed
Description of Warning
Corrective action
by unit
Troubleshooting
IMW-X:IGNITION
FAIL
The Ignition module
identified has failed to
ignite within the allotted
time
(4 minutes).
The unit will index
to next available
burner in the
sequence.
(1) Check sight port of problematic burner. Watch for
hot igniter (glowing red) followed by a flame.
(2) If igniter not hot, check for voltage.
Check wiring. Replace igniter if necessary.
(3) If igniter is hot but no flame, ensure gas supply
connected. Check for 24V at gas valve.
(4) If flame visible, check flame sensor wiring.
Check L1 not wired to N. Consult Factory.
APW-X:AP OPEN
WARN
The air proving
switch identified has
opened while the
unit was operating.
Unit will interrupt
operation and retry
three times.
After a third try a
fault is generated.
(1) Ensure pressure tubes are secure. Check
wiring to A/P switch and to driver board.
(2) Ensure blower is operating. if not,
check wiring and power to blower.
Check blower relay.
(3) Perform blower diagnostic test to ensure A/P switch
remains closed during operation.
(4) Check for suction In pressure tubes. If
switch does not close it may be defective. Consult
Factory.
AOW-X:AP OPEN
WARN
The air proving switch
identified did not close
during blower start-up.
Unit will interrupt
operation and retry
three times.
After a third try a
fault is generated.
(1) Ensure pressure tubes are secure.
Check wiring to A/P switch and to driver
board.
(2) Ensure blower is operating. If not, check wiring and
power to blower. Check blower relay.
(3) Perform blower diagnostic test to ensure A/P switch
remains closed during operation.
(4) Check for suction In pressure tubes. If
switch does not close it may be defective.
Consult Factory.
BHW-X:BLOWER
RPM HIGH
The indicated blower
has an RPM higher
than the lead blower
by more than the
allowable tolerance.
The unit will keep
monitoring blower
RPM and display
this warning if RPM
remains high.
(1) Ensure pressure tubes are secure.
Check wiring to A/P switch and to driver
board.
(2) Ensure blower is operating. If not check wiring and
power to blower. Check blower relay.
(3) Perform blower diagnostic test to ensure A/P switch
remains closed during operation.
(4) Check for suction In pressure tubes. If
switch does not close it may be defective.
Consult Factory.
BLW-X:BLOWER
RPM LOW
The indicated blower
has an RPM lower
than the lead blower
by more than the
allowable tolerance.
The unit will keep
monitoring blower
RPM and display
this warning if RPM
remains low.
(1) Ensure blower in question is securely
connected and is receiving correct
voltage.
(2) Verify blower control wiring connection.
Check blower diagnostic test for abnormalities.
(3) Ensure no restriction on blower.
Ensure no blockage of blower inlet.
(4) Blower speed may decrease due to wear. Safe to operate but
output may be reduced. Order new blower.
HMW: MAINT.
WARNING
The preset service
interval time has
expired.
The unit will
continue to run for
200 hours before a
fault is generated.
(1) Service unit. Consult maintenance
guide in the Nortec manual.
(2) Reset service interval time after
maintenance has been completed.
Troubleshooting
Table 10: GSTC Warning Troubleshooting
73 | GS Series Installation
FTW:FILL
WARNING
The fill valve has
been active for an
extended length of
time and the water
level is still zero
Fill valve remains
activated. Warning
will change to fault
if float level
remains at zero.
(1) Ensure water line is open and that
adequate water supply and pressure
is available.
(2) Check wiring to float board and
fill valve. Check strainer on fill valve inlet.
(3) Check that drain valve, auxiliary
drain valve or manual drain switch
are not activated.
(4) Check fill valve using diagnostic
output test. Consult Factory.
RHW:RH HIGH
WARNING
The measured RH is
above the RH High
alarm setting.
The humidifier will
remain idle until
the measured RH
drops below
setpoint.
(1) Check that RH high setting is correct
for the application.
(2) Check sensor location (too close to steam
distributor or other sources that affect
measurement).
(3) System may be oversized.
Lower manual capacity of the unit.
(4) Consult Factory.
RLW:RH LOW
WARNING
The measured RH is
below the “RH Low”
alarm setting.
The humidifier
should be
operating unless in
standby or lockout
mode.
(1) Check that RH low setting is correct
for the application.
(2) Check sensor location (too close to door,
window, or other sources that affect
measurement).
(3) Humidifier may be in lockout or standby.
Check security loop. Check that all burners
operational.
(4) System may be undersized. Check manual capacity
setting. Consult factory.
RMW:RH LIMIT
WARNING
The RH input
is lower than 3%.
Operation is
interrupted until an
input higher than
3%
is received.
(1) Check connection between sensor and
unit.
(2) Check that sensor is functional.
(3) Ensure controls are located such that
they provide accurate readings.
(4) Consult factory.
NSW:NO
SIGNAL
WARNING
No communication
is detected from
Master unit.
(This unit is set up
as slave)
Operation is
interrupted until
signal is received.
(1) Verify that one unit is configured as
master.
(2) Check connection between master and slave.
(3) Consult factory.
RDW: REMOTE
DISABLED
The unit has been
remotely disabled
through modbus
communication or
Nortec Online.
Operation is
interrupted until
unit is re-enabled
via modbus or
software.
(1) Enable unit through building management
system (BMS) or Nortec Online.
(2) If unit cannot be enabled remotely,
try enabling unit under software
Modbus Settings.
(3) Consult factory.
NBW: NO
BURNERS
AVAIL
All burners have been
disabled via software.
No burners are
available for operation.
The unit will not be
able to respond to
a demand until 1 or
more burners are
enabled.
GS Series Installation | 74
GSTC Fault
Displayed
Description of Warning
Corrective action
by unit
Troubleshooting
(screen)
IMF:NO
BURNERS AVAIL
All burners have
produced an ignition
module failure. No
burners are available
to produce steam.
Unit is unsafe to
operate with this
fault. Investigate
the problem before
restarting unit.
(1) Ensure gas supply is connected and open. Verify
gas supply pressure matches specification label.
(2) Check that igniters get hot/glow during
ignition sequence, followed by a flame.
Check wiring/voltage
(3) If igniter hot but no flame, check for 24V
at gas valve.
(4) If flame visible, check flame sensor
wiring. Verify L1 not wired to N. Consult factory.
AOF-X:AP FAIL
FAULT
The air proving
switch identified
did not close during
blower start-up
after 3 attempts.
Unit is unsafe to
operate with this
fault. Investigate
the problem before
restarting unit.
(1) Ensure pressure tubes are secure.
Check wiring to A/P switch and to driver
board.
(2) Ensure blower is operating. If not,
check wiring and power to blower. Check blower
relay.
(3) Perform blower diagnostic test to
ensure A/P switch closes and opens
during operation.
(4) Check for suction In pressure tubes. If
switch does not close it may be defective.
Consult factory.
ACF-X:AP
CLOSED
The air proving
switch identified
was closed while the
blowers were
inactive.
Unit will remain in
fault mode until
condition is
corrected or unit is
reset.
(1) Ensure pressure tubes are secure. Check
wiring to A/P switch and to driver board.
(2) Check for over/under pressure in room.
Verify proper vent installation. Check
termination for wind.
(3) Perform blower diagnostic test to
ensure A/P switch closes and opens
during operation.
(4) Potential faulty air proving switch. Contact factory.
BNFX:BLOWER
NOT OP
The indicated blower
is not operating or
registered an RPM
below 500 RPM while
being energized.
Unit is unsafe to
operate with this
fault. Investigate
the problem before
restarting unit.
(1) Check electrical connections. Ensure
feedback and power cables are connected to blower
and PCB.
(2) If blower not operating, ensure
blower relay is operating. Check
output from PCB.
(3) If blower is operating, feedback
signal could be missing.
(4) Perform blower diagnostic test to
verify controller is receiving signal. Consult factory.
GVF-X:GAS
VALVE FAIL
The indicated gas
valve was energized
out of sequence or
when not expected
to be energized.
Unit is unsafe to
operate with this
fault. Investigate
the problem before
restarting unit.
(1) Ensure electronics are connected
according to the wiring diagram.
(2) Check connections to all ignition modules
and gas valves. Ensure adequate supply voltage.
(3) Consult factory.
FTF:FILL
FAULT
The fill valve has
been active for an
extended time without
reaching level 1.
Unit will not
operate
without proper
water level.
Investigate
the problem before
restarting unit.
(1) Ensure water line is open and that
adequate water supply and pressure is available.
(2) Check wiring to float board and
fill valve. Check strainer on fill valve inlet.
(3) Check that drain valve, auxiliary
drain valve or manual drain switch are not
activated.
(4) Check fill valve using diagnostic
output test. Consult factory.
Table 11: GSTC Fault Troubleshooting
75 | GS Series Installation
FCF:FILL
CHECK FAULT
The fill valve has
been active for an
extended time
without increasing
a float level
Unit will not
operate without
accurate float level
reading.
Investigate before
restarting unit.
(1) Ensure water line is open and that
adequate water supply and pressure
is available.
(2) Check wiring to float board and
fill valve. Check strainer on fill valve inlet.
(3) Check that drain valve, auxiliary
drain valve or manual drain switch
are not activated.
(4) Check fill valve using diagnostic
output test. Consult factory.
DCF: DRAIN
CHECK
Drain Pump activated
for extended period
without changing
float level
Unit needs to drain
for optimal
performance
(1) Back pressure from drain lines can slow draining of
unit.
(2) Drain Pump could be obstructed.
Clean Drain pump. Check that the drain
Pump is powered.
(3) Ensure Float Level Sensor connected and that
levels change on fill.
FIF: FLOAT
INCONSIST.
On startup the unit
registers that the
float levels do not
increase logically
from 1 to 5
Unit cannot
operate
without accurate
float level reading
(1) Float level sensor is malfunctioning
(2) Inspect all hoses. Inspect all. connections.
Consult factory.
FLF: FLOAT
LEVEL
More than one float
level is registering
at the same time
Unit cannot
operate
without accurate
float level readings.
(1) Float level sensor Is malfunctioning.
Inspect all connections.
(2) Ensure that hoses are properly
connected and unobstructed.
(3) Ensure correct hose from fill valve is
connected to chamber. Consult factory.
KWF: KEEP
WARM FAULT
Keep Warm activated
but tank temperature
has not increased
within time allotted
Unit cannot
operate in such
condition.
(1) Check connection to tank temperature
Sensor. Check to ensure no more than
One burner is disabled.
(2) Check tank to See if hot (caution).
Check electrical Signal to sensor.
(3) Tank temperature Sensor may be
Defective. Consult factory.
OTF: OVER
TEMP FAULT
The exhaust or tank
Safety sensor has
exceeded the safety
limit
Unit cannot
operate
in such condition
(1) Check unit float system. Unit may not be
operating with the correct water levels.
(2) Ensure that exhaust line is open and free
of obstructions.
(3) Consult factory.
HMF: MAINT.
FAULT
The humidifier
maintenance interval
and 72hour window
for cleaning
has expired.
Unit cannot
operate
Is such a condition
(1) Unit requires servicing. Consult
maintenance guide in the Nortec manual.
(2) Service reminder must be cleared after
maintenance. Refer to manual.
GS Series Installation | 76
GSP fault code
displayed
Description of fault
Troubleshooting
NBF
Once the GS controller detects an ignition
module fail, it will index to the next
available ignition module. If all ignition
modules have failed or there are none
available (in the case of a 100 unit) this
fault will be generated.
(1) Check red LED’s on all modules for flashing fault code.
(2) Ensure there is gas supply to the humidifier.
(3) Ensure that the burners have not been disabled
in the software.
(4) Consult factory.
AOF-X
On startup after 3 tries if the AP switch
does not close within the proving period,
this fault will be generated
(1) Check that blue hoses on the Air Proving switch
have not come loose.
(2) Check that wires on the Air Proving switch are on
the N/O contacts
(3) If available, swap Air Proving switch with another
and see if the fault follows the air proving switch,
if so, replace switch
(4) Consult factory
ACF-X
On initial startup if any of the A/P switches
are closed this fault will be generated.
(1) Ensure that wiring on the air proving switch is on
the N/O contacts.
(2) Ensure that there is no continuity between the
switch with the wires off, if so replace switch.
(3) Ensure that there is not a strong positive pressure
in the room holding the switch closed.
(4) Consult factory.
BHF-X
If the blower RPM is above the RPM
tolerance for more than 10 seconds, this
fault is generated and the humidifier stops.
(1) Check wiring to lead blower and ensure a good
connection.
(2) Check lead blower for any restrictions by testing
it in the diagnostics screen.
(3) Consult factory.
BLF-X
If the blower RPM is below the RPM
tolerance for more than 10 seconds, this
fault is generated and the humidifier stops
(1) Check wiring to blower X and ensure a good
connection.
(2) Check blower X for any restrictions by testing it in
the diagnostics screen.
(3) Consult factory.
BNF-X
On startup, if the blower RPM does not
exceed 500 RPM within 5 seconds or if
during operation, the RPM drops below
500 RPM for more than 5 seconds this
fault is generated
(1) Ensure there is power to the blower and that all
wires are making a proper connection.
(2) Consult factory.
GVF-X
If the controller detects that a gas valve
has activated at a time it should not this
fault is
Generated.
(1) Ensure that the ignition module is not miswired
or that the module is not faulty by swapping it
with a known good one. If the problem follows
the ignition module, replace the module.
(2) Consult factory.
GIF-X
Following an ignition module fault if the
modules gas valve activates this fault will
be generated.
(1) Ensure that the ignition module is not miswired
or that the module is not faulty by swapping it
with a known good one. If the problem follows
the ignition module, replace the module.
(2) Consult factory.
DBF
There are many time windows in the GS
software. If, during a drain cycle, the time
window for the water level to drop is
exceeded, this fault is generated.
(1) Ensure that pump is being energized.
(2) Check for blockage in all aspects of the drain
system.
(3) Float board defective.
(4) Consult factory.
Table 12: GSP Fault List
77 | GS Series Installation
FCF
Once every 24 hours (provided the unit is
powered and in an operating or standby
condition) the controller will test the water
level detection circuit. If the test fails this
fault is displayed.
(1) Ensure the proper operation of the fill valve and
drain valve via the diagnostics screen.
(2) Float board is defective.
(3) Consult factory.
WLF
If the controller detects two or more float
level readings, which are not expected (ex.
Switch 1 and 3 ON or switch 1, 2, and 3
ON) this fault will be recorded.
The controller monitors the water level as it
fills and drains. It expects to see the levels
increase logically (1-2-3-4-5). If the water
level increases and jumps a step (1-2-4-5)
this fault will be generated. The same holds
for water level decreasing.
During a keep warn cycle, if the tank
temperature sensor does not open within a
certain time window, this fault is generated.
(1) Ensure that the tank temperature sensor is
connected.
(2) Defective tank temperature switch.
(3) Contact agent for replacement switch.
OTF
If input TB5, # 4 on the logic board goes
low (no 24 Vac detected) this fault will be
generated. This could indicate either the
tank over temperature switch has opened
or the stack over temperature switch has
opened.
(1) Do not operate and consult the factory.
HMF
In the user menu the user sets the
maintenance time. Once this time expires a
warning is displayed. 72 hours later the
warning changes to this fault. The
maintenance time is measured in weighted
operational hours.
With switch 5, #4 deactivated, this fault is
enabled.
(1) Perform tank cleaning and all other maintenance
requirements outlined in the manual.
FTF
Fill time-out fault during fill process. The
GS software monitors the changes in water
level during filling sequence. If ware level
changes do not occur within an expected
time interval, this fault will be generated.
(1) Verify water supply is open.
(2) Verify adequate water supply to unit (30-80psi,
10L/min, minimum ½” dia. Line size).
(3) Verify wire harness and connection between float
chamber and I/O board (TB).
GS Series Installation | 78
GSP Warning
Displayed
Description of Warning
Troubleshooting
IMW-X
Once the controller activates an ignition module, it will allow 4 minutes
for the gas valve to activate. After the trial period, if the gas valve has
not activated, a fault will be generated. The module will be locked out
and the next burner will be indexed.
SEE FAULT LIST
APW-X
Should the air proving switch open while the unit is operating this
warning is generated. The controller shuts down and retries. There are
no limits to the amount of times this warning is generated.
SEE FAULT LIST
AOW-X
On startup if the AP switch does not close within the proving period.
After 3 tries, a fault will be generated.
SEE FAULT LIST
BHW-X
If a blower RPM is above the RPM tolerance limit this warning is
generated. If it is above the RPM tolerance limit for more than 10
seconds a fault will be generated.
SEE FAULT LIST
BLW-X
If a blower RPM is below the RPM tolerance limit this warning is
generated. If it is below the RPM tolerance limit for more than 10
seconds a fault will be generated.
SEE FAULT LIST
HMW
In the user menu the user sets the maintenance time. Once this time
expires this warning is displayed. The maintenance time is measured
in weighted operational hours.
With switch 5, #4 activated, this warning will remain until the warning
is reset in the user level.
SEE FAULT LIST
UNW-6
Low water level has not been reached within expected time interval
during initial fill sequence. Unit will continue filling while warning is
displayed. A Water Fill Fail fault will be generated if the low water level
is not reached after an additional length of time.
SEE FAULT LIST
UNW-C
Keep warm feature has initiated combustion sequence at 75% output.
This occurs when keep warm feature has been activated via dip-switch
settings, the system demand is below minimum and the tank
temperature sensor is registering cold (open contacts).
(1) Warning message
will stop being
displayed once
tank temperature
sensor indicates
water is warm.
(2) Keep warm
feature can be
disabled using dip-switch
settings.
Figure 46: GS Series INDOOR Exploded View - Internal Component
GS Series Installation | 84
#
Description
Part #
GS 100
GS 200
GS 300
GS 400
GS 500
GS 600
101
Clean-Out Door Kit, with Anode, GS/SE, B/B+
2570309
1
1 1 1 1 1
102
Gasket, Tank Cover Plate
2524361
1 1 2 2 3 3 103
Secondary Safety Switch
1504832
1 1 1 1 1 1 104
Fill Box
2526152
1 1 1 1 1 1 105
Vacuum Break Valve 1/2"npt
1505959
1 1 1 1 1 1 106
P-Trap
2553825
1 1 1 1 1 1 107
Dual Fill Valve 10.0 l/min & 0.35 l/min
1505759
1 1 1 1 1 1 108
Heat Exchanger Gasket
Single
2524405
1
Dual
2524403
1 2 2 3 3 109
Direct Vent Air Manifold
GS 100
1506140
1
GS 200
1506141
1
GS 300/400
1506142
1 1
GS 500/600
1506143
1 1 110
Heat Exchanger Replacement Kit
Mini
2528422
1
Single
2528423
1 1
Dual
2528424
1 1 2 2 3 111
Stack High Limit Switch
1506745
1 1 1 1 1 1 112
Exhaust Manifold Gasket
Single
1505973
1
Dual
1505942
1 2 2 3
3
113
Exhaust Manifold
GS 100
1505875
1
GS 200
1505861
1
GS 300/400
1505843
1 1
GS 500/600
1505828
1 1 114
Flexible Gas Hose with fittings
1505960
1 2 3 4 5 6 115
Auxiliary Drain Plug
1507043
1 1 1 1 1 1 116
Auxiliary Drain termination
1506925
1 1 1 1 1 1 117
Drain Pump 24v 60 Hz
1502644
1 1 1 1 1 1 118
Tank Thermal sensor
1506026
1 1 1 1 1 1 119
Float Chamber
1115933
1 1 1 1 1 1 120
Float Chamber Mounting Bracket
1113777
1 1 1 1 1 1 121
Float Board
2511137
1 1 1 1 1
1
122
Lower Mixing Box
1506749
1 1 1 1 1 1 123
Replacement Burner Ass'y
110 - 120V Models
2528416
1 2 3 4 5 6
208-240V Models
1507669
1 2 3 4 5 6 124
Burner Plate Gasket
1505936
1 2 3 4 5 6 125
Sight Port Replacement kit
2528417
1 2 3 4 5
6
Table 14: GS Series INFOOR Exploded View - Internal Components
85 | GS Series Installation
#
Description
Part #
GS 100
GS 200
GS 300
GS 400
GS 500
GS 600
126
Igniter/flame sensor gasket
1506892
1
2 3 4 5 6
127
Hot Surface Igniter Replacement Kit
110 - 120V Models
2528418
1
2 3 4 5 6
208-240V Models
1507695
1
2 3 4 5 6
128
Flame Sensor Replacement Kit
1507694
1
2 3 4 5 6
Igniter/flame sensor Replacement Kit
110 - 120V Models
2528420
1
2 3 4 5 6
208-240V Models
1507712
1
2 3 4 5 6
129
Combustion Blower
110 - 120V Models
2524360
1 2 3 4 5 6
208-240V Models
1502289
1 2 3 4 5 6 130
Air Proving Switch
1504175
1
2 3 4 5 6
131
Gas Valve Assembly
Natural Gas
1507713
1 2 3 4 5 6
Propane
1507714
1 2 3 4 5 6 132
Elbow Assembly for Air Intake
1504204
1
2 3 4 5 6
133
Burner/Blower Gasket
1708208
1
2 3 4 5 6
Not
shown
Bracket, Fan Board Mount
1505899
1
1 2 2 3 3
Not
shown
Fan Board
1505689
1
1 2 2 3 3
Not
shown
Igniter Jump Start Module
1506793
1
2 3 4 5 6
Not
shown
Hose Replacement kit
1507696
1
1 1 1 1 1
Not
shown
Flexible hose for Direct Vent
1502148
1
2 3 4 5 6
Not
shown
Rod, Sacrificial Anode, MG 1" x 4"
2570307
1
1 1 1 1 1
Not
shown
1/4" Tube for air proving (per inch)
1605227
Order (by foot) as required
Table 14: GS Series INFOOR Exploded View - Internal Components - continued
GS Series Installation | 86
This Page Intentionally Left Blank
87 | GS Series Installation
Figure 47: GS Series INDOOR Exploded View - Cabinetry
GS Series Installation | 88
#
Description
Part #
GS 100
GS 200
GS 300
GS 400
GS 500
GS 600
201
Service Door Assembly
Mini
2524439
1
Single
2524440
1
Double
2524441
1 1
Triple
2524458
1
1
202
Front Door Assembly
2535268
1 1 1 1 1 1 203
Recessed Handle
2523444
1 1 1 1 1
1
205
GSTC Processor Board Replacement
2544252
1 1 1 1 1
1
206
Drive Board
2535504
1 1 1 1 1 1 207
Primary Transformer
110 - 120V Models
2532672
1 1 1 1 1
1
208-240V Models
2532673
1 1 1 1 1
1
Fuse for Primary transformer, 6.25 Amp
2523526
1 1 1 1 1 1 208
Ignition Control Module
110 - 120V Models
2525914
1 2 3 4 5
6
208-240V Models
1505987
1 2 3 4 5 6 209
Relay Mount Socket
1703250
1 1 1 1 1
1
210
Blower Relay
1453020
1 1 1 1 1
1
Not
Shown
Slotted wire duct
1506041
order by length required
211
Display Panel w/keypad indoor
2544253
1 1 1 1 1
1
212
On/Off Drain Switch
1453001
1 1 1 1 1
1
213
Remote Fault Board
2521279
1 1 1 1 1
1
Not
Shown
Remote Fault Board Ribbon Cable
2522062
1 1 1 1 1
1
Table 15: GS Series INDOOR Exploded View - Cabinetry
89 | GS Series Installation
Figure 48: GS Series OUTDOOR Exploded View – Cabinetry
GS Series Installation | 90
#
Description
Part #
GS 100
GS 200
GS 300
GS 400
GS 500
GS 600
205
GSTC Processor Board Replacement
2544252
1 1 1 1 1
1
206
Driver board
2535504
1 1 1 1 1
1
207
Primary Transformer
110 - 120V Models
2532672
1 1 1 1 1
1
208-240V Models
2532673
1 1 1 1 1
1
Fuse for Primary transformer, 6.25 Amp
2523526
1 1 1 1 1 1 208
Ignition Control Module
110 - 120V Models
2525914
1 2 3 4 5
6
208-240V Models
1505987
1 2 3 4 5 6 209
Relay Mount Socket
1703250
1 1 1 1 1
1
210
Blower Relay
1453020
1 1 1 1 1
1
213
Remote Fault Board
2521279
1 1 1 1 1
1
Not
Shown
Remote Fault Board ribbon cable
2522062
1 1 1 1 1
1
Not
Shown
Slotted wire duct
1506041
order by length required
311
Display Panel w/keypad outdoor
2544255
1 1 1 1 1
1
212
On-Off-Drain Switch
1453001
1 1 1 1 1 1 313
Thermostat, On/Off, 80F
1508042
1 1 1 1 1
1
322
Vent Pipe 12" Long
3" Dia
1508134
1
4" Dia
1508133
1
5" Dia
1507884
1 1
6" Dia
1507881
1
1
323
Rain Cap
Mini
1508130
1
Single
1508129
1
Double
1507889
1 1
Triple
1507883
1
1
324
Cooling Fan
1507891
1 1 1 1 1
1
342
Pump House Heater 500 watts
1508039
1 1 2 2 3
3
Table 16: GS Series OUTDOOR Exploded View - Cabinetry
91 | GS Series Installation
Figure 49: GS Stand Assembly Instructions
GS Series Installation | 92
Item
GS 100
GS 200
GS 300
GS 400
GS 500
GS 600
Gas Pressure
Natural Gas min (in wc/mbar)
4.5/11.2
Natural Gas max (in wc/mbar)
9/22.4
Propane min (in wc/mbar)
9/22.4
Propane max (in wc/mbar)
13/32.3
Min free air opening (in/cm)
13/33
23/58
35/89
47/119
59/150
71/180
Input
Max (BTU)
140,000
280,000
420,000
560,000
700,000
840,000
Min GSTC (BTU)
45,000
Direct vent min (BTU)
60,000
Gas Piping Size (in/cm)
1/2/1.3
3/4/1.9
1/2.5
1/2.5
1.25/3.2
1.25/3.2
"BH" Vent X X X X X X
"B" Vent X X X X X X
"BH" Exhaust Piping (in/cm)
3/7.6
4/10.2
5/12.7
5/12.7
6/15.2
6/15.2
4/10.2
5/12.7
7/17.8
7/17.8
8/20.3
8/20.3
Appliance Category
I or III
I or III
I or III
I or III
I or III
I or III
Full Weight In (lbs/kg)
416/188
588/266
954/432
974/441
1340/607
1360/616
Empty Weight In (lbs/kg)
266/120
354/160
485/217
529/239
659/298
703/318
User level password
0335
Water consumption (25% bd)
Gallons/liters per hour
433/1639
866/3278
1300/4921
1733/6560
2166/8199
2600/9842
Tank Water Volume
Gallons/liters
18/71
29/111
58/221
55/210
84/320
81/309
Fill valve flow rates
To tank: Gallons/liters per minute
2.64/10
To float chamber: Gallons/liters
per minute
0.09/0.35
Supply water pressure
Min. (psi/kPa)
30/206
Max. (psi/kPa)
80/551
Drain rate (includes D.W.C)
Gallons/Litres per minute
5.2/20
Min drain pipe size (in/cm)
1 to 1.5 / 2.5 to 3.8 OD or larger
Power supply requirements
120 volts a/c
X X X X X
X
208-240 volts a/c 1PH
X X X X X
X
Steam Outlet size (in/cm)
1.75/4.4
3/7.6
3/7.6
4/10.2
4/10.2
4/10.2
Table 17: GS Quick Reference
93 | GS Series Installation
Warranty
Nortec Humidity Inc. and/or Nortec Humidity Ltd. (hereinafter collectively referred to as THE COMPANY),
warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever
date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly
warranted (with the exception of the media) are free from defects in material and workmanship. The heat
exchanger(s) will have an additional warranty that ensures the heat exchanger will be free from defects in
materials and workmanship for an additional year, for a total period of 3 years from installation or 40
months from the manufacturer’s ship date, whichever is earlier. No warranty is made against corrosion,
deterioration, or suitability of substituted materials used as a result of compliance with government
regulations.
THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing replacement parts to
the customer, F.O.B. THE COMPANY’s factory, providing the defective part(s) is returned freight prepaid by
the customer. Parts used for repairs are warranted for the balance of the term of the warranty on the original
humidifier or 90 days, whichever is longer.
The warranties set forth herein are in lieu of all other warranties expressed or implied by law. No liability
whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said
liability shall be limited to the original purchase price for the product. Any further warranty must be in writing,
signed by an officer of THE COMPANY.
THE COMPANY’s limited warranty on accessories, not of the companies manufacture, such as controls,
humidistats, pumps, etc. is limited to the warranty of the original equipment manufacturer from date of
original shipment of humidifier.
THE COMPANY makes no warranty and assumes no liability unless the equipment is installed in strict
accordance with a copy of the catalog and installation manual in effect at the date of purchase and by a
contractor approved by THE COMPANY to install such equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for consequential damage or
damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the
equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for damage resulting from freezing
of the humidifier, supply lines, or drain lines.
THE COMPANY retains the right to change the design, specification and performance criteria of its products
without notice or obligation.