Nortec GH, GH 100, GH 200, GH 300, GH 400 Maintenance Manual

GH Series
Gas-fired Humidifier
Version D
Installation, User &
Maintenance Guide
FOR YOUR SAFETY:
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
WARNING:
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
WARNING:
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
IMPORTANT: Read and save this guide for future reference. This guide to be left with equipment owner.
Form #02-272 150-3230 rev. A
Table Of Contents
GENERAL 1
- WARNING ................................................1
- RECEIVING & UNPACKING EQUIPMENT................................1
- GENERAL SPECIFICATIONS ......................................1
- MODEL DESIGNATION .........................................1
INSTALLATION 1
- LOCATING AND MOUNTING ......................................3
- GAS PIPING ...............................................5
- AIR MANIFOLD/CONNECTOR HOSE INSTALLATION FOR DIRECT VENT ..............6
- PROCEDURE:............................................6
- INTAKE AIR DUCT ............................................7
- TERMINAL LOCATION ..........................................7
- VENTING .................................................7
- STANDARD UNIT ........................................8
- DIRECT VENT UNIT ......................................8
- ADDITIONAL REQUIREMENTS WHEN VENTING THROUGH A SIDEWALL ...........8
- ELECTRICAL ...............................................9
- PRIMARY WIRING .........................................9
- LOW VOLTAGE CONTROL WIRING ...............................9
- CONTROL INSTALLATION .......................................10
- OUTDOOR ENCLOSURE HEATER SETTING .............................10
- BLOWER PACKS ............................................10
- STEAM DISTRIBUTORS FOR DUCTED APPLICATIONS .......................10
- PLUMBING ...............................................12
- FILL WATER SUPPLY LINE ....................................12
- DRAIN LINE ............................................13
- DRAIN WATER COOLER SUPPLY LINE .............................13
- STEAM LINE ............................................14
- WATER TRAP ...........................................15
- CONDENSATE RETURN LINES FOR STEAM DISTRIBUTORS .................15
OPERATION 16
- WATER LEVEL CONTROL .......................................16
- B AND P MODELS .........................................16
- MC MODEL ............................................16
- DRAIN WATER COOLER OPERATION ................................16
- START UP PROCEDURE .......................................17
- FILLING THE SYSTEM ......................................17
- TESTING THE IGNITION SAFETY SHUT-OFF ..........................17
- PRE-PURGE OF GAS VALVE AND MANIFOLD..........................17
- SEQUENCE OF OPERATION .....................................18
- BLOWDOWN CALIBRATION ......................................18
- DRAIN RATE AND BLOWDOWN VOLUME .............................18
- MANUAL STEAM OUTPUT ADJUSTMENT ..............................18
- B MODELS .............................................18
- GHMC DISPLAY OPERATION .....................................18
- SAFETY INSTRUCTIONS........................................19
MAINTENANCE 19
- DRAINING THE TANK .........................................19
- CLEANING THE STAINLESS STEEL TANK & FLOAT CHAMBER ..................19
- COMBUSTION BLOWER ........................................19
- BURNER ................................................20
- BURNER REMOVAL/INSPECTION ................................20
- ADJUSTMENTS/REPLACEMENTS OF COMPONENTS........................20
- GAS VALVE REPLACEMENT ...................................20
- HOT SURFACE IGNITER REPLACEMENT ............................20
- IGNITION MODULE REPLACEMENT ...............................20
- TRANSFORMER REPLACEMENT ................................20
- AIR SWITCH REPLACEMENT...................................21
- DRAIN PUMP REPLACEMENT ..................................21
- COMBUSTION AIR BLOWER REPLACEMENT ..........................21
- TANK REPLACEMENT ......................................21
- HEAT EXCHANGER REPLACEMENT...............................22
- SERVICING THE UNIT .........................................23
- FAULT CONDITIONS ..........................................23
- B AND P MODELS .........................................23
- MC MODELS ............................................23
- SERVICE CHECKS ...........................................23
- FLAME SENSOR..........................................23
- IGNITER CHECK..........................................24
- GAS VALVE SETTING .......................................24
- TROUBLESHOOTING GUIDE .....................................25
- MANDATORY MAINTENANCE SCHEDULE ..............................26
- START-UP AND INSPECTION .....................................27
- VENTING MANUFACTURER ......................................28
- EXTERNAL CONTROLS WIRING CONNECTIONS ..........................29
- GH B/P WIRING DIAGRAM .......................................30
- GH STAND ASSEMBLY.........................................31
- GH ENCLOSURE PHYSICAL DATA ..................................32
- GH ENCLOSURE HEATER INSTALLATION INSTRUCTIONS ....................33
- REPLACEMENT PARTS ......................................34-37
- MAINTENANCE CHART ........................................38
GENERAL
GENERAL SPECIFICATIONS
WARNING
Improper installation, adjustment, alteration,
·
service, maintenance, or use can cause carbon monoxide poisoning, an explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory authorized and listed kits or accessories when modifying this product. A failure to follow this warning can cause electrical shock, fire, personal injury, or death.
Should overheating occur, or the gas fail to shut
·
off, shut off the manual gas valve to the appliance before shutting off the electrical supply.
Do not use this appliance if any part has been
·
under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
This installation guide has been designed to provide assistance when installing, mounting, and sizing a GH Series humidifier. Actual on site application may vary. Consult Technical Services or your local NORTEC representative.
The NORTEC GH Series humidifier is a completely new patented design based on leading edge technology. The GH is designed to provide clean steam humidification at an economical price.
All GH models are available for normal altitude (0-2000 ft elevation) or for high altitude (2000-4500 ft elevation) applications.
GHMC models are also available with enclosure for mounting outside when space is not available. The unit will ship completely installed inside the outdoor enclosure ready for field connection. The enclosure will protect the unit from wind, sun and precipitation.
MODEL DESIGNATION
The unit specification label indicates the model of
gas humidifier according to the following chart:
PRODUCT LINE
(Gas Fired Humidifier)
CONTROLS
B = BASIC (ON/OFF) P= MODULATING MC = D IG ITAL CONTROLLER
c/w KEYPAD
STEAM OUTPUT
(lbs/hr) Normal Altitude
FUEL
N= NATURAL GAS P= PROPANE GAS
GH
MC
100 N DI
HA DV
RECEIVING & UNPACKING EQUIPMENT
1. Check packing slip to ensure ALL material has
been delivered.
2. All material shortages are to be reported to
NORTEC within 48 hours from receipt of goods. NORTEC assumes no responsibility for any material shortages beyond this period.
3. Inspect shipping boxes for damage and note
on shipping waybill accordingly.
4. After unpacking, inspect equipment for
damage and if damage is found, notify the shipper promptly.
5. All NORTEC products are shipped on an
F.O.B. factory basis. Any and all damage, breakage or loss claims are to be made directly to the shipping company.
DE-IONIZED WATER
DIRECT VENT
OPTION
OPTION
INSTALLATION
1. The installation must conform with local
building codes or, in the absence of local codes, with the ANSI Z223.1, National Fuel Gas Code, and/or CAN/CGA B149 Installation Codes. Refer to the Gas Piping section of this manual.
2. The humidifier shall not be connected to a
chimney flue serving any other appliances.
3. Provide for adequate combustion and
ventilation air in accordance with Sections 7.2,
7.3 or 7.4, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1, or Section 5.3 of CAN/CGA B149 Installation
-1-
MODEL GH 100 SPECIFICATIONS
FUEL BLOWER
NATURAL
GAS
PROPANE
(LP GAS)
SPEED
MAX 119,000 119,000 100 100 -0.05 MIN (B,P) 60,000 60,000 50 50 -0.05 MIN (MC) 40,000 60,000 25 50 -0.05
MAX 119,000 119,000 100 100 -0.05 MIN (B,P) 60,000 60,000 50 50 -0.05 MIN (MC) 48,000 60,000 30 50 -0.05
* For high altitude units (2000-4500 ft) the input and steam capacities are de-rated by 10%. STD: Standard Gas Unit DV: Direct Vent Unit
INPUT (BTUH)* STEAM CAPACITY
STD DV STD DV
(LBS/HR)
MANIFOLD PRESS. IN
W.C.
SHIPPING WEIGHT
(LBS)
300 500
300 500
OPERATING
WEIGHT (LBS)
MODEL GH 200 SPECIFICATIONS
FUEL BLOWER
NATURAL
GAS
PROPANE
(LP GAS)
SPEED
MAX 238,000 238,000 200 200 -0.05 MIN (B,P) 120,000 120,000 100 100 -0.05 MIN (MC) 40,000 60,000 25 50 -0.05
MAX 238,000 238,000 200 200 -0.05 MIN (B,P) 120,000 120,000 100 100 -0.05 MIN (MC) 48,000 60,000 30 50 -0.05
INPUT (BTUH)* STEAM CAPACITY
STD DV STD DV
(LBS/HR)
MANIFOLD PRESS. IN
W.C.
SHIPPING WEIGHT
(LBS)
350 660
350 660
OPERATING
WEIGHT (LBS)
* For high altitude units (2000-4500 ft) the input and steam capacities are de-rated by 10%. STD: Standard Gas Unit DV: Direct Vent Unit
MODEL GH 300 SPECIFICATIONS
FUEL BLOWER
NATURAL
GAS
PROPANE
(LP GAS)
SPEED
MAX 357,000 357,000 300 300 -0.05 MIN (B,P) 180,000 180,000 150 150 -0.05 MIN (MC) 40,000 60,000 25 50 -0.05
MAX 357,000 357,000 300 300 -0.05 MIN (B,P) 180,000 180,000 150 150 -0.05 MIN (MC) 48,000 60,000 30 50 -0.05
* For high altitude units (2000-4500 ft) the input and steam capacities are de-rated by 10%. STD: Standard Gas Unit DV: Direct Vent Unit
INPUT (BTUH)* STEAM CAPACITY
STD DV STD DV
(LBS/HR)
MANIFOLD PRESS. IN
W.C.
SHIPPING WEIGHT
(LBS)
800 1200
800 1200
OPERATING
WEIGHT (LBS)
MODEL GH 400 SPECIFICATIONS
FUEL BLOWER
NATURAL
GAS
PROPANE
(LP GAS)
SPEED
MAX 476,000 476,000 400 400 -0.05 MIN (B,P) 240,000 240,000 200 200 -0.05 MIN (MC) 40,000 60,000 25 50 -0.05
MAX 476,000 476,000 400 400 -0.05 MIN (B,P) 240,000 240,000 200 200 -0.05 MIN (MC) 48,000 60,000 30 50 -0.05
INPUT (BTUH)* STEAM CAPACITY
STD DV STD DV
(LBS/HR)
MANIFOLD PRESS. IN
W.C.
SHIPPING WEIGHT
(LBS)
800 1200
800 1200
OPERATING
WEIGHT (LBS)
* For high altitude units (2000-4500 ft) the input and steam capacities are de-rated by 10%. STD: Standard Gas Unit DV: Direct Vent Unit
-2-
Codes, or applicable provisions of the local
O
building codes.
8. For recommended clearances for servicing
refer to Figure #2.
4. The required free area of supply air opening
is: 11 in. sq. (7,000 mm 20 in. sq. (13,000 mm 30 in. Sq. (19,500 mm 40 in. Sq. (26,000 mm
2
), for GH 100
2
), for GH 200
2
), for GH 300
2
), for GH 400
NOTE FOR DIRECT VENT OPTION:
The combustion supply air opening is not required to the room where the appliance is installed since the combustion air requirements will be provided through the inlet air duct (see installation section). To keep electronic components cooled, it is required to keep the environment around the unit at room temperature.
NOTE FOR OUTDOOR ENCLOSURE: Required free area of supply air is provided through the bottom of the unit. Front louvers ensure good air circulation in the summer. These louvers should be blocked for winter operation.
5. Cabinet back and bottom contain air openings
to provide combustion air to the forced draft blower. Either the back or bottom set of openings must have at least 2" (50 mm) clearance to allow for adequate combustion air. For example, if the humidifier is floor mounted, 2" clearance must be maintained to the unit's back surface.
6. Excessive exposure to contaminated
combustion air will result in safety and performance related problems. Known contaminates include halogens, ammonia, and chlorides, excessive dust, lime or dirt. Excessive exposure of electronics to the contaminants will also result in performance related problems. Contact NORTEC Technical Services if you have any questions. If contaminants exist, it is recommended to use the outdoor enclosure option to isolate the unit.
7. All surfaces are zero clearance to combustible
construction.
9. During installation cover the humidifier to
prevent any dust or other contaminants from entering the cabinet when activities such as drilling are taking place.
NOTE: Some insulating materials may be combustible. Prior to installing this appliance examine the area for insulating material. If this appliance is installed in an insulated space, it must be kept free and clear of insulating materials. If insulation is added after the appliance is installed, it will be necessary to examine the area again.
LOCATING AND MOUNTING
GH Series humidifiers are designed to mount on a suitable wall (GH 100 only), GH Stand, or floor. The clearance dimensions shown in this manual are for reference only and are the minimum required for maintenance of the humidifier. Local and National Codes should be consulted prior to final location and installation of the humidifier. NORTEC cannot accept responsibility for installation code violations.
1. Figure #1 shows the locations of all required
connections to the Gas Humidifier. Careful consideration should be given to all of these connections when choosing a location for the humidifier.
Figure #1
EXHAUST VENT C
OUT FROM THE TOP
Steam
Outlet(s)
2. For front and side clearance requirements (for
access during installation, maintenance and troubleshooting), see Figure #2.
MES
Power And Control Wiring
Fill Water Input Line
DWC Water Input Line*
Gas Input Line
Drain
*DWC = Drain Water Cooler
NOTES:
The leveling legs must be left in place when floor mounted on combustible material.
The humidifier shall not be installed directly on carpeting, tile or other combustible material other than wood flooring.
3. Location of the steam distributor should be
minimum of 36” above the humidifier.
4. DO NOT locate humidifier any further than
absolutely necessary from steam distributor location. Net output will be reduced as a result of heat loss through steam hose (see Engineering Manual, Form # -163D). Also,
-3-
p
Figure #2
**
Front
800 mm/31.5”
(min. 50 mm/2”) **
DV: Optional Direct Vent option
ace required for combustion air below or at the back of the unit.
**: S
increased static pressure (over 4.5" W.C.) will result in hot water leaking down the drain. Consult factory if this situation occurs.
5. Where possible, mount humidifier at a height
convenient for servicing.
6. Wall mounting brackets (provided with GH
100) should be securely attached open edge upwards, horizontal, using field-supplied fasteners (minimum of four 3/8" diameter fasteners in each bracket). Attach to a vertical, solid surface. Put a security bolt through the hole provided in the back of the cabinet so that the unit cannot be bumped off the wall bracket. See Figure #3.
0mm
80
(min. 50 mm/2”)**
TOP
min. 915 mm/36”
RIGHT
DV
BOTTOM
7. Make sure humidifier is mounted level. If floor
mounted adjust using leveling legs.
All GH models are equipped with adjustable
leveling legs which have a maximum travel of
1.5”.
- These legs may be used to allow mounting of
an optional stand.
- These legs may be removed and replaced by
longer legs. Factory approval is needed.
- Removal or adjustment of legs requires a
1 1/8” wrench.
Figure #3
-4-
8. Optional stands are available for all GH Series humidifiers. Refer to Shop Drawing Package, Form # 273 for details and part numbers.
9. Clearances around the unit should also be
maintained for good access to the gas humidifier. 3 feet clearance is needed on the right side of the cabinet for GH100/200, 4 feet is needed on the right side of the cabinet for the GH300/400. The front requires 3 feet clearance for all capacities.
GAS PIPING
Installation of piping must be in accordance with local codes, and ANSI Z233.1, “National Fuel Gas Code,” in the United States or CAN/CGA-B149 Installation Codes in Canada.
The following table indicates the maximum and minimum allowable gas pressures for the Gas Humidifier.
10. DO NOT mount humidifier on hot surfaces.
11. DO NOT mount humidifiers in an area where freezing may occur.
12. If humidifiers are mounted on roof, a properly ventilated, temperature controlled, (above freezing), weatherproof enclosure must be used. Consult your local representative for more information on Nortec’s enclosure.
13. DO NOT mount humidifiers on vibrating surface. Consult factory.
14. In earthquake prone areas do not wall mount. Use the existing wall mount brackets to fasten unit to the wall with it sitting on the floor. Maintain spacing for air openings. (See “Installation” item 8).
NOTE FOR OUTDOOR ENCLOSURE:
1. Optional outdoor enclosure can also be used; unit is factory mounted inside the enclosure.
INCHES W.C.
GAS MIN. MAX.
Natural 4.5 14.0
Propane 9.0 14.0
The gas inlet pipe size to the appliance is:
½” NPT for GH 100 3/4” NPT for GH 200 1” NPT for GH 300 / 400
Provide an adequate size gas supply line.
When black iron gas pipe is used, a sediment trap must be located ahead of the humidifier gas controls. In all installations, a manual shut off valve, located outside the cabinet, must be installed. See Figure #4.
Figure #4
2. The enclosure should be installed at a secure distance from any air or exhaust system. (also see local code).
3. The enclosure should be bolted down or
secured if it is to be exposed to high winds.
4. If lifting the enclosure on the roof using a forklift, lift under the unit at cross members for stability. (Strapping belts can also be used.)
5. Clearances around the unit should also be maintained for good access to the gas humidifier. 3 feet of clearance is needed on the right side of the cabinet for GH100/200, 4 feet is needed on the right side of the cabinet for the GH300/400. The front requires 3 feet clearance for all capacities.
1
2
#1: Shut-off Gas Valve #2: Sediment Trap
Leak test all gas connections using a commercial
soap solution made to detect leaks. Bubbles indicate
-5-
gas leakage. Seal all leaks before placing the humidifier in operation.
installed by a qualified installer prior to commissioning the unit.
WARNING: Never use an open flame to check for gas leaks. If a leak does exist, a fire or explosion could occur, resulting in damage, injury or death.
The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or greater than 14” w.c. (3.5 kPa).
Dissipate test pressure from the gas supply line before re-opening the manual shut off valve to the appliance.
NOTES:
1. Failure to follow this procedure may damage
the gas valve. Over pressured gas valves are not covered by warranty.
2. DO NOT use Teflon tape on gas line pipe
threads. A flexible sealant suitable for use with Natural Gas and Propane Gas is recommended.
Procedure:
1. Apply a ring of silicone around the outside of each of the blower adapter connector.
2. Mount a flexible connector hose over the hose connection on each blower adapter and secure using a gear clamp provided with the unit. Care should be taken not to kink or damage the flexible hose. Refer to Figure #5.
Figure #5
3. Plan gas supply piping so it will not interfere
with removal of gas valves or blower assemblies and front or side service doors.
The gas valve is provided with pressure taps to measure gas pressure upstream and downstream, (manifold pressure). The minimum gas pressure shown is for the purpose of input adjustment.
A 1/8" NPT plugged tapping, accessible for test gage connection, must be installed immediately upstream of the gas supply connection to the appliance.
NOTE FOR OUTDOOR ENCLOSURE: Gas lines should be routed through the bottom of the enclosure.
NOTE FOR DIRECT VENT UNITS: The combustion supply air opening is not required to the room where the appliance is installed since the combustion air will be provided through the inlet air duct (see installation notes below). Ventilation is required for cooling of the electronic components
AIR MANIFOLD/CONNECTOR HOSE
INSTALLATION FOR DIRECT VENT
3. Carefully bend the flexible hose(s) to give the “S” shape as shown in the diagram.
4. Mount the air intake manifold to the cabinet base using the mounting bracket located on the bottom of the air manifold (refer to Figure
6). DO NOT PUNCTURE OR ADD ANY HOLES TO THE AIR MANIFOLD.
5. Apply a ring of silicone to the outside of each hose connection on the air manifold.
6. Mount the corresponding flexible connector hose over each hose connection on the air manifold and secure using a gear clamp provided with the unit.
Figure #6
All direct vent units are shipped with the air manifold and connector hoses packaged separately. The connector hoses and air manifold must be
-6-
INTAKE AIR DUCT
TERMINAL LOCATION
All direct vent units require an intake air duct to
provide fresh outside air for combustion.
Each air intake manifold has a single 4-inch (100mm) diameter inlet to which the supply air duct must be connected.
Intake material must be UL or ULC listed 4-inch diameter (I.D.) corrugated 2-Ply aluminum ducting. The following table lists several suppliers of approved intake material.
Supplier
Z-Flex Z-Flex Aluminum Chim
Product
-
ney Liner
Flex-L International Inc. Flexi-Liner
MICHIGAN CHIM-FLEX CHIM-FLEX Aluminum
Liner
Chim Cap Corp. Flex-All Aluminum Liner
The following table details the allowable duct length that can be connected to the direct vent option. Each 90 degree elbow equals 10ft and each 45 degree elbow equals 5ft. If flexible vent material is used, all bends should be smooth and have as large a radius as possible to avoid restricting the combustion air supply.
Allowable Equivalent Intake Lengths
Maximum Minimum
70 ft (21m) 7ft (2.1 m)
The intake duct must terminate at an outside
location with the supplied vent terminal.
The intake and vent terminals must be installed as
shown in Figure 7.
When locating the intake terminal, a minimum distance must be maintained from the exhaust vent terminal to prevent re-circulation of exhaust gases. Figure 7 shows the proper location of intake and exhaust terminals on an outside wall.
Figure #7
Exhaust terminal with opening vertical.
Intake terminal with opening vertical.
4ft-6ft
Keep a minimum of 6“ away from sidewall.
Periodic cleaning of the screens in the terminal is required for proper operation.
Location of intake & vent terminal must comply with all local and national codes.
VENTING
All joints must be positively sealed with a silicone
sealant to ensure that there are no leaks in the duct.
When installed, the intake duct and exhaust vent
should be the same equivalent length.
Condensate may form on the outside of the intake duct, particularly in colder climates. It is recommended to insulate the intake duct to prevent condensation from occurring.
To connect the intake duct to the air manifold:
1. Apply silicone around the outside of the connector on the top of the air manifold. See Figure #6.
2. Mount the intake duct over the connector and secure with an appropriate clamp to ensure a proper seal has been achieved.
CAUTION: The humidifier shall not be connected to a chimney flue serving any other appliances. All venting must be installed in accordance with local and national codes.
NOTE: These requirements apply to both standard, direct vent units and units with outdoor enclosure.
NOTE FOR OUTDOOR ENCLOSURE: It is recommended to vent the gas unit through the sidewalls of the gas enclosure to eliminate possible leakage through the enclosure roof.
The vent pipe must be the same diameter as the vent connector. The supplied vent termination at the humidifier is a MALE CONNECTION. Standard venting hook ups require a female to male path. It is highly recommended that a female to female adapter be assembled directly onto the humidifier. This will establish the proper vent sequencing. Consult with venting contractor/supplier for proper hook up or consult
-7-
manufacturer listing, see page 28. Contact NORTEC for additional information.
each 45° elbow equals 5'. For lengths over 100’, consult factory.
Class B vent must not
be used. Class “BH” vent must be used based on list of approved manufacturers shown in the installation manual.
GH100 exhaust manifold terminates with 3”O.D. Stainless Steel Tubing. GH200, 300 and 400 exhaust manifolds terminate with 4”O.D. Stainless Steel Tubing.
The maximum flue gas temperature at the humidifier vent connector will not exceed 480°F. Use only special gas vents listed for use with Category III or IV gas burning appliances, such as those listed in the venting system chart, see page 28. (Listed to UL Standard 1738 in the USA and ULC-S636 in Canada.)
All venting joints must be positively sealed with high temperature RTV silicone sealant rated for at least 480°F.
Operating Venting Temperature
Normal Maximum
All GH 360-380°F
(182-193°C)
450°F (232°C)
When venting a category IV appliance it is necessary to provide for condensate removal in the venting system. This provision may be met by using the special drain tee as listed in the venting system chart.
When a drain tee is used it is necessary to install a trap in the drain to ensure that flue gases do not vent into the drain. Install the trap with a 12” minimum height of standing water column.
Install the trap a minimum of 12” below flue vent with a depth minimum of 3”.
Direct Vent Unit
A maximum exhaust vent length of only 70 equivalent feet (21m) is permitted with the direct vent option, where each 90º elbow equals 10ft and each 45º elbow equals 5ft. This maximum cannot be exceeded.
All horizontal runs of the vent pipe shall have a minimum rise of 1/4” per foot (21 mm/m) and shall be supported at maximum intervals of 5' (1.5 m) and at each point where an elbow is used.
The vent terminal must be installed within the same atmospheric pressure zone as the combustion air inlet of the humidifier.
Periodic cleaning of the screens in the vent terminal is required for proper operation of the humidifier.
NOTE OUTDOOR ENCLOSURE: Flue gases must be vented out of the enclosure.
ADDITIONAL REQUIREMENTS WHEN VENTING THROUGH A SIDEWALL
For sidewall venting, locate the humidifier as close as possible to the wall being used.
Locate the vent terminal at least three feet above any forced air inlet located within ten feet; or at least four feet below, four feet horizontally from, or one foot above any door, window, or gravity air inlet into any building.
A minimum horizontal clearance of four feet from electric meters, gas meters, regulator and relief equipment is required.
Prior to activating the appliance, ensure that the trap is filled with water and that the drain terminates in accordance with local plumbing codes.
For any vent lengths over 20 feet long, use insulated vent. Also provide condensate removal in the venting system.
WARNING: Provide a screen or barrier to prevent personal injury in areas where inadvertent personnel contact with vent pipe can occur.
Standard Unit
The maximum recommended vent length is 100 equivalent feet where each 90° elbow equals 10' and
Locate the vent terminal at least seven feet above
grade when it is adjacent to public walkways.
Locate the bottom of the vent terminal at least twelve inches above grade or ground, or normally expected snow accumulation level. The snow level may be higher on walls exposed to prevailing winds.
Avoid areas where local experience indicates that condensate drip may cause problems such as above planters, patios, or over public walkways, or over an area where condensate or vapor could create a nuisance or hazard, or could be detrimental to the operation of regulators, relief valves, or other equipment.
-8-
Refer to the vent manufacturer's installation
O
instructions.
Figure #8
ELECTRICAL
PRIMARY WIRING
1. Humidifiers require field wiring to primary
voltage terminal blocks. Power requirement is 120 Vac, 15A fused circuit, single phase. Wiring is fed through a 7/8" hole on upper right hand side of control compartment. See figure #1.
2. When installed, the appliance must be
electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, and/or the CSA C22.1 Electrical Code, if an external electrical source is utilized.
3. Connect ground wire to cabinet ground clamp.
4. External wiring sizes must be in accordance
with NEC and/or CEC and existing local electrical codes and by-laws.
NOTE FOR OUTDOOR ENCLOSURE:
- Primary power should be routed through the grille at the bottom of the unit.
- Ifbackup heater is used, separate240 Vsupply must be provided with disconnect brought to the Enclosure forthe heater.(Heateruses 20A –consultlocal codes for wiringsize) Seeinstallation drawingprovided with the heater for instructions on page 32. Note: Heater may be plugged into 3-pronged, 30 ampere, 240 V outlet.
-
If units operates during the summer, wire exhaust fan provided with the enclosure(120V wires supplied with enclosure), from independent supply.
LOW VOLTAGE CONTROL WIRING
n/Off Signal Loop
(B Models)
External
Internal
A
B
C
12
24 VAC
Available
P/MC MODELS
34
MC MODELS
5
6
8
7
9
Controls are available from NORTEC as accessories and can be ordered with the humidifier. Controls by others may also be used as long as they meet the criteria noted below. The following is a summary of the common types of controls that may be used with NORTEC Gas Humidifiers.
A – Wall or Duct Mounted Control On/Off Humidistat: Wired to make on drop in humidity, break on rise to setpoint. Set to desired RH. Can be a make/break set of contacts from a Building Automation System.
B – Duct Mounted Safety High Limit On/Off Humidistat: Wired to make on drop in humidity, break on rise to safety setpoint. Set to approximately 85% RH as a safety to prevent saturation and wetting in the duct. Highly recommended for ducted applications.
C – Duct Mounted Safety Air Proving On/Off Switch: Wired to make when sensing air flow, break when no air flow. Used as a safety to prevent saturation when there is no air flow. Highly recommended for ducted applications.
D&E – Wall or Duct Mounted Modulating Humidistat: Provides a modulating signal to the unit that represents the output (up to 100%) required from the humidifier. Refer to the sections below that detail the signal ranges that can be used with each model.
All GH models require at least one type of input control signal for unit operation. Refer to the sections below that detail the types of controls that can be used with each model.
Low voltage control terminal strips are provided in the electrical compartment. Internal sides are factory wired. External sides are to be field wired. Refer to the specific control-wiring diagram supplied with each unit.
Field wiring from humidistat to humidifier and between devices should be 18 AWG or heavier and kept as short as possible.
NOTE FOR OUTDOOR ENCLOSURE: Control wiring should be routed through the grill at the bottom of the unit.
GHB MODELS
GHB models will accept on/off controls only (see A, B & C on figure #8). In general, A is essential whereas B and C are optional. On/Off controls are to be wired in series (only one path for current) across terminals 1 and 2 on the low voltage control terminal strip. All on/off controls used must be of the type that the contacts are closed when operation is required and open to shut off the unit. A jumper wire may be placed
-9-
across these terminals to replace on/off controls and provide for constant operation.
Caution: Terminal 1 is the “hot” wire from the 24Vac control transformer; it will trip the 3A breaker on the transformer if any control field wiring touches ground metal.
GHP MODELS
GHP models accept a single 0-10 VDC or 0-20 mA control signal (see D on Figure #8) across terminals 4 and 5 on the low voltage terminal strip to generate a modulating output from the humidifier. Terminals 1 and 3 are 24 Vac and ground respectively and may be used to power a remote mounted modulating humidistat.
An on/off security loop exists across terminals 1 and 2 and should be wired as described for GHB models.
3. Mount duct high limit humidistat downstream
of steam distributors far enough that, under normal humidity and air flow conditions, steam will have been fully absorbed (typically at least 10 feet). It must be located to sense high humidity only when uniform and representative air is over-humidified or approaching saturation.
4. Mount duct air-proving switch so that it is able
to sense air flow or lack of it. Wire it to make when air flow is sensed and break when air flow fails.
5. Check operation of all on/off controls before
starting humidifier.
6. Calibration of controls (on/off or modulation) in
the field may be necessary due to shipping and handling. Verify humidistat accuracy before commissioning system.
GHMC MODELS
GHMC models may be configured for either single or dual channel modulation. Control signals can be 0-10 VDC or 0-20 mA (0-5 VDC, 1-5 VDC, 4-20 mA and 2-10 VDC are also available). The unit must be ordered from the factory for the desired signal type and number of channels. When configured for 2-channel modulation the humidifier will generate steam only if both channels indicate a demand (see D&E on figure #8). If both channels are demanding steam the humidifier will satisfy the lower demand signal.
An on/off security loop exists across terminals 1 and 2 and should be wired as described for GHB models.
CONTROL INSTALLATION
1. Mount any wall humidistat (control or high
limit) over standard electrical box at height similar to typical thermostat. Any wall humidistat should be in location representative of overall space being humidified and not in path of blower pack or air supply grille. Do not mount on an outside wall where temperature fluctuations can affect control response.
2. Mount duct humidistat in location
representative of overall air humidity, usually in return duct. Do not mount it directly in front of steam distributor or in turbulent or mixing zone. Mount humidistat where air's humidity and temperature are uniform and representative of spaces being humidified.
OUTDOOR ENCLOSURE HEATER
SETTING
Position #1 on the heater will maintain the air around the heater at around 60ºF. Each increment changes the set-point by an additional 16ºF. The off position can be obtained by turning the knob counter clockwise. The set-point position is at 3 O’clock.
BLOWER PACKS
1. Blower packs are an optional accessory used
to directly distribute steam to localized areas (such as computer rooms) or in structures that do not have a built-in air distribution system.
2. Blower packs are remote mounted only. See
Blower Pack Manual XX-277 for requirements and installation instructions.
STEAM DISTRIBUTORS FOR DUCTED
APPLICATIONS
1. Any humidifier's steam line may be divided
into multiple branches to feed more than one distributor. Steam supply line “tees” are common copper fittings that are available for this purpose. Do not install zone valves on any of the steam supply lines.
2. Steam distributor locations are typically as
follows: supply air duct, return air duct, air handling unit. Proper location should consider: air temperature, relative humidity before the distributor, air velocity, dimensions
-10-
Loading...
+ 31 hidden pages