Nortec Gas-fired Humidifier, GH, GH 100, GH 200, GH 300 Maintenance Manual

...
GH Series Gas-fired Humidifier
§
s+j\if
Installation, User.&
Maintenance Guide
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors or any other appliance.
liquids
in
the vicinity
of
this
WHAT TO Do not try to light any appliance. Do not touch any electrical switch; do not use any telephone in your building. Immediately call your gas supplier from a neighbor's telephone. Follow the gas supplier's instructions. department.
WARNING: Improper property damage. Refer to this a qualified installer, service agency, or the gas supplier.
WARNING: If
the information in this manual is not followed exactly, a fire or explosion may result
causing property damage, personal injury or loss
IMPORTANT: Read
DO
IF
YOU SMELL GAS:
If you can not reach your gas supplier, call the fire
installation, adjustment, alteration, service or maintenance can cause injury or
manual. For assistance or additional information consuU
of
life.
and
save this guide for future
reference. This guide to be
Form #00-272 Rev. 2
left with equipment owner.
Table
Of
Contents
GENERAL
-WARNING
- RECEIVING & UNPACKING EQUIPMENT
- GENERAL SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
- MODEL DESIGNATION
......
. . . 1
............................
.
. . 1
INSTALLATION
- LOCATING AND MOUNTING
- GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
- AIR MANIFOLD/CONNECTOR HOSE INSTALLATION FOR DIRECT
- PROCEDURE:
-INTAKE
- TERMINAL LOCATION VENTING
-
- ELECTRICAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
AIR DUCT
...............
- STANDARD UNIT
DIRECTVENT UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-
ADDITIONAL REQUIREMENTS WHEN VENTING THROUGH A SIDEWALL
-
- PRIMARY WIRING
- LOW VOLTAGE CONTROL WIRING
......
......
.......
. .
........................................
................................
.
.
...............................
VENT.
. . . . . . .
...........
.
.. ..
..
·
..
.
..
.
..
.
....
·
..
.
...
. 7
.
..
.
...
9
1
1
3
4 5
6 6
6
8 8 8
8
- CONTROL INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
- BLOWER
- STEAM DISTRIBUTORS FOR DUCTED APPLICATIONS. . . . . . . . . . . . . . . . . .
- PLUMBING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
- WATER SUPPLY
-
- STEAM
- WATER
-
PACKS.
DRAIN LINE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
LINE.
TRAP.
CONDENSATE RETURN LINES FOR STEAM DISTRIBUTORS
OPERATION
- WATER LEVEL CONTROL BAND
-
MC MODEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
-
- SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
-
BLOWDOWN CALIBRATION
- MANUAL STEAM
P MODELS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
OUTDOOR ENCLOSURE HEATER SETTING. . . . . . . . . . . . . . . . . . . . . . . . . 17
-
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
..
..
10
..
12
LINE
..........
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
-.
. . . . . . . . . . . . . . . . . . . . . . . . 12
...
·
. 14
15
· . 15
......................................
OUTPUT ADJUSTMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
16
- B MODELS
-
GHMC DISPLAY OPERATION
.............................................
.....................................
17 17
START
-
- SAFETY INSTRUCTIONS
UP PROCEDURE
- FILLING THE SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-
TESTING THE IGNITION SAFETY
.......................................
SHUT-OFF.
..............
.
MAINTENANCE
- DRAINING THE TANK
-
CLEANING THE STAINLESS STEEL
- COMBUSTION
- BURNER
- BURNER
ADJUSTMENTS/REPLACEMENTS OF COMPONENTS
-
-
GAS
-
HOT
-
[GNITION MODULE
- TRANSFORMER REPLACEMENT
-
AIR
-
COMBUSTION AIR BLOWER REPLACEMENT. . . . . . . . . . . . . . . . . . . . . . . . 20
-
TANK
BLOWER.
....................................
REMOVAUINSPECTION . . . . . . . . . . . . . . . . . . . . . . . 18
VALVE REPLACEMENT SURFACE IGNITER REPLACEMENT
SWITCH REPLACEMENT
REPLACEMENT
. . . . . . . . . . . . . . .
REPLACEMENT.
......................................
- HEAT EXCHANGER REPLACEMENT
TANK
& FLOAT CHAMBER
........................
...................................
............................
. . . . . . . . . . . . . . . . . . . . . 19
................................
...................................
..........................
..
.
17
..
17
· . 17 . 17
17
· . 18
· . 18
· . 18
· . 18
19
19
19
19 19
20
20
- SERVICING THE UNIT
- FAULT CONDITIONS
-
BAND P MODELS.
-
MC
MODELS
- SERVICE CHECKS
- FLAME SENSOR. . . . . . . . . . . .
- IGNITER CHECK. . . . . . . . . . . . .
-
GAS
VALVE SETTING
- PREVENTATIVE MAINTENANCE SCHEDULE . START-UP AND INSPECTION
-
-
TROUBLESHOOTING GUIDE . . . . . . .
- REPLACEMENT STAND
- GH
GH ENCLOSURE PHYSICAL DATA
­ENCLOSURE HEATER INSTALLATION INSTRUCTIONS
- GH
- GH DIRECT VENT . . . . . . . . . . . . .
BIP WIRING DIAGRAM. . . . . . . . . . .
- GH
- EXTERNAL
- VENTING MANUFACTURER
PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-29
ASSEMBLY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
CONTROLS WIRING CONNECTIONS
...
..........................................
. . . . . . . . . . . . . . . . .
.................
.........
...........
...............................
.
.....
.
.........................
...
..
.
.....
...
..
· .
21 21
..
.......
.
.
...........
.
.
.
.
.
. .
· .
· .
· .
· .
· .
· . 23
· . 24
· . 25
...
· . 32
· . 33
· .
· . 36
21 21
21 21 21
21
31
34
.
35
GENERAL
WARNING
Improper service, maintenance, monoxide shock, personal injury or property damage. qualified installer, service agency, local gas supplier, information or assistance. The qualified
or
agency listed kits product. A failure to follow this warning can cause death.
Should off, before
• Do under technician to inspect the appliance and to replace any control which has been under water.
This installation guide has been designed to provide assistance sizing a
GH application your
local
installation, adjustment, alteration,
or
use can cause carbon
poisoning, an explosion, fire, electrical
or
other conditions which
may
Consult
or
your distributor
or
branch for
must use only factory authorized and
or
accessories when modifying this
electrical shock, fire, personal injury,
overheating occur,
shut
off
the manual gas valve to the appliance
not
shutting
use
off
this appliance
the electrical supply.
or
the gas fail to shut
if
any part has been
water. Immediately call a qualified service
part
of
the control system and any gas
when
installing, mounting, and
Series humidifier. Actual on site
may
vary. Consult Technical Services
NORTEC
representative.
cause
installer
or
a
or
GENERAL SPECIFICATIONS
The
NORTEC completely new patented design edge technology. The clean steam humidification at an
All GH models are available for
(0-2000 ft elevation)
GH Series
GH
is
or
for
high altitude (2000-4500 ft
humidifier
based
designed
economical
normal
is a
on leading
to
provide
altitude
elevation) applications.
GHMC for mounting outside when unit will ship completely installed inside the enclosure ready for field connection. will protect the unit from wind, sun
models are also available
space
is
and
with
enclosure
not
available.
outdoor
The
enclosure
precipitation.
MODEL DESIGNATION
The
unit specification label indicates the model
gas humidifier according to the following chart:
PRODUCT LINE
(Gas Fired Humidifier)
CONTROLS
B = BASIC (ON/OFF)
P = MODULATING MC = DIGITAL CONTROLLER
cJw
STEAM OUTPUT
(lbSlhr) Normal Altitude
KEYPAD
FUEL N=
NATURAL
P=
PROPANE GAS
GAS
GH MC 100
~!
of
__
_
:
i
!
I
~
N
01
price.
The
of
HA DV
RECEIVING & UNPACKING EQUIPMENT
1 .
Check
been delivered.
2. All material shortages are to be reported to NORTEC goods. NORTEC assumes no responsibility for
3.
Inspect on shipping waybill accordingly.
After
4. damage
shipper
5.
All F.O.B. factory basis. breakage directly to the shipping company.
packing Slip to ensure
within
48
hours from receipt
ALL
material
of
has
any material shortages beyond this period.
shipping boxes for damage and note
unpacking, inspect equipment
and
if
damage is found, notify the
for
promptly.
NORTEC
products are shipped on an
Any
and
,all
or
loss claims are to be made
damage,
DE·IONIZED WATER OPTION
HIGH ALTITUDE OPERATION
DIRECT VENT OPTION
INSTALLATION
1. The installation building codes or, codes, with the ANSI Gas Code, and/or Codes. Refer to the manual.
2.
The humidifier shall not be chimney flue serving
3.
Provide
ventilation air
7.3 of or Section 5.3
for
adequate
or
7.4, Air
the National Fuel Gas Code, ANSI
+-------~
+-------------'
must
conform with local
in
the
absence
2223.1,
CAN/CGA
Gas
Piping section
any
other
combustion
in
accordance with
for
Combustion
of
CAN/CGA
of
local
National Fuel
B 149 Installation
of
connected
to a
appliances.
and
Sections
and
Ventilation,
2223.1,
B149
Installation
this
7.2,
- 1 -
:;~:::::~"7:::::=.';-,",~;::;:-":=~:;:::;::;;:=:~:;;:==::-":===:::::"~:':::'::;::;;::=:::::::;::::::::;."";:!"==:::=:;;:-----:===:::;;..-='"~-===::':=:;:::::::::::--====:.-:;::::~-=:::::=::!:::-..;:;:::=:.;::::::::;!':;;:
MODEL
...
FUEL···
··.·B~~~iRr·iNPUT(BTuH;:··-roR\~i:~iZE
I i I DIAMETER!
i!
I
STO
NATURAL
PROPANE
(LP
.,
For high altitude units (2000-4500 ft) the input and steam capacities are
FUEL INPUT (BTUH)*
~_MAX
GAS
~-----+------~------~--------------------------~------------~------~
GAS)
i
____
+-_11_9_,0_0_O_!~1_1_9_,0_00
MIN
MAX
MIN
65,000 85,000 E
119,000 119,000 9 100 100
65,000 85,000 9 50 70
OV!
__ ~ ____
E
GH
--ST~£~~F;TYTMANiFOW.t.~ESS;NT~~iic-~Ts.tJT!:~0f~g~mu~i
STD
_________
100 SPECIFICATIONS
OV
100
__ ~ ____
50
10_0
70
de-rated
__ ~ ______________
by 10%.
...
-::::.:::::::::"..:::-::;;:::..""!;:=::-:::=::;::::;:::::~:':::;:::;:::-":!::;:''";:::;:::::::';-"::;::===-":;';;:':=::!;:::--,";=;:::;:::":=:':=:::":~":::::::::-'=;:="':::;1
ii
STO
. i
OV
~
______
(LBS)
~
(LBS) I
.,
For
high altitude units (2000-4500 ft) the input and steam capacities are
FUEL
NATURAL 357,000
GAS
1t
For
high altitude units (2000-4500 ft) the
BLOWER
SPEED ORIFICE
(MODEL)
INPUT (BTUH)"
STO
178,000
65,000
357,000
ov
357,000
255,000
85,000
357,000
input
and steam capacities
are
de-rated
300 210
70
de-rated
by
10%. STD: Standard Gas Unit DV:
DIAMETER
OV
-0,2
-0,2 0,00
-0.2
by
10%. STD: Standard Gas
0,00
0.00 1.062"
0.00
1.062"
1.062"
1.062"
Unit
AIR
DV:
350
Direct
Vent
SHIPPING
WEIGHT
(LBS)
800
800
Direct
Vent
660
660
Unit
OPERATIN GWEIGHT
(LBS)
1200
1200
Unit
FUEL
NATURAL MAX
GAS
PROPANE
BLOWER
SPEED
(MODEL) DIAMETER (LBS)
MIN
(B,P)
MIN
MAX
MIN
(B,P)
* For high altitude units (2000-4500 ft) the
INPUT (BTUH)*
476,000
238.000
65.000
476.000
238.000 65,000
OV
476,000 340,000
85,000 476,000 340,000
85.000
input
MODEL
E 400 E 200 E 50
9 9 200 9
and steam capacities are
GH
400 SPECIFICATIONS
STEAM CAPACITY
(LBS/HR)*
STD
400
50 70
de-rated
- 2 -
MANIFOLD PRESS.
DV
400 280
70 400 280
STD
-0,2
-0.2
-0.2
-0.2 0.00
by
10%. STD: Standard Gas
W.C:
OV
0,00 1.062"
0.00 0,00
0,00
0.00
IN
AIR
ORIFICE
1.062~
1.062ft
1.062"
1.062ft
1.062"
Unit
DV:
800
800
Direct
Vent
OPERATIN
GWEIGHT
1200
1200
Unit
-
Codes, or applicable provisions
of
the local
building codes.
4. The required free area
is: 11
in. sq. (7,000
20
in. sq. (13,000
in. Sq. (19,500
30
in. Sq. (26,000
40 NOTE FOR DIRECT
The combustion supply air opening
the
required to
room where the appliance is
of
supply air opening
2
mm
),
for GH 100
mm7"
for
mm
),
for GH 300
2
mm
),
for
VENT OPTION:
GH
GH
200
400
is
installed since the combustion air
be
requirements will
provided through the inlet
air duct (see installation section).Some
is
ventilation
required for cooling of the
electronic components NOTE FOR OUTDOOR ENCLOSURE:
Required free area of supply air
is
provided
through the bottom of the unit. Front louvers
in
ensure good air circulation These louvers should
be
the summer.
blocked for winter
operation.
5.
Cabinet back to provide combustion air
and
bottom contain air openings
to
the forced draft blower. Either the back or bottom set of openings must have at least
to
clearance
allow for adequate combustion
air. For example, if the humidifier
2"
mounted,
clearance must be maintained to
2" (50 mm)
is
floor
the unit's back surface.
6. Excessive exposure combustion air
to
contaminated
wiii result
in
safety and performance related problems. Known contaminates include halogens, ammonia, and chlorides, excessive dust, lime or dirt. Contact NORTEC Technical Services if you have any questions.
not
9.
During installation cover the humidifier
to prevent any dust or other contaminants from entering the cabinet when activities such as drilling are taking place'.
NOTE: Some combustible. Prior the area for insulating installed
in
an and clear of insulating materials. after the appliance
insulating materials may
to
installing this appliance examine
be
material. If this appliance
insulated space, it must be kept free
is
installed, it will
If insulation
be
is
added
necessary to
examine the area again.
LOCATING AND MOUNTING
GH
Series humidifiers are designed
(GH
suitable wall clearance dimensions shown
100 only), GH Stand,
in
this manual are for reference only and are the minimum required for maintenance of the humidifier. Local and National
be
Codes should installation of the humidifier.
consulted prior to final location and
NORTEC cannot accept
responsibility for installation code violations.
1.
Figure
#1
shows the locations connections to the Gas Humidifier. Careful consideration should be given to all connections when choosing a location for the humidifier.
Figure
Steam
1=========::::::::o=utJe=t{$=)
#1
EXHAUST VENT
OUT FROM THE
===+~:=:::;;;l--
to
mount
or
floor. The
of
all required
of
these
COMES
TOP
~~::t~ring
Water Input
Line
Gas Input
Line
Side
is
on
a
7.
All surfaces are zero clearance construction.
NOTES:
- The leveling legs must be left on
floor mounted
combustible material.
The humidifier shall not on
carpeting, tile or other combustible
material other than wood flooring.
8.
For recommended clearances for servicing refer to Figure
#2.
to
combustible
in
place when
be
installed directly
- 3 -
t::::::======::±:==:=f-
Figure #2
Top
View
Min, 36" Of Space
For Frontal Clearance i
I
I
T
Drain
Wall
With Direct
clearance Direct Vent
option
for
2. For front and side clearance requirements (for access during installation, maintenance and
troubleshooting), see Figure #2.
3.
Location minimum
4.
DO NOT locate humidifier any further than absolutely necessary from steam distributor location. Net output of Engineering Manual, Form increased static pressure (over result Consult factory if this situation occurs.
5.
Where possible, mount humidifier at a height convenient for servicing.
6.
Wall mounting brackets (provided with GH
100) should
upwards, horizontal, using field-supplied fasteners (minimum of four
fasteners
vertical, solid surface. Put a security bolt through the hole provided cabinet so that the unit cannot
the
of
the steam distributor should be
of
36" above the humidifier.
will
be
reduced as a result
heat loss through steam hose (see
# -1630). Also,
7"
W.
in
steam leaking down the drain.
be
securely attached open edge
3/8"
diameter
in
each bracket). Attach
in
wall bracket. See Figure #3.
to
the back of the
be
bumped off
C.) will
a
- These legs may longer legs. Factory approval is needed.
- Removal or adjustment square end of a
be
removed and replaced
of
legs requires the
3/8"
socket driver.
10. Optional stands are available for all GH Series
humidifiers. Refer to Shop Drawing Package,
# 273 for details and part numbers.
Form
15
Clearances around the unit should also be maintained for good access the gas humidifier.
is
3 feet clearance the enclosure for on
the right side of the enclosure for the
needed
GH100/200, 4 feet is needed
on
the right side of
GH300/400. The front requires 3 feet
clearance for
16.
DO
NOT mount humidifier on hot surfaces.
17.
DO
NOT mount humidifiers
freezing may occur. If humidifiers
18. ventilated, temperature controlled, (above freezing), weatherproof enclosure. Consult
local representative for more information
your on
Nortec's enclosure.
ail
capacities.
in
an
area where
are-
mounted on roof, a properly
by
Figure
7.
Make sure humidifier mounted adjust using leveling legs.
8.
The GH 100 model adjustable leveling removed for mounting the unit GH stand. Maximum travel of legs
9.
The GH 200, equipped with adjustable leveling legs which have a maximum travel of
GH
#3
c
is
mounted level. If floor
is
equipped with
legs which may be
on
300 and
GH 2".
400 are
an optional
is
2"
19.
DO
NOT mount humidifiers on vibrating
surface. Consult factory.
20.
In
earthquake prone
Use the existing wall mount brackets
to
the wall with it sitting
unit Maintain spacing for air openings.
"Installation"
NOTE FOR OUTDOOR ENCLOSURE:
Optional
is
unit
The enclosure should be installed at a secure distance from any air or exhaust system. (also see local code)
The enclosure should be bolted down or secured if it
If lifting
forklift, lift under the unit at cross members for
stability. (Strapping belts can also be used.)
item
outdoor enclosure can also be used;
factory mounted inside the enclosure.
is
the
enclosure
to
are.:Js
8).
be
exposed
do not wall mount.
on
the floor.
to
high winds.
on
the roof using a
to
(See
GAS PIPING
fasten
- These legs may mounting
of
be
removed
an
optional stand.
to
allow
Installation of piping must
local codes, and ANSI Z233.1, "National Fuel Gas
be
in
accordance with
- 4 -
Code," Installation Codes
minimum
in
the United States or CAN/CGA-B 149
in
Canada.
The
following table indicates the maximum and
allowable gas pressures for the Gas
Humidifier.
INCHESW.C.
GAS MIN.
Natural
Propane
The gas inlet pipe size
~"NPT
for GH 100
3/4" N PT for
1"
NPT for GH300/400
Provide
an
adequate size gas supply line.
When black iron
be
must In
located ahead of the humidifier gas controls.
all installations, a manual shut off valve, located
outside the cabinet, must
GH
gas
4.5
,
9.0
to
the appliance is:
200
pipe
is
used, a sediment trap
be
installed. See Figure #4.
MAX.
14.0
14.0
Figure #4
NOTES:
1.
Failure the gas valve. not covered
2.
DO threads. A flexible with Natural Gas and Propane Gas
to
follow this procedure may damage
Over pressured gas valves are
by
warranty.
NOT use Teflon tape
on
gas line pipe
sealant suitable for use
is
recommended.
3.
Plan
gas
supply piping so it will not interfere with removal of gas valves or blower assemblies
The gas valve
and
front or side service doors.
is
provided with pressure taps to measure gas pressure upstream and downstream, (manifold pressure). The minimum gas pressure
is
shown
for the purpose
A
1/8" NPT plugged tapping, accessible for test
of
input adjustment.
gage connection, must be installed immediately upstream of the gas supply connection to the appliance. The humidifier
shall not be connected to a
chimney flue serving any other appliances.
NOTE FOR OUTDOOR ENCLOSURE: Gas lines
should
routed through the bottom
of
the enclosure
be
For direct vent units, the combustion supply air
is
opening appliance
not required
is
installed since the combustion air requirements will (see installation notes below). Some ventilation required for cooling
to
the room where the
be
provided through the inlet air duct
of
the electronic components
is
,J
Leak test all gas connections using a commercial
to
soap solution made gas leakage. humidifier
Seal
in
operation.
WARNING: Never use
gas leaks.
If a leak does exist, a fire or explosion
could occur, resulting
detect leaks. Bubbles indicate
all
leaks before placing the
an
open flame
in
damage, injury or death.
to
check for
The appliance must be isolated from the gas
by
supply piping system
closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to greater than 14"
W.c.
(3.5 kPa).
or
Dissipate test pressure from the gas supply line
before re-opening the manual shut off
valve to the
appliance.
AIR MANIFOLD/CONNECTOR HOSE
INSTALLATION FOR DIRECT
All direct vent units are shipped with the air
manifold and connector hoses packaged separately. The connector hoses and air manifold must be installed by a qualified installer prior to commissioning the unit.
Figure #5
- 5 -
VENT
Hose
u:uUlcclion
iApply
iiliccne)
Procedure:
1. Apply a ring of silicone around the outside each
of
the blower adapter connector.
2.
Mount a flexible connector hose connection secure using a gear clamp provided with the unit. Care should be taken not to kink damage
3.
Carefully bend the flexible hose(s) to give the
"S" shape
4.
Mount
base using the mounting bracket located on the bottom
6).
DO
HOLES
on
each blower adapter and
the flexible hose. (Refer to Figure #5).
as
shown
the air intake manifold to the cabinet
of
NOT
PUNCTURE OR ADD
TO THE AIR MANIFOLD.
in
the diagram.
the air manifold (refer to Figure
over
the
or
ANY
of
hose
•.
1.·11-1
S_U_p_p_li_e_r
: Z-Flex I Z-Flex
II
Flex-L
'I
I MICHIGAN CHIM-FLEX
:
I
il-~~i~-~-~~-~:~~~-
:b~~~"'~==o~"==,~=~"~~:.c.="'''o,''~==o,,'o,'''~~o,,'''=,~o,,,c."~=~~~,=,c.,,~~=="""="""='"'~=~"',,Jj
length that can be connected to the Each elbow equals bends should be smooth and have as possible to avoid restricting the
______
International_l~ll~~iner
-·--·T~I:~_~I;~~~~=~·-~~~e~--'I
The following table details the
90 degree elbow equals 10ft
Sft.
If flexible vent material is used, all
i
t.-
P_r_o_d_u_c_t
Iney
i '
',,:
CHIM-FLEX
'Liner
______
Aluminum
Liner
~
Aluminum
allowable
direct
and
each
large
combustion
Chim-
___
duct
vent
option.
45
degree
a radius as air supply.
:1
[I
i,i
III
i
Figure #6
cabinet base
5.
Apply
a ring of silicone to the outside
hose
connection on the air manifold.
6.
Mount hose manifold and secure using a gear clamp provided with the unit.
the corresponding flexible
over
each hose connection on
INTAKE AIR DUCT
against rear panel
of
each
connector
the
air
rl
Allowable Equivalent
I Maximum i
I '
I
:170
ft
(21
!
sealant to ensure that there are no leaks in
should be the same equivalent length.
duct, particularly recommended to insulate the intake condensation from occurring.
m) : 7ft (2.1
All jOints must be positively sealed
installed, the intake
When
Condensate may form on the outside
in
To connect the intake duct to
1.
Apply silicone around the outside connector on the top (Figure 6).
2.
Mount the intake duct secure with an appropriate clamp to proper seal has been achieved.
Int~ke
colder climates. It is
Lengths
Minimum
m)
duct
and
duct
the
air manifold:
of
the air manifold
over
the
with
exhaust
to prevent
connector
a silicone
the
duct.
of
the intake
of
the
ensure
~
vent
and
a
ii
All direct
provide fresh outside air for combustion.
Each air intake manifold has a Single 4-inch
(1
OOmm)
must
be connected.
Intake material must be UL or ULC listed 4-inch diameter The
following table lists several suppliers
intake
vent
units require
diameter
(1.0.) corrugated 2-Ply aluminum ducting.
material.
inlet to which the supply air
an
intake air
duct
duct
of
approved
to
TERMINAL LOCATION
The intake duct must terminate at an outside
location with the supplied vent terminal.
The intake and vent terminals
in
shown
distance must be maintained from the
- 6 -
Figure 6.5.
locating the intake terminal, a
When
must
exhaust
be
installed as
minimum
vent
Figure #6.5
The
cabinet.
GH
must be vented through the top of the
terminal Figure 6.5 shows exhaust terminals
to
prevent re-circulation
the
proper location
on
an
outside wall.
of
Periodic cleaning of the screens
exhaust gases.
of
intake and
in
the terminal
required for proper operation.
Location
of
intake & vent terminal must comply
with all local and national codes.
VENTING
CAUTION: The humidifier shall not be connected
to
a chimney flue serving any other appliances. All venting must be installed national codes.
NOTE: These requirements apply to both
standard, direct vent units and units with outdoor
enclosure.
in
accordance with local and
is
NOTE FOR OUTDOOR recommended sidewalls
to
vent the gas unit through the
of
the gas enclosure to eliminate possible
ENCLOSURE:
It
is
leakage through the enclosure root.
The vent pipe must be the same diameter
vent connector.
and
sizes
part numbers. The supplied vent
See following chart
for
as
the
venting system
termination at the humidifier is a MALE CONNECTION. Standard venting
to
female female
male path. It is highly recommended that a
to
female adapter be assembled directly onto
hook
ups require a
the humidifier. This will establish the proper vent sequencing. Consult with venting contractor/supplier for proper hook up. Contact
NORTEC for additional
information.
GH100 units are supplied with a 90 degree elbow
to
(female has the correct dimensions
the knock-outs
installed venting can be connected to this elbow
long can
female) for the vent connection. This elbow
to
align the venting with
in
the top and rear cabinet panels. The
as
a proper seal can
be
replaced with
be
achieved
an
equivalent elbow supplied
or
as
the elbow
the venting manufacturer.
The maximum flue gas temperature at the humidifier vent connector only special gas vents listed for use with Category or
IV
gas burning appliances, such as those listed the venting system chart. (Listed to in
the USA
and
ULC-S636
will not exceed 480°F. Use
III
in
UL
Standard 1738
in
Canada.)
by
,.J
Venting
Model
GH 100
GH
100
GH 100
GH 200 IV Flexmaster GH 300 GH
400
GH 200 GH 300 GH400
GH 200 GH 300 System GH 400
Category
III
III
III
IV
IV
Manufacturer
Flexmaster
Magnaflex
Flex L Int'I Inc.
Magnaflex
Flex L Int'I Inc.
Z-Flex
Z-Flex
Systems
Diameter
:
Approved
Vent
:
3"
3"
3"
4"
4"
4"
StaR-34 System
For
Use With
Rigid
02SVEPXX03
NA
StaR-34 System:
02SVEPXX04
NA
GH
Series Humidifiers
Flex
i
22TL294C03 02SVSRTX03 02SVEDPS03
03SSPLV
:
StaFlex-294
System
22TL294C04 02SVSRTX04 02SVEDPS04
04SSPLV
StaFlex-294 SRTT-04
- 7 -
Vent
Terminal
03SSHVT
.
SRTT-03
04SSHVT
Sidewall
Drain
Tee
NA
SRTDH-03
NA
SRTDH-04
All venting joints must
high temperature
480°F.
least
When venting a category necessary venting system. This provision may be met by using the special drain tee chart.
When a drain trap
in
the drain
into the drain.
of
height
trap accordance with local plumbing codes.
standing water column.
Prior
to
is
filled with water and that the drain terminates
RTV
to
provide for condensate removal
tee
to
ensure that flue gases do not vent
Install the trap with a 12" minimum
activating the appliance, ensure that the
be
positively sealed with
silicone sealant rated for at
IV
appliance it
as
listed
in
the venting system
is
used it
is
necessary
is
in
the
to
install a
in
ADDITIONAL REQUIREMENTS THROUGH
For sidewall venting. locate the humidifier as close
as
possible
Locate the vent terminal at least three feet above any forced air inlet located within ten feet; or four feet below, four feet horizontally from, or one foot above any door, window, or gravity air inlet into any building.
A minimum horizontal clearance electric meters, gas meters, regulator and relief equipment
Locate the vent terminal at least seven feet above
grade when it
A SIDEWALL
to
the wall being used.
is
required
is
..
adjacent
to
WHEN
public walkways.
VENTING
of
four feet from
at
least
For any vent lengths over
insulated vent.
WARNING: Provide a screen or barrier
personal injury
contact with vent pipe
Standard Unit
The maximum recommended vent length
equivalent feet where each 90° elbow equals
45° elbow equals
each should be assumed additional
Direct Vent Unit
A maximum exhaust vent length equivalent feet (21m) option, where each elbow equals 5ft. This maximum cannot be exceeded.
All horizontal runs of the vent pipe shall have a minimum rise of supported at maximum intervals of each point where
The vent terminal must be installed within the same atmospheric pressure zone
air inlet
terminal is required for proper operation humidifier.
of
Periodic cleaning of the screens
in
areas where inadvertent personnel
can
5'.
to
lose 10% output for each
50' equivalent length.
is
90
elbow equals 10ft and each 45
1/4" per foot
an
elbow
the humidifier.
20
feet long, use
to
prevent
occur.
is
100
10'
and
For lengths over 100', unit
of
only 70
permitted with the direct vent
(21
mm/m) and shall be
5'
(1.5 m) and at
is
used.
as
the combustion
in
the vent
of
the
of
Locate the bottom twelve inches above grade or ground, expected snow accumulation level. may
be
higher
on
walls exposed
Avoid areas where condensate drip may cause problems such as above planters, patios, or over public walkways, or over area where condensate or vapor could create a nuisance or hazard, or could be detrimental operation of regulators, relief valves, or other equipment.
Refer
to
the vent manufacturer's installation
instructions.
the vent terminal at least
or
normally
The
snow level
to
prevailing winds.
local experience indicates that
an
to
the
ELECTRICAL
PRIMARY WIRING
1.
Humidifiers require field wiring to primary voltage 120 Vac, 15A fused circuit, single phase.
Wiring
hand side of control compartment.
#1.
2.
When installed, the appliance must electrically grounded codes the National Electrical Code, ANSI/NFPA 70, and/or the CSA external electrical source
terminal blocks. Power requirement
is
fed
through a 7/8" hole
or,
in
the absence
C22.1
in
accordance with local
of
Electrical Code, if
is
on
upper right
See figure
be
local codes, with
utilized.
an
is
NOTE OUTDOOR ENCLOSURE: Flue gases
be
must
vented out of the enclosure.
- 8 -
3.
Connect ground wire to cabinet ground clamp.
4.
External wiring sizes must be
with
NEC
and/or CEC and existing local
electrical codes and by-laws.
in
accordance
NOTE FOR OUTDOOR ENCLOSURE:
- Primary power should be routed through the grille at the
the bottom of If backup heater
-
unit.
is
used, separate 240 supply must be
provided with disconnect brought to the Enclosure for
20A-
the heater. (Heater uses wiring size) heater for instructions
See installation drawing provided with the
on
be plugged into 3-pronged, If units operates during the summer, wire exhaust fan
-
consult local codes for
page 32. Note: Heater may
30
ampere, 240 V outlet.
provided with the enclosure (120Vwires supplied with enclosure). Exhaust fan power can be the same sup-
to
ply then the power
LOW
VOL
rAGE
the unit.
CONTROL WIRING
B - Duct Mounted Safety High Limit On/Off
Humidistat: Wired
on
rise
to
safety setpoint. Set to approximately 85%
RH
as
a safety to prevent saturation and wetting
to
make on drop
in
humidity, break
in
duct. Highly recommended for ducted applications.
C - Duct Mounted Safety Air Proving On/Off
Switch:
Wired to make when sensing air flow, break
when no air flow. Used as a safety to prevent
is
saturation when there
no air flow. Highly
recommended for ducted applications.
D&E ­Humidistat: Provides a modulating signal that represents the output
the
humidifier. Refer
the
signal ranges that can be used with each model.
Wall or Duct Mounted Modulating
to
(up
to 100%) required from
to
the sections below that detail
the unit
the
Figure #7
On/Off Signal Loop
(BModels)
A
sI
-r
C.l
External
Internal
~~
__
~~
__ ~ __
Available
All GH models require at least one type control signal for unit operation. Refer below that detail the types of controls that can be used with each
model.
Low voltage control terminal strips are provided the electrical compartment. Internal sides are factory
wired. External sides are to the specific control-wiring diagram supplied with each unit.
Field wiring from humidistat to humidifier and between devices should be kept as short
as
possible.
Controls are available from
can
be
accessories and
ordered with the humidifier. Controls by others maya/so meet the criteria noted below. The following
of
summary used with
A -
Humidistat: Wired
on
rise
make/break set
the common types
NORTEC Gas Humidifiers.
Wall or Duct Mounted Control On/Off
to
make
on
to
setpoint. Set to desired
of
contacts from a Building Automation
System.
~~
__ ~ __
to
the sections
be
field wired. Refer
18
AWG or heavier and
NORTEC as
be
used as long as they
of
controls that may be
drop
in
humidity, break
RH.
Can be a
of
is
L-~
input
to
a
in
NOTE FOR OUTDOOR ENCLOSURE: Control wiring should be routed through the grill at the bottom of the unit.
MODELS
GHB
GHB models will accept on/off controls only (see
A,
B & C
on
figure #4.1).
Band
whereas be
wired
terminals 1
C are optional. On/Off controls are
in
series (only one path for current) across
and 2 on strip. All on/off controls used must be the
contacts are closed when operation
to
open
across these terminals to replace on/off controls and
.
shut off the unit. A jumper wire may
In
general, A
is
essential
the low voltage control terminal
of
the type that
is
required and
be
placed
provide for constant operation.
Caution: Terminal 1 is the 24Vac control transformer; it the transformer if any control
"hof'
wire from the
will trip the 3A breaker on
field wiring touches
ground metal.
MODELS
GHP GHP models accept a single 0-10 VDC or 0-20
mA
control signal (see D
terminals 4
and 5 on
on
figure #4.1) across
the low voltage terminal strip to
generate a modulating output from the humidifier.
and
Terminals 1 and
may be used
3 are 24 Vac and ground respectively
to
power a remote mounted
modulating humidistat.
An
on/off security loop exists across terminals 1
and 2 and
should be wired as described for GHB
models.
GHMC
GHMC models may or dual channel modulation. Control signals 0-10
VDC
MODELS
be
configured for either single
VDC
or 0-20 mA (0-5 VDC, 1-5 VDC and 2-10
are also available). The unit must
be
ordered
can
be
to
- 9 -
from the factory for the desired signal type and number of
channels. When configured for 2-channel
modulation the humidifier will generate steam only
if both channels indicate a demand (see O&E on figure #4.1). humidifier will satisfy the lower demand
If both channels are demanding steam the
signal.
do not have a built-in air distribution system. Blowers are remote mounted only.
2.
Blower packs are remote mounted only. See Blower Pack Manual XX-277 for requirements and installation instructions.
An on/off security loop exists across terminals 1 and 2 and should be wired as described for GHB models.
CONTROL INSTALLATION
1.
Mount any wall humidistat (control or high limit) over standard electrical box at height similar to typical thermostat. Any wall
in
humidistat should be of
overall space being humidified and not
path
of
blower pack or air supply grille. Do
mount
on
an
outside wall where temperature
fluctuations can affect control response.
2.
Mount duct humidistat representative of overall air humidity, usually in
return duct.
of
steam distributor or
Do
zone. Mount humidistat where air's humidity and temperature are uniform and representative of spaces being humidified.
3.
Mount duct high limit humidistat downstream
of
steam distributors far enough that, under normal humidity and air flow conditions, steam will have been fully absorbed (typically at
feet). It must be located to sense high
10 humidity only when uniform and representative air is over-humidified or approaching saturation.
location representative
in
location
not mount
in
turbulent
it
directly
or
in
mixing
in
not
front
least
STEAM DISTRIBUTORS FOR DUCTED
APPLICATIONS
1.
Any humidifier's steam line may be divided into multiple branches to feed more than one distributor. common copper fittings that are available for this purpose. of the steam supply lines.
2.
Steam distributor locations are typically as follows: supply air duct, return air duct, air handling unit. Proper location should consider: air temperature, relative humidity before the distributor, air velocity, dimensions of the location, amount introduced into the duct, downstream obstructions, and surfaces vulnerable to wetting.
3.
When steam distributors are located they should be least 6 feet
obstruction. result
characteristics, please consult
representative or the factory. (See Engineering Manual, Form #
information
Figure #8.
Steam supply line "tees" are
Do
not install zone valves on any
of
steam being
in
a straight section of duct at
(2
meters) from any elbow or
If the duct
in
poor absorption distance
on
absorption distances.) See
or
plenum conditions
your
-1630
in
local
for
a duct,
4. Mount duct air-proving switch so that to sense air flow or
when air flow
lack of
is
sensed and break when air
it.
flow fails.
5.
Check operation
of
all on/off controls before
starting humidifier.
6.
Calibration of controls (on/off the field may be necessary due to shipping and
handling. Verify humidistat accuracy
before commissioning system.
BLOWER PACKS
1 . Blower packs are
to directly distribute steam to localized areas (such as computer rooms) or
an
optional accessory used
-it
is able
Wire it to make
or
modulation)
in
structures that
in
Figure
NOTE: MuUipie Steam Oislnbutors
Can Reduce
tile
Minll"l1Um
4.
Steam distributors should always span the full width
of
the air stream. Multiple steam
distributors, arranged
MinlrnJm
Distance.
#8
(2m)
6n~
in
a bank, can minimize
absorption distance.
10-
-
Loading...
+ 28 hidden pages