Nortec BACnet User Manual

Important: Read and save these instructions. This guide to be left with equipment owner.
BACnet®, LONWORKS®
Supplemental Installation and Operation Manual
Using BACnet or LonWorks with Nortec Humidifiers. Includes installation, operation maintenance and troubleshooting information.
2574199 –A| 24 October 2013
INSTALLATION DATE (MM/DD/YYYY)
MODEL #
SERIAL #
CYLINDER #
Thank you for choosing Nortec.
Proprietary Notice
This document and the information disclosed herein are proprietary data of Nortec Humidity Ltd. Neither this document nor the information contained herein shall be reproduced, used, or disclosed to others without the written authorization of Nortec Humidity Ltd., except to the extent required for installation or maintenance of recipient’s equipment.
Liability Notice
Nortec does not accept any liability for installations of humidity equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by Nortec.
Copyright Notice
Copyright 2013, Nortec Humidity Ltd. All rights reserved BACnet® is a registered trademark of ASHRAE. LONWORKS® is a registered trademark of Echelon Corporation.
BACnet & LONWORKS Supplemental Install Manual | 2
Contents
Introduction 2
Requirements 2
NH-EL Wiring Connections 3
BACnet MS/TP 3
BACnet IP 4
Addressing and Communication 8
BACnet Communication Set-up 8
Control Signal Setting 9
Control Mapping 10
Options (Lonworks, BTL Certified BACnet) 14
Field Retrofit Installation 14
Addressing and Communication 17
Control Signal Setting 17
Controller Set-up 18
BTL Certified BACnet specific : Changing Unit Addressing 18
Changing Baud Rate (BACnet MSTP Only) 19
BACnet Pics and Bibs 19
LonWorks Variables 19
Troubleshooting 22
APPENDIX A 24
APPENDIX B 26
Warranty 30
CAUTION: Servicing
CAUTION: Electrical
CAUTION: Installation
Disconnect main power before any servicing.
The plumbing and electrical compartments contain high voltage components and
wiring. Access should be limited to authorized personnel only.
During and following operation of the humidifier, the steam and components in
contact with the steam such as the blower pack, steam lines, steam distributors, and condensate lines can become hot and can burn if touched.
Nortec Humidity Ltd does not accept any liability for installations of humidity
equipment installed by unqualified personnel or the use of parts/components/equipment that are not authorized or approved by Nortec Humidity Ltd.
All electrical work should be done according to local and national electrical code. Electrical connection to be performed by a licensed electrician.
Do not mount Humidifier on hot surfaces.
Do not mount in area where freezing can occur.
Do not mount on vibrating surface.
Do not mount on floor.
Regardless of selecting on/off or modulating control method, Nortec humidifiers
must have a closed circuit across its on/off security loop control terminal to operate. Nortec highly recommends the use of a duct high limit humidistat.
Introduction
Nortec Humidifiers equipped with the Integrated Controller (touch screen) can readily connect to BACnet Master Slave Token Passing (BACnet MS/TP) and Internet Protocol (BACnet IP) building management systems (BMS) right out of the box. This document describes how to connect these humidifiers to such a network and defines the parameters that may be monitored. This document also describes the additional options that can be purchased when interfacing with LonWorks or BTL certified BACnet. Contact the factory for more information on other protocols not listed in this manual.
Requirements
All NH-EL humidifiers are capable of Modbus, BACnet MS/TP and BACnet IP connectivity right out of the box and require no additional hardware to interface with these BMS. For Modbus specific details, consult Nortec Modbus Manual 2560599-C.
LonWorks and BTL certified BACnet systems require additional optional hardware – see Options (Lonworks, BTL Certified BACnet) for more details.
Please note: to use the BTL certified BACnet or Lonworks protocols, the jumper J7 must NOT be on. When the jumper J7 is on, the controller will enable the native Modbus protocol available on BMS communication port.
BACnet & LONWORKS Supplemental Install Manual | 2
NH-EL Wiring Connections
Signal Type
Polarity
Recommended Cable
Address
Maximum Recommended Distance from NORTEC Humidifier
A
B
Node
ID
Device
Instance
EIA-485, 2-wire
Net - Net
+
18-24 AWG Shielded, Twisted Pair 120  Impedance
79*
1001*
2300 ft at 9.6 kbps
2000 ft at 38.4 kbps
Using the correct wiring between the humidifier and the BACnet network is important to ensure reliable communications and reduce the impact of electrical interference.
BACnet MS/TP
For BACnet MSTP networks, the recommended wire type is 18 -24 AWG, shielded twisted pair wire with 120 Ohm characteristic impedance. Ensuring the correct shield terminations is necessary to prevent electrical interference. The wire shield should be terminated at either the humidifier or the BACnet system, but not both. This allows induced current to “drain”; if the shield is terminated at both ends it will function as a conductor and can actually increase electrical interference. To minimize signal loss a wire run should not exceed 2000 feet at 38.4 kbps.
Table 1: BACnet MS/TP Parameters
*Default, may vary for multi-unit orders.
3 | BACnet & LONWORKS Supplemental Install Manual
BACnet IP
Signal Type
BACnet IP
Recommended Cable
Address
Maximum Recommended Distance from NORTEC Humidifier
Transmission
Mode
Port
Node
ID
Device
Instance
LAN Standard
UDP
47808
Category 5 Ethernet Cable (CAT 5 or better) with RJ-45 termination
79*
12*
Depends on cable manufacturer, refer to BMS Supplier for recommendations
For BACnet IP networks, the recommended wire type is standard Category 5 Ethernet Cable (CAT 5) with RJ-45 terminations (Category 5E and category 6 cable are also acceptable). Refer to the BMS supplier for maximum recommended lengths of CAT5 cable.
Table 2: BACnet IP Parameters
*Default, may vary for multi-unit orders.
Wiring connections are made directly to the integrated controller circuit board. Figure 1:
Location of Integrated Controller Board shows the location of the board inside the NH-EL.
Figure 1: Location of Integrated Controller Board
BACnet & LONWORKS Supplemental Install Manual | 4
Figure 2: BACnet MS/TP and IP Connection Location show where the physical connections will
be made in order to interface with one of these BMS protocols. For information on Optional protocols, such as Lonworks or BTL certified BACnet, please see Options (Lonworks, BTL certified) for details.
Figure 2: BACnet MS/TP and IP Connection Location
Refer to , Figure 3: BACnet MS/TP Wiring Diagram and Figure 4: BACnet IP Wiring Diagram for instructions on making wiring connections for each respective protocol.
5 | BACnet & LONWORKS Supplemental Install Manual
J15
J1
J2J3
J6
J10
J12
J14
J19
J21
J23
J16
BACnet MS/TP Port
NET NET COMMON
(-)
()+
NH-EL BACnet MS/TP Connection
External wiring ‘by others’
RS-485 cable recommended:
-18-24 AWG stranded
-Twisted pair, Shielded
-120 Ohm impedance
-Terminate shield at one end only
Figure 3: BACnet MS/TP Wiring Diagram
BACnet & LONWORKS Supplemental Install Manual | 6
Figure 4: BACnet IP Wiring Diagram
7 | BACnet & LONWORKS Supplemental Install Manual
Addressing and Communication
BACnet IP
BACnet MSTP
Default IP addressing
IP Type: DHCP IP: 192.168.168.243 Subnet: 255.255.255.000 Gateway: 192.168.168.101
N/A Default BACnet Address
(MAC address)
79
79
Default BACnet Node ID (Device Instance)
12
1001
After wiring connections have been completed, the humidifier needs to be setup to operate and communicate through the BACnet interface.
BACnet Communication Set-up
The following table demonstrates the default addressing found on the NH-EL:
Table 3: BACnet Specific Defaults
Locating the IP addressing in the NH-EL is summarized as follows: Main Menu > 0335 > Configuration > Comms. Menu > Network Parameters >
Note: By default, the NH-EL will have BACnet disabled. To enable BACnet, select BACnet IP or BACnet MSTP under BACnet Parameters. Select the respective protocol and confirm the selection by pressing the Check Mark button. This action is summarized as follows:
Main Menu > 0335 > Configuration > Comms. Menu > BACnet Parameters >
Once BACnet is enabled, addressing can be modified as desired. Locating the BACnet Address (MAC address) in the NH-EL is summarized as follows:
Main Menu > 0335 > Configuration > Comms. Menu > BACnet Parameters > BACnet MSTP address
Locating the BACnet Node ID (Device Instance) in the NH-EL is summarized as follows: Main Menu > 0335 > Configuration > Comms. Menu > BACnet Parameters > Node ID
BACnet & LONWORKS Supplemental Install Manual | 8
Control Signal Setting
Source
Analog: Use hardwired control signal BACnet/IP: Write control signal through BACnet/IP interface BACnet/MS: Write control signal through BACnet/MS interface
Control Mode
Demand: Use a demand control signal RH P: Use a sensor value and proportional RH PI: Use a sensor value and proportional-integral control band
Control Channels
Single: Use a single channel control signal Dual: Use a dual channel control signal
By default the humidifier is configured to operate on a hardwired control signal supplied through the unit terminal strip. This can be changed to allow the humidifier to function entirely through its BACnet interface. *Note: the Humidifier Security loop will still need to be enabled for humidifier to run.
To adjust this setting:
1 Press the Menu icon on the lower left corner of the status screen, to access the menu. 2 When prompted for a password, enter 0335 using the number pad. Press the Check Mark
icon to confirm.
3 Select the Configuration menu. 4 Select the Control Settings menu. The following settings can be adjusted:
Table 4: Control Signal Parameters
Note: Refer to the CONTROL SETTING section of the NH-EL Installation and Operation Manual for more information on the above settings.
5 Press Back repeatedly to return to the home screen when complete.
This procedure is summarized below: Main Menu > 0335 > Configuration > Control Settings >
Source: Analog, BACnet/IP, BACnet/MS, Control Mode: Demand, RH P, or RH PI Control Channels: Single or Dual
9 | BACnet & LONWORKS Supplemental Install Manual
Control Mapping
Parameter Name
Description
BACnet
ID
Format
Range
Unit
R/W
Details
Dinput_A1
Write RH or Demand signal value to control channel 1 for cylinder A
10044
Integer
0 - 100
%
Write
Requires BACnet to be enabled.
For most common configurations, this is the primary control signal
Dinput_A2
Write RH or Demand signal value to control channel 2 for cylinder A
10045
Integer
0 - 100
%
Write
Requires BACnet to be enabled.
Dinput_B1
Write RH or Demand signal value to control channel 1 for cylinder B
10046
Integer
0 - 100
%
Write
Requires BACnet to be enabled.
Only applies to NH-EL-150 and NH-EL-200 with dual channel control enabled
Dinput_B2
Write RH or Demand signal value to control channel 2 for cylinder B
10047
Integer
0 - 100
%
Write
Requires BACnet to be enabled.
Only applies to NH-EL-150 and NH-EL-200 with cylinders dual channel control enabled and cylinders in independent operation mode
Manual_
Capcity_A
Sets a manual capacity limit restriction for cylinder A
10008
Integer
0 - 100
%
Write
Limits output to percentage of total cylinder capacity (for single cylinder) or for cylinder A (NH-EL­150 and NH-EL-200 models only)
Manual_
Capcity_B
Sets a manual capacity limit restriction for cylinder B (if present)
10027
Integer
0 - 100
%
Write
Limits output to percentage capacity for cylinder B (NH-EL­150 and NH-EL-200 models only)
BMS_
Timeout
BMS timeout
for Modbus and BACnet
10043
Integer
0 - 300
s
Write
It is recommend to not change the value from the factory default (300)
Remote_
Disable
Remotely disable steam production for the unit
25
Integer
0 or 1
-
Write
0 = Idle/Humidify 1 = Disabled
SP_Chan_ A1
Writes the desired space setpoint for control channel 1 for cylinder A
10010
Integer
0 - 95
%
Write
Use only when Control Mode (14) is set to RHp or RHpi
Use only when sending RH values to Dinput_A1.
For most common configurations this is the primary space setpoint.
Table 5: BACnet Object Definition List
BACnet & LONWORKS Supplemental Install Manual | 10
SP_Chan_ A2
Writes the desired space setpoint for control channel 2 for cylinder A
10013
Integer
10 - 95
%
Write
Use only when sending RH value to Dinput_A2 with dual channel control enabled
SP_Chan_ B1
Writes the desired space setpoint for control channel 1 for cylinder B
10016
Integer
0 - 95
%
Write
Use only with NH-EL-150 and NH­EL-200 models when sending RH value to Dinput_B1 and cylinders are in independent operation mode
SP_Chan_ B2
Writes the desired space setpoint for control channel 2 for cylinder B
10019
Integer
10 - 95
%
Write
Use only with NH-EL-150 and NH­EL-200 models when sending RH value to Dinput_B2 with dual channel control enabled and cylinders are in independent operation mode
Signal_
Source
Selects signal source to control unit
13
Integer
0 - 4
-
Write
0 = Analog
1 = Modbus
2 = BACnet/IP
3 = BACnet/MS
4 = LonWorks
Control_M ode
Selects method to control unit
14
Integer
1 - 3
-
Write
1 = Demand
2 = RH P
3 = RH PI
Control_
Channel
Selects method to control channels
15
Integer
0 - 1
-
Write
0 = Single Channel
1 = Dual Channel
Input_A1
Displays channel 1 demand for cylinder A
10001
Integer
0 - 100
%
Read
Displays channel 1 demand/sensed RH as a percentage of cylinder capacity for cylinder A
Input_A2
Displays channel 2 demand for cylinder A
10002
Integer
0 - 100
%
Read
Displays channel 2 demand/sensed RH as a percentage of cylinder capacity for cylinder A
Input_B1
Displays channel 1 demand for cylinder B
10003
Integer
0 - 100
%
Read
Displays channel 1 demand/sensed RH as a percentage of cylinder capacity for cylinder B (NH-EL-150 and NH-EL-200 models only)
Input_B2
Displays channel 2 demand for cylinder B
10004
Integer
0 - 100
%
Read
Displays channel 2 demand/sensed RH as a percentage of cylinder capacity for cylinder B (NH-EL-150 and NH-EL-200 models only)
Blower_ Pack_A
Reads the status of the blower pack for cylinder A
4
Integer
0 or 1
-
Read
0 = Open 1 = Closed
11 | BACnet & LONWORKS Supplemental Install Manual
Blower_ Pack_B
Reads the status of the blower pack for cylinder B
6
Integer
0 or 1
-
Read
0 = Open 1 = Closed
Fan_ Activate_A
Indicates if air handle or furnace is activated for cylinder A
1
Integer
0 or 1
-
Read
0 = Not Activated
1 = Activated
Fan_ Activate_B
Indicates if air handle or furnace is activated for cylinder B
2
Integer
0 or 1
-
Read
0 = Not Activated
1 = Activated Do_Fault_
A
Reads the status of a fault on the unit
69
Integer
0 or 1
-
Read
0 = No Fault
1 = Fault
Do_ Service_A
Reads the status of a service request on the unit
67
Integer
0 or 1
-
Read
0 = No Service Required
1 = Service Required
Humidifier _
Status_A
Reads the status of the unit for cylinder A
36
Integer
0 - 9
-
Read
0 = Humidifying
1 = Idle
2 = Idle Drain
3 = Keepwarm
4 = Filling
5 = Draining
6 = Disabled
7 = Safety Loop
8 = Warning
9 = Fault
10 = blower pack
Humidifier _
Status_B
Reads the status of the unit for cylinder A
57
Integer
0 - 9
-
Read
0 = Humidifying
1 = Idle
2 = Idle Drain
3 = Keepwarm
4 = Filling
5 = Draining
6 = Disabled
7 = Safety Loop
8 = Warning
9 = Fault
10 = blower pack
BACnet & LONWORKS Supplemental Install Manual | 12
System_
Demand_A
Reads the demand for cylinder A
10057
Integer
0 – 100
%
Read
Demand Mode:
Summation of Input_A1 and Input_A2
RH Mode:
PID calculation
System_
Demand_ B
Reads the demand for cylinder B
10058
Integer
0 – 100
%
Read
Demand Mode:
Summation of Input_B1 and Input_B2
RH Mode:
PID calculation
Safety_ Loop_A
Reads the status of the safety loop for cylinder A
3
Integer
0 or 1
-
Read
0 = Open
1 = Closed
Safety_ Loop_B
Reads the status of the safety loop for cylinder B
5
Integer
0 or 1
-
Read
0 = Open
1 = Closed
Run_Time _A
Reads operating time for cylinder A
10060
Integer
0 ­5000
Hrs
Read
Displays the total time cylinder A has been running since last reset
Run_Time _B
Reads operating time for cylinder B
10079
Integer
0 ­5000
Hrs
Read
Displays the total time cylinder B has been running since last reset
Weighted_
Hours_A
Reads the weighted time for cylinder A
10061
Integer
0 ­5000
Hrs
Read
An equated run time based on Run_Time_A x System_Demand_A
Weighted_
Hours_B
Reads the weighted time for cylinder B
10080
Integer
0 ­5000
Hrs
Read
An equated run time based on Run_Time_B x System_Demand_B
13 | BACnet & LONWORKS Supplemental Install Manual
Part Number
Kit Name
Kit Description
2574194
Lonworks, NH-EL
Factory installed option for Echelon’s LonWorks protocol
2574193
BACnet MSTP, BTL Certified, NH-EL
Factory installed option for BTL approved protocol for BACnet MSTP
2574192
BACnet IP, BTL Certified, NH-EL
Factory installed option for BTL approved protocol for BACnet IP
Part Number
Kit Name
Kit Description
2574197
Lonworks, NH-EL , Retrofit
Field install option for Echelon’s LonWorks protocol
2574196
BACnet MSTP, BTL , NH-EL Retrofit
Field install option for BTL approved protocol for BACnet MSTP
2574195
BACnet IP, BTL, NH-EL Retrofit
Field install option for BTL approved protocol for BACnet IP
1
Options (Lonworks, BTL Certified BACnet)
Nortec offers additional protocol options that may be purchased if required. Both field and factory installed versions are available and include Lonworks and BTL® (BACnet Testing Lab)1 certified BACnet. See Table #6 and Table #7 for specific part numbers and details.
Table 6: Optional Factory Installed Part Numbers
Table 7: Optional Field Install Part Numbers
Field Retrofit Installation
The kits consist of a single interface card that is mounted on the rear side of the integrated controller. Care should be taken with installation the optional unit in the field. Users will need to install the interface card onto the pins as shown in Figure 5: Mounting Location and Figure 6:
Pin Alignment. Figure 8: BACnet Specific Port and Figure 9: LonWorks Specific Port display the
location of each port for the respective protocol.
BTL is a registered trademark of BACnet International (BI)
BACnet & LONWORKS Supplemental Install Manual | 14
Figure 5: Mounting Location
Figure 6: Pin Alignment
15 | BACnet & LONWORKS Supplemental Install Manual
Figure 7: Installation complete
Figure 8: BACnet Specific Ports
Figure 9: LonWorks Specific Port
BACnet & LONWORKS Supplemental Install Manual | 16
Addressing and Communication
Source
Analog: Use hardwired control signal Modbus: Write control signal through BTL Certified BACnet Option LonWorks: Write control signal through LonWorks Option
Control Mode
Demand: Use a demand control signal RH P: Use a sensor value and proportional RH PI: Use a sensor value and proportional-integral control band
Control Channels
Single: Use a single channel control signal Dual: Use a dual channel control signal
After wiring connections have been completed, the humidifier needs to be setup to operate and communicate through the interface. The initial step is to configure the Control settings to ensure the humidifier points to the installed option.
Control Signal Setting
By default the humidifier is configured operate on a hardwired control signal supplied through the unit terminal strip. This can be changed to allow the humidifier to function entirely through its Optional interface.
To adjust this setting:
1 Press the Menu icon on the lower left corner of the screen, to access the menu. 2 When prompted for a password, enter 0335 using the number pad. Press the Check Mark
icon to confirm.
3 Select the Configuration menu. 4 Select the Control Settings menu. The following settings can be adjusted:
Table 8: BTL / Lonworks Control Signal Parameters
Note: Refer to the CONTROL SETTING section of the NH-EL Installation and Operation Manual for more information on the above settings.
5 Press Back repeatedly to return to the home screen when complete.
This procedure is summarized below: Main Menu > 0335 > Configuration > Control Settings >
Source: Analog, Modbus, LonWorks Control Mode: Demand, RH P, or RH PI Control Channels: Single or Dual
17 | BACnet & LONWORKS Supplemental Install Manual
Controller Set-up
The BACnet BTL or LonWorks options utilize an additional hardware component. Protocol configuration is completed at the factory, prior to final testing. It may be necessary to configure the address parameters in the field.
BACnet IP systems will require a static IP address to communicate on the network. BACnet MS/TP systems require both a device instance and a baud rate to be set. LonWorks systems automatically detect network address parameters and do not require configuration.
BTL Certified BACnet specific : Changing Unit Addressing
The BTL Certified BACnet options utilize an additional hardware component for translation. For address changes in either BACnet MS/TP or BACnet IP, the device instance and BACnet MAC address can be modified easily using the dip switches shown in Figure 10: Dipswitches on BTL
Certified BACnet.
Figure 10: Dipswitches on BTL Certified BACnet
These switches allow you to set a binary value between 1 and 127 inclusive. The methodology for converting numbers to binary is presented in Appendix A. To set the device instance to a value outside of this range, a specific web browser tool may be used to make IP and address modifications in the field, Contact Nortec Technical Services for further detail.
Take care when adjusting switches to ensure the settings are entered as intended. Common settings are tabulated in Appendix A. After an address change has been made, the humidifier must be power cycled for the change to take effect.
BACnet & LONWORKS Supplemental Install Manual | 18
Changing Baud Rate (BACnet MSTP Only)
The baud rate for communications can also be changed through the respective dip switches.
By adjusting the settings according to Appendix A, the baud rate can be changed. For best results it is recommended to set the baud rate to Auto (BACnet MSTP only), 9600, 19200, or
38400. Communication performance varies with building automation system manufacturer and some experimentation with other baud rates may be required to obtain the best performance. The Auto setting is currently only supported for BACnet MSTP networks.
BACnet Pics and Bibs
The Protocol Implementation Conformance Statement or “PICS” describes the BACnet
capabilities of a particular BACnet implementation. It is a written document, created by the manufacturer of a device, which identifies the particular options specified by BACnet that are implemented in the device.
BACnet Interoperability Building Blocks (BIBBs) describe a list of services a BACnet device provides. The main areas that the building blocks are concerned with include: data sharing, trends, schedules, device and system management. BIBBs help specify the interoperability capabilities of a BACnet device. Please contact the factory to obtain a PICS statement or BIBBs profile.
LonWorks Variables
LonWorks uses the identical set of variables/points as BACnet. For a detailed list of the variables, please see Appendix B.
To facilitate the integration of a LonWorks unit within a network, it may be desirable to obtain an External Interface File (XIF). Files of type .xif are used to convey the resources, specific objects and data types which a LonWorks device possesses. The .xif file allows a network integrator to simulate the presence of a networked humidifier even if it is not yet physically connected to the network. In fact, if the integrator has the .xif files of all network devices, a complete system could be simulated and configured off-line. Once the configuration is done, the integrator's software tool can be connected to the actual system and the configuration information can be downloaded.
The XIF file can be retrieved directly from the Optional Interface Card. A Windows based laptop and an Ethernet cable (CAT 5 or better) are required for this process. This process requires the “Remote User Interface” software tool from Fieldserver. It is available by visiting
http://fieldserver.com/techsupport/utility/utility.php and downloading the “Utility” software:
19 | BACnet & LONWORKS Supplemental Install Manual
Figure 11: Software Retrieval
Once this software has been installed, use the following procedure:
1. Locate desired humidifier. Ensure unit is powered on and remove the panel on the Front
side of the humidifier. Locate the Integrated Controller Board inside of the unit.
2. Connect one end of the CAT5 cable into the Ethernet port on the Optional Interface Card
directly.
3. Connect other end of CAT5 cable to the Ethernet port on the laptop.
4. Run the “Remote User Interface” utility by double clicking the shortcut on your desktop (or
Start>Programs>Fieldserver Utilities>Remote User Interface)
5. The program should automatically recognize connected humidifier and bring you to the
“Main Menu”. If it does not, contact Nortec Technical Services at the number on the back
cover of this manual.
6. Type “u” for upload.
7. Type “o” for other. (A warning will appear, press any key to continue.)
8. Type “r” for remote.
BACnet & LONWORKS Supplemental Install Manual | 20
9. Enter “fserver.xif”’ and hit the ‘enter’ key.
10. Type “u” to initiate upload from the humidifier to the laptop.
11. The .xif file will be saved in the folder “Configuration File Folder” located at
Start>Programs>Fieldserver Utilities>Configuration File Folder.
12. Type ‘q’ twice to exit out of the program
13. Locate file in Configuration File Folder and change name to corresponding humidifier, (ex,
“fserverH1.xif” for Humidifier 1)
14. Repeat this procedure for humidifiers changing the name of the .xif once saved to
correspond with the tag of the appropriate humidifier.
21 | BACnet & LONWORKS Supplemental Install Manual
Troubleshooting
Problem
Resolutions
Cannot see/change set object/parameter from BMS
Check control type. Demand type controls use internal algorithms to generate a signal telling the humidifier to operate at a certain output percentage. These of controls do not report the detected humidity level or set point to the humidifier. As a result the set point and space humidity levels cannot be monitored through the humidifier when using demand controls.
Sensor ("transducer") type controls report a sensed humidity value to the humidifier. The set point is configured at the humidifier and the humidifier uses internal algorithms to determine the output percentage. Since the humidifier knows both the set point and humidity level, these values may be monitored through the humidifier.
Cannot establish communication.
Check communication parameters. Nortec humidifiers are capable of BACnet MSTP and IP communication. LonWorks and BTL certified BACnet based systems require an interface card to translate the information, See Options for respective part numbers. Verify Hardware connections from BMS to humidifier as per the installation chapter. Confirm that the protocol has been activated in the humidifier software: main menu>0335>configuration>Comms menu> BACnet MSTP Specific: Check baud rate . Modifying bps may be necessary for some BMS networks. Ensure BACnet Workstation/BAS can handle BACnet slave devices
Cannot read data from object/parameter
Carefully ensure that addresses are mapped correctly. A single incorrect address may cause loss of communication or faults for an entire chain of humidifiers.
Check data type, some network controllers default to integer or binary values depending on variable type.
Only some objects/parameters report data.
Check the baud rate being used on the BMS network. Use of faster baud rates may assist. Check the polling rate being used. High polling rates can interrupt responses from the previous poll of data causing incomplete data transfer. A recommended polling rate is once per minute.
Humidifier will not respond to set point/sensor values/ demand values written over BACnet/LonWorks.
Check that humidifier is configured for automation system. Refer to the "Control Signal Settings" section for your humidifier model. If the setting is "Analog" the humidifier will look for a control signal on the low voltage terminal strip only.
Table 9: General Troubleshooting
BACnet & LONWORKS Supplemental Install Manual | 22
Humidifier will not respond to hardwired controls.
Check that humidifier is configured for "Analog" control. Refer to the "Control Signal Settings" section for your humidifier model. If the setting is "BACnet" or other, the humidifier will look for a control value to be written over that medium.
Intermittent Communications
Check wire type and run length. Wire type should be 18 – 24 AWG, shielded twisted pair wire with 120 ohm characteristic impedance. Chains should generally not exceed 2000 feet total length.
Look for wire runs in close proximity to equipment generating significant electrical noise (such as VFD's, medical equipment, X-ray machinery, servers, etc).
Check that wire shield is terminated at one end only. Terminations at both ends cause shield to conduct electricity and can generate noise.
Confirm correct polarity of conductors at each device. This problem can be the result of Net+ and Net- terminals being crossed.
Check BACnet Device Instance, LonWorks addressing for conflicts with any device. Each device on the network must have a unique address. Devices (humidifiers or otherwise) cannot share addresses.
Invalid data
Check BACnet/LonWorks addresses for conflicts. Each device on the network must have a unique address. Devices (humidifiers or otherwise) cannot share addresses.
More variables or additional information is required from the humidifier.
Contact Nortec Technical Services for additional support.
BACnet MSTP: Cannot pass data to controller. Humidifier does not pass token
Isolate chain and try only Humidifier. Embedded BACnet MSTP functions as a slave device and cannot be setup as a Master. Ensure BACnet Workstation/BAS can handle BACnet slave devices. If not possible, consider the BTL option for BACnet MSTP if problem persists. BTL option for BACnet MSTP will function as a Master device.
23 | BACnet & LONWORKS Supplemental Install Manual
APPENDIX A
Switch
A8
A7
A6
A5
A4
A3
A2
A1
Setting
Off
On
Off
Off
On
On
On
Off
Binary 0 1 0 0 1 1 1 0
Exponential Meaning
27 x 0
26 x 1
25 x 0
24 x 0
23 x 1
22 x 1
21 x 1
20 x 0
Simplified Meaning
128 x 0
64 x 1
32 x 0
16 x 0
8 x 1
4 x 1
2 x 1
1 x 0
Numerical Meaning
0
64 0 0 8 4 2 0
Result
64 + 8 + 4 + 2 = 78
Value
A8
A7
A6
A5
A4
A3
A2
A1
0 (Auto)*
Off
Off
Off
Off
Off
Off
Off
Off 1 Off
Off
Off
Off
Off
Off
Off
On
10
Off
Off
Off
Off
On
Off
On
Off
25
Off
Off
Off
On
On
Off
Off
On
40
Off
Off
On
Off
On
Off
Off
Off
50
Off
Off
On
On
Off
Off
On
Off
75
Off
On
Off
Off
On
Off
On
On
78
Off
On
Off
Off
On
On
On
Off
100
Off
On
On
Off
Off
Off
On
Off
125
Off
On
On
On
On
On
Off
On
127
Off
On
On
On
On
On
On
On
Table 10: Converting Numbers to Binary
Table 11: Common Settings for Addressing - BTL BACnet MSTP
* Auto uses the value in the configuration file.
BACnet & LONWORKS Supplemental Install Manual | 24
Table 12: Common Settings – Baud rate BTL BACnet MS/TP
Setting
B4
B3
B2
B1
Auto*
Off
Off
Off
Off
110
Off
Off
Off
On
300
Off
Off
On
Off
600
Off
Off
On
On
1200
Off
On
Off
Off
2400
Off
On
Off
On
4800
Off
On
On
Off
9600
Off
On
On
On
19200
On
Off
Off
Off
20833
On
Off
Off
On
28800
On
Off
On
Off
38400
On
Off
On
On
57600
On
On
Off
Off
76800
On
On
Off
On
115200
On
On
On
Off
* Auto baud is only supported for BACnet MSTP
25 | BACnet & LONWORKS Supplemental Install Manual
APPENDIX B
Parameter Name
Description
SNVT
#
SNVT
Range
NV
Index
R/W
Details
nviDRHDem_A1
Write RH or Demand signal value to control channel 1 for cylinder A
81
Lev_percent
0 - 100
23
W
Requires LonWorks to be enabled. For most common configurations, this is the primary control signal
nviDRHDem_A2
Write RH or Demand signal value to control channel 2 for cylinder A
81
Lev_percent
0 - 100
24
W
Requires LonWorks to be enabled.
nviDRHDem_B1
Write RH or Demand signal value to control channel 1 for cylinder B
81
Lev_percent
0 - 100
33
W
Requires LonWorks to be enabled. Only applies to NH­EL-150 and NH-EL­200 with dual channel control enabled
nviDRHDem_B2
Write RH or Demand signal value to control channel 2 for cylinder B
81
Lev_percent
0 - 100
34
W
Requires LonWorks to be enabled. Only applies to NH­EL-150 and NH-EL­200 with cylinders dual channel control enabled and cylinders in independent operation mode
nviManCapacity_A
Sets a manual capacity limit restriction for cylinder A
81
Lev_percent
0 - 100
15
W
Limits output to percentage of total cylinder capacity (for single cylinder) or for cylinder A (NH-EL-150 and NH-EL-200 models only)
nviManCapacity_B
Sets a manual capacity limit restriction for cylinder B (if present)
81
Lev_percent
0 - 100
30
W
Limits output to percentage capacity for cylinder B (NH­EL-150 and NH-EL­200 models only)
nviBMStimeout
BMS timeout for Modbus and BACnet
107
SNVT_time_ sec
0 - 300
5
W
It is recommend to not change the value from the factory default (300)
nviDisable
Remotely disable steam production for the unit
95
Switch
0 or 1
44
W
0 = Idle/Humidify 1 = Disabled
Table 13: Parameters
BACnet & LONWORKS Supplemental Install Manual | 26
nviSetPoint_A1
Writes the desired space setpoint for control channel 1 for cylinder A
81
Lev_percent
0 - 95
21
W
Use only when sending RH values to Dinput_A1. Use only when nviCtrlMode (3) is set to RHp or RHpi For most common configurations this is the primary space setpoint
nviSetPoint_A2
Writes the desired space setpoint for control channel 2 for cylinder A
81
Lev_percent
10 - 95
22
W
Use only when sending RH value to Dinput_A2 with dual channel control enabled
nviSetPoint_B1
Writes the desired space setpoint for control channel 1 for cylinder B
81
Lev_percent
0 - 95
36
W
Use only with NH­EL-150 and NH-EL­200 models when sending RH value to Dinput_B1 and cylinders are in independent operation mode
nviSetPoint_B2
Writes the desired space setpoint for control channel 2 for cylinder B
81
Lev_percent
10 - 95
37
W
Use only with NH­EL-150 and NH-EL­200 models when sending RH value to Dinput_B2 with dual channel control enabled and cylinders are in independent operation mode
nviSigSource
Selects signal source to control unit
81
Lev_percent
0 - 4
2
W
0 = Analog 1 = Modbus 2 = BACnet/IP 3 = BACnet/MS 4 = LonWorks
nviCtrlMode
Selects method to control unit
81
Lev_percent
1 - 3
3
W
1 = Demand 2 = RH P 3 = RH PI
nviCtrlChannel
Selects method to control channels
81
Lev_percent
0 - 1
4
W
0 = Single Channel 1 = Dual Channel
nvoRHDem_A1
Displays channel 1 demand for cylinder A
81
Lev_percent
0 - 100
12
R
Displays channel 1 demand/sensed RH as a percentage of cylinder capacity for cylinder A
nvoRHDem_A2
Displays channel 2 demand for cylinder A
81
Lev_percent
0 - 100
13
R
Displays channel 2 demand/sensed RH as a percentage of cylinder capacity for cylinder A
nvoRHDem_B1
Displays channel 1 demand for cylinder B
81
Lev_percent
0 - 100
27
R
Displays channel 1 demand/sensed RH as a percentage of cylinder capacity for cylinder B (NH-EL­150 and NH-EL-200 models only)
27 | BACnet & LONWORKS Supplemental Install Manual
nvoRHDem_B2
Displays channel 2 demand for cylinder B
81
Lev_percent
0 - 100
28
R
Displays channel 2 demand/sensed RH as a percentage of cylinder capacity for cylinder B (NH-EL­150 and NH-EL-200 models only)
nvoBlowerAct_A
Reads the status of the blower pack for cylinder A
95
Switch
0 or 1
46
R
0 = Open 1 = Closed
nvoBlowerAct_B
Reads the status of the blower pack for cylinder B
95
Switch
0 or 1
49
R
0 = Open 1 = Closed
nvoFanAct_A
Indicates if air handle or furnace is activated for cylinder A
95
Switch
0 or 1
47
R
0 = Not Activated 1 = Activated
nvoFanAct_B
Indicates if air handle or furnace is activated for cylinder B
95
Switch
0 or 1
50
R
0 = Not Activated 1 = Activated
nvoFault
Reads the status of a fault on the unit
95
Switch
0 or 1
42
R
0 = No Fault 1 = Fault
nvoService
Reads the status of a service request on the unit
95
Switch
0 or 1
41
R
0 = No Service Required 1 = Service Required
nvoStatusCylA
Reads the status of the unit for cylinder A
81
Lev_percent
0 - 9
1
R
0 = Humidifying 1 = Idle 2 = Idle Drain 3 = Keepwarm 4 = Filling 5 = Draining 6 = Disabled 7 = Safety Loop 8 = Warning 9 = Fault 10 = blower pack
nvoStatusCylB
Reads the status of the unit for cylinder B
95
Switch
0 - 9
N/A
R
0 = Humidifying 1 = Idle 2 = Idle Drain 3 = Keepwarm 4 = Filling 5 = Draining 6 = Disabled 7 = Safety Loop 8 = Warning 9 = Fault 10 = blower pack
nvoSysDem_A
Reads the demand for cylinder A
81
Lev_percent
0 –
100
14
R
Demand Mode: Summation of Input_A1 and Input_A2 RH Mode: PID calculation
BACnet & LONWORKS Supplemental Install Manual | 28
nvoSysDem_B
Reads the demand for cylinder B
81
Lev_percent
0 –
100
29
R
Demand Mode: Summation of Input_B1 and Input_B2 RH Mode: PID calculation
nvoSecurity_A
Reads the status of the safety loop for cylinder A
95
Switch
0 or 1
45
R
0 = Open 1 = Closed
nvoSecurity_B
Reads the status of the safety loop for cylinder B
95
Switch
0 or 1
48
R
0 = Open 1 = Closed
nvoHourOpt_A
Reads operating time for cylinder A
124
SNVT_time_ hour
0 -
5000
10
R
Displays the total time (hrs) cylinder A has been running since last reset
nvoHourOpt_B
Reads operating time for cylinder B
124
SNVT_time_ hour
0 -
5000
25
R
Displays the total time (hrs) cylinder B has been running since last reset
nvoHourWeight_A
Reads the weighted time for cylinder A
124
SNVT_time_ hour
0 -
5000
11
R
An equated run time (hrs) based on Run_Time_A x System_Demand_A
nvoHourWeight_B
Reads the weighted time for cylinder B
124
SNVT_time_ hour
0 -
5000
26
R
An equated run time (hrs) based on Run_Time_B x System_Demand_B
29 | BACnet & LONWORKS Supplemental Install Manual
Warranty
Nortec Humidity Inc. and/or Nortec Humidity Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years after installation or 30 months from
manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and
assembled products, not otherwise expressly warranted (with the exception of the cylinder), are free from defects in material and workmanship. No warranty is made against corrosion, deterioration, or suitability of substituted materials used as a result of compliance with government regulations.
THE COMPANY’s obligations and liabilities under this warranty are limited to furnishing replacement parts to the customer, F.O.B. THE COMPANY’s factory, providing the defective
part(s) is returned freight prepaid by the customer. Parts used for repairs are warranted for the balance of the term of the warranty on the original humidifier or 90 days, whichever is longer.
The warranties set forth herein are in lieu of all other warranties expressed or implied by law. No liability whatsoever shall be attached to THE COMPANY until said products have been paid for in full and then said liability shall be limited to the original purchase price for the product. Any further warranty must be in writing, signed by an officer of THE COMPANY.
THE COMPANY’s limited warranty on accessories, not of the companies manufacture, such as controls, humidistats, pumps, etc. is limited to the warranty of the original equipment manufacturer from date of original shipment of humidifier.
THE COMPANY makes no warranty and assumes no liability unless the equipment is installed in strict accordance with a copy of the catalog and installation manual in effect at the date of purchase and by a contractor approved by THE COMPANY to install such equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for consequential damage or damage resulting directly from misapplication, incorrect sizing or lack of proper maintenance of the equipment.
THE COMPANY makes no warranty and assumes no liability whatsoever for damage resulting from freezing of the humidifier, supply lines, drain lines, or steam distribution systems.
THE COMPANY retains the right to change the design, specification and performance criteria of its products without notice or obligation.
BACnet & LONWORKS Supplemental Install Manual | 30
U.S.A.
826 Proctor Avenue Ogdensburg, NY 13669
CANADA
2740 Fenton Road Ottawa, Ontario K1T 3T7
TEL: 1.866.NORTEC1 FAX: 613.822.7964
EMAIL: nortec@humidity.com WEBSITE: www.humidity.com
Loading...