Nortec 132-3091 User Manual

NH Electrode Steam Humidifiers
Installation,
Operation, and
Maintenance Guide
IMPORTANT: Read and save these instructions. This guide to be left with equipment owner.
Form #03-172 1506262
INSTALLATION 1
RECEIVING & UNPACKING EQUIPMENT ................................1
PRE-INSTALLATION CHECKPOINT ...................................1
BASIC HUMIDIFIER CONFIGURATION..................................1
LOCATION & MOUNTING .........................................2
HUMIDIFIERS ...............................................2
BLOWER PACKS .............................................2
STEAM DISTRIBUTORS..........................................3
PLUMBING .................................................3
WATER SUPPLY LINE...........................................3
DRAIN LINE ................................................3
STEAM LINE AND CONDENSATE RETURN LINE ............................4
ACCESSORIES - FILL CUP EXTENSION KIT(S) .............................4
ELECTRICAL................................................4
PRIMARY VOLTAGE SUPPLY WIRING TO HUMIDIFIER ........................4
LOW VOLTAGE CONTROL WIRING ...................................5
On-Off Controls.............................................5
CONTROL INSTALLATION ........................................5
OPTIONAL MODULATION (CONTINUOUS CONTROLS) ........................5
OPTIONAL MODULATION (CONTINUOUS CONTROL) PACKAGES BY NORTEC ...........7
OPERATION 7
INTRODUCTION ..............................................7
LAYOUT AND FUNCTION .........................................7
NHMC OPERATION ............................................8
START-UP SELF TEST ..........................................8
USER LEVEL................................................9
INFORMING THE USER ..........................................9
SELF-HELP ................................................9
SYSTEM MESSAGES ...........................................9
REMOTE INDICATION...........................................9
DOUBLE UNIT OPERATION .......................................9
NHB/NHP OPERATION ..........................................9
END OF CYLINDER LIFE .........................................9
MANUAL CAPACITY ADJUSTMENT...................................10
OTHER POTENTIOMETERS.......................................10
DETECTING WATER SUPPLY DEFICIENCY ..............................10
REMOTE INDICATION ..........................................10
DOUBLE UNIT OPERATION .......................................10
BLOWER PACK OPERATION ......................................10
MAINTENANCE 10
WHEN TO REPLACE THE STEAM CYLINDER .............................10
HOW TO REMOVE THE STEAM CYLINDER ..............................13
MANDATORY CLEANING OF THE DRAIN VALVE ...........................13
HOW TO INSTALL THE REPLACEMENT CYLINDER ..........................14
BUILT ON AND REMOTE MOUNTED BLOWER PACKS (BOBP’S / RMBP’S) .............15
TROUBLESHOOTING 15
STARTING POINT ............................................15
USING THE WIRING DIAGRAM .....................................21
TERMS USED ..............................................22
WIRING DIAGRAM ..........................................23-25
PRE START-UP CHECKLIST ......................................26
START-UP CHECKLIST AND QUICK REFERENCE...........................27
MAINTENANCE CHECKLIST .....................................28-29
REPLACEMENT PARTS .......................................30-35
INSTALLATION
pply
3. Report any discrepancy immediately.
RECEIVING & UNPACKING EQUIPMENT
1. Check packing slip to ensure ALL material has been delivered.
2. All material shortages are to be reported to NORTEC within 48 hours from receipt of goods. NORTEC assumes no responsibility for any material shortages beyond this period.
3. Inspect shipping boxes for damage and note on shipping waybill accordingly.
4. After unpacking, inspect equipment for damage and if damage is found, notify the shipper promptly.
5. All NORTEC products are shipped on an F.O.B. factory basis. Any and all damage, breakage or loss claims are to be made directly to the shipping company.
PRE-INSTALLATION CHECKPOINT
1. Ensure that available voltage and phase corresponds with humidifier voltage and phase as indicated on humidifier’s nameplate label (see Figure #1).
2. Ensure that the dedicated external disconnect is of sufficient size to handle the rated amps as indicated on the nameplate label. Refer to local codes.
BASIC HUMIDIFIER CONFIGURATION
NORTEC humidifier models NHMC, NHP and NHB share a modular sheet metal cabinet. Each unit has a right side electrical compartment. Each electrical compartment has a hinge-down front door which is removable from any partially or fully opened position. Each electrical compartment has a screw-mounted right side cover which can also be removed for ease of electrical connection. For safety, the door when closed keeps the side cover from being removed.
Single units have a plumbing compartment attached to the left side of the electrical. Double units have a second plumbing compartment. Each plumbing compartment has a hinge-down front door which is not intended to be removed. For safety, the door must be closed in order to engage the shared lock. To avoid any danger, never operate the humidifier with a door off. For safety, each door when closed engages its own safety interlock switch. All switches must be engaged before the unit will operate.
To open the doors, unlock key, lift door up slightly and pull top of door forward. Door will hinge 180 degrees and hang straight down. To remove door, swing door parallel to floor. Then lift up slightly and out. To reinstall door, hold parallel to floor and insert hinge pins at bottom.
Condensate
Return
Figure #1
NH Series Humidifier
Steam Outlet
Drain
Nameplate Label
Water Su
Power And Control Wiring
Clearance Requirements
WALL
WITHOUT BLOWER PACK
TOP VIEW
NOTE: LOCAL AND NATIONAL CODES MAY DEVIATE. PLEASE CONSULT APPLICABLE CODES FOR CLEARANCE REQUIREMENTS IN ALL CASES.
Figure #2
MIN. 36" FRONTAL CLEARANCE.
MIN. 36"SIDE CLEARANCE RECOMMENDED. SEE NOTE.
-1-
LOCATION & MOUNTING
g
HUMIDIFIERS
NH Series humidifiers are designed to mount on a suitable wall or vertical surface. Do not sit on floor due to clearances required for plumbing, electrical, and control entrances. The clearance dimensions shown in this manual are for reference only and are the minimum required for maintenance of the humidifier. Local and National Codes should be consulted prior to final location and installation of the humidifier. NORTEC can not accept responsibility for installation code violations.
1. Location of the humidifier should be below and as
close as possible to the steam distributor location
as possible.
2. For front and side clearance requirements (for
access during installation, maintenance and
troubleshooting), see Figure #2.
3. If possible, DO NOT locate humidifier any further
than absolutely necessary from steam distributor
location, as net output will be reduced as a result
of heat loss through steam hose (see Engineering
Manual, Form -163D). Also, increased static
pressure may necessitate using an accessory fill
cup extension kit.
4. Where possible, mount humidifier at a height
convenient for servicing.
5. Wall mounting bracket provided should be
securely attached horizontally and open edge
upwards, using field-supplied fasteners. Use a
minimum of 3 - #12 x 3" long wood screws, or
Figure #3
Wall Bracket Mounting Detail
WALL
Wall
better, into a vertical structural surface. If any spacer material is used between the bracket and the structural material such as drywall, increase fastener length accordingly. In addition, install a minimum of 2 field supplied fasteners in the holes provided in the back of the unit to prevent the unit from being bumped off the wall bracket. See Figure #3.
6. Make sure humidifier is level.
7. DO NOT mount humidifier on hot surfaces.
8. If humidifiers are mounted on roof, a
thermostatically ventilated weatherproof cabinet by others should be used. Consult factory.
9. DO NOT mount humidifiers in an area where freezing may occur. Use an accessory Low Temperature Protection Kit, if necessary.
10. DO NOT mount humidifiers on vibrating surface. Consult factory.
BLOWER PACKS
1. Blower packs are an optional accessory used to directly distribute steam to localized areas (such as computer rooms) or in structures that do not have a built-in air distribution system.
2. Blower packs are available integrally-mounted on humidifier (built-on blower pack, BOBP, see Figure #4) or detached and field-piped and wired to humidifier (remote mounted blower pack RMBP, see Figure #5).
Figure #4
Built On Blower Pack (BOBP)
Optional Built-On Blower Pack
Single Circuit Humidifier
Built-In Supply Air Grille
Built-In Steam Distributor
Fasten wall bracket
FASTEN WALL BRACKET (FACTORY SUPPLIED) TO
(Factory supplied) to
WALL USING ANCHOR BOLTS
wall using field supplied
(3) SUPPLIED BY OTHERS
fasteners.
005-030
7.7 (19.6cm)
050-200
7.7 (19.6cm)A
7.7”
A
(19.6 cm)
3. All NH Series blower packs consist of a steel cabinet containing: blower/motor powered by voltage directly from the humidifier, fuse, relay, speed select switch (in NH-050 and larger), stainless steel steam distributor, supply air grille with adjustable louvers, and built-in manual reset
-2-
Power And Control Wirin
Wall
Figure #5
)
Remote Mounted Blower Packs (RMBP)
Side
050-100
3.2" (8.0cm)
Condensate
Front
Steam
A
Power and control wiring from humidifier
005-030
3.2" (8.0cm)
safety thermostat to turn off the humidifier if the blower pack gets overheated. Control thermostat, mounted on the steam distributor, starts the fan when steam is generated. When supply voltage differs from voltage required to run blower motor, blower pack will contain a proper transformer. All blower packs provide intake air filters.
For installation details about the blower pack, please refer to the blower pack installation manual located in the blower pack box (Form #XX-239).
WATER SUPPLY LINE
1. Humidifier is intended to operate on potable (cold)
tap water.
2. If the raw water is very hard, NORTEC can
A
provide longer cylinder life on softened water. However, softened water is more conductive and more corrosive. Some hardware and/or software changes may be required, at time of order or in the field. Consult factory.
3. If RO or DI is available, blending may increase
cylinder life. Consult factory.
4. DO NOT use a hot water supply to humidifier.
Minerals will adhere more easily to surfaces and the fill valve’s small flow regulating orifice and could become plugged.
5. Standard fill valves are sized for water pressure
ranging from 30 to 80 psig (ideally 55 to 60 psig). For other pressures, consult factory. This pressure should be measured at the humidifier if the water pressure is suspect.
6. ALWAYS supply and install a shut off valve in the
water supply line dedicated to the humidifier to facilitate servicing. Use ½" OD copper to within 4 feet of the humidifier. Reduce copper to 3/8" OD and connect to the factory-supplied 3/8" olive compression fitting under the humidifier.
DRAIN LINE
STEAM DISTRIBUTORS
1. Steam distributors are used in ducts or air handling units, and are made of stainless steel.
2. Steam distributors can be in vertical or downflow applications.
3. Proper location should consider: air temperature, relative humidity before the distributor, air velocity, dimensions of the location, amount of steam introduced into the duct, downstream obstructions, and surfaces vulnerable.
4. For installation details, please refer to steam distributor installation manual located in the distributor box (Form #XX-231).
5. For calculating absorption distances, refer to H.E.L.P. Software or steam distribution and absorption distances engineering manul (Form #XX-232).
PLUMBING
All water supply and drain line connections
should be installed in accordance with local plumbing codes.
1. Humidifier is equipped with a 7/8" O.D. unthreaded drain outlet on underside of drain canal on bottom of the humidifier (see Figure #6). A field-supplied funnel (see Figure #7) is recommended. It will prevent backup in the drain pan and in the cylinder due to partially blocked or badly installed drain lines. This prevents rusting of the drain pan and arcing due to over-concentration. The drain canal
Figure #6
Drain Line Connection
A
B
Model 005 -030 050 -100
150 -200 Left
150 -200 Right
Bottom View
Ain.(mm)
1.0 (25)
2.2 (55)
2.2 (55)
2.2 (55)
B in.(mm)
5.0 (127)
6.2 (158)
6.2 (158)
19.6(498
Wall
-3-
has been improved to prevent backup despite long
e
A
or gently sloped drain lines but it can not compensate for flat or uphill runs.
2. The drain line should not end in a sink used frequently by personnel, or where plumbing codes prohibit it. Route to a floor drain or equivalent for safety reasons, since drain water from humidifier can be very hot.
3. Keep drain lines as short as possible. Keep drain lines sloped down, not level and not up since low spots in drain lines will accumulate sediment and cause backup. The drain line
should be 7/8" O.D. copper pipe or larger. Do not use plastic pipe for drain lines. Consult factory.
Figure #7
Drain Connection
ClampAnd
1.5” I.D.Hose
ir Gap
NOTE: Steam hose should not reach bottom of the funnel.
Factory Supplied
Stainlesssteel Reducer To ServeAs Funnel Drain (ByOthers)
2" O.D. StainlessSteel Pipe Or 2" I.D.DI Compatible Hos (Not Supplied)
4. To increase allowable water column (allowable positive static pressure) an accessory Fill Cup Extension Kit is available from NORTEC. See Figure #8.
Figure #8
Fill Cup Extension Kit to Overcome Static Pressure
Fill Cup Bracket
Fill Cup
Overflow Hose
Fill Hose To Cylinder
Hose From FillValve
5. Water column requirements are even higher duct static pressure when distributor’s steam outlets are faced with downflow duct applications.
ELECTRICAL
PRIMARY VOLTAGE SUPPLY WIRING TO HUMIDIFIER
STEAM LINE AND CONDENSATE RETURN LINE
1. Check and ensure that available voltage and phase corresponds with operating voltage and
1. Refer to the installation manual of the steam distribution system used in your application.
phase of humidifier as indicated on the humidifier nameplate label (see Figure #1).
Steam Distribution - Form #XX-231, SAM-e - Form #XX-249, Blower Pack - Form #XX-239.
2. Ensure that an adequate power supply is available to carry full humidifier amperage drawn as
ACCESSORIES - FILL CUP EXTENSION KIT(S)
1. The NH Series humidifier is an electrode humidifier. It produces steam at atmospheric pressure. Pressure head must develop to push steam through supply line and into air duct.
2. Combined resistance of duct positive static pressure and steam line resistance creates a small pressure head in steam cylinder. Total amount of positive static pressure head is reflected directly by water column differential that develops between water in the fill cup hose feeding cylinder and water level in cylinder.
3. Standard dimensions of humidifier limit static that can be tolerated before water will be pushed high enough to spill over into overflow tube in fill cup assembly.
specified by rated amps on the humidifier nameplate label refer to local codes.
3. A dedicated external disconnect must be installed. Do not exceed the maximum circuit protection amps as indicated on the nameplate label.
4. Optional internal primary fuses are not intended to substitute for external fuses. Internal primary fuses are a factory added option (when specified) to protect internal primary wires individually.
5. Connect ground wire to cabinet ground clamp. Do not use neutral wire of four wire supply as ground.
6. Single phase humidifiers may be run on three phase power, but load may unbalance power grid.
7. External wiring sizes must be in accordance with NEC and/or CEC and existing local electrical codes and by-laws.
-4-
LOW VOLTAGE CONTROL WIRING
On-Off Controls
Figure #9
External Wiring of On/Off Controls
A B C
4. Each humidifier is supplied with a wiring diagram
inside.
CONTROL INSTALLATION
1. Mount any wall humidistat (control or high limit)
over standard electrical box at height similar to typical thermostat. Any wall humidistat should be in location representative of overall space being humidified and not in path of blower pack or air supply grille. Do not mount on a outside wall where temperature fluctuation can affect control response.
EXTERNAL
810
INTERNAL
Controls are available from NORTEC as accessories. If controls were not ordered with humidifier, they must be purchased supplied by others. The following information is relevant to all controls, factory supplied or otherwise.
A, B and C (described below) are to be wired in series (only one path for current) across terminals 8 and 10 on the low voltage control terminal strip, or replaced with a jumper wire for constant operation. Caution: this is the “hot” wire from the 24V control transformer; it will blow the 3A fuse if any control field wiring touches ground metal.
A - Wall or Duct Mounted Control On/Off Humidistat: Wired to make on drop in humidity, break
on rise to setpoint. Set to desired % RH. Can be a make/break set of contacts from a Building Automation System.
B - Duct Mounted Safety High Limit On/Off Humidistat (if used): Wired to make on drop in
humidity, break on rise to safety setpoint. Set to approximately 85% RH as a safety to help prevent saturation and wetting in the duct.
C - Duct Mounted Safety Air-Proving On/Off Switch (if used): Wired to make when sensing air
flow, break when no air flow. Used as a safety to prevent saturation when no air flow.
1. NORTEC offers various versions of A, B and C to
suit each application. In general, A is essential,
whereas B and C are highly recommended in
ducted applications.
2. Field wiring from humidistat to humidifier and
between devices should be 18 AWG or heavier
and kept as short as possible.
3. Low voltage control terminal strips are provided in
the electrical compartment. Internal sides are
factory wired. External sides are to be field wired.
2. Mount duct humidistat in location representative of overall air humidity, usually return duct. Do not mount it directly in front of steam distributor or in turbulent or mixing zone. Mount it where air’s humidity and temperature are uniform and representative of spaces being humidified.
3. Mount duct high limit humidistat downstream of steam distributors far enough that, under normal humidity and air flow conditions, steam will have been fully absorbed (typically at least 10 feet). It must be located to sense high humidity only when uniform and representative air is over-humidified or approaching saturation.
4. Mount duct air-proving switch so that it is able to sense air flow or lack of it. Wire it to make when air flow is sensed and break when air flow fails.
5. Check operation of all on/off controls before starting humidifier.
6. Calibration of controls (on/off or modulation) in the field may be necessary due to shipping and handling. Verify humidistat accuracy before commissioning system.
OPTIONAL MODULATION (CONTINUOUS CONTROLS)
1. Read on/off controls section first since it is necessary to all control systems.
2. Virtually any modulation (continuous control) external hardware by others (as long as it has %RH setpoint circuitry) may be interfaced with pre-specified factory-configured NHMC/NHP Series pc board via the control terminal strip. The NHB can be used with on-off control only. Use shielded cables for modulation circuits.
3. Modulation (continuous control) by others for use with NHMC/NHP Series humidifiers involves one of several control wiring diagrams. In all cases, modulating signal interfaces through control terminal strip to main pc board inside humidifier.
4. The modulation signal must increase from minimum toward maximum as sensed RH (actual RH) drops below desired RH (%RH setpoint). In response, humidifier’s steam output will increase from minimum toward maximum. When humidifier’s steam output (lbs/hr) matches humidification load (lbs/hr), modulation signal will stabilize.
-5-
l
l
l
(ACTUAL)
Figure #10
Primary Voltage Supply Wiring
PRIMARY (LINE) VOLTAGE WIRING TO UNITVOLTAGE
(BY OTHERS)
L1
L2
- Single Phase Unit.
- Single Phase Supply.
- Required Voltage Between L1 And L2.
- Load Balanced.
L1
L2
L3
Neutral
L1
L2
L3
Neutral
Ground
Ground
- Single Phase Unit.
- 3 Phase Supply.
- Required Voltage Between L1 And L2.
- Load Will Be Unbalanced.
Ground
- Single Phase Unit.
- 3 Phase Supply.
- Required Voltage Between L1 And Neutral.
- Load Will Be Unbalanced.
Ground Wire
Dedicated
Disconnect
Ground Wire
Dedicated
Disconnect
Ground Wire
Dedicated
Disconnect
Circuit
Breaker
Or
Circuit
Breaker
Or
Circuit
Breaker
Or
Ground Leg
2 Pole Termina Block
E
I
X
N
T
T
Ground Leg
2 Pole Termina Block
E
I
X
N
T
T
Ground Leg
2 Pole Termina Block
E
I
X
N
T
T
Ground Wire
L1
L2
L3
Neutral
Ground
Dedicated
Circuit
Breaker
Or
Disconnect
- 3 Phase Unit.
- 3 Phase Supply.
- Required Voltage Between Any Two Legs.
- Load Will Be Balanced.
NOTE: VoltageAt TerminalBlockMust Be InAccordance WithSpec.Label. All Wiring ToBeInAccordance With Existing NationalAnd LocalElectrical Codes.
-6-
Ground Leg
3 Pole Terminal
Block
E
I
X
N
T
T
5. Field-wiring connections for modulation control are to be made to external side of terminals 26, 28, 30 and 32 on humidifier’s control terminal strip. Always refer to the external control’s wiring diagram factory supplied with each NORTEC modulation control option.
6. Varying dc Voltage Modulation Signal Powered by Others: NHMC/NHP Series humidifier can be
factory configured to accept the following vdc signals: 0-3 vdc, 0-10 vdc, 0-16 vdc, 0-20 vdc, 1-5 vdc or 2-10 vdc. Wire according to NORTEC supplied external wiring diagram that comes with each modulation option. To share the signal with more than one humidifier, wire in parallel to each humidifier. If a different signal is desired consult factory.
7. Varying dc milliAmp (mA) Modulation Signal Powered by Others: NHMC/NHP Series humidifier can be factory-configured to accept a standard dc mA signal, if pre-specified. Wire according to NORTEC supplied external wiring diagram that comes with each modulation option. Choose from 0-20 dc mA or 4-20 dc mA. To share the signal with more than one humidifier consult factory.
8.
Varying Resistance (W) Modulation by Others: NHMC/NHP Series humidifiers can be factory configured to power a 3-wire varying resistance modulation humidistat by others, if pre-specified. Wire according to NORTEC supplied external wiring diagram that comes with each modulation
option. Choose from 0-135W, 0-500W or up to 0-1000W. To share the signal with more than one
humidifier consult factory.
pre-selected when ordering the option. NORTEC offers several packages for NHMC/NHP Series humidifiers. Wire according to NORTEC supplied external wiring that comes with each optional modulation package.
3. Optional modulation packages without modulating safety high limit can use on-off safety high limit. Refer to on-off controls section.
4. All versions can use on-off safety air proving switch. Refer to on-off controls section.
OPERATION
INTRODUCTION
The NORTEC NH Series humidifier is a
completely new design based on up-to-date technology. The NHB is designed to provide clean steam humidification at an economical price. It utilizes NORTEC’s patented electronic Auto-Adaptive internal control system for high efficiency, low waste of water and electricity.
The NHP and NHMC utilize NORTEC’s patented
P+I Auto-Adaptive control for greater control of the space humidity. Both the NHP and NHMC use a micro-computer control system for greater flexibility. The NHMC has a liquid crystal display (LCD) to indicate system messages, display RH and temperature. The NHMC can accept dual modulation signals and is NORTEC’s most advanced model.
OPTIONAL MODULATION (CONTINUOUS CONTROL) PACKAGES BY NORTEC
1. Modulation (continuous control) “packages” are offered as accessories by NORTEC. Power supply comes from inside NHMC/NHP Series humidifiers.
Figure #11
Generalized Modulation Wiring
VariesWith Each
Modulation Option
See NORTECSupplied
External Wiring Diagram
_
y
z
+
NHMC/NHP
External
Internal
A
B
C
810 32 30 28 26
2. NORTEC provides the humidity set point circuitry and sensor(s) for wall or duct mounting or both (only applies to NHMC. NHP is only capable of single channel continuous control modulating) as
LAYOUT AND FUNCTION
The NH Series humidifiers consist of a plumbing and an electric compartment. In every case there is at least one steam distributor (SD) for installation in air ducts or blower packs (built on: BOBP, remote mounted: RMBP) for direct space humidification.
Water enters the steam cylinder through the bottom via the drain valve from the fill cup assembly when the 24 volt fill valve solenoid is energized. When water submerges the electrodes, the minerals in the water conduct current that heats the water and produces sterile steam for distribution into the air. The minerals in the water remain in the cylinder which is periodically drained to maintain optimum performance and cylinder life.
Primary electric power is applied to the electrodes in the steam cylinder when the on/off switch is pushed on and all controls options are calling. A primary to 24 volt stepdown transformer provides power to the contactor holding coil(s) via the main control board. The humidifier’s operating status is reported to the user by the green and yellow indicator lights on the front of the unit as shown in following table.
-7-
SIGNAL LIGHT STATUS
NHMC OPERATION
YELLOW GREEN
OFF OFF Off
OFF ON Normal operation
ON ON Replace cylinder or normal
startup operation
ON OFF Operation fault
The prerequisites for getting power and water into
the steam cylinder are as follows:
on/off/drain switch must be switched on
-
control circuit 8-10 must be made
-
modulation humidistat, if present, must be calling
-
control circuit 82-83 must be made
-
control circuit 84-85 must be made
-
cabinet mounted humidistat, if present, must be
­calling
- door interlock switch must be made (interlock switch can be pulled out to operate unit)
START-UP SELF TEST
Observe the LCD display when the on/off/drain switch is first pushed on. The microcomputer pc board will check the system components, display in words what it is doing and provide a message if any faults are found. The start-up self-test sequence will be displayed as follows:
LCD EXPLANATION/COMMENTS
(WHAT YOU READ)
CONDAIRMATIC MC Note the V number. It tells you
the EPROM version.
NORTEC V2...
CONDAIRMATIC MC Note the model type. Ensure
NHMC (model type) compatibility with spec label (name plate). Can be reconfigured if necessary.
SYSTEM TEST Test begins.
LAMP GREEN Observe green signal light on
LAMP YELLOW Observe yellow signal light on
Most water does not contain enough conductivity for full boil on initial start-up. Units will need to concentrate the water over a time period (hours to days). During this process both lights are on.
CONTACT RELAY 1 Provides 24 VAC to 61-20 and
DRAIN VALVE Observe 24 volt solenoid
INLET VALVE Observe 24 volt solenoid
CONTACTOR Observe 24 volt coil activated
CONTACT RELAY 2 Provides 24 VAC to 63-36 and
CONTACT RELAY 3 Provides 24 VAC to 62-40 and
INTERNAL TEST Completion of self test.
LAMP GREEN-YELLOW INTERNAL TEST
external optional yellow lamp at control strip to simulate a fault.
activated on drain valve.
activated on fill valve.
on contactor OR fan activated on blower pack if present.
external optional red lamp at control strip to simulate cylinder spent.
external optional green lamp at control strip.
Observe green and yellow lamps pulse on together as sign that all passed.
-8-
STEAM OUTPUT
INTERNAL TEST
sensor, the LCD will read MAXIMAL LEVEL.
NOTE: If cylinder water reaches the full cylinder
Begins normal operation and displays lbs/hr.
USER LEVEL
REMOTE INDICATION
The keypad has four keys: MENU, é , ê,
ENTER.
Each time the user presses the menu key, the microcomputer will display on the LCD the next operating parameter on the menu. The basic display will read:
Steam output (lbs/hr)
-
Capacity demand
-
Limited capacity
-
Control signal y
-
The display loops back to the top of the menu the next time the user presses the menu key. As NORTEC software updates are incorporated, new parameters will automatically be added to the menu.
INFORMING THE USER
The microcomputer continually monitors the operating status and informs the user in four ways. The first (signal light status), second (optional external lamps tied to the control strip) and third (operating parameters displayed on the alphanumeric LCD display) have been discussed. The fourth way is to interrupt the LCD and display a system message. It only does this as a last resort.
SELF-HELP
The microcomputer applies corrective actions whenever its self-diagnostics identifies a problem that it is able to correct by itself. If the corrective action is not successful then it displays a system message. If the corrective action requires a service person, then the microcomputer’s only resort is to stop the unit and display a system message. The unit never stops unless it has to.
After three days of no call from either the on/off controls or the modulating controls, the drain valve is automatically activated long enough to drain all water from the steam cylinder. This NORTEC exclusive feature will prolong the life of the cylinder.
SYSTEM MESSAGES
Alphanumeric system messages will appear on the LCD display any time the microcomputer decides the user must be informed. The microcomputer does not stop the unit for all system messages. (See the Troubleshooting Section in this manual)
The NHMC is always internally wired to provide 24 VAC to the terminal strip for optional external remote indication. Up to 100 milliamps is available at each of three terminal pairs (61-20, 62-40, 63-36) for activating yellow, green and red lamps ordered as options from NORTEC or for powering field-supplied resistive loads such as lamps.
DOUBLE UNIT OPERATION
Turn both switches on. During start-up self test both sides respond to the self test together. Watch for the lamps to light and the drain, fill and contactor to energize as described on page 15. The LCD, however, only indicates the left circuit [1].
After the self test, the LCD will display the steam output for the left side [1] and both sides will operate normally.
To alternate between parameters for the left side [1] and parameters for the right side [2], press the Enter key.
Use the MENU key to see other parameters besides steam output. To display steam total output
for both sides press the enter key until [S] is displayed.
When a fault occurs on the right side of the double unit, both sets of lamps (and remote relays) will come on indicating that a fault has occurred. The left [master] will display its own faults.
The LCD will indicate which fault has occurred and on which side of the unit, [1] or [2]. The side not faulted will continue to operate as usual.
Display is not available for the right side [2] if the left side is switched off.
NHB/NHP OPERATION
END OF CYLINDER LIFE
When the cylinder is used up and water level can no longer stabilize below full cylinder (due to fully coated electrodes), the yellow light will come back on, in addition to the green light. The disposable cylinder must be replaced.
Although “both lights on” is the same signal at start-up as it is at end of cylinder life, the age of the cylinder enables the user to know when “both lights on” is indicating end of cylinder life. It is wise to keep a new replacement cylinder on hand to avoid downtime when it becomes time to change the disposable cylinder. (See Troubleshooting section.)
-9-
Loading...
+ 28 hidden pages