Norlake KF033SMS Installation Manual

KE2 Evaporator
01/13 Rev. A 151627
Enviro-Control™
thermsolutions
KE2 EvaporatorEfficiency
TM
ENTER
BACK
Installation Instructions
KE2 EvaporatorEfciency
01/13 Rev. A 151627
Factory Default Settings
. . . . . . . . . . . . . . Page 13-14
Enviro-Control™
Installation Instructions
Introduction
The KE2 Evaporator Eciency (KE2 Evap) is an electronically op­erated evaporator controller engineered to save energy in re­frigeration systems through precise control of superheat, space temperature, fan cycling, reducing compressor runtime, and
KE2 Evaporator Eciency - Controls and Communicates
implementing demand defrosts. The KE2 Evap oers quick pay­back, and a life expectancy that matches that of the system. The controller pays for itself, and then continues to pay dividends for the life of the system.
TEV/EEV
Room Temperature
Evaporator Fans
Compressor/
Liquid Line Solenoid
Defrost Heaters
Multiple Alarms
Table of Contents
KE2 Evaporator Eciency
TM
thermsolutions
KE2 EvaporatorEfficiency
ENTER
BACK
KE2 Master View on:
Tablet
KE2 Therm Evaporator Eciency
IP Address: 10.10.50.51 Location: Walk-in Freezer
ABC Contracting
STATUS
MODIFY
(888)555-3358
Mac Address: 00.04.A3.12.07.87
Evaporator FanORoom Temp
Coil Temp
Compressor
System Mode
Cool
DefrostOAux Temp
Superheat
0.0 F
Home SetpointsNetworkSettings
PWR SYS WLAN 4 3 2 1 WAN USB QSS
All Clear
-8.5 F
15.4 F
On
Dig Input 3
Dig Input 1
Dig Input 2
Dis
Dis
Closed
Dis
Sat Temp
Valve Position
Suct Pressure
Suct Temp
TM
thermsolutions
46.0 F
Manual
96.2 F
87.7 F
(
(
(
(
(
(
KE2 Router
Location . . . . . . . . . . . . . . . . . . . . . Page 3
Installation & Wiring . . . . . . . . . . . . Page 3 - 9
Figure1: Installation Locations . . . . . . . . . . . . . .
Figure 2: Return Air Sensor Placement . . . . . . . . .
Figure 3: Proper Sensor Location . . . . . . . . . . . . .
Figure 4: Coil Sensor Placement . . . . . . . . . . . . .
Figure 5: Evaporator Eciency Diagram . . . . . . . .
Figure 7: Wiring Schematic - New Install Figure 8: Wiring Schematic - with Contactor Box
Dimensions . . . . . . . . . . . . . . . . . .Page 9
Figure 9: Dimensions . . . . . . . . . . . . . . . . . . .
Mounting the Controller
Controller Setup
Table 1: Quick Start . . . . . . . . . . . . . . . . . . . .
Adjusting Controller Parameters
. . . . . . . . . . . . . . .Page 10
Table 2: Navigation Through Controller Parameters Page 12 Table 3: Controller Menus and Menu Parameters Pgs. 12-16
Variables Menu . . . . . . . . . . . . . . . . . . . Page 12
Alarm Status Menu
Manual Menu . . . . . . . . . . . . . . . . . . . . Page 14
Setpoint Menu . . . . . . . . . . . . . . . . . . . . .Page 15
Table 4: Defrost Defaults . . . . . . . . . . . . . . . . . Page 16
. . . . . . Page 7
. . . . . . . . . .Page 10
. . .
Page 10-16
. . . . . . . . . . . . . . . . .
Page 3 Page 3 Page 4 Page 5 Page 6
Page 8
Page 9
Page 10
Page 12
Communication . . . . . . . . . . . . . . . . Page 16
Table 5: Ethernet Specications Summary . . . . . . Page 16
Specications . . . . . . . . . . . . . . . . . Page 16
Smart Phone
KE2 Therm Evaporator Eciency
IP Address: 10.10.50.51 Location: Walk-in Freezer
ABC Contracting
STATUS
MODIFY
(888)555-3358
Mac Address: 00.04.A3.12.07.87
CompressorOnSystem Mode
Evaporator FanORoom Temp
Coil Temp
All Clear
Cool
-8.5 F
15.4 F
Dig Input 3
DefrostOAux Temp
Dig Input 1
Dig Input 2
Dis
Dis
Closed
Dis
Sat Temp
Superheat
Valve Position
Suct Pressure
Suct Temp
46.0 F
0.0 F
Manual
96.2 F
87.7 F
Home SetpointsNetworkSettings
PC
KE2 Therm Evaporator Eciency
IP Address: 10.10.50.51 Location: Walk-in Freezer
ABC Contracting
STATUS
MODIFY
(888)555-3358
Mac Address: 00.04.A3.12.07.87
CompressorOnSystem Mode
Evaporator FanORoom Temp
Coil Temp
Cool
-8.5 F
15.4 F
Dig Input 3
DefrostOAux Temp
Dig Input 1
Dig Input 2
Dis
Dis
Closed
Dis
Sat Temp
Superheat
Valve Position
Suct Pressure
Suct Temp
46.0 F
0.0 F
Manual
96.2 F
87.7 F
Home SetpointsNetworkSettings
TM
thermsolutions
All Clear
TM
thermsolutions
KE2 Evaporator
01/13 Rev. A 151627
Enviro-Control™
Installation Instructions
Location
The KE2 Evap was developed with ease of installation in mind. The controller is supplied in an enclosure, and encapsulated to protect the circuitry from moisture damage. This extra level of protection allows the controller to be installed in the refriger­ated space.
When installing the controller, it may either be installed on an interior/exterior wall or on the evaporator. Many evaporators
evaporator or on its housing. Locating the controller as close to the evaporator as possible reduces the amount of wiring when converting existing systems, as well as when it is applied on new applications.
tion providing easy access -- on the wall or near the entrance. This enables the user to easily view the display, and eliminates the need to use a ladder or lift to modify the setpoints or check alarms.
If viewing the temperature outside the walk-in or refrigerated room is desirable, the KE2 Evap may be used as a digital thermo­stat. The controller is then installed near the door of the space
Figure 1 - KE2 Evap Installation Locations
On the evaporator
TM
thermsolutions
KE2 EvaporatorEciency
2
2
ENTER
BACK
On the wall
TM
thermsolutions
KE2 EvaporatorEciency
2
2
ENTER
BACK
See Figure 1 for locations.
If installing the controller on the face of the evaporator, preexist­ing knockouts on the evaporator should be used for installing the high voltage wiring. If knockouts do not preexist, hole(s) may be carefully cut into an unobstructed area of the evapora­tor case. If modifying the face of the evaporator is not feasible or desired, the controller’s conduit knockouts may be used with ½ inch conduit.
The bottom side of the controller includes a cutout with cable tie slots providing a strain relief for the low voltage and sensor wires. Additional knockouts are available on either side if con­duit is preferred.
-
Installation & Wiring
The KE2 Evap is supplied with pluggable connectors for all connections. Pluggable connectors permit the controller to be placed in a safe location while the wiring is installed. They also simplify the wiring, allowing the wires to be fastened to the screw terminals in the open air. Once all wiring is completed using accepted wiring practices, it is plugged into the controller
Although there is one pressure transducer and four temperature sensor inputs, when used with mechanical valves (TEVs), KE2 Evap only requires the (2) sensors supplied with the kit. One sensor reads the return air temperature and the other measures the coil temperature. NOTE! Sensor location is critical to the
proper operation of the controller.
Return Air Temperature Sensor - The air temperature sensor is
installed in the return air of the evaporator using the included sensor mount. Most applications allow the sensor mount to be installed using an existing screw. On evaporators where us­ing an existing screw is not possible, the included self-tapping screw may be used to secure the sensor mount to the evapora­tor. Note: Be careful to avoid damage to an evaporator tube
or causing a leak in the
drip pan. When installing, it is impor-
tant to prevent the air sensor from coming into contact with the mounting bracket, cable ties, or any other solid material. Figure 2 shows an example of how to mount the sensor. The sensor must be a minimum of 6 inches from the coil surface.
Figure 2 - Return Air Sensor Placement
.sutats metsys ro/dna erutarepmet moor eht fo gniweiv ysae rof
At the entrance
>6”
Air Sensor
TM
thermsolutions
KE2 EvaporatorEciency
2
2
ENTER
BACK
Return Air
KE2 EvaporatorEfciency
01/13 Rev. A 151627
Enviro-Control™
Installation Instructions
After the sensor is installed, route the wire back to the control­ler location. When routing sensor wire, it is important to avoid interference from high voltage lines. If sensor wire is run parallel to the high voltage, there is a potential for inductance to aect the sensor reading. This is of particular concern with long wire runs. When extending sensors, use the 18 gage, shielded twist­ed pair. Sensor wires can be run beyond 100 feet when using special considerations. Contact KE2 Therm. After the wire has been successfully routed, it may be connected to the pluggable terminal on the controller.
Coil Temperature Sensor - As a critical input to the control­ler, it is essential the sensor is located at the coldest point on the evaporator coil for optimal operation. The coil sensor is an integral part of the control algorithm used to determine coil ef­ciency, to initialize defrosts, and to terminate defrosts.
KE2 Therm oers general guidance for sensor locations based on the coil construction. Figure 3 shows the recommended lo­cations for the coil sensor for each evaporator type.
When installing on draw through models, the sensor should be located behind the coil in the lower corner nearest the suction header. Blow through models should be installed on the front of the coil, in the upper corner also nearest to the suction header. When installing the sensor into the coil, the sensor should be po­sitioned half way between the circuit tubes and, perpendicular to the face of the coil. When choosing the location, the sensor should not be located adjacent to the electric heating elements. Locating the sensor too close to the elements will cause false defrost termination temperatures. The sensor should be ap­proximately half the distance between the heaters if possible. Figure 4 shows the proper sensor placement.
Figure 3 - Proper Sensor Location
Electric Defrost - Surface Heater
Higher Frost Zone
coldest part of evaporator
Heater Coil
3”
Electric Defrost - Dropped Tube
Higher Frost Zone
coldest part of evaporator
Heater Coil
3”
Ideal Sensor Location
- 1/2 way between heater coils
1/2 way
- insert perpendicular to face of coil
- pinch ns together to hold
Ideal Sensor Location
- 1/2 way between heater coils
3”
- approx. 3” from top and 3” from side
- insert parallel to face of coil
- pinch ns together to hold
Due to the many factors inuencing the evaporator perfor­mance, it is impossible for KE2 Therm to provide the proper loca­tion of every installation. However, the coil sensor is an integral part of the control algorithm used to determine coil eciency to initiate, as well as, terminate defrosts. The coldest point in the coil can be identied from existing system knowledge or by monitoring the normal operation.
Controller Power - The high voltage wiring is protected by a metal shield screwed to the back side of the controller. The shield should be removed to gain access to the wiring connec­tions, making note of the location of the screws. The screws in the upper corners are coarse thread screws, while the screw in the middle is a 4-40 machine screw.
The controller accepts either 115V or 208/240V incoming power. The controller includes metal oxide varistors (MOVs), providing protection from voltage spikes. MOVs use the same technology commonly applied to protect consumer electronics. They func­tion by ltering out voltages high enough to damage the board. When the voltage exceeds the allowed amount, the MOVs short to ground, protecting the circuitry. For additional protection, the board has a replaceable BK/MDL-1/4 fuse in line. The grey plug is accessible without removing the metal shield in the fuse
Air Defrost
Ideal Sensor Location
- lower corner nearest expansion valve, approx. 3” from bottom, and 3” from side
- insert parallel to face of coil
- pinch ns together to hold
3”
3”
KE2 EvaporatorEfciency
Coil Sensor
Defrost Heaters
01/13 Rev. A 151627
Enviro-Control™
Installation Instructions
Figure 4 - Coil Sensor Placement
holder. Depress slightly and turn 1/4 turn counterclockwise to remove. Replace by depressing slightly and turning 1/4 turn clockwise. Do not overtighten.
The board uses a pluggable screw terminal connector to con­nect incoming power. The terminal is located in the top right corner of the controller when the terminals are facing the user. See Figure 5.
Fan and Defrost Relays - There are 2 larger relays on the con­troller with spade connectors. These are used for the evaporator fans and defrost heaters. Due to the spacing of the enclosure the spades require a 90 degree terminal. KE2 Therm has includ­ed (4) spade connectors to assist in wiring the relays.
Evaporator Fan Relay - The fan relay is rated 10A inductive at 240V. One leg of the incoming power for the fans should be connected to the COM terminal of the fan relay, the upper of the two larger relays. The remaining leg, (L2) should be connected to one lead of the fan. The remaining fan lead should be con­nected to the NO (Normally Open) terminal on the fan relay. See
Figure 7.
Defrost Heater Relay - The heater relay is rated 20A resistive at
240V. One leg of the incoming power for the heaters should be connected to the COM terminal of the heater relay, the lower of the two larger relays. The remaining leg, (L2) should be con­nected to one lead of the heater. The remaining heater lead should be connected to the NO (Normally Open) terminal on the heater relay.
Alarm Relay - The alarm relay is rated at 3A inductive at 240V. This relay uses the 3-position pluggable screw terminal to make the connection to the board. The relay may be used to connect an audible alarm, light, or to alert a 3rd party alarm system. One leg of the incoming power supply (L1) should be connected to COM terminal of the alarm relay, the lower of the two smaller relays. The remaining leg, (L2), should be connected to one lead on the alarm. The remaining alarm lead, should be connected to the normally open (NO) position on the terminal.
After all high voltage wiring is completed the metal shield must be replaced and screws tightened.
Additional Inputs
Suction Temperature Sensor - The suction temperature sen-
sor is required when applying the controller with an electronic expansion valve. The sensor’s proximity to the evaporator out­let diers slightly for electronically controlled valves from the placement of a TEV bulb. Due to the more rened control from an electronically controlled valve, the sensor must be placed as close to the outlet of the coil as feasible. Although the dis­tance from the outlet is dierent, the nature of the refrigerant’s ow through the tube remains unchanged, thus the orientation of the sensor remains at the 4 or 8 o’clock position. The sensor should be secured to the suction line using the included wire ties designed for low ambient operation.
Pressure Transducer - In addition to the suction temperature sensor, a pressure transducer is also required for superheat measurement when applying an electronic expansion valve. The pressure tap should be mounted on the top of a horizontal section of tube. It should be located near the suction sensor, ap­proximately 3 inches downstream from the position of the tem­perature sensor.
Auxiliary Temperature Sensor -The auxiliary temperature sen­sor provides exibility and may be used for any purpose desired by the user. The placement of the sensor is dependent on the requirements of the user’s intended application. The Auxiliary Temperature sensor must be supplied by KE2 Therm.
Digital Inputs - The controller includes (3) digital inputs. See Table 3 for conguration options.
Compressor/Liquid Line Solenoid Relay - The compressor re-
lay is rated at 3A induction at 240V. This relay uses the 3-position pluggable screw terminal to make the connection to the board. The relay is not intended to control the compressor directly. It is designed to be used to control the liquid line solenoid or as a pi­lot to the compressor contactor. One leg of the incoming power supply (L1) should be connected to COM terminal of the com­pressor relay, the upper of the two smaller relays. The remaining leg, (L2), should be connected to one lead on the solenoid/com­pressor contactor. The remaining lead, should be connected to the normally open (NO) position on the terminal.
Loading...
+ 11 hidden pages