Nor-Lake General Lab Incubator User Manual

GENERAL LABORATORY REFRIGERATED
INCUBATOR
Installation, Operation and
Maintenance Instructions
GENERAL
Inspection 2 Location 2 Installation General Information 3
OPERATION
Performance Data 3 Theory of Operation 3
MAINTENANCE
Troubleshooting 4 Maintenance Service & Analysis Guide 4
2
2
3
4
02/12 Rev. B 138691
GENERAL
INSPECTION
When the equipment is received, all items should be carefully checked against the bill of lading to ensure all crates and cartons have been received. All units should be inspected for concealed damage by uncrating the units immediately. If any damage is found, it should be reported to the carrier at once, and a claim should be filed with the carrier. This equipment has been inspected and tested in the manufacturing facility and has been crated in accordance with transportation rules and guidelines. Manufacturer is not responsible for freight loss or damage.
LOCATION
Allow a minimum four-inch clearance on the top, rear, and sides of the cabinet for proper ventilation. The cabinet should also be leveled when it is placed in its permanent location. If two or more units are positioned side to side, allow a minimum of 8 inches between cabinets. Choose a site free from rapidly changing ambient temperature conditions. Radiators, air-conditioning outlets and other ventilating outlets can affect the operation of the Refrigerated Incubator by a sudden in rush of air that is different from standard operating conditions. Do not stack items on top of the unit. Vibration during shipping and handling may loosen mechanical connections. Check all connections during installation. Check all wiring, piping and fasteners.
CAUTION
Do not modify cabinet construction or associated equipment assemblies. Do not remove labeling or information supplied with the unit.
INSTALLATION
For electrical requirements see data information and wiring unit diagram located in parts bag, inside of the cabinet. Check the proposed external power outlet/supply to be used to ensure that the voltage, phase and current carrying capacity of the circuit from the electrical panel correspond to the requirements of the cabinet. The power cord of this Refrigerated Incubator is equipped with a three­prong (grounding) plug which mates to a standard three-prong (grounding) receptacle. NEVER extension cord to wire any unit. Refer to the serial tag (nameplate data) for all pertinent electrical
information.
power cord. Do not use a two-prong adapter plug.
Observe all Warning Labels. Disconnect power supply(s) to eliminate injury from electrical shock or moving parts when servicing equipment.
The Refrigerated Incubator should not be operated in an environment where the ambient temperature exceeds 90°F (32.2°C) as the compressor thermal overload will be tripped and will result in a wide band control cycle of approximately ±4°C. Such cycling should not be interpreted as a malfunction of the electronic controls.
When loading the Refrigerated Incubator, a space of ½” minimum should be allowed between adjacent items to allow for maximum air circulation. Temperature uniformity will be adversely affected if air circulation is obstructed.
Excessive frost buildup on the evaporator coil located on the rear cabinet wall will also affect temperature uniformity.
WARNING- SAFETY PRECAUTIONS
Do not, under any circumstances, remove the third (ground) prong from the
use an
- 2 - 02/12 Rev. B 138691
1. Do not place any explosive, combustible or flammable materials inside the Refrigerated Incubator.
2. Do not place sealed containers in the Refrigerated Incubators. Sealed containers filled with materials do not allow for expansion and can develop dangerous vapor pressure as the temperature increases.
3. Avoid liquid spillage within the chamber.
4. Do not evaporate noxious fumes.
5. Do not store containers filled with acidic or caustic solutions as vapors from these materials will attack the evaporator and void the warranty.
GENERAL INFORMATION
The Refrigerated Incubator has been designed to provide maximum temperature control. The Incubator provides dependable and precise performance is obtained through the microprocessor technology in the temperature control circuitry. The C to 50°C. The temperature range will meet a wide variety of applications such as BOD determination, general incubation and preservation of critical materials. Note: If operating below 2°C for extended periods of time, the defrost setting should be turned on.
under counter 6 cu. Ft. refrigerated incubator has an operating range of 5° C to 50°C. This
upright 20 cu. Ft. refrigerated Incubator has an operating range of -10°
OPERATION
PERFORMANCE DATA Upright 20 cu. Ft. Heat-Up Time: From -10°C to 50°C = 120 minutes (Compressor “ON”)
Cool-Down Time: From 50°C to -10°C = 100 minutes Under counter 6 cu. Ft. Heat-Up Time: From 5°C to 50°C = 60 minutes
Cool-Down Time: From 50°C to 5°C = 60 minutes
Note: The above performance figures are based on the following operating conditions: Line Voltage……………………110.5 to 112.5 VAC Ambient Temperature…………22.5° to 24°C
THEORY OF OPERATION
The refrigeration system, defrost heater and air circulating fan are used in conjunction with the microprocessor controlled proportioning circuit to achieve very sensitive temperature control. An RTD (Resistance Temperature Detector) located in the airstream senses any temperature deviation from the set point and heat is provided proportionally to maintain the required temperature. The circulating fan provides even air distribution throughout the cabinet interior and ensures temperature uniformity.
settings. The controller, which is located on the facade of the unit, is factory set. Please see the separate default instructions and explanation of the controls and operation of the controller.
The programmable controller controls the temperature and defrost
MAINTENANCE
- 3 - 02/12 Rev. B 138691
PERIODIC CLEANING
Disconnect power source before servicing or cleaning. Beginning with the initial installation, the interior surfaces of the cabinet should be periodically cleaned
with a solution of warm water and baking soda. This solution will remove any odors from spillage that has occurred. The exterior of the cabinet should also be cleaned frequently with a commercial grade of glass cleaner. Caution: Do not use an abrasive or alkaline solution.
TROUBLESHOOTING
Problems encountered with any constant temperature cabinet are most frequently related to temperature control. Before proceeding with detailed troubleshooting in accordance with the Maintenance Service and Analysis Guide, ensure that the Low Limit and High Limit controls are properly adjusted. If the limit controls are set too close or beyond the operating temperature, the Incubator may constantly go into the alarm mode. This will result in erratic temperature control. If it is ascertained that refrigeration service is required, contact a qualified service person. WARNING - Service should be
performed only by qualified service personnel. Line voltage and moving parts are present in the control and machine compartments that are hazardous to life.
MAINTENANCE SERVICE AND ANALYSIS GUIDE
REFRIGERATION SYSTEM
MALFUNCTION POSSIBLE CAUSE SOLUTION
Compressor will not start - 1. Service cord unplugged 1. Plug in service cord no hum 2. Fuse blown or removed 2. Replace fuse
3. Overload tripped 3. Determine reasons and correct
Compressor will not start - 1. Low voltage to unit 1. Determine reason and correct hums but trips on overload 2. Relay failing to close 2. Determine reason, correct or replace protector
Compressor starts and runs, 1. Low voltage to unit 1. Determine reason and correct but short cycles on overload 2. Overload defective 2. Check current, replace overload protector protector
Relay not operational 1. Voltage too high or too low 1. Determine reason and correct
Refrigerated space too warm 1. Control setting too high 1. Reset control
2. Evaporator coil iced 2. Determine reason and defrost
3. Air flow to condenser or 3. Remove obstruction for free air flow evaporator blocked
Standard temperature system 1. Control setting is too low 1. Reset the control freezes the product
Objectionable noise 1. Fan blade hitting fan shroud 1. Reform or cut away small section of shroud
2. Vibrating fan blade 2. Replace fan blade
Failure to Heat 1. Incorrect Control setting 1. See Control manual
- 4 - 02/12 Rev. B 138691
Loading...