Wall Mounted Systems
General Instructions
Freezer Models 100 or 150
Ceiling Mounted Systems
General Instructions
Outdoor Systems Utilizing a Membrane Roof
OPERATION
Standard Temperature (Cooler) Systems
Low Temperature (Freezer) Systems
Extra Low Temperature (Freezer) Systems
MAINTENANCE
General
Service and Analysis Guide
DIXELL CONTROLLER SETTINGS FOR STANDARD PRS-2
MODELS
DIXELL CONTROLLER SETTINGS FOR CPF060DC-A
MODEL
DIXELL XR01-02CX CONTROLLER MANUAL
DIXELL XR01-02CX CONTROLLER MANUAL
ELECTRICAL DATA
2 - 3
2 - 3
3
4 - 6
4 - 5
5 - 6
7 - 9
7
7 - 9
9
10 - 11
10
11
12
13
14
24
Electrical and Refrigerant information can be found on the
Serial Tag.
7/10 Rev. B 040086
INSTALLATION
WALL MOUNTED SYSTEMS
General Installation Instructions
Note: If the system to be wall mounted is a freezer model 100 or 150, pleasesee the next section with special
instructions on mounting these units.
Carefully raise the entire refrigeration system and insert the projecting sleeve of the evaporator section into
the opening of the walk-in wall. While supporting the system, lock it into position by turning the locks exactly
as you did when locking the walk-in sections together. Make sure that the locks are positively engaged and
insert the plug buttons into the lock access holes when finished. Refer to Figure 1.
Note: Some motor compressors are openly spring mounted to absorb vibration. Be sure that these bolts are
loosened to permit the compressor to float freely on the springs. A reminder label is applied to systems where
this procedure applies.
All systems require a permanent connection to an electrical service and a connection at the junction box
located within the condensing unit housing. Refer to the serial tag for all pertinent electrical data. These
systems must be connected to a power supply disconnect switch and wired according to local and national
electric codes.
Wall Mounted
PRS-2 Refrigeration System
Figure 1
2
No plumbing drain is required, under normal conditions, for indoor installations. A built-in hot gas vaporizer
dissipates the condensate moisture automatically. In outdoor installations, the condensate should be plumbed
to the nearest drain. Check local building codes. Outside drain lines must also be wrapped with a suitable
heater wire if they are ever subjected to below freezing temperatures. Outdoor installations also require the
attachment of the rain hood that will divert rainfall from the upper surface of the evaporator housing. See
Figure 1 for an illustration.
Be sure to allow for sufficient airflow around the condenser. A minimum clearance of two feet is required for
proper unit operation. If multiple units are located in the same area, be sure they do not exhaust hot air flows
into one another.
Please see the section “Instructions for Pre-Charged Lines” if the installation of this system involves the use
of pre-charged lines to connect the evaporator and condenser secti ons.
Freezer Models 100 or 150
1. After uncrating, before attempting to attach the refrigeration system to the walk-in, a substantial
temporary support should be built. The support should be approximately 28 inches high and placed
directly below the wall opening of the walk-in.
Note: Due to the weight of these systems it is highly recommended that proper lifting equipment, such as
a fork truck, be utilized during installation.
2. Lift the refrigeration system onto the temporary support. Determine whether the coil section sleeve is
positioned properly so that it can be inserted into the opening without being bent or damaged. Shim the
system appropriately so that this can be accomplished.
3. Carefully slide the entire system so that the coil section sleeve enters the opening without disturbing the
temporary support below the refrigeration system. Continue until the gasket around the coil section
contacts and seals around the entire perimeter of the coil section. Shim the system and adjust it
accordingly so that the gasket seal will be uniform on all four sides.
4. Using the section-latching wrench provided for the erection of the walk-in, insert the wrench into the latch
access holes of the coil section. Turn each of the locks clockwise until the latches engage the strikes in
the walk-in. Turn the lock until a full stop is encountered. DO NOT REMOVE THE TEMPORARY SUPPORT!
5. Remove the louver assembly and drill four 9/16”
diameter holes through the two upright angles of the
condensing unit section. Drill completely through the
walk-in wall and insert the 1/2" threaded nylon rods.
Secure with the flat washers and nuts provided. Refer
to Figure 2.
6. With the leveling screws threaded completely into the
leg support, insert the leg support into the leg retainers
at the outer corners of the condensing unit section.
Unscrew the leg leveling screws until they contact the
floor or other supporting surface. Note: If the
supporting surface is extremely uneven, suitable
shimming material must be provided under one or both
of the leg supports.
7. Attach the diagonal leg support braces using the
threaded fasteners provided. Make the final
adjustments to the leg leveling screws so that they
serve as supporting devices to the outer edge of the
refrigeration system.
8. Insert plug buttons into each of the latch access holes.
Figure 2
9. Remove the temporary support assembly that was provided in Step 1.
3
CEILING MOUNTED SYSTEMS
General Installation Instructions
This section has the general instructions for installing the ceiling mounted Refrigeration System. Before
proceeding, please also see the following sections on mounting “Outdoor Systems Utilizing a Membrane
Roofing Material”, or “Remote Systems with Curb and Electric Vaporizer”, if applicable.
Note: Due to the weight of these systems, it is highly recommended that proper lifting equipment, such as a
fork truck, be utilized during installation. Also, be sure to allow for sufficient airflow around the condenser. A
minimum clearance of two feet is required for proper unit operation. If multiple units are located in the same
area, be sure they do not exhaust hot air flows into one another.
1. Mount eyebolts to the base of the refrigeration system through the holes that were used to lag the base to
the shipping crate. Note: The holes can be drilled out to a larger diameter, if required, for eyebolts that
are available.
2. Insert chains or cables from an overhead lifting source through the eyebolts and carefully raise the entire
refrigeration system to the top of the walk-in.
3. Position the unit cooler section of the refrigeration system over the hole in the walk-in ceiling section.
4. Align the tabs on the side of the unit cooler section with the predrilled holes in the ceiling section. Before
proceeding to the next step, the cowl cover should be removed. Look inside the unit cooler section and be
sure the air divider in the ceiling section lines up with the black gasket divider in the unit cooler. Simply
bending the ceiling section divider slightly forward or backward may be required. This will prevent any
short cycling of discharge and return air.
5. Fasten the unit cooler section down to the ceiling using the provided drive screws, which can be found in
the small cloth bag. CAUTION! This must be done to prevent the entire refrigeration system from
moving during operation.
Note: On smaller refrigeration systems, you may elect to install the system on the ceiling section while the
section is still on the floor. CAUTION! Make sure to fasten down the system to the ceiling panel. The
ceiling section and the refrigeration system may then be erected together in the normal sequence of assembly
as shown in the walk-in installation instructions. This method is not practical and should not be used with
larger systems of 1 horsepower or above, such as a model CPF100 or CPF150.
4
6. After the system is in place, make sure that the bolts fastening the condensing unit section to the
evaporator section are loose enough so that the two sections can adjust to the ceiling surfaces. Note: On
large systems, 1 horsepower and above, the units are placed on a rack assembly and do not have these
bolts connecting the two sections together. No adjustment is necessary.
Note: Some motor compressors are openly spring mounted to absorb vibration. Be sure that these bolts
are loosened to permit the compressor to float freely on the springs. A reminder label is applied to
systems where this procedure applies.
7. All systems require a permanent connection to an electrical service and a connection at the junction box
located within the condensing unit housing. Refer to the serial tag for all pertinent electrical data. These
systems must be connected to a power supply disconnect switch and wired according to local and
national electric codes. No plumbing drain is required, under normal conditions, since a built-in hot gas
vaporizer dissipates the condensate moisture automatically.
Outdoor Systems Utilizing a Membrane Roofing Material
1. After the walk-in is completely assembled, place the curb face down on top of the ceiling sections,
aligning the opening with the gasket on the curb. To insure proper opening alignment, mark the outside
portion of the curb on the ceiling sections with a marking pencil.
2. Remove the paper from the gasket and position the curb, gasket side down, on the pencil line. Press
down firmly. Note: Movement of the curb is very difficult after the gasket adheres to the ceiling
section. Refer to Figure 3.
Figure 3
Figure 4 Figure 5
3. Lay the membrane roofing material over the walk-in ceiling sections and curb leaving a six inch overhang
on all four sides of the walk-in. Using an utility knife, cut a hole in the membrane roof approximately 1-1/2”
in from the edge of the opening. (The resulting hole in the membrane will be smaller than the ceiling
opening). Fold the 1-1/2” membrane flaps into the opening, notching the membrane around the locators
and divider. Use either staples, roofing nails, sheet metal screws, caulk, glue, etc. to fasten the
membrane roofing material to the inside edge of the curb frame. Refer to Figure 4.
5
4. Set the PRS-2 Refrigeration System over the opening in the curb. Remove the enclosure from
the condensing unit portion of the system and drill two 9/16” holes through the system base, membrane
roof material, curb, and the foamed ceiling section. The holes should be located on opposite sides of the
unit. Insert one 1/2” threaded nylon rod into each hole and place one washer and nut on the condensing
unit end of the threaded nylon rod. Place a second washer and nut on the inside of the walk-in and
tighten securely. Replace the enclosure and attach the outdoor hood with the drive screws provided.
Refer to Figure 5. The nylon rods, washers, and nuts are provided.
6 erugiF
7 erugiF
5. Fold all four corners of the membrane roofing material over the walk-in corners as shown in Figure 6.
6. Attach the trim and door hood by using the provided hex head sheet metal screws. All pieces should be
held down 3-1/8” from the ceiling top as shown in Figure 7. Insure the trim and membrane roof material
cover the joint between the ceiling and wall panels. Note: The trim may have to be cut to fit.
7. Trim off all excess membrane roofing material on the bottom of the aluminum trim using a utility knife.
Note: In outdoor installations, the condensate should be plumbed to the nearest drain. Check local building
codes. Outside drain lines must also be wrapped with a suitable heater wire if they are ever subjected to
below freezing temperatures.
6
OPERATION
STANDARD TEMPERATURE (COOLER) SYSTEMS
The automatic air defrost Refrigeration System for coolers is a basic, unitized
refrigeration system. The system is designed to provide normal storage
temperatures in the Walk-in with a minimum of effort during initial installation.
The system consists of a complete condensing unit, an evaporator coil, a
method for controlling the temperature, and a time switch for setting "off cycle"
defrost. The time switch used to control the defrost cycle has been factory
preset. However, please refer to the following instructions on the operation of
the time switch if an adjustment is ever needed. All cooler systems are
provided with an electronic 24 hour dial time clock. Note: The cooler time
clock is factory set for a 15 minute defrost every 3 hours. Important: It is the
installing contractor’s responsibility to check the operation upon start-up and
make necessary temperature control or thermal expansion valve adjustments
as required for proper operation.
Note: Refrigeration Systems that are designed for outdoor installation will be fitted with electric crankcase
heaters, electrically heated condensate drain tubes, automatic head pressure control valve, and the "pumpdown cycle".
Programming
The 24-hour dial has quarter-hour divisions and AM/PM indications. The time switch is programmed by
pushing the captive trippers to the outer ring position for the entire period that the load is to be turned "on", i.e.
fifteen minutes for each tripper on the 24-hour dial. When the tripper is pushed to the inside, the switch is in
the "off" position. (It is not recommended for the cooler to have defrosts longer than 15 minutes
Defrost Cycle (Cooler System)
The purpose of the defrost cycle is to allow time for any frost formed on the evaporator to melt and clear from
the surface. The time clock stops the condensing unit. During this time, the evaporator fans continue to run,
blowing 35-38°F air over the fins. This process will warm the evaporator above 32°F. After 15 minutes, the
condensing unit should restart.
LOW TEMPERATURE (FREEZER) SYSTEMS
The low temperature, automatic electric defrost Refrigeration System is the most dependable, readily
understood equipment available. It employs a basic refrigeration system with electric elements to provide heat
for defrosting.
Important: It is the installing contractor’s responsibility to check the operation upon start-up and make
necessary temperature control or thermal expansion valve adjustments as required for proper operation.
Note: Refrigeration Systems that are designed for outdoor installation will be fitted with electric crankcase
heaters, electrically heated condensate drain tubes, automatic head pressure control valve, and the "pumpdown cycle".
Note: If you purchased a CPX150DC or CPX151DC extra low temperature system, please also refer to the
instructions under “Extra Low Temperature Systems” as all of the following operations may not pertain.
Note: Some models may have a programmable control used in place of the time switch. This unit is used to
control the temperature and the defrost settings. Please see the separate instructions that are included on the
operation of this control.
.)
7
Time clock adjustments:
Setting the correct time of day - To set the correct time of day simply rotate the
small inner dial counterclockwise until the correct time of day on the large dial
is opposite the "time" indicator. Number of defrosts per day - The timer is
factory set to defrost the evaporator four times a day. If more defrosts are
required, remove a knurled slotted screw from the holder, insert the screw into
the time slot on the large dial where a defrost is desired, and tighten. Defrost
length adjustment - On the small, upper dial there is a pointer that is used to
set a 100% fail-safe feature. The fail-safe of the timer is factory set at 30
minutes. The function of this device is to terminate the defrost if a system
malfunction occurs during defrost.
WARNING ! No adjustment of this device should ever be necessary.
Lengthening the fail-safe time will not lengthen the defrost cycle.
Defrost Cycle (Freezer System Only)
Under low temperature conditions, the air being forced through the evaporator coil is well below freezing at all
times, even during each compressor "off" cycle. Therefore, a source of heat must be supplied to melt the
accumulated frost. To achieve a complete defrost, electric heater elements are attached to the evaporator coil
and to the drain pan. An electric time switch initiates a predetermined number of regular defrost periods per
day. When a defrost period occurs, the time switch stops the evaporator fan(s) and the condensing unit, and
energizes the electric heaters in the evaporator coil and in the drain pan beneath it.
Defrost Cycle Termination
As the defrost cycle progresses and the frost accumulation melts from the fins of the evaporator coil, the
temperature of the finned surfaces of the evaporator coil will rise proportionately with the removal of the frost.
When this temperature reaches about 50°F, a point where the evaporator coil should be completely free of
frost, a defrost termination thermostat attached to the evaporator coil will energize a solenoid coil in the
defrost time switch which will revert the system to the cooling cycle. The fan(s) in the evaporator housing will
not start, however, until the fan delay cycle has expired. See the "Fan Delay" below.
Fan Delay
When a defrost cycle is terminated through the action of the defrost termination thermostat as described in
the section "Defrost Cycle Termination", the electric defrost heaters are de-energized, the compressor starts,
and evaporation resumes in the coil. The evaporator fan(s), however, will not start until the evaporator coil
temperature is reduced to about +20°F. Once this temperature is reached, the fan delay switch action of the
defrost termination thermostat energizes the evaporator fan(s) and they begin operating.
The fan delay feature is an important part of defrosting. If the fan(s) was permitted to start immediately
following a defrost period, the heat that accumulated in the evaporator housing would be circulated
throughout the walk-in, raising the temperature considerably. In addition, any droplets of moisture that
remained clinging to the fins of the evaporator coil would be blown into the storage space. The fan delay
feature provides for a short refrigeration cycle WITHOUT the evaporator fan(s) to prevent these conditions.
Note: During the initial startup of a
PRS-2 Refrigeration System on a warm walk-in, the evaporator
fan(s) will not start until the evaporator coil reaches and maintains +20°F. Further, the evaporator fans may
cycle "on" and "off" several times until the evaporator coil reaches and maintains +20°F.
Refrigeration Controller
All Refrigeration Systems up to and including 100 series, designed for indoor installations, are equipped with
conventional temperature thermostats that sense the "cut-in" and "cut-out" temperatures of the return air to
the evaporator coil. These thermostats are adjustable and require a turn of the dial to change the interior
storage temperature. Note: The control can be reached through the interior louver for adjustment, with
a 6” long shaft flat blade screwdriver. Make adjustments in small increments until the desired
temperature is reached.
Note: Some models may have a programmable control used in place of the time switch. This unit is used to
control the temperature and the defrost settings. Please see the separate instructions that are included on the
operation of this control.
8
All low temperature 150 series refrigeration systems, for
indoor and outdoor installation
cycle" which permits the compressor to pump most of the
refrigerant from the evaporator into its receiver after each
"on" cycle. In this application, the refrigeration controller
regulates the operation of a solenoid valve in the liquid line.
A low-pressure control is installed in the low side of the
system that shuts down the compressor due to low
pressure, which results when the solenoid valve closes the
liquid line. The temperature thermostat is adjustable and
requires a turn of the dial to change the interior storage
temperature.
Drain Tube Heater
All low temperature, ceiling mounted Refrigeration Systems employ a low wattage, electric heater strip. This
heater is spirally wound around the condensate drain tube that extends from the drain pan below the
evaporator coil to the evaporator section housing wall. This heater is energized continually to provide positive
discharge of the condensate moisture to the hot gas vaporizer. The heater and drain tube are covered with an
insulated tape.
, employ a "pump-down
EXTRA LOW TEMPERATURE SYSTEMS – CPX150DC & CPX151DC
These units are equipped with a “Hot Gas By-Pass” defrost system. Defrosting of the evaporator coil and
evaporator drain pan is accomplished by pumping hot refrigerant gas directly into the drain pan defrost loop
and the evaporator coil bypassing the condenser.
A programmable control is used in place of a time switch in these models to control the temperature and the
defrost settings. The programmable control can be found mounted to the control box under the condensing
unit cover. The control is preset at the factory for the operating temperature and the number of defrosts.
Please see the separate instructions that are included on the operation of this control.
Note: Some models may have a programmable control used in place of the temperature control. This unit is
used to control the temperature and the defrost settings. Please see the separate instructions that are
included on the operation of this control.
9
MAINTENANCE
WARNING: When servicing any Refrigeration System or performing any maintenance procedure,
always disconnect the main power supply.
The condensing unit, condensate vaporizer, and the control box on low temperature models are all accessible
by removing the grills or louvers on the condensing unit housing. The evaporator coil section is accessible by
unlatching and removing the evaporator section housing cover. For access to the fan blade(s) and for oiling
the fan motor on some models, remove the louver on the walk-in ceiling.
Cleaning the Condenser
The efficiency of the condensing unit, to a great
extent, depends upon the passage of air freely
through the condenser. For this reason, the
condensing unit should be as clean as possible at all
times and should always have an unrestricted supply
of air.
Cleaning the condenser should be done at a
minimum of every 3 months.
A wire brush should be used to loosen the
accumulation of dust and dirt particles that have attached to the fins of the condenser. Once this
accomplished, a vacuum cleaner can be used to remove the loosened particles. If compressed air is used to
clean the condenser, the air should be directed through the condenser from the fan motor side. Wipe away
any accumulated dust from the compressor motor and related parts.
Lubrication
The evaporator fan motor(s) on ceiling mounted systems 100 series and larger, should be oiled with a good
grade of S.A.E. #20 oil every six months. Evaporator fan motors on ceiling mounted systems less than 100
series and on the ceiling mounted CPX100 model do not require additional oiling.
Evaporator Drain Pan Removal - Ceiling Mounted Models
Remove the drain pan retainer that is located near the end of the drain pan opposite the drain tube. It is
secured by a thumbscrew. Release the drain tube stub from the drain discharge tube and remove the pan. On
freezer models, a drain pan heater is secured to the drain pan bottom by short brackets. Only a slight effort is
required to release the heater element from the brackets. When replacing the drain pan, make sure that the
drain pan stub is properly connected to the drain discharge tube. When replacing the drain pan, the drain tube
must be siliconed to prevent water leakage.
Hot Gas Vaporizer Pan
Condensate from the evaporator pan is discharged into a hot gas vaporizer pan, which is located in the
condensing unit housing. Here the hot discharge gas from the compressor elevates the temperature of the
water and it vaporizes into the atmosphere. This pan should be cleaned periodically to remove solids that
remain after the moisture is evaporated.
10
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.