Norlake AR164-A Owner’s Manual

1
COLD WALL EVAPOR ATOR
Inspection
2
Installation
2
General
2
Location
2
Electrical
2
General Operation
3
General Maintenance
3
Periodic Cleaning
3
Maintenance Service and Analysis Guide
4
MILK COOLERS
Installation, Operation and
Maintenance Instructions
TABLE OF CONTENTS
03/13 004728 Rev. E
2
INSPECTION
When the equipment is received, all items should be carefully checked against the bill of lading to insure all crates and cartons have been received. All units should be inspected for concealed damage by uncrating the units immediately. If any damage is found, it should be reported to the carrier at once, and a claim should be filed with the carrier. This equipment has been inspected and tested in the Manufacturing Facility and has been crated in accordance with transportation rules and guidelines. Manufacturer is not responsible for freight loss or damage.
INSTALLATION
GENERAL
After crate base has been removed, locate the casters and mounting bolts found in the interior of the cabinet. Attach the casters to the caster supports with the (16) self-tapping bolts provided. A power driver must be used to accomplish this. The cabinet may be tipped to a 30 degree angle to allow adequate space for mounting the casters. Precaution must be taken to keep the cabinet from tipping over or moving during this procedure. The cabinet must be allowed to sit a minimum of one hour in its normal upright position before power can be applied.
LOCATION
The self contained refrigeration system located at the bottom of the cabinet requires free air access for proper operation. These guidelines must be followed for cabinets with casters or legs. The two door cabinets must have a clearance of four inches at each side and the rear and open at the top and front. The four door cabinets must have a clearance of four inches at each side and open at the top, front and rear.
ELECTRICAL Check the proposed outlet to be used to insure that the voltage, phase, and current
carrying capacity of the circuit from the electrical panel correspond to the requirements of the cabinet. NEVER use an extension cord to power any unit. All inter wiring between the electrical panel and the unit must be done in accordance with the National Electric Code and all state and local codes. Refer to the Serial Tag for all pertinent electrical information.
Observe all Warning Labels. Disconnect power supply to eliminate injury from electrical shock or moving parts when servicing equipment.
03/13 004728 Rev. E
Loading...
+ 2 hidden pages