Norlake AR081 Installation Manual

MILK COOLERS
Installation, Operation, and
Maintenance Instructions

INSPECTION

When the equipment is received, all items should be carefully checked against the bill of lading to insure all crates and cartons have been received. All units should be inspected for concealed damage by uncrating the units immediately. If any damage is found, it should be reported to the carrier at once, and a claim should be filed with the carrier. This equipment has been inspected and tested in the Nor-Lake Manufacturing Facility and has been crated in accordance with transportation rules and guidelines. Manufacturer is not responsible for freight loss or damage.

INSTALLATION

LOCATION

The self-contained refrigeration system located on the side of the cabinet requires free air access for proper operation. There must be a minimum four-inch clearance between the sides of the compressor compartment and building wall or other equipment.

Physical Specifications

Unit Exterior Dimensions
Model Width x Depth x Height*
AR081 47 1/4” 32 3/4” 33 1/4” AR121 61 1/4” 32 3/4” 33 1/4” AR161 75 1/4” 32 3/4” 33 1/4”
Note: Height dimension includes casters.
NOTE:
If one door is flipped open, the total door assembly may be slid from end to end for ease of accessibility and loading. The total door assembly is also completely removable. However, care must be taken when repositioning the door assembly on the cabinet to insure the correct door is on the correct end of the cabinet, because the location of the locating pins on the interior of the doors is different.
8/06 134682

ELECTRICAL

Check the proposed outlet to be used to insure that the voltage, phase, and current carrying capacity of the circuit from the electrical panel correspond to the requirements of the cabinet. NEVER use an extension cord to power any unit. All wiring between the electrical panel and the unit must be done in accordance with the National Electric Code and all state and local codes. Refer to the Electrical Data below and the Serial Tag for all pertinent electrical information.
Observe all Warning Labels. Disconnect power supply to eliminate injury from electrical shock or moving parts when servicing equipment.

Electrical Data

Unit Type of Plug
Connection Configuration Volt/Hz/Ph
Model AR081 Cord L-15P See Serial Tag
AR121 Cord L-15P See Serial Tag AR161 Cord L-15P See Serial Tag

GENERAL OPERATION

The milk coolers are cooled entirely by forced air evaporator. During the refrigeration process, heat is removed through the evaporator tubing and expelled through the condensing unit. It is important that the flow of air through the side louvers is not restricted in order to ensure the condensing unit operates properly. Under normal operating conditions, any frost that might accumulate on the walls during the "on" cycle of the condensing unit may melt during the "off" cycle. Drains are installed in all milk coolers to accommodate melting frost.
The refrigeration system on this cabinet utilizes a programmable temperature controller to control the temperature and defrost settings. The controller, which is located in the condensing unit enclosure, is factory set. Please see the default settings sheet and separate instructions that are included on the operation of this controller.
During the operation of the refrigeration unit, frost will periodically form on the evaporator coil surface. Each time the compressor cycles “off”, the evaporator fans will continue to run, which will keep the internal temperature uniform and, at the same time, remove any frost build up on the coil. The water produced will collect in the condensing unit drain pan and evaporate.
2
Loading...
+ 3 hidden pages