Nordyne R-410A, X24K, X36K, X48K, P5RF-X24K User Manual And Installation Instructions

...
USER’S MANUAL AND INSTALLATION INSTRUCTIONS
15 SEER 2-Stage R-410A Single Package Air Conditioner
Single Package Air Conditioner
IMPORTANT
Read this owner information to become familiar with the capabilities and use of your appliance. Keep this with literature on other appliances where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your installing contractor or distributor in your area.
INTRODUCTION
Most any air conditioner will keep you cool. Our air conditioner was designed to do it effi ciently. Effi ciency means less cost to you while keeping you comfortable.
WHY YOUR AIR CONDITIONER WORKS SO WELL, SO QUIETLY
1. Air is cooled by a large evaporator coil. Moisture is also removed from the air by this same coil.
2. Air is then delivered through the main duct, via registers, into your home.
3. Return air is drawn through the return register.
4. This air enters the unit, passes through the evaporator coil, is cooled and dehumidi­fi ed. Then the cycle begins again.
2
SECTION 1. OWNER INFORMATION
OPERATING INSTRUCTIONS
To Operate Your Air Conditioner for Cooling—
Thermostat — The 15 SEER Air Conditioner
uses a special two speed compressor to achieve a high level of effi ciency in a compact frame. A two stage cooling 24VAC thermostat can be used with these units. For the highest effi ciency the use of a two-stage cooling thermostat is recommended. Refer to Figure 11 or 12 for a unit wiring diagram.
Cooling Mode:
1. On a call for cooling the thermostat closes, applying 24VAC to the G and Y1 terminals on the control. This closes the compressor contactor, and the compressor operates on 1st stage.
2. If the thermostat is not satisfi ed in the required time, based on the operation of the two-stage cooling thermostat, Y2 will
The indoor blower will cycle on and off to maintain the indoor temperature at the desired heating level.
To Shut Off Your Air Conditioner —Set the thermostat system switch to OFF and the thermostat fan switch to AUTO. (See Figure 1)
The system will not operate, regardless of the thermostat temperature setting.
To Operate the Indoor Blower Continuously—
Set the thermostat fan switch to ON (See Figure 1)
The indoor blower will start immediately, and will run continually until the fan switch is reset to AUTO.
The continuous indoor blower operation can be obtained with the thermostat system switch set in any position, including OFF. The continuous indoor blower operation is typically used to circulate the indoor air to equalize a temperature unbalance due to a sun load, cooking, or fi replace operation.
BEFORE YOU CALL A SERVICEMAN
Let your serviceman check your system at the start of each air conditioning season. He will make sure it’s working right, clean or change fi lters and make any needed adjustments.
System Mode
energize and the compressor will run at second stage. Refer to the thermostat installation instructions for the cooling profi le.
3. When the thermostat is satisfi ed, the G and Y terminals on the control board are de-energized opening the compressor contactor.
To Operate Your Unit for Heating — (If optional heat accessory is installed.)
1. Set the thermostat system switch to HEAT or
AUTO and the thermostat fan switch to AUTO.
(See Figure 1)
2. Set the thermostat temperature to the desired
temperature level using the temperature selector. Please refer to the separate user’s manual for complete thermostat programming instructions.
Fan Mode
Figure 1. Typical Thermostat
Temperature Selector
In addition, follow these simple rules:
1. Never run your system without fi lter. If you do, the cooling coils will get dirty and may become clogged.
2. Set your thermostat at the comfort level you wish -- and then leave it alone. Let it control the operation of the air conditioning system. If you get chilly, turn it up a degree at a time until comfort is restored.
3. It takes longer for an air conditioner to cool your dwelling than it does for your furnace to heat it. Therefore, do not turn the unit on and expect a dramatic drop in temperature, at least not right away. If your home is hot and humid, the temperature will drop slowly.
4. Check your fi lters every ten days in summer to see if they are dirty. To keep them clean, use a mild solution of detergent and water on washable types. Replace non washable fi lters.
5. Keep your outdoor condenser coil clean. You can hose it down when it gets dirty.
If your air conditioner isn’t working:
1. Make sure the fuses are not blown or that your circuit breakers are on.
2. See that your thermostat is set at the desired temperature and that your system’s switch is on “Cool.”
3
3. For free air fl ow, make sure your return register is not covered and that the fi lter is clean.
4. Check the outdoor condenser coil and make sure it is clean and not clogged with grass or leaves.
If your air conditioner still isn’t working, call your nearest distributor.
SECTION 2. INSTALLER INFORMATION
GENERAL Read the following instructions completely
before performing the installation.
These instructions are for the use of qualifi ed personnel specially trained and experienced in the installation of this type of equipment and related system components. Some states require installation and service personnel to be licensed. Unqualifi ed individuals should not attempt to interpret these instructions or install this equipment.
The single packaged air conditioners are de­signed for outdoor installation only and can be readily connected into the high static duct system of a home. The only connections needed for installation are the supply and return ducts, the line voltage, and thermostat wiring. A complete air conditioning system typically consists of:
• Single Package Air Conditioner
• Home Fittings Kit
• Unit Fittings Kit
• Thermostat
The single package air conditioner is completely assembled, factory wired, and factory run tested. The units are ready for easy and immediate installation.
PRE-INSTALLATION CHECK
Before any installation is attempted, the cool­ing load of the area to be conditioned must be calculated and a system of the proper capacity selected. It is recommended that the area to be conditioned be completely insulated and vapor sealed.
The installer should comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedence over any recom­mendations contained in these instructions. Consult local building codes and the National Electrical Code (ANSI CI) for special installation requirements.
4
The electrical supply should be checked to de­termine if adequate power is available. If there is any question concerning the power supply, contact the local power company.
Inspecting Equipment: All units are securely packed at the time of shipment and, upon arrival, should be carefully inspected for damage. Claims for damage (apparent or concealed) should be fi led immediately with the carrier.
CAUTION:
This unit uses refrigerant R-410A. Do NOT under any circumstances use any other refrigerants besides R-410A in this unit. Use of another refrigerant
will damage this unit.
WARNING:
Single Packaged Air Conditioners are shipped fully charged with R-410A refrigerant and ready for installation. When a system is installed according to these instructions, no refrigerant charging is required. If repairs make it necessary for evacuation and charging, it should only be done by qualifi ed, trained personnel thoroughly familiar with this equipment. Some local codes require licensed installation service personnel to service this type of equipment. Under no circumstances should the owner attempt to install and/or service this equipment. Failure to comply with this warning could result in property damage, personal injury or
death.
INSTALLATION
1. SELECT THE BEST LOCATION FOR THE AIR COND ITIONING UNIT
IMPORTANT: DO NOT PLACE UNIT UNDER THE HOME.
• Select a solid, level position, preferably on a
concrete slab, slightly above the grade level, and parallel to the home.
• The hot condenser air must be discharged
up and away from the home, and if possible, in a direction with the prevailing wind.
• Do not place the unit in a confi ned space.
6 ft.
a. Remove the bands from around the unit. b. Unfold the top and bottom cap fl anges. c. Carefully remove the top cap and tube.
24"
3. CLEARANCES
Minimum clearances, as specifi ed in Figure
2, MUST be maintained from adjacent struc­tures to provide room for proper servicing and air circulation.
12"
12"
Figure 2. Minimum Unit Clearances
• If practical, place the air conditioner where it and the ducts will be shaded from the afternoon sun when the heat load is greatest.
• Try to select a site for the unit that is as close as possible to the proposed return grille loca­tion.
• Keep in mind that the length of the supply and return ducts should be kept to a minimum with no sharp radius bends.
2. UNPACK THE UNIT
It is recommended that the unit be unpacked at the installation site to minimize damage due to handling.
CAUTION:
Do not tip the unit on its side. Oil may enter the compressor cylinders and cause starting trouble. If unit has been set on its side, restore to upright posi­tion and do not run for several hours. Then run unit for a few seconds. Do this three or four times with fi ve minutes between runs.
Do NOT install unit in a confi ned or recessed area that will allow discharge air from the unit to re-circulate into the condenser air inlet, through the coil.
Service Access Clearance:
Blower access panel side ........................... 24”
Electrical compartment access panel side .. 12” Clearance between overhang and top of
unit .............................................................72”
Clearance around condenser coil area to wall
or shrubs (excludes duct panel side) ..........12”
Minimum clearance to combustible materials:
Combustible Base (Wood or Class A, B, or C
roof Covering material) .............................. 0”
Supply and Return Air Ducts ...................... 0”
Duct Connection side ................................. 0”
DUCT REQUIREMENTS
The supply duct system, including the number and type of registers, will have much more ef­fect on the performance of an air conditioning system then any other factor. The duct must be suffi ciently large to conduct an adequate amount of air to each register.
Transition Duct Screws
Supply Air
14” Duct Dimples
Return Air
Figure 3. Return and Supply Air Fittings
Figure 4. Return Air Box
5
Loading...
+ 11 hidden pages