Nordyne Upfl ow/Horizontal, G7XA, G7XA046-A, G7XA061-B, G7XA076-B Installation Instructions Manual

...
Page 1
GAS FURNACE
Installation Instructions
G7XA Series - Single Stage High Effi ciency Furnace
80+ AFUE
Upfl ow/Horizontal Model
WARNING:
• PROPOSITION 65 WARNING: This product contains chemicals known to the state of California to cause cancer, birth defects or other reproductive harm.
• This furnace is not approved for installation in mobile homes. Installing this furnace in a mobile home could cause fi re, property damage, and/or personal injury.
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your customer. This includes being able to install the product according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product. Safety should always be the deciding factor when installing this product and using common sense plays an important role as well. Pay attention to all safety warnings and any other special notes highlighted in the manual. Improper installation of the furnace or failure to follow safety warnings could result in serious injury, death, or property damage.
These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Please read all instructions carefully before starting the installation. Return these instructions to the customer’s package for future reference.
WARNING:
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly could result in serious injury or property damage.
• Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
• Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a
neighbors phone. Follow the gas suppliers instructions.
• If you cannot reach your gas supplier, call
the fi re department.
DO NOT DESTROY THIS MANUAL
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
Page 2
2
Page 3
TABLE OF CONTENTS
SAFETY INFORMATION .............................................4
REQUIREMENTS AND CODES .................................. 4
GENERAL INSTRUCTIONS ........................................ 4
Combustion Air Quality ...........................................4
Clearances to Combustible Materials .....................4
Installation in a Garage ...........................................6
Heating Load ...........................................................6
COMBUSTION AIR REQUIREMENTS .......................6
General Information ................................................6
Installation in a Confi ned Space ..............................6
Air From Inside ...................................................6
Outdoor Air Using a Crawl Space or
Vented Attic ........................................................ 6
Outdoor Air Using Vertical Ducts ........................7
Outdoor Air Using Horizontal Ducts ...................7
Air Directly Through an Exterior Wall .................7
Installation in an Unconfi ned Space ........................ 8
VENTING REQUIREMENTS ........................................8
Category I Venting ...................................................8
CIRCULATING AIR REQUIREMENTS ........................9
Plenums and Air Ducts ............................................ 9
Supply Air Connections ...........................................9
Return Air Connections ...........................................9
Side Return Installations .....................................9
Bottom Return Installations ................................. 9
FURNACE INSTALLATION ....................................... 10
General Requirements .......................................... 10
Upfl ow Installation ................................................. 10
Side Return Air Inlet ......................................... 10
Bottom Return Air Inlet .....................................10
Horizontal Installation ............................................ 10
Bottom Panel Removal ..................................... 10
Alternate Bottom Panel Removal ..................... 11
GAS SUPPLY AND PIPING ....................................... 11
Leak Check ........................................................... 11
High Altitude Application........................................ 12
Conversion to LP/Propane ....................................13
ELECTRICAL WIRING ............................................... 13
Low Voltage Wiring ................................................ 13
Line Voltage Wiring ................................................13
Twinning ................................................................. 14
Grounding .............................................................. 15
START-UP & ADJUSTMENTS ...................................15
Pre-Start Checklist ................................................15
Start-Up Procedures ..............................................15
Verifying and Adjusting Input Rate ........................15
Verifying and Adjusting Temperature Rise .............16
Verifying Burner Operation ....................................16
Verify Operation of the Supply Air Limit Switch .....16
OPERATING SEQUENCE .........................................17
Heating Cycle ........................................................17
Cooling Cycle ........................................................17
Fan Mode ..............................................................17
MAINTENANCE .........................................................17
Air Filters ...............................................................17
Blower Compartment ............................................17
Cleaning of Burners ..............................................18
Cleaning of Flue Passages ...................................18
Heat Exchanger and Burner Maintenance ............18
Lubrication ............................................................18
Vent System ..........................................................19
DESCRIPTION OF COMPONENTS ..........................19
TROUBLESHOOTING ...............................................20
FIGURES AND TABLES ............................................21
Figure 16 - Furnace Dimensions ......................21
Airfl ow Data ...........................................................22
Table 5 - Maximum Airfl ow and Temp Rises .....22
Electrical Information.............................................24
Figure 17 - Wiring Diagram ..............................24
Gas Information .....................................................25
Table 6 - Gas Flow Rates.................................25
Table 7 - Gas Pipe Capacities .........................25
Table 8 - High Altitude Deration Chart for
Natural Gas .......................................26
Table 9 - High Altitude Deration Chart for
Propane Gas .....................................26
Location of Furnace Components .........................27
Figure 18 - Upfl ow/Horizontal Gas Furnace
Components ..................................27
INSTALLATION/PERFORMANCE CHECKLIST .......28
3
Page 4
SAFETY INFORMATION
Safety markings are used frequently throughout this
manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
WARNING:
The safety information listed below must be followed during the installation, service, and operation of this furnace. Failure to follow safety recommendations could result in possible damage to the equipment, serious per
injury or death
• Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
• Install this furnace only in a location and position as specifi ed in Table 1 (page 5).
• Provide adequate combustion and ventilation air to the furnace space as specifi ed on pages 6 - 8.
• Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specifi ed on page 8.
• Never test for gas leaks with an open fl ame. Use a commercially available soap solution to check all connections (page 11).
• This furnace is designed to operate with a maximum external pressure rise of 0.5 inches of water column. Consult Table 5 (pages 22 - 23), and the rating plate for the proper circulating air fl ow and temperature rise. NOTE: It is important that the duct system be designed to handle the desired fl ow rate and temperature rise. An improperly designed duct system can result in nuisance shutdowns, and comfort or noise issues.
• When supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See page 9.
• A gas-fi red furnace for installation in a residential garage must be installed as specifi ed on page 6.
.
sonal
GENERAL INSTRUCTIONS
Combustion Air Quality
CAUTION:
Combustion air must not be drawn from a corrosive atmosphere.
To maximize heat exchanger life, the combustion air must be free of chemicals that can form corrosive acidic compounds in the combustion gases. The recommended source of combustion air is to use outdoor air. However, the use of indoor air in most applications is acceptable except as listed:
• If the furnace is installed in a confi ned space it is required that the necessary combustion air come from the outdoors by way of attic, crawl space, air duct, or direct opening. For installations in confi ned spaces, see pages 6 - 7 for combustion air requirements.
• Installation in these locations may require outdoor air for combustion, due to chemical exposures:
Commercial buildings Buildings with indoor pools Furnaces installed in laundry rooms Furnaces installed in hobby or craft rooms Furnaces installed near chemical storage areas
• Exposure to the following substances in the combustion air supply may require outdoor air for combustion:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine based swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon Tetrachloride Halogen type refrigerants Cleaning solvents (Perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric Acid Cements and glues Antistatic fabric softeners Masonry acid washing materials
REQUIREMENTS AND CODES
This furnace must be installed in accordance with these instructions, all applicable local building codes or the current revision of the International Fuel Gas Code.
Any additional codes shown are for reference purposes only and do not necessarily have jurisdiction over local or state codes. Always consult with local authorities before installing any gas appliance.
4
Clearances to Combustible Materials
Access for positioning and servicing the unit must be considered when locating unit. The need to provide clearance for access to panels or doors may require clearance distances over and above the requirements.
Allow 24 inches minimum clearance from the front of the unit. However, 36 inches is strongly recommended.
Specifi c clearance information can be found on the furnace rating plate.
Page 5
UPFLOW/HORIZONTAL INSTALLATION CLEARANCES*
Left Side .................0 Inches Back ...........................0 Inches
Right Side ............. 0 Inches Top .............................0 Inches
Vent ...........................1 Inch
*
Allow 24 in. minimum clearance for servicing.
Recommended clearance is 36 in.
The IFGC requires that single wall metal vent connectors
must maintain a minimum 5” clearance to combustibles, including the outer casing of the furnace.
NOTE: This furnace is listed for installation on combustible or non-combustible fl ooring. However, wood is the only combustible fl ooring allowed for installation.
Front......................... 4 Inches
Table 1. Minimum Clearances to Combustible Materials
WARNING:
TOP
LEFT SIDE
BOTTOM
HORIZONTAL APPLICATION
UPFLOW APPLICATION
RIGHT SIDE
SIDE
TOP
BOTTOM
SIDE
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system
being placed into operation could result in carbon monoxide poisoning or death. The following steps shall be followed with each individual appliance connected to the venting system being placed in operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National
Fuel Gas Code, ANSI Z223. 1/NFPA 54 or the CSA B149.1, Natural Gas and Propane Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage,
corrosion and other defi ciencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fi replace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the fl ame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fi replace dampers and any other gas-fi red burning appliance to their previous conditions of use.
5
Page 6
Installation in a Garage
WARNING:
Do not place combustible material on or against the furnace cabinet or within 6 inches of the vent pipe. Do not place combustible materials, including gasoline and any other fl ammable vapors and liquids, in the vicinity of the furnace.
This Gas-fi red furnace may be installed in a residential garage with the provision that the burners and igniter are located no less than 18 inches (457mm) above the fl oor. The furnace must be located or protected to prevent physical damage by vehicles.
Heating Load
The ductwork should be appropriately sized to the capacity of the furnace to ensure its proper airfl ow rating. For installations above 2,000 ft., the furnace should have a sea level input rating large enough that it will meet the heating load after deration for altitude. Excessive
oversizing of the furnace could cause the furnace and/or vent to fail prematurely.
COMBUSTION AIR REQUIREMENTS
Provisions must be made during the installation of this furnace that provide an adequate supply of air for combustion.
Installation In A Confi ned Space
A confi ned space is an area with volume less than 50 cubic feet per 1,000 Btuh of the combined input rates of all appliances drawing combustion air from that space. Furnace closets, small equipment rooms and garages are confi ned spaces. Furnaces installed in a confi ned space which supply heated air to areas outside the space must draw return air from outside the space and must have the return air ducts tightly sealed to the furnace.
NOTE: The required sizing of these openings is determined by whether inside or outside air is used to support combustion, the method by which the air is brought to the space, and by the total input rate of all appliances in the space. In all cases, the minimum dimension of any combustion air opening is 3 inches.
Air From Inside If combustion air is taken from the heated space, the two openings must each have a free area of at least one square inch per 1,000 Btuh of total input of all appliances in the confi ned space, but not less than 100 square inches of free area (Figure 1). See example.
Example:
If the combined input rate of all appliances is less than or equal to 100,000 Btuh, each opening must have a free area of at least 100 square inches. If the combined input rate of all appliances is 120,000 Btuh, each opening must have a free area of at least 120 square inches.
General Information
• Instructions for determining the adequacy of an installation can be found in the current revision of the IFGC.
Consult local codes for special requirements.
CAUTION:
Exhaust fans, clothes dryers, fi replaces and other appliances that force air from the house to the outdoors can create a negative pressure inside the house, resulting in improper furnace operation or unsafe conditions such as fl ame roll out. It is imperative that suffi cient air exchange with the outdoors is provided to prevent depressurization.
• Air openings on top of the furnace and in closet doors or walls must never be restricted. If the furnace is operated without adequate air for combustion, the fl ame roll-out switch will open, turning off the gas supply to the burners. This safety device is a manually reset
switch. DO NOT reset or install jumper wires across this switch to defeat its function without identifying and correcting the fault condition. If the switch must
be replaced, use only the correct sized part specifi ed in the Replacement Parts List provided online.
6
Vent or
Chimney
NOTES: Each opening must be at least 100 sq. in. or 1 sq. in. per 1,000 Btuh of total input rating, whichever is greater.
Openings must start at no more than 12 inches from the top and bottom of the enclosure.
Water Heater
Total Input Rating
(Btuh)
40,000 100 sq. In 12 inches 60,000 100 sq. In 12 inches
80,000 100 sq. In 12 inches 100,000 100 sq. In 12 inches 120,000 120 sq. In 13 inches 140,000 140 sq. In 14 inches 160,000 160 sq. In 15 inches
Minimum Free Area
(Each Opening)
12" Max.
Furnace
See Notes
12” Max.
See
Notes
Round Duct
Diameter
Figure 1. Combustion Air Drawn from Inside
Outdoor Air from a Crawl Space or Vented Attic When the openings can freely exchange air with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 Btuh of total appliance input.
Page 7
The openings shall exchange directly, or by ducts, with the outdoor spaces (crawl or attic) that freely exchange with the outdoors (Figure 2).
Ventilation louvers
Vent or
Chimney
Attic Insulation
at each end of attic
Outlet air duct must be at least 1 sq. in. per 4,000 Btuh of total input rating. Must
Water Heater
Furnace
extend above attic insulation
Inlet air duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.
Crawl Space
Ventilated Louvers for unheated crawl space
Figure 2. Combustion Air Drawn from a Crawl
Space or Vented Attic
Outdoor Air Using Vertical Ducts If combustion air is taken from outdoors through vertical ducts, the openings and ducts must have a minimum free area of one square inch per 4,000 Btuh of total appliance input. In installations drawing combustion air from a ventilated attic, both air ducts must extend above the attic insulation (Figure 3).
Ventilation Louvers at each end of attic
Vent or Chimney
Water Heater
Total Input Rating
(Btuh)
Attic
Insulation
Furnace
12" Max
Minimum Free Area
(Each Opening)
Outlet Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.
Inlet and Outlet Ducts must extend above attic insulation.
Inlet Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.
Round Duct
Diameter
40,000 100 sq. In 12 inches 60,000 100 sq. In 12 inches
80,000 100 sq. In 12 inches 100,000 100 sq. In 12 inches 120,000 120 sq. In 13 inches 140,000 140 sq. In 14 inches 160,000 160 sq. In 15 inches
Figure 3. Combustion Air Drawn from Outside
Through Vertical Ducts
Outdoor Air Using Horizontal Ducts If combustion air is taken from outdoors through horizontal ducts, the openings and ducts must have a minimum free area of one square inch per 2,000 Btuh of total appliance input (Figure 4).
Vent or
Chimney
12" Max
-
-
-
-
-
-
-
-
-
-
-
See
Note
-
-
-
-
-
-
-
-
-
12" Max
Total Input Rating
(Btuh)
Water Heater
-
-
-
-
-
-
Air Duct
-
Furnace
-
-
-
-
-
-
-
-
Air Duct
-
Minimum Free Area
(Each Opening)
-
-
-
-
NOTE: Each
-
-
-
-
-
opening to outside must be at least 1 sq. in. per 2,000 Btuh of total
-
-
-
-
-
-
input rating.
-
-
-
Round Duct
Diameter
40,000 10 sq. In 5 inches 60,000 15 sq. In 6 inches
80,000 20 sq. In 7 inches 100,000 25 sq. In 8 inches 120,000 30 sq. In 9 inches 140,000 35 sq. In 10 inches 160,000 40 sq. In 10 inches
Figure 4. Combustion Air Drawn from Outside
Through Horizontal Ducts
Air Directly Through An Exterior Wall If combustion air is provided directly through an exterior wall, the two openings must each have free area of at least one square inch per 4,000 Btuh of total appliance input (Figure 5).
Vent or
12" Max
-
-
-
-
-
-
-
-
-
See
Note
-
-
-
-
-
-
-
-
-
12" Max
Total Input Rating
(Btuh)
40,000 10 sq. In 4 inches
60,000 15 sq. In 5 inches
80,000 20 sq. In 5 inches
100,000 25 sq. In 6 inches 120,000 30 sq. In 6 inches 140,000 35 sq. In 7 inches 160,000 40 sq. In 8 inches
Chimney
Furnace
Water Heater
Minimum Free Area
(Each Opening)
NOTE: Each opening
to outside must be at least 1 sq. in. per 4,000 Btuh of total input rating.
Round Duct
Diameter
Figure 5. Combustion Air Drawn from Outside
Through an Exterior Wall
7
Page 8
Installation In An Unconfi ned Space
An unconfi ned space is an area including all rooms not separated by doors with a volume greater than 50 cubic feet per 1,000 Btuh of the combined input rates of all appliances which draw combustion air from that space.
In general, a furnace installed in an unconfi ned space will not require outside air for combustion. However, in homes built for energy effi ciency (low air change rates), it may be necessary to provide outside air to ensure adequate combustion and venting, even though the furnace is located in an unconfi ned space. See example.
Example: A space with a water heater rated at 45,000 Btuh input and a furnace rated at 75,000 Btuh requires a volume of 6,000 cubic feet [50 x (45 + 75) = 6,000] to be considered unconfi ned. If the space has an 8 foot ceiling, the fl oor area of the space must be 750 square feet (6,000 / 8 = 750).
VENTING REQUIREMENTS
WARNING:
Upon completion of the furnace installation, carefully inspect the entire fl ue system both inside and outside the furnace to assure it is properly sealed. Leaks in the fl ue system can result in serious personal injury or death due to exposure of fl ue products, including carbon monoxide.
This furnace must be vented in compliance with the current revision of the International Fuel Gas Code and the instructions provided below. Consult local codes for
special requirements.
Category I Venting
This furnace is listed as a Category I vented appliance. Category I furnaces generally operate with a slight negative pressure (draft) and must be vented vertically or near vertically. Additionally it is important to guard against excessive condensation.
IMPORTANT NOTE: This furnace must never be vented to a chimney or fl ue that services a fi replace or other appliance designed to burn solid fuel. If the furnace vent is to be connected to a chimney serving a fi replace, the fi replace must be sealed off from the chimney.
WARNING:
Venting into an unlined masonry chimney or concrete chimney is prohibited. This may result in improper draft and excess condensation forming in the chimney.
• This furnace may be vented with a dedicated venting system or common vented with other Category I appliances. The vent system dimensions and material must conform to local Codes.
• The venting system should be designed to have the minimum number of elbows or turns. All horizontal runs shall slope upwards from the furnace at ¼ inch per running foot of vent. Supports for the vent pipe must be installed a minimum of every fi ve feet along the vent run to ensure no displacement after installation.
IMPORTANT NOTE: Under no circumstances shall any portion of the vent system extend into or pass through any return air duct, supply air duct, or plenum.
• Single wall vent connectors may be used under the limited capacity ranges found in the vent sizing tables.
It is recommended that Type “B” double wall vent be used for the connector whenever possible. An
existing masonry chimney should be inspected and relined if necessary.
• Single wall metal vertical vents shall not be used for
Category I venting. The furnace vent, if metal, may be insulated if local codes allow. Any part of the vent system, metal vent only, not exposed to weather, but which are exposed to temperatures below 35° F (1° C) must be insulated to prevent condensation. All vent insulation shall be foil backed fi berglass of one inch minimum thickness.
• Sheet metal fasteners should be used to secure the vent
pipe to the furnace fl ue.
• When an existing furnace is removed from a vent system
serving other appliances, the existing vent system may no longer be sized to properly vent the remaining appliances. An improperly sized venting system can result in the formation of condensate, leakage, or spillage. The existing vent system should also be checked to make sure it is in compliance with local codes. If it isn’t, the vent system must be brought into compliance before installing the furnace.
• Category I furnace installations must be connected to a factory built vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction.
8
Page 9
CIRCULATING AIR REQUIREMENTS
WARNING:
Do not allow combustion products to enter the
circulating air supply. Failure to prevent the circulation of combustion products into the living space can create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death.
All return ductwork must be secured to
the furnace with sheet metal screws. For installations in confi ned spaces, all return ductwork must be adequately sealed. When return air is provided through the bottom of the furnace, the joint between the furnace and the return air plenum must be air tight.
The surface that the furnace is mounted on must
provide sound physical support of the furnace with no gaps, cracks or sagging between the furnace and the fl oor or platform.
Return air and circulating air ductwork must
not be connected to any other heat producing device such as a fi replace insert, stove, etc. This may result in fi re, explosion, carbon monoxide poisoning, personal injury, or property damage.
Plenums and Air Ducts
• Supply and return air must be delivered to the furnace
by duct(s) secured to the furnace casing, running full size and without interruption.
• Table 5 (pages 22 - 23) contains the maximum airfl ow
and temperature rise data for each furnace input rate. NOTE: If the maximum airfl ow is 1,600 CFM or more, it is recommended that two openings be used for return air on upfl ow furnaces.
• It is recommended that the outlet duct contain a
removable access panel that is accessible when the furnace is installed in service. The opening shall be of a size that smoke or refl ected light may be observed inside the casing to indicate the presence of leaks in the heat exchanger. The cover for the opening shall be attached in such a manner as to prevent leaks.
• If outside air is used as return air to the furnace for
ventilation or to improve indoor air quality, the system must be designed so that the return air is not less than 60° F (15° C) during operation. If a combination of indoor and outdoor air is used, the ducts and damper system must be designed so that the return air supply to the furnace is equal to the return air supply under normal, indoor return air applications.
• If a cooling system is installed which uses the furnace
blower to provide airfl ow over the indoor coil, the coil
must be installed downstream (on the outlet side) of the furnace or in parallel with the furnace.
• If a cooling system is installed in parallel with the furnace, a damper must be installed to prevent chilled air from entering the furnace and condensing on the heat exchanger. If a manually operated damper is installed, it must be designed so that the furnace will not operate when the damper is in the cooling position or when in heating position, the cooling system is inoperable.
• It is good practice to seal all connections and joints with industrial grade sealing tape or liquid sealant. Requirements for sealing ductwork vary from region to region. Consult with local codes for specific requirements.
Supply Air Connections
To attach the supply air duct to the furnace, bend the furnace fl anges (Figure 16, page 21) upward 90° with wide duct pliers. Position the duct on top of the furnace and secure together with sheet metal screws. The screws must penetrate the sheet metal casing and furnace fl ange. Tape or seal all seams if required by local code.
Return Air Connections
For upfl ow installations, the return air ductwork may be connected to the left side, right side, or bottom. The bottom panel (Figure 16) must be installed for left or right return air. Do not use the back of the furnace for return air.
Side Return Installations
WARNING:
The solid base of the furnace must be in place when the furnace is installed with side return air ducts. Removal of all or part of the base could cause circulation of combustible products into the living space and create potentially hazardous conditions, including carbon monoxide poisoning that could result in personal injury or death.
To attach the return air duct to the left or right side of the furnace, punch out the four knockouts (Figure 16) from the preferred side of the furnace. Using sharp metal cutters, cut an opening between all four knockouts to expose the blower assembly. Position the return air duct over the opening in the side and secure together with sheet metal screws. The screws must penetrate the duct and furnace cabinet.
Bottom Return Installations The bottom panel (Figure 16) must be removed from the bottom of the furnace for bottom return air. Refer to pages 10 - 11 for removal instructions. Position the furnace over the return air duct and secure together with sheet metal screws. The screws must penetrate the duct and furnace cabinet.
9
Page 10
FURNACE INSTALLATION
G7XA series gas furnaces are shipped ready for installation in the upfl ow or horizontal right or left positions. Access for positioning and servicing must be considered when locating the unit. See Table 1 (page 5) for the required clearances needed to move the furnace to its installation point (hallways, doorways, etc).
WARNING:
The furnace must not be installed directly on carpeting, tile, or any combustible material other than wood fl ooring.
General Requirements
• The furnace must be leveled at installation and attached to a properly installed duct system. Refer to pages 8 - 9 for venting and circulating air requirements
• The furnace must be installed so that all electrical components are protected from water.
• The furnace must be installed upstream from a refrigeration system.
Upfl ow Installation
The furnace is shipped with the bottom panel installed. If furnace is installed horizontally, remove the bottom panel from the furnace before attaching the duct system. See Bottom Panel Removal section.
If the furnace will be suspended from the ceiling, assemble a support frame (Figure 7) using slotted iron channel and full threaded rod. Fasten the frame together with nuts, washers, and lockwashers. Secure the support frame to the rafters with lag bolts. The furnace can also be suspended using steel straps around each end of the furnace. The straps should be attached to the furnace with sheet metal screws and to the rafters with bolts.
If the furnace is to be installed in an attic, it is required that a drip pan be placed under the furnace. If the installation is on a combustible platform (Figure 6), it is recommended that the drip pan extend at least 12 inches past the top and front of the furnace.
Note: It is recommended for further reduction of fi re hazard that cement board or sheet metal be placed between the furnace and the combustible fl oor and extend 12 inches beyond the front of the door and top of the furnace.
Side Return Air Inlet This gas furnace is shipped with the bottom panel installed (Figure 16, page 21). If the upfl ow furnace is installed with side return air, the bottom panel must not be removed.
Bottom Return Air Inlet If the furnace is installed where the bottom is the return air inlet, the bottom panel must be removed. See Bottom Panel Removal section.
Horizontal Installation
This gas furnace can be installed horizontally in an attic, basement, crawl space or alcove (Figure 6). It can also be suspended from a ceiling in a basement or utility room in either a right to left airfl ow or left to right airfl ow as shown in Figure 7.
Electrical Supply
Connection
Type “B” Vent
Coil Plenum
Gas Inlet
Combustible Platform
Figure 6. *XA Horizontal Installation on a Platform
10
Nuts (x2)
Lag
Threaded
Rod
Washer
and
Lockwasher
Nuts (x2)
Bolt
Figure 7. *XA Horizontally Suspended
in Attic or Crawl Space
Bottom Panel Removal
The steps listed below explain how to remove the bottom
panel from the furnace. See Figure 8 (page 11).
1. Remove the door (1) from the blower compartment.
2. Disconnect the blower motor wiring harness (2) from the control board.
3. Remove two screws (3) securing the blower assembly (4) to the furnace.
4. Carefully pull the blower assembly (4) out thru the front of the furnace.
5. Remove all screws (5) securing bottom panel (6) to bottom of furnace and front brace (7).
6. Lift up and slide bottom panel (6) out through front of furnace.
7. Reinstall the blower assembly (4) in reverse order.
Page 11
1
Alternate Bottom Panel Removal
If the bottom panel cannot be removed using the previous instructions, the steps below are an alternate method for removing the bottom panel. See Figure 9.
1. Remove the door (1) from the blower compartment .
2. Remove all screws securing the bottom panel (2) to
the front brace (3).
3. Remove two screws (4) securing the furnace cabinet
to the blower deck (5).
4. Remove all screws (6) securing the furnace cabinet
to the bottom panel (2).
5. Remove the screw (7) securing the bottom corner of the
furnace cabinet to the front brace (3).
6. Carefully spread the bottom corner of the furnace
cabinet outwards while sliding the bottom panel (2) out through the front of the furnace.
7. Reassemble the furnace in reverse order.
3
4
6
Figure 8. Bottom Panel Removal
2
7
5
GAS SUPPLY AND PIPING
All gas piping must be installed in compliance with local codes and utility regulations.
IMPORTANT NOTES:
• Some local regulations require the installation of a manual main shut-off valve and ground joint union external to the furnace as shown in Figure 10 (page 12). The shut-off valve should be readily accessible for service and/or emergency use. Consult the local utility or gas supplier for additional requirements regarding placement of the manual main gas shut-off.
• Gas piping must never run in or through air ducts, chimneys, gas vents, or elevator shafts.
• Compounds used to seal joints on gas piping must be resistant to the actions of LP propane gas.
• The main gas valve and main power disconnect to the furnace must be properly labeled by the installer in case emergency shutdown is required.
• A drip leg should be installed in the vertical pipe run to the unit (Figure 10).
Table 7 (page 25) lists gas pipe capacities for standard pipe sizes as a function of length in typical applications based on nominal pressure drop in the line. Table 8 (page 26) contains the orifi ce sizes and manifold pressure at various altitudes for natural gas installations.
The furnace may be installed for either left or right side gas entry. A typical gas service hookup is shown in Figure
10. NOTE: When connecting the gas supply, provide
clearance between the gas supply line and the entry hole in the furnace casing to avoid unwanted noise and/or damage to the furnace.
4
1
5
7
2
3
Figure 9. Alternate Removal Method
Leak Check
WARNING:
FIRE OR EXPLOSION HAZARD Never test for gas leaks with an open fl ame. Check all connections using a commercially available soap solution. A fi re or explosion
6
may result causing property damage, personal injury or loss of life. Failure to follow the safety warnings exactly could result in serious injury, death or property damage.
After the gas piping to the furnace is complete, all connections must be tested for gas leaks. This includes pipe connections at the main gas valve, emergency shutoff valve and fl exible gas connectors (if applicable). Apply the soap and water solution on each joint or union using a small paintbrush. If any bubbling is observed, the connection is not sealed adequately and must be retightened. Repeat the tightening and soap check process until bubbling ceases.
11
Page 12
IMPORTANT NOTE: When pressure testing gas supply lines at pressures greater than 1/2 psig (14 inch W.C.), the gas supply piping system must be disconnected from the furnace to prevent damage to the gas control valve. If the test pressure is less than or equal to 1/2 psig (14 inch W.C.), close the manual shut-off valve.
High Altitude Application
The installation of this furnace at altitudes above 2,000 feet must meet the requirements of the International Fuel Gas Code or local codes. High altitude conversion of this furnace depends on the installation altitude and heating value of the gas (at sea level) from your local gas utility. NOTE: At high altitudes, the heating value is always lower than heating value at sea level.
The *XA furnace is shipped from the factory with orifi ces and gas regulator settings for natural gas operation at sea level. At 2,000 feet, this appliance needs to be derated 4% per 1,000 feet of altitude. For example, the input needs to
UPFLOW FURNACE
be reduced 8% at 2,000 feet, 12% at 3,000 feet, etc. This deration is in reference to the input rate and gas heating value at sea level.
WARNING:
The reduction of input rating necessary for high altitude installation may only be accomplished with factory supplied orifi ces. Do not attempt to drill out orifi ces in the fi eld. Improperly drilled orifi ces may cause fi re, explosion, carbon monoxide poisoning, personal injury or death.
From 2,000 to 5,000 feet, deration may be performed by adjusting the manifold pressure on the gas valve (see page 15). Above 5,000 feet, it is necessary to change both the orifi ce and manifold pressure. Table 8 (page 26) contains the manifold pressure and orifi ce sizes to use at various altitudes for natural gas installations.
1
RCYGW
STATUS
24V
See
Note
8
9 8 7
63 5 4
NEUTRALS
FAN
COOL
HEAT
FLAME
63
180
BLOWER
2
120
5
OFF
90
1
4
DELAY
60
L1A 2
1
XFMR
HIGH
LOW
HUM
EAC
MH
ML
L1
1
See
STATUS
FLAME
Note
180 120
OFF
90
DELAY
60
HIGH
LOW
EAC
MH
ML
8
9 8 7
63 5 4
NEUTRALS
RCYGW
24V
FAN
COOL
HEAT
63
BLOWER
2
5
1
4
L1A 2
1
XFMR
HUM
L1
4
3
7
5
2
6
Left Side Entry
ITEM # and COMPONENT
2
6
Right Side Entry
5
3
(1) Automatic Gas Valve
(w/ manual shut-off)
(2) Burner Assembly (3) Dripleg (4) Elbow
(5) Ground Joint Union (6) Manifold (7) Plug (8) Shut - Off Valve
NOTE: Some utilities require Shut- Off Valve to be 4 to 5 feet above fl oor.
12
Figure 10. Typical Gas Connection
Page 13
When deration is completed, it is required that you measure the gas input rate. This may be accomplished in the usual way, by clocking the gas meter and using the local gas heating value. NOTE: It will be necessary to check the input rate using the actual heating value, (which will be less) because the atmospheric pressure is also lower than sea level. See Verifying and Adjusting the Input Rate (page 15).
Conversion to LP/Propane
WARNING:
The furnace was shipped from the factory equipped to operate on natural gas. Conversion to LP/propane gas must be performed by qualifi ed service personnel using a factory supplied conversion kit. Failure to use the proper conversion kit can cause fi re, explosion, property damage, carbon monoxide poisoning, personal injury, or death.
Conversion to LP/propane is detailed in the installation instructions provided with the conversion kit. Generally, this will require the replacement of the burner orifi ces and the spring found under the cap screw on the pressure regulator.
The LP/Propane Gas Sea Level and High Altitude Conversion Kit (P/N 904923) is an approved conversion kit for LP/propane conversion at altitudes between zero and 10,000 ft. above sea level. If the installation is above 2,000 ft., refer to Table 9 (page 26) to determine the correct orifi ce size and manifold pressure. When conversion is complete, verify the manifold pressure and input rate are correct as listed in Table 9. Please follow the instructions
provided with the kit.
A/C CONDENSING UNIT
CONDENSING UNIT CONTROL BOX
EXPANSION PORT (MOTOR CONNECTION)
COM
ROOM
THERMOSTAT
Connect
R & W
For Heating
Only
NOTE: The “Y” terminal on the control board must be connected to the thermostat for proper cooling mode operation.
FIELD WIRING
LOW VOLTAGE
CONNECTION
R C Y G
W
NEUTRAL LEADS
3 AMP FUSE
9 8 7
6 5 4
NEUTRALS
Figure 11. Low Voltage Field, Four-wire
Heating/Cooling Applications
RCYGW
63 5 4
3
2
1
2
1
24V
SPEED
SELECT
FAN
HUM
STATUS
COOL
HEAT
FLAME
BLOWER
OFF
DELAY
XFMR
HIGH
EAC
MH
ML
L1
ELECTRONIC AIR CLEANER
HUMIDIFIER TAP
RED
GREEN YELLOW
180 120
90 60
LOW
MOTOR SPEED TAPS (NOT USED)
ELECTRICAL WIRING
Electrical connections must be in compliance with all applicable local codes. For electrical requirements, refer to Table 2 (page 14) or the furnace nameplate.
WARNING:
To avoid electric shock, personal injury, or death, turn off the electric power at the disconnect or the main service panel before making any electrical connections.
CAUTION:
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
NOTE: If replacing any of the original wires supplied with
the furnace, the replacement wire must be copper wiring and have a temperature rating of at least 105° F (40° C).
Low Voltage Wiring
The thermostat must be installed according to the instructions supplied by the thermostat manufacturer. The thermostat must not be installed on an outside wall or any other location where its operation may be adversely affected by radiant heat from fi replaces, sunlight, or lighting fi xtures, and convective heat from warm air registers or electrical appliances.
Low voltage connections (24 VAC) from the thermostat are wired to the terminal strip on the integrated control in the furnace. See Figure 11 for proper connections for heating only (two-wire) and heating/cooling (four-wire) applications. Recommended minimum wire gauge for thermostat wiring is shown in Table 2.
NOTE: Set the heat anticipator according to the instructions
supplied by the thermostat manufacturer. To determine the heat anticipator setting, perform the following steps:
1. Add the current draw of the system components; or
2. Measure the current fl ow on the thermostat R-W circuit after the circulating blower motor has started.
Line Voltage Wiring
It is recommended that the line voltage (230 VAC) to the furnace be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the furnace (Table 2).
IMPORTANT NOTES: An electrical disconnect must be installed readily accessible from and located within sight of the furnace. Any other wiring methods must be acceptable to authority having jurisdiction.
13
Page 14
Furnace
Model
Number
G7XA
046-23A 46,000
061-24B 61,000
076-24B 76,000
Furnace
Input
(Btu/hr)
Cabinet
Width
(in.)
¼
14 17 ½
17
½
Nominal
Electrical
Supply
Maximum Operating
Voltage
Minimum
Operating
Voltage
Maximum
Furnace
Amperes
Minimum
Wire
Gauge
230-50-1 230 208 6.3 14 15
230-50-1 230 208 9.7 14 20
230-50-1 230 208 9.7 14 20
092-35C 92,000 21 230-50-1 230 208 11.7 14 20
107-45D 107,000
24
230-50-1 230 208 15.2 12 30
½
** Time-delay fuses or HACR-type circuit breakers are required.
Recommended Thermostat Wire Length
Thermostat Wire Gauge
2 - wire
(Heating only)
4 or 5 wire
(Heating/Cooling)
24 55 ft. 25 ft. 22 90 ft. 45 ft. 20 140 ft. 70 ft. 18 225 ft. 110 ft.
Table 2. Wire Length and Voltage Specifi cations
Maximum
Fuse or Circuit
Breaker Amps**
Field Supplied
Fused Service
Panel
Black (Hot)
White (Neutral)
Field Supplied Disconnect w/in Sight of Furnace
Black
White
Green or Bare
(Ground)
Ground
Field Line Voltage Wiring
Figure 12. Line Voltage Field Wiring
Proper line voltage polarity must be maintained in order for the control system to operate correctly. Verify the incoming neutral line is connected to the white wire and the incoming “hot” line is connected to the black wire. The furnace will not operate unless the polarity and ground are properly connected as shown in Figure 12 or the wiring diagram label inside of the control door.
Junction Box (may be int. or ext. to the furnace). These connections can be made in the field supplied disconnect at the furnace.
Black
White
Ground
Field Supplied
Panel Connector
Factory Line Voltage Wiring
THERMOSTAT
WGYR
R C
G W
FURNACE
Black
White
Y
BOARD
Ground
R C Y G
W
FURNACE
BOARD
Twinning
The control boards on fi xed speed furnaces are capable of being twinned to other furnaces of the same series, only if the following criteria are met:
• The circuit boards are the same.
• The thermostat wires and the 1/4 inch thick quick-connect terminals marked “TWIN” (Figure 13) on the furnace controls must be connected together.
• The fuses must remain installed on each board.
• Twinned furnaces must be properly grounded according to local codes.
14
MOTOR
BOARD
TWIN TERMINAL
A/C
UNIT
MOTOR BOARD
TWIN TERMINAL
FURNACE 1 FURNACE 2
Figure 13. Twinning
IMPORTANT NOTE: G7 furnaces equipped with variable speed iSEER™ motors may not be twinned under any circumstances.
Page 15
Grounding
WARNING:
To minimize personal injury, the furnace cabinet must have an uninterrupted or unbroken electrical ground. The controls used in this furnace require an earth ground to operate properly. Acceptable methods include electrical wire or
conduit approved for ground service. Do not use gas piping as an electrical ground!
START-UP AND ADJUSTMENTS
Pre-Start Check List
Verify the polarity of the connections are correct, the
line voltage power leads are securely connected and the furnace is properly grounded.
Verify the thermostat wires (R, W, Y, and G) are
securely connected to the correct leads on the terminal strip of the circuit board.
Verify the gas line service pressure does not exceed
10.0 inches of W.C., and is not less than 4.5 inches W.C. for natural gas. For LP gas the line service pressure must not exceed 14 in. W.C., and must not be less than 11.0 in. W.C.
Verify the roll-out and manual reset switch is closed.
If necessary, press the red button to reset a switch. If a switch reopens on startup, DO NOT reset the switch without identifying and correcting the fault condition. DO NOT install a jumper wire across a
switch to defeat its function.
Verify the blower door is in place, closing the door
switch in the line voltage circuit.
Verify the gas line has been purged and all connections
are leak free.
Start-up Procedures
Do not perform these steps until all of the checks in the previous steps have been completed:
1. Set the thermostat to the lowest setting.
2. Turn off all electrical power to the furnace.
3. Follow the Operating Instructions on the label attached
to the furnace.
4. Set the thermostat above room temperature and verify
the Operating Sequence (Page 17).
5. After 5 minutes of operation, set the thermostat
below room temperature and verify steps 9 - 10 of the Operating Sequence.
1. Shut off all other gas fi red appliances.
2. Start the furnace and run it for at least 3 minutes.
3. Measure the time (in seconds) required for the gas meter to complete one revolution.
4. Convert the time per revolution to cubic feet of gas per hour using Table 6 (page 25).
5. Multiply the gas fl ow rate in cubic ft per hr by the heating value of the gas in Btu per cubic ft to obtain the input rate in Btuh. See example.
Example:
• Time for 1 revolution of a gas meter with a 1 cubic ft dial = 40 seconds.
• From Table 6 read 90 cubic ft gas per hr.
• Local heating value of the gas (obtained from gas supplier) = 1,040 Btu per cubic ft.
• Input rate = 1,040 x 90 = 93,600 Btuh.
6. The manifold pressure must be set to the appropriate value for each installation by a qualifi ed installer, service agency or the gas supplier.
WARNING:
Do not attempt to drill the gas orifi ces. Use only factory supplied orifices. Improperly drilled orifi ces may cause fi re, explosion, carbon monoxide poisoning, personal injury or death.
a.) Obtain the manifold pressure setting required for
this installation by referring to Table 8 (page 26) for Natural Gas or Table 9 for Propane gas
b.) Remove the regulator capscrew (Figure 14) from
the INLET side of the regulator.
c.) Slowly turn the adjustment screw inside the
regulator to obtain the appropriate manifold pressure. NOTE: Turning the screw clockwise increases the pressure and turning the screw counter-clockwise decreases the pressure. To prevent backing the screw all the way out from the valve, turn the screw slowly.
d.) Replace and tighten the regulator capscrew over
the adjustment screw.
Capscrew
Verifying and Adjusting Input Rate
The input rate must be verifi ed at installation to prevent over-fi ring of the furnace. The input rate must not exceed
the specifi cation listed on the furnace rating plate. At altitudes above 2,000 feet, it must not exceed that on the rating plate less 4% for each 1,000 feet. To determine
the exact input rate, perform these steps:
Figure 14. Regulator Capscrew
15
Page 16
Verifying and Adjusting Temperature Rise
Confi rm the temperature rise through the furnace is within the limits specifi ed on the furnace rating plate. Any temperature rise outside the specifi ed limits could result in premature failure of the heat exchanger.
1. Place thermometers in the retur n and supply air stream as close to the furnace as possible. The thermometer on the supply air side must be shielded from direct radiation from the heat exchanger to avoid false readings.
2. Adjust all registers and duct dampers to the desired position and run the furnace for 10 to 15 minutes before taking any temperature readings. The temperature rise is the difference between the supply and return air temperatures.
For typical duct systems, the temperature rise will fall within the limits specifi ed on the rating plate with the blower speed at the factory recommended setting. If the measured temperature rise is outside the specifi ed limits, it may be necessary to change the speed of the blower.
The *XA furnace is equipped with a multi-speed motor. Heating, cooling, and fan speed selection is made by moving the switch located on the motor control board (Figure 15). NOTE: Lowering the blower speed will increase the temperature rise and a higher blower speed will decrease the temperature rise.
W1
PORT
RCY1
DHUM
TWIN
FAN SPEED
1 2 345 6 7
OFF ON
HEAT
THERMOSTAT
COOL
TERMINAL TO
CONNECTION
TWIN FURNACES
8
NOT USED
CONNECTION TO
FURNACE CONTROL
RED
STATUS
GREEN
BOARD
NOT USED
EXPANSION
MOTOR WIRE
HARNESS
Verifying Burner Operation
CAUTION:
The door over the burners may only be open for inspection purposes only. The door must be installed during unattended operation.
1. Remove the burner compartment door.
2. Set the thermostat above room temperature and observe the ignition sequence. The burner fl ame should carry
over immediately between all burners without lifting off, curling, or fl oating. The fl ames should be blue, without yellow tips.
3. After validating the fl ame, change the thermostat setting to below room temperature.
4. Verify the burner fl ame is completely extinguished.
5. Replace the burner compartment door.
Verify Operation of the Supply Air Limit Switch
A properly functioning limit switch should turn off the gas valve when the return is blocked (time depends on how well the return air is blocked). The circulating air and combustion blowers should continue to run when the limit switch opens.
1. Verify the blower door is securely mounted in place
and that there is power to the furnace.
2. Block the return airfl ow to the furnace by installing
a close-off plate in place of or upstream of the fi lter(s).
3. Set the thermostat above room temperature and
observe the Operating Sequence (page 17).
4. Remove the close-off immediately after the limit
switch opens. If the furnace continues to operate with no return air, set the thermostat below room temperature, shut off the power to the furnace, and replace the limit switch.
Figure 15. Motor Control Board
16
Page 17
OPERATING SEQUENCE
The operating sequences for the heating, cooling, and fan modes are described below. Refer to the fi eld and furnace wiring diagrams: (Figure 11, page 13), (Figure 12, page 14), and (Figure 17, page 24).
Heating Cycle
1. The thermostat calls for heat by energizing the W terminal with 24VAC.
2. The control verifi es if the pressure switch is open.
3. If the pressure switch is open, the control energizes the inducer and waits for the pressure switch to close. The pressure switch must close within 10 seconds.
4. The control runs the inducer for a 30 second pre-purge.
5. The control energizes the igniter output for the appropriate warm-up time limit.
6. The control energizes the gas valve for 3 seconds.
7. If the fl ame proved and ignites the gas, the control de­energizes the igniter. The gas valve and inducer remains energized. The control goes to blower on delay.
8. If fl ame is present, the control energizes the blower on the selected HEAT speed 30 seconds after the gas valve opened. The gas valve and inducer remain energized.
9. When the thermostat demand for heat is satisfi ed, the control de-energizes the gas valve. The inducer output remains on for a 30 second post-purge period.
10. Blower off timing begins when the thermostat is satisfi ed. The control will operate at the selected HEAT speed of 60, 90, 120, or 180 seconds. If the blower off delay jumper is not present, the fan should still operate for 120 seconds at the selected HEAT speed. The Indoor blower motor is de-energized after a blower off delay as selected by the movable jumper.
Cooling Cycle
1. The thermostat calls for cooling by energizing the Y terminal with 24VAC.
2. The control energizes the blower (in cooling speed) and sends 24VAC to the contactor in the condensing unit.
3. When the thermostat removes the call for cooling, the contactor in the outdoor condensing unit is de­energized and the control continues to run the fan for a period of 60 seconds.
Fan Mode
• When the thermostat energizes the G terminal for
continuous fan (without calling for heat or cooling), the indoor fan is energized on the selected FAN speed.
• If a call for cooling occurs during continuous fan, the
blower will switch over to the selected COOL speed.
• If the W terminal receives a call for heat during continuous
fan, the blower will de-energize.
• A call for fan is ignored while in lockout.
MAINTENANCE
WARNING:
These maintenance instructions are primarily intended to assist qualified technicians experienced in the proper maintenance and operation of this appliance.
To prevent electric shock, personal injury, or death, disconnect the electric power before performing any maintenance.
Proper maintenance is most important to achieve the best performance from a furnace. Follow these instructions for years of safe, trouble free operation.
• Always replace the doors on the furnace after servicing or cleaning/changing the fi lters. Do not operate the furnace without all doors and covers in place.
• Verify the thermostat is properly installed and is not being affected by drafts or heat from lamps or other appliances.
• To achieve the best performance and minimize equipment failure it is recommended that a yearly maintenance checkup be performed. At a minimum, this check should include the following items.
Air Filter(s)
WARNING:
Never operate the furnace without a fi lter in place. Dust and lint in the return air can build up on internal components, resulting in loss of effi ciency, equipment damage, and possible fi re.
Air fi lter(s) are not supplied with the furnace as shipped from the factory. The installer must provide a high velocity fi lter and rack for a fi lter in the return air duct adjacent to the furnace, or in a return air grill to the furnace.
NOTE: It is recommended that fi lters be cleaned or replaced monthly. New or newly renovated homes may require more frequent changing until the construction dust has minimized. Filters designed to remove smaller particles such as pollen, may require additional maintenance. Filters for side return and bottom return applications are available from most local distributors.
Blower Compartment
Dirt and lint can create excessive loads on the motor resulting in higher than normal operating temperatures and shortened service life. It is recommended that the blower compartment be cleaned of dirt or lint that may have accumulated in the compartment or on the blower and motor as part of the annual inspection.
17
Page 18
Cleaning of Burners
If the burners must be cleaned, follow steps 1-12. Refer to Figure 18 (page 27) for component locations.
1. Shut off gas supply to the furnace at the meter or at a manual valve in the supply piping.
2. Turn off all power to the furnace and set the thermostat to its lowest setting.
3. Remove the burner door from the furnace.
4. Turn the gas control switch to the OFF position.
CAUTION:
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
5. Disconnect the wires from the gas valve, igniter, fl ame sensor, and fl ame rollout switch.
6. Using two wrenches, separate the ground-joint union in the gas supply piping at the furnace.
7. Remove the piping between the gas valve and the ground-joint union. (If applicable).
8. Remove all screws securing the burner assembly to the furnace.
9. Carefully remove the burner assembly from the furnace.
DO NOT DAMAGE THE IGNITER WHILE REMOVING THE BURNER ASSEMBLY.
10. Inspect the burners for accumulated dust or debris. If necessary carefully clean them with a soft wire brush and a vacuum cleaner. DO NOT DAMAGE THE
IGNITER WHILE CLEANING THE BURNER.
11. Replace all the parts in reverse order that they were removed.
12. Follow the lighting instructions found on the furnace door to return the furnace to operation. Verify proper operation after servicing.
Cleaning Of Flue Passages
If the fl ue passages must be cleaned, follow the steps below. Refer to Figure 18 for component locations.
1. Shut off the gas supply to the fur nace either at the meter or at the manual valve in the gas supply piping.
2. Turn off all power to the furnace and set the thermostat to the lowest temperature setting.
3. Remove the blower door from the furnace.
4. Turn the gas control switch to the OFF position.
5. Disconnect the wires from the gas valve, fl ame sensor, inducer, fl ame roll-out switch, limit switch, pressure switch and igniter.
6. Remove the silicone rubber tube from the inducer.
7. Using two wrenches, separate the ground-joint union in the gas supply piping at the furnace.
8. Remove the piping between the gas valve and the ground-joint union. (If applicable).
9. Remove all screws securing the burner assembly to the furnace.
10. Carefully remove the burner assembly from the furnace. DO NOT DAMAGE THE IGNITER WHILE
REMOVING THE BURNER ASSEMBLY.
11. Remove all screws securing the inducer assembly
to the vent pipe running out of the furnace.
12. Remove all screws securing the inducer assembly
to the collector pan.
13. Carefully remove the inducer assembly and
combustion tube assembly from the furnace.
14. Remove all screws securing the collector pan to the
furnace.
15. Remove the collector pan and gasket from the
furnace.
16. Attach a round wire brush to a length of high grade
stainless steel cable. Attach the other end of the cable to a variable speed reversible drill. Slowly insert the cable into the top portion of the heat exchanger. Operate the drill alternating between forward and reverse, working the cable in and out several times to obtain suffi cient cleaning. Repeat this sequence for each heat exchanger tube.
17. Remove all loosened debris from the heat exchanger
tubes using a vacuum cleaner.
18. Using a bright light, check the condition of the upper
and lower sections of the heat exchanger tubes.
19. Inspect the burners for accumulated dust or debris.
If burners must be cleaned, see Cleaning of Burners section.
20. Replace all the parts in reverse order that they were
removed.
21. Check gaskets for damage and replace if needed.
22. Follow the lighting instructions found on the furnace
door to return the furnace to operation. Verify proper operation after servicing.
Lubrication
The bearings in the blower motor and inducer blower used in these furnaces are pre-lubricated and sealed by the manufacturer. No further oiling of the bearings is required for the life of the motor.
Heat Exchanger and Burner Maintenance
The furnace should operate for many years without soot buildup in the fl ue passageways, however, the fl ue passageways, the vent system, and the burners should be inspected and cleaned (if required) by a qualifi ed service technician annually to ensure continued safe operation. Particular attention must be given to identify deterioration from corrosion or other sources.
18
Page 19
WARNING:
Holes in the vent pipe or heat exchanger can cause combustion products to enter the home. Replace the vent pipe or heat exchanger if leaks are found. Failure to prevent the circulation of combustion products into the living space can create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death.
Vent System
Check the vent pipe and/or chimney to ensure that it is not corroded or blocked by debris. Any corroded section of vent pipe must be replaced, and any obstruction or blockage must be removed prior to operating the furnace.
DESCRIPTION OF COMPONENTS
The descriptions below are various functional components that affect the operation and shutting down of the furnace. Some of these components and their locations are shown in Figure 18 (page 27). Refer to the Operating Sequence section (page 17) for additional component information.
If any component of the furnace must be replaced, use only factory authorized replacement parts specifi ed in the Replacement Parts List provided online.
Blower Limit Switch
Blower switches prevent operation when blower is not operational.
Flame Sensor
The fl ame sensor verifi es when a fl ame has carried over from the igniter to the opposite end burner. If no fl ame is detected, the furnace will shut down within 4 seconds.
Flame Roll-Out Switch
The fl ame roll-out switch verifi es that the burner fl ames are drawn into the heat exchanger tubes. If the burner fl ames are not properly drawn into the heat exchanger, the fl ame roll-out switch will close the gas valve and initiate the shutdown cycle.
Gas Valve
The gas valve controls the fl ow of gas to the burners. When the gas valve is energized it automatically opens and regulates the gas pressure in the manifold.
Inducer Assembly
The inducer assembly vents products of combustion to the outside.
Pressure Switch
The pressure switch verifi es that the inducer is drawing the combustion gases through the heat exchanger. If the fl ame is not properly drawn into the heat exchanger tube, the rollout switch or the fl ame sensor will shut the furnace down.
Supply Air Limit Switch
The supply air limit switch prevents the air temperature leaving the furnace from exceeding the maximum allowable outlet air temperature.
19
Page 20
TROUBLESHOOTING
If the furnace fails to operate check the following:
• Is the thermostat operating properly?
• Are the blower compartment door(s) in place?
• Is the furnace disconnect closed?
• Has the circuit breaker tripped or the control board fuse burned open?
• Is the gas turned on?
• Are any manual reset switches open?
• Is the fi lter dirty or plugged?
• Is the fl ame sensor coated? (Remove and clean with steel wool).
• Are all the LED’s on the furnace control board constantly ON? If not, refer to Tables 3 - 4 or the wiring diagram (Figure 17, page
24) to determine fault condition
IMPORTANT NOTE: The furnace will lock out after 5 failed attempts for ignition and will try again every hour if the call for heat remains.
• If the Inducer Blower is operating, and items above have been verifi ed, check the Blower Limit Switch (Figure 18, page 27) and reset if necessary.
• If the furnace operates when the Blower Limit Switch is reset, contact a qualifi ed service technician to identify and repair the problem.
• If the furnace still doesn’t operate, check the Flame Roll-out Switches (Figure 18, page 27) and reset if necessary.
• If the furnace operates when the Flame Rollout Switch is reset, contact a qualifi ed service technician to identify and repair the problem.
Diagnostic Description
Control Fault (No Power) Off Off
L1/Neutral Polarity Fault Flash Flash
1 Hour Lockout Alternating Flash
Normal Operation On On
Pressure Switch Closed Fault On Flash
Pressure Switch Open Fault Flash On
Open Limit Switch Fault Flash Off
Diagnostic Description Yellow LED
Low Flame Sensor Signal Continuous Flash
Flame Present On
Green
LED
Red LED
Table 3. Furnace Control Board
Fault Conditions
Diagnostic Description
Control Fault (No Power) Off Off
Normal Operation On On
Motor Fault On Flash
Twin Fault (no motor fault) Flash On
Communications Fault Flash Flash
Red LED
Green
LED
Table 4. Motor Control Board
Fault Conditions
20
Page 21
FIGURES AND TABLES
*XA 80+ Upfl ow/Horizontal Furnace
34
D
FRONT BRACE
BOTTOM
23 ½
½
PA NE L
BOTTOM VIEW
25
1 X 3 ½
HOLE FOR GAS
Ø HOLE FOR
ELECTRIC
23
ACCEPTS 4”
TYPE B
VENT PIPE
23
C
TOP VIEW
FLANGES
B
19
Ø ⅞ HOLE FOR
THERMOSTAT
Ø HOLE FOR
ELECTRIC
29 ½
*XA
Model #’s
046E-23A 061E-24B 076E-24B 092E-35C 107E-45D
22 ½
Dim.
14
17
“A”
Dim.
“B”
¼
10
½
11
21 14
½
24
15
22 ¼
25 21 ⁄
1
X 3 ½ X 45°
HOLE FOR GAS
4 KNOCKOUTS
(BOTH SIDES)
¾
¾
¼
Dim.
12
15
19
“C”
Dim.
“D”
12
16
19
22 23
15
⅞ ⅛
22 ¾
LEFT SIDE
28
A
Figure 16. Furnace Dimensions
1
RIGHT SIDE
23
1
¼
21
Page 22
AIRFLOW DATA
*G7XA UPFLOW / HORIZONTAL GAS FURNACE
Model
Number
XA046-A 46,000
XA061-B 61,000
XA076-B 76,000
Heating
Input
(Btuh)
Motor Switch
Setting
1/5 2/6 3/7 4/8 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise
0000
1000
0 1 0 0 600 57 555 61 510
1 1 0 0 705 48 670 51 635 54 600 57
0 0 1 0 775 44 740 46 705 48 665 51
1 0 1 0 900 38 870 39 835 41 800 43 765 45 730 47 695 49 660 52
0 1 1 0 950 36 920 37 890 38 855 40 825 41 795 43 765 45 730 47
1 1 1 0 1000 34 970 35 940 36 910 37 880 39 850 40 820 42 790 43
0 0 0 1 1075 32 1045 33 1015 34 985 35 960 35 925 37 900 38 870 39
1 0 0 1 1110 31 1080 32 1055 32 1025 33 1000 34 975 35 945 36 920 37
0 1 0 1 1170 29 1140 30 1115 31 1090 31 1060 32 1035 33 1010 34 985 35
1 1 0 1 1210 28 1185 29 1160 29 1130 30 1105 31 1080 32 1055 32 1025 33
0 0 1 1 1520 22 1225 28 1200 28 1175 29 1150 30 1120 30 1095 31 1070 32
1 0 1 1 1305 26 1280 27 1255 27 1230 28 1205 28 1180 29 1155 30 1130 30
0 1 1 1 1350 25 1230 28 1305 26 1285 27 1260 27 1240 27 1215 28 1195 29
1 1 1 1 1440 24 1400 24 1365 25 1230 28 1295 26 1255 27 1220 28 1185 29
0000
1000
0 1 0 0 600 74 555 80 510
1 1 0 0 705 63 670 66 635 70 600 74
0 0 1 0 775 57 740 60 705 63 665 67
1 0 1 0 900 49 870 51 835 53 800 56 765 58 730 61 695 64 660 67
0 1 1 0 950 47 920 48 890 50 855 52 825 54 795 56 765 58 730 61
1 1 1 0 1000 44 970 46 940 47 910 49 880 51 850 52 820 54 790 56
0 0 0 1 1075 41 1045 43 1015 44 985 45 960 46 925 48 900 49 870 51
1 0 0 1 1110 40 1080 41 1055 42 1025 43 1000 44 975 46 945 47 920 48
0 1 0 1 1170 38 1140 39 1115 40 1090 41 1060 42 1035 43 1010 44 985 45
1 1 0 1 1210 37 1185 38 1160 38 1130 39 1105 40 1080 41 1055 42 1025 43
0 0 1 1 1520 29 1225 36 1200 37 1175 38 1150 39 1120 40 1095 41 1070 42
1 0 1 1 1305 34 1280 35 1255 35 1230 36 1205 37 1180 38 1155 38 1130 39
0 1 1 1 1350 33 1230 36 1305 34 1285 35 1260 35 1240 36 1215 37 1195 37
1 1 1 1 1440 31 1400 32 1365 33 1230 36 1295 36 1255 35 1220 36 1185 38
0000
1000
0100
1100
0 0 1 0 775 73 740 76 705 80 665 85
1 0 1 0 900 63 870 65 835 67 800 70 765 74 730 77 695 81 660 85
0 1 1 0 950 59 920 61 890 63 855 66 825 68 795 71 765 74 730 77
1 1 1 0 1000 56 970 58 940 60 910 62 880 64 850 66 820 69 790 71
0 0 0 1 1075 52 1045 54 1015 55 985 57 960 59 925 61 900 63 870 65
1 0 0 1 1110 51 1080 52 1055 53 1025 55 1000 56 975 58 945 60 920 61
0 1 0 1 1170 48 1140 49 1115 50 1090 52 1060 53 1035 54 1010 56 985 57
1 1 0 1 1210 47 1185 48 1160 49 1130 50 1105 51 1080 52 1055 53 1025 55
0 0 1 1 1520 37 1225 46 1200 47 1175 48 1150 49 1120 50 1095 51 1070 53
1 0 1 1 1305 43 1280 44 1255 45 1230 46 1205 47 1180 48 1155 49 1130 50
0 1 1 1 1350 42 1230 46 1305 43 1285 44 1260 45 1240 45 1215 46 1195 47
1 1 1 1 1440 39 1400 40 1365 41 1230 46 1295 43 1255 45 1220 46 1185 48
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
External Static Pressure (in.w.c.)
Table 5. Maximum Airfl ow and Temperature Rises (°F) - Upfl ow/Horizontal Gas Furnaces
22
Page 23
G7XA UPFLOW / HORIZONTAL GAS FURNACES
Model
Number
XA092-C 92,000
XA107-D 107,000
Heating
Input
(Btuh)
Notes:
Motor Switch
Setting
1/5 2/6 3/7 4/8 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise
00001125611040 10001205 57 1120 61 1040 66 01001305 52 1225 56 1150 59 1070 64 11001430 48 1350 50 1270 54 1190 57 1110 61 1030 66 00101525 45 1450 47 1375 50 1300 52 1225 56 1150 59 1075 63 1000 68 10101620 42 1540 44 1465 47 1390 49 1315 52 1240 55 1165 58 1090 63 01101695 40 1620 42 1545 44 1465 47 1390 49 1315 52 1235 55 1160 59 11101770 39 1700 40 1630 42 1555 44 1485 46 1410 48 1340 51 1265 54 00011875 36 1805 38 1730 39 1655 41 1580 43 1510 45 1435 47 1340 51 10011905 36 1840 37 1775 38 1710 40 1640 42 1575 43 1510 45 1445 47 01011980 34 1910 36 1845 37 1780 38 1715 40 1650 41 1580 43 1515 45 11012025 34 1960 35 1895 36 1830 37 1765 39 1700 40 1635 42 1570 43 00112085 33 2025 34 1960 35 1900 36 1840 37 1775 38 1715 40 1655 41 10112135 32 2070 33 2010 34 1945 35 1880 36 1815 38 1750 39 1685 40 01112200 31 2145 32 2090 33 2035 33 1980 34 1925 35 1870 36 1820 37 11112280 30 2225 31 2170 31 2115 32 2065 33 2010 34 1955 35 1900 36
00001395 57 1350 59 1305 61 1260 63 1210 66 1165 68 10001465 54 1420 56 1375 58 1330 60 1290 61 1245 64 1200 66 01001555 51 1510 52 1470 54 1425 56 1380 57 1340 59 1295 61 1250 63 11001625 49 1585 50 1540 51 1500 53 1460 54 1415 56 1375 58 1335 59 00101690 47 1650 48 1610 49 1570 50 1530 52 1485 53 1445 55 1405 56 10101760 45 1715 46 1670 47 1625 49 1575 50 1530 52 1485 53 1440 55 01101835 43 1790 44 1745 45 1695 47 1650 48 1605 49 1555 51 1510 52 11101885 42 1840 43 1790 44 1745 45 1700 47 1655 48 1610 49 1565 51 00011945 41 1900 42 1850 43 1805 44 1760 45 1710 46 1665 48 1620 49 10011950 41 1905 42 1860 43 1820 44 1775 45 1735 46 1690 47 1650 48 01012075 38 2030 39 1990 40 1945 41 1900 42 1855 43 1810 44 1770 45 11012125 37 2085 38 2040 39 2000 40 1955 41 1910 41 1870 42 1825 43 00112170 37 2130 37 2090 38 2045 39 2005 40 1965 40 1925 41 1880 42 10112215 36 2180 36 2140 37 2105 38 2070 38 2035 39 2000 40 1965 40 0111 2225 36 2165 37 2100 38 2040 39 1111 2170 37 2120 37 2065 38
1. Motor Switch Settings are for heating speeds using HEAT switches 1, 2, 3, & 4 and cooling speeds using COOL switches 5, 6, 7, & 8.
2. Two openings are recommended for airfl ows above 1,600 CFM if the fi lter(s) is (are) adjacent to the furnace.
3. Data is shown without fi lter.
4. Temperature rises in the table are approximate. Actual temperature rises may vary.
5. Temperature rises that are shaded in grey are for reference only. These conditions are not recommended.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
External Static Pressure (in.w.c.)
Table 5. Continued
23
Page 24
ELECTRICAL INFORMATION
112233445566778899
Green LED Red LED
Control Fault (No Power) Off Off
L1 / Neutral Polarity Fault Flash Flash
1 Hour Lockout
Normal Operation On On
Pressure Switch Closed Fault On Flash
Pressure Switch Open Fault Flash On
Open Limit Switch Fault Flash Off
Low Flame Sensor Signal
Flame Present
Diagnostic Description
FAULT CONDITIONS
Continuous Flash
On
Alternating Flash
Yellow LED Diagnostic Description
BLUE
SPEED
W
W
TORQUE
NONE
HP(PWM)
COMMON
TX
RX
GND
C
R
LIMIT
SWITCH
GND
PWM
C
RX
NONE
MODE
R
TX
W
BLUE
MOTOR
LIMIT
BOARD
CONTROL
SWITCH
RED
BLACK
COOL
FAN SPEED
1185-200
BLUE
HEAT
R C Y1 TWINDEHUM
BLACKBLACK
3/4 AND 1 HP
MOTORS ONLY
YELLOW
GREEN
BROWN
TX
RX
TX
RX
R
R
RED
C
C
BLUE
ORANGE
W
COM
W
COM
WD#710807-C
BLACK
WHITE
BLACK
WHITE
208/240 V
24 V
GREY
RED
SWITCH
THERMOSTAT
SINGLE STAGE
ORANGE
PRESSURE
SWITCH
PRESSURE
If any of the original wire as supplied with the
furnace must be replaced, it must be replaced
with wiring material having a temperature
rating of at least 105° C.
Use copper conductors only.
MODELS)
(ON SELECT
CONDENSATE
For 80+ and 90+ Export Furnaces
Refer to the installation instructions
provided with the kit for the proper
heating and cooling speeds for your
application.
BLACK
WHITE
1234
1234
TO OUTDOOR UNIT
W RX TX COM C R
HIGH
MHMLLOW
FAN
COM
24V
RCYGW
3 AMP FUSE
WHITE
BLACK
ORANGE
ORANGE
HEAT
COOL
RED
GREEN
YELLOW
RELAY
BLWR OFF
GREEN
FLAME SENSOR
123
456
789
RED
LOW
ML
MH
HIGH
EAC
L1
XFMR
HUM
L1A
123
NEUTRALS
456
BLACK
BLACK
YELLOW
YELLOW
1
2
1
2
IGNITOR
GAS
VALVE
BLACK
BLACK
1
2
1
2
C
INDUCER
R
BLACK
BLUE
BLUE BLUE BLUE
BLACK
WHITE
SUPPLY
AIR LIMIT
FLAME
ROLLOUT
LIMIT
VENT
BLACK
WHITE
(ON SELECT MODELS)
DOOR
SWITCH
GREEN
GROUND
BLACK 208/240V
WHITE (NEUTRAL)
LEGEND:
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
24
Figure 17. Wiring Diagram for G7XA Upfl ow Furnace
Page 25
TIME FOR
ONE REVOLUTION
(SECONDS)
10 360 1,800 3,600 66 55 273 545 12 300 1,500 3,000 68 53 265 529 14 257 1,286 2,571 70 51 257 514 16 225 1,125 2,250 72 50 250 500 18 200 1,000 2,000 74 49 243 486 20 180 900 1,800 76 47 237 474 22 164 818 1,636 78 46 231 462 24 150 750 1,500 80 45 225 450 26 138 692 1,385 82 44 220 439 28 129 643 1,286 84 43 214 429 30 120 600 1,200 86 42 209 419 32 113 563 1,125 88 41 205 409 34 106 529 1,059 90 40 200 400 36 100 500 1,000 92 39 196 391 38 95 474 947 94 38 191 383 40 90 450 900 96 38 188 375 42 86 429 857 98 37 184 367 44 82 409 818 100 36 180 360 46 78 391 783 102 35 176 353 48 75 375 750 104 35 173 346 50 72 360 720 106 34 170 340 52 69 346 692 108 33 167 333 54 67 333 667 110 33 164 327 56 64 321 643 112 32 161 321 58 62 310 621 114 32 158 316 60 60 300 600 116 31 155 310 62 58 290 581 118 31 153 305 64 56 281 563 120 30 150 300
GAS INFORMATION
GAS FLOW RATES (CUBIC FEET PER HOUR)
CUBIC FEET PER REVOLUTION
OF GAS METER
1 5 10 1 5 10
TIME FOR
ONE REVOLUTION
(SECONDS)
CUBIC FEET PER REVOLUTION
OF GAS METER
Table 6. Gas Flow Rates
CAPACITY OF BLACK IRON GAS PIPE (CU. FT. PER HOUR)
FOR NATURAL GAS (SPECIFIC GRAVITY - 0.60)
NOMINAL BLACK
IRON PIPE
DIAMETER (IN.)
1/2 130 90 75 65 55 50 45 40
3/4 280 190 150 130 115 105 95 90
1 520 350 285 245 215 195 180 170
1 1/4 1,050 730 590 500 440 400 370 350
1 1/2 1,600 1,100 890 760 670 610
The cubic feet per hour listed in the table above must be greater than the cubic feet per hour of gas fl ow required by the furnace. To determine the cubic feet per hour of gas fl ow required by the furnace, divide the input rate of the furnace by the heating value (from gas supplier) of the gas.
10 20 30 40 50 60 70 80
Cubic Feet Per Hour Required =
LENGTH OF PIPE RUN (FT)
NOTES
Input To Furnace (Btu/hr)
Heating Value of Gas (Btu/Cu. Ft.)
Table 7. Black Iron Gas Pipe Capacities
25
Page 26
ALTITUDE ABOVE
SEA LEVEL
0 to 1,999 FT
2,000 to 2,999 FT
3,000 to 4,999 FT
5,000 to 5,999 FT
6,000 to 7,999 FT
8,000 to 10,000 FT
NATURAL GAS
INPUT (BTU)
46,000 61,000 76,000 107,000
49 49 49 49 ORIFICE SIZE
10.0 10.0 10.0 10.0 MANIFOLD PRESSURE
49 49 49 49 ORIFICE SIZE
9.0 9.0 9.0 9.0 MANIFOLD PRESSURE
49 49 49 49 ORIFICE SIZE
8.5 8.5 8.5 8.5 MANIFOLD PRESSURE
51 51 51 51 ORIFICE SIZE
10.0 10.0 10.0 10.0 MANIFOLD PRESSURE
51 51 51 51 ORIFICE SIZE
9.0 9.0 9.0 9.0 MANIFOLD PRESSURE
51 51 51 51 ORIFICE SIZE
8.5 8.5 8.5 8.5 MANIFOLD PRESSURE
Table 8. High Altitude Deration - Natural Gas
ALTITUDE ABOVE
SEA LEVEL
0 to 1,999 FT
2,000 to 2,999 FT
3,000 to 4,999 FT
5,000 to 5,999 FT
6,000 to 7,999 FT
8,000 to 10,000 FT
PROPANE
INPUT (BTU)
46,000 61,000 76,000 107,000
57 57 57 57 ORIFICE SIZE
10.0 10.0 10.0 10.0 MANIFOLD PRESSURE
57 57 57 57 ORIFICE SIZE
9.0 9.0 9.0 9.0 MANIFOLD PRESSURE
57 57 57 57 ORIFICE SIZE
8.5 8.5 8.5 8.5 MANIFOLD PRESSURE
59 59 59 59 ORIFICE SIZE
10.0 10.0 10.0 10.0 MANIFOLD PRESSURE
59 59 59 59 ORIFICE SIZE
9.0 9.0 9.0 9.0 MANIFOLD PRESSURE
59 59 59 59 ORIFICE SIZE
8.5 8.5 8.5 8.5 MANIFOLD PRESSURE
Table 9. High Altitude Deration - Propane Gas
26
Page 27
LOCATION OF FURNACE COMPONENTS
ITEM COMPONENT NAME
Blower Assembly
1.
Blower Door Switch
2.
Burner Assembly
3.
Flame Roll-Out Switch
4.
Flame Sensor
5.
Furnace Control Board
6.
Gas Manifold
7.
Gas Valve
8.
14
9
2
10
11
8
9 8 7
63 5 4
NEUTRALS
6
RCYGW
STATUS
24V
FAN
COOL
HEAT
FLAME
63
180
BLOWER
2
120
5
OFF
90
1
4
DELAY
60
L1A 2
1
XFMR
HIGH
LOW
HUM
EAC
MH
ML
L1
13
5
7
Igniter
9.
Inducer Assembly
10.
Main Air Limit Switch
11.
Motor Control Board
12.
Pressure Switch
13.
Transformer
14.
Figure 18.
4
Upfl ow/Horizontal Gas Furnace
3
1
12
27
Page 28
INSTALLATION/PERFORMANCE CHECK LIST
INSTALLER NAME:
CITY _______________ STATE _____________
INSTALLATION ADDRESS:
CITY _______________ STATE _____________
UNIT MODEL #
UNIT SERIAL # ____________________________
Minimum clearances per Table 1 (page 5)?
Has the owner’s information been reviewed with the home-owner?
YES NO
YES NO
ELECTRICAL SYSTEM:
Electrical connections tight? YES NO
Line voltage polarity correct? YES NO
Supply Voltage: ______________________ VOLTS
Has the thermostat been calibrated?
Is the thermostat level? YES NO
Is the heat anticipator setting correct?
YES NO
YES NO
GAS SYSTEM:
Gas Type: (circle one)
Gas pipe connections leak tested?
Gas Line Pressure: __________________ (in - W.C.)
Is there adequate fresh air supply for combustion and ventilation?
Natural
Gas
YES NO
YES NO
Propane
Has the literature package been left near the furnace?
YES NO
Installation Altitude: ____________________ (FT.)
Deration Percentage: ___________________ (%)
Furnace Input: _______________________ (Btuh)
Supply Air Temperature: ________________ (° F)
Return Air Temperature: ________________ (° F)
Temperature Rise: ____________________ (° F)
VENTING SYSTEM:
Vent free from restrictions? YES NO
Filter(s) secured in place? YES NO
Filter(s) clean? YES NO
Flue connections tight? YES NO
Is there proper draft? YES NO
O’Fallon, MO
¢708910«¤
708910B
708910B (Replaces 708910A)
Specifi cations and illustrations subject to change
without notice or incurring obligations.
Printed in U.S.A. (07/09)
Loading...