Two-Stage Condensing Furnaces With Fixed and Variable Speed Blowers
95.1% AFUE
*TC Upfl ow/Horizontal Model
WARNING:
• PROPOSITION 65 WARNING: This product
contains chemicals known to the state of
California to cause cancer, birth defects or
other reproductive harm.
• This furnace is not approved for installation
in mobile homes. Installing this furnace in
a mobile home could cause fi re, property
damage, and/or personal injury.
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your
customer. This includes being able to install the product according
to strict safety guidelines and instructing the customer on how to
operate and maintain the equipment for the life of the product.
Safety should always be the deciding factor when installing this
product and using common sense plays an important role as well.
Pay attention to all safety warnings and any other special notes
highlighted in the manual. Improper installation of the furnace
or failure to follow safety warnings could result in serious injury,
death, or property damage.
These instructions are primarily intended to assist qualifi ed
individuals experienced in the proper installation of this appliance.
Some local codes require licensed installation/service personnel
for this type of equipment. Please read all instructions carefully
before starting the installation. Return these instructions to the
customer’s package for future reference.
*TL Downfl ow Model
WARNING:
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly
could result in serious injury or property
damage.
• Installation and service must be performed
by a qualifi ed installer, service agency or
the gas supplier.
• Do not store or use gasoline or other
fl ammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a
neighbors phone. Follow the gas suppliers
instructions.
• If you cannot reach your gas supplier, call
the fi re department.
DO NOT DESTROY.
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
Page 2
TABLE OF CONTENTS
SAFETY INFORMATION .............................................4
Safety markings are used frequently throughout this
manual to designate a degree or level of seriousness and
should not be ignored. WARNING indicates a potentially
hazardous situation that if not avoided, could result in
personal injury or death. CAUTION indicates a potentially
hazardous situation that if not avoided, may result in minor
or moderate injury or property damage.
WARNING:
The safety information listed below must be
followed during the installation, service, and
operation of this furnace. Failure to follow safety
recommendations could result in possible
damage to the equipment, serious per
injury or death
• Use only with type of gas approved for this furnace.
Refer to the furnace rating plate.
• Install this furnace only in a location and position as
specifi ed in Table 1 (page 7).
• Provide adequate combustion and ventilation air to the
furnace space as specifi ed on pages 8 - 10.
• Provide adequate clearances around the vent air intake
terminal as specifi ed in Figures 6 - 9 (pages 12 - 13).
• Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only,
as specifi ed on pages 10 - 14.
• Never test for gas leaks with an open fl ame. Use a
commercially available soap solution to check all
connections. See page 20.
• This furnace is designed to operate with a maximum
external pressure rise of 0.5 inches of water column.
Consult Tables 8 - 10 (pages 35 - 37), and the rating
plate for the proper circulating air fl ow and temperature
rise. It is important that the duct system be designed
to provide the correct fl ow rates and external pressure
rise. An improperly designed duct system can result in
nuisance shutdowns, and comfort or noise issues.
• When supply ducts carry air circulated by the furnace
to areas outside the space containing the furnace, the
return air shall also be handled by duct(s) sealed to
the furnace casing and terminating in the conditioned
space. See page 14.
• A gas-fi red fur nace for installation in a residential garage
must be installed as specifi ed on page 6.
• This furnace may be used for temporary heating of
buildings or structures under construction. See the
guidelines listed on pages 5 - 6.
.
sonal
REQUIREMENTS and CODES
This furnace must be installed in accordance with
these instructions, all applicable local building codes
and the current revision of the National Fuel Gas Code
(NFPA54/ANSI Z223.1) or the Natural Ga s and Propane
Installation Code, CAN/CGA B149.1.
The Commonwealth of Massachusetts requires
compliance with regulation 248 CMR 4.00 and 5.00 for
installation of through – the – wall vented gas appliances
as follows:
1. For direct-vent appliances, mechanical-vent heating
appliances or domestic hot water equipment, where
the bottom of the vent terminal and the air intake is
installed below four feet above grade the following
requirements must be satisfi ed:
a.) A carbon monoxide (CO) detector and alarm shall
be placed on each fl oor level where there are
bedrooms. The detector shall comply with NFPA
720 (2005 Edition) and be mounted in the living
area outside the bedroom(s).
b.) A (CO) detector shall be located in the room that
houses the appliance or equipment and shall:
• Be powered by the same electrical circuit as
the appliance or equipment. Only one service
switch shall power the appliance and the (CO)
detector;
• Have battery back-up power;
• Meet ANSI/UL 2034 Standards and comply with
NFPA 720 (2005 Edition); and Approved and listed
by a Nationally Recognized Testing Laboratory
as recognized under 527 CMR.
c.) A Product-approved vent terminal must be used,
and if applicable, a product-approved air intake must
be used. Installation shall be in strict compliance
with the manufacturer’s instructions. A copy of
the installation instructions shall remain with the
appliance or equipment at the completion of the
installation.
d.) A metal or plastic identifi cation plate shall be
mounted at the exterior of the building, four feet
directly above the location of vent terminal. The
plate shall be of suffi cient size, easily read from
a distance of eight feet away, and read “Gas Vent
Directly Below”.
2. For direct-vent appliances, mechanical-vent heating
appliances or domestic hot water equipment where
the bottom of the vent terminal and the air intake is
installed above four feet above grade the following
requirements must be satisfi ed:
a.) A (CO) detector and alarm shall be placed on
each fl oor level where there are bedrooms. The
detector shall comply with NFPA 720 (2005 Edition)
and be mounted in the living area outside the
bedroom(s).
4
Page 5
b.) The (CO) detector shall:
• Be located in the room that houses the appliance
or equipment;
• Be hard-wired or battery powered or both.
• Shall comply with NFPA 720 (2005 Edition).
c.) A product-approved vent terminal must be used, and
if applicable, a product-approved air intake must be
used. Installation shall be in strict compliance with the
manufacturer’s instr uctions. A copy of the installation
instructions shall remain with the appliance or
equipment at the completion of the installation.
Additional information listed below is for reference
purposes only and does not necessarily have
jurisdiction over local or state codes. Always
consult with local authorities before installing any
gas appliance.
Combustion and Ventilation Air
• US: National Fuel Gas Code (NFGC), Air for
Combustion and Ventilation
• CANADA: Natural Gas and Propane Installation
Codes (NSCNGPIC), Venting Systems and Air Supply
for Appliances
Duct Systems
• US and CANADA: Air Conditioning Contractors
Association (ACCA) Manual D, Sheet Metal and
Air Conditioning Contractors National Association
(SMACNA), or American Society of Heating,
Refrigeration, and Air Conditioning Engineers
(ASHRAE) Fundamentals Handbook
Electrical Connections
• US: National Electrical Code (NEC) ANSI/NFPA 70
• CANADA: Canadian Electrical Code CSA C22.1
Gas Piping and Gas Pipe Pressure Testing
• US: NFGC and National Plumbing Codes
• CANADA: NSCNGPIC
General Installation
• US: Current edition of the NFGC and the NFPA 90B.
For copies, contact the National Fire Protection
Association Inc., Batterymarch Park, Quincy, MA
02269; or American Gas Association, 400 N. Capitol,
N.W., Washington DC 20001 or www.NFPA.org
• CANADA: NSCNGPIC. For a copy, contact Standard
Sales, CSA International, 178 Rexdale Boulevard,
Etobicoke (Toronto), Ontario, M9W 1R3 Canada
Safety
• US: (NFGC) NFPA 54–1999/ANSI Z223.1 and the
Installation Standards, Warm Air Heating and Air
Conditioning Systems ANSI/NFPA 90B.
• CANADA: CAN/CGA-B149.1 and .2–M00 National
Standard of Canada. (NSCNGPIC)
GENERAL INSTRUCTIONS
Combustion Air Quality
CAUTION:
Combustion air must not be drawn from a
corrosive atmosphere.
To maximize heat exchanger life, the combustion air
must be free of chemicals that can form corrosive acidic
compounds in the combustion gases. The recommended
source of combustion air is to use outdoor air. However,
the use of indoor air in most applications is acceptable
except as listed:
• If the furnace is installed as a single pipe installation
in a confi ned space, it is required that the necessary
combustion air come from the outdoors by way of attic,
crawl space, air duct, or direct opening. For Installations
in confi ned spaces, see pages 8 - 10 for combustion
air requirements.
• Installations in these locations may require outdoor air
for combustion, due to chemical exposures:
Commercial buildings
Buildings with indoor pools
Furnaces installed in laundry rooms
Furnaces installed in hobby or craft rooms
Furnaces installed near chemical storage areas
• Exposure to the following substances in the combustion
air supply may require outdoor air for combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon Tetrachloride
Halogen type refrigerants
Cleaning solvents (perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric Acid
Cements and glues
Antistatic fabric softeners
Masonry acid washing materials
Operation of Furnace During Construction
CAUTION:
Failure to follow these instructions will void the
factory warranty and may signifi cantly reduce
the life or the performance of the furnace,
and/or result in other unsafe conditions. It is
the responsibility of the installing contractor
to insure these provisions are met.
5
Page 6
Operating gas furnaces in construction environments can
cause a variety of problems with the furnace. Proper use
of commercial portable space heating equipment during
construction is recommended. This gas furnace may be
used during construction if it is not in violation of any
applicable codes and the following criteria are met:
• The installation must meet all applicable codes. The
furnace must be permanently installed according to
the instructions supplied with the furnace including
electrical supply, gas supply, duct work and venting. The
furnace must be controlled by a thermostat properly
installed according to the instructions supplied with the
furnace and thermostat. The installation must include
a properly installed fi lter in the return air system with
no by-pass air. The fi lter must be inspected frequently
and replaced when necessary.
• Combustion air must be supplied from outside the
structure and located such that dust and gases
from construction activity are not introduced into the
combustion system.
• Provisions must be made to insure that condensate
does not freeze in the furnace or condensate drain lines
during operation and during idle times; for example,
overnight if turned off. (Condensing furnaces only)
• Before occupying the structure: The fi lter must be
replaced or cleaned, the duct work must be inspected
and cleaned of any construction debris, and the furnace
must be cleaned and/or repaired if found to be dirty,
damaged, or malfunctioning in any way by a qualifi ed
HVAC technician. The furnace shall be inspected and
approved by applicable local authority even if this
requires redundant inspections.
• Serial numbers for furnaces used during construction
must be submitted in writing (fax and email also
acceptable). This information will be used to track the
long-term affects of the use during construction on
furnaces. Proof of this submittal shall be available for
the fi nal inspection of the furnace prior to occupancy.
• This furnace is designed to operate with return air
temperatures in ranges normally found in occupied
residences, including setbacks. Minimum continuous
return temperature must not be below 60° F (15° C).
Occasionally a temporary return temperature of 55° F
(12° C) is acceptable. However, operation with a return
temperature below 55° F (12° C) is not allowed.
Heating Load
This furnace should be sized to provide the design heating
load requirement. Heating load estimates can be made
using approved methods available from Air Conditioning
Contractors of America (Manual J); American Society of
Heating, Refrigerating, and Air Conditioning Engineers;
or other approved engineering methods. Excessive
oversizing of the furnace could cause the furnace
and/or vent to fail prematurely. The ductwork should
be appropriately sized to the capacity of the furnace to
ensure its proper airfl ow rating.
6
For installations above 2,000 ft., the furnace should have
a sea level input rating large enough that it will meet the
heating load after deration for altitude.
Two-stage furnaces operate at two input rates to better
meet heating loads. The lower heating rate (low fi re) is
65% of the high fi re rate. The greatest degree of control
over the furnace can be gained by controlling it with a two
stage thermostat. This allows the thermostat to directly
request either high or low fi re. However, it is possible to
operate the furnace using a single stage thermostat. In
this application the furnace control can be set to increase
from low to high fi re, based on a timer. See Autostaging
for Single Stage Thermostats (page 23).
Furnaces are properly sized to meet the expected
maximum heating load. But this load occurs infrequently.
So, during more moderate weather, the furnace is likely
to use low fi re a considerable part of the time. This is
normal and has the benefi t of quieter and more effi cient
operation.
Installation in a Garage
WARNING:
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death.
Do not store or use gasoline or other fl ammable
vapors and liquids in the vicinity of this or any
other appliance. Storage of or use of gasoline
or other fl ammable vapors or liquids in the
vicinity of this or any appliance can result in
serious injury or death.
This Gas-fi red furnace may be installed in a residential
garage with the provision that the burners and igniter
are located no less than 18 inches (457mm) above the
fl oor. The furnace must be located or protected to prevent
physical damage by vehicles.
Clearances to Combustible Materials
This furnace is Design Certifi ed in the U.S. and Canada
by CSA International for the minimum clearances to
combustible material listed in Table 1 (page 7). To obtain
model number and specifi c clearance information, refer
to the furnace rating plate, located inside of the furnace
cabinet.
Access for positioning and servicing the unit must be
considered when locating unit. The need to provide
clearance for access to panels or doors may require
clearance distances over and above the requirements.
Allow 24 inches minimum clearance from the
front of the unit. However 36 inches is strongly
recommended.
Page 7
INSTALLATION CLEARANCES to COMBUSTIBLE MATERIALS
For UPFLOW, HORIZONTAL & DOWNFLOW FURNACES
Left Side ...................................0 InchesVent ............................................. 1 InchTop ...........................................1 Inches
Right Side ................................0 InchesBack .........................................0 InchesFront.......................................4 Inches
UPFLOW APPLICATION
TOP
HORIZONTAL APPLICATION
SIDE
DOWNFLOW APPLICATION
TOP
†
TOP
LEFT SIDE
BOTTOM
†
Allow 24 in. minimum clearance for servicing. Recommended clearance is 36 in.
NOTE: The furnace is listed for installation on combustible or non-combustible fl ooring. However, wood is the only combustible
fl ooring allowed for installation. Downfl ow models must use the appropriate subase kit when installing over a wood fl oor
RIGHT SIDE
SIDE
Table 1. Minimum Clearances to Combustible Materials
WARNING:
BOTTOM
LEFT SIDE
BOTTOM
RIGHT SIDE
.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system
being placed into operation could result in carbon monoxide poisoning or death. The following
steps shall be followed with each individual appliance connected to the venting system being
placed in operation, while all other appliances connected to the venting system are not in
operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National
Fuel Gas Code, ANSI Z223. 1/NFPA 54 or the CSA B149.1, Natural Gas and Propane Installation
Codes and these instructions. Determine that there is no blockage or restriction, leakage,
corrosion and other defi ciencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space
in which the appliance(s) connected to the venting system are located and other spaces
of the building.
4. Close fi replace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on
any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at
maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust
the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after
5 minutes of main burner operation. Use the fl ame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must
be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes.
9. After it has been determined that each appliance connected to the venting system properly
vents when tested as outlined above, return doors, windows, exhaust fans, fi replace
dampers and any other gas-fi red burning appliance to their previous conditions of use.
7
Page 8
COMBUSTION AIR REQUIREMENTS
General Information
WARNING:
Furnace installation using methods other than
those described in the following sections must
comply with the National Fuel Gas Code (NFGC)
and all applicable local codes.
• Instructions for determining the adequacy of combustion
air for an installation can be found in the current revision
of the NFGC (ANSI Z223.1 / NFPA54). Consult local codes for special requirements. These requirements
are for US installations as found in the NFGC.
• The requirements in Canada (B149.1) are structured
differently. Consult with B149.1 and local code offi cials
for Canadian installations.
This condensing furnace is certifi ed for installation either as
a Direct Vent (2-pipe) or Conventional (1-pipe) appliance.
Direct Vent appliances draw combustion air from the
outdoors and vent combustion products back outside.
Installation with air taken from around the furnace is often
referred to as Conventional installation - i.e. only the vent
(exhaust) pipe is provided.
Provisions must be made during the installation of
this furnace that provide an adequate supply of air for
combustion. The combustion air from the outside needs
to be clear of chemicals that can cause corrosion. The
inlet pipe should not be placed near corrosive chemicals
such as those listed on page 6.
Another important consideration when selecting one or
two pipe installation is the quality of the Indoor air which
can sometimes be contaminated with various household
chemicals . These chemicals can cause severe corrosion
in the furnace combustion system.A 2-pipe installation
has the additional advantage that it isolates the system
from the effects of negative pressure in the house.
CAUTION:
Exhaust fans, clothes dryers, fi replaces and
other appliances that force air from the house
to the outdoors can create a negative pressure
inside the house, resulting in improper furnace
operation or unsafe conditions such as fl ame roll
out. It is imperative that suffi cient air exchange
with the outdoors is provided to prevent
depressurization. Additional information about
how to test for negative pressure problems can
be found in the NFGC.
the fl ame roll-out switch will open, turning off the gas
supply to the burners. This safety device is a manually
reset switch. DO NOT install jumper wires across
these switches to defeat their function or reset a
switch without identifying and correcting the fault
condition. If a switch must be replaced, use only the
correct sized part specifi ed in the Replacement Parts
List provided online.
Direct Vent Furnaces
Direct Vent (2-pipe) furnaces draw combustion air directly
from the outdoors and then vent the combustion products
back outside, isolating the entire system from the indoor
space. It is important to make sure that the whole system
is sealed and clearances to combustibles are maintained
regardless of the installation being in a confi ned or
unconfi ned space.
Conventional Furnaces - Confi ned Spaces
A confi ned space is an area with volume less than 50
cubic feet per 1,000 Btuh of the combined input rates of
all appliances drawing combustion air from that space.
Furnace closets, small equipment rooms and garages are
confi ned spaces. Furnaces installed in a confi ned space
which supply heated air to areas outside the space must
draw return air from outside the space and must have
the return air ducts tightly sealed to the furnace. Ducts
must have cross - sectional area at least as large as
the free area of their respective openings to the furnace
space. Attics or crawl spaces must connect freely with
the outdoors if they are the source of air for combustion
and ventilation.
The required sizing of these openings is determined by
whether inside or outside air is used to support combustion,
the method by which the air is brought to the space, and
by the total input rate of all appliances in the space. In
all cases, the minimum dimension of any combustion air
opening is 3 inches.
Air From Inside
If combustion air is taken from the heated space, the two
openings must each have a free area of at least one square
inch per 1,000 Btuh of total input of all appliances in the
confi ned space, but not less than 100 square inches of
free area (Figure 1, page 10).
Example:
If the combined input rate of all appliances is less
than or equal to 100,000 Btuh, each opening must
have a free area of at least 100 square inches. If the
combined input rate of all appliances is 120,000 Btuh,
each opening must have a free area of at least 120
square inches.
NOTE: Air openings on top of the furnace and openings
in closet doors or walls must never be restricted. If the
furnace is operated without adequate air for combustion,
8
Page 9
Vent or
Chimney
Vent or
Chimney
Ventilation Louvers
at each end of attic
Attic
Insulation
Air Duct must be
at least 1 sq. in.
per 4,000 Btuh of
total input rating.
NOTES:
Each opening must be
at least 100 sq. in. or
1 sq. in. per 1,000 Btuh
of total input rating,
whichever is greater.
Openings must start at
no more than 12 inches
from the top and bottom
of the enclosure.
Outdoor Air from a Crawl Space or Vented Attic
When the openings can freely exchange air with the
outdoors, each opening shall have a minimum free area
of 1 square inch per 4,000 Btuh of total appliance input.
The openings shall exchange directly, or by ducts, with
the outdoor spaces (crawl or attic) that freely exchange
with the outdoors (Figure 2).
Air Duct must be
at least 1 sq. in.
per 4,000 Btuh of
total input rating.
12" Max
Round Duct
Diameter
Figure 3. Combustion Air Drawn from Outside
Through Vertical Ducts
Outdoor Air Using Horizontal Ducts
If combustion air is taken from outdoors through horizontal
ducts, the openings and ducts must have a minimum free
area of one square inch per 2,000 Btuh of total appliance
input (Figure 4). Ducts must have cross - sectional area at
least as large as the free area of their respective openings
to the furnace space.
Outdoor Air Using Vertical Ducts
If combustion air is taken from outdoors through vertical
ducts, the openings and ducts must have a minimum free
area of one square inch per 4,000 Btuh of total appliance
input (Figure 3).
Vent or
Chimney
Ventilation Louvers
(each end of attic)
Water
Heater
Inlet Air
---------
---------
NOTE: Air openings shall
each have a free area of
not less than one square
inch per 4,000 Btuh of the
total input rating of all
equipment in the enclosure.
---------
Furnace
Alternate
Air Inlet
Outlet
Air
---------
Ventilation Louvers For
Unheated Crawl Space
Figure 2. Combustion Air Drawn from a Crawl
Space or Vented Attic
Vent or
Chimney
Water
Heater
Air Duct
Furnace
Air Ducts must be
at least 1 sq. in.
per 2,000 Btuh of
total input rating.
Air Directly Through an Exterior Wall
If combustion air is provided directly through an exterior
wall, the two openings must each have free area of at
least one square inch per 4,000 Btuh of total appliance
input (Figure 5).
must be at least 1 sq. in. per
4,000 Btuh of total input rating.
Furnace
Round Duct
Diameter
Figure 5. Combustion Air Drawn from Outside
Through an Exterior Wall
Conventional Furnaces - Unconfi ned Spaces
An unconfi ned space is an area including all rooms not
separated by doors with a volume greater than 50 cubic
feet per 1,000 Btuh of the combined input rates of all
appliances which draw combustion air from that space.
In general, a furnace installed in an unconfi ned space will
not require outside air for combustion. However, in homes
built for energy effi ciency (low air change rates), it may
be necessary to provide outside air to ensure adequate
combustion and venting, even though the furnace is located
in an unconfi ned space. See example.
Example:
A space with a water heater rated at 45,000 Btuh
input and a furnace rated at 75,000 Btuh requires a
volume of 6,000 cubic feet [50 x (45 + 75) = 6,000] to
be considered unconfi ned. If the space has an 8 foot
ceiling, the fl oor area of the space must be 750 square
feet (6,000 / 8 = 750).
VENTING REQUIREMENTS
• This furnace must be vented in compliance with
the current revision of the National Fuel Gas Code
(ANSI-Z223.1/NFPA54) and the instructions
provided below. Consult local codes for special
requirements.
• In Canada, venting shall conform to the requirements of
the current (CAN/CGA B149.1 or .2) installation codes.
Consult local codes for special requirements.
Alternate Method of Providing Air from Outside:
If acceptable under local Codes, it is permitted to
provide outside air using one opening (See NFGC).
Generally, confi ned spaces must have two openings
in the space for combustion air. One opening must
be within 12 inches of the ceiling, and the other
must be within 12 inches of the fl oor. However, an
alternative method recently adopted by the NFGC
uses one opening within 12 inches of the top of the
space. This method may be used if it is acceptable
to the local codes.
The following conditions must be met:
1. The opening must start within 12” of the top of
the structure and connect with the out of doors
through vertical or horizontal ducts or be ducted
to a crawl or attic space that connects with the
out of doors.
2. The opening must have a minimum free area of 1
sq. in. per 3,000 Btu per hour of the total input rating
of all equipment located in the enclosure.
3. The free area must not be less than the sum of all the
areas of the vent connectors in the enclosure.
10
WARNING:
This furnace must not be vented with other
appliances, even if that appliance is of the
condensing type. Common venting can result
in severe corrosion of other appliances or their
venting and can allow combustion gases to
escape through such appliances or vents. Do
not vent the furnace to a fi replace chimney or
building chase.
WARNING:
Upon completion of the furnace installation,
carefully inspect the entire fl ue system both
inside and outside the furnace to assure it is
properly sealed. Leaks in the fl ue system can
result in serious personal injury or death due
to exposure of fl ue products, including carbon
monoxide.
This furnace is classifi ed as a “Category IV” appliance,
which requires special venting materials and installation
procedures.
Page 11
This section specifi es installation requirements for
Conventional (1-pipe) and Direct Vent (2-pipe) piping. For
1- pipe installations, install vent piping as described in
this section and provide air for combustion and ventilation
according to pages 8 - 10. Table 2 contains the maximum
length of vent and combustion air piping for either type
of installation.
Material ....................................... Standard
Category IV appliances operate with positive vent pressure
and therefore require vent systems which are thoroughly
sealed. They also produce liquid condensate, which is
slightly acidic and can cause severe corrosion of ordinary
venting materials. Furnace operation can be adversely
affected by restrictive vent and combustion air piping.
The inducer assembly on this furnace can be rotated to
vent the fl ue products out of the left or right side of the
furnace. This increases the fl exibility of which direction
the vent pipe can exit the furnace.
Vent Pipe Material
Vent and combustion air pipe and fi ttings must be one of
the following materials in the list and must conform to the
indicated ANSI/ASTM standards. Cement must conform
to ASTM Standard D2564 for PVC and Standard D2235
for ABS. PVC primer must meet standard ASTM F656.
When joining PVC piping to ABS, use PVC solvent cement.
(See procedure specifi ed in ASTM Standard D3138)
FURNACE
MODELS
(BTU)
FURNACE
INSTALLATION
SINGLE VENT PIPE LENGTH (FT.)
with 1 long radius elbow**
OUTLET
2” Diameter
In Canada, all plastic vent pipes and fi ttings including any
cement, cleaners, or primers must be certifi ed as a system
to ULC S636. However this requirement does not apply to
the fi nish fl anges or piping internal to the furnace.
Vent Pipe Length and Diameter
In order for the furnace to operate properly, the combustion
air and vent piping must not be excessively restrictive.
• The venting system should be designed to have the
minimum number of elbows or turns.
• All horizontal runs must slope upwards from the furnace
at 1/4 inch minimum per running foot of vent.
• Transition to the fi nal vent diameter should be done as
close to the furnace outlet as practical.
• Always use the same size or a larger pipe for combustion
air that is used for the exhaust vent.
Table 2 indicates the maximum allowable pipe length for
a furnace of known input rate, when installed with piping
DUAL VENT PIPE LENGTH (ft.)
with 1 long radius elbow on each pipe**
OUTLET
3” Diameter
INLET/OUTLET
2” Diameter
INLET/OUTLET
3” Diameter
Upfl ow90909090
60,000
80,000
100,000
120,000
1. Subtract 2.5 ft. for each additional 2 inch long radius elbow, 5 ft. for each additional 2 inch short radius elbow, 3.5 ft. for each additional 3
inch long radius elbow, and 7 ft. for each additional 3 inch short radius elbow. Subtract 5 ft for each 2” tee and 8 ft for each 3” tee. Two 45
degree elbows are equivalent to one 90 degree elbow.
2. The length of pipe needed between the inducer and the fi nish fl ange on downfl ow models is 15”.
3. This table applies for elevations from sea level to 2,000 ft. For higher elevations, decrease pipe lengths by 8% per 1,000 ft of altitude.
Horizontal50905090
Downfl ow30903090
Upfl ow90909090
Horizontal30903090
Downfl ow30903090
Upfl ow60906090
Horizontal30903090
Downfl ow30902590
Upfl owN/A90N/A90
HorizontalN/A90N/A90
Downfl owN/A90N/A90
*NOTES:
Table 2. Vent Pipe Lengths
11
Page 12
of selected diameter and number of elbows. To use the
table, the furnace input rate, the centerline length and the
number of elbows on each pipe must be known.
When estimating the length of vent runs, consideration
must be made to the effect of elbows and other fi ttings.
This is conveniently handled using the idea of “equivalent
length”. This means the fi ttings are assigned a linear
length that accounts for the pressure drop they will cause.
For example: a 2” diameter, long radius elbow is worth
the equivalent of 2.5 feet of linear run. A 90 degree tee
is worth 7 ft.
The equivalent lengths of tees and various elbows are
listed in Table 2. Measure the linear length of the vent run
and then add in the equivalent length of each fi tting. The
total length, including the equivalent fi tting lengths, must
be less than the maximum length specifi ed in Table 2.
on either side of the exterior wall (Figure 36). These
couplings may be required by local code.
• If breakable connections are required in the combustion
air inlet pipe (if present) and exhaust vent piping, then
straight neoprene couplings for 2” or 3” piping with
hose clamps can be used. These couplings can be
ordered through your local furnace distributor. To install
a coupling:
1. Slide the rubber coupling over the end of the pipe
that is attached to the furnace and secure it with
one of the hose clamps.
2. Slide the other end of the rubber coupling onto
the other pipe from the vent.
3. Secure the coupling with the second hose clamp,
ensuring that the connection is tight and leak
free.
Condensing furnace combustion products have very little
buoyancy, so Table 2 is to be used without consideration
of any vertical rise in the piping.
Vent Pipe Installation
CAUTION:
Combustion air must not be drawn from a
corrosive atmosphere.
This furnace has been certifi ed for installation with zero
clearance between vent piping and combustible surfaces.
However, it is good practice to allow space for convenience
in installation and service.
• The quality of outdoor air must also be considered. Be
sure that the combustion air intake is not located near
a source of solvent fumes or other chemicals which can
cause corrosion of the furnace combustion system. (See
list of substances on page 5).
• Route piping as direct as possible between the furnace
and the outdoors. Longer vent runs require larger
diameters. Vent piping must be sloped upwards 1/4”
per foot in the direction from the furnace to the terminal.
This is to ensure that any condensate fl ows back to the
condensate disposal system.
• If a Direct Vent (2-pipe) system is used, the combustion
air intake and the vent exhaust must be located in the
same atmospheric pressure zone. This means both
pipes must exit the building through the same portion
of exterior wall or roof as shown in Figures 6 - 9 (pages
12 - 13) and Figure 36 (page 47).
• Piping must be mechanically supported so that its weight
does not bear on the furnace. Pipe supports must be
installed a minimum of every 5 feet along the vent run to
ensure no displacement after installation. Supports may
be at shorter intervals if necessary to ensure that there
are no sagging sections that can trap condensate. It is
recommended to install couplings along the vent pipe,
12
Outdoor Terminations - Horizontal Venting
Vent and combustion air intake terminations shall be
installed as depicted in Figures 6 & 7 (page 13) and in
accordance with these instructions:
• Vent termination clearances must be consistent with the
NFGC, ANSI 2223.1/NFPA 54 and/or the CSA B149.1,
Natural Gas and Propane Installation Code. Table 15
(page 44) lists the necessary distances from the vent
termination to windows and building air intakes.
• All minimum clearances must be maintained to protect
building materials from degradation by fl ue gases as
shown in Figure 7.
• Vent and combustion air intake terminations must
be located to ensure proper furnace operation and
conformance to applicable codes. A vent terminal
must be located at least 3 feet above any forced air
inlet located within 10 feet. This does not apply to the
combustion air inlet of a direct vent (two pipe) appliance.
In Canada, CSA B149.1, takes precedence over these
instructions. See Table 17 (page 46).
• For optimal performance, vent the furnace through a wall
that experiences the least exposure to winter winds.
• The vent termination shall be located at least 3 ft.
horizontally from any electric meter, gas meter, regulator
and any relief equipment. These distances apply ONLY
Mounting Kit
Faceplate Secured
to Wall with Screws
Typical Both Pipes
Combustion
Air Inlet
Exhaust Vent
Left Side Option
Exhaust
Inlet
12" Min. to Maximum
Expected Snow Level
Typical Both Pipes
90°
Elbow
8" min.
36" max.
Both Sides
Exhaust Vent
Right Side Option
Figure 6. Inlet and Exhaust Pipe Clearances
Page 13
to U.S. installations. In Canada, CSA B149.1, takes
precedence over these instructions.
• Do not install the vent terminal such that exhaust is
directed into window wells, stairwells, under decks
or into alcoves or similar recessed areas, and do not
terminate above any public walkways.
• If venting horizontally, a side wall vent kit is available
according to the pipe diameter size of the installation.
For 2 inch pipe use side wall vent kit #904617, and
for 3 inch pipe use kit #904347. Please follow the
instructions provided with the kit.
• Concentric vent termination kits are available for use
with these furnaces. For 2 Inch pipe use kit #904177
and for 3 inch pipe use kit # 904176. Please follow the
instructions provided with the kit.
• When the vent pipe must exit an exterior wall close to
the grade or expected snow level where it is not possible
to obtain clearances shown in Figure 6, a riser may be
provided as shown in Figure 8. Insulation is required
to prevent freezing of this section of pipe. See Table 3
for vent freezing protection.
Outdoor Terminations - Vertical Venting
Termination spacing requirements from the roof and from
each other are shown in Figure 9.
The roof penetration
must be properly fl ashed and waterproofed with a plumbing
roof boot or equivalent fl ashing. Vent and combustion air
piping may be installed in an existing chimney which is
not in use provided that:
• Both the exhaust vent and air intake run the length of
the chimney.
• The top of the chimney is sealed and weatherproofed.
• The termination clearances shown in Figure 9 are
maintained.
• No other gas fi red or fuel-burning equipment is vented
through the chimney.
90° Elbow
12” Above Maximum
Expected Snow Level
(Typ. Both pipes)
Exhaust Vent
Combustion Air
Direct vent
terminal
50,000 Btuh
or less
9 In.
Note 2
Mechanical
draft vent
terminal
NOTES:
1. All dimensions shown are minimum
requirements.
2. Exterior vent terminations must be located at
least 12 In above the maximum expected snow level.
4ft.
Note 2
4 ft.
Mechanical
draft vent
terminal
12 in.
12 in.
Note 2
Mechanical
draft vent
terminal
Less
than 10 ft.
3 ft.
Forced
Air Inlet
Direct vent
terminal -
more than
50,000 Btuh
Figure 7 Vent Locations
12" Min.
19" Max.
(See Note)
12" Above
Maximum
Expected
Support
Outside
Wall
NOTE: Vent Configuration to Provide 12" Minimum
height above Snow Level.
Snow Level
1/2"
Armaflex
Insulation or
Equivalent
(if required)
Figure 8. Alternate Horizontal Vent Installation
8" Min.
36" Max.
Plumbing Vent
Roof Boot
(Typ. Both Pipes)
Figure 9. Vertical Vent Termination
Vent Freezing Protection
• When the vent pipe is exposed to temperatures below
freezing (i.e., when it passes through unheated spaces,
chimneys, etc.) the pipe must be insulated with 1/2 inch
thick sponge rubber insulation, Armafl ex-type insulation
or equivalent. Insulating pipe is important to avoid
condensate icing.
• Table 3 lists the maximum length of fl ue pipe that can
travel through an unconditioned space or an exterior
space. The total vent length must not exceed the lengths
noted in Table 2 (page 11).For Canadian installations,
please refer to the Canadian Installation Code (CAN/
CGA-B149.1 or 2) and/or local codes.
Maximum Flue Pipe Length
Winter Design
Temperature
Without Insulation
in Unconditioned and
Exterior Spaces
With Insulation
(feet)
(feet)*
204570
020 70
-201060
* = Insulation thickness greater than 3/8 inch, based on
an R value of 3.5 (ft x F x hr) / (BTU x in.)
Table 3. Vent Protection
13
Page 14
• For extremely cold climates or for conditions of short
furnace cycles (i.e. set back thermostat conditions) the
last 18 inches of vent pipe can be reduced. It is acceptable
to reduce from 3” to 2-1/2”, 3” to 2”, or 2” to 1-1/2” if the
total vent length is at least 15 feet in length, the vent
length is within the parameters specifi ed in Table 2 (page
11). The restriction should be counted as 3 equivalent
feet. Smaller vent pipes are less susceptible to freezing,
but must not be excessively restrictive. The length of the
2 inch pipe must not be longer than 18 inches.
• If furnace is installed horizontally, make sure the drainage
port on the in-line drain assembly is pointed downward
to ensure proper drainage of condensate. See Figure
33 - 34 on pages 44- 45.
• To prevent debris or creatures from entering the
combustion system, a protective screen may be installed
over the combustion air intake opening. The screens hole
size must be large enough to prevent air restriction.
Condensate Disposal
The method for disposing of condensate varies according
to local codes. Consult your local code or authority having
jurisdiction.
Each of the condensate drain lines must be J-trapped
using fi eld supplied parts. After the condensate lines are
J-trapped, they may be combined together into a single
run to the drain. The drain lines must be routed downward
to ensure proper drainage from furnace.
Neutralizer kit P/N 902377 is available for use with this
furnace. Please follow the instructions provided with
the kit.
CIRCULATING AIR REQUIREMENTS
WARNING:
Do not allow combustion products to enter the
circulating air supply. Failure to prevent the
circulation of combustion products into the
living space can create potentially hazardous
conditions including carbon monoxide
poisoning that could result in personal injury
or death.
All return ductwork must be secured to
the furnace with sheet metal screws. For
installations in confi ned spaces, all return
ductwork must be adequately sealed. When
return air is provided through the bottom of the
furnace, the joint between the furnace and the
return air plenum must be air tight.
The surface that the furnace is mounted on must
provide sound physical support of the furnace
with no gaps, cracks or sagging between the
furnace and the fl oor or platform.
Return air and circulating air ductwork must
not be connected to any other heat producing
device such as a fi replace insert, stove, etc.
This may result in fi re, explosion, carbon
monoxide poisoning, personal injury, or
property damage.
Existing Installations
When an existing furnace is removed from a vent system
serving other appliances, the existing vent system may
not be sized properly to vent the remaining appliances
(For example: water heater). An improperly sized venting
system can result in the formation of condensate, leakage,
or spillage. The existing vent system should be checked
to make sure it is in compliance with NFGC and must be
brought into compliance before installing the furnace.
NOTE: If replacing an existing furnace, it is possible you
will encounter an existing plastic venting system that is
subject to a Consumer Product Safety Commission recall.
The pipes involved in the recall are High Temperature
Plastic Vent (HTPV). If your venting system contains these pipesDO NOT reuse this venting system! This
recall does not apply to other plastic vent pipes, such
as white PVC or CPVC. Check for details on the CPSC
website or call their toll-free number (800) 758-3688.
Plenums and Air Ducts
• Plenums and air ducts must be installed in accordance
with the Standard for the Installation of Air Conditioning
and Ventilating Systems (NFPA No. 90A) or the
Standard for the Installation of Warm Air Heating and
Air Conditioning Systems (NFPA No. 90B).
• Tables 8 - 10 (pages 35 - 37) contain the maximum
airfl ow and temperature rise data for fi xed and variable
speed motors. If the maximum airfl ow is 1,600 CFM or
more, it is recommended that two openings be used for
return air on upfl ow furnaces. Downfl ow furnaces can
only use one return opening.
• It is recommended that the outlet duct contain a
removable access panel. The opening should be
accessible when the furnace is installed in service and
shall be of a size that smoke or refl ected light may be
observed inside the casing to indicate the presence of
leaks in the heat exchanger. The cover for the opening
shall be attached in such a way as to prevent leaks.
• If outside air is used as return air to the furnace for
ventilation or to improve indoor air quality, the system
must be designed so that the return air is not less than
60° F (15° C) during operation. If a combination of
indoor and outdoor air is used, the ducts and damper
14
Page 15
system must be designed so that the return air supply
to the furnace is equal to the return air supply under
normal, indoor return air applications.
• When a cooling system is installed which uses the
furnace blower to provide airfl ow over the indoor coil,
the coil must be installed downstream (on the outlet
side) of the furnace or in parallel with the furnace.
• If a cooling system is installed in parallel with the furnace,
a damper must be installed to prevent chilled air from
entering the furnace and condensing on the heat
exchanger. If a manually operated damper is installed,
it must be designed so that operation of the furnace is
prevented when the damper is in the cooling position
and operation of the cooling system is prevented when
the damper is in the heating position.
• It is good practice to seal all connections and joints
with industrial grade sealing tape or liquid sealant.
Requirements for sealing ductwork vary from region
to region. Consult with local codes for requirements
specifi c to your area.
Supply Air Connections
The supply air must be delivered to the heated space by
duct(s) secured to the furnace casing, running full size
and without interruption.
Upfl ow and Horizontal Furnaces
To attach the supply air duct to the furnace, bend the
furnace fl anges (Figure 28, page 34) upward 90° with a pair
of wide duct pliers. Position the duct on top of the furnace
and secure together with sheet metal screws. The screws
must penetrate the sheet metal casing and furnace fl ange.
Tape or seal all seams if required by local code.
Downfl ow Furnaces
To attach the supply air duct to the downfl ow furnace,
position the furnace over the duct and secure together
with sheet metal screws. The screws must penetrate the
duct and furnace cabinet.
Return Air Connections
In applications where the supply ducts carry heated air
to areas outside the space where the furnace is installed,
the return air must be delivered to the furnace by duct(s)
secured to the furnace casing, running full size and without
interruption.
Upfl ow Horizontal Furnaces
For upfl ow installations, the return air ductwork may
be connected to the left side, right side, or bottom. The
bottom panel (Figure 28) must be installed for left or right
return air. NOTE: Do not use the back of the furnace
for return air.
the blower assembly. Position the return air duct over
the opening in the side and secure together with sheet
metal screws. The screws must penetrate the duct and
furnace cabinet.
WARNING:
The solid base of the furnace must be in
position when the furnace is installed with side
return air ducts. Removal of all or part of the
base could cause circulation of combustible
products into the living space and create
potentially hazardous conditions, including
carbon monoxide poisoning that could result
in personal injury or death.
Bottom Return Installations
The bottom panel (Figure 28) must be removed from the
bottom of the furnace for bottom return air. If bottom panel
is installed, go to page 15 for removal instructions. Position
the furnace over the return air duct and secure together
with sheet metal screws. The screws must penetrate the
duct and furnace cabinet.
Downfl ow Furnaces
To attach the return air duct to the fur nace, bend the furnace
fl anges (Figure 28, page 34) upward 90° with a pair of
wide duct pliers. Position the duct on top of the furnace
and secure together with sheet metal screws. The screws
must penetrate the sheet metal cabinet and furnace fl ange.
Tape or seal all seams if required by local code.
Acoustical Treatments
Damping ducts, fl exible vibration isolators, or pleated
media-style fi lters on the return air inlet of the furnace
may be used to reduce the transmission of equipment
noise eminating from the furnace. These treatments can
produce a quieter installation, particularly in the heated
space. However, they can increase the pressure drop in
the duct system. Care must be taken to maintain the proper
maximum pressure rise across the furnace, temperature
rise and fl ow rate. This may mean increasing the duct
size and/or reducing the blower speed. These treatments
must be constructed and installed in accordance with
NFPA and SMACNA construction standards. Consult
with local codes for special requirements. For best sound
performance, be sure to install all the needed gaskets and
grommets around penetrations into the furnace, such as
for electrical wiring
Side Return Installations
To attach the return air duct to the left or right side of the
furnace, punch out the four knockouts (Figure 28) from the
preferred side of the furnace. Using sharp metal cutters,
cut an opening between all four knockouts to expose
15
Page 16
FURNACE INSTALLATION
*TC series gas furnaces offer a wide range of installation
options, including installation in the upfl ow or horizontal
positions with either right, left, or upfl ow return air. The
*TL series gas furnaces may only be installed as a down
fl ow application.
General Requirements
• The furnace must be leveled at installation and
attached to a properly installed duct system. See
Table 1 (page 7) for the required clearances needed
to move the furnace to its installation point (hallways,
doorways, stairs, etc).
• The furnace must be installed so that all electrical
components are protected from water.
• The furnace must be installed upstream from a
refrigeration system. (If applicable)
• The cabinet plug must always be used to close the hole
in the side of the furnace when rotating the inducer.
• The furnace requires special venting materials and
installation procedures. See pages 10 -14 for venting
guidelines and specifi cations.
Direct Vent (2-Pipe) Applications
It is important that Direct Vent (2-pipe) systems maintain
an airtight fl ow path from the air inlet to the fl ue gas outlet.
The furnace ships from the factory with two holes in the
cabinet for the air inlet and fl ue gas outlet. In certain
confi gurations, it is necessary to remove and relocate a
plastic cap in the furnace cabinet. If changing the position
of the air inlet and fl ue gas outlet, it is required that the
previous hole be closed off with the plastic cap to maintain
air tightness in the furnace. The hole locations for *TC and
*TL furnaces are shown in Figure 28 (page 34).
Upfl ow Installation
WARNING:
The furnace must not be installed directly on
carpeting, tile, or any combustible material other
than wood fl ooring.
Downfl ow Installation
WARNING:
The furnace must not be installed directly on
carpeting, tile, or any combustible material other
than wood fl ooring.
WARNING:
Failure to install the downfl ow sub-base kit
may result in fi re, property damage or personal
injury.
To install the furnace on combustible fl ooring, a special
sub-base is required. Downfl ow sub-base kits are factory
supplied accessories and are listed according to the cabinet
letter of the furnace. For ‘B’, ‘C’, and ‘D’ size cabinets use
Kit #904911. Please follow the instructions provided
with the kit.
A downfl ow sub-base kit is not necessary if the furnace
is installed on a factory or site-built cased air conditioning
coil. However, the plenum attached to the coil casing
must be installed so that its surfaces are at least 1” from
combustible construction.
Installation on a concrete slab.
1. Create an opening in the fl oor according to the
dimensions in Figure 10.
2. Position the plenum and the furnace as shown in
Figure 11 (page 17).
Opening in concrete floor
“A”
“B”
Side Return Air Inlet
*TC series gas furnaces are shipped with the bottom panel
installed (Figure 28). If the upfl ow furnace is installed using
both side return air inlets, the bottom panel must not be
removed. The bottom panel must be in place if the bottom
of the furnace is not being used as a return.
Bottom Return Air Inlet
If the *TC series gas furnace is installed using the bottom
as a return air inlet and 1 side return, the bottom panel
(Figure 28) must be removed.
16
Cabinet Size Dim. “A” Dim. “B”
‘B’
‘C’
‘D’
Figure 10. Cutout Dimensions
16
20
23
⅝
⅛
⅝
19
19
19
¼
¼
¼
Page 17
Concrete
Floor
Furnace
Sheet
Metal
Plenum
Figure 11. Furnace on a Concrete Slab
Horizontal Installation
WARNING:
The furnace must not be installed directly on
carpeting, tile, or any combustible material other
than wood fl ooring.
The *TC series gas furnace can be installed horizontally
(Figure 12) in an attic, basement, crawl space or alcove.
It can also be suspended from a ceiling in a basement
or utility room in either a right to left airfl ow or left to right
airfl ow as shown in Figure 13.
*TC series furnaces are shipped with the bottom panel
installed. If furnace is installed horizontally, remove the
bottom panel from the furnace before attaching the duct
system. See Bottom Panel Removal section.
If installing the furnace in an attic, it is required that a drip
pan be placed under the furnace. If the installation is on
a combustible platform (Figure 12), it is recommended
that the drip pan extend at least 12 inches past the top
and front of the furnace.
If the furnace will be suspended from the ceiling, assemble
a support frame (Figure 13) using slotted iron channel
and full threaded rod. Fasten the frame together with nuts,
Nuts (x2)
Lag
Bolt
Threaded
Rod
Washer
and
Lockwasher
Nuts (x2)
Figure 13. *TC Horizontally Suspended
in Attic or Crawl Space
washers, and lockwashers. Secure the support frame to the
rafters with lag bolts. The furnace can also be suspended
using steel straps around each end of the furnace. The
straps should be attached to the furnace with sheet metal
screws and to the rafters with bolts.
It is recommended for further reduction of fi re hazard
that cement board or sheet metal be placed between the
furnace and the combustible fl oor and extend 12 inches
beyond the front of the door and top of the furnace.
Bottom Panel Removal
The steps listed below describe how to remove the bottom
panel from the furnace. See Figure 14.
1. Remove the door (1) from the blower compartment.
2. Disconnect the blower motor wiring harness (2) from
the control board.
3. Remove two screws (3) securing the blower assembly
(4) to the furnace.
4. Carefully pull the blower assembly (4) out thru the
front of the furnace.
Electrical Supply
Connection
Coil Plenum
Combustion Air
One-Pipe Installation Shown
Airflow
Condensate Drain Lines Must Be Trapped
With J-Trap or Field Supplied Loop.
Figure 12. *TC Horizontal installation on a Platform
Exhaust Pipe
Vented to Outside
Combustible
Platform
1
3
4
6
2
7
Figure 14. Bottom Panel Removal
5
17
Page 18
5. Remove all screws (5) securing bottom panel (6) to
bottom of furnace and front brace (7).
6. Lift up and slide bottom panel (6) out through front of
furnace.
7. Reinstall the blower assembly (4) in reverse order.
Alternate Bottom Panel Removal
If the bottom panel cannot be removed using the previous
instructions, the steps below are an alternate method for
removing the bottom panel. (See Figure 15).
1. Remove the door (1) from the blower compartment
2. Remove all screws securing the bottom panel (2) to
the front brace (3).
3. Remove two screws (4) securing the furnace cabinet
to the blower deck (5).
4. Remove all screws (6) securing the furnace cabinet
to the bottom panel (2).
5. Remove the screw (7) securing the bottom corner of the
furnace cabinet to the front brace (3).
6. Carefully spread the bottom corner of the furnace
cabinet outwards while sliding the bottom panel (2)
out through the front of the furnace.
7. Reassemble the furnace in reverse order.
Conventional (1 Pipe)
VentUpfl ow
RightOption 1N/AN/AOption 9
UpN/AOption 5Option 6Option 10
LeftOption 2N/AN/AOption 11
VentUpfl ow
RightOption 3N/AN/AOption 12
UpN/AOption 7Option 8Option 13
LeftOption 4N/AN/AOption 14
†
Requires a 2 inch PVC endcap.
Horiz.
Right
Direct Vent (2-pipe)
Horiz.
Right
Horiz.
Left
Horiz.
Left
Downfl ow
†
†
Downfl ow
†
†
Table 4. Vent and Inducer Blower Options
Inducer Assembly Rotation
WARNING:
Inducer rotation must be completed before
the furnace is connected to gas and electric. If
both utilities have been connected, follow the
shutdown procedures printed on the furnace
label and disconnect the electrical supply.
4
1
5
7
6
2
3
Figure 15. Alternate Removal Method
Vent and Inducer Assembly Options
To increase installation fl exibility, the inducer assembly
can be rotated to 2 different positions. Each variation has
slightly different requirements with regard to condensate
disposal and, in some cases, the need to seal the furnace
cabinet. IMPORTANT NOTE: The Inducer Assembly
must never be positioned to vent downwards on
horizontal installs.
CAUTION:
It is good practice to label all wires prior
to disconnection. Wiring errors can cause
improper and dangerous operation.
1. Disconnect the electrical harness (1) from the inducer
assembly (2). See Figure 16.
2. Remove the inducer assembly ground wire (3) from
the blower deck (4) or door.
3. Remove four screws (5) securing the inducer assembly
(2) to the header box (6).
4. Remove drain tube from inline drain assembly.
5. Rotate the inducer assembly (2) to its new position.
5
7
6
2
3
Before using Table 4 (page 19) the number of pipes (1-pipe
or 2-pipe) connected to the furnace must be known. Find
the proper furnace style (upfl ow, horizontal, or downfl ow)
and then the side that the pipes will exit from the furnace.
Finally select the option that properly matches your
installation type from Figures 37 - 39 (pages 48 - 50).I
18
1
4
Figure 16. Inducer Assembly Rotation
Page 19
6. Secure the inducer assembly (2) to the header box (6)
by reinstalling the four screws (5) and the extra screw
provided in the parts package.
7. Remove the cabinet plug (7) from side of furnace and
reinstall in hole on opposite side of cabinet.
8. If applicable, install condensate drain on the in-line
drain assembly. See Figures 37-39 (pages 48 - 50).
9. Reconnect the electrical harness (1) to the inducer
assembly (2).
10. Reconnect the inducer assembly ground wire (3) to
the blower deck (4) or door.
11. Verify proper operation as detailed on the furnace
label.
Accessories
The components in Figures 17 - 19 are included in
the extra parts bag supplied with the purchase of *TC/
*TLfurnaces. Depending on your particular installation,
some of these components are optional and may not be
used. Please refer to the descriptions and accompanying
fi gures when installing these items.
Finish Flange (Fig. 17)
The fi nish fl ange must be installed to vent the combustion
air pipe through the top of the furnace. NOTE: For proper
installation it is important that the pipe and screw holes in
the fi nish fl ange, gasket, and cabinet are aligned.
1. Position fl ange gasket over hole in the furnace
cabinet.
2. Position fi nish fl ange on top of the fl ange gasket.
3. Secure fl ange and gasket to cabinet with three fi eld
supplied sheet metal screws.
rubber grommet should be installed in the 1 5/8” hole
prior to running the gas pipe into the cabinet. No sealants
are required.
The 3/4” rubber grommet is used if venting out the left
side of the cabinet and the drain tube is routed through
the blower deck. Remove the plastic plug from the hole
and install the grommet before routing the drain tube.
ø 2 1/4” Rubber
Grommet
ø 7/8” Rubber
Ø 3/4” Rubber
Grommet
Grommet
Figure 18. Rubber Grommets
PVC TEE, Reducer, and Hose Barbs (Fig. 19)
IMPORTANT NOTES:
Before permanently installing these components,
it is recommended you dry-fi t them fi rst to ensure
proper fi t and alignment with other vent pipes.
The PVC items shown in Figure 19 (page 20) are not
supplied with *TL furnaces.
The 2” PVC tee, reducer, and hose barb are used when
the inducer is rotated to vent out thru the left or right side
of the furnace cabinet.
Inlet Air
Finish Flange
Flange Gasket
Figure 17. Finish Flanges
Rubber Grommets (Fig. 18)
The 2 1/4” rubber grommet is used to seal the opening
between the furnace cabinet and the 2” PVC vent pipe.
The rubber grommet should be installed in the 3” hole
prior to running the vent pipe out of cabinet. No sealants
are required.
The 7/8” rubber grommet is used to seal the opening
between the furnace cabinet and the gas pipe. The
The 1/2” x 3/4” hose barb can be used to route the
condensate drain to the outside of the cabinet. It must
be installed from inside the cabinet with the threaded
end inserted thru the 1 1/16” hole. See Figure 28
2” PVC Pipe from
Inline Drain Assembly
(Not Included)
2” PVC TEE
2” x 1/2” PVC
Reducer
1/2” x 1/2”
Hose Barb
1/2” x 3/4”
Hose Barb
Figure 19. PVC Tee (2”), Reducer and Hose Barb
19
Page 20
(page 34) for hole location The condensate drain should
be connected to the barbed end. Attach 1” PVC drain
line to the threaded end.
drain lines on the outside of the residence be wrapped
with an industry approved insulation or material
allowed by local code.
1. Install the 1/2” x 1/2” hose barb on the 2” PVC reducer.
Do not over tighten! NOTE: Use an adequate amount
of Tefl on tape on the threads. Do not use liquid
sealants.
2. Install the reducer on one end of the PVC tee. Use
appropriate primer and cement to permanently bond
the reducer and tee together.
3. Install the tee on the 2” vent pipe that is extending out
the side of the cabinet. Use appropriate primer and
cement to permanently bond them together.
4. Verify all connections and joints for tight fi t and proper
alignment with other vent pipes.
Condensate Drain Lines
The placement of the condensate drain lines will depend
on the confi guration selected in Table 4 (page 18). The
drain lines can be routed out the left or right side of the
furnace, but must maintain a downward slope to ensure
proper condensate drainage. The J-trap may need to be
rotated to the side that matches your setup in Figures
37 - 39 (pages 48 - 50). To rotate the J-trap, loosen the
clamp on the drain tube, rotate the J-trap to either side,
and retighten the clamp.
Four general rules apply:
• Each condensate drain line must be separately trapped
using a J-Trap or fi eld supplied loop.
• There must always be a drain attached to the collector
at the outlet of the secondary heat exchanger.
• There must always be a drain at the outlet of the inducer
assembly.
• There must always be a drain at the lowest point of the
venting system.
GAS SUPPLY AND PIPING
All gas piping must be installed in compliance with local
codes and utility regulations. In the absence of local
codes the gas line installation must comply with the latest
edition of the National Fuel Gas Code (ANSI Z223.1) or
(CAN/CGA B149.1 or .2) Installation Codes.
IMPORTANT NOTES:
• Some local regulations require the installation of a
manual main shut-off valve and ground joint union
external to the furnace as depicted in Figure 20.
The shut-off valve should be readily accessible for
service and/or emergency use. Consult the local
utility or gas supplier for additional requirements
regarding placement of the manual main gas shutoff.
• Gas piping must never run in or through air ducts,
chimneys, gas vents, or elevator shafts.
• Compounds used on threaded joints of gas piping
must be resistant to the actions of liquefied
petroleum gases.
• The main gas valve and main power disconnect to
the furnace must be properly labeled by the installer
in case emergency shutdown is required.
• Flexible gas connectors are not recommended for
this type of furnace but may be used if allowed by
local jurisdiction. Only new fl exible connectors may
be used. Do not reuse old fl exible gas connectors.
• A drip leg should be installed in the vertical pipe
run to the unit as shown in Figure 20.
Table 12 (page 38) lists gas fl ow capacities for standard
pipe sizes as a function of length in typical applications
based on nominal pressure drop in the line.
Exceptions and clarifi cations to the general rules:
• In some cases, the lowest point in the vent system is
where it connects to the inducer (Options 6 & 8). In this
case one drain at this location is suffi cient.
• If the vent exits the furnace horizontally, the vent may be
turned vertically with a tee. The drip leg formed by the tee must include a drain (Options 1-4, 9, 11, 12, 14).
• In certain cases, it is permitted to drain the inducer back
into the top drain of the collector (Options 1, 3, 5, 7, 9,
10, 12, & 13). To ensure proper drainage of condensate,
make sure the drain line does not sag or becomes
twisted. The drain tube supplied with the furnace may
need to be trimmed.
IMPORTANT NOTE: If the furnace is installed in an
area where temperatures fall below freezing, special
precautions must be made for insulating condensate
drain lines that drain to the outdoors. If condensate
freezes in the lines, this will cause improper operation
or damage to the furnace. It is recommended that all
20
The furnace may be installed for either left or right side gas
entry. When connecting the gas supply, provide clearance
between the gas supply line and the entry hole in the
furnace casing to avoid unwanted noise and/or damage
to the furnace. Typical gas hookups are shown in Figure
20 (page 21).
Leak Check
WARNING:
FIRE OR EXPLOSION HAZARD
Never test for gas leaks with an open fl ame.
Check all connections using a commercially
available soap solution. A fi re or explosion
may result causing property damage, personal
injury or loss of life. Failure to follow the safety
warnings exactly could result in serious injury,
death or property damage.
Page 21
UPFLOW MODELS
6
1
2
6
2
9
3
Note “A”
9
See
Note “A”
See
1
See
Note “B”
5
Left Side Entry
7
4
DOWNFLOW MODELS
4
8
See
Note “B”
8
4
Right Side Entry
7
4
See
Note “A”
9
3
5
See
Note “A”
9
3
5
See
Note “B”
Left Side Entry
2
7
6
8
See
Note “B”
1
Right Side Entry
2
7
5
1
6
ITEM # and COMPONENT
(1) Automatic Gas Valve
(w/ manual shut-off)
(2) Burner Assembly(3) Dripleg
(4) Elbow(5) Ground Joint Union(6) Manifold
(7) Pipe Nipple (8 inch)(8) Plug(9) Shut - Off Valve
NOTE A: Some utilities require Shut- Off Valve to be 4 to 5 feet above fl oor.
NOTE B: Inducer assembly omitted for clarity of pipe installation.
Figure 20. Typical Gas Connections
3
21
Page 22
After the gas piping to the furnace is complete, all
connections must be tested for gas leaks. This includes
pipe connections at the main gas valve, emergency shutoff
valve and fl exible gas connectors (if applicable). The soap
and water solution can be applied on each joint or union
using a small paintbrush. If any bubbling is observed,
the connection is not sealed adequately and must be
retightened. Repeat the tightening and soap check process
until bubbling ceases.
IMPORTANT NOTE: When pressure testing gas supply
lines at pressures greater than 1/2 psig (14 inch W.C.),
the gas supply piping system must be disconnected
from the furnace to prevent damage to the gas control
valve. If the test pressure is less than or equal to 1/2
psig (14 inch W.C.), close the manual shut-off valve.
High Altitude Application
The installation of this furnace at altitudes above 2,000
feet must meet the requirements of the National Fuel Gas
Code or local jurisdiction. In Canada, the requirements for
high altitude are different and governed by CGA B149.1.
Please consult your local code authority.
WARNING:
The reduction of input rating necessary for high
altitude installation may only be accomplished
with factory supplied orifi ces. Do not attempt
to drill out orifi ces in the fi eld. Improperly
drilled orifi ces may cause fi re, explosion,
carbon monoxide poisoning, personal injury
or death.
The furnaces are shipped from the factory with orifi ces
and gas regulator settings for natural gas operation at sea
level altitudes. At 2000 feet, the NFGC requires that this
appliance be derated 4% for each 1000 feet of altitude.
For example, the input needs to be reduced 8% at 2,000
feet, 12% at 3,000 feet, etc. This deration is in reference
to the input rate and gas heating value at sea level.
To derate the furnace requires knowing the heating value of
the gas at the installation site. Heating values at particular
job sites vary for two reasons:
1. The chemical mixture of the gas varies from region
to region and is expressed as the “sea level heating
value”.
2. The heating value varies by altitude. For this reason,
particularly in high altitude areas, the local gas utility
usually specifi es the heating value at the residence’s
gas meter as the “local value”.
For added fl exibility, two tables have been provided for
natural gas installations with high or low heating values at
sea level. Tables 15 and 16 (page 40) contain the orifi ce
sizes and manifold pressure to use at various altitudes.
Table 15 (HIGH) is for natural gas installations with a
22
heating value of more than 1,000 Btu per cubic foot and
Table 16 (LOW) is for less than 1,000 Btu per cubic foot.
To determine which table to use:
1. Consult your local utility for the local heating value at
your installation.
2. From Table 14 (page 39), fi nd your local heating value
as supplied by the utility company. Follow down the
column and stop at your altitude level.
3. If your sea level heating value is HIGH, use Table 15
or if it’s LOW, use Table 16. See example.
Type of Gas: .........................................Natural Gas
Local Heating Value of Gas: ............................750
From Table 14, fi nd 750 and follow down the column,
stop at the 5,000 feet row. The heating value listed is
LOW. Table 16 will be used to determine orifi ce size and
manifold pressure.
After changing the regulator pressure or changing the
orifi ces, it is required that you measure the gas input
rate. This may be accomplished in the usual way, by
clocking the gas meter and using the local gas heating
value. See Verifying and Adjusting the Input Rate section
(page 27).
IMPORTANT NOTE: Observe the action of the burners
to make sure there is no yellowing, lifting or fl ashback
of the fl ame.
Conversion to LP/Propane
WARNING:
The furnace was shipped from the factory
equipped to operate on natural gas. Conversion
to LP/propane gas must be performed by
qualifi ed service personnel using a factory
supplied conversion kit. Failure to use the
proper conversion kit can cause fi re, explosion,
property damage, carbon monoxide poisoning,
personal injury, or death.
Conversion to LP/propane is detailed in the installation
instructions provided with the conversion kit. Generally,
this will require the replacement of the burner orifi ces and
the spring/stem assembly in the pressure regulator.
Approved conversion kits are listed below. Please follow the instructions provided with each kit.
• The United States LP/Propane Gas Sea Level and High
Altitude Conversion Kit (P/N 904914) is for LP/propane
conversion in the United States at altitudes between
2,000 ft. and 10,000 ft. above sea level.
Page 23
• The Canadian LP/Propane Gas Sea Level and High
Altitude Conversion Kit (P/N 904915) is for LP/propane
conversions in Canada at altitudes between zero and
4,500 ft. above sea level.
In the U.S., if installation is above 2,000 ft., refer to Table
13 (page 39) to determine the correct orifi ce size and
regulator pressure. When conversion is complete, verify
the manifold pressure and input rate are correct as listed
in the tables.
ELECTRICAL WIRING
WARNING:
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failure to follow safety warnings exactly could
result in dangerous operation, serious injury,
death or property damage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Before servicing, disconnect all electrical
power to furnace.
• When servicing controls, label all wires prior to
disconnecting. Reconnect wires correctly.
• Verify proper operation after servicing.
• Electrical connections must be in compliance with all
applicable local codes, and the current revision of the
National Electric Code (ANSI/NFPA 70).
• For Canadian installations the electrical connections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).
Fixed Speed Blower Applications
NOTE: This section applies only to furnaces with model
numbers suffi xed with two numbers, followed by a letter,
such as 35C or 45D. If your model has suffi x VA, VB,
VC, or VD, please consult the Variable Speed Blower
Application section.
The fi xed speed motor control board (Figure 29) contains
a set of dip switches for setting the blower speed. Use
pins 1 to 4 to set the blower speed for heating and pins
5 to 8 to set the speed for cooling. To determine the
appropriate switch settings for your installation, refer to
Table 8 (page 35).
For thermostats with a dehumidifi er output, use a fi eld
supplied wire to connect the thermostat’s dehumidifi er
output to the terminal marked “DHUM”. The thermostat
should be set so that the DHUM output should be high
(positive) when dehumidifi cation is needed. See page 25
for additional dehumidifi cation options.
CAUTION:
The terminal marked “Y1_IN” on the variable
speed motor control board is not an output to
drive the outdoor unit. DO NOT connect Y1_IN on
the motor control board to the outdoor unit.
Variable Speed Blower Applications
NOTE: This section applies only to models ending with
the suffi xes VA, VB, VC, or VD.
The variable speed motor control board (Figure 30, page
41) has a set of dip switches for setting the base blower
speed. Use pins 1 to 4 to set the blower speed for heating
and pins 5 to 8 to set the speed for cooling. To determine
the appropriate switch settings for your installation, see
Table 9 (page 36) for heating or Table 10 (page 37) for
cooling.
IMPORTANT NOTE: If replacing any of the original wires
supplied with the furnace, the replacement wire must
be copper wiring and have a temperature rating of at
least 105°F (40°C). For electrical specifi cations, refer
to the furnace nameplate or Table 5 (page 26).
Two-stage furnaces use high effi ciency circulating air
motors that come in two variations and both are controlled
differently. The fi xed speed motor control board (Figure
29, page 41) controls the torque and the variable speed
motor control board (Figure 30) controls the airfl ow at a
constant CFM. Both boards use the same furnace control
board (Figure 29).
Use fi eld supplied wire to connect the thermostat’s
dehumidifi er output to the terminal marked “DHUM”. The
thermostat should be set so that the DHUM output is high
(positive) when dehumidifi cation is needed. See page 25
for additional dehumidifi cation options.
CAUTION:
The variable speed control board is also used
by other appliances. Many of the terminals and
connections on the board are for other appliances
and are not used in the two stage application. The
only two-stage fi eld connection to this board is
the DHUM terminal, used to reduce the blower
speed during cooling. See page 26.
23
Page 24
Wiring Confi gurations
Depending on the type of air conditioning unit and
thermostat used, both blower applications utilize three
basic wiring confi gurations:
Single Stage AC and Single Stage Thermostat (Fig. 21)
This option does not use the full two-stage control
capability of the furnace, but the possibility of timed
autostaging is available. See Autostaging for Single Stage
Thermostats.
• Connect the thermostat’s W output (Figure 21) to the
furnace control boards W1 terminal. This allows the
furnace to always run in low output mode.
• Always connect the thermostat C and R to the furnace
control board C and R.
• For cooling, connect the thermostats Y signal to the
furnace control board Y/Y2 terminal.
• Field supplied wires should also connect Y/Y2 and C
to the outdoor unit’s Y and C terminals.
ROOM THERMOSTAT
(SINGLE STAGE)
W
G
C
1
Y
G
Y/Y2
Y1
TWO STAGE FURNACE BOARD
DHUM
R
A/C CONDENSING UNIT
R
W1
C
W2
Y
C
(SINGLE STAGE)
DHUM
HIGH EFFICIENCY
BLOWER MOTOR
CONTROL BOARD
Figure 21. Wiring Confi guration 1
Single Stage AC and Two Stage Thermostat (Fig. 22)
This option uses the full two stage heating capability of
the furnace with a single stage outdoor unit:
• Connect the thermostat’s W1 and W2 outputs to the
furnace control board’s W1 and W2 terminals.
• Always connect the thermostat C and R to the furnace
control board C and R
• For cooling, connect the thermostats Y signal to the
furnace control board Y/Y2 terminal.
• Field supplied wires should also connect Y/Y2 and C
to the outdoor unit’s Y and C terminals.
ROOM THERMOSTAT
(TWO - STAGE)
W
W
Y
R DHUMC
G
1
2
Y
C
A/C CONDENSING UNIT
(SINGLE STAGE)
DHUM
HIGH EFFICIENCY
BLOWER MOTOR
CONTROL BOARD
Two-Stage AC and Two-Stage Thermostat (Fig. 23)
This option uses the full two stage heating capability of
the furnace with a two stage outdoor unit:
• Connect the thermostat’s W1 and W2 outputs to the
furnace control board’s W1 and W2 terminals.
• Always connect the thermostat C and R to the furnace
control board C and R.
• For cooling, connect the thermostat Y and Y1 to the
furnace control board’s Y/Y2 and Y1 terminal’s.
• Field supplied wires should also connect the Y/Y2 and
Y1 signals to the outdoor unit’s Y and Y1 terminals.
• Connect terminal C to the outdoor unit’s C.
ROOM THERMOSTAT
(TWO STAGE)
W
W
Y
Y
2
1
Y/Y2
Y1
TWO STAGE FURNACE BOARD
DHUM
R
C
G
1
2
Y2
Y1
C
A/C CONDENSING UNIT
(TWO STAGE)
R
G
W1
C
W2
DHUM
HIGH EFFICIENCY
BLOWER MOTOR
CONTROL BOARD
Figure 23. Wiring Confi guration 3
Autostaging for Single Stage Thermostats
The Autostaging feature included on all G7 2-stage
furnaces makes it possible to use a single stage thermostat
and still receive some of the benefi ts of 2-stage furnace
operation. If Autostage is enabled, the furnace will start in
low fi re, but after a period of time jump to high fi re, until the
heating load is met. See Low Voltage Wiring (page 25).
Autostaging options are selected using the Autostage
jumper (Figure 31, page 41) located near the thermostat
screw terminal block. On the circuit board, Autostage
jumper pins are electrically connected on the circuit board
to R, W1, and W2 such that:
1. When the Autostage jumper is in the “SHORT” position,
R is connected to W2. Setting the Autostage jumper
in the “SHORT” position is the same as jumping R to
W2. This connection signals the control to utilize an 8
minute delay between low fi re and high fi re when a call
for heat is supplied via 24V signal to W1.
2. When the Autostage jumper is in the “LONG” position,
W1 and W2 are connected. Setting the Autostage
jumper in the “LONG” position is the same as jumpering
W1 and W2 together. The control board knows that
Autostaging (at 12 minutes, the “LONG” setting) is active
when 24vac inputs from both W1 and W2 are received
at the same time.
R
G
Y/Y2
W1
C
Y1
TWO STAGE FURNACE BOARD
W2
Figure 22. Wiring Confi guration 2
24
Page 25
Autostaging for Two-Stage Thermostats
The Autostage setting on the furnace control board (Figure
31) is disabled when shipped from the factory. This feature
will be not used when paired with a two-stage thermostat.
The Autostage Jumper (P7) must be kept on the NONE
setting to allow the thermostat to adjust stages.
IMPORTANT NOTE: An electrical disconnect must be
installed readily accessible from and located within
sight of the furnace. See Figure 25 (page 26) or the
wiring diagram label inside of the control door. Any
other wiring methods must be acceptable to authority
having jurisdiction.
Please note that on certain thermostats, even without
the Autostage jumper in the “LONG” position, W1 and
W2 may be energized at exactly the same time when
a recovery from a set-back begins, the user adjusts the
set point, or the system is powered on. If W1 and W2 are
energized at exactly the same time for any reason, the
control will operate in the Autostage “LONG” (12 minute)
mode. If the Autostage jumper is in the “NONE” position
and Autostaging is activated unexpectedly for any of the
reasons listed, it will return to normal, staged operation
after the completion of the heating cycle.
Dehumidifi cation Options
Both motor control boards (Figures 29 & 30, page 41)
have a DHUM connection that causes the system to
increase the amount of humidity that is removed from the
circulating air. This is accomplished by reducing the CFM
and allowing the cooling coil to become colder. This will
only occur when there is a call for cooling.
There are many ways that this can be electrically wired:
1. If the room thermostat incorporates a humidity sensor
and DHUM output, connect the DHUM on the thermostat
to the DHUM terminal on the motor control board
(Figure 24).
2. If using a separate humidistat, connect the DHUM
and R terminals on the humidistat to the DHUM
and R terminals on the motor control board.
In this option, the DHUM output of the humidistat must
be set to be normally open and closed when there is
a call for humidifi cation.
3. If a humidistat is not available, it is an acceptable option
to connect the R and DHUM terminals on the motor
control board together with a fi eld supplied wire. This
option causes the blower to run at a reduced CFM for
10 minutes after a call for cooling.
MOTOR
CONTROL BOARD
DHUM
DHUM
R
HUMIDISTAT
Figure 24. DHUM Wiring Confi guration 7
Line Voltage Wiring
It is recommended that the line voltage (115 VAC) to
the furnace be supplied from a dedicated branch circuit
containing the correct fuse or circuit breaker for the furnace
(Table 5, page 26).
R
CAUTION:
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify
proper operation after servicing.
IMPORTANT NOTE: Proper line voltage polarity must
be maintained in order for the control system to
operate correctly. Verify the incoming neutral line is
connected to the white wire and the incoming “hot”
line is connected to the black wire. The furnace will not
operate unless the polarity and ground are properly
connected as shown in Figure 25.
Low Voltage Wiring
The thermostat must be installed according to the
instructions supplied by the thermostat manufacturer.
Low voltage connections (24 VAC) from the thermostat
are wired to the terminal strip on the integrated control
in the furnace. Recommended minimum wire gauge for
thermostat wiring is shown in Table 5.
The thermostat must not be installed on an outside wall or
any other location where its operation may be adversely
affected by radiant heat from fi replaces, sunlight, or lighting
fi xtures, and convective heat from warm air registers or
electrical appliances.
IMPORTANT NOTE: Set the heat anticipator according
to the instructions supplied by the thermostat
manufacturer.
To determine the heat anticipator setting:
1. Add the current draw of the system components; or
2. Measure the current fl ow on the thermostat R-W circuit
after the circulating blower motor has started.
Grounding
WARNING:
To minimize personal injury, the furnace cabinet
must have an uninterrupted or unbroken electrical
ground. The controls used in this furnace
require an earth ground to operate properly.
Acceptable methods include electrical wire or
conduit approved for ground service. Do not
use gas piping as an electrical ground!
25
Page 26
Furnace
Input
(Btuh)
60,000
Cabinet
Width
(in.)
17 ½
Nominal
Electrical
Supply
Maximum
Operating
Voltage
Minimum
Operating
Voltage
Maximum
Furnace
Amperes
Minimum
Wire
Gauge
115-60-11271037.01415
80,00021115-60-11271039.41420
100,00021115-60-11271039.41420
120,000
24
½
115-60-112710312.51425
** Time-delay fuses or HACR-type circuit breakers are required.
Recommended Thermostat Wire Length
Thermostat Wire Gauge
2455 ft.25 ft.
2290 ft.45 ft.
20140 ft.70 ft.
18225 ft.110 ft.
2 - wire
(Heating)
4 or 5 wire
(Cooling)
Table 5. Wire Length and Voltage Specifi cations
Maximum
Fuse or Circuit
Breaker Amps**
Field Supplied
Fused Service
Panel
Black (Hot)
White (Neutral)
Field Supplied
Disconnect w/in
Sight of Furnace
Black
White
Green or Bare
(Ground)
Ground
Field Line Voltage Wiring
Factory Line Voltage Wiring
Figure 25. Line Voltage Field Wiring
Twinning
The control boards on fi xed speed furnaces are capable
of being twinned to other furnace of the same series, only
if the following criteria are met:
• The circuit boards are the same.
• The thermostat wires and the 1/4 inch thick quick-connect
terminals marked “TWIN” (Figure 26) on the furnace
controls must be connected together.
• The fuses must remain installed on each board.
• Twinned furnaces must be properly grounded according
to local codes.
• The autostage jumper must be set to the same pin
setting on both furnace control boards.
Ground
Junction Box (may be int. or ext.
to the furnace). These connections
can be made in the field supplied
disconnect at the furnace.
Black
White
Field Supplied
Panel Connector
THERMOSTAT
W1 G
W2
YR
R
C
Y
G
W1
W2
FURNACE
BOARD
FSHE
BOARD
TWIN TERMINAL
A/C
UNIT
FURNACE 1FURNACE 2
Black
White
Ground
FURNACE
TWIN TERMINAL
R
C
Y
G
W1
W2
BOARD
FSHE
BOARD
Note: Variable speed furnaces cannot be twinned.
26
Figure 26. Twinning
Page 27
START-UP AND ADJUSTMENTS
Pre-Start Check List
√Verify the polarity of the connections are correct, the
line voltage power leads are securely connected and
the furnace is properly grounded.
√Verify that all needed thermostat wires are securely
connected to the correct leads on the terminal strip
of the circuit board. See Figures 21 - 23 (page 24).
√Verify the gas line service pressure does not exceed
10.0 inches of water column, and is not less than 4.5
inches W.C. for natural gas. For LP gas the line service
pressure must not exceed 14 in. W.C., and must not
be less than 11.0 in. W.C..
√Verify the roll-out and manual reset switch is closed.
If necessary, press the button to reset the switch. DO
NOT install a jumper wire across a switch to defeat
its function. If a switch reopens on start-up, DO NOT
reset the switch without identifying and correcting the
fault condition.
√Verify the blower door is in place, closing the door
switch in the line voltage circuit.
√Verify the gas line has been purged and all connections
are leak free.
5. Multiply the gas fl ow rate in cubic feet per hr by the
heating value of the gas in Btu per cubic ft to obtain
the input rate in Btuh. See example.
Example:
• Time for 1 revolution of a gas meter with a 1
cubic foot dial = 40 seconds.
• From Table 11 read 90 cubic ft gas per hr.
• Local heating value of the gas (obtained from
gas supplier) = 1,040 Btu per cubic foot.
• Input rate = 1,040 x 90 = 93,600 Btuh.
6. The manifold pressure must be set to the appropriate
value for each installation by a qualifi ed installer,
service agency or the gas supplier.
WARNING:
Do not attempt to drill the gas orifi ces. Use
only factory supplied orifices. Improperly
drilled orifi ces may cause fi re, explosion,
carbon monoxide poisoning, personal injury
or death.
Start-up Procedures
Do not perform these steps until all of the checks in the
previous steps have been completed:
1. Set the thermostat to the lowest setting.
2. Turn off all electrical power to the furnace.
3. Follow the Operating Instructions on the furnace label.
4. Set the thermostat above room temperature and verify
the Operating Sequence. See page 28.
5. After 5 minutes of operation, set the thermostat below
room temperature and verify steps 11 & 12 of the
Operating Sequence.
Verifying and Adjusting Input Rate
IMPORTANT NOTE: The input rate must not exceed
the rate shown on the furnace rating plate. At altitudes
above 2,000 feet, it must not exceed that on the rating
plate less 4% for each 1,000 feet.
The input rate must be verifi ed for each installation to
prevent over-fi ring of the furnace. To determine the exact
input rate, perform the following procedures:
1. Shut off all other gas fi red appliances.
2. Start and run the furnace in high fi re for at least 3
minutes.
3. Measure the time (in seconds) required for the gas
meter to complete one revolution.
4. Convert the time per revolution to cubic feet of gas
per hour using Table 11 (page 38).
a.) Remove plastic cap from pressure regulator.
b.) Obtain the manifold pressure setting required for
this installation by referring to Table 13 (page 39)
for Propane or Tables 15 or 16 for Natural Gas
(page 40).
c.) Using an Allen wrench, turn the the LO Input
Adjusting Screw on the LO side of the regulator
to adjust the reduced input setting or turn the HI
Input Adjusting Screw (Figure 27) on the side of the
regulator to adjust the full input setting. IMPORTANT
NOTE: Turning the adjusting screw clockwise
increases the pressure and counterclockwise
reduces the pressure.
d.) Reinstall plastic cap after adjustment is complete.
HI Input
Adjusting Screw
Lo Input
Adjusting Screw
Figure 27. HI and LO Input Adjusting Screws
27
Page 28
Verifying and Adjusting Temperature Rise
Confi rm the temperature rise through the furnace is
within the limits specifi ed on the furnace rating plate. Any
temperature rise outside the specifi ed limits could result
in premature failure of the heat exchanger.
1. Place thermometers in the return and supply air
stream as close to the furnace as possible. To avoid
false readings, the thermometer on the supply air
side must be shielded from direct radiation from the
heat exchanger.
2. Adjust all registers and duct dampers to the desired
position and run the furnace for 10 to 15 minutes on
high fi re before taking any temperature readings. The
temperature rise is the difference between the supply
and return air temperatures.
For typical duct systems, the temperature rise will fall
within the limits specifi ed on the rating plate with the
blower speed at the factory recommended setting. If
the measured temperature rise is outside the specifi ed
limits, it may be necessary to change the speed of the
blower. NOTE: Lowering the blower speed increases the
temperature rise and a higher blower speed will decrease
the temperature rise.
The furnace is equipped with a multi-speed motor. Heating
and cooling speed selection is made by moving the switches
on the integrated control located in the furnace.
Verifying Burner Operation
CAUTION:
The door over the burners may only be open
for inspection purposes only. The door must be
installed during unattended operation.
1. Remove the burner compartment door.
2. Set the thermostat above room temperature and
observe the ignition sequence. The burner fl ame
should carry over immediately between all burners
without lifting off, curling, or fl oating. The fl ames should
be blue, without yellow tips.
3. After validating flame characteristics, change
thermostat setting to below room temperature.
4. Verify burner fl ame is completely extinguished.
5. Replace the burner compartment door.
Verifying Operation of the Supply Air Limit Switch
Note: A properly functioning limit switch should turn off
the gas valve when the return is blocked (time depends
on how well the return air is blocked). The circulating air
and combustion blowers should continue to run when the
limit switch opens.
1. Check the blower door and verify that it is securely
mounted in place and that there is power to the
furnace.
28
2. Block the return airfl ow to the furnace by installing
a close-off plate in place of or upstream of the
fi lter(s).
3. Set the thermostat above room temperature and
observe the Operating Sequence.
4. Remove the close-off immediately after the limit switch
opens. If the furnace continues to operate with no
return air, set the thermostat to a temperature below
room temperature, shut off the power to the furnace,
and replace the limit switch.
OPERATING SEQUENCE
The operating sequences for the heating, cooling, and fan
modes are described below. Refer to the fi eld and furnace
wiring diagrams: (Figures 21 - 23, page 24), (Figures 32
- 35, pages 42 - 45) and (Figure 25, page 26).
Heating Cycle
1. The thermostat calls for heat by energizing the W1
terminal with 24VAC.
2. The control checks to see the pressure switch is open.
If the switch is closed, the furnace will shut down for
5 minutes before retrying
3. If the pressure switch is open, the control energizes
the induced draft motor and waits for the pressure
switch to close. The pressure switch must close within
12 seconds.
4. The control runs the inducer for a 30 second pre-purge
time.
5. The control energizes the igniter output for the
appropriate adaptive warm-up time limit.
6. The furnace always ignites the burners in high fi re. If
the call for heat is for low rate, the furnace will move
down to low fi re after the fl ames stabilize.
7. If the fl ame is proved and ignites the gas, the control
de-energizes the igniter. The gas valve and inducer
remains energized. The control goes to blower on
delay.
8. The control energizes the blower on the selected
HEAT speed 30 seconds after the gas valve opened.
The gas valve and inducer remain energized.
9. If there is a call for high fi re, the gas valve moves to the
high fi re position and the blower speeds are increased.
The furnace will remain in high fi re until the demand
for heat is satisfi ed.
10. If autostaging is enabled (single stage thermostat) the
demand for heat has lasted more than the selected
time, the furnace automatically moves up to high fi re.
Autostage times are either SHORT (8 minutes), LONG
(12 minutes) or OFF, depending on the Jumper (P7)
setting on the Furnace Control Board.
11. When the thermostat demand for heat is satisfi ed, the
control de-energizes the gas valve. The inducer output
remains on for a 30 second post-purge period.
Page 29
12. The circulating air blower will continue to run for the
selected Blower Off Delay(P5). This may be 60, 90,
or 120 seconds depending on the Jumper setting on
the Furnace Control Board.
Cooling Cycle
1. The thermostat calls for cooling by energizing the Y/Y2
or Y1 terminal with 24VAC.
2. The control energizes the blower in the cooling speed
and sends 24VAC to the contactor in the condensing
unit.
3. When the thermostat removes the call for cooling,
the contactor in the outdoor condensing unit is deenergized and the control continues to run the fan for
a period of 60 seconds.
TROUBLESHOOTING
If the furnace fails to operate check the following:
• Is the thermostat operating properly?
• Are the blower compartment door(s) in place?
• Is the furnace disconnect closed?
• Has the circuit breaker tripped or the control board
fuse burned open?
• Is the gas turned on?
• Are any manual reset switches open?
• Is the fi lter dirty or plugged?
• Is the fl ame sensor coated? (Remove and clean
with steel wool. Do not use emery cloth or
sandpaper!)
• Is there blockage in the condensate drain switch?
Also verify that there is no double trapping of
condensate.
• Is the secondary heat exchanger free of debris and
clogs?
• Is evaporator coil clean and free of debris
(If applicable).
Fan Mode
• When the thermostat energizes the G terminal for
continuous fan (without calling for heat or cooling), the
indoor fan is energized on the selected FAN speed.
• If a call for cooling occurs during continuous fan, the
blower will switch over to the selected COOL speed.
• If the W terminal receives a call for heat during continuous
fan, the blower will de energize.
• A call for fan is ignored while in lockout.
• The blower will operate at 50% of the selected high
cooling speed for continuous fan operation.
• Are all the LED’s on the furnace and motor control
boards constantly ON? If not, refer to Tables 6 - 7 to
determine fault condition.
IMPORTANT NOTE: The furnace will lock out after 5
failed attempts for ignition and will try again every
hour if the call for heat remains.
• If the Inducer Blower is operating, and items above
have been verifi ed, check the Blower Limit Switch
(Figure 40 or 41, page 51) and reset if necessary.
• If the furnace operates when the Blower Limit Switch is
reset, contact a qualifi ed service technician to identify
and repair the problem.
• If the furnace still doesn’t operate, check the Flame
Roll-out Switches (Figure 40 or 41) and reset if
necessary.
• If the furnace operates when the Flame Rollout Switch
is reset, contact a qualifi ed service technician to identify
and repair the problem.
Diagnostic DescriptionGreen LEDRed LED
Control Fault (No Power)OffOff
L1/Neutral Polarity FaultFlashFlash
1 Hour LockoutAlternating Flash
Normal OperationOnOn
Pressure Switch Closed FaultOnFlash
Pressure Switch Open FaultFlashOn
Open Limit Switch FaultFlashOff
Motor FaultOnOff
Diagnostic DescriptionYellow LED
Low Flame Sensor SignalContinuous Flash
Flame PresentOn
Table 6. Furnace Control Board Fault Conditions
Green
LED
Fixed
Speed
Furnaces
Variable
Speed
Furnaces
Diagnostic Description
Control Fault (No Power)OffOff
Normal OperationOnOn
Motor FaultOnFlash
Twin Fault (no motor fault)FlashOn
Communications FaultFlashFlash
Control Fault (No Power)OffOff
Normal OperationOnOn
Motor FaultOnFlash
Communications FaultFlashFlash
Table 7. Motor Control Board Fault Conditions
Red
LED
29
Page 30
DESCRIPTION OF COMPONENTS
The descriptions below are various functional components
that affect the operation and shutting down of this furnace.
Some of these components and their locations are shown
in Figures 40 and 41 (page 51).If any component of the
furnace must be replaced, use only factory authorized
replacement parts specifi ed in the Replacement Parts
List provided online.
Blower Limit Switch
The Blower switch prevents furnace operation when blower
is not operational.
Condensate Drain Switch
The Condensate Drain Switch will shut down the furnace
if the condensate drain from the Collector Pan becomes
clogged.
Flame Sensor
The fl ame sensor verifi es when a fl ame has carried over
from the igniter to the opposite end burner. If no fl ame is
detected, the furnace will shut down within 4 seconds.
Flame Roll-Out Switch
The fl ame roll-out switch verifi es that the burner fl ames
are drawn into the heat exchanger tubes. If the burner
fl ames are not properly drawn into the heat exchanger, the
fl ame roll-out switch will close the gas valve and initiate
the shutdown cycle.
Gas Valve
The gas valve controls the fl ow of gas to the burners.
When the gas valve is energized it automatically opens
and regulates the gas pressure in the manifold.
Inducer Assembly
The inducer assembly vents products of combustion to
the outside.
Pressure Switch
The pressure switch verifi es that the inducer is drawing
the combustion gases through the heat exchanger. If
the fl ame is not properly drawn into the heat exchanger
tube, the rollout switch or the fl ame sensor will shut the
furnace down.
Supply Air Limit Switch
The supply air limit switch prevents the air temperature
leaving the furnace from exceeding the maximum
allowable outlet air temperature.
MAINTENANCE
WARNING:
These maintenance instructions are primarily
intended to assist qualified technicians
experienced in the proper maintenance and
operation of this appliance.
Proper maintenance is most important to achieve the best
performance from a furnace. Follow these instructions for
years of safe, trouble free operation.
• Always reinstall the doors on the furnace after servicing
or cleaning/changing the fi lters. Do not operate the
furnace without all doors and covers in place.
• Verify that the thermostat is properly installed and is not
affected by drafts or heat from lamps or other appliances.
• To achieve the best performance and minimize
equipment failure it is recommended that a yearly
maintenance checkup be performed. At a minimum,
this check should include the following items:
Air Filter(s)
WARNING:
Never operate the furnace without a fi lter in
place. Dust and lint in the return air can build
up on internal components, resulting in loss
of effi ciency, equipment damage, and possible
fi re.
Note: Air fi lter(s) are not supplied with the furnace as
shipped from the factory. The installer must provide a
high velocity fi lter and rack for a fi lter in the return air
duct adjacent to the furnace, or in a return air grill to the
furnace. It is recommended that fi lters be cleaned or
replaced monthly. New or newly renovated homes may
require more frequent changing until the construction
dust has minimized.
Filters designed to remove smaller particles such as
pollen, may require additional maintenance. Filters for
side return and bottom return applications are available
from most local distributors.
Blower Compartment
Dirt and lint can create excessive loads on the motor
resulting in higher than normal operating temperatures
and shortened service life. It is recommended that the
blower compartment be cleaned of dirt or lint that may
have accumulated in the compartment or on the blower
and motor as part of the annual inspection.
30
Page 31
Cleaning of Burners
If the burners must be cleaned, follow the steps below and
see Figure 40 or 41 (page 51) for component location.
1. Shut off gas supply to the furnace either at the meter
or at a manual valve in the supply piping.
2. Turn off all power to the furnace and set the thermostat
to it’s lowest setting.
3. Remove the burner door from the furnace.
4. Turn the gas control switch to the OFF position.
5. Disconnect the wires from the gas valve, igniter, fl ame
sensor, and fl ame rollout switch.
6. Using two wrenches, separate the ground-joint union
in the gas supply piping at the furnace.
7. Remove the piping between the Gas Valve and the
ground-joint union. (If applicable).
8. Remove all screws securing the Manifold Assembly
to the Burner Box.
9. Carefully remove the burner assembly from the
furnace. DO NOT DAMAGE THE IGNITER WHILE
REMOVING THE BURNER ASSEMBLY.
10. Inspect the burners for accumulated dust or debris.
If necessary carefully clean them with a soft wire
brush and a vacuum cleaner. DO NOT DAMAGE THE
IGNITER WHILE CLEANING THE BURNER.
11. Replace all the parts in reverse order from which they
were removed.
12. Follow the lighting instructions found on the furnace
door to return the furnace to operation. Verify proper
operation after servicing.
Heat Exchanger and Burner Maintenance
The furnace should operate for many years without soot
buildup in the fl ue passageways, however, the fl ue, vent
system, and burners should be inspected and cleaned
(if required) by a qualifi ed service technician annually
to ensure continued safe operation. Pay attention to any
deterioration from corrosion or other sources.
WARNING:
Holes in the vent pipe or heat exchanger can
cause combustion products to enter the home.
Replace the vent pipe or heat exchanger if leaks
are found. Failure to prevent the circulation
of combustion products into the living space
can create potentially hazardous conditions
including carbon monoxide poisoning that
could result in personal injury or death.
Lubrication
The bearings in the blower motor and inducer blower used
in these furnaces are pre-lubricated and sealed by the
manufacturer. No further oiling of the bearings is required
for the life of the motor.
Vent System
Check the inlet pipe (if applicable) and outlet pipe to ensure
they are not blocked by debris. Any damaged section of vent
pipe must be replaced, and any obstruction or blockage
must be removed prior to operating the furnace.
31
Page 32
FRENCH TRANSLATIONS
The following are French translations of important warning statements found within this manual.
AVERTISSEMENT:
RISQUE D’EMPOISONNEMENT AU MONOXYDE DE CARBONED
Le non-respect des consignes suivantes portant sur chacun des appareils raccordés au
système
d’évacuation mis en service pourrait entraîner l’empoisennement au monoxyde de carbone
ou la mort. Les consignes suivantes doivent être observées pour chaque appareil raccordé
au système d’évacuation mis en service si les autres appareils raccordés au système ne sont
pas en service:
1. Sceller toute ouverture non utilisée de la systéme d’évacuation;
2. S’assurer que la systéme d’évacuation présente des dimensions et une pente horizontale
conformes à la norme ANSI Z223.1/NFPA 54, intitulée National Fuel Gas Code ou aux
codes d’installation CSA-B149.1, ainsi qu’aux présentes instructions. S’assurer que la
systéme d’évacuation n’est pas bloquée, restreinte, corrodée, qu’elle ne fuit pas et qu’elle
ne présente aucun autre défaut potentiellement dangereux;
3. Dans la mesure du possible, fermer toutes les portes et fenêtres du bâtiment, et toutes
les portes entre la pièce où se trouve l’appareil raccordé à la systéme d’évacuation et les
autres pièces du bâtiment.
4. Fermer les registres des foyers;
5. Mettre en service les sécheuses et tout autre appareil qui n’est pas raccordé à la systéme
d’évacuation. Faire fonctionner à régime maximal tout ventilateur d’évacuation, tel que
les hottes de cuisinière et les ventilateurs de salles de bains. Ne pas mettre en service les
ventilateurs d’été.
6. Respecter les instructions d’allumage. Mettre en service l’appareil à l’essai. Régler le
thermostat de manière à ce que l’appareil fonctionne sans interruption;
7. Vérifi er s’il y a débordement à l’orifi ce d’évacuation du coupe tirage des appareils dotés
d’un coupe tirage 5 minutes après l’allumage du brûleur principal. Utiliser la fl amme d’une
allumette ou d’une chandelle.
8. Si l’on constate, au cours de l’un des essais qui précèdent, que l’évacuation est défi ciente,
corriger le système d’évacuation conformément à la norm ANSI Z223.1/NFPA 54, National
Fuel Gas Code, et (ou) aux codes d’installation CSA B149.1.
9. Après avoir déterminé que tous les appareils raccordés à la systéme d’évacuation évacuent
correctement tel que prescrit ci-dessus, rouvrir les portes et les fenêtres et remettre les
ventilateurs d’évacuation, les registres de foyers et tout autre appareil fonctionnant au
gaz à leur état de fonctionnement initial.
32
Page 33
AVERTISSEMENT:
RISQUE D’INCENDIE OU D’ EXPLOSION
• Le non-respect des avertissements de
sécurité pourrait entraîner des blessures
graves, la mort ou des dommages matériels.
• L’installation et l’entretien doivent être
effectués par un installateur qualifi é, un
organisme de service ou le fournisseur
de gazstaller, service agency or the gas
supplier.
• Ne pas entreposer ni utiliser de l’essence ni
d’autres vapeurs ou liquides infl ammables
dans le voisinage de cet appareil, ni de tout
autre appareil.
QUE FAIRE S’IL Y A UNE ODEUR DE GAZ
• Ne pas tenter d’allumer aucun appareil.
• Ne toucher à aucun interrupteur électrique;
n’utiliser aucun téléphone dans le bâtiment.
• Évacuer l’immeuble immédiatement.
• Appeler immédiatement le fournisseur de
gaz en employant le téléphone d’un voisin.
Respecter à la lettre les instructions du
fournisseur de gaz.
• Si personne ne répond, appeler le service des
incendies.
AVERTISSEMENT:
RISQUE D’INCENDIE ET D’EXPLOSION
Risque de blessures graves ou de mort.
Ne pas entreposer ni utiliser de l’essence ni
d’autres vapeurs ou liquides infl ammables
dans le voisinage de cet appareil, ni de tout
autre appareil. Le fait d’entreposer ou d’utiliser
de l’essence ou d’autres liquides ou vapeurs
infl ammables à proximité de cet appareil ou de
tout autre appareil peut causer des blessures
graves ou la mort.
AVERTISSEMENT:
RISQUE DE CHOC ÉLECTRIQUE, D’INCENDIE
OU D’EXPLOSION
Le non-respect des avertissements de sécurité
pourrait entraîner un fonctionnement dangereux
de l’appareil, des blessures graves, la mort ou
des dommages matériels.
Un entretein incorrect pourrait entraîner un
fonctionnement dangereux de l’appareil, des
blessures graves, la mort ou des dommages
matériels.
• Couper toute alimentation électrique au
générateur d’air chaud avant de prodéder aux
travaux d’entretein.
• Au moment de l’entretien des commandes,
étiquetez tous les fi ls avant de les débrancher.
S’assurer de les raccorder correctement.
• S’assurer que l’appareil fonctionne
adéquatement aprés l’entretien.
AVERTISSEMENT:
Ne jamais utiliser une flamme nue por
vérifi er la présence des fuites de gaz. Pour la
vérifi cation de tous les joints, utiliser plutôt une
solution savonneuse commerciale fabriquée
spécifi quement pur la détection des fuites de
gaz. Un incendie ou une explosion peut entraîner
des dommages matériels, des blessures ou la
mort.
Le non-respect des avertissements de sécurité
pourrait d’entraîner des blessures graves, la
mort ou des dommages matériels.
33
Page 34
FIGURES AND TABLES
*TC 95.1% Upfl ow/Horizontal Furnace
C
FRONT
BRACE
BOTTOM
PANEL
23 1/2
INLET AIR
BOTTOM
VIEW
Ø 7/8 HOLE FOR
THERMOSTAT
Ø 7/8 HOLE FOR
ELECTRIC
Ø 1 5/8 HOLE
FOR GAS
17 7/8
Ø 1 1/16 HOLE
Ø 3” HOLE
FOR VENT
34 1/2
22 1/4
25 3/8
22 1/2
PIPE
17 1/4
28
LEFT SIDE
TOP VIEW
B
FLANGES
3 ¼
A
19
Ø 7/8 HOLE FOR
THERMOSTAT
Ø 3” HOLE FOR
VENT PIPE
Upfl ow/Horz.
Cabinets
‘B’ Cabinet
‘C’ Cabinet
‘D’ Cabinet
Dim.
“A”
17 ½ 15 ⅞ 16 ⅛
2119 ⅜ 19 ⅝
24 ½ 22 ⅞ 23 ⅛
NOTES:
Dimensions shown in inches.
Ø 7/8 HOLE
FOR ELECTRIC
22 1/2
Ø1 5/8 HOLE
FOR GAS
4 KNOCKOUTS
24 7/8
1
(BOTH SIDES)
Ø 1 1/16 HOLE
RIGHT SIDE
23
Dim.
“B”
Dim.
“C”
15
1 1/4
*TL 95.1% Downfl ow Furnace
C
FRONT
BRACE
BOTTOM
VIEW
18 1/2
2 3/4
Ø 7/8 HOLE
FOR ELECTRIC
1 5/8 X 3 1/2
HOLE FOR GAS
16 1/2
10 1/4
Ø 1 1/16 HOLE
34 1/2
Ø 3” HOLE
FOR VENT
24 1/8
22 1/4
25 1/2
22 1/2
PIPE
28
LEFT SIDE
FLUE
TOP VIEW
FLANGES
3
Downfl ow
Cabinets
B
‘B’ Cabinet
‘C’ Cabinet
‘D’ Cabinet
19
Dim.
“A”
Dim.
“B”
Dim.
“C”
17 ½ 15 ⅞ 16 ⅛
2119 ⅜ 19 ⅝
24 ½ 22 ⅞ 23 ⅛
NOTES:
Dimensions shown in inches.
INLET AIR
7
1/2
Ø 7/8 HOLE FOR
THERMOSTAT
Ø 7/8 HOLE FOR
22 1/4
ELECTRIC
Ø 1 5/8 HOLE
FOR GAS
25
Ø 3” HOLE
FOR VENT
PIPE
22 1/2
22 1/2
25 3/8
17 1/4
Ø 1 1/16 HOLE
A
RIGHT SIDE
29 1/2
17 7/16
34
Figure 28. Furnace Dimensions
Page 35
AIRFLOW DATA
*TC/TL FURNACES WITH FIXED SPEED BLOWERS
Model
Number
1. Motor Switch Settings are for heating speeds using HEAT switches 1, 2, 3, & 4 and
cooling speeds using COOL switches 5, 6, 7, & 8.
2. Two openings are recommended for airfl ows above 1,600 CFM if the fi lter(s) is (are)
CAPACITY OF BLACK IRON GAS PIPE (CU. FT. PER HOUR)
FOR NATURAL GAS (SPECIFIC GRAVITY - 0.60)
NOMINAL BLACK
IRON PIPE
DIAMETER (IN.)
½
¾
1520350285245215195180170
1 ¼ 1,050730590500440400370350
1 ½ 1,6001,100890760670610
The cubic feet per hour listed in the table above must be greater than the cubic feet per hour of gas fl ow required by the
furnace. To determine the cubic feet per hour of gas fl ow required by the furnace, divide the input rate of the furnace by the
heating value (from gas supplier) of the gas.
1020304050607080
13090756555504540
2801901501301151059590
Cubic Feet Per Hour Required =
LENGTH OF PIPE RUN (FT)
NOTES
Input To Furnace (Btu/hr)
Heating Value of Gas (Btu/Cu. Ft.)
Table 12. Black Iron Gas Pipe Capacities
Page 39
ALTITUDE
ABOVE SEA
LEVEL
0 to 1,999 FT
2,000 to 2,999 FT
3,000 to 4,999 FT
5,000 to 5,999 FT
6,000 to 7,999 FT
8,000 to 10,000 FT
Table 13. High Altitude Deration Chart for Propane Gas
PROPANE GAS
INPUT (BTU) and STAGE
60,00080,000100,000120,000
1st 2nd 1st 2nd 1st 2nd1st2nd
55555555ORIFICE SIZE
4.210.04.210.04.210.04.210.0 MANIFOLD PRESSURE
55555555ORIFICE SIZE
4.29.04.29.04.29.04.29.0MANIFOLD PRESSURE
55555555ORIFICE SIZE
4.28.54.28.54.28.54.28.5MANIFOLD PRESSURE
56565656ORIFICE SIZE
4.210.04.210.04.210.04.210.0 MANIFOLD PRESSURE
56565656ORIFICE SIZE
4.29.04.29.04.29.04.29.0MANIFOLD PRESSURE
56565656ORIFICE SIZE
4.28.54.28.54.28.54.28.5MANIFOLD PRESSURE
ALTITUDE
ABOVE
SEA LEVEL
2,000LOWLOWLOWLOWLOWLOWHIGHHIGHHIGH
3,000LOWLOWLOWLOWLOWLOWHIGHHIGHHIGH
4,000LOWLOWLOWLOWLOWHIGHHIGHHIGHHIGH
5,000LOWLOWLOWLOWLOWHIGHHIGHHIGHHIGH
6,000LOWLOWLOWLOWHIGHHIGHHIGHHIGHHIGH
7,000LOWLOWLOWLOWHIGHHIGHHIGHHIGHHIGH
8,000LOWLOWLOW HIGH HIGHHIGHHIGHHIGHHIGH
9,000LOWLOWLOW HIGH HIGHHIGHHIGHHIGHHIGH
10,000LOWLOWHIGH HIGH HIGHHIGHHIGHHIGHHIGH
LOCAL HEATING VALUE, BTU PER CUBIC FOOT
6507007508008509009501,000 1,050
Table 14. Natural Gas Heating Values
39
Page 40
NATURAL GAS - HIGH HEATING VALUE
ALTITUDE
ABOVE
SEA LEVEL
0 to 1,999 FT
2,000 to 2,999 FT
3,000 to 3,999 FT
4,000 to 4,999 FT
5,000 to 5,999 FT
6,000 to 6,999 FT
7,000 to 7,999 FT
8,000 to 8,999 FT
9,000 to 9,999 FT
INPUT (BTU) and STAGE
60,00080,000100,000120,000
1st2nd 1st 2nd 1st 2nd1st 2nd
45454545ORIFICE SIZE
1.73.51.73.51.73.51.73.5MANIFOLD PRESSURE
45454545ORIFICE SIZE
1.73.31.73.31.73.31.73.3MANIFOLD PRESSURE
45454545ORIFICE SIZE
1.73.11.73.11.73.11.73.1MANIFOLD PRESSURE
45454545ORIFICE SIZE
1.72.91.72.91.72.91.72.9MANIFOLD PRESSURE
45454545ORIFICE SIZE
1.72.81.72.81.72.81.72.8MANIFOLD PRESSURE
48484848ORIFICE SIZE
1.73.51.73.51.73.51.73.5MANIFOLD PRESSURE
48484848ORIFICE SIZE
1.73.31.73.31.73.31.73.3MANIFOLD PRESSURE
48484848ORIFICE SIZE
1.73.01.73.01.73.01.73.0MANIFOLD PRESSURE
48484848ORIFICE SIZE
1.72.81.72.81.72.81.72.8MANIFOLD PRESSURE
Table 15. High Altitude Deration Chart for Natural Gas - High Heating Value
NATURAL GAS - LOW HEATING VALUE
ALTITUDE
ABOVE SEA
LEVEL
0 to 1,999 FT
2,000 to 2,999 FT
3,000 to 3,999 FT
4,000 to 4,999 FT
5,000 to 5,999 FT
6,000 to 6,999 FT
7,000 to 7,999 FT
8,000 to 8,999 FT
9,000 to 9,999 FT
60,00080,000100,000120,000
1st 2nd 1st 2nd 1st 2nd 1st 2nd
1.73.51.73.51.73.51.73.5MANIFOLD PRESSURE
1.73.51.73.51.73.51.73.5MANIFOLD PRESSURE
1.73.41.73.41.73.41.73.4MANIFOLD PRESSURE
1.73.21.73.21.73.21.73.2MANIFOLD PRESSURE
1.73.11.73.11.73.11.73.1MANIFOLD PRESSURE
1.72.91.72.91.72.91.72.9MANIFOLD PRESSURE
1.73.51.73.51.73.51.73.5MANIFOLD PRESSURE
1.73.31.73.31.73.31.73.3MANIFOLD PRESSURE
1.73.11.73.11.73.11.73.1MANIFOLD PRESSURE
INPUT (BTU) and STAGE
45454545ORIFICE SIZE
45454545ORIFICE SIZE
45454545ORIFICE SIZE
45454545ORIFICE SIZE
45454545ORIFICE SIZE
45454545ORIFICE SIZE
48484848ORIFICE SIZE
48484848ORIFICE SIZE
48484848ORIFICE SIZE
Table 16. High Altitude Deration Chart for Natural Gas - Low heating Value
40
Page 41
ELECTRICAL INFORMATION
NOT USED
RCY1
CONNECTION TO
DHUM
TWIN
FAN SPEED
1 2 345 6 7
OFF ON
HEAT
THERMOSTAT
COOL
TERMINAL TO
CONNECTION
TWIN FURNACES
8
FURNACE CONTROL
RED
STATUS
GREEN
BOARD
NOT USED
Figure 29. Two-Stage Fixed Speed
Motor Control Board
W1
W2
G
AUTO
STAGE
NONE
SHORT
LONG
FUSE
Y/Y2
Y1
THERMOSTAT CONNECTIONS
10
12
11
7
8
6
4
5
1
293
C
EXPANSION
PORT
MOTOR WIRE
HARNESS
FOR WIRING TO THE
MOTOR CONTROL
BOARD
R
EXPANSION
PORT
GREEN
RED
YELLOW
(FLAME)
OFF
60
90
120
180
BLOWER
DELAY
STATUS
W1
W_OUT
Y/Y2_OUT
Y1_OUT
OUTPUT TERMINALS
H_OUT
OUTPUT
HUMIDIFIER
R
C
FIELD USE
EXPANSION PORT
CONNECTION TO
FURNACE CONTROL
Figure 30. Two-Stage Variable Speed
NOT FOR
BOARD
STATUS LIGHTS
RED
RED
CONNECTION TO
IQ THERMOSTAT
GREEN
FAN SPEED
(IF APPLICABLE)
1 2 345 6 7
OFF ON
HEAT
MOTOR WIRING
Motor Control Board
COOL
HARNESS
L2-OUT
L1-IN
L1-OUT
OUTPUT
DEHUMIDIFIER
DHUM_IN
8
Y1_IN
SENSOR
GROUND
L2-IN
FOR USE
WITH IQ
OUTDOOR
UNITS
INPUT TERMINALS
INPUTS
14325
EAC
XMFR
LINE
LINE
HUM
Figure 31. Two-Stage Furnace Control Board
NEUTRALS
LINE- N
XMFR-N
LINE- N
41
Page 42
112233445566778899
RED
Green LEDRed LED
Control Fault (No Power)OffOff
L1 / Neutral Polarity FaultFlashFlash
1 Hour Lockout
Normal OperationOnOn
Pressure Switch Closed FaultOnFlash
Pressure Switch Open FaultFlashOn
Open Limit Switch FaultFlashOff
Low Flame Sensor Signal
Flame Present
Diagnostic Description
FAULT CONDITIONS
Diagnostic Description
Yellow LED
Continuous Flash
On
Alternating Flash
Motor FaultOnOff
RED
RED
123
123
PAR T O F
MOTOR
BLUE
MOTOR
TORQUE
HP
PWM
NONE
NONE
MODE
SPEED
COMMON
R
C
W
TX
RX
GND
R
C
W
TX
RX
W
GND
WHITE
BLACK
COOL
FAN SPEED
BLUE
HEAT
DEHUM
R C Y1TWIN
MOTOR CHOKE
MOTORS ONLY)
(ON 3/4 AND 1HP
12345
BROWN
RED
ORANGE
YELLOW
BLACKBLACK
GREEN
BLUE
6
BLACK
WHITE
0409
7109160
¢710916+¤
LIMIT
BLOWER
W
BLACK
VIOLET
WHITE
ORANGE
PRESSURE
PRESSURE
RX
TX
COM
C
R
RCY/Y2W2GW1Y1
VIOLET
SWITCH
VIOLET
SWITCH
12
11
10
GREEN
6
9
3
8
5
2
4
1
7
BROWN
C
GAS
VALVE
If any of the origInal wire as supplied with the
furnace must be replaced, it must be replaced
with wiring material having a temperature
rating of at least 105° C.
Use copper conductors only.
BLACK
WHITE
120 V
24 V
BLK W/ WHITE STRIPES
WHITE W/ BLK STRIPES
1234
1234
This wiring diagram shows connections and
termination required for the blower kit only.
Use in addition to the wiring diagram for the
furnace.
SWITCH
PRESSURE
LOW
WIRING DIAGRAM
For 80+ and 90+ 2-Stage Fixed Speed Upflow Furnaces
Clearance above grade, veranda, porch, deck, balcony, or
A =
maximum expected snow level.
B = Clearance to window or door that may be opened.
C = Clearance to permanently closed window
Vertical clearance to ventilated soffi t located above the
D =
terminal within a horizontal distance of 2 feet (61cm) from
the center line of the terminal.
E = Clearance to unventilated soffi t.
F = Clearance to outside corner.
G = Clearance to inside corner.
Clearance to each side of center line extended above
H =
meter/regulator assembly.
I = Clearance to service regulator vent outlet.3 feet (1.83m)
Clearance to non-mechanical air supply inlet to building
J =
or the combustion air inlet to any other appliance.
K = Clearance to mechanical air supply inlet.6 feet (1.83m)
Clearance above paved sidewalk or driveway located on
L =
public property.
M = Clearance under veranda, porch, deck, or balcony.
aIn accordance with the current CSA B149.1 Natural Gas and Propane Installation Guide Code
bIn accordance with the current ANSI Z223.1 / NFPA 54 Natural Fuel Gas Code
cA vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.
dPermitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.
For clearances not specifi ed in ANSI Z223.1 / NFPA 54 or CSA B149.1, the following statement shall be included: “Clearance in accordance with local installation codes, and the
*
requirements of the gas supplier and the manufacturers installation instructions”
AIR SUPPLY INLET
CANADIAN INSTALLATIONS
a
Direct Vent (2-pipe) &
Conventional Vent (1-pipe)
Furnaces
12 inches (30cm)12 inches (30cm)12 inches (30cm)
6 inches (15cm) for
appliances < 10,000 Btuh (3kW)
12 inches (30cm) for appliances
10,000 Btuh - 100,000 Btuh (30kW)
36 inches (91cm) for
appliances > 100,000 Btuh (30Kw)
***
***
***
***
***
3 feet (91cm) within a height 15 feet
above the meter/regulator assembly
6 inches (15cm) for
appliances < 10,000 Btuh (3kW)
12 inches (30cm) for appliances
10,000 Btuh - 100,000 Btuh (30kW)
36 inches (91cm) for
appliances > 100,000 Btuh (30Kw)
7 feet (2.13m)
12 inches (30cm)
c
d
NOTES:
AREA WHERE TERMINAL IS NOT PERMITTED
Direct Vent
(2-pipe) Furnaces
6 inches (15cm) for
appliances < 10,000 Btuh (3kW)
9 inches (23cm) for appliances
10,000 Btuh - 50,000 Btuh (30kW)
12 inches (30cm) for
appliances > 50,000 Btuh (30Kw)
**
**
6 inches (15cm) for
appliances < 10,000 Btuh (3kW)
9 inches (23cm) for appliances
10,000 Btuh - 50,000 Btuh (30kW)
12 inches (30cm) for
appliances > 50,000 Btuh (30Kw)
3 feet (91cm) above if within
10 feet (3m) horizontally
*
**
Table 17. Vent Termination Clearances
46
US INSTALLATIONS
Conventional Vent
(1-pipe) Furnaces
4 ft. (1.2m) below or to side of opening;
1 ft. (300mm) above opening
4 ft. (1.2m) below or to side of opening;
1 ft. (300mm) above opening
3 ft. (91cm) above if within
10 feet (3m) horizontally
b
7 ft. (2.13m)
Page 47
HORIZONTAL VENTING
(2-Pipe Shown)
90°
Elbow
Combustion Air
Straps or Other Suitable
Supports at minimum of 5 ft. Intervals
Seal/Caulk
Around Pipes
at Building
90°
Elbow
Straight Neoprene Coupling
with 2 Hose Clamps* (Optional)
VERTICAL VENTING
(2-Pipe Shown)
Support System on
Vertical Rise
90° Elbow
Upward Pitch - 1/4” per foot
First Support Placed
as Close to Furnace
Connection as Possible
Exhaust Vent
PVC TEE, Reducer,
and 1/2” x 1/2” Hose Barb
Condensate
Drain Line
First Support as Close
to Furnace as Possible
Outlet Exhaust Vent
See Table 2 for PVC Pipe Lengths (Field Supplied)
Wall
Support System on
Vertical Rise
7”
Normal
Snow Level
12” Min.
Straight Neoprene
Combustion Air
Couplings with 2
Hose Clamps
90° Elbow
PVC TEE, Reducer,
Exhaust Vent
and 1/2” x 1/2” Hose Barb
Condensate
Drain Line
See Table 2 for PVC Pipe Lengths
(Field Supplied)
Figure 36. Horizontal and Vertical Venting
Combustion Air
Upward Pitch
1/4” per foot
90°
Elbow
Exhaust Vent
Condensate
Drain Line
47
Page 48
1 Pipe Upflow
Inlet Air
Option
1
Exhaust Vent
PVC TEE
and Reducer
Plug
See View -A-
VIEW -A-
Inline
Drain
NOTES:
1.) All drain lines must be trapped with J-Trap or field supplied loop.
2.) Drain line traps may be positioned inside or outside the cabinet.
Header
Box
Drain
and Reducer
Drain Line
Attached to
3/4 x 1/2
Hose Barb
PVC TEE
Inlet Air
X
Exhaust Vent
See View -B-
(This drain not needed
if “X” is less than 6”.)
VIEW -B-
Header
Box Drain
Inline Drain
(Tubing is routed thru
the blower deck and
side of cabinet.)
Option
2
Plug
See
View -B-
48
Plug
Inlet Air
Option
3
See View -A-
2 Pipe Upflow
Exhaust Vent
PVC TEE
and Reducer
PVC TEE
and Reducer
Drain Line
Attached to
3/4 x 1/2
Hose Barb
Figure 37. Upfl ow Options
Exhaust Vent
Inlet Air
X
Option
4
Plug
See View -B-
Page 49
1 Pipe Horizontal
Option
See View -C-
5
See View -C-
Exhaust Vent
Inlet Air
Inlet Air
Plug
See View -D-
Inline
Drain
VIEW -C-
Option
6
Exhaust Vent
Plug
See View -D-
VIEW -D-
Header Box
Drain
All drain lines must be trapped with J-Trap or field supplied loop.
2 Pipe Horizontal
Option
7
See View -C-
See View -C-
Exhaust Vent
Plug
Inlet Air
Figure 38. Horizontal Options
Inline
Drain
Inlet Air
See View -D-
Option
8
Header Box
Drain
Exhaust Vent
Plug
See View -D-
49
Page 50
1 Pipe Downflow
Option
Plug
9
VIEW -E-
PVC
Inlet Air
Cap
See View -E-
PVC TEE
and Reducer
Exhaust Vent
Drain Line
Attached to
1/2 x 1/2
Hose Barb
Option
Plug
10
See
View -F-
Inlet Air
Exhaust
See Table 2 for
2” PVC Pipe Length
(Field Supplied)
Plug
PVC TEE
and Reducer
Drain Line Attached
to 1/2 x 1/2 Hose Barb
VIEW -F-
PVC
Inlet Air
Option
Cap
11
X
Plug
Exhaust Vent
See View -G-
VIEW -G-
Header Box
Inline
Drain
Drain
NOTES:
1.) All drain lines must be trapped with J-Trap or field supplied loop.
2.) Drain line traps may be positioned inside or outside the cabinet.
2 Pipe Downflow
Option
Plug
12
PVC
Inlet Air
Cap
See View -E-
PVC TEE
and Reducer
Exhaust Vent
Drain Line
Attached to
1/2 x 1/2
Hose Barb
Option
Plug
13
See
View -F-
Inline
Drain
Header Box
Inlet Air
Exhaust
Inline Drain - This drain
Drain
See Table 2 for
2” PVC Pipe Length
(Field Supplied)
Plug
PVC TEE
and Reducer
Drain Line Attached
to 1/2 x 1/2 Hose Barb
not needed if “X”
is less than 6”.
Option
X
Exhaust Vent
14
Header Box
PVC
Inlet Air
Cap
See View -G-
Drain
Plug
50
Figure 39. Downfl ow Options
Page 51
LOCATION OF FURNACE COMPONENTS
AIR
FLOW
ITEMCOMPONENT NAME
1.Blower Assembly
2.Blower Door Switch
3.Burner Assembly
4.Finish Flange
5.Flame Roll-Out Switch
6.Flame Sensor
7.Furnace Control Board
8.Gas Manifold
9.Gas Valve
10.Igniter
11.Inducer Assembly
12.Inducer Limit Switch
13.Inline Drain Assembly
14.
15.Motor Control Board
16.Motor Control Box
17.Pressure Switches
18.Transformer
Motor Choke
(C and D cabinets only)
8
6
17
12
11
2
14
16
4
5
9
10
3
7
AIR FLOW
13
17
18
1
15
Figure 40.
ITEMCOMPONENT NAME
1.Blower Assembly
Blower Door Switch
2.
(behind blower panel)
3.Burner Assembly
4.Finish Flanges
5.Flame Roll-Out Switch
6.Flame Sensor
7.Furnace Control Board
8.Gas Manifold
9.Gas Valve
10.Igniter
11.Inducer Assembly
12.Inducer Limit Switch
13.Inline Drain Assembly
14.
Motor Choke(C and D cabinets only)
15.Motor Control Board
16.Pressure Switches
17.Transformer
Upfl ow/Horizontal Gas Furnace Components
1
14
2
13
AIR
FLOW
12
9
10
8
4
15
7
17
16
11
5
6
3
Figure 41. Downfl ow
Gas Furnace Components
51
Page 52
INSTALLATION/PERFORMANCE CHECK LIST
INSTALLER NAME:
CITY _______________STATE _____________
INSTALLATION ADDRESS:
CITY _______________STATE _____________
UNIT MODEL #
UNIT SERIAL # ____________________________
Minimum clearances per
Table 1 (page 7)?
Has the owner’s infor mation
been reviewed with the
home-owner?
YESNO
YESNO
ELECTRICAL SYSTEM:
Electrical connections tight?YESNO
Line voltage polarity correct?YESNO
Supply Voltage: ______________________ VOLTS
Has the thermostat been
calibrated?
Is the thermostat level?YESNO
Is the heat anticipator setting
correct?
GAS SYSTEM:
Gas Type: (circle one)
Gas pipe connections leaktested?
Gas Line Pressure: __________________ (in - W.C.)
Is there adequate fresh
air supply for combustion
and ventilation?
YESNO
YESNO
Natural
Gas
YESNO
YESNO
Propane
Has the literature package
been left near the
furnace?
Installation Altitude: ____________________ (FT.)
YESNO
Deration Percentage: ___________________ (%)
Furnace Input: _______________________ (Btuh)
Supply Air Temperature: ________________ (° F)
Return Air Temperature: _________________(° F)
Temperature Rise: _____________________(° F)
VENTING SYSTEM:
Vent free from restrictions?YESNO
Filter(s) secured in place?YESNO
Filter(s) clean?YESNO
Flue connections tight?YESNO
Is there proper draft?YESNO
O’Fallon, MO
¢7090475¤
7090470
7090470(Replaces 708810A)
Specifi cations and illustrations subject to change
without notice or incurring obligations.
Printed in U.S.A. (05/09)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.