Nordyne TA UPFLOW, TK DOWNFLOW Installation Instructions Manual

Page 1
TWO-STAGE NONCONDENSING GAS FURNACES WITH FIXED & VARIABLE SPEED BLOWERS - 80+ AFUE
Installation Instructions
*TA UPFLOW / HORIZONTAL MODEL
WARNING:
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly could result in serious injury or property damage.
• Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
• Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fi re department.
*TK DOWNFLOW MODEL
AVERTISSEMENT
RISQUE D’INCENDIE OU D’ EXPLOSION
• Le non-respect des avertissements de sécurité pourrait entraîner des blessures graves, la mort ou des dommages matériels.
• L’installation et l’entretien doivent être effectués par un installateur qualifié, un organisme de service ou le fournisseur de gazstaller, service agency or the gas supplier.
• Ne pas entreposer ni utiliser de l’essence ni d’autres vapeurs ou liquides infl ammables dans le voisinage de cet appareil, ni de tout
autre appareil.
QUE FAIRE S’IL Y A UNE ODEUR DE GAZ
• Ne pas tenter d’allumer aucun appareil.
• Ne toucher à aucun interrupteur électrique; n’utiliser aucun téléphone dans le bâtiment.
• Évacuer l’immeuble immédiatement.
• Appeler immédiatement le fournisseur de gaz en employant le téléphone d’un voisin. Respecter à la lettre les instructions du fournisseur de gaz.
• Si personne ne répond, appeler le service des incendies.
DO NOT DESTROY THIS MANUAL. KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
Page 2
TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION .......................3
REQUIREMENTS AND CODES .................................. 4
Combustion Air Quality .............................................4
Operation of Furnace During Construction ...............4
Installation in a Garage ............................................4
Clearances to Combustible Materials ....................... 5
Heating Load ............................................................5
COMBUSTION AIR & VENTING REQUIREMENTS ....6
General Information .................................................7
Installation in a Confi ned Space ...............................7
Air From Inside ...................................................7
Outdoor Air from a Crawl Space or
Vented Attic ........................................................ 7
Outdoor Air Using Vertical Ducts ........................8
Outdoor Air Using Horizontal Ducts ...................8
Air Directly Through an Exterior Wall .................8
Alternate Method of Providing Air from
Outside ...............................................................9
Installation in an Unconfi ned Space .........................9
Category I Venting ....................................................9
Horizontal Venting ..................................................10
Flexible Vent Systems ............................................ 10
CIRCULATING AIR REQUIREMENTS ......................11
Plenums & Air Ducts ..............................................11
Supply Air Connections ..........................................11
Upfl ow / Horizontal Furnaces ...........................11
Downfl ow Furnaces ..........................................11
Return Air Connections ..........................................11
Upfl ow / Horizontal Furnaces ...........................11
Side Return Installations .............................11
Bottom Return Installations ........................12
Downfl ow Furnaces ..........................................12
Acoustical Treatments ............................................12
FURNACE INSTALLATION .......................................12
General Requirements ........................................... 12
Upfl ow Installation .................................................. 12
Side Return Air Inlet ......................................... 12
Bottom Return Air Inlet ..................................... 12
Downfl ow Installation .............................................. 12
Installation on a Concrete Slab ........................ 13
Horizontal Installation ............................................. 13
Pressure Switches ................................................. 14
Bottom Panel Removal ........................................... 14
Alternate Bottom Panel Removal ..................... 14
GAS SUPPLY & PIPING ............................................15
Leak Check ...........................................................15
High-Altitude Application ........................................16
Conversion to LP / Propane ...................................18
ELECTRICAL WIRING ...............................................18
Line Voltage Wiring ................................................19
Grounding ..............................................................19
Thermostat / Low Voltage Connections .................19
Single Stage AC & Single Stage Heat
Thermostat .......................................................20
Single Stage AC & Two - Stage Heat
Thermostat .......................................................20
Two - Stage AC & Two - Stage Heat
Thermostat .......................................................20
Autostaging for Single Stage Thermostats .............20
Autostaging for Two-Stage Thermostats ................21
Heat Anticipator ......................................................21
Dehumidifi cation Options .......................................21
Blower Speed Confi guration ...................................21
Fixed Speed Blowers ........................................21
Variable Speed Blowers ....................................21
START-UP & ADJUSTMENTS ...................................22
Pre-Start Checklist .................................................22
Start-Up Procedures ..............................................22
Verifying & Adjusting Input Rate ............................22
Verifying & Adjusting Temperature Rise .................23
Verifying Burner Operation ....................................23
Verify Operation of the Supply Air Limit Switch ......23
OPERATING SEQUENCE .........................................23
Heating Cycle .........................................................23
Cooling Cycle .........................................................24
Fan Mode ...............................................................24
MAINTENANCE .........................................................24
Air Filters ................................................................25
Blower Compartment .............................................25
Cleaning of Burners ...............................................25
Cleaning of Flue Passages ....................................25
Heat Exchanger & Burner Maintenance .................26
Lubrication ..............................................................26
Vent System ...........................................................26
DESCRIPTION OF COMPONENTS ..........................26
TROUBLESHOOTING ...............................................27
2
Page 3
FIGURES & TABLES .................................................28
Figure 20 - Furnace Dimensions ...................... 28
Airfl ow Data ............................................................29
Table 5 - Heating / Cooling Airfl ows and
Temperature Rises - Fixed
Table 6 -
Variable Speed ....................................31
Table 7 -
Variable Speed....................................32
Electrical Information ...........................................33
Figure 21 - Two-Stage Fixed Speed Motor
Control Board ..................................33
Figure 22 - Two-Stage Variable Speed
Motor Control Board ........................33
Figure 23 - Two-Stage Furnace Control Board ..33 Figure 24 - Wiring Diagram - Two Stage Fixed
Speed Upfl ow/Horiz. Furnaces ........34
Figure 25 - Wiring Diagram - Two Stage Fixed
Speed Downfl ow Furnaces .............35
Figure 26 - Wiring Diagram - Two Stage Variable
Speed Upfl ow/Horiz. Furnaces .......36
Figure 27 - Wiring Diagram - Two Stage Variable
Speed Downfl ow Furnaces .............37
Gas Information ...................................................38
Table 8 - Gas Flow Rates ..................................38
Table 9 - Gas Pipe Capacities ...........................38
Table 10 - High Altitude Deration Chart for
Propane Gas ....................................39
Table 11 - Natural Gas Heating Values .............39
Table 12 - High Altitude Deration Chart for
Nat. Gas - High Heating Value .........40
Table 13 - High Altitude Deration Chart for
Nat. Gas - Low Heating Value ..........40
Location of Furnace Components ........................41
Figure 28 - Upfl ow / Horizontal Gas Furnace
Components ...................................42
INSTALLATION / PERFORMANCE CHECKLIST .....44
Nominal CFM & Temperature Rises -
Nominal Cooling / Heat Pump CFM -
Speed ......30
IMPORTANT SAFETY INFORMATION
Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
REQUIREMENTS & CODES
WARNING:
The information listed below must be followed during the installation, service, and operation of this furnace. Failure to follow safety recommendations could result in possible damage to the equipment, serious personal injury or death.
• This furnace must be installed in accordance with these instructions, all applicable local building codes and the current revision of the National Fuel Gas Code (NFPA54/ANSI Z223.1) or the Natural Gas and Propane Installation Code, CAN/CGA B149.1.
• Use only with type of gas approved for this furnace. Refer to the furnace rating plate.
• Install this furnace only in a location and position as specifi ed on page 5.
• Provide adequate combustion and ventilation air to the furnace space as specifi ed on pages 6 - 10.
• Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specifi ed on pages 9 - 10.
• Never test for gas leaks with an open fl ame. Use a commercially available soap solution to check all connections. See pages 15 - 16.
• This furnace is designed to operate with a maximum external pressure rise of 0.5 inches of water column. Consult Tables 5 - 7 (pages 30 - 32), and the rating plate for the proper circulating air fl ow and temperature rise. It is important that the duct system be designed to handle the desired fl ow rate and temperature rise. An improperly designed duct system can result in nuisance shutdowns, and comfort or noise issues.
• When supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by duct(s) sealed to the furnace casing and terminating outside the space containing the furnace. See pages 11 - 12.
• This furnace may be used for temporary heating of buildings or structures under construction. See the guidelines listed on pages 4 - 5.
• A gas-fi red furnace for installation in a residential garage must be installed as specifi ed on page 5.
• This furnace is not approved for installation in mobile homes. Installing this furnace in a mobile home could cause fi re, property damage, and/or personal injury.
3
Page 4
Combustion Air Quality
CAUTION:
Combustion air must not be drawn from a corrosive atmosphere.
To maximize heat exchanger life, the combustion air must be free of chemicals that can form corrosive acidic compounds in the combustion gases. The recommended source of combustion air is to use outdoor air. However, the use of indoor air in most applications is acceptable except as listed:
• If the furnace is installed in a confi ned space, it is required that the necessary combustion air come from the outdoors by way of attic, crawl space, air duct, or direct opening. For Installations in confi ned spaces, see pages 7 - 8 for combustion air requirements.
• Installations in these locations may require outdoor air for combustion, due to chemical exposures:
Commercial buildings Buildings with indoor pools Furnaces installed in laundry rooms Furnaces installed in hobby or craft rooms Furnaces installed near chemical storage areas
• Exposure to the following substances in the combustion air supply may require outdoor air for combustion:
Permanent wave solutions Chlorinated waxes and cleaners Chlorine based swimming pool chemicals Water softening chemicals De-icing salts or chemicals Carbon tetrachloride Halogen type refrigerants Cleaning solvents (perchloroethylene) Printing inks, paint removers, varnishes, etc. Hydrochloric acid Cements and glues Antistatic fabric softeners Masonry acid washing materials
Operation of Furnace During Construction
CAUTION:
Failure to follow these instructions will void the factory warranty and may signifi cantly reduce the life or the performance of the furnace, and/ or result in other unsafe conditions. It is the responsibility of the installing contractor to insure these provisions are met.
Operating gas furnaces in construction environments can cause a variety of problems with the furnace. Proper use of commercial portable space heating equipment during construction is recommended. This gas furnace may be used during construction if it is not in violation of any applicable codes and the following criteria are met:
• The installation must meet all applicable codes. The furnace must be permanently installed according to the instructions supplied with the furnace including electrical supply, gas supply, duct work and venting. The furnace must be controlled by a thermostat properly installed according to the instructions supplied with the furnace and thermostat. The installation must include a properly installed fi lter in the return air system with no by-pass air. The fi lter must be inspected frequently and replaced when necessary.
• Combustion air must be supplied from outside the structure and located such that dust and gases from construction activity are not introduced into the combustion system.
• Before occupying the structure: The fi lter must be replaced or cleaned, the duct work must be inspected and cleaned of any construction debris, and the furnace must be cleaned and/or repaired if found to be dirty, damaged, or malfunctioning in any way by a qualifi ed HVAC technician. The furnace shall be inspected and approved by applicable local authority even if this requires redundant inspections.
• Serial numbers for furnaces used during construction must be submitted in writing (fax and email also acceptable). This information will be used to track the long-term affects of the use during construction on furnaces. Proof of this submittal shall be available for the fi nal inspection of the furnace prior to occupancy.
• This furnace is designed to operate with return air temperatures in ranges normally found in occupied residences, including setbacks. Minimum continuous return temperature must not be below 60° F (15° C). Occasionally a temporary return temperature of 55° F (12° C) is acceptable. However, operation with a return temperature below 55° F (12° C) is not allowed.
Installation in a Garage
WARNING:
Do not place combustible materials on or against the furnace cabinet or within 6 inches of the vent pipe. Do not place combustible materials, including gasoline or any other fl ammable vapors and liquids, in the vicinity of the furnace.
This gas-fi red furnace may be installed in a residential garage with the provision that the burners and igniter are located no less than 18 inches (457mm) above the fl oor. The furnace must be located or protected to prevent physical damage by vehicles.
4
Page 5
Clearances to Combustible Materials
This furnace is Design Certifi ed in the U.S. and Canada by CSA International for the minimum clearances to combustible materials. NOTE: The furnace is listed for installation on combustible or non-combustible fl ooring. However, wood is the only combustible fl ooring allowed for installation. Downfl ow models must use the appropriate subase kit when installing over a wood fl oor. To obtain model number and specifi c clearance information, refer to the furnace rating plate, located inside of the furnace cabinet.
Access for positioning and servicing the unit must be considered when locating unit. The need to provide clearance for access to panels or doors may require clearance distances over and above the requirements.
Allow 24 inches minimum clearance from the front of the unit. However 36 inches is strongly recommended.
See Table 1 for minimum clearance requirements.
CLEARANCES TO COMBUSTIBLE MATERIALS
Left Side..................0 Inches Top ..........................0 Inches
Right Side ...............0 Inches Front ......................
Vent ......................... 0 Inches Back ........................0 Inches
Allow 24 in. minimum clearance for servicing. Recommended
clearance is 36 in.
UPFLOW & DOWNFLOW
APPLICATIONS
BACK
TOP
LEFT SIDE
FRONT
VENT
RIGHT SIDE
HORIZONTAL
APPLICATIONS
TOP
VENT
SIDE
SIDE
4 Inches
FRONT
BOTTOM
Table 1. Minimum Clearances to
Combustible Materials
Heating Load
This furnace should be sized to provide the design heating load requirement. Heating load estimates can be made using approved methods available from Air Conditioning Contractors of America (Manual J); American Society of Heating, Refrigerating, and Air Conditioning Engineers; or other approved engineering methods. Excessive
oversizing of the furnace could cause the furnace and/or vent to fail prematurely. The ductwork should
be appropriately sized to the capacity of the furnace to ensure its proper airfl ow rating.
Two-stage furnaces operate at two input rates to better meet heating loads. The lower heating rate (low fi re) is 65% of the high fi re rate. The greatest degree of control over the furnace can be gained by controlling it with a two stage thermostat. This allows the thermostat to directly request either high or low fi re. However, it is possible to operate the furnace using a single stage thermostat. In this application the furnace control can be set to increase from low to high fi re, based on a timer. See Autostaging for Single Stage Thermostats (page 20).
Furnaces are properly sized to meet the expected maximum heating load. But this load occurs infrequently. So, during more moderate weather, the furnace is likely to use low fi re a considerable part of the time. This is normal and has the benefi t of quieter and more effi cient operation.
The information listed below is for reference purposes only and does not necessarily have jurisdiction over local or state codes. Always consult with local authorities before installing
any gas appliance.
Combustion and Ventilation Air
• US: National Fuel Gas Code (NFGC), Air for Combustion and Ventilation
• CANADA: Natural Gas and Propane Installation Codes (NSCNGPIC), Venting Systems and Air Supply for Appliances
Duct Systems
• US and CANADA: Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) Fundamentals Handbook
Electrical Connections
• US: National Electrical Code (NEC) ANSI/NFPA 70
• CANADA: Canadian Electrical Code CSA C22.1
Gas Piping and Gas Pipe Pressure Testing
• US: NFGC and National Plumbing Codes
• CANADA: NSCNGPIC
General Installation
• US: Current edition of the NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or American Gas Association, 400 N. Capitol, N.W., Washington DC 20001 or www.NFPA.org
• CANADA: NSCNGPIC. For a copy, contact Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3 Canada
Safety
• US: (NFGC) NFPA 54–1999/ANSI Z223.1 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B.
• CANADA: CAN/CGA-B149.1 and .2–M00 National Standard of Canada. (NSCNGPIC)
For installations above 2,000 ft., the furnace should have a sea level input rating large enough that it will meet the heating load after deration for altitude.
5
Page 6
COMBUSTION AIR & VENTING REQUIREMENTS
WARNING:
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed with each individual appliance connected to the venting system being placed in operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National
Fuel Gas Code, ANSI Z223.1/NFPA 54 or the CSA B149.1, Natural Gas and Propane Installation Codes and these instructions.
Determine that there is no blockage or restriction, leakage, corrosion and other defi ciencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fi replace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the fl ame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance with the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fi replace dampers and any other gas-fi red burning appliance to their previous conditions of use.
AVERTISSEMENT:
RISQUE D’EMPOISONNEMENT AU
MONOXYDE DE CARBONED
Le non-respect des consignes suivantes portant
sur chacun des appareils raccordés au système d’évacuation mis en service pourrait entraîner l’empoisennement au monoxyde de carbone ou la mort. Les consignes suivantes doivent être observées pour chaque appareil raccordé au système d’évacuation mis en service si les autres appareils raccordés au système ne sont pas en service:
1. Sceller toute ouverture non utilisée de la systéme d’évacuation;
2. S’assurer que la systéme d’évacuation présente des dimensions et une pente horizontale conformes à la norme ANSI Z223.1/NFPA 54, intitulée National Fuel Gas Code ou aux codes d’installation CSA-B149.1, ainsi qu’aux présentes instructions. S’assurer que la systéme d’évacuation n’est pas bloquée, restreinte, corrodée, qu’elle ne fuit pas et qu’elle ne présente aucun autre défaut potentiellement dangereux;
3. Dans la mesure du possible, fermer toutes les portes et fenêtres du bâtiment, et toutes les portes entre la pièce où se trouve l’appareil raccordé à la systéme d’évacuation et les autres pièces du bâtiment.
4. Fermer les registres des foyers;
5. Mettre en service les sécheuses et tout autre appareil qui n’est pas raccordé à la systéme d’évacuation. Faire fonctionner à régime maximal tout ventilateur d’évacuation, tel que les hottes de cuisinière et les ventilateurs de salles de bains. Ne pas mettre en service les ventilateurs d’été.
6. Respecter les instructions d’allumage. Mettre en service l’appareil à l’essai. Régler le thermostat de manière à ce que l’appareil fonctionne sans interruption;
7. Vérifi er s’il y a débordement à l’orifi ce d’évacuation du coupe tirage des appareils dotés d’un coupe tirage 5 minutes après l’allumage du brûleur principal. Utiliser la fl amme d’une allumette ou d’une chandelle.
8. Si l’on constate, au cours de l’un des essais qui précèdent, que l’évacuation est défi ciente, corriger le système d’évacuation conformément à la norm ANSI Z223.1/NFPA 54, National Fuel Gas Code, et (ou) aux codes d’installation CSA B149.1.
9. Après avoir déterminé que tous les appareils raccordés à la systéme d’évacuation évacuent correctement tel que prescrit ci-dessus, rouvrir les portes et les fenêtres et remettre les ventilateurs d’évacuation, les registres de foyers et tout autre appareil fonctionnant au gaz à leur état de fonctionnement initial.
6
Page 7
General Information
WARNING:
Furnace installation using methods other than those described in the following sections must comply with the National Fuel Gas Code (NFGC) and all applicable local codes.
• Instructions for determining the adequacy of combustion air for an installation can be found in the current revision of the NFGC (ANSI Z223.1 / NFPA54). Consult local codes for special requirements. These requirements are for US installations as found in the NFGC.
• The requirements in Canada (B149.1) are structured differently. Consult with B149.1 and local code offi cials for Canadian installations.
Provisions must be made during the installation of this furnace that provide an adequate supply of air for combustion.
the method by which the air is brought to the space, and by the total input rate of all appliances in the space. In all cases, the minimum dimension of any combustion air opening is 3 inches.
Air From Inside
If combustion air is taken from the heated space, the two openings must each have a free area of at least one square inch per 1,000 Btuh of total input of all appliances in the confi ned space, but not less than 100 square inches of free area (Figure 1). See example.
Example:
If the combined input rate of all appliances is less than or equal to 100,000 Btuh, each opening must have a free area of at least 100 square inches. If the combined input rate of all appliances is 120,000 Btuh, each opening must have a free area of at least 120 square inches.
CAUTION:
Exhaust fans, clothes dryers, fi replaces and other appliances that force air from the house to the outdoors can create a negative pressure inside the house, resulting in improper furnace operation or unsafe conditions such as fl ame roll out. It is imperative that suffi cient air exchange with the outdoors is provided to prevent depressurization. Additional information about testing negative pressure problems can be found in the National Fuel Gas Code.
NOTE: Air openings on top of the furnace and openings
in closet doors or walls must never be restricted. If the furnace is operated without adequate air for combustion, the fl ame roll-out switch will open, turning off the gas supply to the burners. This safety device is a manually reset switch. DO NOT install jumper wires across these
switches to defeat their function or reset a switch without identifying and correcting the fault condition.
If a switch must be replaced, use only the correct sized part specifi ed in the Replacement Parts List provided online.
Installation In A Confi ned Space
A confi ned space is an area with volume less than 50 cubic feet per 1,000 Btuh of the combined input rates of all appliances drawing combustion air from that space. Furnace closets, small equipment rooms and garages are confi ned spaces. Furnaces installed in a confi ned space which supply heated air to areas outside the space must draw return air from outside the space and must have the return air ducts tightly sealed to the furnace.
Vent or
Chimney
NOTES: Each opening must be at least 100 sq. in. or 1 sq. in. per 1,000 Btuh of total input rating, whichever is greater.
Openings must start at no more than 12 inches from the top and bottom of the enclosure.
Water Heater
Total Input Rating
(Btuh)
40,000 100 sq. In 12 inches 60,000 100 sq. In 12 inches
80,000 100 sq. In 12 inches 100,000 100 sq. In 12 inches 120,000 120 sq. In 13 inches 140,000 140 sq. In 14 inches 160,000 160 sq. In 15 inches
Minimum Free Area
(Each Opening)
12" Max.
Furnace
See Notes
12” Max.
See
Notes
Round Duct
Diameter
Figure 1. Combustion Air Drawn from Inside
Outdoor Air from a Crawl Space or Vented Attic
When the openings can freely exchange air with the outdoors, each opening shall have a minimum free area of 1 square inch per 4,000 Btuh of total appliance input. The openings shall exchange directly, or by ducts, with the outdoor spaces (crawl or attic) that freely exchange with the outdoors (Figure 2, page 8).
The required sizing of these openings is determined by whether inside or outside air is used to support combustion,
7
Page 8
Ventilation louvers
Vent or
Chimney
Attic Insulation
at each end of attic
Outlet air duct must be at least 1 sq. in. per 4,000 Btuh of total input rating. Must
Wate r Heater
Crawl Space
Furnace
Ventilated Louvers for unheated crawl space
extend above attic insulation
Inlet air duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.
Figure 2. Combustion Air Drawn from a Crawl
Space or Vented Attic
Outdoor Air Using Vertical Ducts
If combustion air is taken from outdoors through vertical ducts, the openings and ducts must have a minimum free area of one square inch per 4,000 Btuh of total appliance input. In installations drawing combustion air from a ventilated attic, both air ducts must extend above the attic insulation (Figure 3).
Ventilation Louvers at each end of attic
Vent or Chimney
Water Heater
Attic
Insulation
Furnace
Outlet Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.
Inlet and Outlet Ducts must extend above attic insulation.
Inlet Air Duct must be at least 1 sq. in. per 4,000 Btuh of total input rating.
12" Max
Total Input Rating
(Btuh)
Minimum Free Area
(Each Opening)
Round Duct
Diameter
40,000 100 sq. In 12 inches 60,000 100 sq. In 12 inches
80,000 100 sq. In 12 inches 100,000 100 sq. In 12 inches 120,000 120 sq. In 13 inches 140,000 140 sq. In 14 inches 160,000 160 sq. In 15 inches
Figure 3. Combustion Air Drawn from Outside
Through Vertical Ducts
Outdoor Air Using Horizontal Ducts
If combustion air is taken from outdoors through horizontal ducts, the openings and ducts must have a minimum free area of one square inch per 2,000 Btuh of total appliance input (Figure 4).
Vent or
Chimney
12" Max
-
-
-
-
-
-
-
-
-
-
-
See
Note
-
-
-
-
-
-
-
-
-
12" Max
Total Input Rating
(Btuh)
-
-
-
-
-
-
Air Duct
-
Furnace
-
-
-
-
-
-
-
-
Air Duct
-
Water Heater
Minimum Free Area
(Each Opening)
-
-
-
-
NOTE: Each
-
-
-
-
-
opening to outside must be at least 1 sq. in. per 2,000 Btuh of total
-
-
-
-
-
-
input rating.
-
-
-
Round Duct
Diameter
40,000 10 sq. In 5 inches 60,000 15 sq. In 6 inches
80,000 20 sq. In 7 inches 100,000 25 sq. In 8 inches 120,000 30 sq. In 9 inches 140,000 35 sq. In 10 inches 160,000 40 sq. In 10 inches
Figure 4. Combustion Air Drawn from Outside
Through Horizontal Ducts
Air Directly Through An Exterior Wall
If combustion air is provided directly through an exterior wall, the two openings must each have free area of at least one square inch per 4,000 Btuh of total appliance input (Figure 5).
Vent or
12" Max
-
-
-
-
-
-
-
-
-
See Note
-
-
-
-
-
-
-
-
-
12" Max
Total Input Rating
(Btuh)
40,000 10 sq. In 4 inches
60,000 15 sq. In 5 inches
80,000 20 sq. In 5 inches
100,000 25 sq. In 6 inches 120,000 30 sq. In 6 inches 140,000 35 sq. In 7 inches 160,000 40 sq. In 8 inches
Figure 5. Combustion Air Drawn from Outside
Chimney
NOTE: Each opening
Furnace
to outside must be at least 1 sq. in. per 4,000 Btuh of total input rating.
Water Heater
Minimum Free Area
(Each Opening)
Through an Exterior Wall
Round Duct
Diameter
8
Page 9
Alternate Method of Providing
Air from Outside:
If acceptable under local Codes, it is permitted to provide outside air using one opening (See NFGC). Generally, confi ned spaces must have two openings in the space for combustion air. One opening must be within 12 inches of the ceiling, and the other must be within 12 inches of the fl oor. However, an alternative method recently adopted by the NFGC uses one opening within 12 inches of the top of the space. This method may be used if it is acceptable to the local codes.
The following conditions must be met:
1. The opening must start within 12” of the top of the structure and connect with the out of doors through vertical or horizontal ducts or be ducted to a crawl or attic space that connects with the out of doors.
2. The opening must have a minimum free area of 1 sq. in. per 3,000 Btu per hour of the total input rating of all equipment located in the enclosure.
3. The free area must not be less than the sum of all the areas of the vent connectors in the enclosure.
Installation In An Unconfi ned Space
An unconfi ned space is an area including all rooms not separated by doors with a volume greater than 50 cubic feet per 1,000 Btuh of the combined input rates of all appliances which draw combustion air from that space.
In general, a furnace installed in an unconfi ned space will not require outside air for combustion. However, in homes built for energy effi ciency (low air change rates), it may be necessary to provide outside air to ensure adequate combustion and venting, even though the furnace is located in an unconfi ned space. See example.
Example:
A space with a water heater rated at 45,000 Btuh input and a furnace rated at 75,000 Btuh requires a volume of 6,000 cubic feet [50 x (45 + 75) = 6,000] to be considered unconfi ned. If the space has an 8 foot ceiling, the fl oor area of the space must be 750 square feet (6,000 / 8 = 750).
Category I Venting
This furnace is listed as a Category I vented appliance. Category I furnaces generally operate with a slight negative pressure (draft) and must be vented vertically or near vertical. Additionally it is important to guard against excessive condensation.
WARNING:
Upon completion of the furnace installation, carefully inspect the entire fl ue system both inside and outside the furnace to assure it is properly sealed. Leaks in the fl ue system can result in serious personal injury or death due to exposure of fl ue products, including carbon monoxide.
• This furnace must be vented in compliance with the current revision of the National Fuel Gas Code (ANSI-Z223.1/NFPA54) and the instructions provided below. Consult local codes for special requirements.
• In Canada, venting shall conform to the requirements of the current (CAN/CGA B149.1 or .2) installation codes.
Consult local codes for special requirements.
• Category I furnace installations must be connected to a factory built chimney or vent complying with a recognized standard, or a masonry or concrete chimney lined with a lining material acceptable to the authority having jurisdiction.
WARNING:
Venting into an unlined masonry chimney or concrete chimney is prohibited. This may result in improper draft and excess condensation forming in the chimney.
• This furnace may be vented with a dedicated venting system or common vented with other Category I appliances. The vent system dimensions and material must conform to the NFGC or local Codes. Generally, this means using Type B vent pipe or a lined masonry chimney. When consulting the vent sizing tables in the NFGC, the MAX capacity of the vent must be greater than the furnaces high fi re rate. The MIN capacity must be lower than the low fi re rate. If the venting system is inappropriate for the furnace, the venting system will need to be modifi ed to comply with NFGC or local codes. The minimum diameter of any vent pipe is 4
inches.
• The venting system should be designed to have the minimum number of elbows or turns. All horizontal runs shall slope upwards from the furnace at ¼ inch per running foot of vent. Supports for the vent pipe must be installed a minimum of every fi ve feet along the vent run to ensure no displacement after installation. Under no circumstances shall any portion of the vent system
9
Page 10
extend into or pass through any return air duct, supply air duct, or plenum.
• Single wall vent connectors may be used under the limited capacity ranges found in the vent sizing tables. It is recommended that Type B double wall vent be used for the connector whenever possible. An existing masonry chimney should be inspected and relined if necessary.
• In the U.S., this furnace must never be vented to a chimney or fl ue that services a fi replace or other appliance designed to burn solid fuel. If the furnace vent is to be connected to a chimney serving a fi replace, the fi replace must be sealed off from the chimney. In Canada, common venting with a fi replace is permitted. Consult B149.1 and your local code authority.
• Single wall metal vertical vents shall not be used for Category I venting. The furnace vent, if metal, may be insulated if local codes allow. Any part of the vent system, metal vent only, not exposed to weather, but which are exposed to temperatures below 35° F (1° C) must be insulated to prevent condensation. All vent insulation shall be foil backed fi berglass of one inch minimum thickness.
• Sheet metal fasteners should be used to secure the vent pipe to the furnace fl ue. However, the NFGC states that alternative vent products may be attached according to the vent manufacturers instructions.
• When an existing furnace is removed from a vent system serving other appliances, the existing vent system may no longer be sized to properly vent the remaining appliances. An improperly sized venting system can result in the formation of condensate, leakage, or spillage. The existing vent system should also be checked to make sure it remains in compliance with the National Fuel Gas Code. If it isn’t, the vent system must be brought into compliance before installing the furnace.
Horizontal Venting
WARNING:
Horizontal vent systems must be sealed with a high temperature sealant that can withstand temperatures of 450° F. Recommended sealants: Dow Corning Sealant 736 RTV; GE 106 RTV; High Tech Ind., High TEMP RED.
This furnace is not approved for horizontal venting without the use of an add-on power venter. Power venters establish negative pressure in the vent piping and the furnace operates as if connected to a Category I vertical vent. The power venter is only for use when exhausting through an exterior wall.
The power venter must be installed according to the instructions provided by the power venter manufacturer and applicable requirements of local codes. For Canadian installations please refer to the Canadian Installation Code (CAN/CGA-B149.1 or 2) and/or local codes.
The outlet of the vent must be at least 12 inches above the highest expected snow accumulation.
Flexible Vent Systems
Flexible venting systems are approved for use providing they are listed for the application and meet all local Code requirements. These systems are primarily used to line existing masonry chimneys. They must be sized to the application according to the sizing tables in the National Fuel Gas Code, including the required 20% reduction in maximum capacity.
Flexible venting systems are permitted to be used as the vent connector. However, great care must be taken to ensure that there are no sags in the venting system which could accumulate condensate. The fl exible vent system must be supported at no more than 5 foot intervals and maintain a minimum slope of ¼ inch per foot of horizontal run.
10
Page 11
CIRCULATING AIR REQUIREMENTS
WARNING:
Do not allow combustion products to enter the circulating air supply. Failure to prevent the circulation of combustion products into the living space can create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death.
All return ductwork must be secured to the furnace with sheet metal screws. For installations in confi ned spaces, all return ductwork must be adequately sealed. When return air is provided through the bottom of the furnace, the joint between the furnace and the return air plenum must be air tight.
The surface that the furnace is mounted on must provide sound physical support of the furnace with no gaps, cracks or sagging between the furnace and the fl oor or platform.
Return air and circulating air ductwork must not be connected to any other heat producing device such as a fi replace insert, stove, etc. This may result in fi re, explosion, carbon monoxide poisoning, personal injury, or property damage.
Plenums and Air Ducts
• Plenums and air ducts must be installed in accordance with the Standard for the Installation of Air Conditioning and Ventilating Systems (NFPA No. 90A) or the Standard for the Installation of Warm Air Heating and Air Conditioning Systems (NFPA No. 90B).
• Tables 5 - 7 (pages 29 - 32) contain the maximum airfl ow and temperature rise data for fi xed and variable speed motors. If the maximum airfl ow is 1,600 CFM or more, it is recommended that two openings be used for return air on upfl ow furnaces. Downfl ow furnaces can only use one return opening.
• It is recommended that the outlet duct contain a removable access panel. The opening should be accessible when the furnace is installed in service and shall be of a size that smoke or refl ected light may be observed inside the casing to indicate the presence of leaks in the heat exchanger. The cover for the opening shall be attached in such a manner as to prevent leaks.
• If outside air is used as return air to the furnace for ventilation or to improve indoor air quality, the system must be designed so that the return air is not less than 60° F (15° C) during operation. If a combination of indoor and outdoor air is used, the ducts and damper system must be designed so that the return air supply to the
furnace is equal to the return air supply under normal, indoor return air applications.
• When a cooling system is installed which uses the furnace blower to provide airfl ow over the indoor coil, the coil must be installed downstream (on the outlet side) of the furnace or in parallel with the furnace.
• If a cooling system is installed in parallel with the furnace, a damper must be installed to prevent chilled air from entering the furnace and condensing on the heat exchanger. If a manually operated damper is installed, it must be designed so that operation of the furnace is prevented when the damper is in the cooling position and operation of the cooling system is prevented when the damper is in the heating position.
• It is good practice to seal all connections and joints with industrial grade sealing tape or liquid sealant. Requirements for sealing ductwork vary from region to region. Consult with local codes for requirements specifi c to your area.
Supply Air Connections
The supply air must be delivered to the heated space by duct(s) secured to the furnace casing, running full size and without interruption.
Upfl ow and Horizontal Furnaces
To attach the supply air duct to the furnace, bend the furnace fl anges (Figure 20, page 28) upward 90° with a pair of wide duct pliers. Position the duct on top of the furnace and secure together with sheet metal screws. The screws must penetrate the sheet metal casing and furnace fl ange. Tape or seal all seams if required by local code.
Downfl ow Furnaces
To attach the supply air duct to the downfl ow furnace, position the furnace over the duct and secure together with sheet metal screws. The screws must penetrate the duct and furnace casing.
Return Air Connections
In applications where the supply ducts carry heated air to areas outside the space where the furnace is installed, the return air must be delivered to the furnace by duct(s) secured to the furnace casing, running full size and without interruption.
Upfl ow and Horizontal Furnaces
For upfl ow installations, the return air ductwork may be connected to the left side, right side, or bottom. The bottom panel (Figure 20) must be installed for left or right return air. NOTE: Do not use the back of the furnace
for return air.
Side Return Installations
To attach the return air duct to the left or right side of the furnace, punch out the four knockouts (Figure 20) from the preferred side of the furnace. Using sharp metal
11
Page 12
cutters, cut an opening between all four knockouts to expose the blower assembly. Position the return air duct over the opening in the side and secure together with sheet metal screws. The screws must penetrate the duct and furnace casing.
WARNING:
The solid base of the furnace must be in place when the furnace is installed with side return air ducts. Removal of all or part of the base could cause circulation of combustible products into the living space and create potentially hazardous conditions, including carbon monoxide poisoning that could result in personal injury or death.
Bottom Return Installations
The bottom panel (Figure 20) must be removed from the bottom of the furnace for bottom return air. If bottom panel is still installed, go to page 14 for removal instructions. Position the furnace over the return air duct and secure together with sheet metal screws. The screws must penetrate the duct and furnace casing.
Downfl ow Furnaces
To attach the return air duct to the furnace, bend the furnace fl anges (Figure 20) upward 90° with a pair of wide duct pliers. Position the duct on top of the furnace and secure together with sheet metal screws. The screws must penetrate the sheet metal casing and furnace fl ange. Tape or seal all seams if required by local code.
Acoustical Treatments
Damping ducts, fl exible vibration isolators, or pleated media-style fi lters on the return air inlet of the furnace may be used to reduce the transmission of equipment noise eminating from the furnace. These treatments can produce a quieter installation, particularly in the heated space. However, they can increase the pressure drop in the duct system. Care must be taken to maintain the proper maximum pressure rise across the furnace, temperature rise and fl ow rate. This may mean increasing the duct size and/or reducing the blower speed. These treatments must be constructed and installed in accordance with NFPA and SMACNA construction standards. Consult with local codes for special requirements. For best sound performance, be sure to install all the needed gaskets and grommets around penetrations into the furnace, such as for electrical wiring.
FURNACE INSTALLATION
*TA series gas furnaces are shipped ready for installation in the upfl ow or horizontal right or left positions. Only the *TK series gas furnace may be used for downfl ow operation.
General Requirements
• The furnace must be leveled at installation and attached to a properly installed duct system. See Table 1 (page 5) for the required clearances needed to move the furnace to its installation point (hallways, doorways, stairs, etc).
• The furnace must be installed so that all electrical components are protected from water.
• The furnace must be installed upstream from a refrigeration system. (If applicable)
• The furnace requires special venting materials and installation procedures. See pages 11 - 12 for venting guidelines and specifi cations.
Upfl ow Installation
WARNING:
The furnace must not be installed directly on carpeting, tile, or any combustible material other than wood fl ooring.
Side Return Air Inlet
*TA series gas furnaces are shipped with the bottom panel installed (Figure 20). If the upfl ow furnace is installed with side return air, the bottom panel must not be removed.
Bottom Return Air Inlet
*TA series gas furnaces are shipped with the bottom panel installed. If the upfl ow furnace is installed with bottom return air, the bottom panel must be removed (See Bottom Panel Removal on page 14).
Downfl ow Installation
WARNING:
The furnace must not be installed directly on carpeting, tile, or any combustible material other than wood fl ooring.
WARNING:
Failure to install the downfl ow sub-base kit may result in fi re, property damage or personal injury.
12
To install the furnace on combustible fl ooring, a special sub-base is required. Downfl ow sub-base kits are factory supplied accessories and are listed according to the cabinet letter of the furnace. For ‘A’ size cabinets use Sub­Base kit #902974 only. For ‘B’, ‘C’, and ‘D’ size cabinets use Kit #904911. Please follow the instructions provided
with the kit.
Page 13
WARNING:
The downfl ow sub-base kit must not be installed directly on carpeting, tile, or any combustible material other than wood fl ooring.
Concrete
Floor
Furnace
A downfl ow sub-base kit is not necessary if the furnace is installed on a factory or site-built cased air conditioning coil. However, the plenum attached to the coil casing must be installed so that its surfaces are at least 1” from combustible construction.
Installation on a concrete slab
1. Create an opening in the fl oor according to the dimensions in Figure 6.
2. Position the plenum and the furnace as shown in Figure 7.
Opening in concrete floor
“A”
“B”
Cabinet Size Dim. “A” Dim. “B”
A 13 B C D
NOTE: Dimensions shown in Inches.
1/4
19 1/4 16 5/8 19 1/4 20 1/8 19 1/4 23 5/8 19 1/4
Sheet
Metal
Plenum
Figure 7. Furnace on a Concrete Slab
Note: Line Contact
Is Permissible
Gas Inlet
Type “B” Vent
Airflow
Coil Plenum
Electrical Supply
Connection
Combustible Platform
Figure 8. *TA Horizontally Installed on a Platform
Figure 6. Cutout Dimensions
Horizontal Installation
WARNING:
The furnace must not be installed directly on carpeting, tile, or any combustible material other than wood fl ooring.
The *TA series gas furnace can be installed horizontally in an attic, basement, crawl space or alcove (Figure 8). It can also be suspended from a ceiling in a basement or utility room in either a right to left airfl ow or left to right airfl ow as shown in Figure 9.
*TA series furnaces are shipped with the bottom panel installed. If furnace is installed horizontally, remove the bottom panel from the furnace before attaching the duct system. See Bottom Panel Removal on page 14.
If installing the furnace in an attic, it is required that a drip pan be placed under the furnace. If the installation is on a combustible platform (Figure 8), it is recommended that the drip pan extend at least 12 inches past the top and front of the furnace.
Nuts (x2)
Lag
Threaded
Rod
Washer
and
Lockwasher
Nuts (x2)
Bolt
Figure 9. *TA Horizontally Suspended in Attic
If suspending the furnace from the ceiling, assemble a support frame (Figure 9) using slotted iron channel and full threaded rod. Fasten the frame together with nuts, washers, and lockwashers. Secure the support frame to the rafters with lag bolts. The furnace can also be suspended using steel straps around each end of the furnace. The straps should be attached to the furnace with sheet metal screws and to the rafters with bolts.
It is recommended for further reduction of fi re hazard that cement board or sheet metal be placed between the furnace and the combustible fl oor and extend 12 inches beyond the front of the door and top of the furnace.
13
Page 14
Pressure Switches
Figure 10 displays the proper routing of pressure switch tubing for *TA & *TK furnaces. On both furnaces, the tubing connects at one end of the pressure switch and is routed directly to the static tap on the inducer assembly. NOTE: The control board in the *TA illustration has been omitted for clarity of tubing installation. There is no need to remove the control board to install your pressure switch tube.
Figure 10. Pressure Switch Tubing for *TA & *TK Furnaces
8
56 7 4
12 3
Bottom Panel Removal
The steps listed below describe how to remove the bottom panel from the furnace. See Figure 11.
1. Remove the blower door (1) from bottom of furnace.
2. Disconnect the wiring harness (2) from the connector.
3. Remove two screws (3) securing the blower assembly (4) to the furnace.
4. Carefully pull the blower assembly (4) out thru the front of the furnace.
5. Remove all screws (5) securing bottom panel (6) to bottom of furnace and front brace (7).
6. Lift up and slide bottom panel (6) out through front of furnace.
7. Reinstall the blower assembly (4) in reverse order it was removed.
1
3
4
2
5
Alternate Bottom Panel Removal
If the bottom panel cannot be removed using the previous instructions, the steps below are an alternate method for removing the bottom panel. See Figure 12.
1. Remove the door (1) from the blower compartment .
2. Remove all screws securing the bottom panel (2) to the front brace (3).
3. Remove two screws (4) securing the furnace cabinet to the blower deck (5).
4. Remove all screws (6) securing the furnace cabinet to the bottom panel (2).
5. Remove the screw (7) securing the bottom corner of the furnace cabinet to the front brace (3).
6. Carefully spread the bottom cor ner of the furnace cabinet outwards while sliding the bottom panel (2) out through the front of the furnace.
7. Reassemble the furnace in reverse order.
4
1
5
7
6
6
7
Figure 11. Bottom Panel Removal
14
2
3
Figure 12. Alternate Removal Method
Page 15
GAS SUPPLY & PIPING
WARNING:
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly could result in serious injury or property damage.
• Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
• Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from
a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call
the fi re department.
• All gas piping must be installed in compliance with local codes and utility regulations. In the absence of local codes the gas line installation must comply with the latest edition of the National Fuel Gas Code (ANSI Z223.1) or (CAN/CGA B149.1 or .2) Installation Codes.
• Some local regulations require the installation of a manual main shut-off valve and ground joint union external to the furnace. The shut-off valve should be readily accessible for service and/or emergency use. Consult the local utility or gas supplier for additional requirements regarding placement of the manual main gas shut-off. See Figure 13 (page 17).
• Gas piping must never run in or through air ducts, chimneys, gas vents, or elevator shafts.
• Compounds used to seal joints on gas piping must be resistant to the actions of LP propane gas.
• The main gas valve and main power disconnect to the furnace must be properly labeled by the installer in case emergency shutdown is required.
• Flexible gas connectors are not recommended for this type of furnace but may be used if allowed by local jurisdiction. The fl exible gas connector must be agency approved and certifi ed for the type of gas being used. Only new fl exible connectors may be used. Do not reuse old fl exible gas connectors.
• A drip leg should be installed in the vertical pipe run to the unit. See Figure 13.
AVERTISSEMENT:
RISQUE D’INCENDIE OU D’ EXPLOSION
• Le non-respect des avertissements de sécurité pourrait entraîner des blessures graves, la mort ou des dommages matériels.
• L’installation et l’entretien doivent être effectués par un installateur qualifié, un organisme de service ou le fournisseur de gazstaller, service agency or the gas supplier.
• Ne pas entreposer ni utiliser de l’essence ni d’autres vapeurs ou liquides infl ammables dans le voisinage de cet appareil, ni de tout autre appareil.
QUE FAIRE S’IL Y A UNE ODEUR DE GAZ
• Ne pas tenter d’allumer aucun appareil.
• Ne toucher à aucun interrupteur électrique; n’utiliser aucun téléphone dans le bâtiment.
• Évacuer l’immeuble immédiatement.
• Appeler immédiatement le fournisseur de gaz en employant le téléphone d’un voisin. Respecter à la lettre les instructions du fournisseur de gaz.
• Si personne ne répond, appeler le service des incendies.
Table 9 (page 38) lists gas pipe capacities for standard pipe sizes as a function of length in typical applications based on nominal pressure drop in the line.
The furnace may be installed for either left or right side gas entry. When connecting the gas supply, provide clearance between the gas supply line and the entry hole in the furnace casing to avoid unwanted noise and/or damage to the furnace. Typical gas hookups are shown in Figure 13.
Leak Check
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury or property damage.
Never test for gas leaks with an open fl ame. Use a commercially available soap solution made specifi cally for the detection of leaks to check all connections. A fi re or explosion may result causing property damage, personal injury or loss of life.
15
Page 16
AVERTISSEMENT:
RISQUE D’INDENDIE OU D’EXPLOSION
appliance be derated 4% for each 1000 feet of altitude. For example, the input needs to be reduced 8% at 2,000 feet, 12% at 3,000 feet, etc. This deration is in reference to the input rate and gas heating value at sea level.
Le non-respect des avertissements de sécurité pourrait d’entraîner des blessures graves, la mort ou des dommages matériels.
Ne jamais utiliser une fl amme nue por vérifi er la présence des fuites de gaz. Pour la vérifi cation de tous les joints, utiliser plutôt une solution savonneuse commerciale fabriquée spécifi quement pur la détection des fuites de gaz. Un incendie ou une explosion peut entraîner des dommages matériels, des blessures ou la mort.
After the gas piping to the furnace is complete, all connections must be tested for gas leaks. This includes pipe connections at the main gas valve, emergency shutoff valve and fl exible gas connectors (if applicable). The soap and water solution can be applied on each joint or union using a small paintbrush. If any bubbling is observed, the connection is not sealed adequately and must be retightened. Repeat the tightening and soap check process until bubbling ceases.
IMPORTANT NOTE: When pressure testing gas supply lines at pressures greater than 1/2 psig (14 inch W.C.), the gas supply piping system must be disconnected from the furnace to prevent damage to the gas control valve. If the test pressure is less than or equal to 1/2 psig (14 inch W.C.), close the manual shut-off valve.
High Altitude Application
High altitude conversion with this furnace depends on the installation altitude and the heating value of the gas. The installation of this furnace at altitudes above 2,000 feet must meet the requirements of the National Fuel Gas Code or local jurisdiction. In Canada, the requirements for high altitude are different and governed by CGA B149.1. Please consult your local code authority.
WARNING:
The reduction of input rating necessary for high altitude installation may only be accomplished with factory supplied orifi ces. Do not attempt to drill out orifi ces in the fi eld. Improperly drilled orifi ces may cause fi re, explosion, carbon monoxide poisoning, personal injury or death.
To derate the furnace requires knowing the heating value of the gas at the installation site. Heating values at particular job sites vary for two reasons:
1. The chemical mixture of the gas varies from region to region and is expressed as the “sea level heating value”.
2. The heating value varies by altitude. For this reason, especially in high altitude areas, the local gas utility specifi es the heating value at the residence’s gas meter as the “local value”.
For added fl exibility, two tables have been provided for natural gas installations with HIGH or LOW heating values at sea level. Tables 12 and 13 (page 40) contain the orifi ce sizes and manifold pressure to use at various altitudes. Table 12 (HIGH) is for natural gas installations with a heating value of more than 1,000 Btu per cubic foot and Table 13 (LOW) is for less than 1,000 Btu per cubic foot. To determine which table to use:
1. Consult the local utility for the local heating value at your installation site.
2. From Table 11 (page 39), fi nd your local heating value as supplied by the utility company. Follow down the column and stop at your altitude level.
3. If your sea level heating value is HIGH, use Table 12 or if it’s LOW, use Table 13.
Installation Example
Elevation: .................................................. 5,000 feet
Type of Gas: ........................................... Natural Gas
Local Heating Value of Gas: ..............................750
From Table 11, fi nd 750 and follow down the column, stop at the 5,000 feet row. The heating value listed is LOW. Table 13 will be used to determine orifi ce size and manifold pressure.
After changing the regulator pressure or changing the orifi ces, it is required that you measure the gas input rate. This may be accomplished in the usual way, by clocking the gas meter and using the local gas heating value. See Verifying & Adjusting the Input Rate section (page 22).
IMPORTANT NOTE: Observe the action of the burners to make sure there is no yellowing, lifting or fl ashback of the fl ame.
The furnaces are shipped from the factory with orifi ces and gas regulator settings for natural gas operation at sea level altitudes. At 2000 feet, the NFGC requires that this
16
Page 17
UPFLOW MODELS
Note “A”
8
3
See
1
1
See
Note “A”
8
4
3
7
5
2
Left Side Entry
6
2
6
Right Side Entry
5
DOWNFLOW MODELS
See
Note “A”
8
7
1
1
See
Note “A”
8
4
3
5
2
Left Side Entry
6
2
Right Side Entry
5
6
3
COMPONENTS:
(1) Automatic Gas Valve
(w/ manual shut-off)
(2) Burner Assembly (3) Dripleg (4) Elbow
(5) Ground Joint Union (6) Manifold (7) Plug (8) Shut - Off Valve
NOTE: Some utilities require Shut- Off Valve to be 4 to 5 feet above fl oor.
Figure 13. Typical Gas Connections
17
Page 18
Conversion to LP / Propane
ELECTRICAL WIRING
WARNING:
The furnace was shipped from the factory equipped to operate on natural gas. Conversion to LP / Propane gas must be performed by qualifi ed service personnel using a factory supplied conversion kit. Failure to use the proper conversion kit can cause fi re, explosion, property damage, carbon monoxide poisoning, personal injury, or death.
Conversion to LP / Propane is detailed in the installation instructions provided with the conversion kit. Generally, this will require the replacement of the burner orifi ces and the spring/stem assembly in the pressure regulator. In the U.S. if installation is above 2,000 ft., refer to Table 10 (page 39) to determine the correct orifi ce size and regulator pressure. See example below.
Installation Example
Elevation: .................................................. 5,000 feet
Type of Gas: .........................................Propane Gas
Input BTUH of Furnace: ................................80,000
From Table 10 , fi nd 5,000 and follow across the row, stop at the 80,000 feet column. At fi rst stage, the manifold pressure listed is 4.2, but at 2nd stage the pressure is
10.0. The listed orifi ce size is 56.
When conversion is complete, verify the manifold pressure and input rate are correct as listed in the Tables. Approved conversion kits are listed below:
• The United States LP / Propane Gas Sea Level and High Altitude Conversion Kit (P/N 904914) is for LP / Propane conversion in the United States at altitudes between zero and 10,000 ft. above sea level. Please follow the instructions provided with the kit.
• The Canadian LP / Propane Gas Sea Level and High Altitude Conversion Kit (P/N 904915) is for LP / Propane conversions in Canada at altitudes between zero and 4,500 ft. above sea level. Please follow the
instructions provided with the kit.
WARNING:
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury or property damage.
Improper servicing could result in dangerous operation, serious injury, death or property damage.
• Before servicing, disconnect all electrical power to furnace.
• When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
• Verify proper operation after servicing.”
AVERTISSEMENT:
RISQUE DE CHOC ÉLECTRIQUE, D’INCENDIE OU D’EXPLOSION
Le non-respect des avertissements de sécurité pourrait entraîner de l’appareil, dommages matériels.
Un entretein incorrect pourrait entraîner un fonctionnement dangereux de l’appareil, des blessures graves, la mort ou des dommages
matériels
• Couper toute alimentation électrique au générateur d’air chaud avant de prodéder aux travaux d’entretein.
• Au moment de l’entretien des commandes, étiquetez tous les fi ls avant de les débrancher. S’assurer de les raccorder correctement.
• S’assurer que l’appareil fonctionne adéquatement aprés l’entretien.
• Electrical connections must be in compliance with all applicable local codes and with the current revision of the National Electric Code (ANSI/NFPA 70).
• For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code (CSA C22.1, and/or local codes).
un fonctionnement dangereux
des blessures graves, la mort ou des
18
Line Voltage Wiring
It is recommended that the line voltage (115 VAC) to the furnace be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the furnace. See Table 2 (page 19).
Page 19
IMPORTANT NOTES:
An electrical disconnect must be installed readily accessible from and located within sight of the furnace. See Figure 14 or the wiring diagram label inside of the control door. Any other wiring methods must be acceptable to authority having jurisdiction.
Proper line voltage polarity must be maintained in order for the control system to operate correctly. Verify the incoming neutral line is connected to the white wire and the incoming “hot” line is connected to the black wire. See Figure 17. The furnace will not operate unless the polarity and ground are properly connected.
If replacing any of the original wires supplied with the furnace, the replacement wire must be copper wiring and have a temperature rating of at least 105°F (40° C). For electrical specifi cations, refer to the furnace nameplate or Table 2.
Grounding
WARNING:
To minimize personal injury, the furnace cabinet must have an uninterrupted or unbroken electrical ground. The controls used in this furnace require an earth ground to operate properly. Acceptable methods include electrical wire or conduit approved for ground service. Do not use gas piping as an electrical ground!
Thermostat / Low Voltage Connections
• The furnace is designed to be controleed by a 24 VAC thermostat. The thermostat’s wiring must comply with the current provisions of the NEC (ANSI/NFPA 70) and with applicable local codes having jurisdiction.
• NORDYNE no longer supports twinning of two stage furnaces. Please contact your furnace distributor for details.
Furnace
Input
(Btuh)
60,000
80,000 100,000 100,000 21 115-60-1 127 103 10.4 14 20 120,000 21 115-60-1 127 103 10.4 14 20 140,000
Thermostat Wire Gauge
Cabinet
Width
(in.)
¼
14
½
17
½
17
½
24
24 55 ft. 25 ft. 22 90 ft. 45 ft. 20 140 ft. 70 ft. 18 225 ft. 110 ft.
Nominal
Electrical
Supply
115-60-1 127 103 7.9 14 15 115-60-1 127 103 7.9 14 15 115-60-1 127 103 7.9 14 15
115-60-1 127 103 13.4 14 30
Maximum Operating
Voltage
2 - wire - Heating 4 or 5 wire - Cooling
Minimum
Operating
Voltage
Recommended Thermostat Wire Length
Maximum
Furnace
Amperes
Minimum
Wire
Gauge
* Time-delay fuses or circuit breakers are required.
Table 2. Wire Length & Voltage Specifi cations
Field Supplied Fused Service
Panel
Field Supplied Disconnect w/in Sight of Furnace
Junction Box (may be int. or ext. to the furnace). These connections can be made in the field supplied disconnect at the furnace.
Maximum
Fuse or Circuit
Breaker Amps*
Black (Hot)
White (Neutral)
Green or Bare
(Ground)
Ground
Field Line Voltage Wiring Factory Line Voltage Wiring
Black
White
Ground
Black
White
Field Supplied
Panel Connector
Figure 14. Line Voltage Field Wiring
Black
White
Ground
19
Page 20
• The thermostat must be installed according to the instructions supplied by the thermostat manufacturer. Low voltage connections (24 VAC) from the thermostat are wired to the terminal strip on the integrated control in the furnace. Recommended minimum wire gauge for thermostat wiring is shown in Table 2.
• The thermostat should be mounted about 5 feet above the fl oor on an inside wall. DO NOT install the thermostat on an outside wall or any other location where its operation may be adversely affected by radiant heat from fi replaces, sunlight, or lighting fi xtures, and convective heat from warm air registers or electrical appliances. Refer to the thermostat manufacturer’s instruction sheet for detailed mounting information.
• Depending on the type of air conditioning unit and thermostat used, both blower applications utilize three basic wiring confi gurations:
Single Stage AC & Single Stage Thermostat
This option does not use the full two-stage control capability of the furnace, but the possibility of timed autostaging is available. See also Autostaging for Single Stage Thermostats:
• Connect the thermostat’s W output to the furnace control boards W1 terminal. This allows the furnace to always run in low output mode. See Figure 15.
• Always connect the thermostat C & R to the furnace control board C & R.
• For cooling, connect the thermostat’s Y signal to the furnace control board’s Y / Y2 terminal.
• Field supplied wires should also connect Y / Y2 & C to the outdoor unit’s Y & C terminals.
ROOM THERMOSTAT
(SINGLE STAGE)
W
G
C
1
Y
DHUM
R
Y C
A/C CONDENSING UNIT
(SINGLE STAGE)
DHUM
HIGH EFFICIENCY
BLOWER MOTOR
CONTROL BOARD
ROOM THERMOSTAT
(TWO - STAGE)
W
W
Y
Y/Y2
Y1
TWO STAGE FURNACE BOARD
R DHUMC
G
1
2
Y C
A/C CONDENSING UNIT
(SINGLE STAGE)
R
G
W1
C
W2
DHUM
HIGH EFFICIENCY
BLOWER MOTOR
CONTROL BOARD
Figure 16. Wiring Confi guration 2
Two-Stage AC & Two-Stage Thermostat
This option uses the full two-stage heating capability of the furnace with a two-stage outdoor unit. See Figure 17.
• Connect the thermostat’s W1 & W2 outputs to the furnace control board’s W1 & W2 terminals.
• Always connect the thermostat C & R to the furnace control board C & R.
• For cooling, connect the thermostat’s Y & Y1 signals to the furnace control board’s Y / Y2 & Y1 terminal’s.
• Field supplied wires should also connect Y / Y2 & Y1 signals to the outdoor unit’s Y & Y1 terminals.
• Connect terminal C to the outdoor unit’s C.
ROOM THERMOSTAT
(TWO STAGE)
W
W
Y
Y
2
1
G
Y/Y2
Y1
TWO STAGE FURNACE BOARD
Figure 17. Wiring Confi guration 3
DHUM
R
C
G
1
2
R
W1
C
W2
Y2 Y1 C
A/C CONDENSING UNIT
(TWO STAGE)
DHUM
HIGH EFFICIENCY
BLOWER MOTOR
CONTROL BOARD
R
G
Y/Y2
W1
C
Y1
TWO STAGE FURNACE BOARD
W2
Figure 15. Wiring Confi guration 1
Single Stage AC & Two-Stage Thermostat
This option uses the full two-stage heating capability of the furnace with a single stage outdoor unit. See Figure 16.
• Connect the thermostat’s W1 & W2 outputs to the furnace control board’s W1 & W2 terminals.
• Always connect the thermostat C & R to the furnace control board C & R.
• For cooling, connect the thermostat’s Y signal to the furnace control board’s Y / Y2 terminal.
• Field supplied wires should also connect Y / Y2 & C to the outdoor unit’s Y & C terminals.
20
Autostaging for Single Stage Thermostats
The Autostaging feature included on all G7 2-stage furnaces make it possible to use a single stage thermostat and still receive some of the benefi ts of 2-stage furnace operation. If Autostage is enabled, the furnace will drop to LOW fi re after initially starting in HIGH fi re. After a period of time (8 or 12 minutes) the furnace will then stage up to HIGH fi re, until the heating load is met. See Figure 15 and the Low Voltage Wiring section (page 19).
Autostaging options are selected using the autostage jumper located near the thermostat terminal block. See Figure 23 (page 33). When the autostage jumper is moved from NONE to SHORT or LONG, the following occurs during a call for heat:
Page 21
1. Setting the Autostage jumper in the SHORT position
signals the control to utilize an 8 minute delay between LOW fi re and HIGH fi re when a call for heat is supplied via 24V signal to W1. This setting is the same as jumping R to W2
2. Setting the Autostage jumper in the LONG position
signals the control to utilize an 12 minute delay between LOW fi re and HIGH fi re when a call for heat is supplied via 24V signal to W1. This setting is the same as jumping W1 to W2
control board together with a fi eld supplied wire. This option causes the blower to run at a reduced CFM for 10 minutes after a call for cooling.
MOTOR
HUMIDISTAT
DHUM
R
CONTROL BOARD
DHUM
R
Figure 18. DHUM Wiring Confi guration
Autostaging for Two-Stage Thermostats
The Autostage setting on the furnace control board (Figure 23, page 33) is disabled when shipped from the factory. This feature will be not used when paired with a two-stage thermostat. The autostage jumper setting (P7) must be kept on NONE to allow the thermostat to adjust stages.
Please note that on certain thermostats, even without the autostage jumper in the LONG position, W1 & W2 may be energized at exactly the same time when a recovery from a set-back begins, the user adjusts the set point, or the system is powered on. If W1 & W2 are energized at exactly the same time for any reason, the control will operate in the autostage LONG (12 minute) mode. If the autostage jumper is in the NONE position and autostaging is activated unexpectedly for any of the reasons listed, it will return to normal, staged operation after the completion of the heating cycle.
Heat Anticipator
Set the heat anticipator according to the instructions supplied by the thermostat manufacturer. To determine the heat anticipator setting:
1. Add the current draw of the system components; or
2. Measure the current fl ow on the thermostat R & W
circuit after the circulating blower motor has started.
Dehumidifi cation Options
Both motor control boards (Figures 21 & 22, page 33) have a DHUM connection that allows the system to increase the amount of humidity that is removed from the circulating air. This is accomplished by reducing the CFM and allowing the cooling coil to become colder. This will only occur when there is a call for cooling. There are many ways that this can be electrically wired.
Blower Speed Confi guration
Two-stage furnaces use high effi ciency circulating air motors that come in two variations and both are controlled differently. The fi xed speed motor control board (Figure 21, page 33) controls the torque and the variable speed motor control board (Figure 22,) controls the airfl ow at a constant CFM. Both boards use the same furnace control board.
Fixed Speed Blowers
NOTE: This section applies only to furnaces with model numbers suffi xed with two numbers, followed by a letter, such as 35C1 or 45D1. If your model has suffi x VA1, VB1, VC1, or VD1, please consult the Variable Speed Blower Application section.
The fi xed speed motor control board (Figure 21) contains a set of dip switches for setting the blower speed. Use pins 1 to 4 to set the blower speed for heating and pins 5 to 8 to set the speed for cooling. To determine the appropriate switch settings for your installation, refer to Table 5 (pages 29 - 30).
For thermostats with a dehumidifi er output, use a fi eld supplied wire to connect the thermostat’s dehumidifi er output to the terminal marked DHUM. The thermostat should be set so that the DHUM output should be high (positive) when dehumidifi cation is needed. See also Dehumidifi cation Options section.
CAUTION:
The terminal marked “Y1_IN” on the variable speed motor control board is not an output to drive the outdoor unit. DO NOT connect Y1_IN on the motor control board to the outdoor unit.
1. If the room thermostat incorporates a humidity sensor
and DHUM output, connect the DHUM on the thermostat to the DHUM terminal on the motor control board. See Figure 18.
2. If using a separate humidistat, connect the DHUM & R
terminals on the humidistat to the DHUM & R terminals on the motor control board. In this option, the DHUM output of the humidistat must be set to be normally open and closed when there is a call for humidifi cation.
3. If a humidistat is not available, it is an acceptable option
to connect the R & DHUM terminals on the motor
Variable Speed Blowers
NOTE: This section applies only to models ending with the suffi xes VA1, VB1, VC1, or VD1.
The variable speed motor control board (Figure 22) has a set of dip switches for setting the base blower speed (CFM). Use pins 1 to 4 to set the blower speed for heating and pins 5 to 8 to set the speed for cooling. To determine the appropriate switch settings for your installation, see Table 6 (page 31) for heating or Table 7 (page 32) for cooling.
21
Page 22
Use fi eld supplied wire to connect the thermostat’s dehumidifi er output to the terminal marked DHUM. The thermostat should be set so that the DHUM output is high (positive) when dehumidifi cation is needed. See also Dehumidifi cation Options section (page 21)
CAUTION:
The variable speed control board is used by other appliances. Many of the terminals and connections on the board are for other appliances and are not used in two­stage applications. The only two-stage fi eld connection to this board is the DHUM terminal, used to reduce blower speed during cooling.
START-UP & ADJUSTMENTS
Pre-Start Check List
Verify the polarity of the connections are correct, the
line voltage power leads are securely connected and the furnace is properly grounded.
Verify that all needed thermostat wires are securely
connected to the correct leads on the terminal strip of the circuit board. See Figures 15 - 17 (page 20).
Verify the gas line service pressure does not exceed
10.0 inches of W.C., and is not less than 4.5 inches W.C. for natural gas. For LP gas the line service pressure must not exceed 14 in. W.C., and must not be less than
11.0 in. W.C.
Verify the roll-out and manual reset switch is closed. If
necessary, press the red button to reset a switch. DO
NOT install a jumper wire across a switch to defeat its function. If a switch reopens on startup, DO NOT
reset the switch without identifying and correcting the fault condition.
Verify the blower door is in place, closing the door switch
in the line voltage circuit.
Verify the gas line has been purged and all connections
are leak free.
Start-up Procedures
Do not perform these steps until all of the checks in the previous steps have been completed:
1. Set the thermostat to the lowest setting.
2. Turn off all electrical power to the furnace.
3. Follow the Operating Instructions on the furnace label.
4. Set the thermostat above room temperature and verify
the Operating Sequence. See page 23.
5. After 5 minutes of operation, set the thermostat below
room temperature and verify steps 11 - 12 of the Operating Sequence (page 24).
the rating plate less 4% for each 1,000 feet. To determine the exact input rate, perform the following procedures:
1. Shut off all other gas fi red appliances.
2. Start and run the furnace in high fi re for at least 3 minutes.
3. Measure the time (in seconds) required for the gas meter to complete one revolution.
4. Convert the time per revolution to cubic feet of gas per hour using Table 8 (page 38).
5. Multiply the gas fl ow rate in cubic feet per hr by the heating value of the gas in Btu per cubic ft to obtain the fi ring rate in Btuh. See example.
Example:
• Time for 1 revolution of a gas meter with a 1 cubic ft dial = 40 seconds.
• From Table 8 read 90 cubic ft gas per hr.
• Local heating value of the gas (obtained from gas supplier) = 1,040 Btu per cubic ft.
• Input rate = 1,040 x 90 = 93,600 Btuh.
6. The manifold pressure must be set to the appropriate value for each installation by a qualifi ed installer, service agency or the gas supplier.
WARNING:
Do not attempt to drill the gas orifi ces. Use only factory supplied orifi ces. Improperly drilled orifi ces may cause fi re, explosion, carbon monoxide poisoning, personal injury or death.
a.) Remove plastic cap from pressure regulator. b.) Obtain the manifold pressure setting required
for this installation by referring to Table 10 (page
39) for Propane or Tables 12 or 13 (page 40) for Natural Gas.
c.) Using an Allen wrench, turn the the LO Input
Adjusting Screw on the LO side of the regulator to adjust the reduced input setting or turn the HI Input Adjusting Screw (Figure 19) on the side of the regulator to adjust the full input setting.
HI Input
Adjusting Screw
Lo Input Adjusting Screw
Verifying & Adjusting Input Rate
The input rate must be verifi ed for each installation to prevent over-fi ring of the furnace. NOTE: The input rate must not exceed the rate shown on the furnace rating plate. At altitudes above 2,000 feet, it must not exceed that on
22
Figure 19. HI & LO Input Adjusting Screws
Page 23
NOTE: Turning the adjusting screw clockwise
increases the pressure and counterclockwise reduces the pressure.
d.) Reinstall plastic cap after adjustment is complete.
Verifying & Adjusting Temperature Rise
Confi rm the temperature rise through the furnace is within the limits specifi ed on the furnace rating plate. Any temperature rise outside the specifi ed limits could result in premature failure of the heat exchanger.
WARNING:
To prevent electric shock, personal injury, or death, disconnect the electric power before performing any maintenance.
1. Place thermometers in the return and supply air stream as close to the furnace as possible. The thermometer on the supply air side must be shielded from direct radiation from the heat exchanger to avoid false readings.
2. Adjust all registers and duct dampers to the desired position and run the furnace in high fi re for 10 to 15 minutes before taking any temperature readings. The temperature rise is the difference between the supply and return air temperatures.
Verifying Operation of the Supply Air Limit Switch
A properly functioning limit switch should turn off the gas valve when the return is blocked (time depends on how well the return air is blocked). The circulating air and combustion blowers should continue to run when the limit switch opens.
1. Check the blower door for secure mounting and that there is power to the furnace.
2. Block the return airfl ow to the furnace by installing a close-off plate in place of or upstream of the fi lter(s).
3. Set the ther mostat above room temperature and observe the Operating Sequence.
4. Remove the close-off immediately after the limit switch opens. If the furnace continues to operate with no return air, set the thermostat below room temperature, shut off the power to the furnace, and replace the limit switch.
OPERATING SEQUENCE
The operating sequences for the heating, cooling, and fan modes are described below. Refer to the fi eld and furnace wiring diagrams: (Figure 14, page 19) , (Figures 15 - 17, page 22), & (Figures 24 - 27, pages 34 - 37).
For typical duct systems, the temperature rise will fall within the limits specifi ed on the rating plate with the blower speed at the factory recommended setting. If the measured temperature rise is outside the specifi ed limits, it may be necessary to change the speed of the blower. NOTE: Lowering the blower speed increases the temperature rise and a higher blower speed will decrease the temperature rise.
The furnace is equipped with a multi-speed motor. Heating, cooling, and fan speed selection is made by moving the switches on the integrated control inside the furnace.
Verifying Burner Operation
CAUTION:
The door over the burners may only be open for inspection purposes only. The door must be installed during unattended operation.
1. Remove the burner compartment door.
2. Set the ther mostat above room temperature and observe the ignition sequence. The burner fl ame should carry over immediately between all burners without lifting off, curling, or fl oating. The fl ames should be blue, without yellow tips.
3. After validating fl ame characteristics, change thermostat setting to below room temperature.
4. Verify burner fl ame is completely extinguished.
5. Replace the burner compartment door.
Heating Cycle
1. The thermostat calls for heat by energizing the W1
terminal with 24VAC.
2. The control checks to see the pressure switch is open. If the switch is closed, the furnace will shut down for 5 minutes before retrying
3. If the pressure switch is open, the control energizes the inducer motor and waits for the pressure switch to close. The pressure switch must close within 12 seconds.
4. The control runs the inducer for a 30 second pre-purge time.
5. The control energizes the igniter output for the appropriate adaptive warm-up time limit.
6. The furnace always ignites the burners in high fi re. If the call for heat is for low rate, the furnace will move down to low fi re after the fl ames stabilize.
7. If the fl ame is proved and ignites the gas, the control de-energizes the igniter. The gas valve and inducer remains energized. The control goes to blower on delay.
8. The control energizes the blower on the selected HEAT speed 30 seconds after the gas valve opened. The gas valve and inducer remain energized.
9. If there is a call for high fi re, the gas valve moves to the high fi re position and the blower speeds are increased. The furnace will remain in high fi re until the demand for heat is satisfi ed.
10. If autostaging is enabled (single stage thermostat) the
demand for heat has lasted more than the selected time, the furnace automatically moves up to high fi r e .
23
Page 24
Autostage times are either SHORT (8 minutes), LONG (12 minutes), or OFF, depending on the Jumper (P7) setting on the furnace control board.
11. When the thermostat demand for heat is satisfi ed, the control de-energizes the gas valve. The inducer output remains on for a 30 second post-purge period.
12. The circulating air blower will continue to run for the selected Blower Off Delay(P5). This may be 60, 90, or 120 seconds depending on the jumper setting on the furnace control board.
Cooling Cycle
1. The thermostat calls for cooling by energizing the Y/Y2
or Y1 terminal with 24VAC.
2. The control energizes the blower in the cooling speed
and sends 24VAC to the contactor in the condensing unit.
3. When the thermostat removes the call for cooling, the
contactor in the outdoor condensing unit is de-energized and the control continues to run the fan for a period of 60 seconds.
Fan Mode
• When the thermostat energizes the G terminal for
continuous fan (without calling for heat or cooling), the indoor fan is energized on the selected FAN speed.
• If a call for cooling occurs during continuous fan, the
blower will switch over to the selected COOL speed.
• If the W ter minal receives a call for heat during continuous
fan, the blower will de energize.
• A call for fan is ignored while in lockout.
• The blower will operate at 50% of the selected high
cooling speed for continuous fan operation.
MAINTENANCE
Proper maintenance is most important to achieve the best performance from a furnace. Follow these instructions for years of safe, trouble free operation.
WARNING:
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury or property damage.
Improper servicing could result in dangerous operation, serious injury, death or property damage.
• Before servicing, disconnect all electrical power to furnace.
• When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
• Verify proper operation after servicing.”
AVERTISSEMENT:
RISQUE DE CHOC ÉLECTRIQUE, D’INCENDIE OU D’EXPLOSION
Le non-respect des avertissements de sécurité pourrait entraîner de l’appareil, dommages matériels.
Un entretein incorrect pourrait entraîner un fonctionnement dangereux de l’appareil, des blessures graves, la mort ou des dommages
matériels
un fonctionnement dangereux
des blessures graves, la mort ou des
24
• Couper toute alimentation électrique au générateur d’air chaud avant de prodéder aux travaux d’entretein.
• Au moment de l’entretien des commandes, étiquetez tous les fi ls avant de les débrancher. S’assurer de les raccorder correctement.
• S’assurer que l’appareil fonctionne adéquatement aprés l’entretien.
• These maintenance instructions are primarily intended to assist qualifi ed technicians experienced in the proper maintenance and operation of this appliance.
• Always reinstall the doors on the furnace after servicing or cleaning/changing the fi lters. Do not operate the furnace without all doors and covers in place.
• Verify that the thermostat is properly installed and is not being affected by drafts or heat from lamps or other appliances.
Page 25
• To achieve the best performance and minimize equipment failure it is recommended that a yearly maintenance checkup be performed. At a minimum, this check should include the following items:
Air Filter(s)
WARNING:
Never operate the furnace without a fi lter in place. Dust and lint in the return air can build up on internal components, resulting in loss of effi ciency, equipment damage, and possible fi re.
Note: Air fi lter(s) are not supplied with the furnace as
shipped from the factory. The installer must provide a high velocity fi lter and rack for a fi lter in the return air duct adjacent to the furnace, or in a return air grill to the furnace. It is recommended that fi lters be 1” or 2” thick and be cleaned or replaced monthly. New or newly renovated homes may require more frequent changing until the construction dust has minimized.
Filters designed to remove smaller particles such as pollen, may require additional maintenance. Filters for side return and bottom return applications are available from most local distributors.
Blower Compartment
Dirt and lint can create excessive loads on the motor resulting in higher than normal operating temperatures and shortened service life. It is recommended that the blower compartment be cleaned of dirt or lint that may have accumulated in the compartment or on the blower and motor as part of the annual inspection.
Cleaning of Burners
If the burners must be cleaned, follow the steps below and see Figure 28 (page 41) for component location.
1. Shut off gas supply to the furnace either at the meter
or at a manual valve in the supply piping.
2. Turn off all power to the furnace and set the thermostat
to its lowest setting.
3. Remove the burner door from the furnace.
4. Turn the gas control knob to the OFF position.
5. Disconnect the wires from the gas valve, igniter, fl ame
sensor, and fl ame rollout switch.
CAUTION:
To prevent damage to the unit or internal components, it is recommended that two wrenches be used when loosening or tightening nuts. Do not over tighten!
6. Using two wrenches, separate the ground-joint union
in the gas supply piping at the furnace.
7. Remove the piping between the gas valve and the
ground-joint union. (If applicable).
8. Remove all screws securing the burner assembly to the furnace.
9. Carefully remove the burner assembly from the furnace.
DO NOT DAMAGE THE IGNITER WHILE REMOVING THE BURNER ASSEMBLY.
10. Inspect the burners for accumulated dust or debris.
If necessary carefully clean them with a soft wire brush and a vacuum cleaner. DO NOT DAMAGE THE
IGNITER WHILE CLEANING THE BURNER.
11. Replace all the parts in reverse order that they were
removed.
12. Follow the lighting instructions found on the furnace
door to return the furnace to operation. Verify proper operation after servicing.
Cleaning Of Flue Passages
If the fl ue passages must be cleaned, follow the steps below. See Figure 28 for component location.
1. Shut off the gas supply to the furnace at the meter or at the manual valve in the gas supply piping.
2. Turn off all power to the furnace and set the thermostat to the lowest temperature setting.
3. Remove the blower door from the furnace.
4. Turn the gas control switch to the OFF position.
5. Disconnect the wires from the gas valve, fl ame sensor, inducer, fl ame roll-out switch, limit switch, pressure switch and igniter.
6. Remove the silicone rubber tube from the inducer.
7. Using two wrenches, separate the ground-joint union in the gas supply piping at the furnace.
8. Remove the piping between the gas valve and the ground-joint union. (If applicable).
9. Remove all screws securing the burner assembly to the furnace.
10. Carefully remove the burner assembly from the
furnace. DO NOT DAMAGE THE IGNITER WHILE
REMOVING THE BURNER ASSEMBLY.
11. *TA models - Remove all screws securing the inducer
assembly to the vent pipe running out of the furnace
*TK models - Remove all screws securing the
combustion air tube assembly to the vent pipe running out of the furnace.
12. Remove all screws securing the inducer assembly to
the collector pan.
13. *TA models - Carefully remove the inducer assembly
from the furnace.
*TK models - Carefully remove the inducer assembly
and combustion tube assembly from the furnace. DO
NOT BREAK THE SEALS AT EACH END OF THE COMBUSTION AIR TUBE.
14. Remove all screws securing the collector pan to the
furnace.
15. Remove the collector pan and gasket from the furnace.
25
Page 26
16. Attach a round wire brush to a length of high grade stainless steel cable. Attach the other end of the cable to a variable speed reversible drill. Slowly insert and rotate the cable into the top portion of the heat exchanger. Operate the drill alternating between forward and reverse, working the cable in and out several times to obtain suffi cient cleaning. Repeat this sequence for each heat exchanger tube.
17. Remove all loosened debris from the heat exchanger tubes using a vacuum cleaner.
18. Using a bright light, check the condition of the upper and lower sections of the heat exchanger tubes.
19. Inspect the burners for accumulated dust or debris. If burners must be cleaned, see Cleaning of Burners
20. Replace all the parts in reverse order that they were removed.
21. Check gaskets for damage. Replace if needed.
22. Follow the lighting instructions found on the furnace door to return the furnace to operation. Verify proper operation after servicing.
Heat Exchanger & Burner Maintenance
The furnace should operate for many years without soot buildup in the fl ue passageways, however, the fl ue, vent system, and the burners should be inspected and cleaned (if required) by a qualifi ed service technician annually to ensure continued safe operation. Pay attention to any deterioration from corrosion or other sources.
DESCRIPTION OF COMPONENTS
The descriptions below are various functional components that affect the operation and shutting down of this furnace. Some of these components and their locations are shown in Figure 28 (page 41). If any component of the furnace must be replaced, use only factory authorized replacement parts specifi ed in the Replacement Parts List provided online.
Blower Limit Switch: Prevents operation when blower is not operational.
Flame Sensor: Verifi es when a fl ame has carried over from the igniter to the opposite end burner. If no fl ame is detected, the furnace will shut down within 4 seconds.
Flame Roll-Out Switch: Verifi es that the burner fl ames are drawn into the heat exchanger tubes. If the burner fl ames are not properly drawn into the heat exchanger, the fl ame roll-out switch will close the gas valve and initiate the shutdown cycle.
Gas Valve: Controls the fl ow of gas to the burners. When the gas valve is energized it automatically opens and regulates the gas pressure in the manifold.
Inducer Assembly: Vents products of combustion to the outside.
Pressure Switch: Verifi es that the inducer is drawing the combustion gases through the heat exchanger. The pressure switch prevents furnace operation with excessive fl ue blockage or improper inducer operation.
WARNING:
Holes in the vent pipe or heat exchanger can cause combustion products to enter the home. Replace the vent pipe or heat exchanger if leaks are found. Failure to prevent the circulation of combustion products into the living space can create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death.
Lubrication
The bearings in the blower motor and inducer blower used in these furnaces are pre-lubricated and sealed by the manufacturer. No further oiling of the bearings is required for the life of the motor.
Vent System
Check the vent pipe and/or chimney to ensure that it is not corroded or blocked by debris. Any corroded section of vent pipe must be replaced, and any obstruction or blockage must be removed prior to operating the furnace.
Supply Air Limit Switch: Prevents the air temperature leaving the furnace from exceeding the maximum allowable outlet air temperature.
26
Page 27
TROUBLESHOOTING
If the furnace fails to operate check the following:
• Is the thermostat operating properly?
• Are the blower compartment door(s) in place?
• Is the furnace disconnect closed?
• Has the circuit breaker tripped or the control board fuse burned open?
• Is the gas turned on?
• Are any manual reset switches open?
• Is the fi lter dirty or plugged?
• Is the fl ame sensor coated? (Remove and clean with steel wool. Do not use emery cloth or sandpaper!)
• Are all the LED’s on the furnace and motor control boards constantly ON? If not, refer to Tables 3 - 4 to determine fault condition.
Diagnostic Description Green LED Red LED
Control Fault (No Power) Off Off
L1/Neutral Polarity Fault Flash Flash
1 Hour Lockout Alternating Flash
Normal Operation On On
Pressure Switch Closed Fault On Flash
Pressure Switch Open Fault Flash On
Open Limit Switch Fault Flash Off
Motor Fault On Off
Diagnostic Description Yellow LED
Low Flame Sensor Signal Continuous Flash
Flame Present On
Table 3. Furnace Control Board Fault Conditions
IMPORTANT NOTE: The furnace will lock out after 5 failed attempts for ignition and will try again every hour if the call for heat remains.
• If the Inducer Blower is operating, and items above have been verifi ed, check the Blower Limit Switch (Figure 28, page 41) and reset if necessary.
• If the furnace operates when the Blower Limit Switch is reset, contact a qualifi ed service technician to identify and repair the problem.
• If the furnace still doesn’t operate, check the Flame Roll-out Switches (Figure 28) and reset if necessary.
• If the furnace operates when the Flame Rollout Switch is reset, contact a qualifi ed service technician to identify and repair the problem.
Fixed
Speed
Furnaces
Variable
Speed
Furnaces
Diagnostic
Description
Control Fault (No Power) Off Off
Normal Operation On On
Motor Fault On Flash
Twin Fault (no motor fault) Flash On
Communications Fault Flash Flash
Control Fault (No Power) Off Off
Normal Operation On On
Motor Fault On Flash
Communications Fault Flash Flash
Green
LED
Table 4. Motor Control Board Fault Conditions
Red LED
27
Page 28
FIGURES & TABLES
*TA 80+ Upfl ow / Horizontal Furnace
Cabinet
Size
‘A’ Cabinet 14 1/4 10 3/4 12 5/8 12 7/8
‘B’ Cabinet 17 1/2 11 3/4 15 7/8 16 1/8
‘C’ Cabinet 21 14 19 3/8 19 7/8
‘D’ Cabinet 24 1/2 15 1/4 22 7/8 23 1/8
NOTE: Dimensions shown in Inches.
Dim.
-A-
Dim.
-B-
25 3/8
Electric
(Ø 7/8)
4 Knockouts
(both sides)
1 1/4
23
LEFT SIDE
Dim.
-C-
Dim.
-D-
(1 5/8 X 3 1/2)
23
15
1
Gas
TOP VIEW
C
FLANGES
23
Accepts 4” Type B Vent Pipe
A
19
B
FRONT VIEW
T-stat
(Ø 7/8)
Electric (Ø 7/8)
29 1/2
22 1/2
BOTTOM VIEW
Front Brace
Bottom
Panel
23 1/2
Gas
(1 5/8 X 3 1/2 X 45°)
28
RIGHT SIDE
D
22 1/4
25
21 3/4
34 1/2
22 3/4
*TK 80+ Downfl ow Furnace
Cabinet
e
Siz
‘A’ Cabinet 14 1/4 10 3/4 12 5/8 12 7/8
‘B’ Cabinet 17 1/2 11 3/4 15 7/8 16 1/8
‘C’ Cabinet 21 14 19 3/8 19 5/8
‘D’ Cabinet 24 1/2 15 1/4 22 7/8 23 1/8
NOTE: Dimensions shown in Inches.
Dim.
-A-
Dim.
-B-
34 1/2
(1 5/8 X 3 1/2)
Dim.
-C-
Electric
(Ø 7/8)
Gas
25 3/8
28
LEFT SIDE
Dim.
-D-
22 1/2
7
TOP VIEW
C
FLANGES
23
Accepts 4” Type B Vent Pipe
A
19
B
FRONT VIEW
T-stat
(Ø 7/8)
Electric (Ø 7/8)
29 1/2
BOTTOM VIEW
18 5/8
(1 5/8 X 3 1/2 X 45°)
22 1/2
7
D
Front
Brace
22 1/4
25
Gas
RIGHT SIDE
28
Figure 20. Furnace Dimensions
Page 29
AIRFLOW DATA
*TA / *TK FURNACES with FIXED SPEED BLOWERS
Model Number
&
Heating Input
(Btuh)
*TA / TK - 060C - 23A1
(60,000)
*TA / TK - 080C - 24B1
(80,000)
*TA - 100C - 24B1
(100,000)
Motor Switch Settings
(0 = OFF, 1 = ON)
1/5 2/6 3/7 4/8 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise
0000 1000
01006007455580510
110070563670666357060074
001077557740607056366567
10109004987051835538005676558730616956466067
01109504792048890508555282554795567655873061
11101,000 44 970 46 940 47 910 49 880 51 850 52 820 54 790 56
00011,075 41 1,045 43 1,015 44 985 45 960 46 925 48 900 49 870 51
10011,110 40 1,080 41 1,055 42 1,025 43 1,000 44 975 46 945 47 920 48
01011,170 38 1,140 39 1,115 40 1,090 41 1,060 42 1,035 43 1,010 44 985 45
11011,210 37 1,185 38 1,160 38 1,130 39 1,105 40 1,080 41 1,055 42 1,025 43
00111,520 29 1,225 36 1,200 37 1,175 38 1,150 39 1,120 40 1,095 41 1,070 42
10111,305 34 1,280 35 1,255 35 1,230 36 1,205 37 1,180 38 1,155 38 1,130 39
01111,350 33 1,230 36 1,305 34 1,285 35 1,260 35 1,240 36 1,215 37 1,195 37 11111,440 31 1,400 32 1,365 33 1,230 36 1,295 36 1,255 35 1,220 36 1,185 38
0000 1000
0100
110072582
001081073
1010940638906784570795757507970085
01109906094563905658606982072775767358169086
11101,055 56 1,015 58 970 61 930 64 890 67 845 70 805 74 760 78
00011,135 52 1,095 54 1,055 56 1,010 59 960 62 930 64 890 67 850 70
10011,185 50 1,145 52 1,105 54 1,065 56 1,030 58 990 60 950 62 910 65
01011,250 47 1,210 49 1,170 51 1,135 52 1,095 54 1,055 56 1,020 58 980 60
11011,290 46 1,255 47 1,220 49 1,180 50 1,145 52 1,110 53 1,075 55 1,040 57
00111,315 45 1,275 46 1,240 48 1,200 49 1,160 51 1,120 53 1,085 55 1,045 57
10111,350 44 1,315 45 1,280 46 1,245 48 1,205 49 1,170 51 1,135 52 1,100 54
01111,390 43 1,350 44 1,315 45 1,275 46 1,240 48 1,200 49 1,160 51 1,125 53 11111,420 42 1,380 43 1,345 44 1,310 45 1,270 47 1,235 48 1,200 49 1,160 51
0000 1000
0100
1100
0010
101094079890838458879593750 700 655 605
0110990759457890582860868209077596735 690
11101,055 70 1,015 73 970 76 930 80 890 83 845 88 805 92 760 97
00011,135 65 1,095 68 1,055 70 1,010 73 790 94 930 80 890 83 850 87
10011,185 63 1,145 65 1,105 67 1,065 70 1,030 72 990 75 950 78 910 81
01011,250 59 1,210 61 1,170 63 1,135 65 1,095 68 1,055 70 1,020 73 980 76
11011,290 57 1,255 59 1,220 61 1,180 63 1,145 65 1,110 67 1,075 69 1,040 71
00111,315 56 1,275 58 1,240 60 1,200 62 1,160 64 1,120 66 1,085 68 1,045 71
10111,350 55 1,315 56 1,280 58 1,245 59 1,205 61 1,170 63 1,135 65 1,100 67
01111,390 53 1,350 55 1,315 56 1,275 58 1,240 60 1,200 62 1,160 64 1,125 66 11111,420 52 1,380 54 1,345 55 1,310 57 1,270 58 1,235 60 1,200 62 1,160 64
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
NOTES:
1. Motor Switch Settings are for heating speeds using HEAT. switches 1, 2, 3, & 4 and cooling speeds using COOL switches 5, 6, 7, & 8.
2. Two openings are recommended for airfl ows above 1,600 CFM if the fi lter(s) is (are) adjacent to the furnace.
3. Data is shown without fi lter
4. Temperature rises in the table are approximate. Actual temperature rises may vary.
5. Temperature rises that are shaded in grey are for reference only. These conditions are not recommended.
6. When in low stage, the circulating airfl ow (2-stage furnaces only) is 70% of the tables high value.
External Static Pressure (in.W.C.)
Table 5. Heating / Cooling Airfl ows (CFM) & Temperature Rises (° F)
29
Page 30
*TA / *TK FURNACES with FIXED SPEED BLOWERS
Model Number
&
Heating Input
(Btuh)
*TA / TK - 100C - 35C1
(100,000)
*TA / TK - 120C - 35C1
(120,000)
*TA / TK - 140C - 45D1
(140,000)
Motor Switch Settings
(0 = OFF, 1 = ON)
1/5 2/6 3/7 4/8 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise
0 0 0 0 1,125 66 1,040 71 960 77
1 0 0 0 1,205 61 1,120 66 1,040 71 960 77
0 1 0 0 1,305 57 1,225 60 1,150 64 1,070 69 995 74 915 81
1 1 0 0 1,430 52 1,350 55 1,270 58 1,190 62 1,110 67 1,030 72 950 78 865 86
0 0 1 0 1,525 49 1,450 51 1,375 54 1,300 57 1,225 60 1,150 64 1,075 69 1,000 74
1 0 1 0 1,620 46 1,540 48 1,465 51 1,390 53 1,315 56 1,240 60 1,165 64 1,090 68
0 1 1 0 1,695 44 1,620 46 1,545 48 1,465 51 1,390 53 1,315 56 1,235 60 1,160 64
1 1 1 0 1,770 42 1,700 44 1,630 45 1,555 48 1,485 50 1,410 53 1,340 55 1,265 59
0 0 0 1 1,875 40 1,805 41 1,730 43 1,655 45 1,580 47 1,510 49 1,435 52 1,340 55
1 0 0 1 1,905 39 1,840 40 1,775 42 1,710 43 1,640 45 1,575 47 1,510 49 1,445 51
0 1 0 1 1,980 37 1,910 39 1,845 40 1,780 42 1,715 43 1,650 45 1,580 47 1,515 49
1 1 0 1 2,025 37 1,960 38 1,895 39 1,830 40 1,765 42 1,700 44 1,635 45 1,570 47
0 0 1 1 2,085 36 2,025 37 1,960 38 1,900 39 1,840 40 1,775 42 1,715 43 1,655 45
1 0 1 1 2,135 35 2,070 36 2,010 37 1,945 38 1,880 39 1,815 41 1,750 42 1,685 44
0 1 1 1 2,200 34 2,145 35 2,090 35 2,035 36 1,980 37 1,925 38 1,870 40 1,820 41
1 1 1 1 2,280 32 2,225 27 2,170 34 2,115 35 2,065 22 2,010 37 1,955 38 1,900 39
0 0 0 0 1,125 79 1,040
1 0 0 0 1,205 74 1,120 79 1,040 85
0 1 0 0 1,305 68 1,225 73 1,150 77 1,070 83
1 1 0 0 1,430 62 1,350 66 1,270 70 1,190 75 1,110 80 1,030 86
0 0 1 0 1,525 58 1,450 61 1,375 65 1,300 68 1,225 73 1,150 77 1,075 83 1,000 89
1 0 1 0 1,620 55 1,540 58 1,465 61 1,390 64 1,315 68 1,240 72 1,165 76 1,090 82
0 1 1 0 1,695 52 1,620 55 1,545 58 1,465 61 1,390 64 1,315 68 1,235 72 1,160 77
1 1 1 0 1,770 50 1,700 52 1,630 55 1,555 57 1,485 60 1,410 63 1,340 66 1,265 70
0 0 0 1 1,875 47 1,805 49 1,730 51 1,655 54 1,580 56 1,510 59 1,435 62 1,340 66
1 0 0 1 1,905 47 1,840 48 1,775 50 1,710 52 1,640 54 1,575 56 1,510 59 1,445 62
0 1 0 1 1,980 45 1,910 47 1,845 48 1,780 50 1,715 52 1,650 54 1,580 56 1,515 59
1 1 0 1 2,025 44 1,960 45 1,895 47 1,830 49 1,765 50 1,700 52 1,635 54 1,570 57
0 0 1 1 2,085 43 2,025 44 1,960 45 1,900 47 1,840 48 1,775 50 1,715 52 1,655 54
1 0 1 1 2,135 42 2,070 43 2,010 44 1,945 46 1,880 47 1,815 49 1,750 51 1,685 53
0 1 1 1 2,200 40 2,145 41 2,090 43 2,035 44 1,980 45 1,925 46 1,870 48 1,820 49
1 1 1 1 2,280 39 2,225 40 2,170 41 2,115 42 2,065 43 2,010 44 1,955 45 1,900 47
0 0 0 0 1,395 74 1,350 77 1,305 79 1,260 82 1,210 86 1,165 89
1 0 0 0 1,465 71 1,420 73 1,375 75 1,330 78 1,290 80 1,245 83 1,200 86
0 1 0 0 1,555 67 1,510 69 1,470 71 1,425 73 1,380 75 1,340 77 1,295 80 1,250 83
1 1 0 0 1,625 64 1,585 65 1,540 67 1,500 69 1,460 71 1,415 73 1,375 75 1,335 78
0 0 1 0 1,690 61 1,650 63 1,610 64 1,570 66 1,530 68 1,485 70 1,445 72 1,405 74
1 0 1 0 1,760 59 1,715 60 1,670 62 1,625 64 1,575 66 1,530 68 1,485 70 1,440 72
0 1 1 0 1,835 57 1,790 58 1,745 59 1,695 61 1,650 63 1,605 65 1,555 67 1,510 69
1 1 1 0 1,885 55 1,840 56 1,790 58 1,745 59 1,700 61 1,655 63 1,610 64 1,565 66
0 0 0 1 1,945 53 1,900 55 1,850 56 1,805 57 1,760 59 1,710 61 1,665 62 1,620 64
1 0 0 1 1,950 53 1,905 54 1,860 56 1,820 57 1,775 58 1,735 60 1,690 61 1,650 63
0 1 0 1 2,075 50 2,030 51 1,990 52 1,945 53 1,900 55 1,855 56 1,810 57 1,770 59
1 1 0 1 2,125 49 2,085 50 2,040 51 2,000 52 1,955 53 1,910 54 1,870 55 1,825 57
0 0 1 1 2,170 48 2,130 49 2,090 50 2,045 51 2,005 52 1,965 53 1,925 54 1,880 55
1 0 1 1 2,215 47 2,180 48 2,140 48 2,105 49 2,070 50 2,035 51 2,000 52 1,965 53
0 1 1 1 2,225 47 2,165 48 2,100 49 2,040 51
1111 2,170 48 2,120 49 2,065 50
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
External Static Pressure (in.W.C.)
NOTES:
1. Motor Switch Settings are for heating speeds using HEAT switches 1, 2, 3, & 4 and cooling speeds using COOL switches 5, 6, 7, & 8.
2. Two openings are recommended for airfl ows above 1,600 CFM if the fi lter(s) is (are) adjacent to the furnace.
3. Data is shown without fi lter.
4. Temperature rises in the table are approximate. Actual temperature rises may vary.
5. Temperature rises that are shaded in grey are for reference only. These conditions are not recommended.
6. When in low stage, the circulating airfl ow is 70% of the tables high value. (2-stage furnaces only)
30
Table 5. Continued
Page 31
“A” CABINET
*TA / TK FURNACES with VARIABLE SPEED BLOWERS
Switch Settings For Heat
(0 = OFF, 1 = ON)
1 2 3 4 CFM Temp Rise (° F)
0 0 0 0 640 69
0 0 0 1 720 62
0 0 1 0 800 56
0 0 1 1 880 51
0 1 0 0 960 46
0 1 0 1 1,040 43
0 1 1 0 1,120 40
0 1 1 1 1,200 37
*TA / TK - 060C - VA1
Input (BTU) 60,000
“B” CABINET
“C” CABINET
Switch Settings For Heat
(0 = OFF, 1 = ON)
1 2 3 4 CFM Temp Rise (°F) CFM Temp Rise (° F)
1 0 0 0 1,000 59 1,000 74
1 0 0 1 1,100 54 1,100 67
1 0 1 0 1,200 49 1,200 62
1 0 1 1 1,300 46 1,300 57
1 1 0 0 1,400 42 1,400 53
1 1 0 1 1,500 40 1,500 49
1 1 1 0 1,600 37 1,600 46
1 1 1 1 1,700 35 1,700 44
Switch Settings For Heat
(0 = OFF, 1 = ON)
1 2 3 4 CFM Temp Rise (° F) CFM Temp Rise (° F)
# 0 0 0 1,000 74 1,000 89
# 0 0 1 1,115 66 1,115 80
# 0 1 0 1,230 60 1,230 72
# 0 1 1 1,345 55 1,345 66
# 1 0 0 1,460 51 1,460 61
# 1 0 1 1,575 47 1,575 56
# 1 1 0 1,690 44 1,690 53
# 1 1 1 1,805 41 1,805 49
*TA / TK - 080C - VB1
Input (BTU) 80,000
*TA / TK - 100C - VC1
Input (BTU) 100,000
*TA - 100C - VB1
Input (BTU) 100,000
*TA / TK - 120C - VC1
Input (BTU) 120,000
Switch Settings For Heat
(0 = OFF, 1 = ON)
1 2 3 4 CFM Temp Rise (° F)
# 0 0 0 1,500 69
# 0 0 1 1,615 64
“D” CABINET
# Switch not used - can be 0 or 1
1. Two openings are recommended for airfl ows above 1,600 CFM if the fi lter(s) is (are) adjacent to the furnace.
2. Temperature rises in the table are approximate. Actual temperature rises may vary.
3. Temperature rises shaded in grey are for reference only. These conditions are not recommended.
# 0 1 0 1,730 60
# 0 1 1 1,845 56
# 1 0 0 1,960 53
# 1 0 1 2,075 50
# 1 1 0 2,190 47
# 1 1 1 2,305 45
Table 6. Nominal Heating Airfl ows (CFM) & Temperature Rise (° F)
*TA / TK - 140C - VD1
Input (BTU) 140,000
NOTES:
31
Page 32
*TA / TK FURNACES with VARIABLE SPEED BLOWERS
“A” CABINET
Switch Settings
(0 = OFF, 1 = ON)
HEAT COOL
1-4 5678LOWHIGH
0 0000 360 525
0 0001 400 580
0 0010 440 635
0 0011 475 690
0 0100 515 745
0 0101 550 800
0 0 1 1 0 590 855
0 0 1 1 1 630 910
0 1 0 0 0 665 965
0 1001 7051,020
0 1 0 1 0 740 1,075
0 1 0 1 1 780 1,130
0 1 1 0 0 820 1,185
0 1 1 0 1 855 1,240
0 1 1 1 0 895 1,295
0 1 1 1 1 930 1,350
CFM
Nominal A/C
& HP Capacity
2 TON
2.5 TON
3 TON
“B” CABINET
Switch Settings
(0 = OFF, 1 = ON)
HEAT COOL
1-4 5678LOWHIGH
1 0000 485 700
1 0001 525 760
1.5 TON
1 0010 565 820
1 0011 605 880
1 0100 650 940
1 0101 6901,000
1 0110 7301,060
1 0111 7751,120
1 1000 8151,180
1 1001 8551,240
1 1010 8951,300
1 1011 9401,360
1 1100 9801,420
1 11011,020 1,480
1 11101,065 1,540
1 11111,105 1,600
CFM
Nominal A/C
& HP Capacity
2 TON
2.5 TON
3 TON
3.5 TON
“C” CABINET
Switch Settings
(0 = OFF, 1 = ON)
HEAT COOL
1-4 5678LOWHIGH
# 0000 7051,025
# 0001 7501,090
# 0010 7951,155
# 0011 8401,220
# 0100 8851,285
# 0101 9301,350
# 0110 9751,415
# 01111,020 1,480
# 10001,065 1,545
# 10011,110 1,610
# 10101,155 1,675
# 10111,200 1,740
# 11001,245 1,805
# 11011,290 1,870
# 11101,335 1,935
# 11111,380 2,000
# Switch not used - can be 0 or 1
CFM
Nominal A/C
& HP Capacity
3.5 TON
4 TON
5 TON
“D” CABINET
Switch Settings
(0 = OFF, 1 = ON)
HEAT COOL
1-4 5678LOWHIGH
# 0000 9651,400
# 0001 9951,440
2.5 TON
3 TON
# 00101,020 1,480
# 00111,050 1,520
# 01001,075 1,560
# 01011,105 1,600
# 01101,130 1,640
# 01111,160 1,680
# 10001,185 1,720
# 10011,215 1,760
# 10101,240 1,800
# 10111,270 1,840
# 11001,295 1,880
# 11011,325 1,920
# 11101,350 1,960
# 11111,380 2,000
# Switch not used - can be 0 or 1
CFM
Nominal A/C & HP
Capacity
3.5 TON
4 TON
5 TON
Table 7. Nominal Cooling / Heat Pump Airfl ows (CFM) for Variable Speed Furnaces
32
Page 33
ELECTRICAL INFORMATION
NOT USED
RCY1
CONNECTION TO
DHUM
TWIN
FAN SPEED
1 2 345 6 7
OFF ON
HEAT
THERMOSTAT
COOL
TERMINAL TO
CONNECTION
TWIN FURNACES
8
FURNACE CONTROL
RED
STATUS
GREEN
BOARD
NOT USED
Figure 21. Two-Stage Fixed Speed
Motor Control Board
W1
W2
G
AUTO
STAGE
NONE
SHORT
LONG
Y/Y2
Y1
THERMOSTAT CONNECTIONS
C
EXPANSION
PORT
MOTOR WIRE
HARNESS
FOR WIRING TO THE
MOTOR CONTROL
BOARD
R
EXPANSION
PORT
GREEN
RED
W1
W_OUT
Y/Y2_OUT
Y1_OUT
OUTPUT TERMINALS
H_OUT
OUTPUT
HUMIDIFIER
R
C
FIELD USE
EXPANSION PORT
CONNECTION TO
FURNACE CONTROL
NOT FOR
BOARD
RED
STATUS LIGHTS
CONNECTION TO
IQ THERMOSTAT
(IF APPLICABLE)
RED
GREEN
1 2 345 6 7
OFF ON
MOTOR WIRING
FAN SPEED
COOL
HEAT
HARNESS
L2-OUT
L1-IN
L1-OUT
OUTPUT
DEHUMIDIFIER
DHUM_IN
8
Y1_IN
SENSOR
GROUND
L2-IN
FOR USE
WITH IQ
OUTDOOR
UNITS
INPUT TERMINALS
10
12
11
7
4
1
INPUTS
8
5
293
6
BLOWER
FUSE
14325
EAC
XMFR
LINE
LINE
HUM
Figure 23. Two-Stage Furnace Control Board
YELLOW
(FLAME)
OFF
DELAY
NEUTRALS
XMFR-N
60
90 120 180
LINE- N
LINE- N
STATUS
Figure 22. Two-Stage Variable Speed
Motor Control Board
33
Page 34
112233445566778899
RED
Green LED Red LED
Control Fault (No Power) Off Off
L1 / Neutral Polarity Fault Flash Flash
1 Hour Lockout
Normal Operation On On
Pressure Switch Closed Fault On Flash
Pressure Switch Open Fault Flash On
Open Limit Switch Fault Flash Off
Low Flame Sensor Signal
Flame Present
Diagnostic Description
FAULT CONDITIONS
Diagnostic Description
Yellow LED
Continuous Flash
On
Alternating Flash
Motor Fault On Off
RED
RED
PAR T O F
123 123
MOTOR
BLUE
MOTOR
TORQUE
HP
PWM
NONE
NONE
MODE
SPEED
COMMON
R
C
W
TX
RX
GND
R
C
W
TX
RX
W
GND
WHITE
BLACK
COOL
FAN SPEED
BLUE
HEAT
DEHUM
R C Y1 TWIN
MOTOR CHOKE
MOTORS ONLY)
(ON 3/4 AND 1HP
12345
BROWN
RED
ORANGE
YELLOW
BLACKBLACK
GREEN
BLUE
6
BLACK
WHITE
0409
7109160
¢710916+¤
LIMIT
BLOWER
W
BLACK
VIOLET
WHITE
ORANGE
PRESSURE
PRESSURE
RX TX COM C R
VIOLET
SWITCH
VIOLET
SWITCH
RCY/Y2 W2GW1Y1
6
9
12
11
10
GREEN
3
8
5
2
4
1
7
BROWN
C
GAS
VALVE
If any of the origInal wire as supplied with the
furnace must be replaced, it must be replaced
with wiring material having a temperature
rating of at least 105° C.
Use copper conductors only.
BLACK
WHITE
120 V
24 V
BLK W/ WHITE STRIPES
WHITE W/ BLK STRIPES
1234
1234
This wiring diagram shows connections and
termination required for the blower kit only.
Use in addition to the wiring diagram for the
furnace.
SWITCH
PRESSURE
LOW
WIRING DIAGRAM
For 80+ and 90+ 2-Stage Fixed Speed Upflow Furnaces
Refer to the Installation Instructions
provided with the kit for the proper
heating and cooling speeds for your
application.
MODELS)
(ON SELECT
CONDENSATE
ORANGE
PRESSURE
HIGH
ORANGE
SWITCH
YELLOW
BROWN
LO
BLWR OFF
RED
HI
LIMIT
BLOWER
XMFR-N
DELAY
BLUE
FLAME SENSOR
BROWN
RED
12345
LINE- N
LINE- N
14325
HUM
LINE
LINE
XMFR
EAC
WHITE BLACK
VENT LIMIT
(ON SELECT
BLUEBLUE
FLAME
ROLL-OUT
SUPPLY
AIR LIMIT
ORANGE
YELLOW
MODELS)
WHITE
GREEN
BLUE
6
BLACK
BLACK
BLUE BLUE
BLACK
WHITE
DOOR
SWITCH
GREEN
GROUND
BLACK 120V
WHITE (NEUTRAL)
BLACK WHITE
RED
BLACK
BLACK
INDUCER
1 1
C
2 2
H
IGNITOR
L
123
123
LEGEND:
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
Figure 24. Wiring Diagram for Two-Stage, Fixed Speed Upfl ow Furnaces
34
Page 35
112233445566778899
RED
Green LED Red LED
Control Fault (No Power) Off Off
L1 / Neutral Polarity Fault Flash Flash
1 Hour Lockout
Normal Operation On On
Pressure Switch Closed Fault On Flash
Pressure Switch Open Fault Flash On
Open Limit Switch Fault Flash Off
Low Flame Sensor Signal
Flame Present
Diagnostic Description
FAULT CONDITIONS
Diagnostic Description
Yellow LED
Continuous Flash
On
Alternating Flash
Motor Fault On Off
RED
PART OF
RED
MOTOR
123 123
WHITE
BLACK
8
8 7 6 5 4 3
MOTOR
TORQU E
2 1
ORANGE
7 6
WHITE
5
BLACK
4
RED
3 2
YELLOW
1
LIMIT
BLOWER
LIMIT
BLOWER DECK
7109170
BLUE
¢7109171¤
COOL
HEAT
0409
HP
PWM
NONE
NONE
MODE
SPEED
COMMON
R
C
W
TX
RX
GND
R
C
W
TX
RX
W
GND
FAN SPEED
R C Y1 TWINDEHUM
MOTOR CHOKE
(ON 3/4 AND 1HP
MODELS ONLY)
BLACK BLACK
LIMIT
BLOWER
BLACK
WHITE
BLUE
WHITE
ORANGE
YELLOW
RED
BLACK
ORANGE
RED
BLACK
WHITE
BLUE
BLUE
BLACK
WHITE
YELLOW
If any of the origInal wire as supplied with the
furnace must be replaced, it must be replaced
with wiring material having a temperature
rating of at least 105° C.
Use copper conductors only.
This wiring diagram shows connections and
termination required for the blower kit only.
Use in addition to the wiring diagram for the
furnace.
WIRING DIAGRAM
Refer to the Installation Instructions
provided with the kit for the proper
heating and cooling speeds for your
For 80+ and 90+ 2-Stage Fixed Speed Downflow Furnaces
application.
WHITE
WHITE W/ BLK STRIPES
120 V
24 V
BLACK
BLK W/ WHITE STRIPES
LOW
HIGH
1234
1234
SWITCH
PRESSURE
SWITCH
PRESSURE
BLACK
WHITE
W RX TX COM C R
RCY/Y2 W2GW1Y1
ORANGE
ORANGE
VIOLET
VIOLET
9
12
8
11
7
10
GREEN
GAS
BLACK
LINE- N
LINE- N
XMFR-N
DELAY
BLWR OFF
BLUE
14325
HUM
LINE
LINE
XMFR
EAC
WHITE
BLACK
MODELS)
VENT LIMIT
(ON SELECT
BLUE
FLAME
ROLL-OUT
BLUE
SUPPLY
AIR LIMIT
WHITE
BLACK
BLACK
WHITE
DOOR
SWITCH
GROUND
(NEUTRAL)
BLACK 120V
GREEN
3
6
5
2
4
1
RED
YELLOW
BROWN
BROWN
FLAME SENSOR
C
HI
LO
VALVE
BLACK WHITE
RED
BLACK
BLACK
INDUCER
1
2
1
2
H
C
IGNITOR
123
123
L
LEGEND:
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
Figure 25. Wiring Diagram for Two-Stage, Fixed Speed Downfl ow Furnaces
35
Page 36
FLAME
ROLL-OUT
SUPPLY
AIR LIMIT
PRESSURE
SWITCH
PRESSURE
SWITCH
PRESSURE
SWITCH
PRESSURE
SWITCH
FLAME SENSOR
GAS
VALVE
HI
LO
C
11
4
1
8
7
10
5
2
9
3
12
6
LINE- N
XMFR-N
LINE
LINE
XMFR
EAC
HUM
LINE- N
14325
R
C
TX
RX
W
COM
IGNITOR
DOOR
SWITCH
RCY/Y2 W2GW1Y1
1
2
1
2
LOW
HIGH
BLOWER
LIMIT
BLOWER
LIMIT
CFM
MOTOR
GNDSENDHUM Y1
H
L2-OUT
L2-IN
L1-IN
L1-OUT
Y1Y/Y2W
CR
HP
SPEED
COMMON
PWM
MODE
OPEN
OPEN
FAULT
R
C
GND
RX
TX
W
C
DX-
DX+
R
RED
GREEN
24 V
120 V
WHITE
BLACK
WHITE W/ BLK STRIPES
BLK W/ WHITE STRIPES
1234
1234
INDUCER
H
L
C
123
123
BLACK
WHITE
BLACK
BLACK
112233445566778899
12345
6
12345
6
COOL
FAN SPEED
HEAT
BLWR OFF
DELAY
RED
RED
RED
PAR T O F
MOTOR
123
123
BLUE
BLUE
BLUE
BLUE
BLUE
BLACK
WHITE
BLACK
BLACK
BLACK
BLACK
WHITE
BLACK
WHITE
WHITE
RED
RED
GREEN
GREEN
BROWN
BROWN
YELLOW
VIOLET
VIOLET
ORANGE
ORANGE
VENT LIMIT
(ON SELECT
MODELS)
BLACK 120V
WHITE (NEUTRAL)
GROUND
CONDENSATE
(ON SELECT
MODELS)
BLACK
VIOLET
For 80+ and 90+ 2-Stage Variable Speed Upflow Furnaces
WIRING DIAGRAM
7109180
FIELD WIRING
LEGEND:
LOW VOLTAGE
HIGH VOLTAGE
Refer to the Installation Instructions
provided with the kit for the proper
heating and cooling speeds for your
application.
If any of the origInal wire as supplied with the
furnace must be replaced, it must be replaced
with wiring material having a temperature
rating of at least 105° C.
Use copper conductors only.
This wiring diagram shows connections and
termination required for the blower kit only.
Use in addition to the wiring diagram for the
furnace.
¢7109187¤
Green LED Red LED
Control Fault (No Power) Off Off
L1 / Neutral Polarity Fault Flash Flash
1 Hour Lockout
Normal Operation On On
Pressure Switch Closed Fault On Flash
Pressure Switch Open Fault Flash On
Open Limit Switch Fault Flash Off
Low Flame Sensor Signal
Flame Present
Diagnostic Description
FAULT CONDITIONS
Diagnostic Description
Yellow LED
Continuous Flash
On
Alternating Flash
Motor Fault On Off
0409
ORANGE
MOTOR CHOKE
(ON 3/4 AND 1HP
MOTORS ONLY)
BLUE BLUE
BLACK
WHITE
BLACK
WHITE
BROWN
RED
ORANGE
YELLOW
GREEN
BLUE
BROWN
RED
ORANGE
YELLOW
GREEN
BLUE
Figure 26. Wiring Diagram for Two-Stage, Variable Speed Upfl ow Furnaces
36
Page 37
Green LED Red LED
Control Fault (No Power) Off Off
L1 / Neutral Polarity Fault Flash Flash
1 Hour Lockout
Normal Operation On On
Pressure Switch Closed Fault On Flash
Pressure Switch Open Fault Flash On
Open Limit Switch Fault Flash Off
Low Flame Sensor Signal
Flame Present
Diagnostic Description
FAULT CONDITIONS
Diagnostic Description
Yellow LED
Continuous Flash
On
Alternating Flash
Motor Fault On Off
112233445566778899
RED
RED
PAR T O F
BLACK
WHITE
LIMIT
BLUE
BLUE
ORANGE
BLACK
BLOWER
BLOWER
BLOWER
WHITE
DECK LIMIT
LIMIT
CFM
MOTOR
RED
123 123
MOTOR
GNDSEN
PWM
MODE
Y1
COOL
FAN SPEED
DHUM
L1OUT
L1-IN
L2-OUT
L2-IN
FAULT
SPEED
HEAT
HP
OPEN
COMMON
GREEN
R
OPEN
RED
DX+
8
8 7 6 5 4 3 2 1
C
DX-
R
ORANGE
7 6
WHITE
5
BLACK
4
RED
3 2
YELLOW
1
C
W
TX
RX
CR
GND
H
Y1Y/Y2W
WHITE
YELLOW
RED
BLACK
0409
7109190
¢710919=¤
If any of the origInal wire as supplied with the
furnace must be replaced, it must be replaced
with wiring material having a temperature
rating of at least 105° C.
Use copper conductors only.
BLACK
WHITE
120 V
24 V
BLK W/ WHITE STRIPES
WHITE W/ BLK STRIPES
1234
1234
This wiring diagram shows connections and
termination required for the blower kit only.
Use in addition to the wiring diagram for the
furnace.
LOW
SWITCH
PRESSURE
W RX TX COM C R
BLACK
BLACK
LINE- N
LINE- N
XMFR-N
DELAY
BLWR OFF
RCY/Y2 W2GW1Y1
6
9
3
12
8
5
2
11
4
1
7
10
14325
HUM
LINE
LINE
XMFR
EAC
ORANGE
YELLOW
RED
BLACK
WHITE
BLUE
BLUE
BLACK
DOOR
SWITCH
WHITE
INDUCER
1 1
C
IGNITOR
2 2
H
L
123
123
WIRING DIAGRAM
Refer to the Installation Instructions
provided with the kit for the proper
heating and cooling speeds for your
For 80+ and 90+ 2-Stage Variable Speed Downflow Furnaces
application.
Figure 27. Wiring Diagram for Two-Stage, Variable Speed Downfl ow Furnaces
HIGH
SWITCH
PRESSURE
GAS
FLAME
FLAME SENSOR
C
HI
LO
VALVE
ROLL-OUT
SUPPLY
AIR LIMIT
GREEN
BLACK 120V
GROUND
WHITE (NEUTRAL)
LEGEND:
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
37
Page 38
GAS INFORMATION
TIME FOR
ONE REVOLUTION
(SECONDS)
10 360 1,800 3,600
12 300 1,500 3,000
14 257 1,286 2,571
16 225 1,125 2,250
18 200 1,000 2,000
20 180 900 1,800
22 164 818 1,636
24 150 750 1,500
26 138 692 1,385
28 129 643 1,286
30 120 600 1,200
32 113 563 1,125
34 106 529 1,059
36 100 500 1,000
38 95 474 947
40 90 450 900
42 86 429 857
44 82 409 818
46 78 391 783
48 75 375 750
50 72 360 720
52 69 346 692
54 67 333 667
56 64 321 643
58 62 310 621
60 60 300 600
62 58 290 581
64 56 281 563
GAS FLOW RATES
CUBIC FEET PER
REVOLUTION OF GAS METER 15 10
GAS FLOW RATES
TIME FOR
ONE REVOLUTION
(SECONDS)
66 55 273 545
68 53 265 529
70 51 257 514
72 50 250 500
74 49 243 486
76 47 237 474
78 46 231 462
80 45 225 450
82 44 220 439
84 43 214 429
86 42 209 419
88 41 205 409
90 40 200 400
92 39 196 391
94 38 191 383
96 38 188 375
98 37 184 367
100 36 180 360
102 35 176 353
104 35 173 346
106 34 170 340
108 33 167 333
110 33 164 327
112 32 161 321
114 32 158 316
116 31 155 310
118 31 153 305
120 30 150 300
CUBIC FEET PER
REVOLUTION OF GAS METER
15 10
38
Table 8. Gas Flow Rates (Cubic Feet per Hour)
GAS PIPE CAPACITIES
Nominal Pipe
Diameter (IN.)
1/2 130 90 75 65 55 50 45 40
3/4 280 190 150 130 115 105 95 90
1 520 350 285 245 215 195 180 170
1 1/4 1,050 730 590 500 440 400 370 350
1 1/2 1,600 1,100 890 760 670 610
10 20 30 40 50 60 70 80
Cubic Feet Per Hour Required =
Length of Pipe Run (Feet)
Input To Furnace (Btu/hr)
Heating Value of Gas (Btu/Cu. Ft.)
NOTE: The cubic feet per hour listed in the table above must be greater than the cubic feet per hour of gas fl ow required by the furnace. To determine the cubic feet per hour of gas fl ow required by the furnace, divide the input rate of the furnace by the heating value (from gas supplier) of the gas.
Table 9. Capacity of Black Iron Gas Pipe (cu. ft. per hour)
for Natural Gas w/ Specifi c Gravity = 0.60
Page 39
PROPANE DERATION CHART
ALTITUDE ABOVE
SEA LEVEL
0 to 1,999 FT
2,000 to 2,999 FT
3,000 to 4,999 FT
5,000 to 5,999 FT
6,000 to 7,999 FT
8,000 to 10,000 FT
INPUT (BTU) & STAGE
60,000 80,000 100,000 120,000 140,000
1st 2nd 1st 2nd 1st 2nd 1st 2nd 1st 2nd
55 55 55 55 55 ORIFICE SIZE
4.2 10.0 4.2 10.0 4.2 10.0 4.2 10.0 4.2 10.0 MANIFOLD PRESSURE
55 55 55 55 55 ORIFICE SIZE
4.2 9.0 4.2 9.0 4.2 9.0 4.2 9.0 4.2 9.0 MANIFOLD PRESSURE
55 55 55 55 55 ORIFICE SIZE
4.2 8.5 4.2 8.5 4.2 8.5 4.2 8.5 4.2 8.5 MANIFOLD PRESSURE
56 56 56 56 56 ORIFICE SIZE
4.2 10.0 4.2 10.0 4.2 10.0 4.2 10.0 4.2 10.0 MANIFOLD PRESSURE
56 56 56 56 56 ORIFICE SIZE
4.2 9.0 4.2 9.0 4.2 9.0 4.2 9.0 4.2 9.0 MANIFOLD PRESSURE
56 56 56 56 56 ORIFICE SIZE
4.2 8.5 4.2 8.5 4.2 8.5 4.2 8.5 4.2 8.5 MANIFOLD PRESSURE
Table 10. High Altitude Deration Chart for Propane Gas
LOCAL HEATING VALUES FOR NATURAL GAS
ALTITUDE ABOVE
SEA LEVEL
2,000 FT LOW LOW LOW LOW LOW LOW
3,000 FT LOW LOW LOW LOW LOW LOW
4,000 FT LOW LOW LOW LOW LOW
5,000 FT LOW LOW LOW LOW LOW
6,000 FT LOW LOW LOW LOW
7,000 FT LOW LOW LOW LOW
8,000 FT LOW LOW LOW
9,000 FT LOW LOW LOW
10,000 FT LOW LOW
650 700 750 800 850 900 950 1,000 1,050
HIGH HIGH HIGH HIGH HIGH HIGH HIGH
BTU PER CUBIC FOOT
HIGH HIGH HIGH HIGH HIGH
HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH
Table 11. Natural Gas Heating Values
HIGH HIGH HIGH
HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH HIGH
39
Page 40
NATURAL GAS with HIGH HEATING VALUE
ALTITUDE ABOVE
SEA LEVEL
0 to 1,999 FT
2,000 to 2,999 FT
3,000 to 3,999 FT
4,000 to 4,999 FT
5,000 to 5,999 FT
6,000 to 6,999 FT
7,000 to 7,999 FT
8,000 to 8,999 FT
9,000 to 9,999 FT
INPUT (BTU) & STAGE
60,000 80,000 100,000 120,000 140,000
1st 2nd 1st 2nd 1st 2nd 1st 2nd 1st 2nd
45 45 45 45 45 ORIFICE SIZE
1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 MANIFOLD PRESSURE
45 45 45 45 45 ORIFICE SIZE
1.7 3.3 1.7 3.3 1.7 3.3 1.7 3.3 1.7 3.3 MANIFOLD PRESSURE
45 45 45 45 45 ORIFICE SIZE
1.7 3.1 1.7 3.1 1.7 3.1 1.7 3.1 1.7 3.1 MANIFOLD PRESSURE
45 45 45 45 45 ORIFICE SIZE
1.7 2.9 1.7 2.9 1.7 2.9 1.7 2.9 1.7 2.9 MANIFOLD PRESSURE
45 45 45 45 45 ORIFICE SIZE
1.7 2.8 1.7 2.8 1.7 2.8 1.7 2.8 1.7 2.8 MANIFOLD PRESSURE
48 48 48 48 48 ORIFICE SIZE
1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 MANIFOLD PRESSURE
48 48 48 48 48 ORIFICE SIZE
1.7 3.3 1.7 3.3 1.7 3.3 1.7 3.3 1.7 3.3 MANIFOLD PRESSURE
48 48 48 48 48 ORIFICE SIZE
1.7 3.0 1.7 3.0 1.7 3.0 1.7 3.0 1.7 3.0 MANIFOLD PRESSURE
48 48 48 48 48 ORIFICE SIZE
1.7 2.8 1.7 2.8 1.7 2.8 1.7 2.8 1.7 2.8 MANIFOLD PRESSURE
Table 12. High Altitude Deration Chart for Natural Gas - High Heating Value
NATURAL GAS with LOW HEATING VALUE
ALTITUDE ABOVE
SEA LEVEL
0 to 1,999 FT
2,000 to 2,999 FT
3,000 to 3,999 FT
4,000 to 4,999 FT
5,000 to 5,999 FT
6,000 to 6,999 FT
7,000 to 7,999 FT
8,000 to 8,999 FT
9,000 to 9,999 FT
60,000 80,000 100,000 120,000 140,000
1st 2nd 1st 2nd 1st 2nd 1st 2nd 1st 2nd
45 45 45 45 45 ORIFICE SIZE
1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 MANIFOLD PRESSURE
45 45 45 45 45 ORIFICE SIZE
1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 MANIFOLD PRESSURE
45 45 45 45 45 ORIFICE SIZE
1.7 3.4 1.7 3.4 1.7 3.4 1.7 3.4 1.7 3.4 MANIFOLD PRESSURE
45 45 45 45 45 ORIFICE SIZE
1.7 3.2 1.7 3.2 1.7 3.2 1.7 3.2 1.7 3.2 MANIFOLD PRESSURE
45 45 45 45 45 ORIFICE SIZE
1.7 3.1 1.7 3.1 1.7 3.1 1.7 3.1 1.7 3.1 MANIFOLD PRESSURE
45 45 45 45 45 ORIFICE SIZE
1.7 2.9 1.7 2.9 1.7 2.9 1.7 2.9 1.7 2.9 MANIFOLD PRESSURE
48 48 48 48 48 ORIFICE SIZE
1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 1.7 3.5 MANIFOLD PRESSURE
48 48 48 48 48 ORIFICE SIZE
1.7 3.3 1.7 3.3 1.7 3.3 1.7 3.3 1.7 3.3 MANIFOLD PRESSURE
48 48 48 48 48 ORIFICE SIZE
1.7 3.1 1.7 3.1 1.7 3.1 1.7 3.1 1.7 3.1 MANIFOLD PRESSURE
INPUT (BTU) & STAGE
Table 13. High Altitude Deration Chart for Natural Gas - Low Heating Value
40
Page 41
LOCATION OF FURNACE COMPONENTS
12 3456 7
8
Main Air
Limit Switch
Inducer
Assembly
Transformer
Igniter
Blower Door Switch
Motor Control Box
Motor Choke
(C & D cabinets only)
Blower Assembly
(behind blower panel)
Motor Choke
(C & D cabinets only)
Blower Door Switch
(behind blower panel)
Roll-Out Switch
Upfl ow / Horizontal Furnace
Combustion Tube
Furnace Control Board Gas Valve
Pressure Switch
Flame Sensor
Gas Manifold
Burner Assembly
Motor Control Board
Blower Assembly
Furnace Control Board
8
56 7 4
12 3
Motor Control Board
Transformer
Pressure Switches
Inducer Assembly
Main Air Limit Switch
Igniter
Assembly
Burner
Roll-Out
Switch
Downfl ow Furnace
Figure 28. Furnace Components
Gas Valve
Gas Manifold
Flame
Sensor
41
Page 42
42
Page 43
43
Page 44
INSTALLATION / PERFORMANCE CHECK LIST
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your customer. This includes being able to install the product according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the product. Safety should always be the deciding factor when installing this product and us­ing common sense plays an important role as well. Pay attention to all safety warnings and any other special notes highlighted in the manual. Improper installation of the furnace or failure to follow safety warnings could result in serious injury, death, or property damage.
These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Please read all instructions carefully before starting the installation. Return these instructions to the customer’s package for future reference.
INSTALLER NAME:
CITY: STATE:
INSTALLATION ADDRESS:
CITY: STATE:
ELECTRICAL SYSTEM:
Electrical connections tight? YES NO
Line voltage polarity correct? YES NO
Supply Voltage: ________________________________ VOLTS
Has the thermostat been calibrated? YES NO
Is the thermostat level? YES NO
Is the heat anticipator setting correct? YES NO
GAS SYSTEM:
Gas Type: (circle one)
Gas pipe connections leak tested? YES NO
Gas Line Pressure: ____________________________ (in - W.C.)
Installation Altitude: ______________________________ (FT.)
Deration Percentage: ______________________________ (%)
Natural
Gas
Propane
UNIT MODEL #
UNIT SERIAL #
Minimum clearances per Table 1 (page 5)?
Has the owner’s information been reviewed with the home-owner?
Has the literature package been left near the furnace?
YES NO
YES NO
YES NO
WARNING:
PROPOSITION 65 WARNING: This product contains chemicals known to the state of California to cause cancer, birth defects or other reproductive harm.
Furnace Input: _________________________________ (Btuh)
Supply Air Temperature: __________________________ (° F)
Return Air Temperature: __________________________ (° F)
Temperature Rise: _______________________________ (° F)
COMBUSTION AIR & VENTING SYSTEM:
Is there adequate fresh air supply for combustion and ventilation?
Vent free from restrictions? YES NO
Filter(s) secured in place? YES NO
Filter(s) clean? YES NO
Flue connections tight? YES NO
Is there proper draft? YES NO
YES NO
O’ Fallon, MO
¢709045)¤
709045A
709045A (Replaces 7090450)
Specifi cations and illustrations subject to change
without notice or incurring obligations.
Printed in U.S.A. (03/10)
Loading...