*TA Full Size Series High Efficiency (Upflow/Horizontal) Two-Stage Furnace
with Fixed Speed Blower
*TK Full Size Series High Efficiency (Downflow) Two-Stage Furnace
with Fixed Speed Blower
*TA 80+ Upflow/Horizontal*TK 80+ Downflow
!
WARNING:
Improper installation, adjustment, alteration, service, or maintenance can
cause injury or property damage. Refer
to this manual. For assistance or
additional information consult a qualified installer, service agency, or the
gas supplier.
!
FOR YOUR SAFETY:
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
These instructions are primarily intended to assist qualified individuals experienced in the proper installation of
this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Read
all instructions carefully before starting the installation.
WHAT TO DO IF YOU
SMELL GAS:
•Do not try to light any appliance.
•Do not touch any electrical switch; do not
use any phone in your building.
•Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
•If you cannot reach your gas supplier, call
the fire department.
2. TEMPERATUR E RISES IN THE TABL E ARE APPROXIMATE. ACTUAL TEMPERATURE RISES MAY VARY
3. TEMPERATURE RISES AND AIRFLOWS FOR EXTERNAL STATIC PRESSURES GREATER THAN 0.5 ARE FOR RFERENCE ONLY.
THESE CONDITIONS ARE NOT RECOMMENDED.
4. TEMPERATURE RISES ARE DISPLAYED AS HIGH FIRE / LOW FIRE
NOTES: 1. AIRFLOW RATES OF 1800 CFM OR MORE REQUIRE TWO RETURN AIR CONNECTIONS. DATA IS FOR OPERATION WITH FILTERS(S
*TK(Btuh)SpeedHP
ModelHeating
NumberInputMotorMotor
060-08A60,000
060-12A60,000
80+ DOWNFLOW FURNACE MODELS
Low**
072-12B72,000Med*1/3
Med-Low*
072-16B72,000 Med-High1/2
100-12B100,000
100-16B100,000
Table 2B. Furnace Airflow Data
100-20B100,000
120-16B120,000
120-20B120,000
‡ = FACTORY SET COOLING
* = FACT ORY SET HIGH FIRE
** = FACTORY SET LOW FIRE
7
Page 8
SAFETY INFORMATION
1. Use only with type of gas approved for this
furnace. Refer to the furnace rating plate.
2. Install this furnace only in a location and position
as specified on Table 3 of these instructions.
3. Provide adequate combustion and ventilation
air to the furnace space as specified on Pages
12 through 17.
4. Combustion products must be discharged
outdoors. Connect this furnace to an approved
vent system only, as specified on Pages 14
through 20.
5. Never test for gas leaks with an open flame. Use
a commercially available soap solution made
specifically for the detection of leaks to check
all connections, as specified on Page 23 of
these instructions.
6. Always install furnace to operate within the
furnace’s intended temperature-rise range with
a duct system which has an external static
pressure within the allowable range, as specified on Table 2 of these instructions. See
furnace rating plate.
7. When a furnace is installed so that supply ducts
carry air circulated by the furnace to areas
outside the space containing the furnace, the
return air shall also be handled by duct(s)
sealed to the furnace casing and terminating
outside the space containing the furnace.
8. A gas-fired furnace for installation in a
residential garage must be installed as
specified on Page 11 of these instructions.
9. The furnace is not to be used for temporary
heating of buildings or structures under construction.
INSTALLATION REQUIREMENTS
Requirements and Codes
This furnace must be installed in accordance
with these instructions, all applicable local building codes, current revision of the National Fuel
Gas Code (ANSI-Z223.1), and in Canada with
the CAN/CGA - B149 installation code. The
current revision of the National Fuel Gas Code
is available from:
American National Standards Institute, Inc.
1430 Broadway
New York, New York 10018
Additional helpful publications are:
NFPA-90A - Installation of
Air Conditioning and Ventilating Systems
NFPA-90B - Warm Air Heating
and Air Conditioning Systems
8
These publications are available from:
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, Massachusetts 02269
IMPORTANT NOTE
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR
4.00 and 5.00 for installation of through – the
– wall vented gas appliances as follows:
(a) For direct-vent appliances, mechanical-
vent heating appliances or domestic hot
water equipment, where the bottom of the
vent terminal and the air intake is installed
below four feet above grade the following
requirements must be satisfied:
1. If there is not one already present, on
each floor level where there are
bedroom(s), a carbon monoxide detector and alarm shall be placed in the
living area outside the bedroom(s).
The carbon monoxide detector shall
comply with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall be
located in the room that houses the
appliance or equipment and shall:
a. Be powered by the same electrical
circuit as the appliance or equipment such that only one service
switch services both the appliance
and the carbon monoxide detector;
b. Have battery back-up power;
c. Meet ANSI/UL 2034 Standards and
comply with NFPA 720 (2005 Edi-
tion); and
d. Have been approved and listed by a
Nationally Recognized Testing Labo-
ratory as recognized under 527
CMR.
3. A Product-approved vent terminal must
be used, and if applicable, a Productapproved air intake must be used.
Installation shall be in strict compliance
with the manufacturer’s instructions. A
copy of the installation instructions shall
remain with the appliance or equipment
at the completion of the installation.
4. A metal or plastic identification plate
shall be mounted at the exterior of the
building, four feet directly above the
Page 9
location of vent terminal. The plate shall
be of sufficient size to be easily read
from a distance of eight feet away, and
read “Gas Vent Directly Below”.
(b) For direct-vent appliances, mechanical-
vent heating appliances or domestic hot
water equipment where the bottom of the
vent terminal and the air intake is installed
above four feet above grade the following
requirements must be satisfied:
1. If there is not one already present, on
each floor level where there are
bedroom(s), a carbon monoxide detector and alarm shall be placed in the
living area outside the bedroom(s).
The carbon monoxide detector shall
comply with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall:
a. Be located in the room that houses
the appliance or equipment;
b. Be either hard-wired or battery pow-
ered or both; and
c. Shall comply with NFPA 720 (2005
Edition).
3. A Product-approved vent terminal must
be used, and if applicable, a Productapproved air intake must be used.
Installation shall be in strict compliance
with the manufacturer’s instructions. A
copy of the installation instructions shall
remain with the appliance or equipment
at the completion of the installation.
!
WARNING:
This furnace is not approved for installation in mobile homes. Installation in a
mobile home could cause fire, property
damage, and/or personal injury.
Location
Upflow gas furnaces are shipped ready for
installation in the upflow or horizontal right or left
positions. The *TK gas furnace is for downflow
operation only. The furnace must be installed on
a level surface, located as close to the vent (or
chimney) and as close to the center of the air
distribution system as possible. See Table 1 for
overall dimensions to determine the required
clearances in hallways, doorways, stairs, etc.
to allow the furnace to be moved to the installation point. The furnace must be installed so
that all electrical components are protected
from water. The furnace must be installed
upstream from a refrigeration system. This
furnace is not to be used for temporary heating
of buildings or structures under construction.
Clearances to Combustibles
This furnace is Design Certified by CSA International for the minimum clearances to combustible material listed in Table 3. Refer to the
furnace rating plate, located inside of the furnace cabinet, for the specific model number and
clearance information.
Access for positioning and servicing the unit
must be considered when locating unit. Twenty
four inches is the minimum required clearance
from the front of the unit for servicing it. Thirty
inches is the minimum required clearance from
the front of the unit for positioning it. Thirty Six
inches is the recommended clearance from
the front of the unit. Please note that a panel
or door can be located such that the minimum
clearance on the rating plate is satisfied, but that
panel or door must be removable and allow the
appropriate clearance for your installation.
This furnace is certified for use on wood flooring. This furnace must not be installed directly
on carpeting, tile, or any combustible material
other than wood flooring.
Downflow Warning (*TK Models):
The design of the downflow furnace is certified
for natural or propane gas and for installation on
non-combustible flooring. A special combustible floor sub-base is required when installing
on a combustible floor. Failure to install the subbase may result in fire, property damage and
personal injury. The special downflow subbases are factory supplied accessories, part
numbers 902974, 902677, 904108 and 904165.
904165 is an adjustable sub-base kit and it can
be used in all cabinet sizes. When the furnace
is installed on a factory or site-built cased air
conditioning coil, the sub-base is not necessary. However, the plenum attached to the coil
casing must be installed such that its surfaces
are at least 1" from combustible construction.
!
CAUTION:
The downflow sub-base must not be
installed directly on carpeting, tile, or any
combustible material other than wood
flooring.
Table 3. Minimum Clearances to Combustible Material
LEFT
SIDE
TOP
RIGHT
SIDE
BOTTOM
10
Page 11
A gas-fired furnace installed in a residential
garage must be installed so the burners and the
igniter are located not less than 18 inches (457
mm) above the floor, and the furnace must be
located or protected to avoid physical damage
by vehicles.
Supply Air Plenum Installation
A. Installation on a concrete slab. - *TK
1. Construct a hole in the floor per the
dimension in Figure 2.
2. Place the plenum and the furnace as
shown in Figure 3.
!
WARNING:
Do not place combustible material on or
against the furnace cabinet or within 6
inches of the vent pipe. Do not place
combustible materials, including gasoline and any other flammable vapors and
liquids, in the vicinity of the furnace.
18.75"
19.25"
Hole in
Floor
*TK 072
*TK 100
*TK 120
13.25"
19.25"
Hole in
Floor
*TK 060
Figure 2. Opening for Concrete Slab
B. Installation on a combustible floor. - *TK
For downflow furnace installation, this furnace is approved for use on combustible
flooring when NORDYNE combustible floor
sub-base kit #904165 is used.
1. Cut hole and frame the hole per the
dimensions in Figure 4.
2. Install the sub-base according to the
installation instructions. (See Figure 5)
18.75"
or 13.25”*
16.75"
1.50"
9.25"
28.38"
2.0"
19.63"
Concrete
Floor
Furnace
Sheet
Metal
Plenum
Figure 3. Furnace on a Concrete Slab
18.75"
20.63"
Hole in
Floor
*TK 072
*TK 100
*TK 120
13.25"
20.63"
Hole in
Floor
*TK 060
Figure 4. Opening in Wood Floor
1.58"
1 inch thick fiberglass 3 lb density
19.75"
or 14.25”*
*Smaller dimension for *TK60
3"
Figure 5. Downflow Sub-Base
Dimensions
Downflow
Sub-base
Furnace
Sheet
Metal
Plenum
Wood
Floor
Figure 6. Furnace with Coil Assembly
on a Wood Floor
11
Page 12
3. When the furnace is installed on a factory or site-built cased air conditioning
coil, the sub-base is not necessary.
However, the plenum attached to the
coil casing must be installed such that its
surface is at least 1” from combustible
material in Figure 6.
VENTING AND COMBUSTION
AIR REQUIREMENTS
General
Provisions must be made in the installation of
this furnace to provide an adequate supply of air
for combustion. Detailed instructions for determining the adequacy of an installation can be
found in the current revision of the National Fuel
Gas Code (ANSI Z223.1 / NFPA54) or in applicable local building codes. Consult local codesfor special requirements. For Canadian installations consult Canadian Installations Codes
and (CAN/CGA B149.1 or .2).
If the furnace is operated with inadequate air for
combustion one of the flame roll-out switches
located in the burner compartment or the vent
switch will open, turning off the gas supply to the
burners. These safety devices are manually
reset switches. DO NOT install jumper wires
across these switches to defeat their function.
DO NOT reset a switch without identifying and
correcting the fault condition. If a switch must be
replaced, use only the correct part specified in
the Replacement Parts List.
Air openings in the furnace door, warm air
registers, and return air grilles must not be
restricted.
When determining combustion air space,
the full rate input of this two-stage furnace
must be used.
Combustion Air Quality
To maximize heat exchanger life, the combustion air must be free of chemicals which form
corrosive acidic compounds in the combustion
gases. The recommended source of combustion air is to use the outdoor air supply. However, the use of indoor air in most applications
is acceptable except as follows:
1. If the furnace is installed in a confined space it
is recommended that the necessary combustion air come from the outdoors by way of attic,
crawl space, air duct, or direct opening.
2. If outdoor combustion air is used, there must be
no exposure to the installations or substances
listed in Item 3 below.
3. The following types of installation may require
Outdoor Air for combustion, due to chemical
exposures:
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry rooms
• Furnaces installed in hobby or craft rooms
• Furnaces installed near chemical storage
areas
Exposure to the following substances in the
combustion air supply may also require Out-door Air for combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes,
etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials
!
CAUTION:
Combustion air must not be drawn from
a corrosive atmosphere.
!
WARNING:
Furnace installation using methods other
than those described in the following
sections must comply with the National
Fuel Gas Code and all applicable local
codes to provide sufficient combustion
air for the furnace.
Installation In An Unconfined Space
An unconfined space is an area including all
rooms not separated by doors with a volume
greater than 50 cubic feet per 1,000 Btuh of the
combined input rates of all appliances which
draw combustion air from that space. For example, a space including a water heater rated
at 45,000 Btuh input and a furnace rated at
75,000 Btuh requires a volume of 6,000 cubic
feet [50 x (45 + 75) = 6,000] to be considered
12
Page 13
unconfined. If the space has an 8 foot ceiling, the
floor area of the space must be 750 square feet
(6,000 / 8 = 750). In general, a furnace installed
in an unconfined space will not require outside
air for combustion. However, in “tight” buildings
(with weather stripping and caulk to reduce
infiltration), it may be necessary to provide
outside air to ensure adequate combustion and
venting, even though the furnace is located in
an unconfined space.
Installation In A Confined Space
A confined space is an area with volume less
than 50 cubic feet per 1,000 Btuh of the combined input rates of all appliances drawing
combustion air from that space. Furnace closets, small equipment rooms and garages are
confined spaces. Furnaces installed in a confined space which supply heated air to areas
outside the space must draw return air from
outside the space and must have the return air
ducts tightly sealed to the furnace. A confined
space must have two openings into the
space for combustion air. One opening
must be within 12 inches of the ceiling, and
the other must be within 12 inches of the
floor. The required sizing of these openings is
determined by whether inside or outside air is
used to support combustion, the method by
which the air is brought to the space, and by the
total input rate of all appliances in the space.
The *TA series furnace may be installed directly
on combustible wood flooring or supports, if
type "B-1" vent pipe is used (See Figure 8). It
is recommended for further reduction of fire
hazard that cement board or sheet metal be
placed between the furnace and the combustible floor and extend 12 inches beyond the front
of the louvered door.
!
WARNING:
Furnaces installed with combustion air
drawn from a heated space which includes exhaust fans, fireplaces, or other
devices that may produce a negative
pressure should be considered confined space installations.
Horizontal Furnace Installation
The *TA series furnaces can be installed horizontally in an attic, basement, crawl space or
alcove. It can be suspended from a ceiling in a
basement or utility room in either a right to left
airflow or left to right airflow. (See Figures 7 and
8.)
If the furnace is to be suspended from the
ceiling, it will be necessary to use steel straps
around each end of the furnace. These straps
should be attached to the furnace with sheet
metal screws and to the rafters with bolts. The
furnace could also be suspended by an angle
iron frame bolted to the rafters. (See Figure 7.)
Access for positioning and servicing must be
considered when locating the unit. Refer to
Table 3, Minimum Clearances to Combustible
Material, for clearance specifications.
Keep all insulating materials away from the
louvered door. Insulating materials may be
combustible.
Figure 7. *TA Horizontal Installation
Suspended in Attic or Crawl Space
Note: Line
Contact is Permissible
Type “B” Vent
Coil Plenum
Electrical
Supply
Connection
Gas Inlet
Combustible
Platform
Louver Door
Figure 8. *TA Horizontal installation on a
Platform
13
Page 14
See the venting section for venting guidelines
and specifications.
Air From Inside (See Figure 9)
If combustion air is taken from the heated
each
space, the two openings must
have a free
area of at least one square inch per 1,000 Btuh
of total input of all appliances in the confined
space, but not less than 100 square inchesof free area. For example, if the combined input
rate of all appliances is less than or equal to
100,000 Btuh, each opening must have a free
area of at least 100 square inches. If the com-
bined input rate of all appliances is 120,000
Btuh, each opening must have a free area of at
least 120 square inches.
Outdoor Air Using Vertical Ducts
(See Figure 10)
If combustion air is taken from outdoors through
vertical ducts, the openings and ducts must
have a minimum free area of one square inch
per 4,000 Btuh of total appliance input. In installations drawing combustion air from a ventilated
attic, both air ducts must extend above the attic
insulation.
100 sq. in.
100 sq. in.
100 sq. in.
100 sq. in.
120 sq. in.
140 sq. in.
160 sq. in.
Furnace
Openings to
adjacent space.
Each opening must
be at least 100 sq. in.
or 1 sq. in. per 1000
Btuh of total input
rating, whichever is
greater. See minimum
area per table.
If combustion air is provided directly through an
exterior wall, the two openings must each have
free area of at least one square inch per 4000
Btuh of total appliance input.
Outdoor Air Using a Crawl Space and Ventilated
Attic (See Figure 12)
When directly communicating with the outdoors, each opening shall have a minimum free
area of 1 square inch per 4,000 Btuh of total
appliance input. The openings shall communicate directly, or by ducts, with the outdoor
spaces (crawl or attic) that freely communicate
with the outdoors.
Outdoor Air Using Horizontal Ducts
(See Figure 13)
If combustion air is taken from outdoors through
horizontal ducts, the openings and ducts must
have a minimum free area of one square inch
per 2,000 Btuh of total appliance input.
In Canada, venting shall conform to the requirements of the current (CAN/CGA B149.1 or .2)
installation codes. Consult local codes for
special requirements.
For Category I furnace installations, the furnace shall be connected to a factory built
chimney or vent complying with a recognized
standard, or a masonry or concrete chimney
lined with a lining material acceptance to the
authority having jurisdiction. Venting into an
unlined masonry chimney or concrete chimney is prohibited.
This furnace must never be vented to a chimney flue servicing a fireplace or other appliance
designed to burn solid fuel. If the furnace vent
is to be connected to a chimney serving a
fireplace, the fireplace must be sealed off from
the chimney. Single wall metal vents shall not be
used for Category I venting, Category I furnaces must be vented vertically or near vertically.
If the unit is installed in an area with an exhaust
fan, provide sufficient ventilation to prevent
negative pressures from occurring in the room.
The combustion air openings must not be restricted in any manner.
VENTING REQUIREMENTS
General
This furnace must be vented in compliance
with, the current revision of the National Fuel
Gas Code (ANSI-Z223.1/NFPA54), with the
instructions provided below.
Vent or
Chimney
Furnace
Water Heater
Ventilation Louvers for
unheated crawl space
Ventilation Louvers at
each end of attic
Attic Insulation
Crawl Space
Outlet Air Duct
must be at least
1 sq. in. per 4000
Btuh of total input
rating. Must extend
above attic insulation.
Inlet Air Duct must
be at least 1 sq. in.
per 4,000 Btuh of
total input rating.
The furnace vent, if metal, may be insulated if
local codes allow. Any part of the vent system,
metal vent only, not exposed to weather, but
which are exposed to ambient temperatures
below 35° F must be insulated to prevent condensation. All vent insulation shall be foil backed
fiberglass of one inch minimum thickness.
Vent or
Furnace
Water Heater
(Each Opening)
Chimney
Minimum
Free Area
20 sq. in.30 sq. in.
40 sq. in.
50 sq. in.
60 sq. in.
70 sq. in.80 sq. in.
-
-
-
-
-
-
-
-
Air Duct
-
-
-
-
-
-
-
-
-
Air Duct
-
Round Duct
Diameter
5"
6"
7"
8"
9"
10"
10"
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
side
st be at lea
g.
12" Max
g
st
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Rating (Btu/hr)
Each openin
to out
mu
1 sq. in. per 2000
Btuh of total input
ratin
Three sheet metal fasteners (field supplied)
should be used to secure the vent pipe to the
furnace flue. These fasteners should be evenly
spaced around the flue diameter, if possible.
Category I - Common Venting
When an existing furnace is removed from a
venting system serving other appliances, the
venting system is likely to be too large to
properly vent the remaining appliances. An
!
WARNING:
improperly sized venting system can result in
the formation of condensate, leakage, spillage,
etc.
The steps outlined in the warning below shall be
followed with each individual appliance connected to the vent system placed in operation,
while all other appliances connected to the vent
system are not in operation:
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the
venting system being placed into operation could result in carbon monoxide
poisoning or death.
The following steps shall be followed for each appliance connected to the
venting system being placed into operation, while all other appliances connected
to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required
in the
Natural Gas and Propane Installation Codes
mine that there is no blockage or restriction, leakage, corrosion and other
deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors
between the space in which the appliance(s) connected to the venting
system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting
system. Turn on any exhaust fans, such as range hoods and bathroom
exhausts, so they are operating at maximum speed. Do not operate a
summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into
operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood
relief opening after 5 minutes of main burner operation. Use the flame of
a match or candle.
8. If improper venting is observed during any of the above tests, the venting
system must be corrected in accordance with the
ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes
9. After it has been determined that each appliance connected to the venting
system properly vents when tested as outlined above, return doors,
windows, exhaust fans, fireplace dampers and any other gas-fired burning
appliance to their previous conditions of use.
National Fuel Gas Code, ANSI Z223. 1/NFPA 54 or the CSA B149.1,
and these instructions. Deter-
National Fuel Gas Code,
.
16
Page 17
The venting system should be designed to
have the minimum number of elbows or turns.
All horizontal runs shall be sloped upwards from
the furnace at 1/4 inch per running foot of vent.
Supports for the vent pipe must be installed a
minimum of every five feet along the vent run to
ensure no displacement after installation.
Under no circumstances shall any portion of
the vent system extend into or pass through
any return air duct, supply air duct, or plenum.
If the furnace is operated with blocked or
restricted venting, the blocked vent switch
located in the vent plate will open, turning off the
gas supply to the burners. The blocked vent
switch is a manually reset device. DO NOT
install a jumper wire across this switch to defeat
its function. DO NOT reset the switch without
identifying and correcting the fault condition
which caused the switch to trip. If this switch
must be replaced, use only the part specified in
the Replacement Parts List.
!
WARNING:
Upon completion of the furnace installation, carefully inspect the entire flue system both inside and outside the furnace
to assure it is properly sealed. Leaks in
the flue system can result in serious
personal injury or death due to exposure
of flue products, including carbon monoxide.
Category III: Horizontal Venting
appliances. When venting horizontal, this is
defined as a Category III furnace, the vent
pressure is positive, and the venting system
must be sealed in both horizontal and vertical
runs.
For horizontal venting installations in both the
United States and Canada the transition assembly must be modified by adding a bleed tube
to the pressure switch tube and bypassing the
vent switch. All model furnaces will require Vent
Kit #903196 for horizontal venting.
NOTE: No bleed tube is required for the *RA
045(C,N)-08 model.
Horizontal Venting For Upflow Models:
1. Remove the rubber tubing from the pressure
switch sensor tube and the collector pan sensor tube. Cut 1/2 inch from one end of the rubber
sensor tube, fold in half and cut along the bend
line. Discard the 1/2 inch long piece of tubing.
Select the correct bleed tube using the table
supplied with vent kit #903196 and place the
other two pieces of tubing on both ends of the
bleed tube. Do not cover the hole in the bleed
tube. Place the assembly back on the pressure
switch sensor tube and the collector pan sensor tube. (See Figure 14.)
Pressure
Switch
Bleed Tube
Sensor
Tubes
NOTE: The reduced NOx models (eighth
character N) are not approved as a Category III (Category III) furnace for use with
horizontal venting.
The furnaces are approved for use with 3"
single wall AL29-4C stainless steel vent
pipe in horizontal vent applications. This
pipe is available from the following manufacturers:
Z-FLEX Inc. - vent brand name (Z-VENT)
Heat-fab Inc. - vent brand name (Saf-T Vent)
Flex-L International - vent brand name (Star-
34 Vent)
This vent pipe must be used for the entire length
of the vent run. The installation must be in
accordance with all instructions supplied by the
vent manufacturer for use on Category III
Collector
Pan
Figure 14. *TA Bleed Tube Installation
2. Remove the nut and restrictor plate from the
vent collar assembly and discard the restrictor
plate. Select the appropriate dilution cover plate
as noted with vent kit #903196. Fit the clearance
hole in the cover plate over the weld stud. The
cover plate must cover the hole(s) on the vent
collar assembly. Tighten the nut securely while
holding the cover plate in position. (See Figure
15.)
3. Bypass the vent switch by removing both wires
from the vent switch and attaching them to the
wire nut. (See Figure 16.)
17
Page 18
Collector
Pan
Cover
Plate
Covered Vent
Nut
Collar Hole
Figure 15. Vent Collar Detail
Switch
Limit
Blue
Switch
Flame
Roll-Out
Switch
Vent
Limit
Blue
Wire Nut
Figure 16. Limit Circuit Wiring
Horizontal Venting: *TK Models:
1. By-pass the vent switch, located on blower
compartment door, by removing both wires
from the switch. Remove wire terminals, strip
wires and tie together in a wire nut. (See Figure
16.)
2. Remove the rubber tubing from the pressure
switch sensor tube and the collector pan sensor tube. Cut the tubing approximately 3" from
one end. Select the appropriate dilution cover
plate as noted with vent kit #903196. Insert the
bleed tube into the tubing. Do not cover thehole in the bleed tube. Place the tubing
assembly back on the pressure switch sensor
tube and collector pan sensor tube. (See Figure
17.)
3. To gain access to the restrictor plate, remove
and discard the combustion tube from the
transition assembly. Insure the seal between
inducer and transition assembly is not
broken. (See Figure 18.)
4. Remove and discard the restrictor plate and
screw from the transition assembly. (See Figure 18.)
5. Install and seal a 4" to 3" reducer to the transition.
(See Figure 19.) Attach the new high temperature vent pipe to the reducer.
!
CAUTION:
Do not drill holes through the vent pipe
or fittings on a horizontal vented furnace. Do not use sheet metal screws, or
rivets. Drilling, screws, or rivets will
cause leaks.
Bleed Tube
Bleed Tube
Orifice
Pressure
Switch
Figure 17. *TK Bleed Tube Installation
The components of the horizontal vent system
must not be penetrated with screws, rivets, or
other devices, either when joining pipes and
fittings or using support straps. All joints must
be sealed with high temperature silicone before
locking bands are installed. If the lengths of pipe
must be cut, the joint must still be sealed with
silicone and the locking band used. When
installing the condensate tube be sure to form
a trap by means of a 3" loop filled with water.
(See Figure 20.)
Keep the number of pipe fittings to a minimum.
Maintain a minimum of 6 inches of air space
between the vent and combustibles at all times,
this includes inside and outside the building.
NOTE: The direction of the male-female joints
from the drain tee to the termination tee is
opposite to standard gas appliance venting.
The male end of the pipes point towards the
furnace.
Combustion
Tube
Remove
and
Discard
Screw
Restrictor
Plate
Transition
Inducer
Figure 18. *TK Horizontal
Vent Modification
18
Page 19
Special 3"
AL29-4C Stainless
Steel
Vent Pipe
with this furnace. The kit includes a power
venter, a side-wall vent hood and a barometric
draft control. It has an electrical interlock to
assure that the furnace will not operate when
the power venter is off.
4" to 3" Reducer
Transition
Figure 19. *TK Reducer Installation
1.Apply an adhesive bead around the
outside of the pipe approximately 1/4"
from the end of the pipe. This includes
the first fitting or pipe attached to the
furnace.
2.Push the pipe and fitting together while
twisting the pipe or fitting. Twisting the
pipe or fitting spreads the adhesive
completely within the fitting socket.
3.When the pipe is at the socket bottom,
inspect the joint. Look for a complete,
uninterrupted ring of adhesive material
around the pipe at the fitting socket.
Additional adhesive or rotation of the
pipe or fitting may be required for a
complete seal. The complete adhesive
material ring provides the seal required
for the positive pressure vent.
4.All vent systems must include a tee and
drain plug for collection and disposal of
condensate. The drain tee must be
installed within the first 5 feet of vent run
to protect the furnace.
The kit is for use only when exhaust is through
an exterior wall, normally with horizontal vent
piping. The power venter establishes negative
pressure in the vent piping and the furnace
operates as if connected to Category I vertical
venting.
Horizontal Venting Requirements
Furnace Pipe Reducer Maximum Max. Feet
InputSize Needed # Elbows Vent Pipe
60,0003"4" to 3"435
72,0003"4" to 3"435
96,0003"4" to 3"435
120,0003"4" to 3"430
Table 4. Horizontal
Venting Requirements
Installation Instructions are provided with the
kit. Installation must conform to those instructions and applicable requirements of local codes.
!
WARNING:
The entire vent system must be sealed
with a high temperature sealant which
will withstand temperatures of 450°F.
Recommended sealants: Dow Corning
Sealant 736 RTV; GE 106 RTV; High
Tech Ind., High TEMP RED.
5.All horizontal sections must have a
slope toward the drain tee of not less
than 1/4" per foot to prevent the collection
of condensate at any location other than
at the tee.
6.Horizontal runs must be supported with
3/4" pipe strap at a maximum of 5 foot
intervals and at each point where an
elbow is used.
7.Maintain a 6 inch minimum air space to
combustibles from all sections of the
stainless steel vent system, except
when a wall thimble is used.
Horizontal Power Venting
— The Tjerlund GPAK-
1 horizontal kit is certified for use
(For combustible
/4" Per
Wall Thimble
wall material)
90˚ Elbow
0-6'
Locking Band
Te e
Drain
Plug
Support
1
Foot Rise
3" Dia. Loop
Figure 20. Typical Horizontal Vent
Installation
Locking
Band
Termination
Te e
Outside
Wall
19
Page 20
r
g
y
g
y
Location of Outdoor Terminations
Horizontal Installation
The vent termination tee must be installed with
the following minimum clearances. (See Figure
21.) Vent termination clearances shall be con-
sistent with the
National Fuel Gas Code, ANSI
2223.1/NFPA 54 and/or the CSA B149.1,
Natural Gas and Propane Installation Code.
VENT TERMINAL
Clearance abov e grade, veranda, porch,
A =
deck, or balc ony
Clearance t o window or door that may be
B =
opened
Clearance t o permanently closed window
C =
Vertical c learance to ventilat ed sof fit
D =
locat ed above t he terminal within a
horizont al dis tanc e of 2 feet (61 cm) from
the center line of the terminal
Clearance to unventilated soff it
E =
Clearance t o outside corne
F =
Clearance t o inside corner
G =
Clearance to each side of c enter line
H =
extended above met er/re
Clearance t o service regulator vent outlet3 feet (1.83 m)
I =
Clearance t o nonmechanical air supply inlet
J =
to building or the combust ion air inlet to any
other appliance
Clearance t o a mechanical air supply inlet6 feet (1. 83 m)3 feet (91 c m) above if wit hin 10 feet (3 m)
K =
Clearance abov e paved sidewalk or paved
L =
driveway located on public property
Clearance under v eranda, porch deck, or
M =
balcony
ulator as sembl
AIR SUPPLY INLET
Canadian Installations
12 inches (30 cm)12 inches (30 cm)
6 inches (15 cm) for applianc es ≤ 10,000
Btuh (3 kW), 12 inc hes (30 c m) for
appliances > 10,000 B tuh (3 k W) and ≤
100,00 Btuh (30 kW), 36 inches (91 cm) for
appliances >100,00 Bt uh (30 kW)
3 feet (91 cm) wit hin a height 15 feet
above t he meter/re
6 inches (15 cm) for applianc es ≤ 10,000
Btuh (3 kW), 12 inc hes (30 c m) for
appliances > 10,000 B tuh (3 k W) and ≤
100,00 Btuh (30 kW), 36 inches (91 cm) for
appliances >100,00 Bt uh (30 kW)
7 feet (2.13 m) †7 feet (2. 13 m)
12 inches (30 cm) ‡
AREA WHERE TERMINAL IS NOT PERMITTED
1
**
**
**
**
**
ulator as sembl
US Installations
4 feet (1. 2 m) below or to s ide of opening;
1 foot (300 mm) above opening
4 feet (1. 2 m) below or to s ide of opening;
1 foot (300 mm) above opening
horizont ally
2
*
*
*
1
In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code
2
In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family
dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in ANSI Z223.1 / NFPA 54 or CSA B149.1, one of the following statement shall be included:
“Clearance in accordance with local installation codes, and the requirements of the gas supplier and the
Figure 21. Vent Termination Clearances for Other Than Direct Vent Furnaces
20
manufacturer’s installation instructions.”
Page 21
All minimum clearances specified must be
maintained to protect building materials from
degradation by flue gases.
1.The termination tee must be 12 inches
above snow level or grade level which
ever is higher. See Figure 22 for alternate method to achieve 12" above snow
level.
2.Avoid areas where condensate drainage
may cause problems such as above
planters, patios, or adjacent to windows
where the steam from the flue gases
may cause fogging. Do not terminate
above any public walkway.
3.Select the point of wall penetration where
the minimum 1/4 inch per foot of upward
slope can be maintained.
4.When penetrating a noncombustible
wall, the hole through the wall must be
large enough to maintain the pitch, pipe
clearance for passage, and provide for
proper sealing. Penetrating a combustible wall requires the use of a wall
thimble. (See Figure 22.) A 6-1/2 inch
square framed opening is required to
insert the thimble halves. The thimble is
adjustable to varying wall thickness and
is held in place by applying sealant to the
male sleeve before assembly. Also run
a bead of sealant around the outer wall
thimble.
5.The vent pipe must extend 1-1/4 inches
through the outer thimble half for a
combustible wall. Be sure to check this
carefully before cutting the vent pipe.
6.Attach a 3 inch coupling to the end of the
pipe that extends through the wall or
thimble. This prevents the vent pipe
from being pushed inward.
7.Cut an 8 inch minimum piece of vent pipe
and connect the coupling to the
termination tee. The inside of the tee
must be a minimum of 12 inches from
the outside of the wall. (See Figure 23.)
Flexible Vent Systems
Flexible gas vent is approved for use in vertical
single vent or common vent installations only.
The minimum distance to combustibles is 1" for
type B insulated and 6" for single wall. The
venting system must be installed in accordance
with the local authorities, the vent manufacturer's
instructions and the instructions listed below.
The flexible vent must be installed in accordance with the venting tables for vertical or
common venting only. The vent system must
be supported in horizontal runs with
3/4" pipe strap at a maximum of 5 foot intervals.
All horizontal sections must have a slope toward the furnace of not less than 1/4" per foot.
The vent must not sag, or have any bends
greater than 90 degrees.
CIRCULATING AIR SUPPLY
General
Plenums and air ducts must be installed in
accordance with the Standard for the Installation of Air Conditioning and Ventilating Systems
(NFPA No. 90A) or the Standard for the Installation of Warm Air Heating and Air Conditioning
Systems (NFPA No. 90B).
Use Wall Thimble at
Vent Points
Termination Tee
Support vent pipe
every 5 feet
Figure 22. Alternate Horizontal
Vent Installation
Ground Level
Combustible
Wall Thimble
(Inner Half)
3" Vent
Pipe
Inner Shield
41/2" Dia.
Combustible
Inside
Wall
Inside
Wall
Outer Overlapping
Shield 6
Wall Thimble Outer Half
Locking Band
Inner
Overlapping
Shield 63/8" Dia.
12" Min
Outside
Combustible
Wall
Figure 23. Typical Termination
1
/2" Dia.
Protective
Screen
3" Termination
Te e
21
Page 22
It is recommended that the outlet duct be provided with a removable access panel. This
opening should be accessible when the furnace
is installed in service and shall be of a size that
smoke or reflected light may be observed inside
the casing to indicate the presence of leaks in
the heat exchanger. The cover for the opening
shall be attached in such a manner as to prevent
leaks.
If outside air is used as return air to the furnace
for ventilation or to improve indoor air quality, the
system must be designed so that the return air
is not less than 50° F (10° C) during operation.
If a combination of indoor and outdoor air is
used, the ducts and damper system must be
designed so that the return air supply to the
furnace is equal to the return air supply under
normal, indoor return air applications.
When a cooling system is installed which uses
the furnace blower to provide airflow over the
indoor coil, the coil must be installed downstream (on the outlet side) of the furnace or in
parallel with the furnace.
If a cooling system is installed in parallel with the
furnace, a damper must be installed to prevent
chilled air from entering the furnace and condensing on the heat exchanger. If a manually
operated damper is installed, it must be designed so that operation of the furnace is prevented when the damper is in the cooling position and operation of the cooling system is
prevented when the damper is in the heating
position.
Return Air
In applications where the supply ducts carry
heated air to areas outside the space in which
the furnace is installed, the return air must be
delivered to the furnace by duct(s) sealed to the
furnace casing, running full size and without
interruption.
!
WARNING:
The solid base of the furnace must be
in place when the furnace is installed
with side return air ducts. Removal of
all or part of the base could cause
products of combustion to be circulated into the living space and create
potentially hazardous conditions, including carbon monoxide poisoning
that could result in personal injury or
death.
For Upflow/Horizontal installations: The
return air ductwork may be connected to any or
all of the following: left side return, right side
return, or bottom return. NOTE: Do not use the
back of the furnace for return air. Table 2, in the
front pages of these instructions, contains the
airflow data for each furnace model. Where
maximum airflow is 1800 CFM or more, two
openings must be used for return air.
Upflow Models- Left Side Entry
Some utilities
require Shut-Off
Valve to be
4 to 5 feet
above floor
Dripleg
Shut-Off Valve
Automatic Gas
Valve (with manual
shut-off)
Ground Joint
Union
22
Manifold
Burner
Assembly
Figure 24. Typical Gas
Service Connection
Downflow Models- Right Side Entry
Shut-Off Valve
Some utilities
require Shut-Off
Valve to be
4 to 5 feet
above floor
Dripleg
Burner
Assembly
Manifold
Automatic Gas
Valve (with manual
shut-off)
Ground Joint
Union
Page 23
!
1/2
130907565555045403/4
280
190
150
130
115
10595901520
350
285
245
215
195
180
170
1 1/4
1050
730
590
500
440
400
370
350
1 1/2
1600
1100
890
760
670
610
560
530
WARNING:
Products of combustion must not be
allowed to enter the return air ductwork or
the circulating air supply. Failure to prevent products of combustion from being
circulated into the living space can create
potentially hazardous conditions including carbon monoxide poisoning that
could result in personal injury or death.
All return ductwork must be secured to
the furnace with sheet metal screws. For
installations in confined spaces, all return ductwork must be adequately sealed
and joints must be taped. When return air
is provided through the bottom of the
furnace, the joint between the furnace
and the return air plenum must be air
tight.
The floor or platform on which the furnace is mounted must provide sound
physical support of the furnace with no
gaps, cracks, or sagging between the
furnace and the floor or platform.
Return air and circulating air ductwork
must not be connected to any other heat
producing device such as a fireplace insert, stove, etc. Doing so may result in fire,
explosion, carbon monoxide poisoning,
personal injury, or property damage.
lation must comply with the latest edition of the
National Fuel Gas Code (ANSI Z223.1) or (CAN/
CGA B149.1 or .2) Installation Codes.
An 1/8 inch NPT tap must be installed in the gas
line to the unit for use when measuring the gas
supply pressure. The tap should be readily
accessible for service use. A drip leg should be
installed in the vertical pipe run to the unit. Table
5 lists gas flow capacities for standard pipe sizes
as a function of length in typical applications
based on nominal pressure drop in the line.
IMPORTANT NOTES:
1. Gas piping must not be run in or through air
ducts, chimneys, gas vents, elevator shafts,
etc.
2. Compounds used on threaded joints of gas
piping must be resistant to the actions of liquefied
petroleum gases.
3. The main manual gas valve and main power
disconnect to the furnace must be properly
labeled by the installer in case emergency
shutdown is required.
Leak Check
After the gas piping to the furnace is complete,
all connections must be tested for gas leaks. To
check for leaks in gas piping systems, use only
a soap and water solution or other approved
method.
GAS SUPPLY AND PIPING
General
This furnace may be installed for either left or
right side gas entry. A typical gas service
hookup is shown in Figure 24. When making the
gas connection provide clearance between the
gas supply line and the entry hole in the furnace
casing to avoid unwanted noise and/or damage
to the furnace.
All gas piping must be installed in compliance
with local codes and utility regulations. Some
local regulations require the installation of a
manual main shut-off valve and ground joint
union external to the furnace. The shut-off valve
should be readily accessible for service and/or
emergency use. Consult the local utility or gas
supplier for additional requirements regarding
placement of the manual main gas shut-off. In
the absence of local codes the gas line instal-
CAPACITY OF BL ACK I RON GAS PIPE (CU. FT. PE R HOUR)
FOR NATURAL GAS (SPECIFIC GRAVITY - 0.60)
NOMINAL LENGTH OF PIPE RUN
BLACK IRON (feet)
PIPE DIAMETER
(in.)1020304050607080
The cub ic f eet per hour list ed in t he table above m ust b e greater t han the c ubic feet
per hour of g as fl ow required by the f urnace.
To determ ine t he cubic feet per hour of gas f low required b y the furnace, div ide the
input rat e of the furnace by the heat ing value of the gas :
Cubic Feet P er Hour Required Input T o Furnace (Btu/ hr)
Heating V alue of Gas (Btu /Cu. Ft .)
Table 5. Capacity of Black Iron Gas Pipe
(cu. ft. per hour) for Natural Gas
(specific gravity = .60)
23
Page 24
!
CAUTION:
Do not use matches, lighters, candles,
or other sources of open flame to check
for gas leaks.
IMPORTANT NOTE:
When pressure testing the gas supply lines
at pressures greater than 1/2 psig (14 inch
W.C.), the furnace must be disconnected
from the gas supply piping system to prevent damage to the gas control valve. If the
test pressure is less than or equal to 1/2 psig
(14 inch W.C.), the furnace must be
isolated from the gas supply line by closing
the manual shut-off valve.
!
WARNING:
!
WARNING:
This furnace was equipped at the factory
for use with natural gas only. A special
kit, supplied by the manufacturer, is required to convert the furnace to operate
on LP/propane gas. Failure to use the
proper conversion kit can cause fire, explosion, property damage, carbon monoxide poisoning, personal injury, or
death.
High Altitude Application
High altitude application with this furnace can be
field performed by a simple adjustment of manifold pressure, and if necessary changing the
orifices. The changes required depend on the
installation altitude and the heating value of the
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in serious injury, death
or property damage.
Never test for gas leaks with an open
flame. Use a commercially available soap
solution made specifically for the detection of leaks to check all connections. A
fire or explosion may result causing property damage, personal injury or loss of
life.
MANIFOLD PRESSURE ADJUSTMENT
Manifold pressures for low and high stages are
independently adjustable. Adjustment tap
locations on the valve are shown in Figure 25.
Manifold pressure would be adjusted below
procedure:
-Turn off gas shut off valve outside furnace.
-Install manometer on the gas valve at the
outlet pressure tap.
-Turn on the shut off. Run furnace at high
fire and set manifold pressure. Also set
manifold pressure while running at low
fire (refer to Tables 7 and 8.)
- Ensure plug is tight after removing
manometer.
HIGH STAGE ADJUSTMENT
UNDER VENT CAP
2-STAG E
OPERATOR
INLET PRESSURE TAP
1/8 NPT
(Honeywell shown)
(4) QUICK DISCONNECT TERMINALS
1ST STAG E
REGULATOR COVER
REGULATOR ADJUST
BENEATH THIS SCREW
gas. The gas heating value based on sea level
can be obtained from your local gas utility. The
heating value of gas at high altitude is always
lower than the sea level heating value. The
heating values used in Tables 6 & 7 are based
on sea level values.
Furnace Ratin
Plate Input (Btu/h)
NatLP
Table 9. Natural and LP gas Orifice Sizes
for Elevations between 5000 and 10,000
ft. Above Sea Level
LP/Propane Gas Conversion
IMPORTANT NOTE: When converting a low
NOx furnace from Natural gas to LP/propane gas, it is necessary to remove the NOx
Baffles from the furnace.
Natural Gas High Altitude Conversion
All factory shipped furnaces are ready to operate between zero and 4999 ft. above sea level.
For higher altitudes (between 5000 and 10,000
ft. above sea level), conversion can be achieved
simply by adjusting the furnace manifold pressure as shown in Table 6.
Conversion of this furnace to utilize LP/propane
gas must be made by qualified service personnel, using factory authorized or approved parts.
Conversion to LP/propane gas can be accomplished by first replacing the natural gas orifices
with the appropriate LP/propane orifices shown
in Table 8 or 9. Note: for installations between
25
Page 26
zero and 5000 ft. above sea level, a, #54 drill size
orifice should be used depending upon the rated
firing rate of the unit (see Table 8 or 9). However
for installations above 5000 ft. above sea level,
a # 55 drill size orifice should be used. After
changing the orifices, use Table 7 to determine
the appropriate manifold pressure for your
installation.
!
WARNING:
To avoid electric shock, personal injury,
or death, turn off the electric power at the
disconnect or the main service panel
before making any electrical connections.
Conversion to LP/propane, sea level, and high
altitude is detailed in the installation instructions
provided with the conversion kit. Approved
conversion kits are listed below.
United States LP/Propane Gas Sea Level and
High Altitude Conversion Kit - P/N 904404.
This kit is for LP/propane conversion in the
United States at altitudes between zero and
10,000 ft. above sea level. Follow the installation instructions supplied with the kit for proper
installation.
Canadian LP/Propane Gas Sea Level and High
Altitude Conversion Kit - P/N 904405.
This kit is for LP/propane conversions in Canada
at altitudes between zero and 4500 ft. above sea
level. Follow the installation instructions supplied with the kit for proper installation.
Furna ceFurnace C abinet N omina lMax imum Minimum Max imum MinimumMaximum
Model Num berInputWidth Elec tr ica l Operating Ope rating Furna ceWireFuse or Cir cuit
*TA ,*TK(Btu/hr) (in.)SupplyVoltageVoltageAmperes Gauge Brea ke r Amps* *
Electrical connections must be made in accordance with all applicable local codes and ordinances, and with the current revision of the
National Electric Code (ANSI/NFPA 70).
For Canadian installations the electrical connections and grounding shall be done in accordance with the current Canadian Electrical
Code (CSA C22.1, Part 1 and/or local codes).
If any of the original wire as supplied with the
furnace must be replaced, it must be replaced
with wire having a temperature rating of at least
105°C. Refer to the furnace nameplate and
Table 10 for electrical requirements.
Note: (†) can be C or N.
**Time-delay fuses or HACR-type circuit breakers are required.
2455 ft.25 ft.
2290 ft.45 ft.
20140 ft.70 ft.
18225 ft.110 ft.
26
2-wire4 or 5-wire
(heating)(cooling)
Table 10. Electrical Data
Page 27
Line Voltage Wiring
The line voltage (115 volt) to the furnace must
be supplied from a dedicated branch circuit
containing the correct fuse or circuit breaker for
the furnace. (See Table 10.) An electrical
disconnect must be installed to be readily accessible from and located within sight of the
furnace. (See the Wiring Diagram label in the
furnace and Figure 35.)
!
CAUTION:
Label all wires prior to disconnection
when servicing controls. Wiring errors
can cause improper and dangerous operation.
Verify proper operation after servicing.
The furnace cabinet must have an uninterrupted, unbroken ground to minimize injury
should an electrical fault condition occur. The
controls used in this furnace require an
earth ground to operate properly. Accept-
able methods for grounding are electrical wire
or conduit approved for electrical ground service. Do not use gas piping as an electrical
ground.
IMPORTANT NOTE:
Proper line voltage polarity must be maintained in order for the control system to
operate correctly. Verify that the incoming
neutral line is connected to the white wire
and the incoming “hot” line is connected
to the black wire. These furnaces will not
operate unless the polarity and ground are
properly connected. See Figure 26.
Field Supplied
Fused Service
Panel
Black (Hot)
White (Neutral)
Green or Bare
(Ground)
Field Supplied
Panel Connector
Black
White
Ground
Field Supplied Disconnect
Within Sight of Furnace
Ground
Black
White
Black
White
Ground
Junction Box (may be internal
or external to the furnace). These
connections can be made in the
field supplied disconnect at the
furnace.
Figure 26. Line Voltage Field Wiring
A/C Condensing Unit
Condensing Unit
Control Box
Blower Off
3 Amp
Fuse
Flame Signal Light
Status Light
HEAT
M1M2M3
R Y G W
Connect
R & W
For
Heating
Only
Room
Thermostat
NOTE: The "Y"
terminal on the
UTEC control board
must be connected
to the thermostat
for proper cooling
mode operation.
FIELD WIRING
Low Voltage
Connections
R C Y G W
COM
24 V
3
6
9
2
5
8
1
4
7
EAC
HUM
Neutrals
Unused Motor Leads
HUM
63
52
41
Timing
(Yellow)
(Red)
COOL
EAC
Field Line Voltage
Wiring
Factory Line
Voltage Wiring
6090120
180
TWIN
XFMR
L1
Figure 27. Low Voltage Field, Four-wire Heating/Cooling Applications
27
Page 28
Low Voltage Wiring
Staging Configurations
These furnaces are factory configured to operate on high fire only, but can be field converted
to operate as two-stage furnaces.
NOTE: T
efficiency, the furnace should be operated in the
factory configuration (high fire only as described in part 2.)
Two stage thermostat configuration
1.
installation a two stage heating thermostat is
used. CAUTION: Disconnect yellow wire with
black stripe from low firing of gas valve. Remove
female connector from yellow/black wire and
strip insulation from end. Connect stripped
yellow wire with black stripe to (W2) from the
thermostat. (See Figure 28). The first stage
bulb (W1) is connected to W on the furnace
control board. On a call for first stage heat, the
furnace will operate at low fire and the blower will
run at a lower speed. On a call for second stage
heat, the furnace will operate at high fire and the
blower will run at a higher speed. The furnace
will stage between low fire, high fire, and off
depending on the thermostat signal.
O achieve full rated capacity and
– For this
2.
High fire only configuration
– As shipped from
the factory, the low and high terminals on the gas
valve. are connected in parallel (See Figure 29).
This defeats the staging feature and the furnace
operates on high fire only. All of the burners will
operate on a call for heat and the variable speed
blower will operate at a higher speed.
Low fire only configuration
3.
– For this installation,
the high terminal is disconnected (See Figure
30). This defeats the staging feature and the
furnace operates on low fire only. The furnace
will run at reduced firing rate and the variable
speed blower will operate at a lower speed.
Outdoor ambient dependent configuration
4.
For this installation, the high and low terminals
are connected in parallel with an outdoor thermostat (open on rise style) in series with the high
terminal (See Figure 31). CAUTION: DO NOT
CONNECT W2 from outdoor thermostat to the
furnace wiring when using the outdoor ambient
dependent configuration. When the outdoor
temperature is above the set point, the outdoor
thermostat opens keeping the high terminal
closed. The furnace operates in the low fire
mode at a lower blower speed. When the
–
Legend
Field Wiring
Factory Wiring:
Low Voltage
High Voltage
AIR CONDITIONER
CONDENSING UNIT
CLOSED END CONNECTOR
DO NOT REMOVE
BROWN
HI
BROWN
YELLOW
LO C
24
N.O
56
N.C
13
24V
DPST
RELAY
TWO STAGE ROOM
THERMOSTAT
R
Y
G
W
W2
C
Y
BROWNBROWN
YELLOW/BLACK
YELLOW
RED - LOW FIRE
BLUE - HIGH FIRE
CONTROL BOARD
HUM
M1
M2
ORANGE
INTEGRATED
COOL
HEAT
EAC
M3
PRESENT ON ALL MODELS
BLACK
YELLOW
BROWN
XFMR
L1
THESE WIRES ARE NOT
1
1
2
2
3
3
4
4
5
5
WHITE
6
6
RC
YG W
963
852
4
7
3 OR 4 SPEED
MOTOR
C
L
RED
ORANGE
BLUE
BLACK
1
H
MH
ML
28
Figure 28. Two Stage Configuration
Page 29
outdoor thermostat closes, the high fire on gas
valve opens and the furnace operates in the
high fire mode at higher blower speed.
Timed staging configuration
5.
– For this installation, the low and high on the gas valve are
connected in parallel with a delay on make timer
(two wire style) in series with the low fire gas
valve (See Figure 32). CAUTION: DO NOT
CONNECT W2 from thermostat to the furnace
wiring when using timed stage configuration.
When the low fire on the gas valve is energized,
the furnace operates in the low fire mode at a
lower blower speed and the timer begins its
delay function. If the room thermostat is not
satisfied before the timer activates, the furnace
will stage to high fire and the blower will operate
at a higher speed until the room thermostat is
satisfied.
Install the thermostat per the manufacturer's
instructions. The low voltage (24 volt) connections from the thermostat are made at the
terminal strip on the control board in the furnace. See Figures 28-32 for the proper connections for heating only (four wire) and heating/cooling (five wire) applications. The recommended minimum wire gauge for thermostat wiring is shown in Table 10.
The thermostat must not be installed on an
outside wall or any other location where its
operation may be adversely affected. Adverse
affects include radiant loading from fireplaces,
sunlight, or lighting fixtures, and convective loading from warm air registers or electrical appliances.
securely connected to the correct leads on the
terminal strip of the circuit board.
3. The gas line service pressure does not exceed
10.0 in. water column (0.36 psig), and is not less
than 4.5 in. water column (0.16 psig) for natural
gas. For LP gas the line service pressure must
not exceed 14 in. water column (0.51 psig), and
must not be less than 11.0 in. w.c. (0.40 psig).
4. The roll-out and vent safety manual reset
switches are closed. If necessary, press the
red button to reset a switch. DO NOT install a
jumper wire across a switch to defeat its
function. If a switch reopens on start-up, DO
NOT reset the switch without identifying and
correcting the fault condition which caused the
switch to trip.
5. The blower door is in place, closing the door
switch in the line voltage circuit.
6. The gas line has been purged and all connections are leak tight.
Start-up Procedures
After all of the above checks have been made:
1. Set the thermostat to the lowest setting.
2. Close the disconnect(s) to provide line voltage
to the furnace.
3. Follow the procedures given on the operating
instruction label attached to the furnace.
4. Set the thermostat above room temperature
and verify the operating sequence. (See the
Sequence of Operation).
5. After the furnace has run for approximately five
minutes, set the thermostat below room temperature and verify steps (9) through (11) of the
Sequence of Operation.
To check the heat anticipator setting either:
1. Add the current draw of the system components; or
2. Measure the current flow on the thermostat RW circuit after the circulating blower motor has
started.
Set the heat anticipator according to the thermostat manufacturer's instructions for heat
anticipator settings.
START-UP AND ADJUSTMENTS
General
Prior to start-up, verify that:
1. The line voltage power leads are securely
connected, that the polarity of the connections
is correct, and that the furnace is properly
grounded.
2. The thermostat wires (R, W, Y, and G) are
Verifying and Adjusting Firing Rate
The firing rate must be verified for each installation
to prevent over-firing the furnace.
IMPORTANT NOTE:
The firing rate must not exceed the rate
shown on the furnace rating plate. At altitudes above 2000 feet it must not exceed
that on the rating plate less 4% for each
1000 feet.
Follow the procedure below to determine the
firing rate.
1. Shut off all other gas fired appliances.
2. Start the furnace and allow it to run for at least
three minutes.
3. Measure the time (in seconds) required for the
gas meter to complete one revolution.
29
Page 30
Legend
Field Wiring
Factory Wiring:
Low Voltage
High Voltage
AIR CONDITIONER
CONDENSING UNIT
CLOSED END CONNECTOR
DO NOT REMOVE
BROWN
HI
BROWN
YELLOW
56
13
LO C
24
N.O
N.C
24V
DPST
RELAY
TWO STAGE ROOM
THERMOSTAT
R
Y
G
W
C
Y
BROWNBROWN
YELLOW/BLACK
YELLOW
RED - LOW FIRE
BLUE - HIGH FIRE
CONTROL BOARD
HUM
M1
M2
ORANGE
INTEGRATED
COOL
HEAT
EAC
M3
PRESENT ON ALL MODELS
BLACK
YELLOW
BROWN
XFMR
L1
THESE WIRES ARE NOT
1
1
2
2
3
3
4
4
5
5
WHITE
6
6
RC
YG W
963
852
4
7
3 OR 4 SPEED
MOTOR
C
RED
ORANGE
BLUE
BLACK
1
H
MH
ML
L
Legend
Field Wiring
Factory Wiring:
Low Voltage
High Voltage
Figure 29. High Fire Only Configuration
TWO STAGE ROOM
THERMOSTAT
R
Y
G
W
AIR CONDITIONER
CONDENSING UNIT
CLOSED END CONNECTOR
DO NOT REMOVE
BROWN
HI
BROWN
YELLOW
56
13
LO C
24
N.O
N.C
24V
DPST
RELAY
C
Y
YELLOW/BLACK
INTEGRATED
CONTROL BOARD
M1
M2
ORANGE
COOL
HEAT
M3
HUM
YELLOW
RED - LOW FIRE
BLUE - HIGH FIRE
BROWNBROWN
YELLOW
BROWN
XFMR
L1
EAC
THESE WIRES ARE NOT
PRESENT ON ALL MODELS
1
1
2
2
3
BLACK
3
4
4
5
5
WHITE
6
6
RC
YG W
963
852
4
7
3 OR 4 SPEED
MOTOR
C
L
RED
ORANGE
BLUE
BLACK
1
H
MH
ML
Figure 30. Low Fire Only Configuration
30
Page 31
Legend
Field Wiring
Factory Wiring:
Low Voltage
High Voltage
AIR CONDITIONER
CONDENSING UNIT
CLOSED END CONNECTOR
DO NOT REMOVE
BROWN
HI
BROWN
YELLOW
LO C
24
N.O
56
N.C
13
24V
DPST
RELAY
TWO STAGE ROOM
THERMOSTAT
R
Y
G
W
C
Y
BROWNBROWN
YELLOW/BLACK
ODT
YELLOW
RED - LOW FIRE
BLUE - HIGH FIRE
INTEGRATED
CONTROL BOARD
HUM
M1
M2
ORANGE
COOL
XFMR
HEAT
EAC
M3
THESE WIRES ARE NOT
PRESENT ON ALL MODELS
BLACK
YELLOW
BROWN
L1
RC
YG W
963
852
4
1
7
3 OR 4 SPEED
MOTOR
C
H
MH
ML
L
1
2
3
4
5
6
RED
1
ORANGE
2
BLUE
3
BLACK
4
5
WHITE
6
Legend
Field Wiring
Factory Wiring:
Low Voltage
High Voltage
Figure 31. Outdoor Ambient Dependent
TWO STAGE ROOM
THERMOSTAT
R
Y
G
W
24V
DPST
C
Y
YELLOW/BLACK
SDT
CONTROL BOARD
HUM
M1
M2
ORANGE
YELLOW
RED - LOW FIRE
BLUE - HIGH FIRE
BROWNBROWN
INTEGRATED
COOL
HEAT
EAC
M3
PRESENT ON ALL MODELS
BLACK
YELLOW
BROWN
XFMR
THESE WIRES ARE NOT
AIR CONDITIONER
CONDENSING UNIT
CLOSED END CONNECTOR
DO NOT REMOVE
BROWN
HI
BROWN
YELLOW
LO C
24
N.O
56
N.C
13
RELAY
RC
YG W
963
852
4
1
7
3 OR 4 SPEED
MOTOR
C
H
MH
ML
RED
ORANGE
BLUE
BLACK
L
L1
1
1
2
2
3
3
4
4
5
5
WHITE
6
6
Figure 32. Timed Two Stage Configuration
31
Page 32
4. Convert the time per revolution to cubic feet of
gas per hour using Table 11.
5. Multiply the gas flow rate in cubic feet per hour
by the heating value of the gas in Btu per cubic
foot to obtain the firing rate in Btu per hour.
Example:
Verifying and Adjusting Temperature Rise
Verify the temperature rise through the furnace
is within the range specified on the furnace
rating plate. Temperature rises outside the
specified range could result in premature heat
exchanger failure.
• Time for 1 revolution of a gas meter with a 1
cubic foot dial = 40 seconds.
• From Table 11 read 90 cubic feet per hour
of gas.
• Heating value of the gas (obtained from gas
supplier) = 1040 Btu per cubic foot.
• Firing rate = 1040 x 90 = 93,600 Btuh.
6. Adjustments to the firing rate can be made by
adjusting the gas manifold pressure. See the
High Altitude Application section for additional
information of firing rate at elevations above
2000 ft.
The manifold pressure must be set to the
appropriate value for your installation. Refer to
either Table 6 for natural gas or Table 7 for LP/
propane gas to verify the manifold pressure
setting required for your particular installation.
To adjust the manifold pressure, remove the
regulator cap and turn the adjusting screw
clockwise to increase pressure or counterclockwise to reduce pressure. Replace the
regulator cap after adjustments are complete.
Place thermometers in the return and supply air
stream as close to the furnace as possible. The
thermometer on the supply air side must be
shielded from direct radiation from the heat
exchanger to avoid false readings. Adjust all
registers and duct dampers to the desired
position and run the furnace for ten to fifteen
minutes before taking any temperature readings. The temperature rise is the difference
between the supply and return air temperatures. For typical duct systems, the temperature rise will fall within the range specified on the
rating plate with the blower speed at the factory
recommended setting. If the temperature rise
measured is outside the range specified, it may
be necessary to change the blower speed.
Lower blower speeds will increase the temperature rise and higher blower speeds will
decrease the temperature rise. The furnace is
equipped with a multi-speed motor. Heating and
cooling speed selection is made by moving the
leads located in the furnace (See Figure 33
blower relay). The wiring diagram on the furnace and Figure 35 show the speed taps for
adjusting motor speed.
!
CAUTION:
Do not re-drill the burner orifices. If the
orifice size must be changed, use only
new orifices.
YELLOW
24
YELLOW
N.O
56
N.C
13
24V
DPST
RELAY
Figure 33. Blower Relay
If it is desired that the blower operate at the same
speed for heating and cooling, tape off the
unused blower lead and install the jumper wire.
The jumper wire should be connected between
the “cool” terminal on the control board and the
3 OR 4 SPEED
MOTOR
CONTROL BOARD
M2
M1
HUM
INTEGRATED
COOL
HEAT
M3
C
XFMR
EAC
LI
1
ORANGE
2
6 PIN
3
PLUG
4
5
WHITE
6
RED
BLUE
BLACK
H
MH
ML
L
32
Page 33
appropriate terminal on the blower relay. Figure
33 shows high fire heating and cooling using the
same blower speed.
The integrated control is factory set to start the
circulating air blower 30 seconds after the gas
valve is opened. The integrated control is factory wired to turn the blower motor off 120
seconds after the gas valve is closed. If necessary for comfort, the “off” time may be changed
by adjusting the Blower Off jumper on the
integrated control. See Figure 34 for blower on
and off time adjustments.
!
WARNING:
To avoid electric shock, personal injury, or death, disconnect the electric
power before performing any maintenance.
Verifying Burner Operation
To verify operation of the burners, make sure
that the furnace door is in place and that there
is power to the furnace. Set the thermostat to a
temperature above room temperature and ob-
serve the ignition sequence. The burner flame
should carry over immediately between all burners. The flames should be blue, without yellow
tips. Flames should extend from each burner
without lifting off, curling, or floating. After verifying satisfactory flame characteristics, set the
thermostat to a temperature below room temperature and verify that the burner flame extinguishes completely.
Verify Operation of the Supply Air Limit
Switch
To verify operation of the supply air limit switch,
make sure that the blower door is in place and
that there is power to the furnace. Block the
return airflow to the furnace by installing a closeoff plate in place of or upstream of the filter(s).
Set the thermostat to a temperature above
room temperature and verify that the Sequence
of Operation is as described in these instructions. The limit switch should function to turn off
the gas valve within approximately four minutes
(the exact time depending on the efficiency of
the close-off in blocking the return air to the
furnace). The circulating air and combustion
blowers should continue to run when the limit
switch opens. Remove the close-off immedi-
Common
Leads
Connect
Neutral
Lead of
Electronic
Air Cleaner
and/or Humidifier
Here.
R C Y G W
EAC
HUM
Humidifier Tap
(.5A@ 120 VAC)
COM
24 V
3
6
9
2
5
8
1
4
7
Neutrals
63
52
41
3 Amp Fuse
Unused Motor
Leads
M1M2M3
HUM
Blower Off
Timing
Flame Signal
Light (Yellow)
Status
Light (Red)
COOL
HEAT
EAC
90
60
120
180
XFMR
L1
Electronic Air Tap
(.5A@ 120 VAC)
Figure 34. Integrated Control
33
Page 34
ately after the limit switch opens. If the furnace
operates for more than four minutes with no
return air, set the thermostat to a temperature
below room temperature, shut off the power to
the furnace, and replace the limit switch.
DESCRIPTION OF COMPONENTS
Figure 36 shows the location of each of the
functional components described below. Also,
refer to the Sequence of Operation Section of
this manual. If any component of the furnace
For Upflow and Downflow Series Residential Furnaces
BLOWER DECK
LIMIT SWITCH
YELLOW
BLUE
SINGLE OR
TWO STAGE ROOM
THERMOSTAT
W2
C
Y
BROWN
24
N.O
56
N.C
13
24V
DPST
RELAY
SUPPLY AIR
LIMIT SWITCH
WHITE (NEUTRAL)
R
Y
G
W
CLOSED END CONNECTOR
DO NOT REMOVE
BROWN
Legend
Field Wiring
Factory Wiring:
Low Voltage
High Voltage
Hi
Gas Valve
BLUE
AIR CONDITIONER
CONDENSING UNIT
C
Lo
BROWN
FAULT CONDITION
Power On
Limit Circuit Open or External Load On "W"
Pressure Switch is Open with Inducer On
Pressure Switch is Closed with Inducer Off
Ignition Failure (Check Ground)
115 VAC & Neutral Reversed or no Ground
False Flame or Gas Valve Relay Shorted
Power Off
FAULT CONDITION
Low Flame Sensor Signal
Flame Present
BLUE
BLACK 120V
GROUND
YELLOW/BLACK
STATUS
LIGHT
1 FLASH
2 FLASHES
3 FLASHES
4 FLASHES
5 FLASHES
Continuous
FLAME
YELLOW
LIGHT
Continuous
Flash
FLAME ROLL-OUT
SWITCH
YELLOW
RED (Low Fire)
BLUE (High-Fire)
RED
ON
OFF
ON
BLUE
SAFETY SWITCH
FLAME SENSOR
VENT
IGNITOR
R
INDUCER
BLUE
RED
YELLOW
112
C
ORANGE
WHITE W/BLK STRIPES
BLK W/ WHITE STRIPES
COM
24 V
R
C
Y
G
W
6
3
9
852
4
71
BROWN
NEUTRALS
EAC
HUM
63
52
BLACK
BLACK
BLACK
BLACK
14
2
1
1
2
2
WHITE
GREEN
3 AMP FUSE
HUM
PRESSURE
SWITCH
M3
M2
M1
ORANGE
ORANGE
BLACK
TRANSFORMER
24 V
BLOWER OFF
COOL
XFMR
HEAT
EAC
THESE WIRES ARE NOT
PRESENT ON ALL MODELS
BLACK
WHITE
TWIN
L1
BLACK
If any of the original wire as supplied with the
furnace must be replaced, it must be replaced
with wiring material having a temperature rating
of at least 105° C.
Use copper conductors only.
BLOWER DOOR
SWITCH
WHITE
120 V
BLACK
FLAME
STATUS
3 OR 4 SPEED
MOTOR
C
BLACK
WHITE
1
1
2
3
4
5
6
RED
2
ORANGE
3
BLUE
4
BLACK
5
6
WD#7105460
H
MH
ML
L
Figure 35. Wiring Diagram for Upflow and Downflow Models
must be replaced, use only factory authorized
replacement parts. See the Replacement Parts
List for the factory authorized replacement for
each component.
Flame Sensor
The flame sensor acts to prove that flame has
carried over from the igniter to the opposite end
burner. If no flame is sensed, the furnace will
shut down within 7 seconds of ignition.
Flame Roll-Out Switch
The flame roll-out switch verifies that the burner
flames are drawn into the heat exchanger
tubes. If the burner flames are not properly
drawn into the heat exchanger, the flame rollout switch will open. The circulating air blower
(and combustion blower, if connected) will
continue to operate if the flame roll-out switch
opens.
Gas Valve
The gas valve controls the flow of gas to the
burners. When the gas valve is energized it
automatically opens and regulates the gas
pressure in the manifold.
Supply Air Limit Switch
The supply air limit switch prevents the air
temperature leaving the furnace from exceeding
the maximum allowable outlet air temperature.
Vent Safety Switch
The vent safety switch shuts the furnace down
if the vent becomes blocked or restricted.
MAINTENANCE
It is recommended that the furnace be checked
yearly. At a minimum, this check should include
the following items.
!
WARNING:
To avoid electrical shock, personal injury, or death, turn off the electric power
at the disconnect or the main service
panel before making any electrical connections.
Pressure Switch
The pressure switch verifies that the inducer is
drawing the combustion gases through the heat
exchanger.
35
Page 36
!
WARNING:
Products of combustion must not be
allowed to enter the living space. Failure
to prevent products of combustion from
being circulated into the living space can
create potentially hazardous conditions
including carbon monoxide poisoning
that could result in personal injury or
death.
Vent System
Check the vent pipe to ensure that it is not
corroded or blocked by debris. Any corroded
section of vent pipe must be replaced, and any
obstruction or blockage must be removed prior
to operating the furnace.
Air Filter(s)
!
WARNING:
Never operate the furnace without a filter
in place. Dust and lint in the return air can
build up on internal components, resulting in loss of efficiency, equipment damage, and possible fire.
Air filter(s) are not supplied with the furnace
as shipped from the factory.
The installer must provide a high velocity filter
and rack for a filter in the return air duct adjacent
to the furnace, or in a return air grill to the furnace.
Filters should be changed or cleaned monthly
during the heating season. New or newly
renovated homes may require more frequent
changing until the construction dust has been
removed.
Filters for side return and bottom return applications are available from your local distributors.
Lubrication
The bearings in the circulating air blower motor
and inducer blower used in these furnaces are
pre-lubricated and sealed at the factory. No
further oiling of the bearings is required for the
life of the motor.
Blower Compartment
The blower compartment should be cleaned
monthly during the heating and cooling seasons
to remove any dirt and lint that may have
accumulated in the compartment or on the
blower and motor. Dirt and lint can create
excessive loads on the motor resulting in higher
than normal operating temperatures and shortened service life.
Heat Exchanger and Burner Maintenance
The furnace should operate for many years
without soot buildup in the flue passageways,
however, the flue passageways, the vent system, and the burners should be inspected and
cleaned (if required) by a qualified serviceman
annually to ensure continued safe operation.
Particular attention must be given to identify
deterioration from corrosion or other sources.
!
WARNING:
Holes in the vent pipe or heat exchanger
can cause products of combustion to
enter the home. Replace the vent pipe or
heat exchanger if leaks are found. Failure
to prevent products of combustion from
being circulated into the living space can
create potentially hazardous conditions
including carbon monoxide poisoning
that could result in personal injury or
death.
Cleaning Of Flue Passages
If the flue passages must be cleaned, follow the
steps below. See Figure 36 for component
location and identification.
1. Shut off the gas supply to the furnace either at
the meter or at the manual valve in the gas
supply piping.
2. Turn off all power to the furnace and set
thethermostat to the lowest temperature
setting.
3. Remove the louvered door from the furnace.
4. Turn the gas control lever to the OFF position.
5. Disconnect the wires from the gas valve,
igniter, flame sensor, combustion air motor,
flame roll-out switch, blocked vent switch, overtemperature limit switch, pressure switch.
!
CAUTION:
Label all wires prior to disconnection
when servicing controls. Wiring errors
can cause improper and dangerous operation.
6. Remove the silicone rubber tube from the
collector pan.
7. For *TA upflow models: Remove the screws
that hold the vent control assembly to the top
panel.
8. Remove the nuts that hold the combustion air
motor to the collector pan, and remove the
complete combustion air blower and combustion tube assembly. BE CAREFUL NOT TO
BREAK THE SEALS AT EACH END OF THE
COMBUSTION AIR TUBE.
9. Remove the screws that hold the collector pan
in place, and remove the collector pan from the
furnace.
10. Using wrenches, separate the ground-joint
union in the gas supply piping at the furnace.
11. Remove the piping between the gas valve and
the ground-joint union, if necessary.
12. Remove the screws that hold the burner assembly in place and remove the burner
assembly. BE EXTREMELY CAREFUL NOT
TO DAMAGE THE IGNITER WHILE REMOVING THE BURNER ASSEMBLY.
13. The furnace heat exchanger tubes can now be
cleaned by the use of a round wire brush
attached to a length of high grade stainless steel
cable, such as drain cleanout cable. Attach
variable speed reversible drill to the other end
of the spring cable. Slowly rotate the cable with
the drill and insert it into the top portion of the heat
exchanger. While reversing the drill, work the
cable in and out several times to obtain sufficient
cleaning. Repeat this sequence for each heat
exchanger tube.
14. When all heat exchanger tubes have been
cleaned, any debris inside the tubes can be
removed with the nozzle of a vacuum cleaner.
15. With a light, check the condition of the upper and
lower sections of the heat exchanger tube.
16. Inspect the burners and clean them (if necessary) with a soft wire brush and/or the nozzle
37
Page 38
of a vacuum cleaner. BE EXTREMELY CARE-
FUL NOT TO DAMAGE THE IGNITER
WHILE CLEANING THE BURNER.
17. Replace all the parts in reverse order from
which they were removed.
18. Follow the lighting instructions found on the
furnace door to return the furnace to operation.
Verify proper operation after servicing.
Cleaning of Burners
If the burners must be cleaned, follow the steps
below. See Figure 36 for component location and
identification.
1. Shut off the gas supply to the furnace either at
the meter or at a manual valve in the supply
piping.
2. Turn off all power to the furnace and set the
thermostat to the lowest temperature setting.
3. Remove the upper louvered door from the
furnace.
4. Turn the gas control lever to the OFF position.
5. Disconnect the wires from the gas valve,
igniter, and flame sensor.
6. Using wrenches, separate the ground-joint
union in the gas supply piping at the furnace.
7. Remove the piping between the gas valve and
the ground-joint union, if necessary.
8. Remove the screws that hold the burner assembly in place and remove the burner assembly. BE EXTREMELY CAREFUL NOT TO
DAMAGE THE IGNITER WHILE REMOVING THE BURNER ASSEMBLY.
9. Inspect the burners and clean them (if necessary) with a soft wire brush and/or the nozzle
of a vacuum cleaner. BE EXTREMELY CARE-
FUL NOT TO DAMAGE THE IGNITER
WHILE CLEANING THE BURNER.
10. Replace all the parts in reverse order from
which they were removed.
11. Follow the lighting instructions found on the
furnace door to return the furnace to operation.
Verify proper operation after servicing.
SYSTEM OPERATION INFORMATION
General
Proper maintenance is most important to achieve
the best performance from a furnace. Follow these
instructions for years of safe, trouble free operation.
1. Do not place combustible materials on or against
the furnace cabinet or within 6 inches of the vent
pipe.
2. Do not store gasoline or any other flammable
vapors and liquids in the vicinity of the furnace.
3. Change or replace the air filters monthly during
any period when the circulating blower is operating regularly.
4. Always replace the doors on the furnace after
servicing or cleaning/changing the filters. Do
not operate the furnace without all doors and
covers in place.
5. Avoid operating the furnace when windows and
doors are open.
6. Be sure that the thermostat is properly
installed and is not being affected by drafts
or heat from lamps or other appliances.
Sequence of Operation
The operating sequences for the heating, cooling,
and fan modes are described below. Refer to the
field and furnace wiring diagrams; Figures 26, 27,
28, 29, 30, 31, 32, 33, 34 and 35.
Heating Mode:
1. On a call for heat the thermostat closes, applying 24 VAC to the W terminal on the control
board.
2. The control board checks for continuity on the
24 VAC limit control circuit (over-temperature
limit switch, flame rollout switches and blocked
vent switch in series). If an open limit is detected
the control board will energize the inducer and
the conditioned air blower. All other system
functions will be inoperable until the limit circuit
closes. While the limit is open, the red LED will
pulse at a rate of 1 blink per unit time.
3. The furnace control checks for continuity across
the pressure switch (24 VAC). If the pressure
switch is closed the heat mode sequence will
not continue. If it remains closed for 10 seconds
the red LED will blink 3 times repetitively until the
fault condition clears.
4. The inducer is energized.
5. The pressure switch will close. If the pressure
switch does not close after 10 seconds the fault
LED will blink 2 times repetitively and the inducer
will continue to run until the switch is closed.
6. The inducer will pre-purge for 30 seconds and
then the igniter will start its warm-up as follows:
Initial Power up: After 30 seconds of igniter
warm-up the gas valve (24 VAC) will then open.
The igniter circuit will stay energized for 3
seconds after the gas valve opens.
After Initial Power up: The control has a programmed adaptive ignition feature which varies
38
Page 39
the warm-up period as follows: If ignition is
successful the warm-up is reduced by 3seconds on each subsequent call for heat until
ignition failure occurs. Upon ignition failure, the
warm-up is increased by 3-seconds on the
next try. If successful, the timing remains fixed
at this level. In general, whenever ignition failure
occurs the warm-up interval is increased by
3-seconds on the next try. And if successful, it
remains there. Minimum and maximum warmup time limits are set at 6 and 54-seconds,
respectively.
7. The furnace control must prove flame via the
flame sensor 5 seconds after the gas valve
opens. If flame is sensed, all burners are on and
the igniter cools off. If no flame is sensed, the gas
valve closes immediately and the inducer continues to run. A second trial for ignition (step 6)
begins if no flame is sensed on the fifth try for
ignition, the furnace control is locked and the red
LED will blink 4 times repetitively. The thermostat must be opened for at least ten seconds to
reset the furnace control after a lock out.
Otherwise, the furnace will attempt another
ignition sequence in 1 hour.
8. The furnace control energizes the circulating
air blower on the heating speed 30 seconds
after the gas valve circuit is energized .
9. When the thermostat has been satisfied, gas
valve is de-energized.
10. The inducer is de-energized after a 30-second
postpurge.
2. The furnace control energizes the circulating
blower (115 VAC) on the cooling speed.
3. When the thermostat is satisfied, the G and Y
terminals on the control board are de-energized
opening the compressor contactor.
4. The circulating air blower is de-energized after
a 90-second delay.
Fan Mode:
1. On a call for fan operation, the thermostat
applies 24 VAC to the G terminal on the furnace
control board.
2. The circulating air blower is energized immediately on the low heating speed.
3. If the furnace is operated in the continuous ON
position at the thermostat and is then switched
to AUTO, the circulating blower will operate for
a specified delay (factory set at 120 seconds).
Furnace Fails to Operate
If the furnace does not operate check the
following:
1. Is the thermostat operating properly?
2. Are the blower compartment door(s) in place?
3. Is the furnace disconnect closed?
4. Has the circuit breaker tripped or the control
board fuse burned open?
5. Is the gas turned on?
6. Are any manual reset switches open?
7. Is the filter dirty or plugged?
8. Is the flame sensor coated? (Remove and
clean with emery cloth.)
11. The furnace control keeps the circulating air
blower energized for 120 seconds (factory set)
or 60, 90, or 180 seconds (field adjustable).
(See Figure 34.)
12. Abnormal conditions: If a limit opens during
operation, the inducer and circulating air blower
continue to operate. The gas valve is deenergized immediately. The blowers continue
to operate until the limit closes. When the limit
closes the inducer blower is de-energized
immediately. The circulating air blower continues to operate for the specified delay (factory
set at 120 seconds).
Cooling Mode:
1. On a call for cooling the thermostat closes,
applying 24 VAC to the G and Y terminals on the
furnace control. This closes the compressor
contactor.
If the furnace locks out after 5 attempts for
ignition, it will try again every hour if a call for heat
remains. If the inducer and circulating air blowers are operating, and items 1 through 8 have
been checked, press the red reset button on the
vent safety switch (See Figure 36). If the furnace operates after depressing the reset button, contact a qualified serviceman to identify
and repair the problem.
If the furnace continues to not operate, depress
the red reset buttons on the flame roll-out
switches. (See Figure 36.) If the furnace operates after depressing the reset buttons, contact
a qualified servicemen to identify and repair the
problem.
Twinning
The two-stage furnace may not be twinned.
39
Page 40
INSTALLATION/PERFORMANCE CHECK LIST
LOCATION _________________ CITY ___________________ STATE ______________
INSTALLER ________________ CITY ___________________ STATE ______________
UNIT MODEL NUMBER ________________________________
UNIT SERIAL NUMBER _________________________________
Minimum Clearances per Table 1? _____
Electrical Connections tight? __________
Line Voltage Polarity correct? _________
Supply Voltage: _________ Volts
Blower Motor HP: ___________________
FUEL TYPE:
Natural Gas _______________________
LP/Propane ________________________
Gas Piping Connections
leak-tested? ______________________
Gas Line Pressure: _________________
(in. water column, with furnace operating)
Manifold Pressure: __________________
(in. water column, with furnace operating)
Is there adequate fresh air supply for
combustion and ventilation? ___________
Are Flue Connections tight? _____________
Is there Proper Draft? _________________
Is Vent free from restrictions? ___________
Is the Filter(s) secured in place? _________
Is the Filter(s) clean? __________________
Has the Thermostat been calibrated? _____
Is the Thermostat level? ________________
Is the Heat Anticipator Setting correct? ____
Has the Owner's Information been reviewed
with the homeowner? __________________
Has the Literature Package been left near
the furnace? _________________________
Furnace Input: _________________ (Btuh)
Supply Air Temperature: _________ (° F)
Return Air Temperature: _________ (° F)
Temperature Rise: ______________ (° F)
¢708509>¤
O'Fallon, MO
7085090
7085090 (Replaces 7084370)
Specifications and illustrations subject to change without
notice and without incurring obligations. Printed in
U.S.A. (11/05)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.