T3BN Series High Effi ciency Commercial Split System
These units have been designed and tested for capacity and effi ciency in accordance with A.R.I. Standards. Split System Heat Pump units, when combined with
our air handlers, offer a high quality, matched heating and cooling system.
These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of heating and/or air conditioning appliances.
Some local codes require licensed installation/service personnel for this type of
equipment. Read all instructions carefully before starting the installation.
OPERATING INSTRUCTIONS
TO OPERATE YOUR HEAT PUMP
FOR COOLING —
1. Set the thermostat system switch to COOL
and the thermostat fan switch to AUTO. (See
Figure 1)
2. Set the thermostat temperature to the
desired temperature level using the
temperature selector. Please refer to
the separate detailed thermostat user’s
manual for complete instructions regarding
thermostat programming. The outdoor unit
and indoor blower will both cycle on and off
to maintain the indoor temperature at the
desired heating level.
2. Set the thermostat temperature to the desired
temperature level using the temperature
selector. Please refer to the separate
detailed thermostat user’s manual for
complete instructions regarding thermostat
programming. The outdoor unit and indoor
blower will both cycle on and off to maintain
the indoor temperature at the desired cooling
level.
NOTE: If the thermostat temperature level is
re-adjusted, or the thermostat system switch
is repositioned, the outdoor unit may not
start immediately. The outdoor unit contains
a protective timer circuit which holds the unit
off for approximately fi ve minutes following a
previous operation, or the interruption of the
main electrical power.
TO OPERATE YOUR HEAT PUMP
FOR HEATING —
1. Set the thermostat system switch to HEAT
and the thermostat fan switch to AUTO. (See
Figure 1)
NOTE: If the thermostat temperature level is
re-adjusted, or the thermostat system switch
is repositioned, the outdoor unit may not
start immediately. The outdoor unit contains
a protective timer circuit which holds the unit
off for approximately fi ve minutes following
a previous operation, or the interruption of
the main electrical power.
Emergency Heat:
The thermostat includes a system switch
position termed EM. HT. This is a back-up
heating mode to be used only if there is a
suspected problem with the outdoor unit. With
the system switch set to EM. HT. the outdoor
unit will be locked off, and supplemental heat
(typically electric resistance heating) will be
used as a source of heat. Sustained use of
electric resistance heat in place of the heat
pump will result in an increase in electric
utility costs.
Defrost:
During cold weather heating operation, the
outdoor unit may develop a coating of snow
and ice on the heat transfer coil. This is
SYSTEM
MODE
2
FAN
SWITCH
Figure 1. Typical Thermostat
TEMPERATURE
SENSOR
normal, and the unit will periodically defrost
itself. During the defrost cycle, the outdoor
fan will stop, and the compressor will continue
to run and heat the outdoor coil, causing the
snow and ice to melt. After the snow and ice
have melted, some steam may rise from the
outdoor unit as the warm coil causes some
melted frost to evaporate.
TO OPERATE YOUR HEAT PUMP
FOR AUTOMATIC COOLING AND
HEATING—
1. Set the thermostat system switch to AUTO
and the thermostat fan switch to AUTO. (See
Figure 1)
Note: Thermostats will vary. Some models
will not include the AUTO mode, and others
will have the AUTO in place of the HEAT and
COOL, and some will include all three.
2. Set the thermostat temperature to the
desired heating and cooling temperature
level(s). The outdoor unit and the indoor
blower will then cycle on and off in either
the heating or cooling mode of operation as
required to automatically maintain the indoor
temperature within the desired limits.
TO SHUT OFF YOUR HEAT
PUMP—
Set the thermostat system switch to OFF and the
thermostat fan switch to AUTO. (See Figure 1)
The system will not operate, regardless of the
thermostat temperature selector(s) setting.
TO OPERATE THE INDOOR
BLOWER CONTINUOUSLY—
Set the thermostat fan switch to ON (See Figure
1). The indoor blower will start immediately, and
will run continually until the fan switch is reset
to AUTO.
TO MAINTAIN YOUR HEAT PUMP—
CAUTION:
Be certain the electrical power to
the outdoor unit and the furnace/air
handler is disconnected before
doing the following recommended
maintenance.
1. Regularly:
a. Clean or replace the indoor air fi lter at the
start of each heating and cooling season,
and when an accumulation of dust and
dirt is visible on the air fi lter. Inspect the
fi lter monthly.
b. Remove any leaves and grass clippings
from the coil in the outdoor unit, being
careful not to damage the aluminum
fi n s .
c. Check for any obstruction such as twigs,
sticks, etc.
d. Certain models have external panels
fabricated from a premium grade
of steel designed to inhibit corrosion. For such units, if the unit is
located in a coastal region or other area
subjected to high concentrations of salt,
then the unit should be hosed off after
storms and monthly otherwise to maintain
its new appearance.
CAUTION:
Do not over-oil, or oil motors not
factory-equipped with oil tubes. The
compressor is hermetically “sealed”
and does not require lubrication.
2. Before Calling a Service Technician, Be
Certain:
The continuous indoor blower operation can be
obtained with the thermostat system switch set
in any position, including OFF.
The continuous indoor blower operation is
typically used to circulate the indoor air to
equalize a temperature unbalance due to a sun
load, cooking, or fi replace operation.
a. The unit thermostat is properly set—see
“To Operate Your Heat Pump for Cooling”
and “To Operate Your Heat Pump for
Heating.”
b. The unit disconnect fuses are in good
condition, and the electrical power to the
unit is turned on.
3
Read Your Warranty
Please read the separate warranty document
completely. It contains valuable information
about your system.
GENERAL INFORMATION
Read the following instructions completely before
performing the installation.
Outdoor Unit Section — Each outdoor unit is
shipped with a refrigerant holding charge.
the instructions provided with the equipment prior
to performing the installation and operational
checkout of the equipment.
Brazing Operations — Installation of equipment
may require brazing operations. Safety codes
must be complied with. Safety equipment (e.g.;
safety glasses, work gloves, fi re extinguisher,
etc.) must be used when performing brazing
operations.
NOTE: DO NOT USE ANY PORTION OF
THE CHARGE FOR PURGING OR LEAK
TESTING.
Matching indoor coils and air handlers may be
shipped with a small holding charge to pressurize
them to keep out contaminants. To release the
pressure, read the indoor section installation
instructions carefully.
Liquid and Suction Lines — Fully annealed,
refrigerant grade copper tubing should be used
when installing the system. Refrigerant suction
line tubing should be fully insulated.
Field Connections for Electrical Power
Supply — All wiring must comply with current
provisions of the “National Electrical Code”
(ANSI/NFPA 70) and with applicable local
codes having jurisdiction. The minimum size of
electrical conductors and circuit protection must
be in compliance with information listed on the
outdoor unit data label.
SAFETY CONSIDERATIONS
Pressures within the System — Split
system heat pump equipment contains liquid
and gaseous refrigerant under pressure.
Installation and servicing of this equipment
should be accomplished by qualifi ed, trained
personnel thoroughly familiar with this type of
equipment. Under no circumstances should the
Homeowner attempt to install and/or service
the equipment.
Labels, Tags, Precautions — When working
with this equipment, follow all precautions in the
literature, on tags, and on labels provided with
the equipment. Read and thoroughly understand
WARNING:
Ensure all electrical power to the unit
is off prior to installing or servicing the
equipment. Failure to do so may cause
personal injury or death.
SITE PREPARATION
Unpacking Equipment — Remove the
cardboard carton and User’s Manual from the
equipment. Take care to not damage tubing
connections when removing from the carton.
Inspect for Damage — Inspect the equipment
for damage prior to installing the equipment at
the job site. Ensure coil fi ns are straight and, if
necessary, comb fi ns to remove fl attened and
bent fi ns.
Preferred Location of the Outdoor Unit at the
Job Site — Conduct a survey of the job site to
determine the optimum location for mounting
the outdoor unit. Overhead obstructions,
poorly ventilated areas, and areas subject to
accumulation of debris should be avoided. The
outdoor unit should be installed no closer than
18 inches from the outside walls of the facility
and in an area free from overhead obstructions
to ensure unrestricted airflow through the
outdoor unit.
Facility Prerequisites — Electrical power
supplied must be adequate for proper operation
of the equipment. The system must be wired and
provided with circuit protection in accordance
with local building codes and the National
Electrical Code.
4
INSTALLING THE OUTDOOR UNIT
Slab Mount — The site selected for a slab mount
installation requires a stable foundation and one
not subject to erosion. The slab should be level
and anchored (if necessary) prior to placing the
equipment on the slab.
Cantilever Mount — The cantilever mount
should be designed with adequate safety factor
to support the weight of the equipment, and for
loads subjected to the mount during operation.
Installed equipment should be adequately
secured to the cantilever mount and levelled
prior to operation of the equipment.
The maximum recommended interconnecting
refrigerant line length is 75 feet, and the
vertical elevation difference between the indoor
and outdoor sections should not exceed 20
feet. Consult long line application guide for
installations in excess of these limits.
Filter Dryer Installation — A fi lter dryer is
provided with the unit and installed inside the
outdoor unit.
Optional Equipment — Optional equipment
(e.g.: liquid line solenoid valves, etc.) should
be installed in strict accordance with the
manufacturer’s installation instructions.
Roof Mount — The method of mounting should
be designed so as not to overload roof structures
nor transmit noise to the interior of the structure.
Refrigerant and electrical line should be routed
through suitably waterproofed openings to
prevent water leaking into the structure.
INSTALLING THE INDOOR UNIT
The indoor section should be installed before
proceeding with routing of refrigerant piping.
Consult the Installation Instructions of the indoor
unit (i.e.: air handler, furnace, etc.) for details
regarding installation.
CONNECTING REFRIGERANT
TUBING BETWEEN THE INDOOR
AND OUTDOOR UNIT
General — Once outdoor and indoor unit
placement has been determined, route refrigerant
tubing between the equipment in accordance with
sound installation practices. Refrigerant tubing
should be routed in a manner that minimizes the
length of tubing and the number of bends in the
tubing. Refrigerant tubing should be supported
in a manner that the tubing will not vibrate or
abrade during system operation. Tubing should
be kept clean of foreign debris during installation
and installation of a liquid line fi lter drier is
recommended if cleanliness or adequacy of
system evacuation is unknown or compromised.
Every effort should be made by the installer
to ensure that the fi eld installed, refrigerant
containing components of the system have been
installed in accordance with these instructions
and sound installation practices so as to insure
reliable system operation and longevity.
ELECTRICAL CONNECTIONS
WARNING:
Turn off all electrical power at the main
circuit box before wiring electrical
power to the outdoor unit. Failure to
comply may cause severe personnel
injury or death.
Wiring Diagram/Schematic — A wiring
diagram/schematic is located on the inside cover
of the electrical box of the outdoor unit. The
installer should become familiar with the wiring
diagram/schematic before making any electrical
connections to the outdoor unit.
Outdoor Unit Connections — The outdoor
unit requires both power and control circuit
electrical connections. Refer to the unit wiring
diagram/schematic for identifi cation and location
of outdoor unit fi eld wiring interfaces.
Control Circuit Wiring — The outdoor unit is
designed to operate from a 24 VAC Class II control
circuit. Control circuit wiring must comply with
the current provisions of the “National Electrical
Code” (ANSI/NFPA 70) and with applicable local
codes having jurisdiction.
Thermostat connections should be made in
accordance with the instructions supplied with
the thermostat, and with the instructions supplied
with the indoor equipment. A typical commercial
installation with a heat pump thermostat and air
handler are shown on the next page.
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.