Nordyne S3BM-120G Owner's Manual

Outdoor Air Conditioner
USER’S INFORMATION AND INSTALLATION INSTRUCTIONS
S3BM-120G High Effi ciency Commercial Split System
Read this owner information thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain this unit. Keep this literature where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your NORDYNE Servicing Contractor (Service PRO).
Any additions, changes, or conversions required for the appliance to satisfactorily meet the application needs must be made by a qualifi ed installer, service agency, or the gas supplier using factory specifi ed and approved parts.
These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Please read all instructions carefully before starting the installation.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
IMPORTANT
TABLE OF CONTENTS
USER’S INFORMATION
SAFETY INFORMATION .............................................3
OPERATING INSTRUCTIONS ..................................... 3
Cooling Operation ....................................................3
Heating Operation ...................................................3
Operating the Indoor Blower Continuously .............. 3
System Shutdown ....................................................3
SYSTEM MAINTENANCE ...........................................3
Regular Cleaning ..................................................... 3
Motor Lubrication ..................................................... 3
TROUBLESHOOTING .................................................3
INSTALLER’S INFORMATION
SAFETY INFORMATION .............................................4
Pressures Within The System ................................. 4
Labels, Tags and Precautions .................................. 4
Brazing Operations .................................................. 4
GENERAL INFORMATION ..........................................4
Condensing Unit ......................................................4
Liquid and Suction Lines .........................................4
Field Connections for Electrical Supply ...................4
SITE PREPARATION ...................................................4
Unpacking the Equipment .......................................4
Inspect For Damage ................................................4
Preferred Location Of The Outdoor Unit ..................4
Facility Prerequisites................................................4
Minimum Circuit Ampacity .......................................5
Maximum Fuse/Circuit Breaker Size ....................... 5
INSTALLING THE OUTDOOR UNIT ............................5
Slab Mount ..............................................................5
Cantilever Mount......................................................5
Roof Mount ..............................................................5
INSTALLING THE INDOOR UNIT ................................5
CONNECTING REFRIGERANT TUBING ....................5
General .................................................................... 5
Optional Equipment .................................................5
ELECTRICAL REQUIREMENTS ................................. 6
Pre-Electrical Checklist .................................................6
Wiring Diagram/Schematic ...........................................6
Supply Control Circuit Wiring ........................................6
Line Voltage ..................................................................6
Outdoor Unit Connections ............................................ 6
Disconnect Switch ........................................................ 6
Optional Equipment ......................................................6
Thermostat Connections ..............................................6
Grounding ..................................................................... 7
STARTUP AND CHECKOUT .......................................7
Air Filters ......................................................................7
Thermostat ...................................................................7
Outdoor Unit ................................................................. 7
System Cooling ............................................................7
Short Cycle Protection .................................................. 7
Heating .........................................................................7
Indoor Blower ...............................................................7
Adjustment Of Refrigerant Charge ............................... 8
Refrigerant Charging Chart ..........................................8
Optional Equipment ......................................................8
2
ACCESSORIES ...........................................................8
Condensing Unit ......................................................8
USER’S INFORMATION
SAFETY INFORMATION
Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
OPERATING INSTRUCTIONS
Cooling Operation
1. Set the thermostat system switch (Figure 1) to COOL or AUTO and the thermostat fan switch to AUTO.
2. Set the thermostat temperature selector to the desired temperature level. The outdoor fan(s), compressor(s), and blower motor(s) will all cycle on and off to maintain the indoor temperature at the desired cooling level.
Heating Operation
1. Set the thermostat system switch (Figure 1) to HEAT or AUTO and the thermostat fan switch to AUTO.
2. Set the thermostat temperature selector to the desired temperature level. The furnace/air handler blower motor(s) will cycle on and off to maintain the indoor
temperature at the desired heating level.
Fan Mode
Fan Mode is typically used to circulate the indoor air to equalize a temperature imbalance due to a solar load, cooking, or fi replace operation. The continuous indoor blower operation can be obtained with the system switch set in any position, including OFF.
Set the thermostat’s fan switch to ON. will start immediately, and run continuously until the fan switch is reset to AUTO.
Temperature
Selector
Thermometer
The indoor blower
System Shutdown
Set the thermostat system switch (See Figure 1) to OFF and the thermostat fan switch to AUTO. NOTE: The system will not operate, regardless of the temperature selector setting.
SYSTEM MAINTENANCE
CAUTION:
Shut off all electrical power to the unit before performing any maintenance or service on the system. Failure to comply may result in personal injury or death.
Proper maintenance is most important to achieve the best performance from the appliance and should be performed by a qualifi ed service technician at least once a year. Follow the maintenance schedule and the instructions below for years of safe, trouble free operation.
Regular Cleaning
• Clean or replace the indoor air fi lter at the start of each heating and cooling season, and when an accumulation of dust and dirt is visible on the air fi lter.
• Remove any leaves and grass clippings from the coil in the outdoor unit, being careful not to damage the aluminum fi ns.
• Check for obstructions, such as twigs, sticks, etc.
Motor Lubrication
CAUTION:
Do not over-fi ll or oil a motor that is not factory equipped with oil tubes. The compressor in this unit is factory sealed and does not require lubrication.
If the furnace/air handler blower motor(s) and the outdoor unit fan motor(s) have oil tubes at the motor bearings, apply 10 drops of SAE No. 20 motor oil to each oil tube before each cooling season.
Fan Switch
Figure 1. Typical Thermostat
System Switch
TROUBLESHOOTING
If the unit fails to operate, check the following:
• The thermostat is properly set. See Cooling Operation for air conditioning or Heating Operation for furnace or air handler.
• The unit disconnect fuses are in good condition and the electrical power to the unit is turned on.
3
INSTALLER’S INFORMATION
SAFETY INFORMATION
Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
WARNING:
Shut off all electrical power to the unit before performing any maintenance or service on the system. Failure to comply may result in personal injury or death.
Pressures within the System
Split system air conditioning equipment contain liquid and gaseous refrigerant under pressure. Installation and servicing of this equipment should be performed by qualifi ed, trained personnel thoroughly familiar with this type of equipment. Under no circumstances should non-qualifi ed personnel attempt to install and/or service the equipment.
Labels, Tags, Precautions
When working with this equipment, follow all precautions in the literature, on tags, and labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment.
Brazing Operations
Installation of equipment may require brazing operations. Safety codes must be complied with. Safety equipment (e.g.; safety glasses, work gloves, fi re extinguisher, etc.) must be used when performing brazing operations.
Please consult your dealer for maintenance information and availability of maintenance contracts. Please read all instructions before installing the unit.
Condensing Unit
Each condensing unit is shipped with a refrigerant holding charge adequate to maintain a positive pressure to keep out contaminants. NOTE: Do not use any portion of the charge for purging or leak testing.
Liquid and Suction Lines
Refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
When condensing unit is matched with two air handlers (two coils) or a dual circuit evaporator coil, refrigerant tubing should be branched between both evaporator coils or circuits using equal lengths of tubing to maintain equal evaporator/circuit performance.
Field Connections for Electrical Power Supply
All wiring must comply with applicable local codes having jurisdiction. The minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label.
SITE PREPARATION
Unpacking Equipment
Remove the cardboard carton and User’s Manual from the equipment. Take care not to damage the tubing connections when removing the carton.
Inspect for Damage
Inspect the equipment for damage prior to installing the equipment at the job site. Ensure coil fi ns are straight and, if necessary, comb fi ns to remove fl attened and bent fi ns.
GENERAL INFORMATION
This unit has been designed and tested for capacity and effi ciency in accordance with A.R.I. 340/360 Standards. This unit will provide many years of safe and dependable comfort, providing it is properly installed and maintained. With regular maintenance, this unit will operate satisfactorily year after year. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment failure, it is recommended that periodic maintenance be performed on this unit. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools.
4
Preferred Location of the Outdoor Unit
Conduct a survey of the job site to determine the optimum location for mounting the outdoor unit. Overhead obstructions, poorly ventilated areas, and areas subject to accumulation of debris should be avoided. The outdoor unit should be installed no closer than 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airfl ow through the outdoor unit.
Facility Prerequisites
Electrical power supplied to the unit must be adequate for proper operation of the equipment. The system must be wired and provided with circuit protection in accordance with local building codes.
Loading...
+ 8 hidden pages