Nordyne R-410A User Manual

Page 1
Outdoor Heat Pump
User’s Manual / Installation Instructions
Two Stage R-410A Split System
Premium Model Shown
IMPORTANT
Please read this information thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain this unit. Keep this literature where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your NORDYNE Servicing Contractor (Service PRO).
These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Please read all instructions carefully before starting the installation.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
Page 2
2
Page 3
USER INFORMATION
Safety Information ........................................ 4
About the Heat Pump ................................... 4
Operating Instructions ................................. 4
Cooling Operation .......................................4
Heating Operation ...................................... 4
Emergency Heat .........................................4
Defrost Operation .......................................4
INSTALLER INFORMATION
Safety Information ........................................ 6
Pressures Within the System .....................6
Labels, Tags, and Precautions .................... 6
Brazing Operations .....................................6
General Information .....................................7
Outdoor Unit ...............................................7
Liquid and Suction Lines ............................ 7
Field Connections for Electrical Power
Supply.........................................................7
Site Preparation ............................................ 7
Unpacking the Equipment .......................... 7
Inspect for Damage .................................... 7
Preferred Location of the Outdoor Unit ....... 7
Facility Prerequisites .................................. 7
Minimum Circuit Ampacity .......................... 7
Maximum Fuse / Circuit Breaker Size ........7
Installing the Indoor Unit .............................7
Installing the Outdoor Unit ..........................7
Slab Mount ................................................ 7
Cantilever Mount ........................................ 7
Roof Mount ................................................8
Connecting Refrigerant Tubing Between
the Indoor and Outdoor Unit .......................8
General Information ....................................8
Filter Drier Installation ................................8
Optional Equipment .................................... 8
Electrical Connections .................................8
Pre - Electrical Checklist.............................8
Wiring Diagram / Schematic ....................... 8
Line Voltage ................................................ 8
Outdoor Unit Connections ..........................9
Control Circuit Wiring ..................................9
Thermostat Connections ............................ 9
Grounding ...................................................9
Low Pressure Switch ..................................9
Operating the Heat Pump for Automatic
Cooling and Heating ...................................5
Oper. the Indoor Blower Continuously ........5
Shutting the Heat Pump Off........................5
System Maintenance .................................... 5
Regular Cleaning ........................................5
Before You Call a Technician ...................... 5
Troubleshooting ............................................ 5
Warranty Information ...................................5
High Pressure Switch .................................9
TM
Comfort Alert
24VAC Power Wiring ............................10
Thermostat Demand Wiring .................10
Interpreting the Diagnostic LED’s .........10
LED Description ...................................10
Two - Speed Outdoor Fan Motor ..............11
Optional Equipment ..................................11
Transformer Upgrade Kit ......................11
Startup & Adjustments...............................11
Pre - Start Checklist .................................11
Thermostat ...............................................11
Outdoor Unit .............................................11
Functional Checkouts ................................11
Cooling .....................................................11
Heating .....................................................11
Indoor Blower ...........................................12
Short Cycle Protection ..............................12
Defrost Cycle Control ...............................12
Defrost Test Procedure .............................12
Anti Short Cycle Timer Test ......................13
Heating Mode .......................................13
Cooling Mode .......................................13
Optional Equipment ..................................13
Adjustment of Refrigerant Charge ............13
Charging R-410A Unit in AC Mode ..........13
Charging R-410A Unit in Heat Mode .......13
Cooling Charging Charts ...........................14
Heating Charging Chart .............................16
Troubleshooting ..........................................17
Diagnostics Module .........10
3
Page 4
USER INFORMATION
SAFETY INFORMATION
IMPORTANT: Safety markings are used
frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
ABOUT THE HEAT PUMP
Your heat pump is a unique, all weather comfort­control appliance that will heat and cool your home year round and provide energy saving comfort. It’s an unknown fact that heat is always in the air, even when the outside temperature is below freezing. The heat pump uses this basic law of physics to provide energy saving heat during the winter months. For example, If the outdoor temperature is 47° F (8° C), your heat pump can deliver approximately 3.5 units of heat energy per each unit of electrical energy used, as compared to a maximum of only 1 unit of heat energy produced with conventional heating systems.
In colder temperatures, the heat pump performs like an air conditioner run in reverse. Available heat energy outside the home is absorbed by the refrigerant and exhausted inside the home. This effi cient process means you only pay for “moving” the heat from the outdoors to the indoor area. You do not pay to generate the heat, as with more traditional furnace designs.
During summer, the heat pump reverses the fl ow of the heat-absorbing refrigerant to become an energy-effi cient, central air conditioner. Excess heat energy inside the home is absorbed by the refrigerant and exhausted outside the home.
Fan
Mode
Figure 1. Digital Thermostat
System
Mode
Temperature
Selector
OPERATING INSTRUCTIONS
Please refer to the thermostat manufacturer’s User manual for detailed programming instructions.
Cooling Operation Only
1. Set the thermostat’s system mode to COOL or AUTO and change the fan mode to AUTO. See Figure 1
2. Set the temperature selector to the desired temperature level. The outdoor fan, compressor, and blower motor will all cycle on and off to maintain the indoor temperature at the desired cooling level.
NOTE: If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately three minutes following a previous operation or the interruption of the main electrical power.
Heating Operation Only
1. Set the thermostat’s system mode to HEAT or AUTO and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired temperature level. The compressor, outdoor fan, and blower motor will cycle on and off to maintain the indoor temperature at the desired heating level.
NOTE: If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately three minutes following a previous operation or the interruption of the main electrical power.
Emergency Heat
Some thermostats may include a system mode called EM HT or AUX HT, etc. This is a back­up heating mode that should only be used if a problem is suspected. With the mode set to EM HT, etc., the compressor and outdoor fan will be locked off and supplemental heat (electric resistance heating) will be used as a source of heat. Sustained use of electric resistance heat in place of the heat pump will result in an increase in electric utility costs.
Defrost Operation
During cold weather heating operation, the outdoor unit will develop a coating of snow and ice on the heat transfer coil. This is normal
4
Page 5
USER INFORMATION
and the unit will defrost itself. This unit features Adaptive Demand Defrost that monitors ambient and coil temperatures to regulate the defrost function accordingly.
At the beginning of the defrost cycle, both the outdoor condenser fan and compressor will turn off. After approximately 30 seconds, the compressor will turn on and begin to heat the outdoor coil causing the ice and snow to melt. NOTE: While the ice and snow is melting, some steam may rise from the outdoor unit as the warm coil causes the melting frost to evaporate. When defrost is completed, the outdoor fan motor will start, and the compressor will turn off again. In approximately 30 seconds the compressor will start up again and continue normal operation.
Operating the Heat Pump for Automatic Cooling and Heating
1. Set the thermostat system switch to AUTO and the thermostat fan switch to AUTO. See Figure 1.
Note: Thermostats will vary. Some models will not include the AUTO mode, and others will have the AUTO in place of the HEAT and COOL, and some will include all three.
2. Set the thermostat temperature to the desired heating and cooling temperature level(s). The outdoor unit and the indoor blower will then cycle on and off in either the heating or cooling mode of operation as required to automatically maintain the indoor temperature within the desired limits.
Operating the Indoor Blower Continuously
The continuous indoor blower operation is typically used to circulate the indoor air to equalize a temperature unbalance due to a sun load, cooking, or fi replace operation.
Set the thermostat fan mode to ON (Figure 1). The indoor blower starts immediately, and will run continually until the fan mode is reset to AUTO.
The continuous indoor blower operation can be obtained with the thermostat system mode set in any position, including OFF.
Shutting the Heat Pump Off
Change the thermostat’s system mode to OFF and the fan mode to AUTO. See Figure 1. NOTE: The system will not operate, regardless of the temperature selector setting.
SYSTEM MAINTENANCE
CAUTION:
Shut off all electrical power to the unit before performing any maintenance or service on the system. Failure to comply may result in personal injury or death.
Proper maintenance is most important to achieve the best performance from the appliance and should be performed by a qualifi ed service technician at least once a year. Follow the maintenance schedule and the instructions below for years of safe, trouble free operation.
Regular Cleaning
• Clean or replace the indoor air fi lter at the start of each heating and cooling season, and when an accumulation of dust and dirt is visible on the air fi lter.
• Remove any leaves and grass clippings from the coil in the outdoor unit, being careful not to damage the aluminum fi ns.
• Check for obstructions, such as twigs, sticks, etc.
TROUBLESHOOTING
If the unit fails to operate, check the following:
• The thermostat is properly set. See Cooling Operation for air conditioning or Heating Operation for furnace or air handler.
• The unit disconnect fuses are in good condition and the electrical power to the unit is turned on.
WARRANTY INFORMATION
A warranty certificate with full details is included with the heat pump. Carefully review these responsibilities with your dealer or service company. The manufacturer will not be responsible for any costs found necessary to correct problems due to improper setup, improper installation, adjustments, improper operating procedure on the part of the user, etc. Some specifi c examples of service calls which are not included in the limited warranty are:
• Correcting wiring problems in the electrical circuit supplying the heat pump.
• Resetting circuit breakers or other switches.
• Adjusting or calibrating of thermostat.
5
Page 6
INSTALLER INFORMATION
SAFETY INFORMATION
IMPORTANT: Safety markings are used
frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
Read the following instructions completely before performing the installation. Unqualifi ed individuals should not attempt to interpret these instructions or install this equipment.
The installer should comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedence over any recommendations contained in these instructions. Consult local building codes and the National Electrical Code (ANSI CI) for special installation requirements.
WARNING:
These units are fully charged with R-410A refrigerant and ready for installation. When a system is installed according to these instructions, no refrigerant charging is required. If repairs make it necessary for evacuation and charging, it should only be attempted by qualifi ed, trained personnel thoroughly familiar with this equipment. Some local codes require licensed installation service personnel to service this type of equipment. Under no circumstances should the homeowner attempt to install and/ or service this equipment. Failure to comply with this warning could result in equipment damage, personal injury, or death.
CAUTION:
This unit uses refrigerant R-410A. DO NOT under any circumstances use any other refrigerant in this unit. Use of another refrigerant will damage the unit.
Pressures within the System
This equipment contains liquid and gaseous refrigerant under high pressure. Installation or servicing should only be performed by qualifi ed trained personnel thoroughly familiar with this type equipment and related system components. Under no circumstances should the Homeowner attempt to install and/or service the equipment.
Labels, Tags, and Precautions
When working with this equipment, follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment.
Brazing Operations
Installation of equipment may require brazing operations. Safety codes must be complied with. Safety equipment (safety glasses, work gloves, fi re extinguisher, etc.) must be used when performing brazing operations.
WARNING:
Verify all electrical power to the unit is off prior to installing or servicing the equipment. Failure to shut off power may cause personal injury or death.
6
Page 7
GENERAL INFORMATION
Split System Heat Pump units are designed for use with a wide variety of fossil fuel furnaces, electric furnaces, air handlers, and evaporator coil combinations equipped with variable speed blowers.
This unit has been designed and tested for capacity and effi ciency in accordance with A.R.I. Standards. This unit will provide many years of safe and dependable comfort, providing it is properly installed and maintained. With regular maintenance, this unit will operate satisfactorily year after year. Abuse, improper use, and/or improper maintenance can shorten the life of the appliance and create unsafe hazards.
To achieve optimum performance and minimize equipment failure, it is recommended that periodic maintenance be performed on this unit. The ability to properly perform maintenance on this equipment requires certain mechanical skills and tools.
Please consult your dealer for maintenance information and availability of maintenance contracts. Please read all instructions before installing the unit.
Outdoor Unit
Each outdoor unit is shipped with a refrigerant charge adequate to operate the outdoor section with an indoor matching coil or air handler. These units include the proper amount of refrigerant for an additional 15 ft. of refrigerant lines the same size as the valve fi ttings.
NOTE: DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING.
Matching coils and air handlers may be shipped with a small holding charge to pressurize them to keep out contaminants. To release the pressure, read the indoor section installation instructions carefully.
Liquid and Suction Lines
Refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
Field Connections for Electrical Power Supply
All wiring must comply with current provisions of the “National Electrical Code” (ANSI/NFPA
70) and with applicable local codes having jurisdiction. The minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label.
SITE PREPARATION
Unpacking the Equipment
Remove the shipping carton and User’s Manual from the equipment. Take care not to damage the tubing connections when removing the carton.
Inspect for Damage
Inspect the equipment for damage prior to installing the equipment at the job site. Verify coil fi ns are straight. If necessary, comb fi ns to remove fl attened or bent fi ns.
Preferred Location of the Outdoor Unit
Survey the job site to determine the best location for mounting the outdoor unit. Overhead obstructions, poorly ventilated areas, and areas subject to accumulation of debris should be avoided. The outdoor unit should be installed no closer than 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airflow through the outdoor unit.
Facility Prerequisites
Electrical power supplied to the unit must be adequate for proper operation of the equipment. The system must be wired and provided with circuit protection in accordance with local building codes.
Minimum Circuit Ampacity
Electrical wiring to the equipment must be compatible and in compliance with the minimum circuit ampacity listed on the outdoor unit data label.
Maximum Fuse / Circuit Breaker Size
Circuit protection for the outdoor unit must be compatible with the maximum fuse/circuit breaker size listed on the outdoor unit data label.
INSTALLING THE INDOOR UNIT
The indoor unit (air handler, furnace, etc.) should be installed prior to the routing of refrigerant piping. Consult the Installation Instructions of the indoor unit for installation details.
INSTALLING THE OUTDOOR UNIT
Slab Mount
The site selected for a slab mount installation requires a stable foundation and not subject to erosion. The slab should be level and anchored (if necessary) prior to installation on the slab.
Cantilever Mount
The cantilever mount should be designed with adequate safety factor to support the weight of the equipment, and for loads subjected to the mount during operation. Installed equipment should be adequately secured to the cantilever mount and levelled prior to operation of the equipment.
7
Page 8
Roof Mount
WARNING:
To avoid the risk of property damage, personal injury, or death, it is the installer’s responsibility to ensure that whatever means are used to move or lift the unit are safe and adequate:
Keep the unit in an upright position at all times.
The method of mounting should be designed so as not to overload roof structures or transmit noise to the interior of the structure. Refrigerant and electrical lines should be routed through suitably waterproofed openings to prevent water leaking into the structure.
CONNECTING REFRIGERANT TUBING
BETWEEN THE INDOOR & OUTDOOR UNIT
• The maximum recommended interconnecting refrigerant line length is 75 feet, and the vertical elevation difference between the indoor and outdoor sections should not exceed 20 feet.
• If precise forming of refrigerant lines is required, a copper tubing bender is recommended. Avoid sharp bends and contact of the refrigerant lines with metal surfaces.
Filter Drier Installation
A fi lter dryer is provided with the unit and must be installed in the liquid line of the system. If the installation replaces a system with a fi lter dryer already present in the liquid line, the fi lter dryer must be replaced with the one supplied with the unit. The fi lter dryer must be installed in strict accordance with the manufacturer’s installation instructions.
Optional Equipment
Optional equipment such as liquid line solenoid valves, twinning kit, low ambient, etc., should be installed in strict accordance with the manufacturer’s installation instructions.
CAUTION:
This system uses R-410A refrigerant with POE oil. When servicing, cover or seal openings to minimize the exposure of the refrigerant system to air to prevent accumulation of moisture and other contaminants.
General Information
After outdoor and indoor unit placement has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices.
• When connecting refrigerant linesets together, it is recommended that dry nitrogen be fl owing through the joints during brazing. This will prevent internal oxidation and scaling from occurring.
• Refrigerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing.
• Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation.
• Tubing should be kept clean of foreign debris during installation.
• Every effort should be made by the installer to ensure that the fi eld installed refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices to insure reliable system operation and longevity.
8
ELECTRICAL CONNECTIONS
WARNING:
Shut off all electrical power to the unit before performing any maintenance or service on the system. Failure to comply may result in personal injury or death.
Pre-Electrical Checklist
Verify that the voltage, frequency and phase
of the supply source are the same as those specifi ed on the unit rating plate.
Verify that the service provided by the utility is
suffi cient to handle the additional load imposed by this equipment.
For minimum circuit ampacity and maximum
overcurrent protection, see unit rating plate.
Wiring Diagram / Schematic
A wiring diagram/schematic is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram/schematic before making any electrical connections to the outdoor unit.
Line Voltage
• Electrical power wiring must comply with the current provisions of the NEC (ANSI/NFPA
70) and with applicable local codes having jurisdiction.
• Provide power supply for the unit in accordance with the unit wiring diagram, and the unit rating plate.
Page 9
• Connect the line-voltage leads to the
p
terminals on the contactor inside the control compartment.
• Use only copper wire for the line voltage power supply to this unit (Table 1). Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit. Use of rain tight conduit is recommended.
• See the unit wiring label for proper high and low voltage wiring. Make all electrical connections in accordance with all applicable codes and ordinances.
• Use a separate branch electrical circuit for this unit. A means of electrical disconnect must be located within sight of and readily accessible to the unit. This switch shall be capable of electrically de-energizing the outdoor unit.
• Overcurrent protection must be provided at the branch circuit distribution panel and sized as shown on the unit rating label and according to applicable local codes.
Outdoor Unit Connections
The outdoor unit requires both power and control circuit electrical connections. Refer to the unit wiring diagram / schematic for identifi cation and location of outdoor unit fi eld wiring interfaces.
Control Circuit Wiring
The outdoor unit is designed to operate from a 24 VAC Class II control circuit. The control circuit wiring must comply with the current provisions of the NEC (ANSI/NFPA 70) and with applicable local codes having jurisdiction.
Thermostat Connections
Thermostat connections should be made in accordance with the instructions supplied with the thermostat, and with the instructions supplied with the indoor equipment. A typical residential installation with a heat pump thermostat and air handler are shown in Figure 2.
COPPER WIRE SIZE — AWG
(1% Voltage Drop)
Supply Wire Length-Feet
200 150 100 50
6 8 10 14 15 46812 20
46810 25
44610 30
3468 35
3468 40
2346 45
2346 50
2346 55
1234 60
Wire Size based on N.E.C. for 60° type copper conductors.
Supply Circuit
Ampacity
Table 1. Copper Wire Size
Grounding
CAUTION:
The unit must have an uninterrupted or unbroken electrical ground to minimize personal injury if an electrical fault should occur. This ground may consist of electrical wire or approved conduit when installed in accordance with national or local codes.
Low-Pressure Switch
A low-pressure switch is factory installed and located internally on the suction line of the outdoor unit. The switch is designed to protect the compressor from a loss of charge by interrupting the thermostat inputs to the unit.
If the suction pressure falls below 5 psig, the switch will open and de-energize the outdoor unit. The switch will close again when the suction pressure increases above 20 psig. NOTE: When the switch opens and then closes, there is a 3 minute short cycling delay before the outdoor unit will energize. Under normal conditions the switch is closed.
High-Pressure Switch
A high-pressure switch is factory installed and located internally on the compressor discharge line of the outdoor unit. If the discharge pressure rises above 650 psig, the switch will open and de-energize the outdoor unit. The switch will close
Thermostat
NOTE: Jumper
W1 & W2 together for shorter staging
time.
Y1
W2
W1
O
Y/Y2
G
R
C
Air Handler
G R W2 C E O Y1
Heat Pum
Figure 2. Typical 2 - Stage Heat Pump w/
Optional Outdoor Thermostat and Variable
Speed Air Handler
Y2
OD
W1
W3
R
W
2
OD
Stat
E
Y1
C
O
Section
Y2
9
Page 10
again after the discharge pressure decreases to
s
460 psig. NOTE: When the switch opens and then closes, there will be a 3 minute short cycling delay before the outdoor unit will energize. Under normal conditions the switch is closed.
TM
Comfort Alert
The Comfort Alert
Diagnostics Module
TM
Diagnostics Module is a breakthrough innovation for troubleshooting heat pump and air conditioning system failures. The module installs easily in the electrical box of the outdoor unit near the compressor contactor. By monitoring and analyzing data from the Copeland scroll compressor and the thermostat demand, the module can accurately detect the cause of electrical and system related failures without any sensors. A fl ashing LED indicator communicates the ALERT code and a diagnostic key is also imprinted on the side of the module to quickly direct the technician to the root cause of a problem. See Figure 3.
NOTE: This module does not provide safety
TM
protection! The Comfort Alert
Diagnostics Module is a monitoring device and cannot control or shut down other devices.
24 VAC Power Wiring
TM
The Comfort Alert
module requires a constant nominal 24 VAC power supply. The module cannot be powered by the C terminal on a defrost board or other control board without experiencing nuisance alerts. NOTE: The wiring to the module’s R & C terminals must be routed directly from the indoor unit or thermostat.
If the constant 24 VAC (R wire) is not present in the outdoor unit, use one of the spare wires in the thermostat cable to bring power to the module. Connect the other end of the spare wire to R at the indoor unit or thermostat.
Interpreting the Diagnostic LED’s When an abnormal system condition occurs, the
TM
Comfort Alert
module displays the appropriate ALERT and/or TRIP LED will fl ash a number of times consecutively, pause and then repeat the process. To identify a Flash Code number, count the number of consecutive fl ashes.
Each time the module powers up, the last ALERT Flash Code that occurred prior to shut down is displayed for one minute. The module will continue to display the LED until the condition returns to normal or if 24 VAC power is removed from the module.
LED Description
• POWER LED (Green): indicates voltage is
present at the power connection of the module.
• ALERT LED (Yellow): communicates an
abnormal system condition through a unique fl ash code. NOTE: The ALERT LED will fl ash consecutively, pause and then repeat the process. The number of consecutive fl ashes, referred to as the Flash Code, correlates to a particular abnormal condition. Detailed descriptions of these ALERT Flash Codes are listed in Table 4 (page 14).
• TRIP LED (Red): indicates a demand signal
is received from the thermostat, but current to the compressor is not detected by the module. The TRIP LED typically indicates if the compressor protector is open or the compressor has no power.
The scroll compressor’s R (run), C (common), and S (star t) wires are routed through the holes in
TM
the Comfort Alert
module marked R, C, and S.
NOTE: The common wire does not need to be routed through the module for it to operate.
Thermostat Demand Wiring
TM
The Comfort Alert
module requires a thermostat demand signal to operate properly. The thermostat demand signal input (labeled Y on the module), should always be connected to the compressor contactor coil. NOTE: When the coil is energized, the demand signal input is 24 VAC. When the coil is not energized, the demand signal input should be less than 0.5 VAC.
NOTES:
• Factory installed modules have different
thermostat demand signal wiring. Always follow manufacturer wiring instructions when replacing the module.
• After the thermostat demand signal is
connected, verify that 24 VAC across Y & C when demand is present.
10
POWER LED
(Green)
ALERT LED
(Yellow)
TRIP LED
(Red)
Figure 3. Comfort Alert
Module
Diagnostic
TM
Diagnostics
Key
Page 11
Outdoor Fan Motor
If unit utilizes a 2-speed condenser fan motor, this motor will operate on low speed when in low cooling, and on high speed when in high cooling. A relay within the control area switches the fan motor from low to high speed using the call for high cooling as the trigger. Other models that utilize BLDC fi xed torque variable speed fan motors will not require a relay.
Optional Equipment
Optional equipment requiring connection to the power or control circuits must be wired in strict accordance with current provisions of the NEC (ANSI/NFPA 70), with applicable local codes having jurisdiction, and the installation instructions provided with the equipment. Optional Equipment (low ambient control, hard start kits, etc.) should be installed in strict accordance with the manufacturer’s installation instructions
Transformer Upgrade Kit If this 2-stage heat pump is installed in conjunction with a gas furnace and fossil fuel kit, the furnace transformer MUST be upgraded to one with a 60 VA rating or using the transformer upgrade kit (904077). To upgrade the transformer:
• Remove the existing transformer and install
the new 60 VA transformer.
• Remove the 3 amp fuse on the furnace control
board and install the 5 amp fuse provided.
NOTE: The new transformer may be larger than the existing transformer that is mounted in the furnace. If this happens, mount the 60 VA transformer using one of the mounting holes in the furnace panel. On the other side either drill a 0.149 hole in the panel and use the existing fastener, or use a self-drilling fastener to secure the other side of the transformer.
STARTUP AND ADJUSTMENTS
Pre-Start Checklist
The following check list should be observed prior to starting the unit.
Is the unit level? Is the wiring correct according to the wiring
diagram and electrical codes?
Inspect wiring for evidence of open, shorted,
and/or improperly wired circuits.
Are all the wiring connections tight? Check
the condenser fan to make sure it turns freely.
Is the overcurrent protection properly sized? Is the thermostat wired correctly? Is it installed
in a proper location?
Verify air fi lters are clean and in place prior
to operating the equipment.
Verify the outdoor coil and top of the unit are
free from obstructions and debris, and all equipment access/control panels are in place.
Thermostat
Set the thermostat’s system mode to OFF, the fan mode to AUTO, and adjust the temperature setpoint to its highest setting.
Outdoor Unit
Prior to applying electrical power to the outdoor unit, verify that the unit has been properly and securely grounded, and that power supply connections have been made at both the facility power interface and outdoor unit.
Verify the outdoor coil and top of the unit are free from obstructions and debris, and all equipment access/control panels are in place.
FUNCTIONAL CHECKOUTS
CAUTION:
These units have a crankcase heater factory installed. Wait 24 hours prior to performing a function checkout to allow for heating of the compressor crankcase. Failure to comply may result in damage and could cause premature failure of the system.
Cooling
Gradually lower the thermostat temperature setpoint below the actual room temperature and observe that the outdoor unit and indoor blower energize. Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
Heating
If heating equipment (furnace, air handler) is provided with the system, lower the thermostat setpoint temperature to the lowest temperature setting and change the thermostat’s function mode to HEAT. The outdoor unit should stop running and the indoor blower will shut off after the preprogrammed delay. Increase the thermostat’s setpoint temperature to the maximum setting. Verify the heating equipment and the indoor blower energize after a short period of time. Feel the air being circulated by the indoor blower and verify that it is warmer than ambient temperature. Listen for any unusual noises. If unusual sounds occur, determine the source of the noise and correct as necessary.
NOTE: Other sources for heating (electric furnace, fossil fuel furnace, air handler with electric heat options, etc.) that interface with the heat pump should be functionally checked to
11
Page 12
verify system operation and compatibility with the heat pump. Refer to the installation instructions for this equipment and perform a functional checkout in accordance with the manufacturer’s instructions.
Indoor Blower
1. Turn the fan mode to ON. Verify that the
indoor blower is operating and that airfl ow is not restricted.
2. Set the fan mode back to AUTO. Blower will
operate at a decreased speed on continuous fan.
Short Cycle Protection
1. With the system operating in COOLING mode,
record the setpoint temperature setting of the thermostat.
2. Gradually raise the setpoint temperature
until the outdoor unit and indoor blower de­energize.
3. Immediately lower the setpoint temperature of
the thermostat to its original setting and verify that the indoor blower is energized and that the outdoor unit remains de-energized.
4. After approximately 3 minutes, verify that the
outdoor unit energizes and the temperature of the air supplied to the facility is cooler than ambient temperature.
Defrost Cycle Control
The defrost cycle is controlled by an Adaptive Demand Defrost algorithm that monitors coil temperature and ambient temperature. Other features of the of the demand defrost board include:
• 4 Field selectable defrost termination
temperatures (50° F - 80° F coil temperature).
• Field selectable compressor delay feature.
• High pressure and low pressure switches.
• Sensing of second stage compressor demand.
• Test/speed up capability.
• Anti short cycle timer (3 minutes) for
compressor protection.
• On board diagnostics with fl ashing LED for
quicker troubleshooting. See Table 2.
Diagnostic Description LED Status
Control Fault (No Power) Off Normal Operation On
ASCD Delay Active (with compressor demand)
Low Pressure Switch Lockout 2 Flashes High Pressure Switch Lockout 3 Flashes Ambient Sensor Fault 4 Flashes Coil Sensor Fault 5 Flashes
Table 2. Control Diagnostic
1 Flash
Control is uncalibrated when power is applied. Calibration occurs after a defrost cycle. The control initiates this sacrifi cial defrost after 34 minutes of accumulated compressor run time in heating with coil temperature below 35° F. The defrost cycle terminates if coil sensor reaches selected termination temperature or after 14 minutes defrost.
Defrost function is disabled if coil temperature is above 35° F. If Ambient sensor is detected as open or shorted, demand defrost will not operate and control will revert to time/temperature defrost operation. If the outdoor coil sensor is detected as open or shorted, the control will not perform demand or time/temperature defrost operation. NOTE: When the defrost cycle initiates, there will be a 30 second compressor delay going into and out of the defrost cycle. This delay may be removed by removing P6 connector on the board.
This 2-stage unit will defrost in second stage regardless of the stage called for by the thermostat.
NOTE: All units are shipped from the factory with the default termination temperature set at 70° F.
Defrost Test Procedure
1. Terminals R - C must have 18-30VAC present between them in order for defrost sequences to be initiated.
2 With heat mode thermostat demand (Y
connected to R), short and hold the TEST pins together. This will energize reversing valve to initiate a forced defrost. NOTE: This will bypass the ASCD and allow the high stage compressor to come on immediately (if the REMOVE FOR NO DELAY jumper at P6 is removed). If the REMOVE FOR NO DELAY jumper at P6 is installed, the compressor will energize immediately following a 30-second delay.
3. Remove the short on the TEST pins.
• If the Coil temperature is above the Terminate
Temperature selection setting, the defrost cycle will be terminated (reversing valve will de-energized).
• If the coil temperature is below the Terminate
Temperature election setting, the defrost cycle will continue for 14 minutes or until the coil temperature rises above the Terminate Temperature selection setting. NOTE: Short the TEST pins for 1 second or more to force the control out of defrost and back to heating mode (reversing valve de-energized). Compressor will turn on immediately (if the REMOVE FOR NO DELAY jumper is removed).
12
Page 13
• If the REMOVE FOR NO DELAY jumper is installed, the compressor will energize immediately following a 30-second delay.
Note: If the Y2 thermostat input is energized (2 - stage system), the second stage will turn on. If the above steps will not initiate a defrost, replace the defrost board.
Anti Short Cycle Timer Test
The 3-minute time delay feature can be bypassed by shorting the TEST pins together.
Heating Mode When the TEST pins are shorted together for more than 1-second, the control will switch between defrost mode and heating mode (as described in the Defrost Test Procedure section).
Cooling Mode When the TEST pins are shorted together for more than 1-second, the Anti Short Cycle Timer will be bypassed.
Optional Equipment
A functional checkout should be performed in accordance with the checkout procedures supplied with the equipment.
Assemblies of indoor coils and outdoor units not listed are not recommended.
Charging an R-410A Unit in AC Mode at Outdoor Temperatures Above 65F.
1. With the system operating at steady-state, measure the liquid refrigerant pressure in psig at the service valve.
2. Measure the liquid refrigerant temperature in Fahrenheit at the service valve.
3. For the temperature measured, determine the required liquid refrigerant pressure from the appropriate charging charts in Figures 4 - 7 (pages 14 & 15).
4. If the pressure measured in step 1 is greater than the required liquid refrigerant pressure determined in step 4, then there is too much charge in the system. Remove refrigerant and repeat steps 1 through 3 until the system is correctly charged.
5. If the pressure measured in step 1 is less than the required liquid refrigerant pressure determined in step 4, then there is too little charge in the system. Add refrigerant and repeat steps 1 through 3 until the system is correctly charged.
ADJUSTMENT OF REFRIGERANT
CHARGE:
CAUTION:
Split system equipment contains liquid and gaseous refrigerant under pressure. Adjustment of refrigerant charge should only be attempted by qualifi ed, trained personnel thoroughly familiar with the equipment. Under no circumstances should the homeowner attempt to install and/or service this equipment. Failure to comply with this warning could result in equipment damage, personal injury, or death.
NOTES:
• The unit must be charged while both fi rst and second stages are operating.
• To achieve rated capacity and effi ciency the compressor must be exposed to refrigerant for at least 24 hours prior to running and then must be run for a minimum of 12 hours.
• The following Refrigerant Charging Charts are applicable to listed assemblies of equipment and at listed airfl ows for the indoor coil.
Tonnage
System Charge
R-410A oz.
2 Ton 185
3 Ton 272
4 Ton 272
5 Ton 272
Table 3. Split System
Heat Pump Charge
Charging an R-410A Unit in Heating Mode.
1. Evacuate the refrigerant system.
2. Weigh in the proper charge per Table 3, using the Heating Charging Chart (Figure 8, page
16) as a guide. Unit charge MUST be verifi ed in cooling season.
3. Verify the unit is operating properly as outlined in the functional checkout (heating section) on page 11.
13
Page 14
475
250
275
300
325
350
375
400
425
450
475
500
70 75 80 85 90 95 100 105 110 115 120 125
Cooling Charging Charts
450
Remove refrigerant when above curve
425
400
375
350
325
Liquid Pressure (psig)
300
275
Add refrigerant when below curve
250
70 75 80 85 90 95 100 105 110 115 120 125
Liquid Temperature (° F)
Figure 4. Charging Chart for 2 Ton Units
Remove refrigerant when above curve
14
Liquid Pressure (psig)
Add refrigerant when below curve
Liquid Temperature (° F)
Figure 5. Charging Chart for 3 Ton Units
Page 15
Cooling Charging Charts (continued)
)
5
500
475
450
425
400
375
350
325
Liquid Pressure (psig)
300
275
250
Remove refrigerant when above curve
Add refrigerant when below curve
70 75 80 85 90 95 100 105 110 115 120 12
Liquid Temperature (° F
Figure 6. Charging Chart for 4 Ton Units
500
475
450
425
400
375
350
325
Liquid Pressure (psig)
300
275
250
Remove refrigerant when above curve
Add refrigerant when below curve
70 75 80 85 90 95 100 105 110 115 120 125
Liquid Temperature (° F)
Figure 7. Charging Chart for 5 Ton Units
15
Page 16
400
Heating Charging Chart
375
Remove refrigerant when above curve
350
325
300
275
250
Liquid Pressure (psig)
225
Add refrigerant when below curve
200
50 55 60 65 70 75 80 85 90
Liquid Temperature (° F)
Figure 8. Heating Charging Chart
16
Page 17
TROUBLESHOOTING
Status
LED
Green
“POWER”
Red “TRIP”
Yellow “ALERT”
Flash Code 1
Status LED
Description
Module has power
Thermostat demand signal Y is present, but compressor is not running
Long Run Time Compressor is running extremely long run cycles
Status LED Troubleshooting Information
Supply voltage is present at module terminals
Compressor protector is open
Check for high head pressure
Check compressor supply voltage
Outdoor unit power disconnect is open
Compressor circuit breaker or fuse(s) is open
Broken wire or connector is not making contact
Low pressure switch open if present in system
Compressor contactor has failed open
Low refrigerant charge
Evaporator blower is not running
Check blower relay coil and contactsCheck blower motor capacitorCheck blower motor for failure or blockageCheck evaporator blower wiring and connectorsCheck indoor blower control boardCheck thermostat wiring for open circuit
Evaporator coil is frozen
Check for low suction pressureCheck for excessively low thermostat settingCheck evaporator airfl ow (coil blockages or return airfi lter)Check ductwork or registers for blockage
Faulty metering device
Check TXV bulb installation (size, location and contact)Check if TXV/fi xed orifi ce is stuck closed or defective
Condenser coil is dirty
Liquid line restriction (fi lter drier blocked if present in system)
Thermostat is malfunctioning
Solenoid plug not connectedY2 not wired at Comfort AlertCheck thermostat sub-base or wiring for short circuitCheck thermostat installation (location, level)
Comfort Alert failure
Yellow “ALERT”
Flash Code 2
System Pressure Tr i p
Discharge or suction
pressure out of limits
compressor overloaded
High head pressure
Check high pressure switch if present in systemCheck if system is overcharged with refrigerantCheck for non-condensable in system
Condenser coil poor air circulation (dirty, blocked, damaged)
Condenser fan is not running
Check fan capacitorCheck fan wiring and connectorsCheck fan motor for failure or blockage
Return air duct has substantial leakage
If low pressure switch present in system, check Flash Code
1 information
Table 4. LED Diagnostics
17
Page 18
TROUBLESHOOTING - CONTINUED
Status LED
Yellow “ALERT”
Flash Code 3
Yellow “ALERT”
Flash Code 4
Yellow “ALERT”
Flash Code 5
Status LED
Description
Short Cycling / Compressor is running only briefl y
Locked Rotor
Open Circuit
Status LED Troubleshooting Information
Thermostat demand signal is intermittent
Low line voltage (contact utility if voltage at disconnect is low)
Excessive liquid refrigerant in compressor
Compressor bearings are seized
Run capacitor has failed
Low line voltage (contact utitlity if voltage at disconnect is
low)
Check wiring connections
Excessive liquid refrigerant in compressor
Compressor bearings are seized
Measure compressor oil level
Outdoor unit power disconnect is open
Compressor circuit breaker or fuse(s) is open
Compressor contactor has failed open
Check compressor contactor wiring and connectors
Check for compressor contactor failure (burned, pitted
or open)
Check wiring and connectors between supply and
compressor
Check for low pilot voltage at compressor contactor coilHigh pressure switch is open and requires manual reset
Open circuit in compressor supply wiring or connections
Unusually long compressor protector reset time due to extreme
ambient temperature
Compressor windings are damaged Check compressor motor winding resistance
Run capacitor has failed
Open circuit in compressor start wiring or connections Check wiring and connectors between supply and the
compressor S terminal
Compressor start winding is damaged
Yellow “ALERT”
Flash Code 6
Open Start Circuit Current only in run circuit
Check compressor motor winding resistance
Open circuit in compressor run wiring or connections
Yellow “ALERT”
Flash Code 7
Open run circuit Current only in start circuit
Check wiring and connectors between supply and the
compressor R terminal
Compressor run winding is damaged Check compressor motor winding resistance
Yellow “ALERT”
Flash Code 8
Yellow “ALERT”
Flash Code 9
* Flash code number corresponds to a number of LED fl ashes, followed by a pause and then
repeated. Trip and alert LED’s fl ashing at same time means control circuit voltage is too low for operation.
Welded Contactor Compressor always runs
Low Voltage Control circuit < 17VAC
Compressor contactor has failed closed
Thermostat demand signal not connected to module
Control circuit transformer is overloaded
Low line voltage (contact utility if voltage at disconnect is low)
Check wiring connections
Table 4. LED Diagnostics - Continued
18
Page 19
TROUBLESHOOTING - CONTINUED
Miswired Module Indication Recommended Troubleshooting Action
Green LED is not on, module
does not power up
Green LED intermittent, module powers up only when compressor runs
Trip LED is on, but system and compressor check OK
TRIP LED and ALERT LED fl ashing together
ALERT Flash CODE 3 displayed incorrectly (Compressor short cycling)
ALERT Flash Code 5, 6, or 7 displayed incorrectly (Open Circuit, Open Start Circuit or Open Run Circuit)
• Determine if both R & C module terminals are connected.
• Verify voltage is present at module’s R & C terminals.
• Determine if R & Y terminals are wired in reverse.
• Verify modules R and C terminals have a constant source.
• Verify Y terminal is connected to 24VAC at contactor coil.
• Verify voltage at contactor coil falls below 0.5VAC when off.
• Verify 24VAC is present across Y & C when thermostat demand signal is present. If not, R & C are reversed wired.
• Verify R and C terminals are supplied with 19 - 28VAC.
• Verify Y terminal is connected to 24VAC at contactor coil.
• Verify voltage at contactor coil falls below 0.5VAC when off.
• Verify the compressor run and start wires are routed through the module’s current sensing holes.
• Verify the Y terminal is connected to 24VAC at contactor coil.
• Verify voltage at contactor coil falls below 0.5VAC when off.
ALERT Flash Code 6 (Open Start Circuit) displayed for Code 7 (Open Run Circuit) or vice-versa
ALERT Flash Code 8 displayed incorrectly (Welded Contactor)
Table 5. Module Wiring Troubleshooting
• Verify the compressor run and start wires are routed through the correct module sensing holes.
• Determine if module’s Y terminal is connected.
• Verify Y terminal is connected to 24VAC at contactor coil.
• Verify 24VAC is present across Y & C when thermostat demand signal is present. If not, R and C are reversed wired.
• Verify voltage at contactor coil falls below 0.5VAC when off.
• Review Thermostat Demand Wiring (page 10) for Y & C wiring.
19
Page 20
INSTALLER: PLEASE LEAVE THESE
INSTALLATION INSTRUCTIONS WITH
THE HOMEOWNER.
¢708868b¤
708868AO’Fallon, MO
Specifi cations and illustrations subject to change
708868A(Replaces 7088680)
without notice t incurring obligations.
Printed in U.S.A. (10/09)
Loading...