Nordyne R-410A User Manual 2

USER’s MANUAL & INSTALLATION INSTRUCTIONS
2 Stage R-410A Single Package Heat Pump
15 SEER
IMPORTANT
Please read this information thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain this unit. Keep this literature where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your NORDYNE Servicing Contractor (Service PRO).
These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of this appliance. Some local codes require licensed installation/service personnel for this type of equipment. Please read all instructions carefully before starting the installation.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
SAFETY INFORMATION ...............................3
USER INFORMATION ...................................3
About the Heat pump ................................ 3
Operating Instructions ...............................3
Cooling Operation ...................................3
Heating Operation ...................................3
Emergency Heat ..................................... 3
Defrost ....................................................3
System Shutdown ...................................4
Warranty Information .................................4
INSTALLER INFORMATION ..........................4
General Information ...................................4
Pre - Installation Check .............................4
Inspecting Equipment ................................ 4
HEAT PUMP INSTALLATION ........................5
Locating the Heat pump ...........................5
Unpacking the Unit ................................... 5
Minimum Clearances ................................5
Service Access Clearance ........................ 5
Clearances to Combustibles ..................... 5
Duct Requirements ...................................5
CONDENSATE DRAINAGE ........................... 5
INSTALLING RETURN and SUPPLY
FITTINGS ....................................................6
Supply Duct .............................................. 6
Return Duct ..............................................6
LOCATING and INSTALLING the
RETURN AIR ASSEMBLY .............................6
LOCATING and INSTALLING the
SUPPLY DAMPERS .......................................7
DUCTING SYSTEM .......................................7
Connecting the Return and Supply Air
Flexible Ducts ............................................ 8
Blower Speed ...........................................8
Defrost Cycle Control ................................9
Ambient Sensor Mounting .......................11
Electric Heat Package .............................11
SYSTEM OPERATION .................................12
Pre - Start Checklist .................................12
Start - Up Procedure ...............................12
Air Circulation .......................................12
System Heating ....................................12
System Cooling ....................................12
Short Cycle Protection..........................12
Emergency Heat ...................................12
Defrost Test Procedure ............................12
Anti Short Cycle Timer Test .....................13
Heating Mode .......................................13
Cooling Mode .......................................13
ADJUSTMENT of REFRIGERANT
CHARGE ..................................................13
Charging an R410A Unit in AC
Mode at Outdoor Temperature
above 65° F ...........................................1 3
Charging an R410A Unit in
Heating Mode ........................................1 3
REFRIGERANT CHARGING CHARTS
for COOLING MODE of OPERATION .........14
Figure 11 - 2 Ton Units ............................14
Figure 12 - 3 Ton Units ............................14
Figure 13 - 4 Ton Units ............................15
Figure 14 - 5 Ton Units ............................15
REFRIGERANT CHARGING TABLES
for HEATING MODE of OPERATION ..........16
Charging Tables - 2 & 3 Ton Units............16
Charging Tables - 4 & 5 Ton Units............17
WIRING DIAGRAMS ....................................18
Figure 15 - 2 & 3 Ton Units ...........................18
Figure 16 - 2 & 3 Ton Units ...........................19
ELECTRICAL CONNECTIONS .....................8
High Voltage ..............................................8
Low Voltage ...............................................8
Overcurrent Protection...............................9
Locating the Thermostat ............................9
2 - Speed Outdoor Fan Motor .................... 9
Low Pressure Switch ................................. 9
High Pressure Switch ................................ 9
2
SAFETY INFORMATION
IMPORTANT: Please read all instructions before
servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
USER INFORMATION
About the Heat Pump
Your heat pump is a unique, all weather comfort­control appliance that will heat and cool your home year round and provide energy saving comfort. It’s an unknown fact that heat is always in the air, even when the outside temperature is below freezing. The heat pump uses this basic law of physics to provide energy saving heat during the winter months. For example, If the outdoor temperature is 47° F (8° C), your heat pump can deliver approximately 3.5 units of heat energy per each unit of electrical energy used, as compared to a maximum of only 1 unit of heat energy produced with conventional heating systems.
In colder temperatures, the heat pump performs like an air conditioner run in reverse. Available heat energy outside the home is absorbed by the refrigerant and exhausted inside the home. This effi cient process means you only pay for “moving” the heat from the outdoors to the indoor area. You do not pay to generate the heat, as is the case with more traditional furnace designs.
During summer, the heat pump reverses the fl ow of the heat-absorbing refrigerant to become an energy-effi cient, central air conditioner. Excess heat energy inside the home is absorbed by the refrigerant and exhausted outside the home.
Operating Instructions
Cooling Operation
1. Set the thermostat’s system mode to COOL or AUTO and change the fan mode to AUTO. See Figure 1
2. Set the temperature selector to the desired temperature level. The outdoor fan, compressor, and blower motor will all cycle on and off to maintain the indoor temperature at the desired cooling level.
NOTE: If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately three minutes following a previous operation or the interruption of the main electrical power.
Heating Operation
1. Set the thermostat’s system mode to HEAT or AUTO and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired temperature level. The compressor, outdoor fan, and blower motor will cycle on and off to maintain the indoor temperature at the desired heating level.
NOTE: If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately three minutes following a previous operation or the interruption of the main electrical power.
Emergency Heat Some thermostats may include a system mode called EM HT or AUX HT, etc. This is a back­up heating mode that should only be used if a problem is suspected. With the mode set to EM HT, etc., the compressor and outdoor fan will be locked off and supplemental heat (electric resistance heating) will be used as a source of heat. Sustained use of electric resistance heat in place of the heat pump will result in an increase in electric utility costs.
Fan
Mode
Figure 1. Digital Thermostat
System
Mode
Temperature
Selector
Defrost During cold weather heating operation, the outdoor unit will develop a coating of snow and ice on the heat transfer coil. This is normal and the unit will defrost itself. This unit features Adaptive Demand Defrost that monitors ambient and coil temperatures to regulate the defrost function accordingly.
3
At the beginning of the defrost cycle, both the outdoor condenser fan and compressor will turn off. After approximately 30 seconds, the compressor will turn on and begin to heat the outdoor coil causing the ice and snow to melt. NOTE: While the ice and snow is melting, some steam may rise from the outdoor unit as the warm coil causes the melting frost to evaporate. When defrost is completed, the outdoor fan motor will start, and the compressor will turn off again. In approximately 30 seconds the compressor will start up again and continue normal operation.
System Shutdown Change the thermostat’s system mode to OFF and the fan mode to AUTO (See Figure 1). NOTE: The system will not operate, regardless of the temperature selector setting.
Warranty Information
A warranty certificate with full details is included with the heat pump. Carefully review these responsibilities with your dealer or service company. The manufacturer will not be responsible for any costs found necessary to correct problems due to improper setup, improper installation, adjustments, improper operating procedure on the part of the user, etc. Some specifi c examples of service calls which are not included in the limited warranty are:
1. Correcting wiring problems in the electrical circuit supplying the heat pump.
2. Resetting circuit breakers or other switches.
3. Adjusting or calibrating of thermostat.
INSTALLER INFORMATION
General Information
The installer should comply with all local codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedence over any recommendations contained in these instructions. Consult local building codes and the National Electrical Code (ANSI CI) for special installation requirements. Read the following
instructions completely before performing the installation.
Some states require installation and service personnel to be licensed. Unqualifi ed individuals
should not attempt to interpret these instructions or install this equipment.
This equipment contains R-410A refrigerant under high pressure. Installation or servicing should only be performed by qualifi ed trained personnel thoroughly familiar with this type equipment and related system components.
CAUTION:
This unit uses refrigerant R-410A. DO NOT under any circumstances use any other refrigerant in this unit. Use of another refrigerant will damage the unit.
Single packaged heat pumps are ready for easy and immediate installation and can be readily connected into the high static duct system of a home. This unit is completely assembled, wired, and run tested at the factory. This heat pump is designed for outdoor installation only. The only connections needed for installation are the supply and return ducts, the line voltage, and thermostat wiring. A complete heat pump system typically consists of:
• Single Package Heat Pump
• Home Fittings Kit
• Unit Fittings Kit
• 2-Stage Cooling/Heating Thermostat
Use of components other than those specifi ed may invalidate ARI Certifi cation, Code Agency Listing, and limited warranty on the air conditioner.
Pre-Installation Check
Before you install this unit, the cooling load of the area to be conditioned must be calculated and a system of the proper capacity selected. It is recommended that the area to be conditioned be completely insulated and vapor sealed.
The electrical supply should be checked to determine if adequate power is available. If there is any question concerning the power supply, contact the local power company.
CAUTION:
To prevent personal injury and/or equipment damage, check thermostat manufacturer’s operation of fan relay circuit when in EMER HEAT. When the thermostat system mode is in the EMER HEAT position, the thermostat must energize the fan relay when the
fan mode is in the AUTO position.
Inspecting Equipment:
All units are securely packed at the time of shipment and, upon arrival, should be carefully inspected for damage. Claims for damage (apparent or concealed) should be filed immediately with the carrier.
4
HEAT PUMP INSTALLATION
Locating the Heat pump
• Select a solid, level position, preferably on a
concrete slab, slightly above the grade level, and parallel to the home. DO NOT PLACE
UNIT UNDER THE HOME.
• The hot condenser air must be discharged up
and away from the home, and if possible, in a direction with the prevailing wind.
• Do not place the unit in a confi ned space.
• If practical, place the heat pump and its ducts
in an area where they will be shaded from the afternoon sun, when the heat load is greatest.
• If possible, select a site for the unit that is as
close as possible to the proposed return grille location.
• The length of the supply and return ducts
should be kept to a minimum with no sharp radius bends.
Unpacking the Unit
It is recommended that the unit be unpacked at the installation site to minimize damage due to handling.
CAUTION:
Do not tip the unit on its side. Oil may enter the compressor cylinders and cause starting trouble. If unit has been set on its side, restore to upright position and do not run for several hours. Then run unit for a few seconds. Do this three or four times with fi ve
minutes between runs.
1. Remove the bands from around the unit.
2. Unfold the top and bottom cap fl anges.
3. Carefully remove the top cap and tube.
Minimum Clearances
Minimum clearances MUST be maintained from adjacent structures to provide room for proper servicing and air circulation. See Figure 2. DO NOT install unit in a confi ned or recessed area that will allow discharge air from the unit to re-circulate into the condenser air inlet, through the coil.
6 ft.
24"
12"
12"
Figure 2. Minimum Unit Clearances
Clearances to Combustible Materials:
Combustible Base (Wood or Class A, B, or C
roof Covering material) ...............................0”
Supply and Return Air Ducts .......................0”
Duct Connection side ..................................0”
Duct Requirements
The supply duct system, including the number and type of registers, will have much more effect on the performance of an air conditioning system then any other factor. The duct must be suffi ciently large to conduct an adequate amount of air to each register.
CONDENSATE DRAINAGE
A 3/4” condensate fi tting extends out of the side of the unit (Figure 3). The drain trap, shipped in the electrical compartment, must be installed to prevent water from collecting inside the unit.
1. Thread the elbow provided with the unit into the drain connection until hand tight.
2. Connect the condensate tubing onto the fi tting, forming a trap near the drain connection.
3. Route the condensate tube from the trap to a suitable drain. NOTE: For proper drainage, make sure the trap is level to the ground and tubing outlet is below trap level.
Elbow
Service Access Clearance:
Blower access panel side .......................... 24”
Electrical compartment access panel side .. . 12” Clearance between overhang and
top of unit ...............................................72”
Clearance around condenser coil area to wall or shrubs (excludes duct panel side) .. 12”
P-Trap
Figure 3. Drain Trap
5
INSTALLING RETURN AND
SUPPLY AIR FITTINGS
The supply and return fi ttings are included with the unit and located in the supply duct. They attach to the unit openings (Figure 4) with a fl ange and bead arrangement and may be, secured with two sheet metal screws. Note: For easier access, install fi ttings before positioning unit in fi nal location.
Supply Duct
1. Position the supply duct collar so the edge of the unit opening fi ts between the fl ange and the bead.
2. Overlap the collar ends keeping the small screw holes underneath.
3. Align the holes in the crimped area and install one screw. Note: It may be necessary to loosen the four screws that hold the transition duct in order to install the supply fi tting. Re-tighten when installation is complete.
4. Tap collar (if necessary) to ensure engagement with unit opening and install second screw.
5. Tighten fi rst screw and rotate collar clockwise so joint is near three o’clock position.
Return Duct
1. Align the slots with the holes in the collar and install two screws.
2. Position the collar over the opening and align the four notches in the collar with the four dimples in the panel.
3. Using self-drilling screws (10-16x.5) attach the collar to the rear panel.
LOCATING AND INSTALLING THE
RETURN AIR ASSEMBLY
To simplify installation, locate and install the return air assembly fi rst. If desired, the return opening can be located inside a closet with louvered doors that has an open area equal to or greater than the 12” x 20” grille furnished. The return air grille can be placed in the wall of a closet and the air ducted into the fi lter box through a boxed-in area at the closet fl oor level. Make sure
the fi lter is readily accessible.
NOTE: The return air box with grille and fi lter
(Figure 5) should not be located in heavy traffi c areas like hallways or center of rooms. A good spot is in a corner or under a table, if a minimum two inch clearance is available.
1. Start the installation from under the home by cutting a small hole in the subfl oor. Determine how the fl oor joist location will affect cutting the opening needed for the return air box. NOTE: Floor joists are generally located on 16” centers, leaving 14-3/8” between joists.
2. After measuring the return air box (approximately 12-1/4” x 20-1/4”), cut the hole through the fl oor so that the box will fi t between the fl oor joists. Care should be taken when cutting through carpeting to avoid snags. NOTE: In most installations it will be necessary to cut a similar hole in the fi berboard directly under the hole in the fl oor. However, if the fl oor is more than ten inches deep, it will only be necessary to cut a hole for the collar on the return air box or for the insulated duct.
3. Set the box into the opening and fasten with screws or nails.
4. Put the fi lter and return air grille in place.
Transition Duct Screws
Supply Air
14” Duct Dimples
Return Air
Figure 4. Return and Supply Air Fittings
6
Figure 5. Return Air Box
LOCATING AND INSTALLING THE
SUPPLY DAMPER(S)
When locating the supply damper(s), carefully check fl oor joists and frame members that could interfere with the installation of the damper or fl exible duct. Ideally, the damper (Figure 6) should be located in the bottom of the main duct, forward of center of the home, at least three feet from the nearest register. The round supply opening in the slanted side of the damper should face the side of the home where the heat pump is located.
1. Locate the center of the heat duct by cutting a small hole in the fi berboard below the duct at the desired location.
2. Cut a hole approximately 3/4” larger than the damper opening in the fi berboard.
3. Cut a 9-1/8” x 13-1/8” hole in the duct and bend over all tabs fl at on the inside of the heat duct.
4. Insert the damper into the duct and bend over all tabs fl at on the inside of the heat duct.
5. Seal the opening between the fi berboard and damper or fl exible duct.
DUCTING SYSTEM
Air ducts should be installed in accordance with the standards of the National Fire Protection Association “Standard for Installation of Air Conditioning and Ventilation Systems” (NFPA 90A), “Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems” (NFPA 90B), these instructions, and all applicable codes.
The supply duct system, including the number and type of registers, will have much more effect on the performance of the system than any other factor. The duct must be suffi ciently large to conduct an adequate amount of air to each register. See Table 1 or Figure 7.
The heat pump system will not cool or heat the home if air is lost to the outside through leaks in the duct system. Ducts that are collapsed or restricted by foreign objects will also prevent adequate air fl ow.
Item
No.
1
12” x 20” Return Air
Description
AUTOMATIC DAMPER IS CLOSED
WHEN HEAT PUMP IS OFF
Figure 6. Supply Damper
2
16” x 20” Air Filter
3
12” x 20” Grille
4
Supply Damper
5
14” Diameter Flex Return Duct
6
12” Diameter Flex Supply Duct
7
12” x 12” x 12” “Y” Fitting
Table 1. Typical Applications
MULTIPLE DUCT APPLICATIONSINGLE DUCT APPLICATION
4
3
2
1
6
3
2
1
4
6
7
4
6
5
5
Figure 7. Single and Multiple Duct Applications
7
Note: For highly resistive duct systems it may be necessary to add an additional return air duct and or supply to achieve maximum performance and prevent coil icing and refrigerant fl ood back.
Connecting the Return and Supply Air Flexible Ducts
• The return duct for all units is 14” diameter.
• The supply duct for all units is 12” diameter.
• The fl exible ducts can be connected to the corresponding fi ttings with the clamps provided with the ducts. Note: To prevent a loss in cooling capacity, make sure all connections are tight.
• The fl exible ducts may be cut to the required length, see instructions packed with duct. Keep
all ducts as short and straight as possible. Avoid sharp bends.
• Ducts may be spliced with sheet metal sleeves and clamps.
• Once the inner duct is connected to the proper fi tting, the insulation and plastic sleeve should be pulled over the connection and clamped.
• Homes with multiple supply ducts (or special applications), a Y fi tting is available to divide the supply air so it can be ducted to different areas of the home for more effi cient cooling. Note: For maximum performance, insulate the Y fi tting.
2. Locate the orange, black and red wires terminated to the blower motor. The orange wire controls the low speed cooling and heating operations, the black wire controls high speed cooling and heating operations and the red wire controls the electric heating operation.
CAUTION:
To avoid personal injury or property damage, make certain that the motor leads cannot come into contact with any metal components of the unit.
3. Verify the required speed from the airfl ow data found in Table 2. Place appropriate wire on the appropriate motor speed tap for the required airfl ow.
4. Check all factory wiring per the unit wiring diagram and inspect the factory wiring connections to be sure none loosened during shipping or installation.
ELECTRICAL CONNECTIONS
Blower Speed
For optimum system performance and comfort, it may be necessary to change the factory speed setting. See Table 2 (page 10) for factory settings. NOTE: Q5RE models have High Effi ciency Motors with 5 speed taps.
WARNING:
To avoid electric shock, personal injury, or death, turn off the electric power at the disconnect or the main service panel before making any electrical connections.
1. Disconnect all electrical power to the unit and remove the service panel.
CAUTION:
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
WARNING:
To avoid electric shock, personal injury, or death, turn off the electric power at the disconnect or the main service panel before making any electrical connections.
High Voltage
1. Install a branch circuit disconnect of adequate size as specifi ed by the National Electrical Code. Locate the disconnect within sight
of the unit.
2. Extend leads through power wiring hole (Figure 9). Connect L1 and L2 directly to the contactor.
3. Ground the heat pump unit using the green grounding screw provided in the control panel.
Low Voltage
1. Route 24V control wires through the sealing grommet (Figure 8) near the power entrance.
2. Connect the control wires to the defrost board and blower relay wire (Figure 9, page 10).
8
High Voltage
Low Voltage
Figure 8. Power Entry
Overcurrent Protection
Generally, the best fuse or breaker for any heat pump is the smallest size that will permit the equipment to run under normal usage and provide maximum equipment protection. Properly sized fuses and breakers also prevent nuisance trips during unit startup. If a fuse blows or a breaker
trips, always determine the reason. Do not arbitrarily install a larger fuse or breaker and do not, in any case, exceed the maximum size listed on the data label of the unit.
Locating the Thermostat
Locate the thermostat away from drafts and slamming doors. The thermostat must not be installed on an outside wall or any other location where its operation may be adversely affected by radiant heat from fi replaces, sunlight, or lighting fi xtures, or convective heat sources such as supply air registers or electrical appliances. Mount on an inside wall approximately fi ve feet from the fl oor.
This heat pump is a two stage Cooling and Heating appliance that requires a 2-stage Cooling/Heating thermostat. The heat-cool thermostat prevents simultaneous operation of the heating and cooling units and is equipped with an ON-AUTO fan mode that allows the home owner to operate the indoor blower when only air circulation is desired.
Connect the low voltage wires to the respective terminals on the thermostat base (Figure 9). See thermostat instruction sheet for more detailed information.
2-Speed Outdoor Fan Motor (Select Models)
If the unit utilizes a 2-speed condenser fan motor, this motor will operate on low speed when in low cooling/heating, and on high speed when in high cooling/heating.
Low Pressure Switch
The low pressure switch is factory installed and located in the suction line internal to the unit. The switch is designed to protect the compressor if a loss of charge occurs. Under normal conditions, the switch is closed.
If the suction pressure falls below 5 psig, then the switch will open and de-energize the unit. The switch will close again once the suction pressure increases above 20 psig. The low pressure switch interrupts the thermostat inputs to the unit. Note: When the switch opens and then closes, there will be a 3 minute short cycling delay before the unit can energize.
High Pressure Switch
The high pressure switch is factory installed and located in the compressor discharge line internal to the unit. The switch is designed to de­energize the system when very high pressures occur during abnormal conditions. Under normal conditions, the switch is closed.
If the discharge pressure rises above 575 psig, the switch will open and de-energize the unit. The switch will close again once the discharge pressure decreases to 460 psig. The high pressure switch interrupts the thermostat inputs to the unit. Note: When the switch opens and then closes, there will be a 3 minute short cycling delay before the unit can energize.
Defrost Cycle Control
The defrost cycle is controlled by an adaptive demand defrost board which features:
• Adaptive Demand Defrost algorithm.
• 4 Field selectable defrost termination temperatures.
• Field selectable delay feature.
• High pressure and low pressure switches.
• Sensing of second stage compressor demand.
• Test/speed up capability.
• Anti short cycle timer (3 minutes) for compressor protection.
• On board diagnostics with fl ashing LED for quicker troubleshooting. See Table 3 (page 11).
The adaptive Demand Defrost controls the defrost cycle in response to an adaptive demand algorithm that uses coil temperature and ambient temperature. It provides user selectable defrost termination temperatures (50° F - 80° F coil temperature).
9
W2
Green
R
O
Y1
Y2
(from Blower Relay)
YR C
Y2
out
out
Y
G
C
E
L
INDOOR
THERMOSTAT
in
Y2 L
out
DF DF2
DEFROST
BOARD
1
Brown
2
Orange 3 4 5 6 7 8 9
Accessory Heat Plug
SUB-BASE
Figure 9. Typical Wiring (Field Supplied) for 2-Stage Cool, 2 Stage Electric Heat
Model Q5RF Wire Color/Speed Tap Motor Speed
Air Flow
(@ 0.3 in WC)
T1 Low 560
Orange/T2 Medium/Low* 600
X24K
Black/T3 Medium** 800
Red/T4 Medium/High*** 1,040
T5 High 1,250
Orange/T1 Low* 600
T2 Medium/Low 750
X36K
Black/T3 Medium** 1,200
Red/T4 Medium/High*** 1,420
T5 High 1,520
Orange/T1 Low* 1,030
T2 Medium/Low 1,240
X48K
Red/T3 Medium*** 1,400
Black/T4 Medium/High** 1,530
T5 High 1,680
Orange/T1 Low 1,060
T2 Medium/Low* 1,200
X60K
Red/T3 Medium*** 1,500
Black/T4 Medium/High** 1,760
T5 High 1,970
* Denotes Factory Set Low Speed Cooling/ Heating
** Denotes Factory Set High Speed Cooling/ Heating
*** Denotes Factory Set Electric Heating Speed
Table 2. Motor Lead Connection
10
Control is uncalibrated when power is applied. Calibration occurs after a defrost cycle. The control initiates defrost after 34 minutes of accumulated compressor run time in heating with coil temperature below 35° F. The defrost cycle terminates when the coil sensor reaches termination temperature or after 14 minutes. Note: All units are shipped from the factory with the default termination temperature set at 70° F.
Defrost function is disabled if coil temperature is above 35° F. If the ambient sensor is detected as open or shorted, demand defrost will not operate and control will revert to time/temperature defrost operation. If the outdoor coil sensor is detected as open or shorted, the control will not perform demand or time/temperature defrost operation. Note: When the defrost cycle initiates, there will be a 30 second compressor delay going into and out of the defrost cycle. This delay may be removed by removing P6 connector on the board.
This 2-stage unit will defrost in second stage regardless of the stage called for by the thermostat.
Diagnostic Description LED Status
Control Fault (No Power) Off
Normal Operation On ASCD Delay Active
(with compressor demand)
1 Flash
Low Pressure Switch Lockout 2 Flashes
High Pressure Switch Lockout 3 Flashes
Ambient Sensor Fault 4 Flashes
Coil Sensor Fault 5 Flashes
6. Install one spacer next between the plastic clip and mounting bracket.
7. Bend the mounting bracket into position. Install the mounting bracket to the unit using the screw in the corner panel.
Nut
Bolt
Nut
Ambient Sensor
Plastic Clip
Star Bushing
Figure 10. Ambient Sensor Mounting
Electric Heat Package (optional)
This heat pump is shipped without an auxiliary electric heat kit installed. If electric heat is desired, an accessory Heater Kit must be fi eld installed. See Specifi cations Sheet for available kits and their application.
• Select the correct size heat package for the
installation.
• Follow installation instructions provided with
each heater kit.
• Installation is most easily accomplished before
making duct or electrical connections.
• Refer to Table 2 (page 10) for blower
speeds.
Table 3. Control Diagnostic
Ambient Sensor Mounting
For optimum performance of the heat pump system, the ambient sensor (Figure 10) must be mounted on the outside of the unit.
1. Remove the mounting bracket and all hardware included in the packet.
2. Remove star bushing from 7/8” hole in corner panel of the unit.
3. Route the ambient sensor through the 7/8” hole in the corner panel of the unit, and then through the 7/8” hole in the mounting bracket.
4. Route the sensor through the star bushing. Use the star bushing to secure the mounting bracket to the unit.
5. Secure the ambient sensor inside the plastic clip and secure it to the mounting bracket with the screw and nut provided.
11
SYSTEM OPERATION
Pre-Start Checklist
The following check list should be observed prior to starting the unit. Is the unit level? Unit should be level or slightly
slanted toward the drain for proper condensate drainage.
Is the unit installed with the proper clearances
as listed in Figure 2 (page 5)?
Is the wiring correct according to the wiring
diagram and electrical codes?
Are all the wiring connections tight? Check the
condenser fan to make sure it turns freely.
Is the overcurrent protection properly sized? Is the thermostat wired correctly? Is it installed
in a proper location?
Start-Up Procedure
The control circuit consists of an anti-short cycle timer that will not let the compressor re-start before three (3) minutes have elapsed.
Set the thermostat system mode to OFF, and the thermostat fan mode to AUTO. Apply power at the disconnect switch and check the system operations:
Air Circulation Leave the thermostat system mode on OFF,
and set the fan mode to ON. Blower should run continuously. Check the air delivery at the supply registers and adjust register openings for balanced air distribution. Examine ductwork for leaks or obstruction if insuffi cient air is detected.
Set the thermostat fan mode to AUTO. The blower should stop running.
System Heating Set the thermostat system mode to HEAT and
the fan mode to AUTO. Change the thermostat temperature selector above the existing room temperature and check for the discharge of warm air at the supply registers.
System Cooling Set the thermostat’s system mode to COOL and
the fan mode to AUTO. Change the thermostat temperature selector below the existing room temperature. Allow the cooling system to operate for several minutes and check for the discharge of cool air at the supply registers.
setting until the whole system de-energizes. Immediately lower the thermostat temperature to the original setting and verify that the indoor blower is energized. After approximately 3 minutes the compressor and the outdoor fan will energize.
Emergency Heat (Available only when Electric heat is supplied)
Set the thermostat’s system mode to EM HT and the fan mode to either AUTO (intermittent air) or to ON (continuous air). Change the thermostat’s temperature selector above the existing room temperature and check the following:
1. The thermostat auxiliary heat light (RED) should be on.
2. The heat pump compressor and the fan should not run; low voltage circuit remains energized.
3. The blower will run according to the thermostat’s fan mode setting.
Defrost Test Procedure
1. Terminals R & C must have 18 - 30V between them for defrost sequences to initiate.
2 With thermostat in heat mode (Y connected to
R), short (and hold) the “TEST” pins together. NOTE: This energizes the reversing valve to
initiate a forced defrost, bypass the ASCD, and allow the high stage compressor to turn on immediately (if the “REMOVE FOR NO DELAY” jumper at P6 is removed). If the “REMOVE FOR NO DELAY” jumper at P6 is installed, the compressor will energize after a 30 second delay.
3. Remove the short on the “TEST” pins.
• If the Coil temperature is above the Terminate Temperature setting, the defrost cycle will terminate (reversing valve de-energizes).
• If the coil temperature is below the Terminate Temperature setting, the defrost cycle will continue for 14 minutes (or until the coil temperature rises above the Terminate Temperature setting). Short the “TEST” pins for 1 second or more to force the control out of defrost and back to heating mode (reversing valve de-energized). Compressor will start immediately (if the “REMOVE FOR NO DELAY” jumper is removed). NOTE: If the “REMOVE FOR NO DELAY” jumper is installed, the compressor will energize after a 30 second delay.
Short Cycle Protection The control circuit is equipped with a time-delay
feature for protection against short cycling. With the system operating in the cooling mode, gradually raise the thermostat temperature
12
Note: If the Y2 thermostat input is energized (on a 2-stage system), the second stage turns on. If the above steps will not initiate a defrost, replace the defrost board.
Anti Short Cycle Timer Test
The 3 minute time delay feature can be bypassed by shorting the “TEST” pins together.
Heating Mode When the “TEST” pins are shorted together for more than 1 second, the control will switch between defrost mode and heating mode as described in the Defrost Test Procedure section (page 12).
determined in step 4, then there is too much charge in the system. Remove refrigerant and repeat steps 1 through 3 until the system is correctly charged.
• If the pressure measured in step 1 is less than the required liquid refrigerant pressure determined in step 4, then there is too little charge in the system. Add refrigerant and repeat steps 1 through 3 until the system is correctly charged.
Cooling Mode When the ‘TEST” pins are shorted together for more than 1 second, the Anti Short Cycle Timer will be bypassed.
ADJUSTMENT OF REFRIGERANT
CHARGE:
CAUTION:
This heat pump contains liquid and gaseous refrigerant under pressure. Adjustment of refrigerant charge should only be attempted by qualifi ed, trained personnel thoroughly familiar with the equipment and safe responsible refrigerant handling procedures. Under no circumstances should the homeowner attempt to install and/or service this equipment. Failure to comply with this warning could result in equipment damage, personal injury, or death.
Charging an R-410A Unit in Heating Mode.
1. Evacuate the refrigerant system.
2. Weigh in the proper charge as shown on the unit rating plate and use the Heating Charging Tables (pages 16 & 17) as a guide. Tables refl ect conditions at high speed operation. Unit charge MUST be verifi ed in cooling season.
3. Verify the unit is operating properly according to the heating functional checkout on page
12.
NOTE: The unit must be charged while both fi rst and second stages are operating.
NOTE: To achieve rated capacity and effi ciency the compressor must be exposed to refrigerant for at least 24 hours prior to running and then must be run for a minimum of 12 hours. See Refrigerant Charging Charts (Figures 11 - 14, pages 14 &
15) for Charging in Cooling Mode.
Charging an R-410A Unit in AC Mode with Outdoor Temperatures Above 65F.
1. With the system operating at steady-state, measure the liquid refrigerant pressure in psig at the service valve.
2. Measure the liquid refrigerant temperature
(° F) at the service valve.
3. For the temperature measured, determine the required liquid refrigerant pressure from the appropriate charging charts.
• If the pressure measured in step 1 is greater than the required liquid refrigerant pressure
13
Refrigerant Charging Charts for
LIQUID PRESSURE (PSIG)
LIQUID TEMP ERATURE (F)
Q5RF-X24K CHARGING CHART
LIQUID PRESSURE (PSIG)
LIQUID TEMP ERATURE (F)
Q5RF-X36K CHARGING CHART
Cooling Mode of Operation
600
575
550
525
500
475
450
425
400
375
350
325
300
275
250
225
200
70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Rem ove refrigerant w hen above curve
Add re frige ra nt w hen below c ur ve
Figure 11. Charging Chart for 2 ton Units
600
575
550
525
500
475
450
425
400
375
350
325
300
275
250
225
200
70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Rem ove refrigerant w hen above curve
Add re frige ra nt w hen below c ur ve
14
Figure 12. Charging Chart for 3 ton Units
Refrigerant Charging Charts for
LIQUID PRESSURE (PSIG)
LIQUID TEMP ERATURE (F)
Q5RF-X60K COOLING CHARGING CHART
LIQUID PRESSURE (PSIG)
LIQUID TEMP ERATURE (F)
Q5RF-X48K CHARGING CHART
Cooling Mode of Operation - Continued
600
575
550
525
500
475
450
425
400
375
350
325
300
275
250
225
200
70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Rem ove refrigerant w hen above curve
Add re frige ra nt w hen below c ur ve
Figure 13. Charging Chart for 4 ton Units
600
575
550
525
500
475
450
425
400
375
350
325
300
275
250
225
200
70 75 80 85 90 95 100 105 110 115 120 125 130 135 140
Rem ove refrigerant w hen above curve
Add re frige ra nt w hen below c ur ve
Figure 14. Charging Chart for 5 ton Units
15
359 177
129
328 158
114
297 139
99
373 165
131
342 149
116
311 134
101
406 201
128
371 177
111
335 153
94
420 188
130
385 168
113
349 147
96
Q5RF-X24K
OUTDOOR TEMPERATURE (DEG. F)
Refrigerant Charging Chart Legend for Heating Mode of Operation:
Refrigerant Charging Tables for Heating Mode of Operation
275 129
84
257 127
69
238 124
54
283 125
86
266 123
71
249 120
56
Q5RF-X36K
OUTDOOR TEMPERATURE (DEG. F)
304 135
79
270 123
65
236 110
52
312 131
81
280 119
67
248 106
54
16
Shaded boxes indicate fl ooded conditions.
vary.
Rated design values. The suction pressure will vary from design value if outdoor air fl ow, entering dry bulb, or entering wet bulb temperatures
0 102030405060
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures greater than charted values indicate an undercharged system.
Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.
Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.
37 205 126 52 226 128 67 247 131 82 268 133 97 283 145 112 314 167 127 345 189
38 212 124 53 232 126 68 252 129 83 272 131 98 290 142 113 321 163 128 352 183
219 122
39
40 226 120 55 244 122 70 261 125 85 279 127 100 304 137 115 335 154 130 366 171
233 118
41
42 240 116 57 255 118 72 271 121 87 286 123 102 318 131 117 349 145 132 380 158
43 247 114 58 261 116 73 276 119 88 290 121 103 325 128 118 356 140 133 387 152
0 102030405060
Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.
Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.
37 188 102 50 224 114 63 261 127 77 297 139 92 321 159 109 357 186 126 392 213
38 195 100 51 230 112 64 265 125 78 301 137 93 328 156 110 364 181 127 399 207
202 98
39
40 209 96 53 242 108 66 275 121 80 308 133 95 342 150 112 378 172 129 413 195
216 94
41
42 223 92 55 254 104 68 284 117 82 315 129 97 356 144 114 392 163 131 427 182
43 230 90 56 260 102 69 289 115 83 319 127 98 363 142 115 399 159 132 434 176
375 169
118
337 161
106
300 152
93
389 157
120
351 152
108
314 146
95
426 179
124
372 160
109
318 142
94
440 167
126
386 152
111
332 137
96
Refrigerant Charging Tables for Heating Mode of Operation - (continued)
Q5RF-X48K
OUTDOOR TEMPERATURE (DEG. F)
Refrigerant Charging Chart Legend for Heating Mode of Operation:
284 149
79
282 151
63
279 153
47
291 145
81
291 147
65
291 149
49
Q5RF-X60KK
OUTDOOR TEMPERATURE (DEG. F)
284 128
78
262 119
63
241 109
48
291 124
80
272 115
65
253 105
50
Shaded boxes indicate fl ooded conditions.
vary.
Rated design values. The suction pressure will vary from design value if outdoor air fl ow, entering dry bulb, or entering wet bulb temperatures
0 102030405060
1. All pressures are listed psig and all temperatures in °F
2. Discharge temperatures greater than charted values indicate an undercharged system.
Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.
Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.
29 263 160 45 268 157 61 272 155 77 276 153 91 286 158 104 323 170 116 361 181
30 270 158 46 273 155 62 277 153 78 280 151 92 293 155 105 330 165 117 368 175
277 156
31
32 284 154 48 285 151 64 286 149 80 287 147 94 307 149 107 344 156 119 382 163
291 152
33
34 298 150 50 297 147 66 296 145 82 295 143 96 321 144 109 358 147 121 396 151
35 305 148 51 303 145 67 301 143 83 298 141 97 328 141 110 365 143 122 403 144
0 102030405060
Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.
Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.
31 205 104 46 229 113 61 253 123 76 277 132 92 304 148 107 358 169 122 412 191
32 212 102 47 235 111 62 258 121 77 280 130 93 311 145 108 365 165 123 419 185
219 100
33
34 226 98 49 247 170 64 267 117 79 288 126 95 325 139 110 379 156 125 433 173
233 96
35
36 240 94 51 258 103 66 277 113 81 295 122 97 339 134 112 393 147 127 447 160
37 247 92 52 264 101 67 282 111 82 299 120 98 346 131 113 400 143 128 454 154
17
9
ORANGE
WIRE
BLACK
WIRE
RED
WIRE
X24K T2
T3 T4
T3 T4
876
5
432
0809
1
710880C
3. Not sutiable on systems that exceed 150V to ground.
4. For replacement wires use conductors suitable for 105°C.
GREY
YELLOW
60HZ/SINGLE PHASE
5. Couper le courant avant de faire letretine.
6. Employez uniquement des conducteurs
7. Ne convient pas aux installations de plus
en cuiver.
de 150V a la terre.
GREEN / YELLOW
N
L
G
C
T1
MOTOR
BLOWER
SET BLOWER WIRING
SEE TABLE FOR FACTORY
208/230 VOLTQ5RF/PPH2RF SERIES SMALL PACKAGE H/P
BLACK
HIGH SPEED
BLOWER RELAY
T2
RED
(24V)
T4
T3
ORANGE
GREY
GREEN
TO “G” ON
T5
BLOWER
BLACK
RED
RELAY
T-STAT
WHITE
BLACK
BLUE
RED
BROWN
ORANGE
YELLOW
BLUE
T-STAT
TO “W3” ON
LOW PRESSURE
COMPRESSOR
L1
L2
BLACK
SWITCH
(SELECT MODELS ONLY)
CONTACTOR
T1
T2
BLACK
BLUE
Y OUT
Y2 OUT
DF2
DF1
AMBIENT
YELLOW
LPS
AMBG
YELLOW
YELLOW / BLACK
HPS
BOARD
DEMAND
DEFROST CONTROL
COIL
YELLOW / BLACK
COILG
BLACK
REV
W2
W2
BLACK
VALV E
OUT
IN
O
Y
Y2
C
LR
MODE L
FACTORY SET INDOOR MOTOR WIRING
SWITCH
HIGH PRESSURE
COIL
REVERSING VALVE
BLACK
BLUE
BLUE
BLACK
BLACK
TO T-STAT
COMPRESSOR
C
ORANGE
X36K T1
BLACK WIRE IS HIGH SPEED COOLING/HEATING
ORANGE WIRE IS LOW SPEED COOLONG/HEATING
MOTOR
OUTDOOR
(Replaces 710880B)
RED WIRE IS AUX. HEATING SPEED (ELECTRIC HEAT)
REFER TO INSTALLATION INSTRUCTIONS FOR CFM DATA
¢710880&¤
F
YELLOW
C
H
CAPACITOR
DAUL
RED
S
R
YELLOW
BLUE
R
S
C
WIRING DIAGRAM
2 TON AND 3 TON
NOTES:
2. For supply connections use copper conductors only.
1. Disconnect all power before servicing.
4. For replacement wires use conductors
3. Not sutiable on systems that exceed 150V to ground.
suitable for 105°C.
COM
TRASFORMER
240V
24V
THERMISTOR
AMBIENT RED
3 AMP FUSE
COIL
THERMISTOR
RED
LEGEND:
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
Figure 15. Q5RF/PPH2RF Series Wiring Diagram - 2 & 3 Ton Units
18
876
ORANGE
WIRE
BLACK
WIRE
RED
WIRE
T4 T3
T4 T3
9
5
GREY
YELLOW
60HZ/SINGLE PHASE
GREEN / YELLOW
7. Couper le courant avant de faire letretine.
208/230 VOLT
de 150V a la terre.
en cuiver.
9. Ne convient pas aux installations de plus
8. Employez uniquement des conducteurs
N
L
G
C
T1
BLOWER
SEE TABLE FOR FACTORY
MOTOR
SET BLOWER WIRING
BLACK
(24V)
HIGH SPEED
BLOWER RELAY
T2
RED
T3
GREY
GREEN
T4
BLOWER
T5
RELAY
T-STAT
TO “G” ON
BLACK
BLACK
WHITE
432
BLUE
RED
RED
1
BROWN
ORANGE
BLUE
T-STAT
TO “W3” ON
SWITCH
LOW PRESSURE
(SELECT MODELS ONLY)
COMPRESSOR
CONTACTOR
L1
T1
L2
T2
BLACK
BLACK
BLACK
SWITCH
HIGH PRESSURE
YELLOW
BLUE
Y OUT
Y2 OUT
DF2
DF1
AMBIENT
AMBG
YELLOW
LPS
DEMAND
0809
710890B
(Replaces 710890A)
X48K T1
X60K T2
MODE L
FACTORY SET INDOOR MOTOR WIRING
BLACK WIRE IS HIGH SPEED COOLING/HEATING
ORANGE WIRE IS LOW SPEED COOLONG/HEATING
RED WIRE IS AUX. HEATING SPEED (ELECTRIC HEAT)
REFER TO INSTALLATION INSTRUCTIONS FOR CFM DATA
¢710890+¤
COIL
REVERSING VALVE
YELLOW / BLACK
YELLOW / BLACK
BLACK
BLACK
BLACK
BLUE
BLUE
BLUE
REV
HPS
VALV E
W2
OUT
IN
W2
O
Y
BOARD
COIL
Y2
C
LR
COILG
DEFROST CONTROL
BLACK
YELLOW
BLACK
TO T-STAT
DAUL
COMPRESSOR
C
WHITE
MOTOR
OUTDOOR
Y1
L1
BROWN
CAPACITOR
YELLOW
Y2
F
C
H
RED
S
R
YELLOW
C
ECM
L2
WIRING DIAGRAM
NOTES:
Q5RF/PPH2RF SERIES SMALL PACKAGE H/P
4 TON AND 5 TON
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
4. For replacement wires use conductors suitable for 105°C.
3. Not sutiable on systems that exceed 150V to ground.
COM
TRASFORMER
240V
24V
THERMISTOR
AMBIENT
RED
3 AMP FUSE
COIL
THERMISTOR
RED
LEGEND:
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
Figure 16. Q5RF/PPH2RF Series Wiring Diagram - 4 & 5 Ton Units
19
INSTALLER
PLEASE LEAVE THESE INSTALLATION
INSTRUCTIONS WITH THE HOMEOWNER.
709064B (Replaces 709064A)
O’Fallon, MO
¢709064-¤
709064B
Specifi cations and illustrations
subject to change without
notice or incurring obligations.
Printed in U.S.A. (09/09)
Loading...