Nordyne Q5RD, Q5RD024K, Q5RD030K, Q5RD036K, Q5RD042K Installation Manual

...
Q5RD SERIES
13 SEER
USER’s MANUAL & INSTALLATION INSTRUCTIONS
Single Package Heat Pump - Single Stage, R-410A
Please read this information thoroughly and become familiar with the capabilities and use of your appliance before attempting to operate or maintain this unit. Keep this literature where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your servicing contractor.
DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
IMPORTANT
USER INFORMATION
About the Heat Pump ................................... 3
Operating Instructions ................................ 3
Cooling Operation .................................... 3
Heating Operation ....................................3
Emergency Heat ......................................3
Defrost .....................................................3
System Shutdown .................................... 3
INSTALLER INFORMATION
Important Safety Information ......................4
General Information .....................................4
Before You Install this Unit ..........................4
Locating the Heat pump ............................ 4
Minimum Clearances .................................5
Service Access Clearance ......................5
Clearances to Combustibles ...................5
Air Duct System .........................................5
Heat Pump Installation .................................5
Unpacking the Unit ....................................5
Installing Return & Supply Air Collars ........5
Supply Duct ............................................5
Return Duct .............................................6
Connecting Return & Supply Air
Flexible Ducts .............................................6
Locating & Installing the Return Air
Assembly .................................................... 6
Locating & Installing the Supply
Dampers ..................................................... 7
Condensate Drainage .................................7
Electrical Connections .................................8
Pre - Electrical Checklist.............................8
Line Voltage ................................................8
Overcurrent Protection ............................... 9
Blower Speed ............................................9
2 - Speed Outdoor Fan Motor ..................9
Defrost Cycle Control .................................9
Ambient Sensor Mounting 10
Thermostat Connections ..........................10
Electric Heat Package ..............................11
Grounding .................................................11
Startup & Adjustments...............................11
Pre - Start Checklist .................................11
Start - Up Procedure ................................11
Air Circulation ........................................11
System Heating .....................................11
System Cooling ......................................11
IMPORTANT SAFETY INFORMATION
Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING indicates a potentially hazardous situation that if not avoided, could result in personal injury or death. CAUTION indicates a potentially hazardous situation that if not avoided, may result in minor or moderate injury or property damage.
Short Cycle Protection ...........................12
Emergency Heat ....................................12
Defrost Test Procedure .............................12
Anti Short Cycle Timer Test ......................12
Heating Mode ........................................12
Cooling Mode .........................................12
Adjustment of Refrigerant Charge ............12
Charging an R-410A Unit in AC Mode
with Outdoor Temp above 65° F ...............12
Charging R-410A Unit in Heat Mode .......13
Component Functions ...............................13
Low Pressure Switch ................................13
High Pressure Switch ...............................13
Unit Maintenance ........................................13
Figures & Tables .........................................13
Figure 9. - Unit Dimensions ....................13
Table 4. - Q5RD Physical Data ...............13
Charging Tables - Cooling Mode ..............14
Table 5. - Q5RD-X24K (2 Ton Units) .......14
Table 6. - Q5RD-X30K (2.5 Ton Units) ....14
Table 7. - Q5RD-X36K (3 Ton Units) .......15
Table 8. - Q5RD-X42K (3.5 Ton Units) ....15
Table 9. - Q5RD-X48K (4 Ton Units) .......16
Table 10. - Q5RD-X60K (5 Ton Units) .....16
Charging Tables - Heating Mode ..............17
Table 11. - Q5RD-X24K (2 Ton Units) .....17
Table 12. - Q5RD-X30K (2.5 Ton Units) ..17
Table 13. - Q5RD-X36K (3 Ton Units) .....18
Table 14. - Q5RD-X42K (3.5 Ton Units) ..18
Table 15. - Q5RD-X48K (4 Ton Units) .....19
Table 16. - Q5RD-X60K (5 Ton Units) .....19
Wiring Diagrams .......................................20
Figure 10. - 2 & 2.5 Ton Units .................20
Figure 11. - 3,4, & 5 Ton Units ................21
Figure 12. - Thermostat Connections .....22
Installation / Performance Checklist .........24
2
USER INFORMATION
ABOUT THE HEAT PUMP
Your heat pump is a unique, all weather comfort­control appliance that will heat and cool your home year round and provide energy saving comfort. It’s an unknown fact that heat is always in the air, even when the outside temperature is below freezing. The heat pump uses this basic law of physics to provide energy saving heat during the winter months. For example, If the outdoor temperature is 47° F (8° C), your heat pump can deliver approximately 3.5 units of heat energy per each unit of electrical energy used, as compared to a maximum of only 1 unit of heat energy produced with conventional heating systems.
In colder temperatures, the heat pump performs like an air conditioner run in reverse. Available heat energy outside the home is absorbed by the refrigerant and exhausted inside the home. This effi cient process means you only pay for “moving” the heat from the outdoors to the indoor area. You do not pay to generate the heat, as is the case with more traditional furnace designs.
During summer, the heat pump reverses the fl ow of the heat-absorbing refrigerant to become an energy-effi cient, central air conditioner. Excess heat energy inside the home is absorbed by the refrigerant and exhausted outside the home.
Operating Instructions
Cooling Operation
1. Set the thermostat’s system mode to COOL or AUTO and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired temperature level. The outdoor fan, compressor, and blower motor will all cycle on and off to maintain the indoor temperature at the desired cooling level.
minutes following a previous operation or the interruption of the main electrical power.
Emergency Heat Some thermostats may include a system mode called EM HT or AUX HT, etc. This is a back­up heating mode that should only be used if a problem is suspected. With the mode set to EM HT, etc., the compressor and outdoor fan will be locked off and supplemental heat (electric resistance heating) will be used as a source of heat (if installed). Sustained use of electric resistance heat in place of the heat pump will result in an increase in electric utility costs.
Defrost During cold weather heating operation, the outdoor unit will develop a coating of snow and ice on the heat transfer coil. This is normal and the unit will defrost itself. This unit features Demand Defrost that monitors ambient and coil temperatures to regulate the defrost function accordingly.
At the beginning of the defrost cycle, both the outdoor condenser fan and compressor will turn off. After approximately 30 seconds, the compressor will turn on and begin to heat the outdoor coil causing the ice and snow to melt. NOTE: While the ice and snow is melting, steam may rise from the outdoor unit as the warm coil causes the melting frost to evaporate. When defrost is completed, the outdoor fan motor will start, and the compressor will turn off again. In approximately 30 seconds the compressor will start up again and continue normal operation.
System Shutdown Change the thermostat’s system mode to OFF and the fan mode to AUTO (See Figure 1). NOTE: The system will not operate, regardless of the temperature selector setting.
Heating Operation
1. Set the thermostat’s system mode to HEAT or AUTO and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired temperature level. The compressor, outdoor fan, and blower motor will cycle on and off to maintain the indoor temperature at the desired heating level.
NOTE: If the temperature level is re-adjusted, or the system mode is reset, the fan and compressor in the outdoor unit may not start immediately. A protective timer circuit holds the compressor and the outdoor fan off for approximately three
Fan
Mode
Figure 1. Digital Thermostat
System
Mode
Temperature
Selector
3
INSTALLER INFORMATION
IMPORTANT SAFETY INFORMATION
WARNING:
The information listed below must be followed during the installation, service, and operation of this unit. Unqualifi ed individuals should not attempt to interpret these instructions or install this equipment. Failure to follow safety recommendations could result in possible damage to the equipment, serious personal injury or de
• The installer must comply with all local
codes and regulations which govern the installation of this type of equipment. Local codes and regulations take precedence over any recommendations contained in these instructions. Consult local building codes and the National Electrical Code (ANSI CI) for special installation requirements.
• This equipment contains liquid and gaseous
refrigerant under high pressure. Installation or servicing should only be performed by qualifi ed trained personnel thoroughly familiar with this type equipment.
• All electrical wiring must be completed in
accordance with local, state and national codes and regulations and with the National Electric Code (ANSI/NFPA 70) or in Canada the Canadian Electric Code Part 1 CSA C22.1.
• Follow all precautions in the literature, on tags,
and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment.
GENERAL INFORMATION
Single packaged heat pumps are ready for easy and immediate installation and can be readily connected into the high static duct system of a home. This unit is completely assembled, wired, and run tested at the factory. This heat pump is designed for outdoor installation only. The only connections needed for installation are the supply and return ducts, the line voltage, and thermostat wiring. Use of components other than those specifi ed may invalidate ARI Certifi cation, Code Agency Listing, and limited warranty on the air conditioner.
4
ath
Before You Install this Unit
The cooling load of the area to be conditioned
must be calculated and a system of the proper capacity selected. It is recommended that the area to be conditioned be completely insulated and vapor sealed.
Check the electrical supply and verify the
power supply is adequate for unit operation. If there is any question concerning the power supply, contact the local power company.
All units are securely packed at the time of
shipment and upon arrival should be carefully inspected for damage prior to installing the equipment at the job site. Verify coil fi ns are straight. If necessary, comb fi ns to remove
.
fl attened or bent fi ns. Claims for damage should be fi led immediately with the carrier.
Please consult your dealer for maintenance
information and availability of maintenance contracts. Please read all instructions before installing the unit.
Locating the Heat Pump
• Survey the job site to determine the best location for mounting the outdoor unit. Select a solid, level position, preferably on a concrete slab, slightly above the grade level, and parallel to the home. If possible, select a site for the unit that is as close as possible to the proposed return grille location. DO NOT PLACE UNIT
UNDER THE HOME.
• The unit should be located with consideration of minimizing the length of the supply and return ducts. If practical, place the heat pump and its ducts in an area where they will be shaded from the afternoon sun, when the heat load is greatest.
• The length of the supply and return ducts should be kept to a minimum with no sharp radius bends.
• Overhead obstructions, poorly ventilated areas, and areas subject to accumulation of debris should be avoided. The hot condenser air must be discharged up and away from the home, and if possible, in a direction with the prevailing wind. Do not place the unit in a confi ned space. See Figure 9 & Table 4 (page
13) for unit dimensions.
• Suffi cient clearance for unobstructed airfl ow through the outdoor coil must be maintained in order to achieve rated performance. See Figure 2 (page 5) for minimum clearances to obstructions.
• Consideration should also be given to availability of electric power, service access, noise, and shade.
Minimum Clearances
Minimum clearances MUST be maintained from adjacent structures to provide room for proper servicing and air circulation. DO NOT install unit in a confi ned or recessed area that will allow discharge air from the unit to re-circulate into the condenser air inlet, through the coil. See Figure 2.
Service Access Clearance:
Blower access panel side ...........................24”
Electrical compartment access panel side .. . 1 2” Clearance between overhang and top
of unit ..................................................... 72”
Clearance around condenser coil area to wall or shrubs (excludes duct panel side) ...12”
Clearances to Combustibles: Combustible base - wood or Class A, B, or C
roof covering material ................................. 0”
Supply & return air ducts ............................. 0”
Duct connection side ................................... 0”
• For highly resistive duct systems it may be necessary to add an additional return air duct and or supply to achieve maximum performance and prevent coil icing and refrigerant fl ood back.
The heat pump system will not cool or
heat the home if air is lost to the outside through leaks in the duct system. Ducts that are collapsed or restricted by foreign objects will also prevent adequate air fl ow.
• All duct work passing through unconditioned space must be properly insulated to minimize duct losses and prevent condensation. Use insulation with an outer vapor barrier. Refer to local codes for insulation material requirements.
HEAT PUMP INSTALLATION
Unpacking the Unit
It is recommended that the unit be unpacked at the installation site to minimize damage due to handling.
12"
24"
TO BE
TOP OF UNIT
UNOBSTRUCTED
0"
Figure 2. Minimum Unit Clearances
Air Duct System
Air ducts should be installed in accordance with the standards of the National Fire Protection Association “Standard for Installation of Air Conditioning and Ventilation Systems” (NFPA 90A), “Standard for Installation of Residence Type Warm Air Heating and Air Conditioning Systems” (NFPA 90B), these instructions, and all applicable codes. NFPA publications are available by writing to: National Fire Protection Association, Batterymarch Park, Quincy, ME 02269 or visit www.NFPA.org on the web.
• Design the duct work according to methods described by the Air Conditioning Contractors of America (ACCA).
• The supply duct system, including the number and type of registers, will have much more effect on the performance of the system than any other factor. The duct must be suffi ciently large to conduct an adequate amount of air to each register. See Figure 5 (page 7).
• Duct work should be attached directly to the unit fl anges for horizontal applications.
12"
CAUTION:
Do not tip the unit on its side. Oil may enter the compressor cylinders and cause starting trouble. If unit has been set on its side, restore to upright position and do not run for several hours. Then run unit for a few seconds. Do this three or four times with fi ve minutes between runs.
1. Remove the bands from around the unit.
2. Unfold the top and bottom cap fl anges.
3. Carefully remove the top cap and tube.
Installing Return & Supply Air Collars
If the supply and return collars are supplied with the unit, they will be located in the supply duct. They can be easily positioned over the unit openings (Figure 3, page 6) and secured with sheet metal screws.
• The diameter of the return duct collar is 14”. NOTE: 2 ton units are designed with 12” returns.
• The diameter of the supply duct collar is 12”.
• Before permanently installing the collars, it is recommended you pre-fi t them over the openings fi rst to determine best fi t and alignment.
Supply Duct
1. Assemble the collar by overlapping the two ends.
NOTE: One end of the collar is slotted and the opposite end has two small holes. Position the end with small screw holes underneath the slotted end.
5
2. Fasten the collar ends with two self drilling sheet metal screws.
3. Position the collar over the opening and align the 4 holes in the collar with the 4 holes (or dimples depending on model) in the rear panel.
4. Using self-drilling screws (10-16x.5), secure the collar to the rear panel.
Return Duct
1. Assemble the collar by overlapping the two ends. NOTE: One end of the collar is slotted and the opposite end has two small holes. Position the end with small screw holes underneath the slotted end.
2. Fasten the collar ends with two self drilling sheet metal screws.
3. Position the collar over the opening. Align the four holes in the collar with the four dimples or holes (depending on unit model) in the panel.
4. Secure the collar to the rear panel using self drilling screws (10-16x.5).
Duct
Transition
Duct Screws
Supply Air
Dimples
Return Air
Figure 3. Return & Supply Air Collars
Locating & Installing the Return Air Assembly
To simplify installation, locate and install the return air assembly fi rst. If desired, the return opening can be located inside a closet with louvered doors that has an open area equal to or greater than a 12” x 20” grille. The return air grille can be placed in the wall of a closet and the ducted into the fi lter box through a boxed-in area at the closet fl oor level. Make sure the fi lter
is readily accessible.
NOTE: The return air box with grille and fi lter
(Figure 4) should not be located in heavy traffi c areas like hallways or center of rooms. A good spot is in a corner or under a table, if a minimum two inch clearance is available.
1. Start the installation from under the home by cutting a small hole in the sub-fl oor. Determine how the fl oor joist location will affect cutting the opening needed for the return air box. NOTE: Floor joists are generally located on 16” centers, leaving 14-3/8” between joists.
2. After measuring the return air box (approximately 12-1/4” x 20-1/4”), cut the hole through the fl oor so that the box will fi t between the fl oor joists. Care should be taken when cutting through carpeting to avoid snags. NOTE: In most installations it will be necessary to cut a similar hole in the fi berboard directly under the hole in the fl oor. However, if the fl oor is more than ten inches deep, it will only be necessary to cut a hole for the collar on the return air box or for the insulated duct.
3. Set the box into the opening and fasten with screws or nails.
4. Put the fi lter and return air grille in place.
Connecting Return & Supply Air Flexible Ducts
• Flexible ducts may be cut to the required length and spliced with sheet metal sleeves and clamps. Keep all ducts as short and
straight as possible. Avoid sharp bends.
Please follow all instructions packed with duct.
• Flexible ducts can be secured to the corresponding collars with the provided clamps. After the inner duct is connected to the collar, pull the insulation and plastic sleeve over the connection and clamp. NOTE: To prevent a loss in cooling capacity, make sure all connections are tight.
• Homes with multiple supply ducts (or special applications), a Y fi tting is available for dividing the supply air to different areas of the home for more effi cient cooling. NOTE: For maximum performance, insulate the Y fi tting.
6
Figure 4. Return Air Box
MULTIPLE DUCT APPLICATIONSINGLE DUCT APPLICATION
Figure 5. Typical Duct Applications
Locating & Installing the Supply Damper(s)
When locating the supply damper(s), carefully check fl oor joists and frame members that could interfere with the installation of the damper or fl exible duct. Ideally, the damper (Figure 6) should be located in the bottom of the main duct, forward of center of the home, at least three feet from the nearest register. The round supply opening in the slanted side of the damper should face the side of the home where the heat pump is located.
1. Locate the center of the heat duct by cutting
a small hole in the fi berboard below the duct at the desired location.
2. Cut a hole approximately 3/4” larger than the
damper opening in the fi berboard.
3. Cut a 9-1/8” x 13-1/8” hole in the duct and
bend over all tabs fl at on the inside of the heat duct.
4. Insert the damper into the duct and bend over
all tabs fl at on the inside of the heat duct.
5. Seal the opening between the fi berboard and
damper or fl exible duct.
Condensate Drainage
A 3/4” condensate fi tting extends out of the side of the unit as shown in Figure 7. The drain trap, shipped in the electrical compartment, must be installed to prevent water from collecting inside the unit.
1. Thread the elbow provided with the unit into the drain connection until hand tight.
2. Connect the condensate tubing onto the fi tting, forming a trap near the drain connection. See Figure 7.
3. Route the condensate tube from the trap to a suitable drain. NOTE: For proper drainage, make sure the trap is level to the ground and tubing outlet is below trap level.
Elbow
AUTOMATIC DAMPER IS CLOSED
Figure 6. Supply Damper
WHEN HEAT PUMP IS OFF
P-Trap
Figure 7. Drain Trap
7
ELECTRICAL CONNECTIONS
WARNING:
To avoid electric shock, personal injury, or death, turn off the electric power at the disconnect or the main service panel before making any electrical connections.
• Electrical connections must be in compliance with all applicable local codes and ordinances, and with the current revision of the National Electric Code (ANSI/NFPA 70).
• For Canadian installations the electrical connections and grounding shall comply with the current Canadian Electrical Code (CSA C22.1 and/or local codes).
Pre-Electrical Checklist:
Verify that the voltage, frequency, and phase
of the supply source match the specifi cations on the unit rating plate.
Verify that the service provided by the utility is
suffi cient to handle the additional load imposed by this equipment. Refer to the unit wiring label for proper high and low voltage wiring.
Verify factory wiring is in accordance with the
unit wiring diagram (Figures 10 & 11, pages 20 & 21). Inspect for loose connections.
Line Voltage
• It is recommended that the line voltage to the unit be supplied from a dedicated branch circuit containing the correct fuse or circuit breaker for the unit.
An electrical disconnect must be located
within sight of and readily accessible to the unit. This switch shall be capable of electrically
de-energizing the outdoor unit. See unit data label for proper incoming fi eld wiring. Any other wiring methods must be acceptable to authority having jurisdiction.
• Provide power supply for the unit in accordance with the unit wiring diagram, and the unit rating plate.
• Connect the line-voltage leads to the terminals on the contactor inside the control compartment. Extend leads through power wiring hole (Figure 8). Connect L1 & L2 directly to the contactor.
• Use only copper wire for the line voltage power supply to this unit as listed in Table 1. Use proper code agency listed conduit and a conduit connector for connecting the supply wires to the unit. Use of rain tight conduit is recommended.
8
• See the unit wiring label for proper high and low voltage wiring. Make all electrical connections in accordance with all applicable codes and ordinances. See Figures 10 & 11 (pages 20 & 21)
CAUTION:
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
• Units are shipped from the factory wired for 240 volt transfor mer operation. For 208V operation, remove the lead from the transformer ter minal marked 240V and connect it to the terminal marked 208V.
COPPER WIRE SIZE — AWG
(1% Voltage Drop)
Supply Wire
Length (Feet)
200 150 100 50
6 8 10 14 15
46812 20
46810 25
44610 30
346 8 35
346 8 40
234 6 45
234 6 50
234 6 55
123 4 60
Wire Size based on N.E.C. for 60° type copper conductors.
Table 1. Copper Wire Size
High Voltage
Low Voltage
Figure 8. Power Entry
Supply
Circuit
Ampacity
Loading...
+ 16 hidden pages