Page 1

Installation, Operation and
Maintenance Manual
Oil Fired Warm Air Furnaces
O4HD-091A-12-FB (Up-Flow Model)
O4HD-091A-14-FA-DV (Up-Flow Model)
O4HD-091A-V-FA (Up-Flow Model with ECM)
FOR YOUR SAFETY:
Do not store or use gasoline or other flammable liquids or
vapors in the vicinity of this, or any other appliance.
ALL INSTALLATIONS MUST MEET ALL
LOCAL, PROVINCIAL/STATE, AND
FEDERAL CODES WHICH MAY
DIFFER FROM THIS MANUAL
NORDYN E INC.
Read this complete manual before
beginning installation. These instructions
must be kept with the furnace for future
reference.
®
C
151B-0810 (Replaces 151B-0909)
Page 2

TABLE OF CONTENTS
1. INTRODUCTION ................................................................................................................................. 3
2. HEAT LOSS ........................................................................................................................................ 3
3. LOCATION OF UNIT .......................................................................................................................... 3
4. AIR CONDITIONING APPLICATIONS ............................................................................................... 4
5. COMBUSTION AIR ............................................................................................................................. 4
6. CHIMNEY VENTING ........................................................................................................................... 4
7. BAROMETRIC DAMPER CONTROL ................................................................................................. 4
8. OPTIONAL SIDE WALL VENTING ..................................................................................................... 5
9a, 9b. FAN TIMER BOARD AND LIMIT CONTROL (FIGURE 4 AND 5) ............................................. 5
10. ELECTRICAL CONNECTIONS ......................................................................................................... 5
11. HUMIDIFIER ...................................................................................................................................... 6
12. PIPING INSTALLATION ................................................................................................................... 6
13. OIL FILTER ....................................................................................................................................... 6
14. OIL BURNER NOZZLES ................................................................................................................... 6
15. OIL BURNER ADJUSTMENT ........................................................................................................... 6
16. BURNER ELECTRODES .................................................................................................................. 7
17. BURNER PRIMARY (SAFETY) CONTROL ...................................................................................... 7
18. COMBUSTION CHAMBER ............................................................................................................... 7
19a, 19b. CIRCULATING AIR BLOWER ................................................................................................ 7
20. MAINTENANCE AND SERVICE ....................................................................................................... 8
21. OPERATING INSTRUCTIONS .......................................................................................................... 9
22. ECM BLOWER MOTOR OPERATION ...................................................................................... 9
APPENDIX A- O4HD-091A-12-FB, O4HD-091A-14-FA-DV AND O4HD-091A-V-FA ........................... 11
A.1 OIL BURNER AIR ADJUSTMENT .................................................................................................. 12
A.2 BURNER ELECTRODES ................................................................................................................ 12
A.3 START UP ....................................................................................................................................... 12
APPENDIX B: WIRING DIAGRAMS ...................................................................................................... 17
OPERATION OF OIL BURNER ............................................................................................................. 19
APPENDIX C OIL PRIMARY CONTROL DETAILED SEQUENCE OF OPERATION ......................... 20
OIL PRIMARY CONTROL LED DIAGNOSTIC LIGHT .......................................................................... 24
FINAL CHECK OUT ............................................................................................................................... 30
HOMEOWNER'S REFERENCE TABLE ................................................................................................ 31
PARTS LISTING: HIGHBOY MODEL: O4HD-091A-12-FB, O4HD-091A-14-FA-DV, AND
O4HD-091A-V-FA .................................................................................................................................. 32
NOTES: .................................................................................................................................................................. 35
Page 3

IMPORTANT:
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
1. INTRODUCTION 3. LOCATION OF UNIT
Please read these instructions completely and carefully
before installing and operating the furnace.
MODELS O4HD-091A-12-FB, O4HD-091A-14-FA-
DV, AND O4HD-091A-V-FA
Models O4HD-091A-12-FB, O4HD-091A-14-FA-DV and
O4HD-091A-V-FA are oil fired forced air up-flow furnaces
with an output capacity range of 59,000 BTU/Hr. to
86,000 BTU/Hr.
I `cAUTION I
DO NOT USE GASOLINE, CRANK CASE OIL, OR
ANY OIL CONTAINING GASOLINE.
All models are CSA listed, (NRTL/C) for use with No. 1
(Stove) and No. 2 (Furnace) Oil. Please refer to the
tables in Appendix A for performance and dimensional
data.
In Canada, the installation of the furnace and related
equipment shall be installed in accordance with the
regulations of CAN/CSA - B139, Installation Code for Oil-
Buming Equipment, as well as in accordance with local
codes.
In the United States of America, the installation of the
furnace and related equipment shall be installed in
accordance with the regulations of NFPA No. 31,
Standard for the Installation of OiI-Buminq Equipment, as
well as in accordance with local codes.
Regulations prescribed in the National Codes and Local
regulations take precedence over the general
instructions provided on this installation manual. When in
doubt, please consult your local authorities.
All models are shipped assembled and pre-wired. The
furnace should be carefully inspected for damage when
being unpacked.
The furnace should be located such that the flue
connection to the chimney is short, direct and
consists of as few elbows as possible. When
possible, the unit should be centralized with respect
to the supply and return air ductwork. A central
location minimizes the trunk duct sizing. All models
may be installed on combustible floors.
The minimum installation clearances are listed in
Table 1.
Table 1: Clearances - (Inches)
Clearance to Combustibles
O4HD-091A-12-FB, O4HD-
Location
Top
Bottom
S/A Plenum
Rear
Sides
Front
Flue Pipe
Enclosure
"18 in. in USA
** 24 in. required for service clearance
091A-14-FA-DV and O4HD-
091A-V-FA
Up flow
1
0
1
1
1
1 **
9*
Closet
2. HEAT LOSS
The maximum hourly heat loss for each heated space
shall be calculated in accordance with the procedures
described in the manuals of the Heating, Refrigeration
and Air Conditioning Institute of Canada (HRAI), or by
other means prescribed, or approved by the local
authority having jurisdiction.
In the United States, Manual J. titled, "Load Calculation"
published by the Air Conditioning Contractors of
America, describes a suitable procedure for calculating
the maximum hourly heat loss.
HEAT EXCHANGER _PORT SCREWS
Before final placement of the furnace, the heat
exchanger support screws shown in the picture may
be removed. This may be preferable if the furnace
rear panel will be inaccessible after installation. The
screws must be removed if the heat exchanger must
be removed from the cabinet.
Page 4

4. AIR CONDITIONING APPLICATIONS
If the furnace is used in conjunction with air conditioning,
the furnace shall be installed in parallel with or upstream
from the evaporator coil to avoid condensation in the
heat exchanger. In a parallel installation, the dampers or
air controlling means must prevent chilled air from
entering the furnace. If the dampers are manually
operated, there must be a means of control to prevent
the operation of either system unless the dampers are in
the full heat or full cool position. The air heated by the
furnace shall not pass through a refrigeration unit unless
the unit is specifically approved for such service.
The blower speed must be checked and adjusted to
compensate for the pressure drop caused by the
evaporator coil. Refer to Appendix B for recommended
wiring and electrical connections of the air conditioning
controls.
5. COMBUSTION AIR
If the furnace is installed in a closet or utility room, two
openings must be provided connecting to a well-
ventilated space (full basement, living room or other
room opening thereto, but not a bedroom or bathroom).
One opening shall be located above the level of the
upper vent opening and one opening below the
combustion air inlet opening in the front of the furnace.
Each opening shall have a minimum free area of 1½
square inches per 1,000 Btu/h of total input rating of all
appliances installed in the room.
regulations, to the requirements of the National
Building Code.
NOTE: THE FURNACE IS APPROVED FOR
USE WITH TYPE L VENT OR EQUIVALENT.
I I cAuTION I
CHIMNEY VENTED VERSIONS OF
FURNACE MUST BE CONNECTED TO A
FLUE HAVING SUFFICIENT DRAFT
TIMES TO ENSURE SAFE AND
OPERATION OF THE APPLIANCE.
NOTE: THE RECOMMENDED FLUE DRAFT
PRESSURE IS -0.02 IN. W.C. (SEE FIG 2.)
The flue pipe must not pass through any floor or
ceiling, but may pass through a wall where suitable
fire protection provisions have been installed. Refer
to the latest edition of CAN/CSA B-139 for rules
governing the installation of oil burning equipment.
In the United States, refer to the latest edition of
NFPA 31 for regulations governing the installation of
oil burning equipment.
See appendix A for burner set-up.
Fig. 2: Checking Over-Fire Draft.
THE
AT ALL
PROPER
For furnaces located in buildings of unusually tight
construction, such as those with high quality weather
stripping, caulking, windows and doors, or storm sashed
windows, or where basement windows are well sealed, a
permanent opening communicating with a well ventilated
attic or with the outdoors shall be provided, using a duct
if necessary. The duct opening shall have a free area of
1½ square inches per 1,000 Btu/h of total input rating of
all appliances to be installed. When a furnace is installed
in a full basement, infiltration is normally adequate to
provide air for combustion and draft operation. Furnace
rooms under 65m3 (700 ft3) should automatically be
treated as confined space.
6. CHIMNEY VENTING
The flue pipe should be as short as possible with
horizontal pipes sloping upward toward the chimney at a
rate of one-quarter inch to the foot. The flue pipe should
not be smaller in cross sectional area than the flue collar
on the furnace. The flue pipe should connect to the
chimney such that the flue pipe extends into, and
terminates flush with the inside surface of the chimney
liner. Seal the joint between the pipe and the lining. The
chimney outlet should be at least two feet above the
highest point of a peaked roof. All unused chimney
openings should be closed. Chimneys must conform to
local, provincial or state codes, or in the absence of local
Over-fire draft access port.
7. BAROMETRIC DAMPER CONTROL.
The barometric damper control, also known as a
draft regulator, is used on conventional chimney
venting only. This control automatically maintains a
constant negative pressure in the furnace to obtain
maximum efficiency. It ensures that proper
pressures are not exceeded. If the chimney does not
develop sufficient draft, the draft control cannot
Page 5

functionproperly.The draft regulator,wheninstalled
shouldbeinthesameroomorenclosureasthefurnace
andshouldnotinterferewiththecombustionairsupplied
to the burner.Thecontrolshouldalsobelocatednear
the furnaceflue outletand installedaccordingto the
instructionssuppliedwiththeregulator.Theflueoutlet
pressure(measuredbetweenthe furnaceand draft
regulator,ortheoilburnermountingplateover-fireddraft
accessport.fig.2)shouldbesetto-0.02in.w.c.
8. OPTIONAL SIDE WALL VENTING
O4HD-091A-14-FA-DV furnace models are
manufactured to be installed as sidewall vented units.
Please refer to Direct Venting Instructions, P/N
240005236 included with the Vent Kit for details. Sidewall
Venting (Direct Venting) requires the use of a specific oil
burner; the Beckett AFII. Please refer to Appendix A,
Table A2.
Note: Sidewall venting requires special attention to
combustion air supply. There is no natural draft in the
venting system between furnace cycles; therefore, if the
indoor pressure is negative relative to the outdoors, the
vent terminal becomes a point of infiltration. This could
lead to oil odour control problems. This problem is
rectified by the use of ducted outdoor air for combustion
(semi-sealed combustion), using the Beckett AFII oil
burner. See Direct Vent Instructions supplied with the
Vent Kits.
9a. FAN TIMER BOARD AND LIMIT CONTROL
(FIG. 4) (page 22)
The Electronic Fan Timer integrates control of all burner
and circulator fan operations. This control is the central
wiring point for most of the electrical components in the
furnace. The United Technologies 1158-120 (O4HD-
091A-12-FB and O4HD-091A-14-FA-DV) has an
adjustable fan on time that is set by selecting the
dipswitch combination displayed in Chart 1. This fan on
delay can be set at 1, 2, 4 or 6 minutes. This provides a
delay between the burner ignition and blower start-up to
eliminate excessive flow of cold air when the blower
comes on. The United Technologies 1158-120 (O4HD-
091A-12-FB and O4HD-091A-14-FA-DV) has an
adjustable fan off time of 30, 60, 90 or 120 seconds
displayed in Chart 1. The fan off delay time starts when
the burner motor is de-energized at the end of a call for
heat. Blower shutdown is delayed to remove any residual
heat from the heat exchanger and improve the annual
efficiency of the furnace.
The electronic fan timer board works in conjunction with
snap disc limit controls, which perform a safety function,
and breaks power to the oil burner primary control, which
shuts off the burner if the furnace over-heats. The limit
control is thermally operated and automatically resets.
The limit control is factory installed, pre-set and is not
adjustable.
If the limit control opens with the United
Technologies 1158-120 (O4HD-091A-12-FB and
O4HD-091A-14-FA-DV) electronic fan control, the
circulating fan will be energized as well. When the
limit closes, the fan off timer will begin. At the end of
the fan off time cycle the burner will be energized,
initiating a normal burner cycle.
CHART 1
United Technologies 1158-120 (O4HD-091A-
12-FB and O4HD-091A-14-FA-DV)
Dip Switch Position Blower Delay Times
1 2 3 4 On Off
Seconds Minutes
Off Off 30
On Off 60
Off On 90
On On 120
Off Off 1
On Off 2
Off On 4
On On 6
9b. FAN TIMER BOARD AND LIMIT
CONTROL (FIG. 5) (page 22)
The United Technologies 1168-1 ECM (O4HD-
091A-V-FA) tap board has an adjustable fan on/off
delay that must be adjusted in accordance with the
furnace input rating (nozzle size). Refer to Table A-
10 (pg 15) for ECM blower set-up.
10. ELECTRICAL CONNECTIONS
The furnace is listed by the Canadian Standards
Association under the NRTL (North American)
Standard. It is factory wired and requires minimal
field wiring. All field wiring should conform to
CAN/CSA C22.1 Canadian Electrical Code, Part 1,
and by local codes, where they prevail. In the United
States, the wiring must be in accordance with the
National Fire Protection Association NFPA-70,
National Electrical Code, and with local codes and
regulations.
The furnace should be wired to a separate and
dedicated circuit in the main electrical panel;
however, accessory equipment such as electronic
air cleaners and humidifiers may be included on the
furnace circuit. Although a suitably located circuit
breaker can be used as a service switch, a separate
service switch is advisable. The service switch is
necessary if reaching the circuit breaker involves
becoming close to the furnace, or if the furnace is
located between the circuit breaker and the means
of entry to the furnace room. The furnace switch
Page 6

(serviceswitch)shouldbeclearlymarked,installedinan
easilyaccessibleareabetweenthefurnaceandfurnace
roomentry,andbelocatedinsucha mannerto reduce
thelikelihoodthatitwouldbemistakenasa lightswitch
orsimilardevice.
The power requirementfor the O4HD-091A-12-FB,
O4HD-091A-14-FA-DVandO4HD-091A-V-FAmodelsis:
120VAC,10, 60Hz.,12A.
In the United States the installation must be in
accordance with NFPA No. 31 and local codes and
authorities.
Install the oil filter as close to the burner as possible.
For further details of the oil supply tank and piping
requirements, please refer to the instructions and
illustrations in the oil burner and oil pump
instructions shipped with the furnace.
Accessoriesrequiring120VACpowersourcessuchas
electronicair cleanersandhumidifiertransformersmay
be poweredfromthe electronicfan timerboardwhere
provisionshavebeenmadefor connections,butshould
havetheirowncontrols.Donotusethedirectdrivemotor
connectionsasapowersource,sincethereisa highrisk
ofdamagingtheaccessoriesbyexposuretohighvoltage
fromthe auto-generatingwindingsof the directdrive
motor.
Thermostatwiring connectionsand air conditioning
contactorlow voltageconnectionsare shownin the
wiringdiagramsin AppendixB. Somemicro-electronic
thermostatsrequireadditionalcontrolsandwiring.Refer
tothethermostatmanufacturer'sinstructions.
Thethermostatshouldbe locatedapproximately5feet
abovethefloor,on an insidewallwherethereis good
naturalair circulation,andwherethethermostatwillbe
exposedto averageroomtemperatures.Avoidlocations
wherethethermostatwillbeexposedtocolddrafts,heat
fromnearbylampsandappliances,exposuretosunlight,
heatfrominsidewallstacks,etc.
Thethermostatheatanticipatorshouldbeadjustedtothe
amperagedraw of the heating control circuit as
measuredatthe"R"and"W"terminalsofthethermostat.
Toreducetheriskof damagingthe heatanticipator,do
notmeasurethiscurrentwiththethermostatconnected
to thecircuit.Measuretheamperagebyconnectingan
ammeterbetweenthetwowiresthatwillconnecttothe
thermostat"R"and"W"terminals.
11. HUMIDIFIER
A humidifier is an optional accessory available through
most heating supplies outlets. Installation should be
carried out in accordance with the humidifier
manufacturer's installation instructions. Water or water
droplets from the humidifier should not be allowed to
come into contact with the furnace heat exchanger. Do
not use direct drive motor connections as a source of
power for 120 VAC humidifiers and humidifier
transformers.
12. PIPING INSTALLATION
The entire fuel system should be installed in accordance
with the requirement of CAN/CSA B-139, and local
regulations. Use only an approved fuel oil tanks piping,
fittings and oil filter.
13. OIL FILTER
All fuel systems should include an oil filter between
the fuel oil storage tank and the oil burner. When
using an oil burner nozzle smaller than 0.65 U.S.
Gallons Per Hour, install an additional 7 to 10 micron
filter as close as possible to the oil burner.
14. OIL BURNER NOZZLES
The O4HD-091A-12-FB, O4HD-091A-14-FA-DV and
O4HD-091A-V-FA are certified for multiple firing
rates, ranging from 59,000 to 86,000 Btu/h. By
manipulating the oil burner nozzle, flame retention
head, static plate and temperature rise; the furnace
may be fired at an ideal rate for a wide range of
structures. Refer to Table A-l, and the furnace
rating plate to determine the proper combinations.
15. OIL BURNER ADJUSTMENT
The burner air supply is adjusted to maintain the fuel
to air ratio to obtain ideal combustion conditions. A
lack of air causes "soft" and "sooty" flames, resulting
in soot build-up throughout the heat exchanger
passages. Excess combustion air causes a bright
roaring fire and high stack temperatures resulting in
poor fuel efficiency. The O4HD-091A-12-FB, O4HD-
091A-14-FA-DV and O4HD-091A-V-FA furnaces
operate most efficiently with a No. 1 smoke spot on
the Bacharach Scale. This is not necessarily the
optimum setting; however, because dust will
inevitably build up on the air moving components of
the oil burner assembly. This will result in decreased
air supply with the potential result of soot building up
in the flue gas passageways of the heat exchanger.
Soot behaves as an insulator and impairs good heat
transfer. Stack temperature will increase, and the
overall efficiency will decrease. As a means of
avoiding this problem, it is advisable to adjust the air
supply to provide no more than a trace smoke spot
on the Bacharach Scale.
See the Venting Instructions included in the Vent
Kits for set-up details for sidewall vented furnaces.
NOTE: SIDEWALL VENTED MODELS
SHOULD BE SET UP TO DELIVER ZERO (0)
SMOKE.
Page 7

I'ACAUTION I
I'ACAUTION I
BEFORE OPERATING THE FURNACE CHECK
BURNER ALIGNMENT WITH COMBUSTION
CHAMBER. THE END CONE OF THE AIR TUBE
MUST BE CENTRED TO THE ACCOMODATING
RING PROVIDED IN THE DESIGN OF THE
COMBUSTION CHAMBER. ADJUST AS
NECESSARY.
16. BURNER ELECTRODES
Correct positioning of the electrode tips with respect to
each other, to the fuel oil nozzle, and to the rest of the
burners is essential for smooth light ups and proper
operation. Refer to the oil burner instructions shipped
with the furnace for electrode specifications.
NOTE: Beckett AF Series Burner electrode specifications
have been revised. They should be adjusted to be 5/16"
above the nozzle centerline.
17. BURNER PRIMARY (SAFETY) CONTROL
The furnace is equipped with a primary combustion
control, sometimes referred to as the burner relay or
burner protector relay, which uses a light sensing device
(cad cell) located in the burner housing, to monitor and
control combustion. Over time, dust or combustion
residuals can build up on the lens of the cad cell
impairing its response to the flame. The cad cell should
be checked for cleanliness and proper alignment if the
primary control frequently shuts down combustion.
I'ACAUTION I
ALL FURNACE CONTROLS ARE SENSITIVE
AND SHOULD NOT BE SUBJECTED TO
TAMPERING. IF PROBLEMS PERSIST, CALL
YOUR SERVICE CONTRACTOR.
18. COMBUSTION CHAMBER
This furnace is equipped with a high quality cerafelt
combustion chamber. It is held in place by a retaining
bracket.
CHECK THE ALIGNMENT OF THE COMBUSTION
CHAMBER AND OIL BURNER BEFORE FIRING.
IT IS POSSIBLE FOR THE COMBUSTION
CHAMBER TO SHIFT IF SUBJECTED TO ROUGH
HANDLING DURING TRANSIT. The combustion
chamber should be inspected for damage or carbon build
up whenever the oil burner is removed for repairs or
routine maintenance.
DO NOT START THE BURNER UNLESS THE
BLOWER ACCESS DOOR IS SECURED IN
PLACE.
19a. CIRCULATING AIR BLOWER (O4HD-
091A-12-FB)
The O4HD-091A-12-FB, O4HD-091A-14-FA-DV and
O4HD-091A-V-FA furnace models are equipped
with direct drive blower systems. O4HD-091A-12-
FB and O4HD-091A-14-FA-DV models are
equipped with PSC motors; O4HD-091A-V-FA
models are equipped with electronically commutated
motors (ECM). Direct drive blower speed
adjustments are not normally required in properly
sized extended plenum duct systems. The motor
RPM and air CFM delivery will vary automatically to
accommodate conditions within the usual range of
external static pressures typical of residential duct
systems. Under-sized duct systems may require a
higher blower speed to obtain a reasonable system
temperature rise. Some older duct systems were not
designed to provide static pressure. They typically
feature special reducing fittings at each branch run
and lack block ends on the trunk ducts. These
systems may require modification to provide some
resistance to the airflow to prevent over-amping of
the direct drive blower motor. Selecting a lower
blower speed may correct this problem. Direct drive
blower speeds are adjusted by changing the "hot"
wires to the motor winding connections. Please refer
to wiring diagrams in Appendix B or the wiring
diagram label affixed to the furnace. THE NEUTRAL
WIRE (normally the w hite w ire) IS NEVER
MOVED TO ADJUST THE BLOWER SPEED.
It is possible and acceptable to use a single blower
speed for both heating and cooling modes. The
simplest method to connect the wiring from both
modes is to use a "piggy-back connector"
accommodating both wires on a single motor tap. It
is also acceptable to connect the selected motor
speed with a pigtail joined to both heating and
cooling speed wires with a wire nut. As a safety
precaution against accidental disconnection of the
wires by vibration, it is advisable to secure the wire
nut and wires with a few wraps of electricians tape.
Page 8

I'ACAUTION I
DO NOT CONNECT POWER LEADS BETWEEN
MOTOR SPEEDS. THE NEUTRAL WIRE MUST
ALWAYS BE CONNECTED TO THE MOTOR'S
DESIGNATED NEUTRAL TERMINAL.
If the joining of the blower speed wiring is done in the
furnace junction box, tape off both ends of the unused
wire.
Do not use the blow er speed w ires as a source of
power to accessories as electronic air cleaners and
humidifier transformers. The unused motor taps auto-
generate sufficiently high voltages to damage accessory
equipment.
20. MAINTENANCE AND SERVICE
Routine Maintenance By Home Owner
Other than remembering to arrange for the annual
professional servicing of the furnace by the service
or installation contractor, the most important routine
service performed by the homeowner is to maintain
the air filter or filters. A dirty filter can cause the
furnace to over-heat, fail to maintain indoor
temperature during cold weather, increase fuel
consumption and cause component failure.
The furnace filter(s) should be inspected, cleaned or
replaced monthly. The furnace is factory equipped
with a semi-permanent type filter. If the filter is
damaged, replace with filters of the same size and
type. (See Appendix A, Table A-8).
I_WARNINGI
DISCONNECT THE POWER SUPPLY TO THE
FURNACE BEFORE OPENING THE BLOWER
ACCESS DOOR TO SERVICE THE AIR FILTER,
FAN AND MOTOR. FAILURE TO SHUT OFF
POWER COULD ALLOW THE BLOWER TO
START UNEXPECTEDLY, CREATING A RISK OF
DEATH OR PERSONAL INJURY.
19b. CIRCULATING AIR BLOWER (O4HD-091A-
V-FA) (See Section 22 Page 9)
During the routine service, inspect the general
condition of the furnace watching for signs of oil
leaks in the vicinity of the oil burner, soot forming on
any external part of the furnace, soot forming around
the joints in the vent pipe, etc. If any of these
conditions are present, please advise your service
or installation contractor.
Annual Service By Contractor
I'ACAUTION I
THE COMBUSTION CHAMBER (FIREPOT) IS
FRAGILE. USE CARE WHEN INSPECTING
AND CLEANING THIS AREA.
The heat exchanger should be inspected
periodically and cleaned if necessary. If cleaning is
necessary, SHUT OFF POWER TO THE FURNACE
and remove the burner. Using a stiff brush with a
wire handle, brush off scale and soot from insidethe
drum and flue pipe. To clean the radiator, remove
the clean-out caps screws, and remove the caps
carefully to avoid tearing the gaskets. A wire brush
can be used to loosen dirt and debris on the inside
surfaces of the radiator. Clean out all accumulated
dirt, soot and debris with a wire handled brush and
an industrial vacuum cleaner. Before replacing the
clean-out caps, inspect the gaskets. If the gaskets
are broken, remove the remnants and replace with
new gaskets.
The blower motor is factory oiled and permanently
sealed. DO NOT LUBRICATE. Excess oil causes
premature electric motor failure.
Inspect the blower fan. Clean if necessary.
Oil Burner Maintenance: Follow the instructions of
the oil burner manufacturer. (See oil burner
manufacturer's instructions supplied with furnace or
burner). It is advisable to change the oil burner
nozzle and oil filter on an annual basis.
8
Page 9

Theventingsystemshouldbecleanedandinspectedfor
signsof deterioration.Replacepittedor perforatedvent
pipeandfittings.Thebarometricdampershouldopen
andclosefreely.
All electricalconnectionsshouldbe checkedto ensure
tightconnections.Safetycontrolssuchasthehighlimit
controlsshouldbetestedforfunctionality.Thefancontrol
shouldbe checkedto ensurethatthe fanon andoff
delayfunctioncontinuestostartandstoptheblowerfan
attheoptimalsettings.
test is complete, shut off electrical power to the
furnace, replace the neutral wire to the blower fan
motor, and then restore power. The blower fan will
start up immediately. Once the temperature has
dropped and the limit control has reset, the fan will
operate until the fan off time is achieved. The oil
burner will then resume operation and continue until
the thermostat is satisfied. Restore the thermostat
setting to a comfortable temperature.
To Shut Down Unit
21. OPERATING INSTRUCTIONS (O4HD-091A-
12-FB AN D O4HD-091A-14-FA-DV)
Before Lighting
Open all supply and return air registers and grilles.
Open all valves in oil pipes.
Turn on electric power supply
To Light Unit
Set the thermostat above room temperature to call for
heat. The burner should start. NOTE: It may be
necessary to press the RESET button on the primary
combustion control relay.
There will be a fan on time delay before the circulating
fan is energized. The United Technologies 1158-120
has an adjustable fan on time that is set by selecting the
dipswitch combination displayed in Chart 1. This fan on
delay can be set at 1,2, 4 or 6 minutes.
Set the thermostat below room temperature. The oil
burner should stop.
The air circulation blower will continue to run until the
time off setting selected on the electronic fan timer
control times out. The United Technologies 1158-120
has an adjustable fan off time of 30, 60, 90 or 120
seconds. The fan timer control adjustments may be
altered if the air at the room registers is uncomfortably
high upon blower start up or shutdown.
The necessary adjustments to the fan control settings
should be determined by measuring the temperature of
the air in the supply air take-off, or within the first few
inches of the supply air trunk. The side mid point of the
transition is usually ideal, providing that the thermometer
probe is beyond the "line of sight" wherein false readings
from radiant heat could be observed. System
temperature rise is the difference in temperature
between the supply air and return air.
To check the operation of the limit switch, shut off power
to the furnace. Temporarily remove the neutral wire from
the direct drive blower motor. Restore the electrical
power to the furnace and set the thermostat above room
temperature.
After three or four minutes of burner operation, the limit
control should turn the burner off. When the limit function
Set the thermostat to the lowest possible setting.
Set the manual switch (if installed) in the Electrical
Power Supply Line to "OFF".
21. OPERATING INSTRUCTIONS (O4HD-
091A-V-FA)
Before Lighting
Open all supply and return air registers and grilles.
Open all valves in oil pipes.
Turn on electric power supply
To Light Unit
Set the thermostat above room temperature to call
for heat. The burner should start. NOTE: It may be
necessary to press the RESET button on the
primary combustion control relay.
There will be a fan on time delay before the
circulating fan is energized. The United
Technologies 1168-1 has an adjustable fan on/off
time delay that is programmed into the ECM motor,
and is set by selecting the SW4 DIP switch
combination displayed in Table A-10 page 15. Fan
on/off delay must be adjusted according to input
(nozzle size).
1. Set the thermostat below room temperature. The
oil burner should stop.
The air circulation blower will continue to run until
the blower off delay setting programmed into the
ECM motor times out.
To check the operation of the limit switch, shut off
power to the furnace. Temporarily remove the 5 pin
power connector plug from the ECM blower motor.
NOTE: Isolate the AC Line pins on the 5 pin
power connector with electrical tape to prey ent
electric shock hazard. Restore the electrical
power to the furnace and set the thermostat above
room temperature.
After three or four minutes of burner operation, the
limit control should turn the burner off. When the
limit function test is complete, shut off electrical
power to the furnace, replace the 5 pin power plug to
the blower fan motor, and then restore power. The
blower fan will start up immediately. Once the
Page 10

temperaturehasdroppedandthelimitcontrolhasreset,
thefanwilloperateuntilthefanofftimeisachieved.The
oilburnerwillthenresumeoperationandcontinueuntil
thethermostatissatisfied.Restorethethermostatsetting
toacomfortabletemperature.
NOTE: IF THE FURNACE IS TO BE SHUT DOWN
FOR AN EXTENDED PERIOD OF TIME, CLOSE
THE OIL SUPPLY VALVE TO THE BURNER.
I'ACAUTION I
DO NOT ATTEMPT TO START THE BURNER
WHEN EXCESS OIL HAS ACCUMULATED,
WHEN THE FURNACE IS FULL OF VAPOUR, OR
WHEN THE COMBUSTION CHAMBER IS VERY
HOT. NEVER BURN GARBAGE OR PAPER IN
THE FURNACE, AND NEVER LEAVE PAPER OR
RAGS AROUND THE UNIT.
22. ECM BLOWER MOTOR OPERATION
(O4HD-091A-V-FA)
Setting Blower "ON" and "OFF" Timings
Blower on/off time delays are handled by ECM
motor programming. Features of this ECM variable
speed motor are that it will deliver a constant airflow
within a wide range of external static pressures, and
also includes:
Soft Start: This ECM variable speed motor will
slowly ramp up to the required operating speed.
This feature in the heating cycle allows the heat
exchanger to reach operating temperature before
the set heat speed, which minimizes noise and
increases comfort.
Soft Stop: At the end of the heating cycle, the ECM
variable speed motor will slowly ramp down. This
feature allows for increased energy efficiency and
reduced noise levels.
Dehumidification: A dehumidification feature has
been programmed into the variable speed motor. At
the start of each cooling cycle, the variable speed
motor will run at 82% of the rated airflow for 7.5
minutes. After 7.5 minutes has elapsed, the motor
will increase to 100% of the rated airflow. This
profile is used to provide dehumidification and
improve system efficiency.
Continuous Fan Operation : When the thermostat
continuous fan (G) switch is on without a call for
heating or cooling, the indoor fan is immediately
energized up to 50% of the cooling speed. This
feature allows continuous circulation of air between
calls for heating or cooling.
If a call for heat (W) or cool (Y) occurs during
continuous fan, the blower will remain energized
10
Page 11

Appendix A- O4HD-091A-12-FB, O4HD-091A-14-FA-DV AN D O4HD-091A-V-FA
O4HD-091A-12-FB, O4HD-091A-14-FA-DV and O4HD-091A-V-FA furnaces may be used with the following oil
burners.
Please note: The Beckett AF oil burner is for applications using indoor air for combustion only. For sidewall
venting applications utilizing outdoor air for combustion, use the Beckett AFII (Balanced Flue) oil burner only.
Table A-1 Beckett AF Oil Burner Set-Up
Beckett AF Series Oil Burners
(For use with chimney vented units only)
Furnace Model Output Burner Nozzle Pump Flow Head 1 Static
BTU/Hr Model Pressure Rate Plate
O4HD-070A-12-FB 2
0.50 / 0.50
59,000 AF76BNHS 100 psig F3 3-¾in.
O4HD-070A-V-FA 2 80°A usgph
O4HD-091A-12-FB 0.65 / 0.65
O4HD-091A-12-FB
76,000 AF76BNHS 80OA 100 psig usgph F3 3-¾in.
O4HD-105A-12-FB 0.75 / 0.75
O4HD-105A-12-FB
86,000 AF76BNHS 80OA 100 psig usgph F3 3-¾in.
Head is shielded by ceramic insulator. _ Low Firing Rate Baffle required when using a 0.50-gallon
nozzle. Bold models indicate the factory equipped firing rate.
Table A-2 Beckett AFII Oil Burner Set-Up
Beckett AFII Series Oil Burners
(For use with sidewall vented units with outdoor combustion air, or chimney vented units with
indoor air for combustion)
Furnace Model Output BTU/Hr Burner Nozzle Pump Flow Head
O4HD-070A-14-FA-DV 65,000 AFII-85 60OA 120 psig usgph FB0
O4HD-091A-14-FA-DV 75,000 AFII-85 60OA 115 psig usgph FB3
O4HD-105A-14-FA-DV 86,000 AFII-85 60OA 115 psig usgph FB3
Model Pressure Rate
0.50 / 0.55
0.60 / 0.65
0.70 / 0.75
11
Page 12

NOTE: Air gate setting may vary for sidewall vented units where air gate must be adjusted to achieve
zero smoke.
A.1 OIL BURNER AIR ADJUSTMENT
For complete details, consult the oil burner instruction
manual provided in the furnace documents envelope.
Beckett AF Burner
Adjust the air shutter by loosening the locking screws
and moving the air shutter, and if necessary, the bulk
air band.
Beckett AFII Burner
Adjust the burner air supply by first loosening the
locking screw located on the black dial to the right of
the burner. Turn the black dial clockwise to increase
the combustion air and counter-clockwise to decrease
the combustion air. Re-tighten the locking screw after
obtaining the proper setting.
A.2 BURNER ELECTRODES
Adjustment of the electrode tips with respect to each
other, the nozzle, and to the rest of the burner is very
important to ensure smooth start-ups and to permit
efficient combustion.
Beckett AF Burner
Electrode gap: 5/32 inch.
Distance above horizontal centerline: 5/16 inch. Older
instruction sheets specify 7/16 inch. The current
specification is 5/16 inch.
Distance ahead of nozzle: 1/16 inch.
"Z" dimension, the distance from the front of the end
cone (head) to the face of the nozzle should be 1-1/8
inches, If a ceramic head is used, the distance from
the end cone to the nozzle face is increased to 1-3/8
inches,
A.3 START UP
The furnace should be operated for a minimum of 10
minutes to reach steady state conditions before fine
tuning combustion. The warm up time is ideal for
testing the oil pump pressure.
Drill a 1/4-inch test port in the venting between the
furnace flue outlet and draft regulator (barometric
damper). Insert a stack thermometer and note the flue
gas temperature. The flue gases should be within a
range of 350°F to 450°F. If the flue gases are below
the range, it may be necessary to slow down the
blower fan. If the flue gases are above the range, the
blower fan may require speeding up. Stack
temperature varies directly with the system
temperature rise. System temperature rise is the
difference between the furnace outlet temperature and
furnace inlet temperature as measured in the vicinity of
the connection between the plenum take-offs and the
trunk ducts. Temperature rise value is listed on the
system rating plate.
Perform a smoke spot test. The smoke spot should not
exceed No. 1 on the Bacharach Scale.
After the air adjustments have been completed, re-
check the draft pressure at the test port on the burner
mounting plate as shown in Figure 2. The draft should
be adjusted to -0.02 inches w.c.
In the United States, the Beckett AF Burner may be
equipped with Beckett's "Inlet Air Shut-Off" to increase
efficiency. (Beckett Part No. AF/A 5861).
NOTE: USE OF THE INLET AIR SHUT-OFF
COULD CAUSE POST COMBUSTION NOZZLE
DRIP.
12
Page 13

Furnace Model
Table A-6 Direct Drive Blower Set-Up PSC Motor
Blower Set-Up Cooling Capacity
0.20 in. w.c. 0.50 in. w.c. CFM
Blower Speed Motor Speed Motor Tons Power Range
O4HD-070A-12-FB
O4HD-070A-14-FA-DV
O4HD-091A-12-FB
O4HD-091A-14-FA-DV
O4HD-105A-12-FB
O4H D-105A-14-FA-DV
100-10T
DD
100-10T
DD
100-10T
DD
Low
Med-Low
Med-
High
1/2 HP
1/2 HP
1/2 HP
Med-Low
Med-High
High
1/2 HP
1/2 HP
1/2 HP
1/2 HP
1/2 HP
1/2 HP
690 - 1500
690 - 1500
690 - 1500
Furnace Model
Table A-7 Direct Drive Blower Characteristics PSC Motor
Blower
Motor
HP
Motor
FLA
AT
Speed
CFM
External Static Pressure - Inches w.c.
0.2 0.3 0.4 0.5 0.6
O4HD-A-12-FB
O4HD-14-FA-DV
070-105
100-10T
DD
1/2 HP 7 60°F
High 1741 1651 1556 1476 1369
Med-
1557 1497 1434 1369 1278
High
Med-
1063 1051 1037 1037 1011
Low
Low 697 697 687 672 646
13
Page 14

Table A-8 Direct Drive Blower Characteristics ECM Motor
Furnace Model
O4HD-070A-V-FA
O4HD-091A-V-FA
O4HD-105A-V-FA
Blower
100-10
DD
Motor
HP
1/2 HP
ECM
Motor
FLA
7.7
AT
60°F
Continuous
Fan
500 - 700
CFM RANGE
Heating
0.28 - 0.48
inches w.c.
825 - 1250
Cooling
0.5 inches
W.C.
600 - 1400
TIP: These Formulae will assist with the design of the ductwork and the determination of
airflow delivew:
CFM = Bonnet Output /(I.OgJx System Tetuloe_at.u_eRise(ATJ)
System Tempeiatu_eRise (AT)= B ozJnetOut.put/(i.0gJx CFM)
14
Page 15

Table A-9 General Dimensions (Inches)
Cabinet
Plenum Openings
Return
Supply Side Bottom
Flue
Diameter
Filter
Shipping
Weight
(LB.)
Furnace Model Width Depth Height Type Size
O4HD-A-12-FB
O4HD-A-14-FA-DV 16 x 25
070-105 22 30 -3/4 49-5/8 20½ x 20 14 x 22 14 x 22 5 Permanent x 1 210
Heiglit
-- '4_ictth-
_J
DeMh
__
Supply --
OO
o
15
Page 16

Table A-10 ECM Blower Set-Up (O4HD-091A-V-FA)
DIP SWITCH ADJUSTMENT CHART
FOR INPUT 0.50 USGPH TO 0.75 USGPH
SW1 - HEAT
DIP Switch
Position
1 2
OFF OFF
ON OFF
OFF ON
ON ON
POS.
A
B
C
D
INPUT
USGPH
0.65
N/A
0.75
0.50
SW3 - ADJUST
DIP Switch
Position
1 2
OFF OFF
ON OFF
OFF ON
ON ON
POS.
A
B
C
D
CFM
O%
(+)15%
(415%
N/A
SW2 - COOL
DIP Switch Position
1 2
OFF OFF
ON OFF
OFF ON
ON ON
POS.
A
B
C
D
AC Size
(TON)
3
2.5
2
1.5
SW4 - DELAY
DIP Switch Position
1 2
OFF OFF
ON OFF
OFF ON
ON ON
POS.
A
B
C
D
INPUT
USGPH
0.65
N/A
0.75
0.50
NOTE:
SWl (HEAT) AND SW4 (DELAY) DIP SWITCHES MUST BOTH BE ADJUSTED ACCORDING TO INPUT (NOZZLE SIZE).
SW2 (COOL): 1 TON is approximately equal to 400 CFM
SW3 (ADJUST): (Heating Mode) Increase OR decrease temperature rise respectively
(Cooling Mode) Increase OR decrease CFM respectively
16
Page 17

APPENDIX B: WIRING DIAGRAMS
Chimney Vent Burner Wiring Diagram
O4HD-091A- 12-FB O4HD-091A-V-
LEGEND/le ege_ede
120v ] FACTORY WIRING
24 V fllage a Fusine
120 V 7 FIELD WIRING
24 V ] filage au champs
(---:)_ GROUND/Terre
I TERMINAL PROVIDED/
point de raccord fourni
L1
l
!
INDOOR / BR__
ventilateur _C oBR-_
-:2
BK
N (COMMON)
WH
O TRANSFORMER/
_nsformateur
530SE L
N
%
Vl WH L
.J J
T1
T2
TERMINAL NOT PROVIDED/point
de raccord non-foumi
BK BLACK/noir Vl VIOLET/violet
BL BLUE/bleu WH WHITE/blanc
BR BROWN/brun YL YELLOW/jaune
GR GREEN/vert GND GROUND/Terre
OR ORANGE/orange CAP CAPACITOR/capaciteur
RD RED/rouge
,,/A_, AUXILIARY LIMIT (IF EQUIPPED)
\ .) limite auxiliaire- si 6quippee
/- \
{\ L)
,\F)
LIMIT/timite
LOW SPEED FAN SWITCH (IF EQUIPPED)
interupteur a basse vitesse (si equipp6e)
BLOCKED VENT SAFETY
f- \ (REQUIRED FOR CANADIAN INSTALLATIONS)
<BVS
\ /' commande d'epreuve de systeme d'evacuation bloque
(requis pourtes instalations au Canada)
_/-i\'_ IGNITER/
\--/ transformateur d'atumage
_- \ VALVE/
IxV) soupappe
POWER SUPPLY 120 VAC 60 HZ
(FUSED DISCONNECT ON HOT LEG)
El aHmentation 120 VAC 60Hz
(disjoincteur avec fusible sur ]e fl d'alimentation)
_BK-- 120V 24V
RD
WH | WHm COM 24V FL
f- \
BK i F '_ BL
\ .-/ \?;/
BL |
I
I ()
I
I
I I
L J
,A>
RD_
1158-1/1168-1
CONTROL
RD
r]
L t oRBK
l_j_-- GR_
. / ,w
/
/ ' ",_3T (T1)
BURNER MOLEX
CONNECTOR/
........._'-T (T2) connecteur molex
du br01eur
30746 Rev A
R_ 1
_------[h:--=L-.
_,__LL CNI
8
9
\ /
RtELLO 40F BURNER/brCileur
(IF AVAILABLE)/(si disponible)
- - RD
- WI-
BK-
--WI-
AL 1808
,f_ / PRIMARY
) 2 CONTROL LI BK
O 3T r /
1
MOTOR,moteur OR--
INTERRUPTED
mtenomp6e BL -- -- /3\
.....CELL F--YL SEiS!R T
so_deaflame
BECKETT AF BURNER/br01eur
BELT DRIVE MOTOR ventilateur a courroie
(IF AVAILABLE) (si disponible)
_WH_
/NLD?NOERR _ _'A°tOeTu/R ..... '
principale .....\
,BK 1158-I
CONTROL
ECM MOTOR ventilateur a ECM
(IF AVAILABLE) (si disponible)
WH_
:%_.\/11-'1",,, .I,,o..o . NEbT
1112134P \ i iii _ iii
" YL C 8 z 6 5 4 3 2 .3
\ _ h" 1168-1
CONTROL
THERMOSTAT CONNECTIONS/ 1158-1
raccorde du thermostat CONTROL
< ) !, _) , ,
,:,w>-!)--[-"
',N C_/'
THERMOSTAT
THERMOSTAT CONNECTIONS/ 1168-1
raccorde du thermostat
CONTROL
0 0 O 0 0 0
': _} {_Y _ _ ':\W/" '::\ Ri }'c'
THERMOSTAT
17
Page 18

Direct Vent Burner Wiring Diagram
O4HD-091A-14-FA-DV
I
LEGEND/le#enae
/20V ] FACTORY WIRING
24V filage a Fusine
/20v ] FIELD WIRING
24V filage au champs
L__ GROUND/Terre
I TERMINAL PROVIDED/
point de raccord foumi
TERMINAL NOT PROVIDED/point
de raccord non-foumi
BK BLACK/noIr VI VIOLET/violet
BL BLUE/bleu WH WHITE/blanc
BR BROWN/brun YL YELLOW/jaune
GR GREEN/vert GND GROUND/Terre
OR ORANGE/orange CAP CAPACITOR/capaciteur
RD RED/rouge
@L_', AUXILIARY LIMIT (IF EQUIPPED)
. limite auxiliaire - si equipp6e
LIMIT/limite
(/-F \ LOW SPEED FAN SWITCH (IF EQUIPPED)
\ --) interupteur a basse vitesse (si 6quippee)
¢-i ;', 'GN'TER/
transforrnateurd'allumage
/ m VALVE/
_NV) soupappe
POWER SUPPLY 120 VAC 60 HZ
(FUSED DISCONNECT ON HOT LEG)
h 1 aHmentation 120VAC 60Hz
(disjoincteur avec fusible sur le fll d'alimentation)
L1 N (COMMON)
INDOOR
BLOWER _BR_,
ventlateur ,/ .=BF_ \\
_;N)_)C ..... L( CAF I
BK WH
TRANSFORMER/
nsformateur
/.I \
BK i: F )
BL _ I "/I
I ()
I
I
I
I
_BK" 120V 24V --
(---_
_WH- COM 24V
=r_ / SWITCH ",,
123 _, i
" C NC
.oiT
WH
I
BK
VI RD
Z1
1-___ IGR_|
I l ....
_ GND
_1
"----1 _--- _T2
CONNECTOR/
connecteur molex
du brQleur
' L '
I' AL :If AL ',:
'\ ./ '\ _/
RD_
1158-1/1168-1
CONTROL
RD'
240005212 Rev A
Vl
TO T1
RIE LLO 40B F B U RN E:/OorT21euT YL _RTF 1
(IF AVAILABLE)/(sidisponiNe) _U WH
530SE L "1
_ RD
I r_ _ WH-II 3
E
'_I B. 7 _
-- _-- RD
_ MOTOR_._ 9 AL 1009
...." MOTOR _ 11 "
"_ .._'_WHI" 12
V] I_/H[ tVl WH
(_/T/ LIMIT RD_\
O T2 L/ BK(H__LV/)
L2 W
INTERRUPTED'
.....2::2
iyL ......... -
PRI',_TARRYL..... d f' _
BECKETT AFII SURNER/br01eur
BELT DRIVE MOTOR
(IF AVAILABLE)
I%°%
ventilateur _ \
principale _
ventilateur a courroie
(si disponible)
_WH_
dOTOR
loteur
1158-1
CONTROL
ECM MOTOR ventitateur a ECM
(IF AVAILABLE) (si disponible)
WH_
" YL C8 7 d s 4 3 2_
\ _ 2/ 1168-1
CONTROL
THERMOSTAT CONNECTIONS/ 1 1 58-1
raccorde du thermostat CONTROL
,::G )
N _J
THERMOSTAT
THERMOSTAT CONNECTIONS/ 1168-1
raccorde du thermostat
CONTROL
0 0 0 0 0 0
i 'Lw;,k R_j
THERMOSTAT
18
Page 19

OPERATION OF OIL BURNER
Once the furnace flue pipe, electrical and oil line
connections have been made, use the following
instructions to set the burner:
Shut off the electrical power to the furnace.
Install an oil pressure gauge to the pressure port on
the oil pump. (Refer to the oil pump specification sheet
included with the burner instructions).
Restore electrical power to the furnace.
Start the furnace and bleed all air from the fuel oil
lines.
Close the purge valve and fire the unit.
Allow the furnace to warm up to normal operating
temperatures. During this time, set the pump pressure
in accordance with the data provided in Appendix A,
Table A-2, and A-5.
When the furnace has reached "steady state" (after
approximately 10 minutes). Set combustion air damper
to get a TRACE of smoke.
Check the system temperature rise. The temperature
rise is the difference between the return air temperature
measured at a point near the return air inlet, and the
supply air temperature measured near the furnace
outlet. The system temperature rise is listed on the
furnace rating plate. If the temperature rise is too high,
the airflow must be increased. If the temperature rise is
too low, the fan should be slowed down.
the heat anticipator. Set the heat anticipator to the
amperage measured.
NOTE: THE FURNACE SHOULD BE RUN
THROUGH AT LEAST THREE FULL CYCLES
BEFORE LEAVING THE INSTALLATION, TO
ENSURE THAT ALL CONTROLS ARE
OPERATING PROPERLY AND AS EXPECTED.
NOTE: ALL JOINTS IN ANY POSITIVE
PRESSURE VENTING SYSTEM MUST BE
CHECKED FOR LEAKS BEFORE LEAVING
THE INSTALLATION SITE.
Turn off the burner. Observing the duct thermometer in
the supply air stream, note the temperature at which
the blower fan stops. The fan adjustments can be
made by moving the dipswitch settings on the timer
control board for fan off delay.
To check the operation of the limit switch, shut off
power to the furnace. Temporarily remove the neutral
wire from the direct drive blower motor. Restore the
electrical power to the furnace and set the thermostat
above room temperature. After three or four minutes of
burner operation, the limit control should turn the
burner off. When the limit function test is complete,
shut off electrical power to the furnace, replace the
neutral wire to the blower fan motor, and then restore
power. The blower fan will start up immediately. Once
the temperature has dropped and the limit control has
reset, the fan will operate until the fan off time is
achieved. The oil burner will then resume operation
and continue until the thermostat is satisfied. Restore
the thermostat setting to a comfortable temperature.
Set the heat anticipator adjustment in the thermostat (if
so equipped), by removing the "R" or "W" wire to the
thermostat, then reading the amperage draw between
the two wires. Failure to remove one of the wires from
the thermostat while performing this test could burn out
3_9
Page 20

APPENDIX C OIL PRIMARY CONTROL DETAILED SEQUENCE OF OPERATION
Power is applied to unit. The oil primary control completes a self-diagnostic procedure. If no light or flame is present,
and unit passes its self-diagnostic procedure, the control enters into the idle mode.
Thermostat calls for heat:
A) Safety check is made for flame (4 second delay).
1) If flame is not present, the oil primary control will apply power to the burner motor and igniter.
2) If flame is present, the control remains in the idle state.
B) Unit enters a pre-purge period of 15 seconds.
C) After 10 seconds, control checks for flame presence.
1) If flame is not present, the oil primary control enters the trial for ignition state.
2) When flame is present, the control enters lock out mode.
D) The Oil Primary Control monitors the burner flame.
1) When flame is present, the control enters ignition carryover state. (Continues to spark for 10 sec.).
a) Provides continuous spark after flame is sensed to assure that burner remains lit.
b) Turns on LED diagnostic light.
c) Starts carryover timer.
(i) Flame and call for heat are monitored.
• If flame is lost and lockout timer has not expired, the control will return to trial for ignition state.
• If flame is lost and lockout timer has expired, the control will enter the recycle state.
• Recycle timer starts.
• Burner motor and igniter and solenoid valve are turned off.
• LED diagnostic light flashes slowly.
E) Carryover timer expires.
1) Enters run state.
a) Igniter turns off.
Combustion continues until thermostat is satisfied, or the oil primary control detects a loss of flame and enters into
Recycle Mode.
F) Thermostat is satisfied - call for heat is terminated:
a) Oil primary control shuts off burner motor and solenoid valve.
(i) If the control utilizes a blower motor off delay, after 30 seconds, flame presence is checked.
• If flame is not present, the control LED diagnostic light is off and returns to idle state.
• If flame is presence is detected, the control enters lock out mode.
20
Page 21

FIGURE 4: UNITED TECHNOLOGIES 1158-120 FAN TIMER BOARD
)4HD-091A-12-FB and C
FIGURE 5: UNITED TECHNOLOGIES 1168-1 ECM TAP BOARD (O4HD-091A-V-FA)
21
Page 22

IDLE STATE
THERMOSTAT CALLS FOR HEAT
4,
SAFETYCHECKFORFLAME(5SEC.) I l
F OIL PRIMARY
REMAINS IN IDLE STATE
1
CONTROL
SEQUENCE of
OPERATION
NO FLAME
BURNER MOTOR & IGNITOR START I
10 SEC.
SAFETY CHECK FOR FLAME (5 SEC.) I
NO FLAME
SOLENOID VALVE OPENS
TRIAL FOR IGNITION
I
4,
BURNER FLAME MONITORED
NO FLAME
FLAME
CARRYOVER STATE
• Provides continuous spark
• LED diagnostic light ON
• Start Carryover Timer
FLAME
CARRYOVER TIMER EXPIRES
FLAME LOST
FLAME
FLAME
,L
I OCKOUT STATE
l
OIL PRIMARY CONTROL:
Shuts off burner motor
Shuts off igniter
Shuts off Solenoid Valve
Fast Flashes LED Diagnostic
Light
FLAME
RUN STATE
• Igniter turns off.
THERMOSTAT SATISFIED
FLAME LOST I
FLAME LOST
4,
OIL PRIMARY CONTROL
SHUTS OFF:
• Burner Motor
• Solenoid Valve
30 SEC.
SAFETY CHECK FOR FLAME (5 SEC.) I
NO FLAME i
RETURNS TO IDLE STATE
RECYCLE TIMER STARTS
OIL PRIMARY CONTROL:
Shuts off Solenoid Valve
Shuts off Igniter
Shuts off Burner Motor
Slow Flashes LED
diagnostic light
I
I
FLAME
22
RECYCLE TIMER EXPIRES
(60 SECONDS
Page 23

Table C-1" 1158-120 ELECTRONIC FAN TIMER BOARD (EFT) DETAILED SEQUENCE OF
OPERATION
Mode Action
EFT closes the oil primary control T - T connections).
Thermostat calls for heat. ("W"
terminal is energized).
Thermostat ends call for heat.
HEAT
COOL energized),
FAN (G terminal is energized),
LIMIT EFT begins heat "fan off" delay sequence.
FAN connected. If fan operation is required by a call for heat, cool, or fan, the EFT switches off the
CW" terminal is de-energized).
Burner fails to light.
Established flame fails.
Thermostat begins call for cool, Cooling contactor is energized immediately,
(G and Y terminals are Circulator fan is energized at cool speed,
Thermostat ends call for cool, (G Cooling contactor is de-energized immediately,
and Y terminals are de-
energized),
Thermostat begins call for fan.
Thermostat ends call for fan. (G
terminal is de-energized). Circulator fan is de-energized immediately,
Limit switch string opens.
Limit switch string closes (with Circulating fan turns off after the selected heat "fan off" timing.
existing call for heat). EFT re-closes the oil primary control T - T connections.
Limit switch string closes
(without existing call for heat), command.
Continuous circulating fan is Circulating fan is energized when there is no call for heat, cool, or fan.
Ignition system and the oil primary control start the furnace. Oil flows as long as the oil
primary control senses flame.
Burner motor is energized and heat "fan on" delay timing begins. When timing is
complete, the circulator fan is energized at heat speed.
The oil primary control is de-energized, terminating the burner cycle.
Heat "fan off" delay timing begins. Length of delay depends on EFT dipswitch settings.
When timing is complete, the circulator fan is de-energized.
EFT returns to standby mode, (Oil primary control and circulator fan are off, unless
continuous fan operation is selected at the thermostat).
Oil primary control locks out within lockout timing, (30 seconds).
Burner motor is de-energized. (Even though thermostat is still calling for heat).
If circulator fan has started, it continues through the selected heat "fan off' delay
period.
Burner motor is de-energized and oil primary control goes into recycle mode.
If the selected heat "fan off" delay timing is longer than the recycle delay timing, the
circulator fan continues to run through the next trial for ignition.
Circulator fan turns off immediately,
Circulator fan is energized immediately at cooling speed,
Oil primary control shuts off burner.
Circulator fan is energized immediately at heat speed.
EFT opens the oil primary control T - T connections. Circulating fan runs as long as
limit string stays open.
If there is a call for cooling or fan, the circulating fan switches from heating to cooling
speed.
Oil primary control is energized, initiating burner light off.
Circulator fan turns off when heat "fan off" delay time is complete.
Normal operation resumes; EFT control is in standby mode awaiting next thermostat
continuous fan speed tap before energizing the other fan speed.
System Response
EAC connected, the circulator fan is energized. EAC connections are not energized when the optional
Electronic Air Cleaner is
HUM Humidity control is connected. Humidifier connections are energized when the oil burner motor is energized.
1168-1 ELECTRONIC FAN TIMER BOARD (EFT) DETAILED SEQUENCE OF OPERATION
Thermostat Input LEDs (LED1-5, LED8)
Six green LEDs are placed behind their respective thermostat connections (Y1, Y/Y2, G, DH, O, and W) and operate whenever a
call is present.
Thermostat calls for heat "W". The 24VAC input signal is passed to pin 2 of P1 and wilt drive the K1 relay that provides
dedicated contacts to the T-T input of the Oil Primary Control. Thermostat calls for cool "YI". The 24VAC input signal is passed
to pin 6 of PI. Thermostat calls for fan "G". The 24VAC input signal is passed to pin 15 of PI. Thermostat calls for
dehumidification "DH". The 24VAC input signal is passed to pin 10 of PI. Thermostat calls for reversing valve "O". The
24VAC input signal is passed to pin 9 of PI.
Electronic air cleaner (EAC) connections are energized when the heat or cool speed of
continuous fan terminal is energized.
23
Page 24

OIL PRIMARY CONTROL LED DIAGNOSTIC
LIGHT
The LED diagnostic light has several functions. It
indicates the state or mode in which the oil burner is
operating. It will also indicate fault conditions, and help
determine cad cell resistance while the burner is
operating.
NORMAL CONDITIONS:
The LED diagnostic light will turn on when the burner
enters the carryover state; the point at which ignition
spark is on, and will remain on through the run state,
where the ignition spark is terminated but the burner
continues to fire.
The LED diagnostic light will turn off at the end of the
burner cycle as the oil primary control enters the idle
state, and will remain off until the next heating cycle.
FAULT CONDITIONS:
If the LED diagnostic light is flashing quickly; 1 Hz (½
second on / ½ second off), the oil primary control is in
the lockout state or in restricted mode. To exit the
lockout state, press the reset button.
If the LED diagnostic light is flashing slowly; 1¼Hz (2
seconds on / 2 seconds off), the oil primary control is
in the recycle state. This indicates that flame sensing
was lost after the lockout timer expired during the
ignition carryover state. The oil primary control will
return to the idle state within 60 seconds.
CAD CELL CONDITION:
If the LED diagnostic light is off, the cad cell is not
sensing flame.
If the LED diagnostic light is on, the cad cell is sensing
flame, or viewing ambient light.
The resistance of the cad cell may be checked while
the oil primary control is in the run state by pressing
the reset button. The LED diagnostic light will flash the
following code:
Table C-2: Cad Cell Resistance
TROUBLESHOOTING
IMPORTANT: Due to the potential hazard of line
voltage, only a trained, experienced service technician
should perform the troubleshooting procedure.
PRELIMINARY STEPS:
Check the diagnostic light for indications of burner
condition. Refer to the oil primary control LED
DIAGNOSTICLIGHTsection for details.
IA° =,o.I
WHEN SIMULATING A CALL FOR HEAT AT
THE OIL PRIMARY CONTROL, DISCONNECT
AT LEAST ONE THERMOSTAT LEAD WIRE
FROM THE T1 - T2 TERMINALS TO PREVENT
DAMAGE TO THE THERMOSTAT.
NEGLECTING THIS PROCEDURE MAY BURN
OUT THE HEAT ANTICIPATOR OF A
STANDARD 24 VAC THERMOSTAT, OR
CAUSE HARM TO COMPONENTS WITHIN A
MICRO-ELECTRONIC THERMOSTAT.
Before checking the oil primary control, perform these
preliminary checks, (repair or replace controls as
necessary):
• Check the power supply; fuse box or breaker,
any service switches, all wiring connections, and
burner motor reset button (if equipped).
• Check the limit switches to ensure that the
switch contacts are closed.
• Check the electrode gap and position.
• Check the contacts between the oil primary
control and the electrodes.
Check oil supply (tank gauge).
Check the oil nozzle, oil filter, and oil valves.
• Check the piping or tubing to the oil tank.
Flashes Resistance in Ohms
1 Less than 400
2 Between 400 - 800
3 Between 800- 1600
4 Between 1600- 5000
• Check the oil pump pressure.
CHECK OIL PRIMARY CONTROL AND
IGNITER
If the trouble does not appear to be in the burner or
ignition hardware, check the oil primary control and the
igniter by using the following equipment:
Screwdriver.
Voltmeter (0 - 150 VAC)
Insulated jumper wires with both ends stripped.
24
Page 25

PRELIMINARY CHECKS:
IAWARNINGI
Make sure that limit switches are closed and those
contacts are clean.
ELECTRICAL SHOCK HAZARD.
TROUBLESHOOTING IS DONE WITH THE
Check for line voltage power on the oil primary
control black and white lead wires.
SYSTEM POWERED. BE CAREFUL TO
OBSERVE ALL NECESSARY PRECAUTIONS
TO PREVENT ELECTRICAL SHOCK OR
Refer to Table C-4 or C-5 for further troubleshooting
information.
EQUIPMENT DAMAGE.
Table C-3: Oil Primary Control TROUBLESHOOTING
Condition: Burner motor does not start when there is a call for heat.
Procedure
1. Check that limit switches are
closed and contacts are clean.
2. Check for line voltage power at
the oil primary control. Voltage
should be 120 Vac between the
black and white lead wires on the
oil primary control.
3. Check indicator light with
burner off, no call for heat (no
flame).
4. Shield cad cell from external
light.
5 Jumper thermostat (T-T)
terminals on oil primary control
IMPORTANT
First remove one thermostat lead
wire.
N/A N/A
N/A N/A
Indicator light is on.
Indicator light is off.
Indicator light turns off.
Indicator light stays on.
Burner starts.
Burner does not start.
Status Corrective Action
for continuity.
Cad celt is defective, sees external light, or connections
have shorted. Go to step 4.
Go to step 5.
Eliminate external light source or permanently shield cad
cell.
Replace cad celt with new cad cell and recheck.
If indicator light does not turn off, remove yellow lead
wires from oil primary control and recheck.
If indicator light is still on, replace the oil primary control.
If the indicator light turns off, replace cad cell bracket
assembly.
Trouble is in thermostat circuit. Check thermostat-wiring
connections.
If connections are clean and tight, check thermostat wires
Disconnect line voltage power and open line switch.
Check all wiring connections.
Tighten any loose connections and recheck.
If burner still doesn't start, replace the oil primary control
If burner still doesn't start, check the oil burner motor. It
may be seized or burned out.
Condition: Burner starts then locks out on safety with indicator light flashing at 1 Hz rate (1/2second on, 1/2second off)
Procedure Status Corrective Action
1. Check that the limit switches
are closed and contacts are clean.
2. Check for line voltage power at
the oil primary control. Voltage ......
should be 120 Vac (nominal)
3. Check indicator light with
burner off, no call for heat (no
flame).
Indicator light is on.
Indicator light is off.
Cad celt or controller is defective, sees external light, or
connections are shorted. Go to step 4.
Go to step 5.
25
Page 26

Table C-3: Oil Primary Control Troubleshooting continued from previous page
Procedure Status
Indicator light turns off.
4. Shield cad cell from external
light.
5. Jumper thermostat (T -T)
terminals on oil primary control
IMPORTANT
First remove one thermostat
lead wire.
Condition: Burner starts then locks out on safety with indicator light flashing at 1 Hz rate (1/2second on, 1/2second
Indicator light stays on.
Burner starts.
Burner does not start.
Eliminate external light source or permanently shield cad cell.
Replace cad celt with new cad cell and recheck.
If indicator light does not turn off, remove cad cell lead wires
from oil primary control and recheck.
If indicator light turns off, replace cad cell bracket assembly.
If indicator light does not turn off, replace controller.
Trouble in thermostat or limit circuit. Check thermostat or limit
wiring connections.
Disconnect the line voltage power and open line switch.
Check all wiring connections.
Tighten any loose connections and recheck.
If burner does not start, replace oil primary control
Corrective Action
off)
6. Reset oil primary control by
pushing in and releasing red
reset button.
7. Listen for spark after burner
turns on (after 2 second delay).
8. Check indicator light after
flame isestablished, but before
oil primary control locks out.
9. Check cad cell sighting for
view of flame.
Disconnect line voltage power
and open line switch.
Unplug cad celt and clean cad
celt face with soft clothe. Check
sighting for clear view of flame.
Replace cad celt in socket.
Reconnect line voltage power
and close line switch.
Start burner.
Indicator light stops flashing.
Indicator light continues to
flash at 1 Hz rate.
Ignition is off
Ignition is on.
Ignition is on but no oil is
being sprayed into the
combustion chamber.
Indicator light is on until the
control locks out and starts
flashing during lockout.
Indicator light stays off.
Burner locks out.
Burner keeps running.
Go to Step 7.
Verify that the control is not in restricted mode. (See notes at
end of this table.). If not in restricted mode, replace oil
primary control
Spark igniter could be defective. Check for line voltage at
igniter terminals. If line voltage is present, replace oil primary
control.
Go to Step 8.
Wait for "Valve ON" delay to complete. Check oil supply, and
oil line valve. Check for filter blockage or seized oil pump.
Replace oil primary control
Go to step 9.
Go to step 10.
System is OK.
26
Page 27

Table C-3: Oil Primary Control Troubleshooting continued.
Procedure
10. Check cad cell.
Disconnect line voltage power
and open line switch.
Remove existing cad cell and
replace with new cad celt.
Disconnect all wires from
thermostat terminals to ensure
that there is no call for heat.
Reconnect line voltage power
and close line switch.
Expose new cad celt to bright
light such as a flashlight.
11. Check cad cell bracket
assembly.
Disconnect line voltage power
and open line switch.
Remove cad cell wires from
quick connect connectors on
and leave control lead wires
open.
Apply power to device.
Place jumper across cad cell
terminals after burner motor
turns on.
NOTE: Restricted Mode - (Limited Reset): In order to limit the accumulation of unburned oil in the combustion chamber, the
control can be reset only 3 times, after which, the control locks out. The reset count returns to zero each time a call for heat is
successfully completed.
To reset from RESTRICTEDMODE:press and hold the reset button for 30 seconds. When the LED flashes twice, the device has
reset.
NOTE: Disable function: Pressing and holding the reset button will disable all functions until the button is released. The burner
will restart at the beginning of the normal heat cycle on SAFETYCHECK.
Status Corrective Action
Indicator light is on. Remount control onto burner housing. Go to step 6.
Indicator light is off.
Indicator light is on.
Indicator light is off.
Go to step 11.
Replace cad cell bracket assembly.
Replace oil primary control.
Table C4: System and General Troubleshooting
Problem Possible Cause Remedy
Thermostat not calling for heat.
No power to furnace.
Furnace will not start. Remove thermostat wires from oil primary control terminals T-T.
Thermostat faulty. Place a jumper across T-T. If furnace starts, replace thermostat,
Oil primary control faulty, wires from oil primary control terminals T1 - T2. Check for 24V
Check thermostat and adjust. Also, check thermostat for
accuracy; if it is a mercury switch type, it might be off level.
Check furnace switch, main electrical panel furnace fuse or
circuit breaker. Also took for any other hand operated switch,
such as an old poorly located furnace switch, which was not
removed during furnace replacement.
thermostat sub-base (if equipped), or both.
Check reset button on oil primary control. Remove thermostat
across T -T. If no voltage is present, check for 115V to oil
primary control. If 115V is present, go to Table C-3.
2"7
Page 28

Table C-4: System and General Troubleshooting continued
Problem
Furnace will not start.
Furnace will not start
without first pushing oil
primary control reset
button.
(Happens on frequent
basis)
Furnace starts, but cuts
out requiring manually
resetting the oil protector
reset button.
Furnace starts, but cuts
out requiring manually
resetting the oil protector
reset button.
Oil burner sputtering at
nozzle Replace fuel oil storage tank filter and / or fuel oil in-line filter.
Possible Cause
Photo Cell wiring shorted or
room light leaking into photo
cell compartment
Open safety switch.
No fuel oil.
Clogged nozzle.
Clogged oil filter.
Low oil pump pressure.
Air getting into fuel oil lines, or
fuel oil line dirty, clogged, or in
some manner defective.
Defective burner motor.
Photo Cell (Cad Cell)
defective.
No fuel oil.
Clogged nozzle.
Clogged oil filter.
Low oil pump pressure.
Air getting into fuel oil lines, or
fuel oil line dirty, clogged, or in
some manner defective.
Defective burner motor.
Water or contaminants in oil.
Frozen oil line.
Electrodes out of adjustment or
defective.
Poor transformer high voltage
connections or defective
transformer.
Fuel oil filter clogged.
Defective oil pump.
Fuel oil line partially clogged or
contains air.
Remedy
Check photo celt (cad celt) wiring for short circuits. Also, check
for room light leaking into cad cell compartment. Repair light
leak if necessary. See Table C-3.
Check for open limit or auxiliary limit. Also, check internal wiring
connections; loose connectors, etc.
Check fuel oil supply. Check that all hand operated fuel oil
valves are in the open position. Fill oil storage tank if necessary.
Replace nozzle with high quality replacement. Use rating plate
or Tables in Appendix A as a guide.
Replace oil tank filter or in-line filter if used.
Connect pressure gauge to oil pump. Adjust pump pressure, or
replace oil pump if necessary. Ensure that erratic pressure
readings are not caused by defective fuel oil line.
Check fuel oil lines. Replace any compression fittings found with
high quality flared fittings. Check for any signs of oil leaks. Any
oil leak is a potential source of air or contaminants.
Check burner motor. If burner motor is cutting out on over-load,
determine why. Replace if necessary.
If cad cell is dirty, clean it. (Determine why cad celt is getting
dirty). If cad celt is poorly aimed, realign it. NOTE: The photocell
should have a resistance of 100 KD in absence of light; a
maximum of 1500 D in the presence of light. Ensure that room
light is not leaking into the cad cell compartment. (See
diagnostic light section).
Check fuel oil supply. Check that all hand operated fuel oil
valves are in the open position. Fill oil storage tank if necessary.
Replace nozzle with high quality replacement. Use rating plate
or Tables in Appendix A as a guide.
Replace oil tank filter or in-line filter if used.
Connect pressure gauge to oil pump. Adjust pump pressure, or
replace oil pump if necessary. Ensure that erratic pressure
readings are not caused by defective fuel oil line.
Check fuel oil lines. Replace any compression fittings found with
high quality flared fittings. Check for any signs of oil leaks. Any
oil leak is a potential source of air or contaminants.
Check burner motor. If burner motor is cutting out on over-load,
determine why. Replace if necessary.
Drain fuel oil storage tank; replace fuel oil. (Consult with fuel oil
supplier).
Gently warm oil line. Insulate oil line. (Outdoor piping size may
require increased diameter).
Check electrode settings. Check electrodes for dirt build-up or
cracks in porcelain.
Check contacts between the igniter and electrodes. If OK,
replace the igniter
Check burner motor and / or fuel oil pump coupling. Check oil
pump pressure. Replace fuel oil pump if necessary.
Bleed air from oil line. If problem persists, replace oil line.
28
Page 29

Table C-4: System and General Troubleshooting continued
Problem Possible Cause
System temperature rise too
high.
Poor "fan off" delay timing
selection, (fan stops too soon).
Excessive fuel oil
consumption. Fuel oil leak.
Stack temperature too high.
Thermostat improperly amperage draw. Increase heat anticipator setting if necessary.
adjusted or in poor location. If the thermostat is being influenced by drafts, sunlight, duct
Insufficient combustion air Adjust the oil burner combustion air band and draft regulator to
adjustment at oil burner, or gain the highest practical CO2 or lowest practical 02 content in
Too much smoke, improper draft pressure, the flue gases. See Burner Set Up.
Heat exchanger partially Check for soot build-up in heat exchanger flue passages,
clogged, especially in the outer radiator.
Poor alignment between oil
Soot building up on blast burner blast tube and fire pot. inside surface of the fire pot.
tube (end coning). Flame impingement caused by Check nozzle size and angle. (See Appendix A). Check distance
Incorrect nozzle angle, from head to inside surface of the fire pot.
Defective fire-pot Check fire-pot. Repair or replace.
Airflow blocked or dirty air
filter.
Thermostat adjustments or amperage draw. Increase heat anticipator setting if necessary.
location. If the thermostat is being influenced by drafts, sunlight, duct
Insufficient airflow, unused rooms. Check system temperature rise. If temperature
Furnace wilt not warm rise is too high, speed up blower fan.
home to desired Test high limit function of all limit switches. Use a duct
temperature. Defective high limit control, obstructions to airflow around limit switch bi-metal elements.
Under-sized nozzle.
Blower fan motor stopping Check blower fan motor amperage draw. Check motor
intermittently on overload, ventilation ports, clean if necessary. Replace motor if necessary.
Burner motor stopping Check burner motor. Replace if necessary.
intermittently on overload.
Home does not heat
evenly Improper distribution of heat. This is not likely to be a furnace problem. Balance duct system.
System temperature rise ideally should not exceed 85°F. Check
for clogged air filters. Check blower fan for excess dirt build-up
or debris. Speed up blower fan if necessary.
Check "fan off" delay timing setting. Use a duct thermometer in
the supply air plenum take-off or first few inches of the supply air
trunk duct. Ideally, the fan wilt shut off at a temperature of 90° -
100°F. Manipulate the dip switch settings to come as close as
possible to this "fan off" temperature.
Check fuel oil line for leaks. Repair or replace if necessary.
Check stack temperature. Stack temperatures will normally
range from 350 ° to 450°F. Check draft regulator. Draft should be
set to -0.02 in. w.c.
Check thermostat heat anticipator setting against measured
work, etc., relocate to more suitable location.
Check alignment. Blast tube should be centered with fire pot
burner opening. Oil burner head should be ¼ inch back from the
Clean or replace air filter.
Check thermostat heat anticipator setting against measured
work, etc., relocate to more suitable location.
Check all dampers. Open closed dampers including registers in
thermometer to assess accuracy of limit control. Check for
Replace control if necessary.
Check nozzle. If problem is not caused by air flow problems, use
larger nozzle, if permitted by rating plate.
Remedy
29
Page 30

Table C-4: System and General Troubleshooting continued
Problem
Supply air temperature
too hot.
Supply air temperature
too cool.
Supply air temperature
too cool during first
moments of furnace
cycle.
Possible Cause
Airflow blocked or dirty air
filter.
Insufficient airflow.
Excess airflow.
Excessive duct losses.
Fan control "fan on" setting too
low.
Excessive duct losses.
FINAL CHECK OUT
ENSURE THAT ALL SAFETY DEVICES AND
ELECTRICAL COMPONENTS HAVE BEEN
SET FOR NORMAL OPERATION. ENSURE
THAT ALL ELECTRICAL CONNECTIONS
ARE TIGHT AND THAT THE WIRING IS
SECURE.
Remedy
Clean or replace air filter.
Check all dampers. Open closed dampers including registers in
unused rooms. Check system temperature rise. If temperature
rise is too high, speed up blower fan.
Check system temperature rise. Slow down blower fan if
necessary.
Check supply air ductwork. Seal leaky joints and seams.
Insulate ductwork if necessary.
Increase "fan on" dipswitch settings on EFT if control has this
option.). Register air deflectors may help.
Check supply air ductwork. Seal leaky joints and seams.
Insulate ductwork if necessary.
_IL IMPORTANT:
Please ensure that the homeowner is informed and
understands:
1. Where the circuit breaker or fuse is located in
the main electrical panel.
2. Where the furnace switch is located, and the
switch "on" and "off" positions if not obvious.
3. Where the oil shut-off valve from the oil storage
tank is located.
4. How to operate the thermostat, and other
related accessories.
5. How to operate the manual reset button on the
primary control, and especially when not to push the
reset button.
6. How and where to visually inspect the venting
system for leaks or other problems.
7. How to inspect, clean and replace the air filter,
and other homeowner maintenance procedures.
8. Who to call for emergency service and routine
annual service.
9. The terms and conditions of the manufacturer's
warranty and the contractor's warranty.
30
Page 31

HOMEOWNER'S REFERENCE TABLE
Model No.
Serial No.
Date Installed
Contractor
Contact
Address
Postal Code
Telephone No.
After Hours No.
FUEL SUPPLIER
Fuel Oil
Supplier
Contact
Telephone No.
After Hours No.
IF DIFFERENT FROM INSTALLATION CONTRACTOR:
Service Tech.
Telephone No.
After Hours No.
31
Page 32

1
2
3
4
5
6
7
LeftSidePanelAssembly
RightSidePanelAssembly
RearPanel
BlowerDivisionAssembly
BasePanel
InnerFrontPanel
BlowerAccessPanel
29187L
29186L
29205L
29189
26216
30066
27721L
8
9
10
11
12
13
14
15
16
17
17
18
18
19
2O
21
24
25
26
27
28
29
30
31
31
32
33
34
TopPanel
HeatExchangerAssembly
CombustionChamberRetainerBracket
ReplacementCombustionChamber
OilBurnerMountingPlate
FlueConnector
PouchGasket
FlueCollarGasket
InsulationRetainer
RadiatorClean-outCover(2perunit)
RadiatorClean-outCoverGasket(2perunit)
Clean-outGasketRetainer
Clean-outTubeGasket
FilterFrame16"X25"
FilterFrameEndSupport
Filter16"X25"X1"Permanent
ControlBox
UpperDoorPanel
LogoBezel
LogoLabel
LimitDisc60T11BOF155°F
FanTimerControl1158-120UTEC
FanTimerControl1168-1ECMUTEC
WireHarness,ControlsFanTimer
WireHarness,Blower
WireHarness,FanTimerBoard,Transformer
WireHarness,ECMControl
WireHarness,ECMSupply
Transformer
DraftRegulator
OilBurnerAssembly,BeckettAF76BNHS
BurnerMotor1/7HP3450RPMPSC
BeckettClean-cutOilPumpA2EA6520
SolidStateIgnitor10SAY-01
OilPrimaryCombustionControl
FlameRetentionHead
Nozzle,0.65/80°A
LowFireKit
LowFiringRateBaffle
Nozzle,0.50/80°A
21437L
28675
27068
27000WP
29869
29005
2080175
21994
20602
29162
240006333
29161
29163
18020
5592B2
2180023
29362
30164L
28479
28563
30071
29388
240007048
29364
29365
29751
240006438
240005742
27738
27494(5")
30067
29689
29688
29522
29664
11961(F3)
210086
29880
25521101
29389
32
Page 33

35
BlowerAssemblyDirectDrive
BlowerAssemblyDirectDriveECM
BlowerHousingandWheel,100-10TDD(O4HD-091A-12-FB
andO4HD-091A-V-FA)
30146
109007271
30626
102000131
109007272
17811
26251
27743
27760
27733
27731
36
BlowerMotor,1/2hp,4-Speed
BlowerMotor,1/2hp,ECMProgrammed
MotorMountingBand- TR6884B
MotorMountArms- 10-10DDBlower(3perunit)
MotorRunCapacitor,10mfd@370Vac
CapacitorStrap
BlowerSlideRail2 Per
RightSidePanel,AirBaffleO4HD-091A-12-FB
O4HD-091A-V-FA
All parts are the same as listed on the previous pages for Models O4HD-091A-12-FB and O4HD-091A-V-FA
except where noted below.
12
13
14
15
25
34
Oil Burner Mounting Plate Assembly
Oil Burner Mounting Plate
Sight Glass Cover Plate
Sight Glass Gasket (2 per unit)
Sight Glass
Flue Connector Assembly 6" to 4" 90° Elbow
Pouch Gasket (Second gasket required for Direct Vent)
Flue Collar Gasket (Second gasket required for Direct Vent)
Upper Door Panel
Beckett Oil Burner AFII 85
Burner Motor 1/7 HP 3450 RPM PSC
Beckett Clean-cut Oil Pump A2EA6520
Solid State Ignitor 10SAY-01
Oil Primary Combustion Control
Air Tube Combination FBX80HGXS
Flame Retention Head (FB3)
Nozzle, 0.60/60°A (O4HD-091A-14-FA-DV only)
29872
29867
29850
29870
29876
28952
2080175
21994
27722L
30069
28907
29688
28558
29649
28561
28533
28017
33
Page 34

Model O4HD-091A-12-FB, O4HD-091A-V-FA, and O4HD-091A-14-FA-DV
®
34
Page 35

NOTES:
NORDYNE, 8000 Phoenix Parkway, O'Fallon, Missouri, 63368
3 5 151B-0810 (Replaces 151B-0909)