NS6QD SERIES - WITH QUICK CONNECT COUPLINGS13 SEER
USER’S MANUAL / INSTALLATION INSTRUCTIONS
OUTDOOR SPLIT SYSTEM AIR CONDITIONER FOR MANUFACTURED HOUSING
Please read this information thoroughly and become familiar with the capabilities and
use of your appliance before attempting to operate or maintain this unit. Keep this
literature where you have easy access to it in the future. If a problem occurs, check the
instructions and follow recommendations given. If these suggestions don’t eliminate
your problem, call your servicing contractor.
The Installation Instructions are primarily intended to assist qualifi ed individuals
experienced in the proper installation of this appliance. Some local codes require licensed
installation/service personnel for this type of equipment. Please read all instructions
carefully before starting the installation.
DO NOT DESTROY. PLEASE READ CAREFULLY AND
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
IMPORTANT
Page 2
USER INFORMATION
Important Safety Information ....................................3
Outdoor Temperatures Above 55° F .......................8
WARRANTY INFORMATION
A warranty certifi cate with full details is included with the
air conditioner. Carefully review these responsibilities with
your dealer or service company. The manufacturer will not
be responsible for any costs found necessary to correct
problems due to improper setup, improper installation,
adjustments, improper operating procedure on the part
of the user, etc. Some specifi c examples of service calls
which are not included in the limited warranty are:
• Correcting wiring problems in the electrical circuit
supplying the air conditioner.
• Resetting circuit breakers or other switches.
• Adjusting or calibrating of thermostat.
Air Conditioner Maintenance .....................................9
Figure 8. Charging Chart for 2 Ton Units .............. 16
Figure 9. Charging Chart for 2.5 Ton Units ........... 16
Figure 10. Charging Chart for 3 Ton Units ............ 17
Figure 11. Charging Chart for 3.5 Ton Units ......... 17
Figure 12. Charging Chart for 4 Ton Units ............ 18
Figure 13. Charging Chart for 5 Ton Units ............ 18
INSTALLATION / PERFORMANCE CHECKLIST ..... 20
2
Page 3
USER INFORMATION
IMPORTANT SAFETY INFORMATION
Safety markings are used frequently throughout this
manual to designate a degree or level of seriousness and
should not be ignored. WARNING indicates a potentially
hazardous situation that if not avoided, could result in
personal injury or death. CAUTION indicates a potentially
hazardous situation that if not avoided, may result in minor
or moderate injury or property damage.
OPERATING INSTRUCTIONS
NOTE: Thermostat styles vary. Some models may not
include the AUTO mode and others will have the AUTO
in place of the HEAT and COOL. Others may include all
three. Please refer to the thermostat manufacturer’s User
manual for detailed programming instructions.
Cooling Operation
1. Set the thermostat’s system mode to COOL or AUTO
and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired
temperature level. The outdoor fan, compressor, and
blower motor will all cycle on and off to maintain the
indoor temperature at the desired cooling level.
NOTE: If the temperature level is re-adjusted, or the
system mode is reset, the fan and compressor in the
outdoor unit may not start immediately. A protective
timer circuit holds the compressor and the outdoor fan
off for approximately 5 minutes following a previous
operation or the interruption of the main electrical
power (if applicable).
Heating Operation
1. Set the thermostat’s system mode to HEAT or AUTO
and change the fan mode to AUTO. See Figure 1.
2. Set the temperature selector to the desired
temperature level. The optional heating equipment
(furnace or electric heat) will cycle on & off to maintain
the indoor temperature at the desired temperature
level.
Operating the AC for Automatic Cooling & Heating
1. Set the thermostat system mode to AUTO and the
thermostat fan mode to AUTO. See Figure 1.
2. Set the thermostat temperature selector to the desired
temperature level. The thermostat will maintain the
desired temperature level by switching between either
the outdoor cooling unit or the indoor heating unit
(furnace or electric heat) automatically.
Operating the Indoor Blower Continuously
The continuous indoor blower operation is typically used to
circulate the indoor air to equalize a temperature unbalance
due to a sun load, cooking, or fi replace operation.
thermostat fan mode to ON (Figure 1). The indoor blower
starts immediately, and will run continually until the fan
mode is reset to AUTO.
Set the
The continuous indoor blower operation can be obtained
with the thermostat system mode set in any position,
including OFF.
Turning the Air Conditioner OFF
Change the thermostat’s system mode to OFF and the fan
mode to AUTO (See Figure 1). NOTE: The system will not
operate, regardless of the temperature selector setting.
Fan
Mode
Figure 1. Digital Thermostat
System
Mode
Temperature
Selector
AIR CONDITIONER MAINTENANCE
Proper maintenance is most important to achieve the best
performance from the appliance and should be performed
frequently at the beginning of each air conditioning season.
WARNING:
Your Air Conditioner contains liquid and gaseous
refrigerant under pressure. Installation and
servicing should only be attempted by qualifi ed,
trained personnel thoroughly familiar with the
equipment and safe responsible refrigerant
handling procedures. Failure to comply with
this warning could result in equipment damage,
personal injury, or death.
• Keep the outdoor unit clean. Hose off periodically and
keep unit fi ns clear of leaves and grass clippings.
• Keep the outdoor unit clear of obstructions.
DO NOT obstruct airfl ow with tall plants or shrubs.
DO NOT store gasoline or other fl ammable materials
on or near the outdoor unit.
• Never operate the appliance without a fi lter installed in
the return air duct. Inspect fi lters frequently and replace
when necessary with fi lter of same dimensional size.
TROUBLESHOOTING
• Check the thermostat setting. Make sure the system
mode and temperature settings are correct.
• Check the electrical panel for tripped circuit breakers.
• Check the fi lters for dust accumulation.
• Check the outdoor unit and make sure it is clean and
not covered with grass or leaves.
3
Page 4
INSTALLER INFORMATION
IMPORTANT SAFETY INFORMATION
INSTALLER: Please read all instructions before servicing
this equipment. Pay attention to all safety warnings and
any other special notes highlighted in the manual. Safety
markings are used frequently throughout this manual to
designate a degree or level of seriousness and should not
be ignored. WARNING indicates a potentially hazardous
situation that if not avoided, could result in personal injury
or death. CAUTION indicates a potentially hazardous
situation that if not avoided, may result in minor or moderate
injury or property damage.
WARNING:
Shut off all electrical power to the unit before
performing any maintenance or service on the
system. Failure to comply may result in personal
injury or death.
WARNING:
Unless noted otherwise in these instructions,
only factory authorized parts or accessory
kits may be used with this product. Improper
installation, service, adjustment, or maintenance
may cause explosion, fi re, electrical shock or
other hazardous conditions which may result in
personal injury or property damage
WARNING:
NS6QD Split System Air conditioners leave
the factory with an R-410A refrigerant holding
charge. Follow all charging instructions for
maximum unit performance and effi ciency. Some
local codes require licensed installation/service
personnel to service this type of equipment.
Refrigerant charging must be done by qualifi ed
personnel familiar with safe and environmentally
responsible refrigerant handling procedures.
Under no circumstances should the owner
attempt to install and/or service this equipment.
Failure to comply with this warning could result
in property damage, personal injury, or death.
CAUTION:
This unit uses refrigerant R-410A. DO NOT use
any other refrigerant in this unit. Use of another
refrigerant will damage the unit.
WARNING:
The information listed below must be followed
during the installation, service, and operation
of this unit. Unqualifi ed individuals should
not attempt to interpret these instructions or
install this equipment. Failure to follow safety
recommendations could result in possible
damage to the equipment, serious per
injury or death
• The installer must comply with all local codes and
regulations which govern the installation of this type
of equipment. Local codes and regulations take
precedence over any recommendations contained in
these instructions. Consult local building codes and
the National Electrical Code (ANSI CI) for special
installation requirements.
• All electrical wiring must be completed in accordance
with local, state and national codes and regulations
and with the National Electric Code (ANSI/NFPA 70)
or in Canada the Canadian Electric Code Part 1 CSA
C.22.1.
• This equipment contains liquid and gaseous refrigerant
under high pressure. DO NOT USE ANY PORTION OF
THE CHARGE FOR PURGING OR LEAK TESTING.
Installation or servicing should only be performed by
qualifi ed trained personnel thoroughly familiar with this
type equipment.
• Fully annealed, refrigerant grade copper tubing should
be used when installing the system. Refrigerant suction
line tubing should be fully insulated.
• Installation of equipment may require brazing
operations. Installer must comply with safety codes
and wear appropriate safety equipment (safety glasses,
work gloves, fi re extinguisher, etc.) when performing
brazing operations.
• Follow all precautions in the literature, on tags, and
on labels provided with the equipment. Read and
thoroughly understand the instructions provided with
the equipment prior to performing the installation and
operational checkout of the equipment.
.
sonal
4
Page 5
AIR CONDITIONER INSTALLATION
General Information
The NS6QD series air conditioner is designed only for
outdoor rooftop or ground level installations. This unit has
been tested for capacity and effi ciency in accordance with
A.H.R.I. Standards and will provide many years of safe
and dependable comfort, providing it is properly installed
and maintained. Abuse, improper use, and/or improper
maintenance can shorten the life of the appliance and
create unsafe hazards.
To achieve optimum performance and minimize equipment
failure, it is recommended that periodic maintenance be
performed on this unit. The ability to properly perform
maintenance on this equipment requires certain
mechanical skills and tools.
Before You Install this Unit
The cooling load of the area to be conditioned must be
calculated and a system of the proper capacity selected.
It is recommended that the area to be conditioned be
completely insulated and vapor sealed.
Check the electrical supply and verify the power supply
is adequate for unit operation. The system must be wired
and provided with circuit protection in accordance with
local building codes. If there is any question concerning
the power supply, contact the local power company.
The indoor section (air handler, furnace, etc) should be
installed before routing the refrigerant tubing. Refer to
the indoor unit's installation instructions for installation
details.
All units are securely packed at the time of shipment and
upon arrival should be carefully inspected for damage
prior to installing the equipment at the job site. Verify
coil fi ns are straight. If necessary, comb fi ns to remove
fl attened or bent fi ns. Claims for damage (apparent or
concealed) should be fi led immediately with the carrier.
Please consult your dealer for maintenance information
and availability of maintenance contracts. Please read
all instructions before installing the unit.
Locating the Air Conditioner
• Survey the job site to determine the best location for
mounting the outdoor unit. See Figure 4 (page 10) for
unit dimensions.
• Overhead obstructions, poorly ventilated areas, and
areas subject to accumulation of debris should be
avoided.
• Suffi cient clearance for unobstructed airfl ow through the
outdoor coil must be maintained in order to achieve rated
performance. For minimum clearances to obstructions,
see Figure 2.
• Consideration should be given to availability of electric
power, service access, noise, and shade.
Packaging Removal
NOTE: To prevent damage to the tubing connections,
carefully remove the carton and user’s manual from the
equipment. Discard the shipping carton.
Ground Level
Ground level installations must be located according to
local building codes or ordinances and these requirements:
• Clearances must be in accordance with those shown
in Figure 2.
• A suitable mounting pad (Figure 3) must be provided
and separate from the building foundation. The pad
must be level and strong enough to support the weight
of the unit. The slab height must be a minimum of 2”
(5 cm) above grade and with adequate drainage.
DO NOT
18"
18"
18"
OBSTRUCT
TOP OF UNIT
Figure 2. Clearance Requirements
2”
Figure 3. Ground Level Installation
18"
5
Page 6
Connecting Refrigerant Tubing Between the Indoor
& Outdoor Unit
CAUTION:
This system uses R-410A refrigerant with POE
oil. When servicing, cover or seal openings to
minimize the exposure of the refrigerant system
to air to prevent accumulation of moisture and
other contaminants.
• A fi lter dryer is provided with the unit and must be
installed in the liquid line of the system. If the installation
replaces a system with a fi lter dryer already present
in the liquid line, the fi lter dryer must be replaced with
the one supplied with the unit. The fi lter dryer must be
installed in strict accordance with the manufacturer’s
installation instructions.
• Optional equipment such as liquid line solenoid valves,
low ambient, etc., should be installed in strict accordance with the manufacturer’s installation instructions.
After outdoor and indoor unit placement has been
determined, route refrigerant tubing between the
equipment in accordance with sound installation practices.
• When connecting refrigerant linesets together, it is
recommended that dry nitrogen be fl owing through
the joints during brazing to prevent internal oxidation
and scaling.
• Refrigerant tubing should be routed in a manner that
minimizes the length of tubing and the number of bends
in the tubing. If precise forming of refrigerant lines is
required, a copper tubing bender is recommended.
Avoid sharp bends and contact of the refrigerant lines
with metal surfaces.
• Refrigerant tubing should be supported in a manner
that the tubing will not vibrate or abrade during system
operation.
• Tubing should be kept clean of foreign debris during
installation.
• Every effort should be made by the installer to ensure
that the fi eld installed refrigerant containing components
of the system have been installed in accordance with
these instructions and sound installation practices to
insure reliable system operation and longevity.
• The maximum recommended interconnecting
refrigerant line lengths is 75 ft. and the vertical elevation
difference between the indoor and outdoor sections
should not exceed 20 ft.
• These units are equipped with single shot quick connect
couplings. Together with the indoor section and line set,
only four coupling connections are required to provide
a 100% sealed system.
- Route the suction line and liquid line between indoor
and outdoor sections, remove protector caps and
plugs
- Lubricate entire surface of the diaphragm O-ring
and threads of the male coupling using the lubricant
supplied with the line set and a small brush.
- Make sure the coupling halves are held in proper
alignment with each other prior to starting the
threads of female coupling nut onto the male half.
Thread coupling halves together by hand until a
defi nite resistance is felt.
- Using a marker, mark a line from the coupling union
nut to the bulkhead then tighten an addition wrench
fl at (60°). See Table 1 for torque values. Repeat for
all couplings.
Coupling
Size
3/8” (10mm)
3/4” (19mm)
7.8” (22mm)
Torque
10-12 Ft-Lbs
(14-16 Nm)
35-45 Ft-Lbs
(47-61 Nm)
10-12 Ft-Lbs
(14-16 Nm)
Male
Coupling
3/4”11/16”5/8”
1-1/8”1-5/16”1”
1-1/8”1-5/16”1”
Female
Coupling
Nut
Female
Coupling
Body
Table 1. Torque Values
ELECTRICAL WIRING
WARNING:
To avoid risk of electrical shock, personal injury,
or death, disconnect all electrical power to the unit
before performing any maintenance or service.
The unit may have more than one electrical
supply.
Label all wires prior to disconnection when
servicing the unit. Wiring errors can cause
improper and dangerous operation.
• All electrical connections must be in compliance with
all applicable local codes and ordinances, and with
the current revision of the National Electric Code
(ANSI/NFPA 70).
• For Canadian installations the electrical connections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).
Pre-Electrical Checklist:
Verify that the voltage, frequency, and phase of the
supply source match the specifi cations on the unit
rating plate. See Table 4 (page 11).
Verify that the service provided by the utility is suffi cient
to handle the additional load imposed by this equipment.
Refer to the unit wiring label for proper voltage wiring.
Verify factory wiring is in accordance with the unit
• A wiring diagram is located on the inside cover of the
electrical box of the outdoor unit. The installer should
become familiar with the wiring diagram before making
any electrical connections to the outdoor unit.
• An electrical disconnect must be located within sight of and readily accessible to the unit. This
switch shall be capable of electrically de-energizing
the outdoor unit.
• Line voltage to the unit should be supplied from a
dedicated branch circuit containing the correct fuse
or circuit breaker for the unit. Incoming fi eld wiring
and minimum size of electrical conductors and circuit
protection must be in compliance with information listed
on the outdoor unit data label. Any other wiring methods
must be acceptable to authority having jurisdiction.
• The outdoor unit requires both power and control circuit
electrical connections. Refer to the wiring diagram /
schematic for identifi cation and location of outdoor unit
fi eld wiring interfaces (Figures 5 - 7, pages 12 - 14).
Make all electrical connections in accordance with all
applicable codes and ordinances.
• Overcurrent protection must be provided at the branch
circuit distribution panel and sized as shown on the unit
rating label and according to applicable local codes.
See the unit rating plate for minimum circuit ampacity
and maximum overcurrent protection limits.
• Provide power supply for the unit in accordance with the
unit wiring diagram, and the unit rating plate. Connect
the line-voltage leads to the terminals on the contactor
inside the control compartment.
• Use only copper wire for the line voltage power supply
to this unit as listed in Table 2. Use proper code agency
listed conduit and a conduit connector for connecting
the supply wires to the unit. Use of rain tight conduit
is recommended.
• 208/230 Volt units are shipped from the factory wired
for 230 volt operation. For 208V operation, remove the
Wire Size based on N.E.C. for 60° type copper conductors.
Table 2. Copper Wire Size
Supply Circuit
Ampacity
lead from the transformer terminal marked 240V and
connect it to the terminal marked 208V.
• Optional equipment requiring connection to the power
or control circuits must be wired in strict accordance
of the NEC (ANSI/NFPA 70), applicable local codes,
and the instructions provided with the equipment.
Grounding
WARNING:
The unit cabinet must have an uninterrupted or
unbroken electrical ground to minimize personal
injury if an electrical fault should occur. Do not
use gas piping as an electrical ground
This unit must be electrically grounded in accordance
with local codes or, in the absence of local codes, with
the National Electrical Code (ANSI/NFPA 70) or the CSA
C22.1 Electrical Code. Use the grounding lug provided in
the control box for grounding the unit.
Thermostat Connections
• Ther mostat connections should be made in accordance
with the instructions supplied with the thermostat and
the indoor equipment.
• The outdoor unit is designed to operate from a 24 VAC
Class II control circuit. The control circuit wiring must
comply with the current provisions of the NEC (ANSI/
NFPA 70) and with applicable local codes having
jurisdiction.
• The low voltage wires must be properly connected to
the units low voltage terminal block. Recommended
wire gauge and wire lengths for typical thermostat
connections are listed in Table 3.
• The thermostat should be mounted about 5 feet
above the fl oor on an inside wall. DO NOT install the
thermostat on an outside wall or any other location
where its operation may be adversely affected by radiant
heat from fi replaces, sunlight, or lighting fi xtures, and
convective heat from warm air registers or electrical
appliances. Refer to the thermostat manufacturer’s
instruction sheet for detailed mounting and installation
information.
Recommended T-Stat Wire
Thermostat
Wire Gauge
245525
229045
2014070
18225110
Table 3. Thermostat Wire Gauge
Unit to T-Stat (Length in FT)
2-Wire
(Heating)
(Heating/Cooling)
!
5-Wire
7
Page 8
START UP & ADJUSTMENTS
Pre-Start Check List
Verify the indoor unit is level and allows proper
condensate drainage.
Verify the outdoor coil and top of the unit are free from
obstructions and debris, and all equipment access/
control panels are in place.
Verify air fi lters are cleaned and properly installed.
Verify duct work is sealed to prevent air leakage.
Verify line voltage power leads are securely connected
and the unit is properly grounded.
Verify low voltage wires are securely connected to the
correct leads on the low voltage terminal strip.
Verify power supply branch circuit overcurrent protection
is sized properly.
Verify the thermostat is wired correctly.
Start-Up Procedures
The thermostat's function mode should be set to OFF and
the fan mode should be set to AUTO. Close all electrical
disconnects to energize the system.
Air Circulation - Indoor Blower
1. Set the thermostat system mode on OFF and the fan
mode to ON.
2. Verify the blower runs continuously. Check the air
delivery at the supply registers and adjust register
openings for balanced air distribution. If insuffi cient
air is detected, examine ductwork for leaks or
obstructions.
3. Set the thermostat fan mode to AUTO and verify the
blower stops running.
System Cooling
1. Set the thermostat’s system mode to COOL and the
fan mode to AUTO. Gradually lower the thermostat
temperature setpoint below room temperature and
verify the outdoor unit and indoor blower energize.
2. Verify blower wheel is spinning in direction indicated
by arrow. Feel the air being circulated by the indoor
blower and verify that it is cooler than ambient
temperature. Listen for any unusual noises. If unusual
sounds occur, determine the source of the noise and
correct as necessary.
3. Verify HI and LO refrigerant pressures.
4. Allow the system to operate for several minutes
and then set the temperature selector above room
temperature. Verify the fan and compressor cycle off
with the thermostat. NOTE: The blower should also
stop unless fan mode is set to the ON position.
System Heating (optional)
1. Set the thermostat's system mode to HEAT and the
temperature mode above room temperature.
2. Verify the optional heating equipment (furnace or
electric heat) and indoor blower energize. Feel the air
being circulated by the indoor blower and verify that
it is warmer than ambient temperature. Listen for any
unusual noises. If unusual sounds occur, determine
the source of the noise and correct as necessary.
Refrigerant Charging
WARNING:
NS6QD Split System Air Conditioners leave
the factory with an R-410A refrigerant holding
charge. Follow these charging instructions for
maximum unit performance and effi ciency. Some
local codes require licensed installation/service
personnel to service this type of equipment.
Refrigerant charging must be done by qualifi ed
personnel familiar with safe and environmentally
responsible refrigerant handling procedures.
Under no circumstances should the owner
attempt to install and/or service this equipment.
Failure to comply with this warning could result
in property damage, personal injury, or death.
After refrigerant line connections are completed, it is
required that you leak check and evacuate the indoor
section and all line connections (using proper methods)
before fi nalizing the full system refrigerant charge. For
fi nal charges based on matched systems and specifi ed
line lengths, see physical and electrical specifi cations
(Table 4, page 11).
• Refrigerant charging charts are applicable only to
matched assemblies of NORDYNE equipment and
listed airfl ows for the indoor coil. Refer to Figures 8 13 (pages 16 - 18) for correct system charging.
• NS6QD outdoor units with indoor coils not listed are
not recommended. Deviations from rated airfl ows or
non-listed combinations may require modifi cation to the
expansion device and refrigerant charging procedures
for proper and effi cient system operation.
• The refrigerant charge can be checked and adjusted
through the service ports provided external to the
outdoor unit. Use only gage line sets which have a
“Schrader” depression device present to actuate the
valve.
Charging an R-410A system in AC mode at outdoor
temperatures above 55° F for optimized sub-cooling of
10° F - 12° F.
1. With the system operating at steady-state, measure
the liquid refrigerant pressure (in psig) at the outdoor
unit service valve.
2. Measure the liquid refrigerant temperature (in
Fahrenheit) at the service valve.
3. Determine the required liquid refrigerant pressure
from the appropriate charging chart (Figures 8 - 13).
• If the pressure measured in Step 1 is greater than
the required liquid refrigerant pressure determined in
Step 3, then there is too much charge in the system.
Remove refrigerant and repeat Steps 1 through 3
until the system is correctly charged.
8
Page 9
• If the pressure measured in Step 1 is less than the
required liquid refrigerant pressure determined in
Step 3, there is too little charge in the system. Add
refrigerant and repeat Steps 1 through 3 until the
system is correctly charged.
AIR CONDITIONER MAINTENANCE
WARNING:
To prevent electrical shock, personal injury, or
death, disconnect all electrical power to the unit
before performing any maintenance or service.
The unit may have more than one electrical
supply.
Proper maintenance is important to achieve optimum
performance from the air conditioner. The ability to properly
perform maintenance on this equipment requires certain
mechanical skills and tools. If you do not possess these
skills, contact your dealer for maintenance. Consult your
local dealer about the availability of maintenance contracts.
Routine maintenance should include the following:
• Inspect and clean or replace air fi lters at the beginning
of each heating and cooling season, or more frequently
if required.
• Inspect the condensate drain and outdoor coil at the
beginning of each cooling season. Remove any debris.
Clean the outdoor coil and louvers as necessary using
a mild detergent and water. Rinse thoroughly with water.
• Inspect the electrical connections for tightness at the
beginning of each heating and cooling season. Service
as necessary.
COMPONENT FUNCTIONS
High Pressure Switch (HPS)
A high-pressure switch is factory-installed and located in
the liquid line internal to the outdoor unit. The switch is
designed to protect the system when very high pressures
occur during abnormal conditions. Under normal
conditions, the switch is closed. If the liquid pressure
rises above 575 psig, then the switch will open and deenergize the outdoor unit. The switch will close again
once the liquid pressure decreases to 460 psig. Please
note that the switch interrupts the thermostat inputs to
the unit. Thus, when the switch opens and then closes,
there may be a 5 minute short cycling delay before the
outdoor unit will energize.
REPLACEMENT PARTS
Replacement parts are available through all Nordyne
Please have the complete model and serial number of the unit
when ordering replacement parts.
ELECTRICAL:
CapacitorsTemperature Limit Switches
CompressorsThermostats
ContactorsTime Delay Relays
Pressure SwitchesTransformers
Relays
MOTORS:
Blower Motor
Fan Motor
COMPONENTS:
Blower AssemblyFan Grille
Cabinet PanelsFilter/Driers
Expansion Valves
distributors.
CAUTION:
The unit should never be operated without a
fi lter in the return air system. Replace disposable
fi lters with the same type and size.
• Do not attempt to add additional oil to motors
unequipped with oil tubes. The compressor is
hermetically sealed at the factory and does not require
lubrication.
Table 4. Electrical Specifi cations & Physical Data
78808988110115
Net113116135157163188
Ship118121140163169194
11
Page 12
WIRING DIAGRAM
Split System Air Conditioner (Outdoor Section)
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105 deg C.
5. For ampacities and overcurrent protection, see unit rating plate..
6. Connect to 24 vac/40ca/class 2 circuit. See furnace/airhandler installation
instructions for control circuit and optional relay/transformer kits.
7. Anti-Shor t Cycle Timer (ASCT ) may or may not be installed in the unit. If desired,
ASCT is fac tory installed on select models only or may be field installed as shown using
manufacturer’s approved kit. If not present, connect Yellow and Black wires per Note 6.
8. DO NOT use a Hard Start Kit on a model with a PTCR installed.
208/230V
L1
(OPTIONAL)
T1
PTCR(If equipped)
H
C
F
24 VOLT FIELD
CONNECTIONS
CC - Contactor Coil
CCH - Crankcase Heater
HPS - High Pressure Switch
CCH
CC
HPS
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
COMPRESSOR
R
S
COMPRESSOR
S
R
(SEE NOTE 7)
ASCT
LEGEND:
CONTACTS
C
C
OUTDOOR FAN
MOTOR
ASCT
L2
T2
ASCT
(SEE
HPS
YELLOW
WIRE NUT
SEE NOTE 6
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs
en cuivre.
3. Ne convient pas aux installations
de plus de 150 volt a la terre.
BLUE
ORANGE
CAPACITOR
YELLOW/
BLACK
NOTE 7)
T2
T1
T3
BLACK
CRANKCASE
(OPTIONAL)
C
DUAL
HEATER
R
S
OUTDOOR
FAN MOTOR
F
H
BLACK
CONTACTOR
C
RED
Single Phase
BLACK
START
RELAY
BLACK
T2
T1
L1
L2
YELLOW
L1 L2
GND
7110050
PTCR
BLACK
GROUNDING
capacitor
BLACK
C
YELLOW
BLACK
S
to T2 on
R
to “H” on
capacitor
3
YELLOW
START
CAPAC
SCREW
RED
to”C” on
capacitor
2
1
Figure 5. NS6QD Wiring Diagram (2 - 2.5 Ton Units)
12
Page 13
Figure 6. NS6QD Wiring Diagram (3 Ton Units)
13
Page 14
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. Not suitable on systems that exceed 150 volts to ground.
4. For replacement wires use conductors suitable for 105˚ C.
5. For ampacities and overcurrent protection, see unit rating plate.
6. Connect to 24 vac/40va/class 2 circuit. See furnace/air handler installation
instructions for control circuit and optional relay/transformer kits.
7.
Anti-Short Cycle Timer (ASCT) may or may not be installed in the unit. If desired,
ASCT is factory installed on select models only or may be field installed as shown using
manufacturer's approved kit. If not present, connect Yellow and Black wires per Note 6.
3. Ne convient pas aux installations de plus de 150 volt a la terre.
ASCT
(See
Note 7.)
HPS
Yellow
T2
T1
T3
Black
See Note 6.
Orange
Blue
Red
or
Yellow
S
Dual
Capacitor
Black
Crankcase
Heater
(Optional)
R
Outdoor
Fan Motor
F
C
H
Black
C
Yellow
Black or
Black White
Red or Red Black
C
Compressor
R
S
Single PhaseSplit System Air Conditioner (Outdoor Section)
T1 T2
L1 L2
Yellow or
Yellow Black
L1 GrdL2
(1 Phase)
Field Supply
Red
Black
Yellow
Start
Capacitor
Contactor
Grounding
Screw
7103880
3
Start
Relay
2
1
Figure 7. NS6QD Wiring Diagram (3.5 - 5 Ton Units)
14
Page 15
NS6QD CHARGING CHARTS - COOLING ONLY
Application Notes on the Use of Charging Charts
• This equipment’s cooling system contains refrigerant under high pressure. Always use safe and
environmentally sound methods when handling refrigerant handling or servicing the unit. Review the
factory literature and safety warnings prior to servicing.
• When repairing system leakages, always use a nitrogen (inert) gas to protect the refrigerant system and pressure
check the repair before re-charging. Always replace the fi lter-dryers when performing any repair to the refrigeration
system with one capable of acid removal. After completing the repairs, evacuate the system to 350 - 500 microns
and weigh in the refrigerant to the amount specifi ed on the unit rating label.
• Charging charts are valid for a variety of indoor, return air conditions and are most infl uenced by the outdoor
ambient temperature, outdoor fan operation and the unit operating voltage. Before using these charts, ensure
the unit is in a stable operating mode. As shown in the charging charts (Figures 8 - 13, page 16 - 18), the ideal
system sub-cooling can vary over the range of operation. Reference the charts to determine the ideal amount of
sub-cooling for a given liquid pressure. Units charged to other values will not perform at the rated unit effi ciency
(EER) or rated Coeffi cient of Performance (COP) in heating mode.
• To inspect a systems operation using quality instruments, match the measured liquid temperature to the units
chart. The measured liquid pressure reading should be within 3% of the charts value for most installations.
• For systems that are operating with more than a 5% deviation, inspect the unit for the proper voltage and phase
balance and the refrigeration system for leaks.
• Units that are operating at less then 95% of the nominal voltage or with a 2% phase imbalance may see a more
signifi cant deviation than the amount stated above.
• DO NOT use the charts in systems that have a fan cycling under low-ambient control. Refer to the low-ambient
kit instructions for more information. (If applicable)
15
Page 16
NS6QD-024K TXV Charging Chart
625
600
575
550
525
500
475
450
425
400
375
Liquid Pressure (psig)
350
325
300
275
250
Remove refrigerant when above curve
SEE NOTE
Add refrigerant when below curve
7580859095100105110115120125130135
Liquid Temperature ( ° F)
Figure 8. Charging Chart for 2 Ton Units
NOTE: Do not add or remove refrigerant if pressure reading is between the curves.
NS6QD-030K TXV Charging Chart
600
575
550
525
Remove refrigerant when above curve
SEE NOTE
Add refrigerant when below curve
7580859095100105110115120125130135
Liquid Pressure (psig)
500
475
450
425
400
375
350
325
300
275
250
16
Liquid Temperature ( ° F)
Figure 9. Charging Chart for 2.5 Ton Units
Page 17
NS6QD-036K TXV Charging Chart
600
575
550
525
500
475
450
425
400
375
Liquid Pressure (psig)
350
325
300
275
250
Remove refrigerant when above curve
SEE NOTE
Add refrigerant when below curve
7580859095100105110115120125130135
Liquid Temperature ( ° F)
Figure 10. Charging Chart for 3 Ton Units
NOTE: Do not add or remove refrigerant if pressure reading is between the curves.
NS6QD-042K TXV Charging Chart
600
575
550
525
Remove refrigerant when above curve
SEE NOTE
Add refrigerant when below curve
7580859095100105110115120125130135
Liquid Pressure (psig)
500
475
450
425
400
375
350
325
300
275
250
Figure 11. Charging Chart for 3.5 Ton Units
Liquid Temperature ( ° F)
17
Page 18
NS6QD-048K TXV Charging Chart
600
575
550
525
500
475
450
425
400
375
Liquid Pressure (psig)
350
325
300
275
250
Remove refrigerant when above curve
SEE NOTE
Add refrigerant when below curve
7580859095100105110115120125130135
Liquid Temperature ( ° F)
Figure 12. Charging Chart for 4 Ton Units
NOTE: Do not add or remove refrigerant if pressure reading is between the curves.
NS6QD-060K TXV Charging Chart
600
575
550
525
Remove refrigerant when above curve
SEE NOTE
Add refrigerant when below curve
7580859095100105110115120125130135
Liquid Pressure (psig)
500
475
450
425
400
375
350
325
300
275
250
18
Liquid Temperature ( ° F)
Figure 13. Charging Chart for 5 Ton Units
Page 19
19
Page 20
INSTALLATION / PERFORMANCE CHECK LIST
INSTALLATION ADDRESS:
CITY ________________________ STATE ________________
UNIT MODEL # ________________________________________
UNIT SERIAL # _______________________________________
Unit Installed Minimum clearances per
Figure 2 (page 5)?
INSTALLER NAME:
CITY _______________________STATE ________________