Read this owner information to become familiar with the capabilities and use
of your appliance. Keep this with literature on other appliances where you
have easy access to it in the future. If a problem occurs, check the instructions
and follow recommendations given. If these suggestions don’t eliminate your
problem, call your installing contractor or distributor in your area.
INTRODUCTION
Most any air conditioner will keep you cool. Our air conditioner was designed to do
it effi ciently. Effi ciency means less cost to you while keeping you comfortable.
WHY YOUR AIR CONDITIONER WORKS SO WELL, SO QUIETLY
1. Air is cooled by a large evaporator coil. Moisture is also removed from the air by
this same coil.
2. Air is then delivered through the main duct, via registers, into your home.
3. Return air is drawn through the return register.
4. This air enters the unit, passes through the evaporator coil, is cooled and dehumidifi ed. Then the cycle begins again.
Page 2
2
Page 3
SECTION 1.
OWNER INFORMATION
OPERATING INSTRUCTIONS
To Operate Your Air Conditioner for Cooling—
To Operate the Indoor Blower Continuously—
Set the thermostat fan switch to ON (See Figure 1)
The indoor blower will start immediately, and
will run continually until the fan switch is reset
to AUTO.
1. Set the thermostat system switch to COOL or
AUTO and the thermostat fan switch to AUTO.
(See Figure 1)
2. Set the thermostat temperature to the desired
temperature level using the temperature selector.
Please refer to the separate thermostat user’s
manual for complete instructions regarding
thermostat programming. The outdoor unit
and indoor blower will both cycle on and off to
maintain the indoor temperature at the desired
cooling level.
To Operate Your Unit for Heating — (If optional
heat accessory is installed.)
1. Set the thermostat system switch to HEAT or
AUTO and the thermostat fan switch to AUTO.
(See Figure 1)
Fan Switch
Temperature Selector
Figure 1. Typical Thermostat
The continuous indoor blower operation can be
obtained with the thermostat system switch set
in any position, including OFF. The continuous
indoor blower operation is typically used to
circulate the indoor air to equalize a temperature
unbalance due to a sun load, cooking, or fi replace
operation.
BEFORE YOU CALL A SERVICEMAN
Let your serviceman check your system at the
start of each air conditioning season. He will
make sure it’s working right, clean or change
fi lters and make any needed adjustments.
In addition, follow these simple rules:
1. Never run your system without fi lter. If you
do, the cooling coils will get dirty and may
become clogged.
2. Set your thermostat at the comfort level you
wish -- and then leave it alone. Let it control
the operation of the air conditioning system.
If you get chilly, turn it up a degree at a time
until comfort is restored.
3. It takes longer for an air conditioner to cool
your dwelling than it does for your furnace to
heat it. Therefore, do not turn the unit on and
expect a dramatic drop in temperature, at
least not right away. If your home is hot and
humid, the temperature will drop slowly.
4. Check your fi lters every ten days in summer
to see if they are dirty. To keep them clean,
use a mild solution of detergent and water
on washable types. Replace non washable
fi lters.
5. Keep your outdoor condenser coil clean.
You can hose it down when it gets dirty.
2. Set the thermostat temperature to the desired
temperature level using the temperature selector.
Please refer to the separate user’s manual for
complete thermostat programming instructions.
The furnace and indoor blower will cycle on and
off to maintain the indoor temperature at the
desired heating level.
To Shut Off Your Air Conditioner —Set the
thermostat system switch to OFF and the
thermostat fan switch to AUTO. (See Figure 1)
The system will not operate, regardless of the
thermostat temperature setting.
If your air conditioner isn’t working:
1. Make sure the fuses are not blown or that
your circuit breakers are on.
2. See that your thermostat is set at the desired
temperature and that your system’s switch
is on “Cool.”
3. For free air fl ow, make sure your return
register is not covered and that the fi lter is
clean.
4. Check the outdoor condenser coil and make
sure it is clean and not clogged with grass
or leaves.
If your air conditioner still isn’t working, call your
nearest distributor.
3
Page 4
SECTION 2.
INSTALLER INFORMATION
GENERAL
Read the following instructions completely
before performing the installation.
These instructions are for the use of qualifi ed
personnel specially trained and experienced
in the installation of this type of equipment
and related system components. Some states
require installation and service personnel to
be licensed. Unqualifi ed individuals should not
attempt to interpret these instructions or install
this equipment.
The single packaged air conditioners are designed for outdoor installation only and can be
readily connected into the high static duct system
of a home. The only connections needed for
installation are the supply and return ducts, the
line voltage, and thermostat wiring. A complete
air conditioning system typically consists of:
• Single Package Air Conditioner
• Home Fittings Kit
• Unit Fittings Kit
• Thermostat
The single package air conditioner is completely
assembled, factory wired, and factory run tested.
The units are ready for easy and immediate
installation.
PRE-INSTALLATION CHECK
Before any installation is attempted, the cooling load of the area to be conditioned must be
calculated and a system of the proper capacity
selected. It is recommended that the area to
be conditioned be completely insulated and
vapor sealed.
for damage (apparent or concealed) should be
fi led immediately with the carrier.
CAUTION:
This unit uses refrigerant R-410A. Do
NOT under any circumstances use
any other refrigerants besides R-410A
in this unit. Use of another refrigerant
will damage this unit.
WARNING:
Single Packaged Air Conditioners are
shipped fully charged with R-410A
refrigerant and ready for installation.
When a system is installed according
to these instructions, no refrigerant
charging is required. If repairs make it
necessary for evacuation and charging,
it should only be done by qualifi ed,
trained personnel thoroughly familiar
with this equipment. Some local codes
require licensed installation service
personnel to service this type of
equipment. Under no circumstances
should the owner attempt to install
and/or service this equipment. Failure
to comply with this warning could result
in property damage, personal injury or
death.
INSTALLATION
1. SELECT THE BEST LOCATION FOR
THE AIR COND ITIONING UNIT
The installer should comply with all local codes
and regulations which govern the installation
of this type of equipment. Local codes and
regulations take precedence over any recommendations contained in these instructions.
Consult local building codes and the National
Electrical Code (ANSI CI) for special installation
requirements.
The electrical supply should be checked to determine if adequate power is available. If there
is any question concerning the power supply,
contact the local power company.
Inspecting Equipment: All units are securely
packed at the time of shipment and, upon arrival,
should be carefully inspected for damage. Claims
4
IMPORTANT: DO NOT PLACE UNIT UNDER
THE HOME.
• Select a solid, level position, preferably on a
concrete slab, slightly above the grade level,
and parallel to the home.
• The hot condenser air must be discharged
up and away from the home, and if possible,
in a direction with the prevailing wind.
• Do not place the unit in a confi ned space.
• If practical, place the air conditioner where it
and the ducts will be shaded from the afternoon sun when the heat load is greatest.
• Try to select a site for the unit that is as close
as possible to the proposed return grille location.
Page 5
6 ft.
24"
12"
12"
Figure 2. Minimum Unit Clearances
• Keep in mind that the length of the supply and
return ducts should be kept to a minimum with
no sharp radius bends.
2. UNPACK THE UNIT
It is recommended that the unit be unpacked
at the installation site to minimize damage due
to handling.
CAUTION:
Do not tip the unit on its side. Oil may
enter the compressor cylinders and
cause starting trouble. If unit has been
set on its side, restore to upright position and do not run for several hours.
Then run unit for a few seconds. Do this
three or four times with fi ve minutes
between runs.
a. Remove the bands from around the unit.
b. Unfold the top and bottom cap fl anges.
c. Carefully remove the top cap and tube.
3. CLEARANCES
Minimum clearances, as specifi ed in Figure
2, MUST be maintained from adjacent structures to provide room for proper servicing
and air circulation.
Do NOT install unit in a confi ned or recessed
area that will allow discharge air from the unit
to re-circulate into the condenser air inlet,
through the coil.
Service Access Clearance:
Blower access panel side ........................... 24”
Electrical compartment access panel side .. 12”
Clearance between overhang and top of
unit .............................................................72”
Clearance around condenser coil area to wall
or shrubs (excludes duct panel side) ..........12”
Supply and Return Air Ducts ...................... 0”
Duct Connection side ................................. 0”
DUCT REQUIREMENTS
The supply duct system, including the number
and type of registers, will have much more effect on the performance of an air conditioning
system then any other factor. The duct must be
suffi ciently large to conduct an adequate amount
of air to each register.
4. INSTALL THE RETURN AND SUPPLY AIR
FITTINGS ON THE UNIT
The supply and return fi ttings are included with
select models. If supplied, the duct fi ttings are
shipped in the supply duct. They attach to the unit
openings with a fl ange and bead arrangement,
secured with two sheet metal screws. Note: For
Transition Duct Screws
Supply Air
14” Duct Dimples
Return Air
Figure 3. Return and Supply Air Fittings
Figure 4. Return Air Box
5
Page 6
ease of access, install fi tting before positioning
unit in fi nal location.
SUPPLY DUCT
Position the supply duct collar, if supplied, so the
edge of the unit opening fi ts between the fl ange
and the bead. Over lap the collar ends keeping the
small screw holes underneath. Align the holes in
the crimped area and install one screw.
Note: It may be necessary to loosen the four
screws that hold the transition duct in order to
install the supply fi tting. Re-tighten when installation is complete.
Tap collar as necessary to ensure engagement
with unit opening and install second screw.
Tighten fi rst screw. Rotate collar clockwise so
joint is near three o’clock position.
RETURN DUCT
Align the 14” return duct slots with the holes in
the collar and install two screws. Position the
collar over the opening and align the four notches
in the collar with the four dimples in the panel.
Using self-drilling screws (10-16x.5) attach the
collar to the rear panel.
5. LOCATING AND INSTALLING THE RETURN AIR ASSEMBLY
To avoid complications, locate and install the
return air assembly fi rst. The return air box
with grille and fi lter (Figure 4) should not be
located in heavy traffi c areas like hallways or
center of rooms. A good spot is in a corner or
under a table, if a minimum two inch clearance
is available. If desired, the return opening can
be located inside a closet with louvered doors
that have an open area equal to or greater than
the 12” x 20” grille furnished. The return air grille
can be placed in the wall of a closet and the air
ducted into the fi lter box through a boxed-in area
at the closet fl oor level. Make sure the fi lter is
readily accessible.
After determining the location of the return air
opening, start the installation from under the
home by cutting a small hole in the fi ber underboard to determine how the fl oor joist location
will affect cutting the opening needed for the box.
Floor joists generally are located on 16” centers,
leaving 14-3/8” between joists. After measuring
the return air box (approximately 12-1/4” x 141/4”), cut the hole through the fl oor so that the
box will fi t between the fl oor joists. Care should
be taken when cutting through carpeting to avoid
snags. In most installations it will be necessary to
cut a similar hole in the fi berboard directly under
the hole in the fl oor. However, if the fl oor is more
than ten inches deep, it will only be necessary
6
Figure 5. Supply Damper
to cut a hole for the collar on the return air box
or for the insulated duct.
Set the box into the opening and fasten with
screws or nails. Put the fi lter and return air
grille in place.
6. LOCATING AND INSTALLING THE
SUPPLY DAMPER(S)
CAUTION:
When a home is not equipped with a
make-ready kit, means must be provided to prevent simultaneous operation of the heating and cooling units.
A heat/cool thermostat is available for
this purpose.
When installing this air conditioning
system in conjunction with a furnace, a
damper must be installed in the furnace
base assembly to prevent cold air being
discharged around the heat exchanger.
Damage to the heat exchanger and
asphyxiation may occur if a damper is
not installed.
Check with the furnace manufacturer
for damper requirements. Failure to
install the required furnace damper
may invalidate code agency listing and
limited warranty on the furnace.
When locating the supply damper(s), carefully
check fl oor joists and frame members that could
interfere with the installation of the damper or
fl exible duct. Ideally, the damper should be
located in the bottom of the main duct, forward
of center of the home, at least three feet from
the nearest register. The round supply opening
in the slanted side of the damper should face
the side of the home where the air conditioner
is located. To locate the center of the heat duct,
fi rst cut a small hole in the fi berboard below the
Page 7
TYPICAL APPLICATIONS
4
3
2
1
5
6
3
2
1
4
6
7
5
4
6
MULTIPLE DUCT APPLICATIONSINGLE DUCT APPLICATION
Ref. No.Description
112” x 20” Return Air
216” x 20” Air Filter
312” x 20” Grille
4Supply Damper
514” Diameter Flex Return Duct
612” Diameter Flex Supply Duct
712” x 12” x 12” “Y” Fitting
Figure 6. Typical Applications
duct at the desired location. After locating the
duct center, cut a hole approximately 3/4” larger
than the damper opening in the fi berboard. Cut
a 9-1/8” x 13-1/8” hole in the duct and bend
over all tabs fl at on the inside of the heat duct.
After inserting the damper into the duct, bend
over all tabs fl at on the inside of the heat duct.
Seal the opening between the fi berboard and
damper or fl exible duct.
DUCTING SYSTEM
DUCT REQUIREMENTS
The supply duct system, including the number
and type of registers, will have much more effect on the performance of an air conditioning
system than any other factor. The duct must be
suffi ciently large to conduct an adequate amount
of air to each register.
Air ducts should be installed in accordance with
the standards of the National Fire Protection
Association “Standard for Installation of Air
Conditioning and Ventilation Systems” (NFPA
90A), “Standard for Installation of Residence
Type Warm Air Heating and Air Conditioning
Systems” (NFPA 90B), these instructions, and
all applicable codes.
THE AIR CONDITIONING OUTPUT OF THE
SYSTEM WILL NOT COOL THE HOME IF THE
AIR IS LOST TO THE OUTSIDE THROUGH
LEAKS IN THE DUCT SYSTEM. ALSO, DUCTS
WHICH ARE COLLAPSED OR RESTRICTED
BY FOREIGN OBJECTS WILL PREVENT
ADEQUATE AIR FLOW.
Note: For highly resistive duct systems it may
be necessary to add an additional return air duct
and or supply to achieve maximum performance
and prevent coil icing and refrigerant fl ood
back.
CONNECTING THE RETURN AND SUPPLY
AIR FLEXIBLE DUCTS
a. The supply duct for all units is 12” in diam-
eter. The return duct is 14” diameter for all
air conditioning units.
7
Page 8
b. The fl exible ducts can be connected to the
corresponding fi ttings with the clamps provided with the ducts. Note: All connections
should be leak tight or a loss in cooling
capacity will result.
c. The fl exible ducts may be cut to the required
length, see instructions packed with duct.
Keep all ducts as short and straight as possible. Avoid sharp bends.
d. Ducts may be spliced with sheet metal
sleeves and clamps. (See Ducting Installation Accessories page 6.)
e. Once the inner duct is connected to the
proper fi tting, the insulation and plastic
sleeve should be pulled over the connection
and clamped.
f. For homes with multiple supply ducts or for
special applications, a Y fi tting is available
to divide the supply air so it can be ducted
to different areas of the home for more effi cient cooling. Note: The Y fi tting should be
insulated for maximum performance.
Elbow
P-Trap
Figure 8. Drain Trap
If High Effi ciency Motor (3.5, 4, and 5 Ton):
1. Disconnect all electrical power to the unit
and remove the blower panel.
2. Locate the orange and red wires terminated
to the blower motor. The orange wire controls
cooling operation while the red wire controls
heating operation.
3. Verify the required speed from the airfl ow
data found in fi gure 7. Place appropriate
wire on the appropriate motor speed tap for
the required airfl ow point.
Blower Speed — For optimum system
performance and comfort, it may be necessary
to change the factory set speed. See fi gure 7 for
factory settings. To change the blower speed:
If Standard Motor (2, 2.5 and 3 Ton):
1. Disconnect all electrical power to the
unit and remove the service panel.
2. Place the desired blower speed lead on the
“COM” terminal. Use another wire tie (fi eld
supplied) to bundle the remaining motor
leads.
Model
P5RD
2 Ton
2.5 Ton
3 Ton
3.5 Ton
4 Ton
5 Ton
* Factory Setting
Wire Color /
Speed Tap
RedLow*770
BlackHigh1064
RedLow770
BlackHigh*1064
RedLow770
BlackHigh*1064
T1Low750
T2Med/Low1000
T3Medium1140
Orange / T4Med/High*1300
Red / T5High*1450
T1Low1340
Red / T2Med/Low*1450
Orange / T3Medium*1500
T4Med/High1650
T5High1970
T1Low1340
Red / T2Med/Low*1450
T3Medium1500
Orange / T4Med/High*1650
T5High1970
Motor
Speed
Air Flow
(0.3 In. WC)
Figure 7. Standard Motor Lead Connection
8
Check all factory wiring per the unit wiring
diagram and inspect the factory wiring connections to be sure none loosened during shipping
or installation.
CAUTION:
To avoid personal injury or property
damage, make certain that the motor
leads cannot come into contact with
any uninsulated metal components
of the unit.
CONDENSATE DRAIN
A 3/4” condensate fi tting extends out of the side
of the unit. The drain trap, shipped in the electrical
compartment, must be installed to prevent water
from collecting inside the unit. Thread the elbow
provided with the unit into the drain connection
until hand tight. Install the trap into the fi tting and
seal the joint. Make sure it is level. Route the
condensate from the trap to a suitable drain. Any
connecting tubing or hose must have the outlet
below the trap level for proper drainage.
WARNING:
Turn off electrical power before servicing controls. Severe electrical shock
may result unless power is turned off.
Unit must be installed in compliance
with the National Electrical Code (NEC)
and local codes.
Page 9
High Voltage
Figure 9. Power Entry
Low Voltage
a. Connect Cooling Thermostat: The cool-
ing thermostat available for use with this
system is equipped with a selector switch.
To shut down the air conditioner, set the
selector switch to the OFF position. Connect the red and yellow wires from the unit
to the R and Y terminals respectively on
the thermostat subbase. Connect the green
wire to the yellow wire at the unit. See the
instruction sheet packed with the thermostat
for detailed methods of mounting.
ELECTRICAL CONNECTIONS
1. ELECTRICAL SERVICE
High Voltage
a. Install a branch circuit disconnect of ad-
equate size per NEC. Locate the disconnect
within sight of the unit.
b. Extend leads through power wiring hole
provided. Connect L1 and L2 directly to the
contactor. (See Figure 9).
c. Ground the air conditioning unit using the
green grounding screw provided in the
control panel.
Low Voltage
a. Route 24v control wires through the sealing
grommet near the power entrance.
b. Connect the control wires to the leads in
the low voltage area. (See Figure 10).
2. OVERCURRENT PROTECTION
In general, the best fuse or breaker for any air
conditioner is the smallest size that will permit
the equipment to run under normal use and
service without nuisance trips. Such a device,
sized properly, gives maximum equipment
protection. The principal reason for specifying
a time delay type is to prevent nuisance trips
when the unit starts.
b. Connect the Heat-Cool Thermostat: The
heat-cool thermostat is equipped with a
system HEAT-COOL switch, which provides
a positive means of preventing simultaneous operation of the heating and cooling
units. The thermostat is also equipped with
an ON-AUTO fan switch which allows the
home owner to operate the indoor blower
when air circulation is desired.
Connect the red, yellow, green and brown
low voltage wires to the R or RC, Y, G and
W terminals respectively on the thermostat
base. The black wire is the 24 volt common
required on some thermostats. See thermostat instruction sheet for more detailed
information.
Refer to furnace installation instructions
for required connections and proper heat
anticipator setting when installing unit with
an external furnace.
c. If two stage heating is desired, an
optional outdoor thermostat may be
installed: Connect the thermostat to the
orange low voltage wire and the W terminal
on the indoor thermostat base (See Figure
10). See the thermostat instructions for
details on setting the outdoor thermostat.
In the event that a fuse does blow or a breaker
trips, always determine the reason. Do not arbitrarily put in a larger fuse or breaker and do not,
in any case, exceed the maximum size listed on
the data label of the unit.
3. LOCATING THE THERMOSTAT
Locate the thermostat away from drafts and
slamming doors and place it where there is a free
fl ow of air. Mount on an inside wall approximately
fi ve feet from the fl oor.
Do not locate near a lamp, kitchen range, direct
sunlight, or in line with air fl ow from supply
registers.
4. ELECTRIC HEAT PACKAGE (OPTIONAL)
The air conditioner is shipped without an auxiliary electric heat kit installed. If electric heat is
desired, an accessory Heater Kit must be fi eld
installed. See Specifi cations Sheet for available
kits and their applications.
• Select the correct size heat package for the
installation.
• Follow installation instructions provided with
each heater kit.
• Installation is most easily accomplished
before making duct or electrical connections.
• The blower must be set to high speed for
electric heat operation.
9
Page 10
Control Wire Legend
Green - Blower Relay
Red - Transformer
24V
Yellow - Cooling 1st
Stage
Brown - Heating 1st
Stage
Orange - Heating 2nd
Stage
Outdoor Thermostat
(Field Supplied)
Figure 10. Low Voltage Connections
4 Wire Heat/Cool Thermostat
Single Stage Electric Heat
R
Y
G
W
Two Stage Electric Heat
R
Y
G
W
Optional
RED
YELLOW
GREEN
BROWN
ORANGE
RED
YELLOW
GREEN
BROWN
ORANGE
2 Wire Cooling Thermostat
R
Y
RED
YELLOW
GREEN
BROWN
SYSTEM OPERATION
1. PRE-START CHECK LIST
The following check list should be observed prior
to starting the unit.
Is the unit level? It should be level or slightly
slanted toward the drain for proper condensate drainage.
Is the unit installed with the proper clear-
ances (See Figure 2)?
Is the wiring correct according to the wiring
diagram and electrical codes?
Are all the wiring connections tight? Check
the condenser fan to make sure it turns
freely.
Is the overcurrent protection properly
sized?
Is the thermostat wired correctly? Is it
installed in a proper location?
2. START-UP PROCEDURE
a. Set the system switch to the OFF posi-
tion.
b. Dial thermostat setting as high as it will
go.
c. Turn on power supply at the disconnect
switch.
d. Set the system switch to ON or COOL.
Set the temperature setting to below room
temperature. Verify that the indoor blower,
outdoor fan, and compressor are energized
and the cooling function starts.
e. Verify that the discharge air grilles are
adjusted and the system is balanced.
f. Verify that there are no air leaks in the duct
work.
g. Verify that the condensate drain is properly
installed and that it functions correctly.
h. Dial the thermostat higher than room tem-
perature. The unit should stop.
i. If using a combination heating-cooling ther-
mostat, set to the HEAT position. Proceed
to check for correct furnace operation.
j. Verify that the furnace controls and burners
or heating elements operate correctly.
k. Instruct the owner on unit operation, fi lter
servicing, and proper thermostat operation.
Refrigerant Charging - Packaged Air Conditioners are fully charged with R410-A refrigerant at
the factory. The system refrigerant charge can be
checked and adjusted by removing the compressor cover panel and attaching gauge lines which
have a “schrader” depression device present
to activate the valve. Draw a vacuum on gauge
lines to remove air before attaching them to the
service ports on the unit. Refrigerant charging
must be done by qualifi ed personnel familiar with
safe and environmentally responsible refrigerant
handling procedures.
10
Page 11
13 SEER - Charging Charts
*Note: All pressures are listed in psig. and all temperatures in °F.
- Shaded Boxes indicate fl ooded conditions
- Rated Design Values. Suction Pressure will be lower than design
value if indoor air fl ow, entering dry bulb, or entering wet bulb
temperatures are lower than design.
- Discharge temperatures greater than charted values indicate an
undercharged system.
2OUTDOOR TEMPERATURE (°F)
TON707580859095100105
Suct.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Press.
Press.
Temp.
Press.
Temp.
Press.
Tem p.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
134 243 132
245 137
136
138 247 143
140
253 141
142 256 144
144278 147
146299 151
148321 153
150324 157 342 156
152346 160 364 158
265 134
267 139
269 144
274 144
287 136
289 140
291 145
296 147
309 138
311 142
313 147
317 150
331 140
333 144
335 148
339 152
353 142
355 146
357 150
360 154
375 144
377 148
379 152
382 156
154367 163 385 161
156389 165 407 163
158410 167
160
Dis.
Temp.
397 147
399 150
401 154
404 158
2.5OUTDOOR TEMPERATURE (°F)
TON707580859095100105
Suct.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Press.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Dis.
Temp.
137 254 133
257 139
139
141 259 144
143
265 142
145 268 144
147290 148
149312 152
151333 156
153337 159 355 159
155358 163 376 162
157380 166 398 164
276 135
279 140
281 146
286 145
299 138
301 142
303 147
308 149
321 140
323 145
325 149
330 152
343 143
345 147
347 151
351 155
365 145
367 149
369 154
373 158
388 148
390 152
392 156
395 160
410 151
412 155
414 159
416 163
159401 169 420 167
161423 171
163
11
Page 12
13 SEER - Charging Charts - Continued
3OUTDOOR TEMPERATURE (°F)
TON707580859095100105
Suct.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Press.
Press.
Temp.
131 267 145
269 151
133
Press.
Temp.
291 148
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Dis.
Tem p.
135 271 156
137
276 156
139 280 159
141304 162
143328 166
145352 169
147355 172 376 172
149379 175 400 174
151403 178 424 177
294 153
296 158
300 159
316 150
318 155
320 160
324 162
340 153
342 157
344 162
348 165
365 155
367 160
369 164
372 168
389 158
391 162
393 166
397 170
413 161
415 165
417 169
421 173
438 163
440 167
442 171
445 175
153427 181 448 180
155452 184
157
3.5OUTDOOR TEMPERATURE (°F)
TON707580859095100105
Suct.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Press.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Dis.
Tem p.
131 269 138
272 143
133
135 274 148
137
278 151
139 281 153
141305 159
143329 164
145352 168
147356 172 376 173
149379 177 400 178
151403 182 424 183
293 143
295 148
298 153
301 156
317 147
319 152
321 157
325 160
341 152
343 157
345 161
349 165
365 157
367 161
369 165
373 169
389 161
391 166
393 170
396 174
413 166
415 170
417 174
420 178
437 171
439 175
441 178
444 183
153427 187 447 187
155451 192
157
12
Page 13
13 SEER - Charging Charts - Continued
4OUTDOOR TEMPERATURE (°F)
TON707580859095100105
Suct.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Press.
Press.
Temp.
131 281 142
283 147
133
Press.
Temp.
306 146
Press.
Temp.
Press.
Tem p.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Dis.
Temp.
135 285 152
137
289 155
139 292 158
141317 162
143341 167
145366 172
147369 175 390 176
149394 180 415 180
151418 185 439 185
308 151
310 156
313 159
330 151
332 155
334 160
338 164
355 155
357 160
359 164
362 168
379 160
381 164
384 168
387 172
404 164
406 168
408 172
412 176
429 168
431 172
433 176
436 181
453 173
455 176
457 180
461 185
153443 189 464 189
155467 194
157
5OUTDOOR TEMPERATURE (°F)
TON707580859095100105
Suct.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Dis.
Liq.
Press.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Tem p.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Dis.
Temp.
129 279 140
281 145
131
133 283 150
135
287 152
137 291 155
139315 160
141340 164
143365 169
145368 173 389 173
147393 177 414 178
149417 182 439 182
304 144
306 149
308 154
312 157
329 148
331 153
333 158
337 161
353 153
356 157
358 162
361 165
378 157
380 161
382 166
386 169
403 161
405 165
407 170
411 174
428 166
430 170
432 174
435 178
453 170
455 174
457 178
460 182
151442 186 463 186
153467 191
155
13
Page 14
WD # 7108260
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
3. Ne convient pas aux installations de plus de 150 V a la terre .
XFMR-R
RELAY
R
BROWN
N.O. N.C.
COM
CONTROL
XFMR-C
BOARD
987
987
WHITE
L
RED
6
6
GREY
YELLOW
BLACK
RED
3
5
4
2
54321
RED
BLUE
WHITE
WHITE
COM
240V
1
RED
L2 L1
T2 T1
CONTACTOR
COMPRESSOR
BLACK
BLACK
C
R
S
OUTDOOR
FAN MOTO R
BLUE
ORANGE
YELLOW
F
H
C
SWITCH
HIGH PRESSURE
YELLOW/BLACK
YELLOW/BLACK
YELLOW
DUAL
CAPACITOR
RED
S
C
COMPRESSOR
BLACK
YELLOW
R
WHITE
C
MOTOR
BLOWER
H
BROWN
CAPACITOR
C
BLACK
SPEEDUP
G
RED
RED
FUSE
3 AMP
2. For supply connections use copper conductors only.
NOTES:
1. Disconnect all power before servicing.
4. For replacement wires use conductors suitable for 105° C.
3. Not suitable on systems that exceed 150 V to ground.
5. See installation instructions for blower motor airflow settings.
Packaged Air Conditioner - Single Phase
14
TRANSFORMER
RED
GREEN
THERMOSTAT
THERMOSTAT
Figure 11. Wiring Diagram
YELLOW
(SELECT MODELS ONLY)
LOW PRESSURE SWITCH
YELLOW
YELLOW
THERMOSTAT
BROWN
ORANGE
LEGEND:
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
Page 15
WD # 7108060
OUTDOOR
S
2. Employez uniquement des conducteurs en cuivre.
1. Couper le courant avant de faire letretien.
3. Ne convient pas aux installations de plus de 150 V a la terre .
BLUE
8
BLACK
6
7
6
GREY
5
543
BLUE
BLACK
RED
432
1
2
1
RED
WHITE
RED
WHITE
COM
240V
TRANSFORMER
L2 L1
T2 T1
CONTACTOR
COMPRESSOR
BLACK
24V
YELLOW
F
H
C
SWITCH
HIGH PRESSURE
YELLOW/BLACK
YELLOW/BLACK
YELLOW
DUAL
CAPACITOR
RED
YELLOW
S
C
COMPRESSOR
BLACK
R
WHITE
987
9
WHITE
GREEN/YELLOW
N
G
L
C
MOTOR
BLOWER
ORANGE
RED
NC
BLACK
COM NO
FAN MOTOR
RED
C
R
ORANGE
LOAD RELAY
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
4. For replacement wires use conductors suitable for 105° C.
3. Not suitable on systems that exceed 150 V to ground.
5. See installation instructions for blower motor airflow settings
Packaged Air Conditioner - Single Phase
Figure 12. Wiring Diagram
3 AMP
GREEN
THERMOSTAT
FUSE
RED
RED
THERMOSTAT
YELLOW
YELLOW
YELLOW
THERMOSTAT
LOW
SWITCH
PRESSURE
MODELS
(SELECT
BROWN
ONLY)
ORANGE
LEGEND:
FIELD WIRING
LOW VOLTAGE
HIGH VOLTAGE
15
Page 16
INSTALLER
PLEASE LEAVE THESE
INSTALLATION INSTRUCTIONS
WITH THE HOMEOWNER.
O'Fallon, MO
¢708901¬¤
7089010
Specifi cations and illustrations subject
7089010
to change without notice and without
incurring obligations.
Printed in U.S.A. (06/08)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.