Nordyne 13 SEER High Effi ciency Split System Installation Manual

Page 1
Outdoor Heat Pump
5
4
1
2
3
6
5
4
3
2
1
6
User’s Information/Installation Instructions
13 SEER High Effi ciency Split System
These units have been designed and tested for capacity and effi ciency in accordance with A.R.I. Standards. Split System Heat Pump units are designed for use with a wide variety of fossil fuel furnaces, electric furnaces, air handlers, and evaporator coil combinations.
These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of heating and/or air conditioning appliances. Some local codes require licensed installation/service personnel for this type of equipment. Read all instructions carefully before starting the installation.
USER’S INFORMATION
IMPORTANT
Read this owner information to become familiar with the capabilities and use of your appliance. Keep this with literature on other appliances where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your servicing contractor.
Heat Pump Principle of Operation
WINTER HEATING
1. Outdoor air enters heat pump.
2. Cold, heat-transfer section (outdoor coil) extracts heat from outdoor air as refrigerant evaporates from a liquid to a gas.
3. Refrigerant, compressed to a hot gas by heat pump, carries the heat to the hot heat­transfer section (indoor coil).
4. Hot, heat-transfer section (indoor coil) releases the heat to indoor air as refrigerant condenses from a gas to a liquid.
5. Air handler circulates the heat throughout the home.
6. Refrigerant returns to outdoor coil and
evaporates once again to absorb more heat.
SUMMER COOLING
1. Indoor air enters the air handler section.
2. Cold, heat-transfer section (indoor coil) extracts heat from indoor air as refrigerant evaporates from a liquid to a cold gas.
3. Refrigerant, drawn to heat pump and compressed to a hot gas by heat pump, carries the heat outdoors.
4. Hot, heat-transfer section (outdoor coil) releases the heat as refrigerant condenses from a gas to a liquid.
5. Heat pump (outdoor fan) discharges the heat to outside air.
6. Refrigerant returns to indoor coil and evaporates once again to absorb more heat.
Page 2
2
Page 3
OPERATING INSTRUCTIONS TO OPERATE YOUR HEAT PUMP
and indoor blower will both cycle on and off to maintain the indoor temperature at the desired heating level.
FOR COOLING —
1. Set the thermostat system switch to COOL and the thermostat fan switch to A UTO . (See
Figure 1)
2. Set the thermostat temperature to the desired temperature level using the temperature selector. Please refer to the separate detailed thermostat user’s manual for complete instructions regarding thermostat programming. The outdoor unit and indoor blower will both cycle on and off to maintain the indoor temperature at the desired cooling level.
NOTE: If the thermostat temperature level is
re-adjusted, or the thermostat system switch is repositioned, the outdoor unit may not start immediately. The outdoor unit contains a protective timer circuit which holds the unit off for approximately fi ve minutes following a previous operation, or the interruption of the main electrical power.
NOTE: If the thermostat temperature lev el is
re-adjusted, or the thermostat system switch is repositioned, the outdoor unit may not start immediately. The outdoor unit contains a protective timer circuit which holds the unit off for approximately fi ve minutes following a previous operation, or the interruption of the main electrical power.
Emergency Heat:
The thermostat includes a system switch
position termed EM. HT. This is a back-up heating mode to be used only if there is a suspected problem with the outdoor unit. With the system switch set to EM. HT . the outdoor unit will be locked off, and supplemental heat (typically electric resistance heating) will be used as a source of heat. Sustained use of electric resistance heat in place of the heat pump will result in an increase in electric utility costs.
Defrost:
TO OPERATE YOUR HEAT PUMP FOR HEATING —
1. Set the thermostat system switch to HEAT
and the thermostat fan switch to A UTO. (See
Figure 1)
2. Set the thermostat temperature to the
desired temperature level using the temperature selector. Please refer to the separate detailed thermostat user’s manual for complete instructions regarding thermostat programming. The outdoor unit
During cold weather heating operation, the
outdoor unit will develop a coating of snow and ice on the heat transfer coil. This is normal, and the unit will periodically defrost itself. During the defrost cycle, the outdoor fan will stop, and the compressor will continue to run and heat the outdoor coil, causing the snow and ice to melt. After the snow and ice have melted, some steam ma y rise from the outdoor unit as the warm coil causes some melted frost to evaporate.
SYSTEM MODE
FAN SWITCH
Figure 1. T ypical Thermostat
TEMPERATU SENSOR
3
Page 4
TO OPERATE YOUR HEAT PUMP FOR AUTOMATIC COOLING AND HEATING—
1. Set the thermostat system switch to AUTO
and the thermostat fan switch to A UTO. (See
Figure 1)
Note: Thermostats will vary. Some models
will not include the AUT O mode , and others will have the A UTO in place of the HEAT and COOL, and some will include all three.
2. Set the thermostat temperature to the
desired heating and cooling temperature level(s). The outdoor unit and the indoor blower will then cycle on and off in either the heating or cooling mode of operation as required to automatically maintain the indoor temperature within the desired limits.
and when an accumulation of dust and dirt is visible on the air fi lter. Inspect the fi lter monthly .
b. Remove any leaves and grass clippings
from the coil in the outdoor unit, being careful not to damage the aluminum fi ns.
c. Check for any obstruction such as twigs,
sticks, etc.
d. Certain models have external panels
fabricated from a premium grade of stainless steel designed to inhibit corrosion. For such units, if the unit is located in a coastal region or other area subjected to high concentrations of salt, then the unit should be hosed off after storms and monthly otherwise to maintain its new appearance.
TO SHUT OFF YOUR HEA T PUMP—
Set the thermostat system switch to OFF and the thermostat fan switch to AUTO. (See Figure 1) The system will not operate, regardless of the thermostat temperature selector(s) setting.
TO OPERATE THE INDOOR BLOWER CONTINUOUSLY—
Set the thermostat fan switch to ON (See Figure
1). The indoor b lower will start immediately , and
will run continually until the fan switch is reset to AUTO.
The continuous indoor blower oper ation can be obtained with the thermostat system switch set in any position, including OFF.
The continuous indoor blower operation is typically used to circulate the indoor air to equalize a temperature unbalance due to a sun load, cooking, or fi replace operation.
TO MAINTAIN YOUR HEAT PUMP—
CAUTION:
Do not over-oil, or oil motors not factory-equipped with oil tubes. The compressor is hermetically “sealed” and does not require lubrication.
2. Before Calling a Service Technician, Be Certain:
a. The unit thermostat is properly set—see
“T o Operate Your Heat Pump for Cooling” and “To Operate Your Heat Pump for Heating.”
b. The unit disconnect fuses are in good
condition, and the electrical power to the unit is turned on.
Read Y our Warranty
Please read the separate warranty document completely. It contains valuable information about your system.
GENERAL INFORMATION
CAUTION:
Be certain the electrical power to the outdoor unit and the furnace/ air handler is disconnected before doing the following recommended maintenance.
1. Regularly:
a. Clean or replace the indoor air fi lter at the
start of each heating and cooling season,
4
Read the following instructions completely before performing the installation.
Outdoor Unit Section — Each outdoor unit is shipped with a refrigerant charge adequate to operate the outdoor section with an indoor matching coil or air handler. Units with braze connections include the proper amount of refrigerant for an additional 15 ft. of refrigerant lines the same size as the valve fi ttings.
Page 5
NOTE: DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING.
Matching coils and air handlers may be shipped with a small holding charge to pressurize them to keep out contaminants. To release the pressure, read the indoor section installation instructions carefully.
Liquid and Suction Lines — Fully annealed, refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
Field Connections for Electrical Power Supply — All wiring must comply with current
provisions of the “National Electrical Code” (ANSI/NFPA 70) and with applicable local codes having jurisdiction. The minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label.
SAFETY CONSIDERATIONS
SITE PREPARATION
Unpacking Equipment — Remove the
cardboard carton and User’s Manual from the equipment. Take care to not damage tubing connections when removing from the carton.
Inspect for Damage — Inspect the equipment for damage prior to installing the equipment at the job site. Ensure coil fi ns are straight and, if necessary, comb fi ns to remove fl attened and bent fi ns.
Preferred Location of the Outdoor Unit at the Job Site — Conduct a survey of the job site to
determine the optimum location for mounting the outdoor unit. Overhead obstructions, poorly ventilated areas, and areas subject to accumulation of debris should be avoided. The outdoor unit should be installed no closer than 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airflow through the outdoor unit.
Pressures within the System — Split system heat pump equipment contains liquid and gaseous refrigerant under pressure. Installation and servicing of this equipment should be accomplished by qualifi ed, trained personnel thoroughly familiar with this type of equipment. Under no circumstances should the Homeowner attempt to install and/or service the equipment.
Labels, Tags, Precautions — When working with this equipment, follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and operational checkout of the equipment.
Brazing Operations — Installation of equipment may require brazing operations. Safety codes must be complied with. Safety equipment (e.g.; safety glasses, work gloves, fi re extinguisher, etc.) must be used when performing brazing operations.
Facility Prerequisites — Electrical power supplied must be adequate for proper operation of the equipment. The system must be wired and provided with circuit protection in accordance with local building codes and the National Electrical Code.
INSTALLING THE OUTDOOR UNIT
Slab Mount — The site selected f or a slab mount
installation requires a stable foundation and one not subject to erosion. The slab should be level and anchored (if necessary) prior to placing the equipment on the slab.
Cantilever Mount — The cantilever mount should be designed with adequate safety factor to support the weight of the equipment, and for loads subjected to the mount during operation. Installed equipment should be adequately secured to the cantilever mount and levelled prior to operation of the equipment.
W ARNING:
Ensure all electrical power to the unit is off prior to installing or servicing the equipment. F ailure to do so may cause personal injury or death.
Roof Mount — The method of mounting should be designed so as not to overload roof structures nor transmit noise to the interior of the structure. Refrigerant and electrical line should be routed through suitably waterproofed openings to prevent water leaking into the structure.
5
Page 6
INSTALLING THE INDOOR UNIT
The indoor section should be installed before proceeding with routing of refrigerant piping. Consult the Installation Instructions of the indoor unit (i.e.: air handler, furnace, etc.) for details regarding installation.
be installed in strict accordance with the manufacturer’s installation instructions.
ELECTRICAL CONNECTIONS
W ARNING:
CONNECTING REFRIGERANT TUBING BETWEEN THE INDOOR AND OUTDOOR UNIT
General — Once outdoor and indoor unit
placement has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices. Refrigerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing. Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation. Tubing should be kept clean of foreign debris during installation and installation of a liquid line fi lter drier is recommended if cleanliness or adequacy of system evacuation is unkno wn or compromised. Every effort should be made by the installer to ensure that the fi eld installed, refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices so as to insure reliable system operation and longevity.
The maximum recommended interconnecting refrigerant line length is 75 feet, and the vertical elevation diff erence between the indoor and outdoor sections should not exceed 20 feet. Consult long line application guide for installations in excess of these limits.
Filter Dryer Installation — A fi lter dryer is provided with PS series models only and must be installed in the liquid line of the system. If the installation replaces a system with a fi lter dryer already present in the liquid line, the fi lter dryer must be replaced with the one supplied with the unit. The fi lter dr yer must be installed in str ict accordance with the manufacturer’ s installation instructions.
For all other series models, installing a fi lter dryer is optional. Ho wev er , it is good installation practice to install a fi lter dryer when replacing the evaporator and/or condenser of a system. When installing, the fi lter dryer must be installed in strict accordance with the manufacturer’s installation instructions.
T urn off all electrical power at the main circuit box before wiring electrical power to the outdoor unit. Failure to comply may cause severe personnel injury or death.
Wiring Diagram/Schematic — A wiring
diagram/schematic is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram/schematic before making any electrical connections to the outdoor unit.
Outdoor Unit Connections — The outdoor unit requires both power and control circuit electrical connections. Refer to the unit wiring diagram/schematic for identifi cation and location of outdoor unit fi eld wiring interfaces.
Control Circuit Wiring — The outdoor unit is designed to operate from a 24 V AC Class II control circuit. Control circuit wiring must comply with the current provisions of the “National Electrical Code” (ANSI/NFP A 70) and with applicable local codes having jurisdiction.
Thermostat connections should be made in accordance with the instructions supplied with the thermostat, and with the instructions supplied with the indoor equipment. A typical residential installation with a heat pump thermostat and air handler are shown below.
Electrical Power Wiring — Electrical power wiring must comply with the current provisions of the “National Electrical Code” (ANSI/ NFPA 70) and with applicable local codes having jurisdiction. Use of rain tight conduit is recommended. Electrical conductors shall ha ve minimum circuit ampacity in compliance with the outdoor unit rating label. The facility shall employ electrical circuit protection at a current rating no greater than that indicated on the outdoor unit rating label. Refer to the unit wiring diagram for connection details.
Minimum Circuit Ampacity — Electrical wiring to the equipment must be compatible and in compliance with the minimum circuit ampacity listed on the outdoor unit data label.
Optional Equipment — Optional equipment (e.g.: liquid line solenoid valves, etc.) should
6
Maximum Fuse/Circuit Breaker Size — Circuit protection for the outdoor unit must be compatible
Page 7
with the maximum fuse/circuit breaker size listed on the outdoor unit data label.
Disconnect Switch — An electrically compatible disconnect switch must be within line of sight of the outdoor unit. This switch shall be capable of electrically de-energizing the outdoor unit.
Optional Equipment — Optional equipment requiring connection to the power or control circuits must be wired in strict accordance with current provisions of the “National Electrical Code” (ANSI/NFPA 70), with applicable local codes having jurisdiction, and the installation instructions provided with the equipment. Optional Equipment (e.g.: liquid line solenoid valves, hard start kits, low suction pressure cutout switch kit, high pressure cutout switch kit, refrigerant compressor crankcase heater, etc.) should be installed in strict accordance with the manufacturer’s installation instructions.
STARTUP AND CHECKOUT
W ARNING:
Ensure electrical power to the unit is off prior to performing the following steps. Failure to do so may cause personal injury or death.
Air Filters — Ensure air fi lters are clean and in
place prior to operating the equipment. Thermostat — Set the room thermostat function
switch to OFF , f an switch to AUT O, and adjust the temperature setpoint to its highest setting.
COPPER WIRE SIZE — AWG
(1% V oltage Drop) Supply Wire Length-Feet Supply Circuit 200 150 100 50 Ampacity
6 8 10 14 15 46812 20 46810 25 44610 30 3468 35 3468 40 2346 45 2346 50
Wire Size based on N.E.C. for 60° type copper conductors.
Prior to applying electrical power to the outdoor unit, ensure that the unit has been properly and securely grounded, and that power supply connections have been made at both the f acility power interface and outdoor unit.
Outdoor Unit — Ensure the outdoor coil and top of the unit are free from obstructions and debris, and all equipment access/control panels are in place.
Using extreme caution, apply power to the unit and inspect the wiring for evidence of open, shorted, and/or improperly wired circuits.
Functional Checkout:
CAUTION:
If equipped with a compressor crankcase heater , wait 24 hours prior to performing a function checkout to allow for heating of the compressor crankcase. Failure to comply may result in damage and could cause
premature failure of the system.
Indoor Blower — Set the thermostat function
switch to COOLING and the fan switch to ON. Verify that the indoor blower is operating and that airfl ow is not restricted. Set the fan switch back to AUTO.
Positive Temperature Coeffi cient Resistor (PTCR) — (select models) A PTCR is factory
installed and located on the control panel of the outdoor unit. The PTCR is a soft start device for use with reciprocating compressors. If a hard start kit is needed on this model the soft star t (PTCR) must be removed fi rst.
Low-Pressure Switch — A low-pressure switch is factory-installed in select models only. If provided, this switch is located in the suction line internal to the outdoor unit. The switch is designed to protect the compressor from a loss of charge. Under nor mal conditions, the switch is closed. If the suction pressure falls below 5 psig, then the switch will open and de-energize the outdoor unit. The switch will close again once the suction pressure increases above 20 psig. Please note that the switch interrupts the thermostat inputs to the unit. Thus, when the switch opens and then closes, there will be a 5 minute short cycling delay before the outdoor unit will energize.
7
Page 8
Green
Thermostat
GRW2CEOY
G
NOTE: Jumper between W2 and E is required when no OD T-Stat is used.
R
C
R
W
OY
2
W
W
2
C
For 2-Stage Heater Kits
Red
Brown
Orange
Black
Air Handler Heat Pump OD
Section
Typical Heat Pump with Standard Air Handler
A typical installation with a heat pump thermostat, air handler, and heat pump with an outdoor thermostat.
Thermostat
GRW2CEOY
Green
Red
White
Black
G
R
W
C
E
R
W
2
O Y
C
Air Handler Heat Pump OD
Section
Typical Heat Pump with
Outdoor Thermostat and Air Handler
8
Page 9
Cooling — Gradually lower the thermostat temperature setpoint below the actual room temperature and observe that the outdoor unit and indoor blower energize. Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature. Listen for any unusual noises. If present, locate and determine the source of the noise and correct as necessary.
Short Cycle Protection — With the system operating in COOLING mode, note the setpoint temperature setting of the thermostat, and gradually raise the setpoint temperature until the outdoor unit and indoor blower de-energize . Immediately lower the setpoint temperature of the thermostat to its original setting and verify that the indoor blower is energized and that the outdoor unit remains de-energized. Verify that, after approximately 5 minutes, the outdoor unit energizes and that the temperature of the air supplied to the facility is cooler than ambient temperature.
Heating — Lower the thermostat setpoint temperature to the lowest obtainable setting and set the thermostat function switch to HEATING. The indoor blower and outdoor unit should stop running. After a minimum of fi ve minutes, increase the setpoint temperature of the thermostat to the maximum setting. V erify that the outdoor unit and indoor blower ha ve energized. Feel the air being circulated by the indoor blower and verify that it is warmer than ambient temperature. Listen for any unusual noises. If present, locate and determine the source of the noise and correct as necessary.
NOTE: Other sources for heating (i.e.: electric furnace, fossil fuel furnace, air handler with electric heat options, etc.) that interface with the unit should be functionally checked to v erify system operation and compatibility . Refer to the installation instructions for this equipment and perform a functional checkout in accordance with the manufacturer’s instructions.
OUTDOOR THERMOSTAT (if supplied)
The outdoor thermostat prevents the electrical auxiliary heat (if used) from operating above 40°F outdoor ambient temperature.
Defrost Cycle Timer — The defrost cycle timer controls the time interval of the hot gas defrost after the defrost sensor closes. It is located in the lower left corner of the defrost control board. Three interval settings are available: 30 minutes, 60 minutes, and 90 minutes. Time setting selection is dependent on the climate where the unit is being installed.
Example 1. Dry climate of Southern Arizona. A 90 minute setting is recommended.
Example 2. Moist climate of Seattle, Washington. A 30 minute setting is recommended.
To set the cycle timer, place the timing pin on the defrost control board to the desired time
interval post. Note: All units are shipped from the factory with
the default time setting of 30 minutes. Maximum heating performance can be achieved b y setting the time to 90 minutes.
DEFROST CONTROL BOARD OPERATION AND TESTING
1. Terminals “R”-”C” must have 24±V present between them in order for the time dela y and defrost sequences to be operational.
2. Jumper the “T2”-”DFT” test pins. This will indicate to the board that the defrost T-stat is closed(if the compressor is running). Defrost T-stat is closed at 32° or below and is open at 68° or above. But it’s state is unknown if the temperature is between 32°F and 68°F. The defrost thermostat tells the board whether a defrost cycle needs to be started or terminated. With the DFT closed the unit will run for 30/60/90 minutes in heat mode and then defrost the outdoor coil. The defrost will turn off the outdoor fan, turn on the compressor and raise the coil temperature to 68°F. This will open the DFT and terminate the defrost. If the DFT does not open the defrost will end after 10 minutes.
3. Defrost board speed-up. With compressor running in heat mode, next jump the “Test” pin to “C” on ter minal strip. This will initiate a defrost test in 5, 10 or 15 seconds (This is determined by the 30, 60 or 90 minute defrost pin settings. The factory setting will be 30 minutes). Note that this will bypass the compressor off delay when the unit goes into defrost test and if left in defrost test, the delay will be bypassed when the test is terminated by the processor. If the jumper is removed before the test is over the processor will perform the remainder of a normal defrost. See step 2 above.
4. Remove the jumpers.
Note: The delay/no-delay pin concerns compressor operation during defrosts. The default setting is delay. Reciprocating compressors
9
Page 10
should only use this setting in conjunction with an approved hard start kit. Scroll compressors that have noise issues while going into or coming out of defrost should use this 30 second delay to reduce the defrost noise. T o switch from no-delay to delay remove the pin from the “no-delay” pin location and shift it to the “delay” pin location.
Optional Equipment — A functional checkout should be performed in accordance with the checkout procedures supplied with the
equipment.
Adjustment of Refrigerant Charge:
Speed up changes:
Manually initiating a defrost will cause the compressor to run continually when entering defrost.
Normal defrost operation:
To test normal defrost operation when the temperature is above 35°F, jumper “R” to “DFT” on the 624656 board and allow the unit to run for 30 minutes. Defrost will continue until the “R” to “DFT” jumper is removed or for 10 minutes. Remove the jumper.
The 5 minute time delay feature can be shortened 1 time to 1 second by jumping the “T est” to “C” terminal. Remove the jumper and repeat as desired.
Note: If jumper is left on the “Test” to “common” pins permanently, the defrost cycle will become inoperable.
Defrost Test Procedure for 624656
1. Jumper “T2” to “DFT” at the test terminals.
2. With unit running in heat mode, shor t the “TEST” terminal to the common terminal near it. This will speed up the board and cause it to enter defrost mode in 5/10/15 seconds depending on the defrost time selection. Compressor delay will not function during speed-up.
3. This test will end in 5 seconds if the “TEST”­common short is not removed.
4. Remov e both the short and the “T2” to “DFT” jumper to terminate the defrost cycle. The 30 second compressor delay should operate normally.
5. Test is complete, reset ther mostat to home owner preference.
CAUTION:
Split system heat pump equipment contains liquid and gaseous refrigerant under pressure. Adjustment of refrigerant charge should only be attempted by qualified, trained personnel thoroughly familiar with the equipment. Under no circumstances should the homeowner attempt to install and/or service this equipment. Failure to comply with this warning could result in equipment damage, personal injury, or death.
NOTE: The following Refrigerant Charging
Charts are applicable to listed assemblies of equipment and at listed airfl ows for the indoor coil. Assemb lies of indoor coils and outdoor units not listed are not recommended and deviations from rated airfl ows or non-listed equipment combinations may require modifi cations to the expansion device(s) and refrigerant charging procedures for proper and effi cient system operation.
Refrigerant Charging Chart — Refer to Refrigerant Charging Charts for correct system charging, and to Orifi ce Usage Chart for correct restrictor sizes.
NOTE: Linesets over 15 feet in length may require additional refrigerant charge. NORDYNE recommends 0.6 oz. of refrigerant per foot for any lineset over 15 feet.
10
Page 11
13 SEER Split System Heat Pump Orifi ce
Model Number
1.5 ton TXV ONLY 0.041 86
2.0 ton TXV ONLY 0.047 109
2.5 ton TXV ONLY 0.053 128
3.0 ton TXV ONLY 0.055 154
3.5 ton TXV ONLY 0.055 189
4.0 ton TXV ONLY 0.065 253
5.0 ton TXV ONLY 0.067 268
Restrictor Bore Size (in)
Indoor Outdoor
System Charge R-22(oz.)
TXV Refrigerant Charging Chart
1.5 Ton HP TXV Charging Chart
350
Remove refrigerent when above curve
325
300
275
250
225
Liquid Pressure (psig)
200
175
Add refrigerent when below curve
150
75 80 85 90 95 100 105 110 115 120 125
Liquid Temperature (F)
2.0 Ton HP Charging Chart
350
Remove refrigerent when above curve
325
300
275
250
225
Liquid Pressure (psig)
200
175
150
75 80 85 90 95 100 105 110 115 120 125
Add refrigerent when below curve
Liquid Temperature (F)
11
Page 12
TXV Refrigerant Charging Chart
2.5 Ton HP TXV Charging Chart
350
Remove refrigerent when above curve
325
300
275
250
225
Liquid Pressure (psig)
200
175
Add refrigerent when below curve
150
75 80 85 90 95 100 105 110 115 120 125
Liquid Temperature (F)
3.0 Ton HP TXV Charging Chart
350
Remove refrigerent when above curve
325
300
275
250
225
Liquid Pressure (psig)
200
175
Add refrigerent when below curve
150
75 80 85 90 95 100 105 110 115 120 125
12
Liquid Temperature (F)
Page 13
TXV Refrigerant Charging Chart
3.5 Ton HP TXV Charging Chart
350
Remove refrigerent when above curve
325
300
275
250
225
Liquid Pressure (psig)
200
175
Add refrigerent when below curve
150
75 80 85 90 95 100 105 110 115 120 125
Liquid Temperature (F)
4.0 Ton HP TXV Charging Chart
350
Remove refrigerent when above curve
325
300
275
250
225
Liquid Pressure (psig)
200
175
Add refrigerent when below curve
150
75 80 85 90 95 100 105 110 115 120 125
Liquid Temperature (F)
13
Page 14
TXV Refrigerant Charging Chart
350
Remove refrigerent when above curve
330
310
290
270
250
230
210
Liquid Temperature (psig)
190
5.0 Ton HP TXV Charging Chart
170
150
75 80 85 90 95 100 105 110 115 120 125 130 135
Add refrigerent when below curve
Liquid Temperature (F)
14
Page 15
OUTDOOR TEMPERATURE (DEG. F)
13 SEER Split System Heating Charts
Refrigerant Charging Charts for Heating Mode of Operation
OUTDOOR TEMPERATURE (DEG. F)
0102030405060
1.5
Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.
TON
Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.
12 116 109 22 134 120 31 152 131 40 170 143 48 174 157 56 188 173 64 203 190
13 123 107 23 140 118 32 157 129 41 174 141 49 181 154 57 195 169 65 210 184
14 130 105 24 146 116 33 162 127 42 177 139 50 188 151 58 202 164 66 217 178
15 137 103 25 152 114 34 166 125 43 181 137 51 195 148 59 209 160 67 224 172
16 144 101 26 158 112 35 171 123 44 185 135 52 202 146 60 216 155 68 231 165
17 151 99 27 164 110 36 176 121 45 188 133 53 209 143 61 223 151 69 238 159
18 158 97 28 170 108 37 181 119 46 192 131 54 216 140 62 230 146 70 245 153
0102030405060
2.0
Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.
TON
Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.
13 121 124 22 138 132 30 154 140 39 171 148 46 175 161 54 188 181 61 201 200
14 128 122 23 143 130 31 159 138 40 175 146 47 182 159 55 195 176 62 208 194
15 135 120 24 149 128 32 164 136 41 179 144 48 189 156 56 202 172 63 215 188
16 142 118 25 155 126 33 169 134 42 182 142 49 196 153 57 209 167 64 222 182
17 149 116 26 161 124 34 174 132 43 186 140 50 203 150 58 216 163 65 229 176
18 156 114 27 167 122 35 178 130 44 190 138 51 210 147 59 223 158 66 236 170
19 163 112 28 173 120 36 183 128 45 193 136 52 217 144 60 230 154 67 243 163
15
Page 16
OUTDOOR TEMPERATURE (DEG. F)
13 SEER Split System Heating Charts
Refrigerant Charging Charts for Heating Mode of Operation
OUTDOOR TEMPERATURE (DEG. F)
0102030405060
2.5
Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.
TON
Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.
16
10 116 100 18 129 113 26 142 126 33 155 140 42 157 153 50 170 166 58 184 178
11 123 98 19 135 111 27 147 124 34 159 138 43 164 150 51 177 161 59 191 172
12 130 96 20 141 109 28 152 122 35 163 136 44 171 147 52 184 157 60 198 166
13 137 94 21 147 107 29 157 120 36 166 134 45 178 144 53 191 152 61 205 160
14 144 92 22 153 105 30 161 118 37 170 132 46 185 141 54 198 148 62 212 154
15 151 90 23 159 103 31 166 116 38 174 130 47 192 139 55 205 143 63 219 148
16 158 88 24 165 101 32 171 114 39 177 128 48 199 136 56 212 139 64 226 141
0102030405060
3.0
Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.
TON
Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.
14 120 96 21 137 109 28 154 121 35 171 133 44 179 152 55 202 176 65 224 201
15 127 94 22 143 107 29 159 119 36 175 131 45 186 149 56 209 172 66 231 195
16 134 92 23 149 105 30 164 117 37 178 129 46 193 146 57 216 167 67 238 189
17 141 90 24 155 103 31 169 115 38 182 127 47 200 143 58 223 163 68 245 183
18 148 88 25 161 101 32 173 113 39 186 125 48 207 140 59 230 158 69 252 177
19 155 86 26 167 99 33 178 111 40 190 123 49 214 137 60 237 154 70 259 171
20 162 84 27 173 97 34 183 109 41 193 121 50 221 135 61 244 149 71 266 164
Page 17
OUTDOOR TEMPERATURE (DEG. F)
13 SEER Split System Heating Charts
Refrigerant Charging Charts for Heating Mode of Operation
OUTDOOR TEMPERATURE (DEG. F)
0102030405060
3.5
Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.
TON
Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.
14 120 101 21 136 113 28 152 124 36 168 135 44 176 156 55 198 188 65 220 220
15 127 99 22 142 111 29 157 122 37 172 133 45 183 154 56 205 184 66 227 214
16 134 97 23 148 109 30 162 120 38 176 131 46 190 151 57 212 179 67 234 208
17 141 95 24 154 107 31 167 118 39 179 129 47 197 148 58 219 175 68 241 202
18 148 93 25 160 105 32 171 116 40 183 127 48 204 145 59 226 170 69 248 196
19 155 91 26 166 103 33 176 114 41 187 125 49 211 142 60 233 166 70 255 190
20 162 89 27 171 101 34 181 112 42 190 123 50 218 139 61 240 161 71 262 184
0102030405060
4.0
Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.
TON
Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.
12 109 77 21 134 95 30 159 113 38 184 131 47 198 153 56 224 180 65 250 208
13 116 75 22 140 93 31 164 111 39 188 129 48 205 150 57 231 176 66 257 202
14 123 73 23 146 91 32 169 109 40 191 127 49 212 148 58 238 171 67 264 195
15 130 71 24 152 89 33 173 107 41 195 125 50 219 145 59 245 167 68 271 189
16 137 69 25 158 87 34 178 105 42 199 123 51 226 142 60 252 162 69 278 183
17 144 67 26 163 85 35 183 103 43 202 121 52 233 139 61 259 158 70 285 177
18 151 65 27 169 83 36 188 101 44 206 119 53 240 136 62 266 153 71 292 171
17
Page 18
OUTDOOR TEMPERATURE (DEG. F)
13 SEER Split System Heating Charts
Refrigerant Charging Charts for Heating Mode of Operation
0102030405060
5
Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch. Suc. Liquid Disch.
TON
Press Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp. Press. Press. Temp.
18
13 121 124 20 142 132 27 164 140 34 185 148 43 201 166 54 233 193 66 266 219
14 128 122 21 148 130 28 169 138 35 189 146 44 208 163 55 240 188 67 273 213
15 135 120 22 154 128 29 173 136 36 193 144 45 215 160 56 247 184 68 280 207
16 142 118 23 160 126 30 178 134 37 196 142 46 222 157 57 254 179 69 287 201
17 149 116 24 166 124 31 183 132 38 200 140 47 229 154 58 261 175 70 294 195
18 156 114 25 172 122 32 188 130 39 204 138 48 236 151 59 268 170 71 301 189
19 163 112 26 178 120 33 193 128 40 207 136 49 243 149 60 275 166 72 308 183
Page 19
19
Page 20
INSTALLER: PLEASE LEAVE
THESE INSTALLATION INSTRUCTIONS
WITH THE HOMEOWNER.
¢708764F¤
708764A
Specifi cations and illustrations subject to change
708764A (Replaces 7087640)
without notice and without incurring obligations.
Printed in U.S.A. (08/08)
Loading...