These units have been designed and tested for capacity and effi ciency in accordance with A.R.I.
Standards. Split System Heat Pump units are designed for use with a wide variety of fossil fuel
furnaces, electric furnaces, air handlers, and evaporator coil combinations.
These instructions are primarily intended to assist qualifi ed individuals experienced in the proper
installation of heating and/or air conditioning appliances. Some local codes require licensed
installation/service personnel for this type of equipment. Read all instructions carefully before
starting the installation.
USER’S INFORMATION
IMPORTANT
Read this owner information to become familiar with the capabilities and use of your appliance.
Keep this with literature on other appliances where you have easy access to it in the future. If a
problem occurs, check the instructions and follow recommendations given. If these suggestions
don’t eliminate your problem, call your servicing contractor.
Heat Pump Principle of Operation
WINTER HEATING
1. Outdoor air enters heat pump.
2. Cold, heat-transfer section (outdoor coil)
extracts heat from outdoor air as refrigerant
evaporates from a liquid to a gas.
3. Refrigerant, compressed to a hot gas by
heat pump, carries the heat to the hot heattransfer section (indoor coil).
4. Hot, heat-transfer section (indoor coil)
releases the heat to indoor air as refrigerant
condenses from a gas to a liquid.
5. Air handler circulates the heat throughout
the home.
6. Refrigerant returns to outdoor coil and
evaporates once again to absorb more
heat.
SUMMER COOLING
1. Indoor air enters the air handler section.
2. Cold, heat-transfer section (indoor coil)
extracts heat from indoor air as refrigerant
evaporates from a liquid to a cold gas.
3. Refrigerant, drawn to heat pump and
compressed to a hot gas by heat pump,
carries the heat outdoors.
4. Hot, heat-transfer section (outdoor coil)
releases the heat as refrigerant condenses
from a gas to a liquid.
5. Heat pump (outdoor fan) discharges the
heat to outside air.
6. Refrigerant returns to indoor coil and
evaporates once again to absorb more
heat.
Page 2
2
Page 3
OPERATING INSTRUCTIONS
TO OPERATE YOUR HEAT PUMP
and indoor blower will both cycle on and off
to maintain the indoor temperature at the
desired heating level.
FOR COOLING —
1. Set the thermostat system switch to COOL
and the thermostat fan switch to A UTO . (See
Figure 1)
2. Set the thermostat temperature to the desired
temperature level using the temperature
selector. Please refer to the separate
detailed thermostat user’s manual for
complete instructions regarding thermostat
programming. The outdoor unit and indoor
blower will both cycle on and off to maintain
the indoor temperature at the desired cooling
level.
NOTE: If the thermostat temperature level is
re-adjusted, or the thermostat system switch
is repositioned, the outdoor unit may not
start immediately. The outdoor unit contains
a protective timer circuit which holds the unit
off for approximately fi ve minutes following a
previous operation, or the interruption of the
main electrical power.
NOTE: If the thermostat temperature lev el is
re-adjusted, or the thermostat system switch
is repositioned, the outdoor unit may not
start immediately. The outdoor unit contains
a protective timer circuit which holds the unit
off for approximately fi ve minutes following
a previous operation, or the interruption of
the main electrical power.
Emergency Heat:
The thermostat includes a system switch
position termed EM. HT. This is a back-up
heating mode to be used only if there is a
suspected problem with the outdoor unit. With
the system switch set to EM. HT . the outdoor
unit will be locked off, and supplemental heat
(typically electric resistance heating) will be
used as a source of heat. Sustained use of
electric resistance heat in place of the heat
pump will result in an increase in electric
utility costs.
Defrost:
TO OPERATE YOUR HEAT PUMP
FOR HEATING —
1. Set the thermostat system switch to HEAT
and the thermostat fan switch to A UTO. (See
Figure 1)
2. Set the thermostat temperature to the
desired temperature level using the
temperature selector. Please refer to
the separate detailed thermostat user’s
manual for complete instructions regarding
thermostat programming. The outdoor unit
During cold weather heating operation, the
outdoor unit will develop a coating of snow
and ice on the heat transfer coil. This is
normal, and the unit will periodically defrost
itself. During the defrost cycle, the outdoor fan
will stop, and the compressor will continue
to run and heat the outdoor coil, causing the
snow and ice to melt. After the snow and ice
have melted, some steam ma y rise from the
outdoor unit as the warm coil causes some
melted frost to evaporate.
SYSTEM
MODE
FAN
SWITCH
Figure 1. T ypical Thermostat
TEMPERATU
SENSOR
3
Page 4
TO OPERATE YOUR HEAT PUMP
FOR AUTOMATIC COOLING AND
HEATING—
1. Set the thermostat system switch to AUTO
and the thermostat fan switch to A UTO. (See
Figure 1)
Note: Thermostats will vary. Some models
will not include the AUT O mode , and others
will have the A UTO in place of the HEAT and
COOL, and some will include all three.
2. Set the thermostat temperature to the
desired heating and cooling temperature
level(s). The outdoor unit and the indoor
blower will then cycle on and off in either
the heating or cooling mode of operation as
required to automatically maintain the indoor
temperature within the desired limits.
and when an accumulation of dust and
dirt is visible on the air fi lter. Inspect the
fi lter monthly .
b. Remove any leaves and grass clippings
from the coil in the outdoor unit, being
careful not to damage the aluminum fi ns.
c. Check for any obstruction such as twigs,
sticks, etc.
d. Certain models have external panels
fabricated from a premium grade of
stainless steel designed to inhibit
corrosion. For such units, if the unit is
located in a coastal region or other area
subjected to high concentrations of salt,
then the unit should be hosed off after
storms and monthly otherwise to maintain
its new appearance.
TO SHUT OFF YOUR HEA T PUMP—
Set the thermostat system switch to OFF and the
thermostat fan switch to AUTO. (See Figure 1)
The system will not operate, regardless of the
thermostat temperature selector(s) setting.
TO OPERATE THE INDOOR
BLOWER CONTINUOUSLY—
Set the thermostat fan switch to ON (See Figure
1). The indoor b lower will start immediately , and
will run continually until the fan switch is reset
to AUTO.
The continuous indoor blower oper ation can be
obtained with the thermostat system switch set
in any position, including OFF.
The continuous indoor blower operation is
typically used to circulate the indoor air to
equalize a temperature unbalance due to a sun
load, cooking, or fi replace operation.
TO MAINTAIN YOUR HEAT PUMP—
CAUTION:
Do not over-oil, or oil motors not
factory-equipped with oil tubes. The
compressor is hermetically “sealed”
and does not require lubrication.
2. Before Calling a Service Technician, Be
Certain:
a. The unit thermostat is properly set—see
“T o Operate Your Heat Pump for Cooling”
and “To Operate Your Heat Pump for
Heating.”
b. The unit disconnect fuses are in good
condition, and the electrical power to the
unit is turned on.
Read Y our Warranty
Please read the separate warranty document
completely. It contains valuable information
about your system.
GENERAL INFORMATION
CAUTION:
Be certain the electrical power to
the outdoor unit and the furnace/
air handler is disconnected before
doing the following recommended
maintenance.
1. Regularly:
a. Clean or replace the indoor air fi lter at the
start of each heating and cooling season,
4
Read the following instructions completely before
performing the installation.
Outdoor Unit Section — Each outdoor unit
is shipped with a refrigerant charge adequate
to operate the outdoor section with an indoor
matching coil or air handler. Units with braze
connections include the proper amount of
refrigerant for an additional 15 ft. of refrigerant
lines the same size as the valve fi ttings.
Page 5
NOTE: DO NOT USE ANY PORTION OF
THE CHARGE FOR PURGING OR LEAK
TESTING.
Matching coils and air handlers may be shipped
with a small holding charge to pressurize them to
keep out contaminants. To release the pressure,
read the indoor section installation instructions
carefully.
Liquid and Suction Lines — Fully annealed,
refrigerant grade copper tubing should be used
when installing the system. Refrigerant suction
line tubing should be fully insulated.
Field Connections for Electrical Power
Supply — All wiring must comply with current
provisions of the “National Electrical Code”
(ANSI/NFPA 70) and with applicable local
codes having jurisdiction. The minimum size of
electrical conductors and circuit protection must
be in compliance with information listed on the
outdoor unit data label.
SAFETY CONSIDERATIONS
SITE PREPARATION
Unpacking Equipment — Remove the
cardboard carton and User’s Manual from the
equipment. Take care to not damage tubing
connections when removing from the carton.
Inspect for Damage — Inspect the equipment
for damage prior to installing the equipment at
the job site. Ensure coil fi ns are straight and, if
necessary, comb fi ns to remove fl attened and
bent fi ns.
Preferred Location of the Outdoor Unit at the
Job Site — Conduct a survey of the job site to
determine the optimum location for mounting
the outdoor unit. Overhead obstructions,
poorly ventilated areas, and areas subject to
accumulation of debris should be avoided. The
outdoor unit should be installed no closer than
18 inches from the outside walls of the facility
and in an area free from overhead obstructions
to ensure unrestricted airflow through the
outdoor unit.
Pressures within the System — Split
system heat pump equipment contains liquid
and gaseous refrigerant under pressure.
Installation and servicing of this equipment
should be accomplished by qualifi ed, trained
personnel thoroughly familiar with this type of
equipment. Under no circumstances should the
Homeowner attempt to install and/or service
the equipment.
Labels, Tags, Precautions — When working
with this equipment, follow all precautions in the
literature, on tags, and on labels provided with
the equipment. Read and thoroughly understand
the instructions provided with the equipment prior
to performing the installation and operational
checkout of the equipment.
Brazing Operations — Installation of equipment
may require brazing operations. Safety codes
must be complied with. Safety equipment (e.g.;
safety glasses, work gloves, fi re extinguisher,
etc.) must be used when performing brazing
operations.
Facility Prerequisites — Electrical power
supplied must be adequate for proper operation
of the equipment. The system must be wired and
provided with circuit protection in accordance
with local building codes and the National
Electrical Code.
INSTALLING THE OUTDOOR UNIT
Slab Mount — The site selected f or a slab mount
installation requires a stable foundation and one
not subject to erosion. The slab should be level
and anchored (if necessary) prior to placing the
equipment on the slab.
Cantilever Mount — The cantilever mount
should be designed with adequate safety factor
to support the weight of the equipment, and for
loads subjected to the mount during operation.
Installed equipment should be adequately
secured to the cantilever mount and levelled
prior to operation of the equipment.
W ARNING:
Ensure all electrical power to the unit
is off prior to installing or servicing the
equipment. F ailure to do so may cause
personal injury or death.
Roof Mount — The method of mounting should
be designed so as not to overload roof structures
nor transmit noise to the interior of the structure.
Refrigerant and electrical line should be routed
through suitably waterproofed openings to
prevent water leaking into the structure.
5
Page 6
INSTALLING THE INDOOR UNIT
The indoor section should be installed before
proceeding with routing of refrigerant piping.
Consult the Installation Instructions of the indoor
unit (i.e.: air handler, furnace, etc.) for details
regarding installation.
be installed in strict accordance with the
manufacturer’s installation instructions.
ELECTRICAL CONNECTIONS
W ARNING:
CONNECTING REFRIGERANT
TUBING BETWEEN THE INDOOR
AND OUTDOOR UNIT
General — Once outdoor and indoor unit
placement has been determined, route refrigerant
tubing between the equipment in accordance with
sound installation practices. Refrigerant tubing
should be routed in a manner that minimizes the
length of tubing and the number of bends in the
tubing. Refrigerant tubing should be supported
in a manner that the tubing will not vibrate or
abrade during system operation. Tubing should
be kept clean of foreign debris during installation
and installation of a liquid line fi lter drier is
recommended if cleanliness or adequacy of
system evacuation is unkno wn or compromised.
Every effort should be made by the installer
to ensure that the fi eld installed, refrigerant
containing components of the system have been
installed in accordance with these instructions
and sound installation practices so as to insure
reliable system operation and longevity.
The maximum recommended interconnecting
refrigerant line length is 75 feet, and the
vertical elevation diff erence between the indoor
and outdoor sections should not exceed 20
feet. Consult long line application guide for
installations in excess of these limits.
Filter Dryer Installation — A fi lter dryer is
provided with PS series models only and must
be installed in the liquid line of the system. If the
installation replaces a system with a fi lter dryer
already present in the liquid line, the fi lter dryer
must be replaced with the one supplied with the
unit. The fi lter dr yer must be installed in str ict
accordance with the manufacturer’ s installation
instructions.
For all other series models, installing a fi lter
dryer is optional. Ho wev er , it is good installation
practice to install a fi lter dryer when replacing
the evaporator and/or condenser of a system.
When installing, the fi lter dryer must be installed
in strict accordance with the manufacturer’s
installation instructions.
T urn off all electrical power at the main
circuit box before wiring electrical
power to the outdoor unit. Failure to
comply may cause severe personnel
injury or death.
Wiring Diagram/Schematic — A wiring
diagram/schematic is located on the inside cover
of the electrical box of the outdoor unit. The
installer should become familiar with the wiring
diagram/schematic before making any electrical
connections to the outdoor unit.
Outdoor Unit Connections — The outdoor
unit requires both power and control circuit
electrical connections. Refer to the unit wiring
diagram/schematic for identifi cation and location
of outdoor unit fi eld wiring interfaces.
Control Circuit Wiring — The outdoor unit is
designed to operate from a 24 V AC Class II control
circuit. Control circuit wiring must comply with
the current provisions of the “National Electrical
Code” (ANSI/NFP A 70) and with applicable local
codes having jurisdiction.
Thermostat connections should be made in
accordance with the instructions supplied with
the thermostat, and with the instructions supplied
with the indoor equipment. A typical residential
installation with a heat pump thermostat and air
handler are shown below.
Electrical Power Wiring — Electrical power
wiring must comply with the current provisions
of the “National Electrical Code” (ANSI/
NFPA 70) and with applicable local codes
having jurisdiction. Use of rain tight conduit is
recommended. Electrical conductors shall ha ve
minimum circuit ampacity in compliance with the
outdoor unit rating label. The facility shall employ
electrical circuit protection at a current rating no
greater than that indicated on the outdoor unit
rating label. Refer to the unit wiring diagram for
connection details.
Minimum Circuit Ampacity — Electrical wiring
to the equipment must be compatible and in
compliance with the minimum circuit ampacity
listed on the outdoor unit data label.
Optional Equipment — Optional equipment
(e.g.: liquid line solenoid valves, etc.) should
6
Maximum Fuse/Circuit Breaker Size — Circuit
protection for the outdoor unit must be compatible
Page 7
with the maximum fuse/circuit breaker size listed
on the outdoor unit data label.
Disconnect Switch — An electrically compatible
disconnect switch must be within line of sight of
the outdoor unit. This switch shall be capable of
electrically de-energizing the outdoor unit.
Optional Equipment — Optional equipment
requiring connection to the power or control
circuits must be wired in strict accordance with
current provisions of the “National Electrical
Code” (ANSI/NFPA 70), with applicable local
codes having jurisdiction, and the installation
instructions provided with the equipment.
Optional Equipment (e.g.: liquid line solenoid
valves, hard start kits, low suction pressure
cutout switch kit, high pressure cutout switch kit,
refrigerant compressor crankcase heater, etc.)
should be installed in strict accordance with the
manufacturer’s installation instructions.
STARTUP AND CHECKOUT
W ARNING:
Ensure electrical power to the unit is
off prior to performing the following
steps. Failure to do so may cause
personal injury or death.
Air Filters — Ensure air fi lters are clean and in
place prior to operating the equipment.
Thermostat — Set the room thermostat function
switch to OFF , f an switch to AUT O, and adjust the
temperature setpoint to its highest setting.
COPPER WIRE SIZE — AWG
(1% V oltage Drop)
Supply Wire Length-FeetSupply Circuit
20015010050Ampacity
Wire Size based on N.E.C. for 60° type copper
conductors.
Prior to applying electrical power to the outdoor
unit, ensure that the unit has been properly and
securely grounded, and that power supply
connections have been made at both the f acility
power interface and outdoor unit.
Outdoor Unit — Ensure the outdoor coil and
top of the unit are free from obstructions and
debris, and all equipment access/control panels
are in place.
Using extreme caution, apply power to the unit
and inspect the wiring for evidence of open,
shorted, and/or improperly wired circuits.
Functional Checkout:
CAUTION:
If equipped with a compressor
crankcase heater , wait 24 hours prior
to performing a function checkout to
allow for heating of the compressor
crankcase. Failure to comply may
result in damage and could cause
premature failure of the system.
Indoor Blower — Set the thermostat function
switch to COOLING and the fan switch to ON.
Verify that the indoor blower is operating and
that airfl ow is not restricted. Set the fan switch
back to AUTO.
Positive Temperature Coeffi cient Resistor
(PTCR) — (select models) A PTCR is factory
installed and located on the control panel of the
outdoor unit. The PTCR is a soft start device for
use with reciprocating compressors. If a hard
start kit is needed on this model the soft star t
(PTCR) must be removed fi rst.
Low-Pressure Switch — A low-pressure
switch is factory-installed in select models only.
If provided, this switch is located in the suction
line internal to the outdoor unit. The switch is
designed to protect the compressor from a loss
of charge. Under nor mal conditions, the switch
is closed. If the suction pressure falls below 5
psig, then the switch will open and de-energize
the outdoor unit. The switch will close again
once the suction pressure increases above 20
psig. Please note that the switch interrupts the
thermostat inputs to the unit. Thus, when the
switch opens and then closes, there will be a 5
minute short cycling delay before the outdoor
unit will energize.
7
Page 8
Green
Thermostat
GRW2CEOY
G
NOTE: Jumper
between W2 and E is
required when no OD
T-Stat is used.
R
C
R
W
OY
2
W
W
2
C
For 2-Stage
Heater
Kits
Red
Brown
Orange
Black
Air HandlerHeat Pump OD
Section
Typical Heat Pump with Standard Air Handler
A typical installation with a heat pump thermostat, air handler, and heat pump with an outdoor
thermostat.
Thermostat
GRW2CEOY
Green
Red
White
Black
G
R
W
C
E
R
W
2
O Y
C
Air HandlerHeat Pump OD
Section
Typical Heat Pump with
Outdoor Thermostat and Air Handler
8
Page 9
Cooling — Gradually lower the thermostat
temperature setpoint below the actual room
temperature and observe that the outdoor unit
and indoor blower energize. Feel the air being
circulated by the indoor blower and verify that
it is cooler than ambient temperature. Listen
for any unusual noises. If present, locate and
determine the source of the noise and correct
as necessary.
Short Cycle Protection — With the system
operating in COOLING mode, note the setpoint
temperature setting of the thermostat, and
gradually raise the setpoint temperature until
the outdoor unit and indoor blower de-energize .
Immediately lower the setpoint temperature of
the thermostat to its original setting and verify
that the indoor blower is energized and that the
outdoor unit remains de-energized. Verify that,
after approximately 5 minutes, the outdoor unit
energizes and that the temperature of the air
supplied to the facility is cooler than ambient
temperature.
Heating — Lower the thermostat setpoint
temperature to the lowest obtainable setting and
set the thermostat function switch to HEATING.
The indoor blower and outdoor unit should stop
running. After a minimum of fi ve minutes, increase
the setpoint temperature of the thermostat to the
maximum setting. V erify that the outdoor unit and
indoor blower ha ve energized. Feel the air being
circulated by the indoor blower and verify that
it is warmer than ambient temperature. Listen
for any unusual noises. If present, locate and
determine the source of the noise and correct
as necessary.
NOTE: Other sources for heating (i.e.: electric
furnace, fossil fuel furnace, air handler with
electric heat options, etc.) that interface with
the unit should be functionally checked to v erify
system operation and compatibility . Refer to the
installation instructions for this equipment and
perform a functional checkout in accordance with
the manufacturer’s instructions.
OUTDOOR THERMOSTAT (if supplied)
The outdoor thermostat prevents the electrical
auxiliary heat (if used) from operating above
40°F outdoor ambient temperature.
Defrost Cycle Timer — The defrost cycle timer
controls the time interval of the hot gas defrost
after the defrost sensor closes. It is located
in the lower left corner of the defrost control
board. Three interval settings are available: 30
minutes, 60 minutes, and 90 minutes. Time setting
selection is dependent on the climate where the
unit is being installed.
Example 1. Dry climate of Southern
Arizona. A 90 minute setting is
recommended.
Example 2. Moist climate of Seattle,
Washington. A 30 minute setting is
recommended.
To set the cycle timer, place the timing pin on
the defrost control board to the desired time
interval post.
Note: All units are shipped from the factory with
the default time setting of 30 minutes. Maximum
heating performance can be achieved b y setting
the time to 90 minutes.
DEFROST CONTROL BOARD OPERATION
AND TESTING
1. Terminals “R”-”C” must have 24±V present
between them in order for the time dela y and
defrost sequences to be operational.
2. Jumper the “T2”-”DFT” test pins. This will
indicate to the board that the defrost T-stat
is closed(if the compressor is running).
Defrost T-stat is closed at 32° or below and
is open at 68° or above. But it’s state is
unknown if the temperature is between 32°F
and 68°F. The defrost thermostat tells the
board whether a defrost cycle needs to be
started or terminated. With the DFT closed
the unit will run for 30/60/90 minutes in heat
mode and then defrost the outdoor coil. The
defrost will turn off the outdoor fan, turn on the
compressor and raise the coil temperature to
68°F. This will open the DFT and terminate
the defrost. If the DFT does not open the
defrost will end after 10 minutes.
3. Defrost board speed-up. With compressor
running in heat mode, next jump the “Test”
pin to “C” on ter minal strip. This will initiate
a defrost test in 5, 10 or 15 seconds (This
is determined by the 30, 60 or 90 minute
defrost pin settings. The factory setting will
be 30 minutes). Note that this will bypass the
compressor off delay when the unit goes into
defrost test and if left in defrost test, the delay
will be bypassed when the test is terminated
by the processor. If the jumper is removed
before the test is over the processor will
perform the remainder of a normal defrost.
See step 2 above.
4. Remove the jumpers.
Note: The delay/no-delay pin concerns
compressor operation during defrosts. The default
setting is delay. Reciprocating compressors
9
Page 10
should only use this setting in conjunction with
an approved hard start kit. Scroll compressors
that have noise issues while going into or coming
out of defrost should use this 30 second delay to
reduce the defrost noise. T o switch from no-delay
to delay remove the pin from the “no-delay” pin
location and shift it to the “delay” pin location.
Optional Equipment — A functional checkout
should be performed in accordance with
the checkout procedures supplied with the
equipment.
Adjustment of Refrigerant Charge:
Speed up changes:
Manually initiating a defrost will cause the
compressor to run continually when entering
defrost.
Normal defrost operation:
To test normal defrost operation when the
temperature is above 35°F, jumper “R” to
“DFT” on the 624656 board and allow the unit
to run for 30 minutes. Defrost will continue
until the “R” to “DFT” jumper is removed or
for 10 minutes. Remove the jumper.
The 5 minute time delay feature can be shortened 1
time to 1 second by jumping the “T est” to “C” terminal.
Remove the jumper and repeat as desired.
Note: If jumper is left on the “Test” to “common”
pins permanently, the defrost cycle will become
inoperable.
Defrost Test Procedure for 624656
1. Jumper “T2” to “DFT” at the test terminals.
2. With unit running in heat mode, shor t the
“TEST” terminal to the common terminal near
it. This will speed up the board and cause
it to enter defrost mode in 5/10/15 seconds
depending on the defrost time selection.
Compressor delay will not function during
speed-up.
3. This test will end in 5 seconds if the “TEST”common short is not removed.
4. Remov e both the short and the “T2” to “DFT”
jumper to terminate the defrost cycle. The
30 second compressor delay should operate
normally.
5. Test is complete, reset ther mostat to home
owner preference.
CAUTION:
Split system heat pump equipment
contains liquid and gaseous refrigerant
under pressure. Adjustment of
refrigerant charge should only be
attempted by qualified, trained
personnel thoroughly familiar with the
equipment. Under no circumstances
should the homeowner attempt to
install and/or service this equipment.
Failure to comply with this warning
could result in equipment damage,
personal injury, or death.
NOTE: The following Refrigerant Charging
Charts are applicable to listed assemblies of
equipment and at listed airfl ows for the indoor
coil. Assemb lies of indoor coils and outdoor units
not listed are not recommended and deviations
from rated airfl ows or non-listed equipment
combinations may require modifi cations to the
expansion device(s) and refrigerant charging
procedures for proper and effi cient system
operation.
Refrigerant Charging Chart — Refer to
Refrigerant Charging Charts for correct system
charging, and to Orifi ce Usage Chart for correct
restrictor sizes.
NOTE: Linesets over 15 feet in length may
require additional refrigerant charge. NORDYNE
recommends 0.6 oz. of refrigerant per foot for
any lineset over 15 feet.
10
Page 11
13 SEER Split System Heat Pump Orifi ce
Model Number
1.5 tonTXV ONLY0.04186
2.0 tonTXV ONLY0.047109
2.5 tonTXV ONLY0.053128
3.0 tonTXV ONLY0.055154
3.5 tonTXV ONLY0.055189
4.0 tonTXV ONLY0.065253
5.0 tonTXV ONLY0.067268
Restrictor Bore Size (in)
IndoorOutdoor
System Charge R-22(oz.)
TXV Refrigerant Charging Chart
1.5 Ton HP TXV Charging Chart
350
Remove refrigerent when above curve
325
300
275
250
225
Liquid Pressure (psig)
200
175
Add refrigerent when below curve
150
7580859095100105110115120125
Liquid Temperature (F)
2.0 Ton HP Charging Chart
350
Remove refrigerent when above curve
325
300
275
250
225
Liquid Pressure (psig)
200
175
150
7580859095100105110115120125
Add refrigerent when below curve
Liquid Temperature (F)
11
Page 12
TXV Refrigerant Charging Chart
2.5 Ton HP TXV Charging Chart
350
Remove refrigerent when above curve
325
300
275
250
225
Liquid Pressure (psig)
200
175
Add refrigerent when below curve
150
7580859095100105110115120125
Liquid Temperature (F)
3.0 Ton HP TXV Charging Chart
350
Remove refrigerent when above curve
325
300
275
250
225
Liquid Pressure (psig)
200
175
Add refrigerent when below curve
150
7580859095100105110115120125
12
Liquid Temperature (F)
Page 13
TXV Refrigerant Charging Chart
3.5 Ton HP TXV Charging Chart
350
Remove refrigerent when above curve
325
300
275
250
225
Liquid Pressure (psig)
200
175
Add refrigerent when below curve
150
7580859095100105110115120125
Liquid Temperature (F)
4.0 Ton HP TXV Charging Chart
350
Remove refrigerent when above curve
325
300
275
250
225
Liquid Pressure (psig)
200
175
Add refrigerent when below curve
150
7580859095100105110115120125
Liquid Temperature (F)
13
Page 14
TXV Refrigerant Charging Chart
350
Remove refrigerent when above curve
330
310
290
270
250
230
210
Liquid Temperature (psig)
190
5.0 Ton HP TXV Charging Chart
170
150
7580859095100105110115120125130135
Add refrigerent when below curve
Liquid Temperature (F)
14
Page 15
OUTDOOR TEMPERATURE (DEG. F)
13 SEER Split System Heating Charts
Refrigerant Charging Charts for Heating Mode of Operation