Nordyne 13+ SEER Extra High Effi ciency Split System User And Installation Manual

Page 1
Outdoor Air Conditioner
User’s Information and Installation Instructions
13+ SEER Extra High Effi ciency Split System
These units have been designed and tested f or capacity and effi ciency in accordance with A.R.I. Standards. Split System Air Conditioning units are designed for use with a wide variety of f ossil fuel furnaces, electric furnaces, air handlers, and evaporator coil combinations.
These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of heating and/or air condi­tioning appliances. Some local codes require licensed installation/service personnel for this type of equipment. Read all instructions carefully before starting the installation.
USER’S INFORMATION
IMPORTANT
Read this owner information to become familiar with the capabilities and use of your appliance. Keep this with literature on other appliances where you have easy access to it in the future.
If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your servicing contractor.
OPERATING INSTRUCTIONS T o Operate Your Air Conditioner for
Cooling —
1. Set the thermostat system switch to COOL or AUTO and the thermostat fan switch to AUTO. (See Figure 1)
2. Set the thermostat temperature to the desired temperature level using the temperature selector. Please refer to the separate thermostat user’s manual for complete instructions regarding ther­mostat programming. The outdoor unit and indoor blower will both cycle on and off to maintain the indoor temperature at the desired cooling level.
SYSTEM SWITCH
FAN SWITCH
TEMPERATURE SCALES
Figure 1. Typical Thermostat
TEMPERATURE SELECTOR
Page 2
To Operate Your Furnace for Heating —
1. Set the thermostat system switch to HEAT or AUT O and the thermostat f an s witch to AUTO. (See Figure 1)
1. Regularly:
a. Clean or replace the indoor air fi lter at the
start of each heating and cooling season, and when an accumulation of dust and dirt is visible on the air fi lter.
2. Set the thermostat temperature to the desired temperature level using the temperature selector. Please refer to the separate user’s manual for complete thermostat programming instructions. The furnace and indoor blower will cycle on and off to maintain the indoor temperature at the desired heating level.
T o Shut Off Y our Air Conditioner —
Set the thermostat system switch to OFF and the thermostat fan switch to AUTO. (See Figure 1)
The system will not operate, regardless of the thermostat temperature setting.
To Operate the Indoor Blower Continuously —
Set the thermostat fan switch to ON (See Figure 1)
b. Remove any leaves and grass clippings
from the coil in the outdoor unit, being careful not to damage the aluminum fi ns.
c. Check for any obstruction, such as twigs,
sticks, etc.
d. Certain models have external panels
fabricated from a premium grade of stainless steel designed to inhibit cor­rosion. For such units, if the unit is located in a coastal region or other area subjected to high concentrations of salt, then the unit should be hosed off after storms and monthly otherwise to maintain its new appearance.
2. Before Each Cooling Season:
If the furnace/air handler blower motor and the outdoor unit fan motor(s) have oil tubes at the motor bearings, apply 10 drops of SAE No. 20 motor oil to each oil tube.
The indoor blower will start immediately, and will run continually until the fan switch is reset to AUTO.
The continuous indoor blower oper ation can be obtained with the thermostat system switch set in any position, including OFF.
The continuous indoor blower operation is typically used to circulate the indoor air to equalize a temperature unbalance due to a sun load, cooking, or fi replace operation.
T o Maintain Your Air Conditioner
CAUTION:
Be certain the electrical power to the outdoor unit and the furnace/ air handler is disconnected before doing the following recommended maintenance.
CAUTION:
Do not over-oil, or oil motors not factory-equipped with oil tubes. The compressor is hermetically “sealed” and does not require lubrication.
3. Before Calling a Service Technician, Be Certain:
a. The unit thermostat is properly set—
see “To Operate Your Air Conditioner for Cooling” and “T o Operate Y our Furnace for Heating.”
b. The unit disconnect fuses are in good
condition, and the electrical power to the unit is turned on.
1. GENERAL INFORMATION
Read the following instructions completely before performing the installation.
2
Page 3
Condensing Unit Section — Each condens­ing unit is shipped with a refrigerant charge adequate to operate the outdoor section with an indoor matching coil or air handler, and 15 feet of refrigeration line.
NOTE: DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING.
Matching coils and air handlers are shipped with a small pressurized holding charge to pressurize them to keep out contaminants. To release the pressure, carefully read the instal­lation instructions provided with the indoor coil or air handler.
Liquid and Suction Lines — Refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
W ARNING:
Ensure all electrical power to the unit is off prior to installing or servicing the equipment. Failure to do so may cause personal injury or death.
3. SITE PREPARATION
Unpacking Equipment — Remove the card-
board carton and User’s Manual from the equipment. T ake care not to damage the tubing connections when removing the carton.
Inspect for Damage — Inspect the equipment for damage prior to installing the equipment at the job site. Ensure coil fi ns are straight and, if necessary, comb fi ns to remove fl attened and bent fi ns.
Field Connections for Electrical Power Supply — All wiring must comply with current
revisions of the National Electrical Code (ANSI/NFPA 70) and with applicable local codes having jurisdiction. The minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label.
2. SAFETY CONSIDERATIONS
Pressures within the System — Split system
air conditioning equipment contains liquid and gaseous refrigerant under pressure. Installation and servicing of this equipment should be per­formed by qualifi ed, trained personnel thoroughly familiar with this type of equipment. Under no circumstances should the Homeowner attempt to install and/or service the equipment.
Labels, Tags, Precautions — When working with this equipment, follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and opera­tional checkout of the equipment.
Preferred Location of the Outdoor Unit at the Job Site — Conduct a survey of the job site to
determine the optimum location for mounting the outdoor unit. Ov erhead obstructions, poorly ventilated areas, and areas subject to accumula­tion of debris should be avoided. The outdoor unit should be installed no closer than 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airfl ow through the outdoor unit.
Facility Prerequisites — Electrical power must be supplied to the equipment. Electrical power supplied must be adequate for proper operation of the equipment. The system must be wired and provided with circuit protection in accordance with local building codes and the National Electrical Code.
Minimum Circuit Ampacity — Electrical wiring to the equipment must be compatible and in compliance with the minimum circuit ampacity listed on the outdoor unit data label.
Maximum Fuse/Circuit Breaker Size — Circuit protection for the outdoor unit must be compat­ible with the maximum fuse/circuit breaker siz e
listed on the outdoor unit data label.
Brazing Operations — Installation of equipment may require brazing operations. Safety codes must be complied with. Safety equipment (e .g.; safety glasses, work gloves, fi re extinguisher, etc.) must be used when performing brazing operations.
4.
INSTALLING THE OUTDOOR UNIT
Slab Mount — The site selected f or a slab mount
installation requires a stable foundation and one
3
Page 4
not subject to erosion. The slab should be level and anchored (if necessary) prior to placing the equipment on the slab.
Cantilever Mount — The cantilever mount should be designed with adequate safety factor to support the weight of the equipment, and for loads subjected to the mount during operation. Installed equipment should be adequately se­cured to the cantilever mount and levelled prior to operation of the equipment.
Roof Mount — The method of mounting should be designed so as not to overload roof structures nor transmit noise to the interior of the structure. Refrigerant and electrical line should be routed through suitably waterproofed openings to pre­vent water leaking into the structure.
ference between the indoor and outdoor sections should not exceed 20 feet.
Filter Dryer Installation — A fi lter dryer is provided with PS series models only and must be installed in the liquid line of the system. If the installation replaces a system with a fi lter dryer already present in the liquid line, the fi lter dryer must be replaced with the one supplied with the unit. The fi lter dr yer must be installed in strict accordance with the manufacturer’ s installation instructions.
For all other series models, installing a fi lter dryer is optional. Ho wev er , it is good installation practice to install a fi lter dryer when replacing the evaporator and/or condenser of a system. When installing, the fi lter dryer must be installed in strict accordance with the manufacturer’s installation instructions.
5. INSTALLING THE INDOOR UNIT
The indoor section should be installed before proceeding with routing of refrigerant piping. Consult the installation instructions of the indoor unit (i.e.: air handler, furnace, etc.) for details regarding installation.
6. CONNECTING REFRIGERANT TUBING BETWEEN THE INDOOR AND OUTDOOR UNIT
General — Once outdoor and indoor unit place-
ment has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices. Refr igerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing. Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation. T ubing should be kept clean of foreign debris during installation and installation of a liquid line fi lter drier is rec­ommended if cleanliness or adequacy of system evacuation is unknown or compromised. Every effort should be made by the installer to ensure that the fi eld installed refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices so as to insure reliable system operation and longevity. The maximum recommended interconnecting refrigerant line length is 75 feet, and the vertical elevation dif-
Optional Equipment — Optional equipment (e.g.: liquid line solenoid valv es, etc.) should be installed in strict accordance with the manufac­turer’s installation instructions.
7. MAKING ELECTRICAL CONNECTIONS
W ARNING:
T urn off all electrical power at the main circuit box before wiring electrical power to the outdoor unit. Failure to comply may cause severe personnel injury or death.
Wiring Diagram/Schematic — A wiring dia-
gram/schematic is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram/schematic before making an y electrical connections to the outdoor unit.
Outdoor Unit Connections — The outdoor unit requires both power and control circuit electrical connections. Refer to the unit wir ing diagram/schematic for identifi cation and location of outdoor unit fi eld wiring interfaces.
Control Circuit Wiring — The outdoor unit is designed to operate from a 24 V AC Class ll control circuit. Control circuit wiring must comply with
4
Page 5
the current provisions of the National Electrical Code (ANSI/NFP A 70) and with applicab le local codes having jurisdiction.
Thermostat Connections — Thermostat con­nections should be made in accordance with the instructions supplied with the thermostat, and with the instructions supplied with the indoor equipment.
Electrical Power Wiring — Electrical power wiring shall comply with the current provisions of the National Electrical Code (ANSI/NFP A 70) and with applicable local codes having jurisdic­tion. Use of rain tight conduit is recommended. Electrical conductors shall have minimum circuit ampacity in compliance with the outdoor unit rat­ing label. The facility shall employ electrical circuit protection at a current rating no greater than that
indicated on the outdoor unit rating label.
temperature setpoint to its highest setting. Prior to applying electrical power to the outdoor unit, ensure that the unit has been properly and securely grounded, and that power supply con­nections have been made at both the facility power interface and outdoor unit.
Outdoor Unit — Ensure the outdoor coil and top of the unit are free from obstructions and debris, and all equipment access/control panels are in place.
Using extreme caution, apply power to the unit and inspect the wiring for evidence of open, shorted, and/or improperly wired circuits.
Functional Checkout:
CAUTION:
Disconnect Switch — An electrically compatible
disconnect switch must be within line of sight of the outdoor unit. This switch shall be capable of electrically de-energizing the outdoor unit.
Optional Equipment — Optional equipment requiring connection to the power or control circuits must be wired in strict accordance with current provisions of the National Electrical Code (ANSI/NFP A 70), with applicable local codes hav­ing jurisdiction, and the installation instructions provided with the equipment. Optional Equip­ment (e.g.: liquid line solenoid valves , hard start kits, low suction pressure cutout switch kit, high pressure cutout switch kit, refrigerant compres­sor crankcase heater, etc.) should be installed in strict accordance with the manufacturer’s installation instructions.
8. STARTUP AND CHECKOUT
If equipped with a compressor crankcase heater , wait 24 hour s prior to performing a function check out to allow for heating of the compressor crankcase. Failure to comply may result in damage and could cause premature failure of the system.
Indoor Blower — Set the thermostat function
switch to COOLING and the fan switch to ON. Verify that the indoor blower is operating and that airfl ow is not restricted. Set the fan switch back to AUTO.
Positive Temperature Coeffi cient Resistor (PTCR) — (select models) A PTCR is factory
installed and located on the control panel of the outdoor unit. The PTCR is a soft start device for use with reciprocating compressors. If a hard start kit is needed on this model the soft star t (PTCR) must be removed fi rst.
W ARNING:
Ensure electrical power to the unit is off prior to performing the following steps. Failure to do so may cause personal injury or death.
Air Filters — Ensure air fi lters are clean and in
place prior to operating the equipment. Thermostat — Set the room thermostat function
switch to OFF, fan switch to AUTO, and move
Low-Pressure Switch — A low-pressure switch is factory-installed in select models only. If provided, this switch is located in the suction line internal to the outdoor unit. The switch is designed to protect the compressor from a loss of charge. Under normal conditions, the switch is closed. If the suction pressure f alls below 5 psig, then the switch will open and de-energize the outdoor unit. The switch will close again once the suction pressure increases above 20 psig.
5
Page 6
Comfort AlertTM Diagnostics (Select Models)
TM
The Comfort Aler t
diagnostics is a break­through innovation for troubleshooting heat pump and air conditioning system failures. The module installs easily in the electrical box of the outdoor unit near the compressor contac­tor. By monitoring and analyzing data from the
®
Copeland Scroll compressor
and the thermostat demand, the module can accurately detect the cause of electrical and system related failures without any sensors. A fl ashing LED indicator communicates the ALERT code and guides the service technician more quickly and accurately to the root cause of a problem.
NOTE: This module does not provide safety protection! The Comfort Alert module is a monitoring device and cannot shut down the compressor directly.
LED Description (See Figure 2)
POWER LED (Green): indicates voltage is pres­ent at the power connection of the module.
ALERT LED (Yellow): communicates an abnormal system condition through a unique fl ash code. The ALER T LED will fl ash a number of times consecutively, pause and then repeat the process. The number of consecutive fl ashes, defi ned as the Flash Code, correlates to a particular abnormal condition. Detailed descriptions of specifi c ALERT Flash Codes are shown in Table 1 of this manual.
TRIP LED (Red): indicates there is a demand signal from the thermostat but no current to the compressor is detected by the module. The TRIP LED typically indicates the compressor protector is open or may indicate missing supply power to the compressor.
The scroll compressor’s run (R), common (C) and start (S) wires are routed through the holes in the Comfort Alert
TM
module marked “R,” “C” and “S.” The common (C) wire need not be routed through the module for it to operate properly.
24 V AC Power Wiring — The Comfort Alert
TM
module requires a constant nominal 24 VAC power supply. The wiring to the module’s R and C terminals must be directly from the indoor unit or thermostat. The module cannot be powered by the C terminal on a defrost board or other control board without experiencing nuisance alerts.
Comfort Alert
L
C
Y
R
C
R L Y
24 Volt Field Connections
LPS
CC
Figure 3. 24VAC Comfort AlertTM
Wiring Diagram
Figure 2. Comfort Alert
6
TM
Diagnostics Module
Page 7
NOTE: Factory installed modules may have different thermostat demand signal wiring, follow manufacturers wiring installations when replacing module.
system operation and compatibility . Ref er to the installation instructions for this equipment and perform a functional checkout in accordance with the manufacturer’s instructions.
NOTE: After the thermostat demand signal is connected, verify Y is phased properly with C by measuring 24 V A C across Y and C when demand is present.
TROUBLESHOOTING Interpreting The Dia gnostic LEDs – When an
abnormal system condition occurs, the Comfort
TM
Alert and/or TRIP LED . The yellow alert LED will fl ash a number of times consecutively, pause and then repeat the process. To identify a Flash Code number, count the n umber of consecutive fl ashes. Every time the module powers up, the last ALERT Flash Code that occurred prior to shut down is displayed for one minute.
Cooling — Gradually lower the thermostat temperature setpoint below the actual room temperature and observe that the outdoor unit and indoor blower energize. Feel the air being circulated by the indoor blower and verify that it is cooler than ambient temperature. Listen for any unusual noises. If present, locate and determine the source of the noise and correct as necessary.
Heating — If provided with heating equipment, lower the thermostat setpoint temperature to the lowest obtainable setting and set the thermostat function switch to HEATING. The indoor blower and outdoor unit should stop running. Increase the setpoint temperature of the thermostat to the maximum setting. Verify that the heating equipment has been energized (i.e., fossil fuel burner operating, etc.) and that the indoor blower energizes after a short period of time. Feel the air being circulated by the indoor blower and verify that it is warmer than ambient temperature. Listen for any unusual noises . If present, locate and determine the source of the noise and cor­rect as necessary.
module displays the appropriate ALERT
Adjustment of Refrigerant Charge:
CAUTION:
Split system air conditioner equipment contains liquid and gaseous refrigerant under pressure. Adjustment of refrigerant charge should only be attempted by qualified, trained personnel thoroughly familiar with the equipment. Under no circumstances should the homeowner attempt to install and/or service this equipment. Failure to comply with this warning could result in equipment damage, personal injury, or death.
NOTE: The following Refrigerant Charging
Charts are applicable to matched assemblies of our equipment and at listed airfl ows for the indoor coil. Assemblies of indoor coils and outdoor units not listed are not recommended and deviations from rated airfl o ws or non-listed equipment combinations may require modifi ca­tions to the expansion device(s) and refrigerant charging procedures for proper and effi cient system operation.
Refrigerant Charging Chart — Refer to Refrigerant Charging Charts for correct system charging, and to Orifi ce Usage Chart for correct restrictor sizes.
NOTE: Linesets over 15 feet in length may require additional refrigerant charge. NORD YNE recommends 0.6 oz. of refrigerant per foot for any lineset over 15 feet.
NOTE: Other sources for heating (i.e.: electric furnace, fossil fuel furnace, air handler with electric heat options, etc.) that interface with the unit should be functionally checked to v erify
Optional Equipment — A functional checkout should be performed in accordance with the checkout procedures supplied with the equip­ment.
7
Page 8
Status LED Status LED Description Status LED Troubleshooting Information
Green “POWER” Module has power Supply voltage is present at module terminals
Red “TRIP” Thermostat demand signal
Y is present, but the compressor is not running
1. Compressor protector is open
2. Outdoor unit power disconnect is open
3. Compressor circuit breaker or fuse(s) is open
4. Broken wire or connector is not making contact
5. Low pressure switch open if present in system
6. Compressor contactor has failed open
Yellow “ALERT” Long Run Time Flash Code 1 Compressor is
running extremely long run cycles
1. Low refrigerant charge
2. Evaporator blower is not running
3. Evaporator coil is frozen
4. Faulty metering device
5. Condenser coil is dirty
6. Liquid line restriction (filter drier blocked if present in system)
7. Thermostat is malfunctioning
8. Comfort Alert Failure
9. Comfort Alert Failure
Yellow “ALERT” System Pressure Trip Flash Code 2 Discharge or suction
pressure out of limits or compressor overloaded
1. High head pressure
2. Condenser coil poor air circulation (dirty, blocked, damaged)
3. Condenser fan is not running
4. Return air duct has substantial leakage
5. If low pressure switch present in system, check Flash Code 1 information
Yellow “ALERT” Short Cycling 1. Thermostat demand signal is intermittent Flash Code 3 Compressor is running 2. Time delay relay or control board defective
only briefly 3. If high pressure switch present go to Flash Code 2 information
4. If low pressure switch present go to Flash Code 1 information
Yellow “ALERT” Locked Rotor Flash Code 4
1. Run capacitor has failed
2. Low line voltage (contact utility if voltage at disconnect is low)
• Check wiring connections
3. Excessive liquid refrigerant in compressor
4. Compressor bearings are seized
• Measure compressor oil level
Yellow “ALERT” Open Circuit Flash Code 5
1. Outdoor unit power disconnect is open
2. Compressor circuit breaker or fuse(s) is open
3. Compressor contactor has failed open
• Check compressor contactor wiring and connectors
• Check for compressor contactor failure (burned, pitted or open)
• Check wiring and connectors between supply and
compressor
• Check for low pilot voltage at compressor contactor coil
4. High pressure switch is open and requires manual reset
5. Open circuit in compressor supply wiring or connections
6. Unusually long compressor protector reset time due to extreme ambient temperature
7. Compressor windings are damaged
• Check compressor motor winding resistance
Yellow “ALERT” Open Start Circuit 1. Run capacitor has failed Flash Code 6 Current only in run circuit 2. Open circuit in compressor start wiring or connections
• Check wiring and connectors between supply and the
compressor “S” terminal
3. Compressor start winding is damaged
• Check compressor motor winding resistance
Yellow “ALERT” Open Run Circuit 1. Open circuit in compressor run wiring or connections Flash Code 7 Current only in start circuit • Check wiring and connectors between supply and the
compressor “R” terminal
2. Compressor run winding is damaged
• Check compressor motor winding resistance
Yellow “ALERT” Welded Contactor 1. Compressor contactor has failed closed Flash Code 8 Compressor always runs 2. Thermostat demand signal not connected to module
Yellow “ALERT” Low Voltage 1. Control circuit transformer is overloaded Flash Code 9 Control circuit < 17VAC 2. Low line voltage (contact util
Check wiring connections
ity if voltage at disconnect is low)
Flash Code number corresponds to a number of LED flashes, followed by a pause and then repeated.
TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation.
Table 1. Interpreting the Diagnostic LEDS
8
Page 9
Miswired Module Indication Recommended Troubleshooting Action Green LED is not on, Determine if both R and C module ter minals are
module does not power up connected. Verify voltage is present at module’s R and
C terminals. Review 24VAC Power Wiring (page 4) for R and C wiring.
Green LED intermittent, Determine if R and Y terminals are wired in reverse. module powers up only Verify module’s R and C terminals have a constant when compressor runs source. Review 24VAC Power Wiring (page 4) for R
and C wiring.
TRIP LED is on but system Verify Y terminal is connected to 24VAC at contactor and compressor check OK coil. Verify voltage at contactor coil falls below 0.5VAC
when off.
TRIP LED and ALERT LED Verify R and C terminals are supplied with 19-28VAC. flashing together
ALERT Flash Code 3 Verify Y terminal is connected to 24VAC at contactor coil. (Compressor Short Cycling) Verify voltage at contactor coil falls below 0.5VAC when displayed incorrectly off.
ALERT Flash Code 5, 6 or 7 Check that compressor run and start wires are through (Open Circuit, Open Start Circuit module’s current sensing holes. V erify Y terminal is or Open Run Circuit) displayed connected to 24VAC at contactor coil. Verify voltage at incorrectly contactor coil falls below 0.5VAC when off.
ALERT Flash Code 6 (Open Check that compressor run and start wires are routed Start Circuit) displayed for Code 7 through the correct module sensing holes. (Open Run Circuit) or vice versa
ALERT Flash Code 8 Determine if module’s Y terminal is connected. Ver ify Y (Welded Contactor) terminal is connected to 24VAC at contactor coil. V er ify displayed incorrectly 24VAC is present across Y and C when thermostat demand
signal is present. If not, R and C are reverse wired. Ver ify voltage at contactor coil falls below 0.5VAC when off.
Table 2. Module Wiring Troubleshooting
9
Page 10
Refrigerant Metering Device
for 13 SEER Split System Air Conditioner
with ZRKA Compressor
Model
Number
1.5 ton 0.050 74
2.0 ton 0.059 98
2.5 ton 0.067 116
3.0 ton 0.075 116
3.5 ton 0.080 170
4.0 ton 0.089 147
5.0 ton 0.099 232
Restrictor Bore
Size (inches)
System Charge
R-22 (oz.)
Refrigerant Metering Device
for 13 SEER Split System Air Conditioner
with CRK7 Compressor
Model
Number
Restrictor Bore
Size (inches)
System Charge
R-22 (oz.)
2.0 ton 0.060 104
2.5 ton 0.067 131
3.0 ton 0.075 136
10
Page 11
Restrictor Refrigerant Charging Charts Legend
For Cooling Mode of Operation
*Note all pressures are listed in psig. and all temperatures in deg. °F.
- Shaded Boxes indicate fl ooded conditions
- Rated Design Values. Suction Pressure will be lower than design value if indoor air fl ow, entering dry bulb, or entering wet bulb temperatures are lower than design.
- Discharge temperatures greater than charted values indicates a refrigerant undercharge.
Restrictor Refrigerant Charging Charts
with ZRKA Compressors
1-1/2 TON
Suc.
Press.
72 170 135 74 76 174 146 78 80 180 153 82 197 157 84 213 162 86 229 166 88 233 170 246 170 90 249 174 262 175 92 266 179 279 179 94 282 183 295 183 96 298 188 98
2
TON
Suc.
Press.
71 150 138 73 75 155 149 77 79 160 157 81 177 160 83 193 162 85 209 165 87 213 169 226 168 89 229 172 242 171 91 245 175 258 174 93 262 178 275 177 95 278 182 97
70 75 80 85 90 95 100 105
Dis.
Dis.
Dis.
Dis.
Press.
Temp.
Press.
172 141
177 150
70 75 80 85 90 95 100 105
Dis.
Press.
152 143
157 154
Dis.
Temp.
186 140 188 145 190 150 193 154
Dis.
Press.
166 142 169 147 171 152 173 157
Temp.
Dis.
Temp.
Dis.
Press.
202 145 204 149 207 154 210 158
Dis.
Press.
183 145 185 150 187 155 189 159
OUTDOOR TEMPERATURE (°F)
Dis.
Dis.
Temp.
Dis.
Temp.
Dis.
Press.
Temp.
219 149 221 154 223 158 226 162
OUTDOOR TEMPERATURE (°F)
Dis.
Dis.
Press.
Temp.
199 148 201 153 203 158 206 162
Dis.
Press.
235 154 237 158 239 162 242 166
Dis.
Press.
215 152 217 156 219 160 222 164
Dis.
Temp.
Dis.
Temp.
Dis.
Press.
251 158 253 162 255 167 259 171
Dis.
Press.
231 155
233 159 235 163
239 167
Dis.
Temp.
Dis.
Temp.
Dis.
Press.
268 162 270 166 272 170 275 175
Dis.
Press.
247 158 249 162 251 166 255 170
Dis.
Temp.
Dis.
Temp.
Dis.
Press.
284 167 286 171 288 174 292 179
Dis.
Press.
263 160 265 164 267 168 271 173
Dis.
Temp.
Dis.
Temp.
11
Page 12
Restrictor Refrigerant Charging Charts
with ZRKA Compressors Continued
2-1/2 TON
Suc.
Press.
70 75 80 85 90 95 100 105
Dis.
Dis.
Dis.
Dis.
Press.
Temp.
Press.
Temp.
Dis.
Press.
OUTDOOR TEMPERATURE (°F)
Dis.
Dis.
Press.
Dis.
Temp.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
71 149 131
151 136
73 75 154 142 77
157 144 79 161 147 81 176 151 83 191 155 85 206 159 87 210 163 221 163 89 225 167 237 167 91 240 171 252 170
164 135 167 140 169 145 172 148
180 139 182 144 184 148 188 152
195 143 197 147 199 152 203 155
210 146 212 151 215 155 218 159
226 150 228 154 230 159 233 163
241 154 243 158 245 162 248 166
256 158 258 161 260 165
264 170 93 255 175 267 174 95 270 179 97
3
OUTDOOR TEMPERATURE (°F)
TON707580859095100105
Suc.
Dis.
Dis.
Dis.
Dis.
Dis.
Dis.
Dis.
Dis.
Dis.
Dis.
Dis.
Dis.
Dis.
Dis.
Dis.
Press.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Press.
Dis.
Temp.
67 149 137
151 142
69 71 153 147 73
156 151 75 160 154 77 175 158 79 191 163 81 207 167 83 210 171 223 171 85 226 175 238 176 87 242 180 254 180
164 142 167 147 169 152 172 155
180 146 182 151 185 156 188 159
196 150 198 155 200 160 203 163
212 155 214 159 216 164 219 168
227 159 229 163 231 168 235 172
243 164 245 168 247 172 251 176
259 168 261 172 263 175
266 180 89 257 184 270 184 91 273 189 93
3-1/2
TON
Suc.
Press.
70 75 80 85 90 95 100 105
Dis.
Dis.
Dis.
Press.
Temp.
Press.
Dis.
Temp.
72 150 143
152 148
74
76 154 153
78
158 157
80 161 160
166 145
168 150 170 155
173 159 82 177 162 84 192 164 86 208 167 88 211 170 223 169 90 227 173 239 171 92 242 175 254 173 94 258 178 270 175 96 273 180 98
12
Dis.
Press.
181 148 183 153 185 157 189 161
OUTDOOR TEMPERATURE (°F)
Dis.
Dis.
Temp.
Press.
197 150 199 155 201 159 204 163
Dis.
Temp.
Dis.
Press.
Temp.
212 152 214 157 216 161 220 165
Dis.
Dis.
Press.
228 155 230 159 232 163 235 167
Dis.
Temp.
Dis.
Press.
243 157 245 161 248 165 251 169
Dis.
Temp.
Dis.
Press.
259 159 261 163 263 166 267 171
Dis.
Temp.
Page 13
Restrictor Refrigerant Charging Charts
with ZRKA Compressors Continued
4
TON
Suc.
Press.
69 145 136 71 73 149 146 75 77 155 154 79 171 158 81 187 162 83 204 165 85 207 169 220 169 87 223 173 236 173 89 239 177 252 177 91 256 181 268 180 93 272 185 95
5
TON
Suc.
Press.
66 151 144 68
70 156 155
72 74 161 162
76 178 167 78 194 171 80 210 175 82 214 179 227 180 84 230 183 243 184
86 246 188 259 188
88 263 193 276 193
90 279 197
92
70 75 80 85 90 95 100 105
Dis.
Dis.
Dis.
Dis.
Press.
Temp.
Press.
147 141
152 152
70 75 80 85 90 95 100 105
Dis.
Press.
153 149
158 160
Dis.
Temp.
161 140 163 145 165 150 168 155
Dis.
Press.
167 149 170 154 172 159 174 164
Temp.
Dis.
Temp.
Dis.
Press.
177 144 179 149 181 154 184 158
Dis.
Press.
184 154 186 159 188 163 191 168
OUTDOOR TEMPERATURE (°F)
Dis.
Dis.
Temp.
Press.
Temp.
193 148
195 153 197 158
200 162
OUTDOOR TEMPERATURE (°F)
Dis.
Dis.
Temp.
Press.
Temp.
200 158 202 163 204 168 207 172
Dis.
Dis.
Dis.
Press.
209 152 211 157 213 161 216 165
Dis.
Press.
216 163 218 167 220 172 223 176
Dis.
Temp.
Dis.
Temp.
Dis.
Press.
Temp.
225 156 227 160 229 165 233 169
Dis.
Press.
Temp.
232 167 234 172 236 176 240 180
Dis.
Dis.
Dis.
Press.
Temp.
241 160
243 164 245 168
249 172
Dis.
Press.
248 172 250 176 252 180 256 184
Dis.
Dis.
Temp.
Dis.
Press.
257 164 259 167 261 171 265 176
Dis.
Press.
264 176
266 180 268 184 272 188
Dis.
Temp.
Dis.
Temp.
Restrictor Refrigerant Charging Charts
2
TON
Suction
Press.
73 154 149 75 156 154 168 149 77 158 159 171 154 183 149 79 163 160 173 159 185 154 198 150 81 167 162 177 161 187 159 200 154 212 150 83 181 164 192 162 202 159 214 155 227 151 85 195 165 206 162 216 159 229 155 241 151 87 209 166 220 163 231 159 243 155 256 152 89 213 169 224 167 234 163 245 159 258 156 91 227 171 238 167 249 164 260 160 93 241 171 252 168 263 164 95 255 172 266 168 97 270 173 99
70 75 80 85 90 95
Dis.
Dis.
Dis.
Press.
Temp.
Press.
Dis.
Temp.
with CRK7 Compressors
OUTDOO R T EMPERATURE (°F)
Dis.
Dis.
Dis.
Dis.
Dis.
Dis.
Press.
Temp.
Press.
Temp.
Press.
Temp.
Dis.
Press.
Dis.
Temp.
100 105
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
13
Page 14
Restrictor Refrigerant Charging Charts
with CRK7 Compressors Continued
2-1/2 TON
Suction
Press.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
OUTDOO R T EMPERATURE (°F)
Dis.
Dis.
Dis.
Temp.
Press.
Temp.
Dis.
Press.
90 95 100 10570 75 80 85
Temp.
Dis.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
73 146 142 75 148 148 160 144 77 150 153 162 149 174 145 79 155 155 164 154 176 150 188 146 81 158 157 168 156 178 154 190 150 202 147 83 172 159 182 157 192 155 204 151 216 148 85 186 161 196 159 206 156 218 153 230 150 87 200 162 210 160 220 157 232 154 244 151 89 203 166 213 164 224 161 234 158 246 155 91 217 167 227 165 238 162 248 158 93 231 169 241 166 252 163 95 245 170 255 167 97 258 172 99
3
TON
Suction
Press.
70 75 80 85 90 95 100 105
Dis.
Dis.
Dis.
Dis.
Press.
Temp.
Press.
Temp.
Dis.
Press.
OUTDOO R T EMPERATURE (°F)
Dis.
Dis.
Dis.
Temp.
Press.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
Dis.
Temp.
Dis.
Press.
70 150 155 72 152 161 164 155 74 154 166 166 160 178 155 76 159 166 168 165 180 160 192 155 78 163 169 173 167 182 165 194 159 206 155 80 176 170 187 167 197 164 209 159 221 155 82 190 170 201 167 211 164 223 159 235 155 84 204 171 214 167 225 163 237 159 249 155 86 207 175 218 171 228 167 239 163 251 159 88 221 175 232 172 242 167 253 163 90 235 176 246 172 256 167 92 249 176 259 172 94 263 176 96
Dis.
Temp.
Dis.
Temp.
14
Page 15
375
350
325
TXV Refrigerant Charging Charts
with ZRKA Compressors
1.5 Ton AC TXV Charging Chart
300
275
250
225
Li qu id Pressu re (p sig)
200
Remove refrigerant when above curve
Add refrigerant when below curve
175
150
75 80 85 90 95 100 105 110 115 120 125 130 135
Li qu id Tem p eratu re (F)
2.0 Ton AC TXV Charging Chart
375
350
325
300
275
250
225
Li qu id Pressu r e (psig)
200
175
150
70 75 80 85 90 95 100 105 110 115 120 125 130 135
Remove refrigerant when above curve
Add refrigerant when below curve
Liquid Tempe rature (F)
15
Page 16
350
325
300
TXV Refrigerant Charging Charts
with ZRKA Compressors Continued
2.5 Ton AC TXV Charging Chart
275
250
225
200
Li qu id Pressu re (p si g )
Remove refrigerant when above curve
Add refrigerant when below curve
175
150
70 75 80 85 90 95 100 105 110 115 120 125 130
Liquid Tempe ra ture (F)
3.0 Ton AC TXV Charging Chart
350
325
300
275
250
225
200
Li qu id Pressu re (p si g )
175
150
70 75 80 85 90 95 100 105 110 115 120 125 130
Remove refrigerant when above curve
16
Add refrigerant when below curve
Liquid Tempe ra ture (F)
Page 17
350
325
300
TXV Refrigerant Charging Charts
with ZRKA Compressors Continued
3.5 Ton AC TXV Charging Chart
275
250
225
200
Li qu id Pressu re (p si g )
175
Remove ref r igerant when above curve
Add refrigerant when below curve
150
125
70 75 80 85 90 95 100 105 110 115 120 125 130
Liquid Tempe ra ture (F)
4.0 Ton AC TXV Charging Chart
350
325
300
275
250
225
200
Li qu id Pressu r e (psig)
175
150
70 75 80 85 90 95 100 105 110 115 120 125 130
Remove refrigerant when above curve
Add refrigerant when below curve
Liquid Tempe rature (F)
17
Page 18
350
325
300
TXV Refrigerant Charging Charts
with ZRKA Compressors Continued
5.0 Ton AC TXV Charging Chart
275
250
225
200
Li qu id Pressu re (p si g )
Remove refrigerant when above curve
Add refrigerant when below curve
175
150
70 75 80 85 90 95 100 105 110 115 120 125 130
Liquid Tempe ra ture (F)
TXV Refrigerant Charging Charts
with CRK7 Compressors
2.0 Ton AC CRK7 TXV Charging Chart
350
Remove refrigerant when above curve
325
300
275
250
225
200
Liq u i d Pressure (psi g )
175
150
70 75 80 85 90 95 100 105 110 115 120 125 130 135
18
Add refrigerant when below curve
Liquid Temperature (F)
Page 19
TXV Refrigerant Charging Charts
with CRK7 Compressors Continued
2.5 Ton AC CRK7 TXV Charging Chart
350
Remove refrigerant when above curve
325
300
275
250
225
200
Liq u i d Pressure (psi g )
175
Add refrigerant when below curve
150
75 80 85 90 95 100 105 110 115 120 125 130
Liquid Temperature (F)
3.0 Ton AC CRK7 TXV Charging Chart
350
Remove refrigerant when above curve
325
300
275
250
225
200
Liq u i d Pressure (psi g )
175
150
70 75 80 85 90 95 100 105 110 115 120 125 130
Add refrigerant when below curve
Liquid Temperature (F)
19
Page 20
¢708451#¤
708451A
INSTALLER: PLEASE LEAVE
THESE INSTALLATION INSTRUCTIONS
WITH THE HOMEOWNER.
708451A (Replaces 7084510)
Specifi cations and illustrations subject to change
without notice and without incurring obligations.
Printed in U.S.A. (01/06)
Loading...