Nordyne 13+ SEER Extra High Effi ciency Split System User And Installation Manual

Outdoor Air Conditioner
User’s Information and Installation Instructions
13+ SEER Extra High Effi ciency Split System
These units have been designed and tested f or capacity and effi ciency in accordance with A.R.I. Standards. Split System Air Conditioning units are designed for use with a wide variety of f ossil fuel furnaces, electric furnaces, air handlers, and evaporator coil combinations.
These instructions are primarily intended to assist qualifi ed individuals experienced in the proper installation of heating and/or air condi­tioning appliances. Some local codes require licensed installation/service personnel for this type of equipment. Read all instructions carefully before starting the installation.
USER’S INFORMATION
IMPORTANT
Read this owner information to become familiar with the capabilities and use of your appliance. Keep this with literature on other appliances where you have easy access to it in the future.
If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your servicing contractor.
OPERATING INSTRUCTIONS T o Operate Your Air Conditioner for
Cooling —
1. Set the thermostat system switch to COOL or AUTO and the thermostat fan switch to AUTO. (See Figure 1)
2. Set the thermostat temperature to the desired temperature level using the temperature selector. Please refer to the separate thermostat user’s manual for complete instructions regarding ther­mostat programming. The outdoor unit and indoor blower will both cycle on and off to maintain the indoor temperature at the desired cooling level.
SYSTEM SWITCH
FAN SWITCH
TEMPERATURE SCALES
Figure 1. Typical Thermostat
TEMPERATURE SELECTOR
To Operate Your Furnace for Heating —
1. Set the thermostat system switch to HEAT or AUT O and the thermostat f an s witch to AUTO. (See Figure 1)
1. Regularly:
a. Clean or replace the indoor air fi lter at the
start of each heating and cooling season, and when an accumulation of dust and dirt is visible on the air fi lter.
2. Set the thermostat temperature to the desired temperature level using the temperature selector. Please refer to the separate user’s manual for complete thermostat programming instructions. The furnace and indoor blower will cycle on and off to maintain the indoor temperature at the desired heating level.
T o Shut Off Y our Air Conditioner —
Set the thermostat system switch to OFF and the thermostat fan switch to AUTO. (See Figure 1)
The system will not operate, regardless of the thermostat temperature setting.
To Operate the Indoor Blower Continuously —
Set the thermostat fan switch to ON (See Figure 1)
b. Remove any leaves and grass clippings
from the coil in the outdoor unit, being careful not to damage the aluminum fi ns.
c. Check for any obstruction, such as twigs,
sticks, etc.
d. Certain models have external panels
fabricated from a premium grade of stainless steel designed to inhibit cor­rosion. For such units, if the unit is located in a coastal region or other area subjected to high concentrations of salt, then the unit should be hosed off after storms and monthly otherwise to maintain its new appearance.
2. Before Each Cooling Season:
If the furnace/air handler blower motor and the outdoor unit fan motor(s) have oil tubes at the motor bearings, apply 10 drops of SAE No. 20 motor oil to each oil tube.
The indoor blower will start immediately, and will run continually until the fan switch is reset to AUTO.
The continuous indoor blower oper ation can be obtained with the thermostat system switch set in any position, including OFF.
The continuous indoor blower operation is typically used to circulate the indoor air to equalize a temperature unbalance due to a sun load, cooking, or fi replace operation.
T o Maintain Your Air Conditioner
CAUTION:
Be certain the electrical power to the outdoor unit and the furnace/ air handler is disconnected before doing the following recommended maintenance.
CAUTION:
Do not over-oil, or oil motors not factory-equipped with oil tubes. The compressor is hermetically “sealed” and does not require lubrication.
3. Before Calling a Service Technician, Be Certain:
a. The unit thermostat is properly set—
see “To Operate Your Air Conditioner for Cooling” and “T o Operate Y our Furnace for Heating.”
b. The unit disconnect fuses are in good
condition, and the electrical power to the unit is turned on.
1. GENERAL INFORMATION
Read the following instructions completely before performing the installation.
2
Condensing Unit Section — Each condens­ing unit is shipped with a refrigerant charge adequate to operate the outdoor section with an indoor matching coil or air handler, and 15 feet of refrigeration line.
NOTE: DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING.
Matching coils and air handlers are shipped with a small pressurized holding charge to pressurize them to keep out contaminants. To release the pressure, carefully read the instal­lation instructions provided with the indoor coil or air handler.
Liquid and Suction Lines — Refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
W ARNING:
Ensure all electrical power to the unit is off prior to installing or servicing the equipment. Failure to do so may cause personal injury or death.
3. SITE PREPARATION
Unpacking Equipment — Remove the card-
board carton and User’s Manual from the equipment. T ake care not to damage the tubing connections when removing the carton.
Inspect for Damage — Inspect the equipment for damage prior to installing the equipment at the job site. Ensure coil fi ns are straight and, if necessary, comb fi ns to remove fl attened and bent fi ns.
Field Connections for Electrical Power Supply — All wiring must comply with current
revisions of the National Electrical Code (ANSI/NFPA 70) and with applicable local codes having jurisdiction. The minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label.
2. SAFETY CONSIDERATIONS
Pressures within the System — Split system
air conditioning equipment contains liquid and gaseous refrigerant under pressure. Installation and servicing of this equipment should be per­formed by qualifi ed, trained personnel thoroughly familiar with this type of equipment. Under no circumstances should the Homeowner attempt to install and/or service the equipment.
Labels, Tags, Precautions — When working with this equipment, follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment prior to performing the installation and opera­tional checkout of the equipment.
Preferred Location of the Outdoor Unit at the Job Site — Conduct a survey of the job site to
determine the optimum location for mounting the outdoor unit. Ov erhead obstructions, poorly ventilated areas, and areas subject to accumula­tion of debris should be avoided. The outdoor unit should be installed no closer than 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airfl ow through the outdoor unit.
Facility Prerequisites — Electrical power must be supplied to the equipment. Electrical power supplied must be adequate for proper operation of the equipment. The system must be wired and provided with circuit protection in accordance with local building codes and the National Electrical Code.
Minimum Circuit Ampacity — Electrical wiring to the equipment must be compatible and in compliance with the minimum circuit ampacity listed on the outdoor unit data label.
Maximum Fuse/Circuit Breaker Size — Circuit protection for the outdoor unit must be compat­ible with the maximum fuse/circuit breaker siz e
listed on the outdoor unit data label.
Brazing Operations — Installation of equipment may require brazing operations. Safety codes must be complied with. Safety equipment (e .g.; safety glasses, work gloves, fi re extinguisher, etc.) must be used when performing brazing operations.
4.
INSTALLING THE OUTDOOR UNIT
Slab Mount — The site selected f or a slab mount
installation requires a stable foundation and one
3
not subject to erosion. The slab should be level and anchored (if necessary) prior to placing the equipment on the slab.
Cantilever Mount — The cantilever mount should be designed with adequate safety factor to support the weight of the equipment, and for loads subjected to the mount during operation. Installed equipment should be adequately se­cured to the cantilever mount and levelled prior to operation of the equipment.
Roof Mount — The method of mounting should be designed so as not to overload roof structures nor transmit noise to the interior of the structure. Refrigerant and electrical line should be routed through suitably waterproofed openings to pre­vent water leaking into the structure.
ference between the indoor and outdoor sections should not exceed 20 feet.
Filter Dryer Installation — A fi lter dryer is provided with PS series models only and must be installed in the liquid line of the system. If the installation replaces a system with a fi lter dryer already present in the liquid line, the fi lter dryer must be replaced with the one supplied with the unit. The fi lter dr yer must be installed in strict accordance with the manufacturer’ s installation instructions.
For all other series models, installing a fi lter dryer is optional. Ho wev er , it is good installation practice to install a fi lter dryer when replacing the evaporator and/or condenser of a system. When installing, the fi lter dryer must be installed in strict accordance with the manufacturer’s installation instructions.
5. INSTALLING THE INDOOR UNIT
The indoor section should be installed before proceeding with routing of refrigerant piping. Consult the installation instructions of the indoor unit (i.e.: air handler, furnace, etc.) for details regarding installation.
6. CONNECTING REFRIGERANT TUBING BETWEEN THE INDOOR AND OUTDOOR UNIT
General — Once outdoor and indoor unit place-
ment has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices. Refr igerant tubing should be routed in a manner that minimizes the length of tubing and the number of bends in the tubing. Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation. T ubing should be kept clean of foreign debris during installation and installation of a liquid line fi lter drier is rec­ommended if cleanliness or adequacy of system evacuation is unknown or compromised. Every effort should be made by the installer to ensure that the fi eld installed refrigerant containing components of the system have been installed in accordance with these instructions and sound installation practices so as to insure reliable system operation and longevity. The maximum recommended interconnecting refrigerant line length is 75 feet, and the vertical elevation dif-
Optional Equipment — Optional equipment (e.g.: liquid line solenoid valv es, etc.) should be installed in strict accordance with the manufac­turer’s installation instructions.
7. MAKING ELECTRICAL CONNECTIONS
W ARNING:
T urn off all electrical power at the main circuit box before wiring electrical power to the outdoor unit. Failure to comply may cause severe personnel injury or death.
Wiring Diagram/Schematic — A wiring dia-
gram/schematic is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram/schematic before making an y electrical connections to the outdoor unit.
Outdoor Unit Connections — The outdoor unit requires both power and control circuit electrical connections. Refer to the unit wir ing diagram/schematic for identifi cation and location of outdoor unit fi eld wiring interfaces.
Control Circuit Wiring — The outdoor unit is designed to operate from a 24 V AC Class ll control circuit. Control circuit wiring must comply with
4
the current provisions of the National Electrical Code (ANSI/NFP A 70) and with applicab le local codes having jurisdiction.
Thermostat Connections — Thermostat con­nections should be made in accordance with the instructions supplied with the thermostat, and with the instructions supplied with the indoor equipment.
Electrical Power Wiring — Electrical power wiring shall comply with the current provisions of the National Electrical Code (ANSI/NFP A 70) and with applicable local codes having jurisdic­tion. Use of rain tight conduit is recommended. Electrical conductors shall have minimum circuit ampacity in compliance with the outdoor unit rat­ing label. The facility shall employ electrical circuit protection at a current rating no greater than that
indicated on the outdoor unit rating label.
temperature setpoint to its highest setting. Prior to applying electrical power to the outdoor unit, ensure that the unit has been properly and securely grounded, and that power supply con­nections have been made at both the facility power interface and outdoor unit.
Outdoor Unit — Ensure the outdoor coil and top of the unit are free from obstructions and debris, and all equipment access/control panels are in place.
Using extreme caution, apply power to the unit and inspect the wiring for evidence of open, shorted, and/or improperly wired circuits.
Functional Checkout:
CAUTION:
Disconnect Switch — An electrically compatible
disconnect switch must be within line of sight of the outdoor unit. This switch shall be capable of electrically de-energizing the outdoor unit.
Optional Equipment — Optional equipment requiring connection to the power or control circuits must be wired in strict accordance with current provisions of the National Electrical Code (ANSI/NFP A 70), with applicable local codes hav­ing jurisdiction, and the installation instructions provided with the equipment. Optional Equip­ment (e.g.: liquid line solenoid valves , hard start kits, low suction pressure cutout switch kit, high pressure cutout switch kit, refrigerant compres­sor crankcase heater, etc.) should be installed in strict accordance with the manufacturer’s installation instructions.
8. STARTUP AND CHECKOUT
If equipped with a compressor crankcase heater , wait 24 hour s prior to performing a function check out to allow for heating of the compressor crankcase. Failure to comply may result in damage and could cause premature failure of the system.
Indoor Blower — Set the thermostat function
switch to COOLING and the fan switch to ON. Verify that the indoor blower is operating and that airfl ow is not restricted. Set the fan switch back to AUTO.
Positive Temperature Coeffi cient Resistor (PTCR) — (select models) A PTCR is factory
installed and located on the control panel of the outdoor unit. The PTCR is a soft start device for use with reciprocating compressors. If a hard start kit is needed on this model the soft star t (PTCR) must be removed fi rst.
W ARNING:
Ensure electrical power to the unit is off prior to performing the following steps. Failure to do so may cause personal injury or death.
Air Filters — Ensure air fi lters are clean and in
place prior to operating the equipment. Thermostat — Set the room thermostat function
switch to OFF, fan switch to AUTO, and move
Low-Pressure Switch — A low-pressure switch is factory-installed in select models only. If provided, this switch is located in the suction line internal to the outdoor unit. The switch is designed to protect the compressor from a loss of charge. Under normal conditions, the switch is closed. If the suction pressure f alls below 5 psig, then the switch will open and de-energize the outdoor unit. The switch will close again once the suction pressure increases above 20 psig.
5
Comfort AlertTM Diagnostics (Select Models)
TM
The Comfort Aler t
diagnostics is a break­through innovation for troubleshooting heat pump and air conditioning system failures. The module installs easily in the electrical box of the outdoor unit near the compressor contac­tor. By monitoring and analyzing data from the
®
Copeland Scroll compressor
and the thermostat demand, the module can accurately detect the cause of electrical and system related failures without any sensors. A fl ashing LED indicator communicates the ALERT code and guides the service technician more quickly and accurately to the root cause of a problem.
NOTE: This module does not provide safety protection! The Comfort Alert module is a monitoring device and cannot shut down the compressor directly.
LED Description (See Figure 2)
POWER LED (Green): indicates voltage is pres­ent at the power connection of the module.
ALERT LED (Yellow): communicates an abnormal system condition through a unique fl ash code. The ALER T LED will fl ash a number of times consecutively, pause and then repeat the process. The number of consecutive fl ashes, defi ned as the Flash Code, correlates to a particular abnormal condition. Detailed descriptions of specifi c ALERT Flash Codes are shown in Table 1 of this manual.
TRIP LED (Red): indicates there is a demand signal from the thermostat but no current to the compressor is detected by the module. The TRIP LED typically indicates the compressor protector is open or may indicate missing supply power to the compressor.
The scroll compressor’s run (R), common (C) and start (S) wires are routed through the holes in the Comfort Alert
TM
module marked “R,” “C” and “S.” The common (C) wire need not be routed through the module for it to operate properly.
24 V AC Power Wiring — The Comfort Alert
TM
module requires a constant nominal 24 VAC power supply. The wiring to the module’s R and C terminals must be directly from the indoor unit or thermostat. The module cannot be powered by the C terminal on a defrost board or other control board without experiencing nuisance alerts.
Comfort Alert
L
C
Y
R
C
R L Y
24 Volt Field Connections
LPS
CC
Figure 3. 24VAC Comfort AlertTM
Wiring Diagram
Figure 2. Comfort Alert
6
TM
Diagnostics Module
Loading...
+ 14 hidden pages