Nordyne 13 SEER User Information

Outdoor Air Conditioner
13 SEER High Efficiency Split System
These units have been designed and tested for capacity and efficiency in accordance with A.R.I. Standards. Split System Heat Pump units are designed for use with a wide variety of fossil fuel furnaces, electric furnaces, air handlers, and evaporator coil combinations.
These instructions are primarily intended to assist qualified individuals experienced in the proper installation of heating and/or air conditioning appliances. Some local codes require licensed installation/service personnel for this type of equipment. Read all instructions carefully before starting the installation.
USER’S INFORMATION
IMPORTANT
Read this owner information to become familiar with the capabilities and use of your appliance. Keep this with literature on other appliances where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your servicing contractor .
To Operate Your Furnace for Heating —
1. Set the thermostat system switch to HEAT or AUTO and the thermostat fan switch to AUTO. (See Figure 1)
2. Set the thermostat temperature to the desired temperature level by pressing the WARMER or COOLER button. Please refer to the separate detailed user's manual for complete thermostat programming instructions. The furnace and indoor blower will cycle on and off to maintain the indoor
temperature at the desired heating level.
To Shut Off Your Air Conditioner —
Set the thermostat system switch to OFF and the thermostat fan switch to AUTO. (See Figure 1)
The system will not operate, regardless of the thermostat temperature setting.
To Operate the Indoor Blower Continuously —
OPERATING INSTRUCTIONS
To Operate Your Air Conditioner for Cooling —
1. Set the thermostat system switch to COOL or AUTO and the thermostat fan switch to AUTO. (See Figure 1)
2. Set the thermostat temperature to the desired temperature level by pressing the WARMER or COOLER button. Please refer to the separate detailed thermostat user's manual for complete instructions regarding thermostat programming. The outdoor unit and indoor blower will both cycle on and off to maintain the indoor
temperature at the desired cooling level.
Set the thermostat fan switch to ON (See Figure 1)
The indoor blower will start immediately, and will run continually until the fan switch is reset to AUTO.
FAN SWITCH
TEMPERATURE SCALES
Figure 1. Typical Thermostat
SYSTEM SWITCH
TEMPERATURE SELECTOR
The continuous indoor blower operation can be obtained with the thermostat system switch set in any position, including OFF.
The continuous indoor blower operation is typically used to circulate the indoor air to equalize a temperature unbalance due to a sun load, cooking, or fireplace operation.
To Maintain Your Air Conditioner
1. GENERAL INFORMATION
Read the following instructions completely be­fore performing the installation.
Condensing Unit Section — Each condens­ing unit is shipped with a refrigerant charge adequate to operate the outdoor section with an indoor matching coil or air handler, and 15 feet of refrigeration line.
!
CAUTION:
Be certain the electrical power to the outdoor unit and the furnace/air handler is disconnected before doing the following recommended maintenance.
1. Regularly:
a. Clean or replace the indoor air filter at the
start of each heating and cooling season, and when an accumulation of dust and dirt is visible on the air filter.
b. Remove any leaves and grass clippings
from the coil in the outdoor unit, being careful not to damage the aluminum fins.
c. Check for any obstruction, such as twigs,
sticks, etc.
2. Before Each Cooling Season:
If the furnace/air handler blower motor and the outdoor unit fan motor(s) have oil tubes at the motor bearings, apply 10 drops of SAE No. 20 motor oil to each oil tube.
!
CAUTION:
Do not over-oil, or oil motors not factory-equipped with oil tubes. The compressor is hermetically “sealed” and does not require lubrication.
3. Before Calling a Service Technician,
Be Certain:
a. The unit thermostat is properly set — see
“To Operate Your Air Conditioner for Cooling” and “To Operate Your Furnace for Heating.”
b. The unit disconnect fuses are in good
condition, and the electrical power to the unit is turned on.
2
NOTE: DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING.
Matching coils and air handlers are shipped with a small pressurized holding charge to pressurize them to keep out contaminants. To release the pressure, read the indoor section installation instructions carefully.
Liquid and Suction Lines — Refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
Field Connections for Electrical Power Supply — All wiring must comply with current
provisions of the “National Electrical Code” (ANSI C1.) and with applicable local codes having jurisdiction. The minimum size of electrical conductors and circuit protection must be in compliance with information listed on the outdoor unit data label.
2. SAFETY CONSIDERATIONS
Pressures within the System — Split system
air conditioning equipment contains liquid and gaseous refrigerant under pressure. Installation and servicing of this equipment should be ac­complished by qualified, trained personnel thor­oughly familiar with this type of equipment. Un­der no circumstances should the Homeowner attempt to install and/or service the equipment.
Labels, Tags, Precautions — When working with this equipment, follow all precautions in the literature, on tags, and on labels provided with the equipment. Read and thoroughly under­stand the instructions provided with the equip­ment prior to performing the installation and operational checkout of the equipment.
Brazing Operations — Installation of equip­ment may require brazing operations. Safety codes must be complied with. Safety equip­ment (e.g.; safety glasses, work gloves, fire extinguisher, etc.) must be used when perform­ing brazing operations.
!
WARNING:
Ensure all electrical power to the unit is off prior to installing or servicing the equipment. Failure to do so may cause personal injury or death.
3. SITE PREPARATION
Unpacking Equipment — Remove the card-
board carton and User's Manual from the equip­ment. Take care not to damage the tubing connections when removing the carton.
Inspect for Damage — Inspect the equipment for damage prior to installing the equipment at the job site. Ensure coil fins are straight and, if necessary, comb fins to remove flattened and bent fins.
Preferred Location of the Outdoor Unit at the Job Site — Conduct a survey of the job site to
determine the optimum location for mounting the outdoor unit. Overhead obstructions, poorly ventilated areas, and areas subject to accumu­lation of debris should be avoided. The outdoor unit should be installed no closer than 18 inches from the outside walls of the facility and in an area free from overhead obstructions to en­sure unrestricted airflow through the outdoor unit.
Facility Prerequisites — Electrical power must be supplied to the equipment. Electrical power supplied must be adequate for proper operation of the equipment. The system must be wired and provided with circuit protection in accor­dance with local building codes and the Na­tional Electrical Code.
Minimum Circuit Ampacity — Electrical wir­ing to the equipment must be compatible and in compliance with the minimum circuit ampacity listed on the outdoor unit data label.
Maximum Fuse/Circuit Breaker Size — Circuit protection for the outdoor unit must be compat­ible with the maximum fuse/circuit breaker size
listed on the outdoor unit data label.
4.
INSTALLING THE OUTDOOR UNIT
Cantilever Mount — The cantilever mount
should be designed with adequate safety factor to support the weight of the equipment, and for loads subjected to the mount during operation. Installed equipment should be adequately se­cured to the cantilever mount and levelled prior to operation of the equipment.
Roof Mount — The method of mounting should be designed so as not to overload roof struc­tures nor transmit noise to the interior of the structure. Refrigerant and electrical line should be routed through suitably waterproofed open­ings to prevent water leaking into the structure.
5. INSTALLING THE INDOOR UNIT
The indoor section should be installed before proceeding with routing of refrigerant piping. Consult the installation instructions of the in­door unit (i.e.: air handler, furnace, etc.) for details regarding installation.
6. CONNECTING REFRIGERANT TUBING BETWEEN THE INDOOR AND OUTDOOR UNIT
General — Once outdoor and indoor unit place-
ment has been determined, route refrigerant tubing between the equipment in accordance with sound installation practices. Refrigerant tubing should be routed in a manner that mini­mizes the length of tubing and the number of bends in the tubing. Refrigerant tubing should be supported in a manner that the tubing will not vibrate or abrade during system operation. Tub­ing should be kept clean of foreign debris during installation and installation of a liquid line filter drier is recommended if cleanliness or adequacy of system evacuation is unknown or compro­mised. Every effort should be made by the installer to ensure that the field installed refrig­erant containing components of the system have been installed in accordance with these instructions and sound installation practices so as to insure reliable system operation and lon­gevity. The maximum recommended intercon­necting refrigerant line length is 75 feet, and the vertical elevation difference between the indoor and outdoor sections should not exceed 20 feet.
Slab Mount — The site selected for a slab mount installation requires a stable foundation and one not subject to erosion. The slab should be level and anchored (if necessary) prior to placing the equipment on the slab.
Optional Equipment — Optional equipment (e.g.: filter/driers, liquid line solenoid valves, etc.) should be installed in strict accordance with the manufacturer’s installation instructions.
3
7. MAKING ELECTRICAL CONNECTIONS
!
WARNING:
Turn off all electrical power at the main circuit box before wiring electrical power to the outdoor unit. Failure to comply may cause severe personnel injury or death.
Optional Equipment — Optional equipment
requiring connection to the power or control circuits must be wired in strict accordance with current provisions of the “National Electrical Code” (ANSI C1.), with applicable local codes having jurisdiction, and the installation instructions pro­vided with the equipment. Optional Equipment (e.g.: liquid line solenoid valves, hard start kits, low suction pressure cutout switch kit, high pres­sure cutout switch kit, refrigerant compressor crankcase heater, etc.) should be installed in strict accordance with the manufacturer’s instal­lation instructions.
Wiring Diagram/Schematic — A wiring dia­gram/schematic is located on the inside cover of the electrical box of the outdoor unit. The installer should become familiar with the wiring diagram/schematic before making any electri­cal connections to the outdoor unit.
Outdoor Unit Connections — The outdoor unit requires both power and control circuit electrical connections. Refer to the unit wiring diagram/schematic for identification and loca­tion of outdoor unit field wiring interfaces.
Control Circuit Wiring — The outdoor unit is designed to operate from a 24 VAC Class ll control circuit. Control circuit wiring must com­ply with the current provisions of the “National Electrical Code” (ANSI C1.) and with applicable local codes having jurisdiction.
Thermostat Connections — Thermostat con­nections should be made in accordance with the instructions supplied with the thermostat, and with the instructions supplied with the in­door equipment.
Electrical Power Wiring — Electrical power wiring shall comply with the current provi­sions of the “National Electrical Code” (ANSI C1.) and with applicable local codes having jurisdiction. Use of rain tight conduit is rec­ommended. Electrical conductors shall have minimum circuit ampacity in compliance with the outdoor unit rating label. The facility shall employ electrical circuit protection at a cur­rent rating no greater than that indicated on
the outdoor unit rating label.
Disconnect Switch — An electrically compat­ible disconnect switch must be within line of sight of the outdoor unit. This switch shall be capable of electrically de-energizing the out­door unit.
8. STARTUP AND CHECKOUT
!
WARNING:
Ensure electrical power to the unit is off prior to performing the following steps. Failure to do so may cause personal injury or death.
Air Filters — Ensure air filters are clean and in
place prior to operating the equipment.
Thermostat — Set the room thermostat func­tion switch to OFF, fan switch to AUTO, and move temperature setpoint to its highest setting. Prior to applying electrical power to the outdoor unit, ensure that the unit has been properly and securely grounded, and that power supply con­nections have been made at both the facility power interface and outdoor unit.
Outdoor Unit — Ensure the outdoor coil and top of the unit are free from obstructions and debris, and all equipment access/control pan­els are in place.
Using extreme caution, apply power to the unit and inspect the wiring for evidence of open, shorted, and/or improperly wired circuits.
Functional Checkout:
!
CAUTION:
If equipped with a compressor crankcase heater, wait 24 hours prior to performing a function checkout to allow for heating of the compressor crankcase. Failure to comply may result in damage and could cause premature failure of the system.
4
Loading...
+ 8 hidden pages