Nordyne 10 SEER Standard Efficiency Split System Owner's Manual

Outdoor Air Conditioner
User’s Information and Installation Instructions
10 SEER Standard Efficiency Split System
These units have been designed and tested for capacity and efficiency in accordance with ARI Standards. Split System Air Conditioning units are designed for use with a wide variety of fossil fuel furnaces, electric furnaces, air handlers, and evaporator coil combinations.
These instructions are primarily intended to assist qualified individuals experienced in the proper installation of heating and/or air conditioning appliances. Some local codes require licensed installation/service personnel for this type of equipment. Read all instructions carefully before starting the installation.
USER’S INFORMATION
IMPORTANT
Read this owner information to become familiar with the capabilities and use of your appliance. Keep this with literature on other appliances where you have easy access to it in the future. If a problem occurs, check the instructions and follow recommendations given. If these suggestions don’t eliminate your problem, call your servicing contractor .
OPERATING INSTRUCTIONS
To Operate Your Air Conditioner for Cooling —
1. Set the thermostat system switch to COOL or AUTO and the thermostat fan switch to AUTO. (See Figure 1)
2. Set the thermostat temperature to the desired temperature level by pressing the WARMER or COOLER button. Please refer to the separate detailed thermostat user's manual for complete instructions regarding thermostat programming. The outdoor unit and indoor blower will both cycle on and off to maintain the indoor temperature at the desired cooling level.
To Operate Your Furnace for Heating —
1. Set the thermostat system switch to HEAT or AUTO and the thermostat fan switch to AUTO. (See Figure 1)
2. Set the thermostat temperature to the desired temperature level by pressing the WARMER or COOLER button. Please refer to the separate detailed user's manual for complete thermostat programming instructions. The furnace and indoor blower will cycle on and off to maintain the indoor temperature at the desired heating level.
To Shut Off Your Air Conditioner —
Set the thermostat system switch to OFF and the thermostat fan switch to AUTO. (See Figure 1)
The system will not operate, regardless of the thermostat temperature setting.
To Operate the Indoor Blower Continuously —
Set the thermostat fan switch to ON (See Figure 1) The indoor blower will start immediately, and will run
continually until the fan switch is reset to AUTO.
Figure 1. Typical Thermostat
The continuous indoor blower operation can be obtained with the thermostat system switch set in any position, including OFF.
The continuous indoor blower operation is typically used to circulate the indoor air to equalize a temperature unbalance due to a sun load, cooking, or fireplace operation.
To Maintain Your Air Conditioner
CAUTION:
!
Be certain the electrical power to the outdoor unit and the furnace/air handler is disconnected before doing the following recommended maintenance.
1. Regularly:
a. Clean or replace the indoor air filter at the start of each
heating and cooling season, and when an accumulation of dust and dirt is visible on the air filter.
b. Remove any leaves and grass clippings from the coil in
the outdoor unit, being careful not to damage the aluminum fins.
c. Check for any obstruction, such as twigs, sticks, etc.
!
CAUTION:
Do not over-oil, or oil motors not factory­equipped with oil tubes. The compressor is hermetically “sealed” and does not require lubrication.
2. Before Each Cooling Season:
If the furnace/air handler blower motor and the outdoor unit fan motor(s) have oil tubes at the motor bearings, apply 10 drops of SAE No. 20 motor oil to each oil tube.
2
3. Before Calling a Service Technician, Be Certain:
a. The unit thermostat is properly set — see “To Operate
Your Air Conditioner for Cooling” and “To Operate Your Furnace for Heating.”
b. The unit disconnect fuses are in good condition, and
the electrical power to the unit is turned on.
Read Your Warranty
Please read the separate warranty document completely. It contains valuable information about your system.
prior to performing the installation and operational checkout of the equipment.
3. SITE PREPARATION
Unpacking Equipment — Remove the cardboard carton
and Homeowner’s Package from the equipment.
1. GENERAL INFORMATION
Read the following instructions completely before performing the installation.
Condensing Unit Section — Each condensing unit is shipped with a refrigerant charge adequate to operate the outdoor section with an indoor matching coil or air handler and 15 feet of refrigeration line.
NOTE: DO NOT USE ANY PORTION OF THE CHARGE FOR PURGING OR LEAK TESTING.
Matching coils and air handlers are shipped with a small holding charge to pressurize them to keep out contaminants. To release the pressure, read the indoor section of the installation instructions carefully.
Liquid and Suction Lines — Refrigerant grade copper tubing should be used when installing the system. Refrigerant suction line tubing should be fully insulated.
Field Connections for Electrical Power Supply — All wiring must comply with the current provisions of the “National Electrical Code” (ANSI C1.) and with applicable local codes having jurisdiction. Size of electrical conductors and circuit protection must be in compliance with the information listed on the outdoor unit data label.
Inspect for Damage — Inspect the equipment for damage prior to installing the equipment at the job site. Ensure coil fins are straight and, if necessary, comb fins to remove flattened and bent fins.
Preferred Location of the Outdoor Unit at the Job Site — Conduct a survey of the job site to determine the
optimum location for mounting the outdoor unit. Overhead obstructions, poorly ventilated areas, and areas subject to accumulation of debris should be avoided. The outdoor unit should be installed no closer than 18 inches from the outside walls of the facility and in an area free from overhead obstructions to ensure unrestricted airflow through the outdoor unit.
Facility Prerequisites — Electrical power supplied must be adequate for proper operation of the equipment. The system must be wired and provided with circuit protection in accordance with local building codes and the National Electrical Code.
Minimum Circuit Ampacity — Electrical wiring to the equipment must be compatible and in compliance with the minimum circuit ampacity listed on the outdoor unit data label.
Maximum Fuse/Circuit Breaker Size — Circuit protection for the outdoor unit must be compatible with the maximum fuse/circuit breaker size listed on the outdoor unit data label.
2. SAFETY CONSIDERATIONS
Pressures Within the System — Split System Air
Conditioning equipment contains liquid and gaseous refrigerant under pressure. Installation and servicing of this equipment should be accomplished by qualified, trained personnel thoroughly familiar with this type of equipment. Under no circumstances should the homeowner attempt to install and/or service the equipment without proper supervision from trained and qualified service personnel.
WARNING:
!
Ensure all electrical power to the unit is off prior to installing or servicing the equipment. Failure to do so may cause personal injury or death.
Labels, Tags, Precautions — When working with this
equipment, follow all precautions in literature, on tags, and on labels provided with the equipment. Read and thoroughly understand the instructions provided with the equipment
4. INSTALLING THE OUTDOOR UNIT
Slab MountThe site selected for a slab mount installation
requires a stable foundation and one not subject to erosion. The slab should be level and anchored (if necessary) prior to placing the equipment on the slab.
Cantilever Mount The cantilever mount should be designed with adequate safety factor to support the weight of the equipment, and for loads the mount is subjected to during operation. Installed equipment should be adequately secured to the cantilever mount and levelled prior to operation of the equipment.
Roof Mount — The method of mounting should be designed so as not to overload roof structures nor transmit noise to the interior of the structure. Refrigerant and electrical lines should be routed through suitably waterproofed openings to prevent water leaking into the structure.
3
Loading...
+ 5 hidden pages