• PROPOSITION 65 WARNING: This product
contains chemicals known to the state of
California to cause cancer, birth defects or
other reproductive harm.
• This furnace is not approved for installation
in mobile homes. Installing this furnace in
a mobile home could cause fi re, property
damage, and/or personal injury.
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your
customer. This includes being able to install the product according
to strict safety guidelines and instructing the customer on how to
operate and maintain the equipment for the life of the product.
Safety should always be the deciding factor when installing this
product and using common sense plays an important role as well.
Pay attention to all safety warnings and any other special notes
highlighted in the manual. Improper installation of the furnace
or failure to follow safety warnings could result in serious injury,
death, or property damage.
These instructions are primarily intended to assist qualifi ed
individuals experienced in the proper installation of this appliance.
Some local codes require licensed installation/service personnel
for this type of equipment. Please read all instructions carefully
before starting the installation. Return these instructions to the
customer’s package for future reference.
WARNING:
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly
could result in serious injury or property
damage.
• Installation and service must be performed
by a qualifi ed installer, service agency or
the gas supplier.
• Do not store or use gasoline or other
fl ammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a
neighbors phone. Follow the gas suppliers
instructions.
• If you cannot reach your gas supplier, call
the fi re department.
DO NOT DESTROY.
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
Page 2
TABLE OF CONTENTS
SAFETY INFORMATION .............................................4
REQUIREMENTS AND CODES .................................. 4
GENERAL INSTRUCTIONS ........................................ 5
Combustion Air Quality ...........................................5
Operation of Furnace During Construction .............5
Installation in a Garage ...........................................6
Airfl ow Data ...........................................................26
Table 2 - Upfl ow/Horizontal Gas Furnaces .......26
Table 3 - Downfl ow Gas Furnaces ....................28
Figure 18 - Upfl ow/Horizontal Gas Furnace
Components ..................................35
Figure 19 - Downfl ow Gas Furnace
Components ..................................35
INSTALLATION/PERFORMANCE CHECKLIST .......36
3
Page 4
SAFETY INFORMATION
Safety markings are used frequently throughout this
manual to designate a degree or level of seriousness and
should not be ignored. WARNING indicates a potentially
hazardous situation that if not avoided, could result in
personal injury or death. CAUTION indicates a potentially
hazardous situation that if not avoided, may result in minor
or moderate injury or property damage.
WARNING:
The safety information listed below must be
followed during the installation, service, and
operation of this furnace. Failure to follow safety
recommendations could result in possible
damage to the equipment, serious per
injury or death
.
sonal
REQUIREMENTS and CODES
This furnace must be installed in accordance with
these instructions, all applicable local building codes
and the current revision of the National Fuel Gas Code
(NFPA54/ANSI Z223.1) or the Natural Gas and Propane
Installation Code, CAN/CGA B149.1.
Additional codes listed below are for reference purposes
only and do not necessarily have jurisdiction over local or
state codes. Always consult with local authorities before
installing any gas appliance.
Combustion and Ventilation Air
• US: National Fuel Gas Code (NFGC), Air for Combustion
and Ventilation
• CANADA: Natural Gas and Propane Installation Codes
(NSCNGPIC), Venting Systems and Air Supply for
Appliances
• Use only with type of gas approved for this furnace.
Refer to the furnace rating plate.
• Install this furnace only in a location and position as
specifi ed in Table 1 (page 23).
• Provide adequate combustion and ventilation air to the
furnace space as specifi ed on Pages 6 - 8.
• Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only,
as specifi ed on Pages 12 - 13.
• Never test for gas leaks with an open fl ame. Use a
commercially available soap solution to check all
connections (Page 15).
• This furnace is designed to operate with a maximum
external pressure rise of 0.5 inches of water column.
Consult Tables 2 and 3 (pages 26 - 28), and the rating
plate for the proper circulating air fl ow and temperature
rise. It is important that the duct system be designed to
handle the desired fl ow rate and temperature rise. An
improperly designed duct system can result in nuisance
shutdowns, and comfort or noise issues.
• When supply ducts carry air circulated by the furnace
to areas outside the space containing the furnace, the
return air shall also be handled by duct(s) sealed to
the furnace casing and terminating outside the space
containing the furnace.
• This furnace may be used for temporary heating of
buildings or structures under construction. See the
guidelines listed on page 5.
• A gas-fi red furnace for installation in a residential garage
must be installed as specifi ed on Page 6.
Duct Systems
• US and CANADA: Air Conditioning Contractors
Association (ACCA) Manual D, Sheet Metal and
Air Conditioning Contractors National Association
(SMACNA), or American Society of Heating,
Refrigeration, and Air Conditioning Engineers
(ASHRAE) Fundamentals Handbook
Electrical Connections
• US: National Electrical Code (NEC) ANSI/NFPA 70
• CANADA: Canadian Electrical Code CSA C22.1
Gas Piping and Gas Pipe Pressure Testing
• US: NFGC and National Plumbing Codes
• CANADA: NSCNGPIC
General Installation
• US: Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association
Inc., Batterymarch Park, Quincy, MA 02269; or American
Gas Association, 400 N. Capitol, N.W., Washington DC
20001 or www.NFPA.org
• CANADA: NSCNGPIC. For a copy, contact Standard
Sales, CSA International, 178 Rexdale Boulevard,
Etobicoke (Toronto), Ontario, M9W 1R3 Canada
Safety
• US: (NFGC) NFPA 54–1999/ANSI Z223.1 and the
Installation Standards, Warm Air Heating and Air
Conditioning Systems ANSI/NFPA 90B.
• CANADA: CAN/CGA-B149.1 and .2–M00 National
Standard of Canada. (NSCNGPIC)
4
Page 5
GENERAL INSTRUCTIONS
Combustion Air Quality
CAUTION:
Combustion air must not be drawn from a
corrosive atmosphere.
To maximize heat exchanger life, the combustion air
must be free of chemicals that can form corrosive acidic
compounds in the combustion gases. The recommended
source of combustion air is to use outdoor air. However,
the use of indoor air in most applications is acceptable
except as listed:
• If the furnace is installed in a confi ned space, it is required
that the necessary combustion air come from the
outdoors by way of attic, crawl space, air duct, or direct
opening. See Installation in a Confi ned Space section
(pages 7 - 8) for combustion air requirements.
• Installations in these locations may require outdoor air
for combustion, due to chemical exposures:
Commercial buildings
Buildings with indoor pools
Furnaces installed in laundry rooms
Furnaces installed in hobby or craft rooms
Furnaces installed near chemical storage areas
• Exposure to the following substances in the combustion
air supply may require outdoor air for combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners
Masonry acid washing materials
Operation of Furnace During Construction
CAUTION:
Failure to follow these instructions will void the
factory warranty and may signifi cantly reduce
the life or the performance of the furnace,
and/or result in other unsafe conditions. It is
the responsibility of the installing contractor
to insure these provisions are met.
Operating gas furnaces in construction environments can
cause a variety of problems with the furnace. Proper use
of commercial portable space heating equipment during
construction is recommended. This gas furnace may be
used during construction if it is not in violation of any
applicable codes and the following criteria are met:
• The installation must meet all applicable codes. The
furnace must be permanently installed according to
the instructions supplied with the furnace including
electrical supply, gas supply, duct work and venting. The
furnace must be controlled by a thermostat properly
installed according to the instructions supplied with the
furnace and thermostat. The installation must include
a properly installed fi lter in the return air system with
no by-pass air. The fi lter must be inspected frequently
and replaced when necessary.
• Combustion air must be supplied from outside the
structure and located such that dust and gases
from construction activity are not introduced into the
combustion system.
• Provisions must be made to insure that condensate
does not freeze in the furnace or condensate drain lines
during operation and during idle times; for example,
overnight if turned off. (Condensing furnaces only)
• Before occupying the structure: The fi lter must be
replaced or cleaned, the duct work must be inspected
and cleaned of any construction debris, and the furnace
must be cleaned and/or repaired if found to be dirty,
damaged, or malfunctioning in any way by a qualifi ed
HVAC technician. The furnace shall be inspected and
approved by applicable local authority even if this
requires redundant inspections.
• Serial numbers for furnaces used during construction
must be submitted in writing (fax and email also
acceptable). This information will be used to track the
long-term affects of the use during construction on
furnaces. Proof of this submittal shall be available for
the fi nal inspection of the furnace prior to occupancy.
• This furnace is designed to operate with return air
temperatures in ranges normally found in occupied
residences, including setbacks. Minimum continuous
return temperature must not be below 60° F (15° C).
Occasionally a temporary return temperature of 55° F
(12° C) is acceptable. However, operation with a return
temperature below 55° F (12° C) is not allowed.
5
Page 6
Installation in a Garage
WARNING:
Do not place combustible materials on or
against the furnace cabinet or within 6 inches
of the vent pipe. Do not place combustible
materials, including gasoline or any other
fl ammable vapors and liquids, in the vicinity
of the furnace.
This Gas-fi red furnace may be installed in a residential
garage with the provision that the burners and igniter
are located no less than 18 inches (457mm) above the
fl oor. The furnace must be located or protected to prevent
physical damage by vehicles.
Heating Load
The furnace should be sized to provide the design heating
load requirement. Heating load estimates can be made
using approved methods available from Air Conditioning
Contractors of America (Manual J); American Society of
Heating, Refrigerating, and Air Conditioning Engineers;
or other approved engineering methods. Excessive
oversizing of the furnace could cause the furnace
and/or vent to fail prematurely. In addition, the ductwork
should be appropriately sized to the capacity of the
furnace to ensure its proper airfl ow rating. For installations
above 2,000 ft., the furnace should have a sea level input
rating large enough that it will meet the heating load after
deration for altitude.
Clearances to Combustible Materials
This furnace is Design Certifi ed in the U.S. and Canada
by CSA International for the minimum clearances to
combustible materials listed in Table 1 (page 23). To obtain
model number and specifi c clearance information, refer
to the furnace rating plate, located inside of the furnace
cabinet.
COMBUSTION AIR REQUIREMENTS
General Information
WARNING:
Furnace installation using methods other than
those described in the following sections must
comply with the National Fuel Gas Code (NFGC)
and all applicable local codes.
• Instructions for determining the adequacy of an
installation can be found in the current revision of the
NFGC (ANSI Z223.1 / NFPA54). Consult local codes for special requirements. These requirements are for
US installations as found in the NFGC.
• The requirements in Canada (B149.1) are structured
differently. Consult with B149.1 and local code offi cials
for Canadian installations.
• Additional reference information for US and Canadian
installations can be found in the Combustion and
Ventilation Air section (page 4).
Provisions must be made during the installation of
this furnace that provide an adequate supply of air for
combustion.
CAUTION:
Exhaust fans, clothes dryers, fi replaces and
other appliances that force air from the house
to the outdoors can create a negative pressure
inside the house, resulting in improper furnace
operation or unsafe conditions such as fl ame roll
out. It is imperative that suffi cient air exchange
with the outdoors is provided to prevent
depressurization. Additional information about
how to test for negative pressure problems can
be found in the NFGC.
Access for positioning and servicing the unit must be
considered when locating unit. The minimum required
clearance from the front of the unit for servicing is 24
inches. The minimum required clearance for positioning
is 30 inches from the front of the unit. The recommended clearance from the front of the unit is 36 inches. The
need to provide clearance for access to panels or doors
may require clearance distances over and above the
requirements.
6
NOTE: Air openings on top of the furnace and openings in
closet doors or walls must never be restricted. If the furnace
is operated without adequate air for combustion, the fl ame
roll-out switch will open, turning off the gas supply to the
burners. This safety device is a manually reset switch.
DO NOT install jumper wires across these switches
to defeat their function or reset a switch without
identifying and correcting the fault condition.
If a switch must be replaced, use only the correct sized
part specifi ed in the Replacement Parts List provided
online.
Page 7
Installation In A Confi ned Space
A confi ned space is an area with volume less than 50
cubic feet per 1,000 Btuh of the combined input rates of
all appliances drawing combustion air from that space.
Furnace closets, small equipment rooms and garages are
confi ned spaces. Furnaces installed in a confi ned space
which supply heated air to areas outside the space must
draw return air from outside the space and must have the
return air ducts tightly sealed to the furnace.
The required sizing of these openings is determined by
whether inside or outside air is used to support combustion,
the method by which the air is brought to the space, and
by the total input rate of all appliances in the space. In
all cases, the minimum dimension of any combustion air
opening is 3 inches.
Outdoor Air Using Vertical Ducts
If combustion air is taken from outdoors through vertical
ducts, the openings and ducts must have a minimum
free area of one square inch per 4,000 Btuh of total
appliance input. In installations drawing combustion air
from a ventilated attic, both air ducts must extend above
the attic insulation (Figure 1).
Ventilation Louvers at
each end of attic
Vent or
Chimney
Water
Heater
Attic
Insulation
Furnace
Outlet Air Duct must
be at least 1 sq. in.
per 4,000 Btuh of
total input rating.
Inlet and Outlet
Ducts must
extend above
attic insulation.
Inlet Air Duct must
be at least 1 sq. in.
per 4,000 Btuh of
total input rating.
Outdoor Air Using Horizontal Ducts
If combustion air is taken from outdoors through horizontal
ducts, the openings and ducts must have a minimum free
area of one square inch per 2,000 Btuh of total appliance
input (Figure 2).
opening to
outside must
be at least 1
sq. in. per 2,000
Btuh of total
-
-
-
-
-
-
input rating.
-
-
-
Round Duct
Diameter
Figure 2. Combustion Air Drawn from Outside
Through Horizontal Ducts
Outdoor Air from a Crawl Space or Vented Attic
When the openings can freely exchange air with the
outdoors, each opening shall have a minimum free area
of 1 square inch per 4,000 Btuh of total appliance input.
The openings shall exchange directly, or by ducts, with
the outdoor spaces (crawl or attic) that freely exchange
with the outdoors (Figure 3).
Ventilation louvers
Chimney
Attic
Insulation
Water
Heater
Vent or
at each end of attic
Furnace
Outlet air duct must be
at least 1 sq. in. per
4,000 Btuh of total
input rating. Must
extend above attic
insulation
Inlet air duct must be at
least 1 sq. in. per 4,000
Btuh of total input rating.
Crawl Space
Ventilated Louvers for
unheated crawl space
Figure 3. Combustion Air Drawn from a Crawl
Space or Vented Attic
7
Page 8
Air Directly Through An Exterior Wall
If combustion air is provided directly through an exterior
wall, the two openings must each have free area of at
least one square inch per 4,000 Btuh of total appliance
input (Figure 4).
to outside must be at
least 1 sq. in. per
4,000 Btuh of total
input rating.
Round Duct
Diameter
Figure 4. Combustion Air Drawn from Outside
Through an Exterior Wall
Alternate Method of Providing Air from Outside:
If acceptable under local Codes, it is permitted to
provide outside air using one opening (See NFGC).
Air From Inside
If combustion air is taken from the heated space, the two
openings must each have a free area of at least one square
inch per 1,000 Btuh of total input of all appliances in the
confi ned space, but not less than 100 square inches of
free area (Figure 5). For example, if the combined input
rate of all appliances is less than or equal to 100,000
Btuh, each opening must have a free area of at least 100
square inches. If the combined input rate of all appliances
is 120,000 Btuh, each opening must have a free area of
at least 120 square inches.
Vent or
Chimney
NOTES:
Each opening must
be at least 100 sq. in.
or 1 sq. in. per 1,000
Btuh of total input rating,
whichever is greater.
Openings must start at
no more than 12 inches
from the top and bottom
of the enclosure.
Generally, confi ned spaces must have two openings
in the space for combustion air. One opening must
be within 12 inches of the ceiling, and the other
must be within 12 inches of the fl oor. However, an
alternative method recently adopted by the NFGC
uses one opening within 12 inches of the top of the
space. This method may be used if it is acceptable
to the local codes.
The following conditions must be met:
1. The opening must start within 12” of the top of the
structure and connect with the out of doors through
vertical or horizontal ducts or be ducted to a crawl
or attic space that connects with the out of doors.
2. The opening must have a minimum free area of 1
sq. in. per 3,000 Btu per hour of the total input rating
of all equipment located in the enclosure.
3. The free area must not be less than the sum of all
the areas of the vent connectors in the enclosure.
8
Installation In An Unconfi ned Space
An unconfi ned space is an area including all rooms not
separated by doors with a volume greater than 50 cubic
feet per 1,000 Btuh of the combined input rates of all
appliances which draw combustion air from that space.
In general, a furnace installed in an unconfi ned space will
not require outside air for combustion. However, in homes
built for energy effi ciency (low air change rates), it may
be necessary to provide outside air to ensure adequate
combustion and venting, even though the furnace is located
in an unconfi ned space. See example.
Example:
A space with a water heater rated at 45,000 Btuh
input and a furnace rated at 75,000 Btuh requires a
volume of 6,000 cubic feet [50 x (45 + 75) = 6,000] to
be considered unconfi ned. If the space has an 8 foot
ceiling, the fl oor area of the space must be 750 square
feet (6,000 / 8 = 750).
Page 9
FURNACE INSTALLATION
General Requirements
*SA series gas furnaces are shipped ready for installation
in the upfl ow or horizontal right or left positions. Only
the *SK series gas furnace may be used for downfl ow
operation.
• The furnace must be leveled at installation and attached
to a properly installed duct system. See Table 1 (page
23) for the required clearances needed to move the
furnace to its installation point (hallways, doorways,
stairs, etc).
• The furnace must be installed so that all electrical
components are protected from water.
• The furnace must be installed upstream from a
refrigeration system.
• Additional reference information for US and Canadian
installations can be found in the General Installation
section (page 4).
Upfl ow Installation
The *SA series gas furnace may be installed directly on
combustible wood fl ooring or supports. This furnace
must not be installed directly on carpeting, tile, or
any combustible material other than wood fl ooring.
For venting guidelines and specifi cations, see Venting
Requirements section (pages 12 - 13).
Access for positioning and servicing must be considered
when locating the unit. See Table 1 (page 23) for clearance
specifi cations.
If the furnace is to be installed in an attic, it is required that
a drip pan be placed under the furnace. If the installation
is on a combustible platform (Figure 6), it is recommended
that the drip pan extend at least 12 inches past the top
and front of the furnace.
WARNING:
The furnace must not be installed directly on
carpeting, tile, or any combustible material other
than wood fl ooring.
It is recommended for further reduction of fi re hazard
that cement board or sheet metal be placed between the
furnace and the combustible fl oor and extend 12 inches
beyond the front of the door and top of the furnace.
Note: Line Contact
Is Permissible
Type “B” Vent
Gas Inlet
Side Return Air Inlet
*SA series gas furnaces are shipped with the bottom
panel installed (Figure 15, page 24). If the upfl ow furnace
is installed with side return air, the bottom panel must not
be removed.
Bottom Return Air Inlet
*SA series gas furnaces are shipped with the bottom
panel installed. If the upfl ow furnace is installed with
bottom return air, the bottom panel must be removed.
See Bottom Panel Removal on page 10.
Horizontal Installation
The *SA series gas furnace can be installed horizontally
in an attic, basement, crawl space or alcove (Figure 6).
It can also be suspended from a ceiling in a basement
or utility room in either a right to left airfl ow or left to right
airfl ow as shown in Figure 7.
*SA series furnaces are shipped with the bottom panel
installed. If the furnace is installed horizontally, remove
the bottom panel from the furnace before attaching the
duct system. See Bottom Panel Removal on page 10.
If the furnace is to be suspended from the ceiling, it will
be necessary to use steel straps around each end of the
furnace. The straps should be attached to the furnace
with sheet metal screws and to the rafters with bolts. The
furnace could also be suspended by an angle iron frame
bolted to the rafters (Figure 7).
Coil Plenum
Electrical Supply
Connection
Combustible
Platform
Figure 6. *SA Horizontal Installation on a Platform
Figure 7. *SA Horizontal Installation
Suspended in Attic or Crawl Space
9
Page 10
Bottom Panel Removal
To remove the bottom panel (Figure 8) from the upfl ow
furnace, perform the following steps:
1. Remove the blower door (1) from bottom of furnace.
2. Disconnect the wiring harness (2) from the
connector.
3. Remove two screws (3) securing the blower assembly
(4) to the furnace.
4. Carefully pull the blower assembly (4) out thru the
front of the furnace.
5. Remove all screws (5) securing bottom panel (6) to
bottom of furnace and front brace (7).
6. Lift up and slide bottom panel (6) out through front of
furnace.
7. Reinstall the blower assembly (4) in reverse order it
was removed.
Bottom Panel
1
Downfl ow Installation
The *SK series gas furnace is certifi ed for installation on
combustible fl ooring. This furnace must not be installed
directly on carpeting, tile, or any combustible material
other than wood fl ooring. For venting guidelines and
specifi cations, see Venting Requirements section (page
12).
WARNING:
Failure to install the downfl ow sub-base kit
may result in fi re, property damage or personal
injury.
To install the furnace on combustible fl ooring, a special
sub-base is required. Downfl ow sub-base kits are factory
supplied accessories and are listed according to the cabinet
letter of the furnace. For ‘A’ size cabinets use Sub-Base
kit #902974 only. For ‘B’, ‘C’, and ‘D’ size cabinets use
Kit #904911. Please follow the instructions provided with the kit.
6
WARNING:
The downfl ow sub-base kit must not be installed
directly on carpeting, tile, or any combustible
material other than wood fl ooring.
A downfl ow sub-base kit is not necessary if the furnace
7
Blower Assembly
5
3
3
2
4
is installed on a factory or site-built cased air conditioning
coil. However, the plenum attached to the coil casing
must be installed so that its surfaces are at least 1” from
combustible construction.
Installation on a concrete slab.
1. Create an opening in the fl oor according to the
dimensions in Figure 9.
2. Position the plenum and the furnace as shown in
Figure 10 (page 11).
Opening in concrete floor
“A”
“B”
Figure 8. Removal of Bottom Panel
10
*SK MODEL
NUMBERS:
054-23A
072-24B
090-24B
108-35C
126-45D
Figure 9. Cutout Dimensions
Dimension
“A”
13
¼
16
⅝
16
⅝
20
⅛
23
⅝
Dimension
“B”
19
19
19
19
19
¼
¼
¼
¼
¼
Page 11
Concrete
Floor
Figure 10. Furnace on a Concrete Slab
Furnace
Sheet
Metal
Plenum
WARNING:
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system
being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed with each individual appliance connected to the venting
system being placed in operation, while all other appliances connected to the venting system
are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National
Fuel Gas Code, ANSI Z223. 1/NFPA 54 or the CSA B149.1, Natural Gas and Propane Installation
Codes and these instructions. Determine that there is no blockage or restriction, leakage,
corrosion and other defi ciencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space
in which the appliance(s) connected to the venting system are located and other spaces
of the building.
4. Close fi replace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on
any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at
maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust
the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after
5 minutes of main burner operation. Use the fl ame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must
be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes.
9. After it has been determined that each appliance connected to the venting system properly
vents when tested as outlined above, return doors, windows, exhaust fans, fi replace
dampers and any other gas-fi red burning appliance to their previous conditions of use.
11
Page 12
VENTING REQUIREMENTS
WARNING:
Upon completion of the furnace installation,
carefully inspect the entire fl ue system both
inside and outside the furnace to assure it is
properly sealed. Leaks in the fl ue system can
result in serious personal injury or death due
to exposure of fl ue products, including carbon
monoxide.
• This furnace must be vented in compliance with
the current revision of the National Fuel Gas Code
(ANSI-Z223.1/NFPA54) and the instructions
provided below. Consult local codes for special
requirements.
• In Canada, venting shall conform to the requirements of
the current (CAN/CGA B149.1 or .2) installation codes.
Consult local codes for special requirements.
• Additional reference information for US and Canadian
installations can be found in the Combustion and
Ventilation Air section (page 4).
Category I Venting
This furnace is listed as a Category I vented appliance.
Category I furnaces generally operate with a slight
negative pressure (draft) and must be vented vertically or
near vertical. Additionally it is important to guard against
excessive condensation.
• Category I furnace installations must be connected to a
factory built chimney or vent complying with a recognized
standard, or a masonry or concrete chimney lined with
a lining material acceptable to the authority having
jurisdiction.
WARNING:
Venting into an unlined masonry chimney or
concrete chimney is prohibited. This may result
in improper draft and excess condensation
forming in the chimney.
• This furnace may be vented with a dedicated venting
system or common vented with other Category I
appliances. The vent system dimensions and material
must conform to the NFGC or local Codes. Generally,
this means using Type B vent pipe or a lined masonry
chimney. When consulting the vent sizing tables in the
NFGC, the MAX capacity of the vent must be greater
than the furnaces high fi re rate. The MIN capacity must
be lower than the low fi re rate. If the venting system is
inappropriate for the furnace, the venting system will need
to be modifi ed to comply with NFGC or local codes.
• The venting system should be designed to have the
minimum number of elbows or turns. All horizontal runs
shall slope upwards from the furnace at ¼ inch per
running foot of vent. Supports for the vent pipe must
be installed a minimum of every fi ve feet along the vent
run to ensure no displacement after installation.Under
no circumstances shall any portion of the vent system
extend into or pass through any return air duct, supply
air duct, or plenum.
• Single wall vent connectors may be used under the
limited capacity ranges found in the vent sizing tables.
It is recommended that Type B double wall vent be
used for the connector whenever possible. An existing
masonry chimney should be inspected and relined if
necessary.
• In the U.S., this furnace must never be vented to
a chimney or fl ue that services a fi replace or other
appliance designed to burn solid fuel. If the furnace
vent is to be connected to a chimney serving a fi replace,
the fi replace must be sealed off from the chimney. In
Canada, common venting with a fi replace is permitted.
Consult B149.1 and your local code authority.
• Single wall metal vertical vents shall not be used for
Category I venting. The furnace vent, if metal, may be
insulated if local codes allow. Any part of the vent system,
metal vent only, not exposed to weather, but which are
exposed to temperatures below 35° F (1°C) must be
insulated to prevent condensation. All vent insulation
shall be foil backed fi berglass of one inch minimum
thickness.
• Sheet metal fasteners should be used to secure the vent
pipe to the furnace fl ue. However, the NFGC lists that
alternative vent products may be attached according to
the vent manufacturers instructions.
• When an existing furnace is removed from a vent system
serving other appliances, the existing vent system may no
longer be sized to properly vent the remaining appliances.
An improperly sized venting system can result in the
formation of condensate, leakage, or spillage. The
existing vent system should also be checked to make
sure it remains in compliance with NFGC. If it isn’t, the
vent system must be brought into compliance before
installing the furnace.
12
Page 13
Horizontal Venting
CIRCULATING AIR REQUIREMENTS
WARNING:
Horizontal vent systems must be sealed with
a high temperature sealant that can withstand
temperatures of 450° F. Recommended sealants:
Dow Corning Sealant 736 RTV; GE 106 RTV;
High Tech Ind., High TEMP RED.
This furnace is not approved for horizontal venting
without the use of an add-on power venter. Power venters
establish negative pressure in the vent piping and the
furnace operates as if connected to a Category I vertical
vent. The power venter is only for use when exhausting
through an exterior wall.
The power venter must be installed according to the
instructions provided by the power venter manufacturer
and applicable requirements of local codes. For Canadian
installations please refer to the Canadian Installation Code
(CAN/CGA-B149.1 or 2) and/or local codes.
The outlet of the vent must be at least 12 inches above
the highest expected snow accumulation.
Flexible Vent Systems
Flexible venting systems are approved for use providing
they are listed for the application and meet all local Code
requirements. These systems are primarily used to line
existing masonry chimneys. They must be sized to the
application according to the sizing tables in the National
Fuel Gas Code, including the required 20% reduction in
maximum capacity.
Flexible venting systems are permitted to be used as the
vent connector. However, great care must be taken to
ensure that there are no sags in the venting system which
could accumulate condensate. The fl exible vent system
must be supported at no more than 5 foot intervals and
maintain a minimum slope of ¼ inch per foot of horizontal
run.
WARNING:
Do not allow combustion products to enter the
circulating air supply. Failure to prevent the
circulation of combustion products into the
living space can create potentially hazardous
conditions including carbon monoxide
poisoning that could result in personal injury
or death.
All return ductwork must be secured to
the furnace with sheet metal screws. For
installations in confi ned spaces, all return
ductwork must be adequately sealed. When
return air is provided through the bottom of the
furnace, the joint between the furnace and the
return air plenum must be air tight.
The surface that the furnace is mounted on must
provide sound physical support of the furnace
with no gaps, cracks or sagging between the
furnace and the fl oor or platform.
Return air and circulating air ductwork must
not be connected to any other heat producing
device such as a fi replace insert, stove, etc.
This may result in fi re, explosion, carbon
monoxide poisoning, personal injury, or
property damage.
Plenums and Air Ducts
• Plenums and air ducts must be installed in accordance
with the Standard for the Installation of Air Conditioning
and Ventilating Systems (NFPA No. 90A) or the
Standard for the Installation of Warm Air Heating and
Air Conditioning Systems (NFPA No. 90B). Additional
reference information for US and Canadian installations
can be found in the Duct Systems section (page 4).
• Table 2 and Table 3 (pages 26-28) contain the airfl ow and
temperature rise data. If the maximum airfl ow is 1,600
CFM or more, it is recommended that two openings be
used for return air on upfl ow furnaces. Downfl ow furnaces
can only use one return opening.
• It is recommended that the outlet duct contain a removable
access panel. The opening should be accessible when
the furnace is installed in service and shall be of a size
that smoke or refl ected light may be observed inside
the casing to indicate the presence of leaks in the heat
exchanger. The cover for the opening shall be attached
in such a manner as to prevent leaks.
• If outside air is used as return air to the furnace for
ventilation or to improve indoor air quality, the system
must be designed so that the return air is not less than
60° F (15° C) during operation. If a combination of indoor
and outdoor air is used, the ducts and damper system
13
Page 14
must be designed so that the return air supply to the
furnace is equal to the return air supply under normal,
indoor return air applications.
• When a cooling system is installed which uses the
furnace blower to provide airfl ow over the indoor coil,
the coil must be installed downstream (on the outlet
side) of the furnace or in parallel with the furnace.
• If a cooling system is installed in parallel with the
furnace, a damper must be installed to prevent chilled air
from entering the furnace and condensing on the heat
exchanger. If a manually operated damper is installed,
it must be designed so that operation of the furnace is
prevented when the damper is in the cooling position
and operation of the cooling system is prevented when
the damper is in the heating position.
Supply Air Connections
The supply air must be delivered to the heated space by
duct(s) secured to the furnace casing, running full size
and without interruption. It is good practice to seal all
connections and joints with industrial grade sealing tape
or liquid sealant. Requirements for sealing ductwork vary
from region to region. Consult with local codes for requirements specifi c to your area.
Upfl ow and Horizontal Furnaces
To attach the supply air duct to the furnace, bend the
furnace fl anges (Figure 15, page 24) upward 90° with a pair
of wide duct pliers. Position the duct on top of the furnace
and secure together with sheet metal screws. The screws
must penetrate the sheet metal casing and furnace fl ange.
Tape or seal all seams if required by local code.
Downfl ow Furnaces
To attach the supply air duct to the downfl ow furnace,
position the furnace over the duct and secure together
with sheet metal screws. The screws must penetrate the
duct and furnace casing.
Return Air Connections
In applications where the supply ducts carry heated air
to areas outside the space where the furnace is installed,
the return air must be delivered to the furnace by duct(s)
secured to the furnace casing, running full size and without
interruption. It is good practice to seal all connections and
joints with industrial grade sealing tape or liquid sealant.
Requirements for sealing ductwork vary from region to
region. Consult with local codes for requirements specifi c
to your area.
Upfl ow and Horizontal Furnaces
For upfl ow installations, the return air ductwork may
be connected to the left side, right side, or bottom. The
bottom panel (Figure 15, page 24) must be installed for
left or right return air. NOTE: Do not use the back of the
furnace for return air.
Side Return Installations
To attach the return air duct to the left or right side of the
furnace, punch out the four knockouts (Figure 15) from
the preferred side of the furnace. Using sharp metal cutters, cut an opening between all four knockouts to expose
the blower assembly. Position the return air duct over
the opening in the side and secure together with sheet
metal screws. The screws must penetrate the duct and
furnace casing.
WARNING:
The solid base of the furnace must be in
place when the furnace is installed with side
return air ducts. Removal of all or part of the
base could cause circulation of combustible
products into the living space and create
potentially hazardous conditions, including
carbon monoxide poisoning that could result
in personal injury or death.
Bottom Return Installations
The bottom panel (Figure 15) must be removed from the
bottom of the furnace for bottom return air. If bottom panel is
still installed, go to page 9 for removal instructions. Position
the furnace over the return air duct and secure together
with sheet metal screws. The screws must penetrate the
duct and furnace casing.
Downfl ow Furnaces
To attach the return air duct to the furnace, bend the furnace
fl anges (Figure 16, page 25) upward 90° with a pair of
wide duct pliers. Position the duct on top of the furnace
and secure together with sheet metal screws. The screws
must penetrate the sheet metal casing and furnace fl ange.
Tape or seal all seams if required by local code.
Acoustical Treatments
Damping ducts, fl exible vibration isolators, or pleated
media-style fi lters on the return air inlet of the furnace
may be used to reduce the transmission of equipment
noise eminating from the furnace. These treatments can
produce a quieter installation, particularly in the heated
space. However, they can increase the pressure drop in
the duct system. Care must be taken to maintain the proper
maximum pressure rise across the furnace, temperature
rise and fl ow rate. This may mean increasing the duct
size and/or reducing the blower speed. These treatments
must be constructed and installed in accordance with
NFPA and SMACNA construction standards. Consult
with local codes for special requirements.For best sound
performance, be sure to install all the needed gaskets and
grommets around penetrations into the furnace, such as
for electrical wiring.
14
Page 15
GAS SUPPLY AND PIPING
All gas piping must be installed in compliance with local
codes and utility regulations.
In the absence of local codes the gas line installation must
comply with the latest edition of the National Fuel Gas
Code (ANSI Z223.1) or (CAN/CGA B149.1 or .2) Installation Codes. Additional reference information for US and
Canadian installations can be found in the Gas Piping and
Gas Pipe Pressure Testing section (page 4).
Shut-Off Valve
(See Note)
Dripleg
Upflow Models - Left Side Entry
Automatic
Gas Valve
(with manual
shut-off)
Manifold
IMPORTANT NOTES:
• Some local regulations require the installation of a manual
main shut-off valve and ground joint union external
to the furnace as depicted in Figure 11. The shut-off
valve should be readily accessible for service and/or
emergency use. Consult the local utility or gas supplier
for additional requirements regarding placement of the
manual main gas shut-off.
• Gas piping must never run in or through air ducts,
chimneys, gas vents, or elevator shafts.
• Compounds used on threaded joints of gas piping must
be resistant to the actions of LP propane gas.
• The main gas valve and main power disconnect to the
furnace must be properly labeled by the installer in case
emergency shutdown is required.
• Flexible gas connectors are not recommended for this
type of furnace but may be used if allowed by local
jurisdiction. The fl exible gas connector must be agency
approved and certifi ed for the type of gas being used.
Only new fl exible connectors may be used. Do not reuse
old fl exible gas connectors.
• A drip leg should be installed in the vertical pipe run to
the unit (Figure 11).
Table 7 (page 31) lists gas pipe capacities for standard
pipe sizes as a function of length in typical applications
based on nominal pressure drop in the line.
The furnace may be installed for either left or right side gas
entry. When connecting the gas supply, provide clearance
between the gas supply line and the entry hole in the
furnace casing to avoid unwanted noise and/or damage
to the furnace. A typical gas service hookup is shown in
Figure 11.
Leak Check
WARNING:
FIRE OR EXPLOSION HAZARD
Never test for gas leaks with an open fl ame.
Check all connections using a commercially
available soap solution. A fi re or explosion
may result causing property damage, personal
injury or loss of life. Failure to follow the safety
warnings exactly could result in serious injury,
death or property damage.
Ground Joint
Union
Burner
Assembly
Downflow Models - Right Side Entry
Automatic
Gas Valve
(with manual
shut-off)
2 Street
Elbows
Burner
Assembly
Note: Some utilities require Shut- Off Valve to be 4 to 5 feet above floor.
Manifold
Shut-Off Valve
(See Note)
Dripleg
Ground Joint
Union
Figure 11. Typical Gas Connection
After the gas piping to the furnace is complete, all
connections must be tested for gas leaks. This includes
pipe connections at the main gas valve, emergency shutoff
valve and fl exible gas connectors (if applicable). The soap
and water solution can be applied on each joint or union
using a small paintbrush. If any bubbling is observed,
the connection is not sealed adequately and must be
retightened. Repeat the tightening and soap check process
until bubbling ceases.
IMPORTANT NOTE: When pressure testing gas supply
lines at pressures greater than 1/2 psig (14 inch W.C.),
the gas supply piping system must be disconnected
from the furnace to prevent damage to the gas control
valve. If the test pressure is less than or equal to 1/2
psig (14 inch W.C.), close the manual shut-off valve.
High Altitude Application
High altitude conversion with this furnace depends on the
installation altitude and the heating value of the gas. The
installation of this furnace at altitudes above 2,000 feet
must meet the requirements of the National Fuel Gas
Code or local jurisdiction. In Canada, the requirements for
high altitude are different and governed by CGA B149.1.
Please consult your local code authority.
15
Page 16
WARNING:
The reduction of input rating necessary for high
altitude installation may only be accomplished
with factory supplied orifi ces. Do not attempt
to drill out orifi ces in the fi eld. Improperly
drilled orifi ces may cause fi re, explosion,
carbon monoxide poisoning, personal injury
or death.
The furnaces are shipped from the factory with orifi ces
and gas regulator settings for natural gas operation at sea
level altitudes. At 2000 feet, the NFGC requires that this
appliance be derated 4% for each 1,000 feet of altitude. For
example, at 2,000 feet the input needs to be reduced 8%
, at 3,000 feet (12%) and etc. This deration is in reference
to the input rate and gas heating value at sea level.
To derate the furnace requires knowing the heating value of
the gas at the installation site. Heating values at particular
job sites vary for two reasons:
1. The chemical mixture of the gas varies from region
to region and is expressed as the “sea level heating
value”.
2. The heating value varies by altitude. For this reason,
especially in high altitude areas, the local gas utility
specifi es the heating value at the residence’s gas
meter as the “local value”.
For added fl exibility, two tables have been provided for
natural gas installations with HIGH or LOW heating
values at sea level. Tables 10 and 11 (page 33) contain
the orifi ce sizes and manifold pressure to use at various
altitudes. Table 10 (High) is for natural gas installations
with a heating value of more than 1,000 Btu per cubic foot
and Table 11 (Low) is for less than 1,000 Btu per cubic
foot.To determine which table to use:
1. Consult the local utility for the local heating value at
your installation site.
2. From Table 9 (page 32), fi nd your local heating value
as supplied by the utility company. Follow down the
column and stop at your altitude level.
3. If your sea level heating value is HIGH, use Table 10
or if it’s LOW, use Table 11 (page 33).
After changing the regulator pressure or the orifi ces, it is
required that you measure the gas input rate. This may be
accomplished in the usual way, by clocking the gas meter
and using the local gas heating value. See Verifying and
Adjusting the Input Rate section (page 18).
IMPORTANT NOTE: Observe the action of the burners
to make sure there is no yellowing, lifting or fl ashback
of the fl ame.
Conversion to LP/Propane
WARNING:
The furnace was shipped from the factory
equipped to operate on natural gas. Conversion
to LP/propane gas must be performed by
qualifi ed service personnel using a factory
supplied conversion kit. Failure to use the
proper conversion kit can cause fi re, explosion,
property damage, carbon monoxide poisoning,
personal injury, or death.
IMPORTANT NOTE: When converting a low NOx furnace
from Natural gas to LP/propane gas, it is necessary
to remove the NOx Baffl es from the furnace.
Conversion to LP/propane is detailed in the installation
instructions provided with the conversion kit. Generally,
this will require the replacement of the burner orifi ces and
the spring found under the cap screw on the pressure
regulator. In the U.S. if installation is above 2,000 ft., refer
to Table 8 (page 32) to determine the correct orifi ce size
and manifold pressure. When conversion is complete, verify
the manifold pressure and input rate are correct as listed
in the Tables. Approved conversion kits are listed below:
• The United States LP/Propane Gas Sea Level and High
Altitude Conversion Kit (P/N 904914) is for LP/propane
conversion in the United States at altitudes between
zero and 10,000 ft. above sea level. Please follow the instructions provided with the kit.
• The Canadian LP/Propane Gas Sea Level and High
Altitude Conversion Kit (P/N 904915) is for LP/propane
conversions in Canada at altitudes between zero and
4,500 ft. above sea level. Please follow the instructions
Type of Gas: .........................................Natural Gas
Local Heating Value of Gas: ............................750
From Table 9, fi nd 750 and follow down the column,
stop at the 5,000 feet row. The heating value listed is
LOW. Table 11 will be used to determine orifi ce size and
manifold pressure.
16
Page 17
ELECTRICAL WIRING
WARNING:
To avoid electric shock, personal injury, or death,
turn off the electric power at the disconnect
or the main service panel before making any
electrical connections.
• Electrical connections must be in compliance with all
applicable local codes and the current revision of the
National Electric Code (ANSI/NFPA 70).
• For Canadian installations the electrical connections
and grounding shall comply with the current Canadian
Electrical Code (CSA C22.1 and/or local codes).
• Additional reference information for US and Canadian
installations can be found in the Electrical Connections
section (page 4).
IMPORTANT NOTE: If replacing any of the original wires
supplied with the furnace, the replacement wire must
be copper wiring and have a temperature rating of at
least 105° F (40° C). For electrical requirements, refer
to the furnace nameplate or Table 4 (page 29).
Low Voltage Wiring
The thermostat must be installed according to the
instructions supplied by the thermostat manufacturer.
Low voltage connections (24 VAC) from the thermostat
are wired to the terminal strip on the integrated control
in the furnace. See Figure 12 for proper connections for
heating only (two-wire) and heating/cooling (four-wire)
applications. Recommended minimum wire gauge for
thermostat wiring is shown in Table 4.
The thermostat must not be installed on an outside wall or
any other location where its operation may be adversely
affected by radiant heat from fi replaces, sunlight, or lighting
fi xtures, and convective heat from warm air registers or
electrical appliances.
A/C CONDENSING UNIT
CONDENSING UNIT
CONTROL BOX
EXPANSION PORT
(MOTOR CONNECTION)
COM
ROOM
THERMOSTAT
Connect
R & W
For Heating
Only
NOTE: The “Y” terminal
on the control board
must be connected to the
thermostat for proper
cooling mode operation.
FIELD WIRING
LOW VOLTAGE
CONNECTION
R
C
Y
G
W
NEUTRAL LEADS
3 AMP
FUSE
63
9
5
8
4
7
6
3
2
5
1
4
NEUTRALS
RCYGW
2
1
24V
SPEED
SELECT
FAN
HUM
STATUS
COOL
HEAT
FLAME
BLOWER
OFF
DELAY
XFMR
HIGH
EAC
MH
ML
L1
ELECTRONIC AIR CLEANER
HUMIDIFIER TAP
RED
GREEN
YELLOW
180
120
90
60
LOW
MOTOR SPEED TAPS
(NOT USED)
Figure 12. Low Voltage Field, Four-wire
Heating/Cooling Applications
Line Voltage Wiring
It is recommended that the line voltage (115 VAC) to
the furnace be supplied from a dedicated branch circuit
containing the correct fuse or circuit breaker for the
furnace (Table 4).
IMPORTANT NOTE: An electrical disconnect must be
installed readily accessible from and located within
sight of the furnace. See Figure 13 or the wiring
diagram label inside of the control door. Any other
wiring methods must be acceptable to authority
having jurisdiction.
Field Supplied
Fused Service
Panel
Field Supplied
Disconnect w/in
Sight of Furnace
Junction Box (may be int. or ext.
to the furnace). These connections
can be made in the field supplied
disconnect at the furnace.
The six pin terminal marked “Expansion Port” is not used
in the single stage furnace as shipped from the factory. It
is used for the furnace control board to communicate to
a fi xed speed or variable speed high effi ciency motor that
may be optionally installed. Please contact your distributor
for the proper upgrade motor kit.
IMPORTANT NOTE: Set the heat anticipator according
to the instructions supplied by the thermostat
manufacturer.
To determine the heat anticipator setting:
1. Add the current draw of the system components; or
2. Measure the current fl ow on the thermostat R-W circuit
after the circulating blower motor has started.
Black (Hot)
White (Neutral)
Green or Bare
(Ground)
Field Line Voltage Wiring
Ground
Black
White
Black
White
Ground
Field Supplied
Panel Connector
Factory Line Voltage Wiring
Black
White
Ground
Figure 13. Line Voltage Field Wiring
CAUTION:
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation. Verify
proper operation after servicing.
17
Page 18
IMPORTANT NOTE: Proper line voltage polarity must
be maintained in order for the control system to
operate correctly. Verify the incoming neutral line is
connected to the white wire and the incoming “hot”
line is connected to the black wire. The furnace will not
operate unless the polarity and ground are properly
connected as shown in Figure 13 (page 17).
Grounding
WARNING:
To minimize personal injury, the furnace cabinet
must have an uninterrupted or unbroken electrical
ground. The controls used in this furnace require
an earth ground to operate properly. Acceptable
methods include electrical wire or conduit
approved for ground service. Do not use gas
piping as an electrical ground!
Twinning
Single stage G7 furnaces are not supplied with a builtin twinning capability. Other valuable features and
enhancements were made to the new control that made it
necessary to remove the twinning capability. All standard
two-stage furnaces equipped with the fi xed speed iSEER™
motor include a twinning terminal on the blower control
board.
However, if both Single stage G7 furnaces are upgraded
to the fi xed speed iSEER ™ blower, the twin terminal on
the blower control boards may be used. Alternately, offthe-shelf furnace twinning kits such as Johnson Controls
(P/N 2TC03700124) may be used. Using this control also
provides the additional feature of two-stage operation by
individually controlling the heat section of each furnace.
Contact your furnace distributor for technical details.
G7 furnaces equipped with variable speed iSEER ™
motors may not be twinned under any
circumstances.
START-UP AND ADJUSTMENTS
Pre-Start Check List
√ Verify the polarity of the connections are correct, the
line voltage power leads are securely connected and
the furnace is properly grounded.
√ Verify the thermostat wires (R, W, Y, and G) are
securely connected to the correct leads on the
terminal strip of the circuit board.
√ Verify the gas line service pressure does not exceed
10.0 inches of W.C., and is not less than 4.5 inches
W.C. for natural gas. For LP gas the line service
pressure must not exceed 14 in. W.C., and must not
be less than 11.0 in. W.C.
√ Verify the roll-out and manual reset switch is closed.
If necessary, press the red button to reset a switch.
Note: DO NOT install a jumper wire across a
switch to defeat its function. If a switch reopens on
startup, DO NOT reset the switch without identifying
and correcting the fault condition.
√ Verify the blower door is in place, closing the door
switch in the line voltage circuit.
√ Verify the gas line has been purged and all connections
are leak free.
Start-up Procedures
Do not perform these steps until all of the checks in the
previous steps have been completed:
1. Set the thermostat to the lowest setting.
2. Turn off all electrical power to the furnace.
3. Follow the Operating Instructions on the label attached
to the furnace.
4. Set the ther mostat above room temperature and verify
the Operating Sequence (Page 20).
5. After 5 minutes of operation, set the thermostat
below room temperature and verify steps 9-10 of the
Operating Sequence (page 20).
Verifying and Adjusting Input Rate
IMPORTANT NOTE: The input rate must not exceed
the rate shown on the furnace rating plate. At altitudes
above 2,000 feet, it must not exceed that on the rating
plate less 4% for each 1,000 feet.
18
The input rate must be verifi ed for each installation to
prevent over-fi ring of the furnace. To determine the exact
input rate, perform the following procedures:
1. Shut off all other gas fi red appliances.
2. Start the furnace and run it for at least 3 minutes.
3. Measure the time (in seconds) required for the gas
meter to complete one revolution.
4. Convert the time per revolution to cubic feet of gas
per hour using Table 6 (page 31).
5. Multiply the gas fl ow rate in cubic ft per hr by the
heating value of the gas in Btu per cubic ft to obtain
the input rate in Btuh or see the example (page 19).
Page 19
Example:
• Time for 1 revolution of a gas meter with a 1
cubic ft dial = 40 seconds.
• From Table 6 read 90 cubic ft gas per hr.
• Local heating value of the gas (obtained from
gas supplier) = 1,040 Btu per cubic ft.
• Input rate = 1,040 x 90 = 93,600 Btuh.
6. The manifold pressure must be set to the appropriate
value for each installation by a qualifi ed installer,
service agency or the gas supplier.
WARNING:
Do not attempt to drill the gas orifi ces. Use
only factory supplied orifices. Improperly
drilled orifi ces may cause fi re, explosion,
carbon monoxide poisoning, personal injury
or death.
a.) Obtain the manifold pressure setting required for
this installation by referring to Table 8 for Propane
or Tables 10 or 11 for Natural Gas (pages 32-33).
b.) Remove the regulator capscrew (Figure 14) from
the INLET side of the regulator.
c.) Slowly turn the adjustment screw inside the regulator
to obtain the appropriate manifold pressure.
NOTE: Turning the screw clockwise increases
the pressure and turning the screw counterclockwise decreases the pressure. To prevent
backing the screw all the way out from the valve,
turn the screw slowly.
d.) Replace and tighten the regulator capscrew over
the adjustment screw.
Verifying and Adjusting Temperature Rise
Confi rm the temperature rise through the furnace is
within the limits specifi ed on the furnace rating plate. Any
temperature rise outside the specifi ed limits could result
in premature failure of the heat exchanger.
WARNING:
To prevent electric shock, personal injury, or
death, disconnect the electric power before
performing any maintenance.
1. Place thermometers in the return and supply air stream
as close to the furnace as possible. The thermometer
on the supply air side must be shielded from direct
radiation from the heat exchanger to avoid false
readings.
2. Adjust all registers and duct dampers to the desired
position and run the furnace for 10 to 15 minutes before
taking any temperature readings. The temperature
rise is the difference between the supply and return
air temperatures.
For typical duct systems, the temperature rise will fall
within the limits specifi ed on the rating plate with the
blower speed at the factory recommended setting. If the
measured temperature rise is outside the specifi ed limits,
it may be necessary to change the speed of the blower.
NOTE: Lowering the blower speed will increase the
temperature rise and a higher blower speed will decrease
the temperature rise.
The furnace is equipped with a multi-speed motor. Heating,
cooling, and fan speed selection is made by moving the
switch on the integrated control located in the furnace.
Verifying Burner Operation
Capscrew
Figure 14. Regulator Capscrew
CAUTION:
The door over the burners may only be open
for inspection purposes only. The door must be
installed during unattended operation.
1. Remove the burner compartment door.
2. Set the thermostat above room temperature and observe
the ignition sequence. NOTE: The burner fl ame should
carry over immediately between all burners without
lifting off, curling, or fl oating. The fl ames should be blue,
without yellow tips.
3. After validating the fl ame, change the thermostat setting
to below room temperature.
4. Verify the burner fl ame is completely extinguished.
5. Replace the burner compartment door.
19
Page 20
Verify Operation of the Supply Air Limit Switch
Note: A properly functioning limit switch should turn off
the gas valve when the return is blocked (time depends
on how well the return air is blocked). The circulating air
and combustion blowers should continue to run when the
limit switch opens.
1. Verify the blower door is securely mounted in place
and that there is power to the furnace.
2. Block the return airfl ow to the furnace by installing
a close-off plate in place of or upstream of the
fi lter(s).
3. Set the thermostat above room temperature and
observe the Operating Sequence.
4. Remove the close-off immediately after the limit
switch opens. If the furnace continues to operate
with no return air, set the thermostat below room
temperature, shut off the power to the furnace, and
replace the limit switch.
OPERATING SEQUENCE
The operating sequences for the heating, cooling, and
fan modes are described below. Refer to the fi eld and
furnace wiring diagrams: (Figures 12-13, page 17) and
(Figure 17, page 30).
for 120 seconds at the selected HEAT speed. The
Indoor blower motor is de-energized after a blower
off delay as selected by the movable jumper.
Cooling Cycle
1. The thermostat calls for cooling by energizing the Y
terminal with 24VAC.
2. The control energizes the blower in the cooling speed
and sends 24VAC to the contactor in the condensing
unit.
3. When the thermostat removes the call for cooling,
the contactor in the outdoor condensing unit is deenergized and the control continues to run the fan for
a period of 60 seconds.
Fan Mode
• When the thermostat energizes the G terminal for
continuous fan (without calling for heat or cooling), the
indoor fan is energized on the selected FAN speed.
• If a call for cooling occurs during continuous fan, the
blower will switch over to the selected COOL speed.
• If the W terminal receives a call for heat during continuous
fan, the blower will de energize.
• A call for fan is ignored while in lockout.
MAINTENANCE
Heating Cycle
1. The thermostat calls for heat by energizing the W
terminal with 24VAC.
2. The control verifi es the pressure switch is open.
3. If the pressure switch is open, the control energizes
the inducer and waits for the pressure switch to close.
The pressure switch must close within 10 seconds.
4. The control runs the inducer for a 30 second prepurge.
5. The control energizes the igniter output for the
appropriate warm-up time limit.
6. The control energizes the main gas valve for 3
seconds.
7. If the fl ame proved and ignites the gas, the control
de-energizes the igniter. The gas valve and inducer
remains energized. The control goes to blower on
delay.
8. If fl ame is present, the control energizes the blower
on the selected HEAT speed 30 seconds after the
gas valve opened. The gas valve and inducer remain
energized.
9. When the thermostat demand for heat is satisfi ed, the
control de-energizes the gas valve. The inducer output
remains on for a 30 second post-purge period.
10. Blower off timing begins when the thermostat is
satisfi ed. The control will operate at the selected HEAT
speed of 60, 90, 120, or 180 seconds. If the blower off
delay jumper is not present, the fan should still operate
WARNING:
These maintenance instructions are primarily
intended to assist qualified technicians
experienced in the proper maintenance and
operation of this appliance.
Proper maintenance is most important to achieve the best
performance from a furnace. Follow these instructions for
years of safe, trouble free operation.
• Always replace the doors on the furnace after servicing
or cleaning/changing the fi lters. Do not operate the
furnace without all doors and covers in place.
• Verify the thermostat is properly installed and is not being
affected by drafts or heat from lamps or other appliances.
• To achieve the best performance and minimize
equipment failure it is recommended that a yearly
maintenance checkup be performed. At a minimum,
this check should include the following items:
Air Filter(s)
WARNING:
Never operate the furnace without a fi lter in
place. Dust and lint in the return air can build
up on internal components, resulting in loss
of effi ciency, equipment damage, and possible
fi re.
20
Page 21
Note: Air fi lter(s) are not supplied with the furnace as
shipped from the factory. The installer must provide a
high velocity fi lter and rack for a fi lter in the return air
duct adjacent to the furnace, or in a return air grill to the
furnace.
replaced monthly. New or newly renovated homes may
require more frequent changing until the construction
dust has minimized.
Filters designed to remove smaller particles such as
pollen, may require additional maintenance. Filters for
side return and bottom return applications are available
from most local distributors.
Blower Compartment
Dirt and lint can create excessive loads on the motor
resulting in higher than normal operating temperatures
and shortened service life. It is recommended that the
blower compartment be cleaned of dirt or lint that may
have accumulated in the compartment or on the blower
and motor as part of the annual inspection.
Cleaning of Burners
If the burners must be cleaned, follow steps 1-12. See
Figure 18 and 19 (page 35) for component location.
1. Shut off gas supply to the furnace at the meter or at
2. Turn off all power to the furnace and set the thermostat
3. Remove the burner door from the furnace.
4. Turn the gas control switch to the OFF position.
5. Disconnect the wires from the gas valve, igniter, fl ame
6. Using two wrenches, separate the ground-joint union
7. Remove the piping between the gas valve and the
8. Remove all screws securing the burner assembly to
9. Carefully remove the burner assembly from the furnace.
10. Inspect the burners for accumulated dust or debris.
11. Replace all the parts in reverse order that they were
12. Follow the lighting instructions found on the furnace
It is recommended that fi lters be cleaned or
a manual valve in the supply piping.
to its lowest setting.
sensor, and fl ame rollout switch.
in the gas supply piping at the furnace.
ground-joint union. (If applicable).
the furnace.
DO NOT DAMAGE THE IGNITER WHILE REMOVING
THE BURNER ASSEMBLY.
If necessary carefully clean them with a soft wire
brush and a vacuum cleaner. DO NOT DAMAGE THE
IGNITER WHILE CLEANING THE BURNER.
removed.
door to return the furnace to operation. Verify proper
operation after servicing.
Cleaning Of Flue Passages
If the fl ue passages must be cleaned, follow the steps
below. See Figures 18 and 19 for component location.
1. Shut off the gas supply to the furnace at the meter or
at the manual valve in the gas supply piping.
2. Turn off all power to the furnace and set the thermostat
to the lowest temperature setting.
3. Remove the blower door from the furnace.
4. Turn the gas control switch to the OFF position.
CAUTION:
Label all wires prior to disconnection when
servicing controls. Wiring errors can cause
improper and dangerous operation.
5. Disconnect the wires from the gas valve, fl ame sensor,
6. Remove the silicone rubber tube from the inducer.
7. Using two wrenches, separate the ground-joint union
in the gas supply piping at the furnace.
8. Remove the piping between the gas valve and the
ground-joint union. (If applicable).
9. Remove all screws securing the burner assembly to
the furnace.
10. Carefully remove the burner assembly from the furnace.
DO NOT DAMAGE THE IGNITER WHILE REMOVING
THE BURNER ASSEMBLY.
11a. Remove all screws securing the inducer assembly
to the vent pipe running out of the furnace
(*SA upfl ow/horizontal models only).
11b. Remove all screws securing the combustion air tube
assembly to the vent pipe running out of the furnace.
(*SK downfl ow models only).
12. Remove all screws securing the inducer assembly
to the collector pan.
13a. Carefully remove the inducer assembly and combus-
tion tube assembly from the furnace. DO NOT BREAK
THE SEALS AT EACH END OF THE COMBUSTION
AIR TUBE. (*SK downfl ow models only).
13b. Carefully remove the inducer assembly from the
furnace (*SA upfl ow/horizontal models only).
14. Remove all screws securing the collector pan to the
furnace.
15. Remove the collector pan and gasket from the
furnace.
16. Attach a round wire brush to a length of high grade
stainless steel cable. Attach the other end of the
cable to a variable speed reversible drill. Slowly insert
and rotate the cable into the top portion of the heat
exchanger. Operate the drill alternating between
21
Page 22
forward and reverse, working the cable in and out
several times to obtain suffi cient cleaning. Repeat
this sequence for each heat exchanger tube.
17. Remove all loosened debris from the heat exchanger
tubes using a vacuum cleaner.
18. Using a bright light, check the condition of the upper
and lower sections of the heat exchanger tubes.
19. Inspect the burners for accumulated dust or debris.
If burners must be cleaned, see Cleaning of Burners
(page 22).
20. Replace all the parts in reverse order that they were
removed.
21. Check gaskets for damage. Replace if needed.
22. Follow the lighting instructions found on the furnace
door to return the furnace to operation. Verify proper
operation after servicing.
Heat Exchanger and Burner Maintenance
The furnace should operate for many years without soot
buildup in the fl ue passageways, however, the fl ue, vent
system, and burners should be inspected and cleaned
(if required) by a qualifi ed service technician annually
to ensure continued safe operation. Pay attention to any
deterioration from corrosion or other sources.
Lubrication
The bearings in the blower motor and inducer blower used
in these furnaces are pre-lubricated and sealed by the
manufacturer. No further oiling of the bearings is required
for the life of the motor.
Vent System
WARNING:
Holes in the vent pipe or heat exchanger can
cause combustion products to enter the home.
Replace the vent pipe or heat exchanger if leaks
are found. Failure to prevent the circulation
of combustion products into the living space
can create potentially hazardous conditions
including carbon monoxide poisoning that
could result in personal injury or death.
TROUBLESHOOTING
If the furnace fails to operate check the following:
• Is the thermostat operating properly?
• Are the blower compartment door(s) in place?
• Is the furnace disconnect closed?
• Has the circuit breaker tripped or the control board
fuse burned open?
• Is the gas turned on?
• Are any manual reset switches open?
• Is the fi lter dirty or plugged?
• Is the fl ame sensor coated? (Remove and clean with
steel wool).
• Are all the LED’s on the furnace control board constantly
ON? If not, refer to Table 5 (page 29) or the wiring diagram
(Figure 17, page 30) to determine fault condition.
IMPORTANT NOTE: The furnace will lock out after 5
failed attempts for ignition and will try again every
hour if the call for heat remains.
• If the Inducer Blower is operating, and items above
have been verifi ed, check the Blower Limit Switch and
reset if necessary. See Figure 18 or 19 (page 35) for
component location.
• If the furnace operates when the Blower Limit Switch is
reset, contact a qualifi ed service technician to identify
and repair the problem.
• If the furnace still doesn’t operate, check the Flame
Roll-out Switches and reset if necessary. See Figure
18 or 19 for component location.
• If the furnace operates when the Flame Rollout Switch
is reset, contact a qualifi ed service technician to identify
and repair the problem.
Check the vent pipe and/or chimney to ensure that it is not
corroded or blocked by debris. Any corroded section of vent
pipe must be replaced, and any obstruction or blockage
must be removed prior to operating the furnace.
22
Page 23
DESCRIPTION OF COMPONENTS
The descriptions below are various functional components
that affect the operation and shutting down of this furnace.
Some of these components and their locations are shown
in Figures 18 and 19.If any component of the furnace
must be replaced, use only factory authorized replacement
parts specifi ed in the Replacement Parts List provided
online.
Blower Limit Switch
Blower switches prevent operation when blower is not
operational.
Flame Sensor
The fl ame sensor verifi es when a fl ame has carried over
from the igniter to the opposite end burner. If no fl ame is
detected, the furnace will shut down within 4 seconds.
Flame Roll-Out Switch
The fl ame roll-out switch verifi es that the burner fl ames
are drawn into the heat exchanger tubes. If the burner
fl ames are not properly drawn into the heat exchanger, the
fl ame roll-out switch will close the gas valve and initiate
the shutdown cycle.
Gas Valve
The gas valve controls the fl ow of gas to the burners.
When the gas valve is energized it automatically opens
and regulates the gas pressure in the manifold.
Inducer Assembly
The inducer assembly vents products of combustion to
the outside.
Pressure Switch
The pressure switch verifi es that the inducer is drawing
the combustion gases through the heat exchanger. If
the fl ame is not properly drawn into the heat exchanger
tube, the rollout switch or the fl ame sensor will shut the
furnace down.
Supply Air Limit Switch
The supply air limit switch prevents the air temperature
leaving the furnace from exceeding the maximum
allowable outlet air temperature.
* These are the listed clearances to combustible materials.
** Allow 24 in. minimum clearance for servicing. Recommended clearance is 36 in.
The furnace is listed for installation on combustible or non-combustible fl ooring. However,
wood is the only combustible fl ooring allowed for installation. Downfl ow models must use
the appropriate subase kit when installing over a wood fl oor.
UPFLOW APPLICATION
TOP
HORIZONTAL APPLICATION
SIDE
DOWNFLOW APPLICATION
TOP
LEFT SIDE
BOTTOM
Table 1. Minimum Clearances to Combustible Material
RIGHT SIDE
TOP
SIDE
BOTTOM
LEFT SIDE
BOTTOM
RIGHT SIDE
23
Page 24
⅞
“D”
12
Dimension
⅝
“C”
12
Dimension
¾
“B”
10
Dimension
¼
“A”
14
Dimension
(†)-23A
*SA
Model #’s
045
054(†)-23A
⅛
16
⅞
15
¾
11
½
17
(†)-24B
072
090(†)-24B
(†)-35C
072
⅞
19
⅜
19
2114
090(†)-35C
FURNACE DIMENSIONS
⅛
22 ⅞ 23
¼
15
NOTES:
(†)-35C
108
½
24
(†)-45D
126
(†) can be C or N
22 ¼
Dimensions shown in Inches.
25
21⁄
22 ¾
⅝ X 3½ X45°
HOLE FOR GAS
1
22 ½
15
(BOTH SIDES)
4 KNOCKOUTS
¼
1
23
RIGHT SIDE
1
C
D
TOP VIEW
FRONT BRACE
19
FLANGES
23
PANEL
BOTTOM
TYPE B
ACCEPTS 4”
BOTTOM VIEW
Ø⅞ HOLE FOR
B
VENT PIPE
THERMOSTAT
25 ⅜
ELECTRIC
Ø ⅞HOLE FOR
1⅝ X 3½
ELECTRIC
HOLE FOR GAS
Ø⅞HOLE FOR
29 ½
A
23
28
LEFT SIDE
23 ½
Figure 15. *SA 80+ High Effi ciency Upfl ow/Horizontal Furnaces
24
½
34
Page 25
“D”
Dimension
“C”
Dimension
“B”
Dimension
¼ 10 ¾ 12 ⅝ 12 ⅞
“A”
14
Dimension
*SK
(†)-23A
Model #’s
054
C
TOP VIEW
17 ½ 11 ¾ 15 ⅞ 16 ⅛
072(†)-24B
⅜ 19 ⅝
19
2114
(†)-35C
108
090(†)-24B
FLANGES
19
NOTES:
½ 15 ¼ 22 ⅞ 23 ⅛
24
126(†)-45D
(†) can be C or N
Dimensions shown in Inches.
¼
22
B
Ø⅞ HOLE
FOR THERMOSTAT
25
1⅝ X 3 ½ X 45°
Ø ⅞ HOLE
FOR ELECTRIC
22 ½
29 ½
HOLE FOR GAS
RIGHT SIDE
7
A
23
TYPE B
VENT PIPE
ACCEPTS 4”
D
FRONT BRACE
BOTTOM VIEW
18 ⅝
Ø⅞ HOLE
FOR ELECTRIC
22 ½
FOR GAS
1⅝ X 3½ HOLE
7
⅜
25
28
LEFT SIDE
½
34
Figure 16. *SK 80+ High Effi ciency Downfl ow Furnaces
CAPACITY OF BLACK IRON GAS PIPE (CU. FT. PER HOUR)
FOR NATURAL GAS (SPECIFIC GRAVITY - 0.60)
NOMINAL BLACK
IRON PIPE
DIAMETER (IN.)
½
¾
1520350285245215195180170
1 ¼ 1,050730590500440400370350
1 ½ 1,6001,100890760670610
The cubic feet per hour listed in the table above must be greater than the cubic feet per hour of gas fl ow required by the
furnace. To determine the cubic feet per hour of gas fl ow required by the furnace, divide the input rate of the furnace by the
heating value (from gas supplier) of the gas.
1020304050607080
13090756555504540
2801901501301151059590
Cubic Feet Per Hour Required =
LENGTH OF PIPE RUN (FT)
NOTES
Input To Furnace (Btu/hr)
Heating Value of Gas (Btu/Cu. Ft.)
Table 7. Black Iron Gas Pipe Capacities
31
Page 32
ALTITUDE ABOVE
SEA LEVEL
0 to 1,999 FT
PROPANE GAS
INPUT (BTU)
45,00054,00072,00090,000108,000126,000
575656565656ORIFICE SIZE
10.010.010.010.010.010.0MANIFOLD PRESSURE
2,000 to 2,999 FT
3,000 to 4,999 FT
5,000 to 5,999 FT
6,000 to 7,999 FT
8,000 to 10,000 FT
575656565656ORIFICE SIZE
9.09.09.09.09.09.0MANIFOLD PRESSURE
575656565656ORIFICE SIZE
8.58.58.58.58.58.5MANIFOLD PRESSURE
595757575757ORIFICE SIZE
10.010.010.010.010.010.0MANIFOLD PRESSURE
595757575757ORIFICE SIZE
9.09.09.09.09.09.0MANIFOLD PRESSURE
595757575757ORIFICE SIZE
8.58.58.58.58.58.5MANIFOLD PRESSURE
Table 8. High Altitude Deration Chart for Propane Gas
ALTITUDE ABOVE
SEA LEVEL
2,000 FTLOWLOWLOWLOWLOWLOWHIGH HIGH HIGH
3,000 FTLOWLOWLOWLOWLOWLOWHIGH HIGH HIGH
4,000 FTLOWLOWLOWLOWLOWHIGHHIGH HIGH HIGH
5,000 FTLOWLOWLOWLOWLOWHIGHHIGH HIGH HIGH
6,000 FTLOWLOWLOWLOW HIGHHIGHHIGHHIGH HIGH
7,000 FTLOWLOWLOWLOW HIGHHIGHHIGHHIGH HIGH
8,000 FTLOWLOWLOWHIGH HIGHHIGHHIGHHIGH HIGH
9,000 FTLOWLOWLOWHIGH HIGHHIGHHIGHHIGH HIGH
10,000 FTLOWLOWHIGH HIGH HIGHHIGHHIGH HIGH HIGH
6507007508008509009501,000 1,050
LOCAL HEATING VALUE (BTU PER CUBIC FOOT)
32
Table 9. Natural Gas Heating Values
Page 33
ALTITUDE ABOVE
SEA LEVEL
0 to 1,999 FT
NATURAL GAS - HIGH HEATING VALUE
INPUT (BTU)
45,00054,00072,00090,000108,000126,000
494747474747ORIFICE SIZE
3.53.53.53.53.53.5MANIFOLD PRESSURE
2,000 to 2,999 FT
3,000 to 3,999 FT
4,000 to 4,999 FT
5,000 to 5,999 FT
6,000 to 6,999 FT
7,000 to 7,999 FT
8,000 to 8,999 FT
9,000 to 9,999 FT
Table 10. High Altitude Deration Chart for Natural Gas - High Heating Value
ALTITUDE ABOVE
SEA LEVEL
0 to 1,999 FT
494747474747ORIFICE SIZE
2.93.23.23.23.23.2MANIFOLD PRESSURE
494747474747ORIFICE SIZE
2.83.03.03.03.03.0MANIFOLD PRESSURE
494747474747ORIFICE SIZE
2.62.82.82.82.82.8MANIFOLD PRESSURE
494747474747ORIFICE SIZE
2.52.72.72.72.72.7MANIFOLD PRESSURE
514949494949ORIFICE SIZE
3.33.53.53.53.53.5MANIFOLD PRESSURE
514949494949ORIFICE SIZE
3.03.33.33.33.33.3MANIFOLD PRESSURE
514949494949ORIFICE SIZE
2.83.03.03.03.03.0MANIFOLD PRESSURE
514949494949ORIFICE SIZE
2.62.82.82.82.82.8MANIFOLD PRESSURE
NATURAL GAS - LOW HEATING VALUE
INPUT (BTU)
45,00054,00072,00090,000108,000126,000
494747474747ORIFICE SIZE
3.53.53.53.53.53.5MANIFOLD PRESSURE
2,000 to 2,999 FT
3,000 to 3,999 FT
4,000 to 4,999 FT
5,000 to 5,999 FT
6,000 to 6,999 FT
7,000 to 7,999 FT
8,000 to 8,999 FT
9,000 to 9,999 FT
494747474747ORIFICE SIZE
3.53.53.53.53.53.5MANIFOLD PRESSURE
494747474747ORIFICE SIZE
3.13.33.33.33.33.3MANIFOLD PRESSURE
494747474747ORIFICE SIZE
2.93.13.13.13.13.1MANIFOLD PRESSURE
494747474747ORIFICE SIZE
2.72.92.92.92.92.9MANIFOLD PRESSURE
494747474747ORIFICE SIZE
2.62.82.82.82.82.8MANIFOLD PRESSURE
514949494949ORIFICE SIZE
3.43.43.43.43.43.4MANIFOLD PRESSURE
514949494949ORIFICE SIZE
3.13.23.23.23.23.2MANIFOLD PRESSURE
514949494949ORIFICE SIZE
2.92.92.92.92.92.9MANIFOLD PRESSURE
Table 11. High Altitude Deration Chart for Natural Gas - Low Heating Value
33
Page 34
34
Page 35
LOCATION OF FURNACE COMPONENTS
ITEM
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
COMPONENT NAME
Blower Assembly
Blower Door Switch
Burner Assembly
Control Board
Flame Sensor
Gas Manifold
Gas Valve
Igniter
Inducer Assembly
Limit Switch
Pressure Switch
Roll-Out Switch
Transformer
9
10
13
12
8
2
9
8
7
63
5
4
NEUTRALS
4
RCYGW
STATUS
24V
FAN
COOL
HEAT
FLAME
63
180
BLOWER
2
120
5
OFF
90
1
4
DELAY
60
L1A
2
1
XFMR
HIGH
LOW
HUM
EAC
MH
ML
L1
7
11
5
6
3
1
ITEM
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
COMPONENT NAME
Blower Assembly
Blower Door Switch
Burner Assembly
Combustion Tube
Control Board
Flame Sensor
Gas Manifold
Gas Valve
Igniter
Inducer Assembly
Limit Switch
Pressure Switch
Roll-Out Switch
Transformer
Figure 18.
Upfl ow/Horizontal Gas Furnace
1
2
4
10
11
13
9
9
8
7
63
5
4
5
4
NEUTRALS
RCYGW
STATUS
24V
FAN
COOL
HEAT
FLAME
63
180
BLOWER
2
120
OFF
90
1
DELAY
60
L1A
2
1
XFMR
HIGH
LOW
HUM
EAC
MH
ML
L1
14
12
8
6
7
3
5
Figure 19. Downfl ow
Gas Furnace
35
Page 36
INSTALLATION/PERFORMANCE CHECK LIST
INSTALLER NAME:
CITY _______________STATE _____________
INSTALLATION ADDRESS:
CITY _______________STATE _____________
UNIT MODEL #
UNIT SERIAL # ____________________________
Minimum clearances per
Table 1 (page 23)?
Has the owner’s information
been reviewed with the
home-owner?
YESNO
YESNO
ELECTRICAL SYSTEM:
Electrical connections tight?YESNO
Line voltage polarity correct?YESNO
Supply Voltage: ______________________ VOLTS
Has the thermostat been
calibrated?
Is the thermostat level?YESNO
Is the heat anticipator setting
correct?
GAS SYSTEM:
Gas Type: (circle one)
Gas pipe connections leak
tested?
Gas Line Pressure: __________________ (in - W.C.)
Is there adequate fresh
air supply for combustion
and ventilation?
YESNO
YESNO
Natural
Gas
YESNO
YESNO
Propane
Has the literature package
been left near the
furnace?
YESNO
Installation Altitude: ____________________ (FT.)
Deration Percentage: ___________________ (%)
Furnace Input: _______________________ (Btuh)
Supply Air Temperature: ________________ (° F)
Return Air Temperature: ________________ (° F)
Temperature Rise: ____________________ (° F)
VENTING SYSTEM:
Vent free from restrictions?YESNO
Filter(s) secured in place?YESNO
Filter(s) clean?YESNO
Flue connections tight?YESNO
Is there proper draft?YESNO
O’Fallon, MO
¢708807>¤
708807D
708807D (Replaces 708807C)
Specifi cations and illustrations subject to change
without notice or incurring obligations.
Printed in U.S.A. (09/08)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.