• PROPOSITION 65 WARNING: This product
contains chemicals known to the state of
California to cause cancer, birth defects or
other reproductive harm.
• This furnace is not approved for installation
in mobile homes. Installing this furnace in
a mobile home could cause fi re, property
damage, and/or personal injury.
ATTENTION INSTALLERS:
It is your responsibility to know this product better than your
customer. This includes being able to install the product according
to strict safety guidelines and instructing the customer on how to
operate and maintain the equipment for the life of the product.
Safety should always be the deciding factor when installing this
product and using common sense plays an important role as well.
Pay attention to all safety warnings and any other special notes
highlighted in the manual. Improper installation of the furnace
or failure to follow safety warnings could result in serious injury,
death, or property damage.
These instructions are primarily intended to assist qualifi ed
individuals experienced in the proper installation of this appliance.
Some local codes require licensed installation/service personnel
for this type of equipment. Please read all instructions carefully
before starting the installation. Return these instructions to the
customer’s package for future reference.
WARNING:
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly
could result in serious injury or property
damage.
• Installation and service must be performed
by a qualifi ed installer, service agency or
the gas supplier.
• Do not store or use gasoline or other
fl ammable vapors and liquids in the
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a
neighbors phone. Follow the gas suppliers
instructions.
• If you cannot reach your gas supplier, call
the fi re department.
DO NOT DESTROY.
KEEP IN A SAFE PLACE FOR FUTURE REFERENCE.
TABLE OF CONTENTS
SAFETY INFORMATION .............................................4
REQUIREMENTS AND CODES .................................. 4
GENERAL INSTRUCTIONS ........................................ 5
Combustion Air Quality ...........................................5
Operation of Furnace During Construction .............5
Installation in a Garage ...........................................6
Airfl ow Data ...........................................................26
Table 2 - Upfl ow/Horizontal Gas Furnaces .......26
Table 3 - Downfl ow Gas Furnaces ....................28
Figure 18 - Upfl ow/Horizontal Gas Furnace
Components ..................................35
Figure 19 - Downfl ow Gas Furnace
Components ..................................35
INSTALLATION/PERFORMANCE CHECKLIST .......36
3
SAFETY INFORMATION
Safety markings are used frequently throughout this
manual to designate a degree or level of seriousness and
should not be ignored. WARNING indicates a potentially
hazardous situation that if not avoided, could result in
personal injury or death. CAUTION indicates a potentially
hazardous situation that if not avoided, may result in minor
or moderate injury or property damage.
WARNING:
The safety information listed below must be
followed during the installation, service, and
operation of this furnace. Failure to follow safety
recommendations could result in possible
damage to the equipment, serious per
injury or death
.
sonal
REQUIREMENTS and CODES
This furnace must be installed in accordance with
these instructions, all applicable local building codes
and the current revision of the National Fuel Gas Code
(NFPA54/ANSI Z223.1) or the Natural Gas and Propane
Installation Code, CAN/CGA B149.1.
Additional codes listed below are for reference purposes
only and do not necessarily have jurisdiction over local or
state codes. Always consult with local authorities before
installing any gas appliance.
Combustion and Ventilation Air
• US: National Fuel Gas Code (NFGC), Air for Combustion
and Ventilation
• CANADA: Natural Gas and Propane Installation Codes
(NSCNGPIC), Venting Systems and Air Supply for
Appliances
• Use only with type of gas approved for this furnace.
Refer to the furnace rating plate.
• Install this furnace only in a location and position as
specifi ed in Table 1 (page 23).
• Provide adequate combustion and ventilation air to the
furnace space as specifi ed on Pages 6 - 8.
• Combustion products must be discharged outdoors.
Connect this furnace to an approved vent system only,
as specifi ed on Pages 12 - 13.
• Never test for gas leaks with an open fl ame. Use a
commercially available soap solution to check all
connections (Page 15).
• This furnace is designed to operate with a maximum
external pressure rise of 0.5 inches of water column.
Consult Tables 2 and 3 (pages 26 - 28), and the rating
plate for the proper circulating air fl ow and temperature
rise. It is important that the duct system be designed to
handle the desired fl ow rate and temperature rise. An
improperly designed duct system can result in nuisance
shutdowns, and comfort or noise issues.
• When supply ducts carry air circulated by the furnace
to areas outside the space containing the furnace, the
return air shall also be handled by duct(s) sealed to
the furnace casing and terminating outside the space
containing the furnace.
• This furnace may be used for temporary heating of
buildings or structures under construction. See the
guidelines listed on page 5.
• A gas-fi red furnace for installation in a residential garage
must be installed as specifi ed on Page 6.
Duct Systems
• US and CANADA: Air Conditioning Contractors
Association (ACCA) Manual D, Sheet Metal and
Air Conditioning Contractors National Association
(SMACNA), or American Society of Heating,
Refrigeration, and Air Conditioning Engineers
(ASHRAE) Fundamentals Handbook
Electrical Connections
• US: National Electrical Code (NEC) ANSI/NFPA 70
• CANADA: Canadian Electrical Code CSA C22.1
Gas Piping and Gas Pipe Pressure Testing
• US: NFGC and National Plumbing Codes
• CANADA: NSCNGPIC
General Installation
• US: Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association
Inc., Batterymarch Park, Quincy, MA 02269; or American
Gas Association, 400 N. Capitol, N.W., Washington DC
20001 or www.NFPA.org
• CANADA: NSCNGPIC. For a copy, contact Standard
Sales, CSA International, 178 Rexdale Boulevard,
Etobicoke (Toronto), Ontario, M9W 1R3 Canada
Safety
• US: (NFGC) NFPA 54–1999/ANSI Z223.1 and the
Installation Standards, Warm Air Heating and Air
Conditioning Systems ANSI/NFPA 90B.
• CANADA: CAN/CGA-B149.1 and .2–M00 National
Standard of Canada. (NSCNGPIC)
4
GENERAL INSTRUCTIONS
Combustion Air Quality
CAUTION:
Combustion air must not be drawn from a
corrosive atmosphere.
To maximize heat exchanger life, the combustion air
must be free of chemicals that can form corrosive acidic
compounds in the combustion gases. The recommended
source of combustion air is to use outdoor air. However,
the use of indoor air in most applications is acceptable
except as listed:
• If the furnace is installed in a confi ned space, it is required
that the necessary combustion air come from the
outdoors by way of attic, crawl space, air duct, or direct
opening. See Installation in a Confi ned Space section
(pages 7 - 8) for combustion air requirements.
• Installations in these locations may require outdoor air
for combustion, due to chemical exposures:
Commercial buildings
Buildings with indoor pools
Furnaces installed in laundry rooms
Furnaces installed in hobby or craft rooms
Furnaces installed near chemical storage areas
• Exposure to the following substances in the combustion
air supply may require outdoor air for combustion:
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine based swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
Cleaning solvents (perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners
Masonry acid washing materials
Operation of Furnace During Construction
CAUTION:
Failure to follow these instructions will void the
factory warranty and may signifi cantly reduce
the life or the performance of the furnace,
and/or result in other unsafe conditions. It is
the responsibility of the installing contractor
to insure these provisions are met.
Operating gas furnaces in construction environments can
cause a variety of problems with the furnace. Proper use
of commercial portable space heating equipment during
construction is recommended. This gas furnace may be
used during construction if it is not in violation of any
applicable codes and the following criteria are met:
• The installation must meet all applicable codes. The
furnace must be permanently installed according to
the instructions supplied with the furnace including
electrical supply, gas supply, duct work and venting. The
furnace must be controlled by a thermostat properly
installed according to the instructions supplied with the
furnace and thermostat. The installation must include
a properly installed fi lter in the return air system with
no by-pass air. The fi lter must be inspected frequently
and replaced when necessary.
• Combustion air must be supplied from outside the
structure and located such that dust and gases
from construction activity are not introduced into the
combustion system.
• Provisions must be made to insure that condensate
does not freeze in the furnace or condensate drain lines
during operation and during idle times; for example,
overnight if turned off. (Condensing furnaces only)
• Before occupying the structure: The fi lter must be
replaced or cleaned, the duct work must be inspected
and cleaned of any construction debris, and the furnace
must be cleaned and/or repaired if found to be dirty,
damaged, or malfunctioning in any way by a qualifi ed
HVAC technician. The furnace shall be inspected and
approved by applicable local authority even if this
requires redundant inspections.
• Serial numbers for furnaces used during construction
must be submitted in writing (fax and email also
acceptable). This information will be used to track the
long-term affects of the use during construction on
furnaces. Proof of this submittal shall be available for
the fi nal inspection of the furnace prior to occupancy.
• This furnace is designed to operate with return air
temperatures in ranges normally found in occupied
residences, including setbacks. Minimum continuous
return temperature must not be below 60° F (15° C).
Occasionally a temporary return temperature of 55° F
(12° C) is acceptable. However, operation with a return
temperature below 55° F (12° C) is not allowed.
5
Installation in a Garage
WARNING:
Do not place combustible materials on or
against the furnace cabinet or within 6 inches
of the vent pipe. Do not place combustible
materials, including gasoline or any other
fl ammable vapors and liquids, in the vicinity
of the furnace.
This Gas-fi red furnace may be installed in a residential
garage with the provision that the burners and igniter
are located no less than 18 inches (457mm) above the
fl oor. The furnace must be located or protected to prevent
physical damage by vehicles.
Heating Load
The furnace should be sized to provide the design heating
load requirement. Heating load estimates can be made
using approved methods available from Air Conditioning
Contractors of America (Manual J); American Society of
Heating, Refrigerating, and Air Conditioning Engineers;
or other approved engineering methods. Excessive
oversizing of the furnace could cause the furnace
and/or vent to fail prematurely. In addition, the ductwork
should be appropriately sized to the capacity of the
furnace to ensure its proper airfl ow rating. For installations
above 2,000 ft., the furnace should have a sea level input
rating large enough that it will meet the heating load after
deration for altitude.
Clearances to Combustible Materials
This furnace is Design Certifi ed in the U.S. and Canada
by CSA International for the minimum clearances to
combustible materials listed in Table 1 (page 23). To obtain
model number and specifi c clearance information, refer
to the furnace rating plate, located inside of the furnace
cabinet.
COMBUSTION AIR REQUIREMENTS
General Information
WARNING:
Furnace installation using methods other than
those described in the following sections must
comply with the National Fuel Gas Code (NFGC)
and all applicable local codes.
• Instructions for determining the adequacy of an
installation can be found in the current revision of the
NFGC (ANSI Z223.1 / NFPA54). Consult local codes for special requirements. These requirements are for
US installations as found in the NFGC.
• The requirements in Canada (B149.1) are structured
differently. Consult with B149.1 and local code offi cials
for Canadian installations.
• Additional reference information for US and Canadian
installations can be found in the Combustion and
Ventilation Air section (page 4).
Provisions must be made during the installation of
this furnace that provide an adequate supply of air for
combustion.
CAUTION:
Exhaust fans, clothes dryers, fi replaces and
other appliances that force air from the house
to the outdoors can create a negative pressure
inside the house, resulting in improper furnace
operation or unsafe conditions such as fl ame roll
out. It is imperative that suffi cient air exchange
with the outdoors is provided to prevent
depressurization. Additional information about
how to test for negative pressure problems can
be found in the NFGC.
Access for positioning and servicing the unit must be
considered when locating unit. The minimum required
clearance from the front of the unit for servicing is 24
inches. The minimum required clearance for positioning
is 30 inches from the front of the unit. The recommended clearance from the front of the unit is 36 inches. The
need to provide clearance for access to panels or doors
may require clearance distances over and above the
requirements.
6
NOTE: Air openings on top of the furnace and openings in
closet doors or walls must never be restricted. If the furnace
is operated without adequate air for combustion, the fl ame
roll-out switch will open, turning off the gas supply to the
burners. This safety device is a manually reset switch.
DO NOT install jumper wires across these switches
to defeat their function or reset a switch without
identifying and correcting the fault condition.
If a switch must be replaced, use only the correct sized
part specifi ed in the Replacement Parts List provided
online.
Installation In A Confi ned Space
A confi ned space is an area with volume less than 50
cubic feet per 1,000 Btuh of the combined input rates of
all appliances drawing combustion air from that space.
Furnace closets, small equipment rooms and garages are
confi ned spaces. Furnaces installed in a confi ned space
which supply heated air to areas outside the space must
draw return air from outside the space and must have the
return air ducts tightly sealed to the furnace.
The required sizing of these openings is determined by
whether inside or outside air is used to support combustion,
the method by which the air is brought to the space, and
by the total input rate of all appliances in the space. In
all cases, the minimum dimension of any combustion air
opening is 3 inches.
Outdoor Air Using Vertical Ducts
If combustion air is taken from outdoors through vertical
ducts, the openings and ducts must have a minimum
free area of one square inch per 4,000 Btuh of total
appliance input. In installations drawing combustion air
from a ventilated attic, both air ducts must extend above
the attic insulation (Figure 1).
Ventilation Louvers at
each end of attic
Vent or
Chimney
Water
Heater
Attic
Insulation
Furnace
Outlet Air Duct must
be at least 1 sq. in.
per 4,000 Btuh of
total input rating.
Inlet and Outlet
Ducts must
extend above
attic insulation.
Inlet Air Duct must
be at least 1 sq. in.
per 4,000 Btuh of
total input rating.
Outdoor Air Using Horizontal Ducts
If combustion air is taken from outdoors through horizontal
ducts, the openings and ducts must have a minimum free
area of one square inch per 2,000 Btuh of total appliance
input (Figure 2).
opening to
outside must
be at least 1
sq. in. per 2,000
Btuh of total
-
-
-
-
-
-
input rating.
-
-
-
Round Duct
Diameter
Figure 2. Combustion Air Drawn from Outside
Through Horizontal Ducts
Outdoor Air from a Crawl Space or Vented Attic
When the openings can freely exchange air with the
outdoors, each opening shall have a minimum free area
of 1 square inch per 4,000 Btuh of total appliance input.
The openings shall exchange directly, or by ducts, with
the outdoor spaces (crawl or attic) that freely exchange
with the outdoors (Figure 3).
Ventilation louvers
Chimney
Attic
Insulation
Water
Heater
Vent or
at each end of attic
Furnace
Outlet air duct must be
at least 1 sq. in. per
4,000 Btuh of total
input rating. Must
extend above attic
insulation
Inlet air duct must be at
least 1 sq. in. per 4,000
Btuh of total input rating.
Crawl Space
Ventilated Louvers for
unheated crawl space
Figure 3. Combustion Air Drawn from a Crawl
Space or Vented Attic
7
Air Directly Through An Exterior Wall
If combustion air is provided directly through an exterior
wall, the two openings must each have free area of at
least one square inch per 4,000 Btuh of total appliance
input (Figure 4).
to outside must be at
least 1 sq. in. per
4,000 Btuh of total
input rating.
Round Duct
Diameter
Figure 4. Combustion Air Drawn from Outside
Through an Exterior Wall
Alternate Method of Providing Air from Outside:
If acceptable under local Codes, it is permitted to
provide outside air using one opening (See NFGC).
Air From Inside
If combustion air is taken from the heated space, the two
openings must each have a free area of at least one square
inch per 1,000 Btuh of total input of all appliances in the
confi ned space, but not less than 100 square inches of
free area (Figure 5). For example, if the combined input
rate of all appliances is less than or equal to 100,000
Btuh, each opening must have a free area of at least 100
square inches. If the combined input rate of all appliances
is 120,000 Btuh, each opening must have a free area of
at least 120 square inches.
Vent or
Chimney
NOTES:
Each opening must
be at least 100 sq. in.
or 1 sq. in. per 1,000
Btuh of total input rating,
whichever is greater.
Openings must start at
no more than 12 inches
from the top and bottom
of the enclosure.
Generally, confi ned spaces must have two openings
in the space for combustion air. One opening must
be within 12 inches of the ceiling, and the other
must be within 12 inches of the fl oor. However, an
alternative method recently adopted by the NFGC
uses one opening within 12 inches of the top of the
space. This method may be used if it is acceptable
to the local codes.
The following conditions must be met:
1. The opening must start within 12” of the top of the
structure and connect with the out of doors through
vertical or horizontal ducts or be ducted to a crawl
or attic space that connects with the out of doors.
2. The opening must have a minimum free area of 1
sq. in. per 3,000 Btu per hour of the total input rating
of all equipment located in the enclosure.
3. The free area must not be less than the sum of all
the areas of the vent connectors in the enclosure.
8
Installation In An Unconfi ned Space
An unconfi ned space is an area including all rooms not
separated by doors with a volume greater than 50 cubic
feet per 1,000 Btuh of the combined input rates of all
appliances which draw combustion air from that space.
In general, a furnace installed in an unconfi ned space will
not require outside air for combustion. However, in homes
built for energy effi ciency (low air change rates), it may
be necessary to provide outside air to ensure adequate
combustion and venting, even though the furnace is located
in an unconfi ned space. See example.
Example:
A space with a water heater rated at 45,000 Btuh
input and a furnace rated at 75,000 Btuh requires a
volume of 6,000 cubic feet [50 x (45 + 75) = 6,000] to
be considered unconfi ned. If the space has an 8 foot
ceiling, the fl oor area of the space must be 750 square
feet (6,000 / 8 = 750).
FURNACE INSTALLATION
General Requirements
*SA series gas furnaces are shipped ready for installation
in the upfl ow or horizontal right or left positions. Only
the *SK series gas furnace may be used for downfl ow
operation.
• The furnace must be leveled at installation and attached
to a properly installed duct system. See Table 1 (page
23) for the required clearances needed to move the
furnace to its installation point (hallways, doorways,
stairs, etc).
• The furnace must be installed so that all electrical
components are protected from water.
• The furnace must be installed upstream from a
refrigeration system.
• Additional reference information for US and Canadian
installations can be found in the General Installation
section (page 4).
Upfl ow Installation
The *SA series gas furnace may be installed directly on
combustible wood fl ooring or supports. This furnace
must not be installed directly on carpeting, tile, or
any combustible material other than wood fl ooring.
For venting guidelines and specifi cations, see Venting
Requirements section (pages 12 - 13).
Access for positioning and servicing must be considered
when locating the unit. See Table 1 (page 23) for clearance
specifi cations.
If the furnace is to be installed in an attic, it is required that
a drip pan be placed under the furnace. If the installation
is on a combustible platform (Figure 6), it is recommended
that the drip pan extend at least 12 inches past the top
and front of the furnace.
WARNING:
The furnace must not be installed directly on
carpeting, tile, or any combustible material other
than wood fl ooring.
It is recommended for further reduction of fi re hazard
that cement board or sheet metal be placed between the
furnace and the combustible fl oor and extend 12 inches
beyond the front of the door and top of the furnace.
Note: Line Contact
Is Permissible
Type “B” Vent
Gas Inlet
Side Return Air Inlet
*SA series gas furnaces are shipped with the bottom
panel installed (Figure 15, page 24). If the upfl ow furnace
is installed with side return air, the bottom panel must not
be removed.
Bottom Return Air Inlet
*SA series gas furnaces are shipped with the bottom
panel installed. If the upfl ow furnace is installed with
bottom return air, the bottom panel must be removed.
See Bottom Panel Removal on page 10.
Horizontal Installation
The *SA series gas furnace can be installed horizontally
in an attic, basement, crawl space or alcove (Figure 6).
It can also be suspended from a ceiling in a basement
or utility room in either a right to left airfl ow or left to right
airfl ow as shown in Figure 7.
*SA series furnaces are shipped with the bottom panel
installed. If the furnace is installed horizontally, remove
the bottom panel from the furnace before attaching the
duct system. See Bottom Panel Removal on page 10.
If the furnace is to be suspended from the ceiling, it will
be necessary to use steel straps around each end of the
furnace. The straps should be attached to the furnace
with sheet metal screws and to the rafters with bolts. The
furnace could also be suspended by an angle iron frame
bolted to the rafters (Figure 7).
Coil Plenum
Electrical Supply
Connection
Combustible
Platform
Figure 6. *SA Horizontal Installation on a Platform
Figure 7. *SA Horizontal Installation
Suspended in Attic or Crawl Space
9
Bottom Panel Removal
To remove the bottom panel (Figure 8) from the upfl ow
furnace, perform the following steps:
1. Remove the blower door (1) from bottom of furnace.
2. Disconnect the wiring harness (2) from the
connector.
3. Remove two screws (3) securing the blower assembly
(4) to the furnace.
4. Carefully pull the blower assembly (4) out thru the
front of the furnace.
5. Remove all screws (5) securing bottom panel (6) to
bottom of furnace and front brace (7).
6. Lift up and slide bottom panel (6) out through front of
furnace.
7. Reinstall the blower assembly (4) in reverse order it
was removed.
Bottom Panel
1
Downfl ow Installation
The *SK series gas furnace is certifi ed for installation on
combustible fl ooring. This furnace must not be installed
directly on carpeting, tile, or any combustible material
other than wood fl ooring. For venting guidelines and
specifi cations, see Venting Requirements section (page
12).
WARNING:
Failure to install the downfl ow sub-base kit
may result in fi re, property damage or personal
injury.
To install the furnace on combustible fl ooring, a special
sub-base is required. Downfl ow sub-base kits are factory
supplied accessories and are listed according to the cabinet
letter of the furnace. For ‘A’ size cabinets use Sub-Base
kit #902974 only. For ‘B’, ‘C’, and ‘D’ size cabinets use
Kit #904911. Please follow the instructions provided with the kit.
6
WARNING:
The downfl ow sub-base kit must not be installed
directly on carpeting, tile, or any combustible
material other than wood fl ooring.
A downfl ow sub-base kit is not necessary if the furnace
7
Blower Assembly
5
3
3
2
4
is installed on a factory or site-built cased air conditioning
coil. However, the plenum attached to the coil casing
must be installed so that its surfaces are at least 1” from
combustible construction.
Installation on a concrete slab.
1. Create an opening in the fl oor according to the
dimensions in Figure 9.
2. Position the plenum and the furnace as shown in
Figure 10 (page 11).
Opening in concrete floor
“A”
“B”
Figure 8. Removal of Bottom Panel
10
*SK MODEL
NUMBERS:
054-23A
072-24B
090-24B
108-35C
126-45D
Figure 9. Cutout Dimensions
Dimension
“A”
13
¼
16
⅝
16
⅝
20
⅛
23
⅝
Dimension
“B”
19
19
19
19
19
¼
¼
¼
¼
¼
Concrete
Floor
Figure 10. Furnace on a Concrete Slab
Furnace
Sheet
Metal
Plenum
WARNING:
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system
being placed into operation could result in carbon monoxide poisoning or death.
The following steps shall be followed with each individual appliance connected to the venting
system being placed in operation, while all other appliances connected to the venting system
are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National
Fuel Gas Code, ANSI Z223. 1/NFPA 54 or the CSA B149.1, Natural Gas and Propane Installation
Codes and these instructions. Determine that there is no blockage or restriction, leakage,
corrosion and other defi ciencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space
in which the appliance(s) connected to the venting system are located and other spaces
of the building.
4. Close fi replace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on
any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at
maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust
the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after
5 minutes of main burner operation. Use the fl ame of a match or candle.
8. If improper venting is observed during any of the above tests, the venting system must
be corrected in accordance with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Codes.
9. After it has been determined that each appliance connected to the venting system properly
vents when tested as outlined above, return doors, windows, exhaust fans, fi replace
dampers and any other gas-fi red burning appliance to their previous conditions of use.
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.