Nordmann Engineering AT4 D Operating Instructions Manual

Page 1
Nordmann AT4 D
Steam generator
NORDMANN
ENGINEERING
OPERATING INSTRUCTIONS
2559432 EN 1412
Page 2
Page 3
Contents
1 Introduction 4
1.1 To the very beginning 4
1.2 Notes on the operating instructions 4
2 For your safety 6
3 Product Overview 8
3.1 Models overview 8
3.2 Identicationoftheunit 9
3.3 Steam generator construction 10
3.4 Functional description 11
3.5 Humidicationsystemoverview 13
4 Operation 14
4.1 Commissioning 14
4.2 Notes on operation 15
4.2.1 Functionofthedisplayandoperatingelements 15
4.2.2 Remoteoperatingandfaultindication 16
temperatures≤0°C 16
4.2.4 Inspectionsduringoperation 16
4.3 Carrying out manual draining 17
4.4 Takingtheunitoutofoperation 17
5 Working with the unit control 18
5.1 Operating the control unit and menu overview 18
5.2 Basic steam bath settings 20
5.2.1 Setting the temperature setpoint (steam bath operation) or humidity setpoint (caldarium operation) 20
5.2.2 Setting the control mode 20
5.2.3 Setting the steam bath time 21
5.2.4 Conguringthefragrancepump(s) 21
5.2.5 Switchingtheeffectlight(Light-2)onandoff 22
5.3 Unit settings in the user settings menu 23
5.3.1 Launchingtheusersettingsmenu 23
5.3.2 Selecting the dialogue language 23
5.3.3 Steam bath control settings 23
5.3.3.1 Setting the operation mode 24
5.3.3.2 Conguringweektimer 24
5.3.3.3 Settingthemaximumheatingtimefor
week timer operation 25
5.3.3.4 Fancontrolsettings 26
5.3.3.5 Fragrance pump control settings 30
5.3.3.6 Lightcontrolsettings 30
5.3.3.7 Sensor signal settings 31
5.3.3.8 Setting the controller type 35
5.3.3.9 Settingtheproportionalrangeforthe internal P/PI controller 35
5.3.3.10 SettingtheintegraltimefortheinternalPIcontroller 35
5.3.3.11 ConguringtheQuasiOn/Offcontrol 36
5.3.3.12 Settingthemaximumdooropeningtime 36
5.3.4 Selecting the cylinder type 37
5.3.5 ConguringtheSCsystem 37
5.3.5.1 Activating/deactivating the SC system 37
5.3.5.2 SettingtheoperationtimeoftheSC-Pump 38
5.3.6 Conguringthecapacitylimitation 38
5.3.7 Watermanagementsettings 39
5.3.7.1 Selectingtheconductivityrangeofthesupplywater 39
5.3.7.2 Settingthedrainfactor 39
5.3.7.3 Settingtheoperatingmodeforstandbyoperation 40
5.3.7.4 Activating/Deactivatingtheforceddraining 42
5.3.7.5 Settingthetimeofoperationafterwhicha forceddrainingtakesplace 43
5.3.8 Setting the date 43
5.3.9 Settingthetime 43
5.3.10 Setting the display contrast 43
5.4 Modbus settings 44
5.4.1 SettingsforModbusnetworks 44
5.4.2 Settingsforthecommunicationwiththe
optional remote terminal 45
5.5 Diagnosticfunctions 46
5.5.1 Interrogationoftheerrorhistory 46
5.5.2 Interrogationofunitinformation 47
5.5.3 Performingremotesteambathtests 48
5.5.4 Performingremoterelaytests 49
5.5.5 PerformingModuletests 49
5.6 Workingwiththeremoteterminal 50
5.6.1 Menuoverviewremoteterminal 50
5.6.2 Remoteterminalsettings 51
5.6.2.1 Selectingthedialoguelanguage 51
5.6.2.2 Settingthenumberofsteamgenerators
connected to the remote terminal 51
5.6.2.3 Interrogationoftheerrorhistoryofthe remote terminal 51
5.6.2.4 Resettingtheerrorhistorylistoftheremoteterminal 52
5.6.2.5 Settingthebaudrate 52
5.6.2.6 Settingthedisplaycontrast 52
6 Maintenance 53
6.1 Importantnotesonmaintenance 53
6.2 Maintenancelist 54
6.3 Removingandinstallingpartsformaintenance 55
6.3.1 Removalandinstallationofthesteamcylinder 55
6.3.2 Removalandinstallationofthedraincup 58
6.3.3 Removalandinstallationofthewatercupand thewaterhoses 59
6.3.4 Removalandinstallationofthedrainpump 60
6.3.5 Removalandinstallationoftheinletvalve 61
6.3.6 Removalandinstallationofthecylinderreceptacle 62
6.4 Notesoncleaningtheunitcomponents 63
6.5 Notesoncleaningagents 65
6.6 Resettingthemaintenanceindication 65
7 Fault elimination 66
7.1 Faultindication 66
7.2 Malfunctionlists 67
7.2.1 Systemfaults 67
7.2.2 Unitfaults 68
7.3 Notesonfaultelimination 70
7.4 Resettingtheerrorindication(redLEDlights) 70
7.5 Replacing the backup battery on the control board 71
8 Taking out of service/Disposal 72
8.1 Takingoutofservice 72
8.2 Disposal/Recycling 72
9 Productspecications 73
9.1 Technicaldata 73
9.2 WiringdiagramNordmannAT4D 74
3
Page 4

1 Introduction

1.1 To the very beginning

We thank you for having purchased the steam generator Nordmann AT4 D.
The steam generator Nordmann AT4 D incorporates the latest technical ad­van ces and meets all recognized safety standards. Nevertheless, improper use of the Nordmann AT4 D may result in danger to the user or third parties and/or impairment of material assets.
To ensure a safe, proper, and economical operation of the steam generator Nordmann AT4 D, please observe and comply with all information and safety instructions contained in the present operating instructions.
If you have questions, which are not or insufciently answered in this
documentation, please contact your Nordmann supplier. They will be glad to assist you.

1.2 Notes on the operating instructions

Limitation
The subject of these operating instructions is the steam generator Nordmann AT4 D
this is necessary for proper operation of the equipment. Further information on accessories can be obtained in the respective instructions.
These operating instructions are restricted to the commissioning, opera- tion, servicing and trouble shooting of the steam generator Nordmann AT4 D and is meant for well trained personnel being sufciently qualied for their respective work.
These operating instructions are supplemented by various separate items of documentation (installation instructions, spare parts list, manuals for ac­cessories, etc.). Where necessary, appropriate cross-references are made to these publications in the present documentation.
. The various accessories are only described insofar as
4
Page 5
Explanation of the symbols used in this manual
CAUTION!
The catchword “CAUTION” designates notes in this documentation that, if neglected, may cause damage and/or malfunction of the unit or other
material assets.
WARNING!
The catchword “WARNING” used in conjunction with the general caution symbol designates safety and danger notes in this documentation that, if neglected, may cause to injury to persons.
DANGER!
The catchword “DANGER” used in conjunction with the general caution symbol designates safety and danger notes in this documentation that, if neglected, may lead to severe injury or even death of persons.
Safekeeping
Please safeguard these operating instructions in a safe place, where it can be immediately accessed. If the equipment changes hands, the documenta­tion should be passed on to the new operator.
If the documentation gets mislaid, please contact your Nordmann supplier.
Language versions
The present operating instructions are available in various languages. Please contact your Nordmann supplier for information.
Copyright protection
The present operating instructions are protected under the Copyright Act. Passing-on and reproduction of the manual (or part thereof) as well as ex­ploitation and communication of the contents are prohibited without written permission by the manufacturer. Violation of copyright terms is subject to
legal prosecution and arises liability for indemnication.
The manufacturer reserves the right to fully exploit commercial patent rights.
5
Page 6

2 For your safety

General
Every person working with the Nordmann AT4 D must have read and un­derstood the present operating instructions before carrying out any work. Knowing and understanding the contents of the operating instructions is a basic requirement for protecting the personnel against any kind of danger, to prevent faulty operation, and to operate the unit safely and correctly.
All ideograms, signs and markings applied to the unit must be observed and kept in readable state.
Qualication of personnel
All actions described in the present operating instructions (operation, main­tenance, etc.) must be carried out only by well trained and sufciently qualied personnel authorised by the owner. For safety and warranty reasons any action beyond the scope of this
manuals must be carried out only by qualied personnel authorised by the
manufacturer.
It is assumed that all persons working with the Nordmann AT4 D are fa­miliar and comply with the appropriate regulations on work safety and the prevention of accidents.
This unit may not be used by persons (including children) with reduced physical, sensory or mental abilities or persons with lacking experience and/ or knowledge, unless they are supervised by a person responsible for their safety or they received instructions on how to operate the unit. Children must be supervised to make sure that they do not play with unit.
Intended use
The steam generator Nordmann AT4 D is intended exclusively for gen­eration of steam for a steam bath within the specied operating condi-
tions (see chapter 9 “Product specications”). Any other type of application
without the express written consent of the manufacturer is considered as not conforming with the intended purpose and may lead to the Nordmann AT4 D becoming dangerous. Operation of the equipment in the intended manner requires that all the
information in these instructions is observed (in particular the safety
instructions).
6
Page 7
Danger that may arise from the unit
DANGER! Danger of electric hazard!
The Nordmann AT4 D is mains powered. One may get in touch with live parts when the unit is open. Touching live parts may cause se­vere injury or danger to life.
Prevention: Before carrying out any work set the Nordmann AT4 D out of operation as described in chapter 4.4 (switch off the unit, disconnect it from the mains and stop the water supply) and secure the unit against inadvertent power-up.
WARNING! Hot water vapour - Danger of scalding!
The Nordmann AT4 D produces hot water vapour. There is danger of scalding when getting in touch with hot water vapour.
Prevention: Do not carry out any work on the steam system during op-
eration (steam lines, steam distributor, etc.). If the steam system is leaky set the Nordmann AT4 D immediately out of operation as described in chapter 4.4. Correctly seal the steam system before putting the unit into operation again.
WARNING! Danger of burning!
During operation the components of the steam system (steam cyl­inder, steam distributor, etc.) get very hot (up to 100 °C). There is
danger of burning when touching the hot components.
Prevention: Before carrying out any work on the steam system set the
Nordmann AT4 D out of operation as described in chapter 4.4, then wait until the components have cooled down sufciently thus preventing dan­ger of burning.
Behaviour in case of danger
If it is suspected that safe operation is no longer possible, then the Nor­dmann AT4 D should immediately be shut down and secured against accidental power-up according to chapter 4.4. This can be the case under the following circumstances: – if the Nordmann AT4 D is damaged – if the electrical installations are damaged – if the Nordmann AT4 D is no longer operating correctly – if connections and/or piping are not sealed
All persons working with the Nordmann AT4 D must report any alterations to the unit that may affect safety to the owner without delay.
Prohibited modications to the unit
No modications must be undertaken on the Nordmann AT4 D without
the express written consent of the manufacturer.
For the replacement of defective components use exclusively original ac- cessories and spare parts available from your Nordmann supplier.
7
Page 8

3 Product Overview

3.1 Models overview

Steam generators Nordmann AT4 D are available with different heating voltages and steam capacities ranging from 5 kg/h up to a maximum of 65 kg/h.
Heating voltage ** Max. steam capacity
in kg/h
5 534 x
8 834 x
400V3
(400 V/3~/50...60 Hz)
400V2
(400 V/2~/50...60 Hz)
230V3
(230 V/3~/50...60 Hz)
230V1
(230 V/1~/50...60 Hz)
** Other heating voltages on request
15 1534 x
23 2364 x
32 3264 x
45 4564 x
65 6564 x
5 524 x
8 824 x
5 532 x
8 832 x
15 1532 x
23 2362 x
32 3262 x
5 522 x
8 822 x
Model
Nordmann AT4 D
Unit size
small medium large
Key model designation
Product designation:
Unit model:
Heating voltage: 400V/3~/50...60Hz: 400V3 400V/2~/50...60Hz: 400V2 230V/3~/50...60Hz: 230V3 230V/1~/50...60Hz: 230V1
Example:
Nordmann AT4 D 4564 400V3
8
Page 9
3.2 Identicationoftheunit
The identication of the unit is found on the type plate:
Type designation Serial number (7 digits) Month/Year
Heating voltage
Maximum steam capacity per unit
Admissible water supply pressure
Field with certication symbols
Power consumption
Control voltage
Nordmann Engineering AG, CH-3562 Pfäfkon
Type: AT4 D 4564 Ser.Nr.: XXXXXXX 02.10 Heating voltage: 400V / 3~ / 50...60Hz Power: 33.8 kW
Steam capacity: 45.0 kg/h Ctrl. Voltage: 230V / 1~ / 50...60Hz Water pressure: 1...10 bar
Made in Switzerland
9
Page 10

3.3 Steam generator construction

16
17
18
19
20
21
22
23
24
29
28
27
26
25
1
2
3
4
5
6
7
8
9
10
11
12
13
30
31
gure shows medium unit
1 Steam cylinder compartment (small, medium, large) 2 Control compartment 3 Power board 4 Main contactor 5 Transformer 6 Steam bath board 7 Connecting terminals 8 Type plate 9 Remote operating and fault indication board (option) 10 Cable openings 11 Control board with CF Card 12 Display and control unit 13 Drain key 14 Operation status indicators 15 Unit switch 16 SC pump
14
15
17 Water cup 18 Filling and draining hose 19 Water supply hose
20 Overow hose
21 Inlet valve 22 Drain pump 23 Drain cup 24 Steam cylinder receptacle 25 Drain hose (manual drain) 26 Steam cylinder 27 Level sensor 28 Steam outlet 29 Electrode plug 30 Drain connector 31 Water supply connector
10
Page 11

3.4 Functional description

The steam generator Nordmann AT4 D is a pressureless steam generator that utilizes an electrode heating. The steam generator Nordmann AT4 D is designed for steam generation for steam baths.
Steam hose
Water cup
Overow hose
Filling and draining hose
Water supply hose
Inlet valve
Level sensor
SC pump
Control board
Drain hose
Electrodes
Steam cylinder
Steam distributor
Current sensor
Power board
Steam bath board
Unit switch
Main contactor
Drain pump
Connecting terminals
Steam cylinder receptacle
Steam generation
Any time steam is requested, the electrodes are supplied with voltage via main contactor. Simultaneously, the inlet valve opens and water enters the steam cylinder from the bottom via water cup and supply line. As soon as the
electrodes come in contact with the water, current begins to ow between
the electrodes, eventually heating and evaporating the water. The more the electrode surface is exposed to water, the higher is the current consumption and thus the steam capacity.
11
Page 12
Upon reaching the requested steam capacity, the inlet valve closes. If the steam generation decreases below a certain percentage of the required capacity, due to lowering of the water level (e.g. because of the evapora­tion process or drainage), the inlet valve opens until the required capacity is available again. If the required steam capacity is lower than the actual output, the inlet valve is closed until the desired capacity is achieved by lowering of the water level (evaporation process).
Level monitoring
A sensor provided in the steam cylinder cover detects when the water level gets too high. The moment the sensor comes in contact with water, the inlet valve closes.
Drainage
As a result of the evaporation process, the conductivity of the water increases due to an escalating mineral concentration. Eventually, an inadmissibly high current consumption would take place if this concentration process were permitted to continue. To prevent this concentration from reaching a value, unsuitably high for the operation, a certain amount of water is perio dically drained from the cylinder and replaced by fresh water.
Lime management
The interval controlled SC pump blows air into the steam cylinder. Thus keeping the solved minerals in the water in motion as a result they are discharged with the automatic drain cycles.
Control steam production
The steam production is controlled steplessly (continuous control) by the KTY temperature sensor (for steam bath operation) or by a humidity sensor (for caldarium operation) and the integrated continuous controller.
Steam bath control
The control of the steam bath components (light, fans, fragrance pumps, bench heating, etc.) is established via the integrated steam bath board.
12
Page 13
3.5 Humidicationsystemoverview
12
DS22
DS35
1
2
3
KTY
14
4
5
Z261
6
7
125...1250 µS/cm
1...10 bar
1...40 °C
1 Steam generator 2 Steam connector 3 Water drain connector 4 Water supply connector 5 Water connection hose G 3/4"- G 3/8"
(included in the delivery) 6 Filter valve (accessory “Z261”) 7 Manometer (installation recommended)
ONOFF
ONOFF
10
11
9
8
13
W22
W35
8 Funnel with siphon (building side) 9 Water drain hose (included in the delivery) 10 Service switch heating voltage supply (building side) 11 Service switch control voltage supply (building side) 12 Steam hose (accessory “DS22”/“DS35”) 13 Steam distributor (accessory “W..”/“DDS...”/“DDL...”) 14 Temperature sensor (accessory “KTY”) or humidity sen-
sor (caldarium operation)
13
Page 14

4 Operation

4.1 Commissioning

Proceed as follows when putting the steam generator into operation:
1. Examine the steam generator and installation for possible damage.
DANGER!
Damaged devices or devices with damaged installation may present danger to human life or cause severe damage to material assets.
Damaged units and/or units with damaged or faulty installation
must not be operated.
2. Check whether the front panels are mounted and correctly xed.
3. Open the lter valve (or the shut-off valve, respectively) in the water supply line.
4. Switch on the service switches for mains supplies (heating and control voltage).
5. Actuate the unit switch of the steam generator. Switch lights up.
AT4D
STARTUP:
INIT MODULE
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu
Light Start
AT4D 65kg/h 400V3
Steam Bath :Heating Temperature :45°C Setpoint :48°C 2011-08-31 12:00:00
Menu
Light Start
AT4D 65kg/h 400V3
Rest Time :45min Temperature :48°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Stop
The steam generator carries out a system test, during which all three LED’s light up. If a failure occurs on the system test, a corresponding error message is shown in the display.
After the system test the unit is in normal operation mode. The display shows the standard operating display (rst page of the indication level). Note: The contents of the standard operating display depends on the actual
operating status and on the conguration of the Nordmann AT4 D and can
differ from the opposite display.
Depending on the selected operating mode of the Nordmann AT4 D, the steam generator must manually be started via the Start/Stop button of the display and control unit or via an external Start/Stop button or the opera­tion runs time-controlled via the day timer or the week timer. As soon as the steam generator is started, the heating current is switched on. The inlet
valve opens (slight delay) and the steam cylinder lls with water. As soon as
the submerged electrodes heat the water up the green LED lights up and after a few minutes (approx. 5–10 minutes, depending on the conductivity of the water) steam is produced.
As soon as the set temperature (steam bath operation) or the set humidity (caldarium operation) in the steam bath cabin is achieved, the light is switched on and the bath phase starts. During the bath phase the fragrance pump (if available) is controlled in accordance with the selected operating mode
and the fan (or the ap actuator) is controlled in accordance with the set
temperature or humidity and the actual temperature or the actual humidity in the steam bath cabin.
14
Page 15
Note: If the Nordmann AT4 D is operated with water of low conductivity it
may happen that the maximum steam capacity is not reached in the rst few
hours of operation. This is normal. As soon as the conductivity has reached
a sufcient level (due to the vaporisation process) the steam generator will
reach the maximum steam capacity.

4.2 Notes on operation

4.2.1 Function of the display and operating elements

Display and control unit
Function: Conguration of the Nordmann AT4 D
Indication of operating parameters Reset of maintenance counter
Performing diagnostic functions
red LED “Malfunction”
Function: The LED lights in case of a severe malfunction of
the unit (Error status). Further operation is not pos­sible any longer. The error message is shown in the display, see chapter 7).
yellow LED “Maintenance”
Function: The LED lights if the steam cylinder must be replaced.
green LED “Humidication”
Function: The LED lights if the unit produces steam.
Drain key
Function: Calls up the dialogue for the manual draining
Unit switch
Function: Switches the unit on and off. The switch is illumi-
nated when the unit is on.
15
Page 16

4.2.2 Remote operating and fault indication

Via the operating and fault indication the following operating status are shown remotely:
Activated remote
indication relay
“Error” A error is present, further operation is
“Service” The steam cylinder is spent and must be
“Steam” Steam demand/Steam production Green LED lights and the
“Unit on” Unit is switched on. Unit switch lights and the
When? Display on unit
normally not possible any longer, the heating voltage is interrupted.
replaced. The unit remains operational for a certain time.
4.2.3 Notesontheoperationatambienttemperatures≤0°C
If during operation ambient temperatures ≤ 0°C must be expected (opera­tion of the Nordmann AT4 D in a protective housing outside the building), the standby draining function must be set to “Full” and the period of time in standby operation after which an automatic cylinder draining takes place must be set to 1 hour (see chapter 5.3.7.3).
Red LED lights and an error message is shown in the display.
Yellow LED lights and the service message is shown in the display.
standard operating dis­play is shown.
standard operating dis­play is shown.

4.2.4 Inspections during operation

During operation the Nordmann AT4 D and the humidication system have
to be inspected weekly. On this occasion check the following:
the water and steam installation for any leakage.
the steam generator and the other system components for correct xing
and any damage.
the electric installation for any damage.
If the inspection reveals any irregularities (e.g. leakage, error indication) or any damaged components take the Nordmann AT4 D out of operation as described in chapter 4.4. Then, contact your Nordmann representative.
16
Page 17

4.3 Carrying out manual draining

Proceed as follows to drain the unit manually:
1. Briey press the drain key. The draining dialogue appears in the display. Note: With double units both cylinders can be drained separately in the draining dialogue.
Manual Drain
Press START or STOP
Cyl.Cyl.B
2. Press the <Start> key. The heating voltage is interrupted and the drain pump starts. The yellow LED ashes. To stop the drain cycle briey press the <Stop> key.
Start
Esc
Note: by pressing the <Esc> key the display unit returns to the indication level. A draining cycle in progress is interrupted automatically.

4.4 Taking the unit out of operation

In order to take the steam generator out of operation, perform the following steps:
1. If the unit has to be switched off because of a malfunction, please note
the error code (number of ashes of the red and yellow LED) of the
actual error message shown in the display.
2. If possible, wait until the drying process of the steam bath cabin is n­ished.
3. Close the shut-off valve in the water supply line.
4. Start manual draining (see chapter 4.3) and wait until the steam cylinder is empty. Note: If the drain pump is defective, the steam cylinder is to be emptied manually via the manual draining hose.
5. Actuate the unit switch.
6. Disconnect steam generator from the mains: Switch off all service switches to mains supplies (heating and control voltage) and secure switches in “off” position against accidentally being switched on, and clearly mark the switches.
7. If ambient temperatures ≤ 0°C must be expected when the unit is out of operation (operation of the Nordmann AT4 D in a protective housing
outside the building): drain the water supply pipe and the water lter (lter valve).
WARNING! Danger of burning!
If steam was produced just before the unit is taken out of operation, wait before opening the unit and let the steam cylinder cool down to prevent danger of burning.
17
Page 18

5 Working with the unit control

Note: if you are working with the optional remote terminal read chapter 5.6
“Working with the remote terminal” rst. The operation of the remote terminal deviates in some points from the operation at the steam generator and some adjustments are blocked via the remote terminal for safety reasons.

5.1 Operating the control unit and menu overview

Operating
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu
Light Start
The operating and display unit is operated via the four keys located just
below the display. The 4 status elds at the bottom of the display show the
active keys the functions assigned to them.
actual key setting
keys
18
Page 19
Menu overview
Display steam bath operation Display caldarium operation
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu
Light Start
Main Menu
Setpoint :48°C
Operat.Mode :Manual Duration :45min Fragrance :Set
Light-2 :O
Esc Set
AT4D 65kg/h 400V3
Steam Bath :Standby Humidity :44.7%rH Setpoint :45%rH 2011-08-31 12:00:00
Menu Licht Start
Modifying temperature setpoint (steam bath operation) or humidity setpoint (caldarium operation) Setting steam bath mode Setting operating time in steam bath mode Fragrance pump settings Setting operating behaviour of light output 2
Main Menu
Fragrance :Set
Light-2 :O
User :Set
Engineering :Set Diagnostic :Set
Esc Set
User Code
3562
Enter Number
Conrm with Set
Esc Set
User
Maintenance :Set
Settings :Set Modbus :Set
Esc Set
Menu User Resetting the maintenance counter – Unit settings – Modbus settings
Indication level
Menu level
Main Menu
Fragrance :Set
Light-2 :O
User :Set
Engineering :Set
Diagnostic :Set
Esc Set
Main Menu
Fragrance :Set
Light-2 :O
User :Set Engineering :Set
Diagnostic :Set
Esc Set
Diagnostic
ErrorHistory:Set
Unit Status :Set Bath Test :Set Remote Test :Set Module Test :Set
Esc Set
Menu Engineering The engineering level requires special knowledge and may only be served by a Nordmann service technician.
Menu Diagnostic Interrogation of the malfunction list – Interrogation of unit information – Carrying out steam bath tests – Carrying out relay tests – Carrying out unit tests
19
Page 20

5.2 Basic steam bath settings

5.2.1 Setting the temperature setpoint (steam bath operation) or humidity setpoint (caldarium operation)

Select “Setpoint” in the main menu, then press the <Set> key.
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
Main Menu
Setpoint :48°C
Operat.Mode :Manual Duration :45min Fragrance :Set
Light-2 :O
Esc Set
In the upcoming modication dialogue set the desired temperature or humidity setpoint.
Factory setting: 48 °C (45 %rH)
Setting range: 25 ... 55 °C (30...90 %rH)

5.2.2 Setting the control mode

Note: this menu item is available only if the operating mode in the steam bath control settings (see chapter 5.3.3.1) is set to “Panel”.
Select “Operat.Mode” in the main menu, then press the <Set> key.
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
Main Menu
Setpoint :48°C
Operat.Mode :Manual
Duration :45min Fragrance :Set
Light-2 :O
Esc Set
Setpoint
48 °C 48 °C
Esc Set
Operat.Mode
Manual
Manual
Timer
Esc Set
In the upcoming modication dialogue select the desired control mode for panel operation.
Factory setting: Manual
Options: Manual, Timer
Description of the control mode settings
Manual: The steam generator must be switched on and off via the Start/Stop key of the display
and control unit or via an external Start/Stop key.
Timer: The steam generator is switched on and off time controlled via the day timer.
The timer settings can be accessed by pressing the <Timer> key in the standard
operating display.
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Timer
Main Menu
Status :O
Start time :12:00 Duration :45min
Esc Set
Status: activate (On) or deactivate (Off) timer function Note: the day timer must be activated every time after the steam
bath time has elapsed.
Start time: set starting time (format: hh:mm)
Duration: set heating time in minutes
20
Page 21

5.2.3 Setting the steam bath time

Note: this menu item is available only if the operating mode in the steam bath control settings (see chapter 5.3.3.1) is set to “Panel” and the control mode is set to “Manual” (see chapter 5.2.2).
Select “Duration” in the main menu, then press the <Set> key.
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
Main Menu
Setpoint :48°C Operat.Mode :Manual
Duration :45min
Fragrance :Set
Light-2 :O
Esc Set
In the upcoming modication dialogue set the desired steam bath time.
Factory setting: 45 minutes
Setting range: 1 ... 1080 minutes
5.2.4 Conguringthefragrancepump(s)
Select “Fragrance” in the main menu, then press the <Set> key. In the upcoming display, select the desired fragrance pump whose settings you want to modify, then press the <Set> key.
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
In the upcoming modication dialogue set the desired intensity level (1-5 or 0: fragrance pump deacti­vated) for the selected fragrance pump.
Factory setting: 0
Setting range: 0: fragrance pump deactivated
1: interval time: 10 minutes, pulse duration: 2 seconds 2: interval time: 8 minutes, pulse duration: 3 seconds 3: interval time: 6 minutes, pulse duration: 3 seconds
4: interval time: 4 minutes, pulse duration: 4 seconds 5: interval time: 3 minutes, pulse duration: 5 seconds
Main Menu
Operat.Mode :Manual Duration :45min
Fragrance :Set
Light-2 :O
User :Set
Esc Set
Duration
45 min 45 min
Esc Set
Fragrance
Aroma1 Level:0
Aroma2 Level:0
Fragrance :Set
Esc Set
Aroma1 Level
0 0
Esc Set
Note: the fragrance pump is active only, if the main contactor of the steam generator is activated and the system is in steam bath operation.
Note: the interval time and the pulse duration of the fragrance injection can be set individually in the engineering level. If necessary, please contact your Nordmann service technician.
21
Page 22

5.2.5 Switching the effect light (Light-2) on and off

Select “Light-2” in the main menu, then press the <Set> key.
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
Main Menu
Duration :45min Fragrance :Set
Light-2 :O
User :Set Engineering :Set
Esc Set
Light-2
O
O
On
Esc Set
In the upcoming modication dialogue you can switch on and off the effect light (Light-2).
Factory setting: Off
Setting range: Off (effect light switched off)
On (effect light switched on)
22
Page 23

5.3 Unit settings in the user settings menu

5.3.1 Launching the user settings menu

Select the user settings menu: Path: Main Menu > User > Password entry: 3562 > Settings
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
Main Menu
Fragrance :Set
Light-2 :O
User :Set
Engineering :Set Diagnostic :Set
Esc Set
User Code
3562
Enter Number
Conrm with Set
Esc Set
The setting parameters appear. Press the < > and < > keys in order to select the individual settings or settings submenus. Detailed information on the different settings are found in the following chapters.

5.3.2 Selecting the dialogue language

Select “Language” in the unit settings menu, then press the <Set> key.
Settings
Language :English
BathSettings:Set Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
Language
English
English
German French Italian
Esc Set
User
Maintenance :Set
Settings :Set
Modbus :Set
Esc Set
Settings
Language :English
BathSettings:Set Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
Water Manag.:Set Date :11-08-31 Time :12:00 Contrast :15
In the upcoming modication dialogue select the desired dialogue language. After conrmation, the unit
automatically switches to the selected dialogue language.
Factory setting: country specic
Options: diverse languages

5.3.3 Steam bath control settings

Select “BathSettings” in the unit settings menu, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
The setting parameter for the steam bath control appear. Press the < > and < > keys in order to select the individual settings or settings submenus. Detailed information on the different settings are found in the following chapters.
BathSettings
Operation :Panel
Fan :Set Fragrance :Set Light :Set Sensor :Set
Esc Set
Control :Int.(P) P-Band :4°C Operat.Range:Set Max.DoorOpen:2min
23
Page 24
5.3.3.1 Setting the operation mode
Select “Operation” in the steam bath settings menu, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Operation :Panel
Fan :Set Fragrance :Set Light :Set Sensor :Set
Esc Set
Opertion
Panel
Panel
WeekTime
Esc Set
In the upcoming modication dialogue you determine, whether the bathing operation shall be started
manually or via the day timer function (Panel) or automatically via the week timer function (WeekTime).
Factory setting: Panel
Options: Panel (manually or day timer controlled)
WeekTime (week timer controlled)
5.3.3.2 Conguringweektimer
Note: this menu item is available only if the operating mode (see chapter 5.3.3.1) is set to “WeekTime”.
– Deactivating the Week Timer :
Select “Week Timer” in the steam bath settings menu, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Operation :WeekTime
Week Timer :Set
Max Heating :24h Fan :Set Fragrance :Set
Esc Set
Week Timer
Timer :On
Event 1 :12:00 Event 2 :13:00 Event 3 :14:00 Event 4 :--:--
Esc Set
Week Timer
Timer :O
Esc Set
Timer
O
O
On
Esc Set
Select “Timer”, then press the <Set> key. In the upcoming modication dialogue deactivate (off) the timer function and conrm the setting with the <Set> key.
If the timer functions is deactivated the Nordmann AT4 remains in standby operation until the timer is activated again or the operating mode is changed to “Panel” (see chapter 5.3.3.1).
24
Page 25
– Activating and conguring the Week Timer :
Select “Week Timer” in the steam bath settings menu, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Operation :WeekTime
Week Timer :Set
Max Heating :24h Fan :Set Fragrance :Set
Esc Set
Week Timer
Timer :On
Event 1 :06:00 Event 2 :18:00 Event 3 :--:-­Event 4 :--:--
Esc Set
Week Timer
Timer :On Event 1 :12:00
Event 2 :13:00
Event 3 :14:00 Event 4 :--:--
Esc Set
Week Timer
Timer :O
Esc Set
Event 2
Weekday :Mo-Fr
Time :13:00 Steam Bath :On
Esc Set
Event 2
Weekday :Mo-Fr
Time :13:00
Steam Bath :On
Esc Set
Event 2
Weekday :Mo-Fr Time :13:00
Steam Bath :On
Esc Set
Timer
On
O
On
Esc Set
Weekday
Mo-Fr
O
Mo-Fr
Mo-Sa Mo-Su
Esc Set
Time
13:00
13:00
Esc Set
Steam Bath
On
O
On
Esc Set
Select “Timer”, then press the <Set> key. In the upcoming modication dialogue activate (On) the timer function and conrm the setting with the <Set> key.
If the timer is activated, up to eight switching points (events 1 - 8) with different operating status
of the steam generator can be dened. Each switching point is dened by a weekday or weekday
range, the switching point and the operating status of the steam generator.
Conguration notes:
– the settings of an event remain active up to the next event. – the software does not check the plausibility of the timer settings. Therefore, make sure your
settings make sense.
5.3.3.3 Setting the maximum heating time for week timer operation
Note: this menu item is available only if the operating mode (see chapter 5.3.3.1) is set to “WeekTime”.
Select “Max.Heating” in the steam bath settings menu, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Operation :WeekTime Week Timer :Set
Max.Heating :24h
Fan :Set Fragrance :Set
Esc Set
In the upcoming modication dialogue set the maximum heating time in hours.
Factory setting: 1 hours
Setting range: 1 ... 24 hours
Max.Heating
24 h 24 h
Esc Set
25
Page 26
5.3.3.4 Fan control settings
– Operation without fan
Select “Fan” in the steam bath settings menu, then press the <Set> key. In the following display select “Mode”, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Operation :Panel
Fan :Set
Fragrance :Set Light :Set Sensor :Set
Esc Set
Fan
Mode :1-Fan
While Light :On Fan Out :Set
Esc Set
Fan
Mode :O
Esc Set
Mode
O
O
1-Fan 2-Fan
Esc Set
Adjust the settings for the operation without fan as follows:
Mode”: Off
Note: use this setting if no fan is connected to the Nordmann AT4 D (e.g. for steam baths with ap
actuators). In the bathing operation without fan the drying phase is omitted.
– Operation with 3-step exhaust air fan
Select “Fan” in the steam bath settings menu, then press the <Set> key. In the following display select “Mode”, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Operation :Panel
Fan :Set
Fragrance :Set Light :Set Sensor :Set
Esc Set
Fan
Mode :O
Esc Set
Mode
1-Fan
O
1-Fan
2-Fan
Esc Set
Fan
Mode :1-Fan
While Light :On Fan Out :Set
Esc Set
Fan
Mode :1-Fan
While Light :On
Fan Out :Set
Esc Set
Fan
Mode :1-Fan While Light :On
Fan Out :Set
Esc Set
While Light
On
O
On
Esc Set
Fan Out
Drying Time :20min
Hysteresis :4°C
Esc Set
Fan Out
Drying Time :20min
Hysteresis :4°C
Esc Set
Adjust the settings for the operation with a 3-step exhaust air fan as follows:
Mode”: 1-Fan
Drying Time
20 min 20 min
Esc Set
Hysteresis
4 °C 4 °C
Esc Set
26
While Light”: If this function is activated (On, factory setting) the 3-step exhaust air fan starts running on step 1, as soon as light 1 or light 2 is switched on in standby mode. The fan stops if the light is switched off again.
Page 27
“Fan Out”: Settings for the control of the exhaust fan.
Drying Time”: Time in minutes the exhaust fan continues to run after the steam bath
time has elapsed to dry the steam bath cabin (Factory setting: 20 min­utes, Setting range: 1...60 minutes).
Hysteresis”: Hysteresis value in °C (steam bath operation) or %rh (caldarium opera- tion) to switch on and off the exhaust fan (Factory setting: 4 °C/18 %rh, Setting range: 2...60 °C/6...65 %rh).
Note: in steam bath operation the exhaust fan switches off if the tempera-
ture or the humidity in the steam bath cabin drops half of the selected hysteresis value below the set setpoint value, and switches on if the temperature or the humidity in the steam bath cabin increases half of the selected hysteresis above the set setpoint value.
27
Page 28
– Operation with supply and exhaust fan
In this operation mode a supply and an exhaust fan is connected to the Nordmann AT4 D.
Select “Fan” in the steam bath settings menu, then press the <Set> key. In the following display select “Mode”, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Operation :Panel
Fan :Set
Fragrance :Set Light :Set Sensor :Set
Esc Set
Fan
Mode :2-Fan
WhileBathing:Supply While Light :On Fan In :Set Fan Out :Set
Esc Set
Fan
Mode :2-Fan
WhileBathing:Supply
While Light :On Fan In :Set Fan Out :Set
Esc Set
Fan
Mode :2-Fan WhileBathing:Supply
While Light :On
Fan In :Set Fan Out :Set
Esc Set
Fan
Mode :2-Fan WhileBathing:Supply While Light :On
Fan In :Set
Fan Out :Set
Esc Set
Fan
Mode :O
Esc Set
WhileBathign
Supply
O
Supply
Exhaust BothFan
Esc Set
While Light
Bei Licht
On
Ein
O
Aus
On
Ein
Esc Set
Esc Set
Fan In
PrePurgeTime:2min
Drying Time :20min Hysterese :4°C
Esc Set
Mode
2-Fan
O
1-Fan
2-Fan
Esc Set
PrePurgeTime
2 min 2 min
Esc Set
Fan
Mode :2-Fan WhileBathing:Supply While Light :On Fan In :Set
Fan Out :Set
Esc Set
Fan In
PrePurgeTime:2min
Drying Time :20min
Hysteresis :4°C
Esc Set
Fan In
PrePurgeTime:2min Drying Time :20min
Hysteresis :4°C
Esc Set
Fan Out
PrePurgeTime:2min
Drying Time :20min Hysteresis :4°C
Esc Set
Fan Out
PrePurgeTime:2min
Drying Time :20min
Hysteresis :4°C
Esc Set
Fan Out
PrePurgeTime:2min Drying Time :20min
Hysteresis :4°C
Drying Time
20 min 20 min
Esc Set
Hysteresis
4 °C 4 °C
Esc Set
PrePurgeTime
2 min 2 min
Esc Set
Drying Time
20 min 20 min
Esc Set
Hysteresis
4 °C 4 °C
28
Esc Set
Esc Set
Page 29
Adjust the settings for the operation with a supply and an exhaust fan as follows:
• Mode
• WhileBathing
”: 2-Fan
”: Activation mode of the fans in bathing operation
 Off” (both fans remain switched off during bathing operation)  Supply” (only the supply air fan is running during bathing operation)  Exhaust” (only the exhaust air fan is running during bathing operation)  BothFan” (both fans are running during bathing operation)  Automat.” (during bathing operation both fans are controlled automatically
dependent on the temperature or the humidity in the steam bath cabin)
• While Light
”: If this function is activated (On, factory setting) the exhaust fan starts run-
ning, as soon as light 1 or light 2 is switched on in standby mode. The fan stops if the light is switched off again.
“Fan In”: Settings for the control of the supply fan.
Note: If the supply fan is controlled with the “RLS” option dependent on the heating voltage (supply fan is running, when the heating voltage contactor is switched on) all software settings of the supply fan are without function.
• PrePurgeTime
”: Time in minutes in the heating phase during which the supply fan is
switched on (Factory setting: 2 minutes, Setting range: 0...60 minutes).
• Drying Time”: Time in minutes the supply fan continues to run after the steam bath time has elapsed to dry the steam bath cabin (Factory setting: 20 minutes, Setting range: 1...60 minutes).
• Hysteresis
”: Hysteresis value in °C (steam bath operation) or %rh (caldarium opera-
tion) to switch on and off the supply fan (Factory setting: 4 °C/18 %rh, Setting range: 2...60 °C/6...65 %rh).
Note: in steam bath operation the supply fan switches off if the tempera-
ture or the humidity in the steam bath cabin drops half of the selected hysteresis value below the set setpoint value, and switches on if the temperature or the humidity in the steam bath cabin increases half of the selected hysteresis above the set setpoint value.
“Fan Out”: Settings for the control of the exhaust fan.
• PrePurgeTime”: Time in minutes in the heating phase during which the exhaust fan is switched on (Factory setting: 2 minutes, Setting range: 0...60 minutes).
• Drying Time”: Time in minutes the exhaust fan continues to run after the steam bath time has elapsed to dry the steam bath cabin (Factory setting: 20 min­utes, Setting range: 1...60 minutes).
• Hysteresis
”: Hysteresis value in °C (steam bath operation) or %rh (caldarium opera-
tion) to switch on and off the exhaust fan (Factory setting: 4 °C/18 %rh, Setting range: 2...60 °C/6...65 %rh).
Note: in steam bath operation the exhaust fan switches off if the tempera-
ture or the humidity in the steam bath cabin drops half of the selected hysteresis value below the set setpoint value, and switches on if the temperature or the humidity in the steam bath cabin increases half of the selected hysteresis above the set setpoint value.
29
Page 30
5.3.3.5 Fragrance pump control settings
At the Nordmann AT4 D control two fragrance pumps can be connected, which can be activated either via the integrated interval control or via an external push-button.
Select “Fragrance” in the steam bath settings menu, then press the <Set> key. In the upcoming display, select the desired fragrance pump whose operating mode you want to modify, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Operation :Panel Fan :Set
Fragrance :Set
Light :Set Sensor :Set
Esc Set
Fragrance
Fragrance-1 :Interval
Fragrance-2 :Interval
Esc Set
Fragrance-1
Interval
Interval
External
Esc Set
In the upcoming modication dialogue select the desired operating mode for the selected fragrance pump.
Factory setting: Interval
Options: Interval (fragrance pump is activated via the integrated interval) External (fragrance pump must be activated manually via an external push-button)
Note: the fragrance pump is active only, if the main contactor of the steam generator is activated and the system is in steam bath operation.
5.3.3.6 Light control settings
At the Nordmann AT4 D control a cabin light (Light-1) or effect light (Light-2) can be connected. Both lights can be switched on independently either manually automatically.
Select “Light” in the steam bath settings menu, then press the <Set> key. In the upcoming display, select the desired light whose operating mode you want to modify, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Fan :Set Fragrance :Set
Light :Set
Sensor :Set Control :Int.(P)
Esc Set
Light
Light-1 :Manual
Light-2 :Manual
Esc Set
Light-1
Automat. Manual
Automat.
Esc Set
Light
Light-1 :Automat.
Light-2 :Manual
LightO :5min
Esc Set
Light
Light-1 :Automat. Light-2 :Manuell
LightO :5min
Esc Set
LightO
5 min 5 min
Esc Set
In the upcoming modication dialogue select the desired operating mode for the selected light.
Factory setting: Manual
Options: Manual (manual activation of light 1 and light 2 via light switches) Automat. (automatic activation of light 1 and light 2 as soon as the set steam
bath temperature (steam bath operation) or the set humidity (caldarium operation) is reached in the steam bath cabin)
Note: if automatic activation of light is selected the menu item “LightOff” appears additionally. With this setting you can determine how long the light remains switched on after the steam bath time has ended (Factory setting: 5 minutes, Setting range: 1... 600 minutes).
30
Page 31
5.3.3.7 Sensor signal settings
With the parameters in the submenu “Sensor” you can congure the sensor signal settings.
– Temperature signal input from analogue temperature sensor (KTY, PT100, PT-1000) connected
to the steam bath print.
Select “Sensor” in the steam bath settings menu, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Fragrance :Set Light :Set
Sensor :Set
Control :Int.(P) P-Band :4°C
Esc Set
Sensor
SignalSource:Analog
Mode :Temp. Type :KTY
Oset :0.0°C
Esc Set
Sensor
SignalSource:Analog
Mode :Temp. Type :KTY
Oset :0.0°C
Esc Set
Sensor
SignalSource:Analog
Mode :Temp.
Type :KTY
Oset :0.0°C
Esc Set
Sensor
SignalSource:Analog Mode :Temp.
Type :KTY
Oset :0.0°C
Esc Set
Sensor
SignalSource:Analog Mode :Temp. Type :KTY
Oset :0.0°C
Esc Set
SignalSource
Analog
Analog
Modbus
Esc Set
Mode
Temp.
Temp.
Humidity
Esc Set
Type
KTY
KTY
PT-100 PT-1000 0-10V
Esc Set
Oset
0.0 °C
0.0 °C
Esc Set
Adjust the parameters in the submenu “Sensor” as follows:
SignalSource”: “Analog
Mode”: “Temp.
Type”: “KTY”, “PT-100” or “PT-1000
Offset”: Temperature offset of the selected temperature sensor to the temperature
value measured with a proofed measuring instrument in the steam bath cabin (Factory setting: 0.0 °C, Setting range: –5 °C...5 °C)
31
Page 32
Linearised 0-10V temperature signal from a temperature sensor or a building management system
connected to the control signal input on the power board of the Nordmann AT4 D.
Select “Sensor” in the steam bath settings menu, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Fragrance :Set Light :Set
Sensor :Set
Control :Int.(P) P-Band :4°C
Esc Set
Sensor
SignalSource:Analog
Mode :Temp. Type :KTY
Oset :0.0°C
Esc Set
Sensor
SignalSource:Analog
Mode :Temp. Type :KTY
Oset :0.0°C
Esc Set
Sensor
SignalSource:Analog
Mode :Temp.
Type :KTY
Oset :0.0°C
Esc Set
Sensor
SignalSource:Analog Mode :Temp.
Type :0-10V
0V-Temp. :0°C 10V-Temp. :100°C
Esc Set
Sensor
SignalSource:Analog Mode :Temp. Type :0-10V
0V-Temp. :0°C
10V-Temp. :100°C
Esc Set
SignalSource
Analog
Analog
Modbus
Esc Set
Mode
Temp.
Temp.
Humidity
Esc Set
Type
0-10V KTY PT100 PT1000
0-10V
Esc Set
0V-Temp.
0 °C 0 °C
Esc Set
Sensor
SignalSource:Analog Mode :Temp. Type :0-10V 0V-Temp. :0°C
10V-Temp. :100°C
Esc Set
10V-Temp.
100 °C 100 °C
Esc Set
Adjust the parameters in the submenu “Sensor” as follows:
SignalSource”: “Analog
Mode”: “Temp.
Type”: “0-10V
0V-Temp.”: 0V temperature value in °C of the connected 0-10V temperature sensor
(Factory setting: 0 °C, Setting range: -50...+20 °C)
10V-Temp.”: 10V temperature value in °C of the connected 0-10V temperature sensor (Factory setting: 100°C, Setting range: +80...+200 °C)
32
Page 33
– Humidity signal input from analogue humidity sensor connected to the signal input on the power
board of the steam generator (caldarium operation).
Select “Sensor” in the steam bath settings menu, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Fragrance :Set Light :Set
Sensor :Set
Control :Int.(P) P-Band :4°C
Esc Set
Sensor
SignalSource:Analog
Mode :Temp. Type :KTY
Oset :0.0°C
Esc Set
Sensor
SignalSource:Analog
Mode :Temp. Type :0-10V
Esc Set
Sensor
SignalSource:Analog
Mode :Humidity
Type :0-10V
Esc Set
Sensor
SignalSource:Analog Mode :Humidity
Type :0-10V
Esc Set
Adjust the parameters in the submenu “Sensor” as follows:
SignalSource”: “Analog
SignalSource
Analog
Analog
Modbus
Esc Set
Mode
Humidity Temp.
Humidity
0-10V
Esc Set
Type
0-10V 0-5VPoti 1-5V
1-10V
2-10V
Esc Set
Mode”: “Humidity
Type”: Sensor signal type (Factory setting: 0–10V, Options: 0–5V, 1–5V, 0–10V,
2–10V, 0–16V, 3.2–16V, 0–20mA, 4–20mA)
33
Page 34
Control signal (temperature or humidity signal) input via Modbus
Select “Sensor” in the steam bath settings menu, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Fragrance :Set Light :Set
Sensor :Set
Control :Int.(P) P-Band :4°C
Esc Set
Sensor
SignalSource:Analog
Mode :Temp. Typ :KTY
Oset :0.0°C
Esc Set
Sensor
SignalSource:Modbus
Timeout :5s Mode :Temp.
Esc Set
Sensor
SignalSource:Modbus
Timeout :5s
Mode :Temp.
Esc Set
Sensor
SignalSource:Modbus Timeout :5s
Mode :Temp.
Esc Set
Adjust the parameters in the submenu “Sensor” as follows:
SignalSource”: “Modbus
SignalSource
Modbus Analog
Modbus
Esc Set
Timeout
5 s 5 s
Esc Set
Mode
Temp.
Temp.
Humidity
Esc Set
Timeout”: Timeout in seconds for signal transmission (Factory setting: 5 seconds, Setting range: 1...600 seconds)
Mode”: Temp. (control via a temperature signal for steam bath operation) or Humid- ity (control via a humidity signal for caldarium operation)
34
Page 35
5.3.3.8 Setting the controller type
Select “Control” in the steam bath settings menu, then press the <Set>.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Light :Set Sensor :Set
Control :Int.(P)
P-Band :4°C Operat.Range:Set
Esc Set
Control
Int.(P)
Int.(P)
Int.(PI)
Esc Set
In the upcoming modication dialogue select the desired controller type.
Factory setting: Int (P)
Options: Int (P) or Int (PI)
5.3.3.9 Setting the proportional range for the internal P/PI controller
Select “P-Band” in the steam bath settings menu, then press the <Set>.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
In the upcoming modication dialogue set the proportional range in °C or %rH (caldarium operation) for
the internal P/PI controller.
Factory setting: 4 °C (18 %rH)
Options: 2...60 °C (6...65 %rH)
BathSettings
Sensor :Set Control :Int.(P)
P-Band :4°C
Operat.Range:Set Max.DoorOpen:2min
Esc Set
P-Band
4 °C 4 °C
Esc Set
5.3.3.10 Setting the integral time for the internal PI controller
Note: this setting is available only if the internal PI controller is activated.
Select “Integr.-Time” in the steam bath settings menu, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
In the upcoming modication dialogue set the integral time in minutes for the internal PI controller.
Factory setting: 2 minutes
Options: 1...60 minutes
BathSettings
Control :Int.(PI) P-Band :4°C
Integr.-Time:2min
Operat.Range:Set Max.DoorOpen:2min
Esc Set
Integr.-Time
2 min 2 min
Esc Set
35
Page 36
5.3.3.11 ConguringtheQuasiOn/Offcontrol
With the parameters in the submenu “Operat.Range” you can control the operation of Nordmann AT4 D in such a way that the steam production is started only from a certain request and stopped again, if the request has dropped by a certain percentage.
Select “Operat.Range” in the steam bath settings menu, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
BathSettings
Control :Int.(PI) P-Band :4°C Integr.-Time:2min
Operat.Range:Set
Max.DoorOpen:2min
Esc Set
Operat.Range
Mode :O
OnThreshold :60% Hysteresis :5%
Esc Set
Operat.Range
Mode :On
OnThreshold :60% Hysteresis :5%
Esc Set
Operat.Range
Mode :On
OnThreshold :60%
Hysteresis :5%
Esc Set
Operat.Range
Mode :On OnThreshold :60%
Hysteresis :5%
Esc Set
Mode
On
O
On
Esc Set
OnThreshold
60 % 60 %
Esc Set
Hysteresis
5 % 5 %
Esc Set
Adjust the parameters in the submenu “Operat.Range” for the quasi On/Off control to the desired values:
Mode”: Activating/Deactivating the quasi On/Off control function (Factory setting: Off)
OnThreshold”: Demand in % of the maximum steam capacity at which the steam production is to
be started (Factory setting: 60 %, Setting range: 30...90 %)
Hysteresis”: Percentage, the request must drop, until the steam operation is stopped (Factory setting: 5 %, Setting range: 1...20%)
5.3.3.12 Setting the maximum door opening time
Select “Max.DoorOpen” in the steam bath settings menu, then press the <Set> key.
Settings
Language :English
BathSettings:Set
Cylinder :4564 SC-System :Set
Power Limit :100%
Esc Set
In the upcoming modication dialogue set the maximum time in minutes the steam bath door may be
open, until the bathing operation is stopped.
Factory setting: 2 minutes
Options: 1...30 minutes
BathSettings
Control :Int.(PI) P-Band :4°C Integr.-Time:2min Operat.Range:Set
Max.DoorOpen:2min
Esc Set
Max.DoorOpen
2 min 2 min
Esc Set
36
Page 37

5.3.4 Selecting the cylinder type

Note: this function is not available via the optional remote terminal.
Select “Cylinder” in the user settings menu, then press the <Set> key.
Settings
Language :English BathSettings:Set
Cylinder :4564
SC-System :Set
Power Limit :100%
Esc Set
Cylinder
6564 3262 3264 4564
6564
Esc Set
In the upcoming modication dialogue select the steam cylinder type installed in the unit (see type plate
on the steam cylinder).
Factory setting: according to the installed cylinder
Options: 522, 524, 532, 534, 822, 824, 832, 834, 1532, 1534, 2362, 2364, 3262, 3264,
4564, 6564
5.3.5 ConguringtheSCsystem
Select “SC-System” in the user settings menu, then press the <Set> key.
Settings
BathSettings:Set Cylinder :4564
SC-System :Set
Power Limit :100%
Water Manag.:Set
Esc Set
The settings parameter for the lime management system appear. Detailed information on the different settings are found in the following chapters.
SC-System
SC-Pump :On
On-Time :20min
Esc Set
5.3.5.1 Activating/deactivating the SC system
Select “SC-Pump” in the SC system settings menu, then press the <Set> key.
Settings
BathSettings:Set Cylinder :4564
SC-System :Set
Power Limit :100%
Water Manag.:Set
Esc Set
SC-System
SC-Pump :On
On-Time :20min
Esc Set
In the upcoming modication dialogue activate or deactivate the SC system.
Factory setting: On
Options: On, Off
SC-Pump
On
O
On
Esc Set
37
Page 38
5.3.5.2 Setting the operation time of the SC-Pump
Select “On-Time” in the SC-System settings menu, then press the <Set> key.
Settings
BathSettings:Set Cylinder :4564
SC-System :Set
Power Limit :100%
Water Manag.:Set
Esc Set
SC-System
SC-Pump :On
OnTime :20min
Esc Set
In the upcoming modication dialogue set the operating time of the SC-Pump per hour in minutes.
Factory setting: 20 minutes
Setting range: 20 ... 60 minutes
5.3.6 Conguringthecapacitylimitation
Select “Power Limit” in the user settings menu, then press the <Set> key.
Settings
Cylinder :4564 SC-System :Set
Power Limit :100%
Water Manag.:Set Date
Esc Set
In the upcoming modication set the desired capacity limitation in % of maximum steam capacity.
Factory setting: 100 %
Setting range: 30 ... 100 %
Power Limit
100 % 100 %
Esc Set
OnTime
20 min 20 min
Esc Set
38
Page 39

5.3.7 Water management settings

Select “Water Manag.” in the user settings menu, then press the <Set> key.
Settings
SC-System :Set
Power Limit :100%
Water Manag.:Set
Date :11-08-31 Time :12:00
Esc Set
Water Manag.
Conductivity:>125µS
Drain Factor:1.0 Idle Operat.:Set Force Drain :On Force Delay :72h
Esc Set
The water management settings appear. Press the < > and < > keys in order to select the individual settings. Detailed information on the different settings are found in the following chapters.
5.3.7.1 Selecting the conductivity range of the supply water
Select “Conductivity” in the water management settings submenu, then press the <Set> key.
Settings
SC-System :Set
Power Limit :100%
Water Manag.:Set
Date :11-08-31 Time :12:00
Esc Set
In the upcoming modication dialogue select the conductivity range of the supply water.
Factory setting: >125 μS/cm
Options: >125 μS/cm, <125 μS/cm
Water Manag.
Conductivity:>125µS
Drain Factor:1.0 Idle Operat.:Set Force Drain :On Force Delay :72h
Esc Set
Conductivity
>125µS
>125µS
<125µS
Esc Set
5.3.7.2 Setting the drain factor
Select “Drain Factor” in the water management settings submenu, then press the <Set> key.
Settings
SC-System :Set
Power Limit :100%
Water Manag.:Set
Date :11-08-31 Time :12:00
Esc Set
In the upcoming modication dialogue set the drain factor in relation to the steam capacity.
Factory setting: 1.0
Setting range: 0.5...2.0
Water Manag.
Conductivity:>125µS
Drain Factor:1.0
Idle Operat.:Set Force Drain :On Force Delay :72h
Esc Set
Drain Factor
1.0
1.0
Esc Set
39
Page 40
5.3.7.3 Setting the operating mode for standby operation
Idle only operation
In this operating mode the cylinder is not emptied in standby operation.
Select “Idle Operat.” in the water management settings submenu, then press the <Set> key. In the upcoming submenu select “Idle Mode”, then press the <Set> key.
Settings
SC-System :Set Power Limit :100%
Water Manag.:Set
Date :11-08-31 Time :12:00
Esc Set
Water Manag.
Conductivity:>125µS Drain Factor:1.0
Idle Operat.:Set
Force Drain :On Force Delay :72h
Esc Set
Idle Operat.
Idle Mode :Drain
Drain Mode :Full Drain Delay :72h
Esc Set
Idle Operat.
Idle Mode :IdleOnly
Esc Set
Idle Mode
IdleOnly
IdleOnly
Drain KeepWarm A.Freeze
Esc Set
In the upcoming modication dialogue set Idle Mode to “IdleOnly”, then press the <Set> key.
Standby operation with partial or complete draining of the steam cylinder
In this operating mode the cylinder is partly or fully drained after a certain time in standby operation.
Select “Idle Operat.” in the water management settings submenu, then press the <Set> key. In the upcoming Idle submenu set the parameters for standby operation with partial or complete draining of the steam cylinder.
Settings
SC-System :Set Power Limit :100%
Water Manag.:Set
Date :11-08-31 Time :12:00
Esc Set
Water Manag.
Conductivity:>125µS Drain Factor:1.0
Idle Operat.:Set
Force Drain :On Force Delay :72h
Esc Set
Idle Operat.
Idle Mode :IdleOnly
Esc Set
Idle Mode
Drain IdleOnly
Drain
KeepWarm A.Freeze
Esc Set
Idle Operat.
Idle Mode :Drain
Drain Mode :Full Drain Delay :72h
Esc Set
Idle Operat.
Idle Mode :Drain
Drain Mode :Full
Drain Delay :72h
Esc Set
Idle Operat.
Idle Mode :Drain Drain Mode :Full
Drain Delay :72h
Esc Set
Drain Mode
Full Partial
Full
Esc Set
Drain Delay
72 h 72 h
Esc Set
Settings:
Idle Mode”: “Drain
Drain Mode”: “Full” (complete draining of the cylinder) or “Partial” (cylinder is drained so
far that the water does not touch the electrodes any longer)
Important: with outdoor operation it is mandatory to set the drain mode
to “Full”.
40
Page 41
• Drain Delay”: period of time in standby operation after which an automatic cylinder drain- ing (partial or complete) takes place (Factory setting: 72 h., Setting range:
1...720 h).
Important: with outdoor operation it is mandatory to set the period of
time in standby operation after which an automatic cylinder draining takes place to 1 hour.
Standby operation with keep warm or keep humidity function
In this operating mode the Nordmann AT4 D produces that much steam that the set temperature or the set humidity (caldarium operation) in the steam bath cabin can be held. After the set period of time in standby operation has elapsed the keep warm or keep humidity function is switched off.
Select“Idle Operat.” in the water management settings submenu, then press the <Set> key. In the upcoming Idle submenu set the parameters for standby operation with keep warm or keep humidity function.
Settings
SC-System :Set Power Limit :100%
Water Manag.:Set
Date :11-08-31 Time :12:00
Esc Set
Water Manag.
Conductivity:>125µS Drain Factor:1.0
Idle Operat.:Set
Force Drain :On Force Delay :72h
Esc Set
Settings:
• Idle Mode”: KeepWarm
• Temperature
”: Desired steam bath cabin temperature, which is to be maintained during the
set duration in the standby operation (Factory setting: 35 °C, Setting range:
10...50 °C)
Idle Operat.
Idle Mode :IdleOnly
Esc Set
Idle Operat.
Idle Mode :KeepWarm
Temperature :35°C MaxHeatTime :2h
Esc Set
Idle Operat.
Idle Mode :KeepWarm
Temperature :35°C
MaxHeatTime :2h
Esc Set
Idle Operat.
Idle Mode :Drain Temperature :35°C
MaxHeatTime :2h
Esc Set
Idle Mode
Drain IdleOnly Drain
KeepWarm
A.Freeze
Esc Set
Temperature
35 °C 35 °C
Esc Set
MaxHeatTime
2 h 2 h
Esc Set
or
“Humidity
”: Desired humidity (caldarium operation ), which is to be maintained during
the set duration in the standby operation (Factory setting: 30 %rH, Setting range: 10...50 %rH)
• MaxHeatTime
”: Max. duration in standby operation the set temperature or humidity is main-
tained (Factory setting: 2 h, Setting range: 1...18 h)
41
Page 42
Standby operation with anti freeze function
In this operating mode the water in the cylinder is warmed up so far in standby operation that the water in the cylinder cannot freeze. Note: the keep warm function works only, if the external safety chain is closed. Therefore this func­tion may not be used for outdoor operation.
Select “Idle Operat.” in the water management settings submenu, then press the <Set> key. In the upcoming Idle submenu set the parameters for standby operation with anti freeze function.
Settings
SC-System :Set
Power Limit :100%
Water Manag.:Set
Date :11-08-31 Time :12:00
Esc Set
Water Manag.
Conductivity:>125µS Drain Factor:1.0
Idle Operat.:Set
Force Drain :On Force Delay :72h
Esc Set
Idle Operat.
Idle Mode :IdleOnly
Esc Set
Idle Operat.
Idle Mode :A.Freeze
Heat Power :50W
Esc Set
Idle Operat.
Idle Mode :A.Freeze
Heat Power :50W
Esc Set
Idle Mode
Drain IdleOnly Drain KeepWarma
A.Freeze
Esc Set
Heat Power
50 W 50 W
Esc Set
Settings:
Idle Mode”: “A.Freeze
Heat Power”: heating power for anti freeze function (Factory setting: 50 W, Setting range:
10...200 W)
5.3.7.4 Activating/Deactivating the forced draining
Select “Force Drain” in the water management settings submenu, then press the <Set> key.
Settings
SC-System :Set
Power Limit :100%
Water Manag.:Set
Date :11-08-31 Time :12:00
Esc Set
Water Manag.
Conductivity:>125µS Drain Factor:1.0 Idle Operat.:Set
Force Drain :On
Force Delay :72h
Esc Set
Force Drain
On
O
On
Esc Set
In the upcoming modication dialogue activate/deactivate the forced draining which takes place after a
certain time of operation (see following setting). Note: The forced draining takes place also during steam production.
Factory setting: Off
Options: On (Forced draining activated)
Off (Forced draining deactivated)
42
Page 43
5.3.7.5 Setting the time of operation after which a forced draining takes place
Select “Force Delay” in the water management settings submenu, then press the <Set> key.
Settings
SC-System :Set
Power Limit :100%
Water Manag.:Set
Date :11-08-31 Time :12:00
Esc Set
In the upcoming modication dialogue set the time of operation after which a forced draining takes place.
Factory setting: 72 hours
Setting range: 1...720 hours

5.3.8 Setting the date

Select “Date” in the user settings menu, then press the <Set> key.
Settings
Power Limit :100%
Water Manag.:Set
Date :11-08-31
Time :12:00 Contrast :50
Esc Set
In the upcoming modication dialogue set the actual date (format:“yyyy-mm-dd”).
Water Manag.
Conductivity:>125µS Drain Factor:1.0 Idle Operat.:Set Force Drain :On
Force Delay :72h
Esc Set
Date
2011-08-31
2011-08-31
Esc Set
Force Delay
72 h 72 h
Esc Set

5.3.9 Setting the time

Select “Time” in the user settings menu, then press the <Set> key.
Settings
Power Limit :100%
Water Manag.:Set Date :11-08-31
Time :12:00
Contrast :50
Esc Set
Time
12:00
12:00
Esc Set
In the upcoming modication dialogue set the actual time (format:“hh:mm”).

5.3.10 Setting the display contrast

Note: this function is not available via the optional remote terminal.
Select “Contrast” in the user settings menu, then press the <Set> key.
Settings
Power Limit :100%
Water Manag.:Set Date :11-08-31 Time :12:00
Contrast :50
Esc Set
Contrast
50 50
Esc Set
In the upcoming modication dialogue set the desired value for the display contrast.
Factory setting: 50
Setting range: 25 (light) ...80 (dark)
43
Page 44

5.4 Modbus settings

Select the Modbus menu: Path: Main Menu > User > Password entry: 3562 > Modbus
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
Main Menu
Fragrance :Set
Light-2 :O
User :Set
Engineering :Set Diagnostic :Set
Esc Set
User Code
3562
Enter Number
Conrm with Set
Esc Set
In the Modbus submenu you can set the parameters for Modbus networks or for the communication with the optional remote terminal. Detailed information on the different settings are found in the follow­ing chapters.

5.4.1 Settings for Modbus networks

Select “Networking” in the Modbus submenu, then press the <Set> key. In the upcoming modication dialogue adjust the settings for the Modbus network operation.
Modbus
Networking :Set
Remote :Set
Networking
Mode Addr. :1
Parity :None1
User
Maintenance :Set Settings :Set
Modbus :Set
Esc Set
Modbus Addr.
1 1
Modbus
Networking :Set
Remote :Set
Esc Set
Esc Set
Esc Set
Networking
Mode Addr. :1
Parity :None1
Esc Set
Networking
Mode Addr. :1
Parity :None1
Esc Set
Esc Set
Parity
None1
None1
None2 Odd Even
Esc Set
Settings:
Modbus Addr.”: Modbus address of the steam generator (Factory setting: 1, Setting range: 1...247).
Parity”: Parity bit for the data transmission (Factory setting: None1, Options: None1, None2, Odd, Even)
Note: for Modbus network operation the baud rate is set to 9600 baud as standard.
44
Page 45

5.4.2 Settings for the communication with the optional remote terminal

Select “Remote” in the Modbus submenu, then press the <Set> key.
– Data upload
Modbus
Networking :Set
Remote :Set
Esc Set
Note: this function is intended only for the service technician of your Nordmann representative.
– Settings for the communication with the optional remote terminal
Note: this function is not available via the optional remote terminal.
Select “Remote” in the Modbus submenu, then press the <Set> key. Then, adjust the settings for communication with the optional remote terminal.
Remote
Settings :Remote
Modbus Addr.:1 Baudrate :9600 Parity :None1
Esc Set
Remote
Settings :Upload
Esc Set
Settings
Upload
Upload
Remote
Esc Set
Modbus
Networking :Set
Remote :Set
Esc Set
Remote
Settings :Upload
Esc Set
Remote
Settings :Remote
Modbus Addr.:1 Baudrate :9600 Parity :None1
Esc Set
Remote
Settings :Remote
Modbus Addr.:1
Baudrate :9600 Parity :None1
Esc Set
Remote
Settings :Remote Modbus Addr.:1
Baudrate :9600
Parity :None1
Esc Set
Remote
Settings :Remote Modbus Addr.:1 Baudrate :9600
Parity :None1
Esc Set
Remote Sett
Remote Upload
Remote
Esc Set
Modbus Addr.
1 1
Esc Set
Baudrate
9600
9600
19200 38400 56800
Esc Set
Parity
None1
None1
None2 Odd Even
Esc Set
Settings:
Settings”: Remote
Modbus Addr.”: Modbus adress of the steam generator
(Factory setting: 1, Setting range: 1...247)
Baudrate”: Baudrate for the data transmission (Factory setting: 9600, Options: 9600, 19200, 38400, 57600)
Parity”: Parity bit for the data transmission (Factory setting: None1, Options: None1, None2, Odd, Even)
45
Page 46

5.5 Diagnostic functions

5.5.1 Interrogation of the error history

The error messages generated by the last 20 malfunctions that occurred are saved in the error history list of the Nordmann AT4 D and can be interrogated.
Select the error history list: Path: Main Menu > Diagnostic > ErrorHistory
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
Main Menu
Fragrance :Set
Light-2 :O
User :Set Engineering :Set
Diagnostic :Set
Esc Set
Diagnostic
ErrorHistory:Set
Unit Status::Set Bath Test :Set Remote Test :Set Module Test :Set
Esc Set
ErrorHistory 01/05 11-03-15 12:34 E23 No Current Phase failure GFCI activated Water supply
Esc Set
ErrorHistory 05/05 11-03-17 16:38 E32 Sensor void No sensor signal Sensor damaged
Esc Set
The last error that occurred is shown with: – running number of the error – date and time of occurrence – error code (Warning: W..., Error: E...) – error message – additional info text regarding the error
Press < > and < > keys, in order to select further error messages in the list.
Press the <Esc> key several times to quit the error history list and to return to the standard operating display.
46
Page 47

5.5.2 Interrogation of unit information

Select the list with the unit information: Path: Main Menu > Diagnostic > Unit Status
Press <
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
> and < > keys, in order to select the unit information available in the list:
Main Menu
Fragrance :Set
Light-2 :O
User :Set Engineering :Set
Diagnostic :Set
Esc Set
Diagnostic
ErrorHistory:Set
Unit Status::Set
Bath Test :Set Remote Test :Set Module Test :Set
Esc Set
Unit Status:
Cylindertype 6564 Cylinder Op. Hour 14 h
Esc Set
Software Version
1.00LA00 Operation Panel Actual current
0.0 A
∑Steam
65 kg/h Actual Request 100 % Actual Temperature 45°C Average Drain Time
0.0s Max. Level Sensor
O
Max. Level Counter 1
Ext. On/O Button O
Ext. Light Button 1
O
Ext. Light Button 2
O Max. Temp. Switch
On
Door Switch
Closed System Operation Hour 20h Inlet valve
O
Outlet Pump
O
Main Contactor
O
SC-Pump
O
Light 1
O
Light 2
O
Fragrance Pump 1
O
Fragrance Pump 2
O
Relay 8
O
Relay 9
O
Fan Relay
1&2 O
Flap Analog Out
0.0V Sensor Analog Out
0.0V Remote Steam
O
Remote Service
O
Remote Error
O
Remote Unit On On
1 2
3
4
5
6
7 8
9 10
11 12
13 14
15 16 17 18
19
20 21 22 23 24 25 26 27
28 29 30 31 32 33 34
1 Type of the steam cylinder 2 Total operating hours of the steam cylinder 3 Software version 4 Set operating control mode 5 Actual nominal current 6 Actual steam capacity 7 Actual demand 8 Actual temperature or actual humidity (caldarium operation) in the steam bath cabin 9 Calculated average drain time in seconds 10 Actual status of the maximum level sensor 11 Counter showing the number of times the maximum level in the steam cylinder has been exceeded 12 Actual status of the external On/Off push-button 13 Actual status of the external push-button of light 1 14 Actual status of the external push-button of light 2 15 Actual status of the maximum temperature device
47
Page 48
16 Actual status steam bath door switch 17 Total operating hours since the initial commissioning 18 Actual operating status inlet valve 19 Actual operating status drain pump 20 Actual operating status main contactor 21 Actual operating status SC pump 22 Actual operating status light 1 23 Actual operating status light 2 24 Actual operating status fragrance pump 1 25 Actual operating status fragrance pump 2 26 Actual operating status relay 8 27 Actual operating status relay 9 28 Actual operating status fan relay
29 Actual voltage on analog ap control output
30 Actual voltage on analog sensor output 31 Actual status remote relay “Steam” 32 Actual status remote relay “Service” 33 Actual status remote relay “Error” 34 Actual status remote relay “Unit on”
Press the <Esc> key several times to quit the unit information list and to return to the standard operat­ing display.

5.5.3 Performing remote steam bath tests

Select the steam bath test: Path: Main Menu > Diagnostic > Bath Test
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
Main Menu
Fragrance :Set
Light-2 :O
User :Set Engineering :Set
Diagnostic :Set
Esc Set
The list with the steam bath tests appears, the rst steam bath test (Light 1) is shown.
Press the < > and < > keys in order to select the further steam bath tests available and press the <Set> key to activate/deactivate the corresponding component for testing or to increase the shown value.
Diagnostic
ErrorHistory:Set Unit Status::Set
Bath Test :Set
Remote Test :Set Module Test :Set
Esc Set
Bath Test
Light 1
Esc Set
O
Light 2
O
Fragrance Pump 1
O
Fragrance Pump 2
O
Relay 8
O
Relay 9
O
Fan Relay
1&2 O
Flap Analog Out
0.0V
Sensor Analog Out
0.0V
48
Page 49

5.5.4 Performing remote relay tests

Select the remote test: Path: Main Menu > Diagnostic > Remote Test
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
Main Menu
Fragrance :Set
Light-2 :O
User :Set Engineering :Set
Diagnostic :Set
Esc Set
The list with the remote relay tests appears, the rst relay test (steam) is shown.
Press the < > and < > keys in order to select the further relay tests available and press the <Set> key to activate/deactivate the corresponding relay for testing.

5.5.5 Performing Module tests

Note: this function is not available via the optional remote terminal.
Select the Module tests: Path: Main Menu > Diagnostic > Module Test
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
Main Menu
Fragrance :Set
Light-2 :O
User :Set Engineering :Set
Diagnostic :Set
Esc Set
Diagnostic
ErrorHistory:Set Unit Status::Set Bath Test :Set
Remote Test :Set
Module Test :Set
Esc Set
Diagnostic
ErrorHistory:Set Unit Status::Set Bath Test :Set Remote Test :Set
Module Test :Set
Esc Set
Remote Test
Remote Steam
Esc Set
Esc Set
O
Remote Service
O
Remote Error
O
Remote Unit On
O
Module Test
Inlet Valve
O
Outlet Pump
Main Contactor
SC-Pump
The list with the module tests appears, the rst test (Inlet Valve) is shown.
Press the <
> and < > keys in order to select the further module tests and press the <Set> key to
activate/deactivate the corresponding component for testing.
O
O
O
49
Page 50

5.6 Working with the remote terminal

5.6.1 Menu overview remote terminal

Standard display Standard display with active malfunction
AT4D Terminal
Remote Units:8
Software :1.00LA00
Menu Local
Main Menu
Language :English
ErrorHistory:Set HistoryReset:Set Baudrate :9600 Contrast :50
Esc Set
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start 1
Warning
W17 Unit missing
Remote Units:8
Info
Menu Local
Info
Menu remote terminal Remote terminal settings (see chapter 5.6.2)
Indication level remote terminal
Warning 17
Unit missing No Connection
with humidier
Esc
Menu level remote terminal
Steam generator 1
Indication level steam generator 1
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start 2
•••
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start 8
Main Menu
Setpoint :48°C
Operat.Mode :Manual Duration :45min Fragrance :Set
Light-2 :O
Esc Set
Menu level steam generator 1
Note: Detailed information regarding the indication and the menu level of the steam generators can be found in chapters 5.1 to 5.5.
Steam generator 2 to max. 8
50
Page 51

5.6.2 Remote terminal settings

5.6.2.1 Selecting the dialogue language
Select “Language” in the main menu, then press the <Set> key.
Main Menu
Language :English
RemoteUnits :8 ErrorHistory:Set HistoryReset:Set Baudrate :9600
Esc Set
Language
English
English
German French Italian
Esc Set
In the upcoming modication dialogue select the desired dialogue language. After conrmation, the unit
automatically switches to the selected dialogue language.
Factory setting: country specic
Options: divers languages
5.6.2.2 Setting the number of steam generators connected to the remote terminal
Select “Remote Units” in the main menu, then press the <Set> key.
Main Menu
Language :English
RemoteUnits :8
ErrorHistory:Set HistoryReset:Set Baudrate :9600
Esc Set
In the upcoming modication dialogue set the number of steam generators connected to the remote terminal.
Factory setting: 1
Setting range: 1...8
RemoteUnits
8 8
Esc Set
5.6.2.3 Interrogation of the error history of the remote terminal
The error messages generated by the last 20 malfunctions that occurred are saved in the error history list of the remote terminal and can be interrogated.
Select “ErrorHistory” in the main menu, then press the <Set> key.
Main Menu
Language :English RemoteUnits :8
ErrorHistory:Set
HistoryReset:Set Baudrate :9600
Esc Set
The last error that occurred is shown with: – running number of the error – date and time of occurrence – error code (Warning: W..., Error: E...) – error message – additional info text regarding the error
ErrorHistory 01/05 11-03-15 12:34 W16 Unit missing no connection
with humidier
Esc Set
ErrorHistory 05/05 15-03-15 16:34 W16 Unit missing no connection
with humidier
Esc Set
Press < > and < > keys, in order to select further error messages in the list.
51
Page 52
Press the <Esc> key several times to quit the error history list and to return to the standard operating display.
5.6.2.4 Resetting the error history list of the remote terminal
Select “HistoryReset” in the main menu, then press the <Set> key.
Main Menu
RemoteUnits :8 ErrorHistory:Set
HistoryReset:Set
Baudrate :9600 Contrast :50
Esc Set
HistoryReset
Are You sure?
No Yes
The reset dialogue appears in the display. Press the <Yes> key in order to reset the error history list.
Note: By pressing the <No> key the reset procedure can be aborted. The remote terminal returns to the main menu.
5.6.2.5 Setting the baudrate
Select “Baudrate” in the main menu, then press the <Set> key.
Main Menu
RemoteUnits :8 ErrorHistory:Set HistoryReset:Set
Baudrate :9600
Contrast :50
Esc Set
Baudrate
9600
9600
19200 38400 56800
Esc Set
In the upcoming modication dialogue set the baudrate for the communication with the steam generator
controls.
Factory setting: 9600
Options: 9600, 19200, 38400, 57600
5.6.2.6 Setting the display contrast
Select “Contrast” in the main menu, then press the <Set> key.
Main Menu
RemoteUnits :8 ErrorHistory:Set HistoryReset:Set Baudrate :9600
Contrast :50
Esc Set
In the upcoming modication dialogue set the desired value for the display contrast of the remote terminal.
Factory setting: 50
Setting range: 25 (light) ...80 (dark)
Contrast
50 50
Esc Set
52
Page 53

6 Maintenance

6.1 Important notes on maintenance

Qualication of personnel
All maintenance work must be carried out only by well qualied and trained personnel authorised by the owner. It is the owner ’s responsibility to verify
proper qualication of the personnel.
General note
The instructions and details for maintenance work must be followed and upheld.
Only the maintenance work described in this documentation may be car­ried out.
Only use original Nordmann spare parts to replace faulty parts.
Safety
Some maintenance work requires removal of the unit covers. Please note the following:
DANGER! Danger of electric hazard!
You may get in touch with live parts when the unit is open. Touching live parts may cause severe injury or even lethal violation. Prevention: Before carrying out any maintenance work set the Nordmann AT4 D out of operation as described in chapter 4.4 (switch off the unit, disconnect it from the mains and stop the water supply) and secure the unit against inadvertent power-up.
CAUTION!
The electronic components inside the steam generator are very sensitive to electrostatic discharge. Prevention: Before carrying out any maintenance work to the electrical or electronic equipment of the steam generator, appropriate measures must be taken to protect the respective components against damage caused by electrostatic discharge (ESD protection).
53
Page 54

6.2 Maintenance list

Components Interval Work to be done
Steam cylinder X Remove and replace.
Drain pump X Remove, disassemble and clean, replace if neces-
Steam cylinder receptacle X Inspect, clean if necessary.
Inlet valve X Remove and clean lter insert, replace if necessary.
Drain cup X Remove and clean if necessary
Drain pipe and siphon X Inspect, clean if necessary (decalcify and rinse out).
Steam installation X X Inspect steam and condensate hoses for cracks and
To maintain operational safety the Nordmann AT4 D steam generator must be maintained at regular intervals. This is differentiated between the first
maintenance after approx. 500 operating hours (I), steam cylinder re­placement after the yellow LED lights (II) and annual maintenance (III).
Below you will nd a summary of the work to be carried out for each of the
three maintenance stages.
I II III
sary.
to see that they are correctly attached, replace faulty hoses.
Water installation X X Inspect water hoses in the unit for cracks and to see that
they are correctly attached, replace faulty hoses. Check supply pipe is tight, make tight if necessary.
Clean water lter, if available.
Electrical installation X X Check all cables in the unit are rmly positioned and
examine status of insulation.
54
Page 55

6.3 Removing and installing parts for maintenance

6.3.1 Removal and installation of the steam cylinder

1 2
1. Undo the screw xing the front panel to the unit using a screwdriver,
then remove the front panel.
2. Release the hose clamp on the steam hose using a screwdriver, then detach the steam hose from the steam outlet connection of the steam cylinder.
Units with steam hose connector with condensate trap (option CT..., not shown): release the two hose clamps on the rubber sleeve using a
screwdriver, then detach the rubber sleeve from the connection in the unit cover and from the steam outlet connection of the steam cylinder.
3 4
3. Remove all plugs from the electrodes and from the level sensor.
4. Loosen the screws of the steam cylinder xing device by a few turns, then push the xing device upwards until it comes loose and remove it.
55
Page 56
5 6
5. Carefully lift steam cylinder away from the cylinder receptacle, then remove it to the front.
CAUTION!
Put steam cylinder down carefully to avoid damage to the lower con­nection piece!
6. Carefully pull the drain screen out of the drain outlet of the steam cylinder. Note: this step must only be carried out if the drain screen is clogged (see chapter 7.2.2 “Unit faults”) and the steam cylinder can still be used.
56
Page 57
522A 822A
brown
Installation of the steam cylinder follows the reverse sequence. Observe the following:
Before installing the steam cylinder in the unit, check the O-ring of the
cylinder receptacle for damage and replace if necessary.
– Moisten the O-ring of the cylinder receptacle with water (do not use
grease or oil), then insert steam cylinder into the socket and push it down to the stop.
– Attach the electrode plugs and the level sensor plug to the respective
electrode and sensor connections in accordance with colour code (see table below).
Steam cylinder type
532A / 534A 832A / 834A
1532A / 1534A
red
2362A / 2364A 3262A / 3264A
black
brown
4564A / 6564A
brown black
black
Sensor white
red
black
Sensor
white
red
blackbrown
brown
Sensor
white
black
red
red
brown
Sensor
white
– Fasten steam hose on the connector of the steam cylinder with hose
clamps.
CAUTION!
– A leaky steam hose can cause damage due to moisture inside the
unit.
– The outlet connector of the steam cylinder is made of plastic. Do
not overtighten the hose clamp on the steam connector of the steam cylinder.
57
Page 58

6.3.2 Removal and installation of the drain cup

1
2
5
4
3
1. Remove overow hose from the connector on the water cup.
2. Remove grounding cable from the grounding lance.
3. Release the hose clamp, then remove water drain hose from the con­nector on the water cup.
4. Undo the two screws xing the drain cup to the unit using a screwdriver,
then remove the drain cup downwards.
5. Undo the screw, then remove grounding lance.
Installation of the drain cup follows the reverse sequence. Important: reattach grounding cable to grounding lance.
58
Page 59

6.3.3 Removal and installation of the water cup and the water hoses

For removing the water cup and the water hoses the steam cylinder must
be removed rst (see chapter 6.3.1).
1. Release hose clamps, then disconnect all hoses from the corresponding connectors and remove the hoses. Note: The hoses connected to the water cup may also be removed to­gether with the water cup (see illustration) and then disconnected from the connectors of the water cup outside the unit.
2. Carefully pull xing clip of the water cup to the front, then push water cup down from the holding device and remove it to the front.
The installation of the water cup and the water hoses follows the reverse
sequence. Before xing the water hoses to the connector using the hose
clamps, align the hoses in a way that they are not twisted.
59
Page 60

6.3.4 Removal and installation of the drain pump

2
1
2
For removing the drain pump the steam cylinder must be removed rst (see
chapter 6.3.1).
1. Detach electric cables (polarity of the cables must not be observed).
2. Release hose clamps and remove the hoses from the connectors.
3. Undo the two screws on the bottom of the housing with Phillips screw­driver, then remove drain pump.
4. Separate the electric motor from the pump body: release the lock on the bayonet catch, then counter-rotate the electric motor and the pump body.
The assembly and the installation of the drain pump follows the reverse sequence. Before assembling the pump, check O-ring for damage and replace if necessary. Then, place the O-ring on the centering collar and moisten the O-ring with water.
3
4
60
Page 61

6.3.5 Removal and installation of the inlet valve

2
1
4
5
3
For removing the inlet valve the steam cylinder must be removed rst (see
chapter 6.3.1).
1. Detach electric cables (polarity of the cables must not be observed).
2. Release hose clamp and remove the hose from the connector.
3. Unlock union nut of the water pipe and remove water pipe.
4. Undo the two screws on the bottom of the housing with Phillips screw­driver, then remove inlet valve.
5. Remove strainer insert with pointed pliers.
The installation of the inlet valve follows the reverse sequence. The union nut of the water pipe must be tightened by hand only.
61
Page 62

6.3.6 Removal and installation of the cylinder receptacle

3
1
For removing the cylinder receptacle the steam cylinder must be removed
rst (see chapter 6.3.1).
1. Release hose clamps and remove hoses from the connectors.
2. Remove hose from SC pump together with the check valve from the corresponding connector on the cylinder receptacle.
3. Undo the screw xing cylinder receptacle to the bottom of the housing
with Phillips screwdriver. Then, turn cylinder receptacle counter clockwise to the stop and remove cylinder receptacle upwards.
4. Remove O-ring from the cylinder receptacle.
4
2
1
62
The installation of the cylinder receptacle follows the reverse sequence. Before mounting the cylinder receptacle, check O-ring for damage and replace if necessary.
Page 63

6.4 Notes on cleaning the unit components

Unit component What to clean and how to clean
Water hoses
Inlet valve
strainer insert
Drain pump
Remove any limescale by slightly knocking on the tubes
using a rubber hammer. Then, rinse the tubes well with hot tap water.
Use a brush (do not use a wire brush) to remove any
limescale inside the inlet valve and on the strainer.
Wash inlet valve and strainer insert with a lukewarm
soap solution, then rinse well with tap water.
Let the inlet valve dry before reinstallation!
Use a brush to remove any limescale from the pump
housing and the pump wheel (do not use a wire brush).
O-ring
Water cup
Then, wipe pump wheel with a damp cloth. Wash the
pump housing with a lukewarm soap solution and rinse well with tap water.
Let the drain pump dry before reinstallation!
Pump wheel
Remove any limescale from the water cup and its con­nectors using a brush (do not use a wire brush).
If the water cup is heavily calcied, place it in an 8%
formic acid solution (observe safety notes in chap- ter 6.5), until the limescale comes off.
Wash the water cup with a lukewarm soap solution and
rinse well with tap water.
63
Page 64
Unit component What to clean and how to clean
Drain screen of the steam cylinder
Drain cup
Cylinder receptacle
Remove any limescale from the drain screen using a
brush (do not use a wire brush) and remove loose limes­cale inside the drain connector of the steam cylinder.
If the drain screen is heavily calcied, place it in an 8%
formic acid solution (observe safety notes in chap- ter 6.5), until the limescale comes off.
Wash the drain screen with a lukewarm soap solution
and rinse well with tap water.
Use a brush to remove any limescale from the drain
cup and the receptacle on the bottom side of the unit (do not use a wire brush).
If the drain cup is heavily calcied, place it in an 8%
formic acid solution (observe safety notes in chap- ter 6.5), until the limescale comes off.
Wash the drain cup and the receptacle on the bottom
side of the unit with a lukewarm soap solution, rinse the parts well with tap water.
Remove any limescale from the cylinder receptacle
and its connectors using a brush (do not use a wire brush).
If the cylinder receptacle is heavily calcied, place it in
an 8% formic acid solution (observe safety notes in
chapter 6.5), until the limescale comes off.
Interior of the unit
(water side only)
• Wash the cylinder receptacle with a lukewarm soap
solution and rinse well with tap water.
Wipe the interior of the unit with a damp cloth without using any cleaning agent.
CAUTION: Take care that the electrical connections and the electronic components remain dry!
64
Page 65

6.5 Notes on cleaning agents

Only use cleaning agents stated in the table above. The use of disinfect­ants is only permitted if they do not leave any toxic residues. In any case the parts must be thoroughly rinsed with water after cleaning.
Formic acid is indeed harmless to the skin, but it attacks the mucous membranes. Therefore prevent your eyes and respiratory tracts from getting in touch with the acid and its vapours (wear goggles and work in a well ventilated room or outside).
CAUTION!
Do not use any solvents, aromatized or halogenised hydrocarbons
or other aggressive substances as they may cause damage to the components of the unit.
It is mandatory to observe and comply with the information and instructions regarding cleaning agents. Observe in particular: all information relating to the protection of personnel, environmental protection and restrictions regarding usage.
WARNING!

6.6 Resetting the maintenance indication

After completing maintenance work, the maintenance indication (yellow LED lights) must be reset:
1. Select the maintenance menu: Path: Main Menu > User > Password: 3562 > Maintenance
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
Main Menu
Fragrance :Set
Light-2 :O
User :Set
Engineering :Set Diagnostic :Set
Esc Set
User Code
3562
Enter Number
Conrm with Set
Esc Set
User
Maintenance :Set
Settings :Set Modbus :Set
Esc Set
Maintenance
HistoryReset:Set
Cyl. Reset :Set
Esc Set
Cyl. Reset
Attention ! Reset
without cyl. Mainten.
is very dangerous!
Are you sure?
No Yes
AT4 D
STARTUP:
Init Module
2. Select “Cyl. Reset”, then press the <Set> key.
3. The reset dialogue appears in the display. Press the <Yes> key to reset the maintenance counter or the maintenance indication respectively. The maintenance counter and the maintenance indication are reset and the control unit is restarted.
Note: by pressing the <No> key the reset procedure can be aborted and the display and control unit returns to the maintenance menu. To return to the standard operating display press the <Esc> key several times.
65
Page 66

7 Fault elimination

7.1 Fault indication

Malfunctions during operation are indicated by the “danger symbol” in the standard operating display. If there is a severe malfunction (unit is
blocked) the red LED lights additionally.
AT4D 65kg/h
Steam Bath :Warm-up Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Stop Info
By pressing the <Info> key additional information can be displayed for each active warning and/or error message. Press the < > and < > keys, in order to scroll between the active warning and/or error messages.
Warning messages
Warning 21
Cyl.Max.Level
Initial operat.->wait Water conduct. Low
Electrodes spent
Menu
The control of the Nordmann AT4 D checks whether there is a temporary problem (e.g. water supply interrupted for a short time) or whether it can resolve the problem by taking necessary measures. If the cause of the malfunction disappears of its own accord or if the control can repair the malfunction, the alarm message will automatically switch off. If the cause of the malfunction does not disappear even after a longer period of time, a error message is triggered.
Error messages
Error 32
Sensor void No sensor signal Sensor damaged
Menu
Additionally to the error message the red LED lights. Further operation is normally not possible any longer, the unit is blocked. To eliminate the malfunction see chapter 7.2 and 7.3. Note: After eliminating the malfunction the error message must be reset (see chapter 7.4).
Note: if you want to see further information of an active warning or error message of a steam generator on the optional remote terminal, select “Exception” in the diagnostic menu of the appropriate steam generator (ap­pears only on the remote terminal), then press <Set> key:
AT4D 65kg/h 400V3
Steam Bath :Standby Temperature :34°C Setpoint :48°C 2011-08-31 12:00:00
Menu Light Start
Main Menu
Fragrance :Set
Light-2 :O
User :Set Engineering :Set
Diagnostic :Set
Esc Set
Diagnostic
Exception :Set
ErrorHistory:Set Unit Status::Set Bath Test :Set Remote Test :Set
Esc Set
Fehler 32
Sensor void No sensor signal Sensor damaged
Esc
66
Page 67

7.2 Malfunction lists

Important! Most operational malfunctions are not caused by faulty equipment but rather by improper installation or disregarding of planning guidelines. Therefore, a complete fault diagnosis always involves a thorough examina­tion of the entire system. Often, the steam hose connection has not been properly executed, or the fault lies with the humidity control system.

7.2.1 System faults

Warning Error Cause Remedy
LED Display LED Display
CF card missing
(Test run possible)
––– ––– red
––– ––– red
––– ––– red
Error
lights
E1: CF card Missing
CF card is empty
Error
lights
E2: CF card Empty
CF card is defective
Error
lights
E3: CF card Invalid
No CF card installed on the control board. Install CF card or start test run.
No data stored on the CF card. Install new CF card.
Invalid data stored on the CF card. Install new CF card.
––– ––– red
lights
Steam bath board not connected
––– ––– red
lights
––– ––– red
lights
––– –––
––– ––– red
lights
Steam bath door open too long
––– ––– red
lights
––– ––– red
lights
CF card is incompatible
Error E4: CF card incompat
Error
E5: Module W Missing
Hardware fault
Error
E10: Flash R/W Fault
Error
E11: Clock R/W Fault
Max. heating time exceeded
Error E13: Max Heating
Error E14: Door open
Program fault
Error
E15: Program Fault
The installed CF card is not compatible with the hardware of the unit or with the basic settings of the control electronics.
Steam bath board not connected to the control board, the system does not start.
Control board defective. Replace control board.
Backup battery on control board discharged.
Steam bath was in operation too long. Check week timer.
Steam bath door was open too long. Close steam bath door.
Program fault, steam generator is blocked.
Install correct CF card. Let your Nord­mann service technician adjust the basic settings.
Connect steam bath board to the control board.
Let have the backup battery be replaced (see chapter 7.5).
Increase maximum heating time.
Check door switch. If no door control is connected: Check whether a cable bridge is connected on the corresponding contacts on the steam bath board.
Please contact your Nordmann supplier.
Test Mode active
–––
Warning W16: Test Mode Active
––– ––– Diagnostic mode active (Remote Test,
Module Test etc.)
Quit diagnostic mode.
67
Page 68
Warning Error Cause Remedy
LED Display LED Display
Humidier missing
–––
Warning W17: Unit Missing
Note: This warning is shown only on the remote terminal.
––– ––– red
––– ––– The optional remote terminal does not
Temperature measurement instable
lights
Error
E18: Temperat.Instab.

7.2.2 Unit faults

Warning Error Cause Remedy
LED Display LED Display
Maximum temperature switch
has triggered
––– ––– red
Max. lling level of
steam cylinder reached
–––
Warning W21: Cyl.Max.Level
Permissible lling time exceeded
(20 minutes)
–––
Warning W22: Max. Filltime
lights
Max. lling level of steam cylinder
reached but no heating current for
lights
Permissible lling time exceeded
lights
Error
E20: Temp.Fuse
more than 30 minutes
red
Error
E21: Cyl.Max.&NoCurr
(more than 4 hours)
red
Error E22: Max. Filltime
Check connecting cable. Check/correctly set
have connection to one or more units.
Instable temperature measurement due to a manipulation at the temperature sensor in the steam bath cabin.
Maximum temperature switch has
triggered
Maximum temperature switch defective or
not connected.
Water conductivity too low (after initial op­eration).
Water conductivity too low for the selected steam cylinder type.
Phase failure heating voltage. Check service switch in the mains supply
Water supply obstructed/shut-off valve closed/water pressure too low.
Inlet valve blocked or defective. Inspect strainer insert in the inlet valve, if
Excessive back pressure in the steam line (pressure in steam bath cabin too high, steam line too long or kinked), causing water loss via lling cup.
Leakage in the water system. Inspect water system and seal if necessary.
Modbus settings (modbus address, interface parameters).
Check temperature sensor in the steam bath cabin.
Check temperature in the steam bath cabin.
Check/replace maximum temperature switch or correctly connect the switch.
Wait until the mineral content of the cylinder has increased
Select correct steam cylinder type.
line and switch on if applicable. Check mains fuse(s) and replace if applicable.
Inspect water supply (lter, water piping, etc.), check/open shut-off valve, check water pressure.
applicable clean strainer insert or replace
inlet valve.
Check pressure in steam bath cabin, inspect steam installation.
68
Page 69
Warning Error Cause Remedy
LED Display LED Display
No electrode current for more than
20 minutes
–––
Warning W23: No Current
Electrode current in relation to the
steam demand too high
–––
Warning W24: Over Current
Max. admissible electrode
current exceeded
–––
Warning W25: Excess Current
––– ––– red
No electrode current for more than
4 hours
red
Error
lights
E23: No Current
Electrode current in relation to the
steam demand too high
red
Error
lights
E24: Over Current
Max. admissible electrode
current exceeded
red
Error
lights
E25: Excess Current
Relay heating voltage jammed
Error
lights
E26: Req.Off Current
Phase failure heating voltage. Inspect/turn on service switch of the mains
supply line. Inspect the fuses of the mains supply, replace if necessary. Check/repalce
main contactor.
Water supply obstructed/shut-off valve closed/water pressure too low.
Inlet valve blocked or defective. Inspect strainer insert of the inlet valve, if
Excessive back pressure in the steam line (pressure in steam bath cabin too high, steam line too long or kinked), causing water loss via lling cup.
Leakage in the water system. Inspect water system and seal if necessary.
Humidity demand has decreased too fast. Automatic adaptation of the operating
Drain pump defective. Inspect drain pump, replace if necessary.
Drain in steam cylinder blocked. Replace steam cylinder.
Water conductivity too high for the selected steam cylinder type.
Drain pump defective. Inspect drain pump, replace if necessary.
Drain in steam cylinder blocked. Replace the steam cylinder.
Water conductivity too high for the selected steam cylinder type.
Relay heating voltage jammed in activated position.
Inspect water supply (lter, water piping, etc.), check/open shut-off valve, check water pressure.
applicable clean strainer insert or replace
inlet valve.
Check pressure in steam bath cabin, inspect steam installation.
point.
Select correct steam cylinder type.
Select correct steam cylinder type.
Inspect relay, replace if necessary.
Foam detection Foam detection (4 automatic drain-
ings within 24 hours)
–––
Warning W27: Foam
Steam cylinder needs service Service interval for
yellow
lights
yellow
lights
Warning W28: Cyl. Maintenance
Steam cylinder needs service Max. operating hours of the steam
Warning W29: Cyl. Maintenance
red
Error
lights
E27: Foam
steam cylinder exceeded
red and
yellow
red and
yellow
Error E28: Cyl. Maintenance
ash
cylinder reached
Error
E29: Cyl. Maintenance
ash
Foaming in steam cylinder. Drain steam cylinder via drain key (sev-
eral times, if necessary). Check quality of the supply water.
Mineral deposits and/or electrodes spent. Replace steam cylinder.
Important: After replacement of the steam cylinder, reset the maintenance counter (see chapter 6.6).
Maximum operating hours of the steam cylinder reached.
Replace steam cylinder.
Important: After replacement of the steam cylinder, reset the maintenance counter (see chapter 6.6).
69
Page 70
Warning Error Cause Remedy
LED Display LED Display
Temperature or humidity sensor
signal missing
–––
Warning W32: Sensor void
Temperature or humidity sensor
signal missing for more
than 1 minute
red
lights
Error
E32: Sensor void
No sensor signal present at signal input. Check sensor , replace if necessary. Inspect
wiring.
Standby mode of
steam cylinder active
–––
Warning W36: Idle Mode active
Forced draining of
steam cylinder active
–––
Warning E37: Forced Drain
Standby mode of
steam cylinder failed
red
lights
Error
W36: Idle Mode failed
––– ––– Forced draining of steam cylinder active. No measures must be taken.

7.3 Notes on fault elimination

For the elimination of faults set the steam generator out of operation as described in chapter 4.4, separate the unit from the mains and secure it against inadvertent power-up.
The elimination of faults must be carried out by qualied and well trained
professionals only. Malfunctions relating to the electrical installation (e.g. replacement of the backup battery, replacement of fuses) must be repaired by authorized personnel or by your Nordmann representative’s service technician only.
Automatic standby operation (Standby­Drain, AntiFreeze, KeepWarm) of steam
cylinder active or failed.
DANGER! Danger of electric hazard!
Warning status: No measures must be taken. Error status: Check water supply, heating voltage supply, main contactor.
Repair work and the replacement of faulty components must be carried out by your Nordmann representative’s service technician only!

7.4 Resetting the error indication (red LED lights)

To reset the error indication:
Disconnect the steam generator from the mains. Wait approx. 5 sec­onds, then reconnect the unit to the mains.
Note: If the fault has not been eliminated, the error indication reappears after a short while.
70
Page 71

7.5 Replacing the backup battery on the control board

1. Set the Nordmann AT4 D out of operation as described in chapter
4.4, disconnect it from the mains and secure the unit against in­advertent power-up.
2. Undo the screw of the front cover of the control compartment, then remove the front cover.
CAUTION!
The electronic components inside the steam generator are very sensitive to electrostatic discharge. Before carrying out the next step, appropriate measures must be taken to protect the electronic
components against damage caused by electrostatic discharge
(ESD protection).
3. Carefully lift-off the display and control unit from the housing frame,
swivel it 90° to the left, then x it to the unit frame again.
4. Undo the fastening screws of the control board, then carefully pull-off the control board from the control unit assembly.
5. Replace the backup battery (CR2032, Lithium 3V).
6. Reassemble the unit in reverse order.
7. If necessary set date and time (see chapter 5.3.8 and 5.3.9).
WARNING! Environmental hazard!
The old battery must be returned to an authorised collecting point for correct disposal/recycling in accordance with local regulations. In no case the old battery must be disposed of in the domestic waste or into the environment.
71
Page 72

8 Taking out of service/Disposal

8.1 Taking out of service

If the Nordmann AT4 D must be replaced or if the humidication system is
not needed any more, proceed as follows:
1. Take the unit out of operation as described in chapter 4.4.
2. Have the unit (and all other system components, if necessary) unmounted
by a qualied service technician.

8.2 Disposal/Recycling

Components not used any more must not be disposed of in the domestic waste. Please dispose of the unit or the individual components in accord­ance with local regulations at the authorised collecting point.
If you have any questions, please contact the responsible authority or your local Nordmann representative.
Thank you for your contribution to environmental protection.
72
Page 73
9 Productspecications

9.1 Technical data

Steam capacity in kg/h 5 8 15 23 32 45 65
Capacity range in kg/h 1...5 1.6...8 3...15 4,6...23 6,4...32 9...45 13...65
Nominal power in kW 3,8 6,0 11,3 17,3 24,0 33,8 48,8
Heating voltage 230V/1~/50..60Hz *
Unit model 522 822
Nominal current in A 16,3 26,1
Steam cylinder type ** 522A 822A
Heating voltage 400V/2~/50..60Hz *
Unit model 524 824
Nominal current in A 9,4 15,0
Steam cylinder type ** 524A 824A
Heating voltage 230V/3~/50..60Hz *
Unit model 532 832 1532 2362 3262
Nominal current in A 9,4 15,1 28,2 43,3 60,2
Steam cylinder type ** 532A 832A 1532A 2362A 3262A
Heating voltage 400V/3~/50..60Hz *
Unit model 534 834 1534 2364 3264 4564 6564
Nominal current in A 5,4 8,7 16,2 24,9 34,6 48,7 70,4
Steam cylinder type ** 534A 834A 1534A 2364A 3264A 4564A 6564A
Steam cylinder type ***
Control voltage 230 V/1~/50..60 Hz
Operating conditions
Admissible water pressure 1...10 bar
Water quality Untreated drinking water with a conductivity of 125...1250 µS/cm
Admissible water temperature 1...40 °C
Admissible ambient temperature 1...40 °C
Admissible ambient humidity max. 75 %rF (non condensing)
Admissible air pressure in the steam bath cabin
Type of protection IP21
Conformity CE, VDE, GOST
Dimensions/Weights
Width in mm 428 428 508 508 563 563 563
Height in mm 575 575 620 620 640 640 640
Depth in mm 255 255 345 345 354 354 354
Net weight in kg 12 19 28 30
Operating weight in kg 17 29 65 67
Water supply connector G 3/4" (male thread)
Water drain connector ø 31 mm (outside diameter)
Steam connector 1x ø 22 1x ø 35 2x ø 35
Options
Cable gland 1x CG
Steam hose connector with condensate trap 1x CT22 1x CT35 2x CT35
Internal control voltage supply
@Link AT4 D @Link AT4 D
Accessories
Filter valve 1x Z261
Nordmann AT4 D Remote Terminal RP
Nordmann AT4 D Touch Screen Panel TSP
Temperature sensor KTY KTY
Steam distributor 1xW22 1xW35 2xW35
Fragrance pump 1xFP 240V
T-piece for fragrance injection 1xTSD22 1xTSD35 2xTSD35
Steam hose / meter 1xDS22 1xDS35 2xDS35
Condensate hose / meter KS10
Condensate drain 1xCD22 1xCD35 2xCD35
EcoTherm insulation hose 1xECT22 1xECT60 2xECT60
50-210VA transformer for 4x50W lamps TRL
* Other heating voltages on request
Steam cylinder for water conductivity from 125 to 1250 µS/cm (standard version)
** *** Steam cylinder for low water conductivity from 80 to 125 µS/cm
534A-L 834A-L 1534A-L 2364A-L 3264A-L 4564A-L ---
-0.8 kPa...1.5 kPa
1x S-CVI 1x M-CVI 1x L-CVI
73
Page 74

9.2 Wiring diagram Nordmann AT4 D

max. 2m
H3
H2
12V 12V
230V
230V 230V
T4
T4
24V
12V
H3
H2
the chain
Last unit in
in between
Mode
External
Mode
Internal
M2
M1
M2
M1
ext.
AT4 D
T3 T2
Supply Light
230V 12V
230V 24V
L N
230V
12V
24V
X X
X
X
Pull up
resistor
resistor
resistor
Pull down
120Ω end
Jumper settings for operation with optional remote terminal **
JP1
JP4
Jumper Function Remote terminal Unit(s)
JP5
A5
switch Excess temperature
board
X6
Steam bath
X24
X14
X31
J3J4
Temperature sensor
SW4 SW3 SW2 SW1
X5
X15
JP5 JP4
Remote Terminal
JP1
D+ D– GND 5V 24V
from contactor to cylinder
X15
Power board
X15
JP5
Unit 2Unit 3Last Unit
JP4 JP1
D+ D– GND 5V 24V
LIGHT 1 LIGHT 2LIGHT IN
F5
8 A 250 VAC
8 A 250 VAC
8 A 250 VAC
L1FUNL1SWNSW
SWITCH
MAIN SUPPLYMODULE B
LIM. SIGN.
JP3
24V 5V
CONT. SIGN.
X21
L NN LL N
24V: 4AT
230V: 1AT
F7
4AT
8 A 250 VAC
8 A 250 VAC
X2
PEPESC2SC1NL1
PEP1NP
EXT. SUP.
5V GND 24V
GNDIN
GNDINV+
J1
LIGHT SUPPLY OUT
12V: 6.3AT
EXT. TRAFO IN
1-Fan Mode
FAN 2
2-Fan Mode
FAN 1
REL8 REL9
X1
X6
X14
X11
X10
FAN 0V
24V 0V18V15V
FAN 0VAC
NO NOAUX1 AUX2COM COM
COM NO COM NO
X27
J2
X26
X25
X23
(Light 24 V) Supply FAN
24V
T1
0V
15V 18V
230V
Mode 1-Fan
Mode 1-Fan
Mode 2-Fan
24V
M3 M4 M5
L N L N LL N N
24V / 12V
PE N N
L1 L1
XE3
Q9
M3 Exhaust air fan 1 (2 fan mode)
M4 Supply air fan 2 (2 fan mode)
FAN
FAN 2
(Supply)
FAN 1
(Exhaust)
Supply on site
(4 A, slow acting)
F7 Internal fuse “steam bath board” Fan
L N PE
F9
230 V/1~/50..60 Hz
M5 Fan (1 fan mode)
Q8 External service switch heating voltage supply
Q9 External service switch control voltage supply
SW1 Door switch steam bath cabin
SW2 On/Off push-button steam bath cabin
SW3 On/Off push-button light 1
SW4 On/Off push-button light 2
T1 Transformer voltage supply fan
T2 Transformer voltage supply light (230V/12V)
T3 External transformer voltage supply light (230V/12V)
XE1 Connection terminal heating voltage
XE3 Connection terminal control voltage
X15 Connection terminal remote panel
U1 External temperature indication (0...10 V / 0...100 °C)
U2 Flap actuator (0...10 V / open...closed)
switch is connected
F8 External fuse heating voltage supply
F9 External fuse control voltage supply
H1 Remote operating and fault indication
H2 Light 1
H3 Light 2
J3 Short circuited, if no excess temperature
J4 Short circuited, if no door switch is connected
JP1 End resistor Remote Terminal **
JP3 Jumper control signal
JP4 Pull up resistor Remote Terminal **
JP5 Pull down resistor Remote Terminal **
K1 Main contactor
M1 Fragrance pump 1
M2 Fragrance pump 2
PE
PE
L1 L2 L3
L1 L2 L3
K1
XE1
Q8
L1 L2 L3
400 V/3~/50..60 Hz
F8
230 V/3~/50..60 Hz
PE
L1 L2
400 V/2~/50..60 Hz
F8
Q8
+ –
Temperature or Humidity in
L1 N PE
230 V/1~/50..60 Hz
F8
Q8
A6
(315 mA, slow acting)
24 V: 4 A, slow acting, 12 V: 6.3 A, slow acting)
24 V supply (315 mA, slow acting)
F4 Internal fuse “Power board” 5 VDC supply
F6 Internal fuse “steam bath board”
U1U2
F5 Internal fuse “steam bath board” Light (230 V: 1 A, slow acting,
X22
L' L'N NPE PE
P
1234
N
P1
MODULE B
PE
SC2
21
SC1
SAFETY CHAIN
5VGND24V
EXT. SUPPLY IN
TEMP S
1234 5678 9
24V
GND TEMP IN 24V LIGHT 2
LIGHT 1
BATH I/O
INPUTS
DOOR
L'N
S1S2
LEVEL SENS.
CURRENT SENSOR
F4 315mAT
REMOTE
D+ D– GND 5V 24V
LINK UP
J2
PUMP 1 PUMP 2
8 A 250 VAC
8 A 250 VAC
8 A 250 VAC
F6
315mAT
CPU BOARD
X3
L'NL'N
X4
L'N
INLET DRAIN CONTA.
SC
F1 6.3 AT
CONTACTORDRAININLETSC SYSTEM
SAFETY CHAIN
LEVEL SENSOR
GND
24V
F3 315mAT
JP5 JP4 JP1
5V
EXTERNAL CON.CPU BOARD
J4
8 A 250 VAC
J3
X16
X15
JP5 JP4 JP1
D+ D– GND 5V 24V
X15
JP5 JP4 JP1
D+ D– GND 5V 24V
J9
Control board
J3
BAT
J2
J1
J4
Temperature out
X4X5
H1
F1
0...10V / 0...100°C
4321
100mA
J1
Flap motor
0...10V / open...closed
21
Max. 60mA
Sensor Supply
X1
Unit ONSteamServiceError
1 2 3 4 5 6 7 8 9 10
operation (used instead of A5)
A5 Temperature sensor with excess temperature switch (e.g. KTY)
A6 Temperature sensor 0...10 V or humidity sensor for caldarium
BAT Backup battery (CR2032, Lithium 3V)
F1 Internal fuse “Power board” (6.3 A, slow acting)
F3 Internal fuse “Power board” 24 VDC supply (315 mA, slow acting)
74
Page 75
© Nordmann Engineering Ltd., Printed in Switzerland
Technical modifications reserved
Page 76
Reg.No. 40002-2
Manufacturer: Nordmann Engineering Ltd.
www.nordmann-engineering.com, info@nordmann-engineering.com
NORDMANN
ENGINEERING
Loading...