Nordmann es4 4 Installation And Operation Instructions Manual

NORDMANN
ENGINEERING
Steam air humidier
INSTALLATION- AND OPERATING INSTRUCTIONS
2569918 EN 1303
Contents
1 Introduction 4
1.1 To the very beginning 4
1.2 Notes on the installation and operating instructions 4
2 For your safety 6
3 Product Overview 8
3.1 Model overview 8
3.2 Identication of the unit 8
3.3 Steam humidier construction 9
3.4 Functional description 10
3.5 Humidication system overview 12
3.6 Accessories 13
3.6.1 Accessories overview 13
3.6.2 Accessory details 14
3.7 Standard delivery 16
3.8 Storing/Transportation/Packaging 16
4 Mounting and installation work 17
4.1 Important notes for mounting and installation work 17
4.2 Installation overview 18
4.3 Mounting the unit 19
4.3.1 Notes on locating the unit 19
4.3.2 Mounting the humidier 21
4.3.3 Inspecting the installed unit 22
4.4 Steam installation 23
4.4.1 Overview steam installation 23
4.4.2 Positioning of the steam distributors in a duct 24
4.4.3 Positioning of the steam distributors in a steam bath 28
4.4.4 Installing the steam distributors 28
4.4.5 Installing the steam and condensate hose 29
4.4.6 Common steam and condensate line errors 33
4.4.7 Inspecting the steam installation 34
4.5 Water installation 35
4.5.1 Overview water installation 35
4.5.2 Notes on water installation 36
4.5.3 Inspecting the water installation 37
4.6 Electric installation 38
4.6.1 Wiring diagram Nordmann ES4 4 38
4.6.2 Notes on electric installation 39
4.6.3 Unit conguration 41
4.6.4 Inspecting the electrical installation 42
6 Maintenance 47
6.1 Important notes on maintenance 47
6.2 Maintenance list 48
6.3 Removing and installing parts for maintenance 49
6.3.1 Removal and installation of the steam cylinder 49
6.3.2 Removal and installation of the drain cup 52
6.3.3 Removal and installation of the water cup and the water hoses 53
6.3.4 Removal and installation of the drain valve 54
6.3.5 Removal and installation of the inlet valve 55
6.4 Notes on cleaning the unit components 56
6.5 Notes on cleaning agents 57
6.6 Resetting the maintenance indication 57
7 Fault elimination 58
7.1 Fault indication 58
7.2 Malfunction lists 59
7.2.1 System faults 59
7.2.2 Unit faults 59
7.3 Notes on fault elimination 61
7.4 Resetting the error indication (red LED lights) 61
8 Taking out of service/Disposal 62
8.1 Taking out of service 62
8.2 Disposal/Recycling 62
9 Product specications 63
9.1 Technical data 63
9.2 Unit dimensions 64
5 Operation 43
5.1 Function of the display and operating elements 43
5.2 Commissioning 44
5.3 Notes on operation 45
5.3.1 Function of the LED's in info mode 45
5.3.2 Inspections during operation 45
5.4 Carrying out manual draining 46
5.5 Taking the unit out of operation 46
3
1 Introduction
1.1 To the very beginning
We thank you for having purchased the steam humidier Nordmann ES4 4.
The steam humidier Nordmann ES4 4 incorporates the latest technical ad van ces and meets all recognized safety standards. Nevertheless, improper use of the Nordmann ES4 4 may result in danger to the user or third parties and/or impairment of material assets.
To ensure a safe, proper, and economical operation of the steam humidier Nordmann ES4 4, please observe and comply with all information and safety instructions contained in the present installation and operating instructions as well as the instructions given in the manuals for the components used in the humidication system.
If you have questions, which are not or insufciently answered in this documentation, please contact your Nordmann supplier. They will be glad
to assist you.
1.2 Notes on the installation and operating instructions
Limitation
The subject of these installation and operating instructions is the steam humidier Nordmann ES4 4. The various accessories (e.g. steam
distributor, steam distribution system, etc.) are only described insofar as this
is necessary for proper operation of the equipment. Further information on
accessories can be obtained in the respective instructions.
These installation and operating instructions are restricted to the installa- tion, commissioning, operation, servicing and trouble shooting of the steam humidier Nordmann ES4 4 and is meant for well trained personnel
being sufciently qualied for their respective work.
These installation and operating instructions are supplemented by various separate items of documentation (spare parts list, manuals for accessories, etc.). Where necessary, appropriate crossreferences are made to these publications in the present documentation.
4
Explanation of the symbols used in this manual
CAUTION!
The catchword “CAUTION” designates notes in this documentation that, if neglected, may cause damage and/or malfunction of the unit or other
material assets.
WARNING!
The catchword “WARNING” used in conjunction with the general caution symbol designates safety and danger notes in this documentation that, if neglected, may cause to injury to persons.
DANGER!
The catchword “DANGER” used in conjunction with the general caution symbol designates safety and danger notes in this documentation that, if neglected, may lead to severe injury or even death of persons.
Safekeeping
Please safeguard these installation and operating instructions in a safe place, where it can be immediately accessed. If the equipment changes hands, the documentation should be passed on to the new operator.
If the documentation gets mislaid, please contact your Nordmann supplier.
Language versions
The present installation and operating instructions are available in various languages. Please contact your Nordmann supplier for information.
Copyright protection
The present installation and operating instructions are protected under the Copyright Act. Passingon and reproduction of the manual (or part thereof) as well as exploitation and communication of the contents are prohibited without written permission by the manufacturer. Violation of copyright terms is subject to legal prosecution and arises liability for indemnication.
The manufacturer reserves the right to fully exploit commercial patent rights.
5
2 For your safety
General
Every person working with the Nordmann ES4 4 must have read and un­derstood the present installation and operating instructions before carrying out any work. Knowing and understanding the contents of the installation and operating instructions is a basic requirement for protecting the personnel against any kind of danger, to prevent faulty operation, and to operate the unit safely and correctly.
All ideograms, signs and markings applied to the unit must be observed and kept in readable state.
Qualication of personnel
All actions described in the present Installation and operating instructions (installation, operation, maintenance, etc.) must be carried out only by well
trained and sufciently qualied personnel authorised by the owner.
For safety and warranty reasons any action beyond the scope of this manuals must be carried out only by qualied personnel authorised by the
manufacturer.
It is assumed that all persons working with the Nordmann ES4 4 are fa­miliar and comply with the appropriate regulations on work safety and the
prevention of accidents.
This unit may not be used by persons (including children) with reduced physical, sensory or mental abilities or persons with lacking experience and/ or knowledge, unless they are supervised by a person responsible for their safety or they received instructions on how to operate the unit. Children must be supervised to make sure that they do not play with unit.
Intended use
The steam humidier Nordmann ES4 4 is intended exclusively for air humidication via a steam distributor or a fan unit approved by the manufacturer within the specied operating conditions (see chapter 9
“Product specications”). Any other type of application without the express written consent of the manufacturer is considered as not conforming with the intended purpose and may lead to the Nordmann ES4 4 becoming dangerous.
Operation of the equipment in the intended manner requires that all the information in these instructions is observed (in particular the safety instructions).
6
Danger that may arise from the unit
DANGER! Danger of electric hazard!
One may get in touch with live parts when the unit is open. Touching live parts may cause severe injury or danger to life.
Prevention: Before carrying out any work set the Nordmann ES4 4 out
of operation as described in chapter 5.5 (switch off the unit, disconnect it from the mains and stop the water supply) and secure the unit against inadvertent powerup.
WARNING! Hot water vapour - Danger of scalding!
The Nordmann ES4 4 produces hot water vapour. There is danger of scalding when getting in touch with hot water vapour.
Prevention: Do not carry out any work on the steam system during op-
eration (steam lines, steam distributor, etc.). If the steam system is leaky set the Nordmann ES4 4 immediately out of operation as described in chapter 5.5. Correctly seal the steam system before putting the unit into
operation again.
WARNING! Danger of burning!
During operation the components of the steam system (e.g. steam cylinder, steam distributor) get very hot (up to 100 °C). There is danger of burning when touching the hot components.
Prevention: Before carrying out any work on the steam system set the
Nordmann ES4 4 out of operation as described in chapter 5.5, then wait until the components have cooled down sufciently thus preventing dan­ger of burning.
Behaviour in case of danger
If it is suspected that safe operation is no longer possible, then the Nor- dmann ES4 4 should immediately be shut down and secured against accidental power-up according to chapter 5.5. This can be the case under the following circumstances:
– if the Nordmann ES4 4 is damaged
– if the electrical installations are damaged – if the Nordmann ES4 4 is no longer operating correctly – if connections and/or piping are not sealed
All persons working with the Nordmann ES4 4 must report any alterations to the unit that may affect safety to the owner without delay.
Prohibited modications to the unit
No modications must be undertaken on the Nordmann ES4 4 without
the express written consent of the manufacturer.
For the replacement of defective components use exclusively original ac- cessories and spare parts available from your Nordmann supplier.
7
3 Product Overview
3.1 Model overview
The steam air humidiers Nordmann ES4 4 are available in the following
version.
Nordmann ES4 4 230V1 230V/1~/50...60Hz 4 kg/h
Key model designation
Product designation
Max.steam capacity in kg/h
Heating voltage: 230V/1~/50...60Hz: 230V1
Model Heating voltage Max. steam capacity
Nordmann ES4 4 230V1
3.2 Identication of the unit
The identication of the unit is found on the type plate:
Heating voltage
Maximum steam capacity per unit
Admissible water supply pressure
Field with certication symbols
Power consumption
Control voltage
Type designation Serial number (7 digits) Month/Year
Nordmann Engineering AG, CH-8808 Pfäfkon
Type: ES4 4 Ser.Nr.: XXXXXXX 11.12 Heating voltage: 230V / 1~ / 50...60Hz Power: 3.1 kW
Steam capacity: 4.0 kg/h Ctrl. Voltage: 230V / 1~ / 50...60Hz Water pressure: 1...10 bar
Made in Switzerland
8
3.3 Steam humidier construction
19
18
17
1
2
10
11
12
13
14
9
20
21
22
15
3
4
5
16
6
7
8
23
1 Housing (small, large) 2 Cable openings, top side 3 Power board (option) 4 Control board with CF Card 5 Terminals supply voltage
6 Drain/info key 7 Operation status indicators
8 Unit switch
9 Water cup
10 Overow hose 11 Filling hose 12 Water supply hose
13 Drain valve 14 Inlet valve 15 Steam cylinder 16 Type plate 17 Electrode plug 18 Level sensor 19 Steam outlet 20 Water supply connector
21 Drain cup 22 Drain connector
23 Cable openings, bottom side
9
3.4 Functional description
The steam humidier Nordmann ES4 4 is a pressureless steam generator that utilizes an electrode heating. The steam humidier Nordmann ES4 4 is designed for air humidication via a steam distributor.
Steam hose
Water cup
Overow hose
Filling hose
Water supply hose
Control
board
Level sensor
Electrodes
Steam distribution pipe
Condensate hose
with siphon
Current sensor
Heating relay
Power board
Inlet valve
Steam cylinder
Unit switch
Drain valve
Base tub
Steam generation
Any time steam is requested, the electrodes are supplied with voltage via the heating relay. Simultaneously, the inlet valve opens and water enters the steam cylinder from the bottom via water cup and supply line. As soon as the electrodes come in contact with the water, current begins to ow between the electrodes, eventually heating and evaporating the water. The more the electrode surface is exposed to water, the higher is the current
consumption and thus the steam capacity.
10
Upon reaching the requested steam capacity, the inlet valve closes. If the steam generation decreases below a certain percentage of the required capacity, due to lowering of the water level (e.g. because of the evapora­tion process or drainage), the inlet valve opens until the required capacity is available again. If the required steam capacity is lower than the actual output, the inlet valve is closed until the desired capacity is achieved by lowering of the water level (evaporation process).
Level monitoring
A sensor provided in the steam cylinder cover detects when the water level gets too high. The moment the sensor comes in contact with water, the inlet valve closes.
Drainage
As a result of the evaporation process, the conductivity of the water increases due to an escalating mineral concentration. Eventually, an inadmissibly high current consumption would take place if this concentration process were permitted to continue. To prevent this concentration from reaching a value, unsuitably high for the operation, a certain amount of water is perio dically drained from the cylinder and replaced by fresh water.
Control
The steam production can be controlled with an external 010V continuous controller or an external humidistat (24 VDC On/Off control).
11
3.5 Humidication system overview
17
DV41
13
DS22
11
14
18
W21
12
KS10
8
15
W22
16
125...1250 µS/cm
1 Steam humidier
2 Steam connector 3 Water drain connector
4 Water supply connector
5 Water connection hose G 3/4"- G 3/8"
(included in the delivery) 6 Filter valve (accessory “Z261”) 7 Manometer (installation recommended) 8 Funnel with siphon (building side) 9 Water drain hose (included in the delivery)
1
2
3
4
DSS22
Z261
6
5
9
7
8
1...10 bar
1...40 °C
10 Service switch control voltage supply (building side) 11 Steam hose (accessory “DS..”/“Z10”) 12 Condensate hose (accessory “KS10”) 13 Steam distribution pipe (accessory “DV41..”) 14 Steam nozzle (accessory “W21”) 15 Steam distributor (accessory “DSS22”) 16 Steam distributor (accessory “W22”) 17 Humidity controller 010V or Humidistat
18 Safety humidistat
10
ONOFF
12
3.6 Accessories
3.6.1 Accessories overview
Accessories for water installation
Nordmann ES4 4
Filter valve Z261 (1 pc. per system)
Accessories for steam installation
Nordmann ES4 4
Steam distribution pipe
(details see chapter 3.6.2.1)
Steam nozzle
(details see chapter 3.6.2.2)
Steam distributor
(details see chapter 3.6.2.3)
Steam distributor
(details see chapter 3.6.2.4)
Steam hose / meter 1x DS22
EcoTherm insulation hose / meter 1x ECT22
Condensate hose / meter 1x KS10
Accessories for humidity control
Duct humidistat HBN (1 pc. per system)
Room humidistat HSN (1 pc. per system)
1x DV41-...
1x W21
1x W22
1x DDS22
Nordmann ES4 4
13
3.6.2 Accessory details
3.6.2.1 Steam distribution pipe DV41-...
The steam distribution pipes are selected on the basis of the duct width (for horizontal installation) or the duct height (for vertical installation) and
the capacity of the steam humidier. Important! Always select the longest possible steam distribution pipe (opti
mum humidication distance).
L
B
Steam distribution pipes for
Nordmann ES4 4
1)
Type DV41-.. in mm
41-200 200 210...400
41-350 350 400...600
41-500 500 550...750
41-650 650 700...900
41-800 800 900...1100
41-1000 1000 1100...1300
41-1200 1200 1300...1600
1)
Material: CrNi steel
Length (L) steam
distribution pipe
2)
2)
special length on request
Duct width (B)
in mm
14
3.6.2.2 Steam nozzle W21
The steam nozzle W21 can be mounted in the ventilation duct horizontally or vertically. Keep a minimum distance clearance (A) of 200 mm between nozzle opening and the opposite duct wall.
64 mm
64 mm
max. 19 mm
ø22.5 mm
ø48.5 mm
A
A
1/2
1/2
3.6.2.3 Steam distributor DSS22 (for steam bath)
64 mm
ø22.5 mm
ø48.5 mm
2/3
1/3
64 mm
max. 19 mm
3.6.2.4 Steam distributor W22 (for steam bath)
ø43 mm
ø22.5 mm
15
3.7 Standard delivery
The standard delivery includes:
– Steam humidier Nordmann ES4 4 with water drain hose and water
connection hose G 3/4"  G 3/8", xing set and installation and operating instructions (this document), packaged in cardboard box – Cardboard box: 550 mm x 360 mm x 300 mm,
shipping weight: ?? kg
– Ordered accessories with operating instructions according chapter 3.6,
packed separately
– Spare parts list
3.8 Storing/Transportation/Packaging
Storing
Store the unit in a protected area meeting the following requirements:
– Room temperature: 1 ... 40 °C – Room humidity: 10 ... 75 %rh
Transportation
For optimum protection always transport the unit in the original packaging.
The weight of the unit is less than 20 kg. Always place the unit on its back side.
Packaging
Keep the original packaging of the Nordmann ES4 4 for later use.
In case you wish to dispose of the packaging, observe the local regulations on waste disposal. Never dispose of the packaging to the environment.
16
4 Mounting and installation work
4.1 Important notes for mounting and installation work
Qualication of personnel
All mounting and installation work must be carried out only by well quali­ed personnel authorised by the owner. It is the owner’s responsibility
to verify proper qualication of the personnel.
General note
Strictly observe and comply with all information given in the present instal­lation and operating instructions regarding the location of the unit and the installation of water, steam and electricity.
Observe and comply with all local regulations dealing with water, steam and electrical installations.
Safety
Some installation work requires removal of the unit cover. Please note the following:
DANGER! Danger of electric hazard!
You may get in touch with live parts when the unit is open. The steam humidier must be connected to the mains only after all mounting and installation work has been completed and the cover has been relocated properly.
CAUTION!
The electronic components inside the humidier are very sensitive to electrostatic discharge. When the unit is open for installation work, ap­propriate measures must be taken to protect these components against damage caused by electrostatic discharge (ESD protection).
17
4.2 Installation overview
A1 / A2
External safety chain
X6
12
ES4 4
SC1SC2
SAFETY
ext.
SC1SC2
Pmax Pmin
W21
Steam installation
see chapter 4.4
800 Pa
-800 Pa
DV41
W21
min. 300 mm
KS10
min. 20 % –
Ømin.
200 mm
W21
min. 5 %
Rmin. 300 mm
DS22
min. 20 %
B3
B3
B2
B1
On/Off-ControlContinuous control 0-10V
JP4
JP3
X1
123
ES4 4
CTRL V+
GND
0-10V
On/Off
A1
CONT.SIGN
– + 0-10V
+
ext.
V+GND CTRL
JP4
JP3
0-10V
On/Off
CONT.SIGN
A2
GND
CTRL V+
On/Off
X1
123
ES4 4
ext.
V+GND CTRL
Heating voltage
ONOFF
X9
MAIN SUPPLY
Mounting the unit
see chapter 4.3
Water installation
see chapter 4.5
Electric installation
see chapter 4.6
125...1250 µS/cm
1...10 bar
1...40 °C
ø 30 mm
G 3/4"
G 1/2"
ø14/7 mm
Z261
G 3/8"
≥ 40 mm
min. 50 cm
L
N PE
PWR
Q3
F5
L1
N
230V1~ 50..60Hz
ES4 4
ext.
18
4.3 Mounting the unit
4.3.1 Notes on locating the unit
min. 250 mm
60...70 °C
Y
min. 400 mm
min. 400 mm
X
1 ... 40 °C max. 75 %rh IP20
Z
min. 600 mm
min. 600 mm
Nordmann ES4 4 230V1
Dimensions housing (X x Y x Z) in mm 285 x 205 x 430
Net weight in kg 8
Operating weight in kg 13
19
The installation site of the steam humidier depends largely on the location of the steam distributor (see chapter 4.4). To ensure proper functioning of the steam humidier and to obtain an optimal efciency, the following points must be considered and observed when choosing the location for the steam humidier:
– Install the steam humidier so that the length of the steam hose is kept
as short as possible (max. 4 m) and that the minimum bend radius
(R= 300 mm) and up-slope (20 %) or down-slope (5 %) of the steam
hose is observed (see chapter 4.4.5).
– The steam humidiers Nordmann ES4 4 are designed for wallmount-
ing. Make sure that the construction (wall, pillar, oormounted console, etc.) to which the humidiers are to be mounted, offers a sufciently high load-bearing capacity (take notice of the weight information found in the dimensions and weights table above), and is suitable for the installation.
CAUTION!
Do not mount the steam humidier directly to the ventilation duct (insufcient stability).
– The back panel of the Nordmann ES4 4 is retaining heat during opera-
tion (max. surface temperature of the metal housing approx. 60  70 °C). Make sure, therefore, that the construction (wall, pillar, etc.) to which the units are to be mounted, does not consist of heatsensitive material.
– Install the steam humidier in such a manner that it is freely accessible
with sufcient space available for maintenance purposes (refer to the above illustration for minimum distances).
– The Nordmann ES4 4 is protected according to IP20. Make sure the
units are installed in a dripproof location and the admissible ambient conditions are complied with.
– The steam humidier Nordmann ES4 4 may only be installed in rooms
with a oor drain.
CAUTION!
If for some reason the Nordmann ES4 4 must be installed in a location without oor drain, it is mandatory to provide a leakage monitoring device to safely interrupt the water supply in case of leakage.
– When xing the Nordmann ES4 4 use only the xing materials sup-
plied with the unit. If xing with the materials supplied is not possible in your particular case, select a method of xing that is of similar stability.
– The Nordmann ES4 4 is designed for installation and operation inside
buildings.
20
4.3.2 Mounting the humidier
a
b
c
e
d
Dimension Nordmann ES4 4 230V1
a 175 mm b 35 mm c 335 mm d 130 mm e 75 mm
Procedure
1. Mark the attachment point “A” on the wall.
2. Drill hole for attachment point “A” (diameter: 8 mm, depth: 40 mm).
3. Insert the supplied plastic plug, and tighten the screw until the distance between the wall and the screw head is 4 mm.
4. Unlock the two screws xing the front panel to the unit, then remove the front panel.
5. Hang up the unit onto the screw and adjust it horizontally and vertically using a spirit level. Then, mark the xing points “B”.
6. Drill the holes for the xing points “B” (diameter: 8 mm, depth: 40 mm).
7. Insert the supplied plastic plugs, and tighten the screws until the distance between the wall and the screw head is 4 mm.
8. Hang the unit up onto the screws. Before tightening the screws, readjust the unit with the spirit level.
9. Reattach the front panel and secure it with the two screws.
21
4.3.3 Inspecting the installed unit
Check the following points:
Is the unit installed in the correct place (see chapter 4.3.1)?
Is the supporting surface stable enough?
Is the unit correctly aligned, vertically and horizontally?
Is the unit properly secured (see chapter 4.3.2)?
Has the front panel of the unit been relocated and correctly xed with
the two screws?
22
4.4 Steam installation
4.4.1 Overview steam installation
800 Pa
Pmax Pmin
-800 Pa
DV41
min. 300 mm
min. 20 % –
W21
min. 5 %
DS22
Rmin. 300 mm
min. 20 %
+
W22
200 mm
min. 5 %
Rmin. 300 mm
Ømin.
KS10
min. 300 mm
DSS22
23
4.4.2 Positioning of the steam distributors in a duct
The location for the steam distributor in the duct should be determined at the time of dimensioning the air conditioning system. Please note the following instructions to ensure proper humidication of the duct air.
Calculating the humidication distance
The water vapour, emitting from the steam distributors, requires a certain distance to be absorbed by the ambient air so that it is no longer visible as
steam. This distance is referred to as humidication distance “B
serves as a basis for the determination of the minimum distances from the
upstream components in the system.
and
N
BN: Humidication distance B
E: Expansion and mixing zone φ1: Supply air humidity before humidication φ2: Supply air humidity after humidication
N
The calculation of the humidication distance “BN” is dependent on several factors. For a rough estimation of the humidication distance “BN”, the fol­lowing table is useful. Recommended standard values listed in this table are based on a supplyair temperature range of 15 °C to 30 °C.
Humidity at inlet
ϕ1 in %rh
40 50 60 70 80 90
5 0.9 1.1 1.4 1.8 2.3 3.5
10 0.8 1.0 1.3 1.7 2.2 3.4
20 0.7 0.9) 1.2 1.5 2.1 3.2
30 0.5 0.8 1.0 1.4 1.9 2.9
40 0.5 0.8 1.2 1.7 2.7
50 0.5 1.0 1.5 2.4
60 0.7 1.2 2.1
70 0.8 1.7
φ1 in %rh: Relative supply air humidity prior to humidication at the lowest supply air tem-
perature
φ2 in %rh: Relative supply air humidity after the steam distribution pipe at maximum capacity
Length of humidication distance BN in m
Humidity at outlet ϕ2 in %rh
24
Example
given: ϕ1= 30 %rh, ϕ2= 70 %rh
humidication distance B
: 1,4 m
N
Minimum distances to be observed
To prevent the water vapour, that is emitting from the steam distributors, from condensing on downstream system components, a minimum distance to the steam distributor must be observed (depends on the humidication distance “B
”).
N
before/after constriction
50 mm
N
0.5 x B
before bend
N
1 x B
after expansion
before branch
N
1 x B
N
0.5 x B
before diffuser before control sensor
N
1 x B
5 x B
N
25
before/after lter/register before/after fan, zone exit
+
50 mm
N *
1.5 x B
N
* 2,5 x B
before aerosol lter
N
1 x B
Installation notes and dimensions
50 mm
1 x B
N
The steam distribution pipes are designed for either horizontal installation (on the duct wall) or, with accessories, for vertical installation (in the duct oor). The outlet orices should always point upwards and at right
angles to the airow.
If possible, the steam distribution pipes should be installed on the pressure
side of the duct (max. duct pressure 1500 Pa). If the steam distribution pipes are installed on the suction side of the duct, the maximum vacuum
must not exceed 800 Pa.
Select a location for the installation, tailored to suit your duct (see the fol­lowing illustrations) and position the steam distribution pipes in the duct so that a uniform distribution of steam is achieved.
26
Positioning the steam distributors in the duct
In positioning the steam distribution pipe DV41.. and the steam nozzle W21, the following dimensions should be observed:
H
1/2
1/2
2/3
H
1/3
min
h
H
1/2
1/2
H min.= 250 mm H ≥400 mm H min.= 200 mm
g min.= 100 mm h min.= 85 mm
A
A
1/2
1/2
2/3
1/3
min
h
A min.= 200 mm
Guidelines for dimensioning the ventilation ducts
– To facilitate the installation of the steam distribution pipes and for control
purposes, a sufciently sized control opening should be planned.
– Within the range of the humidication distance, the ventilation duct
should be waterproofed.
– Air ducts passing through cold rooms should be insulated to prevent
the humidied air from condensing along the duct wall.
– Poor airow conditions within the air duct (e.g. caused by obstacles,
tight bends, etc.) can lead to condensation of the humidied air.
– Steam distribution pipes must not be mounted to round ducts.
If you have questions relating to the dimensioning of ventilation ducts in combination with steam humidiers Nordmann ES4 4, contact your Nord­mann supplier.
27
4.4.3 Positioning of the steam distributors in a steam bath
The positioning of the steam distributors DSS22 and W22 in a steam bath belongs to the clients responsability.
4.4.4 Installing the steam distributors
Detailed information on the installation of steam distributors can be found
in the separate mounting instructions for these products.
28
4.4.5 Installing the steam and condensate hose
Important! Use original steam and condesate hose from your Nordmann supplier exclusively. Other types of hoses can cause undesired operational malfunctions.
Instructions for the hose layout
The hose layout depends on the position of the steam distribution pipe:
– Steam distribution pipe is mounted more than 500 mm above the top
edge of the humidier:
Ømin.
200 mm
min. 20 %
min. 300 mm
Rmin. 300 mm
min. 20 %
+
min. 20 %
max. 4 m
min. 300 mm
+
Rmin. 300 mm
max. 4 m
min. 300 mm
min. 20 %
200 mm
Ømin.
min. 300 mm
min. 20 %
Initially, lead the steam hose with an upslope of at least 20% over a minimum height of 300 mm, then lead the hose with a minimum upslope of 20% and/or a minimum downslope of 5% to the steam
distribution pipe.
The condensate hose is led down to the humidier with a minimum slope of 20 %, in the form of a siphon (min. hose bend diameter Ø200 mm), and inserted into the specied opening until it comes to a stop. Note: If your unit feeds a number of steam distribution pipes, the indi­vidual condensate hoses are to be led into a discharge funnel. Important! Before putting the unit into operation, the siphon of the condensate hose must be lled with water.
29
min. 20 %
+
max. 4 m
Rmin. 300 mm
min. 300 mm
min. 5 %
min. 20 %
Ømin.
200 mm
– Steam distribution pipe is mounted less than 500 mm above the top
edge of the humidier:
min. 300 mm
Obstacle
min. 20 %
+
Rmin. 300 mm
max. 4 m
Install condensate drain (accessory)
at the lowest point
Initially, the steam hose is led with an upslope of at least 20 % over a minimum height of 300 mm above the top edge of the humidier and then down to the steam distribution pipe with a minimum slope of 5 %.
Condensate hose is led down with a minimum slope of 20 %, in the form of a siphon (min. hose bend diameter Ø200 mm), directly into a discharge funnel. Important! Before putting the unit into operation, the siphon of the condensate hose must be lled with water.
min. 5 %
Rmin. 300 mm
min. 20 %
Ømin.
200 mm
min. 20 %
min. 300 mm
+
min. 300 mm
Ømin.
200 mm
min. 20 %
30
– The steam hose should be kept as short as possible (max. 4 m) while
observing the minimum bend radius of 300 mm. Important! Allowance must be made for a pressure loss of 10 mm water column (approx.
100 Pa) per meter steam hose. Note: If your particular installation exceeds the maximum steam hose
length of 4 m contact your Nordmann representative. In any case, steam hoses longer than 4 m must be insulated in their entire length (e.g. with
insulation hose “EcoTherm”).
– Reductions in the cross section such as kinks should be avoided through-
out the entire length of the hose. The installation of a stop cock in the steam hose is not permissible.
– Steam hoses must be prevented from sagging (condensate pockets); if
necessary, support with pipe clamps, trough, or wall brackets, or install
a condensate drain in the steam hose.
Important! When deciding on the length and layout of the hose, it
should be noted that the steam hose may become somewhat shorter with progressive ageing.
Securing the hose
The steam hose must be secured to the steam distribution pipe and humidi er steam outlet by means of hose clamps. Caution! Do not overtighten the hose clamp on the steam connector of the steam humidier.
31
Steam line with xed piping
For steam lines with xed piping, the same instructions apply to the laying of the piping as already described.
min. 20 %
+
max. 4 m
200 mm
Rmin. 5 x D
min. 300 mm
Ømin.
min. 300 mm
min. 20 %
The following additional notes should be observed:
– The minimum internal diameter of the steam line (diameter depend-
ent on the steam humidier) should be applied over the whole length of
the piping.
– Use exclusively copper pipe or stainless steel (min. DIN 1.4301).
– To minimize the condensate formation (=loss), the steam pipes must
be insulated.
– The minimum bend radius for solid pipes is 5 x internal diameter.
– Connection of the steam pipes to the steam distribution pipe and steam
humidier is effected by means of short lengths of steam hose secured with hose clamps.
– Important! Allowance must be made for a pressure loss of 10 mm
water column (approx. 100 Pa) per meter length or per 90° bend.
32
4.4.6 Common steam and condensate line errors
2.
1.
3.
4.
5.
1. Steam hose not led at least 300 mm perpendicularly upwards before rst bend.
2. Minimum bend radius of steam hose of 300 mm not maintained (forming of condesate).
3. Siphon of the condensate hose not at least 300 mm below the steam distribution pipe.
4. No condensate drain installed at vertical transition.
5 . Steam hose not sloped (slope min. 20 %).
33
4.4.7 Inspecting the steam installation
Use the following check list to ascertain that the steam installation was performed correctly:
– Steam distribution pipe
Steam distributors correctly positioned and secured (screws tight-
ened)?
Are the outlet orices at right angles to the air ow direction?
– Steam hose
Maximum length of 4 m?
Minimum bend radius of 300 mm (5 x internal diameter with xed
piping)?
Have the instructions for hose positioning been followed?
Steam hose: no sagging (condensate pocket) or condensate drain
with siphon (hose bend with a minimum diameter of 200 mm) installed at the lowest point?
Rigid steam lines: properly insulated? Correct installation material
used? Minimum internal diameter maintained?
Steam hose(s) securely attached with clamps?
Heat expansion during operation and shortening of the hose with
ageing taken into consideration?
– Condensate hose
Downslope of at least 20 %?
Siphon (min. ø200 mm) existing and lled with water?
Condensate hose correctly xed and not kinked?
34
4.5 Water installation
4.5.1 Overview water installation
ø 30 mm
G 3/4"
G 3/4"
ø14/7 mm
G 1/2"
125...1250 µS/cm
1...10 bar
1...40 °C
Z261
G 3/8"
≥ 40 mm
min. 50 cm
G 3/4"
ø14/7 mm
G 3/8"
ø 30 mm
ø 40/31 mm
35
4.5.2 Notes on water installation
Water supply
The water supply is to be carried out according to the gure found in chapter
4.5.1 and the applicable local regulations for water installations. The indicated connection specications must be observed.
– The installation of the lter valve (accessory “Z261”, alternatively a
shutoff valve and a 5 µm water lter can be used) should be made as close as possible to the steam humidier.
– Admissible mains pressure 1.0 to 10.0 bar (hammer-free system)
For mains pressures >10 bar, the connection must be made via a pres­sure reducing valve (adjusted to 1.0 bar). For mains pressures <1.0 bar please contact your Nordmann supplier.
Notes on water quality:
– For the water supply of the Nordmann ES4 4, use exclusively un-
– The use of additives such as corrosion inhibitors, disinfectants,
– If the Nordmann ES4 4 shall be operated with softened or partly
treated drinking water.
etc. is not allowed, since these additives may endanger health and affect proper operation.
softened water, please contact your Nordmann supplier.
– The connection material must be pressure-proof and certied for use
in drinking water systems.
Important! Before connecting the water line, the line should be well
ushed out.
CAUTION!
The thread at the humidier connection is made of plastic. To avoid overtightening, the union nut of the water pipe must be tightened by
hand only.
Water drain
The water drain is to be carried out according to the gure found in chapter
4.5.1 and the applicable local regulations for water installations. The indi­cated connection specications must be observed.
– Make sure that the drain pipe is correctly xed and easily accessible for
inspections and cleaning purposes.
– The draining temperature is: 80…90 °C. Use temperature-resistant
installation materials only!
36
4.5.3 Inspecting the water installation
Check the following topics:
– Water supply
Has lter valve (accessory “Z261”) or shutoff valve and 5 µm water
lter respectively been installed in supply line?
Have admissible water pressure (1 – 10 bar) and admissible tem-
perature (1 – 40 °C) been observed?
Does the supply capacity match the humidier and is the minimum
inside diameter of the supply pipe maintained throughout the entire length?
Are all components and pipes properly secured and are all threaded
connections securely tightened?
Is the water system properly sealed?
Does the water supply installation meet the requirements of the local
regulations for water installations?
– Water drain
Is the minimum inside diameter of the drain pipe of 40 mm maintained
throughout the entire length?
Has drain pipe been installed with a downslope of at least 10 %?
Has the heat resistance of the material used been veried to be at
least 100 °C?
Is the drain hose properly secured (hose clamps at unit connection
tightened)?
Does the water drain installation meet the requirements of the local
regulations for water installations?
37
4.6 Electric installation
4.6.1 Wiring diagram Nordmann ES4 4
Control board Power board
CF Card
Service
Steam
Driver
J8
RFI
PRO
BASIC
JP4
0-10V
JP3
On/Off
A1
1AT
200mAF
JP2
JP1
5V
24V
GND
CONT.SIGN
– +
0-10V
A2
Set JP2 Remove JP1
F2
F1
CTRL V+
J1 CPU BOARD
J1
Cylinder
0
Settings
1 2 3 4 5 6
ON
Low. Conduct. Standby Drain Force Drain Cylinder A/D CFGI-Modus
Drain Factor
1.0
Power Limit
75%
Drain switch
red yellow green
Error
MAIN CONTACT
X1 X6
12 123
V+GND CTRL
V+GND CTRL
On/Off
J7L
J6N
CYLINDER LEVEL SENSOR
REL4
F3
1AT
SC1SC2
SAFETY
SC1SC2
J
K
B3
B2
B1
J4N
X9
MAIN SUPPLY
L
PWR
Q3
F5
L1
230V1~ 50..60Hz
N PE
N
PE
DRAIN
S1
INLET
L N L N
F4 1AT
N L SWN SWL
SWITCH
X7
Cylinder RD 422
Inlet valve
Drain valve
X8
A1 Continuous controller (active 010V) A2 On/Off controller (passive 24VDC), set jumper on JP1 B1 Ventilation interlock B2 Airow monitor
B3 Safety humidistat
F1 Internal fuse power board: control signal (200 mA, fast acting) F2 Internal fuse power board: control 5 V (1 A, träge) F3 Internal fuse power board: control 24 V (1 A, träge) F4 Internal fuse power board: control voltage (1 A, träge) F5 External fuse supply voltage (see table in chapter 4.6.2) J Short circuited, if no external monitoring devices are connected JP1 Set jumper for voltage output on X1, V+ = 5 V (remove jumper JP1) JP2 Set jumper for voltage output on X1, V+ = 24 V (remove jumper JP2) JP3 Jumper must be removed JP4 Jumoper must be set K External safety chain (24 VDC) Q3 External service switch voltage supply S1 Unit switch REL4 Relay heating S1 Rotary switch "Cylinder type” S2 Potentiometer “Drain factor” S3 Potentiometer “Power limitation” S4 DIP switch “General unit settings” X1 Connection terminal control signal X6 Connection terminal safety chain X7 Connection terminal inlet and outlet valve X8 Connection terminal unit switch X9 Connection terminal voltage supply
38
4.6.2 Notes on electric installation
Important notes
– The electric installation must be carried out according to the wiring dia-
gram in chapter 4.6.1, the notes on electric installation as well as the applicable local regulations. All information given in the wiring diagram must be followed and observed.
– All cables must be lead into the unit via the cable openings equipped
with cable glands (e.g. option “CGcable gland”).
– Make sure the cables do not scrub on any components.
– Maximum cable length and required cross section per wire must be
observed.
– The supply voltage must match the unit voltage stated on the type plate.
Voltage supply (heating voltage)
CAUTION!
Before connecting, ensure that the mains voltage corresponds with the unit voltage stated on the type plate.
The Nordmann ES4 4 is to be connected to the mains supply in accordance with the wiring diagram, via a service switch “Q3” (disconnecting device with a minimum contact opening of 3 mm is an essential requirement) and a fuse “F5” (essential requirement, fuses are to be as detailed in the follow­ing table). The supply wiring is to be fed into the unit via a tensionrelieving device (cable gland) and connected to the terminals “X9”.
Heating voltage Max. steam
capacity
[kg/h]
230V1~ / 50..60Hz 4 3.1 13.5 16
Nominal
power
[kW]
Nominal
current
[A]
Main
fuse F5
[A]
The crosssection of the mains cable must comply with the applicable local regulations (minimum of 1.5 mm2).
39
External safety circuit
To guarantee the safety of the humidication system, monitoring the opera­tion by means of a safety circuit is an absolute requirement.
To accomplish this, the potential-free contacts (max. contact loading 250V/5A) of external moni t or ing devices (e.g. safety high limit humidistat, airow monitor, ventilation interlock, etc.) are connected in series to the
contacts “SC1” and “SC2” of the terminal block “X6” in accordance
with the wiring diagram.
DANGER! Danger of electric hazard!
The mains voltage is connected to terminal block “X6” (up to 240 V). The steam humidier must therefore be isolated from the mains supply (heat­ing and control voltage), before starting the connection work.
If, for whatever reason, no external monitoring devices are connected, a connecting bridge “J” must be installed on the contacts “SC1” and “SC2” of the terminal block “X6”.
Do not apply any extraneous voltage to the terminals.
The crosssection of the cable must comply with the applicable local regula-
tions (minimum of 1 mm
2
).
Control signal
– External continuous humidity controller 0-10V (A1)
An external humidity continuous controller is to be connected to the contacts “IN” (+) and “GND” (–) of the terminal block “X1”.
24 VDC On/Off humidistat (passive)
An 24 VDC On/Off humidistat is to be connected to the contacts “V+” and “IN” of the terminal block “X1”. Note: for the 24 VDC On/Off control a jumper must be set on “JP1” and the jumper on “JP2” msut be removed.
40
4.6.3 Unit conguration
All setting components for the unit congration are located on the control board:
– Rotary switch “Cylinder”: cylinder type
– Potentiometer “Drain Factor”: drain factor
– Potentiometer “Power Limit”: power limitation
– DIP switch “Settings”: general settings
Setting the steam cylinder type (“Cylinder”)
Use the rotary switch “Cylinder” to select the type of steam cylinder used:
Unit type ES4 4 230V1
Steam cylinder type RD 422
Position rotary switch “Cylinder” 0
Setting the drain factor
Use the potentiometer “Drain Factor” to set the drain factor (setting range:
0.5...2.0, factory setting: 1.0).
Setting the power limitation
Use the potentiometer “Power Limit” to set the power limitation in % of the maximum capacity (setting range: 30...100%, factory setting: 100%).
General settings (“Settings”)
With the DIP switches “Settings” you can set different unit parameters. The unit parameters are preset in the factory and may only be modied by the client after consulting the Nordmann representative.
Switch Factory setting Description
1 OFF ON: low water conductivity <125 µS/cm
OFF: normal water conductivity ≥125 µS/cm
2 OFF ON: standby draining (72 hours) activated
OFF: standby draining (72 hours) deactivated
3 OFF ON: forced draining (72 hours) activated
OFF: forced draining (72 hours) deactivated
4 OFF ON: steam cylinder replacement interval 2500 h.
OFF: steam cylinder replacement interval 1500 h.
5 ON ON: the heating voltage is interrupted during draining
of the steam cylinder OFF: the heating voltage is interrupted during draining and relling of the steam cylinder
6 OFF ON: Offset control signal activated (210V)
OFF: Offset control signal deactivated (010V)
41
4.6.4 Inspecting the electrical installation
Check the following points:
Do the supply voltages for heating and control comply with the relevant
voltages given in the wiring diagram?
Is the correct CF Card inserted?
Are the voltage supplies (heating and control voltage) correctly fused?
Is the service switch “Q..” installed in the supply line for to the heating
and control voltage?
Are all components correctly connected according to the wiring diagram?
Are all connecting cables fastened?
Are the connecting cables free of tension (passed through cable glands?)
Does the electric installation meet the applicable local regulations for
electric installations?
Is the front panel mounted and correctly xed with the two screws?
42
5 Operation
5.1 Function of the display and operating elements
Drain/Info key
– press key shortly: Opens and closes the drain valve (manual drain-
ing). Note: the drain valve is automatically closed after 10 minutes.
– press key for a extended period of time (>3 sec.): activating the
info mode
red LED “Error”
– in normal operating mode
– The LED lights in case of a malfunction of the unit. Further opera-
tion is no longer possible, the heating voltage is interrupted.
– The LED ashes alternately with the green LED if the external
safety chain (ventilation interlock, safety humidistat, etc.) is open.
– in info mode
LED ashes in intervals if a malfunction is present. The number of “ashes” per interval indicates the left digit of the error code.
yellow LED “Warning and info indication”
– in normal operating mode
The LED lights if the cylinder maintenance is due (see chapter 6) or
the maintenance indication is not reset after the maintenance (see
chapter 6.6).
– in info mode
LED ashes in intervals if a malfunction is present. The number of “ashes” per interval indicates the right digit of the error code.
green LED “Steam”
– in normal operating mode
– The LED lights if the unit produces steam.
– The LED ashes alternately with the red LED if the external safety
chain (ventilation interlock, safety humidistat, etc.) is open.
– in info mode
LED ashes in intervals. The number of “ashes” per interval multiplied by 10 indicates the current steam output in %.
Unit switch
Switches the unit on and off. The switch is illuminated when the unit is switched on.
43
5.2 Commissioning
Proceed as follows when putting the unit into operation:
1. Examine the steam humidier and installation for possible damage.
DANGER!
Damaged devices or devices with damaged installation may present danger to human life or cause severe damage to material assets.
Damaged units and/or units with damaged or faulty installation must not be operated.
2. Check whether the front panel is mounted and xed with the two screws.
3. Open the shutoff valve in the water supply line.
4. Verify the set humidity value at the humidity controller or at the humidistat, and readjust as required.
5. Switch on the service switch for mains supply.
6. Actuate the unit switch of the steam humidier.
The steam humidier carries out a system test, during which all the LED’s light up.
If, after the system test: – the yellow LED lights permanently, the steam cylinder maintenance
is due (see chapter 6) or the maintenance indication has not been reset (see chapter 6.6).
the red LED lights permanently, a fatal malfunction has occurred (see
chapter 7).
After the system test the unit is in normal operation mode.
As soon as the humidity controller or the humidistat requires humidity, power is switched on for heating. The inlet valve opens (slight delay) and the steam cylinder lls with water. As soon as the submerged electrodes heat the water up the green LED lights up and after a few minutes (approx. 5–10 minutes, depending on the conductivity of the water) steam is produced. Note: If the Nordmann ES4 4 is operated with water of low conductivity it may happen that the maximum steam capacity is not reached in the rst few hours of operation. This is normal. As soon as the conductivity has reached a sufcient level (due to the vaporisation process) the humidier will reach the maximum steam capacity.
44
5.3 Notes on operation
5.3.1 Function of the LED's in info mode
The info mode is activated by pressing the drain/info key for an extended period of time (> 3 seconds). After activating the info mode:
– rst, the green LED ashes. The number of ashes indicates the current
steam output in % of the maximum steam capacity.
Green LED ashing ...
1x 2x 3x 4x 5x 6x 7x 8x 9x 10x
Steam output
in %
10 20 30 40 50 60 70 80 90 100
Note: if no steam production is in progress when the info mode is acti­vated the green LED lights for 3 seconds, then it turns off again.
– then, if a malfunction is present (warning or error) the red and the yellow
LED ash successively. The number of ashes of the red LED indicates the left digit of the error code while the number of ashes of the yellow
LED indicates the right digit of the error code.
Note: If the red LED lights when the info mode is activated the malfunc­tion indicated is an error (E..) otherwise a warning (W..).
This indication procedure is repeated until the info mode is exited automati­cally after 5 minutes or the info mode is exited by pressing the drain/Info
key again.
Examples:
Indication in normal
operating mode
Indication in info mode
Steam output 0 % 50 % 50% 0 %
Error code –– –– W36 E21
green LED lights no yes yes no
red LED lights no no no yes
green LED ashes .. –– 5x 5x ––
red LED ashes .. –– –– 3x 2x
yellow LED ashes .. –– –– 6x 1x
5.3.2 Inspections during operation
During operation the Nordmann ES4 4 and the humidication system have to be inspected weekly. On this occasion check the following:
the water and steam installation for any leakage.
the steam humidier and the other system components for correct xing
and any damage.
the electric installation for any damage.
If the inspection reveals any irregularities (e.g. leakage, error indication)
or any damaged components take the Nordmann ES4 4 out of operation
as described in chapter 5.5. Then, contact your Nordmann representative.
45
5.4 Carrying out manual draining
Proceed as follows to drain the unit manually:
1. Briey press the drain/info key. The heating voltage is interrupted and the drain valve opens. The yellow LED ashes. Note: the drain valve closes after 10 minutes automatically
2. To stop the drain cycle briey press the drain/info key again.
5.5 Taking the unit out of operation
In order to take the steam humidier out of operation, perform the following steps:
1. If the unit has to be switched off because of a malfunction, please note the error code (number of ashes of the red and yellow LED) of the actual error.
2. Close the shutoff valve in the water supply line.
3. Start manual draining (see chapter 5.4) and wait until the steam cylinder
is empty.
4. Actuate the unit switch.
5. Disconnect steam humidier from the mains: Switch off service switch
to mains suppy and secure switch in “off” position against accidentally being switched on and clearly mark the switch.
WARNING! Danger of burning
If steam was produced just before the unit is taken out of operation, wait before opening the unit and let the steam cylinder cool down to prevent danger of burning.
46
6 Maintenance
6.1 Important notes on maintenance
Qualication of personnel
All maintenance work must be carried out only by well qualied and trained personnel authorised by the owner. It is the owner’s responsibility to verify
proper qualication of the personnel.
General note
The instructions and details for maintenance work must be followed and upheld.
Only the maintenance work described in this documentation may be car-
ried out.
Only use original Nordmann spare parts to replace faulty parts.
Safety
Some maintenance work requires removal of the unit cover. Please note the following:
DANGER! Danger of electric hazard!
You may get in touch with live parts when the unit is open. Touching live parts may cause severe injury or even lethal violation. Prevention: Before carrying out any maintenance work set the Nordmann ES4 4 out of operation as described in chapter 5.5 (switch off the unit, disconnect it from the mains and stop the water supply) and secure the unit against inadvertent powerup.
CAUTION!
The electronic components inside the humidier are very sensitive to electrostatic discharge. Prevention: Before carrying out any maintenance work to the electrical or electronic equipment of the humidier, appropriate measures must be taken to protect the respective components against damage caused by electrostatic discharge (ESD protection).
47
6.2 Maintenance list
Components Interval Work to be done
Steam cylinder X Remove and replace.
Drain valve X Remove, disassemble and clean, replace if necessary.
Steam cylinder receptacle X Inspect, clean if necessary.
Inlet valve X Remove and clean lter insert, replace if necessary.
Drain cup X Remove and clean if necessary
Drain pipe and siphon X Inspect, clean if necessary (decalcify and rinse out).
Steam installation X X Inspect steam and condensate hoses for cracks and to
To maintain operational safety the Nordmann ES4 4 steam humidier must be maintained at regular intervals. This is differentiated between the first
maintenance after approx. 500 operating hours (I), steam cylinder re­placement after the yellow LED lights (II) and annual maintenance (III).
Below you will nd a summary of the work to be carried out for each of the
three maintenance stages.
I II III
see that they are correctly attached, replace faulty hoses.
Water installation X X Inspect water hoses in the unit for cracks and to see
that they are correctly attached, replace faulty hoses Check supply pipe is tight, make tight if necessary. Clean water lter, if available.
Electrical installation X X Check all cables in the unit are rmly positioned and
examine status of insulation.
48
6.3 Removing and installing parts for maintenance
6.3.1 Removal and installation of the steam cylinder
1 2
1. Undo the two screws xing the front panel to the unit using a screwdriver, then remove the front panel.
2. Release the hose clamp on the steam hose using a screwdriver, then detach the steam hose from the steam outlet connection of the steam cylinder.
3 4
3. Remove all plugs from the electrodes and from the level sensor.
4. Loosen the screw of the steam cylinder xing device by a few turns, then push the xing device upwards until it comes loose and remove it.
49
5
5. Carefully lift steam cylinder away from the cylinder receptacle, then
remove it to the front.
CAUTION!
Put steam cylinder down carefully to avoid damage to the lower con­nection piece!
50
Installation of the steam cylinder follows the reverse sequence. Observe the following:
Before installing the steam cylinder in the unit, check the Oring of the
cylinder receptacle for damage and replace if necessary.
– Moisten the Oring of the cylinder receptacle with water (do not use
grease or oil), then insert steam cylinder into the receptacle and push it down to the stop.
– Attach the electrode plugs and the level sensor plug to the respective
electrode and sensor connections according to the following table.
Steam cylinder type RD 422
brown
Sensor
white
black
– Fasten steam hose on the connector of the steam cylinder with hose
clamps.
CAUTION!
– A leaky steam hose can cause damage due to moisture inside the
unit.
– The outlet connector of the steam cylinder is made of plastic. Do
not overtighten the hose clamp on the steam connector of the
steam cylinder.
51
6.3.2 Removal and installation of the drain cup
3
2
1
1. Release the hose clamp, then remove water drain hose from the con­nector on the water cup.
2. Undo the three screws xing the drain cup to the unit using a screwdriver, then remove the drain cup downwards.
3. Remove Oring from the annular groove of the drain cup.
Installation of the drain cup follows the reverse sequence. Before assem­bling check Oring of the drain cup and the gasket of the water supply hose for damage and replace if necessary.
52
6.3.3 Removal and installation of the water cup and the water hoses
For removing the water cup and the water hoses the steam cylinder must be removed rst (see chapter 6.3.1).
1. Release hose clamps using pliers, then disconnect all hoses from the
corresponding connectors and remove the hoses.
Note: The hoses connected to the water cup may also be removed to­gether with the water cup (see illustration) and then disconnected from the connectors of the water cup outside the unit.
2. Carefully pull xing clip of the water cup to the front, then push water
cup down from the holding device and remove it to the front.
The installation of the water cup and the water hoses follows the reverse sequence. Before xing the water hoses to the connector using the hose clamps, align the hoses in a way that they are not twisted.
53
6.3.4 Removal and installation of the drain valve
4
1
3
2
For removing the drain valve the steam cylinder must be removed rst (see chapter 6.3.1).
1. Detach electric cables (polarity of the cables must not be observed).
2. Release hose clamp and remove the hose from the connector.
3. Loosen the two screws with Phillips screwdriver, then remove the drain valve.
4. Disassemble the drain valve.
The assembly and the installation of the drain valve follows the reverse sequence. Before assembling the valve, check all Orings and gaskets for damage and replace if necessary.
54
6.3.5 Removal and installation of the inlet valve
1
3
5
4
3
For removing the inlet valve the steam cylinder must not be removed.
1. Detach electric cables (polarity of the cables must not be observed).
2. Release hose clamp and remove the hose from the connector.
3. Unlock union nut of the water pipe and remove water pipe.
4. Loosen the two screws with Phillips screwdriver, then remove inlet valve.
5. Remove strainer insert with pointed pliers
The installation of the inlet valve follows the reverse sequence. The union nut of the water pipe must be tightened by hand only.
55
6.4 Notes on cleaning the unit components
Unit component What to clean and how to clean
Water hoses • Remove any limescale by slightly knocking on the tubes
using a rubber hammer. Then, rinse the tubes well with hot tap water.
Inlet valve
strainer insert
Drain valve
valve housing
valve stem
Water cup Remove any limscale from the water cup and its con-
Use a brush (do not use a wire brush) to remove any limescale inside the inlet valve and on the strainer.
Wash inlet valve and strainer insert with a lukewarm soap solution, then rinse well with tap water.
Let the inlet valve dry before reinstallation!
Use a brush to remove any limscale from the valve housing, the bores and the valve seat on the valve stem (do not use a wire brush).
Wash the valve housing and the valve stem with a lukewarm soap solution, rinse the parts well with tap water and let them dry.
nectors using a brush (do not use a wire brush). If the water cup is heavily calcied, place it in an 8% formic acid solution (observe safety notes in chap- ter 6.5), until the limescale comes off.
56
Wash the water cup with a lukewarm soap solution and rinse well with tap water.
Unit component What to clean and how to clean
Drain cup Use a brush to remove any limscale from the drain cup
and the receptacle on the bottom side of the unit (do not use a wire brush). If the drain cup is heavily calcied, place it in an 8% formic acid solution (observe safety notes in chapter 6.5), until the limescale comes off.
Wash the drain cup and the receptacle on the bottom side of the unit with a lukewarm soap solution, rinse the parts well with tap water.
Interior of the unit (water side only)
6.5 Notes on cleaning agents
Only use cleaning agents stated in the table above. The use of disinfect-
ants is only permitted if they do not leave any toxic residues. In any case the parts must be thoroughly rinsed with water after cleaning.
Formic acid is indeed harmless to the skin, but it attacks the mucous membranes. Therefore prevent your eyes and respiratory tracts from getting in touch with the acid and its vapours (wear goggles and work in a well ventilated room or outside).
CAUTION!
Do not use any solvents, aromatized or halogenized hydrocarbons or other aggressive substances as they may cause damage to the
components of the unit.
Wipe the interior of the unit with a damp cloth without using any cleaning agent.
CAUTION: Take care that the electrical connections and the electronic components remain dry!
WARNING!
It is mandatory to observe and comply with the information and instructions regarding cleaning agents. Observe in particular: all information relating to the protection of personnel, environmental protection and restrictions
regarding usage.
6.6 Resetting the maintenance indication
After completing maintenance work, the maintenance indication (yellow LED lights) must be reset as follows:
Press drain key with the unit switched off and hold down.
Switch on steam humidier via the unit switch.
Hold drain key down until the system test is completed (approx. 10 sec­onds).
57
7 Fault elimination
Important! Most operational malfunctions are not caused by faulty equipment but rather by improper installation or disregarding of planning guidelines. Therefore, a complete fault diagnosis always involves a thorough examina­tion of the entire system. Often, the steam hose connection has not been properly executed, or the fault lies with the humidity control system.
7.1 Fault indication
In case of malfunction during operation, the unit control checks whether there is a temporary problem or whether it can resolve the problem by tak­ing necessary measures. Such malfunctions are not indicated in the nor­mal operation mode. However an appropriate error code with the status
“Warning” is generated.
Note: If the cause of the malfunction disappears of its own accord or if the controls can repair the malfunction, the alarm will automatically reset.
If the control, after several attempts, fails to solve the problem (number of attempts depends on the type of malfunction) or if the problem obstructs further operation, the heating voltage is interrupted via the main contactor.
The red LED lights in normal operation mode and an appropriate error code with the status “Error” is generated.
The error code can be queried in the info mode. Press drain/info key at least 3 seconds to enter the info mode. In the info mode the number
of ashes of the red LED indicates the decade of the error code while the number of ashes of the yellow LED indicates the digit of the error code (refer to chapter 5.3.1 for further information regarding the info mode).
Examples:
Normal operation
mode
Info mode
Error code E2 W21 E21 E37
red LED lights yes no yes yes
red LED ashes .. –– 2x 2x 3x
yellow LED ashes .. 2x 1x 1x 7x
58
7.2 Malfunction lists
7.2.1 System faults
Warning Error Cause Remedy
Code Malfunction Code Malfunction
E1 CF Card missing No CF Card installed on the control
board.
––– ––– E2 CF Card is empty No data stored on the CF Card. Install new CF Card.
––– ––– E3 CF Card is defective Invalid data stored on the CF Card. Install new CF Card.
––– ––– E4 CF Card is
incompatible
––– ––– E10 Hardware fault Control board defective. Replace control board.
The installed CF Card is not compat­ible with the hardware of the unit or with the basic settings of the control electronics.
7.2.2 Unit faults
Install CF Card or start test run.
Install correct CF Card. Let your Nordmann service technician adjust the basic settings.
Warning Error Cause Remedy
Code Malfunction Code Malfunction
W20 External safety
chain is open
W21 Max. lling level of
steam cylinder reached
W22 Permissible lling
time exceeded
(20 minutes)
––– ––– Ventilation interlock open. If applicable, check/turn on ventila-
E21 Max. lling level of
steam cylinder reached but no heating current
E22 Permissible lling
time exceeded
(more than 4 hours)
tion system.
Air ow monitor triggered. Check ventilator/lter of the ventila-
tion system.
Safety humidistat triggered. Wait. If applicable, check safety
humidistat
Water conductivity too low (after initial operation).
Water conductivity too low for type of steam cylinder.
Phase failure heating voltage. Check service switch in the mains
Water supply obstructed/shutoff valve closed/water pressure too low.
Inlet valve blocked or defective. Inspect strainer insert in the inlet valve,
Excessive back pressure in the steam line (duct pressure too high, steam line too long or kinked), causing water loss via lling cup.
Leakage in the water system. Inspect water system and seal if
Wait until the mineral content of the cylinder has increased
Select correct steam cylinder type.
supply line and switch on if applicable. Check mains fuse(s) and replace if applicable.
Inspect water supply (lter, water pip­ing, etc.), check/open shutoff valve, check water pressure.
if applicable clean strainer insert or replace inlet valve.
Check duct pressure, inspect steam installation. If applicable install pres­sure compensation kit (see options).
necessary.
59
Warning Error Cause Remedy
Code Malfunction Code Malfunction
W23 No electrode current
for more than 20 minutes
W24 Electrode current in
relation to the steam demand too high
W25 Max. admissible
electrode current exceeded
––– ––– E26 Main contactor
W27 Foam detection E27 Foam detection (4
W28 Steam cylinder
needs service
W29 Steam cylinder
needs service
W36 Standby draining of
steam cylinder active
W37 Forced draining of
steam cylinder active
E23 No electrode cur-
rent for more than 4 hours
E24 Electrode current in
relation to the steam demand too high
E25 Max. admissible
electrode current exceeded
jammed
automatic drainings within 24 hours)
E28 Service interval for
steam cylinder exceeded
E29 Max. operating
hours of the steam cylinder reached
––– ––– Automatic standby draining of
––– ––– Forced draining of steam cylinder
Phase failure heating voltage. Inspect/turn on service switch of the
mains supply line. Inspect the fuses of the mains supply, replace if necessary.
Water supply obstructed/shutoff valve closed/water pressure too low.
Inlet valve blocked or defective. Inspect strainer insert of the inlet
Excessive back pressure in the steam line (duct pressure too high, steam line too long or kinked), causing water loss via lling cup.
Leakage in the water system. Inspect water system and seal if
Humidity demand has decreased too
fast.
Drain valve defective. Inspect drain valve, replace if nec-
Drain screen in the drain outlet of the steam cylinder clogged.
Water conductivity too high for this
type of steam cylinder.
Drain valve defective. Inspect drain valve, replace if nec-
Drain screen in the drain outlet of the steam cylinder clogged.
Water conductivity too high for this
type of steam cylinder.
Main contactor jammed in activated
position.
Foaming in steam cylinder. Drain steam cylinder via drain key
Mineral deposits and/or electrodes
spent.
Maximum operating hours of the steam cylinder reached.
steam cylinder active.
active.
Inspect water supply (lter, water pip­ing, etc.), check/open shutoff valve, check water pressure.
valve, if applicable clean strainer insert or replace inlet valve.
Check duct pressure, inspect steam installation. If applicable install pres­sure compensation kit (see options).
necessary.
Automatic adaptation of the operat­ing point.
essary.
Clean drain screen (see chapter 6.3.2 and 6.4) or replace steam cylinder.
Select correct steam cylinder type.
essary.
Clean drain screen (see chapter 6.3.2 and 6.4) or replace steam cylinder.
Select correct steam cylinder type.
Inspect main contactor, replace if
necessary.
(several times, if necessary). Check quality of the supply water.
Replace steam cylinder.
Important: After the replacement of the steam cylinder, reset the main­tenance counter (see chapter 6.6).
Replace steam cylinder.
Important: After the replacement of the steam cylinder, reset the main­tenance counter (see chapter 6.6).
No measures must be taken.
No measures must be taken.
60
7.3 Notes on fault elimination
DANGER! Danger of electric hazard!
For the elimination of faults set the steam humidier out of operation as described in chapter 5.5, separate the unit from the mains and secure
it against inadvertent power-up.
The elimination of faults must be carried out by qualied and well trained professionals only. Malfunctions relating to the electrical installation (e.g. replacement of fuses) must be repaired by authorized personnel or by your Nordmann representa­tive’s service technician only.
Repair work and the replacement of faulty components must be carried out by your Nordmann representative’s service technician only!
7.4 Resetting the error indication (red LED lights)
To reset the error indication:
Disconnect the steam air humidier from the mains. Wait approx. 5 seconds, then reconnect the unit to the mains.
Note: If the fault has not been eliminated, the error indication reappears after a short while.
61
8 Taking out of service/Disposal
8.1 Taking out of service
If the Nordmann ES4 4 must be replaced or if the humidication system is not needed any more, proceed as follows:
1. Take the unit out of operation as described in chapter 5.5.
2. Have the unit (and all other system components, if necessary) unmounted by a qualied service technician.
8.2 Disposal/Recycling
Dismantled components must be disposed of and/or recycled according to the local regulations. In case of doubt please contact your Nordmann supplier.
62
9 Product specications
9.1 Technical data
Heating voltage
Steam capacity 4 kg/h
nominal power
Max.
Control voltage
Operating conditions
Admissible water pressure
Water quality Untreated drinking water
Admissible water temperature
Admissible ambient temperature
Admissible ambient humidity
Admissible back pressure in steam hose
Type of protection
Conformity
Dimensionen/Gewichte
Housing (WxHxD)
Water supply connector G 3/4" (male thread)
Water drain connector ø 22 mm
Steam connector ø 22 mm
Net weight
Operating weight
Equipment
Steam cylinder type
Accessories
Filter valve
Steam distribution pipe DV41...
Steam distributor
Steam distributor
Steam hose
EcoTherm insulation hose ECT22
Condensate hose
Duct humidistat
Room humidistat
Nordmann ES4 4 230V1
230V/1~/50..60Hz
3.1 kW
230V/1~/50..60Hz
1...10 bar
with a conductivity of 125...1250 µS/cm
1...40 °C
1...40 °C
max. 75% rh (noncondensing)
-0.8 kPa...0.8 kPa
IP 20
CE, VDE
285 mm x 430 mm x 205 mm
8 kg
13 kg
RD 422
Z261
DSS22
W22
DS22
KS10
HBN
HSN
63
9.2 Unit dimensions
Nordmann ES4 4 (dimensions in mm)
147
205
140
36
G 3/4"
430
69
101
285
ø30
80
175
75 130
35
335
49
64
Notes
65
Notes
© Nordmann Engineering Ltd., Printed in Switzerland
Technical modifications reserved