NORD TI043278910340 User Manual

Technical Information
CONNECTION KIT HTL ENCODER WK 4/2/4*680 OHM Part No. 278910340
Application:
Technical features / Parameters / Data:
Version Series terminals
Mounting Mounting on snap-on DIN rail TS 35
Mounting width 38.5 mm
Electrical connection Screw terminals
Connection cross-section 20-10 AWG (0.5mm² - 4mm² fine-wire / - 6mm² single wire)
Screw tightening torque 0.5 Nm
Control voltage 10 … 30V DC (from frequency inverter or external voltage source)
Schematic circuit diagram, - electrical connection:
(Example of terminal designations for frequency inverter SK 520E)
FI
TTL signal terminals
*according to FI version:
HTL encoder
VO = 15 V / 24V DC Terminal: 42 / 44
TI043_278910340_V1_0_GB.doc
1/2
Connections:
The electrical connection of the encoder and the frequency inverter is via screw terminals according to the table (see illustration above).
Function Wire colour: HTL
encoder
Supply voltage 10 - 30V DC brown / green 1 42 (VO 15VDC) or 44 (VO 24VDC)
0V / GND white / green 2 40 (GND)
Track A brown 3 51 (ENC A+)
Track A / green 4 52 (ENC A-)
Track B grey 5 53 (ENC B+)
Track B / pink 6 54 (ENC B-)
Terminal number Connection kit WK 4/2/4*680 Ohm
Terminal number, frequency inverter
Tools:
Slot-head screwdriver 0.6 x 3.5
Installation data:
Dimensions: [mm] H63 x W38.5 x D48 Mounting: Snap-on rail mounting (35mm snap-on DIN rail / TS35)
Commissioning information:
The connection kit is delivered as individual parts and must be correctly mounted on a snap-on DIN rail on site. The following mounting sequence (starting on the left) must be observed:
1. 2 x through terminal (WK4/U/VO)
2. 4 x fuse terminal (WK 4TKG/U/VO),
3. 1 x Cover plate (AP 4 TK/VO).
The 4 x enclosed diode plugs must be mounted on the insulated base terminals (snap-on). The enclosed labelling strips must also be attached.
The connection between the frequency inverter and the connection kit should be as short as possible. The use of a shielded connection cable is recommended. The shield must be well earthed at both ends. The shield of the encoder cable must also be connected to PE.
Scope of supply:
Item Name Name Number
1 Labelling strip (1 ... 6) 9705A/6/10B 1-10 horizontal 1
2 Diode plug 680 Ohm +/- 11% /0.6W 4
3 Through terminal WK 4/U/VO 2
4 Fuse terminal WK 4 TKG/U/VO 4
5 Cover plate AP 4 TK / VO 1
Getriebebau NORD GmbH & Co. KG
Tel.: +49 45 32 - 40 10 · Fax: +49 45 32 - 40 12 53 · www.nord.com
Rudolf-Diesel-Straße 1 · D-22941 Bargteheide
1.0 First edition 06.07.10 Rck
Version Change Datum Name Document Page
TI 043 278910340 2/2
Connection kit
WK 4/2/4*680 Ohm