NORD BU0590 User Manual

Page 1
NORDAC SK 200E Handbuch Sicherheitshinweise
U
y
GB
B
PROFINET Bus module
BU 0590 GB-0312 Subject to technical amendments 1
for NORD frequenc
inverters SK 5xxE
Page 2
PROFINET bus module for NORD frequency inverters SK 5xxE Safety information
N O R D Frequency inverters
Safety and operating instructions for drive power converters
(as per: Low Voltage Directive 2006/95/EEC )
1. General
During operation, drive power converters may, depending on their protection class, have live, bare, moving or rotating parts or hot surfaces.
Unauthorised removal of covers, improper use, incorrect installation or operation causes a risk of serious personal injury or material damage.
Further information can be found in this documentation.
All transportation, installation, initialisation and maintenance work must be carried out by qualified personnel (compliant with IEC 364, CENELEC HD 384, DIN VDE 0100, IEC 664 or DIN VDE 0110, and national accident prevention regulations).
For the purposes of these basic safety instructions, qualified personnel are persons who are familiar with the assembly, installation, commissioning and operation of this product and who have the relevant qualifications for their work.
2. Proper use in Europe
Drive power converters are components intended for installation in electrical systems or machines.
When installed in machines, the drive power converter cannot be commissioned (i.e. commencement of the proper use) until it has been ensured that the machine meets the provisions of the EC Directive 2006/42/EEC (machine directive); EN 60204 must also be complied with.
Commissioning (i.e. implementation of the proper use) is only permitted when the EMC directive (2004/108/EEC) is complied with.
CE-labelled drive power converters meet the requirements of the Low Voltage Directive 2006/95/EEC. The harmonised standards for drive power converters listed in the declaration of conformity are used.
Technical data and information for connection conditions can be found on the rating plate and in the documentation, and must be complied with.
The drive power converters may only be used for safety functions which are described and explicitly approved.
3. Transport, storage
Information regarding transport, storage and correct handling must be complied with.
4. Installation
The installation and cooling of the equipment must be implemented according to the regulations in the corresponding documentation.
The drive power converter must be protected against impermissible loads. Especially during transport and handling, components must not be deformed and/or insulation distances must not be changed. Touching of electronic components and contacts must be avoided.
Drive power converters have electrostatically sensitive components, which can be easily damaged by incorrect handling. Electrical components must not be mechanically damaged or destroyed (this may cause a health hazard!).
5. Electrical connection
When working on live drive power converters, the applicable national accident prevention regulations must be complied with (e.g. VBG A3, formerly VBG 4).
The electrical installation must be implemented according to the applicable regulations (e.g. cable cross-section, fuses, ground lead connections). Further instructions can be found in the documentation.
Information about EMC-compliant installation – such as shielding, earthing, location of filters and installation of cables can be found in the drive power converter documentation. These instructions must be complied with even with CE marked drive power converters. Compliance with the limiting values specified in the EMC regulations is the responsibility of the manufacturer of the system or machine.
6. operation
Where necessary, systems where drive power converters are installed must be equipped with additional monitoring and protective equipment according to the applicable safety requirements, e.g. legislation concerning technical equipment, accident prevention regulations, etc.
The parameterisation and configuration of the drive power converter must be selected so that no hazards can occur.
All covers must be kept closed during operation.
7. Maintenance and repairs
After the drive power converter is disconnected from the power supply, live equipment components and power connections should not be touched immediately, because of possible charged capacitors. Observe the applicable information signs located on the drive power converter.
Further information can be found in this documentation.
These safety instructions must be kept in a safe place!
2 Subject to technical amendments BU 0590 GB-0312
Page 3
PROFINET bus module for NORD frequency inverters SK 5xxE About this document
Documentation
Designation: BU 0590 GB
Part No.: 607 59 02
Device series: SK TU3-PNT (PROFINET® - Bus module) for SK 5xxE (entire series)
Version list
Designation of previous versions Software
BU 0590 GB, January 2012 Part No. 607 5901 / 0312
Publisher
NOTE
Remarks
Version
V 1.0 R4 First issue
Getriebebau NORD GmbH & Co. KG
Rudolf- Diesel- Str. 1 D-22941 Bargteheide Germany ### http://www.nord.com/
Tel.: +49 (0) 45 32 / 401-0 Fax +49 (0) 45 32 / 401-555
This supplementary operating manual is only valid in conjunction with the operating manual supplied for the respective frequency inverter (Manual BU0500).
Intended use of the frequency inverter
The compliance with the operating instructions is necessary for fault-free operation and the acceptance of possible warranty claims. These operating instructions must be read
before working with the device!
These operating instructions contain important information about servicing. They must therefore be kept close to the device.
The Ethernet module can only be used for the defined frequency inverter series (SK500E). The use of this module with other devices is not permitted and can lead to their destruction.
The Ethernet module and the associated frequency inverter are devices for fixed installation in control cabinets. All details regarding technical data and permissible conditions at the installation site must be complied with.
Commissioning (implementation of the intended use) is not permitted until it has been ensured that the machine complies with the EMC directive 2004/108/EEC and that the conformity of the end product meets the machine directive 2006/42/EEC (note EN 60204).
Getriebebau NORD GmbH & Co. KG, 2012
BU 0590 GB-0312 Subject to technical amendments 3
Page 4
PROFINET bus module for NORD frequency inverters SK 5xxE
1 INTRODUCTION................................................................................................................. ..... 6
1.1 General information ............................................................................................. 6
1.2 The bus system ................................................................................................... 6
1.3 Delivery................................................................................................................ 7
1.4 Scope of supply ................................................................................................... 7
1.5 Certifications........................................................................................................ 7
1.5.1 European EMC Directive ..........................................................................................7
1.5.2 RoHS compliance ..................................................................................................... 7
1.6 Identification System ........................................................................................... 7
2 MODULES................................................................................................................................ 8
2.1 SK 5xxE frequency inverters ............................................................................... 8
2.2 PROFINET - BUS Module................................................................................... 9
2.2.1 Mounting................................................................................................................... 9
2.2.2 Technical data ........................................................................................................ 10
2.2.3 Connections............................................................................................................ 10
2.2.4 Status display via LED............................................................................................ 11
3 COMMISSIONING.................................................................................................................. 13
3.1 Cabling............................................................................................................... 13
3.1.1 Topology................................................................................................................. 13
3.1.2 EMC........................................................................................................................ 13
3.2 Commissioning the bus module ........................................................................ 14
3.2.1 Connecting the bus module ....................................................................................14
3.2.2 Parameter settings of the frequency inverter .......................................................... 14
3.3 Configuration in the Bus system (example SIMATIC Manager)........................ 15
4 COMMUNICATION................................................................................................................ 17
4.1 Process data...................................................................................................... 17
4.1.1 Process data structure............................................................................................ 17
4.1.2 Control word ...........................................................................................................19
4.1.3 Status word............................................................................................................. 20
4.1.4 FI Status Machine................................................................................................... 21
4.1.5 Setpoint and actual values...................................................................................... 23
4.1.6 Example for switching the frequency inverter on and off ........................................ 24
4.1.7 Timeout monitoring ................................................................................................. 24
4.2 Parameter transfer............................................................................................. 25
4.2.1 Function of PROFINET Records............................................................................. 25
4.2.2 Data records ...........................................................................................................26
4.2.3 Data format............................................................................................................. 27
4.2.4 Examples................................................................................................................ 30
5 PARAMETER......................................................................................................................... 34
5.1 Parametersiation of PROFINET bus module SK TU3-PNT .............................. 34
5.1.1 BUS module standard parameters (P15x) ..............................................................34
5.1.2 Parameters specific to PROFINET BUS modules (P16x)....................................... 34
5.1.3 BUS module information parameters, general (P17x) ............................................ 35
5.1.4 BUS module information parameters, bus-specific (P18x) ..................................... 37
5.2 SK5xxE inverter parameters (selection)............................................................ 38
5.2.1 Extra functions........................................................................................................ 38
5.2.2 Information parameters........................................................................................... 41
6 ERROR MONITORING AND ERROR MESSAGES.............................................................. 44
6.1 PROFINET error monitoring.............................................................................. 44
6.2 Error messages in the Bus module SK TU3-PNT ............................................. 44
6.3 Error messages in the SK 5xxE frequency inverter........................................... 44
4 Subject to technical amendments BU 0590 GB-0312
Page 5
Table of Contents
7 LISTS / INDEX ........................................................................................................................45
7.1 Abbreviations......................................................................................................45
7.2 Keyword Index....................................................................................................45
7.3 Figures................................................................................................................46
7.4 Tables.................................................................................................................46
7.5 Keyword index....................................................................................................47
BU 0590 GB-0312 Subject to technical amendments 5
Page 6
PROFINET bus module for NORD frequency inverters SK 5xxE
1 Introduction
1.1 General information
Modern field bus systems, microcontrollers and communication networks have had a great influence on automation systems and have resulted in greater flexibility, availability and ultimately, also a reduction in costs.
The widespread use of PC-based control only became possible with the availability of field bus systems. With increasing control unit performance, the classic field bus ultimately became the limiting criterion for the entire system. It was therefore an obvious step to adapt Ethernet technology, which provides high rates of data transmission in IT applications, to the field of automation.
1.2 The bus system
As a physical transfer medium, PROFINET® transfers many years of experience with PROFIBUS-DP-V1 to Fast Ethernet. In addition to the conventional open Ethernet communication TCP/IP it enables real time communication of process data. PROFINET defines three communication classes, which provide different levels of efficiency and functionality:
TCP/IP or UDP/IP communication without real time capability  Real time communication for process data (>1ms) RT Isochronous real time communication for synchronised process data IRT
Features of the SK TU3-PNT
PROFINET IO real time communication (RT=Real Time and IRT=Isochronous Real Time)
Automatic address assignment via the IO controller using DCP (discovery configuration protocol)
Switched Ethernet
Autonegotiation (negotiation of transfer parameters)
Autocrossover (Transmission and reception cables crossed over in the switch)
Conforms with Class B, C
Performance
100Mbit/s data communication
Full duplex transmission
Transmission of a maximum of five setpoints or actual values possible
6 Subject to technical amendments BU 0590 GB-0312
Page 7
1 Introduction
1.3 Delivery
Check the equipment immediately after delivery/unpacking for transport damage such as deformation or
loose parts.
If there is any damage, contact the carrier immediately and carry out a thorough assessment.
Important! This also applies even if the packaging is undamaged.
1.4 Scope of supply
SK TU3-PNT* PROFINET Bus module for SK 500E frequency inverters IP20
*incl. screw for optional fixing to the FI
1.5 Certifications
1.5.1 European EMC Directive
If NORD frequency inverters or their options are installed according to the recommendations in this instruction manual, it meets all EMC directive requirements, as per the EMC product standard for motor-operated systems EN 61800-3.
1.5.2 RoHS compliance
The bus options described here are designed to be RoHS compliant according to Directive 2002/95/EEC
1.6 Identification System
SK TU3-PNT
Bus system: AS1 = AS-Interface, CAN = CAN, CAO = CANo pen,
ECT = EtherCAT®, PNT = PROFINET ®, etc. Device series: SK TU1 / SK TU2 / SK TU3 / SK TU4
Fig. 1 Type Codes
BU 0590 GB-0312 Subject to technical amendments 7
Page 8
PROFINET bus module for NORD frequency inverters SK 5xxE
2 Modules
2.1 SK 5xxE frequency inverters
By the use of various modules for display, control and parameterisation, the SK 5xxE can be easily adapted to various requirements.
Alphanumerical display and operating modules can be used for simple commissioning. For more complex tasks, various connections to a PC or an automation system can be selected.
The technology unit (Technology Unit, SK TU3-…) is connected externally to the front of the frequency inverter and is therefore easy to access and replace at any time.
In the delivery condition (without technology unit) 2 LEDs (green/red) are visible externally. These indicate the actual device status.
The green LED indicates that the mains voltage is present and operational, while a flashing code that increases in speed shows the degree of overload at the frequency inverter output.
The red LED signals actual error by flashing with a frequency which corresponds to the number code of the error (Manual BU 0500 Section 6).
LED
red/green
Fig. 2 Frequency inverters with SK TU3- optional modules (selection)
WARNING
Modules should not be inserted or removed unless the device is free of voltage. The slots may only be used for the intended modules.
Installation of a technology unit separate from the frequency inverter is not possible. It must be connected directly to the frequency inverter.
NOTE
8 Subject to technical amendments BU 0590 GB-0312
Page 9
2.2 PROFINET - BUS Module
2.2.1 Mounting
The technology units must be installed as follows:
1. Switch off the mains voltage (frequency inverter), observe the waiting period.
2. Push the control terminals cover down slightly or remove.
3. Remove the blank cover by pressing the release on the lower edge and pulling off with an upward turning movement. If necessary, the fixing screw next to the release must be removed.
4. Hook the technology unit onto the upper edge slots and press in lightly until engaged. Ensure full contact with the connector strip and fasten with the screws if necessary (separate packet).
5. Close the control terminal cover again.
2 Modules
3
2 „press“
1
4
Similar to illustration
Fig. 3 Installation of the Technology Unit (optional module)
Further detailed information can be found in the device manual BU 0500.
- www.nord.com
BU 0590 GB-0312 Subject to technical amendments 9
Page 10
PROFINET bus module for NORD frequency inverters SK 5xxE
2.2.2 Technical data
Specification
PROFINET IO
Bus connection Bus termination
Cable Max. cable length Supply voltage
Status display Device address
PE Shield
Table 1 Electrical specifications of the SK TU3-PNT
Max. baud rate 100 MBaud
Electrical isolation 500V
2 RJ45
Performed automatically by the SK TU3-… Technology Unit
Ethernet CAT-5 or better
100m between two Ethernet bus modules
24V 20%, current consumption 150mA
Reverse polarity protected
4 LEDs
via the PROFINET IO controller or parameterisation
Connection via plug pins under the 24V supply
The shields of the two RJ sockets are connected together and connected to PE with a high resistance and capacitance. If several technology units are adjacent to each other, only one board needs to be connected to the PE.
eff
2.2.3 Connections
Name Name
45 46
Table 2 Power supply connections
Signal Name RJ45 Pin
TX+
TX­RX+ RX-
Table 3 RJ45 socket connections
+24V
GND
Transmission Data + 1
Transmission Data - 2
Receive Data +
Receive Data -
SK TU3-…
24V
GND
PE
3
6
Pin 8
Pin 1
10 Subject to technical amendments BU 0590 GB-0312
Page 11
2.2.4 Status display via LED
RUN
DS DE
L / A*
2 Modules
BF
*L / A = Link / Active: on all RJ45 sockets
Fig. 4 Location and designation of the LEDs
RUN
Green LED
Off
Flashing
On
Table 4 Description of the RUN LED (Ethernet Status)
Init Device switched off or initialisation
Waiting for AR
AR established
State Meaning
ERR
Red LED
Off
Double-flashing
Cycle 2 x 0.25 sec
Pause 1s
On
Table 5 Description of the ERR LED (Ethernet errors)
No error PROFINET IO functioning normally
Timeout
Ethernet error, no mains TU3-PNT not connected to any Ethernet participant
State Meaning
- No parameter communication
- No process data communication
- Parameter communication active
- Process data communication active
The IO controller monitoring has detected an error (see parameter P151 or P513)
L
Green LED
Off Off
Flashing
Cycle 0.50 sec
On Off
On On / Flashing
Table 6 Description of the link / Activity LEDs
BU 0590 GB-0312 Subject to technical amendments 11
A
Yellow LED
Flashing
Cycle 0.50 sec
Meaning
Port (RJ45 socket) is not connected to the PROFINET network
Identification signal of the station if a flashing test is performed in the planning tool
Port (RJ45 socket is connected to the PROFINET network, but there is no exchange of data
Data exchange via PROFINET active
Page 12
PROFINET bus module for NORD frequency inverters SK 5xxE
DS
Green LED
Off Off Off
Flashing
Cycle 0.50 sec
On
On Off
Table 7 Description of the DS and DE LEDs
DE
Red LED
Flashing 1...7x
Cycle 0.25sec
Pause 1s
Off
Flashing 1x
Cycle 0.25sec
Meaning
The technology unit does not have a power supply
The technology unit has a fatal system error
Technology unit OK but no FI (frequency inverter) detected
Causes The FI has no power supply or the technology unit is not correctly plugged in
The FI is in an error condition
Technology unit OK and FI detected
12 Subject to technical amendments BU 0590 GB-0312
Page 13
3 Commissioning
3 Commissioning
3.1 Cabling
3.1.1 Topology
The SK TU3-PNT PROFINET IO modules can be connected to each other in star, tree, linear or ring topologies.
PROFINET IO Controller
Fig. 5: Example of PROFINET IO linear topology
TU3-PNT TU3-PNT TU3-PNT
TU3-PNT
PROFINET IO Controller
Switch TU3-PNT
TU3-PNT
Fig. 6: Example of PROFINET IO star topology with switch
3.1.2 EMC
If EMC measures are not in place, high-frequency interference which is mainly caused by switching processes or lightning often causes electronic components in the bus participants to be faulty and error-free operation can no longer be ensured.
Correct laying of the bus cable dampens the electrical influences which may occur in an industrial environment. The following points must be observed:
Implement long connections between bus participants by the shortest possible distances.
Only use plugs with a metal housing.
For the production of bus cables lay the shielding on as wide an area of the plug as possible.
With the parallel installation of bus cables, a minimum distance of 20 cm from should be maintained from
other cables carrying a voltage greater than 60V. In particular, this must be observed for cables to motors or chopper resistors. This applies to lines laid both inside and outside of control cabinets.
The minimum distances for parallel installation may be reduced by shielding cables carrying voltage or
by means of earthed metal dividers in the cable ducts.
Connect SK TU3- Ethernet module to the PE (Connection via the plug pin next to the 24V supply).
BU 0590 GB-0312 Subject to technical amendments 13
Page 14
PROFINET bus module for NORD frequency inverters SK 5xxE
3.2 Commissioning the bus module
3.2.1 Connecting the bus module
Connect the bus module to the PE via the plug pins
Connect the 24V supply via the plug-in terminal. Note the consumption of each module
(Technical Data)
Connect the Ethernet cable
Bus direction PROFINET
Incoming cable
(from master / controller)
Outgoing cable Left or right RJ45 socket
Both RJ45 sockets of the PROFINET module are internally connected via a switch.
Table 8 Bus cable connections
Left or right RJ45 socket
Labelled "1" or "2"
Labelled "1" or "2"
If the bus module is the last participant, the RJ45 socket remains open in the outgoing direction. The
bus connection is performed automatically.
ATTENTION
Each bus module requires a separate PE connection via the plug pin. Otherwise, interference-free operation of the bus module cannot be guaranteed.
3.2.2 Parameter settings of the frequency inverter
The following settings must be made on the frequency inverter (SK 5xxE):
Control via Ethernet TU P509 = "8"
Setpoint via Ethernet TU P510 = "8" or "0" if P509 = "8"
Setting of setpoints via P546, P547 and P548 (SK 500E … SK 535E)
P546 [-01] … [-05] (SK 540E and above)
Setting of actual values via P543, P544 and P545 (SK 500E … SK 535E)
P543 [-01] … [-05] (SK 540E and above)
For a detailed description of the parameters, please refer to the frequency inverter operating manual (BU 0500).
The parameters can be set with NORD parameterisation tools (e.g. NORD CON, SimpleBox) or via the bus master / controller.
14 Subject to technical amendments BU 0590 GB-0312
Page 15
3 Commissioning
3.3 Configuration in the Bus system (example SIMATIC Manager)
In order to carry out planning with the SK TU3-PNT, first of all the GSDML file "GSDML-V2.2-NORD
DRIVESYSTEMS-TU3PNT-20110606.xml" must be installed in the SIMATIC Manager. Select the relevant file in the Hardware Configurator.
The current files for SK 5xxE series frequency inverters can be found on the NORD homepage under
- Documentation - Software - NORDAC Options.
NORD
Fig. 7 Installation of the GSDML file in SIMATIC Manager
After this, the SK TU3-PNT from NORD DRIVESYSTEMS is can then be found in the hardware catalogue of the SIMATIC Hardware Manager and can then be entered into the PROFINET system.
BU 0590 GB-0312 Subject to technical amendments 15
Page 16
PROFINET bus module for NORD frequency inverters SK 5xxE
Fig. 8 Hardware Catalogue: Module selection and specification of data format
The data format of the cyclical IO data is specified via the hardware catalogue. Up to 12 Bytes (=PPO6) are transferred to the frequency inverter in a single cycle.
Fig. 9 Module properties
Properties such as the device number, device name and IP address are entered in the Properties dialogue of the SIMATIC Manager.
16 Subject to technical amendments BU 0590 GB-0312
Page 17
4 Communication
4 Communication
4.1 Process data
Control words and setpoints are transferred from the bus master / controller to the SK TU3-…bus module as process data and in return, the status word and actual values are sent to the bus master / controller from the FI. Transfer is carried out cyclically. The bus master / controller can access these process values directly, as they are stored in the I/O area.
The length and structure of the process data is specified via the PPO types during the planning of the PROFINET network.
The allocation of the values transferred in the setpoint/actual value area of the FI is made via the parameters P543 to P548 or P543 [-01]…[-05].
4.1.1 Process data structure
The structure of the process data is defined by the PPO type.
4.1.1.1 Pure process data communication
Direction of
transmission
1st word 2nd word
... to SK TU3 Control word Setpoint 1
... from the SK TU3 Status word Actual value 1
Table 9: PPO 3
Transmitted data
( 4 Byte )
Direction of
transmission
1st word 2nd word 3rd word 4th word
... to SK TU3 Control word Setpoint 1 Setpoint 2 Setpoint 3
... from the SK TU3 Status word Actual value 1 Actual value 2 Actual value 3
Table 10: PPO 4
Transmitted data
( 8 Byte )
Direction of
transmission
1st word 2nd word 3rd word 4th word 5th word 6th word
Transmitted data
( 12 Byte )
... to SK TU3 Control word Setpoint 1 Setpoint 2 Setpoint 3 Setpoint 4 Setpoint 5
... from the SK TU3 Status word Actual value 1 Actual value 2 Actual value 3 Actual value 4 Actual value 5
Table 11: PPO 6
BU 0590 GB-0312 Subject to technical amendments 17
Page 18
PROFINET bus module for NORD frequency inverters SK 5xxE
4.1.1.2 Process and parameter data communication
The exchange of process and parameter data is possible by selecting the PPO types 1 or 2.
Direction of
transmission
1st word 2nd word 3rd word 4th word 5th word 6th word
... to SK TU3 Parameter
number and order label
... from the SK TU3 Parameter
number and order label
Table 12: PPO 1
Direction of
transmission
1st word 2nd word 3rd word 4th word
... to SK TU3 Parameter number and
order label
... from the SK TU3 Parameter number and
order label
Transmitted data
( 12 Byte )
Parameter index
Parameter index
Parameter value HI
Parameter value HI
Parameter value LO
Parameter value LO
Control word Setpoint 1
Status word Actual value 1
Transmitted data
( 16 Byte )
Parameter index Parameter value HI Parameter value LO
Parameter index Parameter value HI Parameter value LO
Direction of
transmission
5th word 6th word 7th word 8th word
... to SK TU3 Control word Setpoint 1 Setpoint 2 Setpoint 3
... from the SK TU3 Status word Actual value 1 Actual value 2 Actual value 3
Table 13: PPO 2
Transmitted data
( 16 Byte )
18 Subject to technical amendments BU 0590 GB-0312
Page 19
4 Communication
4.1.2 Control word
Bit Value Meaning Remarks
0 0 OFF 1 Reverse with the brake ramp, with disconnection from supply at f=0Hz 1 ON Ready for operation
1 0 OFF 2
1 Operating condition OFF 2 is cancelled
2 0 OFF 3
1 Operating condition OFF 3 is cancelled
3 0 Disable operation
1 Enable operation The output voltage is enabled; ramp to the existing setpoint
4 0 Lock ramp generator
1 Operating condition Enable ramp generator
5 0 Stop ramp generator
1 Enable ramp generator Enable setpoint on ramp generator
6 0 Disable setpoint Selected setpoint value is set to zero on the ramp generator. 1 Enable setpoint Selected ramp generator setpoint is activated.
7 0 No acknowledgement With the switch from 0 to 1, errors which are no longer active are acknowledged. 1 Acknowledge
8 0 1 Bit 8 active
9 0 1 Bit 9 active
10 0 PZD invalid The transmitted process data is invalid. 1 PZD valid Valid process data is transferred from the master.
11 0 1
12 0 1
13 0/1 Reserved
14 0/1
15 0/1
Rotational direction: right
Rotational direction: left
Bit 0 to switch parameter set
Bit 1 to switch parameter set
Cut off voltage; the inverter output voltage is switched off; the FI enters a state where switching on is disabled.
Quick stop with programmed quick stop time; with disconnection from supply at f=0Hz; the FI switches to starting disabled condition.
Cut off voltage; the inverter output voltage is switched off; the FI enters a state where switching on is enabled.
Ramp generator is set to zero; no disconnection from supply at f=0Hz; FI remains in the operation enabled state.
The setpoint currently provided by the ramp generator is "frozen" (frequency is maintained).
Note: When a digital input has been programmed for the "ack.fault" function, this bit must not permanently be set to 1 via the bus (otherwise, edge evaluation would be prevented).
Bus bit 8 from the control word is set. Only for SK 2xxE and SK 5xxE. For further details of the function please refer to parameter (P480).
Bus bit 9 from the control word is set. Only for SK 2xxE and SK 5xxE. For further details of the function please refer to parameter (P480).
Note: If setpoints only are transferred via the bus (setting: interface), this Bit must
be set so that the setpoint transferred is valid.
Rotation right (priority) is on.
Rotation left is on.
00 = Parameter set 1 01 = Parameter set 2
10 = Parameter set 3 11 = Parameter set 4
Table 14 Meaning of individual control word bits
BU 0590 GB-0312 Subject to technical amendments 19
Page 20
PROFINET bus module for NORD frequency inverters SK 5xxE
4.1.3 Status word
Bit Value Meaning Remarks
0 0 Not ready to start 1 Ready to start Initialisation completed, charging relay ON, output voltage disabled
1 0 Not ready for operation
1 Ready for operation
2 0 Operation disabled 1 Operation enabled The output voltage is enabled; ramp to the existing setpoint
3 0 No fault 1 Fault
4 0 OFF 2 OFF2 command applied 1 No OFF 2
5 0 OFF 3 OFF3 command applied 1 No OFF 3
6 0 Starting not disabled 1 Starting disabled Switches first to OFF1, then to ready-to-start status
7 0 No warning 1 Warning Drive operation continues, no acknowledgement necessary
8 0 Actual value not O.K.
1 Actual value O.K. Actual value matches required setpoint (setpoint has been reached)
9 0 Local guidance Guidance on local device has been activated 1 Guidance requested The master has been requested to assume guidance.
10 0 1 Bit 10 active
11 0 1
12 0 1
13 0 1 Bit 13 active
14 0/1
15 0/1
Rotational direction: right
Rotational direction: left
Currently active parameter set 0
Currently active parameter set 1
Causes: No command has been activated, fault is signaled, OFF2 or OFF3 activated, starting disabled state activated
ON command activated, no faults present. The inverter can be started with the command ENABLE OPERATION
Drive fault resulting in stoppage; this state is changed to starting disabled after the fault has been successfully acknowledged
Actual value does not match the setpoint (with posicon: failure to reach setpoint
position)
(with posicon: setpoint has been reached)
Bus bit 10 from the status word is set. For further details of function, please refer to parameter P481.
Inverter output voltage is turning right
Inverter output voltage is turning left
Bus bit 13 from the status word is set. For further details of function, please refer to parameter P481.
00 = Parameter set 1 01 = Parameter set 2
10 = Parameter set 3 11 = Parameter set 4
Table 15 Meaning of individual status word bits
20 Subject to technical amendments BU 0590 GB-0312
Page 21
4 Communication
4.1.4 FI Status Machine
The frequency inverter passes through a status machine. The changes between various states are triggered by the respective control commands in the process data control word. The actual status is returned in the process data status word.
After switching on, the inverter is in switch-on disabled status. This status can only be ended by
transmitting the “Shut down (Off 1)” command.
The answer to a master telegram normally does not yet contain a reaction to the control command. The controller has to check the answers from the slaves as to whether the control command has been carried out.
Status Bit 6
Switch-on
disable
Not ready to start 0 X X 0 0 0 0
Starting disabled 1 X X 0 0 0 0
Ready to start 0 1 1 0 0 0 1
Activated 0 1 1 0 0 1 1
Operation enabled 0 1 1 0 1 1 1
Fault 0 X X 1 0 0 0
Error active 0 X X 1 1 1 1
Emergency stop active
0 0 1 0 1 1 1
Bit 5
Emergency
stop
Bit 4
Disable voltage
Bit 3
Fault
Bit 2
Operation
enabled
Bit 1
Standby
Bit 0
Ready for switch-on
Table 16 Codes for FI status
BU 0590 GB-0312 Subject to technical amendments 21
Page 22
PROFINET bus module for NORD frequency inverters SK 5xxE
Internal status machi ne
1
Not on standby
34568
Sw itching on the inverter
5
6
Emergency stop
active
Bit2 = 0: Emer gency stop
Bit1 = 0: Disable voltage
v Bit2 = 0: Emergency stop
2
Sw itch-on
3
4
disabled
Ready for sw itch-on
Ac tivated
45
Bit0 = 0: Shut dow n
5
5
Bit 3 = 0: Disable operation Bit0 = 1: Sw itch on
3
2
23
Loading relay applied
Bit0 = 0: Shut dow n & Bit1 = 1: Enable voltage & Bit2 = 1: Enable pulses (xxxx x1xx xxxx x110)
2
From any device status
7
Er ror reaction
active
8
Error
f = 0 reached (emergency stop complete)
Er r o r
Er ror reaction complete
Bit3 = 1: Enable operation
&Bit0 = 1: Sw itch on
364
2
Control bits
0. Standby / Shut dow n
1. Dis able / enable voltage
2. Enable pulses / emergency s top
3. Dis able / enable operation
4. Betriebsbedingung / HLG s perren
5. Enable / stop RUE
6. Enable / disable setpoint
7. Er ror acknow ledgement (0
10. Control data valid / invalid
11. Direction of rotation clockwise
12. Direction of rotation anticlockwise
14. Parameter set Bit 0
15. Parameter set Bit 1
1)
Fig. 10 Diagram of the FI Status Machine
Bit3 = 1: Enable operation
5
Operation
enabled
Priority of control commands:
1. Dis able / enable voltage
2. Emergency stop
3. Shut dow n
4. Enable operation
5. Sw itch on
6. Dis able operation
7. Reset error
Bit4 = 0: Move dow n emergenc y s top ramp and
Bit5 = 0: Hold frequenc y
Bit6 = 0: Setpoint = 0%
2
remain in 'Operation enabled'
Coding of status:
1: Bit 0 = 0 2: Bit 6 = 1 3: Bit 0 = 1 4: Bit 1 = 1 5: Bit 2 = 1 6: Bit 5 = 0 7: Bit 2 & Bit 3 = 1 8: Bit 3 = 1
Bit7 01
Er ror acknow ledgement
22 Subject to technical amendments BU 0590 GB-0312
Page 23
4 Communication
4.1.5 Setpoint and actual values
The meanings of setpoints are defined via the FI parameters P546 to P548 (SK 540E and above: P546[-01] … [-05]). For the actual values, this determination is made via the FI parameters P543 to P545 (SK 540E and above: P543[-01] … [-05]).
The transfer of setpoint and actual values is carried out by three different methods, which will be explained below.
Percentage transfer
The process value is transferred as a whole number with a value range of -32768 to 32767 (8000 hex to 7FFF hex). The value 16384 (4000 hex) is equal to 100%. The value -16384 (C000 hex) is equal to -100%.
For frequencies, the 100% value corresponds to the FI parameter "Maximum Frequency" (P105) and for currents, this is the FI parameter "Torque Current Limit" (P112) Frequencies and currents result from the following formulae.
105PValue
Frequency
Value = the 16Bit actual or setpoint value transmitted via Ethernet
16384
Current
16384
112PValue
Formula 1 Formation of 16Bit setpoint/actual value
Binary transmission
Inputs and outputs as well as Digital In bits and Bus Out bits are evaluated for each bit.
Transmission of positions
In the FI, positions have a value range of +/- 50000,000 rotations. A motor rotation can be divided into a maximum of 1000 steps. This scaling is independent of the encoder which is used.
The 32Bit value range is divided into a Low and a High word, so that 2 setpoint/actual values are required for transmission.
Direction of
transmission
1. word 2. word 3. word 4. word
... to SK TU3
... from the SK TU3
Table 17 Depiction of 32Bit setpoint/actual values
Control word 32Bit setpoint Setpoint 3 Status word Actual value 1 32Bit actual value
Transmitted data (8 Byte)
It is also possible to only transmit the Low component of the position. This results in a limited value range from +32,767 to -32,768 rotations. This value range can be extended with the aid of the gear ratio factor (P607 & P608). However, it must be noted that there is an according reduction in the resolution.
BU 0590 GB-0312 Subject to technical amendments 23
Page 24
PROFINET bus module for NORD frequency inverters SK 5xxE
4.1.6 Example for switching the frequency inverter on and off
In this example, a FI will be operated with a setpoint (setpoint frequency) and an actual value (actual frequency). The "Maximum Frequency" is 50Hz.
Parameter settings:
P105 = 500
P543 = 1
P546 = 1
Control word
- - - - - - 0000h 0000h
- - - - - - xx40h 0000h The mains voltage is switched on at the FI
047Eh 0000h xx31h 0000h FI is set to "Standby" status
047Fh
The FI is enabled, the motor is supplied with current and rotates with a frequency of 25Hz.
0047Eh
The FI is disabled again and the motor is without current.
047Fh
The FI is enabled, the motor is supplied with current and rotates with a frequency of 12.5Hz.
Setpoint 1 Status word Actual
value 1
2000h xx37h 2000h
2000h xx31h 0000h
1000h xx37h 1000h
Explanation
FI is set to "Operation enabled" status and controlled with a 50% setpoint.
FI is set to "Standby" status, the motor runs up its parameterised ramp to speed 0 and is switched off.
FI is set to "Operation enabled" status and controlled with a 25% setpoint.
Table 18 Example of setpoint specification
4.1.7 Timeout monitoring
The PROFINET data traffic can be monitored with a watchdog with the aid of the time set in parameter P513. If no further cyclical data is sent from the PROFINET IO controller, a module error is detected and set in the FI (E10.3).
Monitoring via the FI parameter P513 is also possible. This is triggered if the process data contact is interrupted or the process data is transferred with an invalid control word (Bit10 in control word = 0). This function is activated when the first valid process data telegram is received.
24 Subject to technical amendments BU 0590 GB-0312
Page 25
4 Communication
4.2 Parameter transfer
4.2.1 Function of PROFINET Records
The transfer of parameter data (Records) is performed acyclically. All parameters of the FI and the bus module can be accessed. For this the parameters of the SK TU3-PNT are assigned to Slot 2 and the parameters of the frequency inverter to Slot 3.
The illustration below describes the function of Records
IO Controller
Parameter
order
Parameter
response
PROFINET Record
Write Request
Slot 3
Write Response
Slot 3
Read Request
Slot 3
Read Response (-)
Slot 3
Read Request
Slot 3
Read Response (+)
Slot 3
IO Device
Parameter
order
Parameter
response
Fig. 11 Function of PROFINET Record
By means of a "Write Request" the data record is transferred to the IO device (SK TU3-PNT) as a
parameter order.
With "Write Response" the IO controller receives confirmation of the receipt of the message.
The IO controller requests a response from the SK TU3-PNT with "Read Request".
The SK TU3-PNT responds with a "Read Response (-)", if processing is not yet complete.
After processing of the parameter in the SK TU3-PNT the parameter order is concluded with the
transfer of the parameter response to the IO controller by means of "Read Response (+)".
BU 0590 GB-0312 Subject to technical amendments 25
Page 26
PROFINET bus module for NORD frequency inverters SK 5xxE
4.2.2 Data records
4.2.2.1 Data records 100 and 101
The data records are written to Slot 0. The number of the data record determines the relevant target device. For this:
DS 100  Access to the technology unit (parameter range 150…199)
DS 101 Access to the frequency inverter (parameter range 0 … 999, except 150…199)
NOTE
The inverter parameters are mapped in the range 1000 to 1999, i.e. 1000 must be added to the parameter number for parameterisation (e.g. (P508) - P1508).
Field Data size Explanation
Parameter number
and
Order label
Parameter index 2 Bytes Parameter sub-index (see Section 4.2.3.2)
Parameter value 4 Bytes New setting value (See Section 4.2.3.3).
2 Bytes FI or SK TU3 parameter
The parameter number is a 16 Bit value (+1000) and can be obtained from the relevant operating manual for the frequency inverter or technology unit.
The order label is added to the parameter number. (upper Nibble)
Table 19 Structure of data records 100 and 101
4.2.2.2 Data record 47
This data record is written to Slot 0 and is then assigned to the relevant device on the basis of the axis. The format is compliant withe the ProfiDrive profile.
Field Data size Explanation
Order reference 1 Byte The order reference is transferred from the IO controller and is used for the
definitive allocation of the SK TU3-PNT response
Order label 1 Byte Read / write parameter value etc. (see Section 4.2.3 )
Axis 1 Byte Access to SK TU3-PNT parameter or FI parameter
0 = SK TU3-PNT
1 = Frequency inverter
Parameter number 2 Bytes FI or SK TU3 parameter
The parameter number is a 16 Bit value (+1000) and can be obtained from the relevant operating manual for the frequency inverter or technology unit.
Parameter index 2 Bytes Parameter sub-index (see Section 4.2.3.2)
Parameter value 4 Bytes New setting value (See Section 4.2.3.3).
Table 20 Structure of data record 47
4.2.2.3 Transfer of data record via PPO 1 and PPO 2
PPO1 and PPO2 objects are supported in order to simplify the conversion of an existing PROFIBUS system to a PROFINET system. In addition to the cyclical IO data, there are also the acyclical parameter data (see Section 4.2.4.4).
26 Subject to technical amendments BU 0590 GB-0312
Page 27
4 Communication
4.2.3 Data format
4.2.3.1 Order label field
The following table lists all the orders which can be transferred from the PROFINET IO controller to the frequency inverter. The right-hand column contains the response, which is normally sent (response label positive). Only certain response labels are possible, depending on the order label. In case of error (AK
negative) the inverter will always supply the value 7 in the response label (AK) to the IO controller.
AK Function Response label positive
0 No order 0
1 Order parameter value 1 / 2
2 Change parameter value (word) 1
3 Change parameter value (double word) 2
4 Reserved -
5 Reserved -
6 Order parameter value (array) 4 / 5
7 8
9 Order the number of array elements 6
10 Reserved -
Table 21 Orders from the controller with the associated response label of the inverter
Change parameter value (array word) 4
Change parameter value (array double word) 5
The following table lists all the orders which can be transferred from the controller to the frequency inverter or the technology units. The right-hand column contains the response, which is normally sent (response label positive). Only certain response labels are possible, depending on the order label. In case of error (AK negative) the inverter always supplies the value 7 in the response label (AK) to the PROFINET IO controller.
AK Function Response label positive
11 Change parameter value (array double word)
without writing into EEPROM
12 Change parameter value (array word)
without writing into EEPROM
13 Change parameter value (double word)
without writing into EEPROM
5
4
2
14 Change parameter value (word)
without writing into EEPROM
Table 22 Orders from the controller with the associated response label of the inverter or technology unit
1
BU 0590 GB-0312 Subject to technical amendments 27
Page 28
PROFINET bus module for NORD frequency inverters SK 5xxE
AK Function
0 No response
1 Transfer parameter value (word)
2 Transfer parameter value (double word)
4 Transfer parameter value (array word)
5 Transfer parameter value (array double word)
7 Order cannot be executed (with error number in PWE2)
Table 23 Response labels - Meaning
In the response label "Order cannot be executed" (AK = 7), then an error message is added to the
parameter value (PWE2) of the inverter response. For the meanings of the values transferred, please refer
to the following table.
No. Meaning
0 Invalid parameter number
1 Parameter value cannot be changed
2 Lower or upper value limit exceeded
3 Incorrect sub-index
4 No array
5 Invalid data type (at present only for SK 700E)
6 Only resettable (only 0 may be written)
7 Description element cannot be changed
9 Description data not present
201 Invalid order element in the last order received
202 Internal response label cannot be depicted
Table 24 Response labels - Explanation of error numbers for response label = 7
NOTE
Both the order label and the response label are abbreviated as AK. Therefore, care must be taken when reading or interpreting the order processing description in this section.
28 Subject to technical amendments BU 0590 GB-0312
Page 29
4 Communication
4.2.3.2 Parameter index field
The structure and function of the parameter index depends on the type of parameter to be transferred. For values which depend on the parameter set, the parameter set can be selected via Bits 8 and 9 of the Index (0 = parameter set 1, 1 = parameter set 2,...).
If the parameter to be processed is also an array parameter, then the sub-index of the required parameter can additionally be accessed via Bit 10 to Bit 15 of the sub-index (0 = array element 1, 1 = array element 2,…):
Array element Parameter set Index
5 (000101
21 (010101
Table 25 Example: Address formation for array elements or parameters depending on parameter sets
) 2 (01
BIN
) 4 (11
BIN
) 15
BIN
) 57
BIN
= 0001 0101
HEX
= 0101 0111
HEX
BIN
BIN
If a parameter is not dependent on the parameter set, then Bit 8 -15 are used for the sub-index.
Please refer to the operating instructions for details of the structure of the individual parameters and which values may be called up.
If the sub-index is used, nos. 6, 7, 8 or 11, 12 must be used as the order label (see Section 4.2.3.1), in order for the sub-index to be effective.
4.2.3.3 Parameter value field
For each parameter, the transfer of the parameter value is always as a word (16 Bit) or double word (32 Bit) For negative values, the High bytes must be filled up with FF hex.
The parameter value is transferred as an integer value. For parameters with resolutions 0.1 or 0.01 the parameter value must be multiplied by the inverse of the resolution.
Example: A run-up time of 99.99 seconds is to be set.
99.99s  99.99 * 1 / 0.01 = 99.99 * 100 = 9999 Therefore the value 9999
= 270F
dec
must be transferred.
hex
BU 0590 GB-0312 Subject to technical amendments 29
Page 30
PROFINET bus module for NORD frequency inverters SK 5xxE
4.2.4 Examples
4.2.4.1 Reading of module parameter P170 Index 0 (actual error)
Data record 100 is used:
Field Data size Byte Date Explanation
Order label
2 Byte
+
Parameter number
Parameter index 2 Bytes 3
Parameter value 4 Bytes 5
2
4
6
7
8
01 h
+492 h
_________
1492 h
00 h
00 h
00 h
00 h
00 h
00 h
Read parameter value (see Section 4.2.3 )
+
Parameter number P170 (+1000) = 492 h
Parameter sub-index (see Section 4.2.3.2)
Setting value not set with read order
Table 26 Example telegram for reading parameter P170
S7 Code example:
CALL "WRREC" , DB53 WriteRequest REQ :=#bStart
ID :=DW#16#7FC INDEX :=100 Data set 100 LEN :=8 Length: 8 Bytes
DONE :=#bEnde BUSY :=#bBusy ERROR :=#bError STATUS:=#wStatus
RECORD:=P#DB10.DBX0.0 BYTE 8
CALL "RDREC" , DB52 REQ :=#bStart
ID :=DW#16#7FC INDEX :=100
MLEN :=8 VALID := … BUSY := … ERROR := … STATUS:= … LEN := …
RECORD:=P#DB10.DBX12.0 BYTE 8
Diagnosis address
Data: 14h,92h, 00h,00h, 00h,00h, 00h,00h
ReadResponse
Diagnosis address Data set 100
Response: 14h,92h, 00h,00h, 00h,00h, 03h,FCh
The value read is P170 = 1020 (03FCh).
30 Subject to technical amendments BU 0590 GB-0312
Page 31
4.2.4.2 Writing the frequency inverter parameter P102 Index 1 (start-up time)
Data record 101 is used:
Field Data size Byte Date Explanation
Order label
2 Byte
+
Parameter number
Parameter index
2 Bytes 3
(Data record)
Parameter value 4 Bytes 5
2
4
6
7
8
02 h
+
44E h
_________
244E h
01 h
00 h
00 h
00 h
00 h
FA h
Read parameter value (see Section 4.2.3)
+
Parameter number P102 (+1000) = 44E h
Parameter sub-index (see Section 4.2.3.2)
The time 2.5s (250 = FA h) is to be set
4 Communication
Table 27 Example telegram for reading parameter P102[-02]
S7 Code example:
CALL "WRREC" , DB53 WriteRequest REQ :=#bStart
ID :=DW#16#7FC INDEX :=101 LEN :=8
DONE :=#bEnde BUSY :=#bBusy ERROR :=#bError STATUS:=#wStatus
RECORD:=P#DB10.DBX0.0 BYTE 8
CALL "RDREC" , DB52 REQ :=#bStart
ID :=DW#16#7FC INDEX :=101
MLEN :=8 VALID := … BUSY := … ERROR := … STATUS:= … LEN := …
RECORD:=P#DB10.DBX12.0 BYTE 8
Diagnosis address Data record 101 Length: 8 Bytes
Data: 24h, 4Eh, 01h, 00h, 00h, 00h, 00h, FAh
ReadResponse
Reference Data record 101
Response: 14h, 4Eh, 01h, 00h, 00h, 00h, 00h, 00h
BU 0590 GB-0312 Subject to technical amendments 31
Page 32
PROFINET bus module for NORD frequency inverters SK 5xxE
4.2.4.3 Writing the frequency inverter parameter P105 Index 0 (maximum frequency)
The maximum frequency parameter is to be set to the value 60Hz in data record 1 (Index 0).
Data record 47 is used:
Field Data size Byte Date Explanation
Order reference 1 Byte 1 xx h The order reference is used for the precise allocation of the
TU3-PNT response
Order label 1 Byte 2 02 h Write parameter value (see Section 4.2.3)
Axis 1 Byte 3 01 h Access to FI parameter (0=TU3, 1=FI)
Parameter number 2 Bytes 4 5 04 h
Parameter index 2 Bytes 6 7 00 h
Parameter value 4 Bytes 8
9
10
11
Parameter number P105 (+1000) = 451 h
51 h
Parameter sub-index (see Section 4.2.3.2)
00 h
00 h
00 h
The maximum frequency 60Hz (600 = 258 h) is to be set
02 h
58 h
Table 28 Example telegram for writing parameter P105[-01]
S7 Code example:
CALL "WRREC" , DB53 WriteRequest REQ :=#bStart
ID :=DW#16#7FC INDEX :=47 LEN :=11
DONE :=#bEnde BUSY :=#bBusy ERROR :=#bError STATUS:=#wStatus
RECORD:=P#DB10.DBX0.0 BYTE 8 58h
CALL "RDREC" , DB52 REQ :=#bStart
ID :=DW#16#7FC INDEX :=47
MLEN :=11 VALID := … BUSY := … ERROR := … STATUS:= … LEN := …
RECORD:=P#DB10.DBX12.0 BYTE 8 00h
Diagnosis address Data record 47 Length: 11 Bytes
Data: xxh, 02h, 01h, 04h,51h, 00h, 00h, 00h, 00h, 02h,
ReadResponse
Diagnosis address Data record 47
Response: xxh, 02h, 01h, 04h,51h, 00h,00h, 00h,00h, 00h,
32 Subject to technical amendments BU 0590 GB-0312
Page 33
4 Communication
4.2.4.4 Example of telegram structure with parameterisation via PPO1 or PPO2
When transferring parameter orders, it must be taken into account that the slave does not immediately respond to orders in the parameter channel of the master telegram, but a positive response can be delayed by one or more communication cycles. The master must therefore repeat the required order until the corresponding slave response is received. PPO type 1 or PPO type 2 must be selected.
The parameter (P102) "run-up time" (PNU = 102
dec
/ 66
) is to be set to the value 10sec in parameter set 3.
hex
(Only the PKW channel is evaluated). (Only the PKW channel is evaluated.)
As the acceleration time has a frequency-internal resolution of 0.01sec, a parameter value of 10 / 0.01 = 1000 (3E8
) must be transferred for 10 sec.
hex
Procedure:
1) Specify order label ("Change parameter value (array word)" AK = 7)
2) Select parameter (P 102
= P 66
dec
hex
)
3) Select parameter set 3 (IND = 02)
4) Set parameter value (1000
dec
/ 3E8
hex
)
5) Check response telegram (positive for array word = 4)
The telegram is composed as follows in hexadecimal notation:
word 1 2 3 4
Byte 0 1 2 3 4 5 6 7
Designation PKE PKE IND IND PWE PWE PWE PWE
Value 70 66 02 00 00 00 03 E8
When the order has been fully implemented by the inverter, it responds with (hexadecimal):
word 1 2 3 4
Byte 3 4 5 6 7 8 9 10
Designation PKE PKE IND IND PWE PWE PWE PWE
Value 40 66 02 00 00 00 03 E8
ATTENTION
If parameter changes are made (i.e. requests via the PKW area by the control master), care must be taken that the maximum number of permissible writing cycles to the frequency inverter EEPROM (100,000 cycles) is not exceeded. I.e. continuous cyclical writing must be prevented.
For certain applications it is sufficient if the values are only saved in the RAM memory of the frequency inverter. The corresponding setting is made via parameter (P560) "Save in EEPROM".
BU 0590 GB-0312 Subject to technical amendments 33
Page 34
PROFINET bus module for NORD frequency inverters SK 5xxE
5 Parameter
5.1 Parametersiation of PROFINET bus module SK TU3-PNT
The following parameters affect the bus modules.
5.1.1 BUS module standard parameters (P15x)
Access: Read/Write
Parameter
{Factory setting}
P152
0 ...1
{ 0 }
Setting value / Description / Note Device
Factory setting
(Factory setting)
By selecting the appropriate value and confirming it with the ENTER key, the selected parameter range is entered in the factory setting. Once the setting has been made, the value of the parameter returns automatically to 0.
0 = No change: Does not change the parameterisation. 1 = Load factory settings: The complete parameterisation of the FI is reset to the factory
setting. All originally parameterised data are lost.
5.1.2 Parameters specific to PROFINET BUS modules (P16x)
Access: Read/Write
Parameter
{Factory setting}
P160 … [-01] … … [-04]
Setting value / Description / Note Device
IP address
(IP address)
Parameter type
SK TU3-PNT 16 bit
Parameter type
SK TU3-PNT 8 Bit
0 ... 255
{ [-01] = 192 }
{ [-02] = 168 }
{ [-03] = 20 }
{ [-04] = 200 }
P161[-01]
[-04]
0 ... 255
{ [-01] = 255 }
{ [-02] = 255 }
{ [-03] = 255 }
{ [-04] = 0 }
34 Subject to technical amendments BU 0590 GB-0312
Parameterised IP address consisting of four bytes. In case of a change to the IP address (e.g. with NORD CON), this is only saved by writing it to Index 4.
CAUTION: Saving is prevented if the IP address which is entered does not correspond to the
convention. If there are contradictions between the IP address and the mask (P161), the mask is corrected automatically.
Deletion of the IP settings (IP+sub-net mask) is performed by entering IP 0.0.0.0.
[-01] = IP High (NET-ID) [-02] = IP (NET-ID)
IP sub-net mask
(IP sub-net mask)
Parameterised IP mask consisting of four bytes. In case of a change to the IP mask (e.g. with NORD CON), this is only saved by writing it to Index 4.
ATTENTION: Saving is prevented if the entered IP address is inconsistent with the IP address. Example:
IP-Add: 192.168.20.200, IP mask: 255.255.255.0 Correct
IP-Add: 192.168.20.200, IP mask: 255.0.0.0 Error
[-03] = IP (NET ID) [-04] = IP Lo (Host)
SK TU3-PNT 8 Bit
Page 35
Parameter
{Factory setting}
Fehler! Verweisquelle konnte nicht gefunden werden.Fehler! Verweisquelle konnte nicht gefunden werden.
Setting value / Description / Note Device
Parameter type
P162
45 ... 122 The device name can be queried or changed with this parameter. Character strings with a
P163[-01]
[-07]
0 ... 255
all { 0 }
Device name
(Device name)
length of up to 240 characters are possible. Characters 45 to 122 from the ASCII Code can be used.
The name is saved after the entry of a 0 at the end of the character string.
Test alarm
(Test alarm)
This parameter is used, e.g to trigger a diagnostic alarm from a slot during commissioning. A frequency inverter error can be simulated by entering the value of the error (e.g. link circuit overvoltage = E005.0 Value 50) in the slot of the relevant inverter (e.g.: Slot 3). An "incoming" alarm is triggered. If the value is reset to 0 the alarm is "outgoing".
Example:
Trigger alarm with error 5.0 on Slot 2:
P163[-04] = 50 ChannelErrorType= 0x100+50=0x132
[-01] = Slot 0 (DAP - reserved) [-02] = Slot 1 (reserved) [-03] = Slot 2 (TU) [-04] = Slot 3 (FI)
SK TU3-PNT 8 Bit
SK TU3-PNT 8 Bit
[-05] = Slot 4 (reserved) [-06] = Slot 5 (reserved) [-07] = Slot 6 (reserved)
5.1.3 BUS module information parameters, general (P17x)
Access: Read only
Parameter Setting value / Description / Note Device
P170 ...
[-02]
0 ... 5420
P171[-01]
… … [-03]
0.0 ... 9999.9
Present error
(Present error)
Actual errors in the PROFINET module. The error message is reset when the supply voltage is switched off.
Possible error codes:
- 1020 Bus Time Out via P151 (TU4-PNT) or P513 (TU3-PNT)
[-01] = Actual module error [-02] = Actual module error
Software-Version
(Software Version / Revision)
This parameter shows the software and revision numbers in the module. Array 03 provides information about any special versions of the hardware or software A zero stands for the standard version.
[-01] = Version [-02] = Revision
Parameter type
SK TU3-PNT 16 bit
SK TU3-PNT 16 bit
[-03] = Special version
BU 0590 GB-0312 Subject to technical amendments 35
Page 36
PROFINET bus module for NORD frequency inverters SK 5xxE
Parameter Setting value / Description / Note Device
Parameter type
P172
0 ... 2
P173
0 ... 0xFFFF
Configuration
(Configuration level)
The version can be queried in this parameter.
Possible values:
0 = Internal module, (SK CU4) 1 = External module, (SK TU4) 2 = Module SK TU3-PNT
Option status
(Module status)
Explanation of bits:
Bit 0 = Initialisation Bit 1 = AR installed Bit 2 = Reserved Bit 3 = Timeout (P151 / P513) Bit 4 = Reserved Bit 5 = Ethernet connection Bit 6 = Reserved Bit 7 = Reserved Bit 8 = Frequency inverter status Bit 9 = Frequency inverter status
Explanation of frequency inverter status
Bit9 | Bit8 0 0 FI is offline 0 1 FI not supported 1 0 FI is online
SK TU3-PNT 16 bit
SK TU3-PNT 16 bit
P176 … [-01] … … [-27]
P177[-01]
… … [-27]
-32768 ... 32767
PZD bus IN
(Process data bus IN)
Allocation of process data which have been received (data sent from PROFINET IO controller). -32768 ... 32767
[-01] = Bus module outputs [-02] = Control word for FI1 [-03] = Setpoint 1 for FI1 [-04] = Setpoint 2 for FI1
PZD bus OUT
(Process data bus OUT)
Allocation of process data which have been transmitted (data sent to the PROFINET IO controller).
[-01] = Bus module inputs [-02] = Status word from FI1 [-03] = Actual value 1 from FI1 [-04] = Actual value 2 from FI1
SK TU3-PNT 16 bit
[-05] = Bus module outputs [-06] = Control word for FI1 [-07] = Setpoint 1 for FI1 [-08] = Setpoint 2 for FI1
SK TU3-PNT 16 bit
[-05] = Bus module inputs [-06] = Status word from FI1 [-07] = Actual value 1 from FI1 [-08] = Actual value 2 from FI1
36 Subject to technical amendments BU 0590 GB-0312
Page 37
Fehler! Verweisquelle konnte nicht gefunden werden.Fehler! Verweisquelle konnte nicht gefunden werden.
5.1.4 BUS module information parameters, bus-specific (P18x)
Access: Read only
Parameter Setting value / Description / Note Device
P180[-01]
[-07]
0 ... 7
P181[-01]
[-06]
0 ... 255
PPO TYPE
(PPO Type / Module ID)
The module ID (see gsdml file) for the slots can be queried with this parameter. Caution: meaningful values can only be read out with an existing AR.
Possible values:
0 = Empty slot 1 = Reserved slot 2 = DIG-IO, Process data for the TU 3 = PPO3, Process data for the FI
[-01] = Reserved [-02] = Reserved [-03] = Slot 3 (FI) [-04] = Reserved
4 = PPO4, Process data for the FI 5 = PPO6, Process data for the FI 6 = PPO1, Process or parameter data for the FI 7 = PPO2, Process or parameter data for the FI
MAC Address
(MAC Address)
The Ethernet address (MAC address) can be read out from this parameter.
[-01] … [-03] PROFINET identification [-04] … [-06] Manufacturer's address range (NORD: 6000 … 6FFF)
Example: (00:0E:CF:03:60:00)
SK TU3-PNT 8 Bit
SK TU3-PNT 8 Bit
Parameter type
[-05] = Reserved [-06] = Reserved [-07] = Reserved
BU 0590 GB-0312 Subject to technical amendments 37
Page 38
PROFINET bus module for NORD frequency inverters SK 5xxE
5.2 SK5xxE inverter parameters (selection)
The parameters listed below relate the the frequency inverter in combination with the PROFINET bus module. A complete list of inverter parameters can be found in the manual for the frequency inverter (BU0500)).
NOTE: The structure of individual parameters of the frequency inverter versions SK 500E to SK 535E
differs from the structure of the versions SK 540E and SK 545E. Because of this, the relevant parameters descriptions are listed twice.
5.2.1 Extra functions
Access: Read/Write
Parameter
Setting value / Description / Note Device Supervisor Parameter set
{Factory setting}
P509
0 ... 10
{ 0 }
P510 [-01]
[-02]
0 ... 10
{ all 0 }
Source Control Word
(Source control word)
Selection of the interface via which the FI is controlled (for details see BU0500). Also note parameter (P350).
Source setpoints
(Source setpoints)
Selection of the setpoints to be parameterised (For details see BU0500). Also note parameters (P350) and (P351).
SK 5xxE
0 = Control terminals or keyboard 1 = Control terminals 2 = USS (or Modbus RTU: SK 540E and above) 3 = CAN 4 = Profibus 5 = InterBus
[-01] = Main setpoint source [-02] = Auxiliary setpoint source
0 = Automotive 1 = Control terminals 2 = USS (or Modbus RTU: SK 540E and above) 3 = CAN 4 = Profibus 5 = InterBus
6 = CANopen 7 = DeviceNet 8 = Ethernet TU 9 = CAN Broadcast
10 = CANopen Broadcast
SK 5xxE S
6 = CANopen 7 = DeviceNet 8 = Ethernet TU 9 = CAN Broadcast
10 = CANopen Broadcast
P513
-0.1 / 0.0 /
0.1 ... 100.0 sec
{ 0.0 }
38 Subject to technical amendments BU 0590 GB-0312
Telegram time-out
(Telegram time out)
Monitoring function of the active bus interface. Following receipt of a valid telegram, the next one must arrive within the set period. Otherwise the FI reports an error and switches off with the error message E010 >Bus Time Out<.
0.0 = Off: Monitoring is switched off.
-0.1 = no error: Even if communication between BusBox and FI is interrupted (e.g. 24V error,
Box removed, etc.), the FI will continue to operate unchanged.
SK 5xxE S
Page 39
Parameter
{Factory setting}
Fehler! Verweisquelle konnte nicht gefunden werden.Fehler! Verweisquelle konnte nicht gefunden werden.
Setting value / Description / Note Device Supervisor Parameter set
P543
0 ... 24
{ 1 }
P543 [-01] ... [-05]
0 ... 57
{ [-01] = 1 } { [-02] = 4 } { [-03] = 9 } { [-04] = 0 } { [-05] = 0 }
Bus actual value 1
(Actual bus value 1)
The return value 1 can be selected for bus actuation in this parameter.
The possible analog functions can be found in the following table.
NOTE: For further details please refer to the manual BU0500 (P418, P543), the relevant
Bus actual value
(Actual bus values)
In this parameter the return value for bus actuation can be selected.
NOTE: The actual values 4 and 5 must be supported by the relevant bus module. For
[-01] = Actual bus value 1 [-02] = Actual bus value 2 [-03] = Actual bus value 3 [-04] = Actual bus value 4 [-05] = Actual bus value 5
0 = Off 1 = Actual frequency 2 = Actual speed 3 = Electricity 4 = Torque current (100% = P112) 5 = Digital IO status 6 = ... 7 Reserved 8 = Setpoint frequency
9 = Error number 10 = ... 11 Reserved 12 = BusIO Out Bits 0...7 13 = ... 16 Reserved
up to
SK 535E
Bus operating manual or the supplementary POSICON manual BU0510.
SK 540E and
above
further details please refer to the manual BU0500 (P418, P543), the relevant BUS operating manual, the supplementary POSICON manual BU0510 or the supplementary PLC manual BU0550.
17 = Value analog input 1 18 = Value analog input 2 19 = Setpoint frequency master value
(P503)
20 = Set Freq. After Ramp "Setpoint
1
frequency master value after ramp"
21 = Act. Freq. w/o Slip "Actual frequency
without slip master value"
22 = Speed encoder
(only possible with SK 520E and encoder feedback)
23 = Act. freq. with slip, "Actual frequency
with slip" (SW V2.0 and above)
24 = Lead.act.freq.+slip, "Master value,
actual frequency with slip" (SW V2.0 and above)
53 = ... 57 Reserved
S P
S P
P544
0 ... 24
{ 0 }
Bus actual value 2
(Actual bus value 2)
This parameter is identical to P543.
Condition is PPO 2 or PPO 4 type (P507).
up to
SK 535E
S P
1
The assignment of the digital inputs in P543/ 544/ 545 = 5
Bit 0 = DigIn 1 Bit 1 = DigIn 2 Bit 2 = DigIn 3 Bit 3 = DigIn 4 Bit 4 = DigIn 5 Bit 5 = DigIn 6 (SK 520E and above) Bit 6 = DigIn 7 (SK 520E and above) Bit 7 = Dig. func. AIN1 Bit 8 = Dig. func. AIN2 Bit 9 = DigIn 8 (SK 540E and above) Bit 10 = DigIn 1, 1st IOE (SK 540E and above) Bit 11 = DigIn 2, 1st IOE (SK 540E and above) Bit 12 = Out 1/ MFR1 Bit 13 = Out 2/ MFR2 Bit 14 = Out 3/ DOUT1 (SK 520E and above) Bit 15 = Out 4/ DOUT2 (SK 520E and above)
BU 0590 GB-0312 Subject to technical amendments 39
Page 40
PROFINET bus module for NORD frequency inverters SK 5xxE
Parameter
Setting value / Description / Note Device Supervisor Parameter set
{Factory setting}
P545
0 ... 24
{ 0 }
P546
0 ... 55
{ 1 }
P546 [-01]
... [-05]
0 ... 57
{ [-01] = 1 }
all other { 0 }
Bus actual value 3
(Actual bus value 3)
This parameter is identical to P543.
Condition is PPO 2 or PPO 4 type (P507).
Function Bus setpoint 1
(Function of bus - setpoint 1)
In this parameter, a function is allocated to the output setpoint 1 during bus actuation.
The possible analog functions can be found in the following table.
NOTE: For further details please refer to the manual BU0500 (P400, P546), the relevant
Function Bus setpoint
(Function bus - setpoints)
In this parameter, during bus actuation a function is allocated to the setpoint provided.
NOTE: The setpoints 4 and 5 must be supported by the relevant bus module. For further
[-01] = Bus setpoint 1 [-02] = Bus setpoint 2 [-03] = Bus setpoint 3 [-04] = Bus setpoint 4 [-05] = Bus setpoint 5
0 = Off 1 = Setpoint frequency 2 = Torque current limit (P112) 3 = Actual frequency PID 4 = Frequency addition 5 = Frequency subtraction 6 = Current limit (P536) 7 = Maximum frequency (P105) 8 = Actual PID frequency limited 9 = Actual PID frequency monitored
10 = Torque servo mode (P300) 11 = Torque precontrol (P214) 12 = Reserved 13 = Multiplication 14 = Process controller actual value 15 = Process controller setpoint 16 = Process controller lead
up to
SK 535E
up to
SK 535E
BUS operating manual or the supplementary POSICON manual BU0510.
SK 540E and
above
details, please refer to manual BU0500 (P400, P546), the relevant BUS operating manual or the supplementary POSICON manual BU0510.
17 = BusIO In Bits 0...7 18 = Curve travel calculator 19 = Set relays, "Output status"
(P434/441/450/455=38)
20 = Set analog output (P418=31) 21 = …45 reserved from SK 530E and above
BU 0510
46 = Setval.torque p.reg., "Setpoint torque
process controller"
47 = reserved from SK 530E and above
BU 0510
48 = Motor temperature (SK 540E and above) 49 = reserved from SK 540E and above
BU 0510
53 = d-correction F process (SK 540E and
above)
54 = d-correction Torque (SK 540E and above) 55 = d-correction F+torque (SK 540E and
above)
56 = reserved from SK 540E and above
BU 0510
57 = reserved from SK 540E and above
BU 0510
S P
S P
S P
40 Subject to technical amendments BU 0590 GB-0312
Page 41
Parameter
{Factory setting}
Fehler! Verweisquelle konnte nicht gefunden werden.Fehler! Verweisquelle konnte nicht gefunden werden.
Setting value / Description / Note Device Supervisor Parameter set
P547
0 ... 55
{ 0 }
P548
0 ... 55
{ 0 }
Function Bus setpoint 2
(Function of bus - setpoint 2)
This parameter is identical to P546.
Function Bus setpoint 3
(Function of bus - setpoint 3)
This parameter is identical to P546.
5.2.2 Information parameters
Access: Read only
Parameter Setting value / Description / Note Device
P740 [-01]
... [-13]
0000 ... FFFF (hex) This parameter informs
PZD bus in
(Process data bus in)
about the actual control word and the setpoints that are transferred via the bus systems.
For display, a BUS system must be selected in P509
[-01] = Control word
[-02] = Actual bus value 1 [-03] = Actual bus value 2 [-04] = Setpoint 3
[-05] = Bus I/O In Bits (P480)
[-06] = Parameter data In 1 [-07] = Parameter data In 2 [-08] = Parameter data In 3 [-09] = Parameter data In 4 [-10] = Parameter data In 5
[-11] = Setpoint 1 [-12] = Setpoint 2 [-13] = Setpoint 3
up to
SK 535E
up to
SK 535E
up to
SK 535E
S P
S P
Parameter type
S
Control word, source from P509.
Setpoint data from main setpoint (P510 [-01]).
The displayed value depicts all Bus In Bit sources linked with
or.
Data during parameter transfer: Order label (AK), Parameter number (PNU), Index (IND), Parameter value (PWE 1/2)
Setpoint data from the master function value (Broadcast), if P509 = 9/10 (P510 [-02])
BU 0590 GB-0312 Subject to technical amendments 41
Page 42
PROFINET bus module for NORD frequency inverters SK 5xxE
Parameter Setting value / Description / Note Device
Parameter type
P740 [-01]
... [-23]
0000 ... FFFF (hex) This parameter informs
PZD bus in
(Process data bus in)
about the actual control word and the setpoints that are transferred via the bus systems.
For display, a BUS system must be selected in P509
SK 540E
and above
[-01] = Control word
[-02] = Actual bus value 1 [-03] = Actual bus value 2 [-04] = Setpoint 3 [-05] = Setpoint 4 [-06] = Setpoint 5
[-07] = Bus I/O In Bits (P480)
[-08] = Parameter data In 1 [-09] = Parameter data In 2 [-10] = Parameter data In 3 [-11] = Parameter data In 4 [-12] = Parameter data In 5
[-13] = Setpoint 1 [-14] = Setpoint 2 [-15] = Setpoint 3 [-16] = Setpoint 4 [-17] = Setpoint 5
[-18] = PLC control word [-19] = Setpoint 1
[-20] = Setpoint 2 [-21] = Setpoint 3 [-22] = Setpoint 4 [-23] = Setpoint 5
S
Control word, source from P509.
Setpoint data from main setpoint (P510 [-01]).
The displayed value depicts all Bus In Bit sources linked
with or.
Data during parameter transfer: Order label (AK), Parameter number (PNU), Index (IND), Parameter value (PWE 1/2)
Setpoint data from the master function value (Broadcast), if P509 = 9/10 (P510 [-02])
Control word, source PLC
Setpoint data from the PLC.
P741 [-01]
... [-13]
0000 ... FFFF (hex) This parameter provides
PZD bus out
(Process data bus out)
information about the actual status word and the actual values that are transferred via the bus systems.
up to
SK 535E
[-01 ] = Status word
[-02] = Actual value 1 (P543) [-03] = Actual value 2 (P544) [-04] = Actual value 3 (P545)
[-05] = Bus I/O Out Bit (P481)
[-06 ] = Parameter data Out 1 [-07 ] = Parameter data Out 2 [-08] = Parameter data Out 3 [-09] = Parameter data Out 4 [-10] = Parameter data Out 5
[-11] = Actual value 1 master function [-12] = Actual value 2 master function [-13] = Actual value 3 master function
S
Status word, source from P509.
The displayed value depicts all Bus Out Bit sources
linked with or.
Data during parameter transfer.
Actual value of master function 502/P503.
42 Subject to technical amendments BU 0590 GB-0312
Page 43
Fehler! Verweisquelle konnte nicht gefunden werden.Fehler! Verweisquelle konnte nicht gefunden werden.
Parameter Setting value / Description / Note Device
Parameter type
P741 [-01]
... [-23]
0000 ... FFFF (hex) This parameter provides
PZD bus out
(Process data bus out)
information about the actual status word and the actual values that are transferred via the bus systems.
SK 540E
and above
[-01 ] = Status word
[-02] = Actual value 1 (P543 [-01]) [-03] = Actual value 2 (P543 [-02]) [-04] = Actual value 3 (P543 [-03]) [-05] = Actual value 4 (P543 [-04]) [-06] = Actual value 5 (P543 [-05])
[-07] = Bus I/O Out Bit (P481)
[-08] = Parameter data Out 1 [-09] = Parameter data Out 2 [-10] = Parameter data Out 3 [-11] = Parameter data Out 4 [-12] = Parameter data Out 5
[-13] = Actual value 1 master function [-14] = Actual value 2 master function [-15] = Actual value 3 master function [-16] = Actual value 4 master function [-17] = Actual value 5 master function
[-18] = PLC status word [-19] = Actual value 1 PLC
[-20] = Actual value 2 PLC [-21] = Actual value 3 PLC [-22] = Actual value 4 PLC [-23] = Actual value 5 PLC
S
Status word, source from P509.
The displayed value depicts all Bus Out Bit sources
linked with or.
Data during parameter transfer.
Actual value of master function 502/P503.
Status word via PLC
Actual value data via PLC
P745
0.0 ... 999.9 Version status (software version) of the technology unit (SK TU3-xxx), but only when own
P746
0000 ... FFFF (hex) Actual status (readiness, error, communication) of the technology unit (SK TU3-xxx), but only
Option version
(Module version)
processor is present, therefore not for SK TU3-CTR.
Have this data available if you have a technical query.
Option status
(Module status)
when own processor is present, therefore not for SK TU3-CTR.
Example:
0603
hex
High byte = 06 Low byte = 03
Code details can be found in the respective BUS module manual. Different contents are shown depending on the modules.
=> Profibus
hex
=> Module ready + connection to master
hex
SK 5xxE
SK 5xxE S
NOTE
When activated, the functions block current, qu ick sto p , remote control and c ancel er ror
are available at the (local) control terminals. To operate the drive, a high signal must be present on the digital inputs being used before the drive can be enabled.
BU 0590 GB-0312 Subject to technical amendments 43
Page 44
PROFINET bus module for NORD frequency inverters SK 5xxE
6 Error monitoring and error messages
According to the cause, frequency inverters and technology units generate appropriate messages if they deviate from their normal operating status.
6.1 PROFINET error monitoring
An error in the frequency inverter (P700) or in the SK TU3-PNT (P170) results in a diagnostic alarm which is transmitted to the control unit as an "incoming event". The error value is coded as follows:
Error number (P700 or P170) = Alarm number of the diagnostic alarm – 0x100
Example:
During operation, the error E10.3 (P700 Index 1 = 103) = Timeout occurs via the P513 monitoring. The SK TU3-PNT sends a diagnostic alarm with the value 359 (= 100h + 103 = 256 + 103 = 359) to the control unit.
With the aid of parameter P163, e.g. during commissioning, various alarms can be sent in order to test the operation of the control program.
6.2 Error messages in the Bus module SK TU3-PNT
All SK TU3-PNT error messages are displayed in parameter (P170) of the bus module and trigger an error in the connected FI. This is permanently stored in the FI error statistics. The error messages in the bus module memory (P170) parameter are lost when the 24V supply voltage is switched off.
6.3 Error messages in the SK 5xxE frequency inverter
Errors cause the frequency inverters to switch off, in order to prevent a device fault.
The following options are available to reset a fault (acknowledge):
1. Switching the mains off and on again,
2. By an appropriately programmed digital input (P420 ... P425 / P470 = Function 12),
3. By switching of the “enable” on the frequency inverter (if no acknowledgement),
4. By Bus acknowledgement or
5. By P506, the automatic error acknowledgement.
The following error messages are directly associated with the Bus module SK TU3-PNT.
FI Error Code Error register
0 No error
10.3 Timeout via P513 monitoring
10.5 General PROFINET configuration error
10.8 The connection between the FI and the SK TU3-PNT had a timeout
digital input is programmed for
Table 29 SK5xxE error messages associated with the SK TU3-PNT
For a complete overview of the error messages relating to the frequency inverter, please refer to the frequency inverter manual BU0500.
44 Subject to technical amendments BU 0590 GB-0312
Page 45
7 Lists / Index
7.1 Abbreviations
7 Lists / Index
AIN ....... Analog input
AOUT ... Analogue output DI (DIN) Digital input DO (DOUT) Digital output
I / O ....... Input /Output
EEPROM Non-volatile memory
EMC...... Electromagnetic compatibility
FI ……... Frequency inverters
HSW ..... Main setpoint
I/O ......... In / Out (Input / Output)
ISD........ Field current (Current vector control)
7.2 Keyword Index
Baud rate
Binary code
Bit / Byte
Broadcast
DAP
Jitter
XML
………………………………………….
………………………………………….
………………………………………….
………………………………………….
………………………………………….
………………………………………….
………………………………………….
LED....... Light-emitting diode
NSW...... Auxiliary setpoint
P-Box... ParameterBox
PDO...... Process Data Object
S ........... Supervisor Parameter, P003
SW ....... Software version, P707
STW...... Control word
TU ......... Technology Unit (technology module,
e.g.: PROFINET Bus module)
ZSW...... Status word
The transmission rate for serial interfaces in
bits per second
The designation for a code in which
messages are communicated by "0" and "1"
signals.
A bit (binary digit) is the smallest unit of
information in the binary system. A byte has
8 bits.
In a network, all slave participants are
addressed simultaneously by the master.
Device Access Point, designates the
PROFINET IO Bus interface
Designates a slight fluctuation in precision
in the transmission pulse, or the variation in
the transmission time of data packages.
"Extensible Markup Language", abbreviated
XML , contains all essential information
concerning the bus module and all
parameters of FIs which can be connected.
BU 0590 GB-0312 Subject to technical amendments 45
Page 46
PROFINET bus module for NORD frequency inverters SK 5xxE
7.3 Figures
Fig. 1 Type Codes...................................................................................................................................................................... 7
Fig. 2 Frequency inverters with SK TU3- optional modules (selection)...................................................................................... 8
Fig. 3 Installation of the Technology Unit (optional module) ...................................................................................................... 9
Fig. 4 Location and designation of the LEDs ........................................................................................................................... 11
Fig. 5: Example of PROFINET IO linear topology.................................................................................................................... 13
Fig. 6: Example of PROFINET IO star topology with switch .................................................................................................... 13
Fig. 7 Installation of the GSDML file in SIMATIC Manager .....................................................................................................15
Fig. 8 Hardware Catalogue: Module selection and specification of data format...................................................................... 16
Fig. 9 Module properties ......................................................................................................................................................... 16
Fig. 10 Diagram of the FI Status Machine............................................................................................................................... 22
Fig. 11 Function of PROFINET Record................................................................................................................................... 25
7.4 Tables
Table 1 Electrical specifications of the SK TU3-PNT ............................................................................................................... 10
Table 2 Power supply connections ......................................................................................................................................... 10
Table 3 RJ45 socket connections ........................................................................................................................................... 10
Table 4 Description of the RUN LED (Ethernet Status) .......................................................................................................... 11
Table 5 Description of the ERR LED (Ethernet errors) ........................................................................................................... 11
Table 6 Description of the link / Activity LEDs......................................................................................................................... 11
Table 7 Description of the DS and DE LEDs .......................................................................................................................... 12
Table 8 Bus cable connections ............................................................................................................................................... 14
Table 9: PPO 3 ........................................................................................................................................................................17
Table 10: PPO 4 ......................................................................................................................................................................17
Table 11: PPO 6 ......................................................................................................................................................................17
Table 12: PPO 1 ......................................................................................................................................................................18
Table 13: PPO 2 ......................................................................................................................................................................18
Table 14 Meaning of individual control word bits .................................................................................................................... 19
Table 15 Meaning of individual status word bits...................................................................................................................... 20
Table 16 Codes for FI status................................................................................................................................................... 21
Table 17 Depiction of 32Bit setpoint/actual values.................................................................................................................. 23
Table 18 Example of setpoint specification............................................................................................................................. 24
Table 19 Structure of data records 100 and 101..................................................................................................................... 26
Table 20 Structure of data record 47 ...................................................................................................................................... 26
Table 21 Orders from the controller with the associated response label of the inverter.......................................................... 27
Table 22 Orders from the controller with the associated response label of the inverter or technology unit............................. 27
Table 23 Response labels - Meaning...................................................................................................................................... 28
Table 24 Response labels - Explanation of error numbers for response label = 7.................................................................. 28
Table 25 Example: Address formation for array elements or parameters depending on parameter sets................................ 29
Table 26 Example telegram for reading parameter P170 ....................................................................................................... 30
Table 27 Example telegram for reading parameter P102[-02] ................................................................................................31
Table 28 Example telegram for writing parameter P105[-01].................................................................................................. 32
Table 29 SK5xxE error messages associated with the SK TU3-PNT .....................................................................................44
46 Subject to technical amendments BU 0590 GB-0312
Page 47
7.5 Keyword index
A
Actual value................................ 23
B
Bus
actual value (P543) ................ 39
actual value 1 (P543) ............. 39
actual value 2 (P544) ............. 39
F
Factory settings (P152) ..............34
Faults.......................................... 44
Features ....................................... 6
G
GSD............................................ 15
GSDML....................................... 15
7 Lists / Index
Performance .................................6
PPO-Type (P180) .......................37
Present error (P170) ................... 35
Process data............................... 17
Process data bus IN (P176)........ 36
Process data Bus In (P740).. 41, 42
Process data bus OUT (P177).... 36
Process data Bus Out (P741)42, 43
actual value 3 (P545) ............. 40
setpoint (P546)....................... 40
setpoint 1 (P546).................... 40
setpoint 2 (P547).................... 41
setpoint 3 (P548).................... 41
C
CE ................................................ 7
Commissioning..................... 13, 14
Configuration level (P172).......... 36
Connections ............................... 10
Control word............................... 19
D
Data format ................................ 27
Data records............................... 26
Device name (P162) .................. 35
E
EMC ........................................... 13
EMC Directive .............................. 7
Error messages.......................... 44
Example ............................... 24, 30
Extra functions ........................... 38
I
Information parameters ..............41
IP address (P160) ...................... 34
IP sub-net mask (P161).............. 34
L
LED ............................................11
Load factory setting .................... 34
Low Voltage Directive................... 2
M
MAC Address (P181).................. 37
Messages ................................... 44
Module status (P173) .................36
Module status(P746) .................. 43
Module version (P745) ...............43
Mounting....................................... 9
O
Operating status .........................44
P
Parameter................................... 34
PDO............................................ 17
R
Record ........................................ 25
RoHS compliance.........................7
S
Safety information......................... 2
Setpoint ......................................23
Shielding.....................................13
SIMATIC ..................................... 15
SK 5xxE........................................8
Software version (P171) .............35
Source control word (P509) ........38
Source setpoints (P510) .............38
Speed .........................................39
Status displays ...........................11
Status word................................. 20
T
Technical data ............................10
Telegram time out (P513) ........... 38
Test alarm (P163) ....................... 35
Timeout....................................... 24
Topology.....................................13
BU 0590 GB-0312 Subject to technical amendments 47
Page 48
Mat. No. 607 5902 / 0312
Loading...