Compliance with the operating instructions is necessary for fault-free operation and the acceptance of
possible warranty claims. These operating instructions must be read before working with the device!
The BU0560 contains important information on servicing and must be kept near to the device.
The CANopen modules and the corresponding frequency inverters are devices for stationary installation
in control cabinets or decentralised structures. All data regarding technical data and permissible
conditions at the installation site must be complied with.
Commissioning (commencement of the intended use) is not permitted until it has been ensured that the
machine complies with the EMC Directive 2004/108/EEC and that the conformity of the end product
meets the Machinery Directive 2006/42/EEC (observe EN 60204).
Getriebebau NORD GmbH & Co. KG, 2012
BU0560_ERS_GB-0512 Subject to technical amendments 1
Page 2
NORDAC SK 500E - ERS Information Bus connection
This supplement contains excerpts from the manual BU 0500 EN with supplementary entries for the plug-in
CAN/CANopen connection. This is additional information for the SK 500E-xxx-xxx-A-ERS special device series
with a plug-in 7-pin CAN spring terminal bar.
All other information should be obtained from the frequency inverter manual BU0500. For detailed CAN
information, please refer to the operating instructions BU0060 or contact the supplier of the frequency inverter.
Contact assignment of the X9 CAN terminal strip:
X9: for connection to the CAN/
CANopen interface
only SK 500E- … -ERS
DIP switch 1/2:
1 Termination resistor RJ12 for
RS485 interface
2 Termination resistor for CAN /CANopen interface
ON = connected
The 7-pin Phoenix spring terminal bar X9 (CAN plug) is used instead of the two RJ45 plug connectors (from
SK 520E).
X9: [75] CAN-H
[45] +24 V -Ex
[75] CAN-H
[90] Shield
[76] CAN-L
[46] GND-Ex
[76] CAN-L
Terminals 75 and 76 on the spring terminal bar X9 are for connection of the signal leads from CAN High and
CAN Low and are doubled for looping.
NOTE
Until date of bringing the Phoenix spring terminal bar onto the market (approx. the end of the 2
quarter 2012), the WAGO spring terminal bar will be used. Detailed information in this context
are illustrated at the former edition of the BU0560.
nd
2 Subject to technical amendments BU0560_ERS_GB-0512
Page 3
NORDAC SK 500E - ERS Information Control connection details
Wires with a cross-section of 0.2mm² to 1.5mm² (without wire end sleeve) can be connected to the spring
terminals. The type code -ERS is the abbreviation for this special version.
Terminal Function
[factory setting]
Terminal block X11 (1x RJ12), RS485/RS232
1 RS485 A
2 RS485 B
3 GND
Data cable RS485
Reference potential for
Bus signals
4,232 TXD
5,232 RXD
6 +5V
Data cable RS232
internal 5V supply
voltage
optional
Adapter cable
RJ12 to SUB-D9
for direct connection
to a PC with NORD
CON
DIP switches1/2 (top view of SK 5xxE)
Plug designation X11 X9
Data Description / wiring suggestion Parameter
Baud rate
9600…38400Baud
Terminal resistance
R=120 DIP 1 (see
below)
0V digital
P502...P513
Baud rate
9600…38400Baud
5V 20%
RS48 5 _A
RS48 5 _B
GND
TXD
RXD
+5V
RJ12: Pin No. 1 … 6
n.c.
Length 3m
Assignment RS 232
(RxD, TxD, GND)
n.c.
GND
TxD
RxT
+ 5V
Part. No. 278910240
DIP switch 1
Terminal resistor for RS485 interface
(RJ12); ON = switched in
DIP switch 2
Terminal resistor for CAN/CANopen
interface (RJ12); ON = switched in
Terminal block X9, CAN/CANopen (only SK 500E-…-ERS)
75 CAN_H
76 CAN_L
CAN/CANopen signal
90 CAN_SHD Cable shield
Baud rate …500kBaud
RJ45 sockets are connected
in parallel internally.
Termination resistor R=120
46 CAN_GND CAN GND
DIP 2 (see below)
45 CAN_24V
75 CAN_H
76 CAN_L
External 24 VDC
power supply
CAN/CANopen signal
NOTE: To operate
CANbus/CANopen the
interface must be externally
supplied with 24V (capacity
at least 30mA).
1 2
ON
RS485_A
RS485_B
GND
TXD
RXD
+5V
RS232/485 DIP CAN/CANopen
P502...P515
1x spring terminal bar
BU0560_ERS_GB-0512 Subject to technical amendments 3
Page 4
NORDAC SK 500E - ERS Information Electrical data
The "ERS" special versions are only available for the following devices/powers:
SK 500E-750-323-A-ERS 275410076 SK 511E-750-323-A-ERS 275770076
SK 500E-111-323-A-ERS 275410111
SK 500E-221-323-A-ERS 275410221 SK 511E-221-323-A-ERS 275770221
SK 500E-111-340-A-ERS 275420111
SK 500E-301-340-A-ERS 275420301