NORD BU0510 User Manual

GB
BU 0510
Positioning control POSICON
for NORD frequency inverters, SK 530E and above
N O R D Frequency inverters
Safety and operating instructions for drive power converters
(as per: Low Voltage Directive 2006/95/EEC )
1. General During operation, drive power converters may, depending on their
protection class, have live, bare, moving or rotating parts or hot surfaces.
Unauthorised removal of covers, improper use, incorrect installation or operation causes a risk of serious personal injury or material damage.
Further information can be found in this documentation. All transportation, installation, initialisation and maintenance work
must be carried out by qualified personnel (compliant with IEC 364, CENELEC HD 384, DIN VDE 0100, IEC 664 or DIN VDE 0110, and national accident prevention regulations).
For the purposes of these basic safety instructions, qualified personnel are persons who are familiar with the assembly, installation, commissioning and operation of this product and who have the relevant qualifications for their work.
2. Proper use in Europe
Drive power converters are components intended for installation in electrical systems or machines.
When installed in machines, the drive power converter cannot be commissioned (i.e. commencement of the proper use) until it has been ensured that the machine meets the provisions of the EC Directive 2006/42/EEC (machine directive); EN 60204 must also be complied with.
Commissioning (i.e. implementation of the proper use) is only permitted when the EMC directive (2004/108/EEC) is complied with.
CE-labelled drive power converters meet the requirements of the Low Voltage Directive 2006/95/EEC. The harmonised standards for drive power converters listed in the declaration of conformity are used.
Technical data and information for connection conditions can be found on the rating plate and in the documentation, and must be complied with.
The drive power converters may only be used for safety functions which are described and explicitly approved.
3. Transport, storage
Information regarding transport, storage and correct handling must be complied with.
4. Installation
The installation and cooling of the equipment must be implemented according to the regulations in the corresponding documentation.
The drive power converter must be protected against impermissible loads. Especially during transport and handling, components must not be deformed and/or insulation distances must not be changed. Touching of electronic components and contacts must be avoided.
Drive power converters have electrostatically sensitive components, which can be easily damaged by incorrect handling. Electrical components must not be mechanically damaged or destroyed (this may cause a health hazard!).
5. Electrical connection
When working on live drive power converters, the applicable national accident prevention regulations must be complied with (e.g. VBG A3, formerly VBG 4).
The electrical installation must be implemented according to the applicable regulations (e.g. cable cross-section, fuses, ground lead connections). Further instructions can be found in the documentation.
Information about EMC-compliant installation – such as shielding, earthing, location of filters and installation of cables can be found in the drive power converter documentation. These instructions must be complied with even with CE marked drive power converters. Compliance with the limiting values specified in the EMC regulations is the responsibility of the manufacturer of the system or machine.
6. operation
Where necessary, systems where drive power converters are installed must be equipped with additional monitoring and protective equipment according to the applicable safety requirements, e.g. legislation concerning technical equipment, accident prevention regulations, etc.
The parameterisation and configuration of the drive power converter must be selected so that no hazards can occur.
All covers must be kept closed during operation.
7. Maintenance and repairs
After the drive power converter is disconnected from the power supply, live equipment components and power connections should not be touched immediately, because of possible charged capacitors. Observe the applicable information signs located on the drive power converter.
Further information can be found in this documentation.
These safety instructions must be kept in a safe place!
2 Subject to technical alterations BU 0510 GB-3911
POSICON position control for NORD frequency inverters, SK 530E and above About this document
Designation of previous versions
Software Version
Comments
BU 0510 DE, June 2007 Part No. 607 5101 / 2307
V 1.6 R0
First issue
BU 0510 DE, September 2011 Part No. 607 5101 / 3911
V 2.0 R0
Implementation of the SK 54xE series with universal
encoder interface for SIN/COS, Hiperface, Endat 2.1, SSI and BISS encoders,
"Flying Saw" technology function,  extension of static positions from 15 to 63 (for SK 54xE
→4x63 positions, depending on parameter set)
various corrections
NOTE
This supplementary operating manual is only valid in conjunction with the operating manual supplied for the respective frequency inverter (Manual BU0500).
Documentation
Designation: BU 0510 GB Part No.: 607 51 01 Device series: SK 53xE, SK 54xE
Version list
Publisher
Getriebebau NORD GmbH & Co. KG
Rudolf- Diesel- Str. 1 D-22941 Bargteheide Germany http://www.nord.com/ Tel.: +49 (0) 45 32 / 401-0 Fax +49 (0) 45 32 / 401-555
BU 0510 GB-3911 Subject to technical alterations 3
Intended use of the frequency inverter
The compliance with the operating instructions is necessary for fault-free operation and the acceptance of possible warranty claims. These operating instructions must be read before working with the device!
These operating instructions contain important information about servicing. They must therefore be kept close to the device.
SK 500E series frequency inverters are devices for industrial and commercial systems used for the operation of three-phase asynchronous motors with squirrel-cage rotors and Permanent Magnet Synchronous Motors - PMSM (SK 54xE and above). These motors must be suitable for operation with frequency inverters. Other loads must not be connected to the devices.
Series SK 500E frequency inverters are devices for stationary installation in control cabinets. All details regarding technical data and permissible conditions at the installation site must be complied with.
Commissioning (implementation of the intended use) is not permitted until it has been ensured that the machine complies with the EMC directive 204/108/EEC and that the conformity of the end product meets the machine directive 2006/42/EEC (note EN 60204).
Getriebebau NORD GmbH & Co. KG, 2011
4 Subject to technical alterations BU 0510 GB-3911
Contents
1 GENERAL INFORMATION ...................................................................................................... 7
2 ENCODER CONNECTIONS ..................................................................................................... 8
2.1 Terminal blocks .................................................................................................... 8
2.1.1 Terminal blocks SK 53xE Size 1 – 4 ......................................................................... 8
2.1.2 Terminal blocks SK 54xE Size 1 – 4 ......................................................................... 9
2.1.3 Terminal blocks, SK 535E Size 5 and above .......................................................... 10
2.2 Colour and contact assignments for encoders ................................................... 11
2.2.1 Incremental encoders.............................................................................................. 12
2.2.2 Sine encoders (SIN/COS encoders) ....................................................................... 13
2.2.3 Hiperface encoders ................................ ................................................................ . 14
2.2.4 Endat encoders ....................................................................................................... 15
2.2.5 SSI encoders .......................................................................................................... 16
2.2.6 BISS encoders ........................................................................................................ 17
2.3 CANopen absolute encoders ............................................................................. 17
2.3.1 Approved CANopen absolute encoders .................................................................. 18
2.3.2 RJ45 WAGO adapter module ................................................................................. 18
2.3.3 Assignment of the CAN interface on the frequency inverter.................................... 19
3 FUNCTION DESCRIPTION .................................................................................................... 20
3.1 Introduction ......................................................................................................... 20
3.2 Position detection ............................................................................................... 20
3.2.1 Position detection with incremental encoders ......................................................... 20
3.2.2 Position detection with absolute encoders .............................................................. 22
3.2.3 Encoder monitoring ................................ ................................................................ . 26
3.2.4 Positioning with absolute / incremental encoders in absolute mode ....................... 27
3.3 Specifying the setpoint ....................................................................................... 30
3.3.1 Position array – absolute setpoint position via digital inputs or BUS I/O In Bits ...... 30
3.3.2 Position increment array– relative setpoint position via digital inputs or
BUS I/O In Bits ........................................................................................................ 31
3.3.3 Bus setpoints .......................................................................................................... 31
3.4 Teach-In function via digital inputs or Bus I/O In Bits......................................... 32
3.5 Conversion ratio of the setpoint and actual values (P607 and P608) ................ 32
3.6 Position control functions (P600) ........................................................................ 33
3.7 Position control ................................................................................................... 34
3.8 Output messages ............................................................................................... 35
3.8.1 Relays (P434, 441) and digital outputs (P450, P455) ............................................. 35
3.8.2 Output messages via BUS I/O Out Bits (P481) ....................................................... 35
4 PARAMETER SETTINGS ....................................................................................................... 36
4.1 Operating display................................................................................................ 36
4.2 Speed control ..................................................................................................... 37
4.3 Control clamps .................................................................................................... 38
4.4 Extra functions .................................................................................................... 47
4.5 Positioning .......................................................................................................... 50
4.6 Information .......................................................................................................... 58
5 COMMISSIONING................................................................................................................... 60
BU 0510 GB-3911 Subject to technical alterations 5
6 SYNCHRONOUS CONTROL ................................................................................................ 62
6.1 General information ........................................................................................... 62
6.2 Communication settings .................................................................................... 62
6.3 Settings for slave ramp time and maximum frequency ..................................... 63
6.4 Setting the speed and position controls ............................................................ 64
6.5 Taking a speed ratio between master and slave into account .......................... 64
6.6 Monitoring functions .......................................................................................... 64
6.6.1 Achievable precision / Position monitoring ............................................................. 64
6.6.2 Master switch-off on slave error or position slip error ............................................. 65
6.6.3 Slip error monitoring on the slave ........................................................................... 66
6.7 Notes on reference point runs with synchronous operation .............................. 66
6.8 Offset switching in synchronous operation ........................................................ 66
6.9 Flying Saw (extended synchronous operation function) ................................... 67
6.9.1 Determination of acceleration path and initiator position ........................................ 68
6.9.2 Diagonal saw .......................................................................................................... 69
6.9.3 Offset switching in synchronous operation ............................................................. 69
7 TROUBLESHOOTING ........................................................................................................... 70
7.1 Error messages ................................................................................................. 70
7.2 Troubleshooting table ........................................................................................ 72
7.2.1 Sources of faults in servo mode operation (without position control) ...................... 72
7.2.2 General sources of error with positioning control enabled ...................................... 72
7.2.3 Sources of error with incremental position detection (without absolute encoders).. 73
7.2.4 Sources of faults for position detection with absolute encoders.............................. 73
7.2.5 Miscellaneous encoder faults (universal encoder interface) ................................... 74
8 SERVICE INFORMATION / REPAIRS .................................................................................. 75
9 LISTS / INDEX ....................................................................................................................... 76
9.1 Keyword Index ................................................................................................... 76
9.2 Abbreviations: .................................................................................................... 77
9.3 Figures ............................................................................................................... 78
9.4 Tables ................................................................................................................ 78
9.5 Key words .......................................................................................................... 79
6 Subject to technical alterations BU 0510 GB-3911
1 General information
NOTE
This description (BU 0510) only contains a selection of the functions and parameters which are specific and relevant for the positioning function. All standard functions and parameters can be found in the manual (BU 0500).
Due to software updates the parameters described here may differ from those of your device. Therefore care should be taken that both the current NORD CON version and the version of your ParameterBox have the latest software version. In case of doubt, please contact your local NORD agency.
The latest version of all descriptions can be found on the Getriebebau NORD GmbH & Co. KG Internet page (www.nord.com).
SK 53xE and SK 54xE frequency inverters are intermediate voltage circuit converters with fully digital microprocessor technology for controlling the speed of 3-phase motors.
In combination with an incremental encoder or an absolute encoder the standard components form a high­precision positioning drive:
The SK53xE provides 63 programmable absolute positions. The SK54xE provides 252 programmable absolute positions. By means of the position control, the position is maintained even with large load fluctuations. Time-optimised and safe travel up to the target position by means of path calculation. In addition to travelling to absolute positions, up to 4 step lengths (so-called position
increments) can be stored in the frequency inverter.
Required positions can also be transferred via a field bus interface. The positioning function is available as a function extension for the SK 530E and above.
The parameters (P6xx) required for positioning are inserted into the existing inverter menu structure as an additional menu group (Positioning).
The specified setpoint position can be input via the existing digital inputs, the Bus IO In Bits, or via the USS protocol or other field bus system.
1 General
A switchover from speed control to position control (Positioning) can be achieved by switching over the parameters.
Synchronous operation functionality between a master and one or more slave drives is possible via the integrated CAN bus or RS485 interface. In addition, as an extension to the synchronous operation functionality, the "Flying Saw" enables the slave to be deliberately and independently synchronised to or uncoupled from the master.
A round axis function (Modulo axes) is also available for rotating platforms and similar applications. This controls an endless axis with optimisation of travel. According to the required position, the drive rotates clockwise or anticlockwise.
BU 0510 GB-3911 Subject to technical alterations 7
X6:
Incremental encoder input Encoder, e.g.: TTL, 10-30V, RS422, 2048 impulses/rotation
Note:
5V encoders should not be used.
X7:
additional digital inputs and outputs
DIP switch:
Switching from analog inputs AIN2/AIN1 current/voltage setpoint
I = current 0/4...20mA V = voltage 0...10V
NOTE:
AIN2 – upper DIP Switch AIN1 – lower DIP Switch
X8:
VI_S 24V, pulse block input
VO_S 15/24V, output for commissioning without safety switching device
only for SK 53xE
and not with 115VAC
devices
further details in
handbook BU 0530
X4:
analog inputs and outputs
+10V max. 5mA
0...10V or
0/4...20mA
Analog output: 0 …
10V
X5: digital inputs and
voltage supply
R
i DIN
approx. 4.5k
with SK 530E
Terminal 42internal
+15V max. 150mA
+5V max. 250mA
with SK 535E
Terminal 44external
+18-30V min. 800mA
X11:
1x RJ12 socket to connect the RS232 or RS485 interface
X9/X10:
2x RJ45 socket to connect the CAN/CANopen interface
X9 X10 X11
2 Encoder connections
The internal zero point of the inverter can be adjusted by specifying an offset value. A possible reduction ratio between the position measurement system (encoder) and the motor can be taken
into account by the use of transformation and reduction ratios. The motor and the position measurement system (encoder) do not need to have the same direction of rotation. A negative ratio must be set if the direction of rotation is different.
2.1 Terminal blocks
The terminal blocks for the control connections and for the encoder differ between the versions and sizes of the frequency inverter.
2.1.1 Terminal blocks SK 53xE Size 1 – 4
8 Subject to technical alterations BU 0510 GB-3911
Fig. 1: Terminal blocks, SK 53xE Size 1 - 4
2.1.2 Terminal blocks SK 54xE Size 1 – 4
X5: digital inputs and
voltage supply
R
i DIN
approx. 4.5k
with SK 540ETerminal 42
internal
+15V max. 150mA
+5V max. 250mA
with SK 545ETerminal 44
external
+18-30V min. 800mA
X6: Incremental encoder
input
Incremental encoder,
e.g.:
10-30V, TTL, RS422
2048 Imp./Rpm.
Note: 5V encoders should
not be used.
.
X7: additional digital inputs
and outputs
DIP switch:
Switching from analog
inputs AIN2/AIN1
current/voltage setpoint
I = current 0/4...20mA
V = voltage 0...10V
NOTE:
AIN2 – upper DIP Switch
AIN1 – lower DIP Switch
X8: VI_S 24V, input of the
pulse lock
VO_S 15/24V, output for
starting up without safety switching unit
not with 115VAC devices
further details in
handbook BU 0530
X4: analog inputs and
outputs
+10V max. 5mA
0...10V or 0/4...20mA
Analog output: 0 … 10V
X11:1x RJ12 socket to
connect the RS232 or RS485 interface
X9/X10: 2x RJ45 socket to
connect the CAN/CANopen interface
X14: Universal encoder
interface
2 Encoder connection
BU 0510 GB-3911 Subject to technical alterations 9
Fig. 2: Terminal blocks, SK 54xE Size 1 - 4
X5: digital inputs and
voltage supply*
R
i DIN
approx. 4.5k
Terminal 44internal
+24V max. 200mA
*no supply!
X6: Incremental encoder
input
Incremental encoder,
e.g.:
10-30V, TTL, RS422
2048 Imp./Rpm.
Note: 5V encoders should
not be used.
X7: additional digital inputs
and outputs
DIP switch: left = ON / right = OFF
S4: AIN2: ON = 10 Volt
OFF = 0 … 10 Volt S3: AIN1: ON = 10 Volt OFF = 0 … 10 Volt S2: AIN2: I = ON = current 0/4...20mA V = OFF = voltage S1: AIN1: I = ON = current 0/4...20mA V = OFF = voltage
Note: If S2 is set to ON (AIN2 = Current input), S4 must be set to OFF.
If S1 is set to ON (AIN1 = Current input), S3 must be set to OFF.
X4: analog inputs and
outputs
±10V max. 5mA
-10V … +10V or
0...10V or 0/4...20mA
Analog output: 0 … 10V
X11:1x RJ12 socket to
connect the RS232 or RS485 interface
X9/X10: 2x RJ45 socket to
connect the CAN/CANopen interface
2.1.3 Terminal blocks, SK 535E Size 5 and above
Fig. 3: Terminal blocks, SK 535E Size 5 and above
10 Subject to technical alterations BU 0510 GB-3911
2 Encoder connection
ATTENTION
The rotation of the incremental encoder must correspond to that of the motor. Therefore, depending on the rotation direction of the encoder to the motor (possibly reversed), a negative number must be set in parameter P301.
NOTE
The voltage difference between tracks A and B can be measured with the aid of parameter P709 [-09] and [-10]. If the incremental encoder is rotated, the value of both tracks must jump between -0.8V and 0.8V. If the voltage only jumps between 0 and 0.8V the relevant rack is faulty. The position can no longer be determined via the incremental encoder. We recommend to replace the encoder!
2.2 Colour and contact assignments for encoders
The incremental encoder connection is an input for a type with two tracks and TTL-compatible signals for EIA RS 422-compliant drivers. The maximum current consumption of incremental encoders must not exceed 150 mA. The supply voltage for the rotary encoder is 10-30V.
The pulse number per rotation can be between 500 and 8192 increments. This is set with the normal scaling via parameter P301 "Incremental encoder pulse number" in the menu group "Control parameters". For cable lengths > 20 m and motor speeds above 1500 min-1 the encoder should not have more than 2048 pulses/rotation.
For longer cable lengths the cable cross-section must be selected large enough so that the voltage drop in the cable is not too great. This particularly affects the supply cable, in which the cross-section can be increased by connecting several conductors in parallel.
Unlike incremental encoders, for sine encoders or SIN/COS encoders the signals are not in the form of pulses, but rather in the form of sine signals (shifted by 90°).
BU 0510 GB-3911 Subject to technical alterations 11
Function
Cable colours,
for incremental
encoder
Assignment for SK 53xE
Assignment for SK 54xE*
10-30V supply
brown / green
X5:42(/44) 15V (/24V)
X5:42( /X5:44 /X6:49)
15V ( /24V /12V)
0V supply
white / green
X6:40 GND/0V
X5:40 GND/0V
Track A
brown
X6:51 ENC A+
X6:51 ENC A+
Track A inverse
green
X6:52 ENC A-
X6:52 ENC A-
Track B
grey
X6:53 ENC B+
X6:53 ENC B+
Track B inverse
pink
X6:54 ENC B+
X6:54 ENC B+
Track 0
red
--
X14:63 CLK +
Track 0 inverse
black
--
X14:64 CLK-
+ 5V Sense
blue
--
X14:65 DAT +
0V Sense
white
--
X14:66 DAT -
Cable shield
connected to a large area of the frequency inverter housing or shielding angle
*Zero track not necessary for speed feedback or operation of asynchronous machines.
NOTE
If there are deviations from the standard equipment (Type 5820.0H40, 10-30V encoder, TTL/RS422) for the motors, please note the accompanying data sheet or consult your supplier.
2.2.1 Incremental encoders
According to the resolution (pulse number), incremental encoders generate a defined number of pulses for each rotation of the encoder shaft (Track A / Track A inverse) With this, the precise speed of the encoder or motor can be measured by the frequency inverter. By the use of a second track (B / B inverse) shifted by 90° (¼ period), the direction of rotation can also be determined. In turn, the "zero track" (0 / 0 inverse) provides exactly one pulse per rotation and can therefore be used as a referencing signal for positioning systems.
The voltage source can be an external source or the internal voltage (according to the frequency inverter version: 12V /15V /24V).
Table 1: Connection assignments for incremental encoders
Evaluation of the zero track and the Sense signal is necessary for the operation of PMSM (Permanent Magnet Synchronous Motors). The zero impulse is then used for synchronisation of the rotor position. The offset between the zero pulse and the actual "zero" rotor position is set in parameter P334 "Encoder offset". If the Sense cable (+5V Sense and 0V Sense) is not connected, there is no synchronisation to the zero pulse. The zero track is not required for asynchronous machines. Alternative to the commutation of the position, Hiperface, BISS, Endat or SSI encoders with additional Sin/Cos or incremental tracks may be used.
12 Subject to technical alterations BU 0510 GB-3911
2 Encoder connection
Function
Cable colours for Sin/Cos encoders*
Assignment for SK 54xE
10-30V supply
brown
X5:42( /X5:44 /X6:49)
15V ( /24V /12V)
0V supply
white
X5:40 GND/0V
Track A
green
X6:51 ENC A+
Track A inverse
yellow
X6:52 ENC A-
Track B
grey
X6:53 ENC B+
Track B inverse
pink
X6:54 ENC B+
Track 0
blue
X14:63 CLK +
Track 0 inverse
red
X14:64 CLK-
+ V Sense**
brown
X14:65 DAT +
0V Sense**
white
X14:66 DAT -
Cable shield
connected to a large area of the frequency inverter housing or shielding angle
* E.g. Kübler 5824 ** The Sense cables are internally bridged to the voltage supply of the encoder.
Function
Signal designation
Signal voltage
Sine signal
Sin
max. 5V Uss
Cosine signal
Cos
max. 5V Uss
2.2.2 Sine encoders (SIN/COS encoders)
(SK 540E and above)
The use or function of sine encoders is comparable with that for incremental encoders. However, the encoder provides sine wave signals instead of digital pulses.
The voltage source can be an external source or the internal voltage (according to the frequency inverter version: 12V /15V /24V).
Table 2: Connection assignment for SIN/COS encoders
Table 3: Signal details for SIN/COS encoders
BU 0510 GB-3911 Subject to technical alterations 13
Function
Signal designation
Signal voltage
Sine reference voltage
Sin Ref
2,5V Um
Cosine reference voltage
Cos Ref
2,5V Um
Sine signal
Sin
1V Uss
Cosine signal
Cos
1V Uss
NOTE
The voltage difference between the SIN and COS tracks can be measured with the aid of parameter P709 [-09] and [-10]. If the Hiperface encoder is rotated, the voltage difference should range between approx. -0.5V and 0.5V.
U U
2.2.3 Hiperface encoders
(SK 540E and above)
Hiperface is a mixture of incremental encoder and absolute encoder and combines the advantages of both encoder types. The absolute value is initially only formed when the device is switched on and is communicated by the RS485 specification bus parameter interface to the external counter in the controller, which then continues counting incrementally from this absolute value using the analog sine/cosine signal. During operation the counted position is continuously compared with the measured absolute position of the encoder.
Hiperface encoders are suitable for positioning in combination with servo mode. The requirements for the analog signal are shown in the following table. It must be noted that the tolerances
in the voltages affect the precision of the determined position. The supply voltage for the encoder is 7-12V. An external source or the internal 12V voltage can be used as
the voltage supply.
Table 4: Signal details for Hiperface encoders
Fig. 4: Signals for Hiperface encoders
14 Subject to technical alterations BU 0510 GB-3911
2 Encoder connection
Function
Cable colours, for Hiperface encoders
Assignment for SK 540E
7-12V supply
red
X6:49 VO 12V
0V supply
blue
X5:40 GND/0V
+ SIN
white
X6:51 ENC A+
REFSIN
brown
X6:52 ENC A-
+COS
pink
X6:53 ENC B+
REFCOS
black
X6:54 ENC B+
Data + (RS485)
grey or yellow
X14:65 DAT +
Data - (RS485)
green or violet
X14:66 DAT-
Cable shield
connected to a large area of the frequency inverter housing or shielding angle
Function
Cable colours for Endat encoders
Assignment for SK 54xE
3.6-14V supply
brown / green
X6:49 VO 12V
Sensor UB
blue
X6:49 VO 12V
0V supply
white / green
X5:40 GND/0V
Sensor 0V
white
X5:40 GND/0V
Track A
green/black
X6:51 ENC A+
Track A inverse
yellow/black
X6:52 ENC A-
Track B
blue/black
X6:53 ENC B+
Track B inverse
red/black
X6:54 ENC B+
Clock +
violet
X14:63 CLK +
Clock -
yellow
X14:64 CLK-
Data + (RS485)
grey
X14:65 DAT +
Data - (RS485)
pink
X14:66 DAT -
Cable shield
connected to a large area of the frequency inverter housing or shielding angle
Table 5: Connection assignment for Hiperface encoders
2.2.4 Endat encoders
(SK 540E and above)
Endat encoders function in a similar manner to SSI encoders with 2 RS485 channels, whereby the data channel is bi-directional. The communication frequency of the inverter is 200kHz.
Endat encoders are also available with an integrated incremental track. The settings for the incremental track correspond to those of a conventional incremental encoder.
The supply voltage for the encoder is 3.6-14V. An external source (recommended: >5V) or the internal 12V can be used as the voltage supply.
Table 6: Connection assignment for Endat encoders
BU 0510 GB-3911 Subject to technical alterations 15
Function
Cable colours for SSI encoders*
Assignment for SK 54xE
10-30V supply
brown
X5:42( /X5:44 /X6:49)
15V ( /24V /12V)
Sensor UB
red
X5:42( /X5:44 /X6:49)
15V ( /24V /12V)
0V supply
white
X5:40 GND/0V
Sensor 0V
blue
X5:40 GND/0V
Clock +
green
X14:63 CLK +
Clock -
yellow
X14:64 CLK-
Data + (RS485)
grey
X14:65 DAT +
Data - (RS485)
pink
X14:66 DAT -
Cable shield
connected to a large area of the frequency inverter housing or shielding angle
* E.g. Kübler 3670
2.2.5 SSI encoders
(SK 540E and above)
SSI encoders whose signals are TTL-compatible according to EIA RS 422 can be used. The zero point of the absolute encoder is determined by the position of the absolute encoder and should
therefore be adjusted by installation. The clock frequency is 200kHz. With this clock frequency, cable lengths of up to 80m are possible. The
cables should be twisted in pairs and screened. The supply voltage for the encoder is 10-30V. The voltage source can be an external source or the internal
voltage (according to the frequency inverter version: 12V /15V /24V).
Table 7: Connection assignment for SSI encoders
16 Subject to technical alterations BU 0510 GB-3911
2 Encoder connection
Function
Cable colours for BISS encoders*
Assignment for SK 54xE
10-30V supply
brown
X5:42( /X5:44 /X6:49)
15V ( /24V /12V)
0V supply
white
X5:40 GND/0V
Track A
black
X6:51 ENC A+
Track A inverse
violet
X6:52 ENC A-
Track B
grey/pink
X6:53 ENC B+
Track B inverse
red/blue
X6:54 ENC B+
Clock +
green
X14:63 CLK +
Clock -
yellow
X14:64 CLK-
Data + (RS485)
grey
X14:65 DAT +
Data - (RS485)
pink
X14:66 DAT -
Cable shield
connected to a large area of the frequency inverter housing or shielding angle
* E.g. Kübler 5883
2.2.6 BISS encoders
(SK 540E and above)
BISS is a further development of the SSI interface, which also operates with 2 RS485 channels. With BISS encoders, the position is communicated together with a checksum. This provides more reliable communication than SSI.
The encoders are also available with an integrated incremental track. The supply voltage for the encoder is 10-30V. The voltage source can be an external source or the internal
voltage (according to the frequency inverter version: 12V /15V /24V).
Table 8: Connection assignment for BISS encoders
2.3 CANopen absolute encoders
The connection of an absolute encoder to the SK 53xE / SK 54xE is carried out via the internal CANopen interface. As a minimum requirement, the absolute encoder to be connected must have a CAN Bus interface with CANopen protocol. The internal CAN Bus with CANopen protocol can be used for simultaneous control and parameterisation as well as the readout of the absolute encoder position.
The SK 53xE / SK 54xE supports CANopen absolute encoders with the communication profile DS 406. If an absolute encoder supplied by Getriebebau Nord GmbH & Co. KG is used, automatic parameterisation of the absolute encoder via the frequency inverter is possible. Only the CAN address and the baud rate of the encoder still need to be set with the rotary or dip switches on the encoder. All other necessary parameters are set by the frequency inverter via the CAN Bus in the encoder.
BU 0510 GB-3911 Subject to technical alterations 17
Manufacturer
Single-turn encoder
Multiple-turn encoder
Fritz Kübler
www.kuebler.com
Opto-mechanical encoders Type: Sendix 8.5878.XX2X.XXXX.XXXXX
Opto-mechanical encoders Type: Sendix 8.5888.XX2X.XXXX.XXXXX 10-30V DC
FRABA Posital
www.posital.de
No approval at present.
Please request if required
Opto-mechanical encoders Type: OCD-C2X1B-XXXX-XXXX-0CC 10-30V DC, 25Bit 8192 Inc/rev, 4096 rev
Baumer IVO
www.baumer.com
No approval at present.
Please request if required
Magnetic encoders Type: Multivo GOMMH.X205P32 10-30V DC, 29Bit Default setting: Node ID 1, 50KBd Can be parameterised
Supplier
Name
Part no.
WAGO Kontakttechnik GmbH
Ethernet connection module with CAGE CLAMP connection RJ45 transfer module
289-175
WAGO Kontakttechnik GmbH
Accessories: WAGO shield clamp
790-108
Alternative, complete connection module and shield clamp
Part No.
Getriebebau NORD GmbH & Co.KG
Adapter module RJ45/terminal
278910300
2.3.1 Approved CANopen absolute encoders
The following CANopen encoders (with bus cover) are approved:
Table 9: CANopen encoders approved by NORD
2.3.2 RJ45 WAGO adapter module
This adapter module can be used for the simple wiring of functions of the RJ45 connection (24V supply voltage, CANopen absolute encoder, CANbus) with normal cables.
Pre-assembled RJ45 patch cables are connected to the spring-loaded terminals (1-8 + S) with this adapter (for terminal assignments see the following section).
The shield clamp should be used in order to ensure the correct connection and relief of tension on the shield.
Fig. 5: RJ45 WAGO connection module
Table 10: Overview of RJ45 WAGO connection module
18 Subject to technical alterations BU 0510 GB-3911
2 Encoder connection
NOTE
Recommendation: To provide strain relief, the CAN cable can be connected to the screening angle of the EMC Kit (option). Details of the EMC Kit can be found in the BU0500 manual.
DIP switch and 2xRJ45 terminal block, CAN Bus (SK 520E/530E only)
1 CAN_H
CAN Bus signal
max. baud rate
...500kBaud
1 2
ON
DIP switch 2 for CAN Bus
termination resistor
R=120
CAN _H
CAN _L
CAN _GN D
nc
CAN _SHLD
CAN _GN DncCAN _24V
CAN _H
CAN _L
CAN _GN D
nc
CAN _SHLD
CAN _GN DncCAN _24V
RS48 5 _A
RS48 5 _B
GN D
TXD
RXD
+ 5V
RJ45: Pin No. 1 … 8
2 CAN_L
3 CAN_GND
CAN-Bus GND
4 nc
No function 5 nc
6 CAN_SHD
Cable shield
7 CAN_GND
GND / 0V
8 CAN_24V
External 24VDC +/- 25% voltage supply
(Load capacity at least 30mA)
SK 520E or higher: CAN interface, two RJ45
sockets, the bus termination resistor can be switched in.
2.3.3 Assignment of the CAN interface on the frequency inverter
The 24V supply for the absolute encoder and the CAN Bus/CANopen interface must be provided via an external supply. For the assignment of the terminals, please refer to the encoder manufacturer´s operating instructions.
Table 11: Contact assignment for the RJ45 interface
BU 0510 GB-3911 Subject to technical alterations 19
NOTE
With SK 5x5E devices the frequency inverter control unit must be supplied with power for a further 5 minutes after the last position change in order to permanently save the data.
3 Function description
3.1 Introduction
A wide range of positioning and position control tasks can be performed with the positioning function. In order to facilitate the decision as to which configuration provides the optimum solution for the task, the various processes for the setting of setpoints and recording of the actual values are described in the following sections.
The setpoint can be specified as either an absolute or a relative position. An absolute position is recommended for applications with fixed positions, for example with travelling trolleys, lifts, shelf access devices etc. A relative position is advisable primarily for all axes which operate in steps, especially for endless axes such as rotating platforms and pulsed compartmentalised conveyor belts.Specification of setpoints is also possible via the bus (e.g. Profibus, CAN-Bus, …). Here the position can be specified as a value or combination of bits as a position number or increment.
If switching between positioning and speed specifications is required, this can be realised by switching between parameter sets. A position regulation in parameter P600 "Positioning" is parameterised to "ON" in one parameter set and to "OFF" in another parameter set. Switching between the parameter sets can take place at any time, i.e. even during operation.
3.2 Position detection
3.2.1 Position detection with incremental encoders
For an absolute actual position, a reference point is needed, with the aid of which the zero position of the axis is determined. The position detection operates as long as the frequency inverter is supplied with power. The pulses of the incremental encoder are counted in the inverter and added to the actual position. The resolution or pulse number of the incremental encoder is set in parameter P301 "Incremental Encoder Pulse Number". By setting negative pulse numbers, the direction of rotation can be adapted to the installation orientation of the rotary encoder. After switching on the inverter supply voltage, the actual position = 0 (P604"Encoder Type" without the option "Save Position") or it is at the value which was present on shut-down (P604 "Encoder Type" with the option "Save Position").
The recording of the position functions independently of the enabling signal of the inverter and parameter P600 "Positioning". The inverter determines the actual position for as long as it is supplied with power. Changes in position which are carried out with the inverter switched off do not cause a change in the actual position. Therefore a reference point run is therefore normally necessary after each "Mains switch-on" of the frequency inverter.
If the inverter is not operated in Servo- Mode P300 "Servo Mode" the incremental encoder can also be mounted at another position than on the motor shaft. In this case, the speed ratio of the motor to the incremental encoder must be parameterised. Rotations of the incremental encoder are converted to motor revolutions by the inverter with the aid of parameter P607 "Speed Ratio" and P608 "Reduction Ratio".
nM: Motor rotations
nM = nG * Üb / Un nG:: Incremental encoder rotations
Üb: Speed Ratio (P607[-01])
Un: Reduction Ratio (P608[-01])
Example: The incremental encoder is installed on the output side of the gear unit. The gear unit has a ratio of i = 26.3. The
20 Subject to technical alterations BU 0510 GB-3911
following values are parameterised.
P607 Speed ratio: 263; P608 Reduction ratio: 10
NOTE
The direction of rotation of the incremental encoder must comply with the direction of rotation of the motor. With a positive output frequency (clockwise rotation) the actual position value must increase. If the direction of rotation is not correct, this can be adjusted with a negative value in P607 "Speed Ratio".
With the aid of a value which can be parameterised in parameter P609 [-01] "Offset Position" the zero point can be set to a different position to that which is determined by the reference point. The offset is applied after conversion of the encoder rotations to motor rotations. After changes to the speed ratio/reduction ratio P607 [-01] and P608 [-01] the offset position value must be entered again.
3.2.1.1 Reference point run via digital inputs or BUS I/O In bits
The Reference point run is started via one of the digital inputs or one of the Bus IO In bits. For this a digital input must be programmed for the appropriate function (P420-P425 or P470 "Function Digital Input", setting
22). For the Bus IO In Bits the corresponding Bit / Array (P480 "Bus IO In Bits", setting 22) must be parameterised. The direction of the reference point search is specified via the signals "Enable Left/Right". The current setpoint frequency determines the speed of the reference point run. Via one of the digital inputs the reference point is also read in. For this a digital input must be programmed for the appropriate function (P420-P425 or P470 "Function Digital Input", setting 23). For the Bus IO In Bits the corresponding Bit / Array (P480 "Bus IO In Bits", setting 23) must be parameterised.
In order to also realise the function "Reference Point Run" via a serial interface or via the Bus IO In bits, one of the "Bus Setpoint Values" (P546, P547 and P548) must be set to the setting "Bus IO In Bits 0...7" and under P480 "Function Bus I/O IN Bits" the function setting 22 must be assigned to the corresponding bit.
Sequence of the reference point run: With the reference point run enabled, the drive unit moves in the direction of its setpoint value (Enable Right/Left, +/- Setpoint). On reaching the reference point switch, the signal at the digital input or Bus IO In Bit "Reference Point" reverses the direction of travel. Therefore the drive unit moves away from the reference switch again.
If the drive unit is already at the switch at the start of the reference point run, the reference point run is immediately started with the inverse direction of rotation.
After leaving the switch, the actual position is set to the value which is set in parameter P609 "Offset Position". If the value in parameter P609 "Offset Position" is not "0" then the drive immediately moves to its new zero position and remains at this position until the "Reference Point Run" signal is removed.
In the setpoint mode P610 "Position Increment Array" = 1 (relative positioning) the setpoint position is simultaneously set to 0. With appropriate parameterisation of one of the parameters "Digital Output Function" (P434, P441, P450, P455, setting 20 - reference point), the frequency inverter reports the end of the reference point run with corresponding adoption of the reference point. The feedback for the end of the reference point run can also be reported via the Bus IO OUT bits (P481, "Bus IO Out Bits", setting 20).
If an incremental encoder without the function "Save Position" is used (See P604 "Encoder Type") the actual position in parameter P601 "Current Position" is set to "0" when the frequency inverter is switched on. For parameterisation with the function "Save Position" the last saved value is taken as the actual position.
The relay or output message "Reference Point" shows that a valid reference point is available. The relay or outputs are switched off when a reference point run is started and are switched on again after completion of the reference point run.
If the option "Save Position" (P604 "Encoder Type") is not selected (factory setting) the relay or the output are switched off when the inverter is switched on.
If the option "Save Position" is selected the relay or the output are switched on immediately after the inverter is switched on. Control via one of the Bus IO Bits is correspondingly identical.
BU 0510 GB-3911 Subject to technical alterations 21
3 Description of function
NOTE
In this case the frequency inverter does not generate an error message.
Parameter
Meaning
P605[-01] Multi-turn
Number of bits of rotations
P605[-02] Single-turn
Number of bits per one revolution
P605[-03] Sin/Cos periods, Hiperface
Number of bits for Sin/Cos periods per rotation
The reference point run can be cancelled by removing the "Enable" signal or by "Emergency Stop" or "Block Voltage".
For further details of the possible functionality settings, please refer to the relevant parameter description in Section 4 Parameter settings.
3.2.1.2 Reset position via digital inputs or BUS I/O In Bits
tAs an alternative to a reference point run, one of the digital inputs can be programmed to the setting "Reset Position" (P420-P425 or P470, setting 61). Control via one of the Bus IO Bits is correspondingly identical. In
contrast to the reference point function, the input or the Bus IO Bit is always effective and when the signal changes immediately sets the actual position from 0 → 1 to 0. If an offset has been parameterised in parameter P609 "Offset Position", the axis will be displaced by this value. Resetting of the position is carried out independently from the setting of the "Positioning" in parameter P600. In "Position Setpoint Mode" the setpoint position (in parameter P610, 1 = Position increment array) is set to 0.
The precision of reproducibility of the referencing via Reset Position is not as good as with the reference point run - as it depends on the tolerance of the reference point switch and the speed with which the switch is approached. However, the precision achieved is sufficient for many applications. In addition, referencing can be performed without interrupting the positioning.
The function "Reset Position" can also be realised via a serial interface or the Bus IO In Bits. For this, one of the bus setpoint values (P546, P547 and P548) must be set to 17 "Bus IO In bits 0...7" and under P480 "Function Bus I/O In Bits" the function setting 61 must be assigned to the corresponding bit.
For further details of the possible functionality settings, please refer to the relevant parameter description in Section 4.
3.2.2 Position detection with absolute encoders
The absolute encoder transfers the actual position value to the frequency inverter in digital form. The position is always completely available in the absolute encoder and is also correct after displacement of the axis when the inverter is switched off. A reference point run is therefore not necessary.
If an absolute encoder is connected, the parameter P604 "Encoder Type" must be parameterised to one of the absolute functions (Setting 1 or 5-15) of the relevant absolute encoder.
The resolution of the encoder is set in parameter P605.
Table 12: Parameter P605 - Selection of encoder resolution for absolute encoders
22 Subject to technical alterations BU 0510 GB-3911
3 Description of function
NOTE
The maximum possible position in parameter P615 "Maximum Position" results from the resolution of the encoder and the Speed Ratio/Reduction Ratio (P607 and P608). Under no circumstances can the maximum value exceed +/- 65535 (16Bit) rotations. Circulation is not permissible. Endless items, which mainly run in a single direction must be realised with an incremental encoder (See Section 3.2.1). Position setpoints should be internally limited to the maximum possible value range.
If the absolute encoder is not mounted on the motor shaft the gear ratio between the motor and the absolute encoder must be parameterised. Rotations of the absolute encoder are converted to motor revolutions by the inverter with the aid of parameter P607 "Speed Ratio" and P608 "Reduction Ratio".
nM: Motor rotations
nM = nG * Üb / Un nG:: Absolute encoder rotations
Üb: Speed Ratio (P607[-02])
Un: Reduction Ratio (P608[-02])
Example: The absolute encoder is installed on the output side of the gear unit. The gear unit has a ratio of i = 26.3. The
following values are parameterised.
Speed ratio: 263; Reduction ratio: 10
The direction of rotation of the absolute encoder must comply with the direction of rotation of the motor. With a positive output frequency (clockwise rotation) the actual position value must increase. If the direction of rotation is not correct, this can be adjusted with a negative value in P607 "Speed Ratio".
The zero point of the axis can be adjusted with the aid of value which can be parameterised in parameter P609 [-02] "Offset Position". The offset is applied after the calculation. After changes to the Speed Ratio/Reduction Ratio P607 [-02] and P608 [-02] the value in parameter P609 "Offset Position" must be entered again.
If the absolute encoder is not mounted on the motor shaft the gear ratio between the motor and the absolute encoder must be parameterised. Rotations of the absolute encoder are converted to motor revolutions by the inverter with the aid of parameter P607 "Speed Ratio" and P608 "Reduction Ratio".
nM: Motor rotations
nM = nG * Üb / Un nG:: Absolute encoder rotations
Üb: Speed Ratio (P607[-02])
Un: Reduction Ratio (P608[-02])
Example: The absolute encoder is installed on the output side of the gear unit. The gear unit has a ratio of i = 26.3.
The following values are parameterised.
Speed ratio: 263; Reduction ratio: 10
The direction of rotation of the absolute encoder must comply with the direction of rotation of the motor. With a positive output frequency (clockwise rotation) the actual position value must increase. If the direction of rotation is not correct, this can be adjusted with a negative value in P607 "Speed Ratio".
The zero point of the axis can be adjusted with the aid of value which can be parameterised in parameter P609 [-02] "Offset Position". The offset is applied after the calculation. After changes to the Speed Ratio/Reduction Ratio P607 [-02] and P608 [-02] the value in parameter P609 "Offset Position" must be entered again.
BU 0510 GB-3911 Subject to technical alterations 23
P514
Baud rate
[kBaud]
P552 [-01]
Default CAN
Master
[ms]
P552 [-02]
Default CANopen Absolute encoder
[ms]
P552 [-02]
Minimum value for
actual cycle time
[ms]
Bus load caused by
an encoder
[%]
10
50
20
10
42.5
20
25
20
10
21.2
50
10
10 5 17.0
100 5 5 2 17.0
125 5 5 2 13.6
250 5 2 1 17.0
500 5 2 1 8.5
10001 5 2 1 4.25
1
3.2.2.1 Supplementary settings - SSI absolute encoders
Protocol settings for SSI encoders are made in parameter P617. In detail, this defines:
the format in which the positions are transferred (binary / Gray code),  whether a loss of voltage to the encoder is communicated to the FI ("Power Fail Bit") and  whether the encoder supports the communication version "Multiply Transmit" for which the position is
communicated a second time in a mirrored form in order to improve the reliability of the transfer.
3.2.2.2 Supplementary settings - CANopen absolute encoders
The baud rate and the CAN address must be set on the encoder. For the assignment of the switches on the encoder, please refer to the manufacturer´s operating instructions.
The CAN address for the absolute encoder should be set in parameter P515 "CAN Address" according to the following formula:
Encoder CAN address = Inverter CAN address (P515[-01] ) + 1
The CAN baud rate set in the encoder must be identical to the parameter P514 "CAN Baud Rate" and all other participants in the bus system.
If parameterisation of the encoder is carried out via the frequency inverter, the transmission cycle for the absolute encoder position is simultaneously set via the baud rate.
For the operation of several CANopen absolute encoders on a bus system, e.g. for synchronous operation, different transmission cycle times can be set for the CAN master and the CANopen absolute encoders.
With the parameter P552 "CAN Cycle Time" the cycle time for the system bus master mode can be parameterised in Array [-01 and for the CANopen absolute encoder in Array [-02]. Care must be taken that the parameterised values are not lower than the values in the column for the minimum values of the actual cycle time. This value depends on the baud rate set in parameter P514 "CAN Baud Rate".
Table 13: Encoder cycle time dependent on the baud rate
The possible bus load in the system always depends on the real-time specific to the system. Very good results are achieved with a bus load less than 40%. Under no circumstances should a bus load greater than 80% be selected. For the estimation of the bus load, the other possible bus traffic (setpoint and actual values for the FIs and other bus participants) should also be taken into account.
Additional explanations about the CAN interface can be obtained from Manual BU 0060.
Only for testing purposes. Reliable operation is not guaranteed.
24 Subject to technical alterations BU 0510 GB-3911
3 Description of function
NOTE
If an IO extension (e.g. SK TU4-IOE) is also used, it must be noted that the addresses 10 … 13 and 20 … 23 are reserved for this module (For details see Manual BU0200).
Parameter
Meaning
Availability
Setting example
P605 [-01]
Multi-turn resolution in bits
SK 530E and
above
12
4096 Encoder rotations
25Bit
encoder
P605 [-02]
Single-turn resolution in bits
SK 530E and
above
13
8192 Steps per rotation
P605 [-03]
Sin/Cos periods per rotation (Hiperface)
SK 540E and
above
3.2.2.3 Resetting absolute encoders
With the exception of SSI encoders, absolute encoders can be set to the value "0" or to the value set in P609 [­02] "Offset Position" via the functions "Reference Point Run"(see 3.2.1.1).
However, the precision of resetting the encoder position greatly depends on the actual speed of movement, the bus load, the baud rate (CANopen encoders) and the type of encoder. Therefore it is urgently recommended that absolute encoders are only reset when they are at a standstill.
With an SSI encoder the position can only be changed via a position offset P609 [-03]. Resetting ("Reset position" / "Reference Point Run") is not possible.
If both an incremental encoder and an absolute encoder are connected to the frequency inverter, both encoders are reset by performing the functions "Reference Point Run" or "Reset Position".
3.2.2.4 Parameterisation on the frequency inverter
Communication settings If a CANopen absolute encoder is used for position detection, the CAN baud rate (P514) and the CAN
address (P515) must be parameterised on both the encoder and the frequency inverter.
After this, the CAN Bus must be supplied with 24V in order to activate communication between all the connected participants.
For all other absolute encoders such as Endat, SSI, … (SK 540E and above), no communication settings are required between the frequency inverter and the associated encoder.
Encoder data settings The resolution of the absolute encoder is set via the parameter P605 "Absolute Encoder":
Table 14: Parameter P605 - Setting of encoder resolution for absolute encoders The relevant settings should be obtained from the data sheet for the absolute encoder.
The absolute encoder is activated via parameter P604 "Encoder Type". Here, a differentiation is made between normal measurement (for "linear" systems) and "path optimised" measurement (for circulating systems) (see Section 3.2.4).
BU 0510 GB-3911 Subject to technical alterations 25
Loading...
+ 56 hidden pages