NORD BU0505 User Manual

GB
BU 0505
SK 54xE
Users Manual for Frequency Inverters
SK 54xE – Users Manual for Frequency Inverters
During operation, drive power converters may, depending on their protection class, have live, bare, moving or rotating parts or hot
carried out by qualified personnel (comply with IEC 364,
CENELEC HD 384, DIN VDE 0100, IEC 664 and DIN VDE 0110, and
amiliar with the assembly, installation,
Drive power converters are components intended for installation in
When installed in machines, the drive power converter cannot be ensured that the machine meets the provisions of the EC Directive
lso be complied
e installation and cooling of the equipment must be implemented
The drive power converter must be protected against
and handling, components must not be deformed and/or insulation dis tances must not be changed. Touching of electronic components and
Drive power converters have electrostatically sensitive
by incorrect
handling. Electrical components must not be mechanically
When working on live drive power converters, the applicable
t be complied with
section, fuses, ground
lead connections). Further instructions can be found in the
such as shielding, earthing, location of filters and installation of cables can be found in the drive power converter documentation.
rters. Compliance with the limiting values
specified in the EMC regulations is the responsibility of the
Where necessary, systems where drive power converters are
l monitoring and protective equipment according to the applicable safety requirements, e.g. legislation concerning technical equipment,
The parameterisation and configuration of the drive power
supply, live equipment components and power connections
ately, because of possible
charged capacitors. Observe the relevant information signs
NORD frequency inverters

Safety and operating instructions for drive power converters

(as per: Low Voltage Directive 2006/95/EEC )
1. General
surfaces. Unauthorised removal of covers, improper use, incorrect ins tallation or
operation causes a risk of serious personal injury or material damage. Further information can be found in this documentation. All transportation, installation and initialisation and maintenance work
must be national accident prevention regulations).
For the purposes of these basic safety inst ructions, qualified personnel are persons who are f commissioning and operation of this product and who have the relevant qualifications for their work.
2. Proper use in Europe
electrical systems or machines.
commissioned (i.e. commencement of the proper use) until it has been 2006/42/EEC (machine directive); EN 60204 must a
with. Commissioning (i.e. implementation of the proper use) is only permitted
when the EMC directive (2004/108/EEC) is complied with. Drive power converters with the CE mark meet the requirements of the
Low Voltage Directive 2006/95/EEC. The harmoni zed standards stated in the Declaration of Conformity are used for the drive power converters.
Technical data and information for connec tion conditions can be found on the rating plate and in the documentation, and must be complied with.
The drive power converters may only be used for the safety functions which are described and for which they have been explicitly approved.
3. Transport, storage
Information regarding transport, storage and correct handling must be complied with.
4. Installation
Th according to the regulations in the corresponding documentation.
These safety instructions must be kept in a safe place!
Pos: 3 /Anl eitungen/El ektronik/ FU un d Starter/0. Pr ol og / 0.2 Bestimm u ngsgemäße V erwendung der Freq uenzumr ic ht er [BU 0500] @ 0\ mod_1325778851914_388.docx @ 5224 @ @ 1
impermissible loads. Especially during transport
contacts must be avoided.
components, which can be easily damaged damaged or destroyed (this may cause a health hazard!).
5. Electrical connections
national accident prevention regulations mus (e.g. VBG A3, formerly VBG 4).
The electrical installation must be implemented according t o the applicable regulations (e.g. cable cross-
documentation. Information about EMC-compliant installation –
These instructions must be compl ied with even with CE m arked drive power conve
manufacturer of the system or machine.
6. Operation
installed must be equipped with additiona
accident prevention regulations, etc.
converter must be selected so that no hazards can occur. All covers must be kept closed during operation.
7. Maintenance and repairs
After the drive power converter is di sconnected from the power should not be touched immedi located on the drive power converter.
Further information can be found in this documentation.
2 BU 0505 GB-1013
Intended use of the frequency inverter

Intended use of the frequency inverter

Compliance with the operatin g instructions is neces sary for fault-free operation and the acceptance of any warranty claims. These operating instructions must be read before working with the device!
These operating instructions contain important information about servicing. They must therefore be kept close to the device.
SK 500E series frequency inverters are devices for industrial an commercial systems used for the operatio n of three-phase as ynchronous motors with squirr el­cage rotors and Permanent Magnet Synchronous Motors – PMSM (SK 54xE and above) These motors must be suitable for o peration with f requency inverters, othe r loads must not be connected to the devices.
SK 5xxE frequency inverters are devices for stationary installation in control cabinets. All details regarding technical data and permissible conditions at the installation site must be complied with.
Commissioning (com mencement of the intended use) is not perm itted until it has been ensured that the machine complies with the EMC Directive 2004/108/EEC and that the conformity of the end product meets the Machinery Directive 2006/42/EEC (observe EN 60204) .
Pos: 5 /Anl eitungen/El ektronik/ FU und Star ter/0. Pr olog/0.3 Do kumentatio n - Versions l is t e [BU 0505] @ 2\mod_1355497664709_388.docx @ 52474 @ @ 1
Getriebebau NORD GmbH & Co. KG, 2013
BU 0505 GB-1013 3
SK 54xE – Users Manual for Frequency Inverters
SK 5xxE-250-323-A ... SK 5xxE-221-323-A
SK 5xxE-550-340-A ... SK 5xxE-902-340-A

Documentation

Name: BU 0505 Part No.: 607 50 51 Series: SK 500E FI series: SK 540E / SK 545E FI types:
SK 5xxE-250-112-O ... SK 5xxE-750-112-O
SK 5xxE-301-323-A ... SK 5xxE-182-323-A

Version list

Name of previous issues Software
Version
BU 0505 DE, March 2013
Part No. 607 5052 / 1013
Table 1: Version list
Pos: 8 /Anl eitungen/El ektronik/ FU und Star ter/0. Pr olog/0.4 Her ausgeber @ 0\mod_1325779078002_388.docx @ 5270 @ @ 1
V 2.0 R5 First issue,
(0.25 – 0.75kW, 1~ 115V, output 3~ 230V)
0.25 - 2.2kW, 1/3~ 230V, output 3~ 230V) (3.0 – 18.0kW, 3~ 230V, output 3~ 230V) (0.55 – 90.0kW, 3~ 400V, output 3~ 400V)
Remarks
based on BU 0500 DE (Part No.: 6075001/1013)

Publisher

Getriebebau NORD GmbH & Co. KG
Rudolf-Diesel-Str. 1 D-22941 Bargteheide http://www.nord.com/ Tel.: +49 (0) 45 32 / 289-0 Fax +49 (0) 45 32 / 289-2555
=== Ende der Liste für Textmarke Copyright ===
4 BU 0505 GB-1013
Publisher
BU 0505 GB-1013 5
SK 54xE – Users Manual for Frequency Inverters
Pos: 10 /Anl eitungen/ Steuermod ule/Inhalts verzeichni s @ 0\mod_1317978518480_388.docx @ 4078 @ @ 1

Table of Contents

=== Ende der Liste für Textmar ke Inhaltsver zeichnis == =
1. General ....................................................................................................................................................... 10
1.1 Overview .......................................................................................................................................... 10
1.2 Delivery ............................................................................................................................................ 12
1.3 Scope of delivery.............................................................................................................................. 12
1.4 Safety and installation information ................................................................................................... 12
1.4.1 Explanation of labels used .................................................................................................. 13
1.4.2 List of Safety and installation information ........................................................................... 13
1.5 Certifications .................................................................................................................................... 15
1.5.1 European EMC Directive .................................................................................................... 15
1.5.2 UL and cUL approvals for frequency inverters (CSA) ......................................................... 15
1.5.3 C-Tick labelling - No. N 23134 ............................................................................................ 18
1.5.4 RoHS compliant .................................................................................................................. 18
1.6 Type codes / Device versions .......................................................................................................... 18
2. Assembly and installation ........................................................................................................................ 21
2.1 SK 5xxE, standard version ............................................................................................................... 22
2.2 SK 5xxE…-CP in ColdPlate version ................................................................................................. 23
2.3 External heat sink kit ........................................................................................................................ 24
2.4 Snap-on mounting rail kit SK DRK1-… ............................................................................................ 26
2.5 EMC Kit ............................................................................................................................................ 27
2.6 Brake resistor (BR)........................................................................................................................... 28
2.6.1 Electrical data, brake resistor ............................................................................................. 29
2.6.2 Dimensions of bottom-mounted BR SK BR4 ...................................................................... 30
2.6.3 Dimensions, bra ke re sistor chassis SK BR2 ...................................................................... 32
2.7 Mains choke SK CI1......................................................................................................................... 33
2.8 Output choke SK CO1 ...................................................................................................................... 34
2.9 Line filter .......................................................................................................................................... 36
2.10 Electrical connections ...................................................................................................................... 38
2.10.1 Wiring guidelines ................................................................................................................ 39
2.10.2 Adaptation to IT networks ................................................................................................... 40
2.10.3 DC-coupling ........................................................................................................................ 42
2.10.4 Electrical connections, power unit ...................................................................................... 45
2.10.5 Electrical connections, control unit ..................................................................................... 47
2.11 Colour and contact assignments for encoders ................................................................................. 59
2.12 RJ45 WAGO- Connection module ................................................................................................... 63
2.13 Setpoint card ± 10V .......................................................................................................................... 64
3. Displays and control ................................................................................................................................. 65
3.1 Modular assemblies SK 5xxE .......................................................................................................... 65
3.2 Overview of technology units ........................................................................................................... 66
3.3 SimpleBox, SK CSX-0 ...................................................................................................................... 68
4. Commissioning ......................................................................................................................................... 71
4.1 Factory settings ................................................................................................................................ 71
4.2 Minimal configuration of contro l conne ctio ns ................................................................................... 72
4.3 KTY84-130 connection (above software version 1.7)....................................................................... 73
4.4 Frequency addition and subtraction via operating boxes ................................................................. 74
5. Parameters ................................................................................................................................................. 75
6. Operating status messages ................................................................................................................... 148
6.1 Display of messages ...................................................................................................................... 148
6.2 Messages ....................................................................................................................................... 149
7. Technical data ......................................................................................................................................... 157
7.1 General Data SK 500E ................................................................................................................... 157
7.2 Electrical data ................................................................................................................................ 158
7.2.1 Electrical data 115V .......................................................................................................... 158
6 BU 0505 GB-1013
Table of Contents
7.2.2 Electrical data 230V .......................................................................................................... 159
7.2.3 Electrical data 400V .......................................................................................................... 161
7.3 General conditions for ColdPlate technology ................................................................................. 164
8. Additional information ............................................................................................................................ 166
8.1 Setpoint processing........................................................................................................................ 166
8.2 Process controller .......................................................................................................................... 168
8.2.1 Process controller application example ............................................................................ 168
8.2.2 Process controller parameter settin gs .............................................................................. 169
8.3 Electromagnetic Compatibility (abbreviation: EMC) ...................................................................... 170
8.4 EMC limit value classes ................................................................................................................. 170
8.5 Reduced output power ................................................................................................................... 172
8.5.1 Increased heat dissipation due to pulse frequency ........................................................... 172
8.5.2 Reduced overcurrent due to time ..................................................................................... 172
8.5.3 Reduced overcurrent due to output frequency.................................................................. 173
8.5.4 Reduced output current due to mains voltage .................................................................. 175
8.5.5 Reduced output current due to the heat sink temperature ................................................ 175
8.6 Operation with FI circuit breakers ................................................................................................... 175
8.7 Energy Efficiency ........................................................................................................................... 176
8.8 Standardisation of setpoint / target values ..................................................................................... 177
8.9 Definition of setpoint and actual value processing (frequencies) ................................................... 178
9. Maintenance and servicing information ................................................................................................ 179
9.1 Maintenance Instructions ............................................................................................................... 179
9.2 Repair information .......................................................................................................................... 180
9.2.1 Repairs ............................................................................................................................. 180
9.2.2 Internet information ........................................................................................................... 180
9.3 Abbreviations ................................................................................................................................. 181
BU 0505 GB-1013 7
SK 54xE – Users Manual for Frequency Inverters
Pos: 12 /Anl eitungen/ Steuermod ule/Abbildu ngsverzeic hnis @ 0\mod_1317978515699_388.docx @ 3917 @ @ 1

List of illustrations

=== Ende der Liste für Textmar ke Abbildung sverzeich nis ===
Fig. 1 SK 5xxE and accessories ............................................................................................................................ 19
Fig. 2 Frequency inverter type plate (example) ..................................................................................................... 20
Fig. 3 Mounting distances for SK 5xxE .................................................................................................................. 21
Fig. 4 EMC Kit SK EMC2-x .................................................................................................................................. 27
Fig. 5: Top: bottom-mounted brake resistor SK BR4- Bottom: chassis brake resistor SK BR2-... ......................... 28
Fig. 6 Diagram of a DC-coupling ........................................................................................................................... 43
Fig. 7 Diagram of a DC coupli ng w ith an input/f ee dba ck uni t ................................................................................ 44
Fig. 8: Dimensions of setpoint card± 10V .............................................................................................................. 64
Fig. 9: Mod ular ass emblies SK 5xxE ..................................................................................................................... 65
Fig. 10 SimpleBox SK CSX-0 ................................................................................................................................ 68
Fig. 11 Top side of FI with RJ12 / RJ45 connection ............................................................................................. 68
Fig. 12: SimpleBox, SK CSX-0 menu structure ..................................................................................................... 70
Fig. 13 Motor type plate ......................................................................................................................................... 71
Fig. 14: Setpoint processing ................................................................................................................................ 167
Fig. 15: Process controller flow diagram .............................................................................................................. 168
Fig. 16: Heat losses due to pulse frequency ........................................................................................................ 172
Fig. 17: Output current due to mains voltage ....................................................................................................... 175
Fig. 18 Energy efficiency due to automatic flux optimisation ............................................................................... 176
8 BU 0505 GB-1013
List of tables
Pos: 14 /Anl eitungen/ Steuermod ule/Tabell en v er z eichnis @ 0\mod_1317978519199_388.docx @ 4124 @ @ 1

List of tables

=== Ende der Liste für Textmar ke Tabellen verzeichnis ===
Table 1: Version list ................................................................................................................................................. 4
Table 2: Overview of SK 500E performance grading featur es ............................................................................... 11
Table 3: Overview of differing hardware features .................................................................................................. 11
Table 4: EMC Kit SK EMC2-x .............................................................................................................................. 27
Table 5: Electrical data for brake resistor SK BR2-… and SK BR4-… .................................................................. 29
Table 6: Brake resistor temperature switch data ................................................................................................... 30
Table 7: Dimensions of bottom-mounted brake resistor SK BR4-... ...................................................................... 30
Table 8: Dimensions of chassis brake resistor SK BR2-... .................................................................................... 32
Table 9: Mains choke data for SK CI1-..., 1~ 240 V .............................................................................................. 33
Table 10: Mains choke data for SK CI1-..., 3~ 240 V ............................................................................................ 33
Table 11: Mains choke data for SK CI1-..., 3~ 480 V ............................................................................................ 34
Table 12: Output choke data for SK CO1-..., 3~ 240 V.......................................................................................... 35
Table 13: Output choke data for SK CO1-..., 3~ 480 V.......................................................................................... 35
Table 14: Mains filter NHD-... ................................................................................................................................ 36
Table 15: Mains filter LF2-... .................................................................................................................................. 36
Table 16: Mains filter HLD-... ................................................................................................................................. 37
Table 17: Mains filter SK CIF-................................................................................................................................ 37
Table 18: Integrated mains filter ............................................................................................................................ 40
Table 19: Tools 45
Table 20: Connection data .................................................................................................................................... 45
Table 21: Colour and contact assignments for NORD TTL incremental encoders ................................................ 60
Table 22: Colour and contact assignment for SIN/COS encoders ......................................................................... 61
Table 23: Signal details for SIN/COS encoders ..................................................................................................... 61
Table 24: Signal details for Hiperface encoders .................................................................................................... 62
Table 25: Colour and contact assignment for Hiperface encoders ........................................................................ 62
Table 26: RJ45 WAGO connection module ........................................................................................................... 63
Table 27: Setpoint card ± 10V ............................................................................................................................... 64
Table 28: Overview of Technology Units and Control Boxes ................................................................................. 66
Table 29: Overview of Technology Units and Bus Systems .................................................................................. 66
Table 30: Overview of technology units, other optional modules ........................................................................... 67
Table 31: SimpleBox SK CSX-0, functions ............................................................................................................ 69
Table 32: Technical data, ColdPlate 115V / 230V devices .................................................................................. 164
Table 33: Technical data, ColdPlate 400V devices ............................................................................................. 165
Table 34: Overview of standards according to product standard EN 61800-3 ..................................................... 171
Table 35: Overcurrent relative to time ................................................................................................................. 173
Table 36: Overcurrent relative to pulse and output frequency ............................................................................. 174
Table 37: Scaling of setpoints and actual values (Selection) ............................................................................... 177
Table 38: Processing of setpoints and actual values in the frequency inverter ................................................... 178
Pos: 16 /Anl eitungen/ Elektroni k/FU und Star ter/1. All gemeines/ 1. Allgemei n es [BU 0 50 0] @ 0\ mod_1325779554274_388.docx @ 5293 @ 1 @ 1
BU 0505 GB-1013 9
SK 54xE – Users Manual for Frequency Inverters
resistors, filters etc.) may also be subject to modifications.

1. General

The SK 500E series is based on the tried and tested NORD platform. These devices feature a compact design with optimum control characteristics.
These frequency inverters are provided with sensorless vector current control system which in combination with as ynchronous three-ph ase motor types constan tly ensures an optim ised voltage-to­frequency ratio. For the drive unit, this means very hi gh starting and overload torques with constant speed.
As standard, the freque ncy inverters are eq uipped with a fixed heat sink, via whic h the power losses are dissipated to the environment. Altern atively, for sizes 1 - 4 there is the ColdPlate versi on and for sizes 1 and 2 there is also an external heat sink version.
This series of frequenc y inverters can be adapte d to indivi dual requirem ents b y means of t he modular technology units.
Due to the wide range of setting options, these inverters can control all three-phase motors. The power range is from 0.25 kW to 90.0 kW with integrated mains filter.
This manual is base d on the d evice soft ware as state d in the ver sion list (s ee P707). If the frequenc y inverter uses a diff erent s oftw are v ers ion, t his may cause differences. If nec ess ar y, the current manual can be downloaded from the Internet (http://www.nord.com/
).
There are additional descriptions for the optional functions "Functional Safety "(BU 0530) and the "POSICON" positioning system (BU 0510) and the memory programmable "PLC" control units (BU0550). Supplementary descriptions for the optional bus systems are also available
http://www.nord.com/
).
Note
The accessories mentioned in the manual (brake Current details of these are included in separate data sheets, which are listed under www.nord.com unde r the heading Documentation → Manuals → Frequency inverters → Data sheets. The data sheets available at the date of publication of this manual are listed by name in the relevant sections (TI ...).
Accessories
Pos: 17 /Anl eitungen/ Elektroni k/FU und Star ter/1. All gemeines/ 1.1 Überblic k -1- [BU 0500] @ 0\mod_1325779961835_388.docx @ 5316 @ 2 @ 1

1.1 Overview

Properties of the basic frequency inverter SK 500E:
• High starting torque and precise motor speed control setting with sensorless current vector control
• Can be mounted next to each other without addit ion al spac ing
• Permissible ambient temperature range 0 to 50°C (please refer to the technical data)
• Integrated EMC mains filter for limit curve A1 (and B1 for size 1 - 4 devices) as per EN55011 (not for 115V devices)
• Automatic measurement of the stator resistance or determination of the precise motor data
• Programmable direct current braking
• Integrated brake chopper for 4 quadrant operation (optional brake resistors)
• Four separate online switchable parameter sets
• RS232/485 interface via RJ12 plug connector
• USS-integrated (see BU 0050)
10 BU 0505 GB-1013
1 General
Safe pulse block (STO / SS1)*
x x x x BU 0530
2 x CANbus/CANopen interfaces via RJ45 plug
RS485 interface additionally via terminals
x x x
Speed feedback via incremental encoder input
Integrated “POSICON” positioning control
x x BU 0510
CANopen absolute encoder evaluation
x x BU 0510
PLC / SPS – functionality
x BU 0550
(SSI, BISS, Hiperface, EnDat and SIN/COS)
Operation of PMSM Modbus RTU
x BU 0050
5 / 3 6 / 2
7 / 1
Additional potential-isolated PTC input***
x
Number of analog inputs / outputs
2 / 1
2 / 1
2 / 1
2 / 1
2 / 1
2 / 1
Number of relay messages
2 2 2 2 2 2
External 24V supply voltage. Communication with the frequency inverter is
External 24V supply voltage with automatic switchover to the internal 24V low
Feature SK … 50xE 51xE 511E 520E 53xE 54xE
Operating manual BU 0500 BU 0505
Additional
options
x x x x BU 0060
x x x
Universal encoder interface
x BU 0510
(Permanent Magnet Synchronous Motors)
x
Number of digital inputs / outputs** 5 / 0 5 / 0 5 / 0 7 / 2 7 / 2
* not with 115 V devices ** SK 54xE: 2 I/Os can be variably parameterised as inputs or outputs *** alternative "thermistor" function on digital input 5 possible (above size 5 an additional thermistor input is available as standard)
Table 2: Overview of SK 500E performance grading features
Pos: 18 /Anl eitungen/ Elektroni k/FU und Star ter/1. All gemeines/ 1.1 Überbl ick -2- Abweichende Hardwareeigenschaften [BU 0500] @ 1\mod_1340695009508_388.docx @ 28170 @ @ 1
Differing hardware features
Version Description
SK 5xxE--CP compared with SK 5xxE
SK 5x5E compared with SK 5x0E
For size 5 and above in comparison with sizes 1 – 4 (> 4 kW, 230V or > 11 kW, 400V)
Table 3: Overview of differing hardware features
Pos: 19 /Anl eitungen/ Elektroni k/FU und Star ter/1. All gemeines/ 1.2 Lieferu ng @ 0\mo d_1325780242208_388.docx @ 5339 @ 2 @
ColdPlate or external heat sink
possible even without a power connection
Additional, separately mounted PTC input (potential isolated)
voltage generator on failure of the external control voltage.
Processing of both bipolar and analog signals
2 x CANbus/CANopen interfaces via RJ45 plug as standard
BU 0505 GB-1013 11
SK 54xE – Users Manual for Frequency Inverters
RS485 (supplementary description BU 0010), NORD CON PC
, ePlan macros for creating
1

1.2 Delivery

Check the equipm ent immediately after d el ivery/unpacking for tr ansport damage such as def or mation or loose parts.
If there is any damage, contact the carrier immediately and carry out a thorough assessment.
Important! This also applies even if the packaging is undamaged.
Pos: 20 /Anleit u ng e n/Elektro ni k/FU und Start er / 1. Allgemei n es / 1. 3 Lieferumfa ng [BU 0500] @ 0\ mod_1325780384629_388.docx @ 5362 @ 2 @ 1

1.3 Scope of delivery

Standard version: IP20
Integrated brake chopper Integrated EMC mains f ilter for limit curve A1 as per EN55011 (not for 115V
devices) Blanking cover for technology unit slot Screening terminal for control terminals Covering for the control terminals Size 1 to Size 7: Accessory bag with wall mounting br a ck ets Size 8 and above: miscellaneous electrical connection material Operating instructions on CD
Available accessories:
Braking resistor, mains filter, mains chokes, output chokes, link circuit choke (size 8 and above), EMC kit (SK EMV ...), el ectronic brake rec tifier SK EBGR-
1), IO extension for SK 54xE (SK EBIOE-2), interface converter RS232 parameterisation software > www.nord.com <
electrical circuit diagrams > www.nord.com <
Technology units for clipping onto the frequency inverter for control and
parameterisation or as communication interface for various bus systems.
Pos: 21 /Anl eitungen/ Elektroni k/FU und Star ter/1. All gemeines/ 1.4 Sicher heits- und In st allationshi nweise @ 0\mod_1325780428207_388.docx @ 5385 @ 2 @ 1

1.4 Safe ty and installation information

NORD frequency inverter s are equipment for use in industrial high volt age systems and ar e operated at voltages that could lead to severe injuries or death if they are touched.
The frequency inverter a nd its acc es sor ies must only be us ed f or th e p ur pose w hic h is int en ded by the manufacturer. Unauthor ised modifications and the use of spare par ts and additional equipm ent which has not been purchased from or recommended by the manufacturer of the frequency inverter may cause fire, electric shock and injury.
All of the associated covers and protective devices must be used. Installation and other work may only be carried out b y qualified electr icians with strict adherenc e to the
operating instructions. Therefore keep these Operating Instructions at hand, together with all supplementary instructions for any options which are used, and give them to each user.
Local regulations for the installation of electrical equ ipm ent and accident pre vention m ust be complied with.
Pos: 22 /Anl eitungen/ Elektroni k/FU und Star ter/1. All gemeines/ 1.4.1 Erläu terung d er verwendet en Kennzei chnungen @ 1\mod_1341559156309_388.docx @ 30301 @ 3 @ 1
12 BU 0505 GB-1013
1 General
Indicates a possibly dangerous situation, which may result in death or
Indicates a possibly dangerous situation, which may result in slight or
terminals, contact rails and supply cables as well as the PCBs) will cause electric shock with possibly fatal
circuit), the line connection terminals, motor terminals and braking resistor terminals, contact rails, PCBs and supply cables may still conduct hazardous voltages. A motor standstill is not identical to electrical isolation from
after the mains have been switched off! (The equipment may continue to carry hazardous voltages for
has been disconnected from the mains, a connected motor may rotate and possible
generate a dangerous voltage. Touching electrically conducting components may then cause an electric shock
The voltage supply of the frequency inverter may directly or indirectly put it into operation, or touching electrically

1.4.1 Explanation of labels used

DANGER
WARNING
CAUTION
Note
NOTICE
Indicates an immediate danger, which may result in death or serious injury .
serious injury.
minor injuries.
Indicates a possibly harmful situation, which may cause damage to the product or the environment.
Indicates hints for use and useful information.
Pos: 23 /Anl eitungen/ Elektroni k/FU und Star ter/1. All gemeines/ 1.4.2 Aufli stung der Sicherheits - und Inst allationshi nweise @ 1\ mod_1341560303401_388.docx @ 30325 @ 3 @ 1

1.4.2 List of Safety and installation information

DANGER
The frequency inverter operates with a dangerous voltage. Touching certain conducting components (connection consequences.
Even when the motor is at a standstill (e.g. caused by an electronic block, blocked drive or output terminal short-
Danger of electric shock
the mains. Only carry out installations and work if the device is disconnected from the voltage and wait at least 5
minutes up to 5 minutes after being switched off at the mains).
Follow the 5 Safety Rules (1. Switch off the power, 2. Secure against switching on, 3, Check for no voltage, 4. Earth and short circuit, 5. Cover or fence off neighbouring live components).
DANGER
Even if the drive unit with possible fatal consequences.
Therefore prevent connected motors from rotating.
WARNING
conducting components may then cause an electric shock with possible fatal consequences. Therefore, all poles of the voltage supply must be disconnected. For devices with a 3-phase supply,
L1 / L2 / L3 must be disconnected. For devices with a single phase supply, L1 / N must be disconnected. For devices with a DC supply, –DC / +B must be disconnected. Also, the motor cables U / V / W must be disconnected.
Danger of electric shock
Danger of electric shock
BU 0505 GB-1013 13
SK 54xE – Users Manual for Frequency Inverters
Because of this, the frequency inverter is only intended for permanent connection and may not be operated
50178 / VDE 0160 stipulates the installation of a second earthing conductor or an earthing conductor with a
when the mains are switched on. The machinery which it drives (press / chain hoist / roller / fan etc.) may then
Before switching on the mains, secure the danger area by warning and removing all persons from the danger
h suitable measuring equipment. In addition, keep sufficient distance from adjacent
Failure to comply with this may cause damage to the frequency inverter due to impermissible currents in the
The frequency inverter is a product which is intended for use in an industrial environment and is subject to sales
WARNING
In case of a fault, insufficient earthing may cause an electric shock with possibly fatal consequences if the device is touched.
without effective earthing connections which comply with local regulations for large leakage currents (> 3.5mA). EN
cross-section of at least 10mm2.
WARNING
With certain setting conditions, the frequency inverter or the motor which is connected to it may start automatically make an unexpected movement. This may cause various injuries, including to third parties.
area.
CAUTION
The heat sink and all other metal components can heat up to temperatur es abov e 70°C . Touching such components may cause local burns to the affected parts of the body (hands, fingers, etc.). To prevent such injuries, allow sufficient time for cooling down before starting work - the surface temperature
should be checked wit components during installation, or install protection against contact.
Danger of electric shock
Danger of injury if motor starts
Danger of burns
NOTICE
For single phase operation (115/230V) the mains impedance must be at least 100µH for each conductor. If this is not the case, a mains choke must be installed.
components.
NOTICE
restrictions according to IEC 61800-3. Use in a residential environment may require additional EMC measures. For example, electromagnetic interference can be reduced by the use of an optional mains filter.
Damage to the frequency inverter
EMC - Interference
14 BU 0505 GB-1013
1 General
ains filters, mains units and capacitor banks),
NOTICE
ide branch circuit protection. Branch circuit protection
provided in accordance with the manufacturer's instructions, the "National Electric Code" and all additional local
Note
NOTICE
Leakage and residual currents
Due to their principle of operation (e.g. due to integrated m frequency inverters generate leakage currents. For the correct operation of the frequency inverter on a current­sensitive RCD, the use of an all-current sensitive earth leakage circuit breaker (Type B) compliant with EN 50178 / VDE 0160 is necessary.
Note
Operation on TN- / TT- / IT- networks
The frequency inverters are suitable for operation on TN or TT networks as well as for IT networks with the configuration of the integrated mains filter.
Note
Maintenance
In normal use, frequency inverters are maintenance free. The cooling surfaces must be regularly cleaned with compressed air if the ambient air is dusty. In case of long-term shut-down or long-term storage, the capaci tor s must be re-formed (refer to "Technical Data"). Failure to do this will damage these components and will cause a considerable reduction of the service life -
including the immediate destruction of the frequency inverter.
Pos: 24 /Anl eitungen/ Elektroni k/FU und Star ter/1. All gemeines/ 1.5 Zulass ungen @ 0\ mod_1326111302308_388.docx @ 6223 @ 2 @ 1

1.5 Certifications

Pos: 25 /Anl eitungen/ Elektroni k/FU und Star ter/1. All gemeines/ 1.5.1 Eur opäische EM V-Richtlinie @ 0\mod_1325780630565_388.docx @ 5431 @ 3 @ 1

1.5.1 European EMC Directive

If the frequency inverter is installed according to the recommendations in this manual, it meets all EMC directive requirements, as per the EMC prod uc t s tandar d f or m ot or -operated systems EN 618 00-
3.
Pos: 26 /Anl eitungen/ Elektroni k/FU und Star ter/1. All gemeines/ 1.5.2 Zulas sungen Fr equenzumr ichter UL und cUL [BU 0500] @ 0\ mod_1325780690549_388.docx @ 5454 @ 355 @ 1

1.5.2 UL and cUL approvals for frequency inverters (CSA)

All SK 500E frequenc y inverters include motor overlo ad protection. Further technical details c an be found in Section 0.
"Integral solid state short circuit protection does not prov must be provided in accordance with the National Electric Code and any additional local codes."
The integral short-circuit protection does not provide branch circuit protection. Branch circuit protection must be regulations.
“Use 75°C Copper Conductors Only" - “Anschluss von Kupferkabel mit einer Isolationsfestigkeit von mind. 75°C“ (betrifft ausschließlich Anschlussleitungen (Netz- / Motorkabel aber nicht Steuerleitungen))
„These products are intended for use in a pollution degree 2 environment“ - „Das Produkt ist für den Betrieb in Umgebungen mit Verschmutzungsgrad 2 geeignet“
"Maximum Surrounding Air Temperature 40°C" - “Maximale Umgebungstemperatur 40°C”
BU 0505 GB-1013 15
SK 54xE – Users Manual for Frequency Inverters
(symmetrisch), und bei Schutz über eine strombegrenzende Sicherung“ mit hohem
A oder 65 000 A
hutz über Sicherungsautomaten nach UL Kategorie DIVQ (thermischer und elektromagnetischer Auslöser)
Die Stromwerte der Sicherungen und
Wenn diese Klemmen genutzt werden um externe Spannungen (24V) einzuspeisen, so muss für einen UL konformen Anschluss folgendes
(24Vdc) verbunden werden. Eine Sicherung zwischen isoliertem Steuerspannungskreis und
UL- Approval - File No. E171342
Frequency inverter Fuses Circuit Breaker
SK 5xxE-xxx- Size Type Circuit Circuit
1 … 4 5, 6 7 C,J,R,T G, L [V] [A] rms [V] [A] rms
-112
-323
-323
-323
-340 (/ -350)
-340 (/ -350)
-340 (/ -350)
X X X 300 100 000 480 10 000 X X X 300 100 000 480 10 000
X X - 300 65 000 480 65 000 X X X 300 100 000 480 65 000
X X X 600 100 000 480 10 000
X X - 600 65 000 480 65 000 X X X 600 100 000 480 65 000
referring to the table above “Suitable for use on a circuit capable of delivering
not more than 65 000 or 100 000 rms symmetrical Amperes, and when protected by High-Interrupting Capacity, Current Limiting Fuses”.
“Suitable for use on a circuit capable of delivering not more than 10 000 or 65 000 rms symmetrical Amperes, and when protected by a Circuit Breaker (inverse time trip type) in accordance with UL 489”, having an interrupting rating of not less than 10 000 or 65 000 rms symmetrical Amperes, 480 Volts maximum.
The current ratings of the fuses and circuit breakers are stated in Section 0.
Devices of size 5 and above - Use of terminals X12 or X8 "Intended to be connected only to isolated
secondary sources rated 24Vdc. Fuse in accordance with UL 248 rated max. 4 A must be provided externally between the isolated source and this device input".
bezugnehmend zur obigen Tabelle Geeignet für den Einsatz am Netz mit einem max.
Kurzschlussstrom von 65 000 A oder 100 000 A
Ausschaltvermögen. Geeignet für den Einsatz am Netz mit einem max.
Kurzschlussstrom von 10 000 (symmetrisch), und bei Sc
gemäß UL 489, mit einem Mindestaus­schaltvermögen von 10 000 A oder 65 000 A, 480 V Maximum.
Leistungsschalter sind im Kapitel 0 aufgeführt.
berücksichtigt werden: "Darf nur mit isoliertem Steuer-spannungskreis
Supplement for cUL
Compliance with th e cond itions descr ibed below f ulfils the re quirem ents f or cUL approval as per CSA.
16 BU 0505 GB-1013
diesem Eingang muss gemäß UL 248 ausgeführt sein, darf maximal 4 A betragen und muss extern bereitgestellt werden.“
1 General
und bei Schutz über eine strombegrenzende Sicherung“ mit hohem Ausschaltvermögen wie
und bei Schutz über Sicherungsautomaten nach UL Kategorie DIVQ (thermischer und
Die Stromwerte der Sicherungen und
40 für
ist zwischen Einspeisung und
Frequenzumrichter (eingangsseitig) nach
The supplementary requirements as per the cUL listing are fulfilled by the use of an appropriate overvoltage filter For SK500E series frequency inverters, no suitable CSA filter can be provided for the voltage range 1~115V
Frequency Inverters size 1 - 7 “Suitable for use on a circuit capable of delivering
not more than 5 000 rms symmetr i cal Amperes,
• 240 Volts maximum (SK 5xxE-xxx-323) or
• 500 Volts maximum (SK 5xxE-xxx-340 / SK 5xxE-xxx-350) and when protected by High-Interrupting Capacity,
Current Limiting Fuses as described above”.
“Suitable for use on a circuit capable of delivering not more than 5 000 rms symmetr i cal Amperes,
• 240 Volts maximum (SK 5xxE-xxx-323) or
• 500 Volts maximum (SK 5xxE-xxx-340 / SK 5xxE-xxx-350) and when protected by a Circuit Breaker (inverse
time trip type) in accordance with UL 489”, having an interrupting rating of not less than 5 000 rms symmetrical Amperes, 480 Volts maximum.
The current ratings of the fuses and circuit breakers are stated in Section 0.
Devices size 1 - 6 “cUL only in combination with SK CIF-340-30 or
SK CIF-340-60 for 380 - 500V models and SK CIF-323-20 or SK CIF-323-40 for 3 phase 200 - 240V rated models”.
The recognized transient surge suppression filter board has to be connected between supply and the input of the drive according to the instruction manual.
Frequenzumrichter Baugröße 1 - 7 Geeignet für den Einsatz am Netz mit einem max.
Kurzschlussstrom von 5 000 A (symmetrisch),
• 240 Volt Maximum (SK 5xxE-xxx-323) oder
• 500 Volt Maximum (SK 5xxE-xxx-340 / SK 5xxE-xxx-350)
oben beschrieben. Geeignet für den Einsatz am Netz mit einem max.
Kurzschlussstrom von 5 000 A (symmetrisch),
• 240 Volt Maximum (SK 5xxE-xxx-323) oder
• 500 Volt Maximum ( SK 5xxE-xxx-340 / SK 5xxE-xxx-350)
elektromagnetischer Auslöser) gemäß UL 489, mit einem Mindest-ausschaltvermögen von 5 000 A, 480 V Maximum.
Leistungsschalter sind im Kapitel 0 aufgeführt.
cUL Konformität, nur in Kombination mit SK CIF­340-30 oder SK CIF-340-60 für 380 - 500V Typen und SK CIF-323-20 oder SK CIF-323­200 - 240V Typen.
Das entsprechende Spannungs-begrenzungsfilter (SK CIF-xxx-xx)
Handbuchangaben anzuschließen.
Note
SK CIF-323-xx or. SK CIF-340-xx. For devices larger than size 7 no SK CIF-3xx-xx overvoltage filter is required.
Note
(SK 5xxE-xxx-112). For these types, (SK 5xxE-xxx-112) there is therefore NO cUL approval.
1~115V devices: no cUL approval
SK CIF-xxx
Pos: 27 /Anl eitungen/ Elektroni k/FU und Star ter/1. All gemeines/ 1.5.3 C-Tick-Ke nnzeichnu ng - No. N 23134 [SK 5xxE] @ 0\mod_1325835937619_388.docx @ 5480 @ 3 @ 1
BU 0505 GB-1013 17
SK 54xE – Users Manual for Frequency Inverters
SK 500E-250-323-A-CP
Versions: CP = “ColdPlate” or “External heat sink technology” Radio interference filter class: O = without, A or B limit value Mains voltage: x12 = 115V, x23 = 230V, x 40 = 400V, x50 = 500V Number of mains phases: 1 = single phase, 3 = 3-phase * Digits before comma for power: 0 = 0.xx, 1 = 0x.x0, 2 = 0xx.0 Device nominal power (xx): 25 = 0.25kW
, 37 = 0.37kW up to 90 = 90.0kW
Device series: SK 500E
/ SK 505E / SK 510E / SK
511E / SK 515E /
SK 520E / SK 530E / SK 535E / SK 540E / SK 545E
*) designation - 3 - also includes com bined devices
which are intended for single and three-phase operation (please ref er to the technical data)

1.5.3 C-Tick labelling - No. N 23134

Frequency inverters of the NORD product series SK 500E (except 115V devices: SK5xxE-xxx-112-O) comply with all the relevant regulations in Australia and New Zealand.
Pos: 28 /Anl eitungen/ Elektroni k/FU und Star ter/1. All gemeines/ 1.5.4 RoHS- konform @ 0\mod_1325836122418_388.docx @ 5503 @ 3 @ 1

1.5.4 RoHS compliant

The frequency inverters and optional modules are designed to be RoHS compliant according to Directive 2002/95/EU.
Pos: 29 /Anl eitungen/ Elektroni k/FU und Star ter/1. All gemeines/ 1.6 Typensc hlüssel / Geräteaus führung [SK 5xxE] @ 0\ mod_1325859433216_388.docx @ 5526 @ 2 @ 1

1.6 Type codes / Device versions

18 BU 0505 GB-1013
1 General
SK 520E or higher
incl. fastening sc rews
Optional
Wall mount bracket
Technology Unit
including securing screw
additional control
terminals
Analog and digital
control terminals
Fig. 1 SK 5xxE and accessories
Encoder input
for SK 520E and higher
Optional EMC Kit:
Screening angle and clips
BU 0505 GB-1013 19
SK 54xE – Users Manual for Frequency Inverters The type designation resulting from this type code can be obtained from the name plate which is
printed on the frequency inverter below the blank cover.
Fig. 2 Frequency inverter type plate (example)
Pos: 30 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2. Mont age und Inst allation [ BU 0500] @ 0\mod_1325859552792_ 388.docx @ 5572 @ 1 @ 1
20 BU 0505 GB-1013
2 Assembly and installation

2. Assembly and installation

SK 500E freque nc y inv erters are available in vari ous s i zes de pen di ng o n the output. Attentio n must be paid to a suitable position when install ing.
The equipment requires sufficient ventilation to protect against overheating. For this the minimum guideline distances f rom adjacent components above and below the fr equency inverter, which could obstruct the air flow apply.
Distance from device: Mounting can be immediately next to each other. However, for the use of brake resistances m ounted belo w the f reque ncy inverter (not possib le with … -CP devices), the gre ater width must be taken into consid eration, particularly in combination with temperature switches on the brake resistor!
Installation position: The installatio n positio n is normall y vertical. It must be ensur ed that the coo ling ribs on the rear of the frequency inverter are covered with a flat surface to provide good convection.
(above > 100 mm, below > 100 mm)
Warm air must be vented above the device!
Fig. 3 Mounting distances for SK 5xxE
If several inverters are arranged above each other, it must be ensured that the upper air entry temperature limit is not exceede d. (See also Section 0 ) If this is the cas e, it is recommended that an "obstacle" (e.g. a cab le duct) is m ounted between the inverters so tha t the direct air f low (rising warm air) is impeded.
Heat dissipation: If the frequency inverter is insta lled in a control cabinet, a dequate ventilation m ust be ensured. The heat dissipati on in operation is appr ox. 5% (according to the si ze and equipment of the device) of the rated power of the frequency inverter.
Pos: 31 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und I nstallati on/2.1 SK 5x xE in Stand ard-Ausführ ung [BU 0500] @ 0\ mod_1325859863676_388.docx @ 5618 @ 2 @ 1
BU 0505 GB-1013 21
SK 54xE – Users Manual for Frequency Inverters
SK 5xxE-250- … to SK 5xxE-750- ...
Size 1
186
74*
153
220 / 5.5
1.4
SK 5xxE-111- … to SK 5xxE-221- …
Size 2
226
74*
153
260 / 5.5
1.8
SK 5xxE-301- … to SK 5xxE-401- …
Size 3
241
98
181
275 / 5.5
2.7
SK 5xxE-551- 340… to SK 5xxE-751- 340…
Size 4
286
98
181
320 / 5.5
3.1
SK 5xxE-551- 323… to SK 5xxE-751- 323…
Size 5
327
162
224
357
93
5.5
8.0
SK 5xxE-112- 340… to SK 5xxE-152- 340…
Size 5
327
162
224
357
93
5.5
8.0
SK 5xxE-112- 323…
Size 6
367
180
234
397
110
5.5
10.3
SK 5xxE-182- 340… to SK 5xxE-222- 340…
Size 6
367
180
234
397
110
5.5
10.3
SK 5xxE-152- 323… to SK 5xxE-182- 323…
Size 7
456
210
236
485
130
5.5
15
SK 5xxE-302- 340… to SK 5xxE-372- 340…
Size 7
456
210
236
485
130
5.5
16
SK 5xxE-452- 340… to SK 5xxE-552- 340…
Size 8
598
265
286
582
210
8.0
20
SK 5xxE-752- 340… to SK 5xxE-902- 340…
Size 9
636
265
286
620
210
8.0
25
400V (…-340…) and 500V (…-350…) - FI: identical dimensions and weights
*) for the use of brake resistors mounted below the device = 88 mm

2.1 SK 5xxE, standard version

Normally, the frequency inverter is mounted directly on the rear wall of a control cabinet. For th is, two, or f or sizes 5 to 7, f our matc hing wall m ounting brackets are supplied, which are to be inser ted into the he at sink at the rear of the device. For size 8 and above, the mounting device is integrated.
Alternatively, for si zes 1 ... 4 the wall mounting brackets can be insert ed at the side of the cooling el ement in order to minimis e the necessary depth of the control cabinet.
In general, care m ust be taken that the rear of the cool ing e lement is covered with a flat surface and that the device is mounted vertically. This enables optimum convection, which ensures fault-free operation.
Frequency inverter type
Housing
dimensions
Size
A B C D E
Wall-mounting Weight
All dimensions in [mm]
E
Approx.
[kg]
Pos: 32 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.2 SK 5 xxE…-CP in ColdPlate-Ausfü hr u ng [BU 0500] @ 0\mod_1325859970018_388.docx @ 5641 @ 2 @ 1
22 BU 0505 GB-1013
2 Assembly and installation
A
C
B
Ø 4.5mm
H
Ø 4.5mm
H

2.2 SK 5xxE…-CP in ColdPlate version

Instead of a cooling element /fan, ColdPlate versions of the frequency inverter have a flat metal plat e on the rear side which is mounted on an existing mounting plate (e.g. the rear wall of the control cabinet) so as to pro v ide t h ermal conduction. A liq ui d c ooling medium (water, o il) may also be passed through the mounting surface. In this way, not only is the waste heat from the frequency inverter dissipated more effectively, but also the waste heat from the inverter is prevented from remaining inside the control cabinet. In addit ion to the optim isation of the p ower reserved and th e service life of the inverter, this also causes less thermal load on the inside of the control cabinet.
A further advantage of the ColdPlate version is the reduced installation d epth of the device and the fact that in general, there is no need for a fan on the frequency inverter.
Bottom-mounted brake resistors (SK BR4-…) cannot be mounted directly.
Frequency inverter type
SK 5xxE-250- …-CP SK 5xxE-750- …-CP
SK 5xxE-111- …-CP SK 5xxE-221- …-CP
SK 5xxE-301- …-CP SK 5xxE-401- …-CP
SK 5xxE-551- 340…-CP SK 5xxE-751- 340…-CP
Envelope dimensions
[mm]
ColdPlate dimensions [mm]
Size
A / H B C h1 h2 u / k Thickness
Weight
Approx.
[kg]
1 182 95 119 91 - 5.5 10 1.3
2 222 95 119 111 - 5.5 10 1.6
3 237 120 119 75.33 75.33 5.5 10 1.9
4 282 120 119 90.33 90.33 5.5 10 2.3
B
u
u
k
k
h1
h1
h2
SK 5xxE-…CP ColdPlate size 1 and size 2 ColdPlate size 3 and size4
Pos: 33 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.3 Durc hsteck-Kit [BU 05 0 0] @ 0\ mod_1325861024826_388.docx @ 5733 @ 2555 @ 1
BU 0505 GB-1013 23
SK 54xE – Users Manual for Frequency Inverters
Frequency inverter
internal hexagon socket M4x16 (4x)
External heat

2.3 External heat sink kit

External heat sink technology is an optional supplem ent for ColdPlate devices. This is use d if an external cooling system is provided, but no liquid-cooled m ounting plate is available. A c ooling element is mounted on the ColdPlate device, which passes through an opening in the rear panel of the control cabinet into the exterior air-cooled environment. Convection takes place ou tside of the control cabinet, which results in the same advantages as with ColdPlate technology.
Type
type
External heat
Size
sink kit
Part. No.
SK 5xxE-250- …-CP SK 5xxE-750- …-CP
SK 5xxE-111- …-CP SK 5xxE-221- …-CP

Scope of delivery

Dimensions

Type
sink kit
1
2
1=
Heat sink
2=
Gasket
3=
Heat-conducting paste
4=
Cylindrical-head screws wit h
Heat sink dimensions
[mm]
HK BK TK
SK TH1-1
SK TH1-2
Weight
Heat sink
Approx. [kg]
275999050
275999060
BK
TK
SK TH1-1 157 70 100 1.5
SK TH1-2 200 70 110 1.7
24 BU 0505 GB-1013
HK
2 Assembly and installation

Assembly

For installation, a hole with the size of the heat sink must be made in the w all of the control cabinet (note the load bearing capacity).
1. Apply heat-conducting paste to the ColdPlate of the SK 5xxE;
2. firmly fasten the heat sink to the ColdPlate with the 4 enclosed screws;
3. remove any heat conducting paste which exudes;
4. Place the seal between the frequency inverter and the wall of the control cabinet (inside of the control cabinet);
5. Insert the frequency inverter and guide the external heat sink out of the control cabinet through the hole in the wall of the control cabinet;
6. Fasten the frequency inverter to the wall of the control cabinet though all of the 6 or 8 holes in the ColdPlate.
Information
With correct installation, the control cabinet achieves IP54 from the outside at the point of installation.
Protection class IP54
Pos: 34 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.4 Huts chienenmo ntageset S K DRK1-... [BU 0500] @ 0\mod_1325861903944_388.docx @ 5802 @ 255 @ 1
BU 0505 GB-1013 25
SK 54xE – Users Manual for Frequency Inverters
Frequency inverter
on rail. To
2.4 Snap-on mounting r ail kit SK DRK1-…
The snap-on mounting rail set SK DRK1-1 enables size 1 or 2 frequency inverters to be m ounted on a sta ndard T S35 (EN 50022) mounting rail.
Type
type
Snap-on rail
Size
mounting kit
Part. No.
SK 5xxE-250- … SK 5xxE-750- …
SK 5xxE-111- … SK 5xxE-221- …

Scope of delivery

1= 2= 3= 4= 5=
SK DRK1-1
1
2
SK DRK1-2
275999030
275999040
Adapter for snap-on rail mounting Clamp Spacer Fastening plate Screws(2x)

Assembly

1. Push the fastening plate (4) into the guide on the heat sink (arrow);
2. place the spacer plate (3) on the fastening plate (4);
3. connect the snap-on rail mounting adapter (1) and the components (3) + (4) with screws (5).
During assembly, take care that the stirrup (2) points upwards (mains connection side of the inverter).
Then the inverter can be clipped directly onto the snap­release the frequency inverter, the stirrup (2) must be pulled a few millimetres out of the snap-on rail.
Pos: 35 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.5 EMV- Kit [SK5xxE] @ 0 \mod_1325861952008_388.docx @ 5825 @ 2 @ 1
26 BU 0505 GB-1013
2 Assembly and installation
b
Similar to illustration
SK EMC 2-6 Part No. 275999061
Alternatively, the EMC Kit can be simply used as a strain relief (e.g. for the connection cables of a bus system)

2.5 EMC Kit

For optimum EMC-compliant wiring, the optional EMC Kit must be used. This includes a shield bracket, two hamm er clips, two fasten ing screws an d a pre-assem bled PE cable. T he PE cable m ust be connected to the appropriate screw on the shielding bracket and to the PE terminal of the frequency inverter. The connection of further PE connections to the shield bracket is possible with additional ring cable lugs (SK EMC 2-1 and 2-2).
The EMC Kit provides th e pos sibi li t y of attaching the screening of the motor cable to a lar g e sur f ac e of the frequency inverter (interference source). If necessary, a screened brake resistor cable can be attached with the second hammer clip.
The screening angle is attached to the two housing screws on the lower edge (below the U-V-W terminals). The m otor cable screening is earthed to a large area of the s creening angle by means of the hammer clip.
Fig. 4 EMC Kit SK EMC2-x
Device type Size EMC Kit Dimension "b"
SK 5xxE-250- … SK 5xxE-750- Size 1 SK 5xxE-111- … SK 5xxE-221- Size 2
SK 5xxE-301- … SK 5xxE-401- Size 3 SK 5xxE-551-340- … SK 5xxE-751- 340- Size 4 SK 5xxE-551-323- … SK 5xxE-751- 323-
SK 5xxE-112-340- … SK 5xxE-152- 340­SK 5xxE-112-323-
SK 5xxE-182-340- … SK 5xxE-222- 340­SK 5xxE-152-323- … SK 5xxE-182- 323-
SK 5xxE-302-340- … SK 5xxE-372- 340-
Size 5
Size 6
Size 7
SK 5xxE-452-340- … SK 5xxE-902- 340- Size 8/9
SK EMC 2-1
Part No. 275999011
SK EMC 2-2
Part No. 275999021
SK EMC 2-3
Part No. 275999031
SK EMC 2-4 Part No. 275999041
SK EMC 2-5 Part No. 275999051
42 mm
42 mm
52 mm
57 mm
57 mm
100 mm
Table 4: EMC Kit SK EMC2-x
Note
The EMC Kit cannot be combined with ...-CP (ColdPlate) devices. Any cable screening must be earthed to a large area of the mounting surface.
(note the bending radii!).
Pos: 36 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.6 Brems widerst and (BW) [BU 0500] @ 0\mod_1325862128510_388.docx @ 5848 @ 2 @ 1
BU 0505 GB-1013 27
SK 54xE – Users Manual for Frequency Inverters
should be checked with suitable measuring equipment. In addition, keep sufficient distance from adjacent
),inordertoi
SK BR4-... Size 1
SK BR4-... Size 2
SK BR2-... Size 3 SK BR2-... Size 4 and above

2.6 Brake resistor (BR)

CAUTION
Danger of burns
The heat sink and all other metal components can heat up to temperatures above 70°C. Touching such components may cause local burns to the affected parts of the body (hands, fingers, etc.). To prevent such injuries, allow sufficient time for cooling down before starting work - the surface temperature
components during installation, or install protection against contact.
During dynamic brak ing (frequency reduc tion) of a three-phase motor, electrica l energy is retur ned to the inverter. An external br ake resistor can be used in order to prevent the F I from being shut down due to overvoltage. W ith this, the int egrated brake c hopper (electr onic s witch) pul ses the interm ediate circuit voltage (switching wave approx. 420 V/775 V(/825 V) DC, according to the mains voltage) (115 V, 230 V/400 V(/500 V)) to the brake resistor. Here the excess energy is converted into heat.
For inverter powers up to 7.5 kW (230 V: up to 4.0 kW) a standard bottom-mounted resistor (SK BR4-..., IP40) ca n be u s ed. This can additionally be equipped with an opt io na l temperature switch (bi-metal, switching po int 1 00 is enclosed. The resistor and the temperature switch are connected by means of flexible stranded conductors. Approval: UL, cU L
Note: Brake resistors cannot be directly mounted below …-CP (ColdPlate) devices.
For frequency inverters above 3kW chassis resistors (SK BR2-..., IP20) are also available. These must be mounted i n the cont rol c abinet, close to th e fr equenc y invert er. T here is a tem per ature switch on the braking resistor to provide protection against overload. Connection of the resistor and the temperature switch is by means of screw terminals. Approval: UL, cUL
Fig. 5: Top: bottom-mounted brake resistor SK BR4- Bottom: chassis brake resistor SK BR2-...
Pos: 37 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Inst al l ation/2.6. 1 El e ktrische Dat en BW [BU 0500 ] @ 0\ mod_1325862333353_388.docx @ 5871 @ 3 @ 1
28 BU 0505 GB-1013
2 Assembly and installation
SK 5xxE-250-112-O … SK 5xxE-370-112-O
SK 5xxE-550-112-O … SK 5xxE-750-112-O
SK 5xxE-250-323-A … SK 5xxE-370-323-A
SK 5xxE-750-323-A
SK 5xxE-111-323-A … SK 5xxE-221-323-A
2 x 2.5mm
2
L = 0.5m
SK 5xxE-401-323-A
SK 5xxE-751-323-A
SK BR2- 12/1500-C
Part No. 278282015
SK 5xxE-182-323-A …
SK 5xxE-550-340-A … SK 5xxE-750-340-A
SK 5xxE-111-340-A … SK 5xxE-221-340-A
SK 5xxE-301-340-A … SK 5xxE-401-340-A
SK 5xxE-751-340-A
SK 5xxE-401-340-A
SK 5xxE-551-340-A … SK 5xxE-751-340-A
SK 5xxE-112-340-A …
SK 5xxE-182-340-A … SK 5xxE-222-340-A
SK 5xxE-302-340-A … SK 5xxE-372-340-A
SK 5xxE-552-340-A
SK 5xxE-752-340-A … SK 5xxE-902-340-A

2.6.1 Electrical data, brake resistor

Inverter ID Resistor type Resistance
Continuous
rating
Pulse
energy*
Connecting
cable /
terminals
SK 5xxE-550-323-A …
SK 5xxE-301-323-A … SK 5xxE-401-323-A
SK 5xxE-301-323-A …
SK 5xxE-551-323-A …
SK 5xxE-112-323-A SK 5xxE-152-323-A …
SK 5xxE-551-340-A …
SK 5xxE-301-340-A …
SK 5xxE-152-340-A
SK 5xxE-452-340-A …
SK BR4-240/100
Part No. 275991110
SK BR4-150/100
Part No. 275991115
SK BR4-240/100
Part No. 275991110
SK BR4-150/100
Part No. 275991115
SK BR4- 75/200
Part No. 275991120
SK BR4- 35/400
Part No. 275991140
SK BR2- 35/400-C
Part No. 278282045
SK BR2- 22/600-C
Part No. 278282065
SK BR2- 9/2200-C
Part No. 278282122
SK BR4-400/100
Part No. 275991210
SK BR4-220/200
Part No. 275991220
SK BR4-100/400
Part No. 275991240
SK BR4-60/600
Part No. 275991260
SK BR2-100/400-C
Part No. 278282040
SK BR2- 60/600-C
Part No. 278282060
SK BR2- 30/1500-C
Part No. 278282150
SK BR2- 22/2200-C
Part No. 278282220
SK BR2- 12/4000-C
Part No. 278282400
SK BR2- 8/6000-C
Part No. 278282600
SK BR2- 6/7500-C
Part No. 278282750
240
150
240
150
75
35
35
22 12
9
400
220
100
60
100
60
30
22
12
8
6
100 W 1.0 kWs
2 x 1.9mm AWG 14/19
100 W 1.0 kWs
L = 0.5m
100 W 1.0 kWs
2 x 1.9mm
100 W 1.0 kWs
AWG 14/19
L = 0.5m
200 W 3.0 kWs
400 W 6.0 kWs
AWG 14/19
400 W 6.0 kWs 2 x 10mm
600 W 7.5 kWs 2 x 10mm 1500 W 20 kWs 2 x 10mm 2200 W 28 kWs 2 x 10mm
100 W 1.0 kWs
2 x 1.9mm AWG 14/19
200 W 3.0 kWs
400 W 6.0 kWs
L = 0.5m
2 x 2.5mm AWG 14/19
600 W 12.0 kWs
L = 0.5m
400 W 6.0 kWs
2 x 10mm
600 W 7.5 kWs
1500 W 20 kWs
2200 W 28 kWs
2 x 10mm
4000 W 52 kWs
6000 W 78 kWs
7500 W 104 kWs 2 x 25mm
*) Maximum once for 1.2s within 120s
2
2
2
2
2
2
2
2
2
2
2
Table 5: Electrical data for brake resistor SK BR2-… and SK BR4-…
The chassis brak e resistors (SK BR2-…) listed above are equ ipped with a temperature s witch at the factory. An optional temperature switch is available for the bottom-mounted brake resistor (SK BR4-…). In or der to use the signal from the temperature switch it m ust be connected to a free digital input of the frequenc y inverter an d, f or example, parameterised with the fun c tion "Vo ltag e bl oc k" or "Fast stop".
BU 0505 GB-1013 29
SK 54xE – Users Manual for Frequency Inverters
Flexible
L = 0.5m
250Vac
30Vdc
10A
5A
SK BR4-... Size 1 SK BR4-... Size 2
B A C
D
NORDAC SK 5xxE
Optional temperature switch
B A C
D
NORDAC SK 5xxE
Bi-metal temperature switch
for... Part No.
SK BR4-... 275991200 IP40 250Vac
SK BR2-... integrated IP00
Table 6: Brake resistor temperature switch data
Pos: 38 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.6.2 A bmessunge n Unterbau- BW SK BR4 [BU 0500] @ 0\ mod_1325862485335_388.docx @ 5894 @ 3 @ 1
Protection
class
Voltage Current
2.5A with cosϕ=1
1.6A with cosϕ=0.6
125Vac
15A

2.6.2 Dimensions of bottom-mounted BR SK BR4

Resistor type Size A B C
SK BR4-240/100 SK BR4-150/100 SK BR4-400/100
SK BR4- 75/200
SK BR4-220/200
SK BR4-35/400
SK BR4-100/400
Size 1 230 88 175 220 5.5
Size 2 270 88 175 260 5.5
Size 3 285 98 239 275 5.5
Nominal
switching
Dimensions
temperature
100
Width +10mm
(one side)
180°C ± 5K Internal
Fixing dimensions
D
Connecting
cable /
terminals
strand 2 x
0.8mm
2
AWG 18/19
terminals
2 x 4mm
2
SK BR4-60/600
C = Installation depth of the frequency inverter + bottom-mounted brake resistor. All dimensions in mm
Table 7: Dimensions of bottom-mounted brake resistor SK BR4-...
Size 4 330 98 239 320 5.5
30 BU 0505 GB-1013
2 Assembly and installation
Type plate
Temperature switch optional please order separately For fitting by the customer
Temperature switch optional please order separately For fitting by the customer
Type plate
SK BR4-... Size 3 SK BR4-... Size 4
Separate data sheets are available for bott om-mounted brak e resistors SK BR4 abo ve size 3. These can be downloaded at www.nord.com
.
Inverter ID Brake resistor type Part No. Data sheet
SK 5xxE-301-323-A -401-323-A SK 5xxE-301-340-A -401-340-A SK 5xxE-551-340-A -751-340-A
Pos: 39 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.6.3 A bmessunge n Chassis-B W SK BR2 [BU 0500, u. A.] @ 0\mod_1325862658505_388.docx @ 5917 @ 3 @ 1
SK BR4-35/400
SK BR4-100/400
SK BR4-60/600
275991140 TI014 275991140 275991240 TI014 275991240
275991260 TI014 275991260
BU 0505 GB-1013 31
SK 54xE – Users Manual for Frequency Inverters
SK BR2-100/400-C
SK BR2- 35/400-C
SK BR2- 60/600-C
SK BR2- 22/600-C
SK BR2- 30/1500-C
SK BR2- 12/1500-C
SK BR2- 22/2200-C
SK BR2- 9/2200-C
SK BR2- 12/4000-C
560
270
240
530
240
6.5
SK BR2- 8/6000-C
470
600
300
440
2x220
6.5
SK BR2- 6/7500-C
570
600
300
540
2x220
6.5
All dimensions in mm
SK BR2-... FI size 3 and above
(Schematic diagram, model varies according to power)
B
A
E
D
C

2.6.3 Dimensions, brake resistor chassis SK BR2

Resistor type A B C
170 100 240 150 90 4.3
350 92 120 325 78 6.5
560 185 120 530 150 6.5
460 270 120 430 240 6.5
Fixing dimensions
D E
Table 8: Dimensions of chassis brake resistor SK BR2-...
Pos: 40 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.7 Netz drossel S K CI1 [BU 0 500, u.A.] @ 0\mod_1325862740832_388.docx @ 5940 @ 2 @ 1
32 BU 0505 GB-1013
2 Assembly and installation
V at
The choke used
must therefore be installed in a control
a line choke is
being used, in order to avoid possible
Continuous
Part. No.: 278999030
SK CI1-230/20-C
Part. No.: 278999040
All dimensions in [mm]
[mm2]
Continuous
SK CI1-480/100-C
All dimensions in [mm]
[mm2]
D
L2
L1
W1
B2
L1
L2
L22
L12
L3
L32
Similar to illustration

2.7 Mains choke SK CI1

To reduce input side current harmonics, additional inductivity can be installed into the line supply to the inverter.
These chokes ar e specif ied f or a m aximum supply voltage of 230 V or 480 50/60 Hz.
All chokes have a protection class
corresponding to IP00.
cabinet. For frequency inverters w ith an output of
45 kW or more, recommended where several devices are
adverse effects of one device on another.
In addition, the charging currents (mains voltage fluctuations) are significantly reduced.
Input choke 1 x 220 - 240 V
Inverter ID
NORD
SK 500E
0.25 ... 0.75hp
Type
SK CI1-230/8-C
1.1 ... 2.2 kW
Table 9: Mains choke data for SK CI1-..., 1~ 240 V
Input choke 3 x 200 - 240 V
Inverter ID
NORD
SK 500E
0.25 ... 0.75hp
1.1 ... 1.5 kW
2.2 … 3.0 kW
4.0 … 7.5 kW 11 … 15 kW
18 kW
Type
SK CI1-480/6-C
Part. No.: 276993006
SK CI1-480/11-C
Part. No.: 276993011
SK CI1-480/20-C
Part. No.: 276993020
SK CI1-480/40-C
Part. No.: 276993040
SK CI1-480/70-C
Part. No.: 276993070
Part. No.: 276993100
Detail: Mounting
L1 W1 D
current
Inductance
L2 B2
Installation
8 A 2 x 1.0 mH 78 65 89 56 40 M4 4
20 A 2 x 0.4 mH 96 90 106 84 65 M6 10
Detail: Mounting
L1 W1 D
current
Inductance
L2 B2
Installation
6 A 3 x 4.88 mH 96 60 117 71 45 M4 4 11 A 3 x 2.93 mH 120 85 140 105 70 M4 4 20 A 3 x 1.47 mH 155 110 177 135 95 M5 10 40 A 3 x 0.73 mH 155 115 172 135 95 M5 10 70 A 3 x 0.47 mH 185 122 220 170 77 M6 35
100 A 3 x 0.29 mH 240 148 263 180 122 M6 35
Connection
Connection
Table 10: Mains choke data for SK CI1-..., 3~ 240 V
BU 0505 GB-1013 33
SK 54xE – Users Manual for Frequency Inverters
Continuous
Part. No.: 276993006
SK CI1-480/11-C
Part. No.: 276993011
SK CI1-480/20-C
Part. No.: 276993020
Part. No.: 276993040
SK CI1-480/70-C
Part. No.: 276993070
SK CI1-480/100-C
Part. No.: 276993100
SK CI1-480/160-C
Part. No.: 276993160
SK CI1-480/280-C
Part. No.: 276993280
All dimensions in [mm]
[mm2]
To reduce interference signals from the
capacitance in long motor cables, an additional output choke can be installed
These chokes are specified for a
V at
D
L2
L1
W1
B2
U V V2
U2 W W3
Similar to illustration
Input choke 3 x 380 - 480 V
Inverter ID
NORD
SK 500E
0.55 ... 2.2 kW
3.0 ... 4.0 kW
5.5 ... 7.5 kW 11 ... 15 kW
18 ... 30hp 37 … 45 kW 55 … 75 kW
90 kW
* Bolt for copper rail
Table 11: Mains choke data for SK CI1-..., 3~ 480 V
Type
SK CI1-480/6-C
SK CI1-480/40-C
current
Inductance
6 A 3 x 4.88 mH 96 60 117 71 45 M4 4 11 A 3 x 2.93 mH 120 85 140 105 70 M4 4 20 A 3 x 1.47 mH 155 110 177 135 95 M5 10 40 A 3 x 0.73 mH 155 115 172 135 95 M5 10 70 A 3 x 0.47 mH 185 122 220 170 77 M6 35
100 A 3 x 0.29 mH 240 148 263 180 122 M6 35 160 A 3 x 0.18 mH 352 140 268 240 105 M8 M8* 280 A 3 x 0.10 mH 352 169 268 240 133 M10 M16*
Detail: Mounting
L1 W1 D
L2 B2
Connection
Installation

2.8 Output choke SK CO1

motor cable or to compensate for cable
into the inverter output. During installation tak e care that the pulse
frequency of the frequency inverter is set to 3 - 6 kHz (P504 = 3 - 6).
maximum supply voltage of 480 0 - 100 Hz.
An output choke s hould be fitted f or cable le ngths over 100 m/30 m (unshielded/ shielded). All chokes have a protection class corresponding to IP00. The choke used must therefore be installed in a control cabinet.
34 BU 0505 GB-1013
2 Assembly and installation
0.25 … 0.75 kW
SK CI1-480/60-C
Part. No.: 276992060
SK CI1-460/90-C
Part. No.: 276996090
3 x 0.22 mH
All dimensions in [mm]
[mm2]
Installation
SK CI1-460/9-C
SK CI1-460/17-C
SK CI1-460/33-C
Part. No.: 276992060
SK CI1-460/90-C
Part. No.: 276996090
55 … 75 kW
SK CI1-460/170-C
Part. No.: 276996170
90 kW
SK CI1-460/240-C
All dimensions in [mm]
[mm2]
Output choke 3 x200 – 240 V
Inverter ID
NORD
SK 5xxE
1.1 ... 1.5 kW
2.2 ... 4.0 kW
5.5 ... 7.5 kW 11 … 15 kW
18 kW
Type
SK CI1-460/4-C
Part. No.: 276996004
SK CI1-460/9-C
Part. No.: 276996009
SK CI1-460/17-C
Part. No.: 276996017
SK CI1-460/33-C
Part. No.: 276996033
Continuous
current
Inductance
4 A 3 x 3.5 mH 120 104 140 84 75 M6 4
9 A 3 x 2.5 mH 155 110 160 130 71.5 M6 4 17 A 3 x 1.2 mH 185 102 201 170 57.5 M6 10 33 A 3 x 0.6 mH 185 122 201 170 77.5 M6 10 60 A 3 x 0.33 mH 185 112 210 170 67 M8 16
90 A
Table 12: Output choke data for SK CO1-..., 3~ 240 V
Output choke 3 x 380 – 480 V
Inverter ID
NORD
SK 5xxE
Type
Continuous
current
Inductance
Detail: Mounting
L1 W1 D
L2 B2
Connection
352 144 325 224 94 M10 35
Detail: Mounting
L1 W1 D
L2 B2
Connection
0.55 ... 1.5 kW
2.2 ... 3.0 kW
4.0 ... 7.5 kW 11 ... 15 kW
18 ... 30hp
37 … 45 kW
SK CI1-460/4-C
Part. No.: 276996004
Part. No.: 276996009
Part. No.: 276996017
Part. No.: 276996033
SK CI1-480/60-C
4 A 3 x 3.5 mH 120 104 140 84 75 M6 4
9 A 3 x 2.5 mH 155 110 160 130 71.5 M6 4 17 A 3 x 1.2 mH 185 102 201 170 57.5 M6 10 33 A 3 x 0.6 mH 185 122 201 170 77.5 M6 10 60 A 3 x 0.33 mH 185 112 210 170 67 M8 16 90 A 3 x 0.22 mH 352 144 325 224 94 M10 35
170 A 3 x 0.13 mH 412 200 320 264 125 M10 M12*
Part. No.: 276996170
* Bolt for copper rail
Table 13: Output choke data for SK CO1-..., 3~ 480 V
Pos: 42 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und I nstallati on/2.9 Netzf ilter [BU 0 500] @ 0\ mod_1325863166231_388.docx @ 5986 @ 2 @ 1
240 A 3 x 0.07 mH 412 225 320 388 145 M10 M16*
BU 0505 GB-1013 35
SK 54xE – Users Manual for Frequency Inverters

2.9 Line filter

An additional external line filter can be installed into the line supply of the frequency inverter to maintain the increased noise suppression level (class B as per EN 55011).
Pos: 43 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.9 Netz filter -Teil 1 - Netzfilter SK NHD [BU 0 500] @ 1\mod_1331135215479_388.docx @ 17490 @ 5 @ 1

Mains filter SK NHD (up to size 4)

SK NHD type mains filters are so-called bottom-mounted combination filters with integrated mains choke. The mains filter is only intended for three-phase operation.
This provides a com pact unit to im prove the le vel of r adio inter fer ence suppr essi on, whic h can als o be mounted underneath the frequency inverter if there is a shortage of space.
For further information abo ut the overvolt age filter, ple ase ref er to the relevant data s heet. These data sheets can be downloaded from www.nord.com
.
Inverter ID Filter type Part No.
SK 5xxE-250-323-A -750-323-A SK 5xxE-111-323-A -221-323-A SK 5xxE-301-323-A -401-323-A SK 5xxE-550-340-A -750-340-A SK 5xxE-111-340-A -221-340-A SK 5xxE-301-340-A -401-340-A SK 5xxE-551-340-A -751-340-A
Table 14: Mains filter NHD-...
Pos: 44 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.9 Netz filter -Teil 2 - N etzfilter SK LF2 [BU 0500] @ 1\ mod_1331135342246_388.docx @ 17514 @ 5 @ 1
SK NHD-480/6-F SK NHD-480/10-F SK NHD-480/16-F
SK NHD-480/3-F
SK NHD-480/6-F SK NHD-480/10-F SK NHD-480/16-F
278273006 TI030 278273006 278273010 TI030 278273010 278273016 TI030 278273016 278273003 TI030 278273003 278273006 TI030 278273006 278273010 TI030 278273010 278273016 TI030 278273016
Data sheet

Mains filter SK LF2 (size 5 - 6)

SK LF2 type mains filter s are mains filters which can be bottom mounted, and their dimensions are matched to those of the relevant frequency inverter. This enables space-saving installation.
Inverter ID Filter type Part No.
SK 5xxE-551-323-A -751-323-A SK 5xxE-112-323-A
SK LF2-480/45-F SK LF2-480/66-F
278273045 TI030 278273045 278273066 TI030 278273066
Data sheet
SK 5xxE-112-340-A -152-340-A SK 5xxE-182-340-A -222-340-A
Table 15: Mains filter LF2-...
Pos: 45 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.9 Netz filter -Teil 3 - N etz filter SK HLD [B U 05 00] @ 1\mod_1331135394656_388.docx @ 17538 @ 5 @ 1
SK LF2-480/45-F SK LF2-480/66-F
278273045 TI030 278273045 278273066 TI030 278273066
36 BU 0505 GB-1013
2 Assembly and installation
SK 5xxE-551-323-A
SK HLD 110-500/30
270
55
95
255
30
10
SK 5xxE-751-323-A
SK HLD 110-500/42
310
55
95
295
30
10
SK 5xxE-112-323-A
SK HLD 110-500/75
270
85
135
255
60
35
SK 5xxE-182-323-A
SK 5xxE-152-340-A
SK 5xxE-182-340-A
SK HLD 110-500/55
250
85
95
235
60
16
SK 5xxE-222-340-A
SK HLD 110-500/75
270
85
135
255
60
35
SK 5xxE-372-340-A
SK 5xxE-552-340-A
SK 5xxE-902-340-A
2
L1
L2
L3
L3'
L2'
L1'
L2
L1
B2
T
Netz / LINE
Gerät / LOAD
B1

Mains filter SK HLD (above size 5)

In addition, a chassis m ains filter is availab le for inverters of size V and above. This enables Class B radio interf erenc e sup pression up to a max imum motor cable len gth of 25 m.
When connecting the line f ilter, com ply with "W iring guidelines" Secti on 0and "EMC" Section F ehler! Verweisquelle konnte nicht gefunden werden.. In particular, care must be taken that the pulse frequency is set to the default value (P504 = 6kHz). The line filter should be placed as close to the side of the inverter as possible.
The connection is b y means of screw connections o n the upper (mains) and lower (inverter) ends of the filter
Inverter ID
SK 5xxE-152-323-A
SK 5xxE-112-340-A
SK 5xxE-302-340-A
SK 5xxE-452-340-A
SK 5xxE-752-340-A
Table 16: Mains filter HLD-...
Pos: 46 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.9 Netz filter -Teil 4 - Spannungsbegrenzungsfilter SK CIF [BU 0500] @ 0\mod_1325863390898_388.docx @ 6009 @ 5 @ 1
Filter type
[-V/A]
SK HLD 110-500/100
SK HLD 110-500/42
SK HLD 110-500/130
SK HLD 110-500/180
SK HLD 110-500/250

Voltage limitation filter SK CIF

Detail: Mounting Connection
L1 W1 D
L2 B2
cross-
section
270 95 150 255 65 50
310 55 95 295 30 10
270 95 150 255 65 50
380 130 181 365 102 95
450 155 220 435 125 150
All dimensions in mm mm
Up to and including size 6 , the use of a sui table overvolta ge filter is m andatory (see a lso Section 1.5) in order to comply with cU L requirements. For f urther information about the o vervoltage filter, please refer to the relevant data sheet. These data sheets can be downloaded from www.nord.com
SK 5xxE-250-323-A -301-323-A* SK 5xxE-401-323-A -112-323-A* SK 5xxE-550-340-A -751-340-A SK 5xxE-112-340-A -222-340-A
* (only with suitable mains choke)
Table 17: Mains filter SK CIF-...
Pos: 47 /Anl eitungen/ Elektroni k/FU und Star t er/2. Mont ag e un d I ns t al l ation/2.1 0 El e k tr i s ch er Anschluss [BU 0 50 0] @ 0\mod_1325863603644_388.docx @ 6055 @ 2 @ 1
BU 0505 GB-1013 37
.
Inverter ID Filter type Part No.
SK CIF-323-20 SK CIF-323-40
SK CIF-340-30 SK CIF-340-60
276997070 TI030 276997070 276997071 TI030 276997071
276997080 TI030 276997080 276997081 TI030 276997081
Data sheet
SK 54xE – Users Manual for Frequency Inverters
In particular, the general and regional installation and safety regulations for work on high voltage systems (e.g.
lations concerning correct use of tools and the use of personal
Dangerous voltages can be present at the motor connection terminals even when the inverter is switched off.
Note
1 =
Mains connection
L1, L2/N, L3, PE
X1
2 =
Motor connection
U, V, W, PE
X2
3 =
multi-function relay
1 - 4
X3
4 =
Braking resistor
+B, -B
X2
5 =
DC - link circuit
-DC
X2
Above Size 8: + DC, - DC
6 =
Control terminals
IOs, GND, 24Vout, IG, DIP for AIN
X4, X5, X6, X7, X14
7 =
Technology unit
8 =
Link circui t choke
-DC, CP, PE
Above size 8:

2.10 Electrical connections

WARNING
THESE DEVICES MUST BE EARTHED. Safe operation of the devices presupposes that qualified personnel mount and operate it in compliance with the
instructions provided in these operat ing in struc t io ns.
VDE) must be complied with as must the regu protection equipment.
Always use insulated screwdrivers on these terminal fields. Ensure that the input voltage source is not live before setting up or changing connections to the unit.
Make sure that the inverter and motor have the correct supply voltage set.
Thermistor
As with other signal cables, thermistor cables must be laid separately from the motor cables
Depending on the size of the f requency inverter, the connection term inals for the supply cables and the control cables ar e located in different positions. According to the configuration of the frequency inverter, various terminals are not present.
Size 1 - 4 Size 5 - 7 Above size 8
à
38 BU 0505 GB-1013
2 Assembly and installation
9 =
communication
CAN/CANopen; RS232/RS485
à
X9/X10; X11
10 =
Thermistor
T1/2 or TF+/-
X13
Up to size 4 (except SK 54xE): to DIN 5
11 =
Safe pulse block
86, 87, 88, 89
X8
12 =
Control voltage VI 24V
40, 44
X12
Except SK 5x0E and SK 511E
Size 1 - 4 Size 5 - 7 Above size 8
Pos: 48 /Anl eitungen/El ektronik/FU und Start er/2. Mont age und Ins tallation/ 2.10.1 Ver drahtungsr ichtlini en [Allg.] @ 0\mod_1325863475147_388.docx @ 6032 @ 3 @ 1

2.10.1 Wiring guidelines

The frequency inverters have been developed for use in an industrial environment. In this environment, high le vels of electr omagnet ic interf erence can act on the freque ncy inver ter. In gener al, correct installation ensures safe and pro blem-free operation. T o meet the limiting v alues of the EMC directives, the following instructions should be complied with.
1. Ensure that all equipment in the control cabinet is securely earthed using short earthing cables which have large cross-sections and are connecte d to a common ear thing point or earth ing bar. It is especially important that each control unit which is connecte d to the electronic drive technol ogy (e.g. an automatic de vice) has a short c able with a lar ge cross-section, which is connected t o the same earthing point as the dfrequency inverter itself. Flat cables (e.g. metal stirrups) are preferable, as they have a lower impedance at high frequencies.
2. The bonding cable of the m otor contr o lle d by the frequency inverter s hou ld be c on nec ted d irec tly to the earthing terminal of the associated controller. The presence of a central earthing bar in the control cabinet and the grouping together of a ll bonding conductors to this bar normally ensures safe operation.
3. W here poss ible, shield ed cables should be us ed for contr ol circuits . The shie lding at th e cable end should be caref ully sealed and it m ust be e nsured th at th e wires are not laid over longer distances without shielding.
The shields of analog setpoint cables should only be earthed on one side on the device.
4. T he control cables sh ould be installe d as far as possible f rom power cables , using separate ca ble ducts, etc. Where cables cross, an angle of 90° should be ensured as far as possible.
5. Ensure that the contactors in the cabinet are interference protected, either by RC circuits in the case of AC contactors or by free-wheeling diodes for DC contactors, for which the interference traps must be positioned on the contactor coils. Varistors for o ver-voltage limitation are also effective. This inter ference suppression is partic ularl y impor tant when the c ontactors are contro lled by the relay in the frequency inverter.
6. Shi elded or arm oured c ables s hould be use d for the load co nnections (m otor c able). The sh ielding or armouring mus t be earthed at both ends. If possible, earthing should be made directly to t he electrically conducting mounting plate of the control cabinet or the screening angle of the EMC Kit.
BU 0505 GB-1013 39
SK 54xE – Users Manual for Frequency Inverters
The test equipment for high voltage insulations must not be used on cables that are connected to the motor
Jumper positions which are not illustrated below must not be used, as these may cause the destruction of the
In addition, EMC-compliant wiring must be ensured. If required, an optional output choke can be supplied
The safety regulations must be complied with under all circumstances when installing the
frequency inverter!
NOTICE
The control cables, mains cables and motor cables must be laid separately. Under no circumstances may they be installed in a common conduit or installation duct, in order to prevent interference.
controller. Failure to comply with this will cause damage to the drive electronics.
Pos: 49 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.2 Anpassung an IT-Netze [ BU 05 0 0] @ 1\ mod_1331196207398_388.docx @ 17782 @ 355 @ 1
Interference and damage

2.10.2 Adaptation to IT networks

As delivered, the dev ice is conf igured for operat ion in TN or TT net work s. Sim ple adaptat ions m ust be made for operation in an It network. However, these adaptations also cause a deterioration in the suppression of radio interference.
Up to and including s ize 7, the adaptat ion is made wit h jumpers. As delivered, the jum pers are set in the “normal position” . W ith this, the mains filter has its norm al eff ect and leak age c urrent. From size 8 and above there is a DIP switch element. According to the setting of the DIP switch, the f requency inverter is configured for TN/TT network operation or for operation in an IT network (also refer to Sections Fehler! Verweisquelle konnte nicht gefunden werden. and 0).
Frequency inverter Jumper A Jumper B Remarks Leakage current
Size 1 - 4 Position 1 Position 1 Operation in IT network Not applicable Size 1 - 4 Position 3 Position 2 Large filtering effect < 30 mA Size 1 - 4 Position 3 Position 3 Limited effect of filter
Size 5 - 6 Position 0 Position 1 Operation in IT network Not applicable Size 5 - 6 Position 4 Position 2 Large filtering effect < 6 mA Size 7 Position 0 Position 1 Operation in IT network Not applicable Size 7 Position 4 Position 2 Large filtering effect < 6 mA
Size 8 - 9 OFF Operation in IT network < 30 mA Size 8 - 9 ON Large filtering effect < 10 mA
DIP switch "EMC-Filter"
<< 30 mA
> 3.5 mA
Table 18: Integrated mains filter
Adaptation of sizes 1 - 7
NOTICE
frequency inverter.
Jumper positions
40 BU 0505 GB-1013
2 Assembly and installation
= Operation in IT network = Position 1 (reduced leakage current)
= normal position = Position 3
= Operation in IT network = Position 0 (reduced leakage current)
= normal position = Position 4
= Operation in IT network = Position 1
= normal position = Position 2
= reduced leakage current – Position 3
(The set pulse frequency (P504) only has a slight
influence on the leakage current.)
= Operation in IT network = Position 1 (reduced leakage current)
= normal position = Position 2
Geräte- Oberseite
Top side of device
Underside of the device
Underside of the device
Jumper “A” mains input Size 1 - 4
Size 5 - 7
Jumper 'B' motor output Size 1 - 4
Size 5 - 7
BU 0505 GB-1013 41
SK 54xE – Users Manual for Frequency Inverters
"OFF" position. The leakage current is reduced, with a
NOTICE
Errors in the link circuit coupling have especially negative effects on the charging circuits in the inverters or on the
phase devices, care must be taken that the coupling to the same external
Adaptation above size 8
The adaptation to the IT network is carried out via the DIP switch "EMC Filter" (1). As del ivered, this switc h is in t he "ON" position.
For operation in an IT network the switch must be s et to the
deterioration in the EMC com patibil ity.
Pos: 50 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.3 Gl eichspann ungskoppl ung [BU 05 00] @ 1\mod_1331196183481_388.docx @ 17758 @ 3 @ 1

2.10.3 DC-coupling

Overload of link circuits
It is essential to note the following summary of criteria for the setup of a DC supply or the coupling of the link circuits of frequency inverters.
life span of the link circuits - including their complete destruction.
In drive engineering, DC-coupling is advisable if m otors act as drivers and generators at the same time in the system. Here, the energ y from the drive which is acting as a generator can be fed back to the drive which is acti ng as a motor. T he advantages are lo wer energy consumptio n and the sparing use of braking resistor s. In addition, t he e nerg y balance c an be m ade eve n m ore ef ficient with the us e of a regenerative feed back unit or an input/feedbac k unit. In general, in c ase of D C c oupl in g, wh er ever
possible, devices w ith the same power should be c onnected together. Further more, only operational devices (whose link circuits are charged) must be coupled.
Connection
Size 1 … 7 +B, - DC Above size 8: + DC, - DC
NOTICE
DC coupling for single phase devices
For direct current coupling of single­conductor is used. Otherwise the device may be destroyed.
For the 115V devices (SK 5xx-xxx-112-O), no DC coupling is possible.
42 BU 0505 GB-1013
2 Assembly and installation
M
3~
PE U V W +B -B -DC
PE L3 L2 L1
L1 / L L2 / N L3 / ­PE
M
3~
PE U V W +B -B -DC
PE L3 L2 L1
Coupling if
FIs ready
Readiness
message from
all FIs
U1
U2
Fig. 6 Diagram of a DC-coupling
1 The link circuits of the individual frequency inverters must be protected with suitable fuses. 2 The frequency inverters only obtain their power supply via the link circuit. Electrical isolation is
carried out via the power circuit breakers which must be provided in the supplies to the devices.
3 CAUTION! Ensure that the coupling is only made after readiness is reported. Otherwise, there
is a danger that all the frequency inverters will be charged by a single one.
4 Ensure that the coupling is disconnected as soon as one of the devices is no longer ready for
operation.
5 For a high availability a braking resistor must be used. If different sizes of frequency inverters
are used, the braking resistor must be connected to the larger of the two frequency inverters.
6 If devices with the same rating (identical type) are coupled, and the same mains impedances
are in effect (identical lengths of cable to the mains rail), the frequency inverters may be operated without mains chokes. Otherwise a mains choke must be installed in the mains cable of each frequency inverter.
BU 0505 GB-1013 43
SK 54xE – Users Manual for Frequency Inverters
PE U V W +B -B -DC
PE L3 L2 L1
L1 / L L2 / N L3 / ­PE
M
3~
PE U V W +B
-B -DC
PE L3 L2 L1
M
3~
PE L3 L2 L1
Input/feedback
unit
For information on connection and protection, as well as the necessary accessories, please consult the manufacturer of the input/feedback unit.
+ -
Fig. 7 Diagram of a DC coupling with an input/feedback unit
The following points must be taken into consideration in association with a DC supply:
Pos: 51 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.4 Elektrisch er Anschlus s Leistung st eil [BU 0500] @ 0\ mod_1325863684752_388.docx @ 6078 @ 3 @ 1
44 BU 0505 GB-1013
1 Use a connecting cable which is as short as possible between the DC bus and the equipment to
be connected. The connection and protection of the devices in the DC circuit must be carried
out for cable protection and the maximum cross-section of the device. 2 The link circuits of the individual frequency inverters must be protected with suitable fuses. 3 The frequency inverters only obtain their supply via the link circuit. Electrical isolation is carried
out via the power circuit breakers which must be provided in the supplies to the devices. 4 For frequency inverters above size 8, a DC supply is only permissible with an external charging
device.
2 Assembly and installation
Connection to the output side (connection to the motor terminals) may cause the destruction of the brake or the

2.10.4 Electrical connections, power unit

Before connecting the frequency inverter, the following must be observed:
1. Ensure that the mains supply provides the correct voltage and is suitable for the current required.
2. Ens ure that sui table circuit br eak ers with t he s pecified nom inal cur rent range are instal led be tween the voltage source and the inverter.
3. Connect the mains voltage directly to the mains terminals L1-L2/N-L3-PE (for each device)
4. A four-core cable must be used to connect the motor. The cable is connected to the motor terminals PE-U-V-W.
5. If screened m otor cables (r ecom m ended) are us ed, the cable s cree ning m us t also be con nected to a large area of the m etallic screening angle of the EMC Kit, however, at least to the electricall y conducting mounting surface of the control cabinet.
6. Above size 8, the cable lugs which are included in the scope of delivery must be used. After crimping, these must be insulated with shrink hose.
Note
The use of shielded cables is essential in order to maintain the specified radio interference suppression level. If certain wire end sleeves are used, the maximum cross-section which can be connected can be reduced.
To connect the power unit, the following tools must be used:
Frequency inverter Tools Type
Size 1 - 4 Screwdriver SL / PZ1; SL / PH1 Size 5 - 7 Screwdriver SL / PZ2; SL / PH2 Size 8 - 9 Socket wrench SW 13
Table 19: Tools
Connection data:
Frequency inverter BG 1 ... 4 Size 5 Size 6 Size 7 Size 8 Size 9
Rigid cable Ø [mm²] 0.2 … 6 0.5 … 16 0.5 … 35 0.5 … 50 50 95 Flexible cable Ø [mm²] 0.2 … 4 0.5 … 10 0.5 … 25 0.5 … 35 50 95 AWG standard 24-10 20-6 20-2 20-1 1/0 3/0 Starting torque [Nm] 0.5 … 0.6 1.2 … 1.5 2.5 … 4.5 2.5 … 4 15 15
[lb-in] 4.42 … 5.31 10.62 … 13.27 22.12 … 39.82 22.12 … 35.4 135 135
Table 20: Connection data
NOTICE
The voltage supply for an electro-mechanical brake (or its brake rectifier) must be via the mains.
frequency inverter.
Brake voltage supply
Pos: 52 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.4 Elektrisch er Anschlus s Leistung steil -Teil 1 - N etz anschlus s (X 1) [BU 0500] @ 1\ mod_1331195429990_388.docx @ 17590 @ 5 @ 1
BU 0505 GB-1013 45
SK 54xE – Users Manual for Frequency Inverters
NOTICE
It is urgently recommended that the frequency inverter is only operated on a IT network if a braking resistor is
lt occurs in the IT network, this measure prevents an impermissible charging of the
NOTICE
ched as long as the inverter is pulsing (The inverter must be in "Standby" or
Mains connections (X1 – PE, L1, L2/N, L3)
No special safety measures are required on the mains input side of the frequency inverter. It is advisable to use the normal mains fuses (see technical data) and a main switch or circuit breaker.
Frequency inverter data Permissible mains data
Voltage Power 1 ~ 115 V 1 ~ 230 V 3 ~ 230 V 3 ~ 400 V
115 VAC 0.25 … 0.75 kW X 230 VAC 0.25 … 2.2 kW X X 230 VAC ≥ 3.0 kW X 400 VAC ≥ 0.37 kW X
Connections
L/N = L1/L2 L/N = L1/L2 L1/L2/L3 L1/L2/L3
Isolation from or connection to the mains must always be carried out for all the poles and synchronously (L1/L2/L2 or. L1/N).
Operation in IT networks
The use of this frequency inverter on an IT network is possible after modification of the integrated mains filter.
connected. If an earthing fau link circuit capacitor and the associated destruction of the frequency inverter.
For operation with an insulation monitor, the insulation resistance of the frequency inverter must be taken into account.
Pos: 53 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.4 Elektrisch er Anschlus s Leistung steil -Teil 2 - M ot orkabel (X2) [B U 05 0 0] @ 1\ mod_1331195941727_388.docx @ 17638 @ 5 @ 1
Motor cable (X2 - U, V, W, PE)
The motor cable may have a total length of 100m if this is a standard cable (take EMC into consideration). If a s creene d m otor cable is used, or if the c able is laid in a m etal condu it which is wel l earthed, the total length should not exceed 30m.
For greater lengths of cable, an additional output choke (accessory) must be used. For multiple m otor operation the t otal motor cable length cons ists of the sum of the indiv idual cable
lengths.
Output switching
The motor cable must not be swit "Starting disabled" status).
Otherwise the inverter nay be damaged.
Pos: 54 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.4 Elektrisch er Anschlus s Leistung steil -Teil 3 - Bremswiderstand (X2) [BU 0500] @ 1\mod_1331195973501_388.docx @ 17662 @ 5 @ 1
Breake resistor (X2 - +B, -B)
The terminals +B/ -B are inten ded for the connection of a suitable brak ing resistor. A short screened connection should be selected. For the installation of a braking resistor, the large amount of heat which is generated due to its operation (> 70°C) must be taken into account.
Pos: 55 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.5 Elektrisch er Anschlus s Steuert eil [BU 0500 ] @ 0\mod_1325864707420_388.docx @ 6124 @ 3 @ 1
46 BU 0505 GB-1013
2 Assembly and installation
NOTICE
If the cable are laid in parallel, a minimum distance of 20cm must be maintained from cables which carry a
NOTICE

2.10.5 Electrical connections, control unit

The control connections ar e located under the front cover (abo ve size 8 under th e two front c overs) of the frequency inverter. The configuration differs according to the size. Up to size 7, the individual control terminals (X3, X8, X13) are in staggered positions (please also refer to Section 2.10).
Connection data:
Frequency inverter All Size 1 … 4 Size 5 … 7
Terminal block Typically X3
Rigid cable Ø [mm²] 0.14 … 1.5 0.14 … 2.5 0.2 … 6 0.2 … 2.5 Flexible cable Ø [mm²] 0.14 … 1.5 0.14 … 1.5 0.2 … 4 0.2 … 2.5 AWG standard 26-16 26-14 24-10 24-12 Starting torque [Nm] Clamping 0.5 … 0.6 0.5 … 0.6 Clamping
[lb-in] 4.42 … 5.31 4.42 … 5.31
X3, X8,
X12, X13
Above size 8:
X3.1/2,
X15
GND/0V is a common reference potential for analog and digital inputs. Furthermore, it m ust be taken into ac count t hat with SK 5x5E size 1 ... 4 frequency invert ers, term inal
44 is used to feed in the control voltage. However with devices of size 5 and above, this terminal provides a 24V control voltage.
Cable laying
All control cables (including the thermistor) must be laid separately from the mains and the motor cables, in order to prevent interference to the inverter.
voltage >60V The minimum distance may be reduced by screening the cables which carry a voltage, or by the use of earthed metal partitions within the cable conduits.
Total currents
5V / 15V (24V) can be obtained from several terminals if required. With size 1 ... 4, the total output current must not exceed 250mA/150mA (5V/15V). Above Size 5 the limiting value is 250mA/200mA (5V/24V).
Pos: 57 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.5 Elektrisch er Anschlus s Steuert eil- Klemme nbl ock X3 - Relais [SK 54xE] @ 2\mod_1355474566232_388.docx @ 52090 @ 5 @ 1
BU 0505 GB-1013 47
SK 54xE – Users Manual for Frequency Inverters
Terminal block X3, (above size 8: X3.1 and X3.2) - Relay
Relevance
SK 540E SK 545E
Terminals X3: Name
Terminal Function
[Factory setting]
1 2
3 4
Output 1 [Braking control]
Output 2 [Ready/Fault]
Pos: 59 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.5 Elektrisch er Anschlus s Steuert eil- Klemme nbl ock X4 – Analog I/O [SK 54xE] @ 2\mod_1355475239499_388.docx @ 52114 @ 55 @ 1
1 2 3 4
K1.1 K1.2 K2.1 K2.2
Data Description / wiring suggestion Parameter
Relay closing contact 230 VAC, 24 VDC, < 60 VAC in circuits with
safe isolation, ≤ 2 A
Brake control (closes on enabling)
Fault / Ready (closes when FI ready / no fault)
P434 [-01]
P434 [-02]
48 BU 0505 GB-1013
2 Assembly and installation
11 12 14 16 17
R=10k
AIN2:
1
= Current 0/4 … 20 mA
V
= Voltage
AIN1:
V
= Voltage
S4:
AIN2:
ON
= ± 10 V
OFF
= 0 … 10 V
S3:
AIN1:
OFF
= 0 … 10 V
S2:
AIN2:
1
= ON = current 0/4...20 mA
V
= OFF = voltage
S1:
AIN1:
1
= ON = current 0/4...20 mA
If S1 = ON (AIN1 = Current input), S3 must be = OFF.
Terminal block X4 – Analog I/O
Relevance
Terminals X4: Name
SK 540E SK 545E
11 12 14 16 17
VO 10V GND/0V AIN1 AIN2 AOUT1
Terminal Function
[factory setting]
11 10V Reference
voltage
12 Reference potential
for analog signals
14 Analog input 1
[set point frequency]
16 Analog input 2
[no function]
17 Analog output
[no function]
Data Description / wiring suggestion Parameter
10V, 5mA
The analog input controls the output frequency of the frequency inverter.
0V analog
V=0...10V, R I=0/4...20mA, R
=30k,
i
=250,
i
can be switched over with DIP switch, reference voltage GND.
For the use of digital functions 7.5...30V.
Above Size 5:
The possible digital functions are described in Parameter P420.
Above Size 5: Configuration of analog input with DIP
switch (see below)
P400 [-01] P420 [-08]
P400 [-02] P420 [-09]
also -10 … + 10 V signals
0...10V Reference potential GND
Max. load current:
Can be used for an external display or for further processing in a following machine.
P418 [-01]
5mA analog, 20mA digital
Configuration of analog signals
Size 1 … 4
1 = DIP switch: left = I / right = V
1 = Current 0/4 … 20 mA
Above Size 5:
1 = DIP switch: left = ON / right = OFF
ON = ± 10 V
V = OFF = voltage
Note: If S2 = ON (AIN2 = Current input), S4 must be = OFF.
Pos: 61 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.5 Elektrisch er Anschlus s Steuert eil- Klemme nbl ock X5 – Digital In [SK 54xE] @ 2\ mod_1355475285848_388.docx @ 52138 @ 5 @ 1
BU 0505 GB-1013 49
SK 54xE – Users Manual for Frequency Inverters
21 22 23 24 39 38 42 40
motor - PTC
15V
21 22 23 24 39 38 42 40
motor - PTC
GND / 0V
7.5 … 30V
[Fixed frequency 1,
Terminal block X5 – Digital In
Relevance
Terminals X5: Name
SK 540E
21 22 23 24 39 38 42 40
DIN1 DIN2 DIN3 DIN4 TF- TF+ VO 15V GND/0V
Terminal Function
[factory setting]
21 Digital input 1
[ON right]
22 Digital input 2
[ON left]
23 Digital input 3
[parameter set bit0]
24 Digital input 4
P429] 39 Thermistor input ­38 Thermistor input +
42
15V output power supply
40 Reference potential
for digital signals
SK 545E
Data Description / wiring suggestion Parameter
7.5...30V, Ri=6.1k Not suitable for thermistor
evaluation.
Each digital input has a reaction time of ≤ 5ms.
Connection with internal 15V:
P420 [-01]
P420 [-02]
HTL encoders can only be connected to DIN2 and
P420 [-03]
DIN4 Limiting frequencies:
max. 10 kHz min. 15 Hz
P420 [-04]
Connection with external 7,5-30V:
potential isolated thermistor input, which cannot be disabled, for monitoring the motor temperature with a PTC
Supply voltage provided by the
15V ± 20%
frequency inverter for connection to the digital inputs or the supply of a 10-30V encoder.
0V digital Reference potential
50 BU 0505 GB-1013
2 Assembly and installation
21 22 23 24 39 38 44 40
motor - PTC
GND / 0V
18 … 30V
21 22 23 24 25 41 44 40
GND / 0V
18 … 30V
[Fixed frequency 1,
Relevance
Terminals X5:
Name
SK 540E
21 22 23 24 25 / 39 41 / 38 44* 40
DIN1 DIN2 DIN3 DIN4 DIN5 / TF- VO 5V / TF+ V…24V GND/0V
Terminal Function
[factory setting]
21 Digital input 1
[ON right]
22 Digital input 2
[ON left]
23 Digital input 3
[parameter set bit0]
24 Digital input 4
P429] 25 Digital input 5
[no function] 39 Thermistor input ­38 Thermistor input +
41
5V output power supply
44
Size 1 to Size 4 VI 24V supply voltage input
Size 5 and above VO 24V supply voltage output
40 Reference potential
for digital signals
Pos: 63 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.5 Elektrisch er Anschlus s Steuert eil- Klemme nbl ock X6 – Encoder [ S K 54 xE] @ 2\mod_1355475336807_388.docx @ 52162 @ 5 @ 1
SK 545E
SK 510E SK 511E SK 515E SK 520E SK 530E SK 535E
* Terminal 44:
up to Size 4: VI
Size 5 and
above: VO
Data Description / wiring suggestion Parameter
7.5...30V, Ri=6.1k Not suitable for thermistor
evaluation.
Each digital input has a reaction time of ≤ 5ms.
Sizes 1 to 4
P420 [-01]
P420 [-02]
HTL encoders can only be connected to DIN2 and
P420 [-03]
DIN4 Limiting frequencies:
max. 10 kHz min. 15 Hz
P420 [-04]
Above size 5
Available: above size 5 P420 [-05]
available: Size 1 - 4
potential isolated thermistor input, which cannot be disabled, for monitoring the motor temperature with a PTC
Available: above size 5
5V ± 10% 18…30V
at least 800mA (input)
Voltage supply for the FI control unit. Is essential for the function of the frequency inverter.
Supply voltage provided by the frequency inverter for connection to the digital inputs or the supply of a 10-30V
24V ± 25% max. 200mA (output)
encoder. The 24V control voltage is generated by
the FI, however it can alternatively be supplied via the terminals X12:44/40 (size 8 and above: X15:44/40). Supply via terminal X5:44 is not possible.
0V digital Reference potential
BU 0505 GB-1013 51
SK 54xE – Users Manual for Frequency Inverters
Terminal block X6 – Encoder
Relevance
Terminals X6: Name
SK 540E SK 545E
49 51 52 53 54
VO 12V ENC A+ ENC A- ENC B+ ENC B-
Terminal Function
[factory setting]
49
12V output power supply
51 Track A 52 Track A inverse 53 Track B 54 Track B inverse
Pos: 65 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.5 Elektrisch er Anschlus s Steuert eil- Klemme nbl ock X7 – Digital I/O [SK 54 xE] @ 2\ mod_1355475437641_388.docx @ 52186 @ 5 @ 1
Data Description / wiring suggestion Parameter
12V ± 20% max. 150mA
The incremental encoder input can be used for the exact regulation of speed of rotation, additional set point functions or positioning.
TTL, RS422 500…8192Imp./Rpm. Limiting frequencies:
max. 205 kHz min. 250 Hz
An encoder system with 10-30V supply voltage must be used in order to compensate for voltage drop in long cable connections.
Note: Encoders with 5V supply are not suitable in order to set up a system
P300
which operates reliably.
52 BU 0505 GB-1013
2 Assembly and installation
ibed for terminal block X5, DIN1
Not suitable for the evaluation of a motor
The digital input (DIN7) can also be used
scope of functions corresponds to that of
Terminal block X7 – Digital I/O
Relevance
Terminals X7: Name
SK 540E
73 74 26 27 5 7 42 40
RS485 + RS485 - DIN6 DIN7 DOUT1 DOUT2 VO 15V GND/0V
Terminal Function
[factory setting]
73
Data cable RS485
74
26 Digital input 6
[no function] 27 Digital input 7
[no function]
Alternatively: Output 5 (DOUT3)
[no function]
5 Output 3 (DOUT1)
[no function] 7 Output 4 (DOUT2)
[no function] Alternatively:
Digital input 8
[no function]
42
15V output power supply
40 Reference potential
for digital signals
SK 545E
Data Description / wiring suggestion Parameter
Baud rate 9600…38400Baud
Termination resistance R=120
BUS connection parallel to RS485 on RJ12 plug
NOTE: The termination resistance of DIP switch 1 (see RJ12/RJ45) can also be used for terminal 73/74.
As descr
7.5...30V, Ri=3.3k
to DIN5.
thermistor.
as a digital output (DOUT3).
Digital output 15V, max. 20mA
For inductive loads: provide protection with a free-wheeling diode.
If P434 [-05] and P420 [-07] are parameterised with functions, a High signal of the DOUT function results in a High signal for the DIN function.
For evaluation in a control system. The the relay (P434).
The digital output (DOUT2) can also be used as a digital input (DIN3).
7.5...30V, Ri=3.3k
If P434 [-04] and P420 [-10] are parameterised with functions, a High signal of the DOUT function results in a High signal for the DIN function.
Voltage supply for connection to the
15V ± 20%
digital inputs or the supply of a 10-30V encoder
0V digital
P503 P509
P420 [-06]
P420 [-07]
P434 [-05]
P434 [-03]
P434 [-04]
P420 [-10]
BU 0505 GB-1013 53
SK 54xE – Users Manual for Frequency Inverters
As described for terminal block X5, DIN1
Not suitable for the evaluation of a motor
The digital input (DIN7) can also be used
Relevance
Terminals X7:
Name
SK 540E
73 74 26 27 5 7 44* 40
RS485
+
Terminal Function
[factory setting]
73
74
Data cable RS485
26 Digital input 6
[no function] 27 Digital input 7
[no function]
Alternatively: Output 5 (DOUT3)
[no function]
5 Output 3 (DOUT1)
[no function] 7 Output 4 (DOUT2)
[no function]
Alternatively:
Digital input 8
[no function]
44 Size 1 to Size 4
VI 24V supply voltage input
Size 5 and above VO 24V supply voltage output
40 Reference potential
for digital signals
Pos: 67 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Inst al l ation/2.1 0. 5 Elektrisch er Anschluss St euerteil- Kl e m m e nbl ock X8 – Sichere Pulssperre [SK 54xE] @ 2\mod_1355475452079_388.docx @ 52210 @ 5 @ 1
SK 545E
RS485 - DIN6 DIN7 DOUT1 DOUT2 V…24V GND/0V
* Terminal 44:
up to Size 4: VI
Size 5 and
Data Description / wiring suggestion Parameter
Baud rate 9600…38400Baud
Termination resistance R=120
7.5...30V, Ri=3.3k
BUS connection parallel to RS485 on RJ12 plug
NOTE: The termination resistance of DIP switch 1 (see RJ12/RJ45) can also be used for terminal 73/74.
to DIN5.
thermistor.
Digital output S1 to S4 18-30V, according to VI
24V, max. 20mA size 5 and above
DOUT1 and DOUT2:
24V, max. 200mA
For inductive loads: provide protection with a
as a digital output (DOUT3). If P434 [-05] and P420 [-07] are
parameterised with functions, a High signal of the DOUT function results in a High signal for the DIN function.
For evaluation in a control system. The scope of functions corresponds to that of the relay (P434).
free-wheeling diode.
The digital output (DOUT2) can also be used as a digital input (DIN3).
7.5...30V, Ri=3.3k
If P434 [-04] and P420 [-10] are parameterised with functions, a High signal of the DOUT function results in a High signal for the DIN function.
18…30V at least 800mA (input)
Voltage supply for the FI control unit. Is essential for the function of the frequency inverter.
Supply voltage provided by the frequency inverter for connection to the digital inputs or the supply of a 10-30V
24V ± 25% max. 200mA (output)
encoder. The 24V control voltage is generated by
the FI, however it can also be supplied via the terminals X12:44/40. Supply via terminal X7:44 is not possible.
0V digital
above: VO
P503 P509
P420 [-06]
P420 [-07]
P434 [-05]
P434 [-03]
P434 [-04]
P420 [-10]
54 BU 0505 GB-1013
2 Assembly and installation
Terminal block X8 – Safe pulse lock (not with 115V devices)
Relevance
Terminal X8: Name
SK 540E
VO_S 15V VO_S 0V VI_S 0V VI_S 24V
SK 545E
86 87 88 89
Terminal Function
[factory setting]
86 Supply voltage 87 Reference potential 88 Reference potential 89 Input
'safe pulse block'
Relevance
Terminal X8: Name
SK 540E
VO_S 24V VO_S 0V VI_S 0V VI_S 24V
SK 545E
86 87 88 89
Data Description / wiring suggestion Parameter
Details: BU0530!
When setting-up without using a safety function, wire directly to V_IS 24V.
P420 [-…]
Details: BU0530! Fail-safe input
Terminal Function
[factory setting]
86 Supply voltage 87 Reference potential 88 Reference potential 89 Input
'safe pulse block'
Pos: 69 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.5 Elektrisch er Anschlus s Steuerteil - Steckerbloc k X9 und X10 – CAN / CAN o pe n [S K 54xE] @ 2\mod_1355475468662_388.docx @ 52234 @ 5 @ 1
Data Description / wiring suggestion Parameter
Details: BU0530!
When setting-up without using a safety function, wire directly to V_IS 24V.
P420 […]
Details: BU0530! Fail-safe input
BU 0505 GB-1013 55
SK 54xE – Users Manual for Frequency Inverters
CAN _H
CAN _L
CAN _G N D
nc
CAN _SH LD
CAN _G N DncCAN_24V
CAN _H
CAN _L
CAN _G N D
nc
CAN _SH LD
CAN _G N DncCAN_24V
External 24VDC
RS485_A
RS485_B
GND
TXD
RXD
+ 5V
1 2
ON
CAN _H
CAN _L
CAN _GN DncCAN _SHLD
CAN _GN DncCAN_24V
CAN _H
CAN _L
CAN _GN DncCAN _SHLD
CAN _GN DncCAN_24V
Plug connector block X9 and X10 – CAN / CANopen
Relevance
Terminals X9: / X10:
Name
SK 540E SK 545E
1 2 3 4 5 6 7 8
CAN_H CAN_L CAN_GND nc nc CAN_SHD CAN_GND CAN_24V
Contact Function
[factory setting]
1 2
CAN/CANopen signal
3 CAN GND 4
No function
5 6 Cable shi eld 7 GND/0V 8
voltage supply
DIP-1 Termination resistor for RS485 interface
(RJ12); ON = switched in [Default = "OFF"] For RS232 communication DIP1 to "OFF"
Data Description / wiring suggestion Parameter
Baud rate …500kBaud RJ45 sockets are connected
in parallel internally. Terminal resistance
R=120DIP 2 (see below) NOTE: To operate
CANbus/CANopen the interface must be externally supplied with 24V (capacity at least 30 mA).
DIP switch 1/2 (top side of frequency inverter)
X10 X9
2x RJ45: Pin No. 1 … 8
NOTE: This CANopen interface can be used for the evaluation of an absolute encoder. Further details can be found in manual BU 0510.
Recommendation: Provide strain relief (e.g. with EMC Kit)
X11 X10 X9
P503 P509
DIP 2
Pos: 71 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.5 Elektrisch er Anschlus s Steuert eil- Steckerbl ock X11 – RS485 / RS232 [SK 54xE] @ 2\mod_135547 5491285_388.docx @ 52258 @ 5 @ 1
56 BU 0505 GB-1013
Terminal resistor for CAN/CANopen interface (RJ12); ON = switched in [Default = "OFF"]
RS232/485 DIP CAN/CANopen
2 Assembly and installation
RS485_A
RS485_B
GND
TXD
RXD
+5V
RXD
0V
TXD
6
1
5 9
TxD RxT
GND
+ 5V
n.c. n.c.
RS485_A
RS485_B
GND
TXD
RXD
+ 5V
1 2
ON
CAN _H
CAN _L
CAN _GN DncCAN _SHLD
CAN _GN DncCAN_24V
CAN _H
CAN _L
CAN _GN DncCAN _SHLD
CAN _GN DncCAN_24V
Plug connector block X11 – RS485 / RS232
Relevance
Terminals X11: Name
SK 540E SK 545E
1 2 3 4 5 6
RS485 A + RS485 A- GND 232 TXD 232 RXD +5V
Contact Function
[factory setting]
Note: Coupling of two frequency inverters via the RJ12 socket must only be made via the USS BUS (RS485). Care must be taken that
no connection to the data cable is possible via RS232, in order to prevent damage to this interface.
1 2
Data cable RS485
3 Reference potential
for bus signals
(must always be wired!)
4
Data cable RS232
5 6 Inter na l 5V supply
voltage
optional Adapter cable
RJ12 to SUB-D9 for RS232
communication for direct connection
to a PC with NORD CON
Data Description / wiring suggestion Parameter
Baud rate 9600…38400Baud
Terminal resistance R=120DIP 1 (see below)
0V digital
Baud rate 9600…38400Baud
RJ12: Pin No. 1 … 6
5V ± 20% Length 3m
Assignment of the SUB-D9 plug socket:
Part No. 278910240
P503 P509
DIP switch 1/2 (top side of frequency inverter)
DIP-1 Termination resistor for RS485 interface
X11 X10 X9 (RJ12); ON = switched in [Default = "OFF"] For RS232 communication DIP1 to "OFF"
DIP 2
Terminal resistor for CAN/CANopen interface (RJ12); ON = switched in [Default = "OFF"]
RS232/485 DIP CAN/CANopen
Pos: 73 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.5 Elektrisch er Anschlus s Steuert eil- Klemme nbl ock X12 – 24V [SK 54xE] @ 2\mod_1355475508380_388.docx @ 52282 @ 5 @ 1
BU 0505 GB-1013 57
SK 54xE – Users Manual for Frequency Inverters
Voltage supply for the FI control unit. Is
n of the
frequency inverter.
Terminal block X12 – 24 VDC input (only size 5 … 7)
Relevance
Terminals X12: Name
SK 540E
GND VI 24V
SK 545E
40 44
Terminal Function
[factory setting]
44
Voltage supply input
40 Reference potential
for digital signals
Data Description / wiring suggestion Parameter
24V / 30V min. 1000mA
GND/0V Reference potential
Pos: 75 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.5 Elektrisch er Anschlus s Steuert eil- Klemme nbl ock X13 – Motor PTC [SK 5 4xE] @ 2\mod_1355475568437_388.docx @ 52306 @ 5 @ 1
Terminal block X13 – motor PTC (only size 5 … 7)
Relevance
SK 540E
Terminals X13: Name
SK 545E
T1 T2
T1 T1
essential for the functio
Terminal Function
[factory setting]
T1 Thermistor input + EN 60947-8 T2
Thermistor input -
Data Description / wiring suggestion Parameter
On: >3.6 kΩ Off: < 1.65 kΩ
Measurement voltage 5 V at R < 4 kΩ
Pos: 76 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.5 Elektrisch er Anschlus s Steuert eil- Klemme nbl ock X14 – Univ ersal Geber - Interface [SK 54xE] @ 1\mod_1341402965467 _388.docx @ 29493 @ 5 @ 1
The function cannot be switched off, set a jumper if no PTC is present.
58 BU 0505 GB-1013
2 Assembly and installation
Voltage supply for the FI control unit. Is essential for the function of the
Terminal block X14 – Universal encoder interface
Relevance
Terminals X14: Name
SK 540E SK 545E
66 65 64 63
DAT- DAT+ CLK- CLK+
Terminal Function
[factory setting]
66 Signal DAT-
(RS485 DAT-)
65 Signal DAT+
(RS485 DAT+) 64 Signal CLK­63 Signal CLK+
Data Description / wiring suggestion Parameter
For the connection of SSI, BISS, EnDat and Hiperface encoders.
TTL, RS422
For the connection of SSI, BISS and EnDat encoders.
Pos: 78 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.10.5 Elektrisch er Anschlus s Steuert eil- Klemme nbl ock X15 – Motor PT C un d 24V input [SK 54 x E] @ 2\ mod_1355475594559_388.docx @ 52330 @ 5 @ 1
Terminal block X15 – motor PTC and 24V input (above size 8)
Relevance
SK 540E
SK 545E
P300,
(P604,
however only
POSICON)
for
Terminals X15: Name
38 39 44 40
T1 T2 VI 24V GND
Terminal Function
[factory setting]
38
Thermistor input +
39
Thermistor input -
44
Voltage supply input
40 Reference potential
for digital signals
Data Description / wiring suggestion Parameter
EN 60947-8
On: >3.6 kΩ Off: < 1.65 kΩ
The function cannot be switched off, set
a jumper if no PTC is present. Measurement voltage 5 V at R < 4 kΩ
24V … 30V min. 3000mA
frequency inverter. GND/0V Reference potential
Pos: 79 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.11 Far b- und Kontak tb elegung für Dr ehgeber [BU 0 50 0] @ 0\ mod_1325865982124_388.docx @ 6147 @ 2 @ 1

2.11 Colour and contact assignments for encoders

The incremental encod er connect ion is an inp ut for a type w ith two track s and TTL-compatible signa ls for EIA RS 422-c ompliant drivers. The m aximum current consumption of incremental encoders must not exceed 150 mA.
The pulse number per rotation can be between 500 and 8192 increments. This is set with t he normal scaling via parameter P301 "Incremental encoder pulse number" in the menu group "Control parameters". For cable lengths > 20 m and m otor speeds above 1500 rpm the encoder should not have more than 2048 pulses/revolution.
BU 0505 GB-1013 59
SK 54xE – Users Manual for Frequency Inverters
The counting direction of the incremental encoder must correspond to that of the motor. Therefore, depending on jumps between 0 and 0.8V the relevant rack is faulty. The position can no longer be determined via the
30V encoder, TTL/RS422) for the
For longer cable lengths the c able cross-section must be selected large e nough so that the voltage drop in the cable is not too great. This partic ularly aff ects the supply cable, in which the cros s-section can be increased by connecting several conductors in parallel.
Unlike incremental e ncoders, for sine e ncoders or SIN/COS e ncoders the sign als are not in the f orm of pulses, but rather in the form of sine signals (shifted by 90°).
Note
the rotation direction of the encoder to the motor (possibly reversed), a negative number must be set in parameter P301.
Note
The voltage difference between tracks A and B can be measured with the aid of parameter P709 [-09] and [-10]. If the incremental encoder is rotated, the value of both tracks must jump between -0.8V and 0.8V. If the voltage only
incremental encoder. We recommend replacement of the encoder!
Encoder counting direction
Rotary encoder function test
Pos: 80 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.11 Far b- und Kontak tb elegung für Dr ehgeber- Inkrementalgeber [SK 5xxE] @ 1\mod_1331216115763_388.docx @ 17854 @ 5 @ 1

Incremental encoder

According to the resolution (pulse number), incremental encoders generate a defined number of pulses for each rotat ion of the encod er shaft (Tr ack A / Track A invers e) With this , the precise speed of the encoder or m otor can be meas ured by the fr equency in verter. B y the use of a second track (B / B inverse) shifted by 90° (¼ period), the direction of rotation can also be determined.
The supply voltage for t he encoder is 10-30V. The voltage sour ce can be an external source or the internal voltage (according to the frequency inverter version: 12V /15V /24V).
Function
Cable colours,
for incremental encoder
Connections for SK 53xE
Terminal block X5 or X6
10-30V supply brown / green
0V supply white / green Track A brown Track A inverse green Track B grey Track B inverse pink Cable shield connected to a large area of the frequency inverter housing or shielding angle
Table 21: Colour and contact assignments for NORD TTL incremental encoders
42(/44 /49)
15V (/24V /12V)
40 GND/0V 51 ENC A+
52 ENC A-
53 ENC B+
54 ENC B-
Note
If there are deviations from the standard equipment (Type 5820.0H40, 10­motors, please note the accompanying data shee t or consul t your suppl ier.
Incremental encoder data sheet
Pos: 81 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.11 Far b- und Kontak tb elegung für Dr ehgeber- Si nus - Geber [SK 54xE] @ 1\mod_1331216120711_388.docx @ 17878 @ 5 @ 1
60 BU 0505 GB-1013
2 Assembly and installation
* E.g. Kübler 5824

Sinus encoder (SIN/COS encoder)

The use or function of sine encoders is comparable with that for incr emental encoders . However, the encoder provides sine wave signals instead of digital pulses.
The supply voltage for t he encoder is 10-30V. The voltage sour ce can be an external source or the internal voltage (according to the frequency inverter version: 12V /15V /24V).
Function
Cable colours
for Sin/Cos encoder*
10-30V supply brown 0V supply white
Track A green Track A inverse yellow Track B grey Track B inverse pink
Assignment for SK 54xE
Terminal block X5 or X6
42(/44 /49)
15V (/24V /12V)
40 GND/0V 51 ENC A+
52 ENC A-
53 ENC B+
54 ENC B-
Cable shield connected to a large area of the frequency inverter housing or shielding angle
Table 22: Colour and contact assignment for SIN/COS encoders
Function Signal designation Signal voltage
Sine signal Sin max. 5V Uss Cosine signal Cos max. 5V Uss
Table 23: Signal details for SIN/COS encoders
Pos: 82 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.11 Far b- und Kontak tb elegung für Dr ehgeber- Hi p er f ace Geber [S K 54 x E] @ 1\mod_1331216123668_388.docx @ 17902 @ 5 @ 1

Hiperface encoder

Hiperface is a mixtur e of incremental encoder an d absolute enco der and combine s the advantages of both encoder types. The absolute va lue is initially only formed when the device i s switched on and is communicated by the RS485 specification bus parameter interface to the external counter in the controller, which then continues counting incrementally from this absolute value using the analog sine/cosine signal. Dur ing oper atio n the co unted p osition is conti nuous l y compar ed with th e m easured absolute position of the encoder.
Hiperface encoders are suitable for positioning in combination with servo mode. The requirements for the analog signal are shown in the following table. It must be noted that the
tolerances in the voltages affect the precision of the determined position. The supply voltage f or the encoder is 7-12V. An external source or the int ernal 12V voltage can be
used as the voltage supply.
BU 0505 GB-1013 61
SK 54xE – Users Manual for Frequency Inverters
U
U
Function Signal designation Signal voltage
Sine reference voltage Sin Ref 2.5V Um Cosine reference voltage Cos Ref 2.5V Um Sine signal Sin 1V Uss Cosine signal Cos 1V Uss
Table 24: Signal details for Hiperface encoders
ss
Function
Cable colours, for Hiperface
encoders
7-12V supply red 0V supply blue + SIN white REFSIN brown +COS pink REFCOS black Data + (RS485) grey or yellow Data - (RS485) green or violet
Connections for SK 54xE
Terminal block X5, X6 or X14
49 VO 12V 40 GND/0V 51 ENC A+
52 ENC A- 53 ENC B+
54 ENC B-
65 DAT +
66 DAT-
Cable shield connected to a large area of the frequency inverter housing or shielding angle
Table 25: Colour and contact assignment for Hiperface encoders
Note
Rotary encoder function test
The voltage difference between the SIN and COS tracks can be measured with the aid of parameter P709 [-09] and [-10]. If the Hiperface encoder is rotated, the voltage difference should range between approx. -0.5V and
0.5V.
Pos: 83 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.12 RJ 45 WAGO- Ans c hl ussmodul [Al l g . ] @ 0\ mod_1325866182423_388.docx @ 6170 @ 2 @ 1
62 BU 0505 GB-1013
2 Assembly and installation
Contact
1 2 3 4 5 6 7 8 S
Meaning
CAN_H CAN_L CAN_GND nc. nc. CAN_SHD CAN_GND CAN_24V
Shield
Ethernet connection module with CAGE CLAMP
Getriebebau NORD GmbH &

2.12 RJ45 WAGO- Connection module

This adapter module can be used for the simple wiring of functions of the RJ45 conn ec tion (2 4V s up ply voltage, CANopen absolute encoder, CANbus) with normal cables.
Pre-assembled RJ45 p atch cables are connect ed to the spring­loaded terminals (1-8 + S) with this adapter.
The shield clamp should be used in order to ens ure the correct connection and relief of tension on the shield.
Supplier Name Article number
WAGO Kontakttechnik GmbH
connection RJ45 transfer module
WAGO Kontakttechnik GmbH Accessories: WAGO shield clamp 790-108
Alternative, complete connection module and shield clamp Part No.
289-175
Adapter module RJ45/terminal
Co.KG
Table 26: RJ45 WAGO connection module
Pos: 84 /Anl eitungen/ Elektroni k/FU und Star ter/2. Mo ntage und Installati on/2.13 Soll wertkarte ± 10V [BU 0500] @ 0\ mod_1325866300204_388.docx @ 6193 @ 2 @ 1
278910300
BU 0505 GB-1013 63
SK 54xE – Users Manual for Frequency Inverters
verters size 1 to
20mA) with
10V … + 10V)) is
available, this mus t be converte d to a 0 … 10V sig nal b y means of
ter. In this case, the appropriate module is
­mounting and should be in stalled near to the freque ncy inverter in the control cabinet. For further details, please refer to the
60
30
10

2.13 Setpoint car d ± 10V

The analog inputs of series SK 500E frequenc y in 4 can only process unipolar setpo ints ( 0 … 10 V; 0/4 reference to GROUND.
If a bipolar setpo int (analog difference signal (-
a setpoint conver available from NORD. This module is suitable for snap-on rail
supplementary instructions for the setpoint converter.
Note: Frequency inverters of size S5 and above can process both unipolar and bipolar
setpoints by means of configuration with DIP switches.
Supplier Name Article number
Getriebebau NORD GmbH & Co.KG
Table 27: Setpoint card ± 10V
Pos: 85 /Anleitungen/3. /4. Anzeige und Bedienung [BU 0500 / BU 0200]/SK 5xxE/3. Anzeige und Bedienung @ 0\mod_1327492711496_388.docx @ 6260 @ 1 @ 1
Setpoint converter ±10V 0 … 10V
45
Fig. 8: Dimensions of setpoint card± 10V
278910320
64 BU 0505 GB-1013
3 Displays and control
red / green

3. Displays and control

As delivered, without th e te chnolog y unit, 2 LEDs (gre en/red) ar e vis ible ex ternall y. Thes e indica te the actual device status.
The green LED indic ates that the m ains volta ge is pres ent and operati onal, whil e a flashing cod e that increases in speed shows the degree of overload at the frequency inverter output.
The re d LED signals actual error by flashing with a frequenc y which correspo nds to the number c ode of the fault.
Pos: 86 /Anleitungen/3. /4. Anzeige und Bedienung [BU 0500 / BU 0200]/SK 5xxE/3.1 M odulare Baugruppen [SK 5xxE] @ 0\mod_1327492754652_388.docx @ 6283 @ 2 @ 1

3.1 Modular assemblies SK 5xxE

By the use of various m odules for display, control an d parameterisation, the SK 5x xE can be easily adapted to a wide range of requirements.
Alphanumerical display and operating modules can be used for simple commissioning. For more complex tasks, various connections to a PC or an automation system can be selected.
The Technology Unit (Technology Unit, SK TU1-...) is connected externally to the front of the frequency inverter and is therefore easy to access and replace at any time.
LED
Fig. 9: Modular assemblies SK 5xxE
Pos: 87 /Anleitungen/3. /4. Anzeige und Bedienung [BU 0500 / BU 0200]/SK 5xxE/3.2 Ü bersicht der Technol ogieboxen -1- @ 0\mod_1327492858354_388.docx @ 6306 @ 2555 @ 1
BU 0505 GB-1013 65
SK 54xE – Users Manual for Frequency Inverters
7-segment, 4-digit LED display,
ON, OFF, R/L, 0…100%

3.2 Overview of technology units

Detailed information about the options listed below can be found in the relevant documentation.

Control boxes

Module Name Description Data Part No. Document
SK CSX-0 SimpleBox Commissioning,
parameterisation and control of the frequency inverter
SK TU3-CTR ControlBox As for SK CSX-0
+ saving of the parameters of an
7-segment, 4-digit LED display, single button control
keyboard
275900095 BU 0500
275900090 BU 0040
inverter
SK TU3-PAR ParameterBox As for SK CSX-0
+ saving of parameters from up
4-line LCD display (illuminated), keyboard
275900100 BU 0040
to 5 inverters
SK TU3-POT PotentiometerBox Direct contol of the FI
275900110 BU 0500
Table 28: Overview of Technology Units and Control Boxes

Interfaces

Module Interface Data Part No. Document
Normal field bus protocols
SK TU3-AS-1 AS Interface 4 sensors / 2 actuators
5/8 pin screw terminals
SK TU3-CAO CANopen Baud rate 1 Mbit/s
Connector: Sub-D9
SK TU3-DEV DeviceNet Baud rate: 500 KBit/s
5-pole screw terminal
SK TU3-IBS InterBus Baud rate: 500 kBit/s (2Mbit/s)
Connector: 2 x Sub-D9
SK TU3-PBR Profibus DP Baud rate: 1.5 MBaud
Connector: Sub-D9
SK TU3-PBR­24V
Profibus DP Baud rate: 12 MBaud
Connector: Sub-D9 24V DC connection via terminal
Ethernet-based Bus systems
SK TU3-ECT EtherCAT Baud rate: 100 MBaud
Connector: 2 x RJ45 24V DC connection via terminal
SK TU3-PNT PROFINET IO Baud rate: 100 MBaud
Connector: 2 x RJ45 24V DC connection via terminal
SK TU3-POL POWERLINK Baud rate: 100 MBaud
Connector: 2 x RJ45 24V DC connection via terminal
275900170 BU 0090
275900075 BU 0060
275900085 BU 0080
275900065 BU 0070
275900030 BU 0020
275900160 BU 0020
275900180 BU 0570
275900190 BU 0590
275900140 BU 0580
Table 29: Overview of Technology Units and Bus Systems
66 BU 0505 GB-1013
3 Displays and control
The USS protocol is integrated into all SK 5xxE series devices. An interface is available via terminal X11, or if
Electronic brake
on rail
rminals cover down
with an upward turning movement. If
Note
No optional modules are required for communication via USS or Modbus RTU.
present, also via X7:73/74. Modbus RTU is only available with version SK 54xE or higher. For this, the same interfaces as for USS apply. A detailed description of both of these protocols can be found in Manual BU 0050.
USS Bus modules and Modbus RTU

Other optional modules

Module Interface Data Part No. Document
SK EBGR-1
rectifier
SK EBIOE-2 IO extension Extension with 4 DIN, 2 AIN, 2 DOUT and
Table 30: Overview of technology units, other optional modules
Pos: 88 /Anleitungen/3. /4. Anzeige und Bedienung [BU 0500 / BU 0200]/SK 5xxE/3.2 Ü bersicht der Technol ogieboxen -2- Montage @ 1\mod_1340712929975_388 .docx @ 28340 @ 5 @ 1
Extension for direct control of an electro­mechanical brake, IP20, snap­mounting
1 AOUT, IP20, snap-on rail mounting, SK 54xE and higher
19140990 TI 19140990
275900210 TI 275900210

Installing

Note
Modules should not be inserted or removed unless the device is free of voltage. The slots may only be used for the intended modules.
Installation of a technology unit separate from the frequency inverter is not possible. It must be connected directly to the frequency inverter.
Installing the technology unit
The technology units must be installed as follows:
1. Switch off the mains voltage, observe the waiting period.
2. Push the control te slightly or remove.
3. Remove the blank cover, by loosening the release on the lower edge and pulling off
necessary, the attachm ent screw next to the release must be removed.
4. Hook the technology unit onto the upper edge slots and press in lightly until it engages. Ensure full contact with t he connector strip and fasten with the screws if necessary (separat e packet).
5. Close the control terminal cover again.
Pos: 89 /Anl eitungen/ 3. /4. Anzei ge und Be dienung [BU 0500 / BU 0200]/SK 5xxE/3.3 Si mpleBox, SK CSX-0 @ 0\mod_1327493009711_388.docx @ 6329 @ 255555 @ 1
BU 0505 GB-1013 67
SK 54xE – Users Manual for Frequency Inverters
set in parameter P113, or a
If the frequency inverter is enabled, the display changes
lue selected in parameter
>Selection Display value< P001 (factory setting = current
. As all of these elements use the same communication channel, this may cause
edge of the frequency inverter using the RJ12
RJ12
2 x RJ45, not with
SK 500E/505E/510E
X11
X10 X9

3.3 Sim p leBox, SK CSX-0

This option is used as a simple parameterisation, display and control tool for the frequency inverter SK 5xxE. even in active BUS operation, data c an be read out an d parameterisatio n made especially if the frequency inverter slot is occupied with a BUS unit.

Features

• 4-digit, 7-segment LED display
• Single button operation of the frequency inverter
• Display of the active parameter set and operating value After the SimpleBox has been attached, the cable connectors
plugged in and the m ains has been s witched on, horizontal l ines appear in the 4-di git 7-segment display. This disp lay signals the operational readiness of the frequency inverter.
If a jog frequency value is pre­minimum frequency is pre-set in P104, the display flashes with this value.
automatically to the operating va
frequency). The actual parameter set is shown by the 2 LEDs next to the
Fig. 10 SimpleBox SK CSX-0
display on the left in binary code.
NOTICE
The SimpleBox SK CSX 0 must not be used in co mbinat ion with t he SK TU3-POT, SK TU3-CTR, SK TU3-PAR, the handheld control units SK …- 3H or their built-in versions S K …-3E or the Remote control window of the NORD CON software
communication errors.
Parallel operation of control elements

Assembly

The SimpleBox can be a ttached to any tech nology unit (SK TU3-…) or to the blind c over. To remove it, simply pull it of f after the RJ12 connectio n has been detached (pres s in the latching lever on the RJ12 connector).

Connection

The SimpleBox is connec ted to the socket at the upp er
connector/cable. The Bus termination resistor for the RS485 interface
must be set with DIP switch 1 (left).
68 BU 0505 GB-1013
Fig. 11 Top side of FI with RJ12 /
RJ45 connection
3 Displays and control
1
2
The LEDs indicate the actual operating parameter set in the operating display (P000) and
1
2
2
1
1
2
2
1
Briefly pressing the knob = “ENTER” function in order to store a changed parameter or to
If the knob is pressed for a longer period, the display changes to the next higher level, if
Note
In this operating mode, the drive can only be stopped with the button in the operating value display (short press)
Functions of the SimpleBox
When the frequency inverter is ready for operation any initial value (P104/P113 for keyboard operation) is indicated by a flashing display. This frequency is immediately used on being
7-segment LED
display
enabled. During operation, the currently set operating value (selection in P001) or an error code (Section 6)
is displayed. During parameterisation, the parameter numbers or the parameter values are shown.
LEDs
Turn the knob to
the right
Turn the knob to
the left
the current parameter set being parameterised. The display is in binary code.
= P1
= P2
= P3
= P4
Turn the knob to the right in order to increase the parameter number or the parameter value.
Turn the knob to the left in order to reduce the parameter number or the parameter value.
Briefly press the
knob
change from parameter number to parameter value.
Press the knob
for longer
necessary without storing a parameter change.
Table 31: SimpleBox SK CSX-0, functions

Control with the SimpleBox

If P549=1 is set an d the op erating va lue displa y P000 is selected, the dri ve can b e contro lled with th e SimpleBox on the FI.
Depressing the button f or a long time starts the drive, pressing briefly stops it. The speed of rotation can be controlled in the positive and negative range by means of the rotating knob.
or by switching off the mains voltage.
Stopping the drive
BU 0505 GB-1013 69
SK 54xE – Users Manual for Frequency Inverters
P0--
_ _ _ _
P1--
P2--
P4--
P5--
P6--
P7--
P001
P002
P10 0
P10 1
P114
P200
P201
P220
P400
P401
P483
Operating value display
(or operational)
following mains ON
P3--
P300
P301
P327
P003
P 01
P502
P 02
OFF
OFF
Setting: Master function value 1
Setting: Master function value 2
ENTER
ENTER
ENTER
VALUE

Menu structure with the SimpleBox

Fig. 12: SimpleBox, SK CSX-0 menu structure
NOTE: Some parameters, e.g. P 465, P475, P480…P483, P502, P510, P53 4, P701…P706,
P707, P718, P740/741 and P748 have additional levels (arrays), in which further adjustments can be made, e.g.:
Pos: 90 /Anleitungen/4. Inbetriebnahme [BU 0500]/4. Inbetriebnahme @ 0\mod_1327569589301_388.docx @ 7173 @ 1 @ 1
70 BU 0505 GB-1013
4 Commissioning
DANGER
The frequency inverter is not equipped with a line main switch and is therefore always live when connected to the
3~ Mot
IEC 56
IM B3
cos 0.74
cosj 0.74
IP55
Rot. KL 16
Th.Cl.F
EN60034
60 Hz
460 V Y
5.2 A
2.5 kW
1765 /min
1440 /min
P206
P201
P204
P203
P202
P200
9.0 / 5.2 A
50 Hz
2.2 kW
P207
P200 Motor list:
0 = no change 8 = 0.37kW 400V
1 = no motor 9 = 0.50PS 460V 2 = 0.25kW 230V 10 = 0.55kW 230V 3 = 0.33PS 230V 11 = 0.75PS 230V 4 = 0.25kW 400V 12 = 0.55kW 400V 5 = 0.33PS 460V
13 =
0.75PS 460V 6 = 0.37kW 230V 14 = 0.75kW 230V
7 = 0.50PS 230V ....
230 / 400 V D/Y

4. Commissioning

Once the power su pply has been connected to the frequency inverter, it wil l be operational within a few moments. In this state, the fr equency inverter can be set to the requirements of the application, i.e. it can be configured. A c ompletely comprehensive description of all th e parameters is set out in Section 5.
The connected motor m ay only be started after the parameters specific to the application i n question have been set by qualified personnel.
Danger to life!
power supply. Live voltages may therefore be connected to a connected motor at standstill.
Pos: 91 /Anleit u ng e n/4. Inbetri e b na hme [BU 0500] / 4. 1 Werkseinst ellungen @ 0\ mod_1327569750609_388.docx @ 7196 @ 2 @ 1

4.1 Factory settings

All frequency inverter s supplied by Getriebebau NORD ar e pre-programmed with the defau lt setting for standard applicatio ns with 4 pole IE1 three-ph ase motors (s ame voltage and power). For use with motors with other powers or number of poles, the data from the rating plate of the m otor m ust be input into the parameters P201...P207 under the menu item >Motor data<.
NOTE: All data for IE1 motors can be pre-set with parameter P200. After use of this
function has been succes sful, th is param eter is reset to 0 = no ch ang e! The data is loaded automaticall y into parameters P201...P209 – and can b e compared again with the data on the motor rating plate.
Fig. 13 Motor type plate
BU 0505 GB-1013 71
SK 54xE – Users Manual for Frequency Inverters
R = 10k
AIN 1
GND/0V
VO 10V
DIN 1
VO 15V
11 12 14 16 17
21 22 23 24
25 42 40 41
RECOMMENDATION: For the correct operation of the drive unit, it is necessary to input the
motor data (rating plate) as precisely as possible. In particular, an automatic stator resistance measurement using parameter P220 is recommended.
In order to aut omatically determine the stator res istance, set P220 = 1
and then confirm by pressing "ENTER". The value calculated for the
Pos: 92 /Anl eitungen/ 4. Inbetrie bnahme [BU 0500]/4. 2 Minimal konfigurati on der Steu eranschlüs se @ 0\mod_1327569977746_388.docx @ 7219 @ 255 @ 1
line resistance (dependent upon P207) will be saved in P208.

4.2 Minima l configuration of control connections

If the frequency in verter is to be contr olled via the digital and analog inputs, this c an be implemented immediately in the condition as delivered. Settings are not necessary for the moment.

Minimum connections

Potentiometer, 10kOhm
(Function P400 = 1)
(min./max. range = P104/105)
Switch, ON/OFF
(Function P420 = 1)
*Devices SK5x5E: Terminal designation 44 instead of 42: Size 1 - 4: 18V … 30V (accordi ng to input voltage VI)
Size 5 - 7: VO = 24V ± 25%

Basic parameters

If the current setting of the frequency inverter is not known, loading the default setting is recommended à P523 = 1. The inverter is pre-programmed for standard applications in this configuration. If necess ary, the following param eters can be adjusted with the optional Sim pleBox SK CSX-0 or ControlBox TU3-CTR.
72 BU 0505 GB-1013
4 Commissioning
P0--
Display
parameters
_ _ _ _
P1--
Basic parameter
P2--
Motor data
P4--
Control terminals
P5--
Additional
parameter
P7--
Information
As standard, the actual
output frequency is displayed
P102
Acceleration time
0 ... 320s
Motor data
See 4.1 Default Settings
P400
Analog input function
0...10V frequency
Operating value display
(or operational)
following mains ON
P103
Deceleration time
0 ... 320s
P104
Min. frequency
0 ... 400Hz
P105
Max. frequency
0.1 ... 400Hz
P420
Digital input function 1
- ON right -
P523
=1
Load factory data
RV = 2,7 kOhm
AIN 2
GND/0V
VO 10V
11 12 14 16 17
KTY84-130
-1R2
+1R1
X4
Pos: 93 /Anleit u ng e n/4. Inbetri e b na hme [BU 0500] / 4. 3 KTY84-130 A nsc hluss (ab Sof t w ar e V ersion 1.7) @ 0\ mod_1327570228346_388.docx @ 7242 @ 255 @ 1

4.3 KTY84-130 connection (above software version 1.7)

The current vector contro l of the SK 500E s eries can be f urther optim ised by the use of a KTY84-130 temperature sensor (R
th(0°C)
=500, R intermediate mains s witch-off during operation the temperature of the motor is measured directl y and therefore the actual value is always available to the f requency inverter. With this, the regu lator can always achieve optimum speed precision.

Connections (Example SK 500E, analog input 2)

Parameter settings (ExampleSK 500E, analog input 2)

The following parameters must be set for the function of the KTY84-130.
=1000). In particular there is the advan tage that after an
th(100°C)
BU 0505 GB-1013 73
SK 54xE – Users Manual for Frequency Inverters
P0--
Display parameters
to
_ _ _ _
P1--
Basic parameter
P2--
Motor data
P4--
Control terminals
P5--
Additional parameter
P7--
Information
P201
Nominal motor frequency
10 … 400Hz
P406
Mode analog input 2
P406 = 1 (0...10V)
P207
Motor switching
Star/delta
P208
Stator resistance
0 … 300
P220
Parameter identification
P220 1 / 2
P407
Adjustment of analog input 2
P407=1.54V
P405
Analog input function 2
P405=48 (Motor temperature)
P408
Adjustment of analog input 2
P408=2.64V
P001
Motor temperature
-50 ... 150°C
P409
Analog input filter 2
P409=400ms
Note
Excess temperature of the motor is also monitored and at 155°C (switching threshold for the thermistor) causes
1. Set the motor data P201-
P207 according to the type plate
2. Determine the motor stator
resistance P208 at 20°C with P220=1.
3. Analog input 2 function,
P405=48 (Motor temperature)
4. Analog input 2 mode 2,
P406=1 (taking negative temperatures into account)
5. Matc hi ng of analog input 2:
P407= 1.54 V and P408= 2.64 V (with R
=
V
2.7 kΩ)
6. Adjust time constants:
P409=400ms (Maximum value of filter time constant)
7. Motor temperature control:
P001=23 (Temperature display, operation displa y SK TU3-CTR / SK CSX-0)
Temperature ranges
the drive unit to shut down with error message E002. To determine the stator resistance of the motor, the temperature range 15 … 25°C should not be exceeded.
Pos: 94 /Anl eitungen/ 4. Inbetrie bnahme [BU 0500]/4. 4 Frequenz- Addition und Subtraktion über Bedienboxen. @ 0\mod_1327571806191_388.docx @ 7290 @ 2 @ 1

4.4 Freque ncy addition and subtraction via operating boxes

(software version 1.7 and above)
If the parameter P549 (P otentiometerBox Function) is set to 4 “Frequency additi on” or 5 “Frequency subtraction”, a value can be adde d or s ubtrac ted via t he v alue keys
the ParameterBox. If the ENTER key
is confirmed, the v al ue is sav ed in P11 3. The next time the de vice is s tarte d, t he
value will be added or subtracted immediately. As soon as the inverter is enabled, the ControlBox switches to the operating display. With the
ParameterBox, a change of value can only be made in the operating display. If the ControlBox is enabled, parameterisati on is no longer poss ible. Enabling via t he ControlBox or P arameterBox is also no longer possible in this mode, even if P509 = 0 and P510 = 0.
Note: In order to safely activate the ParameterBox in this mode, the STOP key
pressed once.
Pos: 95 /Anleit u ng e n/5. /6. Para me t r i er u ng [B U 05 00 / BU 0200] /5. Paramet er -1- @ 0\mod_1327572853172_388.docx @ 7316 @ 1 @ 1
or with the ControlBox or
m ust be
74 BU 0505 GB-1013
5 Parameters
Operating displays
(P0--)
For the selection of the physical units of the display value.
Basic parameters
(P1--)
Contain the basic inverter settings, e.g. switch on and switch off behaviour and, along with the motor data, and are sufficient for standard applications.
Motor data
specific data, important for ISD current control, and selection of characteristic curve during the setting of dynamic and static boost.
Speed control
(SK 520E or higher)
(P3--)
Settings for the control parameters (current controller, speed controller, etc.) with speed feedback.
Control terminals
(P4--)
Analog input and output scaling, specification of digital input and relay output functions, as well as PID controller
Additional parameters
Functions dealing with e.g. the interface, pulse frequency or error acknowledgement.
Positioning (SK 52xE and higher)
Information
(P7--)
Display of e.g. actual operating values, old error messages, equipment status reports or software version.
Array parameters
-01
-xx
Some parameters in these groups can be programmed and read in several
meter is selected, the array level must also be
selected.
Parameter P523 can be used to load the factory settings for all parameters at any time. This can be helpful, e.g.
meters no longer correspond with the factory
To safeguard the actual parameter settings, these can be transferred to the ControlBox (P550=1) or

5. Parameters

Every frequency inv erter is factor y-set for a m otor of the same po wer. All parameter s can be a djusted "online". There are four switchable parameter sets available during operation. As delivered, all parameters are visible; however, some can be hidden with parameter P003.
NOTICE
As there are dependencies between parameters, it is possible for invalid internal data and operating faults to be generated briefly. Only the inactive or non-critical parameter sets should be adjusted during operation.
Operating faults
The individual param eters are combined in to various groups. The f irst digit of the par ameter number indicates the assignment to a menu group:
Menu group No. Master function
(P2--) Settings for the motor-
param eters.
(P5--)
(P6--)
Setting of the positioning function. Details: please refer to BU 0510.
levels (arrays). After the para
Note
during the commissioning of a frequency inverter whose para settings.
All actual parameter settings will be overwritten, if P523= 1 is set and confirmed with "ENTER".
ParameterBox memories
Parameter P523
Pos: 96 /Anleit u ng e n/5. /6. Para me t r i er u ng [B U 05 00 / BU 0200]/5 . P arameter -2- V erfügbark eit der Para meter @ 1\ mod_1340700117242_388.docx @ 28316 @ 55 @ 1
BU 0505 GB-1013 75
SK 54xE – Users Manual for Frequency Inverters
1
Parameter number
2
Array values
3
Parameter text; Top: P-Box display, bottom: Meaning
4
Special features (e.g.: only available for SK 520E and above)
5
Supervisor parameters (S) are dependent on the settings in P003
6
Parameter set dependent (P) parameter selections in P100
7
Parameter value range
8
Description of the parameter
9
Default values (factory settings) of the parameter
P 01
P502
P 02
OFF
OFF
Setting: Master function value 1
Setting: Master function value 2
ENTER
ENTER
ENTER
VALUE

Availability of parameters

Due to certain configurati on s , the par ameters are subject to c ertain c on dit ions. The following tables list all parameters together with the particular information.

Array parameter display

Some parameters have the option of displaying settings and views in several levels (arra ys). After the parameter is selected, the array le vel is displayed and must then also be selected.
If the ControlBox is used, the ar ray level is shown by _ - 0 1 . W ith the ParameterBox (picture on right) the selection options for the array level
appear at the top left of the display.
For parameterisation with ControlBox SK TU3-CTR:
Pos: 97 /Anleit u ng e n/5. /6. Para me t r i er u ng [B U 05 00 / BU 0200]/P 0 xx Betriebs anz eige @ 0\mod_1327573414463_388.docx @ 7339 @ 5 @ 1

Operating displays

Abbreviations used:
FI = Frequency inverter
SW = Software version, stored in P707.
S = Supervisor parameters are visible or hidden depending on P003.
76 BU 0505 GB-1013
5 Parameters
which is selected
0 =
Actual frequency [Hz]:
Actually supplied output frequency
1 =
Speed [rpm]
Calculated actual speed
Setpoint frequency [Hz]:
3 =
Current [A]
Actual, measured output current
4 =
Torque current [A]:
Output current which causes torque
5 =
Voltage [V AC]:
The Actual AC voltage delivered to the output of the FI
DC link voltage [V DC]
7 =
cos phi
Actual calculated value of the power factor
8 =
Apparent power [kVA]
Actual calculated apparent power
9 =
Effective power [kW]
Actual calculated effective power
10 =
Torque [%]
Actual calculated torque
11 =
Field [%]
Actual calculated field in the motor
12 =
Hours of operation [h]:
Time for which the FI has been connected to mains voltage
13 =
Operating time enable [h]
"Operating time enable" is the time for which the FI was enabled.
14 =
Analog input 1 [%]:
actual value present at analog input 1 of the FI.
Analog input 2 [%]:
16 =
… 18
reserved for Posicon
19 =
Heat sink temperature [°C]:
actual temperature of the FI heat sink.
20 =
Actual utilisation of motor [%]
average motor load, based on the known motor data (P201...P209).
21 =
Actual utilisation of brake resistor [%]
"Utilisation of brake resistor" is the average braking resistor load, based on the known resist ance data (P556...P 557).
22 =
Internal temperature [°C]
Actual internal temperature of the FI (SK 54xE / SK 2xxE)
23 =
Motor temperature
Measured via KTY-84
24 =
… 29
reserved for Posicon
30 =
Actual Setpoint MP-S [Hz]
"Actual setpoint of motor parameter function with saving": function or pre-set (without the drive running).
31 =
… 59
reserved for POSICON or PLC
60 =
R stator ident:
the stator resistance determined by measurement (P220)
R rotor ident:
62 =
L stray stator ident:
the stray inductance determined by meas urement ((P220) Function
2)
63 =
L stator ident:
the inductance determined by measurement ((P220) Function 2)
65 = Reserved
Parameter
{factory setting}
Pos: 98 /Anleit u ng e n/5. /6. Para me t r i er u ng [B U 05 00 / BU 0200]/P ar a meter/P0 00- P099/Parameter P000 – Betriebsa nzeige @ 0 \mod_1327573548773_388.docx @ 7362 @ @ 1
P000
Setting value / Description / Note Supervisor
Operating display
(Operating parameter display)
0.01 ... 9999 In ParameterBoxes with 7-segment displays (e.g. SimpleBox) the operating value in P001 is displayed online.
Important information about the operating status of the drive can be read out as required.
Pos: 99 /Anleit u ng e n/5. /6. Para me t r i er u ng [B U 05 00 / BU 0200]/P ar a meter/P0 00- P099/Para m et er P0 01 – Auswahl Anzeige @ 0\mod_1327573728068_388.docx @ 7386 @ @ 1
P001
0 ... 65 { 0 }
Selection of disp.value
(Selection of display value)
Selection of the operating display of a ParameterBox with 7-segment display (e.g.: SimpleBox)
2 =
6 =
Output frequency equivalent to the actual setpoint. This need not match the actual output frequency.
The "Link voltage" is the internal DC voltage of the FI. Amongst other things, this depends on the level of the mains voltage.
Parameter set
15 =
61 =
actual value present at analog input 2 of the FI.
(P420…=71/72). The nominal value can be read out with this
the rotor resistance determined by measurement ((P220) Function 2)
BU 0505 GB-1013 77
SK 54xE – Users Manual for Frequency Inverters
The selected operating value in parameter P001 >Select of display< is multiplied with the scaling
o be parameterised. 4 parameter sets are available. All
The selection of the operating parameter set is performed via a digital input or the Bus control.
1
2
2
1
1
2
2
1
If enabled via the keyboard (SimpleBox, ControlBox, PotentiometerBox or ParameterBox), the
P002
Display factor
(Display factor)
0.01 ... 999.99
{ 1.00 }
factor in P000 and displayed in >Operating parameter display<. It is therefore possible to display system-spe cif ic oper at ing such as e.g. the throughput quantity
Pos: 101 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P000-P099/ Paramet er P003 – Sup ervisor-Cod e @ 0\mod_1327573882472_ 388.docx @ 7432 @ @ 1
P003 Supervisor-Code
(Supervisor code)
0 ... 9999 { 1 }
Pos: 102 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ P1xx Basis parameter @ 0\mod_1327574618174_388.docx @ 7458 @ 5 @ 1

Basic parameters

Parameter
{factory setting}
Pos: 103 /Anleit ungen/5. / 6. Paramet rierung [BU 0500 / BU 0200]/Par ameter/P 100-P199Par a meter P100 – Par ametersatz @ 0\mod_1327574757831_388.docx @ 7481 @ @ 1
P100
0 ... 3 { 0 }
0 = The Supervisor paramete rs are not visible. 1 = All parameters are visible. 2 = Only the menu group 0 > Operating display< (P001 and P003) is visible.
3 = ... ... 9999, as for setting value 2.
Setting value / Description / Note Supervisor
Parameter set
(Parameter set)
Selection of the parameters sets t parameter set-dependent parameters are identified by P.
Switching can take place during operation (online).
Setting
Digital
inputfunction [8]
S
S
Digital
inputfunction [17]
Parameter set
LEDs
olBox
0 =
Parameter set 1 LOW LOW
1 =
Parameter set 2 HIGH LOW
2 =
Parameter set 3 LOW HIGH
3 =
Parameter set 4 HIGH HIGH
operating parameter set will match the settings in P100.
Pos: 104 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P100-P199 Parameter P 10 1 – Param.-S atz kopier en @ 0\mod_1327574829893_388.docx @ 7504 @ @ 1
78 BU 0505 GB-1013
5 Parameters
After confirmation with the OK / ENTER key, a copy of the parameter set selected in P100
The acceleration time is the time corresponding to the linear frequency rise from 0Hz to the set
imum frequency (P105). If an actual setpoint of <100% is being used, the acceleration time is
The acceleration time can be extended by certain circumstances, e.g. FI overload, setpoint lag,
Care must be taken that the parameter values are realistic. A setting of P102 = 0 is not
50Hz in < 0.1 s) should generally be avoided, as these may
corresponding to the linear frequency reduction from the set
maximum frequency (P105) to 0Hz (P105). If an actual setpoint <100% is being used, the
Care must be taken that the parameter values are realistic. A setting of P103 = 0 is not
P101
0 ... 4 { 0 }
Pos: 105 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P100-P199 Parameter P 10 2 – Hochlaufz eit @ 0\mod_1327574880847_388 .docx @ 7527 @ @ 1
P102
0 ... 320.00 sec { 2.00 } { 5.00 } above size 8
Pos: 106 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/P ar ameter/P 10 0- P199Para me ter P 103 – Bremsz eit @ 0\mod_1327574939362_388.docx @ 7550 @ @ 1
P103
Copy parameter set
(Copy parameter set)
S
>Parameter set< is written to the parameter set dependent on the value selected here
0 = Do not copy 1 = Copy actual to P1: Copies the active parameter set to parameter set 1 2 = Copy actual to P2: Copies the active parameter set to parameter set 2 3 = Copy actual to P3: Copies the active parameter set to parameter set 3 4 = Copy actual to P4: Copies the active parameter set to parameter set 4
Acceleration time
(Acceleration time)
P
max reduced linearly according to the setpoint set.
smoothing, or if the current limit is reached.
NOTE:
permissible for drive units!
Information on ramp gradient:
Ultimately, the moment of inertia of the rotor determines the possible ramp gradient. If the ramp is too steep, the motor may "break down".
Extremely steep ramps (e.g.: 0 ­cause damage to the frequency inverter.
Braking time
(Deceleration time)
P
0 ... 320.00 sec { 2.00 } { 5.00 } above size 8
The braking time is the time deceleration time reduces accordingly.
The braking time can be extended by certain circumstances, e.g. by the selected >Switch-off mode< (P108) or >Ramp smoothing< (P106).
NOTE:
permissible for drive units!
For information about ramp gradients: please refer to parameter (P102)
Pos: 107 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P100-P199 Parameter P 10 4 – Minimale Freq uenz @ 0\mod_1327575009471_388.docx @ 7573 @ @ 1
BU 0505 GB-1013 79
SK 54xE – Users Manual for Frequency Inverters
The minimum frequency is the frequency supplied by the FI as soon as it is enabled and no
In combination with other setpoints (e.g. analog setpoint of fixed frequencies) these are added to
This frequency can be continuously undershot if, during acceleration or braking, the function
abled and once the maximum setpoint is present,
e.g. analog setpoint as per P403, a correspondingly fixed frequency or maximum via the
This frequency can only be overshot by the slip compensation (P212), the function "Maintain
ion digital input = 9) or a change to another parameter set with lower maximum
This parameter enables a smoothing of the acceleration and deceleration ramps. This is
The value to be set is based on the set acceleration and deceleration time, however values <10%
[ ]
100%
% P106
ttt
P102P102TIME ONACCELERATI tot
+=
[ ]
100%
% P106
ttt
P103P103TIME ONDECELERATI tot
+=
P102
P103
Output
frequency
Setpoint
frequency
Time
Currently 10 – 100% from P102
Currently 10 – 100% from P103
P104
0.0 ... 400.0 Hz
{ 0.0 }
Pos: 108 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P100-P199 Parameter P 10 5 – Maximale F requenz @ 0\mod_1327575060751_3 88.docx @ 7596 @ @ 1
P105
0.1 ... 400.0 Hz
{ 50.0 }
Pos: 109 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P100-P199 Parameter P 10 6 – Rampenverrundungen @ 0\mod_1327575116954_388.docx @ 7619 @ @ 1
P106
0 ... 100 % { 0 }
Minimum frequency
(Minimum frequency)
additional setpoint is set.
the set minimum frequency. This frequency is undershot when
a. the drive is accelerated from standstill. b. The FI is blocked. The frequency then reduces to the absolute minimum (P505) before
it is blocked.
c. The FI reverses. The reverse in the rotation field takes place at the absolute minimum
frequency (P505).
"Maintain frequency" (Function Digital input = 9) is executed.
Maximum frequency
( Maximum frequency)
The frequency supplied by the FI after being en ControlBox.
frequency" (funct frequency.
Ramp smoothing
(Ramp smoothing)
necessary for applications where gentle, but dynamic speed change is important. Ramp smoothing is carried out for every setpoint change.
P
P
P
have no effect. The following then applies for the entire acceleration or deceleration time, including rounding:
Pos: 110 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P100-P199 Parameter P 10 7 – Einfallz ei t Br e ms e @ 0\mod_1327575190328_388.docx @ 7642 @ @ 1
80 BU 0505 GB-1013
5 Parameters
dependent delayed reaction time when actuated. This
ns, as the brake only takes over the load after
requency (P505)
For the control of electromagnetic braking (especially for lifting operations) an
nction 1, external brake (P434/441). The
If a time > 0 is set in P107 or P114, at the moment the FI is switched on, the level of
no magnetising current is present,
down and an error message (E016) in this case, P539
motor. For lower powers (< 1.5 kW) the
Output frequency
P107
Brake released
P114 or P107, if P114 = 0
ON signal
P505
OFF signal
Time
P107
0 ... 2.50 s { 0.00 }
Brake reaction time
(Brake reaction time)
Electromagnetic brakes have a physically­can cause a dropping of the load for lifting applicatio a delay.
This reaction time can be taken into account with parameter P107 (Brake control). Within the adjustable reaction time, the FI supplies the set absolute minimum f
and so prevents movement against the brake and load drop when stopping. See also the parameter >Release time< P114 NOTE:
internal relay should be used, see Fu minimum absolute frequency (P505) should never be less than 2.0Hz.
NOTE:
the excitation current (field current) is checked. If the FI remains in magnetising mode and the motor brake is not released.
In order to achieve a shut­must be set to 2 or 3.
Recommendation for applications: Lifting equipment with brake, without speed feedback
P114 = 0.2...0.3sec. * P107 = 0.2...0.3sec. * P201…P208 = Motor data P434 = 1 (ext. brake) P505 = 2...4Hz
for safe start-up P112 = 401 (off) P536 = 2.1 (off) P537 = 150% P539 = 2/3 (I
monitoring)
SD
to prevent load drops P214 = 50...100% (precontrol)
* Setting values (P107/114) depending on the brake type and the size of the
values also tend to be lower. For larger powers (>4.0 kW ) the values tend to be larger than those stated.
Pos: 111 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P100-P199 Parameter P 10 8 – Ausschalt modus @ 0\ mod_1327575421965_388.docx @ 7665 @ @ 1
P
BU 0505 GB-1013 81
SK 54xE – Users Manual for Frequency Inverters
This parameter determines the manner in which the output frequency is reduced after "Blocking" (controller enable à Low).
This function must not be programmed if defined deceleration is required,
This function cannot be used as a positioning function. This function should
P108
Disconnection mode
(Disconnection mode)
0 ... 13 { 1 }
0 = Voltage disable: The output signal is switched off immediately. The FI no longer
supplies an output frequency. The motor is only braked by mechanical friction. Immediately switching the FI on again can lead to an error message.
1 = Ramp down: The current output frequency is reduced in proportion to the remaining
deceleration time, from P103/P105. The DC run-on follows the end of the ramp (if programmed in P559).
2 = Delayed ramping: as for 1 "Ramp", however for generational operation the brake ramp
is extended, or for static operation the output frequency is increased. Under certain conditions, this function can prevent overload switch off or reduce brake resistance power dissipation.
NOTE:
e.g. with lifting mechanisms.
3 = Instant DC braking: The FI switches immediately to the preselected DC current (P109).
This DC current is supplied for the remaining proportion of the >DC brake time< (P110). Depending on the relationship, actual output frequency to max. frequency (P105), the >Time DC brake on< is shortened. The time taken for the motor to stop depends on the application. The time taken to stop depends on the mass inertia of the load and the DC current set (P109). With this type of braking, no energy is returned to the FI; heat loss occurs mainly in the motor rotor.
4 = Const. brake distance, "Constant brake distance": The brake ramp is delayed in starting
if the equipment is not being driven at the maximum output frequency (P105). This results in an approximately similar braking distance for different frequencies.
NOTE:
not be combined with ramp smoothing (P106).
5 = Combi. braking, "Combined braking": Dependent on the actual link voltage (UZW), a
high frequency voltage is switched to the basic frequency (only for linear characteristic curves, P211 = 0 and P212 = 0). The deceleration time is retained where possible (P103). à additional motor warming!
6 = Quadratic ramp: The brake ramp does not follow a linear path, but rather a decreasing
quadratic one.
7 = Quad. ramp with delay, "Quadratic ramp with delay": Combination of functions 2 and 6. 8 = Quad. ramp w. braking, "Quadr atic com bined brak ing": Combination of functions 5 and 6. 9 = Constant accn., "Constant acceleration power": Only applies in field weakening range!
The drive is accelerated or braked using constant electrical power. The course of the ramps depends on the load.
10 = Distance calculator: Constant distance between actual frequency / speed and the set
minimum output frequency (P104).
11 = Const. accn. delay, "Constant acceleration power with delay": Combination of functions
2 and 9.
12 = Const. accn. mode 3, "Constant acceleration power mode 3": as for 11, however with
additional chopper relief.
13 = Switch off delay, "Ramp with switch-off delay":As for 1 "Ramp", however, before the
brake is applied, the drive unit remains at the absolute minimum frequency set in parameter (P505) for the time specified in parameter (P110). Application example: Re-positioning for crane control.
Pos: 112 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P100-P199 Parameter P 10 9 – Strom DC-Bremse @ 0\mod_1327585946142_388.docx @ 7700 @ @ 1
S P
82 BU 0505 GB-1013
5 Parameters
Current setting for the functions of DC current braking (P108 = 3) and combined braking
leration time. A
In the basic setting this limiting
P108 "DC brake current"
Depending on the ratio of the actual output frequency to the max. frequency (P105), the >Time
Directly affects the behaviour of the drive at torque limit. The basic setting of 100% is sufficient for
generating current can be set. This can prevent
It cannot provide any protection against mechanical
The torque current limit can also be set over an infinite range of settings using an analog input.
imum setpoint (compare adjustment 100%, P403/P408) then corresponds to the value
The limit value 20% of current torque cannot be undershot by a smaller analog setpoint
P109
0 ... 250 % { 100 }
Pos: 113 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P100-P199Parameter P110 – Zeit DC-Bremse an @ 0\mod_1327587720502_388.docx @ 7723 @ @ 1
P110
0.00 ... 60.00 sec
{ 2.00 }
Pos: 114 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P100-P199 Parameter P 11 1 – P-Faktor M omentengr . @ 0\mod_1327587790393_388.docx @ 7746 @ @ 1
P111
25 ... 400 % { 100 }
Pos: 115 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P100-P199 Parameter P 11 2 – Momentstromgrenze @ 0\mod_1327587840768_388.docx @ 7769 @ @ 1
P112
DC brake current
(DC brake current)
S P
(P108 = 5). The correct setting value depends on the mechanical load and the required dece
higher setting brings large loads to a standstill more quickly. The 100% setting relates to a current value as stored in the >Nominal current< parameter P203. NOTE: The amount of DC current (0Hz) which the FI can supply is limited. For this value,
plese refer to the table in Section 0
, column: 0Hz.
value is about 110%.
DC braking time on
(DC braking time on)
S P
The time during which the motor has the current selected in parameter applied to it during the DC braking functions (P108 = 3).
DC brake on< is shortened. The time starts running with the removal of the enable and can be interrupted by fresh enablin g.
P factor torque limit
(P factor torque limit)
S P
most drive tasks. If values are too high the drive tends to vibrate as it reaches the torque limit.
If values are too low, the programmed torque limit can be exceeded.
Torque current limit
(Torque current limit)
S P
25 ... 400 % / 401 { 401 }
With this parameter, a limit value for the torque­mechanical overloading of the drive. blockages (movement to stops). A slipping clutch which acts as a safety device must be provided.
The max set in P112.
(P400/405 = 2). However, in servo mode with P300 = 1:
• up to SW version 1.9: not less than 10%
• SW version 2.0 and above: no restriction (motor torques from 0% are possible)!
401 = OFF means the switch-off of the torque current limit! This is also the basic setting for the FI. NOTE: For lifting gear applications, a torque limit must not be used!
Pos: 116 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P100-P199 Parameter P 11 3 – Tippfrequenz @ 0\mod_1327587895377_388.docx @ 7792 @ @ 1
BU 0505 GB-1013 83
SK 54xE – Users Manual for Frequency Inverters
Change of function as of software
to control the FI, the jog frequency is the initial
ls, the jog frequency can be activated via one
The setting of the jog frequency can be done directly via this parameter or, if the FI is enabled via
s set in
The activation of the jog frequency via one of the digital inputs causes the remote
ion, any setpoint
Exception: analog setpoint values which are processed via the functions Frequency
rminals, e.g. jog frequency, fixed frequencies or analog setpoints, are generally added with the correct sign. The set maximum frequency (P105) cannot be exceeded and the minimum frequency (P104) cannot
e a delayed reaction time during ventilation, which depends on
physical factors. This can lead to the motor running while the brake is still applied, which will
During the adjustable ventilation time, the FI supplies the set absolute minimum frequency (P505)
Monitoring of communication at system bus level (in case of error: error message 10.9)
tion is interrupted. If a
module which was previously present is not found after switching on the mains, this does
the FI starts monitoring
If the module is
on" for 5
Note: If error messages which are detected by the optional module (e.g. errors at field bus level)
down of the drive electronics, parameter (P513) must also be set to the
value {-0,1}.
P113
-400.0 ... 400.0 Hz { 0.0 }
version 1.7
Pos: 117 /A nleitunge n/5. /6. Par ametrierung [BU 0500 / BU 0200]/Parameter/P100-P199Parameter P 11 4 – Lü ftzeit Brems e @ 0\mod_1327587947470_ 388.docx @ 7815 @ @ 1
P114
Jog frequency
(Jog frequency)
When usi ng the ControlBox or Parame terBox value following successful enabling.
Alternatively, when control is via the control termina of the digital inputs.
the keyboard, by pressing the ENTER key. In this case, the actual output frequency i parameter P113 and is then available for the nex t start.
NOTE: Software version V1.7 R0 and higher:
control to be switched off in case of bus operation. In addit frequencies present are not taken into account.
addition or Frequency subtraction. Up to software version V1.6 R1: Specified setpoints via the control te
be undershot.
Brake delay off
(Brake release time)
S P
S P
0 ... 2.50 s { 0.00 }
Electromagnetic brakes hav cause the inverter to switch off with an overcurrent report.
This release time can be taken into account in parameter P114 (Brake control).
thus preventing movement against the brake. See also the parameter >Brake reaction time< P107 (setting example).
NOTE:
If the brake ventilation time is set to "0", then P107 is the brake ventilation and reaction time.
Pos: 118 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P100-P199 Parameter P 12 0 – Optionsüberwachung [SK 2xxE, SK 54xE] @ 2\mod_1346931600646_388.docx @ 42230 @ @ 1
P120 [-01] ...
0 ... 2 { 1 }
Option monitoring
(Option monitoring)
[-04]
Array levels: [-01] = Extension 1 (BUS TB) [-02] = Extension 2 (second I/O TB)
Setting values 0 = Monitoring OFF 1 =
2 =
are not to result in a shut-
Auto, communication is only monitored if an existing communica not result in an error
Monitoring only becomes active when an extension starts communication with the F I. Monitoring active immediately "Monitoring active immediately" ,
the correspond ing module immedia tely after the m ains are switch ed on.
not detected on switch-on, the FI remains in the status "not ready for switch­seconds and then triggers an error message.
S
[-03] = Extension 3 (first I/O TB) [-04] = Extension 4 (reserved)
84 BU 0505 GB-1013
5 Parameters
The factory settings for the motor data can be edited with this parameter. The factory setting in
ible digits and pressing the ENTER key, all motor parameters
magnetising time, and is therefore not recommended for motor applications. Possible applications are induction furnaces or other applications with coils and transformers. The
=0.90 /
19 = 1.5 Hp 230V
37 = 7.5 PS 230V
55 = 50.0 PS 460V
73 = 340.0 PS 460V
after the input confirmation, the control of the set motor can be implemented
Information
IE2 motors
For the use of IE2 motors, after the selection of an IE1 motor (P200) the motor data in P201 ...
Pos: 119 /Anleitungen/5. /6. Parametrierung [BU 0500 / BU 0200]/P2xx Motordaten / Kennlinienparameter @ 0\mod_1327588046860_388 .docx @ 7838 @ 5 @ 1

Motor data / Characteristic curve parameters

Parameter
{factory setting}
Pos: 120 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P200 – Mot orliste @ 0 \mod_1327588261094_388.docx @ 7861 @ @ 1
P200
0 ... 73 { 0 }
Setting value / Description / Note Supervisor Parameter set
Motor list
(Motor list)
P
parameters P201...P209 is a 4-pole IE-1 DS standard motor with the nominal FI power setting. By selecting one of the poss
(P201…P209) are adjusted to the selected standard power. The basis for the motor data is a 4-pole DS standard motor
0 = No change to data 1 = No motor: In this setting, the FI operates without current control, slip compensation and pre-
following motor data is set here: 50.0Hz / 1500rpm / 15.0A / 400V / 0.00kW / cos ϕ Star / RS 0.01 / I
2 = 0.25kW 230V 3 = 0.33 Hp 230V 4 = 0.25kW 400V 5 = 0.33 Hp 460V 6 = 0.37kW 230V 7 = 0.50 Hp 230V 8 = 0.37kW 400V
9 = 0.50 Hp 460V 10 = 0.55kW 230V 11 = 0.75 Hp 230V 12 = 0.55kW 400V 13 = 0.75 Hp 460V 14 = 0.75 Hp 230V 15 = 1.0 Hp 230V 16 = 0.75 Hp 400V 17 = 1.0 Hp 460V 18 = 1.1 kW 230V
6.5A
LEER
20 = 1.1 k W 400V 21 = 1.5 Hp 460V 22 = 1.5 Hp 230V 23 = 2.0 Hp 230V 24 = 1.5 Hp 400V 25 = 2.0 Hp 460V 26 = 2.2 k W 230V 27 = 3.0 Hp 230V 28 = 2.2 k W 400V 29 = 3.0 Hp 460V 30 = 3.0 Hp 230V 31 = 3.0 Hp 400V 32 = 4.0 k W 230V 33 = 5.0 PS 230V 34 = 4.0 k W 400V 35 = 5.0 PS 460V 36 = 5.5 k W 230V
38 = 5.5 k W 400V 39 = 7.5 PS 460V 40 = 7.5 k W 230V 41 = 10.0 PS 230V 42 = 7.5 k W 400V 43 = 10.0 PS 460V 44 = 11.0 k W 400V 45 = 15.0 PS 460V 46 = 15.0 k W 400V 47 = 20.0 PS 460V 48 = 18.5 k W 400V 49 = 25.0 PS 460V 50 = 22.0 k W 400V 51 = 30.0 PS 460V 52 = 30.0 k W 400V 53 = 40.0 PS 460V 54 = 37.0 k W 400V
56 = 45.0 k W 400V 57 = 60.0 PS 460V 58 = 55.0 k W 400V 59 = 75.0 PS 460V 60 = 75.0 k W 400V 61 = 100.0 PS 460V 62 = 90.0 k W 400V 63 = 120.0 PS 460V 64 = 110.0 k W 400V 65 = 150.0 PS 460V 66 = 132.0 k W 400V 67 = 180.0 PS 460V 68 = 160.0 k W 400V 69 = 220.0 PS 460V 70 = 200.0 k W 400V 71 = 270.0 PS 460V 72 = 250.0 k W 400V
NOTE:
As P200 returns to = 0 via parameter P205.
P209 must be adapted to the data on the motor type plate.
Pos: 121 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P201 – Mot or Nennfr equenz @ 0\mod_1327588385923_388.docx @ 7884 @ @ 1
BU 0505 GB-1013 85
SK 54xE – Users Manual for Frequency Inverters
The motor nominal frequency determines the V/f break point at which the FI supplies the nominal
the correct calculation and control of the motor slip and
voltage to the motor voltage. In combination with the
P201
10.0 ... 399.9 Hz
∗∗∗
}
{
Pos: 122 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/Parameter/P200-P299/Parameter P 202 – Motor N en ndrehzahl @ 0\ mod_1327588441470_388.docx @ 7907 @ @ 1
P202
150 ... 24000 rpm
***
{
}
Pos: 123 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P203 – Mot or N en ns tr om @ 0\mod_1327588500455_388.docx @ 7930 @ @ 1
P203
0.1 ... 1000.0 A
***
{
}
Pos: 124 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P204 – Mot or Nennspa nnung @ 0\ mod_1327588687111_388.docx @ 7953 @ @ 1
P204
100 ... 800 V
***
{
}
Pos: 125 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P205 – Mot or Nennleis tung @ 0\ mod_1327588736705_388.docx @ 7976 @ @ 1
Nominal motor frequency
(Nominal motor frequency)
S P
voltage (P204) at the output.
Nominal speed
(Nominal motor speed)
S P
The nominal motor speed is important for the speed display (P001 = 1).
Nominal current
(Nominal motor current)
S P
The nominal motor current is a decisive parameter for the current vector control.
Nominal voltage
(Nominal motor voltage)
S P
The >Nominal voltage< matches the mains nominal frequency, the voltage/frequency characteristic curve is produced.
*** These settings are dependent on the nominal power of the FI or the selection in parameter P200.
86 BU 0505 GB-1013
5 Parameters
The motor circuit is decisive for stator resistance measurement (P220) and therefore for current
Has a direct influence on the current control of the FI. Too high a value will lead to a possible
For optimum functioning of the current vector control, the stator resistance must be automatically
y from the motor data if there is a change in the
If the value is to be entered directly, then it must be set as the last motor data. This is
The static boost affects the current that generates the magnetic field. This is equivalent to the no
. The no load current is
P205
0.00 ... 250.00 kW
∗∗∗
}
{
Pos: 126 /A nleitunge n/5. /6. Par ametrierung [BU 0500 / BU 0200]/Paramete r /P200-P299/Param eter P206 – M otor cos p hi @ 0\mod_1327588784877_388.do cx @ 7999 @ @ 1
P206
0.50 ... 0.90
***
{
}
Pos: 127 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P207 – Mot orschaltu ng @ 0\mod_1327589654065_388.docx @ 8022 @ @ 1
P207
0 ... 1
***
{
}
Pos: 128 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P208 – Stat orwiderst an d @ 0\mod_1327589723457_388.docx @ 8045 @ @ 1
P208
0.00 ... 300.00 W
***
}
{
Nominal power
(Nominal motor power output)
P
The motor nominal power controls the motor set via P200.
Cos phi
(Motor cos
ϕ
)
S P
The motor cos ϕ is a decisive parameter for the current vector control.
Star Delta con.
(Star Delta connection)
S P
0 = Star 1 = Delta
vector control.
Stator resistance
(Stator resistance)
S P
Motor stator resistance ⇒ resistance of a phase winding with a DC motor.
overcurrent; too low a value to a motor torque that is too low. The parameter P220 can be used for simple measurement. Parameter P208 can be used for
manual setting or as information about the result of an automatic measurement. NOTE:
measured by the FI.
Pos: 129 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/Parameter/P200-P299/Paramet er P209 – Leer laufstro m @ 0\mod_1327589796537_388 .docx @ 8068 @ @ 1
P209
0.1 ... 1000.0 A
***
{
}
No load current
(No load current)
This value is always calculated automaticall parameter >cos ϕ< P206 and the parameter >Nominal current< P203.
NOTE:
Pos: 130 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P210 – Stati s c her Boost @ 0\mod_1327590156790_388.docx @ 8094 @ @ 1
P210
Static boost
(Static boost)
0 ... 400 % { 100 }
load current of the respective motor and is therefore load-independent calculated using the motor data. The factory setting of 100% is sufficient for normal applications.
Pos: 131 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P211 – Dyn amischer B oost @ 0\mod_1327590224915_388.docx @ 8117 @ @ 1
the only way to ensure that the value will not be overwritten.
S P
S P
*** These settings are dependent on the nominal power of the FI or the selection in parameter P200.
BU 0505 GB-1013 87
SK 54xE – Users Manual for Frequency Inverters
high a value can lead to overcurrent in the FI. Under load therefore, the output voltage will be
to keep the
The factory setting of 100% is optimal when using DC asynchronous motors and correct motor data
mpensation P212
must be set to 0%. This rules out a negative influence. This is equally valid for synchronous motors
for the expected torque requirement to be set in the controller. This
Motor torques (with rotation field right) are entered with a positive sign, generator
The reverse applies for the counter
for switching in an
additional current during the start phase. The application time is limited and can be selected at
With active ISD control (P211 and / or P212 ≠ 0%), parameterisation of P215 ≠ 0 results in incorrect
P211
0 ... 150 % { 100 }
Pos: 132 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P212 – Schl u pfkompens ation @ 0\mod_1327590275572_388.docx @ 8140 @ @ 1
P212
0 ... 150 % { 100 }
Pos: 133 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P213 – Verst. ISD- Regelung @ 0\ mod_1327590323026_388.docx @ 8163 @ @ 1
P213
25 ... 400 % { 100 }
Pos: 134 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/Parameter/P200-P299/Parameter P 214 – Vorhal t Drehmome nt @ 0\mod_1327590368794_388.docx @ 8186 @ @ 1
P214
-200 ... 200 % { 0 }
Pos: 135 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P215 – Boos t Vorhalt @ 0\mod_1327590415702_388.docx @ 8209 @ @ 1
P215
0 ... 200 % { 0 }
Dynamic boost
(Dynamic boost)
S P
The dynamic boost affects the torque generating current and is therefore a load-dependent parameter. The factory 100% setting is also sufficient for typical applications.
Too raised too sharply. Too low a value will lead to insufficient torque.
Slip compensation
(Slip compensation)
S P
The slip compensation increases the output frequency, dependent on load, asynchronous motor speed approximately constant.
has been set. If several motors (different loads or outputs) are operated with one FI, the slip co
that do not have slip due to their design.
ISD ctrl. loop gain
(Amplification of ISD control)
S P
This parameter influences the control dynamics of the FI current vector control (ISD control). Higher settings make the controller faster, lower settings slower.
Dependent on application type, this parameter can be altered, e.g. to avoid unstable operation.
Torque precontrol
(Torque precontrol)
S P
This function allows a value function can be used in lifting applications for a better load transfer during start-up.
NOTE:
torques are entered with a negative sign. clockwise rotation.
Boost precontrol
(Boost precontrol)
S P
Only advisable with linear characteristic curve (P211 = 0% and P212 = 0%). For drives that require a high starting torque, this parameter provides an option
parameter >Time boost precontrol< P216. All current and torque current limits that may have been set (P112 and P536, P537) are deactivated
during the boost lead time. NOTE:
control.
Pos: 136 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P216 – Zeit Boost Vor halt @ 0\mod_1327590478846_388.docx @ 8232 @ @ 1
88 BU 0505 GB-1013
5 Parameters
With the oscillation damping, idling current harmonics can be damped. Parameter 217 is a measure
For oscillation damping the oscillation component is filtered out of the torque current by means of a
nal to P217. The time constant for the high pass
With a set value of 10% for P217, a maximum of ± 0.045Hz are switched in. At 400% in P217, this
This setting influences the maximum possible output voltage of the FI in relation to the mains voltage. Values <100% reduce the voltage to values below that of the mains voltage if this is
equired for motors. Values >100% increase the output voltage to the motor increased the
With this parameter, an automatic adjustment of the magnetizing to the motor load can be made.
The reduction of the field is performed with a time constant of approx. 7.5 sec. On increase of load the field is built up again with a time constant of approx. 300 ms. The reduction of the field is carried
the magnetisation current and the torque current are approximately equal, so that the
motor is operated with “optimum efficiency”. An increase of the field above the setpoint value is not
equired torque only changes slowly (e.g.
pumps and fans). Its effect therefore replaces a quadratic curve, as it adapts the voltage to the
up of the
offs or inversion of
the motor on sudden changes of load, because the missing field would have be
gnetisation current controller is activated. The ISD controller then operates with a subordinate magnetizing controller, which improves the slippage calculation, especially at higher loads. The control times
P216
0.0 ... 10.0 sec { 0 }
Pos: 137 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P217 – Sch wingungsdä mpfung @ 0\mod_1327590520707_388.docx @ 8255 @ @ 1
P217
0 ... 400 % { 10 }
SW1.6 and above
Pos: 138 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P218 – Mo dul ationsgra d @ 0\ mod_1327590589726_388.docx @ 8278 @ @ 1
P218
50 ... 110 % { 100 }
SW 1.5 and above
Pos: 139 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P219 – Aut o. M ag n.anpass ung @ 0\mod_1327590637383_ 388.docx @ 8301 @ @ 1
P219
25 ... 100 % / 101 { 100 }
SW 1.6 and above
Time boost prectrl.
(Time boost precontrol)
S P
Only advisable with linear characteristic curve (P211 = 0% and P212 = 0%). Application time for increased starting cur rent. NOTE: With active ISD control (P211 and / or P212 ≠ 0%), parameterisation of P216 ≠ 0
results in incorrect control.
Oscillation damping
(Oscillation damping)
S P
of the damping power.
high pass filter. This is amplified by P217, inverted and switched to the output frequency. The limit for the value switched is also proportio
filter depends on P213. For higher values of P213 the time constant is lower.
corresponds to ± 1.8Hz The function is not active in “Servo mode, P300”.
Modulation depth
(Modulation depth)
S
r harmonics in the current, which may cause swinging in some motors.
Normally, 100% should be set.
Auto. magn. adjustment
(Automatic magnetisation adjustment)
S
P219 is a limiting value, to which the field in the motor can be reduced. As standard, the value is set to 100%, and therefore no reduction is possible. As m inimum, 25%
can be set.
out so that intended.
This function is intended for applications in which the r load.
NOTE: This must not be used for lifting or applications where a more rapid build-
torque is required, as otherwise there would be overcurrent switch-
101 = automatic, with the setting P219=101 an automatic ma
compensated by a disproportionate torque current.
are considerably faster compared to the Normal ISD control (P219 = 100)
Pos: 140 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P2xx – Regel ungs-/ Ke nnlinien-P arameter @ 0\mod_1327590712994_388.docx @ 8324 @ @ 1
BU 0505 GB-1013 89
SK 54xE – Users Manual for Frequency Inverters
P211
P210
P204
P201
P216
P215
Output
voltage
Output frequency
Time
P2xx Control/characteristic curve parameters
NOTE:
"typical" Settings for the...
Pos: 141 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P220 – Par a.-identifi kation @ 0\ mod_1327590796917_388.docx @ 8347 @ @ 1
Current vector control (factory setting) P201 to P209 = Motor data P210 = 100% P211 = 100% P212 = 100% P213 = 100% P214 = 0% P215 = no significance P216 = no significance
Linear V/f characteristic curve
P201 to P209 = Motor data P210 = 100% (static boost) P211 = 0% P212 = 0% P213 = no significance P214 = no significance P215 = 0% (boost precontrol) P216 = 0s (time dyn. boost)
90 BU 0505 GB-1013
5 Parameters
the motor data is automatically determined by the FI via this
The EMF constant describes the self induction voltage of the motor. The value to be set can be
The typical asymmetric reluctances of the PMSM are compensated with this parameter. The
P220 Para. identification
(Parameter identification)
0 … 2 { 0 }
For devices with powers up to 7.5 kW, parameter. In many cases, a better drive behaviour is possible with the measured motor data.
The identification of all parameters takes some time. Do not switch off the mains voltage during this time. If unfavourable operating characteristics result after identification, select a suitable motor in P200 or set the parameters P201 … P208 manually.
0 = No identification 1 = R
identification: only the stator resistance (display in P208) is determined by multiple
S
measurements.
2 = Motor identification :all motor parameters (P202, P203, P206, P208, P209) are
determined. This function can only be used with devices up to 7.5 kW (230 V to 4.0 kW).
Note! Only carry out the identification of motor data when the motor is cold (15 … 25°C) Warming up of
the motor during operation is taken into account. The FI must be in a “Standby” status For BUS operation, the BUS must be operating without error. The motor power may only be one power level greater or 3 power levels lower than the nominal
power of the FI. In order to enable reliable identification, the motor cable length must not exceed 20m. Before starting the motor identification, the motor data according to the type plate or P200 must be
pre-set. At least the nominal frequency (P201), the nominal speed (P202), the voltage (P204), the power (P205) and the motor circuit (P207) should be known.
Care must be taken that the connection to the motor is not interrupted during the entire measuring process.
If the identification cannot be concluded successfully, the error message E019 is generated. After identification of parameters, P220 is again = 0.
Pos: 142 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P240 – EMK- Konstante PMSM [S K 54xE] @ 0\mod_1327590879934_388.docx @ 8370 @ @ 1
P240 EMF constant PMSM
(EMF constant PMSM)
P
S P
0 … 400 V { 0 }
found on the data sheet for the motor or on the type plate and is scaled to 1000 rpm-1.
0 = ASM is used, "Asynchronous machine is used": No compensation
Pos: 143 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P241 – Induktivitaet PMSM [SK 54xE] @ 0\mod_1327590972170_388.docx @ 8393 @ @ 1
P241 [-01] [-02]
Inductivity PMSM
(Inductivity PMSM)
0.1 ... 200.0 mH { all 20.0 }
inductivities can be measured by the frequency inverter (P220)
[-01] = d axis [-02] = q axis
If q=0 is set, the value of the d axis is adopted automatically.
Pos: 144 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Paramet er P244 – Spitz enstrom PMSM [SK 5 4 xE ] @ 0\ mod_1327591035576_388.docx @ 8416 @ @ 1
P244 Peak current PMSM
(Peak current PMSM)
0.1 … 100.0 A { 20.0 }
Pos: 145 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P200-P299/ Parameter P246 – Mass enträgheit PMSM [SK 54xE] @ 0\ mod_1327591081936_388.docx @ 8439 @ @ 1
This parameter contains the peak current of a synchronous motor.
S P
S P
BU 0505 GB-1013 91
SK 54xE – Users Manual for Frequency Inverters
red in this parameter. For most applications the default setting is sufficient. However, for highly dynamic systems the actual value should ideally be entered. The values for the motors can be obtained from the technical data. The portion of the
This parameter activates speed control with speed measurement via an incremental encoder.
For correct function, an incremental encoder must be connected and the correct pulse number
If the encoder rotation direction is not the same as the FI, (depending on installation and wiring),
. If an incremental encoder
(Please refer to
, by which the speed difference between the setpoint and actual frequency is
multiplied. A value of 100% means that a speed difference of 10% produces a setpoint of 10%.
P246 Mass inertia PMSM
(Mass inertia PMSM)
0.1 … 1000.0 kg*cm² { 5.0 }
Pos: 146 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ P3xx Regel ungspara meter @ 0\mod_1327591132858_388.docx @ 8462 @ 5 @ 1

Control parameters

Only available above SK 520E with the use of an incremental encoder.
Parameter
{factory setting}
Pos: 147 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P300 – Servo Modus @ 0\mod_1327591436317_388.docx @ 8488 @ @ 1
P300
0 ... 1 { 0 }
Pos: 148 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P301 – Drehg eber Auflös ung @ 0\mod_1327591605104_388.docx @ 8511 @ @ 1
P301
The mass inertia of the drive system can be ente
external centrifugal mass (gear unit, machine) must be calculated or determined experimentally.
Setting value / Description / Note Supervisor
Servo mode
(Servo Mode)
This results in a very stable speed behaviour down to the standstill of the motor.
0 = Off 1 = No
NOTE:
must be entered in parameter P301.
Rotary encoder res.
(Rotary encoder resolution)
S P
Parameter set
P
0 ... 17 { 6 }
Pos: 149 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P310 – Dreh zahl Regl er P @ 0\mod_1327591703606_388.docx @ 8534 @ @ 1
P310
0 ... 3200 % { 100 }
Input of the pulse-count per rotation of the connected encoder.
this can be compensated for by selecting the corresponding negative pulse numbers 8...16.
0 = 500 pulses 1 = 512 pulses 2 = 1000 pulses 3 = 1024 pulses 4 = 2000 pulses 5 = 2048 pulses 6 = 4096 pulses 7 = 5000 pulses
8 = -500 pulses
9 = -512 pulses 10 = -1000 pulse s 11 = -1024 pulse s 12 = -2000 pulse s 13 = -2048 pulse s 14 = -4096 pulse s 15 = -5000 pulse s 16 = -8192 pulse s
17 = + 8192 pulses
NOTE:
(P301) is also significant for position control via incremental encoders is used for positioning (P604=1), the setting of the pulse number is made here. POSICON Supplementary Manual)
Speed controller P
(Speed controller P)
P
P-component of the speed encoder (proportional amplification). Amplification factor
Values that are too high can cause the output speed to oscillate.
Pos: 150 /Anleit ungen/5. /6. Parametrierung [BU 0500 / BU 0200]/P arameter/P300-P399/Parameter P 311 – Drehza hl Regler I @ 0\mod_1327591756013_388.docx @ 8557 @ @ 1
92 BU 0505 GB-1013
5 Parameters
The integration component of the controller enables the complete elimination of any control deviation. The value indicates how large the setpoint change is per ms. Values that are too small
Current controller for the torque current. The higher the current controller parameters are set, the
y high values in P312 generally lead
frequency oscillations at low speeds; on the other hand, excessively high values in P313
3, then the torque current control is switched off. In
Determines the maximum voltage increase of the torque current controller. The higher the value, the greater the maximum effect that can be exercised by the torque current controller. Excessive
lues in P314 can specifically lead to instability during transition to the field weakening zone (see
P320). The values for P314 and P317 should always be set roughly the same, so that the field
Current controller for the field current. The higher the current controller parameters are set, the more precisely the current setpoint is maintained. Excessively high values for P315 generally lead
low speeds. On the other hand, excessively high values in P316
generally produce low frequency vibrations across the whole speed range If the value "Zero" is
P311
0 ... 800 % / ms { 20 }
Pos: 151 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P312 – Momentenstromregler P @ 0\mod_1327591805216_388.docx @ 8580 @ @ 1
P312
0 ... 800 % { 200 }
Pos: 152 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P313 – Momentenstromregler I @ 0\mod_1327591883202_388.docx @ 8603 @ @ 1
P313
0 ... 800 % / ms { 125 }
Pos: 153 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P314 – Gre nze M.-stro mregler @ 0\mod_1327591927202_388.docx @ 8626 @ @ 1
P314
0 ... 400 V { 400 }
Speed controller I
(Speed controller I)
P
I-component of the encoder (Integration component).
cause the controller to slow down (reset time is too long).
Torque current controller P
(Torque current controller P)
S P
more precisely the current setpoint is maintained. Excessivel to high­generally produce low frequency oscillations across the whole speed range.
If the value "Zero" is entered in P312 and P31 this case, only the motor model pre-control is used.
Torque current controller I
(Torque current controller I)
S P
I-proportion of the torque current controller. (See also P312 >Torque current controller P<)
Torque current controller limit
(Torque current controller limit)
S P
va
Pos: 154 /Anleit ungen/5. /6. Param etrierung [BU 0500 / BU 0200]/Parameter/P300-P399/Paramet er P315 – Fel dstromreg ler P @ 1\ mod_1328618593561_388.docx @ 15410 @ @ 1
P315
0 ... 800 % { 200 }
Pos: 155 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P316 – Fel dstromregl er I @ 0\mod_1327592705182_388.docx @ 8676 @ @ 1
P316
0 ... 800 % / ms { 125 }
Pos: 156 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P317 – Gre nze Feldstr omregler @ 0\mod_1327592747463_3 88.docx @ 8699 @ @ 1
and torque current controllers are balanced.
Field current controller P
(Field current controller P)
S P
to high frequency vibrations at entered in P315 and P316, then the field current controller is switched off. In this case, only the
motor model pre-control is used.
Field current controller I
(Field current controller I)
S P
I-proportion of the field current controller. See also P315 >Field current controller P<
BU 0505 GB-1013 93
SK 54xE – Users Manual for Frequency Inverters
tage increase of the field current controller. The higher the value, the
greater is the maximum effect that can be exercised by the field current controller. Excessive P320). The values for P314 and P317 should always be set roughly the same, so that the field
oint when the synchronous speed is exceeded. Generally, the field weakening controller has no function; for this reason, the field weakening controller only needs to be set if speeds are set above the nominal motor speed.
ill lead to controller oscillations. The field is not weakened
sufficiently if the values are too small or during dynamic acceleration and/or delay times. The
The field weakening limit determines at which speed / current the controller will begin to weaken
set value of 100% the controller will begin to weaken the field at approximately the
If values much larger than the standard values have been set in P314 and/or P317, then the field
that the control range is actually available
component of the speed control is increased.
P317
0 ... 400 V { 400 }
Pos: 157 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P318 – Fel dschwächreg ler P @ 0\ mod_1327592793650_388.docx @ 8722 @ @ 1
P318
0 ... 800 % { 150 }
Pos: 158 /Anleit ungen/5. / 6. Parametr ierung [BU 0500 / BU 0200]/Par ameter/P 300-P399/Par ameter P3 19 – Feldsc h wäc hregler I @ 0\mod_1327677030485_388.docx @ 875 0 @ @ 1
P319
0 ... 800 % / ms { 20 }
Pos: 159 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P320 – Gre nz e Feldschw äc hr eg ler @ 0\mod_1327677173911_388.docx @ 8773 @ @ 1
P320
0 ... 110 % { 100 }
Field current controller limit
(Field current controller limit)
S P
Determines the maximum vol values in P317 can specifically lead to instability during transition to the field reduction range (see and torque current controllers are balanced.
Field weakening controller P
(Field weakening controller P)
S P
The field weakening controller reduces the field setp
Excessive values for P318 / P319 w downstream current controller can no longer read the current setpoint.
Field weakening controller I
(Field weakening controller I)
S P
Only affects the field weakening range, see P318 >Field weakening controller P<
Field weakening limit
(Field weakening limit)
S P
the field. At a synchronous speed.
Pos: 160 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P321 – Dreh zahlregler I Lü ftzeit @ 0\mod_1327677231913_388.do cx @ 8796 @ @ 1
P321
0 ... 4 { 0 }
Pos: 161 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P325 – Funktion Drehgeber @ 0\mod_1327677283553_388.docx @ 8819 @ @ 1
weakening limit should be correspondingly reduced, so to the current controller.
Speedctr. I Release time
(Speed controller I brake release time)
During the brake release time (P107/P114), the I­This leads to better load take-up, especially with vertical movements.
0 = P311 x 1 1 = P311 x 2 2 = P311 x 4
3 = P311 x 8 4 = P311 x 16
S P
94 BU 0505 GB-1013
5 Parameters
The actual speed list value supplied by an incremental encoder to the FI can be used for various
If the incremental encoder is not mounted directly onto the motor shaft, then the respectively
speed Encoder
speed Motor
P326 =
The limit value for a permitted maximum slip error can be set. If this value is reached, the FI If the permissible speed slip error defined in (P327) is exceeded the error message E013.1 is
P325
0 ... 4 { 0 }
Pos: 162 /Anleit ungen/5. /6. Parametrierung [BU 0500 / BU 0200]/Parameter/P300-P399/Paramet er P326 – Dr ehgeber Ü bersetzung @ 0\mod_1327677354896_388.docx @ 8842 @ @ 1
P326
0.01 ... 100.00 { 1.00 }
Pos: 163 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P327 – Schl eppfehler Drehzahlreg ler @ 0\mod_1327677406270_388.docx @ 8865 @ @ 1
P327
0 ... 3000 rpm { 0 }
Pos: 164 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P328 – Ver zögerung Sc hleppfehl er @ 0\mod_1327677464020_388.docx @ 8888 @ @ 1
P328
0.0 ... 10.0 sec { 0.0 } above SW 2.0
Pos: 165 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/Par ameter/P 30 0- P399/Para meter P330 – Regelverf ahren PMSM [SK 54xE] @ 0\mod_1327677510847_388 .docx @ 8911 @ @ 1
Rotary encoder function
(Rotary encoder function)
functions in the FI.
0 = Speed measurement Servo mode, "Servo mode speed measurement": The actual
motor speed list value is used for the FI servo mode. The ISD control cannot be switched off in this function.
1 = PID actual frequency value: The actual speed of a system is used for speed control.
This function can also be used for controlling a motor with a linear characteristic curve. It is also possible to use an incremental encoder for speed control which is not mounted directly onto the motor. P413 – P416 determine the control.
2 = Frequency addition: The determined speed is added to the actual setpoint value. 3 = Frequency subtraction: The determined speed is subtracted from the actual setpoint. 4 = Maximum frequency: The maximum possible output frequency / speed is limited by the
speed of the encoder.
Ratio encoder
(Encoder transformation ratio)
correct transformation ratio of motor speed to encoder speed must be set.
Only when P325 = 1, 2, 3 or 4, therefore not in Servo mode (motor sp eed contr ol)
Speed slip error
(Speed slip error, speed control)
switches off and indicates error E013.1.
0 = OFF
Only when P325 = 0, therefore in Servo mode (motor speed control)
Speed slip delay
(Speed slip error delay)
suppressed within the time limits which are set here.
0.0 = OFF
BU 0505 GB-1013 95
SK 54xE – Users Manual for Frequency Inverters
Voltage controlled: With the first start of the machine, a voltage indicator is memorised which ensures that the rotor of the machine is set to the rotor position "zero". This typ starting position of the rotor can only be used if there is no counter-torque from the machine (e.g. flywheel drive) at frequency "zero". If this condition is fulfilled, this method of determining the position of the rotor is very precise (<1° electrical). In principle, this method is not suitable for lifting equipment, as there is always a counter
For operation without encoders (in preparation), the following applies: Up to the switch over
frequency P331 the motor (with the nominal current memorised) is driven under voltage control. Once the switch over frequency has been reached, the method of determining the rotor position is switched over to the EMF method. If, taking hysteresis (P332) into account, the frequency falls below the value in (P331), the frequency inverter switches back from the EMF method to voltage controlled operation.
Test signal method: The starting position of the rotor is determined with a test signal. This method also functions at a standstill with the brake applied, however it requires a PMSM with sufficient anisotropy between the inductivity of the d and q axes. The higher this anisotropy is, the greater the precision of the method. By means of parameter (P212) the voltage level of the test signal can be adjusted and with parameter (P213) the position of the motor position control can be adjusted. For motors which are suitable for use with the test signal method, a rotor position accuracy of 5°…10° electrical can be achieved (depending on the motor and the anisotropy
For operation without encoders (in preparation), the following applies: Until the switchover
frequency is reached, the rotor position is determined by means of the test signal method. After this, with the setting "0" it is switched over to the EMF metho
Value from universal encoder,
With this method the starting position of the rotor is determined from the absolute position of a universal encoder (Hiperface, EnDat with Sin/Cos track, BISS with Sin/Cos track or SSI with Sin/Cos track) The universal encoder type is set in parameter (P604). For this position information to be unique it must be known (or determined) how this rotor position relates to the absolute position of the universal encoder. This is performed via offset parameter (P334). Motors should be delivered either with a starting rotor position "zero" or the starting rotor position must be marked on the motor.If this value is not available, the offset value can also be determined with the settings "0" and"1" of parameter (P330). For this the drive unit is started with the setting "0" or "1". After the first start the offset value which has been determined is saved in parameter (P334).However, this value is volatile, i.e. it is only saved in the RAM. In order to save it in the EEPROM, it must be briefly changed and then set back to the determined value. After this, fine tuning can be carried out with the motor idling. For this, the drive is operated in closed loop mode (P300=1) at as high a speed as possible below the field weakening point. From the starting point, the offset is gradually adjusted so that the value of the voltage component U
(P723) is as close to zero as possible. For this, a balance between the positive and negative direction of rotati Usually the value "zero" will not be completely achieved, as at higher speeds the drive is subjected to a slight load due to the motor fan. The universal encoder should be located on the motor shaft.
Value from CANopen encoder,
As for "2", however a
CANopen absolute encoder is used to determine the starting position of the rotor.
If there is an incremental encoder with a "null track" on the motor shaft, the "null track" can also be used to determine the position of the stator. The zero impulse is then used for synchronisation of the rotor position.
The offset between the zero pulse and the actual "zero" rotor position is set in parameter (P334) "Encoder offset". If the Sense cable (+5V Sense and 0V Sense) is not connected, there is no synchronisation to the zero pulse. Parameter (P330) must be set to "0" or "1". The value which needs to be set for parameter (P334) must be determined experimentally or must be enclosed with the motor.
P330
0 ... 3 { 1 }
Regulation PMSM
(Regulation PMSM)
Determination of the regulation of n<n
0 =
1 =
SWITHOVER
(See P331).
S
PMSM (Permanent Magnet Synchronous Motor s) at speed
e of
-torque.
).
2 =
3 =
d
"Value from universal encoder":
"Value from CANopen encoder":
NOTE:
Pos: 166 /Anleit ungen/5. / 6. Paramet rierung [BU 0500 / BU 0200]/Par ameter/P 300-P399/P arameter P3 31 – Umschaltfrequenz PMSM [SK 54xE] @ 0\mod_1327677873447_388.docx @ 8934 @ @ 1
96 BU 0505 GB-1013
d.
the
on must be sought.
5 Parameters
Definition of the frequency up to which in operation without encoder the control method of a
is activated according to (P330). In this case,
off point in order to prevent oscillation on the
fied in (P330) (and vice
(Permanent Magnet Synchronous Motors). The zero impulse is then used for synchronisation of the rotor position. The offset between the zero pulse and the actual
P331
1.0 ... 100.0 % { 15.0 }
Pos: 167 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P332 – Hyst erese Ums chaltfrequ enz PMSM [ SK 54xE] @ 0\mod_1327677923148_388.docx @ 8957 @ @ 1
P332
0.1 ... 25.0 % { 2.0 }
Pos: 168 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P333 – Flus s-Rückko pplungsfakt or PMSM [S K 54xE] @ 0 \mod_1327677965944_388.docx @ 8980 @ @ 1
P333
0 ... 400 % { 100 }
Pos: 169 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P334 – Geber offset PMSM [SK 54xE] @ 0\mod_1327678017910_388.docx @ 9003 @ @ 1
P334
-0,500 ... 0,500 rev { 0,000 }
Switchover freq. PMSM
(Switchover frequency PMSM )
S P
PMSM (Permanent Magnet Synchronous Motor)
100 % corresponds to the nominal motor frequency from (P201).
Hyst. Switchover PMS M
(Switchover frequency hysteresis PMSM)
S P
Difference between the switch-on and switch­transition of operation without encoder into the control method speci versa).
Flux feedback factor PMSM
(Flux feedback factor PMSM)
S P
- In preparation ­The parameter is significant for operation without encoders.
Encoder offset PMSM
(Encoder offset PMSM)
S
Evaluation of the zero track and the Sense signal is necessary for the operation of PMSM
"zero" rotor position is set in parameter (P334) "Encoder offset". If the Sense cable (+5 V Sense and 0 V Sense) is not connected, there is no synchronisation to the zero pulse.
Pos: 170 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P300-P399/ Paramet er P350 ff. - Infofeld @ 2\m od_1355738281779_388.docx @ 52511 @ @ 1
Information
PLC parameter P350 ff.
The description of the PLC-relevant parameters above P350 can be found in the manual BU 0550.
Pos: 171 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ P4xx Steu erklemmen @ 0\mod_1327678262854_388.docx @ 9027 @ 5 @ 1
BU 0505 GB-1013 97
SK 54xE – Users Manual for Frequency Inverters
In addition to the internal analog inputs, analog functions from the digital inputs DIN 2 and DIN 3
Assignment of the analog functions is carried out in the relevant array of parameter P400. The
09]. The functions which can be set correspond to those of the digital
Value
Function
Description
00
Off
The analog input has no function. After the FI has been enabled via the control terminals, it will supply the set minimum frequency (P104).
01
Setpoint frequency
The specified analog range (matching of analog input) varies the output frequency between the set minimum and maximum frequencies (P104/P105).
02
Torque current limit
Based on the set torque current limit (P112), this can be altered by means of an analog
orque current limit P112. 20%
cannot be undershot (with P300=1, not below 10%)!
03
Actual frequency PID*
Is required in order to set up a control circuit. The analog input (actual value) is
quency is adjusted as far as possible until the actual value equals the setpoint (see control values P413...P415).
04
Frequency addition **
The supplied frequency value is added to the setpoint.
05
Frequency subtraction**
he supplied frequency value is subtracted from the setpoint.
06
Current limit
Based on the set current limit (P1536), this can be altered via the analog input.

Control terminals

Parameter
{factory setting}
Pos: 173 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P400-P499/ Paramet er P400 – Funktion Analogeingang [SK 54x E] @ 0\mod_1327679014607_388.docx @ 9073 @ @ 1
P400 [-01] ... [-08]
0 ... 82 { [-01] = 1 } all other { 0 }
Setting value / Description / Note Supervisor
Digital analog input
(Analog input function)
P
[-01] = Analog input 1: analog input 1, integrated into the FI [-02] = Analog input 2: analog input 2, integrated into the FI [-03] = External analog input 1, "External analog input 1": Analog input 1 of the first IO
extension
[-04] = External analog input 2, "External analog input 2": Analog input 2 of the first IO
extension
[-05] = External Analog input 1, 2nd IOE, "External analog input 1 of the 2nd IOE": Analog
input 1 of the second IO extension
[-06] = External Analog input 2, 2nd IOE, "External analog input 2 of the 2nd IOE": Analog
input 2 of the second IO extension
[-07] = Analog function, Dig2, "Analog function of digital input 2": Analog function of digital
input 2 integrated into the FI. With this setting, digital input DIN2 is set to evaluate pulse signals. The pulses are then evaluated as an analog signal according to the function which is set here.
[-08] = Analog function, Dig3, "Analog function of digital input 3": Analog function of digital
input 3 integrated into the FI. With this setting, digital input DIN3 is set to evaluate pulse signals. The pulses are then evaluated as an analog signal according to the function which is set here.
Parameter set
or the analog inputs of optional IO extension modules can also be processed.
possible analog functions can be found in the following table. Assignment of digital functions to the analog inputs 1 and 2 of the motor controller is carried out in
parameter P420 [-08] or [­inputs (see table after P420).
The possible functions are listed in the following tables.
Pos: 174 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/Parameter/P400-P499/Paramet er P400 – Liste der analogen Funktionen der analogen Eingänge [SK 5xxE] @ 0\mod_1327679124524_388.docx @ 9096 @ 5 @ 1

List of possible analog functions of the analog inputs

value. 100% setpoint here corresponds to the set t
compared with the setpoint (e.g. fixed frequency). The output fre
98 BU 0505 GB-1013
5 Parameters
Value
Function
Description
07
Maximum frequency
The maximum frequency of the FI is varied. 100% corresponds to the setting in
nds to the setting in parameter P410. The values for the
minimum/maximum output frequencies (P104/P105) cannot be undershot/exceeded
08
Actual PID frequency
Like Function 3, Actual frequency PID, however the output frequency cannot fall below
(no change to rotation
direction)
09
monitored*
Like Function 3, Actual frequency PID, however the FI switches the output frequency off when the minimum frequency P104 is reached.
10
Servo mode
In servo mode ((P300) = "1") the motor torque can be set or limited using this function. Here the speed controller is switched off and a torque control is activated. The analog
rmware version SW 2.0, this function can be also be used with reduced control precision without servo mode or for ((P300) = "0").
11
A function which enables a value for the anticipated torque requirement to be entered
(interference factor switching). This function can be used to improve
the load take-up of lifting equipment with separate load detection.
12
Reserved
13
The setpoint is multiplied by the stated analog value. The analog value adjusted to 100% then corresponds to a multiplication factor of 1.
14
Actual value process
Activates the process controller, analog input 1 is connected to the actual value sensor
20 mA) is set
in P401.
15
setpoint *
The actual
value must be specified using another input.
16
Process controller precontrol *:
adds an adjustable additional setpoint after the pro cess cont r oller.
46
Setpoint Torque Process controller
48
Motor temperature
Motor temperature measurement with KTY-84, details in Section 0
53
d-correction F process
"Diameter correction for PID process controller frequency"
54
d-correction Torque
"Diameter correction of torque"
55
d-correction F + Torque
"Diameter correction for PID process controller frequency and torque"
*) further details regarding the process controller can be found in Section 0and P400
parameter P411. 0% correspo
limited*
Actual frequency PID
torque
Torque precontrol
Multiplication
controller *
Process controller
the programmed minimum frequency value in Parameter P104.
input is then the source of the setpoint value. Above fi
in the controller
(compensator, air can, flow volume meter, etc.). The mode (0-10 V or 0/4-
as function 14, however the setpoint is specified (e.g. by a potentiometer).
Process controller torque setp oint
**) The limits of these values are set by the parameters >Minimum frequency auxiliary setpoints< P410 and >Maximum frequency auxiliary setpoints< P411.
Further analog functions (47/49/56/57/58) are only relevant for POSICON.
NOTE: An overview of the scaling of the various setpoints can be found in Section 8.8.
Pos: 176 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P400-P499/ Paramet er P400 – List e der digi talen Funk tionen der analogen Ei ngänge [S K 54xE] @ 2\mod_1355489064948_388.docx @ 52354 @ 5 @ 1
BU 0505 GB-1013 99
SK 54xE – Users Manual for Frequency Inverters
to an analog signal which is less
than the 0% adjustment (P402).
range setting of the
P505), the drive stands still when the minimum
frequency (P104) is smaller than the absolute minimum frequency (P505). A brake that is
If the minimum frequency (P104) is greater than the absolute minimum frequency (P505),
um frequency (P104), the brake controlled by the FI is not

List of possible digital functions of the analog inputs

The analog inputs of the F I can also be parameteris ed to process d igital signals. The digital f unctions are set in parameter P420 [-08] or [-09].
If a digital function is ass i g ned to an ana log i nput , th e analog function of the r el evant inp ut must be set to {0} "Off" in order to prevent misinterpretation of the signals.
A detailed description of the digital func tions can be found af ter param eter P420. The func tions of the digital inputs are identical to the digital functions of the analog inputs.
Permissible voltage when using digital functions: 7.5...30 V.
NOTE:
The analog inputs with digit al f unc tions d o not comply with EN61131-2 (Type 1 digital inputs), bec a us e the idling currents are too low.
Pos: 177 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter überschri ft - Fortsetz u ng Ta b el l e @ 1\ mod_1331566123473_388.docx @ 18340 @ @ 1
Parameter
{factory setting}
Pos: 179 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P400-P499/ Paramet er P401 – Modus Analogeingang [SK 54xE] @ 0\mod_1327679475386_388.docx @ 9165 @ @ 1
P401 [-01] ... [-06]
0 ... 5 { all 0 }
Pos: 180 /A nleitunge n/5. /6. Par ametrieru ng [BU 0500 / BU 0200]/ Parameter/ P400-P499/ Paramet er P401 – Mo dus Analogei ngang - Mo dusliste @ 2\mod_1355489392924_388.docx @ 52378 @ @ 1
Setting value / Description / Note Supervisor
Analog input mode
(Mode analog input)
Parameter set
This parameter determines how the frequency inverter reacts
[-01] = Analog input 1: analog input 1, integrated into the FI [-02] = Analog input 2: analog input 2, integrated into the FI [-03] = External analog input 1, "External analog input 1": Analog input 1 of the first IO
extension
[-04] = External analog input 2, "External analog input 2": Analog input 2 of the first IO
extension
[-05] = External Analog input 1, 2nd IOE, "External analog input 1 of the 2nd IOE": Analog
input 1 of the second IO extension
[-06] = External Analog input 2, 2nd IOE, "External analog input 2 of the 2nd IOE": Analog
input 2 of the second IO extension
0 = 0 – 10V limited: An analog setpoint smaller than the programmed adjustment 0% (P402)
does not lead to undershooting of the programmed minimum frequency (P104).
1 = 0 - 10V: If a setpoint smaller than the programmed adjustment 0% (P402) is present, this
can cause a change in direction rotation. This allows rotation direction reversal using a simple voltage source and potentiometer.
E.g. internal setpoint with rotation direction change: P402 = 5 V, P104 = 0 Hz, Potentiometer 0-10 V à Rotation direction change at 5 V in mid­potentiometer.
At the moment of reversal (hysteresis = ±
100 BU 0505 GB-1013
controlled by the FI will have entered the hysteresis range.
the drive reverses when the minimum frequency is reached. In the hysteresis range ± P104, the FI supplies the minim applied.
Loading...