PROFINET bus module for NORD frequency inverters SK 200E Safety information
N O R D Frequency inverters
Safety and operating instructions for
drive power converters
(as per: Low Voltage Directive 2006/95/EEC )
1. General
During operation, drive power converters may, depending on their
protection class, have live, bare, moving or rotating parts or hot
surfaces.
Unauthorised removal of covers, improper use, incorrect installation
or operation causes a risk of serious personal injury or material
damage.
Further information can be found in this documentation.
All transportation, installation, initialisation and maintenance work
must be carried out by qualified personnel (compliant with IEC
364, CENELEC HD 384, DIN VDE 0100, IEC 664 or DIN VDE 0110,
and national accident prevention regulations).
For the purposes of these basic safety instructions, qualified
personnel are persons who are familiar with the assembly,
installation, commissioning and operation of this product and who
have the relevant qualifications for their work.
2. Proper use in Europe
Drive power converters are components intended for installation in
electrical systems or machines.
When installed in machines, the drive power converter cannot be
commissioned (i.e. commencement of the proper use) until it has
been ensured that the machine meets the provisions of the EC
Directive 2006/42/EEC (machine directive); EN 60204 must also be
complied with.
Commissioning (i.e. implementation of the proper use) is only
permitted when the EMC directive (2004/108/EEC) is complied with.
Drive power converters with the CE mark meet the requirements of
the Low Voltage Directive 2006/95/EEC. The harmonized standards
stated in the Declaration of Conformity are used for the drive power
converters.
Technical data and information for connection conditions can be
found on the rating plate and in the documentation, and must be
complied with.
The drive power converters may only be used for the safety
functions which are described and for which they have been
explicitly approved.
3. Transport, storage
Information regarding transport, storage and correct handling must
be complied with.
4. Installation
The installation and cooling of the equipment must be implemented
according to the regulations in the corresponding documentation.
The drive power converters must be protected against
impermissible loads. Especially during transport and
handling, components must not be deformed and/or
insulation distances must not be changed. Touching of
electronic components and contacts must be avoided.
Drive power converters have electrostatically sensitive
components, which can be easily damaged by incorrect
handling. Electrical components must not be mechanically
damaged or destroyed (this may cause a health hazard!).
5. Electrical connections
When working on live drive power converters, the applicable
national accident prevention regulations must be complied
with (e.g. VBG A3, formerly VBG 4).
The electrical installation must be implemented according to
the applicable regulations (e.g. cable cross-section, fuses,
ground lead connections). Further information is contained
in the documentation.
Information about EMC-compliant installation – such as
shielding, earthing, location of filters and installation of
cables can be found in the drive power converter
documentation. These instructions must be complied with
even with CE marked drive power converters. Compliance
with the limiting values specified in the EMC regulations is
the responsibility of the manufacturer of the system or
machine.
6. Operation
Where necessary, systems where drive power converters
are installed must be equipped with additional monitoring
and protective equipment according to the applicable safety
requirements, e.g. legislation concerning technical
equipment, accident prevention regulations, etc.
The parameterisation and configuration of the drive power
converter must be selected so that no hazards can occur.
All covers must be kept closed during operation.
7. Maintenance and repairs
After the drive power converter is disconnected from the
power supply, live equipment components and power
connections should not be touched immediately, because of
possible charged capacitors. Observe the relevant
information signs located on the drive power converter.
Further information can be found in this documentation.
These safety instructions must be kept in a safe place!
2 BU 0290 GB-4312
Page 3
Documentation
Designation of
previous issues
Software
Version
Remarks
BU 0290 GB, October 2012
Part No. 607 2902 / 4312
V 1.1 R0
First issue
NOTE
This supplementary operating manual is only valid in conjunction with the operating manual
supplied for the respective frequency inverter (Manual BU0200).
Designation: BU 0290 GB
Part No.: 607 29 01
Device series: PROFINET IO for SK 200E
Device types: SK TU4-PNT(-C) with SK TI4-TU BUS
Compliance with the operating instructions is essential for fault-free operation and the
acceptance of any warranty claims. These operating instructions must be read before
working with the device!
These operating instructions contain important information about servicing. They must
therefore be kept close to the device.
The field bus technology options described here are intended for use in combination with SK
200 E series frequency inverters. Use of SK TU4-EPNT(-C) technology units is also possible
with the SK 500E series. The use of these technology options with other devices is not
permitted and can lead to their destruction.
The field bus technology options and the associated frequency inverters are devices for fixed
installation on motors or in equipment close to the motor to be operated. All details
regarding technical data and permissible conditions at the installation site must be
complied with.
Commissioning (commencement of the intended use) is not permitted until it has been ensured
that the machine complies with the EMC Directive 2004/108/EEC and that the conformity of
the end product meets the Machinery Directive 2006/42/EEC (observe EN 60204).
Getriebebau NORD GmbH & Co. KG, 2012
BU 0290 GB-4312 3
Page 4
PROFINET bus module for NORD frequency inverters SK 200E
1 GENERAL ................................................................................................................................ 6
1.1 The bus system ................................................................................................... 6
10.1 List of illustrations ............................................................................................. 73
10.2 List of tables ..................................................................................................... 73
10.3 Keyword index .................................................................................................. 74
BU 0290 GB-4312 5
Page 6
PROFINET bus module for NORD frequency inverters SK 200E
1 General
Modern field bus systems, microcontrollers and communication networks have had a great influence on
automation systems and have resulted in greater flexibility, availability and ultimately, also a reduction in
costs.
The widespread use of PC-based control only became possible with the availability of field bus systems.
With increasing control unit performance, the classic field bus ultimately became the limiting criterion for the
entire system. It was therefore an obvious step to adapt Ethernet technology, which provides high rates of
data transmission in IT applications, to the field of automation.
1.1 The bus system
As a physical transfer medium, PROFINET® transfers many years of experience with PROFIBUS-DP-V1 to
Fast Ethernet. In addition to the conventional open Ethernet communication TCP/IP it enables real time
communication of process data. PROFINET defines three communication classes, which provide different
levels of efficiency and functionality:
TCP/IP or UDP/IP communication without real time capability
Real time communication for process data (>1ms) RT
Isochronous real time communication for synchronised process data IRT
Features of the SK TU4-PNT(-C)
PROFINET IO real time communication (RT=Real Time and IRT=Isochronous Real Time)
Automatic address assignment via the IO controller using DCP (discovery configuration protocol)
Switched Ethernet
Autonegotiation (negotiation of transfer parameters)
Autocrossover (Transmission and reception cables crossed over in the switch)
Conforms with Class B, C
PROFINET IO bus cable connection via RJ45 plug - connector
Connection of I/Os and system bus via screw terminals and optionally via M12 round connectors
Display of specific PROFINET IO status with 2 LEDs
Specific DEVICE or FI status display with 2 LEDs
Eight integrated 24V inputs and two 24V outputs
Available as a version in a separate housing (optionally IP55 / IP66)
An interface (RS232/RS485) via an integrated RJ12 socket is available for parameter access by
means of the manual control unit SK PAR-3H or via NORDCON software.
Performance
Electrically isolated bus interface 500V
eff
100Mbit/s data communication
Full duplex transmission
Transmission of a maximum of five setpoints or actual values to the frequency inverter
Cyclic parameterisation (PPO 1 + 2) or acyclic parameterisation (Records)
PROFINET Bus Gateway solution → up to 4 frequency inverters can be connected to a PROFINET
bus module
Almost unlimited participants in the PROFINET system possible (limited by the controller)
6 Subject to technical amendments BU 0290 GB-4312
Page 7
1.2 Delivery
Check the equipment immediately after delivery/unpacking for transport damage such as deformation or
loose parts.
If there is any damage, contact the carrier immediately and carry out a thorough assessment.
Important! This also applies even if the packaging is undamaged.
1.3 Scope of supply
Standard version: SK TU4-PNT(-C)IP55 (optionally IP66)Operating instructions as PDF file on CD ROM
including NORD CON, (Windows PC-based parameterisation software)
Available accessories: SK TI4-TU-BUS(-C) (bus connection unit, required for SK TU4…)SK TIE4-WMK-TU, wall-mounting kit TU4
M12 round plug connector (Section 8.2 "Cable glands and shielding connections")Matching RJ12 to SUB-D9 adapter cable to connection to a PC
ParameterBox: SK PAR-3H, plain text LCD display
1.4 Certifications
1 General
1.4.1 European EMC Directive
If the NORD frequency inverter or its options are installed according to the
recommendations in this instruction manual, it meets all EMC directive
requirements, as per the EMC product standard for motor-operated systems
EN 61800-3. (see also Section 8.1.3 , "Cable layout and shielding (EMC
measures)")
1.4.2 RoHS compliance
The bus options described here are designed to be RoHS compliant
according to Directive 2002/95/EEC
BU 0290 GB-4312 Subject to technical amendments 7
Page 8
PROFINET bus module for NORD frequency inverters SK 200E
SK TU4-PNT (-C-M12-WMK-TU)
Wall mounting kit: for external technology units, TU4
M12 system connectors: only TU4, alternative to terminals (not for PROFINET)
IP protection class: Standard = IP55, C = „coated“ IP66
Option type: CAO = CANopen, PBR = Profibus, PNT = PROFINET
DEV = DeviceNet, IOE = I/O-extension
Option series: TU4 = external Technology Unit
CU4 = internal customer unit (not for PROFINET)
(...) Options, only implemented if required.
Optional external
technology unit, SK TU4-…(Examples)
1.5 Type code / Optional BUS modules
BUS = Bus module or I/O extension
8 Subject to technical amendments BU 0290 GB-4312
Page 9
1.6 Version with protection class IP55 / IP66
NOTE
The modules for the IP66 design are identified by an additional "-C" and are modified
according to the following special measures!
NOTE
For all versions, care must be taken that the cable and the cable gland are carefully
matched. This is essential to ensure that the required protection class is maintained.
NORD SK 200E frequency inverters and the external additional modules are available in all sizes and
powers in the protection classes IP55 (standard) or IP66 (optional).
The protection class IP66 must always be stated when ordering!
There are no restrictions or differences to the scope of functions in either protection class. In order to
differentiate the protection classes, modules with protection class IP66 are given an extra “-C” (coated
coated PCBs) in their type designation.
e.g. SK TU4-PNT-C
IP55 version:
The IP55 version of the external technology units is the standard version. Both versions (inverter-mounted
– as a supplement to the frequency inverter or wall mounted on the wall bracket) are available.
IP66 version:
In contrast to the IP55 version the IP66 version is a modified option. With this design, both versions
(inverter-mounted or wall-mounted) are also available. The modules available for the IP66 version (adapter
units, technology units and customer units) have the same functionalities as the corresponding modules for
the IP55 version.
1 General
Special measures:
Impregnated PCBs, coated housing
Diaphragm valve for pressure compensation on temperature changes.
Low pressure test
A free M12 screw connection is required for low pressure testing. After successful testing, a
diaphragm valve is inserted here. This screw connections is therefore no longer available
for a cable gland.
BU 0290 GB-4312 Subject to technical amendments 9
Page 10
PROFINET bus module for NORD frequency inverters SK 200E
SK 200E with external technology unit SK TU4-…
and BUS connection module SK TI4-TU-BUS
SK TIE4-WMK-TU with BUS connection module SK TI4-TU-BUS
and external technology unit SK TU4-PNT
NOTE
Modules should not be inserted or removed unless the device is free of voltage. The slots
may only be used for the intended modules.
Mounting of the external technology unit remote from the frequency inverter is possible with the
additional wall-mounting kit (SK TIE4-WMK-TU). However, a maximum cable length of 30m
should not be exceeded.
The external technology units (SK TU4-...) cannot be operated without the BUS connection unit
(SK TI4-TU-BUS)!
NOTE
Only one technology unit (SK CU4-... or SK TU4-...) can be connected to a system bus.
2 Assembly and installation
2.1 Installation and assembly
Only external technology units (Technology Units) are available for PROFINET IO. These are tailored to the
NORD SK 200E frequency inverter series.
These are used to connect SK 200E series speed regulated drive units to overriding automation systems via
the PROFINET IO field bus.
The technology units (Technology Unit, SK TU4-...) are externally attached to the SK 200E connection unit
and are therefore easy to access. Mounting of the SK TU4-... separate from the frequency inverter is possible
by means of the wall mounting kit SK TIE4-WMK-TU. The electrical connection to the SK 200E is made via the
internal system bus. Optionally, 4 or 5 pin M12 round connectors are available (for installation on the BUS
connection unit SK TI4-TU-BUS), which can be used for connection of the digital I/Os and the system bus
cables.
10 Subject to technical amendments BU 0290 GB-4312
Page 11
2.1.1 Overview of PROFINET IO modules
Bus Module
Description
Data
PROFINET IO module*)
SK TU4-PNT(-C)
Part No. 275281115 (IP55)
Part No. 275281165 (IP66)
This option enables control of the SK 200E via
PROFINET IO.
This option is installed externally to the frequency
inverter.
According to the installation location, at least one
"BUS connection unit"* is required.
Supported profile:
CoE
Baud rate:
up to 100 MBaud
Connection:
36 pin spring terminal bar
of the “BUS connection unit”*
8x Digital inputs:
Low: 0-5V, High: 11-30V
2x Digital outputs:
0/24V
System bus
Connection unit for TU4
SK TI4-TU-BUS
Part No. 275280000 (IP55)
Part No. 275280500 (IP66)
The connection unit is always required in order to
use an external technology unit (SK TU4-...). This
implements the connection of the technology unit to
the SK 200E or the wall-mounting kit.
Connection:
36 pin spring terminal bar
36x 2.5mm2
AWG 26-14
spring terminals
TU4 Wall-mounting kit
SK TIE4-WMK-TU
Part. No. 275274002
With the wall mounting kit, a technology unit can be
used/installed separately from the SK 200E.
*)
in order to use the TU4 modules, a suitable
SK TI4-TU-BUS connection unit must always be available!
2 Assembly and installation
Table 1 Overview of PROFINET IO modules
BU 0290 GB-4312 Subject to technical amendments 11
Page 12
PROFINET bus module for NORD frequency inverters SK 200E
WARNING
Installation must be carried out by qualified personnel only, paying particular attention to
safety and warning instructions.
Modules must not be installed or removed unless the device is free of voltage. The slots
may only be used for the intended modules.
Mounting of the technology unit remote from the frequency inverter is possible with the additional wall mounting kit SK TIE4-WMK-TU.
136
58
External BUS connection unit SK TI4-TU-BUS
2.1.2 Installing the SK TU4-PNT-... technology unit
Together with the BUS connection unit SK TI4-TU-BUS(-C) the technology unit SK TU4-PNT-…(-C) forms a
stand-alone functional unit. This can be attached to the SK 200E frequency inverter or installed separately by
means of the optional SK TIE4-WMK-TU wall-mounting kit.
2.1.2.1 Dimensions of the SK TI4-WMK-TU wall-mounting kit
The optional wall-mounting kit has the following dimensions.
Fig. 1 Wall-mounting kit SK TIE4-WMK-TU, dimensions
2.1.2.2 BUS connection unit SK TI4-TU-BUS(-C)
Various cable glands closed by caps are located on the sides of the BUS
connection unit.
The following holes are available as cable inlets:
2 x 1 M20 x 1.5 (on sides)
4 M16 x 1.5 (underside)
2 M25 x 1.5 (rear side, without caps)
The transparent screw-on cover (M20 x 1.5) on the upper right serves as access to the diagnostic interface
(RJ12 socket, interface RS232/RS485). The upper left screw-on cover is not used.
12 Subject to technical amendments BU 0290 GB-4312
Page 13
2 Assembly and installation
Technology unit SK TU4-PNT BUS Connection Unit SK TI4-TU-BUS
Mounting an external technology unit on the SK 200E (example)
Wall-mounting kit SK TI4-WMK-TU
Wall-mounting kit SK TI4-WMK-TU with field bus technology unit
2.1.2.3 Mounting the SK TI4-TU-BUS on the SK 200E
The screw fittings and seals required for installation are enclosed with the modules or are fitted to the intended
locations.
Mounting of the technology unit on the SK 200E must be carried out as follows:
1. Switch off the mains.
2. Remove the two M25 caps on the required side of the frequency inverter (right / left).
3. Remove the printed circuit board (with terminal bar)
from the BUS connection unit.
4. Install the SK TI4-TU-BUS with the enclosed seal on
the SK 200E using the 4 enclosed bolts.
5. Screw in both of the enclosed M25 to M12
reductions from the inside of the connection unit of
the frequency inverter. (Purpose: to avoid damage to the
internal wiring in the area of the junction of the
SK TI4-TU-...(connector unit for optional external modules) to the
SK TI4-… (frequency inverter connector unit))
6. Replace the printed circuit board (See point 3) and
carry out the electrical connections.
7. Fit and screw on the SK TU4 module.
2.1.2.4 Wall-mounting the SK TI4-TU-BUS
The screw fittings (except for anchoring screws) and
seals required for installation are enclosed with the
modules or are fitted to the intended locations.
The connecting cable between the technology unit and
the SK 200E should not be longer than 30m.
1. Mount the SK TI4-TU-BUS connecting unit with
adhered seal on the wall-mounting kit. To do this:
Insert the 2 x cheese-head screws (enclosed with
wall-mounting kit) into the (countersunk) holes from
the outside and with the 2 x bolts (enclosed with the
wall-mounting kit) securely screw both components
together from the inside (BUS connection unit).
2. Make a suitable cable connection between the technology unit and the frequency inverter. Take care that
there is appropriate screw fitting and sealing of the modules. The cable sets enclosed with the BUS
connection unit are not used.
3. Fit and screw on the SK TU4 module.
BU 0290 GB-4312 Subject to technical amendments 13
Page 14
PROFINET bus module for NORD frequency inverters SK 200E
WARNING
THE DEVICES MUST BE EARTHED.
Safe operation of the devices requires that is installed and commissioned by qualified personnel
in compliance with the instructions provided in this Manual.
In particular, the general and regional installation and safety regulations for work on high voltage
systems (e.g. VDE) must be complied with as must the regulations concerning correct use of tools
and the use of personal protection equipment.
Dangerous voltages can be present at the motor connection terminals of the frequency inverter
even when the inverter is switched off. Always use insulated screwdrivers on these terminal fields.
Ensure that the input voltage source is not live before setting up or changing connections to the
unit.
Make sure that the inverter and motor are specified for the correct supply voltage.
Outgoing cable, fixed
connection e.g. for system
bus or 24V supply
Incoming cable, fixed
connection e.g. for system
bus or 24V supply
Cable gland for system bus cable pair
and 24V supply for direct attachment
to SK 200E
No function,
do not use
Diagnostic access
RJ 12 socket
Cable gland for system bus cable pair
and 24V supply for direct attachment
to SK 200E
M16 cable gland or installation of M12 round plug connection for:
24V and 24V (for DO) supply
System bus
I/O peripherals: sensors and actuators
2.2 Electrical connection
2.2.1 Cable gland
Both the SK 200E connection unit and the bus module provide extensive facilities for the connection of all the
required cables. The cables may enter the housing via cable glands and be connected to the terminal bar.
However, appropriate round plug connections (e.g.: M12 round plug connectors in M16 cable glands) may be
fitted in order to provide a plug-in solution.
Fig. 2 Cable gland on the BUS module / connection unit
14 Subject to technical amendments BU 0290 GB-4312
Page 15
Specification
PROFINET IO
Max. baud rate 100 MBaud
Electrical isolation 500V
eff
Bus connection
2 RJ45
Bus termination
Performed automatically by the SK TU4-… technology unit
Cable
Ethernet CAT-5 or better
Max. cable length
100m between two Ethernet bus modules
Supply voltage
24V 20%, current consumption ≈ 100mA
Reverse polarity protected
Status display
4 LEDs
Device address
via the PROFINET IO controller or parameterisation
PE
Connection via plug pins under the 24V supply
Shield
The shields of the two RJ sockets are connected together and connected to PE with a
high resistance and capacitance.
Signal
Name
RJ45 Pin
TX+
Transmission Data +
1
TX-
Transmission Data -
2
RX+
Receive Data +
3
RX-
Receive Data -
6
Designation
Data
Rigid cable cross-section
0.14 … 2.5mm²
Flexible cable cross-section
0.14 … 1.5mm²
AWG standard
AWG 26-14
Tightening torque (for screw terminals)
0.5 … 0.6Nm
Pin 1
Pin 8
2.2.2 Control connections
2.2.2.1 Field bus (PROFINET IO)
2 Assembly and installation
Table 2 Electrical specifications of the SK TU4-PNT
The field bus cable must only be connected to the two RJ45 sockets mounted on the front.
Table 3 RJ45 socket connections
2.2.2.2 Peripherals (system bus and IOs)
The PROFINET IO modules must be provided with a 24V DC (±20%, 100mA) control voltage. Wire end
sleeves must be used for flexible cables.
Within the terminal box (unshielded cable section) the data cables (system bus) must be installed as short as
possible and of equal length. Associated data cables (e.g.: Sys+ and Sys-) must be twisted.
BU 0290 GB-4312 Subject to technical amendments 15
Page 16
PROFINET bus module for NORD frequency inverters SK 200E
NOTE
The cable shielding must be connected to the functional earthing 1(usually the
electrically conducting mounting plate) in order to prevent EMC interference in the
device.
In order to achieve this, for PROFINET connections it is mandatory that the metallic metric
EMC screws are used for the connection of the PROFINET shielding lead to the frequency
inverter or the housing of the technology unit. This ensures a wide area connection of the
functional earthing.
Digital inputs
System bus level and digital inputs
Digital outputs
24V DIN 5 DIN 6 0V 24V
(as
for 1)
24V
(as
for 1)
24V
(as
for 1)
0V
0V
DIN 1
0V
24V
(as
for 1)
DIN 2
0V
24V
(as
for 1)
24V 2
DO 1
0V 2
1 3 5 7 9
11
13
15
17
19
21
23
25
27
29
31
33
35
2 4 6 8 10
12
14
16
18
20
22
24
26
28
30
32
34
36
24V
(as
for 1)
DIN 7 DIN 8 0V 24V
(as
for 1)
24V
(as
for 1)
Sys +
Sys -
0V
DIN 3
0V
24V
(as
for 1)
DIN 4
0V
24V
(as
for 1)
24V 2
DO 2
0V 2
SK 205E... - bus connection unit (SK TI4)
SK TU4-ECT... - bus connection unit (SK TI4-TU-BUS)
Voltage
source
24V DC
NOTE
Looping of the 24V supply or GND is possible, however the maximum current load of 3A
must not be exceeded with the module.
Only adjacent terminals (e.g.: 11/12) may be used for looping.
Terminals 1/2 are preferentially for use with sensors and with maximum loads of 500mA.
1
Illustration of the terminal bar of the bus connection unit
SK TI4-TU-BUS with allocation of functions
Potential level: system bus
Potential level: system bus
Potential level: DOs
The double spring terminal bar is divided into 2 potential levels (system bus and digital outputs).
A separate power source should be used for the supply of the DOs. However, by bridging 24V 2 and 0V 2 to
one of the terminals of the system bus level (24V and 0V) it is possible to implement the supply of the DOs.
However, in this case it should be noted that there is an increased risk of introducing interference into the bus
cables.
Connection of up to 8 sensors and 2 actuators is made via the terminal bar.
Connection example: SK TU4-PNT to SK 200E
In systems, electrical equipment is usually connected to a functional earth. This serves as a means to dissipate leakage and
interference currents in order to ensure EMC characteristics and must therefore be implemented according to high frequency technology
aspects.
16 Subject to technical amendments BU 0290 GB-4312
Page 17
Control connection details
Terminal/
Designation
Function
Data
Description /
wiring suggestion
Parameter
1 24V
2
9
10
24V supply
(Module and system bus
level)
24VDC ±20%
≈ 100 mA
reverse polarity protected
Max. permissible current
load: 500mA
Connection of supply voltage
for module and 24V source for
supply of the digital inputs
(DIN1 to DIN8)
via DC/DC converter to
Terminal 11.
-
3 DIN5
Digital input 5
(I/O PROFINET DIN5)
Low 0V ... 5V
High 15V ... 30V
Ri = 10k
Input capacitance 10nF
Scan rate 1 ms
Inputs as per
EN 61131-2 Type 1
Each digital input has a
reaction time of 3 ms.
P174
4 DIN7
Digital input 7
(I/O PROFINET DIN7)
P174
5 DIN6
Digital input 6
(I/O PROFINET DIN6)
P174
6 DIN8
Digital input 8
(I/O PROFINET DIN8)
P174
7 0V
8
GND
Reference potential
for digital signals
As for terminal 15
GND for system bus and digital
inputs (DIN1 to DIN8)
via connection of DC/DC
converter to Terminal 15
-
11 24V
12
13
24V supply
(Module and system bus
level)
As for terminal 1
However, max. permissible
current load: 3A
Connection of supply voltage
for module and 24V source for
supply of the digital inputs
(DIN1 to DIN8)
-
15 0V
17
18
GND
Reference potential
for digital signals
-
14 Sys+
System bus
data cable +
System bus
interface
-
16 Sys-
System bus
data cable -
-
19 DIN1
Digital input 1
(I/O PROFINET DIN1)
Low 0V ... 5V
High 15V ... 30V
Ri = 8.1k
Input capacitance 10nF
Scan rate 1 ms
Inputs as per
EN 61131-2Type 1
Each digital input has a
reaction time of 3 ms.
P174
20 DIN3
Digital input 3
(I/O PROFINET DIN3)
P174
21 0V
22
GND
Reference potential
for digital signals
As for terminal 15
Connection of supply voltage
for module and 24V source for
supply of the digital inputs
(DIN1 to DIN8)
-
23 24V
24
24V supply
(Module and system bus
level)
As for terminal 1
However, max. permissible
current load: 3A
-
2 Assembly and installation
BU 0290 GB-4312 Subject to technical amendments 17
Page 18
PROFINET bus module for NORD frequency inverters SK 200E
Terminal/
Designation
Function
Data
Description /
wiring suggestion
Parameter
25 DIN2
Digital input 2
(I/O PROFINET DIN2)
Low 0V ... 5V
High 15V ... 30V
Ri = 8.1k
Input capacitance 10nF
Scan rate 1 ms
Inputs as per
EN 61131-2Type 1
Each digital input has a
reaction time of 3 ms.
P174
26 DIN4
Digital input 4
(I/O PROFINET DIN4)
P174
27 0V
28
GND
Reference potential
for digital signals
As for terminal 15
Connection of supply voltage
for module and 24V source for
supply of the digital inputs
(DIN1 to DIN8)
-
29 24V
30
24V supply
(Module and system bus
level)
As for terminal 1
However, max. permissible
current load: 3A
-
Potential isolation
31 24V2
24V supply
of digital outputs
24VDC -/+20%
Up to 1A, according to load
reverse polarity protected
Supply voltage connection for
digital outputs (DO1 and DO2)
If necessary, bridge to 24V
terminal
-
32 0V2
GND 2
Reference potential
for digital outputs
Ground for digital outputs (DO1
and DO2)
If necessary, bridge to 0V
terminal
-
33 DO1
Digital output 1
(I/O PROFINET DO1)
Low = 0V
High: 24V
Rated current: 500mA each
The digital outputs should be
used with a separate 24V
supply
P150
P175
34 DO2
Digital output 2
(I/O PROFINET DO2)
P150
P175
35 0V2
36
GND 2
Reference potential
for digital outputs
Ground for digital outputs (DO1
and DO2)
If necessary, bridge to 0V
terminal
-
Table 4 Connection assignment of BUS connection unit for PROFINET IO
18 Subject to technical amendments BU 0290 GB-4312
Page 19
3 Displays and diagnosis
RJ12
LEDs
Potentiometers
RJ12
LEDs Potentiometers
Frequency inverterSK 205E
viewing window (transparent screw-on cover) for
diagnostic interface RJ12, status LEDs, potentiometer
PROFINET Module SK TU4-PNT with
SK TI4-TU-BUS and SK TIE4-WMK-TU
Status LEDs and screw connection for RJ12
diagnostic interface
RJ12
BUS Status BS and BE
Status LED S/E
3 Displays and diagnosis
Various diagnosis possibilities are available, depending on the device. Operating conditions or errors are
visualised by means of LEDs. PC-based communication or the connection of a parameterisation unit is
possible via an RS232 interface (RJ12 diagnostic socket).
3.1 LED displays
Both the SK 200E frequency inverter and the PROFINET modules provide LED status and diagnostic displays
to indicate the various statuses.
A differentiation into 2 categories is made
Module or module-specific displays (S and E or DS and DE)
PROFINET-specific displays
(- physical status: L/A in and L/A out
- Process status: RUN and BF)
3.1.1 Device-specific display versions
3.1.1.1 frequency inverter SK200E
LED S/E
The double LED S/E indicates the operating status of the
frequency inverter by change of colour and different flashing
frequencies. A device error is indicated by cyclic red flashing
of the LED. The frequency of the flashing signals
corresponds to the error number (Manual BU 0200).
LEDs RUN and BF
The dual LEDsRUN (BUS State) and BF (BUS Fault)
indicate the status of the system bus communication module.
Various bus communication errors are indicated by means of
different flashing frequencies.
A detailed description of the LED displays of the frequency
inverter can be found in the main manual (BU0200).
BU 0290 GB-4312 Subject to technical amendments 19
Page 20
PROFINET bus module for NORD frequency inverters SK 200E
3.1.1.2 Technology unit SK TU4-PNT
LEDs LINK and ACT
The single colour LINK LEDs indicate the physical connection to
the Ethernet bus.
The single colourACT (Activity) LEDs indicate bus activity (data
transfer).
LEDs RUN and BF
The single colour LEDs RUN(PROFINET RUN) and BF
(PROFINET BUS FAULT) indicate the PROFINET communication
status.
LEDs DS and DE
The dual colour LEDs DS (Device State) and DE (Device Error) indicate the
status of the module and the status of the system bus.
A detailed description of the LED displays for this module can be found in Section 3.1.2 "Signal status LEDs".
20 Subject to technical amendments BU 0290 GB-4312
Page 21
3 Displays and diagnosis
DS
(Device State)
Green LED
DE
(Device Error)
Red LED
Meaning
long flashing = 0.5 s on / 1 s off
short flashing = 0.25 s on / 1 s off
OFF
OFF
Technology unit not ready, no control voltage
ON
OFF
Technology unit ready, no error, at least one frequency inverter is
communicating via the system bus
ON
Short flashing
Technology unit ready, however
one or more of the connected frequency inverters has a fault status
(see frequency inverter manual)
Long flashing
OFF
Technology unit ready and at least one further subscriber is connected
to the system bus, but
No frequency inverter on the system bus (or connection interrupted)
Address error for one or more system bus participants
Long flashing
Short flashing
Flash interval
1 x - 1s pause
System bus is in status "Bus Warning"
Communication on system bus interrupted or
no other participant present on the system bus
Long flashing
Short flashing
Flash interval
2 x - 1s pause
System bus is in status "Bus off" or
the system bus 24V power supply was interrupted during operation
Long flashing
Short flashing
Flash interval
3 x - 1s pause
No system bus 24V power supply
(system bus is in status "Bus off")
Long flashing
Short flashing
Flash interval
4 x - 1s pause
PROFINET error of the technology unit
Details: LED flashing code: RUN and BF
(Section 3.1.2.2 "PROFINET displays"
OFF
Short flashing
Flash interval
1…7 x - 1s pause
System error, internal program sequence interrupted
This manual only describes the LED signal statuses of the PROFINET IO modules. Information for the
frequency inverter LEDs (SK 200E) can be found in the relevant manual (BU0200).
The statuses indicated by the LED can be read out with the aid of a parameterisation tool from Getriebebau
Nord (NORDCON software ParameterBox) and also of course via the information parameter (P173) “Module
Status” (See Section 6.2.3 "BUS module information parameters, general (P17x)").
3.1.2.1 Module-specific displays
The status of the technology unit or the system bus is indicated by the LEDs DS and DE.
Table 5 LED display, DS and GB
BU 0290 GB-4312 Subject to technical amendments 21
Page 22
PROFINET bus module for NORD frequency inverters SK 200E
RUN
Green LED
Meaning
Flashing = 2.5 Hz (0.4 s cycle 0.2 s on / 0.2 s off)
OFF
Module not in operation
Device switched off or initialisation
Flashing
Waiting for AR (no connection to the PROFINET-IO controller)
no parameter communication
no process data communication
ON
AR established (a connection to the PROFINET IO controller has been set up)
Parameter communication active
Process data communication active
BF
Red LED
Meaning
Flashing = 2.5 Hz (0.4 s cycle 0.2 s on / 0.2 s off)
Double flash = 2 x brief flashes
Ethernet error
SK TU4-PNT is not (physically) connected to an Ethernet participant
Double Flash
Watchdog - Timeout
PROFINET or FI timeout (P151)
Link
Green LED
Activity
Yellow LED
Meaning
Off
Off
Port (RJ45 socket) is not connected to the PROFINET network
On
Off
Port (RJ45 socket is connected to the PROFINET network, but there
is no exchange of data
On
On / Flashing
Data exchange via PROFINET active
3.1.2.2 PROFINET displays
The communication status of the PROFINET IO module is indicated by the LEDs RUN and BF.
RUN = PROFINET IO bus status
BF = PROFINET IO bus fault
PROFINET IO status display
Table 6 RUN LED display
PROFINET IO error display
Table 7 BF LED display
The physical status of the field bus system (PROFINET IO) is indicated by the LINK /ACTIVITY LEDs, which
are located directly next to the RJ45 socket on the front panel.
Display of PROFINET Link and Active connections
Table 8 LED display, Link and Activity
22 Subject to technical amendments BU 0290 GB-4312
Page 23
3 Displays and diagnosis
Terminal/
Designation
Function
Data
Description /
wiring suggestion
Parameter
Diagnostic access / RJ12, RS485/RS232
1 RS485 A
Data cable RS485
Baud rate
9600…38400Baud
Termination
resistor R=120
to be set by customer at
the final participant.
Simultaneous use of several diagnostic sockets with several diagnostic tools may lead to
errors during communication. Therefore, only one diagnostic socket within a system bus
network should be used.
ParameterBox SK PAR-3H
3.2 RJ12 Diagnostic socket
All participants which are coupled via a common system bus (field bus module / frequency inverter (up to 4
devices)) can be read out and edited/parameterised via an RJ12 diagnostic socket. This can be either the
diagnostic socket of the frequency inverter or that of the BUS connection units. This provides users with a
convenient facility to perform diagnosis and parameterisation from a central point, without having to access the
particular frequency inverter at its location.
Table 9 RJ12 socket connections
The bus speed of the diagnostic interface is 38400 baud. Communication is carried out according to the USS
protocol.
The ParameterBox SK PAR-3H is available as a diagnostic tool.
The necessary connecting cables are included in the scope of
delivery of the ParameterBox. For a detailed description of use,
please refer to Manual BU0040.
BU 0290 GB-4312 Subject to technical amendments 23
Page 24
PROFINET bus module for NORD frequency inverters SK 200E
Terminal/
Designation
Function
Data
Description / wiring suggestion
Parameter
Accessory cable (optional) for PC connection
Adapter cable
RJ12 to SUB-D9
... for direct
connection to a PC
with NORD CON
software
Length 3m
Assignment RS 232
(RxD, TxD, GND)
Part. No. 278910240
TxD
RxT
GND
+24V
n.c.
n.c.
Assignment of SUB-D9 connector:
Pin2: RS232_TxD
Pin3: RS232_RxD
Pin5: GND
Device
External
technology unit
Frequency inverter
with address 32
(system bus)
Frequency inverter
with address 34
(system bus)
Frequency inverter
with address 36
(system bus)
Frequency inverter
with address 38
(system bus)
USS
address
30 1 2 3 4
RxD
GND
TxD
6 1 5
9
Underside of SK 200E
8x DIP switches
Alternatively, diagnosis can be performed via a Windows PC with the aid of NORD CON software (available
free of charge from www.nord.com). The necessary connection cable (RJ12 - SUB D9) is available from
Getriebebau Nord GmbH as part number 278910240. If necessary, an interface converter from SUB D9 to
USB2.0 is commercially available.
Table 10 Connection of RJ12 adapter cable to SUB-D9
No special settings are required to set up communication with the individual diagnostic tools.
The allocation of addresses is defined via the system bus addressing. The display of the diagnostic tool is
according to the following table, whereby the frequency inverter which is directly connected to the diagnostic
tool is automatically assigned the address “0”.
Note
Setting of the system bus address is carried out via two DIP
switches (DIP 1 and 2) on the underside of the SK 200E- frequency
inverter. For further details, please refer to the frequency inverter
manual (BU 0220). The address of the BUS module is defined as
“30”.
Fig. 3: DIP switches (system bus), frequency inverter
24 Subject to technical amendments BU 0290 GB-4312
Page 25
4 Commissioning
PROFINET
IO controller
TU4-PNT
TU4-PNT
TU4-PNT
PROFINET
IO controller
Switch
TU4-PNT
TU4-PNT
TU4-PNT
4 Commissioning
After installation of the components, and connection of the control and signal cables to the control terminal
bar of the module the module must be integrated into the field bus. Then the PROFINET IO module must be
implemented in the automation concept. In this section, the design of hardware in the SIMATIC Manager is
shown as an example. Finally, some parameters for the PROFINET connection in the frequency inverter must
be adapted.
4.1 Cabling
4.1.1 Topology
The SK TU4-PNT (PROFINET IO) modules can be connected to each other in star, tree, linear or ring
topologies.
Fig. 4: Example of PROFINET IO linear topology
Fig. 5: Example of PROFINET IO star topology with switch
4.1.2 EMC
If EMC measures are not in place, high-frequency interference which is mainly caused by switching processes
or lightning often causes electronic components in the bus participants to be faulty and error-free operation can
no longer be ensured.
Correct laying of the bus cable dampens the electrical influences which may occur in an industrial
environment. The following points must be observed:
Implement long connections between bus participants by the shortest possible distances.
Only use plugs with a metal housing.
For the production of bus cables lay the shielding on as wide an area of the plug as possible.
With the parallel installation of bus cables, a minimum distance of 20 cm should be maintained from other
cables carrying a voltage greater than 60V. In particular, this must be observed for cables to motors or
chopper resistors. This applies to lines laid both inside and outside of control cabinets.
The minimum distances for parallel installation may be reduced by shielding cables carrying voltage or by
means of earthed metal dividers in the cable ducts.
Connect each SK TU4 Ethernet module to the PE (PE terminal inside the module)
BU 0290 GB-4312 Subject to technical amendments 25
Page 26
PROFINET bus module for NORD frequency inverters SK 200E
4.2 Parameter settings of the frequency inverter
4.2.1 Parameter settings of the SK 200E frequency inverter
The following settings must be made on the SK 200E:
FI address (preferably set via DIP switches (DIP1 and 2)), if several FIs are connected to an
SK TU4-PNT (Gateway mode)
Set the control and setpoints (preferably via DIP switches (DIP3)), or via parameter:
Control via "system bus" P509 = 3
Setpoints via "system bus" P510 = 3 or 0 if P509 = 3
Setting of setpoints via P546 [-01] … [-03]
Setting of actual values via P543 [-01] … [-03]
A precise description of the parameters can be found in Section 6.1 of this supplementary manual or in the
SK 200E operating manual.
The parameters can be set with NORD parameterisation tools or via the PROFINET IO controller.
4.2.2 Parameter settings of the SK 500E frequency inverter
The following settings must be made on the SK 500E:
Control via "CANopen" P509 = 6
Setpoints via "CANopen" P510 = 6 or 0 if P509 = 6
Setting of setpoints via P546, P547 and P548 (SK 54xE and above: P546 [-01] … P546 [-05])
Setting of actual values via P543, P544 and P545 (SK 54xE and above: P543 [-01] … P543 [-05])
Setting of system bus monitoring via P513 = 0.6s
Setting of the baud rate via P514 = 5 (corresponds to 250kB)
Setting of the system bus addresses via P515 [-01] = 32, 34, 36 or 38
For a detailed description of the parameters, please refer to the SK 500E operating manual.
The parameters can be set with NORD parameterisation tools or via the PROFINET IO controller.
26 Subject to technical amendments BU 0290 GB-4312
Page 27
4 Commissioning
4.3 Configuration in the Bus system (example SIMATIC Manager)
In order to carry out planning with the SK TU4-PNT, first of all the GSDML file "GSDML-V2.2-NORD
DRIVESYSTEMS-TUXPNT-201xxxxx.xm" must be installed in the SIMATIC Manager. Select the relevant file
in the Hardware Configurator.
The current gsdml files are available on the NORD homepage under NORD - Dokumentation - Software -
NORDAC Options.
Fig. 6 Installation of the GSDML file in the SIMATIC Manager
After this, the SK TU4-PNT from NORD DRIVESYSTEMS can then be found in the hardware catalogue of the
SIMATIC Hardware Manager and can then be entered into the PROFINET system.
BU 0290 GB-4312 Subject to technical amendments 27
Page 28
PROFINET bus module for NORD frequency inverters SK 200E
Fig. 7 Hardware Catalogue: Module selection and specification of data format
The data format of the cyclical IO data is specified via the hardware catalogue. Up to 12 Bytes (=PPO6) are
transferred to the frequency inverter in a single cycle.
Fig. 8 Module properties
Properties such as the device number, device name and IP address are entered in the Properties dialogue of
the SIMATIC Manager.
28 Subject to technical amendments BU 0290 GB-4312
Page 29
5 PROFINET - Data transfer
Direction of
transmission
Transmitted data
( 4 Byte )
1st word
2nd word
... to SK TU4
Control word
Setpoint 1
... from the SK TU4
Status word
Actual
value 1
Direction of
transmission
Transmitted data
( 8 Byte )
1st word
2nd word
3rd word
4th word
... to SK TU4
Control word
Setpoint
1
Setpoint
2
Setpoint
3
... from the SK TU4
Status word
Actual
value 1
Actual
value 2
Actual
value 3
Direction of
transmission
Transmitted data
( 12 Byte )
1st word
2nd word
3rd word
4th word
5th word
6th word
... to SK TU4
Control word
Setpoint
1
Setpoint
2
Setpoint
3
Setpoint
4
Setpoint
5
... from the SK TU4
Status word
Actual
value 1
Actual
value 2
Actual
value 3
Actual
value 4
Actual
value 5
5 Communication
5.1 Process data
Control words and setpoints are transferred from the bus master / controller to the SK TU4-…bus module as
process data and in return, the status word and actual values are sent to the bus master / controller from the
FI. Transfer is carried out cyclically. The bus master / controller can access these process values directly, as
they are stored in the IO area.
The length and structure of the process data is specified via the PPO types during the planning of the
PROFINET network.
The allocation of the values transferred in the setpoint/actual value area of the FI is made via the parameters
P543 to P548 or P543 [-01]…[-05] and P546 [-01] …[-05]..
5.1.1 Process data structure
The structure of the process data is defined by the PPO type.
5.1.1.1 Pure process data communication
Table 11: PPO 3
Table 12: PPO 4
Table 13: PPO 6
BU 0290 GB-4312 Subject to technical amendments 29
Page 30
PROFINET bus module for NORD frequency inverters SK 200E
Direction of
transmission
Transmitted data
( 12 Byte )
1st word
2nd word
3rd word
4th word
5th word
6th word
... to SK TU4
Parameter
number and
order label
Parameter
index
Parameter
value HI
Parameter
value LO
Control word
Setpoint 1
... from the SK TU4
Parameter
number and
order label
Parameter
index
Parameter
value HI
Parameter
value LO
Status word
Actual value 1
Direction of
transmission
Transmitted data
( 16 Byte )
1st word
2nd word
3rd word
4th word
... to SK TU4
Parameter number and
order label
Parameter index
Parameter value HI
Parameter value LO
... from the SK TU4
Parameter number and
order label
Parameter index
Parameter value HI
Parameter value LO
Direction of
transmission
Transmitted data
( 16 Byte )
5th word
6th word
7th word
8th word
... to SK TU4
Control word
Setpoint 1
Setpoint 2
Setpoint 3
... from the SK TU4
Status word
Actual value 1
Actual value 2
Actual value 3
5.1.1.2 Process and parameter data communication
The exchange of process and parameter data is possible by selecting the PPO types 1 or 2.
Table 14: PPO 1
Table 15: PPO 2
30 Subject to technical amendments BU 0290 GB-4312
Page 31
5 PROFINET - Data transfer
Bit
Value
Meaning
Remarks
0 0 Not ready for operation
Reverse with the brake ramp, with disconnection from supply at f=0Hz (OFF1)
1
Ready for operation
Frequency inverter ready for operation
1
0
Disable voltage
Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is disabled. (OFF2)
1 Do not disable voltage
Operating condition OFF 2 is cancelled
2
0
Emergency Stop active
Quick stop with programmed quick stop time; with disconnection from supply
at f=0Hz; the FI switches to starting disabled condition (OFF3).
1 Emergency Stop not active
Operating condition OFF 3 is cancelled
3 0 Disable operation
Disable voltage; the inverter output voltage is switched off; the FI enters a
state where switching on is enabled.
1
Enable operation
The output voltage is enabled; ramp to the existing setpoint
4 0 Pulse not enabled
Ramp generator is set to zero; no disconnection from supply at f=0Hz; FI
remains in the operation enabled state.
1
Enable pulses
Ramp generator enabled
5 0 Ramp not enabled
The setpoint currently provided by the ramp generator is "frozen" (frequency is
maintained).
1
Enable ramp
Setpoint on ramp generator enabled.
6 0 Setpoint not enabled
Selected setpoint value is set to zero on the ramp generator.
1
Enable setpoint
Selected ramp generator setpoint is activated.
7 0 No acknowledgement
With the switch from 0 to 1, errors which are no longer active are
acknowledged.
1
Acknowledge error (01)
Note: If a digital input has been programmed for the "ack.fault" function, this
bit must not permanently be set to 1 via the bus (otherwise, flank evaluation
would be prevented).
8 0
1
Start function 480, 11
Bus bit 8 from the control word is set. Only for SK 2xxE and SK 5xxE. For
further details of the function please refer to parameter (P480).
9 0
1
Start function 480, 12
Bus bit 9 from the control word is set. Only for SK 2xxE and SK 5xxE. For
further details of the function please refer to parameter (P480).
10 0 Control data invalid
The transmitted process data is invalid.
1
Control data valid
Valid process data is transferred from the master.
Note: In order for the transmitted setpoint to be valid, this bit must also be set
(setting: interface), even if only setpoint values are transmitted via the bus.
11 0
1
Rotation right is on
Rotational direction right (priority) ON*
12 0
1
Rotation left is on
Rotational direction left ON*
13
0/1
Reserved
Reserved
14
0/1
Parameter set Bit 0 ON
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
15
0/1
Parameter set Bit 1 ON
5.1.2 Control word
The control word (STW) is the first word transferred to the frequency inverter in the process data area in an
order telegram. For example, a control word "Ready for switch-on" corresponds to 047E
command "Standby" should be the first command which is transferred to the inverter.
. In general the
(hex)
* If Bit 12=0, then "Direction of rotation right ON" applies
Table 16 Meaning of individual control word bits
BU 0290 GB-4312 Subject to technical amendments 31
Page 32
PROFINET bus module for NORD frequency inverters SK 200E
Bit
Value
Meaning
Remarks
0 0 Not ready to start
1
Ready to start
Initialisation completed, charging relay ON, output voltage disabled
1 0 Not ready for operation
Causes: ON command has not been activated, fault is signaled, OFF2 or OFF3
activated, starting disabled state activated
1
Ready for operation
ON command activated, no faults present. The inverter can be started with the
command ENABLE OPERATION
2 0 Operation not enabled
1
Operation enabled
The output voltage is enabled; ramp to the existing setpoint
3 0 No error
1
Fault
Drive fault resulting in stoppage; this state is changed to starting disabled after
the fault has been successfully acknowledged
4 0 Voltage not enabled
OFF2 command applied
1
Voltage enabled
5 0
Emergency stop
OFF3 command applied
1 No emergency stop
6 0 Starting not disabled
1
Starting disabled
Switches first to OFF1, then to ready-to-start status
7 0 No warning
1
Warning active
Drive operation continues, no acknowledgement necessary
8 0 Setpoint not reached
Actual value does not match the setpoint (with posicon: failure to reach setpoint
position)
1
Setpoint reached
Actual value matches required setpoint (setpoint has been reached)
(with posicon: setpoint has been reached)
9 0 Bus control not active
Guidance on local device has been activated
1
Bus controller active
The master has been requested to assume guidance.
10 0
1
Start function 481.9
Bus bit 10 from the status word is set. For further details of function, please refer
to parameter P481.
11 0
1
Rotation right is on
Inverter output voltage is turning right
12 0
1
Rotation left is on
Inverter output voltage is turning left
13 0
1
Start function 481.10
Bus bit 13 from the status word is set.For further details of function, please refer
to parameter P481.
14
0/1
Parameter set Bit 0 ON
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
15
0/1
Parameter set Bit 1 ON
5.1.3 Status word
In the inverter response telegram, in the area of the process data the status word (ZSW) is transferred as the
first word. The meaning of the individual bits deviate for some types of devices.
Table 17 Meaning of individual status word bits
32 Subject to technical amendments BU 0290 GB-4312
Page 33
5 PROFINET - Data transfer
Status
Bit 6
Switch-on
disable
Bit 5
Emergency
stop
Bit 4
Disable
voltage
Bit 3
Fault
Bit 2
Operation
enabled
Bit 1
Standby
Bit 0
Ready for
switch-on
Not ready to start
0 X X 0 0 0 0
Starting disabled
1 X X 0 0 0 0
Ready to start
0 1 1 0 0 0 1
Activated 0 1 1 0 0 1
1
Operation enabled
0 1 1 0 1 1 1
Fault 0 X X 1 0 0
0
Error active
0 X X 1 1 1 1
Emergency stop active
0 0 1 0 1 1 1
5.1.4 FI Status Machine
The frequency inverter passes through a status machine. The changes between various states are triggered
by the respective control commands in the process data control word. The actual status is returned in the
process data status word.
After switching on, the inverter is in switch-on disabled status. This status can only be ended by transmitting
the “Shut down (Off 1)” command.
The answer to a master telegram normally does not yet contain a reaction to the control command. The
controller must check the answers from the slaves as to whether the control command has been carried out.
Table 18 Codes for FI status
BU 0290 GB-4312 Subject to technical amendments 33
Page 34
PROFINET bus module for NORD frequency inverters SK 200E
The transfer of setpoint and actual values is carried out by three different methods, which will be explained
below.
Percentage transfer
The process value is transferred as a whole number with a value range of -32768 to 32767 (8000 hex to 7FFF
hex). The value 16384 (4000 hex) is equal to 100%. The value -16384 (C000 hex) is equal to -100%.
For frequencies, the 100% value corresponds to the FI parameter "Maximum Frequency" (P105) and for
currents, this is the FI parameter "Torque Current Limit" (P112) Frequencies and currents result from the
following formulae.
Value = the 16Bit actual or setpoint value transmitted via Ethernet
Formula 1 Formation of 16Bit setpoint/actual value
Binary transmission
Inputs and outputs as well as Digital In bits and Bus Out bits are evaluated for each bit.
Transmission of positions
In the FI, positions have a value range of +/- 50000,000 rotations. A motor rotation can be divided into a
maximum of 1000 steps. This scaling is independent of the encoder which is used.
The 32Bit value range is divided into a Low and a High word, so that 2 setpoint/actual values are required for
transmission.
Table 19 Depiction of 32Bit setpoint/actual values
It is also possible to only transmit the Low component of the position. This results in a limited value range from
+32,767 to -32,768 rotations. This value range can be extended with the aid of the gear ratio factor (P607 &
P608). However, it must be noted that there is an according reduction in the resolution.
BU 0290 GB-4312 Subject to technical amendments 35
Page 36
PROFINET bus module for NORD frequency inverters SK 200E
Control
word
Setpoint 1
Status
word
Actual
value 1
Explanation
- - -
- - -
0000h
0000h - - -
- - -
xx40h
0000h
The mains voltage is switched on at the FI
047Eh
0000h
xx31h
0000h
FI is set to "Standby" status
047Fh
2000h
xx37h
2000h
FI is set to "Operation enabled" status and controlled with a
50% setpoint.
The FI is enabled, the motor is supplied with current and rotates with a frequency of 25Hz.
0047Eh
2000h
xx31h
0000h
FI is set to "Standby" status, the motor runs up its
parameterised ramp to speed 0 and is switched off.
The FI is disabled again and the motor is without current.
047Fh
1000h
xx37h
1000h
FI is set to "Operation enabled" status and controlled with a
25% setpoint.
The FI is enabled, the motor is supplied with current and rotates with a frequency of 12.5Hz.
5.1.6 Example for switching the frequency inverter on and off
In this example, a frequency inverter will be operated with a setpoint (setpoint frequency) and an actual value
(actual frequency). The "Maximum Frequency" is 50Hz.
Parameter settings:
P105 = 500
P543 = 1
P546 = 1
Table 20 Example of setpoint specification
5.1.7 Timeout monitoring
The PROFINET IO data traffic can be monitored with a watchdog with the aid of the time set in parameter
P151. If no further cyclical data is sent from the PROFINET IO controller, a module error is detected and set in
the FI (E10.3).
Monitoring via the FI parameter P513 is also possible. This is triggered if the process data contact is
interrupted or the process data is transferred with an invalid control word (Bit10 in control word = 0). This
function is activated when the first valid process data telegram is received.
36 Subject to technical amendments BU 0290 GB-4312
Page 37
5 PROFINET - Data transfer
IO controller
Parameter
order
PROFINET Record
IO Device
Parameter
order
Parameter
response
Write Request
Slot 3
Read Request
Slot 3
Read Response (-)
Slot 3
Read Request
Slot 3
Write Response
Slot 3
Read Response (+)
Slot 3
Parameter
response
5.2 Parameter transfer
5.2.1 Function of PROFINET Records
The transfer of parameter data (Records) is performed acyclically. All parameters of the FI and the bus module
can be accessed. For this the parameters of the SK TU4-PNT are assigned to Slot 2 and the parameters of the
frequency inverters 1 ... 4 are assigned to Slot 3 ... 6.
The illustration below describes the function of Records
Fig. 10 Function of PROFINET Record
By means of a "Write Request" the data record is transferred to the IO device (SK TU4-PNT) as a
parameter order.
With "Write Response" the IO controller receives confirmation of the receipt of the message.
The IO controller requests a response from the SK TU4-PNT with "Read Request".
The SK TU4-PNT responds with a "Read Response (-)", if processing is not yet complete.
After processing of the parameter in the SK TU4-PNT the parameter order is concluded with the transfer
of the parameter response to the IO controller by means of "Read Response (+)".
BU 0290 GB-4312 Subject to technical amendments 37
Page 38
PROFINET bus module for NORD frequency inverters SK 200E
NOTE
The inverter parameters are mapped in the range 1000 to 1999, i.e. 1000 must be added to the
parameter number for parameterisation (e.g. (P508) - P1508).
Field
Data size
Explanation
Parameter number
and
order label
2 Bytes
FI or SK TU4 parameter
The parameter number is a 16 Bit value (+1000) and can be obtained from
the relevant operating manual for the frequency inverter or technology unit.
The order label is added to the parameter number. (upper Nibble)
Parameter index
2 Bytes
Parameter sub-index (see Section 5.2.3.2)
Parameter value
4 Bytes
New setting value (See Section 5.2.3.3).
Field
Data size
Explanation
Order reference
1 Byte
The order reference is transferred from the IO controller and is used for the
definitive allocation of the SK TU4-PNT response
Order label
1 Byte
Read / write parameter value etc. (see Section 5.2.3.1)
Axis
1 Byte
Access to SK TU4-PNT parameter or FI parameter
0 = SK TU4-PNT
1 = Frequency inverter 1
2 = Frequency inverter 2
3 = Frequency inverter 3
4 = Frequency inverter 4
Parameter number
2 Bytes
FI or SK TU4 parameter
The parameter number is a 16 Bit value (+1000) and can be obtained from
the relevant operating manual for the frequency inverter or technology unit.
Parameter index
2 Bytes
Parameter sub-index (see Section 5.2.3.2)
Parameter value
4 Bytes
New setting value (See Section 5.2.3.3).
5.2.2 Data records
5.2.2.1 Data records 100 to 104
The data records are written to Slot 0. The number of the data record determines the relevant target device.
For this:
DS 100 Access to the technology unit (parameter range 150…199)
DS 101 Access to the frequency inverter 1 (parameter range 0 … 999, except 150…199)…
DS 104 Access to the frequency inverter 4 (parameter range 0 … 999, except 150…199)
Table 21 Structure of data records 100 and 101
5.2.2.2 Data record 47
This data record is written to Slot 0 and is then assigned to the relevant device on the basis of the axis. The
format is compliant withe the ProfiDrive profile.
Table 22 Structure of data record 47
38 Subject to technical amendments BU 0290 GB-4312
Page 39
5 PROFINET - Data transfer
AK
Function
Response label positive
0
No order
0
1
Order parameter value
1 / 2
2
Change parameter value (word)
1
3
Change parameter value (double word)
2
4
Reserved
-
5
Reserved
-
6
Order parameter value (array)
4 / 5
7
Change parameter value (array word)
4 8 Change parameter value (array double word)
5 9 Order the number of array elements
6
10
Reserved
-
AK
Function
Response label positive
11
Change parameter value (array double word)
without writing into EEPROM
5
12
Change parameter value (array word)
without writing into EEPROM
4
13
Change parameter value (double word)
without writing into EEPROM
2
14
Change parameter value (word)
without writing into EEPROM
1
5.2.2.3 Transfer of data record via PPO 1 and PPO 2
PPO1 and PPO2 objects are supported in order to simplify the conversion of an existing PROFIBUS DP
system to a PROFINET IO system. In addition to the cyclical IO data, there are also the acyclical parameter
data (see Section 5.2.4.4).
5.2.3 Data format
5.2.3.1 Order label field
The following table lists all the orders which can be transferred from the PROFINET IO controller to the
frequency inverter. The right-hand column contains the response, which is normally sent (response label
positive). Only certain response labels are possible, depending on the order label. In case of error (AK
negative) the inverter will always supply the value 7 in the response label (AK) to the IO controller.
Table 23 Orders from the controller with the associated response label of the inverter
The following table lists all the orders which can be transferred from the controller to the frequency inverter or
the technology units. The right-hand column contains the response, which is normally sent (response label
positive). Only certain response labels are possible, depending on the order label. In case of error (AK
negative) the inverter always supplies the value 7 in the response label (AK) to the PROFINET IO controller.
Table 24 Orders from the controller with the associated response label of the inverter or technology unit
BU 0290 GB-4312 Subject to technical amendments 39
Page 40
PROFINET bus module for NORD frequency inverters SK 200E
AK
Function
0
No response
1
Transfer parameter value (word)
2
Transfer parameter value (double word)
4
Transfer parameter value (array word)
5
Transfer parameter value (array double word)
7
Order cannot be executed (with error number in PWE2)
No.
Meaning
0
Invalid parameter number
1
Parameter value cannot be changed
2
Lower or upper value limit exceeded
3
Incorrect sub-index
4
No array
5
Invalid data type (at present only for SK 700E)
6
Only resettable (only 0 may be written)
7
Description element cannot be changed
9
Description data not present
201
Invalid order element in the last order received
202
Internal response label cannot be depicted
NOTE
Both the order label and the response label are abbreviated as AK. Therefore, care must be
taken when reading or interpreting the order processing description in this section.
Table 25 Response labels - Meaning
In the response label "Order cannot be executed" (AK = 7), then an error message is added to the parameter
value (PWE2) of the inverter response. For the meanings of the values transferred, please refer to the
following table.
Table 26 Response labels – Explanation of error numbers for response label = 7
40 Subject to technical amendments BU 0290 GB-4312
Page 41
5 PROFINET - Data transfer
Array element
Parameter set
Index
5 (000101
BIN
)
2 (01
BIN
)
15
HEX
= 0001 0101
BIN
21 (010101
BIN
)
4 (11
BIN
)
57
HEX
= 0101 0111
BIN
5.2.3.2 Parameter index field
The structure and function of the parameter index depends on the type of parameter to be transferred. For
values which depend on the parameter set, the parameter set can be selected via Bits 8 and 9 of the Index (0
= parameter set 1, 1 = parameter set 2,...).
If the parameter to be processed is also an array parameter, then the sub-index of the required parameter can
additionally be accessed via Bit 10 to Bit 15 of the sub-index (0 = array element 1, 1 = array element 2,…):
Table 27 Example : Address formation for array elements or parameters depending on parameter sets
If a parameter is not dependent on the parameter set, then Bits 8 – 15 are used for the sub-index.
Please refer to the operating instructions for details of the structure of the individual parameters and which
values may be called up.
If the sub-index is used, nos. 6, 7, 8 or 11, 12 must be used as the order label (see Section ), in order for the
sub-index to be effective (refer to Section 5.2.3.1).
5.2.3.3 Parameter value field
For each parameter, the transfer of the parameter value is always as a word (16 Bit) or double word (32 Bit)
For negative values, the High bytes must be filled up with FF
hex
.
The parameter value is transferred as an integer value. For parameters with resolutions 0.1 or 0.01 the
parameter value must be multiplied by the inverse of the resolution.
Example: A run-up time of 99.99 seconds is to be set.
99.99s 99.99 * 1/99.99 = 99,99 * 100 = 9999.
Therefore the value 9999
= 270F
dec
must be transferred.
hex
BU 0290 GB-4312 Subject to technical amendments 41
Page 42
PROFINET bus module for NORD frequency inverters SK 200E
Field
Data size
Byte
Datum
Explanation
Order label
+
Parameter number
2 Byte
2
01h
+
4 92 h
_________
1 4 92 h
Request parameter value (Read) (refer to Section 5.2.3.1)
+
Parameter number P170 (170
dec
+1000
dec
) = 492 h
Parameter index
2 Bytes
3 4 00 h
00 h
Parameter sub-index (refer to Section 5.2.3.2)
Parameter value
4 Bytes
5
6
7
8
00 h
00 h
00 h
00 h
Setting value not set with read order
5.2.4 Examples
5.2.4.1 Reading of module parameter P170 Index 0 (actual error)
Data record 100 is used:
Table 28 Example telegram for reading parameter P170
S7 Code example:
CALL "WRREC" , DB53 WriteRequest
REQ :=#bStart
ID :=DW#16#7FC Diagnosis address
INDEX :=100 Data record 100
LEN :=8 Length: 8 Bytes
44 Subject to technical amendments BU 0290 GB-4312
Page 45
5 PROFINET - Data transfer
Word
1 2 3
4
Byte
0 1 2 3 4 5 6
7
Designation
PKE
PKE
IND
IND
PWE
PWE
PWE
PWE
Value
70
66
02
00
00
00
03
E8
Word
1 2 3
4
Byte
3 4 5 6 7 8 9
10
Designation
PKE
PKE
IND
IND
PWE
PWE
PWE
PWE
Value
40
66
02
00
00
00
03
E8
ATTENTION
If parameter changes are made (i.e. requests via the PKW area by the control master), care
must be taken that the maximum number of permissible writing cycles to the frequency
inverter EEPROM (100,000 cycles) is not exceeded. I.e. continuous cyclical writing must be
prevented.
For certain applications it is sufficient if the values are only saved in the RAM memory of the
frequency inverter. The corresponding setting is made via parameter (P560) "Save in
EEPROM".
5.2.4.4 Example of telegram structure with parameterisation via PPO1 or PPO2
When transferring parameter orders, it must be taken into account that the slave does not immediately respond
to orders in the parameter channel of the master telegram, but a positive response can be delayed by one or
more communication cycles. The master must therefore repeat the required order until the corresponding slave
response is received. PPO type 1 or PPO type 2 must be selected.
The parameter (P102) "run-up time" (PNU = 102
dec
/ 66
) is to be set to the value 10sec in parameter set 3.
hex
(Only the PKW channel is evaluated.)
As the acceleration time has an internal inverter resolution of 0.01sec, a parameter value of 10 / 0.01 = 1000
(3E8
) must be transferred.
hex
Procedure:
1) Specify order label ("Change parameter value (array word)" → AK = 7)
2) Select parameter (P 102
= P 66
dec
hex
)
3) Select parameter set 3 (IND = 02)
4) Set parameter word (1000
dec
/ 3E8
hex
)
5) Check response telegram (positive for array word = 4)
The telegram is composed as follows in hexadecimal notation:
When the order has been fully implemented by the inverter, it responds with (hexadecimal):
BU 0290 GB-4312 Subject to technical amendments 45
Page 46
PROFINET bus module for NORD frequency inverters SK 200E
0 = Monitoring OFF
1 = Auto, communication is only monitored if
an existing communication is interrupted.
If a module which was previously present
is not found when the network is switched
on, this does not result in an error.
Monitoring only becomes active when the
extension begins communication with the
FI.
2 = Monitoring active immediately; the FI
starts monitoring the corresponding
module immediately after it is switched
on. If the module is not detected on
switch-on, the FI remains in the status
"not ready for switch-on" for
5 seconds and then triggers an error
message.
6 Parameters
In order to enable communication via PROFINET IO, the frequency inverter and the PROFINET IO technology
unit must be parameterised accordingly.
6.1 Parameters for frequency inverter SK200E
The following list of parameters for the frequency inverter series SK 200E are directly relevant for the operation
of the frequency inverter via PROFINET IO. A complete list of parameters for the frequency inverter (SK 200E)
can be found in the relevant manual (BU0200).
6.1.1 Basic parameters (P1xx)
46 Subject to technical amendments BU 0290 GB-4312
In the SK 200E, up to 4 freely programmable digital inputs are available. The only restriction is
with the versions SK 215E and SK 235E. Here, the fourth digital input is always the input for the
function "Safe Stop".
... [-01] = Digital input 1 (DIN1), Enable right as factory setting,
control terminal 21
... [-02] = Digital input 2 (DIN2), Enable left as factory setting,
control terminal 22
… [-03] = Digital input 3 (DIN3), fixed frequency 1 (P465 [-01]) as factory setting,
control terminal 23
… [-04] = Digital input 4 (DIN4), fixed frequency 2 (P465 [-02]) as factory setting, not with SK
215/235E "Safe Stop", control terminal 24
Various functions can be programmed. For the complete list, please refer to the SK 200E
frequency inverter manual (BU0200).
NOTE:The additional digital inputs of the field bus group are managed via parameter
(P480).
Value
Function
Description
Signal
00
No function
Input switched off.
---
…
14 1
Remote control
With bus system control, low level switches the control to control
via control terminals.
High
…
1
Also effective for bus control (RS232, RS485, CANbus, CANopen, DeviceNet, Profibus, InterBus, AS-Interface)
The Bus I/O In Bits are perceived as digital inputs. They can be set to the same functions
(P420).
These I/O bits can also be used in combination with the AS Interface (SK 225E or SK 235E) or
the I/O extension (SK CU4-IOE or SK TU4-IOE).
… [-01] = Bus I/O In Bit 0
… [-02] = Bus I/O In Bit 1
… [-03] = Bus I/O In Bit 2
… [-04] = Bus I/O In Bit 3
… [-05] = Bus I/O In Bit 4
… [-06] = Bus I/O In Bit 5
… [-07] = Bus I/O In Bit 6
… [-08] = Bus I/O In Bit 7
… [-09] = Flag 1
… [-10] = Flag 2
… [-11] = Bit 8 BUS control word
… [-12] = Bit 9 BUS control word
The possible functions for the bus In bits can be found in the table of functions for the digital
inputs in parameter (P420).
6 Parameters
Excerpt...
BU 0290 GB-4312 Subject to technical amendments 47
Page 48
PROFINET bus module for NORD frequency inverters SK 200E
The bus I/O Out bits are perceived as multi-function relay outputs. They can be set to the same
functions (P434).
These I/O bits can also be used in combination with the AS Interface (SK 225E or SK 235E) or
the I/O extension (SK CU4-IOE or SK TU4-IOE).
… [-01] = Bus I/O Out Bit 0
… [-02] = Bus I/O Out Bit 1
… [-03] = Bus I/O Out Bit 2
… [-04] = Bus I/O Out Bit 3
… [-05] = Bus I/O Out Bit 4
… [-06] = Bus I/O Out Bit 5
… [-07] =Flag 1
… [-08] = Flag 2
… [-09] = Bit 10 BUS status word
… [-10] = Bit 13 BUS status word
The possible functions for the bus Out bits can be found in the table of functions for the relay
(P434)
P482... [-01]
...... [-10]
Norm. BusIO Out Bits
(Standardisation of bus I/O Out bits)
SK 2xxE
-400 … 400 %
{ all 100 }
Adjustment of the limit values of the bus Out bits. For a negative value, the output function will
be output negative.
Once the limit value is reached and positive values are delivered, the output produces a High
signal, for negative setting values a Low signal.
P483... [-01]
...... [-10]
Hyst. BusIO Out Bits
(Hysteresis of bus I/O Out bits)
SK 2xxE
S
1 … 100 %
{ all 10 }
Difference between switch-on and switch-off point to prevent oscillation of the output signal.
48 Subject to technical amendments BU 0290 GB-4312
Page 49
6.1.3 Supplementary parameters (P5xx)
Parameters
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P509
Source Control Word
(Source control word)
SK 2xxE
S
0 ... 4
{ 0 }
Selection of the interface via which the FI is controlled.
0 = Control terminals or keyboard control** with the SimpleBox (if (P510)=0), the
ParameterBox or via BUS I/O Bits.
1 = Only control terminals *, the FI can only be controlled via the digital and analog input
signals or via the bus I/O bits.
2 = USS *, the control signals (enable, rotation direction, etc.) are transferred via the RS485
interface, the setpoint via the analog input or the fixed frequencies.
3 = System bus *, the control signals (enable, direction of rotation, ...) are transferred via the
system bus (the field bus module and the frequency inverter communicate via the
system bus). I.e. the setting "3" - "System bus" must be selected in parameter (P509)
for control of the frequency inverter via the field bus.
4 = System bus broadcast *
*) Keyboard control (SimpleBox, ParameterBox, PotentiometerBox) is disabled,
parameterisation is still possible.
**) If the communication during keyboard control is interrupted (time out 0.5 sec), the
FI will disable without an error message.
NOTE:
For details of the optional bus systems, please refer to the relevant supplementary bus manuals
(BU02x0).
As an alternative to setting the parameter, System Bus can also be selected with DIP switch 3.
P510 ... [-01]
... [-02]
Setpoint source
(Setpoint source)
SK 2xxE
S
0 ... 4
{ [-01] = 0 }
{ [-02] = 0 }
Selection of the setpoint source to be parameterised.
… [-01] = Main setpoint source
… [-02] = Subsidiary setpoint source
Selection of the interface via which the FI receives the setpoint.
0 = Auto: The setpoint source is automatically
derived from the setting in the parameter P509
>Control word source<.
1 = Control terminals, digital and analog inputs
control the frequency, including fixed frequencies
2 = USS
3 = System bus
4 = System bus broadcast
6 Parameters
BU 0290 GB-4312 Subject to technical amendments 49
Page 50
PROFINET bus module for NORD frequency inverters SK 200E
Parameters
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P513
Telegram timeout
(Telegram timeout)
SK 2xxE
S
-0.1 / 0.0 /
0.1 ... 100.0 s
{ 0.0 }
If the frequency inverter is directly controlled via the CAN protocol or via RS485, this
communication path can be monitored via parameter (P513). Following receipt of a valid
telegram, the next one must arrive within the set period. Otherwise the FI reports an error and
switches off with the error message E010 >Bus Time Out<.
The inverter monitors the system bus communication via parameter (P120). Therefore
parameter (P513) must usually be left in the factory setting {0.0}. Parameter (P513) must only
be set to {-,0,1} if faults detected by the optional module (e.g. communication errors on the field
bus level) are not to result in the drive unit being switched off.
0.0 = Off: Monitoring is switched off.
-0.1 = No error: Even if the bus module detects an error, this does not cause the
frequency inverter to be switched off.
0.1… =On: Monitoring is activated.
Note: If a setting is made in this parameter in spite of this, values lower than 0.6s cause an error
in the FI due to the fixed definition of the system bus baud rate.
P514
CAN baud rate
(CAN baud rate (system bus))
SK 2xxE
S
0 ... 7
{ 5 }**
Setting of the transfer rate (transfer speed) via the system bus interface. All bus participants
must have the same baud rate setting.
5 = 10kBaud
6 = 20kBaud
7 = 50kBaud
8 = 100kBaud
9 = 125kBaud
10 = 250kBaud**
11 = 500kBaud
12 = 1Mbaud *
*) Reliable operation cannot be guaranteed
**) for communication with the bus module, the parameter must be left at the factory setting
(250kBaud) otherwise no communication is possible.
P515... [-01]
…... [-03]
CAN bus address
(CAN address(system bus))
SK 2xxE
S
0 ... 255 dec
{ all 32 dec}
or { all 20 hex}
Setting of the system bus address.
… [-01] = Receive address for system bus
… [-02] = Broadcast – Receive address for system bus (slave)
… [-03] = Broadcast – Transmit address for system bus (master)
NOTE:
If up to four SK 200E are to be linked via the system bus, the addresses must be set as follows
FI 1 = 32, FI 2 = 34, FI 3 = 36, FI 4 = 38.
The system bus addresses should be set via the DIP switches 1/2 (Fig. 3)
50 Subject to technical amendments BU 0290 GB-4312
The return value can be selected for bus actuation in this parameter.
NOTE:For further details, please refer to the description of (P418).
… [-01] = Actual bus value 1
… [-02] = Actual bus value 2
… [-03] = Actual bus value 3
Possible values which can be set:
0 = Off
1 = Actual frequency
2 = Actual speed
3 = Current
4 = Torque current (100% = P112)
5 = State of digital inputs and outputs2
6 = ... 7 Reserved
8 = Setpoint frequency
9 = Error number
10 = ... 11 Reserved
12 = Bus Out bits 0...7
13 = ... 16 Reserved
17 = Value analog input 1 (P400)
18 = Value analog input 2 (P400)
19 = Setpoint frequency master value (P503)
20 = Setpoint frequency after master value ramp
21 = Actual frequency without master value slip
22 = Speed from encoder
In this parameter, a function is allocated to the output setpoint during bus actuation.
NOTE:For further details please refer to the description of (P400).
… [-01] = Bus setpoint value 1
… [-02] = Bus setpoint value 2
… [-03] = Bus setpoint value 3
Possible values which can be set:
0 = Off
1 = Setpoint frequency (16 bit)
2 = Frequency addition
3 = Frequency subtraction
4 = Minimum frequency
5 = Maximum frequency
6 = PI process controller actual value
7 = PI process controller setpoint
8 = Actual frequency PID
9 = Actual PID frequency limited
10 = Actual PID frequency monitored
11 = Limiting torque current
12 = Torque current switch-off limit
13 = Limiting current
14 = Current switch-off limit
15 = Ramp time
16 = Lead torque (P214) multiplication
17 = Servo mode torque
18 = Curve travel calculator
19 = Digital In bits 0...7
20 = ...24 reserved for Posicon
2
Bit 0 = DigIn 1 (FU)
Bit 1 = DigIn 2 (FU)
Bit 2 = DigIn 3 (FU)
Bit 3 = DigIn 4 (FU)
Bit 4 = PTC input (FU)
Bit 5 = Reserved
Bit 6 = DigOut 3 (DO1, 1.SK…IOE)
Bit 7 = DigOut 4 (DO2, 1.SK…IOE)
Bit 8 = DigIn 5 (DI1, 1.SK…IOE)
Bit 9 = DigIn 6 (DI2, 1.SK…IOE)
Bit 10 = DigIn 7 (DI3, 1.SK…IOE)
Bit 11 = DigIn 8 (DI4, 1.SK…IOE)
Bit 12 = DigOut 1 (FU)
Bit 13 = mech. brake (FU)
Bit 14 = DigOut 2 (FI) (SK 2x0E)
Bit 15 = Reserved
The assignment of the digital inputs for P543 = 5
BU 0290 GB-4312 Subject to technical amendments 51
Page 52
PROFINET bus module for NORD frequency inverters SK 200E
Parameters
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P552… [-01]
… [-02]
CAN master cycle
(CAN master cycle time (system bus))
SK 2xxE
S
0 / 0.1 … 100.0 ms
{ 0 }
In this parameter, the cycle time for the system bus master mode and the CAN open encoder is
set (see P503/514/515):
… [01] = Cycle time for system bus master functions
… [02] = Cycle time for system absolute value encoder
With the setting 0 = "Auto" the default value (see table) is used.
According to the Baud rate set, there are different minimum values for the actual cycle time:
Baud rate
Minimum value tZ
Default system bus master
Default system bus abs.
10kBaud
10ms
50ms
20ms
20kBaud
10ms
25ms
20ms
50kBaud
5ms
10ms
10ms
100kBaud
2ms
5ms
5ms
125kBaud
2ms
5ms
5ms
250kBaud
1ms
5ms
2ms
500kBaud
1ms
5ms
2ms
1000kBaud:
1ms
5ms
2ms
P560
Parameter, saving mode
(Parameter, saving mode)
SK 2xxE
S
0 ... 1
{ 1 }
0 = Changes to the parameter settings are no longer saved on the EEPROM. Previously
saved settings remain stored, even if the FI is disconnected from the mains; however
new changes are not saved after a mains failure.
1 = All parameter changes are automatically written to the EEPROM and remain stored there
even if the FI is disconnected from the mains supply.
NOTE:If BUS communication is used to implement parameter changes, it must be
ensured that the maximum number of write cycles (100,000 x) in the EEPROM is
not exceeded.
52 Subject to technical amendments BU 0290 GB-4312
Page 53
6.1.4 Information parameters (P7xx)
Parameters
Setting value / Description / Note
Device
Supervisor
Parameter
set
P700[-01]
...[-03]
Present operating status
(Present operating status)
SK 2xxE
0.0 ... 25.4
Display of current messages for the present operating status of the frequency inverter such as
errors, warnings or the reason why switch-on is disabled. For details of the messages, see BU
0200.
[-01] = Present fault, shows the currently active (unacknowledged) fault.
[-02] = Present warning, indicates a current warning message.
[-03] = Reason for disabled starting, indicates the reason for an active start disable.
NOTE
SimpleBox/ControlBox: with the SimpleBox or ControlBox only warning messages and errors
can be displayed. Display of the messages is in encoded form.
ParameterBox: with the ParameterBox the messages are displayed in plain text. In addition, the
reason for a possible disabling of starting can also be displayed.
Bus: The display of bus-level error messages is made in decimal integer format. If this value is
divided by 10, the display corresponds to that in the SimpleBox or ControlBox.
Example: Display: 20 → Error number: 2.0
P701... [-01]
...... [-05]
Last fault 1..5
(Last fault 1 ... 5)
SK 2xxE
0.0 ... 25.4
This parameter stores the last 5 faults. Further details are described in the frequency inverter
manual (BU0200).
With the SimpleBox the corresponding memory location 1...5 (Array parameter), must be
selected and confirmed with the ENTER key in order to read the stored error code.
P740... [-01]
…
... [-13]
Process data bus In
(Process data bus in)
SK 2xxE
S
0000 ... FFFF (hex)
This parameter provides information about the actual control word (STW) and the setpoints
(SW1-3) that are transferred via the bus systems.
For values to be displayed, a bus system must be selected in P509.
The displayed value depicts all Bus In bit sources
linked with OR.
… [-06 ] = Parameter data In 1
… [-07 ] = Parameter data In 2
… [-08 ] = Parameter data In 3
… [-09 ] = Parameter data In 4
… [-10 ] = Parameter data In 5
Data during parameter transfer: Order label
(AK), Parameter number (PNU), Index (IND),
Parameter value (PWE 1/2)
Setpoint data from master function value
(Broadcast), if P509/510 = 4 (P502/P503)
6 Parameters
BU 0290 GB-4312 Subject to technical amendments 53
Page 54
PROFINET bus module for NORD frequency inverters SK 200E
Parameters
Setting value / Description / Note
Device
Supervisor
Parameter
set
P741... [-01]
...
... [-10]
Process data bus Out
(Process data bus out)
SK 2xxE
S
0000 ... FFFF (hex)
This parameter provides information about the actual status word and the actual values that are
transferred via the bus systems.
… [-01 ] = Status word
Status word
... [-02] = Actual value 1 (P543 [-01])
... [-03] = Actual value 2 (P543 [-02])
... [-04] = Actual value 3 (P543 [-03])
... [-05] = Bus I/O Out Bit (P481)
The displayed value depicts all bus Out bit sources
linked with OR.
… [-06 ] = Parameter data Out 1
… [-07 ] = Parameter data Out 2
… [-08 ] = Parameter data Out 3
… [-09 ] = Parameter data Out 4
… [-10 ] = Parameter data Out 5
Data during parameter transfer.
P748
CANopen status
(CANopen status (system bus status))
SK 2xxE
0000 ... FFFF (hex)
or
0 ... 65535 (dec)
Shows the status of the system bus.
Bit 0:
Bit 1:
Bit 2:
Bit 3:
Bit 4:
Bit 5:
Bit 6:
Bit 7:
Bit 8:
Bit 9:
Bit 10:
24V Bus supply voltage
CANbus in "Bus Warning" status
CANbus in "Bus Off" status
Bus module is online
Additional module 1 is online
Additional module 2 is online
The protocol of the CAN module is 0 = CAN / 1 = CANopen
Vacant
"Bootup Message" sent
CANopen NMT State
CANopen NMT State
CANopen NMT State
Bit 10
Bit 9
Stopped
Pre- Operational
Operational
0
0
1
0
1
0
P749
Status of DIP switches
(Status of DIP switches)
SK 2xxE
0000 ... 00FF (hex)
or
0 ... 255 (dec)
This parameter shows the current setting of the FI (Fig. 3) DIP switch.
54 Subject to technical amendments BU 0290 GB-4312
Page 55
Parameters
{Factory setting}
Setting value / Description / Note
Device
Parameter
type
P150
Set relays
(Set relays / digital outputs)
SK TU4-PNT
8 bit
0 ... 4
{ 0 }
0 = Via bus
1 = Outputs OFF
2 = Output 1 ON (DO1)
3 = Output 2 ON (DO2)
4 = Outputs 1 and 2 ON
P151
Timeout for external bus
(Timeout for external bus)
SK TU4-PNT
16 bit
0 ... 32767 ms
{ 0 }
Monitoring function of the active bus technology unit. Following receipt of a valid telegram, the
next one must arrive within the set period. Otherwise the inverter reports an error and switches
off with the error message E010 / E10.2 >Bus Time Out< >Bus Time Out<.
0 = OFF: Monitoring is switched off.
Behaviour is identical to parameter (P513) telegram timeout for SK 200E.
P152
Factory setting
(Load factory setting)
SK TU4-PNT
8 bit
0 ... 1
{ 0 }
By selecting the appropriate value and confirming it with the ENTER key, the selected
parameter range is entered in the factory setting. Once the setting has been made, the value of
the parameter returns automatically to 0.
0 = No change: Does not change the parameterisation.
1 = Load factory settings: The complete parameterisation of the FI reverts to the factory
setting. All originally parameterised data are lost.
P153… [-01]
… [-02]
Min. system bus cycle
(Minimum system bus cycle time)
SK TU4-PNT
16 bit
0 ... 250 ms
{ [-01] = 10 }
{ [-02] = 05 }
In order to reduce the bus load, an inhibit time for the system bus can be set in this parameter.
… [-01] = SDO Inhibit time
… [-02] = PDO Inhibit time
P154… [-01]
… [-02]
TB-IO access
(Access to technology unit IOs)
SK TU4-PNT
8 bit
0 ... 5
{ [-01] = 0 }
{ [-02] = 0 }
The writing and reading rights of the connected frequency inverter to the inputs and outputs of
the technology unit are assigned in this parameter.
… [-01 ] = Inputs
… [-02] = Outputs
0 = Off, no effect
1 = Broadcast, read all FIs
2 = FI 1, reads and writes to the IOs
3 = FI 2, reads and writes to the IOs
4 = FI 3, reads and writes to the IOs
5 = FI 4, reads and writes to the IOs
6.2 Parameterisation of the bus module (SK TU4-…)
The following parameters affect the bus modules.
6.2.1 BUS module standard parameters (P15x)
6 Parameters
BU 0290 GB-4312 Subject to technical amendments 55
Page 56
PROFINET bus module for NORD frequency inverters SK 200E
Parameterised IP address consisting of four bytes. In case of a change to the IP address (e.g.
with NORD CON), this is only saved by writing it to Index 4.
NB: Saving is prevented if the IP address which is entered does not correspond to the
convention. If there are contradictions between the IP address and the mask (P161), the mask
is corrected automatically.
Deletion of the IP settings (IP+sub-net mask) is performed by entering IP 0.0.0.0.
Parameterised IP mask consisting of four bytes. In case of a change to the IP mask (e.g. with
NORD CON), this is only saved by writing it to Index 4.
NB: Saving is prevented if the entered IP address is inconsistent with the IP address.
Example:
IP-Add: 192.168.20.200, IP mask: 255.255.255.0 Correct
IP-Add: 192.168.20.200, IP mask: 255.0.0.0 Error
P162
Device name
(Device name)
SK TU4-PNT
8 bit
45 ... 122
The device name can be queried or changed with this parameter. Character strings with a
length of up to 240 characters are possible. Characters 45 to 122 from the ASCII Code can be
used.
The name is saved after the entry of a 0 at the end of the character string.
P163… [-01]
…… [-07]
Alarm test
(Test alarm)
SK TU4-PNT
8 bit
0 ... 255
all { 0 }
This parameter is used, e.g to trigger a diagnostic alarm from a slot during commissioning. A
frequency inverter error can be simulated by entering the value of the error (e.g. link circuit
overvoltage = E005.0 Value 50) in the slot of the relevant inverter (e.g.: Slot 3). An
"incoming" alarm is triggered. If the value is reset to 0 the alarm is "outgoing".
Example:
Trigger alarm with error 5.0 on Slot 2:
P163[-04] = 50 ChannelErrorType= 0x100+50=0x132
6.2.2 Parameters specific to PROFINET IO modules (P16x)
Access: Read / Write
56 Subject to technical amendments BU 0290 GB-4312
Page 57
6.2.3 BUS module information parameters, general (P17x)
Parameters
Setting value / Description / Note
Device
Parameter
type
P170... [-01]
... [-02]
Present error
(Present fault / error)
SK TU4-PNT
16 bit
0 ... 9999
Actual error present. Further details in Section 7.2 "Error messages".
… [-01 ] = Current module error
… [-02 ] = Last module error
Possible values:
1000 = EEPROM error
1010 = System bus 24V missing
1020 = System bus timeout (see time in P151)
1030 = System bus OFF
Specific to PROFINET IO)
5500 = No Ethernet connection
5501 = Hardware error
P171 ... [-01]
...
... [-03]
Software version
(Software version / revision)
SK TU4-PNT
16 bit
0,0 ... 9999.9
This parameter shows the software and revision numbers in the module. Array 03 provides
information about any special versions of the hardware or software A zero stands for the
standard version.
… [-01] = Software version
… [-02] = Software revision
… [-03] = Special version
P172
Configuration
(Configuration)
SK TU4-PNT
16 bit
0 ... 3
The version can be queried in this parameter.
Possible displayed values:
0 = Internal module (SK CU4)
1 = External module (SK TU4)
2 = Bus TB via SPI (SK TU3)
6 Parameters
BU 0290 GB-4312 Subject to technical amendments 57
Page 58
PROFINET bus module for NORD frequency inverters SK 200E
Parameters
Setting value / Description / Note
Device
Parameter
type
P173
Module status
(Module status)
SK TU4-PNT
16 bit
0 ... FFFF (hex)
Explanation of bits:
Bit 0 = Initialisation
Bit 1 = AR installed
Bit 2 = Reserved
Bit 3 = Timeout (P151 / P513)
Bit 4 = Reserved
Bit 5 = Ethernet connection
Bit 6 = System bus “BUS WARNING”
Bit 7 = System bus "BUS OFF"
Bit 8 = Status FI 1
Bit 9 = Status FI 1
Bit 10= Status FI 2
Bit 11= Status FI 2
Bit 12= Status FI 3
Bit 13= Status FI 3
Bit 14= Status FI 4
Bit 15= Status FI 4
Status for FI x:
Bit High Bit Low status
0 0 FI is offline
0 1 unknown FI
1 0 FI is online
1 1 FI missing or switched off
P174
Status of digital input
(Status of digital inputs)
SK TU4-PNT
8 bit
0 ... 255
dec
(00000000 ... 11111111)
bin
Instantaneous view of input level logic.
Possible displayed values:
Bit 0= Input 1 ((DIN1) (of BUS module))
Bit 1= Input 2 ((DIN2) (of BUS module))
Bit 2= Input 3 ((DIN3) (of BUS module))
Bit 3= Input 4 ((DIN4) (of BUS module))
Bit 4= Input 5 ((DIN5) (of BUS module))
Bit 5= Input 6 ((DIN6) (of BUS module))
Bit 6= Input 7 ((DIN7) (of BUS module))
Bit 7= Input 8 ((DIN8) (of BUS module))
P175
Relay status
(Status of relays / Digital outputs)
SK TU4-PNT
8 bit
0 ... 3
dec
(00 ... 11)
bin
Instantaneous view of output level logic.
Possible displayed values:
Bit 0= Output 1 ((DO1) (of BUS module))
Bit 1= Output 2 ((DO2) (of BUS module))
58 Subject to technical amendments BU 0290 GB-4312
Page 59
6 Parameters
Parameters
Setting value / Description / Note
Device
Parameter
type
P176 ... [-01]
...
... [-25]
Process data Bus In
(process data, Bus In)
SK TU4-PNT
16 bit
-32768 ... 32767
Bus data received from PROFINET IO controller
… [-01] = Bus module outputs
… [-02] = Control word FI 1
… [-03] = Setpoint 1 for FI 1
… [-04] = Setpoint 2 for FI 1
… [-05] = Setpoint 3 for FI 1
… [-06] = Setpoint 4 for FI 1
… [-07] = Setpoint 5 for FI 1
… [-08] = Control word FI 2
… [-09] = Setpoint 1 for FI 2
… [-10] = Setpoint 2 for FI 2
… [-11] = Setpoint 3 for FI 2
… [-12] = Setpoint 4 for FI 2
… [-13] = Setpoint 5 for FI 2
…
… [-25] = Setpoint 5 for FI 4
P177 ... [-01]
...
... [-25]
Process data Bus Out
(Process data Bus Out)
SK TU4-PNT
16 bit
-32768 ... 32767
Bus data sent from PROFINET IO controller
… [-01] = Bus module inputs
… [-02] = Status word FI 1
… [-03] = Actual value 1 for FI 1
… [-04] = Actual value 2 for FI 1
… [-05] = Actual value 3 for FI 1
… [-06] = Actual value 4 for FI 1
… [-07] = Actual value 5 for FI 1
… [-10] = Status word FI 2
… [-11] = Actual value 1 for FI 2
… [-12] = Actual value 2 for FI 2
… [-13] = Actual value 3 for FI 2
… [-14] = Actual value 4 for FI 2
… [-15] = Actual value 5 for FI 2
…
… [-25] = Actual value 5 for FI 5
BU 0290 GB-4312 Subject to technical amendments 59
Page 60
PROFINET bus module for NORD frequency inverters SK 200E
Parameters
Setting value / Description / Note
Device
Parameter
type
P180… [-01]
…… [-07]
PPO TYPE
(PPO Type / Module ID)
SK TU4-PNT
8 bit
0 ... 7
The module ID (see gsdml file) for the slots can be queried with this parameter. Caution:
meaningful values can only be read out with an existing AR.
Possible values:
0 = Empty slot
1 = Reserved slot
2 = DIG-IO, Process data for the TU
3 = PPO3, Process data for the FI
4 = PPO4, Process data for the FI
5 = PPO6, Process data for the FI
6 = PPO1, Process or parameter data for the FI
7 = PPO2, Process or parameter data for the FI
The Ethernet address (MAC address) can be read out from this parameter.
[-01] … [-03] PROFINET identification
[-04] … [-06] Manufacturer's address range (NORD: from 03.60.00)
Example: (00:0E:CF:03:60:00)
P185… [-01]
…… [-04]
Present IP address
(Present IP address)
SK TU4-PNT
8 bit
0 ... 255
The present IP address can be read out from this parameter.
This may deviate from the saved address (P160) if the PROFINET IO controller reconfigures the
parameter.
[-01] … [-04] IP address
P186… [-01]
…… [-04]
Present IP sub-net mask
(Present IP sub-net mask)
SK TU4-PNT
8 bit
0 ... 255
The present IP mask can be read out from this parameter.
This may deviate from the saved mask (P161) if the PROFINET IO controller reconfigures the
parameter.
[-01] … [-04] IP mask
NOTE
When activated, the functions Disable Current, Quick Stop, Remote Control and
Acknowledge Error, are available at the (local) terminals. To operate the drive, a High
signal must be present on the digital inputs being used before the drive can be enabled.
6.2.4 Module information parameters specific to the bus (P18x)
Access: Read only
60 Subject to technical amendments BU 0290 GB-4312
Page 61
7 Error monitoring and error messages
NOTE
An error relating to the PROFINET IO communication is only displayed (P170 [-01]) for as
long as it is active. Once the error is remedied, the message is automatically deleted and is
archived in parameter (P170 [-02]) as the last error message.
If the power supply is interrupted before the error is remedied, the error is lost, i.e. it is not
archived.
NOTE
The display of a bus error is shown in the operating display of the SimpleBox SK CSX-3H by
means of the error group number E1000. In order to obtain the precise error number, the
module information parameter (P170) must be selected. The current error is shown in Array
[-01] of this parameter, the last error is stored in Array [-02].
7 Error monitoring and error messages
7.1 Error monitoring
The majority of bus module and frequency inverter functions and operating data are continuously monitored
and simultaneously compared with limiting values. If a deviation is detected, the bus module or inverter reacts
with a warning or an error message.
For detailed information, please refer to the relevant main manual of the frequency inverter.
Errors cause the frequency inverters to switch off, in order to prevent a device fault.
The following options are available to reset a fault (acknowledge):
1. Switching the mains off and on again,
2. by means of a correspondingly programmed digital input
(SK 200E: (P420) [-…], function {12} or
SK 500E: (P420 ... P425), function {12}),
3. by switching off the “enable” on the frequency inverter
(if no digital input is programmed for acknowledgement),
4. by Bus acknowledgement or
5. by parameter (P506), "automatic error acknowledgement".
Visualisation of the inverter error codes is made via the frequency inverter (see relevant manual).
Errors which are attributable to bus operation are visualised via the bus module. The precise error message is
displayed in parameter (P170).
7.1.1 Error monitoring details
Various monitoring functions are available to ensure reliable bus operation.
Timeout monitoring at the field bus level (PROFINET IO) by means of
o PROFINET watchdogs
o Parameter (P151)
Timeout monitoring at system bus level
o Parameter (P120) or (P513)
Function monitoring within the bus module
o Parameter (P170)
With the aid of the "Timeout Monitoring" communication problems are detected, which are either related to
general functionalities ("No bus communication") or are related to special modules ("Failure of a participant").
General process data monitoring of a Technology Unit (SK xU4-…)
The parameter (P151) "Timeout external bus" generally monitors the existence of bus communication. If no
process data is received within the parameterised monitoring time (The content of the process data is
irrelevant) the subscriber assumes that the bus communication to this subscriber is generally faulty and reports
an error.
BU 0290 GB-4312 Subject to technical amendments 61
Page 62
PROFINET bus module for NORD frequency inverters SK 200E
Format
Error number
Alarm code
Alarm number
Decimal
10.3 = 103
dec
256
dec
103 + 256 = 359
dec
Hexadecimal
= 67
hex
100
hex
= 167
hex
This error is also triggered if process data with an invalid control word (Bit 10 in control word = 0) is received.
This function is activated when the first valid process data telegram is received.
General monitoring of frequency inverter process data
SK 500E series frequency inverters offer the facility for monitoring the active bus interface by means of the
parameter (P513) "Telegram timeout". If the frequency inverter does not receive a telegram within the time
entered here, it assumes that there is a general fault with the bus communication and reports an error.
Note: With SK 200E series frequency inverters, the function of this parameter is implemented by parameter
(P120). Communication errors are therefore reported via the bus module. Parameterisation of (P513) is
therefore not necessary. (P513) should be left at the factory setting.
Option monitoring
With the parameter (P120) "Option monitoring", SK 200E series frequency inverters provide the facility for
monitoring connected technology units (SK xU4-…) with regard to their current functional status. Generally,
this function corresponds to monitoring via parameter (P513). This parameter (P513) should therefore be left
at the factory setting.
7.1.2 PROFINET error monitoring
An error in the frequency inverter (P700) or in the SK TU4-PNT (P170) results in a diagnostic alarm which is
transmitted to the control unit as an "incoming event". The error value is coded as follows:
Error number (Value from P700 or P170) + 100 h = Alarm number of the diagnostic alarm
Example:
During operation, the error E10.3 (P700 Index 1 = 103) = Timeout occurs via the P151 monitoring. The
SK TU4-PNT sends a diagnostic alarm with the value 359 (= 100h + 103 = 256 + 103 = 359) to the control unit.
If the error is no longer present a diagnostic alarm ("incident removed") is sent, which resets the error in the
control unit.
With the aid of parameter P163, e.g. during commissioning, various alarms can be sent in order to test the
operation of the control program.
Loss or switch-off of an inverter connected via the system bus:
On loss of connection of the SK TU4-PNT to an FU connected via the system bus an alarm with the error
number 1000 (in the diagnostic buffer of the IO controller --> 256+1000=1256) is sent. This error is not saved
in P170 and is only intended to give information about the loss of the FU as a switch-off of the connected FU
may be part of the application.
62 Subject to technical amendments BU 0290 GB-4312
Page 63
7 Error monitoring and error messages
Error number
Display in the
SimpleBox
Fault
Text in the ParameterBox
Cause
Remedy
Group
Details in
P700 / P701
E010
10.0
Connection error
Contact to SK TU4-PNT interrupted. (SK 500E)
10.3
Timeout via (P151)
Telegram transfer is faulty.
Check watchdog time (P151)
Check physical bus connections
Contains cyclic telegrams
10.4
Hardware error, IOs
An error has occurred at the IO interfaces
Check connections (short circuit)
Restart the module
10.5
General PROFINET
configuration error
A general configuration error has occurred.
No Ethernet connection.
10.8
Timeout - connection error
The connection between the FI and the SK TU4-PNT had a
timeout
10.9
Module missing / P120
The module entered in parameter (P120) is not available.
7.2 Error messages
7.2.1 Table of possible error messages (caused by the bus) in the frequency inverter
The following error messages concern bus-related messages which are indicated on the frequency inverter.
A complete list of error messages for the frequency inverter (SK 200E) can be found in the relevant manual
(BU0200).
BU 0290 GB-4312 Subject to technical amendments 63
Page 64
PROFINET bus module for NORD frequency inverters SK 200E
Error number
Fault
Text in the ParameterBox
Cause
Remedy
Group
Details in
P170
E1000
1000
EEPROM error
Module faulty
1010
System bus 24V missing
Check connections and supply cables
Ensure 24V voltage supply
1020
System bus timeout
Check time set in parameter (P151).
Telegram transfer is faulty.
Check external connection
Check bus protocol program process.
Check bus master.
1030
System bus OFF
Check connections and supply cables
Ensure 24V voltage supply
Check bus master.
5500
No Ethernet
No Ethernet connection
Connect module to Ethernet
5501
Hardware error, IO chip
EMC fault or IO chip defective
Check connections, shielding, cable run
Restart module
7.2.2 Table of possible error messages in the bus module
The following error messages concern bus-related messages, which are indicated on the PROFINET module
SK TU4-PNT(-…)) All SK TU4-PNT error messages are displayed in parameter (P170) of the bus module and
trigger an error in the connected FI. This is permanently stored in the FI error statistics. The error messages in
the bus module memory (P170) parameter are lost when the 24V supply voltage is switched off.
64 Subject to technical amendments BU 0290 GB-4312
Page 65
8 Additional information
Fixed cable
Freely laid cable
Bending radius of cable
Minimum radius
5 x cable diameter
Minimum radius
10 x cable diameter
Correct
Incorrect
NOTE
If earthing potential values are different, transient current may flow through shielding which
is connected on both sides. This may be a danger to electronic components. Differences in
potential must be reduced by means of adequate potential equalisation.
8 Additional information
8.1 Bus Configuration
In an industrial environment the correct installation of the bus system is particularly
important in order to reduce potential interference. The following points are designed to
help prevent interference and problems right from the start. The installation guidelines are
not complete and applicable safety and accident prevention guidelines must be complied
with.
8.1.1 Layout of the PROFINET IO bus cable
A PROFINET IO network can consist of an almost unlimited number of participants. In can be set up as a
linear structure (NORD standard), as a tree structure, or as a ring system. There are practically no restrictions
to the extent of the network, as each participant functions as a repeater and amplifies the bus signal. Only the
distance between neighbouring participants is limited to 100m.
8.1.2 Cable material
Copper cables should be used for the bus. The cables must at least fulfil the Ethernet standard CAT-5.
8.1.3 Cable layout and shielding (EMC measures)
If EMC measures are not in place, high-frequency interference which is mainly caused by switching processes
or lightning often causes electronic components in the bus participants to be faulty and error-free operation can
no longer be ensured.
Correct laying of the bus cable dampens the electrical influences which may occur in an industrial
environment. The following points must be observed:
Implement long connections between bus participants by the shortest possible distances.
Connect each SK TU4-PNT module to the PE.
Only use plugs with a metal housing.
For the production of PROFINET cables, lay the shielding on as wide an area of the plug as possible.
With the parallel installation of bus cables, a minimum distance of 20 cm should be maintained from other
cables carrying a voltage greater than 60V. In particular, this must be observed especially for cables to
motors or chopper resistors. This applies to cables laid both inside and outside of control cabinets.
The minimum distances for parallel installation may be reduced by shielding cables carrying voltage or by
means of earthed metal dividers in the cable ducts.
Special attention should be paid to bending radii:
BU 0290 GB-4312 Subject to technical amendments 65
Page 66
PROFINET bus module for NORD frequency inverters SK 200E
Nowadays, field bus systems are a normal part of plant technology. The sensitivity of these systems to
electromagnetic interference (EMC) means that it is essential to protect bus systems from outside interference
by means of uninterrupted or complete screening. Therefore the use of shielded cables and metal screw
couplings or plug connectors has become standard. Assuming correct installation (e.g.: 360° screen
connection - including at contact points, compliance with tightening torques, bending radii, IP protection
classes (≥IP66),…), the operational reliability of the field bus system can be optimised.
The EMC effect of a cable shield is largely dependent on its contacts to the housing and its earthing on one or
both ends. The shielding effect of a housing must not be influenced by incoming or outgoing screened cables.
It is recommended that the shield is exposed directly at the point of entry and connection of the cable gland
with the reference potential surface and the use of an EMC cable. At the same time this opening in the housing
is "sealed" against the electromagnetic field. The connection from the cable shield to the housing must have a
DC and and inductive resistance which is as low as possible. This depends on the frequency. This low contact
resistance is achieved by the use of a ring-shaped 360° contacting of the cable shielding and short
connections to the housing via the connecting thread.
8.2.1 Fixed connection (cable gland)
Metallic EMC cable glands with a shielding concept should be used to minimise EMC problems.
These special M16 x 1.5 EMC cable glands must be fitted in the relevant connection unit (SK TI4-…(-BUS)) of
the frequency inverter or the PROFINET IO module.
Assembly
For the M16 x 1.5 EMC cable gland, 5 mm of the shielding of the cable /conductor is exposed and slightly
spread out. The insulating foil of the Profibus cable must be cut off and must not be folded back.
Function
When the pressure screw is tightened, the sealing insert presses the shielding mesh onto the cone of the
earthing insert. The entire circumference (360°) of the shielding mesh is contacted. The mesh ends in the
cable gland. This produces a large area, low resistance conductive connection between the shield, the
earthing insert and the screw fitting and the housing.
For further information regarding the correct installation of EMC cable glands, please refer to the relevant
manufacturer´s data sheets.
66 Subject to technical amendments BU 0290 GB-4312
Page 67
8 Additional information
Flanged coupling
Flanged plug
connector
Designation
A coding
B coding
D coding
Example
Connector (socket)
Format
M12
M12
M12
Coupling version
with coding groove
with coding pin
with coding pin and
groove
Plug connector version
with coding pin
with coding groove
with coding groove and
pin
Field of use
System bus
CANopen
DeviceNet
24V supply
Sensors and actuators
PROFIBUS DP
EtherCAT
PROFINET
EtherNet/IP
POWERLINK
8.2.2 Connection with M12 round plug connectors
In order to implement detachable connections, the cable connections for the system bus
and for sensors and actuators, as well as for the 24V- supply voltage can be designed with
plug-in connectors.
Here, freely adjustable M12 flanged connectors with metric M16 x 1.5 threads should be
used for installation in the relevant housing (SK TI4-…(-BUS)).
This allows the use of angled or straight M12 round plug connectors for the cable
connection.
If required, Getriebebau Nord GmbH can equip the device to be delivered accordingly, or
can enclose the required plug with the delivery.
EMC compatible assembly is carried out in the same manner as for the assembly of the
cable glands (Section 8.2.1 "Fixed connection (cable gland)").
8.2.3 Round plug connectors
Getriebebau Nord GmbH offers a selection of suitable plug connectors and couplings, which can be installed in
the connection units of the frequency inverters or the field bus module, or enclosed with the delivery as
required. The corresponding plug connectors, couplings and Y connectors are also commercially available.
However, a limited selection can also be obtained from Getriebebau NORD GmbH.
Coding
Round plug connectors are coded. Coding is by means of a pin or a groove on the contact base. The most
common codings are the so-called A and B coding. This serves to protect against incorrect coupling of the
various field bus systems.
BU 0290 GB-4312 Subject to technical amendments 67
Page 68
PROFINET bus module for NORD frequency inverters SK 200E
System components
Description
Data
System bus
SK TIE4-M12-SYSS
Part No. 275274506 (IP67)
The protection class is only valid
when screwed together!
M12 flanged plug
to connect theincoming system bus cable to the
technology unit
M12 round plug connector
A coded, 5 pin, adjustable
direction
PIN 1
not used
PIN 2
+24V
brown
PIN 3
GND
blue
PIN 4
Sys-H
black
PIN 5
Sys-L
grey
Plastic body and screw cap in
light blue
SK TIE4-M12-SYSM
Part No. 275274505 (IP67)
The protection class is only valid
when screwed together!
M12 flanged plug
to connect theoutgoing system bus cable to the
technology unit
M12 round plug connector
A coded, 5 pin, adjustable
direction
PIN 1
not used
PIN 2
+24V
brown
PIN 3
GND
blue
PIN 4
Sys-H
black
PIN 5
Sys-L
grey
Plastic body and screw cap in
light blue
External voltage supply
SK TIE4-M12-POW
Part No. 275274507 (IP67)
The protection class is only valid
when screwed together!
M12 flanged plug
to connect a24V- supply to the technology unit
M12 round plug connector
A coded, 5 pin, adjustable
direction
PIN 1
+24V (out)
brown
PIN 2
not used
PIN 3
GND
blue
PIN 4
not used
PIN 5
not used
Plastic body and screw cap in
black
Sensors and actuators
SK TIE4-M12-INI
Part No. 275274503 (IP67)
The protection class is only valid
when screwed together!
M12 flanged plug
to connect sensors and actuators to the technology
unit
M12 round plug connector
A coded, 5 pin, adjustable
direction
PIN 1
+24V (out)
brown
PIN 2
Diagnosis /opener
white
PIN 3
GND
blue
PIN 4
Sensor or control
signal
black
PIN 5
not used
Plastic body and screw cap in
grey
8.2.3.1 M12 flanged connector
The following flanged plugs and flanged couplings are available for installation in devices.
68 Subject to technical amendments BU 0290 GB-4312
For preference, pre-assembled PROFINET bus cables and connection components should
be used.
For certain applications, vibration-proof round plug connectors should be used.
3
2
The following plug connectors are recommended by Getriebebau NORD GmbH.
M12 connector
D coded
8 Additional information
BU 0290 GB-4312 Subject to technical amendments 69
Page 70
PROFINET bus module for NORD frequency inverters SK 200E
Supplier
Designation
Part no.:
MURR Elektronik
M12 wrench set for M12 round plug connectors with
calibrated torque of 0.6Nm
7000-99102-0000000
Franz Binder GmbH
M12 torque wrench for M12 round plug connectors with
calibrated torque of 0.6Nm
07-0079-000
NOTE
In order to ensure a secure, sealed and vibration-proof connection, connecting components
with hexagonal fittings should be used.
Special tools enable tightening to a defined torque (operational reliability).
M12
Wrench
8.2.3.3 Assembly tools
The observance of the tightening torques for making plug connections is of vital importance. For M12 plug
connectors, the optimum torque is 0.6Nm.
Suitable assembly tools are commercially available.
8.3 System bus
With NORD inverter technology, units or modules communicate via a dedicated system bus. With the
introduction of the SK 200E frequency inverter series and the associated components SK CU4-… and
SK TU4-… functions and interfaces were implemented in this system bus, which allow users to make useful
adaptations without having detailed knowledge of the function of the bus system (data allocation / error
handling, etc.).
A decisive advantage is provided by the fact that the system bus is no longer restricted to a single inverter and
a directly connected module, but rather that up to 4 frequency inverters can jointly use a BUS interface (e.g.:
PROFINET IO). This increases the number of possible participants on a field bus system (by a factor of 4) with
comparatively low investment costs.
The system bus address of the BUS modules (SK CU4-… and SK TU4-…) is set to "5". The system bus
address of the up to 4 frequency inverters which can be connected are set by means of DIP switches (see
manual BU 0200) on the relevant frequency inverter, optionally between 32 / 34 / 36 and 38, whereby no
address may be doubly assigned within a system bus system.
70 Subject to technical amendments BU 0290 GB-4312
Page 71
8 Additional information
NOTE
If possible, the reason for returning the component/device should be stated. If necessary,
at least one contact for queries should be stated.
This is important in order to keep repair times as short and efficient as possible.
On request you can obtain a suitable goods return voucher from us.
8.4 Repairs
The device must be sent to the following address if it needs repairing:
NORD Electronic DRIVESYSTEMS GmbH
Tjüchkampstr. 37
26605 Aurich, Germany
For queries about repairs, please contact:
Getriebebau NORD GmbH & Co. KG
Tel.: 04532 / 289-2515
Fax: 04532 / 289-2555
If a frequency inverter or accessories are sent in for repair, no liability can be accepted for any added
components, e.g. such as line cables, potentiometer, external displays, etc.!
Please remove all non-original parts from the frequency inverter.
BU 0290 GB-4312 Subject to technical amendments 71
Page 72
PROFINET bus module for NORD frequency inverters SK 200E
Address
Assigned or defined designation of a bus subscriber
ASIC
Application Specific Integrated Circuit”,
Baud rate
The transmission rate for serial interfaces in bits per second
Binary code
The designation for a code in which messages are communicated by "0" and "1" signals.
Bit / Byte
A bit (binary digit) is the smallest unit of information in the binary system. A byte has 8 bits.
Broadcast
In a network, all slave participants are addressed simultaneously by the master.
EMCY message
Emergency messages (error telegrams)
GSD
Device master data, format for the description of automation devices which communicate via
PROFIBUS
GSDML
GSD Markup Language, format for the description of automation devices which communicate
via PROFINET
Jitter
Designates a slight fluctuation in precision in the transmission pulse, or the variation in the
transmission time of data packages.
Abs.
Absolute
BE
Bus error (fault)
Size
Bus module
BR
Bus ready
BS
BUS state (status)
D, DI, DIN
Digital IN
DE
DEVICE error (fault)
DO, DOUT
Digital OUT
DS
DEVICE state (status)
EMC
Electromagnetic compatibility
FI
Frequency inverter
GND
Earth
HW
Hardware
I16
16 bit value (integer)
I/O
IN / OUT, input and output
IND
Index
IW
Actual value
NMT
Network Management
P
parameter which depends on a
parameter set
PPO
Process data object
PZD
Process data
RO
Read Only
RW
Read and Write
SDO
Service Data Object
STR
String value
STW
Control word
SW
Software / Setpoint
TU
Technologie Unit (external technology
unit)
U8 (U16 / U32)
8 bit (16 / 32 bit) value, unsigned
(without prefix)
ZBG
Additional module
ZSW
Status word
9 Index
9.1 Keyword Index:
9.2 Abbreviations used:
72 Subject to technical amendments BU 0290 GB-4312
Page 73
10 Keyword index
10 Listings
10.1 List of illustrations
Fig. 1 Wall-mounting kit SK TIE4-WMK-TU, dimensions.......................................................................................................... 12
Fig. 2 Cable gland on the BUS module / connection unit ........................................................................................................ 14
Fig. 3: DIP switches (system bus), frequency inverter ............................................................................................................. 24
Fig. 4: Example of PROFINET IO linear topology .................................................................................................................... 25
Fig. 5: Example of PROFINET IO star topology with switch ..................................................................................................... 25
Fig. 6 Installation of the GSDML file in the SIMATIC Manager ................................................................................................ 27
Fig. 7 Hardware Catalogue: Module selection and specification of data format ...................................................................... 28
Fig. 9 Diagram of the FI Status Machine ................................................................................................................................. 34
Fig. 10 Function of PROFINET Record ................................................................................................................................... 37
10.2 List of tables
Table 1 Overview of PROFINET IO modules ........................................................................................................................... 11
Table 2 Electrical specifications of the SK TU4-PNT ............................................................................................................... 15
Table 4 Connection assignment of BUS connection unit for PROFINET IO............................................................................ 18
Table 5 LED display, DS and GB ............................................................................................................................................ 21
Table 6 RUN LED display ....................................................................................................................................................... 22
Table 7 BF LED display........................................................................................................................................................... 22
Table 8 LED display, Link and Activity .................................................................................................................................... 22
Table 16 Meaning of individual control word bits ..................................................................................................................... 31
Table 17 Meaning of individual status word bits ...................................................................................................................... 32
Table 18 Codes for FI status ................................................................................................................................................... 33
Table 19 Depiction of 32Bit setpoint/actual values .................................................................................................................. 35
Table 20 Example of setpoint specification ............................................................................................................................. 36
Table 21 Structure of data records 100 and 101 ..................................................................................................................... 38
Table 22 Structure of data record 47 ....................................................................................................................................... 38
Table 23 Orders from the controller with the associated response label of the inverter .......................................................... 39
Table 24 Orders from the controller with the associated response label of the inverter or technology unit ............................. 39
Table 25 Response labels - Meaning ...................................................................................................................................... 40
Table 26 Response labels – Explanation of error numbers for response label = 7 ................................................................. 40
Table 27 Example : Address formation for array elements or parameters depending on parameter sets ............................... 41
Table 28 Example telegram for reading parameter P170 ........................................................................................................ 42
Table 29 Example telegram for reading parameter P102[-02] ................................................................................................. 43
Table 30 Example telegram for writing parameter P105[-01] .................................................................................................. 44
BU 0290 GB-4312 Subject to technical amendments 73
Page 74
PROFINET bus module for NORD frequency inverters SK 200E