NORD BU0240 User Manual

U
0
0
y
GB
B
NORDAC SK 200E
Brief instructions for frequenc
inverters
NORDAC SK 200E Manual Safety information
N O R D A C SK 200E frequency inverters
Safety and operating instructions for drive power converters
(as per: Low Voltage Directive 2006/95/EEC )
1. General
During operation, drive power converters may, depending on their protection class, have live, bare, moving or rotating parts or hot surfaces.
Unauthorised removal of covers, improper use, incorrect installation or operation causes a risk of serious personal injury or material damage.
Further information can be found in this documentation.
All transportation, installation, initialisation and maintenance work must be carried out by qualified personnel (compliant with IEC 364, CENELEC HD 384, DIN VDE 0100, IEC 664 or DIN VDE 0110, and national accident prevention regulations).
For the purposes of these basic safety instructions, qualified personnel are persons who are familiar with the assembly, installation, commissioning and operation of this product and who have the relevant qualifications for their work.
2. Proper use in Europe
Drive power converters are components intended for installation in electrical systems or machines.
When installed in machines, the drive power converter cannot be commissioned (i.e. commencement of the proper use) until it has been ensured that the machine meets the provisions of the EC Directive 2006/42/EEC (machine directive); EN 60204 must also be complied with.
Commissioning (i.e. implementation of the proper use) is only permitted when the EMC directive (2004/108/EEC) is complied with.
CE-labelled drive power converters meet the requirements of the Low Voltage Directive 2006/95/EEC. The harmonised standards for drive power converters listed in the declaration of conformity are used.
Technical data and information for connection conditions can be found on the rating plate and in the documentation, and must be complied with.
The drive power converters may only be used for safety functions which are described and explicitly approved.
3. Transport, storage
Information regarding transport, storage and correct handling must be complied with.
4. Installation
The installation and cooling of the equipment must be implemented according to the regulations in the corresponding documentation.
The drive power converter must be protected against impermissible loads. Especially during transport and handling, components must not be deformed and/or insulation distances must not be changed. Touching of electronic components and contacts must be avoided.
Drive power converters have electrostatically sensitive components, which can be easily damaged by incorrect handling. Electrical components must not be mechanically damaged or destroyed (this may cause a health hazard!).
5. Electrical connection
When working on live drive power converters, the applicable national accident prevention regulations must be complied with (e.g. VBG A3, formerly VBG 4).
The electrical installation must be implemented according to the applicable regulations (e.g. cable cross-section, fuses, ground lead connections). Further instructions can be found in the documentation.
Information about EMC-compliant installation – such as shielding, earthing, location of filters and installation of cables can be found in the drive power converter documentation. These instructions must be complied with even with CE marked drive power converters. Compliance with the limiting values specified in the EMC regulations is the responsibility of the manufacturer of the system or machine.
6. Operation
Where necessary, systems where drive power converters are installed must be equipped with additional monitoring and protective equipment according to the applicable safety requirements, e.g. legislation concerning technical equipment, accident prevention regulations, etc.
The parameterisation and configuration of the drive power converter must be selected so that no hazards can occur.
All covers must be kept closed during operation.
7. Maintenance and repairs
After the drive power converter is disconnected from the power supply, live equipment components and power connections should not be touched immediately, because of possible charged capacitors. Observe the applicable information signs located on the drive power converter.
Further information can be found in this documentation.
These safety instructions must be kept in a safe place!
2 BU 0240 GB
NORDAC SK 200E Manual Concerning this document
Intended use of the frequency inverter
Compliance with the operating instructions is necessary for fault-free operation and the
acceptance of possible warranty claims. These operating instructions must be read before
working with the device!
These operating instructions contain important information about servicing. They must therefore be kept close to the device.
SK 200E frequency inverters are devices for industrial and commercial plants for operating three-phase asynchronous motors with squirrel-cage rotors. These motors must be suitable for operation with frequency inverters. Other loads must not be connected to the devices.
SK 200E frequency inverters are devices for fixed installation on motors or in the vicinity of the motors to be operated. All details regarding technical data and permissible conditions at the installation site must be complied with.
Commissioning (implementation of the intended use) is not permitted until it has been ensured that the machine complies with the EMC directive 2004/108/EEC and that the conformity of the end product meets the machine directive 2006/42/EEC (note EN 60204).
© Getriebebau NORD GmbH & Co. KG, 2010
BU 0240 GB 3
NORDAC SK 200E Manual
Documentation
Designation: BU 0240 GB
Part No.: 607 24 02
Device series: SK 205E, SK 215E, SK 225E, SK 235E
Device types: SK 2xxE-250-112-O ... SK 2xxE-750-112-O, 0.25 - 0.75kW, 1~ 100-120V, 230V Output
SK 2xxE-250-123-O ... SK 2xxE-111-123-A, 0.25 - 1.1kW, 1~ 220-240V SK 2xxE-250-323-O ... SK 2xxE-401-323-A, 0.25 - 4.0kW, 3~ 220-240V SK 2xxE-550-340-O ... SK 2xxE-751-340-A, 0.55 - 7.5kW, 3~ 380-500V
Version list
Designation of previous versions Software
BU 0240 GB, June 2010
Part No. 607 2401 / 2210
Publisher
Getriebebau NORD GmbH & Co. KG
Rudolf- Diesel- Str. 1 D-22941 Bargteheide Germany http://www.nord.com/
Tel.: +49 (0) 45 32 / 401-0 Fax +49 (0) 45 32 / 401-555
Standards and approvals
All devices of the entire SK 200E series comply with the standards and directives listed below. For detailed information, please refer to the main manual BU0200.
Standard / Directive Logo Comments
EMC
Comments
Version
V 1.2 R0 First version based on BU 0200 DE / 1310
EN 61800-3
UL
cUL
C-Tick
RoHS
File No. E171342
File No. E171342
N 23134
2002/95/EU RoHS compliant
NOTE
These brief instructions only contain a limited amount of information. For a detailed description of use and the technical details of the SK 2 00E an d its o ptio ns, pl ease refe r to the main document BU0200.
4 BU 0240 GB
Table of Contents
1 GENERAL INFORMATION ......................................................................................................6
1.1 Delivery.................................................................................................................6
1.2 Safety and installation information .......................................................................7
1.3 Wiring guidelines ..................................................................................................9
1.4 Nomenclature / type codes.................................................................................10
2 ASSEMBLY AND INSTALLATION........................................................................................12
2.1 Installation and assembly ...................................................................................12
2.2 Electrical connection ..........................................................................................14
2.3 Electrical connection of power unit.....................................................................15
2.4 Electrical connection of SK 200E control unit ....................................................16
3 SK 200E DISPLAYS AND CONTROL...................................................................................18
4 COMMISSIONING, SK 200E..................................................................................................19
4.1 Commissioning stages .......................................................................................19
4.1.1 Connection..............................................................................................................19
4.1.2 Configuration...........................................................................................................20
4.1.3 Commissioning examples ....................................................................................... 24
4.2 ATEX Zone 22 for SK 2x5E................................................................................26
4.2.1 Modified SK 2x5E for compliance with Category 3D............................................... 27
4.2.2 Options for ATEX Zone 22 3D ................................................................................27
4.2.3 Maximum output voltage and torque reduction ....................................................... 30
4.2.4 Commissioning information.....................................................................................31
4.2.5 EC declaration of conformity ................................................................................... 32
5 PARAMETERISATION OF FREQUENCY INVERTER SK 200E ..........................................33
6 OPERATING STATUS MESSAGES AND LED DISPLAYS..................................................35
7 TECHNICAL DATA FREQUENCY INVERTER......................................................................37
8 MAINTENANCE AND SERVICING INFORMATION..............................................................38
9 KEYWORD INDEX..................................................................................................................39
BU 0240 GB 5
NORDAC SK 200E Manual
1 General information
These brief instructions for the SK 200E are based on the user manual for the frequency inverter - BU0200.
In addition to information concerning safety and use, this document also contains selected information on commissioning, as well as use of the frequency inverter in explosion hazard areas (ATEX Zone 22).
This manual is based on the device software V1.2 R0 (see P707) of the SK 200E. If the frequency inverter uses a different software version, this may cause differences.
A detailed description of the SK 200E and its options can be found in the user manual (BU0200). This and other documents can be downloaded free of charge from
www.nord.com.
1.1 Delivery
Check the equipment immediately after delivery/unpacking for transport damage such as deformation or
loose parts.
If there is any damage, contact the carrier immediately and carry out a thorough assessment.
Important! This also applies even if the packaging is undamaged.
6 BU 0240 GB
1.2 Safety and installation information
NORDAC SK 200E frequency inverters are devices for use in industrial high voltage systems and are
operated at voltages that could lead to severe injuries or death if they are touched.
Installation and other work may only be carried out by qualified electricians and with the device disconnected. The operating instructions must always be available to these persons and must be strictly observed.
Local regulations for the installation of electrical equipment and accident prevention must be complied with.
The equipment continues to carry hazardous voltages for up to 5 minutes switched off at the mains.
For single phase operation (115/230V) the mains impedance must be at least 100μH for each conductor. If this is not the case, a mains choke must be installed.
For safe isolation from the mains, all poles of the supply cable to the frequency inverter must be able to be disconnected.
Even during motor standstill (e.g. caused by a release block, blocked drive or output terminal short circuit), the line connection terminals, motor terminals and braking resistor terminals may still conduct hazardous voltages
. A motor standstill is not identical to
electrical isolation from the mains.
Warning: with certain settings, the frequency inverter/motor can start up automatically
after the mains are switched on.
The frequency inverter is only intended for permanent connection and may not be operated without effective earthing connections which comply with the local regulations for large leakage currents (> 3.5mA). VDE 0160 stipulates the installation of a second earthing conductor or an earthing conductor cross-section of at least 10 mm
Normal FI-circuit breakers are not suitable as the sole protection for three-phase
frequency inverters if the local regulations do not permit a possible DC proportion in the fault current. According to EN 50178 / VDE 0160, the FI circuit breaker must be an all­current sensitive FI circuit breaker (type B).
In normal use, NORDAC SK 200E frequency inverters are maintenance free. The cooling surfaces must be regularly cleaned with compressed air if the ambient air is dusty.
after being
2
.
1 General
CAUTION
The heat sink and all other metal components can heat up to temperatures above 70°C.
When mounting, sufficient distance from neighbouring components must be maintained. When working on the components, allow sufficient cooling time beforehand
Protection against accidental contact may need to be provided.
ATTENTION
DANGER TO LIFE
The power unit can continue to carry voltages for up to 5 minutes after being switched off at the mains. Inverter terminals, motor cables and motor terminals may carry voltage!
Touching open or free terminals, cables and equipment components can lead to severe injury or death!
Work may only be carried out by qualified specialist electricians and with the electrical supply to the equipment disconnected!
!
BU 0240 GB 7
NORDAC SK 200E Manual
CAUTION
WARNING
Children and the general public must be kept away from the equipment!
The equipment may only be used for the purpose intended by the manufacturer. Unauthorised modifications and the use of spare parts and additional equipment which has not been purchased from or recommended by the manufacturer of the device may cause fire, electric shock and injury.
Keep these operating instructions in an accessible location and give them to all operators!
This product intended for use in an industrial environment and is subject to sales restrictions according to IEC 61800-3. In a domestic environment, this product can cause high frequency interference, in which case the user may be required to take appropriate measures.
An appropriate measure would be the inclusion of a recommended mains filter.
8 BU 0240 GB
1.3 Wiring guidelines
The frequency inverter has been developed for use in an industrial environment. In this environment, high levels of electromagnetic interference can influence the frequency inverter. In general, correct installation ensures safe and problem-free operation. To meet the limiting values of the EMC directives, the following instructions should be complied with.
(1) Ensure that all equipment in the control cabinet is securely earthed using short earthing cables which
have large cross-sections and are connected to a common earthing point or earthing bar. It is especially important that all control devices connected to the frequency inverters (e.g. an automation device) are connected to the same earthing point as the inverter itself, using a short cable with large cross-section. Flat conductors (e.g. metal clamps) are preferable, as they have a lower impedance at high frequencies.
(2) The bonding cable of the motor controlled by the frequency inverter should be connected directly to the
earthing terminal of the associated frequency inverter. The presence of a central earthing bar in the control cabinet and the grouping together of all bonding conductors to this bar normally ensures safe operation.
(3) Where possible, shielded cables should be used for control loops. The shielding at the cable end
should be carefully sealed and it must be ensured that the wires are not laid over longer distances without shielding.
The shields of analog setpoint cables should only be earthed on one side on the frequency inverter.
(4) The control cables should be installed as far as possible from power cables, using separate cable
ducts, etc. Where cables cross, an angle of 90° should be ensured as far as possible.
(5) Ensure that the contactors and brake chokes in the cabinet are interference protected, either by RC
circuits in the case of AC contactors, or by “free-wheeling” diodes for DC contactors, for which the interference protectors must be positioned on the contactor coils. Varistors for over-voltage
limitation are also effective. This interference suppression is particularly important when the contactors are controlled by the relay in the frequency inverter.
(6) Use screened or armoured cable for the load connections (motor cable) and earth the
screening/armour at both ends, if possible to the frequency inverter bonding.
In addition, an EMC-compliant cabling must be ensured.
The safety regulations must be complied with under all circumstances when installing the
frequency inverter!
1 General
NOTE
The control cables, line cables and motor cables must be laid separately. In no case should they be laid in the same protective pipes/installation ducts.
The test for high voltage insulations must not be used on cables which are connected to the frequency inverter.
ATTENTION
With the use of a ParameterBox SK PAR-3H this must never be simultaneously connected to the frequency inverter and the PC, as potential shifts may cause damage, especially to the PC. (See also Manual BU0040)
BU 0240 GB 9
NORDAC SK 200E Manual
1.4 Nomenclature / type codes
Unique type codes have been defined for the individual modules and devices. These provide individual details of the device type and its electrical data, protection class, fixing version and special versions. A differentiation is made according to the following groups:
Group Example of type code
Frequency inverter - basic device SK 205E-550-323-A (-C)
Adapter unit - frequency inverter SK TI4-1-205-1 (-C-WMK-1)
Connection unit - Technology Unit SK TI4-TU-BUS (-C-WMK-TU)
Optional modules SK TU4-CAO (-C-M12)
Extension modules SK TIE4-M12-CAO
Frequency inverter
Adapter unit
The type designation resulting from this type code can be obtained from the rating plate which is attached to or printed on the relevant module.
Example: Frequency inverter rating plate
10 BU 0240 GB
Frequency inverter type code
SK 205E-370-323-A (-C)
IP protection class: Standard = IP55, C = „coated“ IP66 Radio interference filter: O = without, A = Class A1, B = Class B1 Mains voltage: x12 = 115V, x23 = 230V, x40 = 400V Number of mains phases: 1xx = single phase, 3xx = 3-phase Digits before comma for power: 0 = 0.xx, 1 = 0x.x0, 2 = 0xx.0 Device nominal power: 250 = 0.25kW, 370 = 0.37kW, ... 751 = 7.5kW Device series: SK 205E, SK 215E, SK 225E, SK 235E
Adapter Unit type code
1 General
(...) Options, only implemented if required.
SK TI4-1-205-1 (-C-WMK-1)
Wall mounting kit: -1 = S I + II, -2 = S III
IP protection class: Standard = IP55, C = „coated“ IP66 Mains connection: 1 = 1~ 115/230V*, 3 = 3~ 230/400V* Suitable device types: 205 = SK 205E, 215 = SK 215E,
225 = SK 225E, 235 = SK 235E
Size: 1 = S I, 2 = S II, 3 = S III Device series: SK TI4 = Connection Unit SK TI4
*) The voltage depends on the frequency inverter used;
please also refer to the technical data.
(...) Options, only implemented if required.
The description of the type codes for the options can be found in BU0200.
BU 0240 GB 11
NORDAC SK 200E Manual
2 Assembly and installation
2.1 Installation and assembly
NORDAC SK 200E frequency inverters are available in various sizes depending on their output. Connection of the SK 200E to the motor or the wall-mounting unit is made by means of the a suitable size of connection unit SK T14-… The frequency inverter is mounted by means of integrated plug contacts.
The devices require adequate ventilation to protect against overheating.
Motor-mounted version Mounting must therefore always be carried out as shown in the illustration. For permanently low motor speeds and self-ventilated motors, a reduction in power similar to the wall-mounted version must be taken into account.
: Here, the ventilation of the motor is integrated into the cooling concept of the FI.
Wall-mounted version
: In continuous operation (S1), mounting away from the motor causes a reduction in the power of the FI by one power level. This means that relative to the motor, the FU must be selected one power level larger.
NOTE
For further details of the power reduction and the possible ambient temperatures, please refer to the technical data in BU0200
12 BU 0240 GB
Loading...
+ 28 hidden pages