PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE Safety information
2 BU 0220 GB-0912
Page 3
PROFIBUS DP – Zusatzanleitung für NORD Frequenzumrichter SK 200E Safety information
NORD frequency inverters
Safety and operating instructions for drive power converters
(as per: Low Voltage Directive 2006/95/EEC )
1. General
During operation, drive power converters may, depending on their
protection class, have live, bare, moving or rotating parts or hot
surfaces.
Unauthorised removal of covers, improper use, incorrect installation
or operation causes a risk of serious personal injury or material
damage.
Further information can be found in this documentation.
All transportation, installation, initialisation and maintenance work
must be carried out by qualified personnel (compliant with
IEC 364, CENELEC HD 384, DIN VDE 0100, IEC 664 or
DIN VDE 0110, and national accident prevention regulations).
For the purposes of these basic safety instructions, qualified
personnel are persons who are familiar with the assembly,
installation, commissioning and operation of this product and who
have the relevant qualifications for their work.
2. Proper use in Europe
Drive power converters are components intended for installation in
electrical systems or machines.
When installed in machines, the drive power converter cannot be
commissioned (i.e. commencement of the proper use) until it has
been ensured that the machine meets the provisions of the EC
Directive 2006/42/EEC (machine directive); EN 60204 must also be
complied with.
Commissioning (i.e. implementation of the proper use) is only
permitted when the EMC directive (2004/108/EEC) is complied with.
CE-labelled drive power converters meet the requirements of the
Low Voltage Directive 2006/95/EEC. The harmonised standards for
drive power converters listed in the declaration of conformity are
used.
Technical data and information for connection conditions can be
found on the rating plate and in the documentation, and must be
complied with.
The drive power converters may only be used for safety functions
which are described and explicitly approved.
3. Transport, storage
Information regarding transport, storage and correct handling must
be complied with.
4. Installation
The installation and cooling of the equipment must be implemented
according to the regulations in the corresponding documentation.
The drive power converter must be protected against
impermissible loads. Especially during transport and
handling, components must not be deformed and/or
insulation distances must not be changed. Touching of
electronic components and contacts must be avoided.
Drive power converters have electrostatically sensitive
components, which can be easily damaged by incorrect
handling. Electrical components must not be mechanically
damaged or destroyed (this may cause a health hazard!).
5. Electrical connection
When working on live drive power converters, the applicable
national accident prevention regulations must be complied
with (e.g. VBG A3, formerly VBG 4).
The electrical installation must be implemented according to
the applicable regulations (e.g. cable cross-section, fuses,
ground lead connections). Further instructions can be found
in the documentation.
Information about EMC-compliant installation – such as
shielding, earthing, location of filters and installation of
cables can be found in the drive power converter
documentation. These instructions must be complied with
even with CE marked drive power converters. Compliance
with the limiting values specified in the EMC regulations is
the responsibility of the manufacturer of the system or
machine.
6. operation
Where necessary, systems where drive power converters
are installed must be equipped with additional monitoring
and protective equipment according to the applicable safety
requirements, e.g. legislation concerning technical
equipment, accident prevention regulations, etc.
The parameterisation and configuration of the drive power
converter must be selected so that no hazards can occur.
All covers must be kept closed during operation.
7. Maintenance and repairs
After the drive power converter is disconnected from the
power supply, live equipment components and power
connections should not be touched immediately, because of
possible charged capacitors. Observe the applicable
information signs located on the drive power converter.
Further information can be found in this documentation.
These safety instructions must be kept in a safe place!
BU 0220 GB-0912 3
Page 4
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE About this document
Designation of previous versions
Software
Version
Remarks
BU 0220 DE, June 2009
Part No. 607 2201 / 2609
V 1.1 R1
First issue
BU 0220 GB, February 2012
Part No. 607 2201 / 0912
V 1.2 R0
The bus module also recognises the SK 54xE,
Firmware update also possible via the CAN system bus,
Error corrections (e.g. connection via the Profibus data
cables PBA / PBB)
Supplements to Section 7.2.1.7 and 7.2.1.8 (assignment of
functions BIT 8/9 STW or BIT 10/13 ZSW
Parameters (P153) and (P154) supplemented
NOTE
This supplementary operating manual is only valid in conjunction with the operating manual
supplied for the respective frequency inverter.
Documentation
Designation: BU 0220 GB
Part No.: 607 22 01
Device series: PROFIBUS DP for SK 2xxE
Device types: SK CU4-PBR
SK TU4-PBR(-C) with SK TI4-TU-BUS SK TU4-PBR-M12(-C) with SK TI4-TU-BUS
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE zu diesem Dokument
Intended use of the frequency inverter
The compliance with the operating instructions is necessary for fault-free operation and
the acceptance of possible warranty claims. These operating instructions must be read
before working with the device!
These operating instructions contain important information about servicing. They must
therefore be kept close to the device.
The field bus technology options described here are intended for use in combination with
SK 200 E series frequency inverters. The SK 5xxE can only be used with other series by
means of SK TU4-... Technology Units. The use of these technology options with other
devices is not permitted and can lead to their destruction.
The field bus technology options and the associated frequency inverters are devices for fixed
installation on motors or in equipment close to the motor to be operated. All details regarding
technical data and permissible conditions at the installation site must be complied with.
Commissioning (implementation of the intended use) is not permitted until it has been
ensured that the machine complies with the EMC directive 204/108/EEC and that the
conformity of the end product meets the machine directive 2006/42/EEC (note EN 60204).
Getriebebau NORD GmbH & Co. KG, 2012
BU 0220 GB-0912 5
Page 6
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
1 GENERAL INFORMATION ...................................................................................................... 8
9 INDEX ...................................................................................................................................... 96
10 KEYWORD INDEX ................................................................................................................ 98
BU 0220 GB-0912 7
Page 8
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
1 General information
Various technology options are available for Getriebebau Nord frequency inverters. General information
regarding these can be found in the relevant main manual of the frequency inverter series (e.g. Manual
BU0200 for the SK 200E frequency inverter series). Further information concerning special technology
options (e.g. the field bus module) is included in the relevant supplementary operating instructions.
This PROFIBUS DP documentation contains supplementary descriptions concerning the PROFIBUS DP
options for the SK 200E frequency inverter series.
The description of other optional modules (e.g. CANopen) is dealt with in other supplementary documentation.
In order to set up communication with PROFIBUS DP, either an internal Customer Unit or an external
PROFIBUS DP Technology Unit (according to the particular application) must be installed and connected.
The PROFIBUS DP bus system
A large number of different automation devices can exchange data with frequency inverters using
PROFIBUS DP. PLC's, PC's, operating and monitoring devices can all communicate via a uniform bus in
serial bit mode. PROFIBUS DP is primarily used for communication between sensor and actuator where
system response needs to be very fast. PROFIBUS DP is used where the time for rapid and complex
communication between the individual devices is critical. PROFIBUS DP is a suitable alternative to
expensive 24-volt parallel signal transmission and transmission of measured values. This type of
PROFIBUS, which is optimised to speed, is used for instance for operating frequency inverters on
automation devices.
PROFIBUS communication is standardised and specified in the international standards IEC 61158 and
IEC 61784. Application and planning aspects are specified and documented in the guidelines of the
PROFIBUS users´ organisation (PNO). This ensures intercommunication between devices from different
manufacturers. Data exchange is specified in DIN 19245 Part 1 and 2 and application-specific upgrades in
Part 3 of this standard. Within the European field bus standardisation process, PROFIBUS is integrated into
the European field bus standard EN 50170.
8 Subject to technical amendments BU 0220 GB-0912
Page 9
1 General information
1.1 Overview
Features of the PROFIBUS DP modules
Electrically isolated bus interface
Transfer rate: 12Mbit/s
Easy connection, optionally via M12 round plugs or screw terminals
Looping of the PROFIBUS DP via the module
Integrated bus terminating resistor (switchable)
PROFIBUS DP-specific status indication with 2 LEDs on the internal (Customer Unit) and external
(Technology Unit) technology option
DEVICE or FI-specific status indication with 2 LEDs on the internal (Customer Unit) and external
(Technology Unit) technology option
PROFIBUS DP basic functionality as per DP-V0
Acyclic data traffic as per DP-V1
Up to four 24V inputs and two 24V outputs are integrated into the bus module
Direct connection of up to 4 sensors and 2 activators via M12 round plug connectors on the
SK TU4-PBR-M12(-C) version. Visualisation of signal status via LEDs
Transmission and reading of process and parameter data
PROFIBUS DP Gateway solution → up to 4 frequency inverters can be connected to a
PROFIBUS DP module
Up to 122 PROFIBUS DP modules can be connected to the bus. This enables the operation of up to
488 frequency inverters on one bus.
Automatic detection of baud rate and PPO type by the PROFIBUS DP module
"Simultaneous" access by up to 4 PROFIBUS DP masters (1 x DPM1 and up to 3 x DPM2) possible.
The DPM2 masters do not need to be permanently connected to the PROFIBUS DP network for
communication.
Interface (RS232/RS485) for parameter access by means of the SK PAR-3H manual control unit or
NORDCON software via RJ12 connector (Except for SK CU4-PBR. Here parameter access via the
SK 2xxE frequency inverter is possible)
Available as versions for installation in the inverter (IP20) or in a separate housing (optionally
IP55 / IP66)
1.2 Delivery
Check the equipment immediately after delivery/unpacking for transport damage such as deformation or
loose parts.
If there is any damage, contact the carrier immediately and carry out a thorough assessment.
Important! This also applies even if the packaging is undamaged.
BU 0220 GB-0912 Subject to technical amendments 9
Page 10
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
1.3 Scope of supply
Standard version: SK CU4-PBRIP20 or
SK TU4-PBR(-M12)(-C)IP55 (optionally IP66)Operating instructions as PDF file on CD ROM
including NORDCON, (Windows PC-based parameterisation software)
Available accessories: SK TI4-TU-BUS(-C) (bus connection unit, required for SK TU4…)SK TIE4-WMK-TU, wall-mounting kit TU4
M12 round plug connector (Section 8.2 "Cable glands and shielding connections")Matching RJ12 to SUB-D9 adapter cable to connection to a PC
ParameterBox: SK PAR-3H, ParameterBox, plain text LCD display
1.4 Certifications
1.4.1 European EMC Directive
If the SK 2xxE frequency inverter or its options are installed according to the
recommendations in this instruction manual, it meets all EMC directive
requirements, as per the EMC product standard for motor-operated systems
EN 61800-3. (see also Section 8.1.3 "Cable layout and shielding (EMC
measures)")
1.4.2 RoHS compliance
SK 200E series frequency inverters or their options are designed to be RoHS
compliant according to Directive 2002/95/EEC
10 Subject to technical amendments BU 0220 GB-0912
Page 11
1.5 Type code / Optional BUS modules
SK TU4-PBR (-C-M12-WMK-TU)
Wall mounting kit: for external technology unit, TU4
M12 system connector: only TU4, alternative to terminals
IP protection class: Standard = IP55, C = "coated" IP66
Option type: CAO = CANopen, PBR = Profibus,
DEV = DeviceNet, IOE = I/O extension
Option series: TU4 = external technology unit
CU4 = internal customer unit
(...) Options, only implemented if required.
Optional internal
customer unit, SK CU4-…
Optional external
technology unit, SK TU4-…
BUS = Bus module or I/O extension
1 General information
BU 0220 GB-0912 Subject to technical amendments 11
Page 12
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
NOTE
The modules for the IP66 design are identified by an additional "-C" and are modified
according to the following special measures!
NOTE
For all versions, care must be taken that the cable and the cable gland are carefully
matched. This is essential to ensure that the required protection class is maintained.
1.6 Version with protection class IP55 / IP66
The SK 2xxE frequency inverter and the externaladditional modules are available with protection classes
IP55 (Standard) or IP66 (optional) and in all sizes and power ratings.
The protection class IP66 must always be stated when ordering!
There are no restrictions or differences to the scope of functions in either protection class. In order to
differentiate the protection classes, modules with protection class IP66 are given an extra "-C" (coated
coated PCBs) in their type designation.
e.g. SK TU4-PBR-C
IP55 version:
The IP55 version of the external technology units is the standard version. Both versions (inverter-mounted –
as a supplement to the frequency inverter or wall mounted on the wall bracket) are available.
IP66 version:
In contrast to the IP55 version the IP66 version is a modified option. With this design, both versions
(inverter-mounted or wall-mounted) are also available. The modules available for the IP66 version (adapter
units, technology units and customer units) have the same functionalities as the corresponding modules for
the IP55 version.
Special measures:
Impregnated PCBs, coated housing
Diaphragm valve for pressure compensation on temperature changes.
Low pressure test
A free M12 screw connection is required for low pressure testing. After successful testing, a
diaphragm valve is inserted here. This screw connection is therefore no longer available for
a cable gland.
12 Subject to technical amendments BU 0220 GB-0912
Page 13
2 Assembly and installation
SK TI4-… with integrated technology unit
SK CU4-…
SK 200E with external technology unit SK TU4-...
and BUS connection module SK T14-TU-BUS
SK TIE4-WMK-TU
with BUS connection module SK T14-TU-BUS and
external technology unit SK TU4-... or SK TU4-...-M12
Optional internal
customer units, SK CU4-…
2 Assembly and installation
2.1 Installation and assembly
Internal and external technology modules designed for the SK 2xxE frequency inverter series are available for
PROFIBUS DP. Except for the number of digital inputs and outputs, the functionalities of the various
PROFIBUS modules are identical.
These are used to connect SK 200E series speed regulated drive units to overriding automation systems via
the PROFIBUS DP field bus.
The internal technology modules (Customer Unit, SK CU4-...) – designated as the customer unit – are
integrated into the connection unit of the SK 2xxE. Electrical connection to the SK 2xxE is made via the
internal system bus. The connection to external peripheral devices is made via screw terminals. The use of the
optionally available 4 or 5 pin M12 round plug connector, installed in the connection unit of the SK 2xxE,
provides a possible interface for connection to the field bus. A maximum of one customer interface (including
any 24V module) can be installed in the SK 2xxE frequency inverter.
BU 0220 GB-0912 Subject to technical amendments 13
Page 14
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
NOTE
Modules should not be inserted or removed unless the device is free of voltage. The slots
may only be used for the intended modules.
Mounting of the external technology unit remote from the frequency inverter is possible with the
additional wall-mounting kit (SK TIE4-WMK-TU). However, a maximum cable length of 30m
should not be exceeded.
The external technology units (SK TU4-...(-M12) cannot be operated without the BUS
connection unit (SK T14-TU-BUS)!
NOTE
Only one field bus module (e.g. SK CU4-PBR or. SK TU4-PBR) can be connected to a
single system bus.
Optional external
technology unit, SK TU4-…
The external technology modules (Technology Unit, SK TU4-...) – designated as the technology unit – are
externally attached to the SK 2xxE connection unit and are therefore easy to access. Mounting of the SK TU4-...
separate from the frequency inverter is possible by means of the wall mounting kit SK TIE4-WMK-TU.
Electrical connection to the SK 2xxE is made via the internal system bus. 4 or 5 pin M12 round plug
connectors (for installation in the BUS connection unit SK TI4-TU-BUS) are available as an option for
connection of the field bus cable. The external modules are also available as a version with integrated M12
round plug connectors (SK TU4-xxx-M12). These enable the connection of up to 4 digital inputs and 2 digital
outputs.
14 Subject to technical amendments BU 0220 GB-0912
Page 15
2.1.1 Overview of the PROFIBUS DP modules
Bus Module
Description
Data
Profibus module
SK CU4-PBR
Part No. 275271000 (IP20)
This option enables control of the SK 2xxE via
PROFIBUS DP.
This option is integrated into the connection unit of
the frequency inverter.
Protocol:
DP-V0 (cyclical data traffic)
DP-V1 (acyclic data traffic)
Baud rate:
up to 12 MBaud
Connection:
16-terminal screw terminal bar
2x digital inputs:
Low: 0-5V, High: 11-30V
System bus
Profibus module *)
SK TU4-PBR(-C)
Part No. 275281100 (IP55)
Part No. 275281150 (IP66)
This option enables control of the SK 2xxE via
PROFIBUS DP.
This option is installed externally to the frequency
inverter.
According to the installation location, at least one
"BUS connection unit"* is required.
Protocol:
DP-V0 (cyclical data traffic)
DP-V1 (acyclic data traffic)
Baud rate:
up to 12 MBaud
Connection:
36 pin spring terminal bar of the
“BUS connection unit” *
4x digital inputs:
Low: 0-5V, High: 11-30V
2x Digital outputs:
0/24V
System bus
Profibus module with M12 *)
SK TU4-PBR-M12(-C)
Part No. 275281200 (IP55)
Part No. 275281250 (IP66)
This option enables control of the SK 2xxE via
PROFIBUS DP.
This option is installed externally to the frequency
inverter.
According to the installation location, at least one
"BUS connection unit"* is required.
As SK TU4-PBR, but with:
6x M12 socket for the connection
of up to 4 sensors and 2
actuators via 5 pin M12 round
plug connectors (A coded)
Connection unit for TU4
SK TI4-TU-BUS
Part No. 275280000 (IP55)
Part No. 275280500 (IP66)
The connection unit is always required in order to
use an external technology unit (SK TU4-...). This
implements the mechanical and electrical
connection of the Technology Unit to the SK 2xxE
or the wall-mounting kit.
Connection:
36 pin spring terminal bar
36x 2,5mm2
AWG 26-14
Spring terminals
TU4 Wall-mounting kit
SK TIE4-WMK-TU
Part. No. 275274002
With the wall mounting kit, a technology unit can be
used/installed separately from the SK 2xxE.
*)
in order to use the TU4 modules, a suitable SK TI4-TU-BUS connection unit must always be available!
2 Assembly and installation
BU 0220 GB-0912 Subject to technical amendments 15
Page 16
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
WARNING
Installation must be carried out by qualified personnel only, paying particular attention to
safety and warning instructions.
Modules must not be inserted or removed unless the device is free of voltage. The slots
may only be used for the intended modules.
Installation of the SK CU4-... customer unit remote from the frequency inverter is not permitted.
This must be mounted directly in the connection unit of the SK 2xxE frequency inverter.
SK TI4-… with integrated technology unit
SK CU4-PBR
internal customer unit SK CU4-PBR
Bag enclosed with internal customer unit
Function
Terminal label
Cable colour
Power supply
(between frequency inverter and customer unit)
44
24V
brown
40
GND
blue
System bus
77
SYS+
black
78
SYS-
grey
NOTE
Set the termination resistors of the system bus!
see Section 2.2.3 "Configuration")
2.1.2 Installing the Customer Unit SK CU4-PBR
The installation of customer units is carried out in the connection unit SK T14-…of the SK 2xxE underneath the
control terminal bar. Fastening is by means of the terminal bar of the frequency inverter and two M4x20 screws
(bag enclosed with the customer unit). Only one customer unit per FI is possible!
The pre-assembled cables for connection to the frequency inverter (SK 2xxE) are also included in the bag
enclosed with the customer unit. Connections are made according to the following table:
16 Subject to technical amendments BU 0220 GB-0912
Page 17
2 Assembly and installation
WARNING
Installation must be carried out by qualified personnel only, paying particular attention to
safety and warning instructions.
Modules must not be installed or removed unless the device is free of voltage. The slots
may only be used for the intended modules.
Mounting of the external technology unit remote from the frequency inverter is possible with the
additional wall-mounting kit (SK TIE4-WMK-TU).
NOTE
The IP protection class is not complied with if the screw connections are not connected
properly. In this case, the module may be damaged by the entry of dirt or moisture.
136
Flan
External BUS connection unit =
SK TI4-TU-BUS
2.1.3 Installing the SK TU4-PBR-… technology unit
Together with the BUS connection unit SK TI4-TU-BUS(-C) the technology unit SK TU4-PBR-…(-C) forms a
stand-alone functional unit. This can be attached to the SK 2xxE frequency inverter or installed separately by
means of the optional SK TIE4-WMK-TU wall-mounting kit.
2.1.3.1 Dimensions of the SK TI4-WMK-TU wall-mounting kit
The optional wall-mounting kit has the following dimensions.
2.1.3.2 BUS connection unit SK T14-TU-BUS(-C)
Various cable glands closed by caps are located on the sides of the BUS
connection unit.
The following holes are available as cable inlets:
2 x 1 M20 x 1.5 (on sides)
4 M16 x 1.5 (underside)
2 M25 x 1.5 (rear side, without caps)
The transparent screw-on cover (M20 x 1.5) on the upper right serves as access to the diagnostic interface
(RJ12 socket, interface RS232/RS485). The top left screw connection is a blank screw cap.
BU 0220 GB-0912 Subject to technical amendments 17
Page 18
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Mounting the external technology unit on the SK 200E
Technology unit SK TU4-PBR (-M12) BUS connection unit SK T14-TU-BUS
Bus Technology Unit with wall-mounting kit
2.1.3.3 Mounting the SK TI4-TU-BUS on the SK 200E
The screw fittings and seals required for installation are enclosed with the modules or are fitted to the intended
locations.
Mounting of the technology unit on the SK 200E
must be carried out as follows:
1. Switch off the mains.
2. Remove the two M25 caps on the required side
of the frequency inverter (right / left).
3. Remove the printed circuit board (with terminal
bar) from the BUS connection unit.
4. Install the SK T14TUBUS (with adhered seal) on
the SK 200E using the 4 enclosed bolts.
5. Replace the printed circuit board (See point 3)
and carry out the electrical connections.
6. Fit and screw on the SK TU4 module.
2.1.3.4 Wall-mounting the SK TI4-TU-BUS
The screw fittings (except for anchoring screws) and
seals required for installation are enclosed with the
modules or are fitted to the intended locations.
The connecting cable between the technology unit
and the SK 2xxE should not be longer than 30m.
1. Mount the SK T14-TU-BUS connecting unit with
adhered seal on the wall-mounting kit. To do this:
Insert the 2 x cheese-head screws (enclosed with
wall-mounting kit) into the (countersunk) holes
from the outside and with the 2 x bolts (enclosed
with the wall-mounting kit) securely screw both
components together from the inside (BUS
connection unit).
2. Make a suitable cable connection between the technology unit and the frequency inverter. Take care that
there is appropriate screw fitting and sealing of the modules. The cable sets enclosed with the BUS
connection unit are not used.
3. Fit and screw on the SK TU4 module.
18 Subject to technical amendments BU 0220 GB-0912
Page 19
2 Assembly and installation
WARNING
THE DEVICES MUST BE EARTHED.
Safe operation of the devices requires that is installed and commissioned by qualified personnel
in compliance with the instructions provided in this Manual.
In particular, the general and regional installation and safety regulations for work on high voltage
systems (e.g. VDE) must be complied with as must the regulations concerning correct use of tools
and the use of personal protection equipment.
Dangerous voltages can be present at the motor connection terminals of the frequency inverter
even when the inverter is switched off. Always use insulated screwdrivers on these terminal fields.
Ensure that the input voltage source is not live before setting up or changing connections to the
unit.
Make sure that the inverter and motor are specified for the correct supply voltage.
Outgoing cable, fixed
connection e.g. for system
bus or 24V supply
Incoming cable, fixed
connection e.g. for system
bus or 24V supply
Cable gland for system bus cable pair
and 24V supply for direct attachment
to SK 200E
No function,
do not use
Diagnostic access
RJ 12 socket
Cable gland for system bus cable pair
and 24V supply for direct attachment
to SK 200E
M16 cable gland or installation of M12 round plug connection for:
incoming and outgoing PROFIBUS DP cable
24V and 24V (for DO) supply
System bus
I/O peripherals: sensors and actuators
2.2 Electrical connection
2.2.1 Cable gland
Both the SK 200E connection unit and the bus module provide extensive facilities for the connection of all the
required cables. The cables may enter the housing via cable glands and be connected to the terminal bar.
However, appropriate round plug connections (e.g.: M12 round plug connectors in M16 cable glands) may be
fitted in order to provide a plug-in solution.
BU 0220 GB-0912 Subject to technical amendments 19
Page 20
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Name
Data
Rigid cable cross-section
0.14 … 2.5mm²
Flexible cable cross-section
0.14 … 1.5mm²
AWG standard
AWG 26-14
Tightening torque (for screw terminals)
0.5 … 0.6Nm
NOTE
The PROFIBUS DP is already installed in the customer unit with voltage isolation from the
other signal connections.
In case of EMC problems, voltage separation of the field bus supply, the digital inputs and
system bus interface and for the external technology unit also for the two additional digital
outputs should be provided.
NOTE
The cable shielding must be connected to the functional earthing 1 (usually the
electrically conducting mounting plate) in order to prevent EMC interference in the
device.
In order to achieve this, for PROFIBUS DP connections it is mandatory that the metallic
metric EMC screws are used for the connection of the PROFIBUS DP shielding lead to the
frequency inverter or the housing of the technology unit. This ensures a wide area
connection of the functional earthing.
1
2.2.2 Control connections
The PROFIBUS DP modules must be provided with a 24V DC (±20%, 100mA) control voltage. Wire end
sleeves must be used for flexible cables.
Within the terminal box (unshielded cable section) the data cables (e.g. PROFIBUS DP, system bus) must be
installed as short as possible and of equal length. Associated data cables (e.g.: Sys+ and Sys-) must be
twisted.
In systems, electrical equipment is usually connected to a functional earth. This serves as a means to dissipate leakage
and interference currents in order to ensure EMC characteristics and must therefore be implemented according to high
frequency technology aspects.
20 Subject to technical amendments BU 0220 GB-0912
Page 21
2.2.2.1 Control connections SK CU4-PBR
NOTE
Looping of the 24V supply voltage (terminals 40/44) is possible, however a maximum
current load of 2A for the SK CU4-PBR must not be exceeded.
46
81
82
47
83
46
81
82
44
40
78
77
C2
C1
40
44
PBR A
PBR B
PBR A
PBR B
Sys+
Sys-
GND B
GND B
VP +5V
Incoming
PROFIBUS DP cable
Outgoing
PROFIBUS DP cable
Connection of the 24V power
supply from the SK 2xxE
System bus connection
from the SK 2xxE
Potential level: System bus
Potential level: Field bus
24V
GND
Connection to the
terminal block of the SK CU4-PBR
SK CU4-
SK 2xxE-
The terminal bar of the customer unit SK CU4-PBR is divided into two potential levels.
2 Assembly and installation
Connection of up to 2 sensors is made on the terminal bar (terminals C1 and C2).
BU 0220 GB-0912 Subject to technical amendments 21
Page 22
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Terminal/
Name
Function
Data
Description / wiring suggestion
Parameter
44 24V
24V supply
(Module, field and system
bus level)
24VDC ±20%
≈ 90mA
reverse polarity protected
max. permissible current
load: 2A
Connection of supply voltage for
module and 24V source for supply
of the digital inputs (DIN1 and
DIN2)
-
40 GND / 0V
Reference potential
for digital signals
-
C1 DIN1
Digital input 1
(I/O PROFIBUS DP DIN1)
Low 0V ... 5V
High 15V ... 30V
Ri = 8.1k
Input capacitance 10nF
Scan rate 1 ms
Each digital input has a reaction
time of 1ms.
Inputs as per EN 61131-2 Type 1
P174
C2 DIN2
Digital input 2
(I/O PROFIBUS DP DIN2)
P174
77 Sys H
System bus
data cable +
System bus
interface
-
78 Sys L
System bus
data cable -
-
40 GND / 0V
Reference potential
for digital signals
24VDC ±20%
≈ 90mA
reverse polarity protected
max. permissible current
load: 2A
Connection of supply voltage for
module and 24V source for supply
of the digital inputs (DIN1 and
DIN2)
-
44 24V
24V supply
(Module, field and system
bus level)
Potential isolation
82 PBR B
(incoming)
Bus +
(red lead)
RxD/TxD-P
RS485 transfer
The use of twisted, shielded twoconductor cable / Type A Profibus
cable is highly recommended
-
81 PBR A
(incoming)
Bus (green lead)
RxD/TxD-N
-
46 GND/
0V BUS
Data ground bus
-
83 RTS
Ready to send
-
47 VO/
5V BUS
+5V bus supply
voltage
Internal Profibus voltage
supply
Note: Must not be used externally!
-
82 PBR B
(outgoing)
Bus
(red lead)
RxD/TxD-P
RS485 transfer
The use of twisted, shielded twoconductor cable / Type A Profibus
cable is highly recommended
-
81 PBR A
(outgoing)
Bus
(green lead)
RxD/TxD-N
-
46 GND/
0V BUS
Data ground bus
-
Control connection details
22 Subject to technical amendments BU 0220 GB-0912
Page 23
2 Assembly and installation
Field bus level
PROFIBUS DP
System bus level and digital inputs
Digital outputs
24V
PB B
IN
PB A
IN
0V-B
RTS
24V
(as 1)
24V
(as 1)
0V
GND
0V
GND
DIN 1
0V
GND
24V
(as 1)
DIN 2
0V
GND
24V
(as 1)
24V 2
DO 1
0V 2
1 3 5 7 9
11
13
15
17
19
21
23
25
27
29
31
33
35 2 4 6 8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
24V
(as 1)
PB B
OUT
PB A
OUT
0V-B
(as 8)
+5V B 24V
(as 1)
Sys +
Sys -
0V
GND
DIN 3
0V
GND
24V
(as 1)
DIN 4
0V
GND
24V
(as 1)
0V 2
DO 2
0V 2
SK 205E…-Connection unit (SK TI4…)
SK TU4-PBR…-Connection unit (SK TI4-TU-BUS)
Voltage
Source
24V DC
PROFIBUS
Subscriber
X-1
PROFIBUS
Subscriber
X+1
Terminal block of the bus Adapter Unit
SK TI4-TU-BUS and assignment of functions
Potential level: Field bus
Potential level: System bus
Potential level: DOs
2.2.2.2 Control connections of the SK TU4-PBR(-...)
The double spring-loaded terminal bar of the bus connection unit is colour coded, and therefore indicates the
three different potential levels.
Terminals 1 and 2 have the same potential as the 24V terminals of the system bus level (e.g. Terminal 11).
However, electrical connection between these terminals is only implemented by mounting the bus module onto
the bus connection unit. Terminals 1 and 2 must only be used to supply sensors. Looping of a 24V supply must
not be performed via these terminals (1 and 2).
A separate power source can be used for the supply of the DOs. However, it is possible to implement the
supply of the DOs by bridging 24V 2 and 0V 2 to one of the terminals of the system bus level (24V and 0V).
However, in this case it should be noted that there is an increased risk of introducing interference into the bus
cables.
Connection of the sensors and actuators is made via the terminal bar. Alternatively, the SK TU4-PBR-M12
enables the connection of the digital I/Os via the M12 round plug connector (5 pin socket, A-coded) mounted
on the front.
Double use of the inputs via the terminal bar and the M12 round plug connector must be avoided.
Connection example: SK TU4-PBR to SK 205E
BU 0220 GB-0912 Subject to technical amendments 23
Page 24
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
NOTE
The data cables (Terminals 3/4 or Terminals 5/6) or the Terminals 1 and 2 to Terminal 11
are only contacted by mounting the bus module.
NOTE
Looping of the 24V supply voltage or GND is possible (except for Terminals 1 and 2),
however a maximum current load of 3A for the SK TU4-PBR(-…) must not be exceeded.
Only adjacent terminals (e.g.: X5:11/12) may be used for looping.
Terminals 1/2 are preferentially for use with sensors and maximum loads of 500mA.
Wiring of the M12-plug
connector to
SK TU4-…-M12
Coupling detail
Pin numbering
Details of the M12 connections of the SK TU4-…-M12
The special wiring of the M12 round plug connector enables the connection of both single and double sensors,
which are equipped with normal M12 system connectors in the standard sensor/actuator configuration.
With the use of M12 round plug
connectors, the terminal bar
connectors for the digital inputs
(Terminals 19, 20, 25, 26) must not be
used.
24 Subject to technical amendments BU 0220 GB-0912
Page 25
Control connection details
Terminal/
Name
Function
Data
Description / wiring suggestion
Parameter
1 24V
2
24V supply
(Module, field and system
bus level)
24VDC ±20%
≈ 90 mA
reverse polarity protected
Max. permissible current
load: 500mA
Connection of the sensor supply
voltage
via DC/DC converter to Terminal
11.
-
Potential isolation
3 PB B
(incoming)
4
(outgoing)
PBR B
Bus + (red lead)
RxD/TxD-N
RS485 transfer
The use of twisted, shielded twoconductor cable / Type A Profibus
cable is highly recommended
-
5 PB A
(incoming)
6
(outgoing)
PBR A
Bus - (green lead)
RxD/TxD-P
-
7 0V-B
8
Data ground bus
Reference potential for
internal Profibus voltage
supply
-
9 RTS
Ready to send
-
10 5V B
5V bus supply
voltage
Internal Profibus voltage
supply
Note: Must not be used externally!
-
Potential isolation
11 24V
12
13
24V supply
(Module, field and system
bus level)
As for terminal 1
However, max.
permissible current load:
3A
Connection of supply voltage for
module and 24V source for supply
of the digital inputs (DIN1 to DIN4)
-
15 0V
17
18
GND
Reference potential
for digital signals
-
14 Sys +
System bus
data cable +
System bus
interface
-
16 Sys -
System bus
data cable -
-
19 DIN1
Digital input 1
(I/O Profibus DIN1)
Low 0V ... 5V
High 15V ... 30V
Ri = 8.1k
Input capacitance 10nF
Scan rate 1 ms
Inputs as per EN 61131-2
Type 1
Each digital input has a reaction
time of 1ms.
P174
20 DIN3
Digital input 3
(I/O Profibus DIN3)
P174
2 Assembly and installation
BU 0220 GB-0912 Subject to technical amendments 25
Page 26
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Terminal/
Name
Function
Data
Description / wiring suggestion
Parameter
21 0V
22
GND
Reference potential
for digital signals
As for terminal 15
Connection of supply voltage for
module and 24V source for supply
of the digital inputs (DIN1 to DIN4)
-
23 24V
24
24V supply
(Module, field and system
bus level)
As for terminal 1
However, max.
permissible current load:
3A
-
25 DIN2
Digital input 2
(I/O Profibus DIN2)
Low 0V ... 5V
High 15V ... 30V
Ri = 8.1k
Input capacitance 10nF
Scan rate 1 ms
Inputs as per EN 61131-2
Type 1
Each digital input has a reaction
time of 1ms.
P174
26 DIN4
Digital input 4
(I/O Profibus DIN4)
P174
27 0V
28
GND
Reference potential
for digital signals
As for terminal 15
Connection of supply voltage for
module and 24V source for supply
of the digital inputs (DIN1 to DIN4)
-
29 24V
30
24V supply
(Module, field and system
bus level)
As for terminal 1
However, max.
permissible current load:
3A
-
Potential isolation
31 24V2
24V supply
of digital outputs
24VDC -/+20%
Up to 1A, according to
load
reverse polarity protected
Supply voltage connection for
digital outputs (DO1 and DO2)
If necessary, bridge to 24V terminal
-
32 0V2
GND 2
Reference potential
for digital outputs
Ground for digital outputs (DO1
and DO2)
If necessary, bridge to 0V terminal
-
33 DO1
Digital output 1
(I/O Profibus DO1)
Low = 0V
High: 24V
Rated current: 500mA
each
The digital outputs should be used
with a separate 24V supply
P175
34 DO2
Digital output 2
(I/O Profibus DO2)
P175
35 0V2
36
GND 2
Reference potential
for digital outputs
Ground for digital outputs (DO1
and DO2)
If necessary, bridge to 0V terminal
-
26 Subject to technical amendments BU 0220 GB-0912
Page 27
2 Assembly and installation
E.g.: SK CU4-PBR
E.g.: SK 200E
PROFIBUS DP module (view of DIP switch)
SK 200E (internal view)
System bus
termination resistor
Field bus (PROFIBUS DP)
termination resistor
System bus
termination resistor
Customer unit SK CU4-PBR
Technology unit SK TU4-PBR
DIP switch 3 + 8 part
BUS termination
2.2.3 Configuration
The configuration for all PROFIBUS DP module versions is identical. All necessary settings are made using
the hardware via a DIP switch element (3+8 part switching block).
Addressing
Note:
PROFIBUS DP - Address: Setting only via DIP switch in binary code
Permissible address range: 3 … 125 → other addresses result in an error message
Address changes: only become effective after switching the BUS module off and
on again
Termination resistor
The termination of the BUS system is made for the first and last participants by connecting the relevant
termination resistors (DIP switch).
BU 0220 GB-0912 Subject to technical amendments 27
Page 28
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
NOTE
For the termination of the PROFIBUS DP both termination resistors "PB Term" must be set to
"ON".
Area
Meaning
DIP Switch
ON - OFF
Configuration
example
Addressing
No significance
-
-
Address bit 6
26 = 64 0
Address bit 5
25 = 32 0
Address bit 4
24 = 16 0
Address bit 3
23 = 8 8
Address bit 2
22 = 4 4
Address bit 1
21 = 2 2
Address bit 0
20 = 1 0
Example address:
14
BUS
termination
PB Term.
OFF *
PB Term.
OFF *
S-Bus Term.
ON
* in order to terminate the PROFIBUS DP, both DIP switches must be set to "PB Term".
PPO-Type
The PPO type used by the bus master is automatically detected by the PROFIBUS DP modules (SK CU4-PBR
und SK TU4-PBR-…).
Configuration example
A PROFIBUS participant SK TU4-PBR is connected to an SK 200E series frequency inverter via a BUS
connection unit SK T14-TU-BUS. The field bus address (PROFIBUS DP address) is to be "14". The
PROFIBUS DP subscriber is not a final subscriber. The system bus only includes the frequency inverter and
the PROFIBUS DP module. The termination resistor for the system bus is to be set at the frequency inverter.
The DIP switches on the PROFIBUS DP module must be set as follows:
28 Subject to technical amendments BU 0220 GB-0912
Page 29
3 Displays and diagnosis
RJ12
LEDs
Potis
RJ12
LEDs
Potis
PROFIBUS DP module SK CU4-PBR
status LEDs
PROFIBUS DP module unit SK TU4-PBR-M12 with
SK TI4-TU-BUS and SK TIE4-WMK-TU
Status LEDs and viewing window (transparent screw-on
cover) for RJ12 diagnostic interface
Frequency inverter SK 200E
viewing window (transparent screw-on cover) for
diagnostic interface RJ12, status LEDs, potentiometer
3 Displays and diagnosis
Various diagnosis possibilities are available, depending on the device. Operating conditions or errors are
visualised by means of LEDs. PC-based communication or the connection of a parameterisation unit is
possible via an RS232 interface (RJ12 diagnostic socket).
3.1 LED displays
Both the SK 200E frequency inverter and the CANopen modules provide LED status and diagnostic displays to
indicate the various statuses.
A differentiation into 3 categories is made
Module or module-specific displays (S and E or DS and DE)
Displays specific to PROFIBUS DP ((BS)BR and BE)
Status displays for the additional digital I/Os of the module (D1/2 or DI1...4 and DO1/2)
The possible displays differ according to the device.
3.1.1 Device-specific display versions
3.1.1.1 frequency inverter SK200E
LED S/E
The double LED S/E indicates the operating status of the
frequency inverter by change of colour and different flashing
frequencies. A device error is indicated by cyclic red flashing of
the LED. The frequency of the flashing signals corresponds to
the error number (Manual BU 0200).
LEDs BS and BE
The dual LEDsBS (BUS State) and BE (BUS Error) indicate
the status of the system bus communication module. Various
bus communication errors are indicated by means of different
flashing frequencies.
A detailed description of the LED displays of the frequency
inverter can be found in the main manual (BU0200).
BU 0220 GB-0912 Subject to technical amendments 29
Page 30
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
3.1.1.2 Customer unit SK CU4-PBR
LEDs BR (or BS) and BE
The dual LEDs BR (BUS Ready) and BE (BUS Error) indicate the
communication status of the PROFIBUS DP.
LEDs DS and DE
The dual colour LEDs DS (Device State) and DE (Device Error) indicate
the status of the module and the status of the system bus.
LEDs D1 and D2
The single colour LEDs D1 (DIN 1 (Digital input 1)) and D2 (DIN 2 (Digital input 2)) indicate the signal status of the
digital inputs of the PROFIBUS DP module. The corresponding LED lights up in case of a High signal.
A detailed description of the LED displays for this module can be found in Section 3.1.2 "Signal status LEDs".
3.1.1.3 Technology unit SK TU4-PBR (-M12)
LEDs BR (or BS) and BE
The dual LEDs BR (BUS Ready) and BE (BUS Error) indicate the
communication status of the PROFIBUS DP.
LEDs DS and DE
The dual colour LEDs DS (Device State) and DE (Device Error)
indicate the status of the module and the status of the system bus.
LEDs DI1 to DI4 and DO1 and DO2
The single colour LEDs DI1 (DIN 1 (digital input 1)) to DI4 (DIN 4 (digital input 2)) and DO1 (DOUT 1 (digital
output 1) and DO2 (DOUT 2 (digital output 2)) indicate the signal status of the digital inputs or outputs of the
PROFIBUS DP module. The corresponding LED lights up in case of a High signal.
These LEDs are only available in the PROFIBUS DP module SK TU4-PBR-M12.
A detailed description of the LED displays for this module can be found in Section 3.1.2 "Signal status LEDs".
30 Subject to technical amendments BU 0220 GB-0912
This manual only describes the LED signal statuses of the PROFIBUS DP modules. Information for the
frequency inverter LEDs (SK 2xxE) can be found in the relevant manual (BU0200).
3.1.2.1 Module-specific displays
The status of the technology unit or the system bus is indicated by the LEDs DS and DE.
BU 0220 GB-0912 Subject to technical amendments 31
Page 32
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
LED
(dual colour)
BR
Bus Ready
LED
(dual colour)
BE
Bus Error
Meaning
... Slow flashing = 2Hz (0.5s cycle)
OFF
OFF
Technology unit not ready, no control voltage or
system error is indicated
Details: LED flashing code: DS and DE
(Section 3.1.2.1 "Module-specific displays").
ON (green)
OFF
Normal operation, cyclic data exchange via PROFIBUS DP
Flashing 0.5s
(green)
OFF
Technology unit not yet configured from DP master, no cyclic data
exchange
PROFIBUS DP cable not connected
Address error
DP master in STOP
Hardware configuration fault
(e.g. more than 4 frequency inverters are to be accessed)
ON (red):
ON (red):
Communication timeout
"Address monitoring time" in DP master expired
ON (red):
Flashing 0.5s
(red)
Communication timeout
Timeout in process data reception
the time set in parameter (P151) has expired, without new process
data being received
Flashing 0.5s
(red)
Flashing 0.5s
(red)
No communication between technology unit and DP master
Incorrect address range
(Address can be set with DIP switch,
Permissible range: 3 .. 125)
Module faulty
3.1.2.2 PROFIBUS DP displays
The status of the PROFIBUS DP module is indicated by the BR and BE LEDs.
32 Subject to technical amendments BU 0220 GB-0912
Page 33
3 Displays and diagnosis
I/O Channel
Status display
Meaning
Customer unit SK CU4-PBR
LED (green)
Digital input 1
D1
ON
High potential on terminal C1
OFF
Low potential on terminal C1
Digital input 2
D2
ON
High potential on terminal C2
OFF
Low potential on terminal C2
Technology unit SK TU4-PBR-M12(-C)
LED (yellow)
Digital input 1
DI1
ON
High potential on terminal 19 or on M12 socket DI1
OFF
Low potential on terminal 19 or on M12 socket DI1
Digital input 2
DI2
ON
High potential on terminal 25 or on M12 socket DI2
OFF
Low potential on terminal 25 or on M12 socket DI2
Digital input 3
DI3
ON
High potential on terminal 20 or on M12 socket DI3
OFF
Low potential on terminal 20 or on M12 socket DI3
Digital input 4
DI4
ON
High potential on terminal 26 or on M12 socket DI4
OFF
Low potential on terminal 26 or on M12 socket DI4
Digital output 1
DO1
ON
High potential on terminal 33 or on M12 socket DO1
OFF
Low potential on terminal 33 or on M12 socket DO1
Digital output 2
DO2
ON
High potential on terminal 34 or on M12 socket DO1
OFF
Low potential on terminal 34 or on M12 socket DO1
3.1.2.3 I/O Displays
The status of additional digital inputs and outputs on the BUS module is indicated by corresponding LEDs
(except for SK TU4-PBR(-C)).
BU 0220 GB-0912 Subject to technical amendments 33
Page 34
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Terminal/
Name
Function
Data
Description / wiring suggestion
Parameter
Diagnostic access / RJ12, RS485/RS232
1 RS485 A
Data cable RS485
Baud rate
9600…38400Baud
Termination resistor
R=120
to be set by customer at
the final subscriber.
Simultaneous use of several diagnostic sockets with several diagnostic tools may lead to
errors during communication. Therefore, only one diagnostic socket within a system bus
network should be used.
3.2 RJ12 Diagnostic socket
All participants which are coupled via a common system bus (field bus module / frequency inverter (up to 4
devices)) can be read out and edited/parameterised via an RJ12 diagnostic socket. Either the diagnostic socket
of the frequency inverter or that of the BUS connection units can be used. This provides users with a convenient
facility to perform diagnosis and parameterisation from a central point, without having to access the particular
frequency inverter at its location.
Although the customer unit SK CU4-PBR does not have an RJ12 connection, it can be accessed from any other
participant (frequency inverter) on the same system bus.
The bus speed of the diagnostic interface is 38400 baud. Communication is carried out according to the USS
protocol.
The NORDCON software and the ParameterBox SK PAR-3H
are available as diagnostic tools.
For a detailed description of the use of these ParameterBoxes,
please refer to Manual BU0040. The NORDCON software is
available free of charge under www.nord.com. Connection cables
for the SK PAR-3H are included in the scope of delivery of the
box. The necessary cables for connecting the bus module to
the PC (RJ12-SUB/D) can be ordered under the part number
278910240. Adapters for connection to a USB port are
commercially available.
34 Subject to technical amendments BU 0220 GB-0912
Page 35
3 Displays and diagnosis
Underside of SK 200E
8x DIP switches
Terminal/
Name
Function
Data
Description / wiring suggestion
Parameter
Accessory cable (optional) for PC connection
Adapter cable
RJ12 to SUB-D9
... for direct
connection to a PC
with NORD CON
software
Length 3m
Assignment RS 232
(RxD, TxD, GND)
Part. No. 278910240
TxD
RxT
GND
+24V
n.c.
n.c.
Assignment of SUBD9 connector:
Pin2: RS232_TxD
Pin3: RS232_RxD
Pin5: GND
RxD
GND
TxD
6 1 5
9
Device
External
technology unit
Frequency inverter
with address 32
(system bus)
Frequency inverter
with address 34
(system bus)
Frequency inverter
with address 36
(system bus)
Frequency inverter
with address 38
(system bus)
USS
address
30 1 2 3 4
Alternatively, diagnosis can be performed via a Windows PC with the aid of NORD CON software (available free of
charge from www.nord.com). The necessary connection cable (RJ12 - SUB D9) is available from Getriebebau
Nord GmbH as part number 278910240. If necessary, an interface converter from SUB D9 to USB2.0 is
commercially available.
No special settings are required to set up communication with the individual diagnostic tools.
The allocation of addresses is defined via the system bus addressing. The display of the diagnostic tool is
according to the following table, whereby the frequency inverter which is directly connected to the diagnostic
tool is automatically assigned the address “0”.
Note
Setting of the system bus address is carried out via two DIP
switches (DIP 1 and 2) on the underside of the SK 200Efrequency inverter. For further details, please refer to the frequency
inverter manual (BU 0220). The address of the BUS module is
defined as “30”.
BU 0220 GB-0912 Subject to technical amendments 35
Page 36
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Installing GSD files
GSD file selection
4 Commissioning
In order to operate the SK 200E frequency inverter with the PROFIBUS DP protocol, in addition to the bus
connection to the master, the PROFIBUS DP modules must be implemented in the automation concept. This
section describes the hardware planning and network structure on the basis of a SIMATIC S7 project with
diagrams from the planning tool STEP 7. In addition, several parameters for the PROFIBUS DP connection must
be changed and set in the frequency inverter (Section 5"Parameterisation").
4.1 GSD file
The GSD file (Device Master Data file) must be integrated into the engineering system for the DP master for
configuration and setup of the PROFIBUS network. For this, in the HW config. mask of the SIMATIC Manager, the
function install GSD files must be executed under the menu item Extras. For the integration of the GSD files, no
other project must be open in the Hardware config.
For SK 200E applications on PROFIBUS DP, the GSD file NORD0BA8.GSD must be installed, as this is the only
file which contains the SK xU4-PBR (-M12) with DPV1 functionality. This file is contained on the documentation
CD, which is provided with the hardware. Updates on a daily basis are available on www.nord.com.
4.2 Hardware configuration: Configuration of the PROFIBUS DP Technology Unit
After the DP master has been planned and the PROFIBUS
DP has been linked, DP slave can be selected from the
catalogue and copied onto the network bus string.
After installation of the GSD file (NORD0BA8.GSD), the DP
slaves from Getriebebau NORD are saved in the directory
"PROFIBUS-DP/Weitere FELDGERÄTE/Antriebe/NORD".
After this, the configuration mask for the planned NORD
drive unit can be opened by clicking on the DP slave symbol
in the configuration mask.
Allocation of the DP slave participants to the PROFIBUS DP
is then carried out.
The number of frequency inverters to be operated on a
technology unit must then be defined. This results in the
number of PPO type modules to be integrated in the Hardware config. of STEP 7.
A separate PPO module in the DP slave must be used for the input and output data of each connected
SK 200E frequency inverter. This must be configured on the corresponding slot of the participant.
36 Subject to technical amendments BU 0220 GB-0912
Page 37
4 Commissioning
PROFIBUS address
Setting the PROFIBUS DP with DIP switches (Section 2.2.3
"Configuration
")
Integration of the DP slave (technology
unit) on the PROFIBUS DP
Select the components from the catalogue and integrate
them into the PROFIBUS DP string.
The frequency inverters connected to
the technology unit must be defined
Specification of the frequency inverter designation and
allocation of the associated addresses / slot allocation.
Configuration of the DP slave
Assign the names and addresses
Selection of PPO types
Each frequency inverter must be assigned a PPO type
(parameterise on the appropriate slot)
Technology unit I/Os
For the use of additional technology unit I/Os, the Profibus
module I/O must be integrated into Slot 1 of the DP slave
Slot
Cyclic process data
transfer
Device
1
Profibus I/O Modules
Technology unit I/Os
2
PPO type 1 to 4
Frequency inverter 1
3
PPO type 1 to 4
Frequency inverter 2
4
PPO type 1 to 4
Frequency inverter 3
5
PPO type 1 to 4
Frequency inverter 4
Index
Acyclic parameter
transfer
Device
100
only parameter data
Technology unit
101
only parameter data
Frequency inverter 1
102
only parameter data
Frequency inverter 2
103
only parameter data
Frequency inverter 3
104
only parameter data
Frequency inverter 4
Configuration steps
The following items must be configured in the planning of an SK CU4-… or SK TU4-PBR(-M12) technology
unit:
4.2.1 DP slave slot assignment
The following slot assignments must be observed in the DP slave for the planning of frequency inverters:
Cyclic data traffic
The assignment of the input and output address ranges to the frequency inverters is made via the assignment
of the slot position.
Acyclic data traffic
The assignment of acyclic data packages to the individual frequency inverters and the technology unit is not
carried out via the slot position, but rather via Slot 0 and the relevant index (Table):
Therefore no settings and configurations are required in the Hardware config. of the SIMATIC Manager are
necessary for the use of acyclic data traffic for the transfer of parameter data.
BU 0220 GB-0912 Subject to technical amendments 37
Page 38
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
NORD Modules
The system modules SFB 52 "RDREC" (read record) and SFB 53 "WRREC" to be used for acyclic data traffic in
the PLC program sequence access Slot 0 via the "diagnosis address" of the PROFIBUS DP technology unit.
The "diagnosis address" can be read out via the "object properties" of the DP slave.
Use of these system modules requires additional details of the index (see previous table) and the length,
whereby due to the transfer of parameter data via the USS protocol (includes parameter data transfer), the
length is always 8 byte (see also Section 7.2 "PROFIBUS DP PPO types").
4.2.2 Definition of PPO types
For cyclic data traffic, the Parameter- Process data Object (PPO) with which the
process data (PZD) is transferred from the DP master to the frequency inverter is
defined. The following settings may be selected:
Universal module no function
Empty Empty slot
PPO type 1 to 4 for PKW and PZD
Profibus I/O Modules to control additional input and output
signals of the bus module
4.2.2.1 Universal module
A universal module is not defined. This setting has no function.
4.2.2.2 Empty
The setting Empty must always be selected if there is no device (frequency inverter) connected to the slot or
the I/Os of the BUS module are not to be accessed.
4.2.2.3 PPO type 1 to 4
The setting of the PPO types is reserved for the connected frequency inverters (integrated into "Slots 2 - 5").
Here, each frequency inverter must be assigned the intended (required) PPO type.
With PPO types 1 and 2, both process data and parameters can be cyclically communicated between the DP
master and the frequency inverter.
With PPO types 3 and 4, only process data is transferred.
More detailed information about PPO type definitions is given in Section 7.2 "PROFIBUS DP PPO types".
The PROFIBUS DP modules (SK CU4-PBR and SK TU4-PBR-…) are equipped with an automatic PPO type
detection.
38 Subject to technical amendments BU 0220 GB-0912
Page 39
4 Commissioning
NOTE
The digital inputs of the PROFIBUS DP modules (SK CU4-PBR and SK TU4-PBR-…) cannot
be directly assigned with frequency inverter functionalities. These must be transferred via the
PROFIBUS and can be returned to the frequency inverter from the bus master via bits 8 and 9
of the control word by assignment of the required function in the BUS I/O In bits (P480 [-11] or
[-12]).
PLC I/Os
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Inputs
n. c.
n. c.
n. c.
n. c.
DIN4
DIN3
DIN2
DIN1
Outputs
n. c.
n. c.
n. c.
n. c.
n. c.
n. c.
DO2
DO1
4.2.2.4 Profibus I/O Modules
This setting variant is exclusively reserved for the PROFIBUS DP module SK CU4-PBR or SK TU4-PBR…)
which is connected to the system bus. This setting enables the DP master to directly access the digital I/Os of
the module. In this 1 byte module, the digital outputs must be set as "output byte" and the digital inputs as
"input byte".
The "Profibus module I/O" must always be set to Slot 1 in the DP slave.
If the additional I/Os are not used, an "empty module" must be set on Slot 1.
The bits are allocated to the inputs and outputs as follows:
BU 0220 GB-0912 Subject to technical amendments 39
Page 40
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
DP slave properties
Access monitoring setting
ATTENTION
In case of errors, disabling of access monitoring can result in the outputs of the affected
slaves not being set to "0". It is therefore strongly recommended that the access monitoring
is only disabled for test purposes during commissioning.
4.2.3 Timeout monitoring
There are two different communication monitoring variants.
4.2.3.1 Access monitoring of DP master
Access monitoring is a monitoring function which is controlled by the PROFIBUS DP master. With this, the DP
master communicates a calculated time interval to each DP slave, within which a communication step must
take place. If this time interval is exceeded the DP slave exits the "data exchange mode" and switches to the
so-called safe mode. The frequency inverter to which it is connected is set to error status (Error E010 → 10.2).
During system planning, the access monitoring time is automatically calculated for the entire PROFIBUS DP
network by the software tool STEP 7 / SIMATIC Manager. This value usually corresponds to 6x the "worst
case" cycle time, and is in the range between 10ms to 650s.
The access monitoring serves as a protective function against incorrect parameterisation or failure of the
transfer facilities and can by explicitly enabled or disabled for each individual DP slave.
4.2.3.2 DP slave watchdog
The technology unit provides an additional timeout monitoring function. This can be enabled by the user in
parameter (P151) "External bus timeout" and set in ms steps. The time-out time must be set to at least 2x the value of the Profibus cycle time in parameter (P151). This watchdog function is started on receipt of the
first valid PROFIBUS DP telegram (STW Bit 10 = "1" signal ("Process data valid")).
If all process data telegrams (PZD) are declared as invalid (STW Bit 10 = "0") the error message E10.2 is
generated. The bus module switches off all of its outputs (0V). This situation occurs if the automation device is
in STOP mode and the PROFIBUS DP master continues to send telegrams with data content "0".
As long as one of the connected frequency inverters is still in an error status, i.e. an error message has not
been acknowledged, the technology unit remains in timeout error status.
40 Subject to technical amendments BU 0220 GB-0912
0 = Monitoring OFF
1 = Auto, communication is only monitored if an
existing communication is interrupted. If a
module which was previously present is not
found after switching on the mains, this does
not result in an error
Monitoring only becomes active when an
extension starts communication with the FI.
2 = Monitoring active immediately; the FI starts
monitoring the corresponding module
immediately after it is switched on. If the
module is not detected on switch-on, the FI
remains in the status "not ready for switch-on"
for 5 seconds and then triggers an error
message.
5 Parameterisation
In order to enable communication via PROFIBUS DP, the frequency inverter and the PROFIBUS DP
technology Unit must be parameterised accordingly.
With the PROFIBUS DP protocol, the inverter parameters are mapped in the range 1000 to 1999, i.e. for
parameterisation via the bus in cyclic data traffic (PPO type 1 or 2) 1000 must be added to the parameter
numbers (e.g. (P508) - (P1508).
5.1 Parameterisation of frequency inverter SK 200E
The following list of parameters for the frequency inverter series SK 200E are directly relevant for the operation
of the frequency inverter via PROFIBUS DP. A complete list of parameters for the frequency inverter
(SK 200E) can be found in the relevant manual (BU0200).
5.1.1 Basic parameters (P100)
BU 0220 GB-0912 Subject to technical amendments 41
Page 42
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
In the SK 200E, up to 4 freely programmable digital inputs are available. The only restriction is
with the versions SK 215E and SK 235E. Here, the fourth digital input is always the input for the
function "Safe Stop".
… [-01] = Digital input 1 (DIN1), Enable right as factory setting, control terminal 21
… [-02] = Digital input 2 (DIN2), Enable left as factory setting, control terminal 22
… [-03] = Digital input 3 (DIN3), fixed frequency 1 (P465 [-01]) as factory setting,
control terminal 23
… [-04] = Digital input 4 (DIN4), fixed frequency 2 (P465 [-02]) as factory setting,
(not with SK 215/235E "Safe Stop"), control terminal 24
Various functions can be programmed. For the complete list, please refer to the SK 200E
frequency inverter manual (BU0200).
NOTE: The additional digital inputs of the field bus group are managed via parameter (P480).
Value
Function
Description
Signal
00
No function
Input switched off.
---
…
141
Remote control
With bus system control, Low level switches the control to control
via control terminals.
High
…
1
Also effective for bus control (RS232, RS485, CANbus, CANopen, DeviceNet, Profibus, InterBus, AS-Interface)
5.1.2 Control clamp parameter (P400)
Excerpt...
42 Subject to technical amendments BU 0220 GB-0912
The Bus I/O In Bits are perceived as digital inputs. They can be set to the same functions
(P420).
These I/O bits can also be used in combination with the AS Interface (SK 225E or SK 235E) or
the I/O extension (SK CU4-IOE or SK TU4-IOE).
… [-01] = Bus I/O In Bit 0
… [-02] = Bus I/O In Bit 1
… [-03] = Bus I/O In Bit 2
… [-04] = Bus I/O In Bit 3
… [-05] = Bus I/O In Bit 4
… [-06] = Bus I/O In Bit 5
… [-07] = Bus I/O In Bit 6
… [-08] = Bus I/O In Bit 7
… [-09] = Flag 1
… [-10] = Flag 2
… [-11] = Bit 8 BUS control word
… [-12] = Bit 9 BUS control word
The possible functions for the bus In bits can be found in the table of functions for the digital
inputs in parameter P420.
The bus I/O Out bits are perceived as multi-function relay outputs. They can be set to the same
functions (P434).
These I/O bits can also be used in combination with the AS Interface (SK 225E or SK 235E) or
the I/O extension (SK CU4-IOE or SK TU4-IOE).
… [-01] = Bus I/O Out Bit 0
… [-02] = Bus I/O Out Bit 1
… [-03] = Bus I/O Out Bit 2
… [-04] = Bus I/O Out Bit 3
… [-05] = Bus I/O Out Bit 4
… [-06] = Bus I/O Out Bit 5
… [-07] =Flag 1
… [-08] = Flag 2
… [-09] = Bit 10 BUS status word
… [-10] = Bit 13 BUS status word
The possible functions for the Bus Out Bits can be found in the table of functions for the relay
P434.
P482 ... [-01]
...
... [-08]
Standardisation of bus I/O Out bits
-400 … 400 %
{ all 100 }
Adjustment of the limit values of the bus Out bits. For a negative value, the output function will
be output negative.
Once the limit value is reached and positive values are delivered, the output produces a High
signal, for negative setting values a Low signal.
P483 ... [-01]
...
... [-08]
Hysteresis of bus I/O Out bits
S
1 … 100 %
{ all 10 }
Difference between switch-on and switch-off point to prevent oscillation of the output signal.
BU 0220 GB-0912 Subject to technical amendments 43
Page 44
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P509
Source Control Word
S
0 ... 4
{ 0 }
Selection of the interface via which the FI is controlled.
0 = Control terminals or keyboard control** with the SimpleBox (if (P510)=0), the
ParameterBox or via BUS I/O Bits.
1 = Only control terminals *, the FI can only be controlled via the digital and analog input
signals or via the Bus I/O Bits.
2 = USS control word *, the control signals (enable, rotation direction, etc.) are transferred
via the RS485 interface, the setpoint via the analog input or the fixed frequencies.
3 = System bus *, the control signals (enable, direction of rotation, ...) are transferred via the
system bus (the field bus module and the frequency inverter communicate via the
system bus). I.e. the setting "3" - "System bus" must be selected in parameter (P509)
for control of the frequency inverter via the field bus.
4 = System bus broadcast *
*) Keyboard control (SimpleBox, ParameterBox, PotentiometerBox) is disabled,
parameterisation is still possible.
**) If the communication during keyboard control is interrupted (time out 0.5 sec), the
FI will disable without an error message.
NOTE:
For details of the optional bus systems, please refer to the relevant supplementary bus manuals
(BU02x0).
- www.nord.com –
As an alternative to setting the parameter, System Bus can also be selected with DIP switch 3.
P510 ... [-01]
... [-02]
Setpoint source
S
0 ... 4
{ [-01] = 0 }
{ [-02] = 0 }
Selection of the setpoint source to be parameterised.
… [-01] = Main setpoint source
… [-02] = Subsidiary setpoint source
Selection of the interface via which the FI receives the setpoint.
0 = Auto: The setpoint source is automatically derived
from the setting in the parameter P509 >Control
word source<.
1 = Control terminals, digital and analog inputs
control the frequency, including fixed frequencies
2 = USS
3 = System bus
4 = System bus broadcast
P513
Telegram time-out
S
-0.1 / 0.0 /
0.1 ... 100.0 sec
{ 0.0 }
Monitoring function of the active bus interface. Following receipt of a valid telegram, the next
one must arrive within the set period. Otherwise the FI reports an error and switches off with the
error message E010 >Bus Time Out<.
0.0 = Off: Monitoring is switched off.
-0.1 = no error: Even if communication between BusBox and FI is interrupted (e.g. 24V error,
Box removed, etc.), the FI will continue to operate unchanged.
Note:
In BUS mode (e.g.: PROFIBUS DP), monitoring is controlled via parameter (P120). Settings in
parameter (P513) therefore have no effect.
Exception: Setting {-0,1}
5.1.3 Supplementary parameters (P500)
44 Subject to technical amendments BU 0220 GB-0912
Page 45
5 Parameterisation
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P514
CAN baud rate (system bus)
S
0 ... 7
{ 5 }**
Setting of the transfer rate (transfer speed) via the system bus interface. All bus participants
must have the same baud rate setting.
0 = 10kBaud
1 = 20kBaud
2 = 50kBaud
3 = 100kBaud
4 = 125kBaud
5 = 250kBaud**
6 = 500kBaud
7 = 1Mbaud *
*) Reliable operation cannot be guaranteed
**) for communication with the bus module, the parameter must be left at the factory setting
(250kBaud) otherwise no communication is possible.
P515 ... [-01]
…... [-03]
CAN address (system bus)
S
0 ... 255 dec
{ all 32 dec}
or { all 20 hex}
Setting of the system bus address.
… [-01] = Receive address for system bus
… [-02] = Broadcast – Receive address for system bus (slave)
… [-02] = Broadcast – Transmit address for system bus (master)
NOTE:
If up to four SK 200E are to be linked via the system bus, the addresses must be set as follows
FI 1 = 32, FI 2 = 34, FI 3 = 36, FI 4 = 38.
The system bus addresses should be set via the DIP switches 1/2 (Section 2.2.3).
The return value can be selected for bus actuation in this parameter.
NOTE:For further details, please refer to the description for P418.
… [-01] = Actual bus value 1
… [-02] = Actual bus value 2 (only for PPO Type 2 or 4)
… [-03] = Actual bus value 3 (only for PPO Type 2 or 4)
Possible values which can be set:
0 = Off
1 = Actual frequency
2 = Actual speed
3 = Electricity
4 = Torque current (100% = P112)
5 = State of digital inputs and outputs 2
6 = ... 7 Reserved
8 = Setpoint frequency
9 = Error number
10 = ... 11 Reserved
12 = Bus Out bits 0...7
13 = ... 16 Reserved
17 = Value analog input 1 (BU0200)
18 = Value analog input 2 (BU0200)
19 = Setpoint frequency master value (P503)
20 = Setpoint frequency after master value
ramp
21 = Actual frequency without master value slip
22 = Speed from encoder
23 = Actual frequency with slip
24 = Master value, actual freq. with slip
2
The assignment of the dig. inputs for P543 = 5
Bit 0 = DigIn 1
Bit 4 = PTC input
Bit 8 = DigIn 5
Bit 12 = DigOut 1
BU 0220 GB-0912 Subject to technical amendments 45
Bit 1 = DigIn 2
(FI)
Bit 5 = Reserved Bit 6 = DigOut 3
[FI]
(DI1, 1.SK…IOE)
(FI)
Bit 9 = DigIn 6
Bit 13 = mech. brake
Bit 2 = DigIn 3
(FI)
(DI2, 1.SK…IOE)
Bit 10 = DigIn 7
Bit 14 = DigOut 2
(FI)
Bit 3 = DigIn 4
(FI)
(DO1, 1.SK…IOE)
(DI3, 1.SK…IOE)
(FI)
Bit 7 = DigOut 4
Bit 11 = DigIn 8
(FI)
(DO2, 1.SK…IOE)
(DI4, 1.SK…IOE)
Bit 15 = Reserved
Page 46
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
In this parameter, a function is allocated to the output setpoint during bus actuation.
NOTE:For further details, please refer to the description for P400.
… [-01] = Bus setpoint value 1
… [-02] = Setpoint bus value 2 (only for PPO Type 2 or 4)
… [-03] = Setpoint bus value 3 (only for PPO Type 2 or 4)
Possible values which can be set:
0 = Off
1 = Setpoint frequency (16 bit)
2 = Frequency addition
3 = Frequency subtraction
4 = Minimum frequency
5 = Maximum frequency
6 = PI process controller actual value
7 = PI process controller setpoint
8 = Actual frequency PI
9 = Actual PI frequency limited
10 = Actual PI frequency monitored
11 = Limiting torque current
12 = Torque current switch-off limit
13 = Limiting current
14 = Current switch-off limit
15 = Ramp time
16 = Lead torque (P214) multiplication
17 = Multiplication
18 = Curve travel calculator
19 = Servo mode torque
20 = BusIO In Bits 0-7
21 = ...24 reserved for Posicon
31 = Digital output IOE
32 = Analog output IOE
46 Subject to technical amendments BU 0220 GB-0912
Page 47
5 Parameterisation
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P552… [-01]
… [-02]
System bus master cycle time
S
0 / 0.1 … 100.0 ms
{ 0 }
In this parameter, the cycle time for the system bus master mode and the CAN open encoder is
set (see P503/514/515):
… [01] = Cycle time for system bus master functions
… [02] = Cycle time for system bus absolute value encoder
With the setting 0 “Auto” the default value (see table) is used.
According to the Baud rate set, there are different minimum values for the actual cycle time:
Baud rate
Minimum value tZ
Default system bus master
Default system bus abs.
10kBaud
10ms
50ms
20ms
20kBaud
10ms
25ms
20ms
50kBaud
5ms
10ms
10ms
100kBaud
2ms
5ms
5ms
125kBaud
2ms
5ms
5ms
250kBaud
1ms
5ms
2ms
500kBaud
1ms
5ms
2ms
1000kBaud:
1ms
5ms
2ms
P560
Save in EEPROM
S
0 ... 1
{ 1 }
0 = Changes to the parameter settings are no longer saved on the EEPROM. Previously
saved settings remain stored, even if the FI is disconnected from the mains; however
new changes are not saved after a mains failure.
1 = All parameter changes are automatically written to the EEPROM and remain stored there
even if the FI is disconnected from the mains supply.
NOTE:If BUS communication is used to implement parameter changes, it must be
ensured that the maximum number of write cycles (100,000 x) in the EEPROM is
not exceeded.
BU 0220 GB-0912 Subject to technical amendments 47
Page 48
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P700
Actual error
0.0 ... 21.4
Actual error present. Further details are described in the frequency inverter manual (BU0200).
SimpleBox: Descriptions of the individual error numbers can be found in the point Error
messages.
ParameterBox: Errors are displayed in plain text, further information can be found in the point
Error messages.
P701 ... [-01]
...
... [-05]
Last fault 1...5
0.0 ... 21.4
This parameter stores the last 5 faults. Further details are described in the frequency inverter
manual (BU0200).
With the SimpleBox the corresponding memory location 1...5 (Array parameter), must be
selected and confirmed with the ENTER key in order to read the stored error code.
P740... [-01]
…
... [-13]
Process data bus In
S
0000 ... FFFF (hex)
This parameter provides information about the actual control word (STW) and the setpoints
(SW1-3) that are transferred via the bus systems.
For values to be displayed, a bus system must be selected in P509.
Setpoint data from main setpoint P510 - 01.
… [-05 ] = Bus I/O In Bits (P480)
The displayed value depicts all Bus In Bit sources
linked with or.
… [-06 ] = Parameter data In 1
… [-07 ] = Parameter data In 2
… [-08 ] = Parameter data In 3
… [-09 ] = Parameter data In 4
… [-10 ] = Parameter data In 5
Data during parameter transfer: Order label (AK),
Parameter number (PNU),
Index (IND), Parameter value (PWE 1/2)
Setpoint data from master function value
(Broadcast), if P509/510 = 4 (P502/P503)
5.1.4 Information parameters (P700)
48 Subject to technical amendments BU 0220 GB-0912
Page 49
5 Parameterisation
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P741... [-01]
...
... [-10]
Process data bus Out
S
0000 ... FFFF (hex)
This parameter provides information about the actual status word and the actual values that are
transferred via the bus systems.
... [-01] = Status word
Status word
... [-02] = Actual value 1 (P543 [-01])
... [-03] = Actual value 2 (P543 [-02])
... [-04] = Actual value 3 (P543 [-03])
... [-05] = Bus I/O Out Bit (P481)
The displayed value depicts all Bus Out Bit sources
linked with or.
... [-06] = Parameter data Out 1
... [-07] = Parameter data Out 2
... [-08] = Parameter data Out 3
... [-09] = Parameter data Out 4
... [-10] = Parameter data Out 5
Data during parameter transfer.
P748
System bus status
0000 ... FFFF (hex)
or
0 ... 65535 (dec)
Shows the status of the system bus.
Bit 0:
Bit 1:
Bit 2:
Bit 3:
Bit 4:
Bit 5:
Bit 6:
Bit 7:
Bit 8:
Bit 9:
Bit 10:
24V Bus supply voltage
CANbus in "Bus Warning" status
CANbus in "Bus Off" status
Bus module is online
Additional module 1 is online
Additional module 2 is online
The protocol of the CAN module is 0 = CAN / 1 = CANopen
Vacant
"Bootup Message" sent
CANopen NMT State
CANopen NMT State
CANopen NMT State
Bit 10
Bit 9
Stopped
Pre-Operational
Operational
0
0
1
0
1
0
P749
DIP switch status
0000 ... 01FF (hex)
or
0 ... 511 (dec)
This parameter shows the actual setting of the FI DIP switch "S1" (See BU0200).
BU 0220 GB-0912 Subject to technical amendments 49
Page 50
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P150
Set relays
0 ... 4
{ 0 }
0 = Via bus
1 = Outputs OFF
2 = Output 1 to (DO1)
3 = Output 2 to (DO2)
4 = Outputs 1 and 2 ON
P151
Timeout for external bus
0 ... 32767 ms
{ 0 }
Monitoring function of the relevant active bus technology unit. Following receipt of a valid
telegram, the next one must arrive within the set period. Otherwise the inverter reports an error
and switches off with the error message E010 / E10.3 >Bus Time Out<.
0 = Off: Monitoring is switched off.
Behaviour is identical to parameter (P513) telegram timeout for SK 200E.
NOTE: The time-out time must be set to at least 2x the value of the Profibus cycle time
in parameter (P151).
P152
Factory setting
0 ... 1
{ 0 }
By selecting the appropriate value and confirming it with the ENTER key, the selected
parameter range is entered in the factory setting. Once the setting has been made, the value of
the parameter returns automatically to 0.
0 = No change: Does not change the parameterisation.
1 = Load factory settings: The complete parameterisation of the FI is reset to the factory
setting. All originally parameterised data are lost.
P153 ... [-01]
... [-02]
Minimum system bus cycle
0 ... 250 ms
{ [-01] = 10 }
{ [-02] = 5 }
Reduction of the bus load on the system bus by adjustment of the minimum cycle time (inhibit
time):
… [-01] = SDO Inhibit time
… [-02] = PDO inhibit time
P154 ... [-01]
... [-02]
TB-IO access
0 ... 5
{ [-01] = 0 }
{ [-02] = 0 }
SW V1.1R0 and
higher
Direct access to the frequency inverter via 2 digital inputs and/or 2 digital outputs of the bus
module SK xU4-PBR:
… [-01 ] = Access to inputs
Definition of functions:
DigIn1 of the bus module (P480[-11])
DigIn2 of the bus module (P480[-12])
… [-02] = Access to outputs
DigOut1 of bus module (P481[-09])
DigOut2 of bus module (P481[-10])
Settings:
3 = No effect: The IOs are not evaluated by the FI.
Bits 8 and 9 of the control word can be set or
read out via the PLC. (Section 7.2.1.7, 7.2.1.8)
4 = Broadcast: (This setting can only be used with
(P154[-01])) - All FIs read the inputs, the
settings for (P154[-02]) have no effect.
5 = FI 1: reads and writes the IO
6 = FI 2: reads and writes the IO
7 = FI 3: reads and writes the IO
8 = FI 4: reads and writes the IO
5.2 Parameterisation of the bus module (SK CU4-… or SK TU4-…)
The following parameters affect the bus modules.
5.2.1 BUS module standard parameters (P150)
50 Subject to technical amendments BU 0220 GB-0912
Page 51
5.2.2 BUS module information parameters, general (P170)
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P170 ... [-01]
... [-02]
Actual error
0 ... 9999
Further details in Section 6.2 "Error messages".
… [-01 ] = Current module error
… [-02 ] = Last module error
Possible values:
1000 = EEPROM error
1010 = System bus 24V missing
1020 = System bus timeout (see time in P151)
1030 = System bus OFF
Specific to PROFIBUS DP
5000 = PROFIBUS ASIC error
5010 = PROFIBUS address incorrect
5020 = PROFIBUS timeout
P171 ... [-01]
...
... [-03]
Software version/ Revision
0,0 ... 9999.9
This parameter shows the software and revision numbers in the module. Array 03 provides
information about any special versions of the hardware or software A zero stands for the
standard version.
… [-01] = Software version
… [-02] = Software revision
… [-03] = Special version
P172
Configuration
0 ... 2
The version can be queried in this parameter.
Possible values:
0= internal module
1= external module
2 = Bus TO via SPI
5 Parameterisation
BU 0220 GB-0912 Subject to technical amendments 51
Page 52
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P173
Module status
0 ... FFFF (hex)
Possible values:
Bit 0 = Bus status “PREOPERATIONAL” (PROFIBUS DP initialisation active)
Bit 1 = Bus status “OPERATIONAL” (Data exchange active)
Bit 2 = Node-guarding timeout (PROFIBUS DP master watchdog)
Bit 3 = Timeout (time in P151)
Bit 4 = Module system error
Bit 5 = Reserved
Bit 6 = System bus “BUS WARNING”
Bit 7 = System bus “BUS OFF”
Bit 8 = Status FI 1
Bit 9 = Status FI 1
Bit 10= Status FI 2
Bit 11= Status FI 2
Bit 12= Status FI 3
Bit 13= Status FI 3
Bit 14= Status FI 4
Bit 15= Status FI 4
Status for FI x:
Bit High Bit Low Status
0 0 FI is offline
0 1 unknown FI
1 0 FI is online
1 1 FI missing or switched off
P174
Digital inputs
0 ... 15
Instantaneous view of input level logic.
Possible values:
Bit 0= Input 1 (DIN1 of the bus module)
Bit 1= Input 2 (DIN2 of the bus module)
Bit 2= Input 3 (DIN3 of the bus module)
Bit 3= Input 4 (DIN4 of the bus module)
P175
Digital outputs
0 ... 3
Instantaneous view of output level logic.
Possible values:
Bit 1= Output 1 (DO1 of the bus module)
Bit 2= Output 2 (DO2 of the bus module)
52 Subject to technical amendments BU 0220 GB-0912
Page 53
5 Parameterisation
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P176 ... [-01]
...
... [-17]
Process data bus In
-32768 ... 32767
Bus data received from PROFIBUS DP master
… [-01] = Bus module outputs
… [-02] = Control word FI 1
… [-03] = Setpoint 1 for FI 1
… [-04] = Setpoint 2 for FI 1
… [-05] = Setpoint 3 for FI 1
… [-06] = Control word FI 2
… [-07] = Setpoint 1 for FI 2
… [-08] = Setpoint 2 for FI 2
… [-09] = Setpoint 3 for FI 2
… [-10] = Control word FI 3
… [-11] = Setpoint 1 for FI 3
… [-12] = Setpoint 2 for FI 3
… [-13] = Setpoint 3 for FI 3
… [-14] = Control word FI 4
… [-15] = Setpoint 1 for FI 4
… [-16] = Setpoint 2 for FI 4
… [-17] = Setpoint 3 for FI 4
P177 ... [-01]
...
... [-17]
Process data bus Out
-32768 ... 32767
Bus data transmitted to PROFIBUS DP master
… [-01] = Bus module inputs
… [-02] = Status word FI 1
… [-03] = Actual value 1 for FI 1
… [-04] = Actual value 2 for FI 1
… [-05] = Actual value 3 for FI 1
… [-06] = Status word FI 2
… [-07] = Actual value 1 for FI 2
… [-08] = Actual value 2 for FI 2
… [-09] = Actual value 3 for FI 2
… [-10] = Status word FI 3
… [-11] = Actual value 1 for FI 3
… [-12] = Actual value 2 for FI 3
… [-13] = Actual value 3 for FI 3
… [-14] = Status word FI 4
… [-15] = Actual value 1 for FI 4
… [-16] = Actual value 2 for FI 4
… [-17] = Actual value 3 for FI 4
BU 0220 GB-0912 Subject to technical amendments 53
Page 54
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P180
Profibus address
3 ... 125
Shows the PROFIBUS address which is set with the DIP switch. Setting of the address is only
carried out via the DIP switch (see Section 2.2.3 ). After the new setting of addresses, all the
devices on this bus must be restarted by switching the power supply off and on again.
Note:
Addresses 0 to 2 and 126 are reserved for PROFIBUS DP special services.
P181
Profibus baud rate
0 ... 15
Shows the automatically detected baud rate:
Possible values:
0 =
12
Mbit/s
6 =
93,75
kbit/s
1 =
6
Mbit/s
7 =
45,45
kbit/s
2 =
3
Mbit/s
8 =
19,20
kbit/s
3 =
1,5
Mbit/s
9 =
9,60
kbit/s
4 =
500
kbit/s
10 …
14
Reserved
5 =
187,5
kbit/s
15 =
after reset and during a baud rate scan
Note:
The baud rate which is set by the bus master is independently detected by the SK xU4-PBR
module. The restriction of the cable length for the set baud rate must be taken into account.
(Section 8.1.2 "Cable material").
P182 ... [-01]
...
... [-05]
PPO-Type
0 ... 255
… [-01] = Bus module
… [-02 ] = FI 1
… [-03 ] = FI 2
… [-04 ] = FI 3
… [-05 ] = FI 4
Shows the actually selected PPO type. Selection of the required PPO type is made via the PLC
configuration program. (Section 7.2 "PROFIBUS DP PPO types"):
0 = no participant configured
48 = Bus module
245 = PPO type 1
247 = PPO type 2
241 = PPO type 3
243 = PPO type 4
5.2.3 Module information parameters specific to the bus (P180)
54 Subject to technical amendments BU 0220 GB-0912
Page 55
6 Error monitoring and error messages
NOTE
The display of a bus error is shown in the operating display of the SimpleBox SK CSX3H by
means of the error group number E1000. In order to obtain the precise error number, the
module information parameter P170 must be selected. The current error is shown in Array
[01] of this parameter; the last error is stored in Array [02].
6 Error monitoring and error messages
6.1 Error monitoring
The majority of bus module and frequency inverter functions and operating data are continuously monitored
and simultaneously compared with limiting values. If a deviation is detected, the bus module or inverter reacts
with a warning or an error message.
For basic information, please refer to the relevant main manual of the frequency inverter.
Errors cause the frequency inverters to switch off, in order to prevent a device fault.
The following options are available to reset a fault (acknowledge):
1. Switching the mains off and on again,
2. by means of a correspondingly programmed digital input
(SK 200E: (P420) [-…], function {12} or
SK 500E: (P420 ... P425), function {12}),
3. By switching of the “enable” on the frequency inverter
(if no digital input is programmed for acknowledgement),
4. By Bus acknowledgement or
5. By P506, the automatic error acknowledgement.
Visualisation of the inverter error codes is made via the frequency inverter (see relevant manual).
Errors which are attributable to bus operation are visualised via the bus module. The precise error message is
displayed in parameter (P170).
The PROFIBUS DP module monitors the following functions:
Cyclic connection to bus master via the PROFIBUS DP watchdog function
(parameterisation is carried out in the bus master)
Cyclic connection to the bus master and valid control data via the bus module parameter (P151)
BU 0220 GB-0912 Subject to technical amendments 55
Page 56
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Display in the
SimpleBox
Fault
Text in the ParameterBox
Cause
Remedy
Group
Details in
P700[-01] /
P701
E010
10.0
Bus Timeout
(Telegram time-out /
Bus off 24V int. CANbus)
Data transfer is faulty. Check P513.
Check physical bus connections
Check Bus Master.
Check 24V supply of internal CAN/CANopen Bus.
Nodeguarding error (internal CANopen)
Bus Off error (internal CANbus)
10.2
External bus module
telegram timeout
(Timeout Profibus Watchdog)
Telegram transfer is faulty.
Check physical bus connections
PLC is in the "STOP" or "ERROR" state.
10.3
Timeout via (P151)
Telegram transfer is faulty.
Check watchdog time (P151)
Check physical bus connections
Check bus protocol program process.
PLC is in the "STOP" or "ERROR" state.
10.4
External bus module
initialisation failure
Profibus ASIC in the bus module cannot be accessed
10.8
External module
communication failure
Connection fault / error in the external module to the FI
10.9
Module not found
The module entered in parameter (P120) is not available.
6.2 Error messages
6.2.1 Table of possible error messages (caused by the bus) in the frequency inverter
The following error messages concern bus-related messages which are indicated on the frequency inverter. A
complete list of error messages for the frequency inverter (SK 200E) can be found in the relevant manual
(BU0200).
56 Subject to technical amendments BU 0220 GB-0912
Page 57
6 Error monitoring and error messages
Display
in the SimpleBox
Fault
Text in the ParameterBox
Cause
Remedy
Group
Details in
P170
E1000
1000
EEPROM error
Module faulty
1010
System bus 24V missing
Check connections and supply cables
Ensure 24V voltage supply
1020
System bus timeout
Check physical bus connections
FI has been switched off
1030
System bus OFF
Check physical bus connections
5000
PROFIBUS ASIC error
Profibus system error (ASIC cannot be accessed)
5010
PROFIBUS address incorrect
Comply with address range 3 ... 125
5020
PROFIBUS timeout
Telegram transfer is faulty.
Check physical bus connections
6.2.2 Table of possible error messages in the bus module
The following error messages concern bus-related messages, which are indicated on the PROFIBUS DP
module (SK CU4-PBR or SK TU4-PBR(-…)).
BU 0220 GB-0912 Subject to technical amendments 57
Page 58
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
MASTER
SLAVE
Parameter order
Control word + setpoints
Parameter response
Status word + actual value
PKW area
PZD area
Order telegram
Response telegram
Processing
7 PROFIBUS DP data transfer
7.1 Structure of reference data
This section describes the cyclic data traffic between the DP master and the frequency inverter.
The reference data is divided into two sections:
PKW section (Parameter Code Value (parameterisation level))
PZD section (Process data (process data level))
Parameter values can be read and written via the PKW section of the reference data. All tasks which are
carried out via the PKW interface are essentially tasks for configuration, monitoring or diagnosis.
The PZD section serves to control the frequency inverter. The control word or status word as well as the
setpoint and actual values are transferred in the process data.
Access always consists of an order and a response telegram. In the order telegram, the reference data is
transferred to the slave. In the response telegram, the reference data is transferred from the slave to the
master. The structure of both telegrams is identical.
Fig.: Telegram traffic / structure of reference data area
Processing of the process data is carried out immediately in the FI (high priority), in order to ensure a rapid
reaction to control commands or a change in status can be transmitted to the master without delay.
On the other hand, the processing speed of the PKW data has a lower priority, so that processing may take
considerably longer.
58 Subject to technical amendments BU 0220 GB-0912
Page 59
7 PROFIBUS DP data transfer
Type
Task
PPO1
extended parameter data telegram with 32 bit parameter values and process data
PPO2
Telegram with extended process data (main and two auxiliary setpoint values) and 32 bit parameter
value
PPO3
Process data telegram with main setpoint value without parameter data
PPO4
extended process data telegram with main and auxiliary setpoint values without parameter data
PKW
PZD
PKE
IND
PWE
PWE
PZD1
PZD2
PZD3
PZD4
STW
SW1
SW2
SW3
ZSW
IW1
IW2
IW3
1. word
2. word
3. word
4. word
5. word
6. word
7. word
8. word
PPO 1
PPO 2 1. word
2. word
3. word
4. word
PPO3
PPO4
7.2 PROFIBUS DP PPO types
For cyclic data traffic, the Parameter- Process data Object (PPO) with which the process data (PZD) and
parameters (PKW) are transferred from the DP master to the frequency inverter is defined. The frequency inverter
can process PPO types 1, 2, 3 or 4.
PPO3 and PPO4 are purely process data objects for applications which do not require parameter processing.
Note: A PLC can normally only consistently transfer double words by means of I/O memory access. For
longer data formats (PKW channel always / PZD data with PPO2 or PPO4) system functions (e.g.
SFC 14, consistent data reading / SFC15, consistent data writing) must be used.
Structure of PPO types
BU 0220 GB-0912 Subject to technical amendments 59
Page 60
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
1.(/5.) word
2.(/6.) word
3.(/7.) word
4.(/8.) word
PZD area with
1x16-Bit setpoint
STW
ZSW
SW1
IW1
PP0 Type
(1,)3
PZD area with up to 3
16-Bit setpoints
STW
ZSW
SW1
IW1
SW2
IW2
SW3
IW3
PP0 Type
(2,)4
Note: 32-Bit setpoints consist of High and Low words (16-Bit each).
7.2.1 Process data (PZD)
In the process data area (PZD), control words and setpoints are transferred from the master to the slave
(frequency inverter) and in return, status words and actual values are sent from the slave to the master. The
structure of the PZD area is always the same in terms of the sequence of its elements (words), however,
dependent upon direction of data Master inverter / inverter Master, it is described differently.
The process data area of the reference data has the following structure:
- STW: Control Word; length 16 bit, order telegram
contains control bits (e.g. enable, rapid stop, error acknowledgement)
- ZSW: Status Word; length 16 bit, response telegram
contains status bits (e.g. FI running, fault)
- SW1..3: Setpoints; maximum 3 possible, 16 or 32Bit, order telegram
e.g. frequency setpoint value, position setpoint value, torque setpoint value
- IW1..3: Actual values; maximum 3 possible, 16 or 32Bit, response telegram
e.g. actual frequency value, actual position value, actual torque value
60 Subject to technical amendments BU 0220 GB-0912
Page 61
7 PROFIBUS DP data transfer
PZD1
PZD2
PZD3
PZD4
STW
SW1
SW2/3
SW2/3
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
Bit
Value
Meaning
Remarks
0 0 OFF 1
Reverse with the brake ramp, with disconnection from supply at f=0Hz
1 ON
Ready for operation
1 0 OFF 2
Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is disabled.
1 Operating condition
OFF 2 is cancelled
2 0 OFF 3
Quick stop with programmed quick stop time; with disconnection from supply at
f=0Hz; the FI switches to starting disabled condition.
1 Operating condition
OFF 3 is cancelled
3 0 Disable operation
Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is enabled.
1 Enable operation
The output voltage is enabled; ramp to the existing setpoint
4 0 Lock ramp generator
Ramp generator is set to zero; no disconnection from supply at f=0Hz; FI remains
in the operation enabled state.
1 Operating condition
Enable ramp generator
5 0 Stop ramp generator
The setpoint currently provided by the ramp generator is "frozen" (frequency is
maintained).
1 Enable ramp generator
Enable setpoint on ramp generator
6 0 Disable setpoint
Selected setpoint value is set to zero on the ramp generator.
1 Enable setpoint
Selected ramp generator setpoint is activated.
7 0 No acknowledgement
With the switch from 0 to 1, errors which are no longer active are acknowledged.
1 Acknowledge
Note: When a digital input has been programmed for the "ack.fault" function, this
bit must not permanently be set to 1 via the bus (otherwise, edge evaluation
would be prevented).
8 0
1 Bit 8 active
Bus bit 8 from the control word is set. (only for SK 200E and SK 500E)
For further details of function, please refer to parameter (P480) and Section 7.2.1.7.
9 0
1 Bit 9 active
Bus bit 9 from the control word is set. (only for SK 200E and SK 500E)
For further details of function, please refer to parameter (P480) and Section 7.2.1.7.
10 0 PZD invalid
The transmitted process data is invalid.
1 PZD valid
Valid process data is transferred from the master.
Note: If only setpoints are transferred via the bus, this bit must be set so that the
transferred setpoint is valid.
11 0
1 Rotational direction:
right
Rotational direction right (priority) ON*
12 0
1 Rotational direction:
left
Rotational direction left ON*
13
0/1 Reserved
14
0/1
Bit 0 to switch
parameter set
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
15
0/1
Bit 1 to switch
parameter set
* If Bit 12=0, then "Direction of rotation right ON" applies
7.2.1.1 Control word (STW)
The control word (STW) is the first word transferred to the frequency inverter in the process data section in an
order telegram. For example, a control word "Ready for switch-on" corresponds to 047E
ultimately enabled with 047F
(hex)
.
. The FI is
(hex)
Meaning of the individual bits:
BU 0220 GB-0912 Subject to technical amendments 61
Page 62
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
PZD1
PZD2
PZD3
PZD4
ZSW
IW1
IW2/3
IW2/3
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
Bit
Value
Meaning
Remarks
0 0 Not ready to start
1
Ready to start
Initialisation completed, charging relay ON, output voltage disabled
1 0 Not ready for operation
Causes: No command has been activated, fault is signaled, OFF2 or OFF3
activated, starting disabled state activated
1 Ready for operation
ON command activated, no faults present. The inverter can be started with the
command ENABLE OPERATION
2 0 Operation disabled
1 Operation enabled
The output voltage is enabled; ramp to the existing setpoint
3 0 No fault
1 Fault
Drive fault resulting in stoppage; this state is changed to starting disabled after
the fault has been successfully acknowledged
4 0 OFF 2
OFF2 command applied
1 No OFF 2
5 0
OFF 3
OFF3 command applied
1 No OFF 3
6 0
Starting not disabled
1
Starting disabled
Switches first to OFF1, then to ready-to-start status
7 0 No warning
1
Warning
Drive operation continues, no acknowledgement necessary
8 0 Actual value not O.K.
Actual value does not match the setpoint (with posicon: failure to reach setpoint
position)
1 Actual value O.K.
Actual value matches required setpoint (setpoint has been reached)
(with posicon: setpoint has been reached)
9 0 Local guidance
Guidance on local device has been activated
1 Guidance requested
The master has been requested to assume guidance.
10 0
1 Bit 10 active
Bus bit 10 from the status word is set. For further details of function, please refer
to parameter P481 and Section 7.2.1.8.
11 0
1 Rotational direction:
right
Inverter output voltage is turning right
12 0
1 Rotational direction:
left
Inverter output voltage is turning left
13 0
1 Bit 13 active
Bus bit 13 from the status word is set.For further details of function, please refer
to parameter P481 and Section 7.2.1.8.
14
0/1
Currently active
parameter set 0
00 = Parameter set 1
01 = Parameter set 2
10 = Parameter set 3
11 = Parameter set 4
15
0/1
Currently active
parameter set 1
7.2.1.2 Status word (ZSW)
In the inverter response telegram, in the area of the process data the status word (ZSW) is transferred as the
first word. For example, the status word "Ready for switch-on" corresponds to 0B31
status word "Inverter operating" corresponds to 0B37
(hex)
.
. For example, the
(hex)
Meaning of the individual bits:
62 Subject to technical amendments BU 0220 GB-0912
Page 63
7 PROFIBUS DP data transfer
PZD1
PZD2
PZD3
PZD4
STW
SW1
SW2
SW3
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
Setting
100% is equal to
Off
Setpoint frequency, actual frequency PID, actual
frequency PID limited, actual frequency PID monitored,
frequency addition, frequency subtraction, maximum
frequency
Maximum frequency
Torque current limit
Torque current limit (P112)
Current limit
Inverter rated current
Servo mode torque
Rated torque
Torque precontrol
Torque precontrol (P214)
PZD1
PZD2
PZD3
PZD4
STW
SW1
SW2
SW3
7.2.1.3 Setpoint 1 (SW1)
The function of the first setpoint is set in the parameter "Function bus setpoint 1" (SK 200E: (P546[01]) or
SK 500E: (P546)) (see relevant frequency inverter manual).
In the order telegram, setpoint 1 follows immediately after the control word. Setpoint 1 is pre-set to the transfer
of a setpoint frequency (16 bit value).
The setpoint is transferred as an integer in the range -32768 to 32767 (8000 hex to 7FFF hex), whereby 16384
(4000 hex) is exactly 100% and -16383 (C000 hex) corresponds to -100%. Due to this resolution, setpoints
(depending on function) of up to ± 200% can be transferred.
A setpoint of 100% corresponds to the respective nominal value:
7.2.1.4 Setpoints 2 and 3 (SW2/3)
If the PPO type 2 or 4 is used, in addition to setpoint 1, a second setpoint can be transferred in word PZD3 and
a third setpoint in PZD4.
The definition of these two setpoints corresponds to that of setpoint 1.
However, the transfer of a third (maximum 16 Bit) setpoint is only possible if the other two setpoints are also 16
Bit values.
If the transfer of a 32 bit setpoint is necessary (Example: setpoint position), this must be divided into two 16 bit
values, i.e. into two PZDs (position High and Low word). It does not matter in which of the three process
data words (PZD2 and above) the two position words are transferred.
The definition in the frequency inverter can then, for example, be made via the parameters:
PZD3: „Bus function - setpoint 2" (SK 200E / SK 54xE: (P546[-02]) or SK 500E (P547)) and
PZD4: „Bus function - setpoint 3" (SK 200E / SK 54xE: (P546[-03]) or SK 500E (P548))
BU 0220 GB-0912 Subject to technical amendments 63
Page 64
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
PZD1
PZD2
PZD3
PZD4
ZSW
IW1
IW2
IW3
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
PZD1
PZD2
PZD3
PZD4
ZSW
IW1
IW2
IW3
Example
If a position setpoint is to be transferred (Prerequisite: posicon inverter functionality) this can be performed
either as a 16 bit or 32 bit value. The resolution is always 0.001 rotations/step.
A value range of +32767 (= 32.767 revolutions) to -32768 (= -32.768 revolutions) is possible as a 16 Bit value.
Here, exactly one PZD word is required in order to transfer the position.
The full position range of +/- 50000.000 revolutions is available as a 32 Bit value. Here, exactly two PZD
words are required in order to transfer the position.
7.2.1.5 Actual value 1 (IW1)
The function of the first actual value is set in the parameter "Function bus actual value 1" (SK 200E: (P543[01])
or SK 500E: (P543)) (see relevant frequency inverter manual).
In the order telegram, actual value 1 follows immediately after the control word. The actual value 1 is pre-set to
the transfer of the current output frequency of the frequency inverter (16 bit value).
The actual value is transferred as an integer in the range -32768 to 32767 (8000 hex to 7FFF hex), whereby in
the settings "actual frequency", "actual speed", "current" and "torque current", the values 16384 (4000 hex)
exactly correspond to 100% and -16383 (C000 hex) correspond to exactly -100%. Due to this resolution,
setpoints (depending on function) of up to ± 200% can be transferred.
7.2.1.6 Actual values 2 and 3 (IW2/3)
If the PPO type 2 or 4 is used, in addition to actual value 1, a second actual value can be transferred in word
PZD3 and a third actual value in PZD4.
The definition of these two actual values corresponds to that of actual value 1.
If the transfer of a 32 bit actual value is necessary (Example: actual position), this must be divided into two 16
bit values, i.e. into two PZDs (position High and Low word).
The definition in the frequency inverter can then, for example, be made via the parameters:
PZD3: „Bus function - Actual value 2" (SK 200E / SK 54xE: (P543[-02]) or SK 500E (P544)) and
PZD4: „Bus function - Actual value 3" (SK 200E / SK 54xE: (P543[-03]) or SK 500E (P545))
64 Subject to technical amendments BU 0220 GB-0912
Page 65
7 PROFIBUS DP data transfer
7.2.1.7 BIT8 and BIT9 control word
Up to 2 inverter functions can be set directly via the bus master or the PLC by means of the control word. For
this, the required digital function (see list in parameter P420) must be assigned to Bit 8 of the control word via
parameter (P480 [-11]). The same procedure should be applied to Bit 9 of the control word and the function
assigned in parameter (P480 [-12]).
Example:
The values of analog inputs 1 and 2 are to be switched off as necessary via the PROFIBUS master on the
frequency inverter.
Solution:
Set parameter (P480 [-11]) to function "19" "Analog input 1 ON/OFF"
Set parameter (P480 [-12]) to function "20" "Analog input 2 ON/OFF"
In order to process the value from analog input 1 in the frequency inverter, Bit 8 must be set in the control
word. Otherwise the value will not be taken into account by the frequency inverter.
In order to process the value from analog input 2 in the frequency inverter, Bit 9 must be set in the control
word. Otherwise the value will not be taken into account by the frequency inverter.
Alternatively, the digital inputs 1 and 2 of the SK xU4-... module can also be processed directly by the
frequency inverter. For this, the FI which is allowed access to the inputs must be selected in parameter
(P154[-01]). Assignment of the functions is carried out via parameter (P480[-11]) or (P480[-12]) as described
above.
7.2.1.8 BIT10 and BIT13 status word
In the same way as Bit 8 and 9 of the control word, 2 functions can be described in the status word, which set
Bits 10 or 13 on the occurrence of the relevant inverter status. The list of possible functions corresponds to the
"Relay function" or the "Digital output function" (see parameter (P434)).
Example:
The inverter warning "Overcurrent warning" is to be communicated directly in the status word of the frequency
inverter.
Solution:
Set parameter (P481 [-09]) to function "9" "Overcurrent warning"
If the conditions for the triggering of the "Overcurrent warning" are fulfilled in the frequency inverter, the
inverter sets Bit 10 of the status word to the value "1".
Alternatively, the digital outputs 1 and 2 of the SK xU4-... module can also be processed directly by the
frequency inverter. For this, the FI which is allowed access to the inputs must be selected in parameter
(P154[-02]). Assignment of the functions is carried out via parameter (P481[-09]) or (P481[-10]) as described
above.
BU 0220 GB-0912 Subject to technical amendments 65
Page 66
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Status
Bit 6
Switch-on
disable
Bit 5
Emergency
stop
Bit 4
Disable
voltage
Bit 3
Fault
Bit 2
Operation
enabled
Bit 1
Standby
Bit 0
Ready for
switch-on
Not ready to start
0 X X 0 0 0 0
Starting disabled
1 X X 0 0 0 0
Ready to start
0 1 1 0 0 0 1
Activated 0 1 1 0 0 1
1
Operation enabled
0 1 1 0 1 1 1
Fault 0 X X 1 0 0
0
Error active
0 X X 1 1 1 1
Emergency stop
active
0 0 1 0 1 1 1
7.2.2 The status machine
The frequency inverter passes through a status machine. The changes between various states are triggered
by the respective control commands in the process data control word. The actual status is returned in the
process data status word.
After switching on, the frequency inverter is in Switch-on disabled status. This status can only be ended by
transmitting the “Shut down (Off 1)” command.
The answer to a master telegram normally does not yet contain a reaction to the control command. The
controller has to check the answers from the slaves as to whether the control command has been carried out.
The following bits indicate the status of the frequency inverter:
66 Subject to technical amendments BU 0220 GB-0912
Page 67
Switch-on
disabled
Standby
Activated
Operation enabled
Fast stop active
Error reaction
active
Fault
From all device statuses
34568
45
5
Not on standby
Switching on the inverter
Loading relay applied
Fault
Error reaction complete
Bit0 = 0:Shut down
& Bit1 = 1: Enable voltage
& Bit2 = 1: Enable pulses
(xxxx x1xx xxxx x110)
Bit 3 = 0:Disable operationBit0 = 1:Sw itch on
Bit3 = 1:Enable operation
Bit2 = 0:Fast stop
Bit1 = 0:Disable voltage
v Bit2 = 0:Fast stop
Priority of control commands:
1. Disable voltage
2. Fast stop
3. Shut down
4. Enable operation
5. Switch on
6. Disable operation
7. Reset error
Designation of statuses:
1: Bit 0 = 0
2: Bit 6 = 1
3: Bit 0 = 1
4: Bit 1 = 1
5: Bit 2 = 1
6: Bit 5 = 0
7: Bit 2 & Bit 3 = 1
8: Bit 3 = 1
3
5
23
364
2
2
1
2
3
7
8
f = 0 reached
(fast stop complete)
Bit701
Error acknowledgement
Control bits
0. Ready for operation / shut down
1. Disable / enable voltage
2. Enable pulses / emergency stop
3. Disable / enable operation
4. Operation condition / block RUE
5. Enable / stop RUE
6. Enable / disablesetpoint
7. Error acknowledgement (01)
10. Control data valid / invalid
11. Rotation right
12. Rotation left
14. Parameter set Bit 0
15. Parameter set Bit 1
4
5
6
Bit4 = 0:Move down emergency stop ramp and
remain in 'Operation enabled'
Bit5 = 0:Hold frequency
Bit6 = 0:Setpoint = 0%
Bit0 = 0:Shut down
5
Bit3 = 1:Enable operation
& Bit0 = 1: Sw itch on
2
Internal status machine
2
7 PROFIBUS DP data transfer
BU 0220 GB-0912 Subject to technical amendments 67
Page 68
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
ATTENTION
If parameter changes are made (i.e. requests via the PKW area by the control master), care
must be taken that the maximum number of permissible writing cycles to the frequency
inverter EEPROM (100,000 cycles) is not exceeded. I.e. continuous cyclical writing must be
prevented.
For certain applications it is sufficient if the values are only saved in the RAM memory of the
frequency inverter. The corresponding setting is made via parameter (P560) "Save in
EEPROM".
1 2 3 4
PKE
IND
PWE1
PWE2
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
SPM
AK
PNU
NOTE
With the PROFIBUS DP protocol, the inverter parameters are mapped in the range from
1000 to 1999 i.e. for parameterisation via the bus, 1000 must be added to the parameter
numbers (e.g. P508 PNU=1508).
Both the order label and the response label are abbreviated as AK. Therefore, care must be
taken when reading or interpreting the order processing description in this section.
7.2.3 Parameter area (Parameter code value PKW)
Using the PKW mechanism, parameter processing can be carried out in the cyclical data traffic. For this the
master formulates an order and the inverter formulates the appropriate response to this. The parameter area is
only used for transfer with PPO type 1 and PPO type 2.
In principle, the parameter range consists of a parameter identification, in which the type of order (Write,
Read etc.) and the relevant parameters are specified. Individual parameter sets or array elements can be
addressed with the aid of the Index. The parameter value contains the value to be written or read.
Note:A parameter order must be repeated until the inverter responds with the corresponding response
telegram.
7.2.3.1 Parameter label (PKE)
The order or response and the associated parameters are encrypted in the parameter label (PKE).
The parameter label (PKE) is always a 16 bit value. This is divided into the following areas:
PNU:Bits 0 to 10 contain the number of the required parameter (PNU), or the number of the current
parameter in the response telegram of the frequency inverter.
The parameter numbers (PNU) for the particular frequency inverter series can be found in the
relevant frequency inverter manual.
SPM: Bit 11 is the toggle-bit for spontaneous messages. This function is not supported!
AK: Bits 12 to 15 contain the order or response label.
68 Subject to technical amendments BU 0220 GB-0912
Page 69
7 PROFIBUS DP data transfer
AK
Function
Response label positive
0
No order
0
1
Order parameter value
1 / 2
2
Change parameter value (word)
1 3 Change parameter value (double word)
2 4 Reserved
- 5 Reserved
- 6 Order parameter value (array)
4 / 5
7
Change parameter value (array word)
4 8 Change parameter value (array double word)
5 9 Order the number of array elements
6
10
Reserved
-
Additional orders for SK 200E frequency inverter
11
Change parameter value (array double word)
without writing to the EEPROM
5
12
Change parameter value (array word)
without writing to the EEPROM
4
13
Change parameter value (double word)
without writing to the EEPROM
2
14
Change parameter value (word)
without writing to the EEPROM
1
AK
Function
0
No response
1
Transfer parameter value (word)
2
Transfer parameter value (double word)*
4
Transfer parameter value (array word)
5
Transfer parameter value (array double word)*
7
Order cannot be executed (with error number in PWE2)
Meaning of the values sent in the order label:
The following table lists all the orders which can be transferred from the master to the inverter. The right-hand
column contains the response, which is normally sent (response label positive). Only certain response labels
are possible, depending on the order label. In case of error (AK negative) the inverter will always supply the value
7 in the response label (AK) to the master.
Meaning of the values sent in the response label:
* Only for PPO type 2 and PPO type 4
As long as an order has not yet been executed, the inverter provides the response to the last order. Therefore
the master must always check whether the received response matches the order sent.
For the plausibility check, the value in the response label (AK), the received parameter number (PNU) with the
corresponding Index (IND) as well as the current parameter value (PWE) can be used for the description of
parameters.
BU 0220 GB-0912 Subject to technical amendments 69
Page 70
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
No.
Meaning
0
Invalid parameter number
1
Parameter value cannot be changed
2
Lower or upper value limit exceeded
3
Incorrect sub-index
4
No array
5
Invalid data type
6
Only resettable (only 0 may be written)
7
Description element cannot be changed
9
Description data not available or
for acyclic access a READ command was triggered without a previous
WRITE command
101
the frequency inverter to be accessed does not exist
102
the frequency inverter to be accessed does not exist
103
The frequency inverter to be accessed exists, but the query does not
arrive, as the frequency inverter is being heavily queried by another
participant.
201
Invalid order element in the last order received
202
Internal response label cannot be depicted
Error messages if the order cannot be executed
In the response label "Order cannot be executed" (AK = 7), then an error message is added to the parameter
value (PWE2) of the inverter response. The meanings of the transferred values are:
70 Subject to technical amendments BU 0220 GB-0912
Page 71
7 PROFIBUS DP data transfer
1 2 3 4
PKE
IND
PWE1
PWE2
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
P1-P4
No information / all 0
Array 1-64
P1-P4
Sub-index
Array element
Parameter set
Index
5 (000101
BIN
)
2 (01
BIN
)
15
HEX
= 0001 0101
BIN
21 (010101
BIN
)
4 (11
BIN
)
57
HEX
= 0101 0111
BIN
NOTE
32 Bit parameter values are only used with the posicon option. All relevant parameters are
described in the additional posicon instruction manual.
7.2.3.2 Parameter index Sub-index (IND)
The structure and function of the parameter index (IND) depends on the type of parameter to be transferred.
For values which depend on the parameter set, the parameter set can be selected via Bits 8 and 9 of the Index
(IND) (0 = parameter set 1, 1 = parameter set 2, ...).
If the parameter to be processed is also an array parameter (e.g. position array for the PosiCon option), then
the sub-index of the required parameter can additionally be accessed via Bit 10 to Bit 15 of the sub-index
(0 = array element 1, 1 = array element 2, …):
If a paramenter is not dependent on the parameter set, then Bit 8 -15 are used for the sub-index.
The structure of individual parameters and the values which can be called up via the sub-indices can be found in
Section 5 "Parameterisation" of this supplementary manual or in the relevant section of the inverter manual.
For the use of sub-indices, one of the numbers 6, 7, 8 or 11, 12 must be used as the order label (see
previous section), in order to be effective.
7.2.3.3 Parameter value (PWE)
The transfer of the parameter value (PWE) is made in PPO types 1 and 2 and always as a word (16 bit) or
double word (32 bit) according to the parameter. Only one parameter value can be transferred in a telegram.
Only one parameter value can be transferred in a telegram.
A 32 bit parameter value comprises of PWE1 (higher value word) and PWE2 (lower value word). A 16 Bit
parameter value is transferred in PWE2. For negative values the high word must be set to FFFF
hex
.
The parameter value is transferred as an integer value. For parameters with resolutions 0.1 or 0.01 the
parameter value must be multiplied by the inverse of the resolution.
Example: A run-up time of 99.99 seconds is to be set.
99.99s 99.99 * 1 / 0.01 = 99.99 * 100 = 9999
Therefore the value 9999
= 270F
dec
is to be transferred.
hex
BU 0220 GB-0912 Subject to technical amendments 71
Page 72
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
word 5 6
Byte
8 9 10
11
Designation
ZSW
IW1
Value
0B
70
00
00
Bit
Value
Value
HEX
Meaning
15
0 0 Parameter set Bit 1 off
14 0 Parameter set Bit 0 off
13 0 Reserved
12 0 Rotation left is off
11
1 W Rotation right is on
10 0 Reference value undershot
9 1 Bus controller
8 1 Setpoint = actual value
7
0 7 No warning
6 1 Starting disabled
5 1 No emergency stop
4 1 Voltage not disabled
3
0 0 No fault
2 0 Operation disabled
1 0 Not ready for operation
0 0 Not on standby
word 5 6
Byte
8 9 10
11
Designation
STW
SW1
Value
04
7E
00
00
7.3 Example telegrams
7.3.1 Switch-on disabled → Standby
A frequency inverter is to be switched from the "Switch-on disabled" status (STW Bit 0 – 0), which is active
when the device is switched on, to the "Standby" status (STW Bit 0 = 1). The PPO type 1 (Section 7.2) is used,
however only the PZD channel is considered.
Procedure:
1) Check last status word (e.g. ZSW 0B 70)
2) Generate control word (STW 04 7E)
3) Check response telegram (ZSW 0B 31)
Procedure - Details
1) Check last status word (ZSW 0B 70)
2) Generate control word (STW 04 7E)
The frequency inverter is set to Standby status with the following telegram.
72 Subject to technical amendments BU 0220 GB-0912
Page 73
7 PROFIBUS DP data transfer
word 5 6
Byte
8 9 10
11
Designation
ZSW
IW1
Value
0B
31
00
00
NOTE
The control telegram must be sent cyclically as the frequency inverter may not switch to the
required status within the response time of a telegram.
3) Check response telegram (ZSW 0B 31)
After changing to Standby status, the frequency inverter delivers the following response telegram:
BU 0220 GB-0912 Subject to technical amendments 73
Page 74
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
word 5 6
Byte
8 9 10
11
Designation
ZSW
IW1
Value
0B
31
00
00
word 5 6
Byte
8 9 10
11
Designation
STW
SW1
Value
04
7F
20
00
word 5 6
Byte
8 9 10
11
Designation
ZSW
IW1
Value
0B
37
20
00
7.3.2 Enable with 50% setpoint
A frequency inverter in the "Standby" status must be enabled for clockwise rotation with 50% setpoint. The
PPO type 1 (Section 7.2) is used, however only the PZD channel is considered.
Procedure:
1) Check last status word (e.g. ZSW 0B 31)
2) Generate control word (STW 04 7F) and specify setpoint (SW1 20 00 (=50%))
3) Check response telegram (ZSW 0B 37, IW1 20 00)
Procedure - Details
1) Check last status word (e.g. ZSW 0B 31)
2) Generate control word (STW 04 7F) and specify setpoint (SW1 20 00 (=50%))
The frequency inverter accelerates the motor in the ramp. When the inverter reaches 50% setpoint, it
responds with the following telegram.
3) Check response telegram (ZSW 0B 37, IW1 20 00)
74 Subject to technical amendments BU 0220 GB-0912
Page 75
7 PROFIBUS DP data transfer
word 1 2 3 4
Byte
0 1 2 3 4 5 6 7 Designation
PKE
IND
PWE
PWE
Value
74
4E
02
00
00
00
03
E8
word 1 2 3 4
Byte
3 4 5 6 7 8 9
10
Designation
PKE
IND
PWE
PWE
Value
44
4E
02
00
00
00
03
E8
ATTENTION
If parameter changes are made (i.e. requests via the PKW area by the control master), care
must be taken that the maximum number of permissible writing cycles to the frequency
inverter EEPROM (100,000 cycles) is not exceeded. I.e. continuous cyclical writing must be
prevented.
For certain applications it is sufficient if the values are only saved in the RAM memory of the
frequency inverter. The corresponding setting is made via parameter (P560) "Save in
EEPROM".
7.3.3 Writing a parameter
When transferring parameter orders, it must be taken into account that the slave does not immediately respond
to orders in the parameter channel of the master telegram, but a positive response can be delayed by one or
more communication cycles. The master must therefore repeat the required order until the corresponding slave
response is received. PPO type 1 or PPO type 2 must be selected (Section 7.2).
The parameter (P102) "run-up time" (PNU = 102
the PKW channel is evaluated). (Only the PKW channel is evaluated.)
As the acceleration time has a frequency-internal resolution of 0.01sec, a parameter value of 10 / 0.01 = 1000
(3E8
) must be transferred for 2 sec.
hex
Procedure:
1) Specify order label ("Change parameter value (array word)" → AK = 7)
dec
/ 66
) is to be set to the value 10sec in parameter set 3. (Only
hex
2) Select parameter (P 102
+ 1000 = P 1102 = P 44E
dec
hex
)
3) Select parameter set 3 (IND = 02)
4) Set parameter value (1000
dec
/ 3E8
hex
)
5) Check response telegram (positive for array word = 4)
The telegram is composed as follows in hexadecimal notation:
When the order has been fully implemented by the inverter, it responds with (hexadecimal):
BU 0220 GB-0912 Subject to technical amendments 75
Page 76
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Transfer rate
Baud rate [kBit/s]
9.6
19.2
45.45
93.75
187.5
500
1500
3000
6000
12000
Cable length [m]
Cable type A
1200
1200
1200
1200
1000
400
200
100
100
100
Parameter
Value
Number of wires
2 (twisted)
Impedance
150 Ω (3 to 20 MHz)
Capacitance
< 30pF/m
Loop resistance
< 110 Ω/km
Cable cross section
> 0.32 mm²
8 Additional information
8.1 Bus Configuration
In an industrial environment the correct installation of the Bus system is particularly
important in order to reduce potential interference. The following points are designed to
help prevent interference and problems right from the start. The installation guidelines are
not complete and applicable safety and accident prevention guidelines must be complied
with.
8.1.1 Laying the PROFIBUS DP cable
A bus segment consists of a maximum of 32 participants. Several segments can be connected together by
means of repeaters. In this way, up to 126 participants can participate in reference data traffic. It should be
noted that the reaction time increases as the number of participants increases.
The data transfer physics of the serial bus system by means of twisted two-wire cable (with
connected shielding) is defined in the specification of the interference-proof RS485 interface.
For applications with potentially high electromagnetic interference (EMC) and for long
distances, optic fiber cable should be used as the cable medium and fiber optic couplers
should be used for connection.
8.1.2 Cable material
The frequency inverter is usually connected to the PROFIBUS DP system by a twisted, shielded two-wire
cable. In EN 50 170, this bus cable is specified as cable type A. The guaranteed transfer speeds or transfer
distances can only be achieved without errors if the specific cable parameters are complied with.
With these cable types, the following extensions in length result:
These cable length details are defined for a bus segment with 32 participants.
It must be noted that
the maximum cable length determines the transfer rate and vice versa,
the transfer rate is set identically for all masters connected to the bus,
the slaves support the set baud rate (see GSD file).
The standard PROFIBUS DP cable must comply with the following cable specifications:
76 Subject to technical amendments BU 0220 GB-0912
Page 77
8 Additional information
NOTE
The lower the shielding resistance of the PROFIBUS DP cable, the better the EMC quality.
The electromagnetic compatibility (EMC) describes the normally required state, that
technical devices do not interfere with each other due to electrical or electromagnetic
effects.
Fixed cable
Freely laid cable
Bending radius of cable
Minimum radius
5 x cable diameter
Minimum radius
10 x cable diameter
Correct
Incorrect
NOTE
If earthing potential values are different, transient current may flow through shielding which
is connected on both sides. This may be a danger to electronic components. Differences in
potential must be reduced by means of adequate potential equalisation.
8.1.3 Cable layout and shielding (EMC measures)
If EMC measures are not in place, high-frequency interference which is mainly caused by switching processes
or lightning often causes electronic components in the bus subscribers to be faulty and error-free operation can
no longer be ensured.
Appropriate shielding of the bus cable reduces electrical interference which can arise in an industrial
environment.
The best shielding characteristics are achieved with the following measures:
Do not make cable connections shorter than 1m between bus participants
Avoid long connections between bus subscribers
Shield the bus cable on both ends with large-area connection to the plug housing
Avoid spur lines (above 1.5MBaud spur lines are no longer permissible)
Avoid extensions to bus cables via plug connectors
Bus lines should be laid with a minimum spacing of 20cm to other lines which carry a voltage higher than 60V.
This applies to lines laid inside and outside of control cabinets.
Special attention should be paid to bending radii:
BU 0220 GB-0912 Subject to technical amendments 77
Page 78
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
8.1.4 Recommendations of the PROFIBUS users´ association
Under www.profibus.com/pb/ important information in association with PROFIBUS can be found in the Internet,
including:
"Installation guidelines for PROFIBUS-DP/FMS", September 1998, Order No. 2.111
Guideline Assembling, Version 1.06, Order Number 8.021/8.022
Guideline Commissioning, Version, 1.02, Order Number 8.031/8.032
Planning recommendations: www.profibus.com/downloads
E.g.: PB-Planung-Beiheft_8041_V10_Aug09.pdf
78 Subject to technical amendments BU 0220 GB-0912
Nowadays, field bus systems are a normal part of plant technology. The sensitivity of these systems to
electromagnetic interference (EMC) means that it is essential to protect bus systems from outside interference
by means of uninterrupted or complete screening. Therefore the use of shielded cables and metal screw
couplings or plug connectors has become standard. Assuming correct installation (e.g.: 360° screen connection
- including at contact points, compliance with tightening torques, bending radii, IP-protection classes (≥ IP66),…),
the operational reliability of the field bus system can be optimised.
The EMC effect of a cable shield is largely dependent on its contacts to the housing and its earthing on one or
both ends. The shielding effect of a housing must not be influenced by incoming or outgoing screened cables.
It is recommended that the shield is exposed directly at the point of entry and connection of the cable gland
with the reference potential surface and the use of an EMC cable. At the same time this opening in the housing
is "sealed" against the electromagnetic field. The connection from the cable shield to the housing must have a
DC and and inductive resistance which is as low as possible. This depends on the frequency. This low contact
resistance is achieved by the use of a ring-shaped 360° contacting of the cable shielding and short
connections to the housing via the connecting thread.
8.2.1 Fixed connection (cable gland)
Metallic EMC cable glands with a shielding concept should be used to minimise EMC problems.
These special M16 x 1.5 EMC cable glands must be fitted in the relevant connection unit (SK TI4-…(-BUS)) of the
frequency inverter or the PROFIBUS DP module.
Mounting
For the M16 x 1.5 EMC cable gland, 5 mm of the shielding of the cable /conductor is exposed and slightly
spread out. The insulating foil of the Profibus cable must be cut off and must not be folded back.
BU 0220 GB-0912 Subject to technical amendments 79
Function
When the pressure screw is tightened, the sealing insert presses the shielding mesh onto the cone of the
earthing insert. The entire circumference (360°) of the shielding mesh is contacted. The mesh ends in the
cable gland. This produces a large area, low resistance conductive connection between the shield, the
earthing insert and the screw fitting and the housing.
For further information regarding the correct installation of EMC cable glands, please refer to the relevant
manufacturer´s data sheets.
Page 80
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Flanged coupling
Flanged plug
Name
A coding
B coding
Example: Coupling
Format
M12
M12
Coupling version
with coding groove
with coding pin
Plug version
with coding pin
with coding groove
Field of use
System bus
CANopen
DeviceNet
24V supply
sensors and actuators
PROFIBUS DP
8.2.2 Connection with M12 round plug connectors
In order to implement detachable connections, the cable connections for the field and
system bus and for sensors and actuators, as well as for the 24V supply voltage can be
designed with plug-in connectors.
Here, freely adjustable M12 flanged connectors with metric M16 x 1.5 threads should be
used for installation in the relevant housing ((SK TI4-…(-BUS)).
This allows the use of angled or straight M12 round plug connectors for the cable
connection.
If required, Getriebebau Nord GmbH can equip the device to be delivered accordingly, or
can enclose the required plug with the delivery.
EMC compatible assembly is carried out in the same manner as for the assembly of the
cable glands (Section 8.2.1 "Fixed connection (cable gland)
").
8.2.3 Round plug connectors
Getriebebau Nord GmbH offers a selection of suitable plugs and couplings, which can be
installed in the connection units of the frequency inverters or the field bus module, or
enclosed with the delivery as required. The corresponding plugs, couplings and Y
connectors are also commercially available. However, a limited selection can be obtained from Getriebebau
NORD GmbH.
Coding
Round plug connectors are coded. Coding is by means of a pin or a groove on the contact base. The most
common codings are the so-called A and B coding. This serves to protect against incorrect coupling of the
various field bus systems.
80 Subject to technical amendments BU 0220 GB-0912
Page 81
8.2.3.1 M12 flanged connector
System
components
Description
Data
System bus
SK TIE4-M12-SYSS
Part. No. 275274506
M12 flanged plug
to connect the incoming system bus cable
A-coded, 5-pin
PIN 1 n. c.
PIN 2 +24V (brown)
PIN 3 GND (blue)
PIN 4 Sys-H (black)
PIN 5 Sys-L (gray)
Plastic body in light blue
SK TIE4-M12-SYSM
Part. No. 275274505
M12 flanged plug
to connect the outgoingsystem bus cable
A-coded, 5-pin
PIN 1 n. c.
PIN 2 +24V (brown)
PIN 3 GND (blue)
PIN 4 Sys-H (black)
PIN 5 Sys-L (gray)
Plastic body in light blue
External voltage supply
SK TIE4-M12-POW
Part. No. 275274507
M12 flanged plug
to connect a 24V- supply
A-coded, 4-pin
PIN 1 +24V (brown)
PIN 2 n. c.
PIN 3 GND (blue)
PIN 4 n. c.
PIN 5 n. c.
Plastic body in black
Sensors and actuators
SK TIE4-M12-INI
Part. No. 275274503
M12 flanged plug
to connect sensors and actuators
A-coded, 4-pin
PIN 1 +24V (brown)
PIN 2 DI or DO (white)
PIN 3 GND (blue)
PIN 4 DI or DO (black)
PIN 5 n. c.
Plastic body in black
PROFIBUS DP
SK TIE4-M12-PBR
Part. No. 275274500
Kit consisting of M12
flanged plug and
flanged socket
M12 flanged plug
to connect the incoming PROFIBUS DP cable
The following plug connectors are recommended by Getriebebau NORD GmbH. Plug connectors with a socalled Part No. can also be supplied by Getriebebau NORD GmbH.
M12 connector
B coded
M12 socket
B coded
If required, ready-made profibus cables of various lengths can be obtained from the manufacturers listed here.
82 Subject to technical amendments BU 0220 GB-0912
Page 83
8 Additional information
NOTE
In order to ensure a secure, sealed and vibration-proof connection, connecting components
with hexagonal fittings should be used.
Special tools enable tightening to a defined torque (operational reliability).
Supplier
Name
Part no.
MURR Elektronik
M12 wrench set for M12 round connectors with calibrated
torque of 0.6Nm
7000-99102-0000000
Franz Binder GmbH
M12 torque wrench for M12 round connectors with
calibrated torque of 0.6Nm
07-0079-000
M12
wrench
8.2.3.3 Assembly tools
The observance of the tightening torques for making plug connections is of vital importance. For M12 plug
connectors, the optimum torque is 0.6Nm.
Suitable assembly tools are commercially available.
BU 0220 GB-0912 Subject to technical amendments 83
Page 84
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
8.3 PROFIBUS DP technology and protocol
The PROFIBUS (Process Field Bus) is the fastest standardised (open) bus system for field use. This
technology enables consistent communication down to the lowest field level and is widely used in production,
process and building automation systems. PROFIBUS is standardised in the international standard IEC 61158.
It is a multi-master system and therefore enables the joint operation of several automation, engineering or
visualisation systems with decentralised peripheral devices on a common field bus. The protocol describes the
process rules for the transfer of data. The protocol specifies both the format of messages as well as the flow of
data in data transfer. A wide variety of field devices can therefore be easily interlinked. In case of failure of
individual field devices, data transfer to the remaining bus subscribers continues uninterrupted.
The system configuration or bus structure can be implemented both as a mono-master system (only one
master) and as a multi-master system (several masters).
8.3.1 Overview /Protocol architecture
The ISO/OSI layer model describes the communication between the individual participants (slaves) of a
communication or automation system. Of the seven defined OSI layers, PROFIBUS uses layers 1, 2 and 7.
PROFIBUS DP only uses layers 1 and 2 and the DP user interface.
Layer 1 Physical layerdefines the hardware, coding, speed etc. of data transfer
Layer 2 Connection layerdescribes the bus access procedure including data
security, i.e. it defines the physics of transfer
Layer 7 Application layerdefines the interface to the application program with the
application-orientated commands.
Layer 2 of the ISO/OSI model includes
the general format for data transfer telegrams
the bus access mechanisms
the security mechanisms
the times to be complied with
possible transfer services.
The user only has a slight influence on the design of layer 2, as almost all services are included in the
available PROFIBUS ASICs.
84 Subject to technical amendments BU 0220 GB-0912
Page 85
8 Additional information
Diagram of telegram sequence
DP Slave 1
DP Slave 2
DP Slave 3
PROFIBUS
DP master Class 1
PROFIBUS
DP master Class 2
Token
DP Slave 4
8.3.2 Device types
PROFIBUS DP is an acronym for "Process Field Bus for Decentralised Peripherals" i.e. for the simple, rapid,
cyclic and deterministic exchange of process data between a PROFIBUS DP master and the assigned
PROFIBUS DP slaves connected to the field bus. The exchange of process data takes place between central
automation devices such as PLCs, PCs or process control systems and decentralised field devices such as
drive units, valves, analysis devices and frequency inverters. Exchange of process data is mainly carried out
cyclically between the PROFIBUS DP participants (master ↔ slaves).
Each PROFIBUS DP system can consist of a wide range of different devices. These are divided into three
classes:
DP master Class 1 (DPM1)This master controls the cyclic reference data traffic, i.e. process data is
automatically exchanged with the DP slaves (I/Os) in a repetitive
sequence. Typical devices for central control are memory-programmed
control units (PLCs) or PCs.
DP master Class 2 (DPM2)These masters are engineering, planning or operating devices (OP,
touch-panels).
They can also access the bus acyclically and additionally enable the
configuration and parameterisation of intelligent field devices such as
frequency inverters. A DPM2 master does not need to be permanently
present on the Profibus DP.
DP SlaveSlaves are peripheral devices with a direct interface to the I/Os, such as
I/Os, drive units, valves, measurement transducers, frequency inverters
etc., which read in input information and output information to the
peripheral devices.
PROFIBUS DP is specially designed for production automation and uses the RS485 standard as the transfer
method. RS485 is the most commonly used transfer method and enables transfer rates of up to 12 MBaud. A
shielded twisted wire cable is used.
PROFIBUS DP is designed both for rapid time-critical applications as well as for complex communication
tasks.
A DP master Class 1 sends a status state (master
status) to all assigned and connected slaves in a
cyclic time interval which can be configured. If the
operating parameter "Auto Clear" is set to "TRUE",
the DPM1 master switches the outputs of all
associated slaves to the safe condition, i.e. to "0"
in case of failure of a slave.
BU 0220 GB-0912 Subject to technical amendments 85
Page 86
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Direct
response
Confirmation with data
Command, data (if necessary)
DP master
DP slave
Command, data (if necessary)
DP master
DP slave
8.3.2.1 PROFIBUS master
PROFIBUS masters are field devices, which take the initiative for the exchange of data with field devices which
operate as slaves. A master has the sole access right to slaves on the bus and determines the data transfer on
the bus. The master may send out messages without request if it has an access right (token). In the case of
several masters in a bus structure, only the master which currently has access rights may send messages. In
contrast to the DP slaves, masters are designated as active participants, which have bus access rights for a
limited period of time (token-holding time).
All data which a PROFIBUS master requires for the exchange of data with the slaves (e.g. I/O area), must be
created before the system is started and loaded into the master ( GSD file).
The main tasks of a master are:
exchange of data with the planned slaves
coordination of bus access
execution of error handling
providing the user with slave data
The following data transfer services are defined for the PROFIBUS DP:
SRD:Send and request data with acknowledge.
In a message cycle, the master sends output data to a slave and as a response receives
the input data back in the same cycle.
SDN: Send data with no acknowledge, allows the transmission of broadcast telegrams
(unacknowledged telegrams).
The PROFIBUS DP master cyclically reads the input information from the connected DP slaves and cyclically
writes the output information to the DP slaves.
PROFIBUS DP masters exist as
modules within a PLC
CPU module with integrated PLC
standard PC modules
Stand-alone boards
86 Subject to technical amendments BU 0220 GB-0912
Page 87
8 Additional information
8.3.2.2 PROFIBUS slave
PROFIBUS DP slaves are peripheral devices such as I/Os, drive units, HMIs, valves, measurement
transponders, frequency inverters. The DP slaves do not receive any access rights, i.e. they can only confirm
messages from the master or send messages to the master when requested. DP slaves are designated as
passive participants. A slave reads in input information and sends out output information to the peripherals.
Because a slave only requires a small portion of the protocol, they are simple to implement in the PROFIBUS
system configuration. The amount of input and output information depends on the device and can be up to a
maximum of 246 input and 246 output bytes.
All data which a PROFIBUS master requires for the exchange of data (e.g. I/O area) with the slave and its
implementation is provided by means of a DeviceMasterFile (GSD file) which is specific to the particular
manufacturer.
The slaves are decentrally coupled to the PLC control unit or the automation device via the transfer medium
(PROFIBUS cable and RS485) and complete the configuration of the system.
DP-V0 Basic functionalities for cyclic data traffic
DP-V1 Extensions for acyclic data traffic
DP-V2 Special extensions and additions for data traffic between slaves
Getriebebau NORD GmbH supports the PROFIBUS DP performance levels DP-V0 and DP-V1.
8.3.3.1 PROFIBUS DP-V0
DP-V0 describes the basic functionalities of the DP communication protocol.
Cyclic exchange of process data / transfer of reference data between the DP master and slave(s)
Diagnosis specific to the station, module and channel
Telegram format: PPO types 1 - 4
Device classes: DPM1, DPM2 and slave
Access times*: Reading access (parameter queries) - approx. 30ms
Writing access (parameter changes) - approx. 50ms
* for 1 - 4 frequency inverters for each BUS technology unit
Parameterisation is possible with the use of PPO types 1 and 2
Note:
The bus cycle time must be less than the program cycle time of the central automation device.
Data traffic between the DPM1 and the slaves is structured into the parameterisation, configuration and data
transfer phases.
BU 0220 GB-0912 Subject to technical amendments 87
Page 88
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Name
Meaning
Value range
TS
Master address
0 to 126
Baud rate
Transfer rate
10 options
(Section 8.1.2 "Cable material")
TSL
Slot Time
52 216-1 (bit times)
min T
SDR
Smallest Station Delay Responder
20 to 216-1 (bit times)
max T
SDR
Largest Station Delay Responder
20 to 216-1 (bit times)
T
QUI
Quiet Time
0 to 28-1 (bit times) (standard value =0)
T
SET
Setup Time
20 to 28-1 (bit times)
TTR
Target Rotation Time
20 to 224-1 (bit times)
G
GAP Update factor (token cycles)
1 to 100 (Standard value = 10)
HSA
Highest Station Address
2 to 126 (Standard value = 126)
Max retry limit
Maximum retries (number of repeat telegrams)
0 to 8
8.3.3.2 PROFIBUS DP-V1
Amongst other things, DP-V1 contains additions for process automation and a series of event-related
functions, in particular acyclic data traffic.
Acyclic exchange of process data for parameterisation, operation, observation and alarm processing of
intelligent field devices in parallel with the cyclic reference data traffic.
Diagnostic functions, status alarm, update alarm and alarm processing specific to the manufacturer.
Exchange of data during the DP slave initialisation phase
DP-Master Class 2 - Communication (Section 8.3.2 "Device types" - E.g.: touch panel)
DP master - master communication (between masters)
Acyclic data traffic, which is made possible by DP-V1 allows the parameterisation and calibration of the
connected field devices simultaneously to the cyclic exchange of data.For this, a four-word I/O module is used,
which corresponds to the Parameter Label Value (PKW) section of PPO types 1 and 2 (see also Section 7.2
"PROFIBUS DP PPO types").
Up to 4 frequency inverters connected via a BUS technology unit can be managed independently from the
master via this channel. A DP master Class 1 (DPM1, e.g. PLC or PC) can simultaneously access up to three
DP master Class 2 (DPM2, engineering, planning or control devices) in parallel to a technology unit.
Requirements by more complex applications and devices (field devices for process automation, intelligent
operating and observations devices, frequency inverters), which often require parameterisation during
operation, can therefore be easily implemented.
With the use of this performance class, the parameter values are only rarely changed in comparison to the
cyclic measurement values.
8.3.4 Terminology (selection)
8.3.4.1 Bus parameters
Bus parameters are settings which define the time-related behaviour on the physical PROFIBUS DP. The
following standardised parameters are set in the DP master by means of the configuration tool. In more recent
configuration tools, this is usually carried out automatically:
88 Subject to technical amendments BU 0220 GB-0912
Page 89
8 Additional information
Diagram of bus cycle time
8.3.4.2 Transfer rate (baud rate)
The processing of all DP slaves describes a cycle. The time required for this depends on the transfer rate, the
number of DP slaves and the net data to be sent.
For the transfer of 512 bit input and 512 bit output data divided over 32 bus participants, the PROFIBUS DP
requires approx. 1ms with a transfer rate of 12 Mbit/s.
A baud rate of 1.5Mbit/s extends the average cycle time to approx. 6ms.
8.3.4.3 FREEZE and SYNC mode
In addition to the automatic participant-related transfer of reference data, DPM1 masters can also
simultaneously sent some control commands to the bus participants for synchronisation of the DP slaves.
These control commands are sent as multicast (transfer of messages from a point to a group). The following
only lists and describes some of the operating modes/control commands. Detailed information about the basic
functionalities is explained in the relevant specialist PROFIBUS DP books.
Note:FREEZE and SYNC functions are used e.g. in applications which require synchronisation.
(simultaneous control or acceptance of new setpoints for several DP-slaves or the simultaneous
recording of actual process values)
Control command FREEZE
The PROFIBUS DP master sends a FREEZE control command to one or a group of DP slaves (PROFIBUS
DP technology unit). The slaves which are addressed in this way "freeze" their current status (actual values).
The transfer of the data to the DP-master is then carried out cyclically. The "frozen" data is retained until it is
updated by a renewed FREEZE command, or the status is revoked by an UNFREEZE command.
Control command SYNC
The PROFIBUS DP master sends a SYNC control command to one or a group of DP slaves (PROFIBUS DP
technology unit). The slaves which are addressed in this way "freeze" their current setpoints. The following
incoming setpoints are saved in the DP-slave, however, they are not effective for the process. The saved data
is switched to the outputs after the next SYNC command. In the following cycle, an UNSYNC command
causes the new setpoints to be adopted and ends SYNC operation.
BU 0220 GB-0912 Subject to technical amendments 89
Page 90
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
parameter
PKW
Reading
and writing of
DP master
t
DP Slave 1
DP Slave 2
DP Slave 3
DP Slave 1
DP Slave 2
DP Slave 3
DP Slave 2
DP Slave 1
DP Slave 2
Cyclic PZD
Acyclic PKW
Cyclic PZD
Reading and
writing of the
process data
PZD
PROFIBUS DP
DP-V1
8.3.4.4 Cyclic and acyclic data traffic
The PROFIBUS technology units enable field bus access to all parameters and functions of the frequency
inverter.
Cyclic reference data traffic (process data) enables rapid control of bus participants. Via the standardised
process data channel (parameter process data object (PPO)) setpoints (setpoint frequency, position setpoints,
current limits etc.) are transferred from the automation device to the frequency inverter. Via the same process
data channel, actual values (actual frequency, actual position, current values, error numbers etc.) and status
information is read back from the frequency inverter to the automation device. Selection of the PPO type is
carried out via the hardware manager (Section 4.2.2 ). The SK xU4-PBR bus module automatically detects the
PPO type which is used and sets it for communication to the frequency inverter.
However, some applications require interventions by the user (adaptation of parameters). These interventions
can be carried out
cyclically via the parameter code value channel (only PPO types 1 or 2 and only for frequency inverter
parameters) within the process data, or also
acyclically via special READ / WRITE commands according to the PROFIBUS DP-V1 specification.
Parameter adaptations of the Profibus module SK xU4-PBR (parameter (P150) ... (P154) can only be carried
out via acyclic data communication.
The acyclic data traffic is carried out parallel to the cyclic reference data traffic of the process information
during operation and can only be used for parameterisation. For the acyclic data traffic, a 4 byte data block,
which corresponds to the PKW component of PPO types 1 and 2 is transferred via the PROFIBUS DP.
The acyclic exchange of data sets can extend over several bus cycles or their "gaps".
With SIMATIC STEP 7 applications, two ready-made system modules are available for the handling of acyclic
data traffic.
90 Subject to technical amendments BU 0220 GB-0912
Page 91
8 Additional information
Reading parameters
Within the DPM2 master program, the system module SFB52 "RDREC" (read record) is used to read
parameters. This system module reads the data set of the addressed component (module) of a DP slave. This
may be a central module or a decentralised component (PROFIBUS DP), a technology unit. If an error occurs
during data transfer, this is indicated via an output parameter (ERROR and STATUS) of the system module.
Several settings must be noted for the use of this system module.
If for example a DP-V1 slave is planned via GSD (Rev. 3 or later), the DP master must be set to "DPV1".
Otherwise (example setting "S7 compatible") no data sets may be read with SFB 52 from the I/O modules in
the application program, as the DP master would be addressed to the wrong slot (planned slot +3).
The SFB 52 "RDREC" is an asynchronous SFB, i.e. processing extends over several SFB call-ups.
Sequence
To read the parameter of the frequency inverter, the PROFIBUS DP master first sends a WRITE control
command to the relevant DP slave (PROFIBUS DP technology unit), which confirms the query. A READ
command triggers the transfer of the parameter data to the control unit.
The issue of a read command (SFB 52) without a previous write command (SFB 53), results in an error
message (E009) by the relevant frequency inverter.
Writing parameters
Within the DPM2 master program, the system module SFB52 "WRREC" (write record) is used to write
parameters. This system module writes (transfers) the data set of the addressed component (module) of a DP
slave. Several interface settings in the DP master interface must be noted to ensure correct operation.
The SFB 53 "WRREC" is an asynchronous SFB, i.e. processing extends over several SFB call-ups.
Sequence
To change the parameter of the frequency inverter, the PROFIBUS DP master first sends a WRITE control
command to the relevant DP slave (PROFIBUS DP technology unit), which confirms the query. If necessary,
the transferred parameter changes can be checked by means of a READ command.
BU 0220 GB-0912 Subject to technical amendments 91
Page 92
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
8.3.4.5 Device master data (GSD file)
All performance features of the NORDAC PROFIBUS DP module are collated in a device master file
(electronic data sheet). The structure, content and coding of the device master file (GSD) are used
(standardised in a readable ASCII text file) for simple PROFIBUS DP communication. The GSD file enables
the convenient planning of NORDAC frequency inverters via tools from various control unit suppliers. In
addition to general information, the GSD file also contains specifications for communication, which are specific
to the manufacturer. These specifications are structured into three sections:
General Data Details of the manufacturer and the device, software and hardware version
numbers, supported transfer rates etc.
Master data Specific parameter details for the master, upload and download facilities.
Slave data Specific parameter details of the slave, number and type of I/O channels,
diagnostic texts and module details for modular device structures.
The standardised GSD files are included in the scope of delivery of the devices (frequency inverters) (enclosed
documentation CD (Electronic Product Documentation)) and are available for download free of charge from the
Getriebebau NORD GmbH homepage under www.nord.com.
For the decentralised SK 200E device series with the associated technology units SK CU4-… or SK TU4-…
the GSD file
NORD0BA8.GSD (SK 200E technology unit, incl. DP-V1, 12MBaud)
must be implemented.
This GSD file differs from the previous files provided by Getriebebau NORD GmbH, among other things in the
extension of the DP-V1 functionality.
In the SIMATIC S7 Manager, the configuration data is stored under the Slave_Family (Code 1 = Drives), e.g.
under the heading Further field devices under Drive units in the catalogue directory NORD@DPV1 of the
hardware configuration manager. By means of parameterisation Auto_Baud_supp (Value = 1) the automatic
baud rate detection is switched on. The function Set_Slave_Add_supp (Value = 0) is disabled, so that the
slave address cannot be set from the DP master. The setting of several modules is supported by the setting
Modular_Station (Value = 1). For further information, please refer to the above GSD file.
The PROFIBUS users´ organisation archives this information for all manufacturers and provides this in
Internet.
8.3.4.6 Ident number
In order for the PROFIBUS DP master to uniquely identify the various DP devices, the slaves are labelled with
an ident number which is specific to the manufacturer. On start-up of the PROFIBUS DP master, the ident
numbers of the connected DP slaves are compared with the ident numbers in the specified planning data in
the planning tool.
In order to rule out planning errors and malfunctions, the transfer of reference data only begins once the
correct device types have been connected to the correct station addresses on the bus and have been
recognised by the master.
The ident numbers for Profibus modules from Getriebebau NORD are as follows:
75310BA8
92 Subject to technical amendments BU 0220 GB-0912
all Profibus modules for the device series except for SK 200E → SK TU4-… and SK CU4-…
hex
Technology units for the device series SK 200E → SK TU4-… and SK CU4-…
hex
Page 93
8 Additional information
8.3.4.7 Consistent data transfer
A PLC can normally only consistently transfer double words by means of I/O memory access. For longer data
formats (PKW channel always / PZD data with PPO2 or PPO4) system functions (e.g. SFC 14, consistent data
reading / SFC15, consistent data writing) must be used.
8.3.4.8 I&M function
I&M functionality is only supported to a limited extent by Getriebebau NORD PROFIBUS technology units
SK CU4-PBR and SK TU4-PBR (…-M12) via the acyclic communication channel (DP-V1). The I&M functions
specify the manner of a unified representation of the data which describe PROFIBUS DP devices (electronic
type plate). DPM2 masters, such as engineering tools can read and interpret the data of the electronic type
plate via an allocation/encryption on the PNO Internet homepage. Among other things, information concerning
the manufacturer´s designation, hardware and software version numbers and details of association with a
particular profile are transferred.
The Getriebebau NORD Manufacturer ID is: 393
dec
.
The company name is: NORD Electronic DRIVESYSTEMS GmbH.
BU 0220 GB-0912 Subject to technical amendments 93
Page 94
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Terminal77 = System bus + (CAN H)
Terminal78 = System bus - (CAN L)
Terminal numbers may differ
8.4 System bus
SK 2xxE series frequency inverters and components communicate with each other via the system bus. This
bus system is a CAN bus with CANopen protocol. Up to four frequency inverters and their associated
components (field bus module, absolute encoder, I/O modules etc.) can be connected to the system bus.
Integration of the components into the system bus does not require any specific knowledge of the bus on the
part of the user.
Only the proper physical configuration of the bus system and if necessary the correct addressing of the
participants need to be taken into account by the user.
The system bus address of the bus modules (SK CU4-… and SK TU4-…) is set to "5". The system bus
address of the up to 4 frequency inverters which can be connected are set by means of DIP switches (see
manual BU 0200) on the relevant frequency inverter, optionally between 32 / 34 / 36 and 38, whereby no
address may be doubly assigned within a system bus system.
For detailed information regarding the system bus (physical structure, integration and addressing of further
components) please refer to the inverter manual BU0200.
94 Subject to technical amendments BU 0220 GB-0912
Page 95
8 Additional information
NOTE
If possible, the reason for returning the component/device should be stated. If necessary, at
least one contact for queries should be stated.
This is important in order to keep repair times as short and efficient as possible.
On request you can obtain a suitable goods return voucher from Getriebebau
NORD GmbH.
8.5 Repairs
The device must be sent to the following address if it needs repairing:
NORD Electronic DRIVESYSTEMS GmbH
Tjüchkampstr. 37
26605 Aurich, Germany
For queries about repairs, please contact:
Getriebebau NORD GmbH & Co. KG
Telephone: 04532 / 401-515
Fax: 04532 / 401-555
If a frequency inverter or accessories are sent in for repair, no liability can be accepted for any added
components, e.g. such as line cables, potentiometer, external displays, etc.!
Please remove all non-original parts from the frequency inverter.
BU 0220 GB-0912 Subject to technical amendments 95
Page 96
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE
Address
ASIC
Assigned or specified designation of a DP slave.
Integrated circuit specific to the application
Baud rate
The transmission rate for serial interfaces in bits per second
Binary code
The designation for a code in which messages are communicated by "0"
and "1" signals.
Bit / Byte
A bit (binary digit) is the smallest unit of information in the binary system.
A byte has 8 bits.
Broadcast
In a network, all slave participants are addressed simultaneously by the
master.
DPM1
DP masters Class 1 implement the reference data traffic to the DP
slaves. The DPM1 is the central automation device for PROFIBUS DP.
DPM2
In addition to reference data traffic, Class 2 DP masters enable further
event-controlled functions such as control, commissioning and planning
tasks. The DPM2 is a planning or configuration device for PROFIBUS
DP.
DP
Protocol for decentralised peripherals. With PROFIBUS DP this
describes the connection between the automation device and the bus
participants and is a standardised specification.
DP-V0
The central control unit (bus master)cyclically reads the incoming
information (e.g. actual values and status word) from the slaves and
writes the outgoing information (e.g. control word and setpoints) to the
slaves.
DP-V1
In addition to DP-V1 an acyclic data traffic between the central control
unit (bus master) and the connected slaves can be carried out. Transfer
of acyclic data is carried out in parallel to the cyclic data traffic between
the bus participants.
GSD
Device master data
Electronic data sheet
ISO
The International Standards Organisation is the international association
of standardisation organisations and produces international standards in all
fields, with the exception of electricity and electronics.
I&M
I&M stands for "Identification & Maintenance Functions" and is a
functionality of the PNO for all PROFIBUS devices which support acyclic
data traffic.
OSI layer model
The Open Systems Interconnection Reference Model defines the
elements, structures and tasks necessary for data communication and
assigns these to the times for the communication process in seven
consecutive layers.
PROFIBUS DP
PROFIBUS DP is a field bus variant for production automation. RS485
interfaces are used for transfer. The DP communication protocol differs
in its performance levels and various application profiles.
9 Index
Keyword Index:
96 Subject to technical amendments BU 0220 GB
Page 97
BE
Bus error (fault)
BR
Bus ready
BS
BUS state (status)
CU
Customer Unit (customer interface - internal technology unit)
D, DI, DIN
Digital IN
EN
DEVICE error (fault)
DO, DOUT
Digital OUT
DP
Decentralized peripheral
DS
DEVICE state (status)
EMC
Electromagnetic compatibility
FI
Frequency inverters
GND
Earth
HW
IND
Hardware
Index
I/O
IN / OUT, input and output
IW
I&M
Actual value
Identification & Maintenance Functions
P
PKE
PKW
parameter which depends on a parameter set
Parameter identifier
Parameter identifier Value
PNO
PROFIBUS users´ organisation
PPO
PWE
PZD
STW
Parameter Process data Object
Parameter Value
Process data
Control word
SW
Software / Setpoint
TU
Technologie Unit (external technology unit)
ZSW
Status word
Abbreviations used:
9 Index
BU 0220 GB-0912 Subject to technical amendments 97
Page 98
PROFIBUS DP – Supplementary manualfor NORD Frequency Inverter SK 2xxE