NORD BU0060 User Manual

Page 1
GB
BU 0060
CANopen
Supplementary manual options for NORD - Frequency Inverters
Page 2
CANopen – Supplementary manual options for NORD - Frequency Inverters
protection class, have live, bare, moving or rotating parts or hot
must be carried out by qualified personnel (comply with IEC 364, CENELEC HD 384, DIN VDE 0100, IEC 664 and DIN VDE 0110, and
are persons who are familiar with the assembly, installation,
Drive power converters are components intended for installation in
When installed in machines, the drive power converter cannot be
d that the machine meets the provisions of the EC Directive
2006/42/EEC (machine directive); EN 60204 must also be complied
The installation and cooling of the equipment must be implemented
The drive power converter must be protected against impermissible loads. Especially during transport and handling, components must not be deformed and/or insulation dis tances must not be changed. Touching of electronic components and
Drive power converters have electrostatically sensitive components, which can be easily damaged by incorrect handling. Electrical components must not be mechanically
When working on live drive power converters, the applicable
section, fuses, ground
lead connections). Further instructions can be found in the
such as
shielding, earthing, location of filters and installation of cables
e drive power converter documentation.
drive power converters. Compliance with the limiting values specified in the EMC regulations is the responsibility of the
Where necessary, systems where drive power converters are installed must be equipped with additional monitoring and protective equipment according to the applicable safety requirements, e.g. legislation concerning technical equipment,
The parameterisation and configuration of the drive power
supply, live equipment components and power connections should not be touched immediately, because of possible charged capacitors. Observe the relevant information signs
NORD frequency inverters

Safety and operating instructions for drive power converters

(as per: Low Voltage Directive 2006/95/EEC )
1. General
During operation, drive power converters may, depending on their surfaces.
Unauthorised removal of covers, im proper use, incorrect installation or operation causes a risk of serious personal injury or material damage.
Further information can be found in this documentation. All transportation, installation and initialisation and maintenance work
national accident prevention regulations). For the purposes of these basic safety inst ructions, qualified personnel
commissioning and operation of this product and who have the relevant qualifications for their work.
2. Proper use in Europe
electrical systems or machines.
commissioned (i.e. commencement of the proper use) until it has been ensure
with. Commissioning (i.e. implementation of the proper use) is only permitted
when the EMC directive (2004/108/EEC) is complied with. Drive power converters with the CE mark meet the requirements of the
Low Voltage Directive 2006/95/EEC. The harmoni zed standards stated in the Declaration of Conformity are used for the drive power converters.
Technical data and information for connec tion conditions can be found on the rating plate and in the documentation, and must be complied with.
The drive power converters may only be used for the safety f unctions which are described and for which they have been explicitly approved.
3. Transport, storage
Information regarding transport, storage and correct handling must be complied with.
4. Installation
according to the regulations in the corresponding documentation.
Pos: 3 /Anleit ung en/Elektr oni k/Bussyste m e/ 0. Prolog/CAN o pen [BU0060]/D okumentati on - Versionsl is t e [CANopen, BU 0 060] @ 1\mod_1341305744229_388.docx @ 28569 @ @ 1
These safety instructions must be kept in a safe place!
contacts must be avoided.
damaged or destroyed (this may cause a health hazard!).
5. Electrical connections
national accident prevention regulations must be compli ed with (e.g. VBG A3, formerly VBG 4).
The electrical installation must be implemented according t o the applicable regulations (e.g. cable cross-
documentation. Information about EMC-compliant installation –
can be found in th These instructions must be compl ied with even with CE m arked
manufacturer of the system or machine.
6. Operation
accident prevention regulations, etc.
converter must be selected so that no hazards can occur. All covers must be kept closed during operation.
7. Maintenance and repairs
After the drive power converter is di sconnected from the power
located on the drive power converter. Further information can be found in this documentation.
2 BU 0060 GB-4112
Page 3
Documentation
Modification of SK 500/520/530E parameters, correction of recommended M8/M12 connector and IW2/3 modification,
Combination of BU 0030 + BU 0060 = BU 0060. This now
specific CAN bus) and
Supplementation of parameters for inverter variants: SK 54xE. Removal details of the vector mc series. Modification of the
and correction of small errors, revision of examples, supplementation of example for SDO communication, tables, control word and status word:
respective frequency inverter. This is an essential prerequisite for the availability of all the relevant information

Documentation

Name: Part No.: 607 06 01 Device series:
CANnord /CANopen for SK 300E, SK 5xxE, SK 700E, SK 750E

Version list

Name of previous issues Software
Version
BU 0060 EN, May 2005 Part No. 607 06 02 / 1005
BU 0060 DE, November 2006 Part No. 607 06 02 / 4606
BU 0060 EN, May 2007 Part No. 607 06 02 / 1807
BU 0060 EN, May 2010 Part No. 607 06 02 / 2010
BU 0060 DE, October 2012 Part No. 607 06 02 / 4112
V. 1.1 R0 First issue
V. 1.2 R1
V. 1.2 R1
V. 1.2 R1 Correction of errors (e.g. (P748): „CANopen NMT State“),
V. 1.2 R1
Remarks
inclusion of CANnord data
only contains CANnord (Nord­CANopen.
RJ45 connection module supplemented
structure in the document
Designations revised.
Table 1: Version list
Pos: 4 /Anleit ung en/Elektr oni k/FU und Starter /0. Prolog /0.4 Herausg eber @ 0\mod_1325779078002_388.docx @ 5270 @ @ 1

Publisher

Getriebebau NORD GmbH & Co. KG
Rudolf-Diesel-Str. 1 D-22941 Bargteheide http://www.nord.com/ Tel.: +49 (0) 45 32 / 289-0 Fax +49 (0) 45 32 / 289-2555
Pos: 5 /Anleit ungen/Elektr onik/Bussys teme/0. Prol og/Hinweis Gültigkeit der Zusatza nleitung @ 1 \mod_1333613175 766_388.docx @ 21236 @ @ 1
NOTICE Supplementary operating manual
This supplementary operating manual is only valid in conjunction with the operating manual supplied for the required for the safe commissioning of the frequency inverter.
Pos: 6 /Anl eitungen/El ektronik/Bus systeme/0. Prolog/Bes timmungsge mäße Verwe ndung der Freq uenzumric hter [BU00x 0] @ 1\mod_1333613411565_388.docx @ 21259 @ @ 1
BU 0060 GB-4112 3
Page 4
CANopen – Supplementary manual options for NORD - Frequency Inverters

Intended use of the frequency inverter

Compliance with the operating instructions is necessar y for fault-free operation and the acceptance of any warranty claims. These operating instructions must be read before working with the device!
These operating instructions contain important information about servicing. They must therefore be kept close to the device.
The described optional modules can only be used for the specifically defined frequency inverter ser ies, use across s eries is only possible with the SK CU1-… module for SK 700E and SK 75 0E, or the SK TU2-... module with SK 300E and SK 750E. The use of th ese modules with oth er devices is not per mitted and can le ad to their destruction.
The described optional modules and the corresponding frequency inverters are, according to their type, devices for stationary installation in control cabinets or decentralised structures. All details regarding technical data and permissible conditions at the installation site must be complied with.
Commissioning (com mencement of the intended use) is not perm itted until it has been ensured that the machine complies with the EMC Directive 2004/108/EEC and that the conformity of the end product meets the Machinery Directive 2006/42/EEC (observe EN 60204) .
=== Ende der Liste für Textmarke Copyri ght ===
Getriebebau NORD GmbH & Co. KG, 2012
4 BU 0060 GB-4112
Page 5
Intended use of the frequency inverter
BU 0060 GB-4112 5
Page 6
CANopen – Supplementary manual options for NORD - Frequency Inverters
Pos: 8 /Anl eitungen/St euermodule/ Inhaltsverz ei c h ni s @ 0\ mod_1317978518480_388.docx @ 4078 @ @ 1

Table of Contents

=== Ende der Liste für T extmarke I nhaltsverzei chnis ===
1. Introduction ............................................................................................................................................... 11
1.1 General ............................................................................................................................................ 11
1.2 The bus system ................................................................................................................................ 11
1.2.1 CAN Bus ............................................................................................................................. 11
1.2.2 CANopen ............................................................................................................................ 11
1.2.3 CANnord ............................................................................................................................. 12
1.3 CAN for NORD frequency inverters ................................................................................................. 12
1.3.1 CAN Bus features, physics ................................................................................................. 12
1.3.2 CANopen features .............................................................................................................. 12
1.3.3 CANnord features ............................................................................................................... 12
1.4 Delivery ............................................................................................................................................ 12
1.5 Scope of delivery.............................................................................................................................. 13
1.6 Certifications .................................................................................................................................... 13
1.6.1 European EMC Directive .................................................................................................... 13
1.6.2 RoHS compliant .................................................................................................................. 13
1.7 Type code ........................................................................................................................................ 14
2. Modules ...................................................................................................................................................... 15
2.1 Modular assemblies SK 5xxE .......................................................................................................... 15
2.1.1 SK 5xxE CANnord / CANopen, overview ........................................................................... 16
2.1.2 CANnord / CANopen, internal RJ45 connection (SK 511E and above) .............................. 17
2.1.3 RJ45 WAGO- Connection module ...................................................................................... 19
2.1.4 CANopen module, SK TU3-CAO ........................................................................................ 20
2.1.5 Installing ............................................................................................................................. 21
2.2 Modular units SK 700E (SK 750E) ................................................................................................... 22
2.2.1 SK TU1- CANnord / CANopen module, overview ............................................................... 23
2.2.2 CANnord module, SK TU1-CAN ......................................................................................... 23
2.2.3 CANopen module, SK TU1-CAO ........................................................................................ 24
2.2.4 Installation of the SK TU1 technology unit .......................................................................... 25
2.2.5 CANnord module, SK CU1-CAN ........................................................................................ 26
2.2.6 CANnord module, SK CU1-CAN-RJ ................................................................................... 27
2.2.7 Installation of the SK CU1-xxx customer unit...................................................................... 28
2.3 Modular units trio SK 300E and SK 750E ........................................................................................ 31
2.3.1 SK TU2- CANopen module, overview ................................................................................ 31
2.3.2 CANopen module, SK TU2-CAO ........................................................................................ 32
2.3.3 Installation of the SK TU2 technology unit .......................................................................... 33
2.3.4 Recommended connector and accessory components ...................................................... 34
3. Bus Configuration ..................................................................................................................................... 37
3.1 Laying the bus cables ...................................................................................................................... 37
3.2 Cable material .................................................................................................................................. 37
3.3 Cable layout and shielding (EMC measures) ................................................................................... 38
4. Communication and Protocol .................................................................................................................. 39
4.1 Processing of Process Data in the Frequency Inverter .................................................................... 39
4.1.1 Process data - General (PZD) ............................................................................................ 39
4.1.2 Control word (STW) ............................................................................................................ 40
4.1.3 Status word (ZSW) ............................................................................................................. 41
4.1.4 Frequency inverter status machine ..................................................................................... 42
4.1.5 Setpoint (SW) ..................................................................................................................... 44
4.1.6 Actual value (IW) ................................................................................................................ 46
4.1.7 Standardisation of setpoint / target values .......................................................................... 48
4.2 The CANnord protocol ..................................................................................................................... 49
4.2.1 Message objects ................................................................................................................. 49
4.2.2 Identifier .............................................................................................................................. 49
4.2.3 Identifier example ............................................................................................................... 50
4.2.4 Sequence of data transfer .................................................................................................. 50
4.2.5 Broadcast telegrams ........................................................................................................... 51
4.2.6 Parametrerisation in CAN mode ......................................................................................... 52
4.3 The CANopen protocol ..................................................................................................................... 56
6 BU 0060 GB-4112
Page 7
Table of Contents
4.3.1 Network Management (NMT) ............................................................................................. 57
4.3.2 Drive profile DS 402 ........................................................................................................... 57
4.3.3 Process data transfer in CANopen mode (PDO commu nicat i on) ....................................... 57
4.3.4 Parameterisation in CANopen mode (SDO communication) .............................................. 60
4.3.5 Object Index ....................................................................................................................... 64
5. Parameters ................................................................................................................................................. 68
5.1 BUS parameter data for SK 300E/700E/750E ................................................................................. 69
5.1.1 Control terminals ................................................................................................................ 69
5.1.2 Additional parameters ......................................................................................................... 70
5.1.3 Information.......................................................................................................................... 75
5.2 SK 5xxE BUS Parameters ............................................................................................................... 78
5.2.1 Control terminals ................................................................................................................ 78
5.2.2 Additional parameters ......................................................................................................... 80
5.2.3 Information.......................................................................................................................... 86
6. Operating status messages ..................................................................................................................... 90
6.1 Error monitoring ............................................................................................................................... 90
6.1.1 Status via parameter display .............................................................................................. 91
6.1.2 LED display with the technology unit: ................................................................................. 92
6.1.3 Emergency Object telegram for inverter error messages ................................................... 93
6.1.4 Error lists, ........................................................................................................................... 93
7. Examples ................................................................................................................................................... 95
7.1 Mains switch-on ............................................................................................................................... 95
7.2 Operational settting of the bus participant ........................................................................................ 95
7.3 Process data (PDO) ......................................................................................................................... 95
7.4 Reading and writing parameter data (SDO) ..................................................................................... 98
8. Additional information .............................................................................................................................. 99
8.1 Electronic data sheet (eds file) ......................................................................................................... 99
8.2 Further documents ........................................................................................................................... 99
8.3 Repair information ............................................................................................................................ 99
8.3.1 Repairs ............................................................................................................................... 99
8.3.2 Internet information ........................................................................................................... 100
8.4 Keyword Index ............................................................................................................................... 100
8.5 Abbreviations ................................................................................................................................. 101
BU 0060 GB-4112 7
Page 8
CANopen – Supplementary manual options for NORD - Frequency Inverters
8 BU 0060 GB-4112
Page 9
List of illustrations
Pos: 10 /Anl eitungen/St euermodule/ Abbildungs verzeichnis @ 0\mod_1317978515699_388.docx @ 3917 @ @ 1

List of illustrations

=== Ende der Liste für T extmarke A bbildungsver zeichnis == =
Fig. 1: Mod ular assemblies SK 5xxE ..................................................................................................................... 15
Figure 2: SK 5xxE -configuration CANnord / CANopen ......................................................................................... 16
Fig. 3: Frequency inverter SK 700E and technology units ..................................................................................... 22
Figure 4: SK CU1-CAN terminal assignment ......................................................................................................... 26
Figure 5: SK CU1-CAN-RJ terminal assignment ................................................................................................... 27
Fig. 6: Frequency inverters SK 300E and SK 750E ............................................................................................... 31
Fig. 7: Installation and cable laying informa tio n ..................................................................................................... 38
Fig. 8: Status Machine of the Frequency Inverter .................................................................................................. 43
Figure 9: Sequence of data transfer ...................................................................................................................... 51
Figure 10: Velocity Mode CiA DSP 402 V1.1 page 178 ......................................................................................... 57
BU 0060 GB-4112 9
Page 10
CANopen – Supplementary manual options for NORD - Frequency Inverters
Pos: 12 /Anleit u ng e n/Steuermo d ul e/ Tabellenver z eichnis @ 0\mod_1317978519199_388.docx @ 4124 @ @ 1

List of tables

=== Ende der Liste für T extmarke Ta bellenverz eichnis ===
Table 1: Version list ................................................................................................................................................. 3
Table 2: Details of SK 5xxE – BUS -configuration via RJ45 .................................................................................. 17
Table 3: RJ45 WAGO connection module ............................................................................................................. 19
Table 4: SK TU1-CAN / -CAO, overview of technology units ................................................................................ 23
Table 5: SK TU3-CAO, Overview of Technology Units .......................................................................................... 31
Table 6: Transfer speeds versus cable length ....................................................................................................... 37
Table 7: Control word (STW) ................................................................................................................................. 40
Table 8: Status word (ZSW) .................................................................................................................................. 41
Table 9: Scaling of setpoints and actual values (Selection) ................................................................................... 48
Table 10: CANnord - Determination of message object identifiers ........................................................................ 49
Table 11: Identifier example .................................................................................................................................. 50
Table 12: Assignment of CAN address (P515) to the broadcast identifier ............................................................. 51
Table 13: Network Management (NMT) ................................................................................................................ 57
Table 14: PDO types ............................................................................................................................................. 57
Table 15: PDO modes ........................................................................................................................................... 58
Table 16: Transmitting parameter data via SDO ................................................................................................... 61
Table 17: Loading parameter data via SDO .......................................................................................................... 62
Table 18: Error message (0x06010002 = attempted writing access to a read-only object) ................................... 62
Table 19: Error codes – P ara meter co mmuni cati on .............................................................................................. 62
Table 20: Index table for transmit and receive PDOs of the inverter ..................................................................... 63
Table 21: Description of PDO COB-ID entry.......................................................................................................... 63
Table 22: Communication objects (DS 301) .......................................................................................................... 64
Table 23: PDO objects (DS 301) .......................................................................................................................... 65
Table 24: Object drive profile DS 402 .................................................................................................................... 66
Table 25: Frequency inverter object s .................................................................................................................... 67
Table 26: CANnord/CANopen status, parameter P748 ......................................................................................... 91
Table 27: LED display, CANnord communication status ....................................................................................... 92
Table 28: LED display, CANopen communication status ...................................................................................... 92
Table 29: LED display, CANopen module status ................................................................................................... 92
Table 30: Structure of error message (Time-out through P513) ............................................................................ 93
Table 31: Assignment of CAN open errors to inverter errors ................................................................................. 94
Pos: 14 /Anl eitungen/El ektronik/Bus systeme/1 . Einführung /!Kapitel Ei nführung @ 1\mod_1333611560104_388.docx @ 21163 @ 1 @ 1
10 BU 0060 GB-4112
Page 11
1 Introduction

1. Introduction

Pos: 15 /Anleit u ng e n/Elektroni k/Bussyste m e/ 1 . Ei nf ührung/CAN open [BU006 0]/ Allgemeine s [C AN open] @ 1\mod_1341315444218_388.docx @ 28631 @ 2 @ 1

1.1 General

This CANnord/ CANopen documentation is valid for the NORD series trio SK 300E, SK 500E, SK 700E, SK 750E. F or discontinued device series ( e.g. vector m c) which are no longer supplied, the technical documentation is available on request (older version of BU0060).
The respective basic devices are delivered with a blank cover for the tec hnology unit slot. The bas ic models do not have any components for parameterisation and control.
In order to set up communication w ith CANnord/ CANopen, either a CANnord/ CANopen customer unit or a Technologiebaugruppe CANnord/ CANopen technology module (according to the device series) must be installed and connected.
The only exceptions to this from the SK 5xxE series are the types above SK 511E, in which the CANnord/CANopen function is integrated as standard and can be used via an RJ45 plug connector.
Pos: 16 /Anleit u ng e n/Elektroni k/Bussyste m e/ 1 . Ei nf ührung/CAN open [BU006 0]/ D as Bussystem [C AN open] @ 1\mod_1341316184406_388.docx @ 28656 @ 2 @ 1

1.2 The bus system

Pos: 17 /Anl eitungen/El ektronik/Bus systeme/1 . Ei nf ührung/CAN open [BU006 0]/ C ANBus @ 1\mod_1341316398266_388.docx @ 28680 @ 3 @ 1

1.2.1 CAN Bus

The CANbus enables powerful automation systems to be realised with distributed intelligence. The reason for the broad application of the CANb us protocol is mainl y the availability of ver y reasonably priced protocol components.
CANbus is based on linear topol ogy. Using repeaters, branch-like topo logies are possible. Solutions based on fibre optic condu ctors as well as double wire lines can be us ed. T he conflict recognition a nd resolution, as well as err or r ec ognit ion, integr a ted i n th e CAN bus pr ot oc ol, ena ble s high bus ut ilis at ion and data security.
Bus access rights are not issued by a higher-level control unit. Instead, each subscriber can start transmitting a mes sage as soon as t he b us is f ree (m ulti-m aster capabili ty). W ith s im ultaneous ac cess of several participants, th e participant with the highes t priority receives th e access rights. The priorit y is assigned according to the identifier of the messenger in CANbus.
Pos: 18 /Anleitungen/Elektronik/Bussysteme/1. Einführung/CANopen [BU0060]/CANopen @ 1\mod_1341316519123_388.docx @ 28704 @ 3 @ 1

1.2.2 CANopen

CANopen is an open c omm unications profile for various i ndustrial autom ation system s. It is bas ed on the CANbus system (Controller Area Network), developed by Bosch, and describes the layers 1 (physical layer) and 2 (data transmission) of the OSI reference model (ISO 11898). CANopen was specified by the international CAN-in-Automation (CiA) organisation and defines the communication mechanisms (process data, parameterisation, monitoring etc.) via the CANopen bus.
CANopen can be used for data exchange between devices from different manufacturers. Alongside the comm unication pr ofile, C ANopen def ines device pr ofiles for the mos t important t ypes of
device used in industrial automation technology, e.g. digital and analog I/Os, drives, etc. The CiA CANopen sp ecification DS-301 and DS-402 is supported (does not apply for the integr ated
RJ45 interface of the SK 5xxE series (SK 511E and above)).
Pos: 19 /Anl eitungen/El ektronik/Bus systeme/1 . Einführung /CANopen [ BU0060]/CAN nord @ 1\mod_1341316759316_388.docx @ 28728 @ 3 @ 1
BU 0060 GB-4112 11
Page 12
CANopen – Supplementary manual options for NORD - Frequency Inverters

1.2.3 CANnord

CANnord is a specif ic bus system from Getriebebau NORD. Further d etails can be found i n Section
4.2.
Pos: 20 /Anl eitungen/El ektronik/Bus systeme/1 . Einführung /CANopen [ BU0060]/CAN bei NORD F requenzumri chtern (Mer kmale) [BU0 060] @ 1\mod_1341317168995_388.docx @ 28752 @ 2 @ 1

1.3 CAN for NORD frequency inverters

Pos: 21 /Anleit u ng e n/Elektroni k/Bussyste m e/ 1 . Ei nf ührung/CAN open [BU006 0]/Merkmale C AN Bus, Ph ysik @ 1\mod_1341317227732_388.docx @ 28776 @ 3 @ 1

1.3.1 CAN Bus features, physics

• Electrically isolated bus interface
• Transfer rate from 10 kBit/s to 500 kBit/s (optionally up to 1 Mbit/s)
• Connection to frequency inverter via Sub-D9 connector, M12 system connector, RJ45 connector or screw/plug-in terminals (depending on option/device)
• CAN interface as per specifications 2.0A and 2.0B
• Up to 110 nodes (e.g. frequency inverters) on one bus
• Additional termination resistor (depending on option/device)
• Status display with 2 or 4 LEDs (not with SK 500E/520E/530E)
• External 24V supply required (~70mA for SK 300E/ SK 5xxE/ 700E/ 750E with technology unit CANopen, ~30mA for SK 5xxE (SK 511E and above) via internal RJ45 connection CANnord/ CANopen)
• TO supports 29 Bit + 11 Bit Identifier
• Internal interface (RJ45) for SK 5xxE (SK 511E and above) only 11 Bit Identifier
Pos: 22 /Anleit u ng e n/Elektroni k/Bussyste m e/ 1 . Ei nf ührung/CAN open [BU006 0]/ M erkmale CANo p en @ 1\mod_1341317959787_388.docx @ 288 00 @ 3 @ 1

1.3.2 C ANopen features

• Programming of all frequency inverter parameters using SDO
• Supports DS-301 communications profile and DS-402 drive profile (with technology units)
• Dynamic mapping (4 TPDOs und 4 RPDOs) with technology units
• Heartbeat/ Node Guarding
Pos: 23 /Anl eitungen/El ektronik/Bus systeme/1 . Einführung /CANopen [ BU0060]/Mer kmale CANn ord @ 1\mod_1341318067232_388.docx @ 28824 @ 3 @ 1

1.3.3 C ANnord features

• Programming of all frequency inverter parameters using SDO
• Setpoint/actual values read/write
• Error messages
• Time out function
Pos: 24 /Anl eitungen/El ektronik/FU und Starter /1. Allgemei nes/1.2 Li eferung @ 0 \mod_1325780242208_388.docx @ 5339 @ 2 @ 1

1.4 Delivery

Check the equipm ent immediately after d el ivery/unpacking for trans p or t damage such as deformation or loose parts.
If there is any damage, contact the carrier immediately and carry out a thorough assessment.
Important! This also applies even if the packaging is undamaged.
Pos: 25 /Anl eitungen/Elektroni k/Bussysteme/1. Einführung/CANopen [BU0060]/Lieferumfang [CANopen, SK 300E - SK 750E] @ 1\mod_1341318451836_388.docx @ 28848 @ 2 @ 1
12 BU 0060 GB-4112
Page 13
1 Introduction
SK TU1-CAN
for SK 700E
IP20
or
SK TU2-CAO
for SK 300E / SK 750E
IP55
or
SK TU2-CAO-C
for SK 300E / SK 750E
IP66
or
SK CU1-CAN
for SK 700E / SK 750E
IP00
or SK CU1-CAN-RJ
for SK 700E / SK 750E
IP00

1.5 Scope of delivery

Technology unit
Customer interface
The operating instr uctions for the above bus m odules or the relevant freque ncy inverters as well as the NORDCON parameterisation software are available for download free of charge under
www.nord.com
. In addition, a documentation CD is provided with every frequency inverter
(designation: EPD), on which the above data is also provided.
SK TU1-CAO for SK 700E IP20 or
SK TU3-CAO for SK 5xxE IP20 or
Information
Flat connecting sleeve for PE connection
The technology units SK TU1 and SK TU3 are also supplied with a flat connecting sleeve. This sleeve must be used to produce a correct PE connection of the technology unit via an appropriate cable (cross-section 1.5mm ²).
Pos: 26 /Anl eitungen/El ektronik/FU und Starter /1. Allgemei nes/1.5 Z ulassungen @ 0\mod_1326111302308 _388.docx @ 6223 @ 2 @ 1

1.6 Certifications

Pos: 27 /Anl eitungen/El ektronik/FU und Starter /1. Allgemei nes/1.5.1 E uropäische EMV-Richtlinie @ 0\mod_1325780630565_388.docx @ 5431 @ 3 @ 1

1.6.1 European EMC Directive

If the frequency inverter is installed according to the recommendations in this manual, it meets all EMC directive requirements, as per the EMC product standard for motor-operated systems EN 61800-3.
Pos: 28 /Anl eitungen/El ektronik/FU und Starter /1. Allgemei nes/1.5.4 R oHS-konfor m @ 0\ mod_1325836122418_388.docx @ 5503 @ 3 @ 1

1.6.2 RoHS compliant

The frequency inverters and optional modules are designed to be RoHS compliant according to Directive 2002/95/EU.
Pos: 29 /Anl eitungen/El ektronik/Bus systeme/1 . Einführung /Typenschl üssel [SK TU 1-3, CU1] @ 1\mod_1336641489466_388.docx @ 26262 @ 2 @ 1
BU 0060 GB-4112 13
Page 14
CANopen – Supplementary manual options for NORD - Frequency Inverters
SK TU2-PBR(-24V-KL-ATEX-C)
Higher IP protection class (IP66) ATEX version Special version e.g.: KL= version with conn ect ion term ina ls Version with external 24V supply Device type: AS1 = AS-Interface, CAO = CANopen, DEV =
DeviceNet, IBS = InterBus, ECT = EtherCAT, PBR = Profibus, PNT = ProfiNET
Device series: SK TU1 / SK TU2 / SK TU3 / SK CU1

1.7 Type code

Pos: 30 /Anleitungen/Elektronik/Bussysteme/2. Baugruppen/!Kapitel Baugruppen @ 1\mod_1333614552265_388.docx @ 21333 @ 1 @ 1
14 BU 0060 GB-4112
Page 15
2 Modules
red / green

2. Modules

Pos: 31 /Anleit u ng e n/3. Anzeige un d Bedienung [S K 50 0E]/SK 5xxE/ 3. 1 M o dulare Baugru p pen [SK 5xxE] @ 0\ mod_1327492754652_388.docx @ 6283 @ 2 @ 1

2.1 Modular assemblies SK 5xxE

By the use of various m odules for display, control an d parameterisation, the SK 5xx E can be easily adapted to a wide range of requirements.
Alphanumerical display and operating modules can be used for simple commissioning. For more complex tasks, various connections to a PC or an automation system can be selected.
The Technology Unit (Technology Unit, SK TU1-...) is connected externally to the front of the frequency inverter and is therefore easy to access and replace at any time.
LED
Fig. 1: Modular assemblies SK 5xxE
Pos: 32 /Anl eitungen/El ektronik/Bus systeme/2 . Baugruppe n/CANopen [BU0060]/SK 5xxE CANnor d / CANope n, Überblick @ 1\mod_1341392266116_388.docx @ 28997 @ 3 @ 1
BU 0060 GB-4112 15
Page 16
CANopen – Supplementary manual options for NORD - Frequency Inverters
CANopen
CANnord or CANopen
SK 5xxE (entire series)
SK 511E and above
SUB D9 connector
Input/output via RJ45 sockets
Additional termination resistor
Additional termination resistor
External 24V +/- 25% voltage supply, approx. 80mA
External 24V +/- 25% voltage supply, approx. 30mA
Rotary coding switch for baud rate and address
Parameter P514 / P515 for baud rate and address
Drive profile DS 301 and DS 402
Drive profile DS 301
By means of appropriate measures, ensure that no vibrations or tensile forces act on the cabling. In particular, the

2.1.1 SK 5xxE C ANnord / CANopen, overview

SK TU3-CAO internal RJ45 connection
Figure 2: SK 5xxE -configuration CANnord / CANopen
Information
RJ45 connector cabling must be free of any tension.
Pos: 33 /Anleit u ng e n/Elektroni k/Bussyste m e/ 2 . Ba ugruppen/CA N open [BU006 0]/ C ANnord / CANop e n, Interner RJ4 5 A n sc hl uss @ 1\mod_1341396988811_388.docx @ 29198 @ 3 @ 1
Strain relief
16 BU 0060 GB-4112
Page 17
2 Modules
ve, a CANnord/CANopen interface is
Information
The baud rate is set in the frequency inverter parameter P514. Transfer rates of up to 500 kbit/s can be used. (Optionally up to 1 Mbit/s)
30mA) and is connected via the RJ45 connector.
for the last bus participant is located
next to the BUS connection. Switch No. 2 = ON.
The BUS address is set in the frequency inverter parameter P515.
0…255
0…127
2x RJ45 sockets are connected in parallel internally.

2.1.2 C ANnord / CANopen, internal RJ45 connection (SK 511E and above)

With SK 511E and abo integrated and can be accessed via RJ45 connections.
To use the CANnord /CANo pen, the b us m ust be pr ovided wit h an external 24V voltage supply. The CAN participant can therefore be identified by the mast er system even without a voltage sup ply to the frequency inverter.
There is no internal coupli ng between the control voltage level of the frequency inverter and the bus system.
Control voltage
Baud rate (P514)
Supply voltage
Termination resistor
BUS address (P515)
BUS connection
Table 2: Details of SK 5xxE – BUS -configuration via RJ45
CANnord (P509 = 3) CANopen (P509 = 6)
The supply voltage is 24V DC ±25% (pin 8 = 24V, pin 7 = GND, approx.
The termination resistor R=120
Pos: 34 /Anl eitungen/El ektronik/FU und Starter /2. Montag e und Install ation/2.10. 5 Elektris cher Anschlu s s St euerteil- St ec kerblock X9 un d X1 0 – C AN / CANope n [SK 500.. .535E] @ 1\ mod_1341402404239_388.docx @ 29385 @ 5 @ 1
BU 0060 GB-4112 17
Page 18
CANopen – Supplementary manual options for NORD - Frequency Inverters
CAN _H
CAN _L
CAN _GN D
nc
CAN _SH LD
CAN _GN DncCAN_24V
CAN _H
CAN _L
CAN _GN D
nc
CAN _SH LD
CAN _GN DncCAN_24V
be used for the evaluation of an absolute
External 24VDC
RS485_A
RS485_B
GND
TXD
RXD
+ 5V
1 2
ON
CAN _H
CAN _L
CAN _G N DncCAN _SHLD
CAN _G N DncCAN_24V
CAN _H
CAN _L
CAN _G N DncCAN _SHLD
CAN _G N DncCAN_24V
Control block X9 and X10 – CAN / CANopen
Relevance
Terminals X9: / X10:
Name
SK 500E SK 505E SK 510E
1 2 3 4 5 6 7 8
CAN_H CAN_L CAN_GND nc nc CAN_SHD CAN_GND CAN_24V
SK 511E SK 515E SK 520E SK 530E SK 535E
Contact Function
[factory setting]
1 2
CAN/CANopen signal
3 CAN GND 4
No function
5 6 Cable shield 7 GND/0V 8
voltage supply
DIP-1 Termination resistor for RS485 interface
(RJ12); ON = switched in [Default = "OFF"] For RS232 communication DIP1 to "OFF"
Data Description / wiring suggestion Parameter
Baud rate …500kBaud RJ45 sockets are connected
in parallel internally. Terminal resistance
R=120DIP 2 (see below) NOTE: To operate
CANbus/CANopen the interface must be externally supplied with 24V (capacity at least 30 mA).
DIP switch 1/2 (top side of frequency inverter)
X10 X9
2x RJ45: Pin No. 1 … 8
NOTE: For frequency inverters SK 530E and above, this CANopen interface can
encoder. Further details can be found in manual BU 0510.
Recommendation: Provide strain relief (e.g. with EMC Kit)
X11 X10 X9
P503 P509
DIP 2
Terminal resistor for CAN/CANopen interface (RJ12); ON = switched in [Default = "OFF"]
Pos: 35 /Anl eitungen/El ektronik/FU und Starter /2. Montag e und Install ation/2.12 R J45 WAGO- Anschlussmod ul [Allg.] @ 0\mod_1325866182423_388.docx @ 6170 @ 3 @ 1
18 BU 0060 GB-4112
RS232/485 DIP CAN/CANopen
Page 19
2 Modules
Contact
1 2 3 4 5 6 7 8 S
Meaning
CAN_H CAN_L CAN_GND nc. nc. CAN_SHD CAN_GND CAN_24V
Shield
Ethernet connection module with CAGE CLAMP Getriebebau NORD GmbH &

2.1.3 RJ45 W AGO- Connection module

This adapter module can be used for the simple wiring of functions of the RJ45 conn ec tion (2 4V s up ply voltage, CANopen absolute encoder, CANbus) with normal cables.
Pre-assembled RJ45 p atch cables are connect ed to the spring­loaded terminals (1-8 + S) with this adapter.
The shield clamp should be used in order to ens ure the correct connection and relief of tension on the shield.
Supplier Name Article number
WAGO Kontakttechnik GmbH
connection RJ45 transfer module
WAGO Kontakttechnik GmbH Accessories: WAGO shield clamp 790-108
Alternative, complete connection module and shield clamp Part No.
289-175
Adapter module RJ45/terminal
Co.KG
Table 3: RJ45 WAGO connection module
Pos: 36 /Anl eitungen/El ektronik/Bus systeme/2 . Baugruppen/CANopen [BU0060]/CANopen Modul, SK TU3-CAO @ 1\mod_1341821626734_388.docx @ 30351 @ 3 @ 1
278910300
BU 0060 GB-4112 19
Page 20
CANopen – Supplementary manual options for NORD - Frequency Inverters
This CANopen module can be
occupies the technology slot
Alternatively, the SimpleBox SK
must be
V external
master system even without a
purpose are set using a rotary
CR
(green)
CANopen RUN
CE
(red)
CANopen ERROR
GB
(red)
Module error
(ON)
Connected
Connection to PE of the interference in the Bus lines
GND
CAN_L
6
1
5
9
GND
CAN_H
24V in
rotary coding switch are not transferred to the frequency inverter or saved. Changed

2.1.4 C ANopen module, SK TU3-CAO

used for all SK 500E devices. It
which can then no longer b e used for control and display modules.
CSX-0 can be plugged in to the CANopen module and connected to the frequency inverter via the RS232/485 interface.
The CANopen module
provided with a 24 power supply (via SUB – D9
connection). This C AN participant can therefore be identified by the
voltage supply to the frequency inverter. The data requir ed for this
coding switch. This Bus data is read in when the 24V is applied from the frequency inverter.
1 CANopen Status LEDs
DR (green) Module status
2 Termination resistor
(OFF) Not connect ed
3 Shielding terminal
frequency inverter to suppress
4 SUB – D9
Baud rate (BAUD)
Transfer rates of up to 500 kbit/s can be used (optionally up to 1Mbit/s). If BAUD is set to PGM the value from parameter P514 is used as the baud rate.
Supply voltage
The supply voltage is 24 V DC ±25% (Pin 9 = 24 V, Pin 3 = GND, approx. 80 m A). The connection is made via the SUB-D9 connector.
Termination resistor
The termination resistor for the last Bus participant is located on the CANopen Bus module.
CAN address, setting the ID (IDx1 and ID10)
The rotary switches IDx1 and IDx10 can be used to set the node identifier in decimal code in the range from 01...99
Example: Node ID = 64
If BAUD is set to PGM the value from param eter P515 of the frequenc y inverter is used as the node identifier.
Information
The settings made using the settings are only adopted when the 24V supply is applied ("Power ON").
Pos: 37 /Anleit u ng e n/3. Anzeige un d Bedienung [S K 50 0E]/SK 5xxE/ 3. 2 Ü b ersicht der Tec hn ologiebox en -2- M ontage @ 1 \mod_1340712929975_388.docx @ 28340 @ 3 @ 1
dez
.
à
IDx10 = 6, IDx1 = 4
Rotary coding switches
20 BU 0060 GB-4112
Page 21
2 Modules
Push the control terminals cover down
with an upward turning movement. If

2.1.5 Installing

note
Modules should not be inserted or removed unless the device is free of voltage. The slots may only be used for the intended modules.
Installation of a technology unit separate from the frequency inverter is not possible. It must be connected directly to the frequency inverter.
Installing the technology unit
The technology units must be installed as follows:
1. Switch off the mains voltage, observe the waiting period.
2. slightly or remove.
3. Remove the blank cover, by loosening the release on the lower edge and pulling off
necessary, the attachm ent screw next to the release must be removed.
4. Hook the technology unit onto the upper edge slots and press in lightly until it engages. Ensure full contact with t he connector strip and fasten with the screws if necessary (separat e packet).
5. Close the control terminal cover again.
Pos: 38 /Anleitungen/Elekt r oni k/Bussysteme/2. Baugruppen/Modulare Baugruppen SK 700E (SK 750E) @ 1\mod_1335270209732_388.docx @ 21746 @ 2 @ 1
BU 0060 GB-4112 21
Page 22
CANopen – Supplementary manual options for NORD - Frequency Inverters

2.2 Modular units SK 700E (SK 750E)

By the use of various modules for display, control and parameterisation, the S K 700E can be easily adapted to various requirements.
Alphanumerical display and operating modules can be used for simple commissioning. For more complex tasks, various connections to a PC or an automation system can be selected.
The Technology Unit (Technology Unit, SK TU1-...) is connected externally to the front of the frequency inverter and is therefore easy to access and replace at any time.
In addition, further modules (customer interfaces and special extensions) can be used in the frequency inverter for the processing of digital and analogue signals and for speed control or positioning.
Fig. 3: Frequency inverter SK 700E and technology units
Pos: 39 /Anleitungen/Elektronik/Bussysteme/2. Baugruppen/CANopen [BU0060]/SK TU1- CANnord / CANo pen Modul, Üb erblick @ 1\ mod_1341922786333_388.docx @ 31133 @ 3 @ 1
22 BU 0060 GB-4112
Page 23
2 Modules
Part No. 278200070
CANopen module
This option enables control of the SK 700E via the
1 CANopen interface
Part No. 278200075
frequency inverters enables parameterisation and control of devices as per the CAN
on a single Bus. Termination resistors are integrated and can
ansfer rate can be set to
integrated in the CANnord protocol enables maximum Bus
Transmitting CAN
RxD
(green)
Receiving CAN data
(ON)
Connected
(OFF)
Not connected
GND
CAN_L
6
1
5
9
GND
CAN_H

2.2.1 SK TU1- CANnord / CANopen module, overview

The communication modules SK TU1-CAN bor S K TU1-CAO are used to connect drive units of the SK 700E series to higher level automation systems via CANnord or CANopen.
Module Description Data
CANnord module
SK TU1-CAN
This option enables control of the SK 700E via the CAN serial port.
1 CANnord interface Connector: Sub-D9
SK TU1-CAO
Table 4: SK TU1-CAN / -CAO, overview of technology units
Pos: 40 /Anleit u ng e n/Elektroni k/Bussyste m e/ 2 . Ba ugruppen/CA N open [BU006 0]/ C ANnord Modul , S K TU1- CAN @ 1\mod_1341830232485_388.docx @ 30405 @ 3 @ 1

2.2.2 C ANnord module, SK TU1-CAN

The CANnord interface on NORD
CANopen serial port.
1 CANnord Status LEDs
TxD (green)
specifications 2.0A and 2.0B. Up to 110 nodes can be addressed
2 Termination resistor
be switched in. The tr
between 10 kBit and 500 Kbit/s. The conflict and error recognition
usage and data security.
Connector: Sub-D9
data
3 SUB – D9
Pos: 41 /Anleitungen/Elektronik/Bussysteme/2. Baugruppen/CANopen [BU0060]/CANopen Modul, SK T U1-CAO @ 1\mod_1341836350786_388.docx @ 30480 @ 3 @ 1
BU 0060 GB-4112 23
Page 24
CANopen – Supplementary manual options for NORD - Frequency Inverters
This CANopen module can be
occupies the technology slot
must be
V external
master system even without a voltage supply to the frequency
purpose are set using a rotary coding switch. This Bus data is
CE
(red)
CANopen ERROR
DR
(green)
Module status
(ON)
Connected
(OFF)
not connected
Connection to PE of the interference in the Bus lines
GND
CAN_L
6
1
5
9
GND
CAN_H
24V in
The settings made using the rotary coding switch are not transferred to the frequency inverter or saved. Changed

2.2.3 C ANopen module, SK TU1-CAO

used for all SK 700E devices. It
which can then no long er be used for control and display modules. The CANopen module
provided with a 24 power supply (via SUB – D9
connection). This CAN par ticipant can therefore be i dentified by the
inverter. The data re quired f or this
read in when the 24 V is applied from the frequency inverter.
1 CANopen Status LEDs
CR (green) CANopen RUN
GB (red) Module error
2 Termination resistor
3 Shielding terminal
frequency inverter to suppress
4 SUB – D9
Baud rate (BAUD)
Transfer rates of up to 500 kbit/s can be used (optionally up to 1Mbit/s). If BAUD is set to PGM the value from parameter P514 is used as the baud rate.
Supply voltage
The supply voltage is 24 V DC ±25% (Pin 9 = 24 V, Pin 3 = GND, approx. 80 m A). The connection is made via the SUB-D9 connector.
Termination resistor
The termination resistor for the last Bus participant is located on the CANopen Bus module.
CAN address, setting the ID (IDx1 and ID10)
The rotary switches IDx1 and IDx10 can be used to set the node identifier in decimal code in the range from 01...99
Example: Node ID = 64
dez
If BAUD is set to PGM the value from param eter P515 of the frequenc y inverter is used as the node identifier.
Information
.
à
IDx10 = 6, IDx1 = 4
Rotary coding switches
settings are only adopted when the 24V supply is applied ("Power ON").
Pos: 42 /Anleitungen/Elekt r oni k/Bussysteme/2. Baugruppen/Montage der SK TU1-Technologiebox @ 1\mod_1335275468416_388.docx @ 21922 @ 3 @ 1
24 BU 0060 GB-4112
Page 25
2 Modules
the intended modules. Installation remote from the frequency inverter is not possible. It must be connected

2.2.4 Installation of the SK TU1 technology unit

WARNING Electric shock
Modules must not be inserted or removed unless the device is free of voltage. The slots may only be used for directly to the frequency inverter.
Failure to comply with this may result in an electric shock, which my cause serious injury and the destruction of the frequency inverter and the module.
Installation of the technology units must be carried out as follows:
1. Switch off the mains voltage, observe the waiting period.
2. Remove the dummy cover by actuating the unlocking device on the top and bottom edge.
3. Press the technology unit onto the mounting surface, until it audibly engages.
Pos: 43 /Anleit u ng e n/Elektroni k/Bussyste m e/ 2 . Ba ugruppen/CA N open [BU006 0]/ C ANnord Modul , S K CU1- CAN @ 1\mod_1341839331541_388.do cx @ 30530 @ 3 @ 1
BU 0060 GB-4112 25
Page 26
CANopen – Supplementary manual options for NORD - Frequency Inverters
units also have
conventional digital inputs and
control can be actuated or warnings can be sent to another
X5.2
DigIN
P421
X5.3
CAN
P514 / P515
(ON)
Connected
(OFF)
not connected
Cabling can be implemented using Western connectors and
1, 2, 7, 8
n. c.
3, 6
GND
5
CAN_H (+)
Housing
PE (shield)
NOTE: All control voltages are based on a common re ference potential 0V / GND.
X5.1
X5.2
X5.3
01 REL1.1 02 REL1.2
41 VO +5V 40 GND /0V 75 CAN1 H 76 CAN1 L
21 DIG IN 1
42 VO +15V
Data leads for the Bus system used:
Output of PLC: 7.5 ... 33V
Output relay: Max. 2.0A 28V DC /230 V AC
Digital input 1 (P420)
Voltage supply: 5V, max. 300 mA
Voltage supply: 15V, max. 300mA
Plug connector MC 1.5/4-G-3.81
RJ 45 plug connector

2.2.5 C ANnord module, SK CU1-CAN

In addition to data connec tions, all Bus customer
1 Connection terminals*
X5.1 Relay P434
outputs. By means of a rela y contact, brake
system.
* max. 1.5mm²
2 Termination resistor
The digital input has a 2.5V s witching threshold for the evaluation of the temperature sensor. T he input can, however, also be used f or an emergency stop function.
commercial network cables (twisted pair, modular connector 8P8C, RJ45), networking of several devices is possible with T-connectors.
3 RJ45 contact
assignment
4 CAN_L (-)
Pos: 44 /Anleit u ng e n/Elektroni k/Bussyste m e/ 2 . Ba ugruppen/CA N open [BU006 0]/ Klemmenbel eg ung SK CU1-CAN @ 1\mod_1341842861016_388.docx @ 30581 @ 5 @ 1
SK CU1-CAN terminal assignment
Figure 4: SK CU1-CAN terminal assignment
Pos: 45 /Anleit u ng e n/Elektroni k/Bussyste m e/ 2 . Ba ugruppen/CA N open [BU006 0]/ C ANnord Modul , S K CU1- CAN-RJ @ 1\mod_1341843668047_388.docx @ 30631 @ 3 @ 1
26 BU 0060 GB-4112
Page 27
2 Modules
offers high functionality of digital signal processing and 2 parallel
control can be actuated or warnings can be sent to another
X7.2
DigIN
P420 … P424
X7.3
CAN
P509 … P515
* X7.3: 2 x RJ45 sockets
(ON)
Connected
(OFF)
not connected
Western connectors and
1, 2, 7, 8
n. c.
3, 6
GND
5
CAN_H (+)
Housing
PE (shield)
CANnord Digital inputs:
DIG IN 1
DIG IN 2
DIG IN 3
DIG IN 4
DIG IN 5
Voltage supply: 15V, max. 300mA
39 TS
-
X7.1
X7.2
X7.3
21 DIG IN 1
22 DIG IN 2
23 DIG IN 3
24 DIG IN 4
42 VO +15V
40 GND /0V
38 TS +
01 REL1.1
02 REL1.2
25 DIG IN 5
- n.c.
- n.c.
- CAN - GND
- CAN - L
- CAN - H
- CAN - GND
- n.c.
- n.c.
- n.c.
- n.c.
- CAN - GND
- CAN - L
- CAN - H
- CAN - GND
- n.c.
- n.c.
Output relay: max. 2,0A 28V DC /230V AC
Floating contact
or
PLC output:
7.5...33V
Data leads for the Bus system used:
Plug connector MC 1.5/4-G-3.81
RJ 45 plug connector
Plug connector MC 1.5/4-G-3.81
RJ 45 plug connector
DIP switch for termination resistor for CAN Bus system!

2.2.6 C ANnord module, SK CU1-CAN-RJ

The customer interface (customer unit) CANnord with RJ4 5 c onnect or
1 Connection terminals*
X7.1 Relay P434 … P436
switched data connect ions. 5 digital inputs are available to control the frequency inverter.
By means of a rela y contact, brake
* X7.1: max. 1.5 mm² * X7.2: max. 1.0 mm²
2 Termination resistor
system.
The digital inputs of the CANnord module cannot process analog setpoints!
Cabling can be implemented using commercial network cables (twisted pair, modular connector 8P8C, RJ45), networking of several devices is possible with T-connectors.
3 RJ45 contact
assignment
4 CAN_L (-)
Pos: 46 /Anleit u ng e n/Elektroni k/Bussyste m e/ 2 . Ba ugruppen/CA N open [BU006 0]/ Klemmenbel eg ung SK CU1-CAN -RJ @ 1\mod_1341903432432_388.docx @ 30691 @ 5 @ 1
SK CU1-CAN-RJ terminal assignment
Figure 5: SK CU1-CAN-RJ terminal assignment
Pos: 47 /Anleitungen/Elektronik/Bussysteme/2. Baugruppen/Montage der SK CU1-PBR Kundensc hnittstelle @ 1\mod_1335343413917_388.docx @ 22255 @ 3555 @ 1
BU 0060 GB-4112 27
Page 28
CANopen – Supplementary manual options for NORD - Frequency Inverters
WARNING
from the frequency inverter is not possible. It must be connected
Following the insertion, replacement or removal of modules, and once the equipment has been switched on
Remove the cover grille from the screws and levering out the device
Using light pressure push the
releases then make the necessary connections. Then insert the
Kundenschnittstelle
Sondererweiterung
Technologiebox
Verrieglungsstift
CLOSED
OPEN
Verriegelung geschlossen Verriegelung geöffnet
interface
extension
Lock closed

2.2.7 Installation of the SK CU1-xxx customer unit

Modules must not be inserted or removed unless the device is free of voltage. The slots may only be used for the intended modules. Installation remote directly to the frequency inverter.
Failure to comply wi th this may result in an electric shock, which my cause serious injury and the destruction of the frequency inverter and the module.
Note
again, this procedure is indicated with the mes s age E017 Customer unit changed. This message can be directly reset by the usual measures.
Installing the customer unit
1. Switch off the m ains voltage, observe the waiting period.
2. connection area by loosening the 2
cover (slot) or simply pull it out.
3. Locking lever in the "„open“ position.
4. customer unit into the upper guide rai l until it engages.
5. Locking lever in the „closed“ position.
6. Remove the conn ec tor by pressing the
7. Replace all covers.
connectors until they engage.
electric shock
Error message E017
Technology unit Locking lever
Customer
Special
28 BU 0060 GB-4112
Page 29
2 Modules
Remove the cover grille from the connection area by loosening the 2
and levering out the device
the customer unit out of its engaged
Removing the customer unit
1. Switch off the mains voltage, observe the waiting period.
2. screws
cover (slot) or simply pull it out.
3. Locking lever in the "„open“ position.
4. Using a screwdriver (as shown), lever position and then remove it by hand.
5. Locking lever in the „closed“ position.
6. Replace all covers.
BU 0060 GB-4112 29
Page 30
CANopen – Supplementary manual options for NORD - Frequency Inverters
The procedure is as described above;
Getriebebau NORD
GmbH & Co. KG D-22941 Bargteheide / Germany
Typ/Part-No: SK_XU1_POS 7820055/10C195890
Input: 6 x digital 15V / 24V Output: 2 x relay 5A 250V~/AC1 Interface: 1 x encoder A,B,N RS422 1 x SSI DAT/CLK RS422
X10.1
X10.2
X10.3
5 DIG IN 1
6 DIG IN 2
7 DIG IN 3
8 DIG IN 4
11 +15V
1 REL1.1
2 REL1.2
3 REL2.1
4 REL2.2
9 DIG IN 3
10 DIG IN 4
12 0V / GND
13 SSI CLK+
14 SSI CLK-
15 SSI DAT+
16 SSI DAT-
17 +5V
18 0V / GND
19 SPUR A+
20 SPUR A-
23 SPUR N+
21 SPUR B+
22 SPUR B-
24 SPUR N-
X10.3
Getriebebau NORD
GmbH & Co. KG D-22941 Bargteheide / Germany
Typ/Part-No/ID: SK_CU1_MLT 7820051/10C195890
Input: 2 x analog -10...10V / 0...20mA 6 x digital 15V / 24V Output: 2 x analog 0...10V 2 x relay 5A 250V~/AC1
X2.1
X2.2
X2.3
11 VREF 10V
12 AGND/0V
14 AIN 1 +
16 AIN 2 +
17 AOUT1
21 DIG IN 1
22 DIG IN 2
23 DIG IN 3
24 DIG IN 4
42 VO +15V
1 REL1.1
2 REL1.2
3 REL2.1
4 REL2.2
25 DIG IN 5
26 DIG IN 6
18 AOUT2
41 VO +5V
40 GND/0V
0/4...20mA (ON)
AIN 1
-10/0...10V (OFF)
0/4...20mA (ON)
AIN 2
-10/0...10V (OFF)
Customer
interface
Special
extension
Getriebebau NORD
GmbH & Co. KG D-22941 Bargteheide / Germany
Typ/Part-No: SK_XU1_POS 7820055/10C195890
Input: 6 x digital 15V / 24V Output: 2 x relay 5A 250V~/AC1 Interface: 1 x encoder A,B,N RS422 1 x SSI DAT/CLK RS422
X10.1
X10.2
X10.3
5 DIG IN 1
6 DIG IN 2
7 DIG IN 3
8 DIG IN 4
11 +15V
1 REL1.1
2 REL1.2
3 REL2.1
4 REL2.2
9 DIG IN 3
10 DIG IN 4
12 0V / GND
13 SSI CLK+
14 SSI CLK-
15 SSI DAT+
16 SSI DAT-
17 +5V
18 0V / GND
19 SPUR A+
20 SPUR A-
23 SPUR N+
21 SPUR B+
22 SPUR B-
24 SPUR N-
X10.3
Getriebebau NORD
GmbH & Co. KG D-22941 Bargteheide / Germany
Typ/Part-No/ID: SK_CU1_MLT 7820051/10C195890
Input: 2 x analog -10...10V / 0...20mA 6 x digital 15V / 24V Output: 2 x analog 0...10V 2 x relay 5A 250V~/AC1
X2.1
X2.2
X2.3
11 VREF 10V
12 AGND/0V
14 AIN 1 +
16 AIN 2 +
17 AOUT1
21 DIG IN 1
22 DIG IN 2
23 DIG IN 3
24 DIG IN 4
42 VO +15V
1 REL1.1
2 REL1.2
3 REL2.1
4 REL2.2
25 DIG IN 5
26 DIG IN 6
18 AOUT2
41 VO +5V
40 GND/0V
0/4...20mA (ON)
AIN 1
-10/0...10V (OFF)
0/4...20mA (ON)
AIN 2
-10/0...10V (OFF)
Customer-
interface
Special-
extension
Deviating position of the customer unit for SK 700E above 30 kW and all SK 750E devices Installation
however no locking lever is present. The modules engage on the front edge when they are inserted.
Dismantling
As shown, simply le ver out from the upper edge. If this is diff icult, simply unfasten the locking hook on the f ront e dge.
Pos: 48 /Anleitungen/Elektronik/Bussysteme/2. Baugruppen/Modulare Baugruppen trio SK 300E und SK 750E @ 1\mod_1335348745477_388. doc x @ 22556 @ 2 @ 1
30 BU 0060 GB-4112
Page 31
2 Modules
CANopen module
IP55
This option enables control
1 CANopen interface
CANopen module
IP66
Information
it is fully compatible with the

2.3 Modular units trio SK 300E and SK 750E

Technology units are optiona l modules with which a dditional functions in the f requency inverter can
be added depending on requirem ents. The high level of protection of the frequency inverter remains with all technology units.
Fig. 6: Frequency inverters SK 300E and SK 750E
Pos: 49 /Anleitungen/Elektronik/Bussysteme/2. Baugruppen/CANopen [BU0060]/SK TU2- CANopen Modul, Ü berblick @ 1\mod_1341907894144_388.docx @ 30720 @ 3 @ 1

2.3.1 SK TU2- CANopen module, overview

The communication m odule SK TU2-CAO, is us ed to connect drives f rom the trio SK 300E and 750E device series to h igher leve l autom ation s ystem s via CANop en. B oth the SK 300E fr equency i nverter s and the external technology units are available in the protection classes IP55 (standard) and IP66 (optional). The type design ation of the SK 300E and t he modules in the pro tection clas s IP66 is given an additional code "-C" (coated → coated board) to differentiate the IP55 and IP66 protection classes. For SK 750E frequency inver ters, the protection c lass is specified b y the type of cooling. IP54 for air­cooled devices and IP65 for water-cooled SK 750E frequency inverters.
Module Protectio
n class
SK TU2-CAO
of the SK 300E/750E via the serial CANopen port.
SK TU2-CAO-C
Table 5: SK TU3-CAO, Overview of Technology Units
Description Data
2 x 5-pin M12 system plug connector Part No. 275130100 (IP55) Part No. 275170100 (IP66)
Information
Modules of the IP66 version have an additional "C" in the type code and are modified with several special measures (see Manual SK 300E or SK 750E).
The SK 300E must have at least software version 1.6 R1 (see P707) so that CANopen protocol.
Pos: 50 /Anleitungen/Elektronik/Bussysteme/2. Baugruppen/CANopen [BU0060]/CANopen Modul, SK TU2-CAO @ 1\mod_1341927267491_388.docx @ 31318 @ 3 @ 1
BU 0060 GB-4112 31
IP66 version
Firmware version
Page 32
CANopen – Supplementary manual options for NORD - Frequency Inverters
connection). This CAN participant can therefore be
ing switch.
V is applied from the
CR
(green)
CANopen RUN
CE
(red)
CANopen ERROR
DR
(green)
Module status
GB
(red)
Module error
Error
(red)
Inverter error*
* The flashing frequency corresponds to the error number (see BU0300)
ID-L
Addressing ( ID x 1 )
Baud
Baud rate
1
PE (shield) *
3
GND 4 CAN-H
* Pin 1 and housing
Information
The settings made using the rotary coding switch are not transferred to the frequency inverter or saved. Changed
Stift
(Bus-In)
Buchse
(Bus-Out)
(aus Bauteilesicht, A-kodiert)
2
1
4
3
5
1
2
3
5
4

2.3.2 C ANopen module, SK TU2-CAO

The CANopen module must be provided with a 24 V external power supply (via SUB - D9
identified by the master system even without a voltage sup ply to the frequency invert er. The data required for this purpose a re set using a rotary cod This Bus data is read in when the 24 frequency inverter.
3 Rotary coding switches
ID-H Addressing ( ID x 10 )
1 CANopen Status LEDs
2 SK 300E status LEDs
On (green) Mains voltage applied
4 M12 BUS-In / BUS-Out
4 Plug connector
2 +24V
5 CAN-L
assignment:
Baud rate (BAUD)
Transfer rates of up to 500 kbit/s can be used (optionally up to 1Mbit/s). If BAUD is set to PGM the value from parameter P514 is used as the baud rate.
Supply voltage
The supply voltage is 24 V DC ±25% (Pin 9 = 24 V, Pin 3 = GND, approx. 80 m A). The connection is made via the SUB-D9 connector.
Termination resistor
The termination resist or for the last bus participant can be s witched to the output (BUS-Out) of the final frequency inverter as the termination connector.
CAN address, setting the ID (ID-L and ID-H)
The rotary switches ID-L and ID-H c an be us ed to set the node identifier in decim al code in t he range from 01...99
Example: Node ID = 64
dez
.
à
ID-H = 6, ID-L = 4
If BAUD is set to PGM the value from param eter P515 of the frequenc y inverter is used as the node identifier.
Rotary coding switches
settings are only adopted when the 24V supply is applied ("Power ON").
Pos: 51 /Anleitungen/Elekt r oni k/Bussysteme/2. Baugruppen/Montage der SK TU2-Technologiebox @ 1\mod_1335440910321_388.docx @ 22864 @ 35 @ 1
32 BU 0060 GB-4112
Page 33
2 Modules
the intended modules. Installation remote from the frequency inverter is not possible. It must be connected
is being
technology unit to ensure it is fully earthed. Operation is not permi tted if

2.3.3 Installation of the SK TU2 technology unit

WARNING
Modules must not be inserted or removed unless the device is free of voltage. The slots may only be used for directly to the frequency inverter.
Failure to comply with this may result in an electric shock, which my cause serious injury and the destruction of the frequency inverter and the module.
Electric shock
Installing the technology unit
1. Switch off the mains voltage, observe the waiting period.
2. Unscrew the 6 fastening screws of the blind plate land remove the blind plate (Fig.1).
3. Attach the PE connec tion on the inside of the technology unit which installed (Fig. 2). Fit the seal together
Screw 4
Screw 2 Scre w 1
Screw 6 Scre w 5
Screw 3
with the technology unit on the surface of the frequency inverter. Ensure that the connector strip makes full contact.
4. Lightly tighten all 6 fastening screws.
5. Now tighten the 6 fastening screws in the specified sequence fr om 1 to 6 (see
Fig. 1
Fig. 1) and with the torque s tated in the table.
Frequency inverter size Screw size Tightening torque
Size 1 Size 2
M4 x 8 1.5Nm ± 20%
NOTICE
Note the earthing cable! Make sure the earthing line is plugged into the plate of the standard device and each technology unit. This cable
must be connected when installing the there is no secure PE connection to the frequency inverter and to the technology unit, beacause frequency inverter and technology unit could be destroyed!
Earthing / Grounding
BU 0060 GB-4112 33
Fig. 2
Page 34
CANopen – Supplementary manual options for NORD - Frequency Inverters
With IP66 versions, care must also be taken that the cables and cable glands at least comply with protection
The components listed below or in this section should only be regarded as recommendations. For further
Please observe the manufacturer's information regarding installation and the corresponding installation
MURR Elektronik
M12 plug, 6...8mm, 5-pin, screwed, IP67, shielded
7000-13321-0000000
7000-13361-0000000
Franz Binder GmbH
M12 plug, 6...8mm, 5-pin, screwed, IP67,
99 1437 812 05
99 1437 822 05
NOTICE
During installation, attention must be paid to proper sealing (do not forget the rubber seal!), to prevent the entry of moisture.
class IP66, so that compliance with protection class IP66 is ens ured on the frequency inverter.
Entry of moisture
Pos: 52 /Anleitungen/Elektronik/Bussysteme/2. Baugruppen/Stecker- und Zubehör- Komponenten/!Empfohlene Stecker- un d Z u be hör- Komponenten @ 1\mod_1335448576891_388.docx @ 23681 @ 3 @ 1

2.3.4 Recommended connector and accessory components

Note
information please refer to the particular manufacturer's information and data sheets.
guidelines.
Pos: 53 /Anleitungen/Elektronik/Bussysteme/2. Baugruppen/Stecker- und Zubehör- Ko mponenten/M 12 Rundstec kverbinder C AN [CAN] @ 1\mod_1342001545219_388.docx @ 31482 @ 56666 @ 1
M12 round plug CAN connector
Information
For preference, pre-assembled CAN bus cables and connection components should be used. For certain applications, vibration-proof round plug connectors should be used.
Recommendations of products
Connection components
M12 connector
A coded
Supplier Name Part no.:
straight angled
34 BU 0060 GB-4112
Page 35
M12 socket
MURR Elektronik
M12 socket, 6..8mm, 5-pin, screwed, IP67, shielded
Franz Binder GmbH
M12 socket, 6…8mm, 5-pin, screwed, IP67,
MURR Elektronik
Termination resistor, plug
pin, straight,
Lumberg
Bus terminating resistor, M12
MURR Elektronik
Phoenix Contact GmbH
pin, parallel
A coded
2 Modules
Supplier Name Part no.:
straight angled
7000-13401-0000000 7000-13441-0000000
99 1436 812 05 99 1436 822 05
M12 termination resistor
A coded
Supplier Name Part no.:
M12- T connectors
A coded
Supplier Name Part no.:
& Co. KG
connector M12, 5­IP67
plug connector
M12 plug to 2x M12 socket, 5­pin, parallel distributor, IP67
M12 socket to M12 plug and socket, 5­distributor, IP67
7000-13461-0000000
RST ST
7000-41141-0000000
1541186
BU 0060 GB-4112 35
Page 36
CANopen – Supplementary manual options for NORD - Frequency Inverters
MURR Elektronik
M12 wrench set for M12 round connectors with
M12 torque wrench for M12 round connectors with
proof connection, connecting components with hexagonal
Pos: 54 /Anleitungen/Elektronik/Bussysteme/2. Baugruppen/Stecker- und Zubehör- Ko mponenten/M ontagewer kzeug für M12 Rundsteck verbinder @ 1\mod_1335514816410_388.docx @ 24212 @ 5 @ 1
Installation tools for M12 round plug connectors
Torque wrench for assembly of M12 plug connectors The M12 torque wre nch set is used to c heck the optim um tightening t orque of M12 r ound connec tors.
The torque wrench is calibrated to the optimum tightening torque is 0.6Nm.
Supplier Name Article No. / Part No.
7000-99102-0000000
calibrated torque of 0.6Nm
Franz Binder GmbH
07-0079-000
calibrated torque of 0.6Nm
Note
In order to ensure a secure, sealed and vibration­fittings should be used.
By means of the corresponding installation tools, after completion of installation work, all M12 round connectors should be tightened to a torque of 0.6Nm with an M12 wrench.
Mounting connecting components
Pos: 55 /Anl eitungen/El ektronik/Bus systeme/3 . Busaufbau/ CANopen [ BU0060]/!Ka pitel Busauf bau @ 1\mod_1342078795031_388.docx @ 31754 @ 1 @ 1
36 BU 0060 GB-4112
Page 37
3 Bus Configuration
Up to 25m
70 mΩ/m
≥ 0.25 mm2, AWG23
1 Mbit/s
25 - 50m
70 mΩ/m
≥ 0.25 mm2, AWG23
800 kBits/s
50 - 80m
< 60 mΩ/m
≥ 0.34 mm2, AWG22
500 kBits/s
80m - 230m
< 40 mΩ/m
≥ 0.5 mm2, AWG21
250 kBits/s
230m – 480m
< 26 mΩ/m
≥ 0.75 mm2, AWG18
125 kBits/s
480m – 1km
< 20 mΩ/m
≥ 1 mm2, AWG…
50 kBits/s

3. Bus Configuration

A CAN network consists of a maximum of 128 part icipants (nodes) and is based on a linear to pology. The number of subscribers is dependent on the driver modules (standard approx. 100 nodes). Repeaters must be used for a high number of nodes.
With NORD frequency inverters, a twisted two-wire line is used for data transfer.
Pos: 56 /Anleit u ng e n/Elektroni k/Bussyste m e/ 3 . Bus aufbau/CAN open [BU00 60] / V er l eg ung der Buskab el @ 1\ mod_1342078992314_388.docx @ 31779 @ 2 @ 1

3.1 Laying the bus cables

In an industrial environm ent the corr ect install ation of the bus system is par ticularly im portant in order to reduce potential i nterference. The following points ar e designed to help prevent interferenc e and problems right from the start. The installation guidelines are not com plete and applicable safety and accident prevention guidelines must be complied with.
Pos: 57 /Anleit u ng e n/Elektroni k/Bussyste m e/ 3 . Bus aufbau/CAN open [BU00 60] / L ei t ung smaterial @ 1\ mod_1342079075458_38 8.docx @ 31 804 @ 2 @ 1

3.2 Cable material

The frequency inverter is usually connected to the CANnord system by a twisted, shielded two-wire cable. The guaranteed tran sf er speeds or trans fer dis t ances c an on ly be ac hiev ed without err ors if the specific cable parameters are complied with.
Bus cable length Resistance Cable cross-section Possible transfer rates
Table 6: Transfer speeds versus cable length
The interface complies with I SO 11898. T he m axim um perm issible voltag e on the CAN_L and C AN _H cables is -8V … +8V.
Pos: 58 /Anl eitungen/El ektronik/Bus systeme/3 . Busaufbau/ Leitungsf ührung und Sc hirmung (EM V- Maßnahm en) @ 1\mod_1335520188525_388.doc x @ 24384 @ 2 @ 1
BU 0060 GB-4112 37
Page 38
CANopen – Supplementary manual options for NORD - Frequency Inverters
Minimum radius
Minimum radius
Correct
Incorrect
NOTICE
If earthing potential values are different, transient current may flow through shielding whi ch is connected on both

3.3 Cable layout and shielding (EMC measures)

If EMC measures are not in place, high-frequenc y interference which is m ainly caused by switching processes or lightning often causes electronic components in the bus subscribers to be faulty and error-free operation can no longer be ensured.
Appropriate shielding of the bus cable reduces electri cal interference which can aris e in an industrial environment.
The best shielding qualities can be achieved with the following measures:
• Do not make cable connections shorter than 1 m between bus participants
• Avoid long connections between bus participants
• Shield the bus cable at both ends with large-area connection to the plug housing
• Avoid spur lines
• Avoid extensions to bus cables via plug connectors
Bus lines should be laid with a minim um spacing of 20 cm to other lines which c arry a voltage higher than 60 V. This applies to lines laid inside and outside of control cabinets.
Special attention should be paid to bending radii:
Fixed cable Freely laid cable Bending radius of cable
5 x cable diameter
Fig. 7: Installation and cable laying information
10 x cable diameter
Potential equalisation
sides. This may be a danger to electronic components. Differences in potential must be reduced by means of adequate potential equalisatio n.
Pos: 59 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/!Ka pitel Kommu nikation und Protokoll @ 1\ mod_1342081745953_388.docx @ 31856 @ 1 @ 1
38 BU 0060 GB-4112
Page 39
4 Communication and Protocol
Information
STW
Control Word; length 16 bit, order telegram error acknowledgement)
ZSW
Status Word; length 16 bit, response telegram
cont
SW 1 … 3
Setpoints; 3 x 16 bit or 1 x 32 bit and 1 x 16 bit, order telegram, e.g. frequency setpoint,
IW 1 … 3
Actual values; 3 x 16 bit or 1 x 32 bit and 1 x 16 bit, response telegram, e.g. actual frequency, If CANnord / CANopen is implemented via the internal RJ45 sockets, the setpoints and actual values 4 and 5 can

4. Communication and Protoc ol

Pos: 60 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Informa tion Datenfor mat Little Endi a n @ 2\ mod_1347891008211_388.docx @ 47676 @ @ 1
Data transfer is performed in Little Endian format. This means that in the data word, the High byte follows after the Low byte. Example: "047E" à 7E 04.
Pos: 61 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/Pr ozessdatenver arbeitung i m FU allge mein/!Prozes sdatenverar beitung im Frequenzumri chter @ 1\ mod_13363800 77511_388.docx @ 25252 @ 2 @ 1

4.1 Processing of Process Data in the Frequency Inverter

Pos: 62 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Datenü bertragung all gemein/zu Prozessdat enverarbeit ung im Frequ en z u mr i c hter [CANope n BU 0060] @ 1\mod_1342603933090_388.docx @ 34008 @ @ 1
The following CAN profile specifications apply to process data transfer with all CANnord/CANopen interfaces in NORD frequency inverters. This protocol is used when P551 = 0 is set.
Pos: 63 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/Pr ozessdatenver arbeitung i m FU allge mein/Prozes sdaten allg emein (PZD) @ 1\mod_1336385071672_388.docx @ 25423 @ 3 @ 1

4.1.1 Process dat a - General (PZD)

In the process data area (PZD) , control words and setpoints are transferred fr om the master to the frequency inverter and in return, status words and actual values are sent from the inverter to the master. The structure of the PZD area is always the same in terms of the sequence of its elements (words), however, depe ndent upon d irection of data Mas ter à Slave / Slave à Master, it is described differently.
Little Endian data format
The process data area of the reference data has the following structure:
position setpoint, torque setpoint.
actual position, actual torque.
Pos: 64 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Datenü bertragung all gemein/Pr ozessdaten al lgemein (PZ D) - Ergänzung SK54xE [CANopen über RJ45] @ 2\mod_1347371435376_388.docx @ 45481 @ @ 1
Information
SK 54xE – CAN via RJ45
also be communicated (SK 54xE and above).
Pos: 65 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/Pr ozessdatenver arbeitung i m FU allge mein/Steuer wort (STW) @ 1\mod_1336386809690_388.docx @ 25519 @ 3 @ 1
BU 0060 GB-4112 39
Page 40
CANopen – Supplementary manual options for NORD - Frequency Inverters
Valu e
0 0 Not ready for operation
Reverse with the brake ramp, with disconnection from supply at f=0Hz (OFF1)
1
Ready for operation
Frequency inverter ready for operation
Disable voltage
where switching on is disabled. (OFF2)
1 Do not disable voltage
Operating condition OFF 2 is cancelled
Emergency Stop
f=0Hz; the FI switches to starting disabled condition (OFF3).
1 Emergency Stop not active
Operating condition OFF 3 is cancelled
3 0 Disable operation
Cut off voltage; the inverter output voltage is switched off; the FI enters a state 1
Enable operation
The output voltage is enabled; ramp to the exis ting setpoint
4 0 Pulse not enabled
Ramp generator is set to zero; no disconnection from supply at f=0Hz; FI remains in the operation enabled state.
1
Enable pulses
Enable ramp generator
5 0 Ramp not enabled
The setpoint currently provided by the ramp generator is "frozen" (frequency is maintained).
1
Enable ramp
Enable setpoint on ramp generator
6 0 Setpoint not enabled
Selected setpoint value is set to zero on the ram p generator.
1
Enable setpoint
Selected ramp generator setpoint is activated.
7 0 No acknowledgement
With the switch from 0 to 1, errors which are no longer active are ack nowledged.
1
Acknowledge error
Note: If a digital input has been programmed for the "ack.fault" function, this bit be prevented).
8 0
1
Start function 480, 11
Bus bit 8 from the control word is set. Only for SK 2xxE and SK 5xxE. For further details of the function please refer to parameter P480.
9 0
1
Start function 480, 12
Bus bit 9 from the control word is set. Only for SK 2xxE and SK 5xxE. For further details of the function please refer to parameter P480.
10 0 Control data invalid
The transmitted process data is invalid.
1
Control data valid
Valid process data is trans ferred from the master. (setting: interface), even if only setpoint values are transmitted via the bus.
11 0
1
Rotation right is on
Rotational direction right (priority) ON*
12 0
1
Rotation left is on
Rotational direction left ON*
13
0/1
Reserved
Reserved
14
0/1
Parameter set Bit 0 ON
15
0/1
Parameter set Bit 1 ON

4.1.2 Control word (STW)

The control word (STW ) is the firs t word transf erred to the f requenc y inverter in th e process data ar ea in an order telegram . For example, a control word "Ready for switch-on " corresponds to 047E general the command "Standby" should be the first command which is transferred to the inverter.
(hex)
. In
Bit
1 0
2 0
Meaning Remarks
Cut off voltage; the inverter output voltage is switched off; the FI enters a state
active
Quick stop with programmed quick stop time; with disconnection from supply at
where switching on is enabled.
(0à1)
must not permanently be set to 1 via the bus (otherwise, flank evaluation would
Note: In order for the transmitted setpoint to be valid, this bit must also be set
00 = Parameter set 1 01 = Parameter set 2
* If Bit 12=0, then "Direction of rotation right ON" applies
Table 7: Control word (STW)
Pos: 66 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/Pr ozessdatenver arbeitung i m FU allge mein/Zustan dswort (ZSW) @ 1\mod_1336386086317_388.docx @ 25495 @ 3 @ 1
10 = Parameter set 3 11 = Parameter set 4
40 BU 0060 GB-4112
Page 41
4 Communication and Protocol
Valu e
0 0 Not ready to start
1
Ready to start
Initialisation completed, charging relay ON, output voltage disabled
1 0 Not ready for operation
Causes: No command has been activated, fault is signal ed, O FF 2 or OFF3 activated, starting disabled sta te activ ated
1
Ready for operation
ON command activated, no faults present. The inverter can be started with the command ENABLE OPERATION
2 0 Operation not enabled
1
Operation enabled
The output voltage is enabled; ramp to the existing setpoint
3 0 No error
1
Fault
Drive fault resulting in stoppage; this state is changed to starting disabled after the fault has been successfully acknowledged
4 0 Voltage not enabled
OFF2 command applied
1
Voltage enabled
5 0
Emergency stop
OFF3 command applied
1 No emergency stop
6 0
Starting not disabled
1
Starting disabled
Switches first to OFF1, then to ready-to-start status
7 0 No warning
1
Warning active
Drive operation continues, no acknowledgement necessary
8 0 Setpoint not reached
Actual value does not match the setpoint (with posicon: failure to reach setpoint position)
1
Setpoint reached
Actual value matches required setpoint (setpoint has been reached) (with posicon: setpoint has been reached)
9 0 Bus control not active
Guidance on local device has been activated
1
Bus controller active
The master has been requested to assume guidance.
10 0
1
Start function 481.9
Bus bit 10 from the status word is set. For further details of function, please refer 11 0
1
Rotation right is on
Inverter output voltage is turning right
12 0
1
Rotation left is on
Inverter output voltage is turning left
13 0
Start function 481.10 to parameter P481.
15
0/1
Parameter set Bit 1 ON

4.1.3 Status word (ZSW)

In the inverter res po ns e t el egram, in the area of th e pr oc ess data th e s ta tus w ord ( ZSW) is transferred as the first word. The meaning of the individual bits deviate for some types of devices.
Bit
Meaning Remarks
1
14 0/1
Table 8: Status word (ZSW)
Pos: 67 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/Pr ozessdatenver arbeitung i m FU allgemei n /Zustands m asc hi ne des Freque nz umrichters @ 1\ mod_1336391920819_388.docx @ 25639 @ 3 @ 1
Parameter set Bit 0 ON
to parameter P481.
Bus bit 1 3 from the status word is set. For further details of function, please refer
00 = Parameter set 1 01 = Parameter set 2
10 = Parameter set 3 11 = Parameter set 4
BU 0060 GB-4112 41
Page 42
CANopen – Supplementary manual options for NORD - Frequency Inverters
Switch-on
disable
Emergency
stop
Disable voltage
Fault
Operation
enabled
Standby
Ready for
switch-on
Not ready to start
0 X X 0 0 0 0
Starting disabled
1 X X 0 0 0 0
Ready to start
0 1 1 0 0 0 1
Activated
0 1 1 0 0 1 1
Operation enabled
0 1 1 0 1 1 1
Fault
0 X X 1 0 0 0
Error active
0 X X 1 1 1 1
Emergency stop
active

4.1.4 Frequency inverter status machine

The frequency inverter passes through a status m achine. The changes between various states are triggered by the res pective control comm ands in the process data c ontrol word. The actual st atus is returned in the process data status word.
After switching on, the inverter is in switch-on disabled status. This status can only be ended by transmitting the “Shut down (Off 1)” command.
The answer to a m aster telegram normally does not yet contain a reaction to the contr ol command. The controller must c heck the answers from the slaves as to whether the contr ol command has been carried out.
The following bits indicate the status of the frequency inverter:
Status Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 0 1 0 1 1 1
42 BU 0060 GB-4112
Page 43
4 Communication and Protocol
Internal st atus machi ne
3 4 5 6 8
1
Not on standby
Switching on the inverter
5
6
Emergency stop
active
Bit2 = 0: Emergency stop
Bit1 = 0: Disable voltage
v Bit2 = 0: Emergency stop
2
Switch-on
4 5
Bit0 = 0: Shut dow n
3
Ready for
2
5
Bit 3 = 0:Disable operation Bit0 = 1: Sw itch on
3
5
2 3
sw itch-on
4
Activated
Loading relay applied
disabled
Bit0 = 0: Shut dow n & Bit1 = 1: Enable voltage & Bit2 = 1: Enable pulses (xxxx x1xx xxxx x110)
2
From any device status
7
Error reaction
active
8
Error
f = 0 reached (emergency stop com plete)
Error
Error reaction complete
Bit3 = 1: Enable operation
& Bit0 = 1: Switch on
5
Operation
2
3 64
Control bits
0. Standby / Shut dow n
1. Disable / enable voltage
2. Enable pulses / emergency stop
3. Disable / enable operation
4. Betriebsbedingung / HLG sperren
5. Enable / stop RUE
6. Enable / disable setpoint
7. Error acknowledgement (0
10. Control data valid / invalid
11. Direction of rotation clockwise
12. Direction of rotation anticlockwise
14. Parameter set Bit 0
15. Parameter set Bit 1
è
1)
enabled
Priority of control commands:
1. Disable / enable voltage
2. Emergency stop
3. Shut down
4. Enable operation
5. Switch on
6. Disable operation
7. Reset error
Fig. 8: Status Machine of the Frequency Inverter
Pos: 68 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/Pr ozessdatenver arbeitung i m FU allge mein/Sollwer t (SW) @ 1\ mod_13363902 48316_388.docx @ 25543 @ 355 @ 1
Bit3 = 1: Enable operation
Bit4 = 0: Move down emergency stop ramp and
remain in 'Operation enabled'
Bit5 = 0: Hold frequency Bit6 = 0: Setpoint = 0%
2
Coding of status:
1: Bit 0 = 0 2: Bit 6 = 1 3: Bit 0 = 1 4: Bit 1 = 1 5: Bit 2 = 1 6: Bit 5 = 0 7: Bit 2 & Bit 3 = 1 8: Bit 3 = 1
Bit7 0è1
Error acknowledgement
BU 0060 GB-4112 43
Page 44
CANopen – Supplementary manual options for NORD - Frequency Inverters

4.1.5 Setpoi nt (SW)

The function of the 1st setpoint is set in parameter P546 (respectively P546 [-01]). The following options are available:
Setpoint frequency (16 bit)
The setpoint frequency in setpoint 1 is transferred as a 16 Bit value as standard. Setpoint 1 is transferred to the inverter as the second word in the process data area of the order telegram.
PZD1 PZD2 PZD3 PZD4 STW
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
The setpoint is transf erred as a whole number with a value range of -32768 to 32767 (8000 hex to 7FFF hex). The value 16384 (4000 hex) is equal to 100%. The value C000 HEX corresponds to ­100%. A setpoint of 100% c orresponds to the param eter maximum frequ ency (parameter P105) set in the same parameter set.
SW1 SW2/3 SW2/3
Setpoint position (16 or 32 Bit)
Using the posicon special extension POSICON ( SK XU1 -POS) of the SK 700E , the abs olute setpoint position can be transfer red in setpoint 1 . It can be trans ferred as a 16 or 32 Bit value with a res olution of 1=0.001 revolutions. In addition, the control terminals (POSICON control bits setting) can be transferred in binary.
The SK 53xE / SK54xE version of the SK 500E series is also able to transfer pos itions, however here, the 32 Bit position is divided into two 16 Bit components (Low word and High word). The assignment of the tw o 16 Bit components is then carr ied out via appropriate parameterisat ion on 2 arbitrary setpoints (e.g.: SW1 and SW2).
16-Bit setpoint position setting:
As a 16 Bit value, a range of +32767 (= 32,767 revolutions) to -32768 (= -32,768 revolutions) is possible. The 16 Bit setpoint pos ition is transferred as the sec ond word in the process data area (as with the setpoint, see above)
32-Bit setpoint position setting:
As a 32 Bit value, the full position range of +/- 50000,000 revolutions is available. With the SK 700E/750E, the 32 Bit setpoi nt position is transferred in the area of the proces s data as the second and third word. With the SK 500E in any t wo of the thre e words PZD 2, PZD3, PZD 4.
PZD1 PZD2 PZD3 PZD4
STW SW1, 32 Bit SW2
P546=3, 32bit setpoint position
SK 700E/750E
POSICON
SW1, 16 Bit SW2, 16 Bit SW3
44 BU 0060 GB-4112
P546=21 (23)
Low word
P546[-01]=21
(23)
Low word
P547=22 (24)
High word
P546[-02]=22
(24)
High word
SK 54xE
SK 53xE
Page 45
4 Communication and Protocol
Bits 0-5
Position array/position increm ent
Bit 6
Approach reference point
Bit 7
Reference point
Bit 8
Teach-in
Bit 9
Quit teach-in
Bit 10
Reset position
Bits 0-3
Position array/position increm ent
Bits 4-7
Vacant
Bits 8­15
no significance
Posicon control bits setting:
A 16 Bit value is transf erred in which the control term inals of the posicon special extens ion unit are mapped. The setpoint position is based on the position array / position increment as per the P610 setpoint mode.
The transferred Bits have the following meaning (see Manual BU 0510 / BU 0710):
SK 7x0E + SK XU1-POS
Bit Function
SK 53xE / SK 54xE
Bit Function
Pos: 69 /Anleit u ng e n/Elektroni k/Bussyste m e/ 4 . Ko mmunikatio n und Protokoll + Prozessdate ntransfer/ Prozessdaten verarbeit ung im FU allg emein/Soll wert 2 und 3 @ 1\mod_1336390666445_388.docx @ 25567 @ 5 @ 1
Setpoints 2 and 3
In addition to setpoint 1, two further setpoints can be transferred. The division to the process data words PZD3 and PZD4 depends on the inverter series:
PZD1 PZD2 PZD3 PZD4
STW SW1 SW3 SW2 SK 300E, SK 7x0E STW SW1 SW2 SW3 SK 5xxE
SK 7x0E: thir d setpoint value can o nly be tr ansferred if a 32 Bit setp oint value is not transf erred in the first setpoint.
PZD1 PZD2 PZD3 PZD4
STW
SW1 SW2
The second and third s et po ints are al wa ys 16 Bit . T he f unc tion of th e s ec ond an d third s et po int c a n be set in the inverter under th e parameter 'Fct. Bus Set point 2' (P547 or P546 [-02]) as well as 'Fct. Bus Setpoint 3' (P548 or P546 [-03]).
Both setpoints are tra nsferred as whole numbers in t he range (-32768 to 32767). The valu e 16384 (4000 HEX) correspon ds to 100%. The value C0 00 HEX is equal to –100 %, so that setpoints in th e range –200% to +200% c an be tr ansf erred. A setpoint of 100% corr esponds to th e res pective nom inal value (Section 4.1.7).
In addition, posicon c o ntrol bits can also be transferred here.
Pos: 70 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/Pr ozessdatenver arbeitung i m FU allgemein/Sollwert 4 und 5 [CANopen] @ 2\mod_1348567622494_388.docx @ 48423 @ 5 @ 1
BU 0060 GB-4112 45
Page 46
CANopen – Supplementary manual options for NORD - Frequency Inverters
Bits 0-5
Digital input 1-6
Bit 6-11 for POSICON special extension unit
Digital input 7-12
Bit 6 for encoder special extension unit
Digital input 7
Bits 12-15
Multifunctional relay 1-4
Bits 0-4
Digital input 1-5
Bit 5-6 (above SK 520E)
Digital input 6-7
Bits 12-15
Relay and digital outputs 1 - 4
Setpoints 4 and 5
SK 540E and SK 545E freq uency in verters c an also pr ocess the 16 bit setp oints 4 and 5. T he f unction of these setpoints can be set in the inver ter under the parameter 'Fct. Bus Setpoint 4' (P546 [-04]) as well as 'Fct. Bus Setpoint 5' (P546 [-05]).
The value range and scaling corespond to setpoints 2 and 3.
Pos: 71 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/Pr ozessdatenver arbeitung i m FU allgemein/Istwert (IW) @ 1\mod_1336391486983_388.docx @ 25591 @ 3 @ 1

4.1.6 Actual value (IW)

The actual value 1, i. e. the actual outpu t frequenc y of the inverter, is tr ansferred as a 1 6 Bit value as standard in the actual value 1. T he actual val ue 1 is transf erred to the m aster in t he inverter r esponse telegram as the second word in the process data area.
PZD1 PZD2 PZD3 PZD4 ZSW IW1 IW2/3 IW2/3
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
The actual value 1 is trans ferred as a whole number in the rang e -32768 to 32767. In addit ion to the actual frequency, other actual inverter values can be transferred. The setting is made in P543 (or P543 [-01]) 'Actual bus value 1'.
The settings ‘Actual frequency’, ‘Actual speed’, ‘Current’ and ‘Torque current’ are transferred as percentages of the respective nominal values. The value 16384 (4000 HEX) corres ponds to 100%. The value C000 HEX corresponds to -100%. Actual values in the range –200% to +200% can be transferred.
With the setting ‘Digital I/O status’, the states of the control terminals and the relay (MFR) /digital outputs can be transferred:
SK 300E/700E/750E
Bit Status
SK 5xxE
Bit Status
With the settings ‘Actual position’ and ‘Setpoint position’, the actual absolu te position is transferred. The resolution is 1 = 0.001 revolutions.
46 BU 0060 GB-4112
Page 47
4 Communication and Protocol
If with SK 700/750E th e value 'Setpoint positi on 32Bit' is set in param eter P546 'Setpoint 1 funct ion', the actua l value of the set point p osition or actual p osition is also tra nsfer red as a 32Bit valu e in PZD2 and PZD3:
PZD1 PZD2 PZD3 PZD4
ZSW IW1 IW2
Pos: 72 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/Pr ozessdatenver arbeitung i m FU allge mein/Istwert 2 und 3 @ 1\ mod_1336391763600_388.docx @ 25615 @ 5 @ 1
Actual value 2 and 3
It is possible to forward two more actual values to the controller. The assignment of the actual val ues 2 and 3 to the process data words PZD3 and PZD4 is c arried out
in the same way as the assignm ent of setpoints 2 and 3. These also differ in sequence b etween the SK 5xxE and other inverter series.
SK 300E/SK 700E/SK 750E The actual value 2 (IW 2) is transm itted in PZD4. T he value to be transferred ca n be selected "Actual
bus value 2" (P544). Actua l value 3 (IW 3) can be transmitted in PDZ3 if act ual value 1 is not a 32 Bit value. The value to be transferred can be selected "Actual bus value 3" (P545).
SK 5xxE The actual value 2 (IW 2) is transm itted in PZD3. T he value to be transferred ca n be selected "Actual
bus value 2" (P544 or P5 43 [-02]). The actual value 3 (IW3) is transmitted in PZD4. T he value to be
transferred can be selected "Actual bus value 3" (P545 bzw. P543 [-03]).
Pos: 73 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/Pr ozessdatenver arbeitung i m FU allgemein/Istwert 4 und 5 [CANopen] @ 2\mod_1348569353474_388.docx @ 48448 @ 5 @ 1
Actual value 4 and 5
SK 540E and SK 545E freq uency in verters c an also pr ocess the 16 bit setp oints 4 and 5. T he f unction of these actual values is set in the inverter un der the param eters ' Actual bus value 4' (P543 [-0 4]) and 'Actual bus value 5' (P543 [-05])
The value range and the scalling correspond to thise of the other actual values.
Pos: 74 /Anl eitungen/8. /9. Zusatzi nformation en [BU 0500 / BU 0200]/8 .8 Normier ung Soll- /8.8 Normierung Soll- / Istwerte [BU 0500] @ 0\ mod_1328189360846_388.docx @ 14466 @ 3 @ 1
BU 0060 GB-4112 47
Page 48
CANopen – Supplementary manual options for NORD - Frequency Inverters
Name
Analog signal
Bus signal
Setpoint values
Value
Standardisatio
Value
Max.val
Type
100% =
-100% =
Standardisation
Limitati
absolut
e
Setpoint frequency
{01}
0-10V
P104 … P105
±100%
16384
INT
4000 16384
dez
C000
-
16385
dez
4000
*
f
setpoint
[Hz]/P105
P105
Frequency
{04}
0-10V
P410 … P411
±200%
32767
INT
4000 16384
C000
-
4000
*
P105
Frequency
0-10V
P410 … P411
±200%
32767
INT
4000 16384
C000
-
4000
*
P105
Max. frequency
{07}
0-10V
P411
±200%
32767
INT
4000 16384
C000
-
4000
*
P105
Actual
{14}
0-10V
P105*
±100%
16384
INT
4000 16384
C000
-
4000
*
P105
Setpoint process
{ 15 }
0-10V
P105*
4000 16384
C000
-
4000
*
{2}
4000 16384
4000
{6}
U
(V)/10V
4000 16384
4000
Actual values
Actual frequency
0-10V
P201*
4000 16384
C000
-
4000
*
Actual speed
{02}
0-10V
P202* U
AOut
(V)/10V
±200%
32767
INT
4000 16384
dez
C000
-
16385
dez
4000
*
n[rpm]/P202
Current
{03}
0-10V
P203* U
AOut
(V)/10V
±200%
32767
INT
4000 16384
dez
C000
-
16385
dez
4000
*
f[Hz]/P105
Torque current
0-10V
P112* 100/
±200%
32767
INT
4000 16384
C000
-
4000
*
Master value
{19} … {24}
0-10V
P105*
4000 16384
C000
-
4000
*
4000 16384
C000
-
4000 of pairs of poles
or 4000
hex
*n[rpm]/P202

4.1.7 Standar di sation of setpoint / target values

The following table cont ains details f or the s tandardis ation of typical s etpoint and actual values. These details relate to parameters (P400), (P418), (P543), (P546), (P740) or (P741).
{Function}
addition
subtraction
{ 05 }
valueProcess
controller
controller
Torque current
limit
Current limit
{Function}
{01}
{04}
Setpoint frequency
range
(10V=100%)
(10V=100%)
(10V=100%)
(10V=100%)
(10V=100%)
(10V=100%)
0-10V
(10V=100%)
0-10V
(10V=100%)
n
(min - max)
(min - max)
(min - max)
U
(V)/10V
AIN
U
(V)/10V
AIN
P112*
(V)/10V
U
AIN
P536*
AIN
range
±100% 16384 INT
0-100% 16384 INT
0-100% 16384 INT
(10V=100%)
(10V=100%)
(10V=100%)
(10V=100%)
U
(V)/10V
AOut
√((P203)²-
±100% 16384 INT
(P209)²)* U
(V)/10V
AOut
(10V=100%)
U
AOut
(V)/10V
±100% 16384 INT
ue
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex
dez
dez
dez
dez
dez
dez
dez
dez
dez
dez
16385
16385
16385
16385
16385
/
/
16385
16385
16385
hex
hex
f
dez
setpoint
hex
f
dez
setpoint
hex
f
dez
soll
hex
f
dez
setpoint
hex
f
dez
setpoint
hex
f[Hz]/P201
dez
hex
hex
hex
Iq[A]/(P112)*100/
dez
√((P203)²-(P209)²)
hex
f[Hz]/P105
dez
hex
hex
[Hz]/P411
hex
[Hz]/P411
hex
[Hz]/P411
hex
[Hz]/P105
hex
[Hz]/P105
* I[A]/P112 P112
hex
* I[A]/P536 P536
hex
hex
hex
hex
hex
hex
on
P105
Speed from rotary
encoder
{22}
/ /
±200% 32767 INT
hex
dez
16385
hex
dez
* n[rpm]/
hex
P201*60/Number
Table 9: Scaling of setpoints and actual values (Selection)
Pos: 75 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANn ord Proto koll/Das CAN nord Protokol l [CAN] @ 1\ mod_1342081930160_388.docx @ 31880 @ 2 @ 1
48 BU 0060 GB-4112
Page 49
4 Communication and Protocol
SK 540E and SK 545E devices enabl e processing of up to 5 setpoints or actual values. However,
this is only possible with a bus configuration via the integrated RJ45 interfaces. For the two additional values, 5
1*
Process data Master à Frequency inverter
(CAN address*2) + 0
2
Process data inverter à Master
(CAN address*2) + 1
3
Parameter order Master à Inverter
(CAN address*2) + 512
4
Parameter response inverter à Master
(CAN address*2) + 513
5
Broadcast process data Master à Inverter
1024 - 1032 (1)
* Only if broadcast is set in frequency inverter

4.2 The CANnord protocol

Pos: 76 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANn ord Proto koll/Nachrich tenobjekte [ CAN] @ 1\mod_1342081958846_388.docx @ 31904 @ 3 @ 1

4.2.1 Message object s

The control and param eterisation of NORD f requenc y inverter is im plem ented via CANn ord using f our message objec ts. T he message obj ects are iden tifie d by various ident ifiers . The f ollowing s ervices are available for a logic master (client):
• Transmit process data (control word and target value) – confirmed or broadcast
• Receive process data (status word and actual value)
• Transmit parameter order (read or write)
• Receive parameter order response identifier / parameter value
• Transfer of setpoint positions with SK 700E with PosiCon option, SK 53xE / SK 54xE
• Transfer of the actual frequency inverter status during operatio n
Information
Communication direction
The data directions "transmit", "receive" are relative to the logic master or client.
The process objects (1. + 2.) can be 4 Bytes (transfer of setpoint) or 8 Bytes (transfer of several setpoints) long. Parameter objects are always 8 Bytes long.
Information
In CAN mode
bytes must be transmitted, whereby the 5th byte is a dummy.
SK 54xE – 2 additional setpoints and actual values
Pos: 77 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANn ord Protokoll/Id e ntifi er [CAN] @ 1\mod_1342082437125_388. docx @ 31928 @ 3 @ 1

4.2.2 Identifier

The standard CAN (2.0A) permits maximum 2048 different identifier s. Each identifier represents the address for a message objec t, w hereby a frequency inverter uses at l eas t 4 dif f erent message objects. In addition, so-called broadcast identifiers can be assigned.
The identifier of the message object can be derived from the CANnord address (P515):
Serial No. Message objects Determination of the identifier
Table 10: CANnord - Determination of message object identifiers
The identifier also spec ifies the pr iorit y in the C ANnor d protoc ol (the h igher the ide ntifier, th e lower the priority). Process data therefore always automatically have higher priority.
In Extended Fram e telegra ms, a c onstant part is adde d to the ident ifier . The Ex tended ID is ge nerated by adding 18 null bits, so that the ident ifier for extended and standard f ormats can be the same. The identifier format is automatically recognised.
Pos: 78 /Anleit u ng e n/Elektroni k/Bussyste m e/ 4 . Ko mmunikatio n und Protokoll + Prozessdate ntransfer/ CANopen [BU 0060]/Das C ANnord Prot okoll/Beispi el Indentifi er [CAN] @ 1\mod_1342084923171_388.docx @ 31976 @ 3 @ 1
BU 0060 GB-4112 49
Page 50
CANopen – Supplementary manual options for NORD - Frequency Inverters
CAN bus address
100
dez
Process data Master à Frequency inverter
200
Process data frequency inverter à Master
201
Parameter order Master à Frequency inverter
712
Parameter response frequency inverter à Master
713 Broadcast identifier No. 4
1027
dez
Broadcast identifier No. 9 (all)
1032
dez

4.2.3 Identi fier example

In the frequency inverter, the CANnord address (P515) is set to the value 100. This results in the following identifier:
Message objects Identifier
dez
dez
dez
dez
Table 11: Identifier example
Based on the above exam ple, the master transmits its proc ess data to the f requency inverter with the identifier 200. As a respons e, it receives the actual v alues with the identifier 201. A param eter is sen t with the identifier 712 to th e frequenc y inverter, th e respons e of the fr equency inverter is sent with t he identifier 713.
If P509 is set to 11, the broadcast identifiers 1027 and 1032 are also valid.
Pos: 79 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANn ord Protokoll /Ablauf der Da te n üb ertragung [C AN ] @ 1\mod_1342085421991_388.docx @ 32000 @ 3 @ 1

4.2.4 Sequence of data transfer

If the user sends process data to the frequency inverter, it responds via the appropriate message channel. It acts in the same way with parameter orders.
The following delays occur between transmitting and receiving:
Process data (t
Parameter data (t
If an error occurs in the frequency inverter, it immediately transmits its status word and actual value via the PZD channel. The er ror state is indicate d by the error bit in the status word. The current er ror number can then be read out via the PKW channel.
) approx 1 to 3 ms
PZD
) approx. 5 to 10 ms
PKW
50 BU 0060 GB-4112
Page 51
4 Communication and Protocol
from FI
Setpoint from Master
Actual value
from FI
Parameter order from Master
Timing process data
t
PZD
Timing parameter data
Parameter response
t
PKW
Figure 9: Sequence of data transfer
Pos: 80 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANn ord Protokoll /Broadcas t- Telegramm e [CAN] @ 1\mod_1342083279128_388.docx @ 31952 @ 3 @ 1

4.2.5 Broadcast telegrams

To control several frequency inverters simultaneously (e.g. same enable and same setpoint), it is possible to address frequency inverter groups or all f requency inverters using broadcas t telegrams. This means that, in add it ion to the identifiers d esc r ibed ab ov e, add it ion al br oa dcas t id ent if iers f or eac h frequency inverter ar e also valid. A ra nge of 32 addr esses is assigne d to one broadcas t identifier. Al l connected frequency inverters can be controlled using the broadcast identifier 1032.
CAN address (P515) Broadcast identifier
00 - 31 1024 (400h) 32 - 63 1025 (401h) 64 - 95 1026 (402h) 96 - 127 1027 (403h) 128 - 159 1028 (404h) 160 - 191 1029 (405h) 192 - 223 1030 (406h) 224 - 255 1031 (407h) 0 - 255 1032 (408h)
Table 12: Assignment of CAN address (P515) to the broadcast identifier
BU 0060 GB-4112 51
Page 52
CANopen – Supplementary manual options for NORD - Frequency Inverters
1 2 3
4
PKE
IND
PWE1
PWE2
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
the inverter parameter num bers (PNU) of the particular inverter series please refer to the relevant operating
Information
Both the order label and the respons e label are abbreviated as AK. Therefore, care must be taken when reading
The broadcast function is activated when the interface parameter (P509=11) is set to CAN broadcast. This assumes that the control data and setpoint are specified via CANnord. Only process data can be transferred with broadcast telegrams. Status data are not returned
(unconfirmed service).
Pos: 81 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANn ord Proto koll/Parametr ierung im M ode CAN [CAN ] @ 2\mod_1347285948586_388.docx @ 44341 @ 3 @ 1

4.2.6 Parametrer i sati on in CAN mode

In order to process a parameter (read or write / change an inverter parameter) a unique order telegram is sent to the f requency inverter from the m aster. The FI responds with the corresponding response.
In principle, the area of the telegram which is relevant for processing the parameter consists of a parameter identification , in which the type of ord er (Write, Read etc.) a nd the relevant param eters are specified. Indivi dual p aram eter sets or arra y elements can b e addres sed with the a id of the Index. The parameter value contains the value to be written or read.
Pos: 82 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANn ord Protokoll /Paramet erkennung (P KE) [CAN] @ 2\mod_1347286233845_388.docx @ 44366 @ 5555 @ 1
Parameter label (PKE)
The order or response and the associated parameters are encrypted in the parameter label (PKE).
AK
SPM
PNU
The parameter label (PKE) is always a 16 bit value.
PNU
Bits 0 to 10 contain the number of the required parameter (PNU), or the number of the current parameter in the response telegram of the frequency inverter.
Information
For instructions.
Parameter number PNU
SPM Bit 11 is the toggle-bit for spontaneous messages. This function is not supported! AK
Bits 12 to 15 contain the order or response label.
Labelling: AK
or interpreting the order processing des cription in this section.
52 BU 0060 GB-4112
Page 53
4 Communication and Protocol
0
No order
0
1
Order parameter value
1 / 2
2
Change parameter value (word)
1 3 Change parameter value (double word)
2 4 Reserved
- 5 Reserved
- 6 Order parameter value (array)
4 / 5
7
Change parameter value (array word)
4 8 Change parameter value (array double word)
5 9 Order the number of array elements
6
10
Reserved
-
11
Change parameter value (array double word) to the EEPROM
5
EEPROM
13
Change parameter value (double word)
w it the
EEPROM
2
14
Change parameter value (word) EEPROM
1 0
No response
1
Transfer parameter value (word)
2
Transfer parameter value (double word)*
4
Transfer parameter value (array word)
5
Transfer parameter value (array double word)*
7
Order cannot be executed (with error number in PWE2)
* Only for PPO Type 2
Meanings of the values sent in the order label,:
The following table lists all the orders which can be transfer red from the master to the inverter. The right-hand column contains the response, which is normally sent (response label positive). Only certain response labels ar e possible, depending on the order l abel. In case of error ( AK negative) t he inverter will always supply the value 7 in the response label (AK) to the master.
AK Function Response label positive
12 Change parameter value (array word)
4
Meanings of the values sent in the response label,:
AK Function
As long as an order has n ot yet been executed, the i nverter provides the respo nse to the last order. Therefore the master must always check whether the received response matches the order sent.
For the plausibility check, the value in the response label (AK), the received parameter number (PNU) with the corresponding Index (IND) as well as the current parameter value (PWE) can be used for the description of parameters.
BU 0060 GB-4112 53
Page 54
CANopen – Supplementary manual options for NORD - Frequency Inverters
0
Invalid parameter number
1
Parameter value cannot be changed
2
Lower or upper value limit exceeded
3
Incorrect sub-index
4
No array
5
Invalid data type (at present only for SK 700E)
6
Only resettable (only 0 may be written)
7
Description element cannot be changed
9
Description data not present
201
Invalid order element in the last order received
202
Internal response label cannot be depicted
1 2 3
4
PKE
IND
PWE1
PWE2
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
Array 1-64
P1-P4
Sub-index
Error messages if the order cannot be executed
In the response label "Ord er cannot be executed" (A K = 7), then an error message is added to the parameter value (PW E2) of the inver ter response. For the meanin gs of the values transferred, please refer to the following table.
AK Meaning
Pos: 83 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANn ord Protokoll /Subinde x (IND) [CAN] @ 2\mod_134728657334 7_388.docx @ 44391 @ 5 @ 1
Sub-index (IND)
No information / all 0
P1-P4
The structure and function of the parameter index (IND) depends on the type of parameter to be transferred. For values w hi ch depe nd o n t h e parameter set, the parameter set can be selected vi a B its 0 and 1 of the Index (IND) (0 = parameter set 1, 1 = parameter set 2,...).
If the parameter to be processed is also an array parameter (e.g. position array for the POSICON option), then the sub-ind ex of the required param eter can addition ally be acces sed via Bit 2 to Bi t 7 of the sub-index (0 = array element 1, 1 = array element 2,…):
Array element Parameter set Index
5 (000101
21 (010101
) 2 (01
BIN
) 4 (11
BIN
) 15
BIN
) 57
BIN
= 0001 0101
HEX
= 0101 0111
HEX
BIN
BIN
If a parameter is not dependent on the parameter set, then Bits 0 -7 are used for the sub-index. Please refer to the operating instr uctions for details of the struc ture of the individual parameters and
which values may be called up.
If the sub-index is used, nos. 6, 7, 8 or 11, 12 must be used as the order label, in order for the sub-index to be effective.
Pos: 84 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANn ord Proto koll/Paramet er- Wert (PWE) [CAN] @ 2\mod_1347287056551_388.docx @ 44416 @ 5 @ 1
54 BU 0060 GB-4112
Page 55
4 Communication and Protocol
32 Bit parameter values are only used with the posicon option. All relevant parameters are described in the
Parameter value (PWE)
According to the type of the PPO or param eter, transf er of the param eter value (PW E) is always as a word (16 Bit) or double word (32 Bit) Only one parameter value can be transferred in a telegram.
A 32 bit parameter val ue compr ises PWE1 (High value word) and PWE2 (Low v alue word, 4th word). A 16 Bit param eter value is transferred in PWE2. For negative values the High word must be set to FFFF hex.
Information
supplementary posicon instruction manual.
32 bit parameter values
The parameter value is transferred as an integ er value. For parameters with r esolutions 0.1 or 0.01 the parameter value must be multiplied by the inverse of the resolution.
Example
A run-up time of 99.99 seconds is to be set.
99.99s à 99.99 * 1 / 0.01 = 99.99 * 100 = 9999 Therefore the value 9999
Pos: 85 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANo pen Proto koll/Das CAN open Protok oll [CANopen] @ 1\mod_1342086717076_388.docx @ 32024 @ 2 @ 1
= 270F
dec
must be transferred.
hex
BU 0060 GB-4112 55
Page 56
CANopen – Supplementary manual options for NORD - Frequency Inverters
Object Index (OI)
The OI contains all objects of the device. Objects depict the visible functionality. They
ccess is gained via SDOs. An object is
addressed via the Index (16 Bit) and the SubIndex (8Bit). The OI is divided into the
A000h...FFFFh: Reserved
Service data obj.
SDOs are used for confirmed transfer of data of any length between two network subscribers: The SDO cli ent is the initiating subscriber and has direct access to the OI
the SDO server (read and write). The SDO transfer is normally used for
parameterisation and service purpo ses .
Process data obj.
PDOs are used for transferring process data. The process data can contain a maximum
confirmation. The significance of the data transferred is determined by the identifier and the set PDO mapping. A PDO always has a producer (transmitter). Several consumers (receivers) may exist.
PDO mapping
sible to set which objects
(setpoint/actual values) are transferred into the PDO telegrams.
Identifier
Every CAN message has an 11 bit identifier. This identifier is used for addressing and CANopen defines a preset identifier assignment which facilitates communication
The 11 bit identifier is
10 8 8 7 6 5 4 3 2 1 0
Function code
Node identifiers (1-127)
NMT
0000
0 SYNC
0001
80h
1005h-1007h
Time stamp
0010
100h
1012h, 1013h
Emergency
0001
81h – FFh
1014h, 1015h
PDO1 (Tx)
0011
181h – 1FFh
1800h, 1A00h
PDO1 (Rx)
0100
201h – 27Fh
1400h, 1600h
PDO2 (Tx)
0101
281h – 2FFh
1801h, 1A01h
PDO2 (Rx)
0110
301h – 37Fh
1401h, 1601h
PDO3 (Tx)
0111
381h – 3FFh
1802h, 1A02h
PDO3 (Rx)
1000
401h – 47Fh
1403h, 1602h
PDO4 (Tx)
1001
481h – 4FFh
1803h, 1A03h
PDO4 (Rx)
1010
501h – 57Fh
1403h, 1603h
SDO (Tx)
1011
581h – 5FFh
1200h
SDO (Rx)
1100
601h – 67Fh
1200h
NMT Error Control
1110
701h – 77Fh
1016h, 1017h

4.3 The CANopen protocol

contain data, parameters or functions. A following areas:
0000h...1FFFh: Communication specific objects 2000h...5FFFh: Manufacturer-specific objects 6000h...9FFFh: Standardised device profile objects
(SDO)
inputs of
(PDO)
of 8 bytes. Transfer is made without
In objects 1600h-1603h / 1A00h..1A03h it is pos
priority assignment. between a higher level device and up to 127 other devices.
broken down as follows:
Object Function code Resulting COB-ID OI entry
Pos: 86 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANo pen Proto koll/Netzwer k Management (NMT) [CANopen] @ 1\mod_1342093966683_388.docx @ 32048 @ 3 @ 1
56 BU 0060 GB-4112
Page 57
4 Communication and Protocol
Pre-Operational
The inverter enters this state after initialisation. This state is used for bus module configuration. Data traffic via SDO objects is possible. The PDO channel is blocked.
Identifier = 0x00 // Data byte 0 Operational
The bus is fully operational, SDO and PDO objects can be transmitted
Identifier = 0x00 // Data byte 0 = 0x01 // Data byte 1 = 0x00
Stopped
Transfer of SDO and PDO objects is blocked, only NMT messages can be transferred
Identifier = 0x00 // Data byte 0 = 0x02 // Data byte 1 = 0x00
Information
The drive profile is not s upported if the CANbus is implemented via the integrated RJ 45 sockets for SK 5xxE
Receive PDO
control data
... receives data
Transmit PDO
Status data
.... transmits data

4.3.1 Network Management (NMT)

The individual states of the CANopen network can be activated with the following commands:
Status Description Commands for setting the
operational state
= 0x80 // Data byte 1 = 0x00
Table 13: Network Management (NMT)
Pos: 87 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANo pen Proto koll/Antriebs profil DS 40 2 [CANopen] @ 1\mod_1342100366594_388. docx @ 32218 @ 3 @ 1

4.3.2 Dri ve profile DS 402

Together with the module SK TUx-CAO the frequency inverter supports the drive profile DS 402 Velocity Mode (speed profile).
The profile is only valid in parameter set 1 and is activated via parameter (P551).
Figure 10: Velocity Mode CiA DSP 402 V1.1 page 178
When the drive profile is activated (P551 = On), objects 6040 - 6044 instead of 3000 - 3003 are relev ant.
inverters.
Drive profile DS 402
Pos: 88 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANo pen Proto koll/Prozess datentransf er im CANop en Mode (PDO Ko m mu ni kation) [CAN op en] @ 1\mod_1342094906407_388. docx @ 32072 @ 3 @ 1

4.3.3 Process dat a transfer in CANopen mode (PDO communication)

PDOs (Process Data Objects) are used for transferring process data.
PDO mode Data type Frequency inverter ...
Table 14: PDO types
NORD frequency inverter s have up to 4 trans mit and 4 rec eive PDOs which are identified b y different identifiers.
Transfer of PDOs is m ade without conf irmation. T he significanc e of the data tr ansf erred is determ ined by the CAN identifiers being used and the PDO mapping. A maximum of 8 bytes of data is transferred.
Pos: 89 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANo pen Proto koll/PDO- Betr iebsarten (tr ansmissio n type) [CAN open] @ 1\mod_1342096212798_388 .docx @ 32096 @ 5 @ 1
BU 0060 GB-4112 57
Page 58
CANopen – Supplementary manual options for NORD - Frequency Inverters
0
PDO is transmitted if a SYNC command has been received and the data (status) has changed since the last SYNC command.
1 - 240
PDO is transmitted if 1..240 SYNC commands have been received, whether the data (status) has changed or not.
252, 253
Reserved
254, 255
The PDO is transmitted imm ediately if the data (status) has changed (standard setting).
0 - 240
Data from the Receive PDO is only processed after the next SYNC command has been received.
252, 253
Reserved
254, 255
Data from Receive PDO is processed immediately (standard setting).
1 2 3 4 Control Word (16 Bit)
Setpoint 1 (16 Bit)
3000
Control word (STW)
3001
Status word (ZSW)
3002
1
Setpoint 1 (SW1) 16 Bit
3003
1
Actual value 1 (IW1) 16 Bit
2 Setpoint 2 (SW2) 16 Bit
2
Actual value 2 (IW2) 16 Bit
3 Setpoint 3 (SW3) 16 Bit
3
Actual value 3 (IW3) 16 Bit
Bit
5 Setpoint 5 (SW5) 16 Bit
Only SK 54xE
5 Actual value 5 (IW5) 16 Bit
4 Setpoint 1 (SW1) 32 Bit
Only SK 7x0E
4 Actual value 1 (IW1) 32 Bit
PDO operating modes (transmission type)
The “transmission type” determines when a transmit PDO is transmitted and when the data from a receive PDO is proc essed. T hes e settings are s et in o bjects 1400-1403 and 1800-1803. The f ollo wing settings can be made with NORD frequency inverters:
Transmission type Value
Transmit PDO (Tx)
Receive PDO (Rx)
Table 15: PDO modes
Pos: 90 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANo pen Protokoll/PDO- Mapping [CANopen] @ 1\mod_1342098118786_388.docx @ 32120 @ 5 @ 1
PDO mapping
The assignment of proces s data in the receive and transm it PDOs is set under P DO m apping (obj ects 1600-1603 and 1A00-1A03). Up to 8 bytes of data can be transferred in each PDO. Mapping determines where which pieces of data are placed in these 8 bytes, e.g.:
PDO data bytes
The control word, status word, the setpoint values and actua l values can be set using the following object numbers:
Index Sub-
index
4 Setpoint 4 (SW4) 16 Bit
Control object Index Sub-
index
Only SK 54xE
4 Actual value 4 (IW4) 16
Status object
An entry in the object i ndex determines the setti ng ( obj ec ts 1600-1603 and 1A00-1A0 3). T his specifies which object of the device is transferred to which point of the PDO.
58 BU 0060 GB-4112
Page 59
4 Communication and Protocol
PDO1 (Tx)
4 Byte
180h + NODE-ID
ZSW
IW1
PDO1 (Rx)
4 Byte
200h + NODE-ID
STW
SW1
PDO2 (Tx)
8 Byte
280h + NODE-ID
ZSW
IW1
IW3 *
IW2 *
PDO2 (Rx)
8 Byte
300h + NODE-ID
STW
SW1
SW3 *
SW2 *
PDO3 (Tx)
8 Byte
380h + NODE-ID
ZSW
IW1 (32 Bit)
IW2
PDO3 (Rx)
8 Byte
400h + NODE-ID
STW
SW1 (32Bit)
SW2
PDO4 (Tx)
2 Byte
480h + NODE-ID
ZSW
PDO4 (Rx)
2 Byte
500h + NODE-ID
STW
3rd word = IW/SW2, 4th word = IW/SW3
PDO1 (Tx)
8 Byte
180h + NODE-ID
ZSW
IW1
IW2
IW3
PDO1 (Rx)
8 Byte
200h + NODE-ID
STW
SW1
SW2
SW3
absolute encoder
Information
NORD frequency inverters support dynamic mapping and dummy mapping!
Pos: 91 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANo pen Proto koll/PDO- Mapping SK 300E, SK 5xxE (SK TU3-...), SK 700E, SK 750E [CANopen] @ 1\mod_1342098845033_388.docx @ 32144 @ 6 @ 1
PDO mapping SK 300E, SK 5xxE (SK TU3-…), SK 700E, SK 750E
PDO type Length Identifier 1st word 2nd word 3rd word 4th word
*) In the SK 5xxE devices, the IW/SW 3/2 are ass igned inversely to the words.
In the default setting, all rec eive PDOs are active. A d ecision is made when s ending mes sages to the applicable identifier whether one setpoint or up to three setpoints can be evaluated.
With transmit PDOs, only PDO 1 is active, while PDOs 2 to 4 are deactivated. If the application requires the sending of several actual values, the corresponding PDO must be switched on. In the following example, trans mit PDO 2 is activated, the default setting transm its a status word and three actual values. For th is, the following messages m ust be sent via the SDO paramet er channel (see Section 4.3.4):
Set the NMT status machine for the inverter to the state "Pre-Operational"
Deactivate PDO 1 à SDO telegram (Index=0x1800 / Subindex=1 / Data=0xc0000181)
Activate PDO 2 à SDO telegram (Index=0x1801 / Subindex=1 / Data=0x40000281)
Set the NMT status machine for the inverter to the state "Operational"
PDO 1 is deactivated to prevent the bus load from rising unnecessarily. The PDO is
activated/deactivated via Bit 31 in the corresponding parameter.
Pos: 92 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANo pen Proto koll/PDO- Mappi ng SK 511 E bis SK 535E über intern en RJ45 Ans chluss [CAN open] @ 1\mod_1342099915579_388.docx @ 32168 @ 6 @ 1
PDO mapping, SK 511E up to SK 535E via internal RJ45 connection
PDO type Length Identifier 1st word 2nd word 3rd word 4th word
PDO2 (Rx) 4 Byte 300h + (NODE-ID +1) IW1 (32 Bit) of an
Pos: 93 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANo pen Protokoll/PDO- Mapping S K 5 40 E bi s SK 5 45 E über internen RJ45 Anschluss [CANopen] @ 2\mod_1347885363093_388.docx @ 47651 @ 6 @ 1
BU 0060 GB-4112 59
Page 60
CANopen – Supplementary manual options for NORD - Frequency Inverters
PDO1 (Tx)
8 Byte
180h + NODE-ID
ZSW
IW1
IW2
IW3
PDO1 (Rx)
8 Byte
200h + NODE-ID
STW
SW1
SW2
SW3
PDO2 (Tx)
5 Byte
280h + NODE-ID
IW4
IW5
PDO2 (Rx)
5 Byte
300h + NODE-ID
SW4
SW5
PDO3 (Rx)
4 Byte
400h + (NODE-ID +1)
IW1 (32 Bit) of an absolute encoder
IDNodexIDSende += 6000
IDNodexIDEmpfangs += 5800
PDO mapping, SK 540E up to SK 545E via internal RJ45 connection
PDO type Length Identifier 1st word 2nd word 3rd word 4th word
Pos: 94 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANo pen Proto koll/Inhibit T ime [CANop en] @ 1\mod_1342432696269_388.docx @ 32299 @ 5 @ 1
Inhibit Time
Each transmit PDO h as a param eter "In hibit T ime" (0x 1800 – 0x1803 Sub-Index 3). T his can be used to set a minimum s end interval between t wo PDO m essages. I n network s with nu mer ous subscribers , the bus load can be influenced with this value. The default setting is 10 ms (Value x 100µs).
Pos: 95 /Anleit u ng e n/Elektroni k/Bussyste m e/ 4 . Ko mmunikatio n und Proto koll + Prozes sdatentrans fer/CANope n [BU0060]/D as CANopen Protokoll/ Event Timer [CANopen] @ 1\mod_1342432843212_388.docx @ 32323 @ 5 @ 1
Event Timer
The Parameter Event Tim e (0x1800 – 0x1803 Subind ex 5) can be used for all transm it PDOs. Once this value is exc eeded, the PDOs are transmitted c yclically. The default setting is 2 50 ms (Value x 1ms).
Pos: 96 /Anleit u ng e n/Elektroni k/Bussyste m e/ 4 . Ko mmunikatio n und Proto koll + Prozes sdatentrans fer/CANope n [BU0060]/D as CANopen Protokoll/ Einstellung en am PDO [C ANopen] @ 1 \mod_1342431680963_388.docx @ 32251 @ 5 @ 1
PDO settings
All settings for the PDOs are implemented via the SDO parameter channel (Section 4.3.4). The settings made are no t stored permanent ly in the devic e, i.e. a reset of the 24 V po wer supply will
reset the changed parameters to the default values.
Pos: 97 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANo pen Proto koll/Parametr ierung im M ode CANope n (SDO Komm unikation) [C ANopen] @ 1\mod_1342433191459_388.doc x @ 32347 @ 3 @ 1

4.3.4 Paramet erisati on in CANopen mode (SDO communication)

Access to all parameters of the fr equency inver ter and the CANop en Box is im ple m ented via so-called service data objects ( SDO). Access is via handshake bet ween client and s erver, i.e. aft er a message is transmitted, the response must be waited for before a new message can be sent.
Transmit and receive addresses for SDO access seen from the PLC
The Node ID of the frequency in verter is set via the "ID-H" an d "ID-L" s witches on the CANopen Box or in the PGM mode via parameter P515.
Pos: 98 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANo pen Proto kollSenden von P ar a m et er d aten über SDO [C AN open] @ 1\mod_1342433465499_388.docx @ 32371 @ 5 @ 1
60 BU 0060 GB-4112
Page 61
4 Communication and Protocol
0x2B
0x66
0x20
0x01
0x67
0x00
0x00
0x00
Data à user data (Parameter value): The values of the selected parameter are transferred
(1.03s = 103
dec
= 0067
hex
)
32 Bit value: 76 BC 2A 00
(2800,758rev = 2800758
dec
= 002ABC76
hex
)
Sub-Index à Parameter index or array value: The selected parameter set and the array element of the parameter
For parameters which neither depend on parameter sets nor consist
Column
1 2 3 4 Row
P-set 1
P-set 2
P-set 3
P-set 4
1
Array [-01]
0x01
0x02
0x03
0x04
2
Array [-02]
0x05
0x06
0x07
0x08
3
Array [-03]
0x09
0x0A
0x0B
0x0C
4
Array [-04]
0x0D
0x0E
0x0F
0x10
Index à Parameter number of the frequency inverter:
The control byte à specifies the data length and the order:
0x23 = Transmit 32 bit value
Response
Any other response corresponds to a termination of parameter communication.
Transmitting parameter data via SDO
Transmission of parameter data = Writing a parameter value into the frequency inverter. Example: Parameter P102 (acceleration time), 1.03s
Control
Index Sub-index Data
byte
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7
in this area.
16 Bit value: 67 00 00 00
are coded in this area. of array elements, the sub-index is 00
hex
For all other cases, the following overview applies:
The parameters are mapped in the area above 2000
=66
Parameter P102 = 102
dec
à 2000
hex
0x2B = Transmit 16 bit value
0x60 =
Table 16: Transmitting parameter data via SDO
Pos: 99 /Anl eitungen/El ektronik/Bus systeme/4 . Kommunikat ion und Pr otokoll + Pr ozessdatentr ansfer/CAN open [BU00 60]/Das CANo pen Proto koll Laden von Para meterdaten über SDO [C ANopen] @ 1 \mod_1342434267834_388.docx @ 32395 @ 5 @ 1
Error-free telegram received
Loading parameter data via SDO
Loading of param eter data is carried out in a sim ilar manner to the transm ission of parameter data. For this, the master sends a read order (con trol byte 0x40) to the frequency inver ter, which specifies which parameter a nd which array or which param eter set is to be read out. Th e data area remains empty (everything 0).
The response telegram corresponds to the order telegram, whereby the status byte specifies the length of the response data (response 16/32 bit) and the data area which contains the parameter value which has been read out.
hex
+ 66
= 2066
hex
hex
:
à 66 20
hex
BU 0060 GB-4112 61
Page 62
CANopen – Supplementary manual options for NORD - Frequency Inverters
0x40
0x20
0x66
0x01
0x00
0x00
0x00
0x00
0x4B
0x20
0x66
0x01
0x67
0x00
0x00
0x00
control byte
0x40 = Load value
Response
0x80 =
Response to an incorrect order
0x80
0x00
0x18
0x01
0x02
0x00
0x01
0x06
0x0601 0001
Access to write-only parameter
0x0601 0002
Access to read-only object
0x0607 0010
Data type or parameter length do not match
0x0609 0030
Parameter value range overflow
0x0609 0031
Parameter value range overflow
0x0609 0032
Parameter value range undershot
0x0609 0011
Sub-Index of parameter does not exist
Example: Read out parameter P102, Response: P102, 1.03s
Control byte/
Index Sub-index Data
Status byte
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7
Requirement
Response
The
0x4B = 0x43 =
Table 17: Loading parameter data via SDO
Pos: 100 /A nleitungen/El ektronik/B ussysteme/ 4. Kommuni kation und Pr otokoll + Pr ozessdate ntransfer/C ANopen [BU0 060]/Das CAN open Proto kollAbbruch der Paramet erkommunik ation (SDO) [CANopen] @ 1\mod_1342434882348_388.docx @ 32420 @ 5 @ 1
à states the order:
Deliver the 16 bit value which has been read out Deliver the 32 bit value which has been read out
Cancelling of parameter communication (SDO)
If problems occur during parameter communication ( e.g. value range over flow), a cancel telegram is sent. This can be recognis ed by the num ber 0x80 in b yte 0. The cause of the cancellation is indicated in bytes 4 to 7.
Control
byte
Last index used Error code
Byte 0 Byte 1 Byte 2 Byte 3 B yte 4 Byte 5 Byte 6 Byte 7
Table 18: Error message (0x06010002 = attempted writing access to a read-only object)
Error code Description
Table 19: Error codes – Parameter communication
Pos: 101 /A nleitungen/El ektronik/B ussysteme/ 4. Kommuni kation und Pr otokoll + Pr ozessdate ntransfer/C ANopen [BU0 060]/Das CAN open Protokol l / Ändern der COB- ID (Adresse) eines PDOs [CANopen] @ 1\ mod_1342431982191_388.docx @ 32275 @ 5 @ 1
62 BU 0060 GB-4112
Page 63
4 Communication and Protocol
PDO 1
0x1400 Sub 1
0x1800 Sub 1
PDO 2
0x1401 Sub 1
0x1801 Sub 1
PDO 3
0x1402 Sub 1
0x1802 Sub 1
PDO 4
0x1403 Sub 1
0x1803 Sub 1
0
PDO is active
1
PDO is switched off
30
1
29 to 11
0
10 to 0
X
PDO identifier ( COB – ID )
Changing the COB-ID (address) of a PDO
Changes to the identifier of a PDO can only be made when the NMT status machine of the inverter is in the "Pre-Operational" state.
Each Transmit and Receive PDO has its own parameter for this setting.
PDO Receive PDO Send PDO
Table 20: Index table for transmit and receive PDOs of the inverter
The following parameter is a 32 bit value, which includes other information in addition to the identifier.
Bit number Value Meaning
31
Values cannot be changed
Table 21: Description of PDO COB-ID entry
The PDO identifier is stored in bits 0 to 1 0. The bit 31 must be set to null, other wise the PDO will be deactivated. If, e.g. th e identif ier for a trans mit PDO is changed t o 0x201, the value 0x 4000020 1 must be entered in the appropriate parameter.
The new identifier becomes valid by setting the NMT status machine to the "Operational" state.
Pos: 102 /Anleit ungen/Ele ktr onik/Buss ys t e me/4. Kommu nikation und Protokoll + Prozessdat entransfer/C ANopen [B U0060]/Das C ANopen Pro tokoll/CANo pen Objekte/ Objektverz eichnis @ 1\mod_1342606056063_388.docx @ 34032 @ 3 @ 1
BU 0060 GB-4112 63
Page 64
CANopen – Supplementary manual options for NORD - Frequency Inverters
1000
-
Device type
Device type and functionality
RO
U32
1001
-
Error register
Error register
RO
U8
1002
-
Status Register
Status of the module
RO
U32
1003
ARR
Pre-defined Error
Error signaled by an emergency
U8 0
Number of errors
Number of errors ; 0 deletes the error list
RW
U8 1 Error code
Error number
RO
U32
1005
-
COB-ID SYNC
Identifier for SYNC mess ages (Default 80h)
RW
U32 1008
-
Device name
Device name
RO
STR
1009
-
Hardware version
Hardware configuration
RO
STR
100A
-
Software Version
Software version FI+CO
RO
STR
100C
-
Guard Time
Guard time (0=off)
ms
RW
U16
100D
-
Life Time Factor
Life time = life time factor * guard time
RW
U16
1014
-
COB-ID Emergency Object
Identifier Emergency Object (80h+Node-ID)
RW
U32 1015
-
Inhibit Time EMCY
Minimum repeat time
ms
RW
U16
1017
-
Producer Heartbeat Time
Cycle Time of Heartbeat
ms
RW
U16
1018
REC
Identity object
General device information
U32 0
Largest sub-index
Number of elements
RO
U8 1
Vendor ID
Manufacturer identification
RO
U32 2
Product code
Device version (product number)
RO
U32
3 Revision number
Software version and revision number
RO
U32 4 Serial number
Serial number
RO
U32
1200
REC
Default Server SDO
SDO server
0x22
0 Largest sub-index
Number of elements
RO
U8
1 COB_ID Server>Client (rx)
Identifier receive SDO (600h +ID)
RO
U32
2 COB_ID Server>Client (tx)
Identifier transmit SDO (580h +ID)
RO
U32

4.3.5 Object Index

All available objects are contained in the NORD frequency inverter “Electronic data sheet” (eds file).
Pos: 103 /A nleitungen/El ektronik/B ussysteme/ 4. Kommuni kation und Pr otokoll + Pr ozessdate ntransfer/C ANopen [BU0 060]/Das CAN open Protokol l /C ANopen Obje k te/ CANopen Profi l D S 30 1 @ 1\ mod_1342606177463_388.docx @ 34226 @ 5 @ 1
CANopen profile DS 301
Pos: 104 /A nleitungen/El ektronik/B ussysteme/ 4. Kommuni kation und Pr otokoll + Pr ozessdate ntransfer/C ANopen [BU0 060]/Das CAN open Protokoll/CANopen Objekte/Kommuni kationsobjekte (1000hex – 1200hex) [zu DS 301] @ 1\mod_1342606247446_388.docx @ 34620 @ 6 @ 1
Communication objects (1000
- 1200
hex
hex
)
Index
(hex)
Sub Object Description Unit Access Type
object
Table 22: Communication object s (DS 301)
Pos: 105 /Anleit ungen/Ele ktr onik/Buss ys t e me/4. Kommuni kation und Protokoll + Prozessdat entransfer/C ANopen [BU 0060]/Das C ANopen Pro tokoll/CANo pen Objekte/ PDO Objekt e (1400hex – 1A03hex) [zu D S 301] @ 1 \mod_1342611822021_388.docx @ 34644 @ 6 @ 1
64 BU 0060 GB-4112
Page 65
4 Communication and Protocol
1400­1403
REC
Receive PDO Communication Parameter
Receive PDO characteristics
RW
0x21 0 Largest sub-index
Number of elements
RO
U8
1 COB-ID used by PDO
Identifier receive PDO
RW
U32 2
Transmission type
Receive PDO type
RW
U8 3
Not used
Not used
- - 4
Reserved
Reserved
- - 5
Not used
Not used
- -
1603
Receive PDO Mapping Parameter
0 Largest sub-index
Number of elements
RW
U8 1-4
PDO mapping
Mapped objects
RW
U32
1800­1803
REC
Transmit PDO Communication Parameter
Transmit PDO chara ct eristics
RW
0x21 0 Largest sub-index
Number of elements
RO
U8 1
COB-ID used by PDO
Identifier receive PDO
RW
U32 2
Transmission type
Send PDO type
RW
U8
3 Inhibit Time
Minimum transmit time
100µ s
RW
U16 4 Reserved
Reserved
- - 5
Event Timer
Cyclic transmit timer
ms
RW
U16
1A00-
REC
Transmit PDO Mapping
Send PDO mapping
RW
0x21 0 Largest sub-index
Number of elements
RW
U8 1-4
PDO mapping
Mapped objects
RW
U32
PDO objects (1400
- 1A04
hex
hex
)
Index
(hex)
1600-
Sub Object Description Unit Access Type
REC
Receive PDO mapping RW 0x21
1A03
Table 23: PDO objects (DS 301)
Pos: 106 /A nleitungen/El ektronik/B ussysteme/ 4. Kommuni kation und Pr otokoll + Pr ozessdate ntransfer/C ANopen [BU0 060]/Das CAN open Protokol l /C ANopen Obje k te/ CANopen Antri ebs- Profil DS402 - Objekt (603Fhex - 6049hex) @ 1\mod_1342613783140_388.docx @ 34769 @ 5 @ 1
Parameter
BU 0060 GB-4112 65
Page 66
CANopen – Supplementary manual options for NORD - Frequency Inverters
603F
-
Error code
Error description
-
RO
U32
6040
-
Control word
Control word
-
RW
U16
6041
-
Status word
Status word
-
R0
U16
6042
-
Vl_target_velocity
Speed setpoint
rpm
RW
I16
6043
-
Vl_velocity_demand
Setpoint speed after ram p
rpm
RO
I16
6044
-
Vl_control_effort
Actual speed value
rpm
RO
I16
unt
1 Vl_velocity_min_amount
Min. speed value
rpm
RW
U32 2
Vl_velocity_max_amount
Max. speed value
rpm
RW
U32
6048
REC
Vl_velocity_acceleration
Speed acceleration
-
RO
REC
1 Delta_speed
Delta speed
rpm
RW
U32
2 Delta_time
Delta time
s
RW
U16
6049
REC
Vl_velocity_deceleration
Speed deceleration
-
RO
REC
1 Delta_speed
Delta speed
rpm
RW
U32 2
Delta_time
Delta time
s
RW
U16
CANopen drive profile DS402 - Objects (603F
– 6049
hex
hex
)
Index
(hex)
Sub Object Description Unit Access Type
6046 ARR Vl_velocity_min_max_amo
Table 24: Object drive profile DS 402
Pos: 107 /A nleitungen/El ektronik/B ussysteme/ 4. Kommuni kation und Pr otokoll + Pr ozessdate ntransfer/C ANopen [BU0 060]/Das CAN open Protokol l /C ANopen Obje k te/ Frequenzu mri c hter - Objekt (2000hex - 3003hex) @ 1\mod_1342615089512_388.docx @ 34794 @ 5 @ 1
Speed min/max amount - RO ARR
66 BU 0060 GB-4112
Page 67
4 Communication and Protocol
2000­23E7
-
Manufacturer Spec. Parameter
FI parameters manual)
-
-
- 3000
Control word
Control word (STW)
U16
3001
Status word
Status word (ZSW)
U16
3002
0
Largest sub-index
Number of elements
U8 1
Setpoint 1
Setpoint 1 (SW1) 16 Bit
U16
2 Setpoint 2
Setpoint 2 (SW2) 16 Bit
U16
3 Setpoint 3
Setpoint 3 (SW3) 16 Bit
U16
4*
Setpoint 4
Setpoint 4 (SW4) 16 Bit
U16
5*
Setpoint 5
Setpoint 5 (SW5) 16 Bit
U16
4**
Setpoint 1 (long)
Setpoint 1 (SW1) 32bit
U32
3003
0
Largest sub-index
Number of elements
U8 1
Actual Value 1
Actual value 1 (IW1) 16 Bit
U16
2 Actual Value 2
Actual value 2 (IW2) 16 Bit
U16
3 Actual Value 3
Actual value 3 (IW3) 16 Bit
U16
4*
Actual Value 4
Actual value 4 (IW4) 16 Bit
U16
5*
Actual Value 5
Actual value 5 (IW5) 16 Bit
U16
4**
Actual Value 1 (long)
Actual value 1 (IW1) 32bit
U32
* Only SK 7x0E
Frequency inverter objects (2000
hex
- 3003
hex
)
Index
(hex)
* Only SK 54xE
Sub Object Description Unit Access Type
Table 25: Frequency inverter objects
Pos: 108 /Anleit ungen/Ele ktronik/Buss ysteme/5. P arameter/! Kapitel Par ameter [CAN open BU0060] @ 1\mod_1342439979075_388.docx @ 32469 @ 1 @ 1
BU 0060 GB-4112 67
Page 68
CANopen – Supplementary manual options for NORD - Frequency Inverters
signal must be present on the digital inputs being used

5. Parameters

To operate the inverter with the CANnord/CANopen protocol, the bus must be connected to the master and some settings have to be made on the frequency inverter.
With CANopen protocol, the inverter parameters are mapped in the range 2000 8192 must be added to the value 2000
to 9191
dec
, i.e. when parameterisation is carried out via the bus, the parameter numbers
dec
(e.g. P508 à obj . 21FC
hex
hex
).
to 23E7
hex
hex
=
The frequency inverter can always be parameterised. The control source can be selected with parameter P509 (contro l word) and param eter P510 (setpoi nt source). The te legram down tim e P513 can be selected depending on the bus system.
Information
According to the type or equipment of the frequency inverter, individual parameters may be different or restricted.
Deviating Parameter Set t in g s
Information
When activated, the functions block voltage, quick stop, remote control and cancel error, are available at the (local) control terminals. To operate the drive, a High before the drive can be enabled.
Control terminal functions
Pos: 109 /Anleit ungen/Ele ktr onik/Buss ys t e me/5. Paramet er / BUS Paramet er SK 30 0 E / 700E / 750E @ 1\mod_1335530232658_388.docx @ 24698 @ 2 @ 1
68 BU 0060 GB-4112
Page 69
5 Parameters
The Bus I/O In Bits are perceived as digital inputs. They can be set to the same functions
In order to use this function, one of the bus setpoints (P546, P547, P548) must be s et to >Bus I/O
The possible functions for the Bus In Bits can be found in the table of functions for the digital
can be accessed with the ControlBox. A
The bus I/O Out bits are perceived as digital outputs. These can be set to the same functions as
In order to use this function, one of the bus setpoints (P543, P544, P545) must be s et to >Bus I/O
The possible functions for the Bus Out Bits can be found in the table of functions for the digital
Note
ControlBox at SK 300E
of the first array can be accessed with the ControlBox. A

5.1 BUS parameter data for SK 300E/700E/750E

Pos: 110 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/P4xx Steuerklem men @ 0\mod_1327678262854_388.do cx @ 9027 @ 5 @ 1

5.1.1 Control t ermi nals

Parameter
{factory setting}
Pos: 111 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P400-P 499/Param eter P480 – Fu n ktion Bus I/O In Bit s [S K 300E, SK 700E] @ 1\mod_1335776613691_388.docx @ 24730 @ @ 1
Setting value / Description / Note Supervisor
P480 [-01] ... [-08]
0 ... 62 { all 0 }
Pos: 112 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P400-P 499/Param eter P481 – Fu nktion Bus I /O Out Bits [ SK 300E, S K 700E] @ 1\ mod_1335777244985_388.docx @ 24 754 @ @ 1
P481 [-01] ... [-08]
Function BusIO In Bits
(Function Bus I/O In Bits)
S
(P420...425).
In Bits 0-7 <. The required function must then be assigned to the relevant bit.
[-01] = Bus I/O In Bit 0 [-02] = Bus I/O In Bit 1 [-03] = Bus I/O In Bit 2 [-04] = Bus I/O In Bit 3
[-06] = Bus I/O In Bit 5 [-07] = Bus I/O In Bit 6 [-08] = Bus I/O In Bit 7
[-05] = Bus I/O In Bit 4
inputs P420...425.
Note ControlBox at SK 300E
SK 300E: Only the value of the first array ParameterBox or the NORDCON software is required to access the other arrays.
Function BusIO Out Bits
(Function Bus I/O Out Bits)
S
Parameter set
0 ... 38 { all 0 }
P434 … P443; P624 … P629 (only SK 7x0E with POSICON).
In Bits 0-7 <. The required function must then be assigned to the relevant bit.
[-01] = Bus I/O Out Bit 0 [-02] = Bus I/O Out Bit 1 [-03] = Bus I/O Out Bit 2
[-06] = Bus I/O Out Bit 5 [-07] = Bus I/O Out Bit 6 [-08] = Bus I/O Out Bit 7
[-04] = Bus I/O Out Bit 3 [-05] = Bus I/O Out Bit 4
outputs or the relays P434.
SK 300E: Only the value ParameterBox or the NORDCON software is required to access the other arrays.
Pos: 113 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P400-P 499/Param eter P482 – Nor mierung Bus I/O Out Bits [SK 300 E, SK 7 00E] @ 1\ mod_133577915 4763_388.docx @ 24778 @ @ 1
BU 0060 GB-4112 69
Page 70
CANopen – Supplementary manual options for NORD - Frequency Inverters
Adjustment of the limit values of the relay functions/Bus Out Bits. For a negative value, the output
reached and the setting values are positive, the relay contact closes, with
(1st word),
ip (4th word) are
Information
USS mode
P482 [-01] ...
Norm. BusIO Out Bits
(Standardisation of bus I/O Out bits )
[-08]
-400 … 400 % { all 100 }
function will be output negative. When the limit value is
negative setting values the relay contact opens. The assignment of the arrays correspond to those of parameter (P481).
Pos: 114 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P400-P 499/Param eter P483 – Hyst erese Bus I/O Out Bits [SK 300E, SK 700E] @ 1\mod_1335779289990_388.docx @ 24802 @ @ 1
P483 [-01] ...
1 … 100 % { all 10 }
Hyst. BusIO Out Bits
(Hysteresis of bus I/O Out bits)
[-08]
Difference between switch-on and sw itch-off poi nt to prevent oscillation of the output signal. The assignment of the arrays correspond to those of parameter (P481).
Pos: 115 /Anleit ungen/5. / 6. Parametri erung [BU 0 500 / BU 020 0]/P5xx Zus atzparameter @ 0\mod_1328091531180_388.docx @ 10880 @ 5 @ 1

5.1.2 Additional parameters

Parameter
{factory setting}
Pos: 116 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P503 – Leitfunktion Ausgabe [SK 300E, SK 7x0E] @ 1\mod_1342447391451_388.docx @ 32493 @ @ 1
P503
0 ... 5 { 0 }
Setting value / Description / Note Supervisor Parameter set
Master function output
(Master function output)
For master-slave applications this parameter specifies on which bus s ystem the master transmits the control word and the m aster values for the slave. On the slave, parameters (P509), (P510), (P546 )(… (P548)) define the source from which the slave obtains the control word and the master values from the master and how these are to be processed by the slave.
Only the master frequency (setpoint 1 and control word) is transferred with Mode 1, while the actual values selected in P543, P544 and P545 are transferred in Mode 2.
In Mode 3 a 32Bit actual position and a 16 bit setpoint speed (after ramp) is outp ut. M ode 3 is required for synchronous control with the Posic on option.
Mode 4 can be used for curve control in torque-coupled vehicles. The status w ord the actual setpoint frequency before the speed ramp (2nd word), the actual torque current standardised to the torque limit (3rd word) and the actual frequency without sl transmitted.
0 = Off 1 = USS mode 1 3 = USS mode 2 5 = USS mode 3 7 = USS mode 4 2 = CAN Mode 1 4 = CAN Mode 2 6 = CAN Mode 3 8 = CAN Mode 4
up to 250kBaud
S
S
S
Each USS mode prevents communication with a PC and NORD CON.
Pos: 117 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P509 – Sc hnittstelle [SK 300E, S K 700E - CANo pen] @ 1\mod_1342448673313_388.docx @ 32517 @ @ 1
70 BU 0060 GB-4112
Page 71
5 Parameters
**) If the communication during keyboard control is interrupted (time out 0.5 sec),
P509
0 ... 21 { 0 }
Interface
(Interface)
Selection of the interface via which the FI is controlled.
0 = Control terminals or keyboard control ** with the ControlBox (if P510=0), the
ParameterBox (not ext. P-box) or via BUS I/O Bits.
1 = Only control terminals , the FI can onl y be controlled via the digital and analog
inputs or via the bus I/O Bits.
5 = CAN setpoint*, the frequency setpoint is transferred via CAN. Control via the digital
inputs is still active.
6 = CAN control word*, the control signals (enable, direction of rotation, ...) are
transferred via UCAN, the setpoint via the analog input or the fixed frequencies.
7 = CAN*, all control data is transferred via CAN. The analog input and the digital inputs
have no function (except safety functions)
11 = CAN Broadcast*, the inverter receives all of the control data via CAN without
responding to the master (e.g. for the synchronisation function). The analog input and the digital inputs have no function (except safety functions)
15 = CANopen setpoint*, as for setting 5, but CANopen
16 = CANopen control word*, as for setting 6, but CANopen
17 = CANopen*, as for setting 7, but CANopen
*) Keyboard control (ControlBox, ParameterBox) is blocked, parameterisation is still possible.
Pos: 118 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P510 – Sc hnittstelle Busnebensol l werte [SK 700E] @ 1\ mod_1335780555886_388.docx @ 24850 @ @ 1
P510
0 ... 8 { all 0 }
Pos: 119 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P513 – Tel egrammausf allzeit @ 0 \mod_1328092407709_388.docx @ 11180 @ @ 1
the FI will block without an error message.
Bus interface auxiliary setpoint
(Bus interface auxiliary setpoin t s)
SK 700E/
SK750E
S
Selection of the interface via which the FI is controlled.
0 = Auto (=P509): The source of the auxiliary setpoint is automatically derived from the
setting in the parameter P509 >Interface<
1 = USS 2 = CANbus 3 = Profibus 4 = InterBus 5 = CANopen 6 = DeviceNet 7 =
Reserved
8 = CAN Broadcast
BU 0060 GB-4112 71
Page 72
CANopen – Supplementary manual options for NORD - Frequency Inverters
Monitoring function of the active bus interface. Following recei pt of a valid telegram, the next one
and switches off with the error
: Even if communication between BusBox and FI is interrupted (e.g. 24V error,
Used to set the transfer rate (transfer speed) via the CANbus interface. All bus participants must have the same baud rate setting. With the use of the CANopen technology unit, settings from this
the technology unit has been set to
Information
On, a Reset Node message or a Power On of the
Setting of the basic CANbus address for CAN and CANopen. With the use of the CANopen
rotary coding switch on
Information
Data takeover
The baud rate is only read after a Power On, a Reset Node message or a Power On of the
P513
-0.1 / 0.0 /
0.1 ... 1000 s { 0.0 }
Pos: 120 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P514 – CAN -Baudrate @ 0\mod_1328092466350_388.docx @ 11203 @ @ 1
P514
0 ... 7 { 4 }
Telegram time-out
(Telegram time out)
must arrive within the set period. Otherwise the FI reports an error message E010 >Bus Time Out<.
0.0 = Off: Monitoring is switched off.
-0.1 = No error
Box removed, etc.), the FI will continue to operate unchanged.
CAN baud rate
(CAN baud rate)
parameter are only valid if the BAUD rotary coding switch on
PGM.
0 = 10kBaud 1 = 20kBaud 2 = 50kBaud
3 = 100kBaud 4 = 125kBaud 5 = 250kBaud
*) Reliable operation cannot be guaranteed
Data takeover
S
6 = 500kBaud 7 = 1MBaud *
(for test purposes only)
Pos: 121 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P515 – CAN -Adresse [SK 300E, SK 7x0E . CANopen] @ 1\mod_1342517855338_388 .docx @ 32814 @ @ 1
P515
0 ... 255 { 50 }
Pos: 122 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/ Parameter/P500-P599/Param eter P543 – B us-Istwert 1 [SK 300E, SK 7x0 E] @ 1\mod_1335781763553_388.docx @ 24880 @ @ 1
The baud rate is only read after a Power 24V bus supply.
CAN address
(CAN address)
technology unit, settings from this parameter are only valid if the BAUD the technology unit has been set to PGM.
24V bus supply.
72 BU 0060 GB-4112
Page 73
5 Parameters
Note
Actual position (only with POSICON, SK 7x0E)
Actual frequency
Setpoint position (only with POSICON, SK 7x0E)
2 =
Actual speed
8 =
Setpoint frequency
3 =
Current
9 =
Error number
Actual position increment (only with
POSICON, SK 7x0E)1
Digital IO status 2
Setpoint position increment (on ly with
POSICON, SK 7x0E)1
12 =
BusIO Out Bits 0...7
P543
0 ... 12 { 1 }
Pos: 123 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P544 – B us-Istwert 2 [SK 300E, SK 7x0E] @ 1\ mod_1342518732806_388.docx @ 33038 @ @ 1
P544
Bus actual value 1
(Actual bus value 1)
SK 300E /
SK 7x0E
S P
The return value 1 can be selected for bus actuation in this parameter.
Settings
For detailed informationen concerning the settings, please refer to the description of parameter P418 for the respective frequency inverter.
Off
0 =
1 =
Torque current (100% = P112)
4 =
5 =
Actual bus value 2
(Actual bus value 2)
6 =
7 =
10 =
11 =
SK 300E /
SK 7x0E
S P
0 ... 12
This parameter is identical to P543.
{ 0 }
Pos: 124 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P545 – B us-Istwert 3 [SK 300E, SK 7x0E] @ 1\ mod_1342518842434_388.docx @ 330 62 @ @ 1
P545
0 ... 12
Actual bus value 3
(Actual bus value 3)
This parameter is identical to P543.
SK 300E /
SK 7x0E
S P
{ 0 }
Pos: 125 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P546 – B us-Sollwert 1 [SK 30 0E, SK 7x0E] @ 1\mod_1335786897102_388.docx @ 24952 @ @ 1
1
Setpoint/actual position corresponding to an 8192 increment encoder.
2
The assignment of the digital inputs in P543/ 544/ 545 = 5 for SK 700E/ SK 750E
Bit 0 = DigIn 1 Bit 1 = DigIn 2 Bit 2 = DigIn 3 Bit 3 = DigIn 4
Bit 4 = DigIn 5 Bit 5 = DigIn 6 Bit 6 = DigIn 7 (POS or ENC) Bit 7 = DigIn 8 (POS) Bit 8 = DigIn 9 (POS) Bit 9 = DigIn 10 (POS) Bit 10 = DigIn 11 (POS) Bit 11 = DigIn 12 (POS) Bit 12 = REL 1 Bit 13 = REL 2 Bit 14 = REL 3 (POS) Bit 15 = REL 4 (POS)
BU 0060 GB-4112 73
Page 74
CANopen – Supplementary manual options for NORD - Frequency Inverters
In this parameter, a function is allocated to the output setpoint 1 during bus actuation. The
type 2 or 4)
(P214)
SK 7x0E)
2 =
Torque current limit (P112)
13 =
Multiplication (only SK 7x0E)
3 =
Actual frequency PID
14 =
Process controller actual value
4 =
Frequency addition
15 =
Process controller setpoint
5 =
Frequency subtraction
16 =
Process controller lead
6 =
Current limit (only SK 7x0E) (P536)
17 =
BusIO In Bits 0...7
(P105)
SK 7x0E)
8 =
Actual PID frequency limited
19 =
Set relays (P541)
P546
0 ... 7 { 1 }
Pos: 126 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Paramet er P547 – Bus -Sollwert 2 [SK 30 0 E, SK 7x0E] @ 1\mod_1335788467112_388.do cx @ 24976 @ @ 1
P547
0 ... 20 { 0 }
Bus setpoint 1
(Bus setpoint 1)
SK 300E /
SK 7x0E
S P
settings 2 to 6 are only relevant for type SK 700E and SK 750E inverters in combination with the POSICON option.
0 = Off 1 = Setpoint frequency (16 bit) 2 = 16 Bit setpoint position 3 = 32 Bit Bit setpoint position (PPO
Bus setpoint 2
(Bus setpoint 2)
4 = POSICON control terminals (16 Bit)3 5 = Setpoint position (16 Bit) 6 = Setpoint position (32 Bit) increment 7 = Bus I/O In Bits 0-7
SK 300E /
SK 7x0E
S P
In this parameter, a function is allocated to the setpoint 2 which is output during bus actuation.
0 =
Off
1 =
Setpoint frequency
11 =
Torque precontrol (only SK 7x0E)
12 =
POSICON control terminals (only
Pos: 127 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P548 – B us-Sollwert 3 [SK 30 0E, SK 7x0E] @ 1\mod_1335790742656_388.docx @ 25000 @ @ 1
P548
0 ... 20 { 0 }
7 =
Maximum frequency (only SK 7x0E)
9 =
Actual PID frequency monitored
10 =
Torque
Bus setpoint 3
(Bus setpoint 3)
18 =
Curve travel calculator (only
20 = Set analog output (P542)
SK 300E /
SK 7x0E
S P
In this parameter, a function is assigned to the delivered setpoint 3 (SW3) for bus control. This is identical to parameter P547 and is only present if P546 ≠ 3 and 6.
3
The "reference run", "teach-in" and "reset position can be controlled via the other bits: Bit 0: Pos. array / Pos. increment Bit 1: Pos. array / Pos. increment Bit 2: Pos. array / Pos. increment Bit 3: Pos. array / Pos. increment Bit 4: Pos. array / Pos. increment Bit 5: Pos. array / Pos. increment Bit 6: Approach reference point Bit 7: R e f. point Bit 8: Teac h- In Bit 9: Quit Teach- In Bit 10: Reset pos.
74 BU 0060 GB-4112
Page 75
5 Parameters
Note
This parameter shows the software and revision
the FI. This can be significant when
Array 03 provides information about any special versions of the hardware or software A zero
This parameter informs about the actual control word and the setpoints that are transferred via the bus
P551
0 … 1
Drive profile
(Drive profile)
According to the option the relevant process data profiles can be activated with this parameter.
S
{ 0 }
System
CANopen DeviceNet InterBus
Technology module SK TUx-CAO SK TUx-DEV SK TUx-IBS Setting
0 = OFF =
1 = ON =
DS402 profile AC Drives profile Drivecom profile
USS protocol (Profile "Nord")
Activation of profiles
This parameter is only effective for pluggable technology modules (SK TU3-…).
Pos: 129 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/P7xx I nformatio nen @ 0\mod_1328170311705_388.docx @ 12293 @ 5 @ 1

5.1.3 Information

Parameter Setting value / Description / Note Supervisor Parameter set
Pos: 130 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P700-P 799/Param eter P707 – S oftware-Versi on/-Revision @ 0\mod_1328171743458_388.docx @ 12479 @ @ 1
P707 [-01] ... [-03]
Software-Version
(Software version/ revision)
0.0 ... 9999.9
Pos: 131 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P700-P 799/Param eter P740 – Prozessdaten Bus In [SK 300E, SK 7x0E] @ 1\mod_1335791131327_388.docx @ 25024 @ @ 1
P740 [-01] ... [-06]
0000 ... FFFF (hex)
Pos: 132 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P700-P 799/Param eter P741 – Prozessdaten Bus Out [SK 300E / SK 7x0E] @ 1\mod_1335791437905_388.docx @ 25048 @ @ 1
numbers in different FIs are assigned the same settings.
stands for the standard version.
Process data Bus In
(Process data bus in)
Series SK 300E: [-01 ] = Control word
systems. For display, a BUS system
must be selected in P509
[-02] = setpoint value 1 [-03] = setpoint value 2 [-04] = setpoint value 3
[-05] = Bus I/O In Bits (P480) [-06] = Bus I/O In Bits (P480)
... [-01] = Version number (1.7) ... [-02] = Revision number (R0) ... [-03] = Special version of hard-/software (0.0)
SK 300E /
SK 7x0E
S
Series SK 7x0E: [-01 ] = Control word
[-02] = setpoint value 1 [-03] = Setpoint val. 1 High byte [-04] = setpoint value 2 [-05] = setpoint value 3
BU 0060 GB-4112 75
Page 76
CANopen – Supplementary manual options for NORD - Frequency Inverters
information about the actual status word and the actual values that are transferred
xxx), but only when own
Version status (software version) of the installed option module(s) but only when own processor is present, i.e. not for
codes specific to the bus can be found in the section "Error monitoring" of the
P741 [-01] ...
0000 ... FFFF (hex) This parameter provides
Process data Bus Out
(Process data bus out)
[-06]
via the bus systems.
Series SK 300E [-01] = Status word
[-02] = Actual value 1 [-03] = Actual value 2 [-04] = Actual value 3
SK 300E /
SK 7x0E
Series SK 7x0E [-01] = Status word
[-02] = Actual value 1 [-03] = Actual val. 1 High byte [-04] = Actual value 2 [-05] = Actual value 3
[-05] = Bus I/O Out Bit (P481) [-06] = Bus I/O Out Bit (P481)
Pos: 133 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P700-P 799/Param eter P745 – B aug r u p pen Version [SK 3 00 E] @ 1\mod_1335791798489_388.docx @ 25072 @ @ 1
P745
Module version
(Module version)
SK 300E
0.0 ... 3276.7 Version status (software version) of the technology unit (SK TU2-
processor is present, i.e. not for SK TU2-CTR. Have this data available if you have a technical query.
Pos: 134 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P700-P 799/Param eter P745 – B aug r u p pen Version [SK 7 x 0E ] @ 1\ mod_13357920 03777_388.docx @ 25096 @ @ 1
P745 [-01] ...
0000 ... FFFF (hex)
Module version
(Module version)
[-03]
SK TU1-CTR. Have this data available if you have a technical query.
SK 7x0E
[-01] = Technology unit [-02] = Customer unit [-03] = Special extension unit
S
S
Pos: 135 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Parameter/P700-P799/Parameter P7 46 – Baugruppen Zustand [SK 300E] @ 1\mod_1335792492116_388.docx @ 25120 @ @ 1
P746
Module status
(Module status)
SK 300E
S
0000 ... FFFF (hex) Shows the actual status (readiness, error, communication) of the technology unit (SK TU2-xxx),
but only when own processor is present, i.e. not for SK TU2-CTR. Example: 0603
hex
High byte = 06 Low byte = 03
à Profibus
hex
à Module ready + connection to master
hex
Details of the relevant supplementary instru c tion s.
Pos: 136 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P700-P 799/Param eter P746 – B augruppen Zus tand [SK 7 x0E] @ 1\mo d_1335792880284 _388.docx @ 25144 @ @ 1
76 BU 0060 GB-4112
Page 77
5 Parameters
P746 [-01] ... [-03]
Module status
(Module status)
SK 7x0E
0000 ... FFFF (hex) Shows the actual status (readiness, error, communication) of
the installed technology unit(s) (if active), but only when own processor is present, i.e. not for SK TU1-CTR.
Example: 0603
hex
High byte = 06 Low byte = 03
à Profibus
hex
à Module ready + connection to master
hex
Details of the codes specific to the bus can be found in the section "Error monitoring" of the relevant supplementary instructions.
Pos: 137 /A nleitungen/El ektronik/B ussysteme/ 5. Parameter /BUS Para meter SK 5x xE @ 1\mod_1336378272615_388.docx @ 25201 @ 2 @ 1
S
[-01] = Technology unit [-02] = Customer unit [-03] = Special extension unit
BU 0060 GB-4112 77
Page 78
CANopen – Supplementary manual options for NORD - Frequency Inverters
The SK 54xE frequency inverter can administer 5 setpoint or actual values (each 16 bit). However, via the
... the bus system only provides the possibility of processing setpoint or actual values 1 ...
in association with IO extension modules these I/O bits can also process their
The possible functions for the Bus In Bits can be found in the table of functions for the digital

5.2 SK 5xxE BUS Parameters

Information
technology unit SK TU3-
3.
Pos: 138 /Anleit ungen/5. /6. Parametrierung [BU 0500 / BU 0200]/P4xx Steuerklemm en @ 0\mod_1327678262854_388.docx @ 9027 @ 5 @ 1

5.2.1 Control t ermi nals

Parameter
{factory setting}
Pos: 139 /Anleit ungen/5. / 6. Parametri erung [BU 0 500 / BU 020 0]/Parameter /P400-P499/ Parameter P480 – Funktion Bus I/O In Bits [S K 5 x xE] @ 0\ mod_1328002641156_388.docx @ 10779 @ @ 1
P480 [-01] ...
0 ... 80 { all 0 }
Setting value / Description / Note Supervisor
Function BusIO In Bits
(Bus I/O In Bits function)
[-12]
The Bus I/O In Bits are perceived as digital inputs (P420). They can be set to the same functions. In order to use this function, one of the bus setpoints (P546) must be set to >Bus I/O In Bits 0 -7
<. The required function must then be assigned to the relevant bit. With the SK 54xE
input signals.
[-01] = Bus I/O In Bit 0 (or SK54xE and above: + DI1 of the second IOE) [-02] = Bus I/O In Bit 1 (or SK54xE and above: + DI2 of the second IOE) [-03] = Bus I/O In Bit 2 (or SK54xE and above: + DI3 of the second IOE) [-04] = Bus I/O In Bit 3 (or SK54xE and above: + DI4 of the second IOE) [-05] = Bus I/O In Bit 4 (or SK54xE and above: + DI1 of the first IOE) [-06] = Bus I/O In Bit 5 (or SK54xE and above: + DI2 of the first IOE) [-07] = Bus I/O In Bit 6 (or SK54xE and above: + DI3 of the first IOE) [-08] = Bus I/O In Bit 7 (or SK54xE and above: + DI4 of the first IOE) [-09] = Flag 1 [-10] = Flag 2 [-11] = Bit 8 BUS control word [-12] = Bit 9 BUS control word
Number of bus setpoints and actual values
S
Parameter set
inputs. Function {14} "Remote contr ol" is not pos sib le.
Pos: 140 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P400-P 499/Param eter P481 – Funktion Bus I/O Out B its [SK 5xxE] @ 0\mod_1328002703095_388.docx @ 10802 @ @ 1
78 BU 0060 GB-4112
Page 79
5 Parameters
perceived as digital outputs (P434). They can be set to the same
in association with IO extension modules these I/O bits can also process their
functions for the Bus Out Bits can be found in the table of functions for the digital
Adjustment of the limit values of the relay functions/Bus Out Bits. For a negative value, the output
values are positive, the relay contact closes, with
P481 [-01] ... [-10]
0 ... 39 { all 0 }
Pos: 141 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P400-P 499/Param eter P482 – Nor mierung Bus I/O Out Bits [SK 5xx E] @ 0\mod_1328002779143_388.docx @ 10825 @ @ 1
P482 [-01] ...
[-10]
Function BusIO Out Bits
(Function of Bus I/O Out Bits)
The bus I/O Out bits are functions.
In order to use this function, one of the bus setpoints (P543) must be set to >Bus I/O In Bits 0-7 <. The required function must then be assigned to the relevant bit.
With the SK 54xE input signals.
[-01] = Bus I/O Out Bit 0 [-02] = Bus I/O Out Bit 1 [-03] = Bus I/O Out Bit 2 [-04] = Bus I/O Out Bit 3 [-05] = Bus I/O Out Bit 4 (or SK54xE and above: + DO1 of the first IOE) [-06] = Bus I/O Out Bit 5 (or SK54xE and above: + DO2 of the first IOE) [-07] = Bus I/O Out Bit 6 / Flag 1 (or SK54xE and above: + DO1 of the second IOE) [-08] = Bus I/O Out Bit 7 / Flag 2 (or SK54xE and above: + DO2 of the second IOE) [-09] = Bit 10 BUS status word [-10] = Bit 13 BUS status word
The possible outputs or the relays.
For further details, please refer to the manual for the AS interface, BU 0090.
Norm. BusIO Out Bits
(Scaling of bus I/O Out bits)
S
S
-400…400 % { all 100 }
Pos: 142 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P400-P 499/Param eter P483 – Hyst erese Bus I/O Out Bits [SK 5xxE] @ 0\ mod_1328002828441_388.docx @ 10 848 @ @ 1
P483 [-01] ... [-10]
1…100 % { all 10 }
Pos: 143 /Anleit ungen/5. / 6. Parametri erung [BU 0 500 / BU 020 0]/P5xx Zus atzparameter @ 0\mod_1328091531180_388.docx @ 10880 @ 5 @ 1
function will be output negative. When the limit value is reached and the setting
negative setting values the relay contact opens. The assignment of the arrays correspond to those of parameter (P481).
Hyst. BusIO Out Bits
(Hysteresis of bus I/O Out bits)
Difference between switch-on and sw itch-off poi nt to prevent oscillation of the output signal. The assignment of the arrays correspond to those of parameter (P481).
S
BU 0060 GB-4112 79
Page 80
CANopen – Supplementary manual options for NORD - Frequency Inverters
535E:
master values). The assignment of these
this parameter specifies on which bus system the master transmits
the control word and the master values (P502) for the slave. On the slave, parameters (P509),

5.2.2 Additional parameters

Parameter
{factory setting}
Pos: 144 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P502 – Wer t L ei tf unktion @ 0\mod_1328091690836_388.do cx @ 10927 @ @ 1
P502 [-01] ... [-05]
0 ... 57 { all 0 }
Pos: 145 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P503 – Leitfunktion Ausgabe @ 0\ mod_1328091743696_388.docx @ 10950 @ @ 1
P503
Setting value / Description / Note Supervisor Parameter set
Value Masterfunction
(Value master function)
S P
Selection of the master value of a Master for output to a bus system (see P503) - (up to SK max. 3 master values, SK 540 and above: max. 5 master values to the slave is carried out via (P546) (...(P548)):
[-01] = Master value 1 [-02] = Master value 2 [-03] = Master value 3
SK 540E and above:
[-04] = Master value 4 [-05] = Master value 5
Selection of possible setting values for master values:
00 = Off 01 = Actual frequency 02 = Actual speed 03 = Electricity 04 = Torque current 05 = State of digital inputs and
outputs
06 = Reserved 07 = Reserved 08 = Setpoint frequency
09 = Error message 10 = Reserved 11 = Reserved 12 = Digital Ou t Bit 0…7 13 = Reserved 14 = Reserved 15 = Reserved 16 = Reserved 17 = Value analog input 1 18 = Value analog input 2
19 = Setpoint frequency
master value 20 = Setpoint freq. after
master val ramp 21 = Actual freq. without
master value slip
22 = Speed encoder 23 = Actual freq. with slip
(SW V2.0 and above)
24 = Master value, act. freq. with slip
(SW V2.0 and above)
53 = ... 57 Reserved
Master function output
(Master function output)
S
0 ... 5 { 0 }
For master-slave applications (P510), (P546 ... ) define the source from which the slave obtains the control word and the master
values from the master and how these are to be processed by the slave.
0 = Off: no output of control word and master valu es. 1 = USS: output of control words and master values to USS. 2 = CAN: output of control words and master values to CAN (up to
250 kBaud).
3 = CANopen: output of control words and master values to CANopen. 4 = System bus active: no output of control word and master values, however via the
ParameterBox or NORD CON, all participants whic h are set to System bus active are visible.
5 = CANopen+Sys.bus active: output of control word and master values on CAN open via
the ParameterBox or NORD CON, all participants which are set to system bus active are visible.
Pos: 146 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P509 – Quel l e Steuerwort @ 0\ mod_1328092104264_388.docx @ 11088 @ @ 1
80 BU 0060 GB-4112
Page 81
5 Parameters
, the FI can only be controlled via the digital and analog inputs or
*) Keyboard control (ControlBox, ParameterBox, PotentiometerBox) is blocked,
**) If the communication during keyboard control is interrupted (time out 0.5 sec),
based bus systems (e.g.:
Parameterisation of a frequency inverter via a field bus connection requires
For details about the respective Bus systems please
P509
0 ... 10 { 0 }
Source Control Word
(Source control word)
Selection of the interface via which the FI is controlled.
0 = Control terminals or keyboard control ** with the ControlBox (if P510=0), the
ParameterBox (not ext. p-box) or via BUS I/O Bits.
1 = Only control terminals
via the bus I/O Bits.
2 = USS control word *, the control signals (enable, direction of rotation, ...) are transferred
via the RS485 interface. The setpoint is transferred via the analog input or the fixed frequencies. Above SK 540E this setting should also be selected if communication via Modbus RTU is intended. The frequency inverter automatically detects whether this is a USS protocol or a Modbus protocol.
3 = CAN control word * 4 = Profibus control word * 5 = InterBus control word *
NOTE:
6 = CANopen control word * 7 = DeviceNet control word * 8 = Ethernet TU*** control word*
refer to the respective Options descriptions.
www.nord.com -
9 = CAN Broadcast *
10 = CANopen Broadcast *
parameterisation is still possibl e.
Pos: 147 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P510 – Q uel l e Sollwerte @ 0\mod_1328092251176_388.docx @ 11111 @ @ 1
P510 [-01] [-02]
0 ... 10 { all 0 }
Pos: 148 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P513 – Tel egrammausf allzeit @ 0 \mod_1328092407709_388.docx @ 11180 @ @ 1
the FI will block without an error message.
***) The Ethernet TU setting must be used for all NORD Ethernet-
EtherCAT: SK TU3-ECT, PROFINET: SK TU3-PNT).
Note:
parameter (P509) "Control Terminals" to be set to the appropriate bus syste m
Setpoint source
(Setpoint source)
S
Selection of the setpoint source to be parameterised.
[-01] = Main setpoint source [-02] = Auxiliary setpoint source
Selection of the interface via which the FI recei ves the setpoint.
0 = Auto (=P509): The source of the auxiliary setpoint is
automatically derived from the setting in the parameter P509 >Interface<
1 = Control terminals, digital and analog inputs control
the frequency, including fixed frequencies
2 = USS (or Modbus RTU SK 540E and above) 3 = CAN
4 = Profibus 5 = InterBus 6 = CANopen 7 = DeviceNet 8 = Ethernet TU 9 = CAN Broadcast
10 = CANopen Broadcast
BU 0060 GB-4112 81
Page 82
CANopen – Supplementary manual options for NORD - Frequency Inverters
Monitoring function of the active bus interface. Following recei pt of a valid telegram, the next one
Otherwise the FI reports an error and switches off with the error
: Even if communication between BusBox and FI is interrupted (e.g. 24V error,
Used to set the transfer rate (transfer speed) via the CANbus interface. All bus participants must have the same baud rate setting. With the use of the CANopen technology unit, settings from this
the technology unit has been set to
Information
On, a Reset Node message or a Power On of the
Setting of the basic CANbus address for CAN and CANopen. With the use of the CANopen
The baud rate is only read after a Power On, a Reset Node message or a Power On of the
P513
-0.1 / 0.0 /
0.1 ... 1000 s { 0.0 }
Pos: 149 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P514 – CAN -Baudrate @ 0\mod_1328092466350_388.docx @ 11203 @ @ 1
P514
0 ... 7 { 4 }
Telegram time-out
(Telegram time out)
must arrive within the set period. message E010 >Bus Time Out<.
0.0 = Off: Monitoring is switched off.
-0.1 = No error
Box removed, etc.), the FI will continue to operate unchanged.
CAN baud rate
(CAN baud rate)
parameter are only valid if the BAUD rotary coding switch on
PGM.
0 = 10kBaud 1 = 20kBaud 2 = 50kBaud
3 = 100kBaud 4 = 125kBaud 5 = 250kBaud
*) Reliable operation cannot be guaranteed
Data takeover
S
6 = 500kBaud 7 = 1MBaud *
(for test purposes only)
Pos: 150 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P515 – CAN -Adresse @ 0\mod_1328092561242_388.docx @ 11226 @ @ 1
P515 [-01] ... [-03]
0 ... 255 { all 50 }
The baud rate is only read after a Power 24V bus supply.
CAN address
(CAN address)
technology unit, settings from this parameter are only valid if the BAUD rotary coding switch on the technology unit has been set to PGM.
Information Data takeover
24V bus supply.
From software version 1.6 and above, this can be set in three levels:
[-01] = Slave address, Receipt address for CAN and CANopen (as before) [-02] = Broadcast slave address, Broadcast – receipt address for CANopen (Slave) [-03] = Master address, Broadcast – Transmission address for CANopen (Master)
Pos: 151 /Anleit ungen/5. /6. Parametrierung [BU 0500 / BU 0200]/Parameter/P500-P599/Parameter P5 43 – Bus-Istwer t 1 [S K 50 0. . . 53 5E] @ 0\mod_1328097541755_388.docx @ 11824 @ @ 1
82 BU 0060 GB-4112
Page 83
5 Parameters
For further details please refer to the manual for the frequency inverter (P418, P543),
relevant bus module. For
further details please refer to the manual for the frequency inverter (P418, P543),
0 =
Off
13 =
... 16 Reserved
1 =
Actual frequency
17 =
Value analog input 1
2 =
Actual speed
18 =
Value analog input 2
3 =
Current
19 =
Setpoint frequency master value(P503)
4 =
Torque current (100% = P112)
20 =
Setpoint frequency master value after
"Setpoint frequency master
value after ramp"
5 =
Digital IO status 4
21 =
Act. freq. without slip master value
"Actual frequency without slip master value"
6 =
22 =
Speed encoder
sible with
SK 520E and encoder feedback)
8 =
Setpoint frequency
23 =
Actual frequency with slip, "Actual
9 =
Error number
24 =
Master value, actual freq. with slip,
(SW V2.0 and above)
10 =
... 11 Reserved
53 =
... 57 Reserved
12 =
BusIO Out Bits 0...7
P543
0 ... 24 { 1 }
Pos: 152 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P543 – B us-Istwerte [SK 54xE] @ 0\mod_1328097636349_388.docx @ 11847 @ @ 1
P543 [-01] ...
[-05]
0 ... 57 { [-01] = 1 }
{ [-02] = 4 } { [-03] = 9 } { [-04] = 0 } { [-05] = 0 }
Actual bus value 1
(Actual bus value 3)
S P
The return value 1 can be s elected for bus actuation in this parameter. The possible analog functions can be found in the following table. NOTE:
the relevant BUS operating instructions or BU 0510.
Bus actual value
(Bus – Actual value)
S P
In this parameter the return value for bus actuation can be selected. NOTE: The actual values 4 and 5 must be supported by the
the relevant BUS operating instructions or the manuals BU 0510 / BU0550.
[-01] = Bus - Actual value 1 [-02] = Bus - Actual value 2 [-03] = Bus - Actual value 3 [-04] = Bus - Actual value 4 [-05] = Bus - Actual value 5
Pos: 153 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P544 – B us-Istwert 2 [SK 50 0. ..535E] @ 0\mod_1328097766412_388.do cx @ 11870 @ @ 1
P544
0 ... 24 { 0 }
Pos: 154 /Anleit ungen/5. /6. Parametrier ung [BU 05 00 / BU 0200] /Parameter/ P500-P599/P arameter P 545 – Bus-Istw er t 3 [ S K 50 0...535E] @ 0\ mod_1328097880052_388.docx @ 11893 @ @ 1
... 7 Reserved
Actual bus value 2
(Actual bus value 2)
This parameter is identical to P543. Condition is PPO 2 or PPO 4 type (P507).
ramp
(only pos
frequency with slip"
(SW V2.0 and above)
"Master value, actual freq. with slip"
S P
4
The assignment of the digital inputs in P543/ 544/ 545 = 5
Bit 0 = DigIn 1 Bit 1 = DigIn 2 Bit 2 = DigIn 3 Bit 3 = DigIn 4 Bit 4 = DigIn 5 Bit 8 = Dig. func. AIN1 AIN2 Bit 12 = Out 1/ MFR1
BU 0060 GB-4112 83
Bit 5 = DigIn 6 (SK 520E and above) Bit 6 = DigIn 7 (SK 520E and above) Bit 7 = Dig. func. AIN1
Bit 9 = DigIn 8 (SK 540E and above) Bit 10 = DigIn 1, 1.IOE (SK 540E and above) Bit 11 = DigIn 2, 1.IOE (SK 540E and above)
Bit 13 = Out 2/ MFR2 Bit 14 = Out 3/ DOUT1 (SK 520E and above) Bit 15 = Out 4/ DOUT2 (SK 520E and above)
Page 84
CANopen – Supplementary manual options for NORD - Frequency Inverters
For further details please refer to the manual for the frequency inverter (P400, P546),
The setpoints 4 and 5 must be supported by the relevant bus module. For further
(P400, P546), the
0 =
Off
16 =
Process controller lead
1 =
Setpoint frequency
17 =
BusIO In Bits 0...7
2 =
Torque current limit (P112)
18 =
Curve travel calculator
3 =
Actual frequency PID
19 =
Set relays, "Output status" (P434/441/450/455=38)
4 =
Frequency addition
20 =
Set analog output (P418=31)
5 =
Frequency subtraction
21 =
... 45 reserved from SK 530E and above à BU 0510
6 =
46 =
torque process controller"
7 =
Maximum frequency (P105)
47 =
reserved from SK 530E and above à BU 0510
8 =
Actual PID frequency limited
48 =
Motor temperature (SK 540E a nd above)
9 =
Actual PID frequency monitored
49 =
reserved from SK 540E and above à BU 0510
10 =
Torque servo mode (P300)
53 =
d-correction F process (SK 540E and above)
11 =
Torque precontrol (P214)
54 =
d-correction Torque (SK 540E and abov e)
12 =
Reserved
55 =
d-correction F+torque (SK 540E and
13 =
Multiplication
56 =
reserved from SK 540E and above à BU 0510
14 =
57 =
BU 0510
15 =
Process controller setpoint
P545
0 ... 24 { 0 }
Pos: 155 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P546 – Funktion Bus-Sollwert 1 [SK 500...535E] @ 0\mod_132809796 2990_388.docx @ 11916 @ @ 1
P546
0 ... 55 { 1 }
Pos: 156 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P546 – Funktion Bus-Sollwerte [SK 54xE] @ 0\mod_1328098077630_388.docx @ 11939 @ @ 1
P546 [-01] ... [-05]
0 ... 57 { [-01] = 1 } all other { 0 }
Actual bus value 3
(Actual bus value 3)
S P
This parameter is identical to P543. Condition is PPO 2 or PPO 4 type (P507).
Digital Bus setpoint 1
(Function of bus setpoint 1)
S P
In this parameter, a function is allocated to the output setpoint 1 during bus actuation. The possible analog functions can be found in the following table. NOTE:
the relevant BUS operating instructions or the manuals BU 0510 / BU0550.
Digital Bus setpoint
(Function of bus setpoint)
S P
In this parameter, during bus actuation a function is allocated to the setpoint provided. NOTE:
details please refer to the manual for the frequency inverter relevant BUS operating instructions or the manuals BU 0510 / BU0550.
[-01] = Bus setpoint 1 [-02] = Bus setpoint 2 [-03] = Bus setpoint 3 [-04] = Bus setpoint 4 [-05] = Bus setpoint 5
Pos: 157 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P547 – Funktion Bus-Sollwert 2 [SK 500...535E] @ 0\mod_132809818 0008_388.docx @ 11962 @ @ 1
84 BU 0060 GB-4112
Current limit (P536)
Process controller actual value
Setpoint Torque processreg., "Setpoint
above)
reserved from SK 540E and above à
Page 85
5 Parameters
Note
P547
0 ... 55 { 0 }
Pos: 158 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P548 – Funktion Bus-Sollwert 3 [SK 500...535E] @ 0\mod_1328098278323_388.docx @ 11985 @ @ 1
P548
0 ... 55 { 0 }
P551
0 … 1 { 0 }
Digital Bus setpoint 2
(Function of bus setpoint 2)
S P
This parameter is identical to P546.
Digital Bus setpoint 3
(Function of bus setpoint 3)
S P
This parameter is identical to P546.
Drive profile
(Drive profile)
S
According to the option the relevant process data profiles can be activated with this parameter.
System
CANopen DeviceNet InterBus
Technology module SK TUx-CAO SK TUx-DEV SK TUx-IBS Setting
0 = OFF =
USS protocol (Profile "Nord")
Pos: 160 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P500-P 599/Param eter P560 – P arameter Speic hermode @ 0\mod_1328098918376_388.docx @ 12238 @ @ 1
P560
0 ... 2 { 1 }
Pos: 161 /Anl eitungen/5. / 6. Parametr ierung [BU 0500 / BU 02 00]/P7xx Inf ormationen @ 0\mod_1328170311705_388. docx @ 12293 @ 5 @ 1
1 = ON =
DS402 profile AC Drives pro file Drivecom profile
Activation of profiles
This parameter is only effective for pluggable technology modules (SK TU3-…).
Parameter, Saving mode
(Saving mode parameter)
0 = Only in RAM, changes to the parameter settings are no longer saved on the EEPROM.
All previously saved settings are retained, even if the FI is disconnected from the mains.
1 = RAM and EEPROM, all parameter changes are automatically written to the EEPROM
and remain stored there even if the FI is disconnected from the mains supply.
2 =
OFF, no saving in RAM and EEPROM possible (no parameter changes are accepted)
NOTE:
If BUS communication is us ed to implement parameter changes, it must be ensured that the maximum number of write cycles (100,000 x) in the EEPROM is not exceeded.
S
BU 0060 GB-4112 85
Page 86
CANopen – Supplementary manual options for NORD - Frequency Inverters
This parameter shows the software and revision numbers in the FI. This can be significant when
Array 03 provides information about any special versions of the hardware or software A zero
This parameter informs word and the setpoints that
are transferred via the bus

5.2.3 Information

Parameter Setting value / Description / Note Supervisor Parameter set
Pos: 162 /Anleit ungen/5. /6. Parametrier ung [BU 05 00 / BU 0200] /Parameter/ P700-P799/P arameter P 707 – Softwar e-Version/-Revision @ 0\mod_1328171743458_388.docx @ 12479 @ @ 1
P707 [-01] ... [-03]
Software-Version
(Software version/ revision)
0.0 ... 9999.9
Pos: 163 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P700-P 799/Param eter P740 – Prozessdaten Bus In [SK 500...535E] @ 0\mod_132817524 8086_388.docx @ 13313 @ @ 1
P740 [-01] ...
[-13]
0000 ... FFFF (hex)
Pos: 164 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P700-P 799/Param eter P740 – Prozessdaten Bus In [SK 54xE] @ 0\mod_1328177837899_388.docx @ 13336 @ @ 1
different FIs are assigned the same settings.
stands for the standard version.
Process Data Bus In
(Process data Bus In)
about the actual control
systems. For display, a BUS system
must be selected in P509
[-01 ] = Control word [-02] = setpoint value 1
[-03] = setpoint value 2 [-04] = setpoint value 3
[-05] = Bus I/O In Bits (P480)
[-06] = Parameter data In 1 [-07] = Parameter data In 2 [-08] = Parameter data In 3 [-09] = Parameter data In 4 [-10] = Parameter data In 5
[-11] = setpoint value 1 [-12] = setpoint value 2 [-13] = setpoint value 3
... ... [-01] = Version number (1.7)
... ... [-02] = Revision number (R0)
... ... [-03] = Special version of
hardware/software (0.0)
S
Control word, source from P509.
Setpoint data from main setpoint (P510 [-01]).
The displayed value depicts all Bus In Bit sources linked with "OR".
Data during parameter transfer: Order label (AK),Parameter number (PNU), Index (IND), Parameter value (PWE 1/2)
Setpoint data from the master function value (Broadcast), if P509 = 9/10 (P510 [-02])
86 BU 0060 GB-4112
Page 87
5 Parameters
This parameter informs about the actual control word and the setpoints that are transferred via the bus
This parameter provides information about the actual status word and the actual values that are transferred
P740 [-01] ... [-23]
Process Data Bus In
(Process data Bus In)
S
0000 ... FFFF (hex)
Pos: 165 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P700-P 799/Param eter P741 – Prozessdaten Bus Out [SK 500...535E] @ 0\mod_1328177890266_388.docx @ 13359 @ @ 1
P741 [-01] ... [-13]
[-01 ] = Control word [-02] = setpoint value 1
systems. For display, a BUS system
must be selected in P509
[-03] = setpoint value 2 [-04] = setpoint value 3 [-05] = setpoint value 4 [-06] = setpoint value 5
[-07] = Bus I/O In Bits (P480)
[-08] = Parameter data In 1 [-09] = Parameter data In 2 [-10] = Parameter data In 3 [-11] = Parameter data In 4 [-12] = Parameter data In 5
[-13] = setpoint value 1 [-14] = setpoint value 2 [-15] = setpoint value 3 [-16] = setpoint value 4 [-17] = setpoint value 5
[-18] = PLC control word [-19] = setpoint value 1
[-20] = setpoint value 2 [-21] = setpoint value 3 [-22] = setpoint value 4 [-23] = setpoint value 5
Process Data Bus Out
(Process data Bus Out)
Control word, source from P509.
Setpoint data from main setpoint (P510 [-01]).
The displayed value depicts all Bus In Bit sources linked with "OR".
Data during parameter transfer: Order label (AK),Parameter number (PNU), Index (IND), Parameter value (PWE 1/2)
Setpoint data from the master function value (Broadcast), if P509 = 9/10 (P510 [-02])
Control word, source PLC
Setpoint data from the PLC.
S
0000 ... FFFF (hex)
Pos: 166 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P700-P 799/Param eter P741 – Prozessdaten Bus Out [SK 54xE] @ 0\mod_1328177956772_388.docx @ 13382 @ @ 1
via the bus systems.
[-01] = Status word [-02] = Actual value 1 (P543)
[-03] = Actual value 2 (P544) [-04] = Actual value 3 (P545)
[-05] = Bus I/O Out Bit (P481)
[-06 ] = Parameter data Out 1 [-07 ] = Parameter data Out 2 [-08 ] = Parameter data Out 3 [-09 ] = Parameter data Out 4 [-10 ] = Parameter data Out 5
[-11] = Actual value 1 master
function
[-12] = Actual value 2 master
function
[-13] = Actual value 3 master
function
Status word, source from P509.
The displayed value depicts all Bus OUT Bit sourc es linked with " OR".
Data during parameter transfer.
Actual value of master function P502 / P503.
BU 0060 GB-4112 87
Page 88
CANopen – Supplementary manual options for NORD - Frequency Inverters
This parameter provides information about the actual status word and the actual values that are transferred
xxx), but only when own
Details of the codes specific to the bus can be found in the section "Error monitoring" of the
P741 [-01] ...
0000 ... FFFF (hex)
Pos: 167 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P700-P 799/Param eter P745 – B aug r u p pen Version @ 0\mod_1328178182499_388.docx @ 13474 @ @ 1
P745
-3276.8 ... 3276.8 Version status (software version) of the technology unit (SK TU3-
Pos: 168 /Anl eitungen/5. / 6. Parametr ierung [BU 0500 / BU 02 00]/Parame ter/P700-P7 99/Paramet er P746 – Baugruppen Zustand PBR [SK 5xxE] @ 1\mod_1335793579623_388.docx @ 25168 @ @ 1
P746
Process Data Bus Out
(Process data Bus Out)
[-23]
[-01] = Status word [-02] = Actual value 1 (P543 [-01])
via the bus systems.
[-03] = Actual value 2 (P543 [-02]) [-04] = Actual value 3 (P543 [-03]) [-05] = Actual value 4 (P543 [-04]) [-06] = Actual value 5 (P543 [-05])
[-07] = Bus I/O Out Bit (P481)
[-08 ] = Parameter data Out 1 [-09 ] = Parameter data Out 2 [-10 ] = Parameter data Out 3 [-11 ] = Parameter data Out 4 [-12 ] = Parameter data Out 5
[-13] = Actual value 1 master
function
[-14] = Actual value 2 master
function
[-15] = Actual value 3 master
function
[-16] = Actual value 4 master
function
[-17] = Actual value 5 master
function
[-18] = PLC status word [-19] = Actual value 1 PLC
[-20] = Actual value 2 PLC [-21] = Actual value 3 PLC [-22] = Actual value 4 PLC [-23] = Actual value 5 PLC
Module version
(Module version)
processor is present, i.e. not for SK TU3-CTR. Have this data available if you have a technical query.
Module status
(Module status)
S
Status word, source from P509.
The displayed value depicts all Bus OUT Bit sourc es linked with " OR".
Data during parameter transfer.
Actual value of master function P502 / P503.
Status word via PLC
Actual value data via PLC
S
0000 ... FFFF (hex) Shows the actual status (readiness, error, communication) of the technology unit (SK TU3-xxx),
but only when own processor is present, i.e. not for SK TU3-CTR. Example: 0603
hex
High byte = 06 Low byte = 03
à Profibus
hex
à Module ready + connection to master
hex
relevant supplementary instru c tion s.
Pos: 169 /A nleitungen/5 . /6. Param etrierung [BU 0500 / BU 0200]/Para meter/P700-P 799/Param eter P748 – St atus CANopen @ 0\mod_1328178317375_388. docx @ 13543 @ @ 1
88 BU 0060 GB-4112
Page 89
5 Parameters
P748 [-01] ... [-03]
0000 ... FFFF (hex)
Pos: 170 /Anleit ungen/6. /7. Mel dungen zum Bet r i e bsz ustand [BU 05 00 / B U 02 00]/SK 5xxE 6. M el d u ng en zum Betrieb s zu s ta nd @ 0\mod_1328182661026_388.docx @ 13845 @ 1555 @ 1
SK 520E or
higher
S
Status CANopen
(CANopen status) [01] = CANbus/CANopen status [-02] = reserved [-03] = reserved
Bit 0 = 24V bus voltage supply Bit 1 = CANbus in "Bus Warning" status Bit 2 = CANbus in "Bus Off" status Bit 3 ... Bit 5 = free Bit 6 = Protocol of the CAN module is 0 =
CAN or 1 = CANopen Bit 7 = free Bit 8 = "Bootsup Message" sent Bit 9 = CANopen NMT State Bit 10 = CANopen NMT State Bit 11 = free Bit 12 ... 14 = reserved Bit 15 = free
CANopen NMT State Bit 10 Bit 9
Pre-Operational =
Stopped =
Operational =
0 0 1
0 1 0
BU 0060 GB-4112 89
Page 90
CANopen – Supplementary manual options for NORD - Frequency Inverters

6. Operating status messages

Frequency inverters and technology units gen erate appropriate messages if they deviate from their normal operating status. There is a differentiation between warning and error messages. If the frequency inverter is in the status "Start disabled", the reason for this can also be displayed.

Frequency inverter start disabled

If the frequency inverter is i n the s ta tus "N ot Re ady" or "Start Disabled", th e r easo n for this is indicated in the third array element of parameter (P700).
Display is only possible with the NORD CON software or the ParameterBox (SK PAR-3H).

Warning messages

Warning messages are g enerate d as soon as a def ined limit is r eac hed. H owev er th is does not c ause the frequency inver ter to switch of f. These mess ages can be displa yed via the arra y element [-02] in parameter (P700) unti l either the reas on for the warning is no long er present or the fr equenc y inverter has gone into a fault state with an error message.

Error messages

Errors cause the frequency inverters to switch off, in order to prevent a device fault. The following options are available to reset a fault (acknowledge):
• Switching the mains off and on again,
• By an appropriately programmed digital input (P420 ... P425 / P470 = Function 12),
• By switching off the “enable” on the frequency inverter (if no digital input is programmed for acknowledgement),
• By Bus acknowledgem ent or
• By P506, automatic error acknowledgement.
Device LEDs: As delivered (without the technology unit) 2 LEDs (green/red) are visible
externally. These indicate the actual device status.
The green LED indicates that the mains voltage is present and operational,
while a flashing code that increases in speed sho ws the degree of overload at the frequency inverter output.
The red LED signals actual error by flashing with a frequency which
corresponds to the number code of the fault.
Pos: 171 /A nleitungen/El ektronik/B ussysteme/ 6. Meldunge n zum Betrie bszustand / Fehlerüber wachung/Fehl erüberwac hung [CANop en] @ 1\mod_1342764821361_388.docx @ 35735 @ 2 @ 1

6.1 Error monitoring

Various methods of err or monitoring are avai lable for the f ield bus level. De pending on the tec hnolog y which is used, this enables the status of modules and communication to be indicated with LED displays, inverter parameters and field bus telegrams.
Pos: 172 /Anleit ungen/Ele ktr onik/Buss ys t e me/6. Meldunge n zum Betriebsz ustand / Fehler ü berwachung / S t at us über Paramet er anzeige [CAN open] @ 1\mod_1342702734266_388.docx @ 35681 @ 355 @ 1
90 BU 0060 GB-4112
Page 91
6 Operating status messages
0
1
3 – 5
6
The protocol of the CAN module is: 0 = CAN 1 = CANopen
7
Vacant
8
1 = "Bootsup Message" sent
9 – 10
CANopen NMT State
Status
Bit 10
Bit 9
Stopped
0 0 Pre-Operational
0 1 Operational
1
0
11 – 15
Reserved

6.1.1 Stat us via parameter display

Module status of the technology unit
In parameter P746, the status of the CANopen technology unit can be read. For the SK 700E, par ameter P746 is a sub-index parameter . The status of the CANn ord / CANopen
technology unit (SK TU1-…) is shown in sub-index 0 (or Array -01), the status of the CANnord customer interface (SK CU1-…) is shown in sub-index 1 (or Array -02).
The parameter contains binary coded information which is displayed in hexadecimal:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Module ID
CANopen=0Chex Module in status “operational” Initialisation active
Module error Timeout error Initialisation error (0) Reserved (0)
Module ready
Reserved (0)
Status of internal CANnord/CANopen, SK 511E and above
If the internal RJ45 C AN no rd/C AN ope n i terface (SK 511E and a bo ve) is us ed , p arameter P748 arra y ­01 can be used to display the status of the device.
The display is coded in hexadecimal, the individual bits are listed below:
Bit Meaning
1 = 24V Bus supply voltage 1 = CAN Bus in "Bus Warning" status
2
1 = CAN Bus in "Bus Off" status Vacant
Table 26: CANnord/CANopen status, parameter P748
Pos: 173 /Anleit ungen/Ele ktr onik/Buss ys t e me/6. Meldunge n zum Betriebsz ustand / Fehler ü berwachung / LE D Anzeige bei der Tec h n ol ogiebox [CANopen] @ 1\mod_1342764433366_ 388.docx @ 35711 @ 355 @ 1
BU 0060 GB-4112 91
Page 92
CANopen – Supplementary manual options for NORD - Frequency Inverters
TxD (green)
Transmitting CAN data
RxD (green)
Receiving CAN data
CR (green)
Single flashing (1s)
CANopen status STOPPED
Flashing (0.5s)
CANopen status PRE-OPERATIONAL
No other subscriber is in the bus or the wiring is faulty. (only possible when flashing with CE)
To:
CANopen status OPERATIONAL
CE (red)
Off
No error
Flashing
Bus warning, CAN controller error counter has reached or exceeded
No other subscribers available
To:
Bus off, CAN controller has disconnected from the bus because a
DR (green)
Off
No voltage supply
Flashing
Initialisation (init. phase)
On
Module OK
DE (red)
Off
No error
Flashing (0.2s)
Initialisation phase
Flashing (0.5s)
Timeout error
Single flashing (1s)
Inverter error (see frequency inverter instructions)
To:
System error, e.g. plug contact not correct

6.1.2 LED display with the technology unit:

The status of the technology unit is indicated by the integrated LEDs:
CANnord LED display
LED Meaning
Table 27: LED display, CANnord communication status
LED display CANopen
LED Display Meaning
Flashing (0.25s)
the warning limit.
Check wiring / shielding / termination resistors
serious error has occurred, e.g.:
Wiring error Incorrect baud rate set
Table 28: LED display, CANopen communication status
LED Display Meaning
Table 29: LED display, CANopen module status
Pos: 174 /A nleitungen/El ektronik/B ussysteme/ 6. Meldunge n zum Betrie bszustand / Fehlerüber wachung/E mergency Obj ect - Telegramm zu Fehlermeldungen des Umrichter s [C ANopen] @ 1\mod_1342773771516_388.docx @ 35 761 @ 3 @ 1
92 BU 0060 GB-4112
Page 93
6 Operating status messages
0x00
0x81
0x01
0x00
0x00
0x00
0x00
0x00
IDNodexIDSende += 800
1000
General error
The error number transmitted by FI is not known to the TO. It must be read out via P700 or another actual value.
4210
1.0
Inverter overtemperature
4310
2.0 / 2.1
Motor overtemperature / … I2t
2310
3.0
Inverter overcurrent
7112
3.1
Chopper overcurrent
2211
3.2
IGBT overcurrent (125%)
2212
3.3
IGBT overcurrent fast (150%)
2200
4.0 / 4.1
Module overcurrent / pulse switch-off overcurrent
3210
5.0
Link circuit overvoltage
3110
5.1
Mains overvoltage
3230
6.0
Link voltage undervoltage (charging error)
3120
6.1
Mains undervoltage
3130
7.0
Phase failure
6310
8.0
EEPROM parameter loss
5530
8.1 / 8.2
Invalid inverter type / copy error ext. EEPROM
8100
10.0 / 10.1 / 10.2 / 10.3 / 10.4 /
10.5 / 10.6 / 10.7
Telegram downtime, initialisation error, system error 5000
10.8
Communication error ext. Module
5110
11.0
ADU customer unit error
9000
12.0 / 12.1 / 12.2
Watchdog – customer/switch-off limit reach ed
7305
13.0
Incremental encoder 1

6.1.3 Emergency Object telegram for inverter error messages

If an internal error occurs in the frequenc y inverter, an error m essage is sent automatically via the CANbus.
Error message Error
Not used
register
Byte 0 Byte 1 Byte 2 Byte 3 B yte 4 Byte 5 Byte 6 Byte 7
Table 30: Structure of error message (Time-out through P 513)
After the error is reset, the Emergency Object is sent with the error mess age null. The Transmit ID for the error telegram is based on the following formula:
The Node ID of the freque ncy inverter is s et via the "ID -H" (or "ID x10")a nd "ID -L" (or "IDx1") s witches on the CANopen unit or in the PGM mode via parameter P515.
Pos: 175 /A nleitungen/El ektronik/B ussysteme/ 6. Meldunge n zum Betrie bszustand / Fehlerüber wachung/Fehl erliste [C ANopen] @ 1 \mod_1342775226242_388.docx @ 35791 @ 3 @ 1

6.1.4 Error lists,

CANopen
error
(hex)
FI error number Meaning
BU 0060 GB-4112 93
Page 94
CANopen – Supplementary manual options for NORD - Frequency Inverters
8400
13.1
Speed slip error
8300
13.2
Slip error switch-off monitoring
8710
13.5
Flying saw acceleration too low
8711
13.6
Flying saw value incorrect
8600
14.0 / 14.1
Reserved
8612
14.2
Reference limit
7300
14.3
Sensor
7306
14.4
Incremental encoder 2
7310
14.5
Speed sensor
7320
14.6 / 14.7 / 14.8
Position sensor
6000
15.0 / 15.1 / 15.2 / 15.3 / 15.4 /
20.7 / 20.9 / 21.0
System error, device software
motor / motor current monitoring during brake
operation
5300
17.0
Control panel
FF10
18.0
Safety circuit
FF11
19.0
Parameter identification error
5510
20.0
RAM data memory
5520
20.8
EPROM error
7330
25.0
Hiper. abs./inc. error
7331
25.1
Universal encoder communication
7332
25.2
No correspondence Universal Encoder
7333
25.3
Universal encoder resolution
7334
25.4
Universal encoder error
CANopen
error
(hex)
FI error number Meaning
15.5 / 15.6 / 15.7 / 15.8 / 20.1 /
20.2 / 20.3 / 20.4 / 20.5 / 20.6 /
7120 16.0 / 16.1 Phase error
Table 31: Assignment of CAN open errors to inverter errors
Pos: 176 /Anleit ungen/Ele ktronik/Buss ysteme/7. B eispiel- Teleg ramme/!K api t el Bei s piele @ 1\mod_1336400823408_388.doc x @ 25786 @ 1 @ 1
94 BU 0060 GB-4112
Page 95
7 Examples
P509
Setpoint source
6 or 17
CANopen
P510
Setpoint source
0
Auto
P515 (or rotary coding switch on the bus module)
CAN address
50
(50
= 32
)
P551
Drive profile
0
Off

7. Examples

Various examples are shown below to clarify the control and parameterisation of the frequency inverter with the bus system.
Pos: 177 /Anleit ungen/Ele ktr onik/Buss ys t e me/7. Beispiel - T elegramme/N etzeinsch alt en [CANopen BU 0060] @ 1\mod_1342785004232_388.docx @ 35839 @ 25 @ 1

7.1 Mains switch-on

After the CAN participant h as been s witched on it logs into th e s ystem with the CAN ID: 700 ID.

Example

+ Node
hex
Node ID: 50
dec
à 32
hex
Mains On à if the participant was recognised 732
is transmitted.
hex
As no valid telegram was sent at this time, the inverter switches to the status " Starting disabled" (à status word: 0B40).
Pos: 178 /Anleit ungen/Ele ktr onik/Buss ys t e me/7. Beispiel - Telegramme/Operational setzen der Bus Teilnehmer [CAN open BU0060] @ 1\mod_1342786735533_388.docx @ 35863 @ 2 @ 1

7.2 Operational settting of the bus participant

Be sending 0001 to ID000 all participants are set to "Operational".
Pos: 179 /Anleit ungen/Ele ktr onik/Buss ys t e me/7. Beispiel - T elegramme/ Prozessdate n (PDO) [CAN open BU00 60] @ 1\mod_1342776486166_388.doc x @ 35815 @ 2555 @ 1

7.3 Process data (PDO)

The exchange of process data is carried out via PDOs and is illustra t ed in the follo wing example.

Example:

Communication via: Technology unit SK TU4-CAO Scope of data: STW and SW1 Communication settings on the frequency inverter
Parameter number Parameter name Setting Meaning
Identifier:
CAN ID for Rx-PDO1: 200 CAN ID for Tx-PDO1: 180
BU 0060 GB-4112 95
(Node ID)
hex
hex
+ NODE-ID à 200 + NODE-ID à 180
hex
hex
+ 32 + 32
= 232
hex
= 1B2
hex
dec
hex
(control word + setpoint 1)
hex
(status word + actu al valu e 1)
hex
Page 96
CANopen – Supplementary manual options for NORD - Frequency Inverters
Process data word 1
Process data word 2
Byte 0
Byte 1
Byte 2
Byte 3
Byte 0
Byte 1
Byte 2
Byte 3
Object 3001 (status word)
Object 3003 Sub 1 (actual
value 1)
be transferred. The
Byte 0
Byte 1
Byte 2
Byte 3
7E
04
00
00
Order
31
0B
00
00
Response
Byte 0
Byte 1
Byte 2
Byte 3
Mapping:
CAN-ID
for Rx-PDO1
Object 3000 (control word) Object 3002 Sub 1 (setpoint 1)
CAN-ID
for Tx-PDO1
Information
Objects 3002 and 3003
Objects 3002 and 3003 can be used to specify which setpoint or actual value is to significance of the setpoints or actual values is set using the parameters P543-P548 in the frequency inverter.
Information
Data transfer is performed in Little Endian format. This means that in the data word, the High byte follows after the Low byte. Example: "047E" à 7E 04.
Little Endian data format
In order to be able to control the frequency inverter, the CANopen status must first be set to “Operational”

Setting the frequency inverter to "Ready for switch-on"

After switching on, the frequency inverter is in “Switch-on block” status. It has to be switched to "Standby" status using a contr ol command. To do so, the c ontrol word “0x047E” m ust be transmitted. The PDO telegram therefore has the following structure:
CAN-ID
232 1B2
hex
hex
hex
hex
hex
hex
hex
hex
hex
hex

Enabling the frequency inverter with 50% o f its maximum frequency

The drive unit is to operate at 50% of its maximum frequency. 100% corresponds to a setpoint of 4000
. Therefore "0x047F" must be sent as the control word and "0x2000" must be sent as the
hex
setpoint:
96 BU 0060 GB-4112
CAN-ID
232
hex
1B2
hex
7F
04
hex
37
0B
hex
00
hex
00
hex
20
hex
20
hex
hex
hex
Order
Response
Page 97
7 Examples
14 0 Parameter set Bit 0 off
14 0 Parameter set Bit 0 off
13 0 Reserved
13 0 Not function P481,10
11
0 4 Rotational direction: right
11
1 B Rotation right is on
10 1 Control data valid
10 0 Not function P481, 9
8 0 Not function P481, 11
8 1
Setpoint reached
7
0 7 No (error) acknowledgement
7 0 3 No warning
6 1 Enable setpoint
6 0
Starting not disabled
4 1 Enable pulses
4 1
Voltage enabled
3
1 E Operation enabled
3 0 1 No error
1 1 Do not disable voltage
1 0
Not ready for operation
0 0 Not ready for operation
0 1
Ready to start
Structure of the control word / sta tu s word
PZD1 PZD2
STW
ZSW
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Example: "Ready to start"
Control word Status word
Bit Value Value
15 0
Meaning Bit Value Value
HEX
Parameter set Bit 1 off 15 0
SW1
IW1
Meaning
HEX
Parameter set Bit 1 off
0
12 0 Rotation left is off 12 0 Rotation left is off
9 0 Not function P481, 12 9 1 Bus controller active
5 1 Enable ramp 5 1 No emergency stop
2 1 Emergency Stop not active 2 0 Operation not enabled
0
Pos: 180 /Anleit ungen/Ele ktr onik/Buss ys t e me/7. Beispiel - T elegramme/ Parameterda ten lesen u nd schreibe n (SDO) [CAN open BU006 0] @ 1\mod_1342787161229_388.docx @ 35887 @ 25 @ 1
BU 0060 GB-4112 97
Page 98
CANopen – Supplementary manual options for NORD - Frequency Inverters
Node ID
=50
dec
= 32
hex
Transmission address:
= 632
hex
(600
hex
+ 32
hex
)
Receive address:
= 5B2
hex
(580
hex
+ 32
hex
)
P102 „"Acceleration time":
= 102
dec
= 66
hex
à 2000
hex
+ 66
hex
= 2066
hex
Parameter set 1
= 01
hex
Value 1.03s:
= 1.03s à integer value: =103
dec
= 0067
hex
Control byte:
Send 16 bit value:
= 2B
hex
Load 16 bit value:
= 40
hex
"P102 acceleration time") into
Writing to the RAM of the frequency inverter should therefore be used for writing parameter data. The setting for

7.4 Reading and writing parameter data (SDO)

Reading and writing of parameter data is performed via SDOs and is illustrated in the following examples.
Detailed information a bout t he s tr uct ure of an S DO ( e.g : def init io n of the c ontro l bytes) can be found in Section 4.3.4.
Information
Parameters are mapped in objects above 2000

Example

Telegrams: Writing parameter data
Sending a parameter
setting to the FI:
ID 632 à 2B 6620 01 67 00 At the transmission address: 632
value with the value 0067 („P102 acceleration time“) in parameter set 1 Array 1 (01
hex
Parameter objects
!
the control byte 2B
hex
(1,03s ) is written in the parameter 2066
hex
for a 16Bit
hex
).
hex
hex
Reading parameter data
Loading a parameter
setting from the FI:
Query to the FI
ID 632 à 40 6620 01 At the transmission addres s: 632
the c ontrol byte 40
hex
for the r equest
hex
is sent to the frequency inverter to read out the saved value from the parameter 2066
(01
).
hex
("P102 accelerat ion tim e") iin para met er set 1 Arra y 1
hex
Response from the FI
ID 5B2 à 4B 6620 01 6700 At the receiving address: 5B2
delivered from the parameter 2066 parameter set 1 Array 1 (01
Pos: 181 /Anleit ungen/Ele ktronik/Buss ysteme/7. B eispiel- Teleg ramme/ - Ac htung - EEPR OM Sc hr eibzyklen @ 1\ mod_1343037906181_388.docx @ 35 917 @ @ 1
ATTENTION
The maximum number or write cycles on the EEPROM of the frequency inverters is limited to 100,000 cycles. Continuous writing to the EEPROM therefore results in the destruction of the EEPROM.
this is made in parameter P560 of the frequency inverter.
Pos: 182 /Anleit ungen/Ele ktr onik/Buss ys t e me/8. Zusatzin formation en /! Kapitel Zusa tzi nf ormationen @ 1\ mod_1336402432149_388.docx @ 25883 @ 1 @ 1
EEPROM writing cycles
the 16 bit value (status byte 4B
hex
(
hex
) with the value of 0067
hex
hex
(1.03s).
hex
) is
98 BU 0060 GB-4112
Page 99
8 Additional information

8. Additional information

Pos: 183 /Anleit ungen/Ele ktr onik/Buss ys t e me/8. Zusatzin formation en/Electronic Data Sheet ( eds – Datei ) [CANopen] @ 1\mod_1343038497213_388.docx @ 35941 @ 2 @ 1

8.1 Electronic data sheet (eds file)

All available objects ar e contained in the (SK***E.eds) “Electronic data sheet” (e ds file). This can be downloaded free of charge from www.nord.com
http://www2.nord.com/cms/de/documentation/software/software_detail_14558.jsp#top
The selection of the correct file is made according to the name of the relevant bus module (e.g. SK TU3-CAO). The correct assignment can be found in the attached readme.txt file. If necessary, various versions of the eds file are available for sele ction. In this case, the correct vers ion must be selected according to the firmware version of the frequency inverter (P707).
Pos: 184 /A nleitungen/El ektronik/B ussysteme/ 8. Zusatzin formationen /Weiterführ ende Dokumente [CANopen] @ 1\mod_1343040138440_388.docx @ 35965 @ 2 @ 1

8.2 Further documents

Internet www.can-cia.org www.drivecom.org Literature CIA draft Standard 301
.
CIA draft Standard 402
Pos: 185 /Anleit ungen/Ele ktr onik/FU und St ar t er/9. Wartung s - u n d Servicehin w ei se /9.2 Reparat ur hi nweise @ 0\mod_1328189697671_388.do cx @ 14558 @ 233 @ 1

8.3 Repair information

If you contact our technical support, please have the precise device type (rating plate/display), accessories and/or opt ions, the software vers ion used (P707) and the series number (name plate) at hand.

8.3.1 Repairs

The device must be sent to the following address if it needs repairing:
NORD Electronic DRIVESYSTEMS GmbH
Tjüchkampstraße 37
26605 Aurich, Germany
For queries about repairs, please contact:
Getriebebau NORD GmbH & Co. KG
Tel.: 04532 / 289-2515 Fax: 04532 / 289-2555
If a frequency inv erter is s e nt i n f or repair, no liabilit y can be accepted for any added components, e.g. such as mains cables, potentiometer, external displays, etc.!
Please remove all non-original parts from the frequency inverter.
BU 0060 GB-4112 99
Page 100
CANopen – Supplementary manual options for NORD - Frequency Inverters
possible, the reason for returning the component/device should be stated. If necessary, at least one contact for
ATTENTION
ASIC
Integrated circuit specific to the application
Baud rate
The transmission rate for serial interfaces in bits per second
Binary code
The designation for a code in which messages are communicated by "0" and "1" signals.
of 8 bits.
Broadcast
In a network, all slave participants are addressed simultaneously by the master.
CAN
Controller Area Network is an asynchronous serial field bus system
CANopen
Designates a communications protocol based on CAN
COB - ID
Communication Object Identifi er à Identifier of a CAN/CANopen message
EDS
Electronic Data Sheet
EMCY message
Emergency message (error telegram)
the sequence in which the bytes are processed in a data word. In this case
first the Low byte and then the High byte
Identifier
Unique definition of a message ("addressing") à Address of a CAN message box (i.e. addressing of a message and not the participant); a node may have several identifiers .
ISO
The International Standards Organisation is the international association of standardisation organisations and produces international standards in all fields, with the exception of electricity and electronics.
Node
Bus participant, e.g. an FI, I/O module, etc.
OSI layer model
The Open Systems Interconnection Reference Model (OSI) defines the elements, structures and tasks necessary for data communication and assigns these to the times for the communication process in seven consecutive layers.
Polling
Cyclical querying of individual components by a central component (NMT master / NMT slave)
Producer-consumer
A participant (producer) places data on the bus, all other participants (consumers)
this message and decide on the basis of the identifier, whether this message is
relevant to them.
Information
Reason for return
If queries should be stated.
This is important in order to keep repair times as short and efficient as possible. On request you can also obtain a suitable return goods voucher from Getriebebau NORD.
Unless otherwise agreed, the device is reset to the factory settings after inspection or repair.
Possible Consequential Damage
In order to rule out the possibility that the cause of a device fault is due to an optional module, the connected optional modules should also be returned in cas e of a fault.

8.3.2 Internet information

You can also find the comprehensive manual in German and in English on our Internet site.
www.nord.com
Pos: 186 /Anleit ungen/Ele ktr onik/Buss ys t e me/8. Zusatzin formation en /S achwortreg i ster [ C AN open] @ 1\mod_1343043607709_388.docx @ 35989 @ 2 @ 1

8.4 Keyword Index

Bit / Byte A bit (binary digit) is the sm allest unit of information in the binary system. A byte consi sts
Little Endian Describes
model
receive
Pos: 187 /A nleitungen/El ektronik/B ussysteme/ 8. Zusatzin formationen /Abkürzung en @ 1\mod_1336403850373_388.docx @ 26002 @ 2 @ 1
100 BU 0060 GB-4112
Loading...